Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:20
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820
Simulation Timestamp: 2020-06-03 19:20:54
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1667.12 | 797.55 | 797.55 |
Net Site Energy | 1667.12 | 797.55 | 797.55 |
Total Source Energy | 5279.78 | 2525.83 | 2525.83 |
Net Source Energy | 5279.78 | 2525.83 | 2525.83 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 554.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 587.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 110.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 227.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 58.73 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1667.12 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 554.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 587.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 110.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 227.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 58.73 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 333.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 402.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 797.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 333.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 402.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 797.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1667.124 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1667.124 | 100.00 |
Total On-Site and Utility Electric Sources | 1667.124 | 100.00 |
Total Electricity End Uses | 1667.124 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 42.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 512.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_HI_HONOLULU
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Latitude [deg] | 21.32 |
Longitude [deg] | -157.9 |
Elevation [m] | 2.00 |
Time Zone | -10.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 21.0784 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 22.5208 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.3680 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.3680 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.3680 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 15.8795 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 15.8795 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 15.8795 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 15.8795 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 15.8795 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 18.4215 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 18.4215 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-SEP-12:50 | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 59179.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 36581.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13193.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5419.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 122463.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 59179.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 36581.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13193.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5419.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1754.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1859.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 351.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 720.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 186.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5279.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 839.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 889.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 344.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 88.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2525.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 839.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 889.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 344.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 88.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2525.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.98 |
SMSTORE1 DIRECT AIR | 1.04 |
SMSTORE2 DIRECT AIR | 1.04 |
SMSTORE3 DIRECT AIR | 1.04 |
SMSTORE4 DIRECT AIR | 1.04 |
LGSTORE2 DIRECT AIR | 1.89 |
SMSTORE5 DIRECT AIR | 0.986953 |
SMSTORE6 DIRECT AIR | 0.981355 |
SMSTORE7 DIRECT AIR | 0.980418 |
SMSTORE8 DIRECT AIR | 1.07 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.98 | 1.98 | 1.98 | 1.98 | 1.98 | 1.98 | 1.00 | 1.00 | 1.98 |
PSZ-AC_2:2 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.00 | 1.04 |
PSZ-AC_3:3 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.00 | 1.04 |
PSZ-AC_4:4 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.00 | 1.04 |
PSZ-AC_5:5 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.00 | 1.04 |
PSZ-AC_6:6 | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.00 | 1.00 | 1.89 |
PSZ-AC_7:7 | 0.986953 | 0.986953 | 0.986953 | 0.986953 | 0.986953 | 0.986953 | 1.00 | 1.00 | 0.986953 |
PSZ-AC_8:8 | 0.981355 | 0.981355 | 0.981355 | 0.981355 | 0.981355 | 0.981355 | 1.00 | 1.00 | 0.981355 |
PSZ-AC_9:9 | 0.980418 | 0.980418 | 0.980418 | 0.980418 | 0.980418 | 0.980418 | 1.00 | 1.00 | 0.980418 |
PSZ-AC_10:10 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.00 | 1.00 | 1.07 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.98 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 1.04 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 1.04 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 1.04 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 1.04 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 1.89 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 0.986953 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 0.981355 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 0.980418 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 1.07 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.98 | 1.98 | 1.98 | 1.98 | 45795.98 | 47767.09 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 1.04 | 23955.67 | 25073.19 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 1.04 | 23863.65 | 24945.57 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 1.04 | 23916.15 | 25014.85 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 1.04 | 23840.05 | 25207.23 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.89 | 1.89 | 1.89 | 1.89 | 44028.02 | 45523.87 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.986953 | 0.986953 | 0.986953 | 0.986953 | 22993.96 | 23777.38 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.981355 | 0.981355 | 0.981355 | 0.981355 | 22897.70 | 23649.23 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.980418 | 0.980418 | 0.980418 | 0.980418 | 22882.71 | 23628.32 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 1.07 | 24360.05 | 25669.45 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 1.98 | 0.991610 | 1.98 | 43381.57 | 45795.98 | 22897.99 | 45795.98 | 0.694558 | 0.694560 | 0.694560 | 0.694560 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.04 | 0.521810 | 1.04 | 22682.81 | 23955.67 | 11977.83 | 23955.67 | 0.696134 | 0.696140 | 0.696140 | 0.696140 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.04 | 0.519025 | 1.04 | 22598.10 | 23863.65 | 11931.83 | 23863.65 | 0.695736 | 0.695740 | 0.695740 | 0.695740 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.04 | 0.520545 | 1.04 | 22646.81 | 23916.15 | 11958.08 | 23916.15 | 0.695929 | 0.695930 | 0.695930 | 0.695930 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.04 | 0.518310 | 1.04 | 22576.58 | 23840.05 | 11920.02 | 23840.05 | 0.695633 | 0.695630 | 0.695630 | 0.695630 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 1.89 | 0.942505 | 1.89 | 41740.82 | 44028.02 | 22014.01 | 44028.02 | 0.691565 | 0.691570 | 0.691570 | 0.691570 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 0.986950 | 0.493475 | 0.986950 | 21795.48 | 22993.96 | 11496.98 | 22993.96 | 0.692224 | 0.692220 | 0.692220 | 0.692220 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 0.981350 | 0.490675 | 0.981350 | 21706.49 | 22897.70 | 11448.85 | 22897.70 | 0.691834 | 0.691840 | 0.691840 | 0.691840 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 0.980420 | 0.490210 | 0.980420 | 21692.90 | 22882.71 | 11441.35 | 22882.71 | 0.691757 | 0.691760 | 0.691760 | 0.691760 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.07 | 0.534875 | 1.07 | 23054.34 | 24360.05 | 12180.02 | 24360.05 | 0.698261 | 0.698260 | 0.698260 | 0.698260 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.98 | 2122.14 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1155.46 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1149.29 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1152.65 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1147.70 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.89 | 2017.05 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.986953 | 1092.71 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.981355 | 1086.52 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.980418 | 1085.48 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1184.38 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 47767.09 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 25073.19 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 24945.57 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 25014.85 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 25207.23 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 45523.87 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 23777.38 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 23649.23 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 23628.32 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 25669.45 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.20 | 24.80 | 23.70 | 22.50 | 22.80 | 23.20 | 23.80 | 25.20 | 25.90 | 26.90 | 27.10 | 26.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Honolulu Intl Arpt HI USA TMY3 WMO#=911820 | 21.32 | -157.93 | -10.00 | 2.00 | 101301 | 1.2040 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.92 | 4.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 21.078 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.378 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 22.521 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 26.821 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.368 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.668 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.368 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.668 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.368 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.668 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 5532.190 | 15.879 | 184.430 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5532.190 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 1811.251 | 5.199 | 60.383 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1811.251 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1156.875 | 6.641 | 77.135 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1156.875 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 5532.190 | 15.879 | 184.430 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5532.190 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.4678 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.903 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.37383775E-12 | 0.81582362E-15 | -0.12542534E-12 | 0.11541335E-15 |
23 | 6 | 0.32294454E-07 | 0.13597119E-09 | 0.73677206E-08 | -0.15476624E-12 |
24 | 5 | -0.20833553E-03 | 0.11386595E-05 | -0.10688959E-03 | 0.72710034E-08 |
25 | 4 | 0.31322919 | 0.54351077E-03 | 0.10727732 | -0.36571185E-04 |
26 | 3 | -7.6832781 | 0.16549290E-01 | -2.4626776 | 0.31053958E-01 |
27 | 2 | 42.245606 | 0.57933024E-01 | 15.771342 | -0.34865193 |
28 | 1 | -81.598353 | 0.25789083E-01 | -29.595166 | 1.1010509 |
29 | 0 | 46.824332 | 0.51189598E-03 | 16.280659 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 29 | 1 | VerySmooth | 2.843 | 0.252 | 0.162 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.16139 | 0.61114 | 0.61114 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.286 | 8.224E-004 | 4.530E-004 | 0.571 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 0.164 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.204 | 1.172E-003 | 5.440E-004 | 0.815 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 22512.52532 | 27015.03038 | 1.65268 | 1.98322 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 32.20000 | 1.43490E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 5649.49637 | 6779.39565 | 0.23629 | 0.41145 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 11846.60124 | 14215.92149 | 0.86969 | 1.04362 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 32.14083 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 2659.84658 | 3191.81589 | 0.11170 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 11783.50172 | 14140.20207 | 0.86505 | 1.03805 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 32.08167 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 2607.81248 | 3129.37497 | 0.11245 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 11818.14899 | 14181.77878 | 0.86757 | 1.04109 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 32.02250 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 2642.19356 | 3170.63227 | 0.11393 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 11767.41389 | 14120.89667 | 0.86385 | 1.03662 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 32.02250 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 2749.02426 | 3298.82912 | 0.11854 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 21398.77201 | 25678.52641 | 1.57085 | 1.88501 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 32.02250 | 1.43490E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 6201.45627 | 7441.74753 | 0.25855 | 0.41145 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 11204.06303 | 13444.87563 | 0.82246 | 0.98695 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.96333 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 3198.84519 | 3838.61423 | 0.13389 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 11140.51987 | 13368.62384 | 0.81780 | 0.98135 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.96333 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 3196.35681 | 3835.62817 | 0.13379 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 11129.88617 | 13355.86340 | 0.81701 | 0.98042 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.96333 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 3402.61715 | 4083.14058 | 0.14220 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 12144.84651 | 14573.81581 | 0.89146 | 1.06975 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 31.84500 | 1.43490E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 3817.65756 | 4581.18907 | 0.15928 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 16.20000 | 1.15180E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 30736.66 | 1.98322 | 1.98322 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 11847.79 | 0.41145 | 0.41145 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:30:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 16062.41 | 1.04362 | 1.04362 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:50:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 15981.22 | 1.03805 | 1.03805 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16020.16 | 1.04109 | 1.04109 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 15959.84 | 1.03662 | 1.03662 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 08:10:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 29388.40 | 1.88501 | 1.88501 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 11847.79 | 0.41145 | 0.41145 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 15283.67 | 0.98695 | 0.98695 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 11:20:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 15208.52 | 0.98135 | 0.98135 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:40:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 15193.51 | 0.98042 | 0.98042 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 16329.42 | 1.06975 | 1.06975 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 5923.90 | 0.20573 | 0.20573 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 20:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.98322 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04362 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03805 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04109 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03662 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.88501 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98695 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98135 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98042 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06975 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.98322 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.98322 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.98322 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.98322 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.98322 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.98322 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04362 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04362 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04362 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04362 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04362 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04362 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03805 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03805 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03805 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03805 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03805 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.03805 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04109 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04109 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04109 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04109 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04109 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04109 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03662 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03662 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03662 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03662 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03662 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.03662 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.88501 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.88501 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.88501 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.88501 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.88501 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.88501 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98695 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98695 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98695 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98695 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98695 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98695 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98135 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98135 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98135 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98135 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98135 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98135 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98042 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98042 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98042 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98042 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98042 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98042 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06975 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06975 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06975 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06975 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06975 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06975 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.98322 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.04362 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.03805 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.04109 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.03662 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.88501 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.98695 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.98135 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.98042 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.06975 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.98322 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.98322 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.98322 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.98322 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.98322 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.98322 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.99161 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.98322 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 43381.57232 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 45795.98000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 22897.99000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 45795.98000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69456 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69456 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69456 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69456 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 45795.98000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 47767.09138 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.98322 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2122.13917 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 47767.09138 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04362 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04362 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04362 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04362 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.04362 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04362 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52181 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.04362 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22682.80668 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23955.67000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11977.83500 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 23955.67000 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69613 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69614 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69614 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69614 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23955.67000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25073.18824 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04362 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1155.45693 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25073.18824 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03805 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03805 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03805 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03805 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.03805 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03805 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51903 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.03805 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22598.09716 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23863.65000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11931.82500 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 23863.65000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69574 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69574 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69574 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69574 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23863.65000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24945.57364 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03805 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1149.29159 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 24945.57364 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04109 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04109 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04109 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04109 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.04109 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04109 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52055 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.04109 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22646.81406 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23916.15000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11958.07500 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 23916.15000 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69593 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69593 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69593 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69593 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23916.15000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25014.85282 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04109 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1152.64816 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25014.85282 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03662 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03662 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03662 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03662 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.03662 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03662 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51831 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.03662 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22576.58370 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23840.05000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11920.02500 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 23840.05000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69563 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69563 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69563 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69563 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23840.05000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25207.22557 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03662 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1147.69929 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25207.22557 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.88501 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.88501 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.88501 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.88501 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.88501 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.88501 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.94251 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.88501 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 41740.81630 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 44028.02000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 22014.01000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 44028.02000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69157 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69157 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69157 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69157 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 44028.02000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 45523.87300 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.88501 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2017.05435 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 45523.87300 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98695 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98695 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98695 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98695 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98695 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98695 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49348 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.98695 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21795.47697 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22993.96000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11496.98000 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22993.96000 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69222 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69222 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69222 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69222 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22993.96000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23777.37781 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98695 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1092.71327 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 23777.37781 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98135 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98135 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98135 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98135 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98135 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98135 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49068 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.98135 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21706.49443 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22897.70000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11448.85000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22897.70000 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69183 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69184 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69184 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69184 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22897.70000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23649.23269 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98135 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1086.51568 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 23649.23269 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98042 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98042 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98042 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98042 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98042 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98042 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49021 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.98042 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21692.89897 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22882.71000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11441.35500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22882.71000 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69176 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69176 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69176 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69176 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22882.71000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23628.31689 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98042 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1085.47830 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 23628.31689 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06975 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06975 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06975 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06975 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.06975 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06975 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53488 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.06975 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 23054.33725 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 24360.05000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12180.02500 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 24360.05000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69826 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69826 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69826 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69826 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24360.05000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25669.44681 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06975 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1184.38380 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25669.44681 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 44233.6 | 11.13 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 23133.6 | 32.88 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 23045.9 | 44.30 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 23096.0 | 55.49 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 23023.4 | 66.97 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 42542.7 | 46.90 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 22216.3 | 102.49 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 22124.4 | 114.25 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 22110.2 | 125.65 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 23517.5 | 129.03 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.5924288889E-002 | 0.1251441081 | Pass | Pass | 6.3094799019E-002 | 0.4268586426 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 2.7030229487E-002 | 0.1398063770 | Pass | Pass | 9.5001345498E-002 | 0.8135210024 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 5.5130343103E-002 | 0.2201388572 | Pass | Pass | 0.3705872835 | 3.5013331231 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.5410598512E-002 | 0.2229885212 | Pass | Pass | 0.6870353234 | 7.2584720418 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 5.4928695916E-002 | 0.2198957828 | Pass | Pass | 0.3683933643 | 3.4881705084 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 5.8628381200E-002 | 0.2255078462 | Pass | Pass | 0.2913532302 | 2.2946895336 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 5.8661020946E-002 | 0.2268444632 | Pass | Pass | 0.1251496282 | 0.6261666459 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 5.8875705387E-002 | 0.2261928912 | Pass | Pass | 0.1070075495 | 0.5720793980 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.9728231932E-002 | 0.2257703043 | Pass | Pass | 0.2487293275 | 1.5300627662 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 6.5362631791E-002 | 0.2318557005 | Pass | Pass | 0.1022566165 | 0.5692894564 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.00 | 16.20 | Wetbulb [C] | 1.90 | 320.00 |
HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 32.20 | 7.10 | 23.30 | Wetbulb [C] | 6.70 | 60.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.843 | 0.252 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.843 | 0.252 | 0.251 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.843 | 0.252 | 0.251 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 15.8795 | 348.39 | 5532.19 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 102.16 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 5.1990 | 348.39 | 1811.25 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 33.45 |
SMSTORE1_LIGHTS | SMSTORE1 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 51.08 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 6.6413 | 174.19 | 1156.88 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 21.36 |
SMSTORE2_LIGHTS | SMSTORE2 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 40.48 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
SMSTORE3_LIGHTS | SMSTORE3 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 40.48 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
SMSTORE4_LIGHTS | SMSTORE4 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 40.48 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
LGSTORE2_LIGHTS | LGSTORE2 | 15.8795 | 348.39 | 5532.19 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 74.42 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.21 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.21 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.21 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.21 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 9.2108 | 4180.64 | 38506.89 | 587.06 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7048.38 | AstronomicalClock | - | 83.86 | 83.86 | 110.95 | |
Exterior Lighting Total | 7048.38 | 110.95 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 45795.98 | 31808.06 | 13987.92 | 0.69 | 3.73 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 23955.67 | 16676.50 | 7279.17 | 0.70 | 3.80 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 23863.65 | 16602.90 | 7260.75 | 0.70 | 3.80 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 23916.15 | 16643.97 | 7272.18 | 0.70 | 3.80 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 23840.05 | 16583.85 | 7256.20 | 0.70 | 3.80 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 44028.02 | 30448.46 | 13579.56 | 0.69 | 3.73 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22993.96 | 15916.88 | 7077.08 | 0.69 | 3.80 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22897.70 | 15841.54 | 7056.16 | 0.69 | 3.80 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22882.71 | 15829.34 | 7053.37 | 0.69 | 3.80 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 24360.05 | 17009.65 | 7350.40 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 44233.6 | 11.13 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 23133.6 | 32.88 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 23045.9 | 44.30 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 23096.0 | 55.49 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 23023.4 | 66.97 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 42542.7 | 46.90 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 22216.3 | 102.49 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 22124.4 | 114.25 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 22110.2 | 125.65 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 23517.5 | 129.03 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 47767.09 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25073.19 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 24945.57 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25014.85 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25207.23 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 45523.87 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 23777.38 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 23649.23 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 23628.32 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25669.45 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.98 | 2122.14 | 1070.05 | 1.00 | 1.32 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1155.46 | 1107.16 | 1.00 | 1.39 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1149.29 | 1107.16 | 1.00 | 1.39 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1152.65 | 1107.16 | 1.00 | 1.39 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1147.70 | 1107.16 | 1.00 | 1.39 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.89 | 2017.05 | 1070.05 | 1.00 | 1.32 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1092.71 | 1107.16 | 1.00 | 1.41 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1086.52 | 1107.16 | 1.00 | 1.41 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1085.48 | 1107.16 | 1.00 | 1.41 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1184.38 | 1107.16 | 1.00 | 1.39 | General | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 22512.53 | 27015.03 | 77.54 | 1.653 | 1.983 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 23.89 | 23.88 | 0.00986 | 32.20 | 0.01435 | 0.411 | 0.00 |
SMSTORE1 | 11846.60 | 14215.92 | 81.61 | 0.870 | 1.044 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.00989 | 32.14 | 0.01435 | 0.206 | 0.00 |
SMSTORE2 | 11783.50 | 14140.20 | 81.18 | 0.865 | 1.038 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.88 | 0.00990 | 32.08 | 0.01435 | 0.206 | 0.00 |
SMSTORE3 | 11818.15 | 14181.78 | 81.41 | 0.868 | 1.041 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 23.89 | 23.88 | 0.00989 | 32.02 | 0.01435 | 0.206 | 0.00 |
SMSTORE4 | 11767.41 | 14120.90 | 81.06 | 0.864 | 1.037 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 23.89 | 23.88 | 0.00990 | 32.02 | 0.01435 | 0.206 | 0.00 |
LGSTORE2 | 21398.77 | 25678.53 | 73.71 | 1.571 | 1.885 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 23.89 | 23.88 | 0.00989 | 32.02 | 0.01435 | 0.411 | 0.00 |
SMSTORE5 | 11204.06 | 13444.88 | 77.18 | 0.822 | 0.987 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 23.89 | 23.88 | 0.00995 | 31.96 | 0.01435 | 0.206 | 0.00 |
SMSTORE6 | 11140.52 | 13368.62 | 76.75 | 0.818 | 0.981 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 23.89 | 23.88 | 0.00995 | 31.96 | 0.01435 | 0.206 | 0.00 |
SMSTORE7 | 11129.89 | 13355.86 | 76.67 | 0.817 | 0.980 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 23.89 | 23.88 | 0.00995 | 31.96 | 0.01435 | 0.206 | 0.00 |
SMSTORE8 | 12144.85 | 14573.82 | 83.66 | 0.891 | 1.070 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 23.89 | 23.88 | 0.00990 | 31.85 | 0.01435 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 5649.50 | 6779.40 | 19.46 | 0.236 | 0.411 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00960 | 16.20 | 0.01152 | 0.411 | 0.00 |
SMSTORE1 | 2659.85 | 3191.82 | 18.32 | 0.112 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00940 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE2 | 2607.81 | 3129.37 | 17.96 | 0.112 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 21.11 | 21.11 | 0.01000 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE3 | 2642.19 | 3170.63 | 18.20 | 0.114 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 21.11 | 21.11 | 0.00998 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE4 | 2749.02 | 3298.83 | 18.94 | 0.119 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:00:00 | 21.11 | 21.11 | 0.00994 | 16.20 | 0.01152 | 0.206 | 0.00 |
LGSTORE2 | 6201.46 | 7441.75 | 21.36 | 0.259 | 0.411 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00978 | 16.20 | 0.01152 | 0.411 | 0.00 |
SMSTORE5 | 3198.85 | 3838.61 | 22.04 | 0.134 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00979 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE6 | 3196.36 | 3835.63 | 22.02 | 0.134 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00979 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE7 | 3402.62 | 4083.14 | 23.44 | 0.142 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.00973 | 16.20 | 0.01152 | 0.206 | 0.00 |
SMSTORE8 | 3817.66 | 4581.19 | 26.30 | 0.159 | 0.206 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:00:00 | 21.11 | 21.11 | 0.01003 | 16.20 | 0.01152 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.98 | 1.98 | 0.41 | 0.41 | 1.9832 | 1.9832 | 1.9832 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.04 | 1.04 | 0.21 | 0.21 | 1.0436 | 1.0436 | 1.0436 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.04 | 1.04 | 0.21 | 0.21 | 1.0381 | 1.0381 | 1.0381 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.04 | 1.04 | 0.21 | 0.21 | 1.0411 | 1.0411 | 1.0411 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.04 | 1.04 | 0.21 | 0.21 | 1.0366 | 1.0366 | 1.0366 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.89 | 1.89 | 0.41 | 0.41 | 1.8850 | 1.8850 | 1.8850 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.99 | 0.99 | 0.21 | 0.21 | 0.9870 | 0.9870 | 0.9870 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 0.98 | 0.98 | 0.21 | 0.21 | 0.9814 | 0.9814 | 0.9814 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 0.98 | 0.98 | 0.21 | 0.21 | 0.9804 | 0.9804 | 0.9804 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.07 | 1.07 | 0.21 | 0.21 | 1.0698 | 1.0698 | 1.0698 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 45795.980 | 0.000 | 1.983220 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 45795.98 | 32505.08 | 1.983220 | 25.61 | 18.80 | 0.01079468 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 20.7467 | 23.88 | 0.00986423 | 53.3472 | 22512.53 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 47767.091 | 47767.091 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:30:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:30:00 | 47767.09 | 47767.09 | 1.983220 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 20.7467 | 21.11 | 0.00959547 | 61.4463 | 3374.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 23955.670 | 0.000 | 1.043620 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23955.67 | 17023.90 | 1.043620 | 25.52 | 18.76 | 0.01077126 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 19.7128 | 23.88 | 0.00989165 | 53.4936 | 11843.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 25073.188 | 25073.188 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:50:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:50:00 | 25073.19 | 25073.19 | 1.043624 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 19.7127 | 21.11 | 0.00940338 | 60.2353 | 1075.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 23863.650 | 0.000 | 1.038050 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23863.65 | 16939.51 | 1.038050 | 25.53 | 18.77 | 0.01078162 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 19.8186 | 23.88 | 0.00989603 | 53.5169 | 11775.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 24945.574 | 24945.574 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 24945.57 | 24945.57 | 1.038055 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 19.8185 | 21.11 | 0.00999521 | 63.9630 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 23916.150 | 0.000 | 1.041090 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 23916.15 | 16985.87 | 1.041090 | 25.53 | 18.76 | 0.01077667 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 19.7607 | 23.88 | 0.00989039 | 53.4868 | 11807.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 25014.853 | 25014.853 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 25014.85 | 25014.85 | 1.041087 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 19.7608 | 21.11 | 0.00998361 | 63.8899 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 23840.050 | 0.000 | 1.036620 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 23840.05 | 16917.74 | 1.036620 | 25.54 | 18.77 | 0.01078436 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 19.8459 | 23.88 | 0.00989515 | 53.5122 | 11756.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 25207.226 | 25207.226 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 08:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 08:10:00 | 25207.23 | 25207.23 | 1.036617 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 19.8460 | 21.11 | 0.00994247 | 63.6307 | 1026.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 44028.020 | 0.000 | 1.885010 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 44028.02 | 31023.75 | 1.885010 | 25.70 | 18.89 | 0.01086773 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 21.8277 | 23.88 | 0.00988717 | 53.4688 | 21371.40 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 45523.873 | 45523.873 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 45523.87 | 45523.87 | 1.885014 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 21.8276 | 21.11 | 0.00978086 | 62.6141 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 22993.960 | 0.000 | 0.986950 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 22993.96 | 16161.64 | 0.986950 | 25.62 | 18.87 | 0.01087432 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 20.8447 | 23.88 | 0.00994742 | 53.7902 | 11184.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 23777.378 | 23777.378 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 11:20:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 11:20:00 | 23777.38 | 23777.38 | 0.986953 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 20.8446 | 21.11 | 0.00979112 | 62.6785 | 1815.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 22897.700 | 0.000 | 0.981350 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 22897.70 | 16076.36 | 0.981350 | 25.63 | 18.88 | 0.01088475 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 20.9636 | 23.88 | 0.00995383 | 53.8244 | 11120.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 23649.233 | 23649.233 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:40:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:40:00 | 23649.23 | 23649.23 | 0.981355 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 20.9635 | 21.11 | 0.00979317 | 62.6914 | 1969.29 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 22882.710 | 0.000 | 0.980420 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 22882.71 | 16062.30 | 0.980420 | 25.63 | 18.88 | 0.01088685 | 12.80 | 12.10 | 0.00850000 | 32.20 | 0.01434902 | 23.30 | 20.9835 | 23.88 | 0.00995491 | 53.8301 | 11108.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 23628.317 | 23628.317 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 23628.32 | 23628.32 | 0.980418 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 20.9836 | 21.11 | 0.00973425 | 62.3199 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 24360.050 | 0.000 | 1.069750 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 24360.05 | 17299.15 | 1.069750 | 25.42 | 18.71 | 0.01075938 | 12.80 | 12.10 | 0.00850000 | 31.85 | 0.01434902 | 23.20 | 19.2313 | 23.88 | 0.00990467 | 53.5629 | 12144.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 25669.447 | 25669.447 | -999.0 | -999.0 | -999.000 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 20:20:00 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 20:20:00 | 25669.45 | 25669.45 | 1.069751 | 16.20 | 16.20 | 0.01151798 | 40.00 | 21.15 | 0.00800000 | 16.20 | 0.01151798 | 16.20 | 19.2313 | 21.11 | 0.01002854 | 64.1719 | 1754.36 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 45795.980 | 0.000 | 1.983220 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9068 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 45795.98 | 32505.08 | 1.0000 | 2.38784287 | 1.983220 | 25.61 | 18.80 | 0.01079468 | 53244.6 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45795.98 | 32.20 | 0.01434902 | 23.30 | 0.41145340 | 20.7467 | 23.88 | 0.00986423 | 23.88 | 0.00986423 | 53.3472 | 22512.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 47767.091 | 47767.091 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.983220 | 2.38784290 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:30:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:30:00 | 47767.09 | 47767.09 | 1.0000 | 2.38784290 | 1.983220 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47767.09 | 16.20 | 0.01151798 | 16.20 | 0.41145340 | 20.7467 | 21.11 | 0.00948942 | 21.11 | 0.00959547 | 61.4463 | 3374.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23955.670 | 0.000 | 1.043620 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8632 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23955.67 | 17023.90 | 1.0000 | 1.25654268 | 1.043620 | 25.52 | 18.76 | 0.01077126 | 53097.1 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23955.67 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 19.7128 | 23.88 | 0.00989256 | 23.88 | 0.00989165 | 53.4936 | 11843.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25073.188 | 25073.188 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.043624 | 1.25654696 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:50:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:50:00 | 25073.19 | 25073.19 | 1.0000 | 1.25654696 | 1.043624 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25073.19 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 19.7127 | 21.11 | 0.00888047 | 21.11 | 0.00940338 | 60.2353 | 1075.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23863.650 | 0.000 | 1.038050 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8825 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23863.65 | 16939.51 | 1.0000 | 1.24983627 | 1.038050 | 25.53 | 18.77 | 0.01078162 | 53133.3 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23863.65 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 19.8186 | 23.88 | 0.00989908 | 23.88 | 0.00989603 | 53.5169 | 11775.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24945.574 | 24945.574 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.038055 | 1.24984221 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 24945.57 | 24945.57 | 1.0000 | 1.24984221 | 1.038055 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24945.57 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 19.8185 | 21.11 | 0.00000000 | 21.11 | 0.00999521 | 63.9630 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23916.150 | 0.000 | 1.041090 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8733 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 23916.15 | 16985.87 | 1.0000 | 1.25349650 | 1.041090 | 25.53 | 18.76 | 0.01077667 | 53116.0 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23916.15 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 19.7607 | 23.88 | 0.00989598 | 23.88 | 0.00989039 | 53.4868 | 11807.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25014.853 | 25014.853 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.041087 | 1.25349245 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 25014.85 | 25014.85 | 1.0000 | 1.25349245 | 1.041087 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25014.85 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 19.7608 | 21.11 | 0.00000000 | 21.11 | 0.00998361 | 63.8899 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23840.050 | 0.000 | 1.036620 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8876 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 23840.05 | 16917.74 | 1.0000 | 1.24811452 | 1.036620 | 25.54 | 18.77 | 0.01078436 | 53142.9 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23840.05 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 19.8459 | 23.88 | 0.00990081 | 23.88 | 0.00989515 | 53.5122 | 11756.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25207.226 | 25207.226 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.036617 | 1.24811061 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 08:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 08:10:00 | 25207.23 | 25207.23 | 1.0000 | 1.24811061 | 1.036617 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25207.23 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 19.8460 | 20.82 | 0.00170065 | 21.11 | 0.00994247 | 63.6307 | 1026.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 44028.020 | 0.000 | 1.885010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0426 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 44028.02 | 31023.75 | 1.0000 | 2.26959575 | 1.885010 | 25.70 | 18.89 | 0.01086773 | 53525.4 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 44028.02 | 32.20 | 0.01434902 | 23.30 | 0.41145340 | 21.8277 | 23.88 | 0.00989412 | 23.88 | 0.00988717 | 53.4688 | 21371.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 45523.873 | 45523.873 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.885014 | 2.26960086 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 45523.87 | 45523.87 | 1.0000 | 2.26960086 | 1.885014 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45523.87 | 16.20 | 0.01151798 | 16.20 | 0.41145340 | 21.8276 | 21.11 | 0.00000000 | 21.11 | 0.00978086 | 62.6141 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22993.960 | 0.000 | 0.986950 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0548 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 22993.96 | 16161.64 | 1.0000 | 1.18831069 | 0.986950 | 25.62 | 18.87 | 0.01087432 | 53458.8 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22993.96 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 20.8447 | 23.88 | 0.00995736 | 23.88 | 0.00994742 | 53.7902 | 11184.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23777.378 | 23777.378 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.986953 | 1.18831390 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 11:20:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 11:20:00 | 23777.38 | 23777.38 | 1.0000 | 1.18831390 | 0.986953 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23777.38 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 20.8446 | 21.11 | 0.00943880 | 21.11 | 0.00979112 | 62.6785 | 1815.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22897.700 | 0.000 | 0.981350 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0742 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 22897.70 | 16076.36 | 1.0000 | 1.18156816 | 0.981350 | 25.63 | 18.88 | 0.01088475 | 53495.6 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22897.70 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 20.9636 | 23.88 | 0.00996392 | 23.88 | 0.00995383 | 53.8244 | 11120.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23649.233 | 23649.233 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.981355 | 1.18157409 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:40:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 10:40:00 | 23649.23 | 23649.23 | 1.0000 | 1.18157409 | 0.981355 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23649.23 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 20.9635 | 21.11 | 0.00957262 | 21.11 | 0.00979317 | 62.6914 | 1969.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22882.710 | 0.000 | 0.980420 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0781 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 22882.71 | 16062.30 | 1.0000 | 1.18044842 | 0.980420 | 25.63 | 18.88 | 0.01088685 | 53503.0 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22882.71 | 32.20 | 0.01434902 | 23.30 | 0.20572670 | 20.9835 | 23.88 | 0.00996524 | 23.88 | 0.00995491 | 53.8301 | 11108.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23628.317 | 23628.317 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.980418 | 1.18044595 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:10:00 | 23628.32 | 23628.32 | 1.0000 | 1.18044595 | 0.980418 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23628.32 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 20.9836 | 21.11 | 0.00000000 | 21.11 | 0.00973425 | 62.3199 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24360.050 | 0.000 | 1.069750 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8411 | 1004.8586 | 1.2040 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 24360.05 | 17299.15 | 1.0000 | 1.28800381 | 1.069750 | 25.42 | 18.71 | 0.01075938 | 52956.7 | 12.80 | 12.10 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24360.05 | 31.85 | 0.01434902 | 23.20 | 0.20572670 | 19.2313 | 23.89 | 0.00990467 | 23.88 | 0.00990467 | 53.5629 | 12144.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25669.447 | 25669.447 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2040 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.069751 | 1.28800462 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 20:20:00 | unknown | unknown | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 20:20:00 | 25669.45 | 25669.45 | 1.0000 | 1.28800462 | 1.069751 | 16.20 | 16.20 | 0.01151798 | 45431.0 | 40.00 | 21.15 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25669.45 | 16.20 | 0.01151798 | 16.20 | 0.20572670 | 19.2313 | 21.11 | 0.00967158 | 21.11 | 0.01002854 | 64.1719 | 1754.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 5823.00 | 272.67 | 272.67 |
SMSTORE1 | 5777.50 | 116.33 | 116.17 |
SMSTORE2 | 4388.67 | 228.83 | 228.83 |
SMSTORE3 | 4388.33 | 227.00 | 227.00 |
SMSTORE4 | 4386.00 | 235.83 | 235.83 |
LGSTORE2 | 4013.17 | 233.00 | 233.00 |
SMSTORE5 | 4000.00 | 234.83 | 234.83 |
SMSTORE6 | 3996.67 | 239.67 | 239.67 |
SMSTORE7 | 3994.00 | 246.50 | 246.50 |
SMSTORE8 | 3996.83 | 279.83 | 279.83 |
Facility | 5927.67 | 512.33 | 512.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 16.50 | 0.00 | 16.50 |
SMSTORE1 | 0.00 | 6.50 | 0.00 | 6.50 |
SMSTORE2 | 0.00 | 14.17 | 0.00 | 14.17 |
SMSTORE3 | 0.00 | 13.67 | 0.00 | 13.67 |
SMSTORE4 | 0.00 | 13.00 | 0.00 | 13.00 |
LGSTORE2 | 0.00 | 27.67 | 0.00 | 27.67 |
SMSTORE5 | 0.00 | 22.50 | 0.00 | 22.50 |
SMSTORE6 | 0.00 | 22.17 | 0.00 | 22.17 |
SMSTORE7 | 0.00 | 20.67 | 0.00 | 20.67 |
SMSTORE8 | 0.00 | 18.83 | 0.00 | 18.83 |
Facility | 0.00 | 42.50 | 0.00 | 42.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.842 | 0.373 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.692 | 0.399 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.843 | 0.519 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.843 | 0.519 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.843 | 0.519 | 0.000 | 0.000 |
LGSTORE2 | 13.22 | 30.00 | 1805.20 | 0.843 | 0.487 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 0.843 | 0.553 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 0.843 | 0.553 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 0.843 | 0.553 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 0.843 | 0.598 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.826 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.121 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.824 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.824 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.824 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.22 | 30.00 | 1805.20 | 0.826 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 0.825 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 0.825 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 0.825 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 0.825 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1667.12 | 3592.76 | 01-JAN-07:20 | 122463.91 | 03-SEP-12:50 |
Electricity:Building | 715.79 | 2374.76 | 01-JAN-00:10 | 44671.08 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 161.97 | 442.08 | 01-JAN-00:10 | 8324.52 | 01-JAN-10:10 |
InteriorLights:Electricity | 587.07 | 1925.34 | 01-JAN-00:10 | 36581.55 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 135.61 | 367.17 | 01-JAN-00:10 | 6976.27 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 587.07 | 1925.34 | 01-JAN-00:10 | 36581.55 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 85.62 | 233.60 | 01-JAN-00:10 | 4400.95 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 72.45 | 196.15 | 01-JAN-00:10 | 3726.82 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 62.39 | 214.85 | 01-JAN-00:10 | 4044.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 51.92 | 177.40 | 01-JAN-00:10 | 3370.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 62.39 | 214.85 | 01-JAN-00:10 | 4044.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 51.92 | 177.40 | 01-JAN-00:10 | 3370.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 62.39 | 214.85 | 01-JAN-00:10 | 4044.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 51.92 | 177.40 | 01-JAN-00:10 | 3370.57 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 93.68 | 351.51 | 01-JAN-00:10 | 6603.84 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 74.42 | 276.61 | 01-JAN-00:10 | 5255.58 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 46.84 | 175.76 | 01-JAN-00:10 | 3301.92 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 37.21 | 138.30 | 01-JAN-00:10 | 2627.79 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 46.84 | 175.76 | 01-JAN-00:10 | 3301.92 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 37.21 | 138.30 | 01-JAN-00:10 | 2627.79 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 46.84 | 175.76 | 01-JAN-00:10 | 3301.92 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 37.21 | 138.30 | 01-JAN-00:10 | 2627.79 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 46.84 | 175.76 | 01-JAN-00:10 | 3301.92 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 37.21 | 138.30 | 01-JAN-00:10 | 2627.79 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
Electricity:Plant | 58.73 | 1218.00 | 01-JAN-09:10 | 11778.79 | 05-JAN-12:50 |
WaterSystems:Electricity | 58.73 | 1218.00 | 01-JAN-09:10 | 11778.79 | 05-JAN-12:50 |
Water Heater:WaterSystems:Electricity | 58.73 | 1218.00 | 01-JAN-09:10 | 11778.79 | 05-JAN-12:50 |
ElectricityPurchased:Facility | 1667.12 | 3592.76 | 01-JAN-07:20 | 122463.91 | 03-SEP-12:50 |
ElectricityPurchased:Plant | 1667.12 | 3592.76 | 01-JAN-07:20 | 122463.91 | 03-SEP-12:50 |
Cogeneration:ElectricityPurchased | 1667.12 | 3592.76 | 01-JAN-07:20 | 122463.91 | 03-SEP-12:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1667.12 | 3592.76 | 01-JAN-07:20 | 122463.91 | 03-SEP-12:50 |
ElectricityNet:Plant | 1667.12 | 3592.76 | 01-JAN-07:20 | 122463.91 | 03-SEP-12:50 |
Cogeneration:ElectricityNet | 1667.12 | 3592.76 | 01-JAN-07:20 | 122463.91 | 03-SEP-12:50 |
Electricity:HVAC | 781.65 | 0.00 | 01-JAN-00:10 | 73227.33 | 03-SEP-13:00 |
Fans:Electricity | 227.58 | 0.00 | 01-JAN-00:10 | 13193.38 | 06-JAN-20:50 |
General:Fans:Electricity | 227.58 | 0.00 | 01-JAN-00:10 | 13193.38 | 06-JAN-20:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 554.07 | 0.00 | 01-JAN-00:10 | 60033.95 | 03-SEP-13:00 |
ExteriorLights:Electricity | 110.95 | 0.00 | 01-JAN-07:20 | 7048.38 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 110.95 | 0.00 | 01-JAN-07:20 | 7048.38 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Gas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 3159.12 | 0.00 | 01-JAN-00:10 | 333788.08 | 03-SEP-13:00 |
EnergyTransfer:Building | 1064.32 | 0.00 | 01-JAN-00:10 | 109825.55 | 11-OCT-13:00 |
EnergyTransfer:Zone:LGSTORE1 | 220.17 | 0.00 | 01-JAN-00:10 | 18194.85 | 01-OCT-13:00 |
Heating:EnergyTransfer | 10.66 | 0.00 | 01-JAN-00:10 | 20559.60 | 03-SEP-16:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.96 | 0.00 | 01-JAN-00:10 | 1855.81 | 06-JUL-07:10 |
Cooling:EnergyTransfer | 1053.66 | 0.00 | 01-JAN-00:10 | 109825.55 | 11-OCT-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 219.21 | 0.00 | 01-JAN-00:10 | 18194.85 | 01-OCT-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 115.77 | 0.00 | 01-JAN-00:10 | 9565.61 | 01-OCT-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.49 | 0.00 | 01-JAN-00:10 | 1033.00 | 30-MAR-08:20 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 115.28 | 0.00 | 01-JAN-00:10 | 9565.61 | 01-OCT-13:00 |
EnergyTransfer:Zone:SMSTORE2 | 87.85 | 0.00 | 01-JAN-00:10 | 9473.76 | 01-OCT-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.12 | 0.00 | 01-JAN-00:10 | 2288.96 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 86.73 | 0.00 | 01-JAN-00:10 | 9473.76 | 01-OCT-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 87.96 | 0.00 | 01-JAN-00:10 | 9512.65 | 01-OCT-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.10 | 0.00 | 01-JAN-00:10 | 2286.98 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 86.86 | 0.00 | 01-JAN-00:10 | 9512.65 | 01-OCT-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 86.52 | 0.00 | 01-JAN-00:10 | 9425.02 | 01-OCT-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.17 | 0.00 | 01-JAN-00:10 | 2291.11 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 85.35 | 0.00 | 01-JAN-00:10 | 9425.02 | 01-OCT-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 149.98 | 0.00 | 01-JAN-00:10 | 17241.60 | 03-SEP-14:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.70 | 0.00 | 01-JAN-00:10 | 4513.55 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 148.28 | 0.00 | 01-JAN-00:10 | 17241.60 | 03-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE5 | 78.08 | 0.00 | 01-JAN-00:10 | 9101.02 | 03-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.99 | 0.00 | 01-JAN-00:10 | 2300.52 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 77.10 | 0.00 | 01-JAN-00:10 | 9101.02 | 03-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 77.35 | 0.00 | 01-JAN-00:10 | 9046.77 | 03-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 1.01 | 0.00 | 01-JAN-00:10 | 2301.98 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 76.34 | 0.00 | 01-JAN-00:10 | 9046.77 | 03-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 76.69 | 0.00 | 01-JAN-00:10 | 9054.54 | 03-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 1.05 | 0.00 | 01-JAN-00:10 | 2302.24 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 75.64 | 0.00 | 01-JAN-00:10 | 9054.54 | 03-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE8 | 83.94 | 0.00 | 01-JAN-00:10 | 10100.59 | 03-SEP-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 1.08 | 0.00 | 01-JAN-00:10 | 2274.26 | 03-SEP-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 82.87 | 0.00 | 01-JAN-00:10 | 10100.59 | 03-SEP-13:00 |
EnergyTransfer:HVAC | 2094.81 | 0.00 | 01-JAN-00:10 | 228666.93 | 19-AUG-15:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 2094.81 | 0.00 | 01-JAN-00:10 | 228666.93 | 19-AUG-15:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.961 | -219.203 | 0.000 | 0.000 | 12.368 | 135.611 | 26.357 | 15.834 | 0.000 | 17.865 | 16.062 | 0.000 | -3.131 | 0.000 | -2.724 | -0.000 |
SMSTORE1 | 0.000 | 0.000 | 0.494 | -115.273 | 0.000 | 0.000 | 6.184 | 72.445 | 13.179 | 7.921 | 0.000 | 9.698 | 7.851 | 0.000 | -1.566 | 0.000 | -0.933 | -0.000 |
SMSTORE2 | 0.000 | 0.000 | 1.121 | -86.730 | 0.000 | 0.000 | 3.715 | 51.921 | 10.467 | 7.892 | 0.000 | 9.512 | 5.172 | 0.000 | -1.782 | 0.000 | -1.288 | -0.000 |
SMSTORE3 | 0.000 | 0.000 | 1.098 | -86.861 | 0.000 | 0.000 | 3.715 | 51.921 | 10.467 | 7.890 | 0.000 | 9.511 | 5.349 | 0.000 | -1.792 | 0.000 | -1.299 | -0.001 |
SMSTORE4 | 0.000 | 0.000 | 1.169 | -85.345 | 0.000 | 0.000 | 3.715 | 51.921 | 10.467 | 7.898 | 0.000 | 9.512 | 3.687 | 0.000 | -1.765 | 0.000 | -1.259 | -0.000 |
LGSTORE2 | 0.000 | 0.000 | 1.699 | -148.277 | 0.000 | 0.000 | 12.752 | 74.416 | 19.261 | 15.756 | 0.000 | 16.681 | 13.534 | 0.000 | -3.359 | 0.000 | -2.461 | -0.001 |
SMSTORE5 | 0.000 | 0.000 | 0.986 | -77.096 | 0.000 | 0.000 | 6.376 | 37.208 | 9.631 | 7.888 | 0.000 | 9.470 | 8.417 | 0.000 | -1.641 | 0.000 | -1.238 | -0.000 |
SMSTORE6 | 0.000 | 0.000 | 1.007 | -76.337 | 0.000 | 0.000 | 6.376 | 37.208 | 9.631 | 7.895 | 0.000 | 9.471 | 7.603 | 0.000 | -1.630 | 0.000 | -1.224 | -0.000 |
SMSTORE7 | 0.000 | 0.000 | 1.051 | -75.634 | 0.000 | 0.000 | 6.376 | 37.208 | 9.631 | 7.899 | 0.000 | 9.472 | 6.807 | 0.000 | -1.617 | 0.000 | -1.193 | -0.000 |
SMSTORE8 | 0.000 | 0.000 | 1.076 | -82.863 | 0.000 | 0.000 | 6.376 | 37.208 | 9.631 | 7.861 | 0.000 | 10.173 | 14.527 | 0.000 | -1.598 | 0.000 | -2.389 | -0.001 |
Total Facility | 0.000 | 0.000 | 10.661 | -1053.620 | 0.000 | 0.000 | 67.954 | 587.066 | 128.721 | 94.734 | 0.000 | 111.365 | 89.008 | 0.000 | -19.881 | 0.000 | -16.008 | -0.003 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 | -36916.38 | 0.00 | 0.00 | 93.95 | 3671.72 | 749.03 | 1918.16 | 0.00 | 0.00 | 30699.76 | 0.00 | -0.00 | 0.00 | -216.24 | 0.00 |
SMSTORE1 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 | -19554.38 | 0.00 | 0.00 | 46.27 | 1961.49 | 374.52 | 953.85 | 0.00 | 0.00 | 16332.48 | 0.00 | -0.00 | 0.00 | -114.23 | 0.00 |
SMSTORE2 | 20-JAN-08:62 | 0.00 | 0.00 | 0.00 | -18703.32 | 0.00 | 0.00 | 47.45 | 1773.99 | 374.52 | 679.13 | 0.00 | 0.00 | 15970.92 | 0.00 | -0.00 | 0.00 | -142.68 | 0.00 |
SMSTORE3 | 20-JAN-08:62 | 0.00 | 0.00 | 0.00 | -18559.01 | 0.00 | 0.00 | 47.49 | 1773.99 | 374.52 | 679.44 | 0.00 | 0.00 | 15826.24 | 0.00 | -0.00 | 0.00 | -142.66 | 0.00 |
SMSTORE4 | 25-DEC-09:02 | 0.00 | 0.00 | 0.00 | -17876.83 | 0.00 | 0.00 | 44.72 | 1773.99 | 374.52 | 975.54 | 0.00 | 0.00 | 14820.98 | 0.00 | -0.00 | 0.00 | -112.91 | 0.00 |
LGSTORE2 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 | -35075.29 | 0.00 | 0.00 | 208.96 | 2766.09 | 749.03 | 1916.82 | 0.00 | 0.00 | 29621.81 | 0.00 | -0.00 | 0.00 | -187.42 | 0.00 |
SMSTORE5 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 | -18240.29 | 0.00 | 0.00 | 104.46 | 1383.05 | 374.52 | 957.63 | 0.00 | 0.00 | 15523.56 | 0.00 | -0.00 | 0.00 | -102.91 | 0.00 |
SMSTORE6 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 | -18134.29 | 0.00 | 0.00 | 104.75 | 1383.05 | 374.52 | 958.57 | 0.00 | 0.00 | 15414.94 | 0.00 | -0.00 | 0.00 | -101.53 | 0.00 |
SMSTORE7 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 | -18050.04 | 0.00 | 0.00 | 105.53 | 1383.05 | 374.52 | 960.56 | 0.00 | 0.00 | 15323.84 | 0.00 | -0.00 | 0.00 | -97.46 | 0.00 |
SMSTORE8 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 | -19185.24 | 0.00 | 0.00 | 106.19 | 1383.05 | 374.52 | 962.44 | 0.00 | 0.00 | 16467.83 | 0.00 | -0.00 | 0.00 | -108.78 | 0.00 |
Total Facility | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 | -175803.99 | 0.00 | 0.00 | 1085.31 | 24043.21 | 5393.02 | 11551.38 | 0.00 | 0.00 | 134920.28 | 0.00 | 0.00 | 0.00 | -1189.21 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-NOV-09:06 | 0.00 | 0.00 | 4726.81 | 0.00 | 0.00 | 0.00 | 84.33 | 3671.72 | 749.03 | 1887.15 | 0.00 | 454.15 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -11573.20 |
SMSTORE1 | 02-SEP-08:06 | 0.00 | 0.00 | 2446.99 | 0.00 | 0.00 | 0.00 | 42.17 | 1961.49 | 374.52 | 167.89 | 0.00 | 194.06 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5187.11 |
SMSTORE2 | 03-SEP-16:02 | 0.00 | 0.00 | 2737.33 | 0.00 | 0.00 | 0.00 | 52.54 | 1773.99 | 374.52 | 437.22 | 0.00 | 2222.91 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7598.51 |
SMSTORE3 | 03-SEP-16:02 | 0.00 | 0.00 | 2736.60 | 0.00 | 0.00 | 0.00 | 52.54 | 1773.99 | 374.52 | 436.94 | 0.00 | 2222.45 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7597.02 |
SMSTORE4 | 03-SEP-16:02 | 0.00 | 0.00 | 2738.19 | 0.00 | 0.00 | 0.00 | 52.54 | 1773.99 | 374.52 | 437.10 | 0.00 | 2223.24 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7599.58 |
LGSTORE2 | 03-SEP-16:02 | 0.00 | 0.00 | 5395.07 | 0.00 | 0.00 | 0.00 | 231.17 | 2766.09 | 749.03 | 871.10 | 0.00 | 3929.62 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -13942.09 |
SMSTORE5 | 03-SEP-16:02 | 0.00 | 0.00 | 2734.54 | 0.00 | 0.00 | 0.00 | 115.59 | 1383.05 | 374.52 | 438.72 | 0.00 | 2227.94 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7274.34 |
SMSTORE6 | 03-SEP-16:02 | 0.00 | 0.00 | 2734.29 | 0.00 | 0.00 | 0.00 | 115.59 | 1383.05 | 374.52 | 439.06 | 0.00 | 2228.53 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7275.03 |
SMSTORE7 | 03-SEP-16:02 | 0.00 | 0.00 | 2733.97 | 0.00 | 0.00 | 0.00 | 115.59 | 1383.05 | 374.52 | 438.78 | 0.00 | 2228.57 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7274.47 |
SMSTORE8 | 03-SEP-16:02 | 0.00 | 0.00 | 2733.32 | 0.00 | 0.00 | 0.00 | 115.59 | 1383.05 | 374.52 | 434.40 | 0.00 | 2357.31 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7398.18 |
Total Facility | 03-SEP-16:02 | -27144.26 | 27144.26 | 24543.31 | -27144.26 | 0.00 | 0.00 | 2742.60 | 24323.33 | 5393.02 | 5271.06 | 0.00 | 26294.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -61423.11 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9832 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.9832 | 0.2075 | 1.0000 | 0.4115 | 0.2075 | ||
PSZ-AC_2:2 | 1.0436 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0436 | 0.1971 | 1.0000 | 0.2057 | 0.1971 | ||
PSZ-AC_3:3 | 1.0381 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0381 | 0.1982 | 1.0000 | 0.2057 | 0.1982 | ||
PSZ-AC_4:4 | 1.0411 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0411 | 0.1976 | 1.0000 | 0.2057 | 0.1976 | ||
PSZ-AC_5:5 | 1.0366 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0366 | 0.1985 | 1.0000 | 0.2057 | 0.1985 | ||
PSZ-AC_6:6 | 1.8850 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.8850 | 0.2183 | 1.0000 | 0.4115 | 0.2183 | ||
PSZ-AC_7:7 | 0.9870 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9870 | 0.2084 | 1.0000 | 0.2057 | 0.2084 | ||
PSZ-AC_8:8 | 0.9814 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9814 | 0.2096 | 1.0000 | 0.2057 | 0.2096 | ||
PSZ-AC_9:9 | 0.9804 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9804 | 0.2098 | 1.0000 | 0.2057 | 0.2098 | ||
PSZ-AC_10:10 | 1.0698 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0698 | 0.1923 | 1.0000 | 0.2057 | 0.1923 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9832 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.9832 | 1.0000 | 1.0000 | 0.4115 | 0.2075 | ||
PSZ-AC_2:2 | 1.0436 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0436 | 1.0000 | 1.0000 | 0.2057 | 0.1971 | ||
PSZ-AC_3:3 | 1.0381 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0381 | 1.0000 | 1.0000 | 0.2057 | 0.1982 | ||
PSZ-AC_4:4 | 1.0411 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0411 | 1.0000 | 1.0000 | 0.2057 | 0.1976 | ||
PSZ-AC_5:5 | 1.0366 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0366 | 1.0000 | 1.0000 | 0.2057 | 0.1985 | ||
PSZ-AC_6:6 | 1.8850 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.8850 | 1.0000 | 1.0000 | 0.4115 | 0.2183 | ||
PSZ-AC_7:7 | 0.9870 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9870 | 1.0000 | 1.0000 | 0.2057 | 0.2084 | ||
PSZ-AC_8:8 | 0.9814 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9814 | 1.0000 | 1.0000 | 0.2057 | 0.2096 | ||
PSZ-AC_9:9 | 0.9804 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9804 | 1.0000 | 1.0000 | 0.2057 | 0.2098 | ||
PSZ-AC_10:10 | 1.0698 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0698 | 1.0000 | 1.0000 | 0.2057 | 0.1923 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.9832 | 1.9832 | 1.9832 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.0436 | 1.0436 | 1.0436 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.0381 | 1.0381 | 1.0381 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.0411 | 1.0411 | 1.0411 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.0366 | 1.0366 | 1.0366 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.8850 | 1.8850 | 1.8850 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.9870 | 0.9870 | 0.9870 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.9814 | 0.9814 | 0.9814 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.9804 | 0.9804 | 0.9804 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0698 | 1.0698 | 1.0698 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9832 | 1.9832 | 1.9832 | 1.9832 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0436 | 1.0436 | 1.0436 | 1.0436 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0381 | 1.0381 | 1.0381 | 1.0381 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0411 | 1.0411 | 1.0411 | 1.0411 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0366 | 1.0366 | 1.0366 | 1.0366 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8850 | 1.8850 | 1.8850 | 1.8850 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9870 | 0.9870 | 0.9870 | 0.9870 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9814 | 0.9814 | 0.9814 | 0.9814 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9804 | 0.9804 | 0.9804 | 0.9804 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0698 | 1.0698 | 1.0698 | 1.0698 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.9832 | 1.9832 | 1.9832 | 0.4115 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.0436 | 1.0436 | 1.0436 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.0381 | 1.0381 | 1.0381 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.0411 | 1.0411 | 1.0411 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.0366 | 1.0366 | 1.0366 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.8850 | 1.8850 | 1.8850 | 0.4115 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.9870 | 0.9870 | 0.9870 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.9814 | 0.9814 | 0.9814 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.9804 | 0.9804 | 0.9804 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0698 | 1.0698 | 1.0698 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9832 | 1.9832 | 1.9832 | 1.9832 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0436 | 1.0436 | 1.0436 | 1.0436 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0381 | 1.0381 | 1.0381 | 1.0381 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0411 | 1.0411 | 1.0411 | 1.0411 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0366 | 1.0366 | 1.0366 | 1.0366 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8850 | 1.8850 | 1.8850 | 1.8850 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9870 | 0.9870 | 0.9870 | 0.9870 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9814 | 0.9814 | 0.9814 | 0.9814 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9804 | 0.9804 | 0.9804 | 0.9804 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0698 | 1.0698 | 1.0698 | 1.0698 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:54
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Total gross floor area [m2] | 2090.32 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 42.50 |
Number of hours not met | 42.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 554.07 | 60033.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 587.07 | 36581.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 110.95 | 7048.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 227.58 | 13193.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 58.73 | 11778.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1667.12 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1667.12 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 280.85 |
Space Heating | 0.00 |
Space Cooling | 265.06 |
Fans (All) | 108.87 |
Service Water Heating | 28.10 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 797.55 |
Subtotal | 797.55 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 35.21 |
Space Heating | 0.00 |
Space Cooling | 33.23 |
Fans (All) | 13.65 |
Service Water Heating | 3.52 |
Receptacle Equipment | 7.72 |
Miscellaneous | 6.66 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5131. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Meter
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Meter
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_HI_HONOLULU
For: Meter
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161723E+11 | 36921.00 | 20-JAN-09:02 | 21.97 | 14.73 | 0.752550E+09 | 898.98 | 14-JAN-13:09 | 21.38 | 18.57 |
February | 0.150228E+11 | 33449.74 | 07-FEB-09:02 | 21.88 | 15.23 | 0.679298E+09 | 898.97 | 12-FEB-17:30 | 23.35 | 17.58 |
March | 0.167153E+11 | 33866.03 | 07-MAR-09:02 | 22.38 | 15.98 | 0.745652E+09 | 898.97 | 05-MAR-17:30 | 24.15 | 18.72 |
April | 0.161548E+11 | 33082.80 | 01-APR-08:62 | 21.88 | 15.99 | 0.727139E+09 | 898.98 | 02-APR-16:19 | 25.40 | 17.89 |
May | 0.185478E+11 | 31624.57 | 31-MAY-08:61 | 25.18 | 18.55 | 0.748613E+09 | 898.96 | 28-MAY-16:30 | 28.05 | 20.56 |
June | 0.185692E+11 | 29755.93 | 06-JUN-08:61 | 25.12 | 19.80 | 0.723357E+09 | 898.96 | 04-JUN-16:19 | 27.93 | 20.11 |
July | 0.205387E+11 | 29102.20 | 18-JUL-08:61 | 27.48 | 20.47 | 0.754924E+09 | 898.96 | 30-JUL-16:30 | 29.15 | 21.02 |
August | 0.208382E+11 | 28529.57 | 24-AUG-08:61 | 26.05 | 20.82 | 0.744593E+09 | 898.95 | 06-AUG-16:30 | 28.30 | 21.99 |
September | 0.203364E+11 | 28918.44 | 27-SEP-08:61 | 26.38 | 20.21 | 0.729440E+09 | 898.95 | 17-SEP-16:30 | 28.60 | 21.38 |
October | 0.204277E+11 | 28474.20 | 17-OCT-08:61 | 24.68 | 20.11 | 0.752849E+09 | 898.96 | 08-OCT-16:30 | 29.75 | 21.78 |
November | 0.182943E+11 | 32144.35 | 26-NOV-08:62 | 21.38 | 17.99 | 0.728143E+09 | 898.97 | 26-NOV-17:30 | 23.05 | 18.06 |
December | 0.175921E+11 | 34921.28 | 19-DEC-09:01 | 23.27 | 16.59 | 0.756448E+09 | 898.98 | 25-DEC-17:30 | 23.95 | 17.26 |
Annual Sum or Average | 0.219210E+12 | 0.884301E+10 | ||||||||
Minimum of Months | 0.150228E+11 | 28474.20 | 21.38 | 14.73 | 0.679298E+09 | 898.95 | 21.38 | 17.26 | ||
Maximum of Months | 0.208382E+11 | 36921.00 | 27.48 | 20.82 | 0.756448E+09 | 898.98 | 29.75 | 21.99 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.866932E+10 | 19556.56 | 20-JAN-09:02 | 21.97 | 14.73 | 0.376324E+09 | 449.49 | 14-JAN-13:09 | 21.38 | 18.57 |
February | 0.797984E+10 | 18472.50 | 07-FEB-09:02 | 21.88 | 15.23 | 0.339690E+09 | 449.48 | 12-FEB-17:30 | 23.35 | 17.58 |
March | 0.885892E+10 | 18078.93 | 07-MAR-09:02 | 22.38 | 15.98 | 0.372883E+09 | 449.48 | 05-MAR-17:30 | 24.15 | 18.72 |
April | 0.856721E+10 | 17798.58 | 30-APR-07:02 | 22.15 | 17.80 | 0.363617E+09 | 449.49 | 02-APR-16:19 | 25.40 | 17.89 |
May | 0.977764E+10 | 17156.21 | 21-MAY-07:02 | 22.57 | 19.59 | 0.374344E+09 | 449.48 | 28-MAY-16:30 | 28.05 | 20.56 |
June | 0.971171E+10 | 16502.65 | 06-JUN-08:61 | 25.12 | 19.80 | 0.361702E+09 | 449.48 | 04-JUN-16:19 | 27.93 | 20.11 |
July | 0.107012E+11 | 15700.73 | 18-JUL-08:61 | 27.48 | 20.47 | 0.377473E+09 | 449.48 | 30-JUL-16:30 | 29.15 | 21.02 |
August | 0.108188E+11 | 15685.59 | 24-AUG-08:61 | 26.05 | 20.82 | 0.372311E+09 | 449.48 | 06-AUG-16:30 | 28.30 | 21.99 |
September | 0.104990E+11 | 15825.76 | 24-SEP-07:02 | 24.60 | 22.61 | 0.364729E+09 | 449.48 | 17-SEP-16:30 | 28.60 | 21.38 |
October | 0.107216E+11 | 16063.89 | 15-OCT-07:02 | 22.95 | 21.24 | 0.376451E+09 | 449.48 | 08-OCT-16:30 | 29.75 | 21.78 |
November | 0.962205E+10 | 17765.56 | 26-NOV-08:62 | 21.38 | 17.99 | 0.364095E+09 | 449.48 | 26-NOV-17:30 | 23.05 | 18.06 |
December | 0.934972E+10 | 18592.40 | 19-DEC-09:01 | 23.27 | 16.59 | 0.378258E+09 | 449.49 | 25-DEC-17:30 | 23.95 | 17.26 |
Annual Sum or Average | 0.115277E+12 | 0.442188E+10 | ||||||||
Minimum of Months | 0.797984E+10 | 15685.59 | 21.38 | 14.73 | 0.339690E+09 | 449.48 | 21.38 | 17.26 | ||
Maximum of Months | 0.108188E+11 | 19556.56 | 27.48 | 22.61 | 0.378258E+09 | 449.49 | 29.75 | 21.99 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.636913E+10 | 18706.70 | 20-JAN-08:62 | 20.78 | 14.46 | 0.224280E+09 | 449.49 | 14-JAN-13:09 | 21.38 | 18.57 |
February | 0.584400E+10 | 15631.58 | 09-FEB-08:62 | 21.05 | 17.84 | 0.203753E+09 | 449.48 | 11-FEB-13:50 | 24.08 | 16.32 |
March | 0.658940E+10 | 17170.13 | 07-MAR-08:62 | 20.37 | 15.41 | 0.230279E+09 | 449.47 | 25-MAR-12:09 | 26.52 | 17.81 |
April | 0.627244E+10 | 17299.59 | 02-APR-08:62 | 22.80 | 17.14 | 0.219238E+09 | 449.47 | 01-APR-12:09 | 25.50 | 17.03 |
May | 0.740003E+10 | 16304.51 | 31-MAY-07:02 | 23.58 | 18.09 | 0.227525E+09 | 449.45 | 27-MAY-12:09 | 29.60 | 20.63 |
June | 0.742449E+10 | 15089.78 | 11-JUN-08:61 | 25.72 | 20.07 | 0.222700E+09 | 449.44 | 10-JUN-12:09 | 29.40 | 20.95 |
July | 0.809886E+10 | 15200.93 | 18-JUL-07:01 | 26.28 | 19.61 | 0.224470E+09 | 449.43 | 08-JUL-12:09 | 31.20 | 21.97 |
August | 0.842420E+10 | 14621.00 | 23-AUG-07:01 | 25.37 | 20.57 | 0.230659E+09 | 449.41 | 05-AUG-12:00 | 30.00 | 21.62 |
September | 0.793774E+10 | 14798.73 | 27-SEP-07:01 | 25.18 | 20.08 | 0.219581E+09 | 449.41 | 16-SEP-12:09 | 27.20 | 22.88 |
October | 0.817166E+10 | 14986.10 | 17-OCT-07:01 | 23.48 | 19.40 | 0.224664E+09 | 449.41 | 28-OCT-12:09 | 30.18 | 22.21 |
November | 0.729188E+10 | 16488.12 | 15-NOV-08:61 | 23.98 | 18.53 | 0.216921E+09 | 449.40 | 25-NOV-13:09 | 28.30 | 22.38 |
December | 0.690984E+10 | 17958.39 | 25-DEC-09:02 | 22.75 | 16.77 | 0.224127E+09 | 449.46 | 23-DEC-13:09 | 25.77 | 17.78 |
Annual Sum or Average | 0.867337E+11 | 0.266820E+10 | ||||||||
Minimum of Months | 0.584400E+10 | 14621.00 | 20.37 | 14.46 | 0.203753E+09 | 449.40 | 21.38 | 16.32 | ||
Maximum of Months | 0.842420E+10 | 18706.70 | 26.28 | 20.57 | 0.230659E+09 | 449.49 | 31.20 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.635347E+10 | 18562.35 | 20-JAN-08:62 | 20.78 | 14.46 | 0.224278E+09 | 449.49 | 14-JAN-13:09 | 21.38 | 18.57 |
February | 0.583292E+10 | 15649.07 | 09-FEB-08:62 | 21.05 | 17.84 | 0.203751E+09 | 449.48 | 11-FEB-13:50 | 24.08 | 16.32 |
March | 0.658101E+10 | 17200.42 | 07-MAR-08:62 | 20.37 | 15.41 | 0.230277E+09 | 449.47 | 25-MAR-12:09 | 26.52 | 17.81 |
April | 0.626180E+10 | 17342.01 | 02-APR-08:62 | 22.80 | 17.14 | 0.219237E+09 | 449.47 | 01-APR-12:09 | 25.50 | 17.03 |
May | 0.741183E+10 | 16355.04 | 31-MAY-07:02 | 23.58 | 18.09 | 0.227526E+09 | 449.45 | 27-MAY-12:09 | 29.60 | 20.63 |
June | 0.743822E+10 | 15141.14 | 11-JUN-08:61 | 25.72 | 20.07 | 0.222700E+09 | 449.44 | 10-JUN-12:09 | 29.40 | 20.95 |
July | 0.813418E+10 | 15254.28 | 18-JUL-07:01 | 26.28 | 19.61 | 0.224471E+09 | 449.43 | 08-JUL-12:09 | 31.20 | 21.97 |
August | 0.845246E+10 | 14669.17 | 23-AUG-07:01 | 25.37 | 20.57 | 0.230660E+09 | 449.41 | 05-AUG-12:00 | 30.00 | 21.62 |
September | 0.798068E+10 | 14847.55 | 27-SEP-07:01 | 25.18 | 20.08 | 0.219584E+09 | 449.41 | 16-SEP-12:09 | 27.20 | 22.88 |
October | 0.820888E+10 | 15038.01 | 17-OCT-07:01 | 23.48 | 19.40 | 0.224667E+09 | 449.41 | 28-OCT-12:09 | 30.18 | 22.21 |
November | 0.730037E+10 | 16527.47 | 15-NOV-08:61 | 23.98 | 18.53 | 0.216921E+09 | 449.40 | 25-NOV-13:09 | 28.30 | 22.38 |
December | 0.690792E+10 | 18009.84 | 25-DEC-09:02 | 22.75 | 16.77 | 0.224127E+09 | 449.46 | 23-DEC-13:09 | 25.77 | 17.78 |
Annual Sum or Average | 0.868637E+11 | 0.266820E+10 | ||||||||
Minimum of Months | 0.583292E+10 | 14669.17 | 20.37 | 14.46 | 0.203751E+09 | 449.40 | 21.38 | 16.32 | ||
Maximum of Months | 0.845246E+10 | 18562.35 | 26.28 | 20.57 | 0.230660E+09 | 449.49 | 31.20 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.621690E+10 | 17711.62 | 10-JAN-08:62 | 21.78 | 15.25 | 0.224258E+09 | 449.49 | 14-JAN-13:09 | 21.38 | 18.57 |
February | 0.570385E+10 | 15227.14 | 01-FEB-08:62 | 22.15 | 19.31 | 0.203733E+09 | 449.48 | 11-FEB-13:50 | 24.08 | 16.32 |
March | 0.643028E+10 | 16182.37 | 24-MAR-07:03 | 20.28 | 15.65 | 0.230257E+09 | 449.47 | 25-MAR-12:09 | 26.52 | 17.81 |
April | 0.612082E+10 | 17214.57 | 02-APR-08:62 | 22.80 | 17.14 | 0.219216E+09 | 449.47 | 01-APR-12:09 | 25.50 | 17.03 |
May | 0.728066E+10 | 16230.39 | 31-MAY-07:02 | 23.58 | 18.09 | 0.227507E+09 | 449.45 | 27-MAY-12:09 | 29.60 | 20.63 |
June | 0.731754E+10 | 15058.49 | 11-JUN-08:61 | 25.72 | 20.07 | 0.222685E+09 | 449.44 | 10-JUN-12:09 | 29.40 | 20.95 |
July | 0.802260E+10 | 15168.40 | 18-JUL-07:01 | 26.28 | 19.61 | 0.224456E+09 | 449.43 | 08-JUL-12:09 | 31.20 | 21.97 |
August | 0.833145E+10 | 14577.12 | 23-AUG-07:01 | 25.37 | 20.57 | 0.230644E+09 | 449.41 | 05-AUG-12:00 | 30.00 | 21.62 |
September | 0.787092E+10 | 14754.87 | 27-SEP-07:01 | 25.18 | 20.08 | 0.219569E+09 | 449.41 | 16-SEP-12:09 | 27.20 | 22.88 |
October | 0.809009E+10 | 14948.16 | 17-OCT-07:01 | 23.48 | 19.40 | 0.224650E+09 | 449.41 | 28-OCT-12:09 | 30.18 | 22.21 |
November | 0.718427E+10 | 16407.76 | 15-NOV-08:61 | 23.98 | 18.53 | 0.216905E+09 | 449.41 | 25-NOV-13:09 | 28.30 | 22.38 |
December | 0.677899E+10 | 17880.06 | 25-DEC-09:02 | 22.75 | 16.77 | 0.224109E+09 | 449.46 | 23-DEC-13:09 | 25.77 | 17.78 |
Annual Sum or Average | 0.853484E+11 | 0.266799E+10 | ||||||||
Minimum of Months | 0.570385E+10 | 14577.12 | 20.28 | 15.25 | 0.203733E+09 | 449.41 | 21.38 | 16.32 | ||
Maximum of Months | 0.833145E+10 | 17880.06 | 26.28 | 20.57 | 0.230644E+09 | 449.49 | 31.20 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107133E+11 | 35079.93 | 20-JAN-09:02 | 21.97 | 14.73 | 0.765731E+09 | 1198.64 | 21-JAN-15:09 | 22.98 | 17.97 |
February | 0.987684E+10 | 30950.45 | 07-FEB-09:02 | 21.88 | 15.23 | 0.697279E+09 | 1198.60 | 11-FEB-15:00 | 23.90 | 16.33 |
March | 0.111613E+11 | 32007.50 | 07-MAR-09:02 | 22.38 | 15.98 | 0.789624E+09 | 1198.58 | 25-MAR-14:09 | 26.10 | 17.78 |
April | 0.105540E+11 | 31658.70 | 02-APR-09:02 | 23.27 | 17.24 | 0.752426E+09 | 1198.58 | 01-APR-14:09 | 25.60 | 17.37 |
May | 0.126833E+11 | 30453.66 | 31-MAY-08:61 | 25.18 | 18.55 | 0.778290E+09 | 1198.49 | 20-MAY-14:09 | 28.80 | 21.96 |
June | 0.127326E+11 | 28312.95 | 06-JUN-08:61 | 25.12 | 19.80 | 0.763362E+09 | 1198.50 | 03-JUN-14:00 | 28.30 | 20.42 |
July | 0.139458E+11 | 27940.26 | 18-JUL-08:61 | 27.48 | 20.47 | 0.768157E+09 | 1198.46 | 01-JUL-14:00 | 31.10 | 21.52 |
August | 0.145628E+11 | 27315.31 | 23-AUG-08:61 | 27.48 | 20.81 | 0.790374E+09 | 1198.42 | 05-AUG-14:09 | 31.60 | 22.39 |
September | 0.137378E+11 | 27494.52 | 27-SEP-08:61 | 26.38 | 20.21 | 0.753130E+09 | 1198.42 | 09-SEP-14:30 | 30.00 | 22.64 |
October | 0.141379E+11 | 27556.63 | 17-OCT-08:61 | 24.68 | 20.11 | 0.766580E+09 | 1198.42 | 21-OCT-14:00 | 28.90 | 22.67 |
November | 0.124848E+11 | 30399.18 | 15-NOV-09:01 | 24.68 | 18.73 | 0.738020E+09 | 1198.49 | 25-NOV-15:00 | 26.10 | 20.73 |
December | 0.116927E+11 | 33267.17 | 25-DEC-10:01 | 23.65 | 17.35 | 0.767295E+09 | 1198.57 | 23-DEC-15:00 | 24.60 | 17.23 |
Annual Sum or Average | 0.148283E+12 | 0.913027E+10 | ||||||||
Minimum of Months | 0.987684E+10 | 27315.31 | 21.88 | 14.73 | 0.697279E+09 | 1198.42 | 22.98 | 16.33 | ||
Maximum of Months | 0.145628E+11 | 35079.93 | 27.48 | 20.81 | 0.790374E+09 | 1198.64 | 31.60 | 22.67 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.553765E+10 | 18242.77 | 20-JAN-09:02 | 21.97 | 14.73 | 0.382861E+09 | 599.32 | 21-JAN-15:09 | 22.98 | 17.97 |
February | 0.510639E+10 | 15332.90 | 07-FEB-09:02 | 21.88 | 15.23 | 0.348632E+09 | 599.30 | 11-FEB-15:00 | 23.90 | 16.33 |
March | 0.577348E+10 | 16644.17 | 07-MAR-09:02 | 22.38 | 15.98 | 0.394805E+09 | 599.29 | 25-MAR-14:09 | 26.10 | 17.78 |
April | 0.546783E+10 | 16469.17 | 02-APR-09:02 | 23.27 | 17.24 | 0.376203E+09 | 599.29 | 01-APR-14:09 | 25.60 | 17.37 |
May | 0.660024E+10 | 15830.24 | 31-MAY-08:61 | 25.18 | 18.55 | 0.389131E+09 | 599.24 | 27-MAY-14:00 | 29.40 | 20.56 |
June | 0.662157E+10 | 14721.52 | 06-JUN-08:61 | 25.12 | 19.80 | 0.381671E+09 | 599.25 | 03-JUN-14:00 | 28.30 | 20.42 |
July | 0.728279E+10 | 14554.43 | 18-JUL-08:61 | 27.48 | 20.47 | 0.384070E+09 | 599.22 | 01-JUL-14:00 | 31.10 | 21.52 |
August | 0.760871E+10 | 14224.20 | 23-AUG-08:61 | 27.48 | 20.81 | 0.395173E+09 | 599.20 | 05-AUG-14:09 | 31.60 | 22.39 |
September | 0.716229E+10 | 14308.37 | 27-SEP-08:61 | 26.38 | 20.21 | 0.376553E+09 | 599.20 | 09-SEP-14:09 | 30.40 | 22.54 |
October | 0.738563E+10 | 14337.91 | 17-OCT-08:61 | 24.68 | 20.11 | 0.383279E+09 | 599.20 | 21-OCT-14:00 | 28.90 | 22.67 |
November | 0.649056E+10 | 15808.05 | 15-NOV-09:01 | 24.68 | 18.73 | 0.369002E+09 | 599.24 | 25-NOV-15:00 | 26.10 | 20.73 |
December | 0.606190E+10 | 17323.26 | 25-DEC-10:01 | 23.65 | 17.35 | 0.383639E+09 | 599.28 | 23-DEC-15:00 | 24.60 | 17.23 |
Annual Sum or Average | 0.770990E+11 | 0.456502E+10 | ||||||||
Minimum of Months | 0.510639E+10 | 14224.20 | 21.88 | 14.73 | 0.348632E+09 | 599.20 | 22.98 | 16.33 | ||
Maximum of Months | 0.760871E+10 | 18242.77 | 27.48 | 20.81 | 0.395173E+09 | 599.32 | 31.60 | 22.67 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.547084E+10 | 18136.77 | 20-JAN-09:02 | 21.97 | 14.73 | 0.382851E+09 | 599.32 | 21-JAN-15:09 | 22.98 | 17.97 |
February | 0.504425E+10 | 15007.89 | 06-FEB-09:01 | 24.13 | 17.20 | 0.348624E+09 | 599.30 | 11-FEB-15:00 | 23.90 | 16.33 |
March | 0.570451E+10 | 16545.58 | 07-MAR-09:02 | 22.38 | 15.98 | 0.394796E+09 | 599.29 | 25-MAR-14:09 | 26.10 | 17.78 |
April | 0.540476E+10 | 16370.06 | 02-APR-09:02 | 23.27 | 17.24 | 0.376195E+09 | 599.29 | 01-APR-14:09 | 25.60 | 17.37 |
May | 0.653506E+10 | 15733.87 | 31-MAY-08:61 | 25.18 | 18.55 | 0.389123E+09 | 599.24 | 27-MAY-14:00 | 29.40 | 20.56 |
June | 0.656043E+10 | 14623.93 | 06-JUN-08:61 | 25.12 | 19.80 | 0.381666E+09 | 599.25 | 03-JUN-14:00 | 28.30 | 20.42 |
July | 0.722112E+10 | 14478.33 | 18-JUL-08:61 | 27.48 | 20.47 | 0.384064E+09 | 599.22 | 01-JUL-14:00 | 31.10 | 21.52 |
August | 0.754804E+10 | 14148.61 | 23-AUG-08:61 | 27.48 | 20.81 | 0.395169E+09 | 599.20 | 05-AUG-14:09 | 31.60 | 22.39 |
September | 0.710293E+10 | 14234.07 | 27-SEP-08:61 | 26.38 | 20.21 | 0.376548E+09 | 599.20 | 09-SEP-14:09 | 30.40 | 22.54 |
October | 0.732501E+10 | 14248.55 | 17-OCT-08:61 | 24.68 | 20.11 | 0.383273E+09 | 599.20 | 21-OCT-14:00 | 28.90 | 22.67 |
November | 0.642778E+10 | 15709.09 | 15-NOV-09:01 | 24.68 | 18.73 | 0.368996E+09 | 599.24 | 25-NOV-15:00 | 26.10 | 20.73 |
December | 0.599530E+10 | 17219.17 | 25-DEC-10:01 | 23.65 | 17.35 | 0.383630E+09 | 599.29 | 23-DEC-15:00 | 24.60 | 17.23 |
Annual Sum or Average | 0.763400E+11 | 0.456493E+10 | ||||||||
Minimum of Months | 0.504425E+10 | 14148.61 | 21.97 | 14.73 | 0.348624E+09 | 599.20 | 22.98 | 16.33 | ||
Maximum of Months | 0.754804E+10 | 18136.77 | 27.48 | 20.81 | 0.395169E+09 | 599.32 | 31.60 | 22.67 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.537885E+10 | 18052.54 | 20-JAN-09:02 | 21.97 | 14.73 | 0.382832E+09 | 599.32 | 21-JAN-15:09 | 22.98 | 17.97 |
February | 0.495348E+10 | 14920.93 | 06-FEB-09:01 | 24.13 | 17.20 | 0.348606E+09 | 599.30 | 11-FEB-15:00 | 23.90 | 16.33 |
March | 0.560698E+10 | 16460.71 | 07-MAR-09:02 | 22.38 | 15.98 | 0.394778E+09 | 599.29 | 25-MAR-14:09 | 26.10 | 17.78 |
April | 0.532662E+10 | 16284.93 | 02-APR-09:02 | 23.27 | 17.24 | 0.376176E+09 | 599.29 | 01-APR-14:09 | 25.60 | 17.37 |
May | 0.648026E+10 | 15661.66 | 31-MAY-08:61 | 25.18 | 18.55 | 0.389110E+09 | 599.24 | 27-MAY-14:00 | 29.40 | 20.56 |
June | 0.651358E+10 | 14554.99 | 06-JUN-08:61 | 25.12 | 19.80 | 0.381657E+09 | 599.25 | 03-JUN-14:00 | 28.30 | 20.42 |
July | 0.719175E+10 | 14448.73 | 18-JUL-08:61 | 27.48 | 20.47 | 0.384060E+09 | 599.22 | 01-JUL-14:00 | 31.10 | 21.52 |
August | 0.752758E+10 | 14121.34 | 23-AUG-08:61 | 27.48 | 20.81 | 0.395163E+09 | 599.20 | 05-AUG-14:09 | 31.60 | 22.39 |
September | 0.707320E+10 | 14206.61 | 27-SEP-08:61 | 26.38 | 20.21 | 0.376543E+09 | 599.20 | 09-SEP-14:09 | 30.40 | 22.54 |
October | 0.729417E+10 | 14196.09 | 17-OCT-08:61 | 24.68 | 20.11 | 0.383265E+09 | 599.20 | 21-OCT-14:00 | 28.90 | 22.67 |
November | 0.637007E+10 | 15646.61 | 15-NOV-09:01 | 24.68 | 18.73 | 0.368986E+09 | 599.24 | 25-NOV-15:00 | 26.10 | 20.73 |
December | 0.592040E+10 | 17136.86 | 25-DEC-10:01 | 23.65 | 17.35 | 0.383615E+09 | 599.29 | 23-DEC-15:00 | 24.60 | 17.23 |
Annual Sum or Average | 0.756369E+11 | 0.456479E+10 | ||||||||
Minimum of Months | 0.495348E+10 | 14121.34 | 21.97 | 14.73 | 0.348606E+09 | 599.20 | 22.98 | 16.33 | ||
Maximum of Months | 0.752758E+10 | 18052.54 | 27.48 | 20.81 | 0.395163E+09 | 599.32 | 31.60 | 22.67 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.573452E+10 | 19187.90 | 20-JAN-09:02 | 21.97 | 14.73 | 0.382843E+09 | 599.32 | 21-JAN-15:09 | 22.98 | 17.97 |
February | 0.520039E+10 | 15982.01 | 06-FEB-09:01 | 24.13 | 17.20 | 0.348612E+09 | 599.30 | 11-FEB-15:00 | 23.90 | 16.33 |
March | 0.594572E+10 | 17081.56 | 26-MAR-09:02 | 24.27 | 17.17 | 0.394782E+09 | 599.29 | 25-MAR-14:09 | 26.10 | 17.78 |
April | 0.579344E+10 | 17401.12 | 02-APR-09:02 | 23.27 | 17.24 | 0.376202E+09 | 599.29 | 01-APR-14:09 | 25.60 | 17.37 |
May | 0.718277E+10 | 16620.79 | 31-MAY-08:61 | 25.18 | 18.55 | 0.389152E+09 | 599.24 | 27-MAY-14:00 | 29.40 | 20.56 |
June | 0.722878E+10 | 15292.17 | 11-JUN-09:01 | 26.43 | 20.50 | 0.381690E+09 | 599.25 | 03-JUN-14:00 | 28.30 | 20.42 |
July | 0.804786E+10 | 15308.06 | 18-JUL-08:61 | 27.48 | 20.47 | 0.384108E+09 | 599.22 | 01-JUL-14:00 | 31.10 | 21.52 |
August | 0.850356E+10 | 14681.41 | 23-AUG-08:61 | 27.48 | 20.81 | 0.395206E+09 | 599.19 | 05-AUG-14:00 | 31.10 | 22.32 |
September | 0.782486E+10 | 15124.57 | 27-SEP-08:61 | 26.38 | 20.21 | 0.376588E+09 | 599.20 | 09-SEP-14:09 | 30.40 | 22.54 |
October | 0.814377E+10 | 14914.69 | 17-OCT-08:61 | 24.68 | 20.11 | 0.383311E+09 | 599.19 | 21-OCT-14:00 | 28.90 | 22.67 |
November | 0.690994E+10 | 16759.45 | 15-NOV-09:01 | 24.68 | 18.73 | 0.369014E+09 | 599.24 | 25-NOV-15:00 | 26.10 | 20.73 |
December | 0.635091E+10 | 18367.19 | 25-DEC-10:01 | 23.65 | 17.35 | 0.383638E+09 | 599.29 | 23-DEC-15:00 | 24.60 | 17.23 |
Annual Sum or Average | 0.828665E+11 | 0.456515E+10 | ||||||||
Minimum of Months | 0.520039E+10 | 14681.41 | 21.97 | 14.73 | 0.348612E+09 | 599.19 | 22.98 | 16.33 | ||
Maximum of Months | 0.850356E+10 | 19187.90 | 27.48 | 20.81 | 0.395206E+09 | 599.32 | 31.10 | 22.67 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44771240.22 | 3345.40 | 09-JAN-09:05 | 24.87 |
February | 66445264.62 | 3732.83 | 03-FEB-09:06 | 26.10 |
March | 66693485.83 | 3632.66 | 15-MAR-08:06 | 25.87 |
April | 63985548.78 | 3649.37 | 10-APR-08:06 | 25.87 |
May | 0.114560E+09 | 3921.65 | 19-MAY-08:06 | 26.97 |
June | 0.112944E+09 | 4061.33 | 21-JUN-08:06 | 27.32 |
July | 86678607.59 | 4555.17 | 12-JUL-08:06 | 28.07 |
August | 99056347.86 | 4487.98 | 10-AUG-08:06 | 27.98 |
September | 94191678.42 | 3956.32 | 07-SEP-08:06 | 26.88 |
October | 87305215.47 | 4520.52 | 12-OCT-08:06 | 28.07 |
November | 74890621.67 | 4727.50 | 06-NOV-09:06 | 28.40 |
December | 48940062.72 | 3620.51 | 02-DEC-09:06 | 26.20 |
Annual Sum or Average | 0.960462E+09 | |||
Minimum of Months | 44771240.22 | 3345.40 | 24.87 | |
Maximum of Months | 0.114560E+09 | 4727.50 | 28.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22904555.22 | 1812.05 | 09-JAN-09:05 | 24.87 |
February | 35627581.46 | 1912.66 | 03-FEB-09:06 | 26.10 |
March | 36293907.41 | 1903.59 | 15-MAR-08:06 | 25.87 |
April | 33603510.85 | 1917.80 | 10-APR-08:06 | 25.87 |
May | 57724297.58 | 2012.08 | 09-MAY-08:06 | 26.88 |
June | 56039933.43 | 2017.21 | 11-JUN-07:05 | 25.10 |
July | 42800800.17 | 2342.97 | 17-JUL-08:06 | 27.98 |
August | 50947433.21 | 2341.71 | 02-AUG-08:06 | 27.98 |
September | 50227094.19 | 2447.12 | 02-SEP-08:06 | 28.58 |
October | 45818972.31 | 2438.21 | 07-OCT-08:06 | 28.40 |
November | 37706734.76 | 2364.68 | 06-NOV-09:06 | 28.40 |
December | 24650738.67 | 1965.76 | 06-DEC-09:06 | 26.43 |
Annual Sum or Average | 0.494346E+09 | |||
Minimum of Months | 22904555.22 | 1812.05 | 24.87 | |
Maximum of Months | 57724297.58 | 2447.12 | 28.58 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31832204.53 | 1516.02 | 29-JAN-09:05 | 23.68 |
February | 41610671.24 | 1542.12 | 05-FEB-09:06 | 24.50 |
March | 49631163.58 | 1514.83 | 12-MAR-16:12 | 27.03 |
April | 59139052.19 | 1768.28 | 30-APR-08:05 | 24.60 |
May | 0.109410E+09 | 1935.47 | 14-MAY-08:06 | 26.28 |
June | 0.131768E+09 | 2035.23 | 18-JUN-08:06 | 26.85 |
July | 0.145873E+09 | 2203.62 | 09-JUL-16:12 | 30.20 |
August | 0.144674E+09 | 2488.30 | 20-AUG-16:02 | 31.42 |
September | 0.138668E+09 | 2736.81 | 03-SEP-16:02 | 32.62 |
October | 0.121410E+09 | 2603.83 | 01-OCT-16:02 | 31.93 |
November | 85282625.86 | 2171.20 | 23-NOV-09:06 | 27.38 |
December | 61121558.37 | 1819.93 | 03-DEC-09:07 | 26.10 |
Annual Sum or Average | 0.112042E+10 | |||
Minimum of Months | 31832204.53 | 1514.83 | 23.68 | |
Maximum of Months | 0.145873E+09 | 2736.81 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31616724.34 | 1525.67 | 29-JAN-09:05 | 23.68 |
February | 41906267.77 | 1549.25 | 05-FEB-09:06 | 24.50 |
March | 49925081.16 | 1518.98 | 12-MAR-16:12 | 27.03 |
April | 59427163.81 | 1774.03 | 30-APR-08:05 | 24.60 |
May | 0.108549E+09 | 1939.01 | 14-MAY-08:06 | 26.28 |
June | 0.128658E+09 | 2035.74 | 18-JUN-08:06 | 26.85 |
July | 0.141064E+09 | 2205.96 | 09-JUL-16:12 | 30.20 |
August | 0.139950E+09 | 2488.38 | 20-AUG-16:02 | 31.42 |
September | 0.134125E+09 | 2736.07 | 03-SEP-16:02 | 32.62 |
October | 0.118776E+09 | 2604.33 | 01-OCT-16:02 | 31.93 |
November | 82620199.35 | 2171.21 | 23-NOV-09:06 | 27.38 |
December | 60946888.55 | 1825.22 | 03-DEC-09:07 | 26.10 |
Annual Sum or Average | 0.109756E+10 | |||
Minimum of Months | 31616724.34 | 1518.98 | 23.68 | |
Maximum of Months | 0.141064E+09 | 2736.07 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33701599.51 | 1540.87 | 29-JAN-09:05 | 23.68 |
February | 43483545.03 | 1559.17 | 13-FEB-08:05 | 23.98 |
March | 52219083.56 | 1519.82 | 12-MAR-16:12 | 27.03 |
April | 62834567.83 | 1787.38 | 30-APR-08:05 | 24.60 |
May | 0.113291E+09 | 1936.40 | 14-MAY-08:06 | 26.28 |
June | 0.137863E+09 | 2036.82 | 18-JUN-08:06 | 26.85 |
July | 0.150796E+09 | 2205.87 | 09-JUL-16:12 | 30.20 |
August | 0.149558E+09 | 2490.14 | 20-AUG-16:02 | 31.42 |
September | 0.144346E+09 | 2737.67 | 03-SEP-16:02 | 32.62 |
October | 0.125296E+09 | 2606.19 | 01-OCT-16:02 | 31.93 |
November | 90037848.26 | 2173.27 | 23-NOV-09:06 | 27.38 |
December | 65178661.44 | 1822.85 | 03-DEC-09:07 | 26.10 |
Annual Sum or Average | 0.116861E+10 | |||
Minimum of Months | 33701599.51 | 1519.82 | 23.68 | |
Maximum of Months | 0.150796E+09 | 2737.67 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70545809.88 | 3187.21 | 04-JAN-09:06 | 25.78 |
February | 0.103166E+09 | 3573.02 | 03-FEB-09:06 | 26.10 |
March | 0.110351E+09 | 3525.54 | 19-MAR-09:06 | 25.78 |
April | 0.125042E+09 | 3941.80 | 09-APR-09:06 | 27.12 |
May | 0.185729E+09 | 4376.29 | 21-MAY-09:06 | 28.07 |
June | 0.179995E+09 | 4248.81 | 18-JUN-09:06 | 27.75 |
July | 0.186546E+09 | 4610.44 | 04-JUL-09:06 | 28.40 |
August | 0.174798E+09 | 4886.29 | 20-AUG-16:02 | 31.42 |
September | 0.184932E+09 | 5394.10 | 03-SEP-16:02 | 32.62 |
October | 0.169283E+09 | 5123.56 | 01-OCT-16:02 | 31.93 |
November | 0.123191E+09 | 4589.19 | 23-NOV-10:06 | 28.40 |
December | 84973698.47 | 3624.73 | 15-DEC-09:06 | 26.52 |
Annual Sum or Average | 0.169855E+10 | |||
Minimum of Months | 70545809.88 | 3187.21 | 25.78 | |
Maximum of Months | 0.186546E+09 | 5394.10 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43682481.94 | 2044.98 | 08-JAN-10:06 | 27.12 |
February | 60867156.92 | 1816.56 | 03-FEB-09:06 | 26.10 |
March | 63518900.93 | 1810.72 | 19-MAR-09:06 | 25.78 |
April | 71953769.63 | 1986.03 | 09-APR-09:06 | 27.12 |
May | 0.103730E+09 | 2205.87 | 21-MAY-09:06 | 28.07 |
June | 0.102862E+09 | 2218.07 | 18-JUN-09:06 | 27.75 |
July | 0.109061E+09 | 2381.57 | 04-JUL-09:06 | 28.40 |
August | 0.101782E+09 | 2484.36 | 20-AUG-16:02 | 31.42 |
September | 0.105708E+09 | 2734.02 | 03-SEP-16:02 | 32.62 |
October | 95955266.11 | 2601.04 | 01-OCT-16:02 | 31.93 |
November | 72854073.74 | 2370.84 | 23-NOV-10:06 | 28.40 |
December | 53627718.04 | 1829.62 | 15-DEC-09:06 | 26.52 |
Annual Sum or Average | 0.985603E+09 | |||
Minimum of Months | 43682481.94 | 1810.72 | 25.78 | |
Maximum of Months | 0.109061E+09 | 2734.02 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44221161.95 | 2037.82 | 08-JAN-10:06 | 27.12 |
February | 61545298.46 | 1797.83 | 26-FEB-10:06 | 26.20 |
March | 64264880.06 | 1788.86 | 19-MAR-09:06 | 25.78 |
April | 73076872.26 | 1983.93 | 09-APR-09:06 | 27.12 |
May | 0.105027E+09 | 2206.05 | 21-MAY-09:06 | 28.07 |
June | 0.106261E+09 | 2049.89 | 21-JUN-08:06 | 27.32 |
July | 0.111256E+09 | 2396.03 | 16-JUL-09:06 | 28.48 |
August | 0.105266E+09 | 2483.82 | 20-AUG-16:02 | 31.42 |
September | 0.108585E+09 | 2733.77 | 03-SEP-16:02 | 32.62 |
October | 98705814.41 | 2600.75 | 01-OCT-16:02 | 31.93 |
November | 75184344.39 | 2348.87 | 23-NOV-10:06 | 28.40 |
December | 53808558.25 | 1830.47 | 15-DEC-09:06 | 26.52 |
Annual Sum or Average | 0.100720E+10 | |||
Minimum of Months | 44221161.95 | 1788.86 | 25.78 | |
Maximum of Months | 0.111256E+09 | 2733.77 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 47038603.85 | 2031.49 | 08-JAN-10:06 | 27.12 |
February | 64046304.93 | 1799.98 | 26-FEB-10:06 | 26.20 |
March | 66295970.99 | 1872.65 | 12-MAR-09:06 | 26.28 |
April | 75287144.64 | 1980.26 | 23-APR-09:06 | 26.47 |
May | 0.108362E+09 | 2204.11 | 21-MAY-09:06 | 28.07 |
June | 0.109383E+09 | 2202.82 | 18-JUN-09:06 | 27.75 |
July | 0.117558E+09 | 2389.47 | 16-JUL-09:06 | 28.48 |
August | 0.110325E+09 | 2483.47 | 20-AUG-16:02 | 31.42 |
September | 0.112404E+09 | 2733.45 | 03-SEP-16:02 | 32.62 |
October | 0.102668E+09 | 2601.57 | 01-OCT-16:02 | 31.93 |
November | 80640768.82 | 2346.25 | 23-NOV-10:06 | 28.40 |
December | 56812168.25 | 1828.82 | 15-DEC-09:06 | 26.52 |
Annual Sum or Average | 0.105082E+10 | |||
Minimum of Months | 47038603.85 | 1799.98 | 26.20 | |
Maximum of Months | 0.117558E+09 | 2733.45 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55204601.09 | 2127.37 | 08-JAN-10:06 | 27.12 |
February | 75117868.40 | 2074.14 | 20-FEB-10:06 | 26.78 |
March | 76953521.07 | 1957.35 | 12-MAR-09:06 | 26.28 |
April | 83529232.22 | 2070.00 | 23-APR-09:06 | 26.47 |
May | 0.107606E+09 | 2172.34 | 07-MAY-09:06 | 27.38 |
June | 0.104640E+09 | 2266.18 | 18-JUN-09:06 | 27.75 |
July | 0.111589E+09 | 2482.41 | 02-JUL-09:06 | 28.40 |
August | 0.103378E+09 | 2492.55 | 20-AUG-16:02 | 31.42 |
September | 0.114699E+09 | 2732.78 | 03-SEP-16:02 | 32.62 |
October | 0.102550E+09 | 2611.81 | 01-OCT-16:02 | 31.93 |
November | 79418072.83 | 2468.67 | 23-NOV-10:06 | 28.40 |
December | 61103745.66 | 1935.91 | 02-DEC-09:06 | 26.20 |
Annual Sum or Average | 0.107579E+10 | |||
Minimum of Months | 55204601.09 | 1935.91 | 26.20 | |
Maximum of Months | 0.114699E+09 | 2732.78 | 32.62 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.114998E+11 | 6976.27 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.104054E+11 | 6976.27 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.115236E+11 | 6976.27 | 01-MAR-10:09 | 0.223972E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.111588E+11 | 6976.27 | 01-APR-09:09 | 0.216880E+10 | 1348.26 | 01-APR-09:09 |
May | 0.114998E+11 | 6976.27 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.111588E+11 | 6976.27 | 01-JUN-09:09 | 0.216880E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.115236E+11 | 6976.27 | 01-JUL-09:09 | 0.223972E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.114998E+11 | 6976.27 | 01-AUG-09:09 | 0.223514E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.111826E+11 | 6976.27 | 01-SEP-09:09 | 0.217339E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.114998E+11 | 6976.27 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.111112E+11 | 6976.27 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.115474E+11 | 6976.27 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.135611E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.104054E+11 | 6976.27 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.115474E+11 | 6976.27 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.614337E+10 | 3726.82 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.555869E+10 | 3726.82 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.615608E+10 | 3726.82 | 01-MAR-10:09 | 0.111986E+10 | 674.13 | 01-MAR-10:09 |
April | 0.596119E+10 | 3726.82 | 01-APR-09:09 | 0.108440E+10 | 674.13 | 01-APR-09:09 |
May | 0.614337E+10 | 3726.82 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.596119E+10 | 3726.82 | 01-JUN-09:09 | 0.108440E+10 | 674.13 | 01-JUN-09:09 |
July | 0.615608E+10 | 3726.82 | 01-JUL-09:09 | 0.111986E+10 | 674.13 | 01-JUL-09:09 |
August | 0.614337E+10 | 3726.82 | 01-AUG-09:09 | 0.111757E+10 | 674.13 | 01-AUG-09:09 |
September | 0.597390E+10 | 3726.82 | 01-SEP-09:09 | 0.108669E+10 | 674.13 | 01-SEP-09:09 |
October | 0.614337E+10 | 3726.82 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.593577E+10 | 3726.82 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.616879E+10 | 3726.82 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.724452E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.555869E+10 | 3726.82 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.616879E+10 | 3726.82 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.438359E+10 | 3370.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.396975E+10 | 3370.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.447555E+10 | 3370.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.425331E+10 | 3370.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.442957E+10 | 3370.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.432228E+10 | 3370.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.436060E+10 | 3370.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.447555E+10 | 3370.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.425331E+10 | 3370.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.438359E+10 | 3370.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.425331E+10 | 3370.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.436060E+10 | 3370.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.519210E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.396975E+10 | 3370.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.447555E+10 | 3370.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.438359E+10 | 3370.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.396975E+10 | 3370.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.447555E+10 | 3370.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.425331E+10 | 3370.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.442957E+10 | 3370.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.432228E+10 | 3370.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.436060E+10 | 3370.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.447555E+10 | 3370.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.425331E+10 | 3370.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.438359E+10 | 3370.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.425331E+10 | 3370.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.436060E+10 | 3370.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.519210E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.396975E+10 | 3370.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.447555E+10 | 3370.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.438359E+10 | 3370.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.396975E+10 | 3370.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.447555E+10 | 3370.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.425331E+10 | 3370.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.442957E+10 | 3370.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.432228E+10 | 3370.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.436060E+10 | 3370.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.447555E+10 | 3370.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.425331E+10 | 3370.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.438359E+10 | 3370.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.425331E+10 | 3370.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.436060E+10 | 3370.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.519210E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.396975E+10 | 3370.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.447555E+10 | 3370.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.627948E+10 | 5255.58 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.568798E+10 | 5255.58 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.642287E+10 | 5255.58 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.609426E+10 | 5255.58 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.635118E+10 | 5255.58 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.620181E+10 | 5255.58 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.624363E+10 | 5255.58 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.642287E+10 | 5255.58 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.609426E+10 | 5255.58 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.627948E+10 | 5255.58 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.609426E+10 | 5255.58 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.624363E+10 | 5255.58 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.744157E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.568798E+10 | 5255.58 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.642287E+10 | 5255.58 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.313974E+10 | 2627.79 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.284399E+10 | 2627.79 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.321144E+10 | 2627.79 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.304713E+10 | 2627.79 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.317559E+10 | 2627.79 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.310090E+10 | 2627.79 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.312181E+10 | 2627.79 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.321144E+10 | 2627.79 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.304713E+10 | 2627.79 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.313974E+10 | 2627.79 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.304713E+10 | 2627.79 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.312181E+10 | 2627.79 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.372078E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.284399E+10 | 2627.79 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.321144E+10 | 2627.79 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.313974E+10 | 2627.79 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.284399E+10 | 2627.79 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.321144E+10 | 2627.79 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.304713E+10 | 2627.79 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.317559E+10 | 2627.79 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.310090E+10 | 2627.79 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.312181E+10 | 2627.79 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.321144E+10 | 2627.79 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.304713E+10 | 2627.79 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.313974E+10 | 2627.79 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.304713E+10 | 2627.79 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.312181E+10 | 2627.79 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.372078E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.284399E+10 | 2627.79 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.321144E+10 | 2627.79 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.313974E+10 | 2627.79 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.284399E+10 | 2627.79 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.321144E+10 | 2627.79 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.304713E+10 | 2627.79 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.317559E+10 | 2627.79 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.310090E+10 | 2627.79 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.312181E+10 | 2627.79 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.321144E+10 | 2627.79 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.304713E+10 | 2627.79 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.313974E+10 | 2627.79 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.304713E+10 | 2627.79 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.312181E+10 | 2627.79 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.372078E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.284399E+10 | 2627.79 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.321144E+10 | 2627.79 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.313974E+10 | 2627.79 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.284399E+10 | 2627.79 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.321144E+10 | 2627.79 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.304713E+10 | 2627.79 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.317559E+10 | 2627.79 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.310090E+10 | 2627.79 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.312181E+10 | 2627.79 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.321144E+10 | 2627.79 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.304713E+10 | 2627.79 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.313974E+10 | 2627.79 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.304713E+10 | 2627.79 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.312181E+10 | 2627.79 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.372078E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.284399E+10 | 2627.79 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.321144E+10 | 2627.79 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.114998E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592311E+09 | 0.525618E+09 |
February | 0.163016E+10 | 0.104054E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641868E+09 | 0.303487E+09 |
March | 0.178954E+10 | 0.115236E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982227E+09 | 0.331253E+09 |
April | 0.174484E+10 | 0.111588E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107452E+10 | 0.291426E+09 |
May | 0.179537E+10 | 0.114998E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168776E+10 | 0.181010E+09 |
June | 0.173447E+10 | 0.111588E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167297E+10 | 0.147340E+09 |
July | 0.181028E+10 | 0.115236E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230983E+10 | 0.113382E+09 |
August | 0.178501E+10 | 0.114998E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251518E+10 | 0.101200E+09 |
September | 0.174937E+10 | 0.111826E+11 | 0.217339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208805E+10 | 82284681.51 |
October | 0.180574E+10 | 0.114998E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218310E+10 | 0.112164E+09 |
November | 0.174613E+10 | 0.111112E+11 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129099E+10 | 0.226654E+09 |
December | 0.181481E+10 | 0.115474E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826635E+09 | 0.307953E+09 |
Annual Sum or Average | 0.212115E+11 | 0.135611E+12 | 0.263573E+11 | 0.178654E+11 | 0.272377E+10 | ||||
Minimum of Months | 0.163016E+10 | 0.104054E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592311E+09 | 82284681.51 |
Maximum of Months | 0.181481E+10 | 0.115474E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251518E+10 | 0.525618E+09 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.614337E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326628E+09 | 0.203727E+09 |
February | 0.815075E+09 | 0.555869E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354301E+09 | 0.108460E+09 |
March | 0.894769E+09 | 0.615608E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538798E+09 | 0.110899E+09 |
April | 0.872416E+09 | 0.596119E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587664E+09 | 96643216.81 |
May | 0.897684E+09 | 0.614337E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921668E+09 | 57831190.37 |
June | 0.867232E+09 | 0.596119E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900298E+09 | 46940514.53 |
July | 0.905135E+09 | 0.615608E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124264E+10 | 35545370.85 |
August | 0.892501E+09 | 0.614337E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135898E+10 | 32020002.09 |
September | 0.874683E+09 | 0.597390E+10 | 0.108669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112218E+10 | 26069583.43 |
October | 0.902868E+09 | 0.614337E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119351E+10 | 36265958.46 |
November | 0.873064E+09 | 0.593577E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697574E+09 | 73184568.61 |
December | 0.907403E+09 | 0.616879E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453304E+09 | 0.105708E+09 |
Annual Sum or Average | 0.106057E+11 | 0.724452E+11 | 0.131787E+11 | 0.969755E+10 | 0.933294E+09 | ||||
Minimum of Months | 0.815075E+09 | 0.555869E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326628E+09 | 26069583.43 |
Maximum of Months | 0.907403E+09 | 0.616879E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135898E+10 | 0.203727E+09 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323399E+09 | 0.247298E+09 |
February | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349994E+09 | 0.142828E+09 |
March | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531117E+09 | 0.145415E+09 |
April | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577300E+09 | 0.138238E+09 |
May | 0.544247E+09 | 0.442957E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905611E+09 | 84279122.34 |
June | 0.532585E+09 | 0.432228E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881651E+09 | 72459996.66 |
July | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121050E+10 | 58865230.02 |
August | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133665E+10 | 47133861.09 |
September | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109283E+10 | 40972231.30 |
October | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116622E+10 | 51488724.31 |
November | 0.518979E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686310E+09 | 0.107833E+09 |
December | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450117E+09 | 0.150712E+09 |
Annual Sum or Average | 0.638324E+10 | 0.519210E+11 | 0.104672E+11 | 0.951170E+10 | 0.128752E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323399E+09 | 40972231.30 |
Maximum of Months | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133665E+10 | 0.247298E+09 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323399E+09 | 0.247176E+09 |
February | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349994E+09 | 0.142888E+09 |
March | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531118E+09 | 0.145653E+09 |
April | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577304E+09 | 0.138367E+09 |
May | 0.544247E+09 | 0.442957E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905586E+09 | 85106911.99 |
June | 0.532585E+09 | 0.432228E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881605E+09 | 73864115.61 |
July | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121026E+10 | 61247735.93 |
August | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133651E+10 | 48982093.95 |
September | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109234E+10 | 43021128.40 |
October | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116610E+10 | 52873412.28 |
November | 0.518979E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686299E+09 | 0.108753E+09 |
December | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450116E+09 | 0.151129E+09 |
Annual Sum or Average | 0.638324E+10 | 0.519210E+11 | 0.104672E+11 | 0.951063E+10 | 0.129906E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323399E+09 | 43021128.40 |
Maximum of Months | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133651E+10 | 0.247176E+09 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323407E+09 | 0.244009E+09 |
February | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350003E+09 | 0.140388E+09 |
March | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531140E+09 | 0.142582E+09 |
April | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577347E+09 | 0.134916E+09 |
May | 0.544247E+09 | 0.442957E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905695E+09 | 82007676.85 |
June | 0.532585E+09 | 0.432228E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881733E+09 | 69763749.72 |
July | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121058E+10 | 56833206.12 |
August | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133670E+10 | 45353830.54 |
September | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109273E+10 | 39563065.30 |
October | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116628E+10 | 50310701.99 |
November | 0.518979E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686347E+09 | 0.105297E+09 |
December | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450127E+09 | 0.147705E+09 |
Annual Sum or Average | 0.638324E+10 | 0.519210E+11 | 0.104672E+11 | 0.951209E+10 | 0.125873E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323407E+09 | 39563065.30 |
Maximum of Months | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133670E+10 | 0.244009E+09 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.627948E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567201E+09 | 0.472941E+09 |
February | 0.167188E+10 | 0.568798E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612259E+09 | 0.277211E+09 |
March | 0.189386E+10 | 0.642287E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.933787E+09 | 0.286326E+09 |
April | 0.180380E+10 | 0.609426E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101479E+10 | 0.271088E+09 |
May | 0.186509E+10 | 0.635118E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158763E+10 | 0.163174E+09 |
June | 0.182945E+10 | 0.620181E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154563E+10 | 0.132087E+09 |
July | 0.183943E+10 | 0.624363E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212127E+10 | 0.101353E+09 |
August | 0.189386E+10 | 0.642287E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234600E+10 | 83538519.02 |
September | 0.180380E+10 | 0.609426E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191823E+10 | 72304334.79 |
October | 0.183632E+10 | 0.627948E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204566E+10 | 99734002.83 |
November | 0.176881E+10 | 0.609426E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120033E+10 | 0.206564E+09 |
December | 0.183943E+10 | 0.624363E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788341E+09 | 0.295167E+09 |
Annual Sum or Average | 0.218821E+11 | 0.744157E+11 | 0.192612E+11 | 0.166811E+11 | 0.246149E+10 | ||||
Minimum of Months | 0.167188E+10 | 0.568798E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567201E+09 | 72304334.79 |
Maximum of Months | 0.189386E+10 | 0.642287E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234600E+10 | 0.472941E+09 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322511E+09 | 0.248212E+09 |
February | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348212E+09 | 0.143003E+09 |
March | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530580E+09 | 0.144870E+09 |
April | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576355E+09 | 0.136510E+09 |
May | 0.932542E+09 | 0.317559E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901700E+09 | 80284996.99 |
June | 0.914724E+09 | 0.310090E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876405E+09 | 63146030.25 |
July | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120330E+10 | 47376572.65 |
August | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133113E+10 | 39259366.47 |
September | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108809E+10 | 33567554.07 |
October | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116259E+10 | 48831889.08 |
November | 0.884402E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680788E+09 | 0.102711E+09 |
December | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448017E+09 | 0.150193E+09 |
Annual Sum or Average | 0.109410E+11 | 0.372078E+11 | 0.963059E+10 | 0.946968E+10 | 0.123797E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322511E+09 | 33567554.07 |
Maximum of Months | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133113E+10 | 0.248212E+09 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322521E+09 | 0.246881E+09 |
February | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348219E+09 | 0.141938E+09 |
March | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530599E+09 | 0.143664E+09 |
April | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576378E+09 | 0.135178E+09 |
May | 0.932542E+09 | 0.317559E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901778E+09 | 79173736.65 |
June | 0.914724E+09 | 0.310090E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876503E+09 | 61823954.74 |
July | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120358E+10 | 46121177.07 |
August | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133131E+10 | 38276974.67 |
September | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108836E+10 | 32593389.27 |
October | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116276E+10 | 48065904.57 |
November | 0.884402E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680831E+09 | 0.101442E+09 |
December | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448026E+09 | 0.148787E+09 |
Annual Sum or Average | 0.109410E+11 | 0.372078E+11 | 0.963059E+10 | 0.947087E+10 | 0.122395E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322521E+09 | 32593389.27 |
Maximum of Months | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133131E+10 | 0.246881E+09 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322534E+09 | 0.243563E+09 |
February | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348237E+09 | 0.139251E+09 |
March | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530625E+09 | 0.140777E+09 |
April | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576415E+09 | 0.131950E+09 |
May | 0.932542E+09 | 0.317559E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901869E+09 | 76758457.84 |
June | 0.914724E+09 | 0.310090E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876668E+09 | 58897192.47 |
July | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120388E+10 | 43470409.66 |
August | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133151E+10 | 36398228.18 |
September | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108865E+10 | 30718814.20 |
October | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116299E+10 | 46655291.54 |
November | 0.884402E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680897E+09 | 98713339.29 |
December | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448037E+09 | 0.145583E+09 |
Annual Sum or Average | 0.109410E+11 | 0.372078E+11 | 0.963059E+10 | 0.947231E+10 | 0.119274E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322534E+09 | 30718814.20 |
Maximum of Months | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133151E+10 | 0.243563E+09 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340178E+09 | 0.420672E+09 |
February | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366576E+09 | 0.260613E+09 |
March | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563550E+09 | 0.286458E+09 |
April | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614675E+09 | 0.268967E+09 |
May | 0.932542E+09 | 0.317559E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962982E+09 | 0.166313E+09 |
June | 0.914724E+09 | 0.310090E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951914E+09 | 0.131440E+09 |
July | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130500E+10 | 0.102068E+09 |
August | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143809E+10 | 86504857.79 |
September | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118204E+10 | 72173507.96 |
October | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123616E+10 | 0.103690E+09 |
November | 0.884402E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736928E+09 | 0.207056E+09 |
December | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475152E+09 | 0.283148E+09 |
Annual Sum or Average | 0.109410E+11 | 0.372078E+11 | 0.963059E+10 | 0.101732E+11 | 0.238910E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340178E+09 | 72173507.96 |
Maximum of Months | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143809E+10 | 0.420672E+09 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 6976.27 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2655.92 | 06-JAN-13:00 | 2255.17 | 25-JAN-12:10 |
February | 2159.72 | 03-FEB-13:09 | 6976.27 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2401.01 | 25-FEB-13:00 | 1108.47 | 06-FEB-18:00 |
March | 2159.72 | 03-MAR-13:09 | 6976.27 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3011.26 | 29-MAR-13:00 | 839.59 | 03-MAR-15:00 |
April | 2159.72 | 01-APR-12:09 | 6976.27 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3033.90 | 09-APR-14:00 | 983.66 | 27-APR-06:00 |
May | 2159.72 | 05-MAY-12:09 | 6976.27 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3600.56 | 17-MAY-13:00 | 549.49 | 31-MAY-04:00 |
June | 2159.72 | 02-JUN-12:09 | 6976.27 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3382.34 | 29-JUN-11:10 | 379.17 | 13-JUN-05:00 |
July | 2159.72 | 01-JUL-12:09 | 6976.27 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4060.81 | 09-JUL-12:00 | 393.03 | 13-JUL-06:00 |
August | 2159.72 | 04-AUG-12:09 | 6976.27 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4332.52 | 11-AUG-14:00 | 312.34 | 13-AUG-03:00 |
September | 2159.72 | 01-SEP-12:09 | 6976.27 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4726.05 | 03-SEP-13:00 | 334.21 | 30-SEP-06:00 |
October | 2159.72 | 01-OCT-12:09 | 6976.27 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4567.73 | 01-OCT-13:00 | 414.43 | 19-OCT-07:03 |
November | 2159.72 | 03-NOV-12:09 | 6976.27 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3419.07 | 04-NOV-13:00 | 1124.23 | 25-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 6976.27 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3270.21 | 13-DEC-14:00 | 1021.56 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 6976.27 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2401.01 | 312.34 | |||||
Maximum of Months | 2159.72 | 6976.27 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4726.05 | 2255.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 3726.82 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1479.03 | 06-JAN-13:00 | 1256.99 | 25-JAN-12:10 |
February | 1079.86 | 03-FEB-13:09 | 3726.82 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.47 | 25-FEB-13:00 | 611.99 | 06-FEB-18:00 |
March | 1079.86 | 03-MAR-13:09 | 3726.82 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1658.14 | 29-MAR-13:00 | 464.74 | 03-MAR-15:00 |
April | 1079.86 | 01-APR-12:09 | 3726.82 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1666.23 | 09-APR-14:00 | 470.34 | 11-APR-14:00 |
May | 1079.86 | 05-MAY-12:09 | 3726.82 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1967.24 | 17-MAY-13:00 | 170.02 | 04-MAY-08:00 |
June | 1079.86 | 02-JUN-12:09 | 3726.82 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1842.33 | 29-JUN-11:10 | 116.97 | 13-JUN-08:00 |
July | 1079.86 | 01-JUL-12:09 | 3726.82 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2242.00 | 09-JUL-12:00 | 119.34 | 13-JUL-06:00 |
August | 1079.86 | 04-AUG-12:09 | 3726.82 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2392.01 | 11-AUG-14:00 | 135.44 | 26-AUG-07:10 |
September | 1079.86 | 01-SEP-12:09 | 3726.82 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2567.77 | 03-SEP-13:00 | 127.89 | 19-SEP-07:10 |
October | 1079.86 | 01-OCT-12:09 | 3726.82 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2521.87 | 01-OCT-13:00 | 224.12 | 19-OCT-07:03 |
November | 1079.86 | 03-NOV-12:09 | 3726.82 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1852.99 | 04-NOV-13:00 | 615.83 | 25-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 3726.82 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1810.33 | 13-DEC-14:00 | 573.59 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3726.82 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.47 | 116.97 | |||||
Maximum of Months | 1079.86 | 3726.82 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2567.77 | 1256.99 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3370.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1479.02 | 06-JAN-13:00 | 1256.99 | 25-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 3370.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.50 | 25-FEB-13:00 | 893.69 | 12-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3370.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1658.13 | 29-MAR-13:00 | 832.03 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3370.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1666.20 | 09-APR-14:00 | 617.76 | 16-APR-17:00 |
May | 1079.86 | 06-MAY-12:09 | 3370.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1967.23 | 17-MAY-13:00 | 742.93 | 14-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 3370.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1842.31 | 29-JUN-11:10 | 178.30 | 25-JUN-17:00 |
July | 1079.86 | 01-JUL-12:09 | 3370.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2242.01 | 09-JUL-12:00 | 130.50 | 22-JUL-18:10 |
August | 1079.86 | 05-AUG-12:09 | 3370.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2391.97 | 11-AUG-14:00 | 164.53 | 06-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3370.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2567.73 | 03-SEP-13:00 | 141.12 | 30-SEP-18:10 |
October | 1079.86 | 07-OCT-12:09 | 3370.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2521.83 | 01-OCT-13:00 | 694.05 | 22-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3370.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1852.98 | 04-NOV-13:00 | 865.37 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3370.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1810.32 | 13-DEC-14:00 | 1056.44 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.50 | 130.50 | |||||
Maximum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2567.73 | 1256.99 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3370.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1479.02 | 06-JAN-13:00 | 1257.00 | 25-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 3370.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.49 | 25-FEB-13:00 | 891.58 | 12-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3370.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1658.13 | 29-MAR-13:00 | 831.87 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3370.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1666.20 | 09-APR-14:00 | 618.31 | 16-APR-17:00 |
May | 1079.86 | 06-MAY-12:09 | 3370.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1967.23 | 17-MAY-13:00 | 747.19 | 14-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 3370.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1842.31 | 29-JUN-11:10 | 184.12 | 25-JUN-17:00 |
July | 1079.86 | 01-JUL-12:09 | 3370.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2242.01 | 09-JUL-12:00 | 131.88 | 22-JUL-18:10 |
August | 1079.86 | 05-AUG-12:09 | 3370.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2391.97 | 11-AUG-14:00 | 170.70 | 06-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3370.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2567.74 | 03-SEP-13:00 | 143.19 | 30-SEP-18:10 |
October | 1079.86 | 07-OCT-12:09 | 3370.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2521.83 | 01-OCT-13:00 | 696.97 | 22-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3370.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1852.98 | 04-NOV-13:00 | 865.54 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3370.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1810.31 | 13-DEC-14:00 | 1056.12 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.49 | 131.88 | |||||
Maximum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2567.74 | 1257.00 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3370.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1479.01 | 06-JAN-13:00 | 1257.00 | 25-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 3370.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.48 | 25-FEB-13:00 | 878.47 | 12-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3370.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1658.13 | 29-MAR-13:00 | 819.47 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3370.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1666.20 | 09-APR-14:00 | 605.32 | 16-APR-17:00 |
May | 1079.86 | 06-MAY-12:09 | 3370.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1967.22 | 17-MAY-13:00 | 736.25 | 14-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 3370.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1842.31 | 29-JUN-11:10 | 174.02 | 25-JUN-17:00 |
July | 1079.86 | 01-JUL-12:09 | 3370.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2242.01 | 09-JUL-12:00 | 127.87 | 22-JUL-18:10 |
August | 1079.86 | 05-AUG-12:09 | 3370.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2391.96 | 11-AUG-14:00 | 160.72 | 06-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3370.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2567.73 | 03-SEP-13:00 | 137.68 | 30-SEP-18:10 |
October | 1079.86 | 07-OCT-12:09 | 3370.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2521.83 | 01-OCT-13:00 | 684.63 | 22-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3370.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1852.97 | 04-NOV-13:00 | 854.09 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3370.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1810.31 | 13-DEC-14:00 | 1044.37 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.48 | 127.87 | |||||
Maximum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2567.73 | 1257.00 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 5255.58 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2597.36 | 06-JAN-13:00 | 2207.13 | 25-JAN-12:10 |
February | 2879.63 | 04-FEB-15:09 | 5255.58 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2359.18 | 25-FEB-13:00 | 1482.43 | 12-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 5255.58 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2916.76 | 29-MAR-13:00 | 1389.98 | 05-MAR-18:00 |
April | 2879.63 | 01-APR-14:09 | 5255.58 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2932.08 | 09-APR-14:00 | 1017.19 | 16-APR-17:00 |
May | 2879.63 | 06-MAY-14:09 | 5255.58 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3464.50 | 17-MAY-13:00 | 1256.80 | 14-MAY-17:00 |
June | 2879.63 | 03-JUN-14:09 | 5255.58 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3246.06 | 29-JUN-11:10 | 274.10 | 25-JUN-17:00 |
July | 2879.63 | 01-JUL-14:09 | 5255.58 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3942.18 | 09-JUL-12:00 | 224.62 | 22-JUL-18:10 |
August | 2879.63 | 05-AUG-14:09 | 5255.58 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4205.89 | 11-AUG-14:00 | 260.22 | 06-AUG-07:02 |
September | 2879.63 | 02-SEP-14:09 | 5255.58 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4525.72 | 03-SEP-13:00 | 244.12 | 30-SEP-18:10 |
October | 2879.63 | 07-OCT-14:09 | 5255.58 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4434.21 | 01-OCT-13:00 | 1161.22 | 22-OCT-17:00 |
November | 2879.63 | 04-NOV-14:09 | 5255.58 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3267.20 | 04-NOV-13:00 | 1450.60 | 26-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 5255.58 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3181.94 | 13-DEC-14:00 | 1776.94 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 5255.58 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2359.18 | 224.62 | |||||
Maximum of Months | 2879.63 | 5255.58 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4525.72 | 2207.13 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2627.79 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1479.04 | 06-JAN-13:00 | 1256.98 | 25-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 2627.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.52 | 25-FEB-13:00 | 831.70 | 12-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2627.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1658.16 | 29-MAR-13:00 | 776.07 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2627.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1666.21 | 09-APR-14:00 | 564.19 | 16-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 2627.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1967.26 | 17-MAY-13:00 | 695.59 | 14-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 2627.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1842.37 | 29-JUN-11:10 | 133.07 | 25-JUN-17:00 |
July | 1439.81 | 01-JUL-14:09 | 2627.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2242.01 | 09-JUL-12:00 | 111.53 | 22-JUL-18:10 |
August | 1439.81 | 05-AUG-14:09 | 2627.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2391.98 | 11-AUG-14:00 | 136.53 | 06-AUG-07:02 |
September | 1439.81 | 02-SEP-14:09 | 2627.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2567.73 | 03-SEP-13:00 | 121.42 | 19-SEP-07:10 |
October | 1439.81 | 07-OCT-14:09 | 2627.79 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2521.83 | 01-OCT-13:00 | 650.34 | 22-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2627.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1852.97 | 04-NOV-13:00 | 810.93 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2627.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1810.35 | 13-DEC-14:00 | 997.14 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.52 | 111.53 | |||||
Maximum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2567.73 | 1256.98 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2627.79 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1479.04 | 06-JAN-13:00 | 1256.99 | 25-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 2627.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.52 | 25-FEB-13:00 | 825.43 | 12-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2627.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1658.15 | 29-MAR-13:00 | 769.99 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2627.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1666.21 | 09-APR-14:00 | 558.67 | 16-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 2627.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1967.26 | 17-MAY-13:00 | 689.71 | 14-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 2627.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1842.37 | 29-JUN-11:10 | 127.28 | 25-JUN-17:00 |
July | 1439.81 | 01-JUL-14:09 | 2627.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2242.00 | 09-JUL-12:00 | 109.57 | 22-JUL-18:10 |
August | 1439.81 | 05-AUG-14:09 | 2627.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2391.98 | 11-AUG-14:00 | 134.46 | 06-AUG-07:02 |
September | 1439.81 | 02-SEP-14:09 | 2627.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2567.73 | 03-SEP-13:00 | 120.09 | 19-SEP-07:10 |
October | 1439.81 | 07-OCT-14:09 | 2627.79 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2521.83 | 01-OCT-13:00 | 645.33 | 22-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2627.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1852.97 | 04-NOV-13:00 | 804.68 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2627.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1810.35 | 13-DEC-14:00 | 991.03 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.52 | 109.57 | |||||
Maximum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2567.73 | 1256.99 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2627.79 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1479.04 | 06-JAN-13:00 | 1256.99 | 25-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 2627.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.51 | 25-FEB-13:00 | 813.39 | 12-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2627.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1658.15 | 29-MAR-13:00 | 761.06 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2627.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1666.21 | 09-APR-14:00 | 548.23 | 16-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 2627.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1967.26 | 17-MAY-13:00 | 684.02 | 14-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 2627.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1842.37 | 29-JUN-11:10 | 122.53 | 25-JUN-17:00 |
July | 1439.81 | 01-JUL-14:09 | 2627.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2242.00 | 09-JUL-12:00 | 108.10 | 22-JUL-18:10 |
August | 1439.81 | 05-AUG-14:09 | 2627.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2391.98 | 11-AUG-14:00 | 130.18 | 06-AUG-07:02 |
September | 1439.81 | 02-SEP-14:09 | 2627.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2567.73 | 03-SEP-13:00 | 117.19 | 19-SEP-07:10 |
October | 1439.81 | 07-OCT-14:09 | 2627.79 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2521.83 | 01-OCT-13:00 | 638.66 | 22-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2627.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1852.97 | 04-NOV-13:00 | 796.04 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2627.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1810.34 | 13-DEC-14:00 | 983.11 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1344.51 | 108.10 | |||||
Maximum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2567.73 | 1256.99 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2627.79 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1537.57 | 06-JAN-13:00 | 1304.95 | 25-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 2627.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1386.41 | 25-FEB-13:00 | 849.55 | 12-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2627.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1752.57 | 29-MAR-13:00 | 816.82 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2627.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1767.86 | 09-APR-14:00 | 652.50 | 01-APR-18:10 |
May | 1439.81 | 06-MAY-14:09 | 2627.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2103.20 | 17-MAY-13:00 | 747.43 | 14-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 2627.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1978.56 | 29-JUN-11:10 | 289.33 | 08-JUN-23:00 |
July | 1439.81 | 01-JUL-14:09 | 2627.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2360.53 | 09-JUL-12:00 | 236.82 | 13-JUL-06:00 |
August | 1439.81 | 05-AUG-14:09 | 2627.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2518.39 | 11-AUG-14:00 | 222.02 | 13-AUG-03:00 |
September | 1439.81 | 02-SEP-14:09 | 2627.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2767.76 | 03-SEP-13:00 | 235.14 | 30-SEP-18:10 |
October | 1439.81 | 07-OCT-14:09 | 2627.79 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2655.10 | 01-OCT-13:00 | 711.89 | 22-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2627.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2004.63 | 04-NOV-13:00 | 848.04 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2627.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1898.54 | 13-DEC-14:00 | 1030.22 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1386.41 | 222.02 | |||||
Maximum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2767.76 | 1304.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36921.00 | 20-JAN-09:02 | 899.88 | 18358.60 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.24 |
February | 33449.74 | 07-FEB-09:02 | 719.91 | 14686.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.76 |
March | 33866.03 | 07-MAR-09:02 | 899.88 | 18358.60 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.85 |
April | 33082.80 | 01-APR-08:62 | 719.91 | 14686.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.46 |
May | 31624.57 | 31-MAY-08:61 | 1259.84 | 25702.04 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.60 |
June | 29755.93 | 06-JUN-08:61 | 1439.81 | 29373.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.61 |
July | 29102.20 | 18-JUL-08:61 | 1439.81 | 29373.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 144.77 | 0.00 |
August | 28529.57 | 24-AUG-08:61 | 1439.81 | 29373.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 |
September | 28918.44 | 27-SEP-08:61 | 1439.81 | 29373.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 25.15 | 0.00 |
October | 28474.20 | 17-OCT-08:61 | 1439.81 | 29373.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.48 |
November | 32144.35 | 26-NOV-08:62 | 899.88 | 1835.86 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.65 |
December | 34921.28 | 19-DEC-09:01 | 1259.84 | 25702.04 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.90 |
Annual Sum or Average | |||||||||||
Minimum of Months | 28474.20 | 719.91 | 1835.86 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36921.00 | 1439.81 | 29373.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 144.77 | 287.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19556.56 | 20-JAN-09:02 | 449.94 | 9807.43 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.23 |
February | 18472.50 | 07-FEB-09:02 | 359.95 | 7845.94 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.26 |
March | 18078.93 | 07-MAR-09:02 | 449.94 | 9807.43 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.79 |
April | 17798.58 | 30-APR-07:02 | 449.94 | 980.74 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.00 |
May | 17156.21 | 21-MAY-07:02 | 449.94 | 980.74 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.45 |
June | 16502.65 | 06-JUN-08:61 | 719.90 | 15691.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.76 |
July | 15700.73 | 18-JUL-08:61 | 719.90 | 15691.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 68.71 | 0.00 |
August | 15685.59 | 24-AUG-08:61 | 719.90 | 15691.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 |
September | 15825.76 | 24-SEP-07:02 | 539.93 | 1176.89 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.21 |
October | 16063.89 | 15-OCT-07:02 | 539.93 | 1176.89 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.98 |
November | 17765.56 | 26-NOV-08:62 | 449.94 | 980.74 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.92 |
December | 18592.40 | 19-DEC-09:01 | 629.92 | 13730.40 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.69 |
Annual Sum or Average | |||||||||||
Minimum of Months | 15685.59 | 359.95 | 980.74 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19556.56 | 719.90 | 15691.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 68.71 | 146.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18706.70 | 20-JAN-08:62 | 359.95 | 7095.94 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.68 |
February | 15631.58 | 09-FEB-08:62 | 359.95 | 7095.94 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.81 |
March | 17170.13 | 07-MAR-08:62 | 359.95 | 7095.94 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.73 |
April | 17299.59 | 02-APR-08:62 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.78 |
May | 16304.51 | 31-MAY-07:02 | 539.93 | 10643.91 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.62 |
June | 15089.78 | 11-JUN-08:61 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.25 |
July | 15200.93 | 18-JUL-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 | 0.00 |
August | 14621.00 | 23-AUG-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.34 |
September | 14798.73 | 27-SEP-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.51 |
October | 14986.10 | 17-OCT-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.45 |
November | 16488.12 | 15-NOV-08:61 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.12 |
December | 17958.39 | 25-DEC-09:02 | 539.93 | 10643.91 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.19 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14621.00 | 359.95 | 7095.94 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18706.70 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 | 157.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18562.35 | 20-JAN-08:62 | 359.95 | 7095.94 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.66 |
February | 15649.07 | 09-FEB-08:62 | 359.95 | 7095.94 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.02 |
March | 17200.42 | 07-MAR-08:62 | 359.95 | 7095.94 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.38 |
April | 17342.01 | 02-APR-08:62 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.94 |
May | 16355.04 | 31-MAY-07:02 | 539.93 | 10643.91 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.35 |
June | 15141.14 | 11-JUN-08:61 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.27 |
July | 15254.28 | 18-JUL-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 | 0.00 |
August | 14669.17 | 23-AUG-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.30 |
September | 14847.55 | 27-SEP-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.46 |
October | 15038.01 | 17-OCT-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.49 |
November | 16527.47 | 15-NOV-08:61 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.13 |
December | 18009.84 | 25-DEC-09:02 | 539.93 | 10643.91 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.78 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14669.17 | 359.95 | 7095.94 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18562.35 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 | 157.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17711.62 | 10-JAN-08:62 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.82 |
February | 15227.14 | 01-FEB-08:62 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.06 |
March | 16182.37 | 24-MAR-07:03 | 359.95 | 7095.94 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.66 |
April | 17214.57 | 02-APR-08:62 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.84 |
May | 16230.39 | 31-MAY-07:02 | 539.93 | 10643.91 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.44 |
June | 15058.49 | 11-JUN-08:61 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.27 |
July | 15168.40 | 18-JUL-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 | 0.00 |
August | 14577.12 | 23-AUG-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.30 |
September | 14754.87 | 27-SEP-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.49 |
October | 14948.16 | 17-OCT-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.79 |
November | 16407.76 | 15-NOV-08:61 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.73 |
December | 17880.06 | 25-DEC-09:02 | 539.93 | 10643.91 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.91 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14577.12 | 359.95 | 7095.94 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17880.06 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 | 167.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35079.93 | 20-JAN-09:02 | 1979.74 | 13830.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.42 |
February | 30950.45 | 07-FEB-09:02 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.93 |
March | 32007.50 | 07-MAR-09:02 | 1979.74 | 13830.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.56 |
April | 31658.70 | 02-APR-09:02 | 1979.74 | 13830.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.26 |
May | 30453.66 | 31-MAY-08:61 | 2771.64 | 19362.66 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.86 |
June | 28312.95 | 06-JUN-08:61 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.88 |
July | 27940.26 | 18-JUL-08:61 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 118.80 | 0.00 |
August | 27315.31 | 23-AUG-08:61 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 104.19 | 0.00 |
September | 27494.52 | 27-SEP-08:61 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 | 0.00 |
October | 27556.63 | 17-OCT-08:61 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.33 |
November | 30399.18 | 15-NOV-09:01 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.51 |
December | 33267.17 | 25-DEC-10:01 | 2771.64 | 19362.66 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.25 |
Annual Sum or Average | |||||||||||
Minimum of Months | 27315.31 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35079.93 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 118.80 | 187.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18242.77 | 20-JAN-09:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.91 |
February | 15332.90 | 07-FEB-09:02 | 791.89 | 5532.19 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.89 |
March | 16644.17 | 07-MAR-09:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.03 |
April | 16469.17 | 02-APR-09:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.16 |
May | 15830.24 | 31-MAY-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.11 |
June | 14721.52 | 06-JUN-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.85 |
July | 14554.43 | 18-JUL-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 66.72 | 0.00 |
August | 14224.20 | 23-AUG-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 59.27 | 0.00 |
September | 14308.37 | 27-SEP-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 | 0.00 |
October | 14337.91 | 17-OCT-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.69 |
November | 15808.05 | 15-NOV-09:01 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.43 |
December | 17323.26 | 25-DEC-10:01 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.04 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14224.20 | 791.89 | 5532.19 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18242.77 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 66.72 | 102.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18136.77 | 20-JAN-09:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.53 |
February | 15007.89 | 06-FEB-09:01 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.01 |
March | 16545.58 | 07-MAR-09:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.68 |
April | 16370.06 | 02-APR-09:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.60 |
May | 15733.87 | 31-MAY-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.62 |
June | 14623.93 | 06-JUN-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.53 |
July | 14478.33 | 18-JUL-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 66.62 | 0.00 |
August | 14148.61 | 23-AUG-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 59.20 | 0.00 |
September | 14234.07 | 27-SEP-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 | 0.00 |
October | 14248.55 | 17-OCT-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.54 |
November | 15709.09 | 15-NOV-09:01 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.73 |
December | 17219.17 | 25-DEC-10:01 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.51 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14148.61 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18136.77 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 66.62 | 101.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18052.54 | 20-JAN-09:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.46 |
February | 14920.93 | 06-FEB-09:01 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.17 |
March | 16460.71 | 07-MAR-09:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.61 |
April | 16284.93 | 02-APR-09:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.15 |
May | 15661.66 | 31-MAY-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.92 |
June | 14554.99 | 06-JUN-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.81 |
July | 14448.73 | 18-JUL-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 66.65 | 0.00 |
August | 14121.34 | 23-AUG-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 59.26 | 0.00 |
September | 14206.61 | 27-SEP-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 11.92 | 0.00 |
October | 14196.09 | 17-OCT-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.40 |
November | 15646.61 | 15-NOV-09:01 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.58 |
December | 17136.86 | 25-DEC-10:01 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.29 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14121.34 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18052.54 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 66.65 | 97.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19187.90 | 20-JAN-09:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.78 |
February | 15982.01 | 06-FEB-09:01 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.64 |
March | 17081.56 | 26-MAR-09:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 |
April | 17401.12 | 02-APR-09:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.28 |
May | 16620.79 | 31-MAY-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.47 |
June | 15292.17 | 11-JUN-09:01 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 19.38 | 0.00 |
July | 15308.06 | 18-JUL-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 92.18 | 0.00 |
August | 14681.41 | 23-AUG-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 73.41 | 0.00 |
September | 15124.57 | 27-SEP-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 18.15 | 0.00 |
October | 14914.69 | 17-OCT-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.16 |
November | 16759.45 | 15-NOV-09:01 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.00 |
December | 18367.19 | 25-DEC-10:01 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.42 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14681.41 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19187.90 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 92.18 | 119.42 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.130960E+12 | 113722.65 | 03-JAN-14:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.122359E+12 | 111716.46 | 19-FEB-14:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.135212E+12 | 111133.75 | 13-MAR-14:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.128640E+12 | 110036.00 | 24-APR-14:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.141537E+12 | 113193.71 | 18-MAY-14:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.139107E+12 | 111578.46 | 29-JUN-13:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.147695E+12 | 118773.04 | 11-JUL-12:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.151763E+12 | 121186.73 | 19-AUG-14:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.145594E+12 | 122463.91 | 03-SEP-12:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.149389E+12 | 120924.86 | 11-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.138023E+12 | 118027.14 | 22-NOV-13:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.136844E+12 | 112617.75 | 13-DEC-14:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.166712E+13 | 0.00 | ||||
Minimum of Months | 0.122359E+12 | 110036.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.151763E+12 | 122463.91 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.496324E+11 | 0.103357E+11 | 0.108804E+11 | 0.00 | 0.192096E+11 | 0.00 | 0.00 | 0.358747E+11 | 0.00 | 0.00 | 0.00 | 0.502749E+10 | 0.00 |
February | 0.449372E+11 | 0.902052E+10 | 0.985143E+10 | 0.00 | 0.174031E+11 | 0.00 | 0.00 | 0.365985E+11 | 0.00 | 0.00 | 0.00 | 0.454783E+10 | 0.00 |
March | 0.503750E+11 | 0.952800E+10 | 0.110523E+11 | 0.00 | 0.195287E+11 | 0.00 | 0.00 | 0.396844E+11 | 0.00 | 0.00 | 0.00 | 0.504384E+10 | 0.00 |
April | 0.481627E+11 | 0.874140E+10 | 0.105581E+11 | 0.00 | 0.186416E+11 | 0.00 | 0.00 | 0.377023E+11 | 0.00 | 0.00 | 0.00 | 0.483345E+10 | 0.00 |
May | 0.499854E+11 | 0.863991E+10 | 0.109629E+11 | 0.00 | 0.193859E+11 | 0.00 | 0.00 | 0.475947E+11 | 0.00 | 0.00 | 0.00 | 0.496857E+10 | 0.00 |
June | 0.486922E+11 | 0.817471E+10 | 0.106818E+11 | 0.00 | 0.188937E+11 | 0.00 | 0.00 | 0.478629E+11 | 0.00 | 0.00 | 0.00 | 0.480142E+10 | 0.00 |
July | 0.494924E+11 | 0.850035E+10 | 0.108460E+11 | 0.00 | 0.191895E+11 | 0.00 | 0.00 | 0.547454E+11 | 0.00 | 0.00 | 0.00 | 0.492133E+10 | 0.00 |
August | 0.503385E+11 | 0.886405E+10 | 0.110454E+11 | 0.00 | 0.195565E+11 | 0.00 | 0.00 | 0.570007E+11 | 0.00 | 0.00 | 0.00 | 0.495829E+10 | 0.00 |
September | 0.481992E+11 | 0.902475E+10 | 0.105649E+11 | 0.00 | 0.187037E+11 | 0.00 | 0.00 | 0.543062E+11 | 0.00 | 0.00 | 0.00 | 0.479526E+10 | 0.00 |
October | 0.496324E+11 | 0.978597E+10 | 0.108804E+11 | 0.00 | 0.192557E+11 | 0.00 | 0.00 | 0.548606E+11 | 0.00 | 0.00 | 0.00 | 0.497374E+10 | 0.00 |
November | 0.480897E+11 | 0.989170E+10 | 0.105443E+11 | 0.00 | 0.186474E+11 | 0.00 | 0.00 | 0.460083E+11 | 0.00 | 0.00 | 0.00 | 0.484138E+10 | 0.00 |
December | 0.495289E+11 | 0.104457E+11 | 0.108529E+11 | 0.00 | 0.191675E+11 | 0.00 | 0.00 | 0.418295E+11 | 0.00 | 0.00 | 0.00 | 0.501983E+10 | 0.00 |
Annual Sum or Average | 0.587066E+12 | 0.110953E+12 | 0.128721E+12 | 0.227583E+12 | 0.00 | 0.554068E+12 | 0.587324E+11 | ||||||
Minimum of Months | 0.449372E+11 | 0.817471E+10 | 0.985143E+10 | 0.00 | 0.174031E+11 | 0.00 | 0.00 | 0.358747E+11 | 0.00 | 0.00 | 0.00 | 0.454783E+10 | 0.00 |
Maximum of Months | 0.503750E+11 | 0.104457E+11 | 0.110523E+11 | 0.00 | 0.195565E+11 | 0.00 | 0.00 | 0.570007E+11 | 0.00 | 0.00 | 0.00 | 0.504384E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 36581.55 | 01-JAN-11:09 | 7048.38 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 13193.38 | 06-JAN-20:49 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 36581.55 | 01-FEB-10:09 | 7048.38 | 01-FEB-00:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 13193.38 | 01-FEB-20:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 36581.55 | 01-MAR-10:09 | 7048.38 | 01-MAR-00:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 13193.38 | 01-MAR-18:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 36581.55 | 01-APR-09:09 | 7048.38 | 01-APR-00:10 | 8089.53 | 01-APR-09:09 | 0.00 | 13193.38 | 02-APR-09:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 36581.55 | 01-MAY-09:09 | 7048.38 | 01-MAY-00:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 13193.38 | 21-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 36581.55 | 01-JUN-09:09 | 7048.38 | 01-JUN-00:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 13193.38 | 01-JUN-07:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 36581.55 | 01-JUL-09:09 | 7048.38 | 01-JUL-00:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 13193.38 | 18-JUL-17:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 36581.55 | 01-AUG-09:09 | 7048.38 | 01-AUG-00:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 13193.38 | 16-AUG-19:40 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 36581.55 | 01-SEP-09:09 | 7048.38 | 01-SEP-00:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 13193.38 | 05-SEP-19:19 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 36581.55 | 01-OCT-10:09 | 7048.38 | 01-OCT-00:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 13193.38 | 27-OCT-09:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 36581.55 | 01-NOV-09:09 | 7048.38 | 01-NOV-00:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 13193.38 | 09-NOV-20:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 36581.55 | 01-DEC-10:09 | 7048.38 | 01-DEC-00:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 13193.38 | 04-DEC-19:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 36581.55 | 7048.38 | 8089.53 | 0.00 | 13193.38 | 0.00 | 0.00 | |||||
Maximum of Months | 36581.55 | 7048.38 | 8089.53 | 0.00 | 13193.38 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 47215.06 | 01-JAN-13:50 | 0.00 | 0.00 | 0.00 | 11778.79 | 05-JAN-12:50 | 0.00 |
February | 48898.53 | 19-FEB-13:00 | 0.00 | 0.00 | 0.00 | 9674.03 | 02-FEB-14:39 | 0.00 |
March | 47834.56 | 13-MAR-14:09 | 0.00 | 0.00 | 0.00 | 9673.99 | 08-MAR-13:50 | 0.00 |
April | 45102.02 | 24-APR-13:00 | 0.00 | 0.00 | 0.00 | 9669.06 | 06-APR-13:30 | 0.00 |
May | 50158.28 | 13-MAY-13:00 | 0.00 | 0.00 | 0.00 | 7672.30 | 18-MAY-14:30 | 0.00 |
June | 48843.56 | 29-JUN-12:00 | 0.00 | 0.00 | 0.00 | 9216.36 | 01-JUN-13:09 | 0.00 |
July | 54768.70 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 7552.47 | 19-JUL-12:30 | 0.00 |
August | 58325.40 | 19-AUG-14:00 | 0.00 | 0.00 | 0.00 | 7553.58 | 29-AUG-12:30 | 0.00 |
September | 60033.95 | 03-SEP-12:00 | 0.00 | 0.00 | 0.00 | 7554.42 | 12-SEP-12:00 | 0.00 |
October | 58146.66 | 15-OCT-12:00 | 0.00 | 0.00 | 0.00 | 7557.35 | 21-OCT-12:39 | 0.00 |
November | 52921.42 | 06-NOV-13:00 | 0.00 | 0.00 | 0.00 | 9672.20 | 08-NOV-13:20 | 0.00 |
December | 50277.15 | 13-DEC-13:00 | 0.00 | 0.00 | 0.00 | 9646.25 | 14-DEC-18:49 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 45102.02 | 0.00 | 0.00 | 0.00 | 7552.47 | 0.00 | ||
Maximum of Months | 60033.95 | 0.00 | 0.00 | 0.00 | 11778.79 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 113722.65 | 03-JAN-14:09 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13193.38 | 0.00 | 0.00 | 46185.00 | 0.00 |
February | 111716.46 | 19-FEB-14:50 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13193.38 | 0.00 | 0.00 | 46327.25 | 0.00 |
March | 111133.75 | 13-MAR-14:09 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13193.38 | 0.00 | 0.00 | 47834.56 | 0.00 |
April | 110036.00 | 24-APR-14:20 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13193.38 | 0.00 | 0.00 | 44630.72 | 0.00 |
May | 113193.71 | 18-MAY-14:30 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13193.38 | 0.00 | 0.00 | 47656.95 | 0.00 |
June | 111578.46 | 29-JUN-13:50 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13193.38 | 0.00 | 0.00 | 48273.73 | 0.00 |
July | 118773.04 | 11-JUL-12:39 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13193.38 | 0.00 | 0.00 | 53548.58 | 0.00 |
August | 121186.73 | 19-AUG-14:50 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13193.38 | 0.00 | 0.00 | 58226.58 | 0.00 |
September | 122463.91 | 03-SEP-12:50 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13193.38 | 0.00 | 0.00 | 59179.59 | 0.00 |
October | 120924.86 | 11-OCT-12:00 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13193.38 | 0.00 | 0.00 | 57616.66 | 0.00 |
November | 118027.14 | 22-NOV-13:30 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13193.38 | 0.00 | 0.00 | 52602.99 | 0.00 |
December | 112617.75 | 13-DEC-14:50 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13193.38 | 0.00 | 0.00 | 47800.32 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 110036.00 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13193.38 | 0.00 | 0.00 | 44630.72 | 0.00 | |
Maximum of Months | 122463.91 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13193.38 | 0.00 | 0.00 | 59179.59 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.55 | 0.50 | 24.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.51 | 0.50 | 24.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.47 | 1.17 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.51 | 3.00 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.50 | 3.83 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.54 | 3.00 | 24.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.50 | 1.83 | 24.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.50 | 1.83 | 24.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.49 | 0.83 | 24.49 |
Annual Sum or Average | 0.00 | 0.00 | 16.50 | 24.51 | 16.50 | 24.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.55 | 3.83 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.52 | 0.33 | 24.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.48 | 1.17 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.47 | 1.17 | 24.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.48 | 2.33 | 24.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.45 | 0.67 | 24.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.50 | 24.47 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
Annual Sum or Average | 0.00 | 0.00 | 6.50 | 24.48 | 6.50 | 24.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.52 | 2.33 | 24.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.56 | 0.33 | 24.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.50 | 24.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.33 | 24.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.50 | 2.50 | 24.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.49 | 2.67 | 24.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.52 | 3.50 | 24.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.50 | 2.00 | 24.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.48 | 1.67 | 24.48 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.50 | 0.67 | 24.50 |
Annual Sum or Average | 0.00 | 0.00 | 14.17 | 24.50 | 14.17 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.56 | 3.50 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.56 | 0.33 | 24.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.50 | 24.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.33 | 24.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.50 | 2.67 | 24.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.48 | 2.50 | 24.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.52 | 3.50 | 24.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.49 | 2.00 | 24.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.49 | 1.17 | 24.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.50 | 0.67 | 24.50 |
Annual Sum or Average | 0.00 | 0.00 | 13.67 | 24.50 | 13.67 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.56 | 3.50 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.51 | 0.33 | 24.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.50 | 24.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.33 | 24.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.50 | 2.17 | 24.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.49 | 2.33 | 24.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.52 | 3.50 | 24.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.50 | 1.83 | 24.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.49 | 1.33 | 24.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.50 | 0.67 | 24.50 |
Annual Sum or Average | 0.00 | 0.00 | 13.00 | 24.50 | 13.00 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.52 | 3.50 | 24.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.51 | 0.67 | 24.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.54 | 0.83 | 24.54 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.49 | 1.83 | 24.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.48 | 3.17 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.53 | 5.00 | 24.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.53 | 4.67 | 24.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.58 | 4.00 | 24.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.55 | 3.17 | 24.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.52 | 3.17 | 24.52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.55 | 1.00 | 24.55 |
Annual Sum or Average | 0.00 | 0.00 | 27.67 | 24.53 | 27.67 | 24.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.58 | 5.00 | 24.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.50 | 24.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.52 | 0.67 | 24.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.49 | 1.00 | 24.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.48 | 1.67 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.51 | 4.17 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.51 | 4.00 | 24.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.55 | 4.00 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.53 | 3.00 | 24.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.50 | 2.50 | 24.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.53 | 1.00 | 24.53 |
Annual Sum or Average | 0.00 | 0.00 | 22.50 | 24.52 | 22.50 | 24.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.55 | 4.17 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.50 | 24.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.51 | 0.67 | 24.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.49 | 0.83 | 24.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.48 | 1.67 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.51 | 4.33 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.52 | 3.83 | 24.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.55 | 4.00 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.54 | 3.00 | 24.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.51 | 2.33 | 24.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.53 | 1.00 | 24.53 |
Annual Sum or Average | 0.00 | 0.00 | 22.17 | 24.52 | 22.17 | 24.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.55 | 4.33 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.50 | 24.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.51 | 0.50 | 24.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.50 | 0.67 | 24.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.48 | 1.33 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.52 | 4.00 | 24.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.52 | 3.50 | 24.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.56 | 3.83 | 24.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.53 | 3.00 | 24.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.51 | 2.33 | 24.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.52 | 1.00 | 24.52 |
Annual Sum or Average | 0.00 | 0.00 | 20.67 | 24.52 | 20.67 | 24.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.56 | 4.00 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.33 | 24.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.50 | 24.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.48 | 0.67 | 24.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.46 | 1.17 | 24.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.51 | 3.50 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.50 | 3.33 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.54 | 3.50 | 24.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.51 | 2.83 | 24.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.49 | 2.17 | 24.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.51 | 0.83 | 24.51 |
Annual Sum or Average | 0.00 | 0.00 | 18.83 | 24.51 | 18.83 | 24.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.54 | 3.50 | 24.54 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.67 | 25.28 | 488.00 | 23.95 | 5.67 | 25.28 |
February | 38.83 | 24.20 | 444.33 | 23.94 | 38.83 | 24.20 |
March | 16.00 | 24.46 | 492.50 | 23.94 | 16.00 | 24.46 |
April | 3.50 | 25.17 | 478.17 | 23.95 | 3.50 | 25.17 |
May | 16.17 | 25.32 | 496.00 | 23.98 | 16.17 | 25.32 |
June | 23.67 | 25.52 | 480.00 | 23.98 | 23.67 | 25.52 |
July | 35.17 | 25.18 | 496.00 | 23.98 | 35.17 | 25.18 |
August | 34.50 | 25.37 | 496.00 | 24.00 | 34.50 | 25.37 |
September | 39.50 | 24.84 | 480.00 | 23.98 | 39.50 | 24.84 |
October | 24.83 | 25.18 | 496.00 | 23.97 | 24.83 | 25.18 |
November | 21.00 | 25.22 | 480.00 | 23.98 | 21.00 | 25.22 |
December | 13.83 | 25.07 | 496.00 | 23.96 | 13.83 | 25.07 |
Annual Sum or Average | 272.67 | 25.01 | 5823.00 | 23.97 | 272.67 | 25.01 |
Minimum of Months | 3.50 | 24.20 | 444.33 | 23.94 | 3.50 | 24.20 |
Maximum of Months | 39.50 | 25.52 | 496.00 | 24.00 | 39.50 | 25.52 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 25.17 | 477.50 | 23.96 | 1.00 | 25.17 |
February | 26.67 | 24.02 | 436.67 | 23.95 | 26.67 | 24.02 |
March | 7.67 | 23.97 | 481.50 | 23.95 | 7.50 | 23.97 |
April | 0.00 | 0.00 | 471.17 | 23.95 | 0.00 | 0.00 |
May | 3.17 | 25.32 | 495.67 | 23.98 | 3.17 | 25.32 |
June | 4.67 | 25.37 | 480.00 | 23.99 | 4.67 | 25.37 |
July | 19.00 | 25.20 | 496.00 | 23.98 | 19.00 | 25.20 |
August | 14.17 | 25.63 | 496.00 | 24.00 | 14.17 | 25.63 |
September | 24.50 | 24.87 | 480.00 | 23.98 | 24.50 | 24.87 |
October | 4.67 | 24.93 | 496.00 | 23.97 | 4.67 | 24.93 |
November | 6.83 | 25.35 | 478.17 | 23.98 | 6.83 | 25.35 |
December | 4.00 | 24.89 | 488.83 | 23.96 | 4.00 | 24.89 |
Annual Sum or Average | 116.33 | 24.83 | 5777.50 | 23.97 | 116.17 | 24.83 |
Minimum of Months | 0.00 | 0.00 | 436.67 | 23.95 | 0.00 | 0.00 |
Maximum of Months | 26.67 | 25.63 | 496.00 | 24.00 | 26.67 | 25.63 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.00 | 24.51 | 367.67 | 24.04 | 5.00 | 24.51 |
February | 43.33 | 24.28 | 333.67 | 24.05 | 43.33 | 24.28 |
March | 14.17 | 24.21 | 378.33 | 24.05 | 14.17 | 24.21 |
April | 3.00 | 25.05 | 360.00 | 24.06 | 3.00 | 25.05 |
May | 13.17 | 24.93 | 375.00 | 24.09 | 13.17 | 24.93 |
June | 13.00 | 24.86 | 366.00 | 24.10 | 13.00 | 24.86 |
July | 27.67 | 24.96 | 369.00 | 24.13 | 27.67 | 24.96 |
August | 23.67 | 24.99 | 379.00 | 24.12 | 23.67 | 24.99 |
September | 35.50 | 24.91 | 360.00 | 24.13 | 35.50 | 24.91 |
October | 23.50 | 24.94 | 371.00 | 24.11 | 23.50 | 24.94 |
November | 13.50 | 24.53 | 360.00 | 24.08 | 13.50 | 24.53 |
December | 13.33 | 24.53 | 369.00 | 24.06 | 13.33 | 24.53 |
Annual Sum or Average | 228.83 | 24.71 | 4388.67 | 24.08 | 228.83 | 24.71 |
Minimum of Months | 3.00 | 24.21 | 333.67 | 24.04 | 3.00 | 24.21 |
Maximum of Months | 43.33 | 25.05 | 379.00 | 24.13 | 43.33 | 25.05 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.00 | 24.51 | 367.50 | 24.04 | 5.00 | 24.51 |
February | 43.67 | 24.28 | 333.50 | 24.05 | 43.67 | 24.28 |
March | 14.00 | 24.21 | 378.33 | 24.05 | 14.00 | 24.21 |
April | 3.00 | 25.06 | 360.00 | 24.06 | 3.00 | 25.06 |
May | 13.17 | 24.93 | 375.00 | 24.09 | 13.17 | 24.93 |
June | 13.00 | 24.91 | 366.00 | 24.10 | 13.00 | 24.91 |
July | 27.50 | 24.96 | 369.00 | 24.13 | 27.50 | 24.96 |
August | 23.50 | 25.00 | 379.00 | 24.12 | 23.50 | 25.00 |
September | 34.83 | 24.93 | 360.00 | 24.13 | 34.83 | 24.93 |
October | 23.33 | 24.95 | 371.00 | 24.11 | 23.33 | 24.95 |
November | 13.33 | 24.54 | 360.00 | 24.08 | 13.33 | 24.54 |
December | 12.67 | 24.56 | 369.00 | 24.06 | 12.67 | 24.56 |
Annual Sum or Average | 227.00 | 24.72 | 4388.33 | 24.08 | 227.00 | 24.72 |
Minimum of Months | 3.00 | 24.21 | 333.50 | 24.04 | 3.00 | 24.21 |
Maximum of Months | 43.67 | 25.06 | 379.00 | 24.13 | 43.67 | 25.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 24.48 | 366.67 | 24.03 | 5.17 | 24.48 |
February | 45.33 | 24.28 | 333.17 | 24.04 | 45.33 | 24.28 |
March | 14.83 | 24.21 | 377.33 | 24.05 | 14.83 | 24.21 |
April | 3.33 | 24.93 | 359.83 | 24.05 | 3.33 | 24.93 |
May | 13.67 | 24.87 | 375.00 | 24.08 | 13.67 | 24.87 |
June | 13.17 | 24.80 | 366.00 | 24.09 | 13.17 | 24.80 |
July | 28.00 | 24.93 | 369.00 | 24.12 | 28.00 | 24.93 |
August | 23.83 | 24.94 | 379.00 | 24.12 | 23.83 | 24.94 |
September | 37.17 | 24.85 | 360.00 | 24.12 | 37.17 | 24.85 |
October | 23.67 | 24.90 | 371.00 | 24.11 | 23.67 | 24.90 |
November | 13.50 | 24.48 | 360.00 | 24.07 | 13.50 | 24.48 |
December | 14.17 | 24.48 | 369.00 | 24.05 | 14.17 | 24.48 |
Annual Sum or Average | 235.83 | 24.67 | 4386.00 | 24.08 | 235.83 | 24.67 |
Minimum of Months | 3.33 | 24.21 | 333.17 | 24.03 | 3.33 | 24.21 |
Maximum of Months | 45.33 | 24.94 | 379.00 | 24.12 | 45.33 | 24.94 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.83 | 24.60 | 333.17 | 23.94 | 4.83 | 24.60 |
February | 47.67 | 24.13 | 303.67 | 23.95 | 47.67 | 24.13 |
March | 16.00 | 24.16 | 345.67 | 23.94 | 16.00 | 24.16 |
April | 3.50 | 24.92 | 328.17 | 23.96 | 3.50 | 24.92 |
May | 11.50 | 24.79 | 344.00 | 23.97 | 11.50 | 24.79 |
June | 12.83 | 24.74 | 336.00 | 23.96 | 12.83 | 24.74 |
July | 27.17 | 24.74 | 338.00 | 24.00 | 27.17 | 24.74 |
August | 21.17 | 24.84 | 348.00 | 23.97 | 21.17 | 24.84 |
September | 38.17 | 24.59 | 330.00 | 23.99 | 38.17 | 24.59 |
October | 21.33 | 24.85 | 340.00 | 23.98 | 21.33 | 24.85 |
November | 13.83 | 24.42 | 330.00 | 23.96 | 13.83 | 24.42 |
December | 15.00 | 24.51 | 336.50 | 23.96 | 15.00 | 24.51 |
Annual Sum or Average | 233.00 | 24.54 | 4013.17 | 23.97 | 233.00 | 24.54 |
Minimum of Months | 3.50 | 24.13 | 303.67 | 23.94 | 3.50 | 24.13 |
Maximum of Months | 47.67 | 24.92 | 348.00 | 24.00 | 47.67 | 24.92 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.83 | 24.59 | 328.33 | 23.94 | 4.83 | 24.59 |
February | 47.50 | 24.12 | 301.17 | 23.95 | 47.50 | 24.12 |
March | 16.33 | 24.17 | 342.00 | 23.94 | 16.33 | 24.17 |
April | 3.17 | 24.82 | 327.50 | 23.96 | 3.17 | 24.82 |
May | 11.00 | 24.64 | 344.00 | 23.97 | 11.00 | 24.64 |
June | 12.00 | 24.58 | 336.00 | 23.96 | 12.00 | 24.58 |
July | 28.83 | 24.61 | 338.00 | 24.00 | 28.83 | 24.61 |
August | 20.33 | 24.80 | 348.00 | 23.97 | 20.33 | 24.80 |
September | 40.00 | 24.54 | 330.00 | 23.99 | 40.00 | 24.54 |
October | 21.00 | 24.82 | 340.00 | 23.98 | 21.00 | 24.82 |
November | 14.33 | 24.42 | 330.00 | 23.96 | 14.33 | 24.42 |
December | 15.50 | 24.51 | 335.00 | 23.96 | 15.50 | 24.51 |
Annual Sum or Average | 234.83 | 24.49 | 4000.00 | 23.96 | 234.83 | 24.49 |
Minimum of Months | 3.17 | 24.12 | 301.17 | 23.94 | 3.17 | 24.12 |
Maximum of Months | 47.50 | 24.82 | 348.00 | 24.00 | 47.50 | 24.82 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.83 | 24.58 | 327.17 | 23.94 | 4.83 | 24.58 |
February | 48.67 | 24.11 | 300.33 | 23.95 | 48.67 | 24.11 |
March | 16.67 | 24.18 | 341.17 | 23.94 | 16.67 | 24.18 |
April | 3.33 | 24.77 | 327.33 | 23.96 | 3.33 | 24.77 |
May | 11.17 | 24.62 | 344.00 | 23.96 | 11.17 | 24.62 |
June | 12.17 | 24.57 | 336.00 | 23.96 | 12.17 | 24.57 |
July | 29.00 | 24.59 | 338.00 | 24.00 | 29.00 | 24.59 |
August | 20.67 | 24.76 | 348.00 | 23.97 | 20.67 | 24.76 |
September | 41.00 | 24.52 | 330.00 | 23.99 | 41.00 | 24.52 |
October | 21.33 | 24.78 | 340.00 | 23.98 | 21.33 | 24.78 |
November | 15.00 | 24.40 | 330.00 | 23.96 | 15.00 | 24.40 |
December | 15.83 | 24.49 | 334.67 | 23.95 | 15.83 | 24.49 |
Annual Sum or Average | 239.67 | 24.47 | 3996.67 | 23.96 | 239.67 | 24.47 |
Minimum of Months | 3.33 | 24.11 | 300.33 | 23.94 | 3.33 | 24.11 |
Maximum of Months | 48.67 | 24.78 | 348.00 | 24.00 | 48.67 | 24.78 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 24.57 | 326.33 | 23.94 | 5.33 | 24.57 |
February | 51.50 | 24.10 | 299.83 | 23.95 | 51.50 | 24.10 |
March | 17.67 | 24.18 | 339.83 | 23.94 | 17.67 | 24.18 |
April | 3.50 | 24.70 | 327.33 | 23.96 | 3.50 | 24.70 |
May | 11.33 | 24.60 | 344.00 | 23.96 | 11.33 | 24.60 |
June | 12.17 | 24.56 | 336.00 | 23.96 | 12.17 | 24.56 |
July | 29.33 | 24.58 | 338.00 | 23.99 | 29.33 | 24.58 |
August | 21.17 | 24.73 | 348.00 | 23.97 | 21.17 | 24.73 |
September | 41.50 | 24.51 | 330.00 | 23.99 | 41.50 | 24.51 |
October | 21.50 | 24.76 | 340.00 | 23.98 | 21.50 | 24.76 |
November | 15.33 | 24.38 | 330.00 | 23.96 | 15.33 | 24.38 |
December | 16.17 | 24.47 | 334.67 | 23.95 | 16.17 | 24.47 |
Annual Sum or Average | 246.50 | 24.45 | 3994.00 | 23.96 | 246.50 | 24.45 |
Minimum of Months | 3.50 | 24.10 | 299.83 | 23.94 | 3.50 | 24.10 |
Maximum of Months | 51.50 | 24.76 | 348.00 | 23.99 | 51.50 | 24.76 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 24.43 | 328.17 | 23.94 | 6.17 | 24.43 |
February | 58.17 | 24.08 | 300.17 | 23.95 | 58.17 | 24.08 |
March | 21.00 | 24.13 | 340.50 | 23.94 | 21.00 | 24.13 |
April | 5.67 | 24.54 | 327.33 | 23.96 | 5.67 | 24.54 |
May | 15.00 | 24.63 | 344.00 | 23.97 | 15.00 | 24.63 |
June | 16.33 | 24.59 | 336.00 | 23.96 | 16.33 | 24.59 |
July | 31.67 | 24.69 | 338.00 | 24.00 | 31.67 | 24.69 |
August | 23.83 | 24.78 | 348.00 | 23.97 | 23.83 | 24.78 |
September | 42.17 | 24.56 | 330.00 | 23.99 | 42.17 | 24.56 |
October | 24.50 | 24.81 | 340.00 | 23.99 | 24.50 | 24.81 |
November | 16.83 | 24.36 | 330.00 | 23.96 | 16.83 | 24.36 |
December | 18.50 | 24.43 | 334.67 | 23.96 | 18.50 | 24.43 |
Annual Sum or Average | 279.83 | 24.46 | 3996.83 | 23.97 | 279.83 | 24.46 |
Minimum of Months | 5.67 | 24.08 | 300.17 | 23.94 | 5.67 | 24.08 |
Maximum of Months | 58.17 | 24.81 | 348.00 | 24.00 | 58.17 | 24.81 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.96386 | 50.30932 | 0.56910 | 11.90928 |
February | 448.00000 | 23.95946 | 55.12704 | 0.60412 | 12.79411 |
March | 496.00000 | 23.95273 | 51.95320 | 0.57874 | 12.12943 |
April | 480.00000 | 23.96156 | 50.99236 | 0.57303 | 11.97112 |
May | 496.00000 | 23.99536 | 53.58985 | -0.2233 | 6.25960 |
June | 480.00000 | 24.00631 | 54.20286 | -0.2045 | 6.14991 |
July | 496.00000 | 24.00536 | 55.62581 | -0.1796 | 5.98633 |
August | 496.00000 | 24.01955 | 55.46947 | -0.1748 | 5.95798 |
September | 480.00000 | 24.00008 | 56.92961 | -0.1620 | 5.82017 |
October | 496.00000 | 23.99186 | 55.75738 | 0.64670 | 13.91502 |
November | 480.00000 | 24.00132 | 54.60486 | 0.63105 | 13.54490 |
December | 496.00000 | 23.97501 | 53.01078 | 0.60380 | 12.80594 |
Annual Sum or Average | 5840.00000 | 23.98619 | 53.95243 | 0.26981 | 9.91970 |
Minimum of Months | 448.00000 | 23.95273 | 50.30932 | -0.2233 | 5.82017 |
Maximum of Months | 496.00000 | 24.01955 | 56.92961 | 0.64670 | 13.91502 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.97212 | 48.58652 | 0.54844 | 11.43181 |
February | 448.00000 | 23.96721 | 52.82159 | 0.57724 | 12.14095 |
March | 496.00000 | 23.96213 | 50.11194 | 0.55499 | 11.57111 |
April | 480.00000 | 23.96975 | 49.25873 | 0.54965 | 11.43308 |
May | 496.00000 | 24.00123 | 51.70282 | -0.2564 | 6.61721 |
June | 480.00000 | 24.00991 | 52.51274 | -0.2397 | 6.49860 |
July | 496.00000 | 24.00696 | 53.86362 | -0.2186 | 6.32785 |
August | 496.00000 | 24.02143 | 53.72218 | -0.2153 | 6.30262 |
September | 480.00000 | 24.00124 | 55.10998 | -0.2053 | 6.16986 |
October | 496.00000 | 23.99577 | 53.73922 | 0.61574 | 13.10178 |
November | 480.00000 | 24.00526 | 52.67857 | 0.60249 | 12.80991 |
December | 496.00000 | 23.98072 | 51.08334 | 0.57858 | 12.18642 |
Annual Sum or Average | 5840.00000 | 23.99128 | 52.09015 | 0.23893 | 9.70135 |
Minimum of Months | 448.00000 | 23.96213 | 48.58652 | -0.2564 | 6.16986 |
Maximum of Months | 496.00000 | 24.02143 | 55.10998 | 0.61574 | 13.10178 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.02736 | 50.54565 | 0.57823 | 12.15649 |
February | 336.00000 | 24.03654 | 55.65336 | 0.61496 | 13.14013 |
March | 379.00000 | 24.03504 | 52.31107 | 0.58716 | 12.40274 |
April | 360.00000 | 24.04639 | 51.28925 | 0.58142 | 12.24421 |
May | 375.00000 | 24.07747 | 53.85826 | -0.2131 | 6.32634 |
June | 366.00000 | 24.08825 | 54.50918 | -0.1971 | 6.20966 |
July | 369.00000 | 24.11431 | 55.75462 | -0.1662 | 6.09406 |
August | 379.00000 | 24.10682 | 55.55335 | -0.1699 | 6.10029 |
September | 360.00000 | 24.11314 | 57.21243 | -0.1508 | 6.02913 |
October | 371.00000 | 24.09782 | 56.03328 | 0.66077 | 14.43047 |
November | 360.00000 | 24.07111 | 54.93189 | 0.63925 | 13.78215 |
December | 369.00000 | 24.05115 | 53.38668 | 0.61499 | 13.12833 |
Annual Sum or Average | 4395.00000 | 24.07234 | 54.23831 | 0.27830 | 10.14099 |
Minimum of Months | 336.00000 | 24.02736 | 50.54565 | -0.2131 | 6.02913 |
Maximum of Months | 379.00000 | 24.11431 | 57.21243 | 0.66077 | 14.43047 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.02688 | 50.56339 | 0.57770 | 12.14432 |
February | 336.00000 | 24.03621 | 55.67178 | 0.61457 | 13.13073 |
March | 379.00000 | 24.03474 | 52.32211 | 0.58687 | 12.39576 |
April | 360.00000 | 24.04608 | 51.30274 | 0.58104 | 12.23514 |
May | 375.00000 | 24.07773 | 53.84512 | -0.2126 | 6.32524 |
June | 366.00000 | 24.08829 | 54.49214 | -0.1965 | 6.20784 |
July | 369.00000 | 24.11467 | 55.70964 | -0.1647 | 6.09008 |
August | 379.00000 | 24.10692 | 55.51738 | -0.1687 | 6.09624 |
September | 360.00000 | 24.11353 | 57.15174 | -0.1490 | 6.02524 |
October | 371.00000 | 24.09835 | 55.98479 | 0.66180 | 14.46277 |
November | 360.00000 | 24.07106 | 54.92106 | 0.63948 | 13.79017 |
December | 369.00000 | 24.05103 | 53.39018 | 0.61490 | 13.12705 |
Annual Sum or Average | 4395.00000 | 24.07235 | 54.22419 | 0.27874 | 10.13993 |
Minimum of Months | 336.00000 | 24.02688 | 50.56339 | -0.2126 | 6.02524 |
Maximum of Months | 379.00000 | 24.11467 | 57.15174 | 0.66180 | 14.46277 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.02293 | 50.70976 | 0.57502 | 12.07481 |
February | 336.00000 | 24.03214 | 55.86912 | 0.61203 | 13.05963 |
March | 379.00000 | 24.03079 | 52.49700 | 0.58397 | 12.31873 |
April | 360.00000 | 24.04171 | 51.46604 | 0.57803 | 12.15508 |
May | 375.00000 | 24.07384 | 53.99552 | -0.2162 | 6.34234 |
June | 366.00000 | 24.08528 | 54.64153 | -0.1998 | 6.21985 |
July | 369.00000 | 24.11186 | 55.84697 | -0.1675 | 6.09264 |
August | 379.00000 | 24.10397 | 55.66219 | -0.1718 | 6.10132 |
September | 360.00000 | 24.11090 | 57.30418 | -0.1517 | 6.02706 |
October | 371.00000 | 24.09513 | 56.13128 | 0.65990 | 14.40215 |
November | 360.00000 | 24.06792 | 55.07055 | 0.63756 | 13.73153 |
December | 369.00000 | 24.04746 | 53.54609 | 0.61265 | 13.06232 |
Annual Sum or Average | 4395.00000 | 24.06889 | 54.37957 | 0.27601 | 10.10333 |
Minimum of Months | 336.00000 | 24.02293 | 50.70976 | -0.2162 | 6.02706 |
Maximum of Months | 379.00000 | 24.11186 | 57.30418 | 0.65990 | 14.40215 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.96045 | 51.58296 | 0.56650 | 11.85778 |
February | 308.00000 | 23.96922 | 56.82321 | 0.60451 | 12.84059 |
March | 348.00000 | 23.95483 | 53.37041 | 0.57314 | 12.01611 |
April | 330.00000 | 23.97215 | 52.29491 | 0.56732 | 11.86233 |
May | 344.00000 | 23.99000 | 54.75673 | -0.2341 | 6.42112 |
June | 336.00000 | 23.98795 | 55.50048 | -0.2199 | 6.27381 |
July | 338.00000 | 24.01684 | 56.69049 | -0.1847 | 6.08311 |
August | 348.00000 | 23.99531 | 56.42007 | -0.1935 | 6.10629 |
September | 330.00000 | 24.01118 | 58.15008 | -0.1690 | 5.99663 |
October | 340.00000 | 24.00333 | 56.82725 | 0.64894 | 14.04010 |
November | 330.00000 | 23.98715 | 55.92186 | 0.62739 | 13.42270 |
December | 338.00000 | 23.97628 | 54.42487 | 0.60301 | 12.78676 |
Annual Sum or Average | 4030.00000 | 23.98543 | 55.21356 | 0.26229 | 9.94655 |
Minimum of Months | 308.00000 | 23.95483 | 51.58296 | -0.2341 | 5.99663 |
Maximum of Months | 348.00000 | 24.01684 | 58.15008 | 0.64894 | 14.04010 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.96009 | 51.64606 | 0.54969 | 11.46068 |
February | 308.00000 | 23.96839 | 56.93444 | 0.58748 | 12.41156 |
March | 348.00000 | 23.95425 | 53.45289 | 0.55585 | 11.60196 |
April | 330.00000 | 23.97135 | 52.35540 | 0.54977 | 11.44840 |
May | 344.00000 | 23.98859 | 54.84256 | -0.2604 | 6.69150 |
June | 336.00000 | 23.98695 | 55.58725 | -0.2470 | 6.53784 |
July | 338.00000 | 24.01624 | 56.78029 | -0.2128 | 6.32113 |
August | 348.00000 | 23.99409 | 56.50038 | -0.2219 | 6.35312 |
September | 330.00000 | 24.01022 | 58.26474 | -0.1976 | 6.21779 |
October | 340.00000 | 24.00249 | 56.92020 | 0.62929 | 13.51114 |
November | 330.00000 | 23.98623 | 56.01457 | 0.60876 | 12.93554 |
December | 338.00000 | 23.97561 | 54.51490 | 0.58536 | 12.34263 |
Annual Sum or Average | 4030.00000 | 23.98458 | 55.30086 | 0.24031 | 9.79332 |
Minimum of Months | 308.00000 | 23.95425 | 51.64606 | -0.2604 | 6.21779 |
Maximum of Months | 348.00000 | 24.01624 | 58.26474 | 0.62929 | 13.51114 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.95904 | 51.71862 | 0.54743 | 11.40675 |
February | 308.00000 | 23.96739 | 57.03083 | 0.58531 | 12.35613 |
March | 348.00000 | 23.95333 | 53.53131 | 0.55360 | 11.54778 |
April | 330.00000 | 23.97043 | 52.42616 | 0.54756 | 11.39521 |
May | 344.00000 | 23.98776 | 54.91291 | -0.2636 | 6.72173 |
June | 336.00000 | 23.98650 | 55.65854 | -0.2500 | 6.56569 |
July | 338.00000 | 24.01586 | 56.84741 | -0.2157 | 6.34343 |
August | 348.00000 | 23.99385 | 56.56432 | -0.2247 | 6.37664 |
September | 330.00000 | 24.00976 | 58.33857 | -0.2005 | 6.23795 |
October | 340.00000 | 24.00193 | 56.98879 | 0.62737 | 13.45848 |
November | 330.00000 | 23.98563 | 56.09165 | 0.60674 | 12.88209 |
December | 338.00000 | 23.97467 | 54.59257 | 0.58321 | 12.28785 |
Annual Sum or Average | 4030.00000 | 23.98389 | 55.37467 | 0.23784 | 9.77254 |
Minimum of Months | 308.00000 | 23.95333 | 51.71862 | -0.2636 | 6.23795 |
Maximum of Months | 348.00000 | 24.01586 | 58.33857 | 0.62737 | 13.45848 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.95681 | 51.83816 | 0.54635 | 11.37915 |
February | 308.00000 | 23.96509 | 57.19220 | 0.58418 | 12.32550 |
March | 348.00000 | 23.95131 | 53.66521 | 0.55249 | 11.51992 |
April | 330.00000 | 23.96829 | 52.53331 | 0.54684 | 11.37565 |
May | 344.00000 | 23.98629 | 54.98765 | -0.2635 | 6.71471 |
June | 336.00000 | 23.98552 | 55.72554 | -0.2494 | 6.55541 |
July | 338.00000 | 24.01540 | 56.89461 | -0.2143 | 6.32873 |
August | 348.00000 | 23.99318 | 56.59869 | -0.2230 | 6.35775 |
September | 330.00000 | 24.00932 | 58.39020 | -0.1991 | 6.22520 |
October | 340.00000 | 24.00105 | 57.03745 | 0.62834 | 13.48249 |
November | 330.00000 | 23.98449 | 56.18038 | 0.60686 | 12.88292 |
December | 338.00000 | 23.97290 | 54.69700 | 0.58276 | 12.27447 |
Annual Sum or Average | 4030.00000 | 23.98252 | 55.46067 | 0.23799 | 9.75947 |
Minimum of Months | 308.00000 | 23.95131 | 51.83816 | -0.2635 | 6.22520 |
Maximum of Months | 348.00000 | 24.01540 | 58.39020 | 0.62834 | 13.48249 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.95754 | 51.90136 | 0.55955 | 11.69914 |
February | 308.00000 | 23.96502 | 57.39414 | 0.59498 | 12.60404 |
March | 348.00000 | 23.95118 | 53.89445 | 0.56519 | 11.82665 |
April | 330.00000 | 23.97060 | 52.54345 | 0.56390 | 11.78477 |
May | 344.00000 | 23.99020 | 54.86573 | -0.2312 | 6.41002 |
June | 336.00000 | 23.98851 | 55.64347 | -0.2165 | 6.26263 |
July | 338.00000 | 24.01940 | 56.72281 | -0.1768 | 6.05565 |
August | 348.00000 | 23.99689 | 56.35609 | -0.1815 | 6.04718 |
September | 330.00000 | 24.01290 | 58.32388 | -0.1646 | 5.99574 |
October | 340.00000 | 24.00480 | 56.79209 | 0.65469 | 14.21699 |
November | 330.00000 | 23.98705 | 56.21733 | 0.62536 | 13.38454 |
December | 338.00000 | 23.97499 | 54.72519 | 0.59813 | 12.67408 |
Annual Sum or Average | 4030.00000 | 23.98499 | 55.42872 | 0.26251 | 9.88537 |
Minimum of Months | 308.00000 | 23.95118 | 51.90136 | -0.2312 | 5.99574 |
Maximum of Months | 348.00000 | 24.01940 | 58.32388 | 0.65469 | 14.21699 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.278156E+11 | 0.741463E+10 | 476.40 | 0.198992E+11 | 0.791635E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 50432.44 | 02-JAN-09:01 | 39920.72 | 20-JAN-09:02 | 22667.01 | 31-JAN-09:02 | 11058.72 | 04-JAN-09:01 | 0.00 | 01-JAN-00:05 |
February | 0.290395E+11 | 0.759780E+10 | 430.90 | 0.188732E+11 | 0.101663E+11 | 0.00 | 1.00 | 01-FEB-09:02 | 0.00 | 01-FEB-00:05 | 52433.08 | 18-FEB-09:01 | 36906.83 | 07-FEB-09:02 | 27971.19 | 18-FEB-09:03 | 11130.02 | 23-FEB-09:01 | 0.00 | 01-FEB-00:05 |
March | 0.305030E+11 | 0.814327E+10 | 475.66 | 0.213512E+11 | 0.915174E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 51220.72 | 03-MAR-09:02 | 37037.73 | 07-MAR-09:02 | 26155.11 | 03-MAR-09:03 | 11042.30 | 15-MAR-08:61 | 0.00 | 01-MAR-00:05 |
April | 0.291509E+11 | 0.784860E+10 | 461.91 | 0.209336E+11 | 0.821728E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 50083.62 | 25-APR-08:61 | 36519.10 | 01-APR-08:62 | 20324.12 | 19-APR-08:62 | 11026.63 | 10-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.361898E+11 | 0.971960E+10 | 480.45 | 0.250145E+11 | 0.111753E+11 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 51604.90 | 10-MAY-08:61 | 35070.77 | 31-MAY-08:61 | 25424.53 | 10-MAY-08:05 | 11204.52 | 09-MAY-08:13 | 0.00 | 01-MAY-00:10 |
June | 0.365633E+11 | 0.978462E+10 | 471.21 | 0.250817E+11 | 0.114815E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 50995.84 | 14-JUN-08:61 | 32906.07 | 06-JUN-08:61 | 22875.03 | 14-JUN-08:05 | 11230.18 | 21-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.422282E+11 | 0.113115E+11 | 494.84 | 0.284480E+11 | 0.137802E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 52201.22 | 20-JUL-08:61 | 33299.46 | 18-JUL-08:61 | 26964.31 | 20-JUL-08:04 | 11355.22 | 17-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.428468E+11 | 0.115313E+11 | 488.80 | 0.290490E+11 | 0.137978E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 51176.84 | 01-AUG-08:61 | 32516.92 | 23-AUG-08:61 | 23537.07 | 01-AUG-08:05 | 11368.41 | 12-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.427983E+11 | 0.113232E+11 | 475.96 | 0.279368E+11 | 0.148615E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 52241.93 | 30-SEP-08:61 | 32587.78 | 27-SEP-08:61 | 27756.10 | 30-SEP-08:04 | 11445.82 | 02-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.419910E+11 | 0.112155E+11 | 483.56 | 0.280809E+11 | 0.139101E+11 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:03 | 51036.23 | 13-OCT-08:61 | 32057.35 | 28-OCT-08:61 | 23029.41 | 10-OCT-08:05 | 11395.92 | 07-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.356067E+11 | 0.942834E+10 | 470.80 | 0.239842E+11 | 0.116226E+11 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 51363.90 | 01-NOV-08:61 | 34782.43 | 26-NOV-08:62 | 24358.47 | 01-NOV-08:05 | 11392.42 | 06-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.329251E+11 | 0.869595E+10 | 483.43 | 0.224133E+11 | 0.105118E+11 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-01:05 | 51149.51 | 03-DEC-08:61 | 37530.11 | 19-DEC-09:01 | 23798.18 | 03-DEC-08:04 | 11151.90 | 06-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.427658E+12 | 0.114014E+12 | 5693.92 | 0.291066E+12 | 0.136593E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.278156E+11 | 0.741463E+10 | 430.90 | 0.188732E+11 | 0.791635E+10 | 0.00 | 1.00 | 0.00 | 50083.62 | 32057.35 | 20324.12 | 11026.63 | 0.00 | |||||||
Maximum of Months | 0.428468E+11 | 0.115313E+11 | 494.84 | 0.290490E+11 | 0.148615E+11 | 0.00 | 1.00 | 0.00 | 52433.08 | 39920.72 | 27971.19 | 11445.82 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.143017E+11 | 0.379847E+10 | 477.66 | 0.105312E+11 | 0.377050E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 26121.69 | 02-JAN-09:01 | 21257.38 | 20-JAN-09:02 | 10598.34 | 31-JAN-09:02 | 5668.93 | 04-JAN-09:01 | 0.00 | 01-JAN-00:05 |
February | 0.146845E+11 | 0.383521E+10 | 431.46 | 0.987437E+10 | 0.481009E+10 | 0.00 | 1.00 | 01-FEB-09:02 | 0.00 | 01-FEB-00:05 | 27022.86 | 18-FEB-09:01 | 20491.83 | 07-FEB-09:02 | 13209.07 | 17-FEB-09:04 | 5711.66 | 23-FEB-09:01 | 0.00 | 01-FEB-00:05 |
March | 0.154600E+11 | 0.411606E+10 | 475.51 | 0.111288E+11 | 0.433127E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 26512.76 | 03-MAR-09:02 | 19869.05 | 07-MAR-09:02 | 12368.64 | 03-MAR-09:03 | 5660.00 | 15-MAR-08:61 | 0.00 | 01-MAR-00:05 |
April | 0.146976E+11 | 0.394916E+10 | 462.20 | 0.108445E+11 | 0.385307E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 25838.87 | 25-APR-08:61 | 19538.59 | 30-APR-07:02 | 9552.60 | 19-APR-08:62 | 5652.30 | 10-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.180149E+11 | 0.483416E+10 | 482.74 | 0.127987E+11 | 0.521619E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 26649.95 | 10-MAY-08:61 | 18942.49 | 21-MAY-07:02 | 12049.27 | 10-MAY-08:05 | 5751.08 | 09-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.180683E+11 | 0.483351E+10 | 473.33 | 0.127133E+11 | 0.535495E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 26421.90 | 14-JUN-08:61 | 18363.49 | 04-JUN-07:02 | 11006.39 | 14-JUN-08:13 | 5763.35 | 21-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.206874E+11 | 0.555170E+10 | 496.03 | 0.143133E+11 | 0.637414E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 27033.80 | 20-JUL-08:61 | 17969.86 | 18-JUL-08:61 | 13164.38 | 20-JUL-08:05 | 5828.09 | 17-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.210106E+11 | 0.566066E+10 | 490.58 | 0.146111E+11 | 0.639950E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 26471.83 | 01-AUG-08:61 | 17776.57 | 23-AUG-08:61 | 11300.29 | 01-AUG-08:05 | 5830.33 | 12-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.207782E+11 | 0.551551E+10 | 477.76 | 0.139414E+11 | 0.683680E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 27014.64 | 30-SEP-08:61 | 17838.53 | 24-SEP-07:02 | 13343.74 | 30-SEP-08:05 | 5870.70 | 02-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.207166E+11 | 0.553775E+10 | 485.21 | 0.142501E+11 | 0.646656E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:03 | 26393.53 | 13-OCT-08:61 | 17713.68 | 28-OCT-08:61 | 10838.68 | 13-OCT-08:13 | 5854.11 | 07-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.177473E+11 | 0.469489E+10 | 472.90 | 0.123004E+11 | 0.544690E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 26608.28 | 01-NOV-08:61 | 19298.60 | 26-NOV-08:62 | 11816.36 | 01-NOV-08:05 | 5847.54 | 06-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.165731E+11 | 0.437077E+10 | 484.17 | 0.116355E+11 | 0.493758E+10 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-01:05 | 26413.42 | 03-DEC-08:61 | 20109.29 | 25-DEC-08:62 | 11205.67 | 03-DEC-08:04 | 5727.01 | 06-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.212740E+12 | 0.566978E+11 | 5709.54 | 0.148943E+12 | 0.637976E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.143017E+11 | 0.379847E+10 | 431.46 | 0.987437E+10 | 0.377050E+10 | 0.00 | 1.00 | 0.00 | 25838.87 | 17713.68 | 9552.60 | 5652.30 | 0.00 | |||||||
Maximum of Months | 0.210106E+11 | 0.566066E+10 | 496.03 | 0.146111E+11 | 0.683680E+10 | 0.00 | 1.00 | 0.00 | 27033.80 | 21257.38 | 13343.74 | 5870.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.112173E+11 | 0.294270E+10 | 337.20 | 0.806623E+10 | 0.315105E+10 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:05 | 26411.90 | 01-JAN-09:01 | 20416.83 | 20-JAN-08:62 | 11921.91 | 31-JAN-08:04 | 5610.16 | 01-JAN-09:01 | 0.00 | 01-JAN-00:05 |
February | 0.116193E+11 | 0.299146E+10 | 306.61 | 0.757988E+10 | 0.403940E+10 | 0.00 | 1.00 | 01-FEB-08:62 | 0.00 | 01-FEB-00:05 | 27406.11 | 18-FEB-08:61 | 17291.76 | 09-FEB-08:62 | 15072.58 | 18-FEB-08:61 | 5618.39 | 18-FEB-08:13 | 0.00 | 01-FEB-00:05 |
March | 0.123343E+11 | 0.324690E+10 | 345.49 | 0.866657E+10 | 0.366774E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 26671.16 | 13-MAR-07:02 | 18715.94 | 07-MAR-08:62 | 13107.09 | 03-MAR-08:62 | 5521.24 | 15-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.115796E+11 | 0.307443E+10 | 327.85 | 0.834199E+10 | 0.323766E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 26291.73 | 24-APR-07:02 | 19103.52 | 02-APR-08:62 | 11816.15 | 24-APR-07:03 | 5568.25 | 09-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.146162E+11 | 0.386861E+10 | 345.62 | 0.101521E+11 | 0.446416E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 26840.61 | 10-MAY-07:01 | 17983.15 | 31-MAY-07:02 | 13206.84 | 15-MAY-07:03 | 5697.64 | 14-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.147845E+11 | 0.389082E+10 | 346.93 | 0.101425E+11 | 0.464208E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 26511.54 | 14-JUN-07:01 | 16914.32 | 11-JUN-08:61 | 11753.38 | 14-JUN-07:05 | 5729.22 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.167343E+11 | 0.441231E+10 | 355.72 | 0.113121E+11 | 0.542218E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 27075.94 | 21-JUL-07:01 | 17155.33 | 18-JUL-07:01 | 13706.54 | 21-JUL-07:05 | 5768.45 | 23-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.173842E+11 | 0.461371E+10 | 361.47 | 0.118499E+11 | 0.553428E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 26754.76 | 19-AUG-07:01 | 16361.72 | 23-AUG-07:01 | 12622.46 | 25-AUG-07:04 | 5824.20 | 27-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.167675E+11 | 0.436156E+10 | 348.53 | 0.109691E+11 | 0.579838E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 27121.53 | 25-SEP-07:01 | 16493.58 | 27-SEP-07:01 | 13932.50 | 25-SEP-07:04 | 5877.91 | 03-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.168183E+11 | 0.442213E+10 | 348.01 | 0.113144E+11 | 0.550386E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 26705.34 | 01-OCT-08:61 | 16262.35 | 17-OCT-07:01 | 13160.53 | 10-OCT-07:04 | 5798.40 | 08-OCT-08:13 | 0.00 | 01-OCT-00:03 |
November | 0.143837E+11 | 0.374607E+10 | 337.74 | 0.972315E+10 | 0.466051E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 26680.80 | 24-NOV-08:61 | 17898.00 | 15-NOV-08:61 | 12391.07 | 11-NOV-09:03 | 5762.97 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.131302E+11 | 0.340646E+10 | 340.68 | 0.896382E+10 | 0.416641E+10 | 0.00 | 1.00 | 01-DEC-08:61 | 0.00 | 01-DEC-00:10 | 26739.05 | 03-DEC-09:01 | 19472.86 | 25-DEC-09:02 | 12552.71 | 03-DEC-09:13 | 5689.97 | 03-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.171369E+12 | 0.449771E+11 | 4101.86 | 0.117082E+12 | 0.542877E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.112173E+11 | 0.294270E+10 | 306.61 | 0.757988E+10 | 0.315105E+10 | 0.00 | 1.00 | 0.00 | 26291.73 | 16262.35 | 11753.38 | 5521.24 | 0.00 | |||||||
Maximum of Months | 0.173842E+11 | 0.461371E+10 | 361.47 | 0.118499E+11 | 0.579838E+10 | 0.00 | 1.00 | 0.00 | 27406.11 | 20416.83 | 15072.58 | 5877.91 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.112019E+11 | 0.293981E+10 | 337.37 | 0.805564E+10 | 0.314628E+10 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:05 | 26476.43 | 01-JAN-09:01 | 20271.59 | 20-JAN-08:62 | 11939.41 | 31-JAN-08:04 | 5622.69 | 01-JAN-09:01 | 0.00 | 01-JAN-00:05 |
February | 0.116075E+11 | 0.298962E+10 | 306.61 | 0.757279E+10 | 0.403474E+10 | 0.00 | 1.00 | 01-FEB-08:62 | 0.00 | 01-FEB-00:05 | 27467.26 | 18-FEB-08:61 | 17324.82 | 09-FEB-08:62 | 15100.84 | 18-FEB-08:61 | 5630.75 | 18-FEB-08:13 | 0.00 | 01-FEB-00:05 |
March | 0.123271E+11 | 0.324614E+10 | 345.55 | 0.866270E+10 | 0.366443E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 26733.73 | 13-MAR-07:02 | 18759.14 | 07-MAR-08:62 | 13129.83 | 03-MAR-08:62 | 5533.55 | 15-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.115697E+11 | 0.307293E+10 | 327.85 | 0.833562E+10 | 0.323405E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 26351.25 | 24-APR-07:02 | 19156.12 | 02-APR-08:62 | 11832.39 | 24-APR-07:03 | 5580.71 | 09-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.146353E+11 | 0.387433E+10 | 345.58 | 0.101691E+11 | 0.446619E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 26895.36 | 10-MAY-07:01 | 18038.85 | 31-MAY-07:02 | 13209.51 | 15-MAY-07:03 | 5710.05 | 14-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.148092E+11 | 0.389814E+10 | 347.46 | 0.101641E+11 | 0.464519E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 26567.05 | 14-JUN-07:01 | 16970.55 | 11-JUN-08:61 | 11766.00 | 14-JUN-07:05 | 5741.62 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.167888E+11 | 0.442710E+10 | 357.66 | 0.113570E+11 | 0.543183E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 27130.38 | 21-JUL-07:01 | 17216.16 | 18-JUL-07:01 | 13717.23 | 21-JUL-07:05 | 5781.05 | 23-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.174294E+11 | 0.462634E+10 | 363.20 | 0.118880E+11 | 0.554135E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 26811.59 | 19-AUG-07:01 | 16416.40 | 23-AUG-07:01 | 12635.53 | 25-AUG-07:04 | 5836.46 | 27-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.168332E+11 | 0.437872E+10 | 349.60 | 0.110217E+11 | 0.581148E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 27162.63 | 24-SEP-08:61 | 16549.08 | 27-SEP-07:01 | 13940.82 | 30-SEP-07:04 | 5890.59 | 03-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.168720E+11 | 0.443628E+10 | 348.66 | 0.113587E+11 | 0.551328E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 26759.98 | 10-OCT-07:01 | 16320.07 | 17-OCT-07:01 | 13149.74 | 10-OCT-07:04 | 5810.94 | 08-OCT-08:13 | 0.00 | 01-OCT-00:03 |
November | 0.144010E+11 | 0.375159E+10 | 338.74 | 0.973909E+10 | 0.466196E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 26732.52 | 24-NOV-08:61 | 17944.27 | 15-NOV-08:61 | 12411.97 | 11-NOV-09:03 | 5775.53 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.131315E+11 | 0.340777E+10 | 340.98 | 0.896668E+10 | 0.416479E+10 | 0.00 | 1.00 | 01-DEC-08:61 | 0.00 | 01-DEC-00:10 | 26792.28 | 03-DEC-09:01 | 19532.19 | 25-DEC-09:02 | 12540.81 | 03-DEC-09:13 | 5702.50 | 03-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.171607E+12 | 0.450488E+11 | 4109.27 | 0.117291E+12 | 0.543156E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.112019E+11 | 0.293981E+10 | 306.61 | 0.757279E+10 | 0.314628E+10 | 0.00 | 1.00 | 0.00 | 26351.25 | 16320.07 | 11766.00 | 5533.55 | 0.00 | |||||||
Maximum of Months | 0.174294E+11 | 0.462634E+10 | 363.20 | 0.118880E+11 | 0.581148E+10 | 0.00 | 1.00 | 0.00 | 27467.26 | 20271.59 | 15100.84 | 5890.59 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.110268E+11 | 0.289722E+10 | 337.27 | 0.791293E+10 | 0.311385E+10 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:05 | 26386.41 | 01-JAN-09:01 | 19292.96 | 10-JAN-08:62 | 11876.42 | 31-JAN-08:62 | 5604.62 | 01-JAN-09:01 | 0.00 | 01-JAN-00:05 |
February | 0.114336E+11 | 0.294810E+10 | 306.56 | 0.743823E+10 | 0.399538E+10 | 0.00 | 1.00 | 01-FEB-08:62 | 0.00 | 01-FEB-00:05 | 27371.31 | 18-FEB-08:61 | 16874.89 | 13-FEB-08:62 | 15120.25 | 18-FEB-08:61 | 5612.84 | 18-FEB-08:13 | 0.00 | 01-FEB-00:05 |
March | 0.121314E+11 | 0.319864E+10 | 345.57 | 0.850546E+10 | 0.362595E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 26639.86 | 13-MAR-07:02 | 17768.08 | 19-MAR-08:62 | 13153.98 | 03-MAR-08:62 | 5515.19 | 15-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.113874E+11 | 0.302825E+10 | 327.68 | 0.818747E+10 | 0.319994E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 26258.31 | 24-APR-07:02 | 19031.07 | 02-APR-08:62 | 11846.43 | 24-APR-07:03 | 5562.37 | 09-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.144613E+11 | 0.383189E+10 | 344.55 | 0.100288E+11 | 0.443247E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 26817.24 | 10-MAY-07:01 | 17920.95 | 31-MAY-07:02 | 13212.30 | 15-MAY-07:03 | 5692.11 | 14-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.146397E+11 | 0.385646E+10 | 344.84 | 0.100284E+11 | 0.461124E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 26492.47 | 14-JUN-07:01 | 16880.15 | 11-JUN-08:61 | 11778.15 | 14-JUN-07:05 | 5723.69 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.166290E+11 | 0.438724E+10 | 354.56 | 0.112293E+11 | 0.539966E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 27068.36 | 21-JUL-07:01 | 17120.89 | 18-JUL-07:01 | 13760.83 | 21-JUL-07:05 | 5762.80 | 23-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.172592E+11 | 0.458402E+10 | 359.65 | 0.117512E+11 | 0.550800E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 26727.92 | 19-AUG-07:01 | 16316.93 | 23-AUG-07:01 | 12659.26 | 25-AUG-07:04 | 5818.29 | 27-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.166718E+11 | 0.433877E+10 | 346.91 | 0.108951E+11 | 0.577670E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 27095.87 | 24-SEP-08:61 | 16448.56 | 27-SEP-07:01 | 13969.70 | 30-SEP-07:04 | 5872.09 | 03-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.167091E+11 | 0.439616E+10 | 347.20 | 0.112280E+11 | 0.548107E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 26682.24 | 01-OCT-08:61 | 16227.09 | 17-OCT-07:01 | 13134.78 | 10-OCT-07:04 | 5792.80 | 08-OCT-08:13 | 0.00 | 01-OCT-00:03 |
November | 0.142385E+11 | 0.371198E+10 | 335.95 | 0.961025E+10 | 0.462828E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 26656.80 | 24-NOV-08:61 | 17831.45 | 15-NOV-08:61 | 12430.77 | 11-NOV-09:03 | 5757.55 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.129588E+11 | 0.336626E+10 | 340.03 | 0.882889E+10 | 0.412996E+10 | 0.00 | 1.00 | 01-DEC-08:61 | 0.00 | 01-DEC-00:10 | 26723.05 | 03-DEC-09:01 | 19409.74 | 25-DEC-09:02 | 12577.91 | 03-DEC-09:13 | 5684.33 | 03-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.169547E+12 | 0.445450E+11 | 4090.78 | 0.115644E+12 | 0.539025E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.110268E+11 | 0.289722E+10 | 306.56 | 0.743823E+10 | 0.311385E+10 | 0.00 | 1.00 | 0.00 | 26258.31 | 16227.09 | 11778.15 | 5515.19 | 0.00 | |||||||
Maximum of Months | 0.172592E+11 | 0.458402E+10 | 359.65 | 0.117512E+11 | 0.577670E+10 | 0.00 | 1.00 | 0.00 | 27371.31 | 19409.74 | 15120.25 | 5872.09 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.194781E+11 | 0.520850E+10 | 329.72 | 0.137263E+11 | 0.575184E+10 | 0.00 | 1.00 | 01-JAN-10:01 | 0.00 | 01-JAN-00:05 | 48725.35 | 02-JAN-09:01 | 37805.09 | 20-JAN-09:02 | 21471.48 | 31-JAN-09:02 | 10791.48 | 08-JAN-10:01 | 0.00 | 01-JAN-00:05 |
February | 0.203749E+11 | 0.533652E+10 | 298.51 | 0.129676E+11 | 0.740737E+10 | 0.00 | 1.00 | 01-FEB-09:02 | 0.00 | 01-FEB-00:05 | 50439.81 | 18-FEB-09:01 | 34000.21 | 07-FEB-09:02 | 27274.26 | 18-FEB-09:01 | 10777.53 | 19-FEB-10:13 | 0.00 | 01-FEB-00:05 |
March | 0.217013E+11 | 0.582139E+10 | 338.19 | 0.149468E+11 | 0.675444E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 49389.30 | 13-MAR-08:61 | 34908.32 | 07-MAR-09:02 | 25135.48 | 03-MAR-09:03 | 10700.64 | 12-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.202158E+11 | 0.547198E+10 | 318.42 | 0.142921E+11 | 0.592371E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 48522.38 | 24-APR-08:61 | 35076.09 | 30-APR-09:01 | 21062.50 | 24-APR-08:04 | 10771.17 | 09-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.259611E+11 | 0.699412E+10 | 338.95 | 0.177315E+11 | 0.822963E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 49429.00 | 15-MAY-08:61 | 33663.39 | 31-MAY-08:61 | 23976.11 | 10-MAY-08:05 | 10880.80 | 21-MAY-09:01 | 0.00 | 01-MAY-00:10 |
June | 0.262739E+11 | 0.703742E+10 | 338.32 | 0.177136E+11 | 0.856022E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 48933.52 | 14-JUN-08:61 | 31230.45 | 06-JUN-08:61 | 21769.90 | 14-JUN-08:05 | 10867.06 | 18-JUN-09:01 | 0.00 | 01-JUN-00:10 |
July | 0.299176E+11 | 0.801900E+10 | 346.64 | 0.198888E+11 | 0.100289E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 50078.96 | 20-JUL-08:61 | 31907.12 | 18-JUL-08:61 | 25631.12 | 20-JUL-08:05 | 11029.04 | 09-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.312608E+11 | 0.844020E+10 | 354.38 | 0.209860E+11 | 0.102748E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 49234.05 | 28-AUG-08:61 | 31298.52 | 23-AUG-08:61 | 22540.75 | 28-AUG-08:05 | 11130.51 | 27-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.300425E+11 | 0.794283E+10 | 334.59 | 0.193352E+11 | 0.107073E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 50118.10 | 30-SEP-08:61 | 30936.31 | 27-SEP-08:61 | 26595.21 | 30-SEP-08:04 | 11108.09 | 03-SEP-09:13 | 0.00 | 01-SEP-00:10 |
October | 0.302271E+11 | 0.808076E+10 | 339.65 | 0.200129E+11 | 0.102142E+11 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 49575.88 | 10-OCT-08:61 | 30369.62 | 27-OCT-08:61 | 24122.35 | 23-OCT-08:04 | 11134.71 | 01-OCT-09:13 | 0.00 | 01-OCT-00:03 |
November | 0.254824E+11 | 0.675322E+10 | 331.34 | 0.169015E+11 | 0.858095E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 49242.62 | 01-NOV-08:61 | 33040.09 | 15-NOV-09:01 | 23049.33 | 01-NOV-08:05 | 10955.29 | 06-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.230140E+11 | 0.608189E+10 | 330.40 | 0.153946E+11 | 0.761943E+10 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 49679.09 | 03-DEC-10:01 | 35687.17 | 25-DEC-10:01 | 24530.39 | 03-DEC-10:13 | 10720.61 | 06-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.303950E+12 | 0.811878E+11 | 3999.12 | 0.203897E+12 | 0.100053E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.194781E+11 | 0.520850E+10 | 298.51 | 0.129676E+11 | 0.575184E+10 | 0.00 | 1.00 | 0.00 | 48522.38 | 30369.62 | 21062.50 | 10700.64 | 0.00 | |||||||
Maximum of Months | 0.312608E+11 | 0.844020E+10 | 354.38 | 0.209860E+11 | 0.107073E+11 | 0.00 | 1.00 | 0.00 | 50439.81 | 37805.09 | 27274.26 | 11134.71 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.101273E+11 | 0.266204E+10 | 329.69 | 0.715118E+10 | 0.297612E+10 | 0.00 | 1.00 | 01-JAN-10:01 | 0.00 | 01-JAN-00:05 | 25455.30 | 02-JAN-09:01 | 19806.09 | 20-JAN-09:02 | 11147.97 | 31-JAN-09:02 | 5537.45 | 08-JAN-10:01 | 0.00 | 01-JAN-00:05 |
February | 0.105831E+11 | 0.272519E+10 | 298.47 | 0.674875E+10 | 0.383436E+10 | 0.00 | 1.00 | 01-FEB-09:02 | 0.00 | 01-FEB-00:05 | 26334.85 | 18-FEB-09:01 | 17004.47 | 07-FEB-09:02 | 14225.10 | 18-FEB-09:01 | 5529.83 | 19-FEB-10:13 | 0.00 | 01-FEB-00:05 |
March | 0.112725E+11 | 0.297296E+10 | 338.39 | 0.777679E+10 | 0.349570E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 25808.71 | 13-MAR-08:61 | 18291.99 | 07-MAR-09:02 | 13065.45 | 03-MAR-09:03 | 5490.49 | 12-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.105055E+11 | 0.279573E+10 | 318.52 | 0.744004E+10 | 0.306550E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 25349.53 | 24-APR-08:61 | 18318.95 | 30-APR-09:01 | 11000.17 | 24-APR-08:04 | 5527.29 | 09-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.134973E+11 | 0.357539E+10 | 338.34 | 0.923289E+10 | 0.426439E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 25832.82 | 15-MAY-08:61 | 17601.62 | 31-MAY-08:61 | 12480.24 | 10-MAY-08:05 | 5583.69 | 21-MAY-09:01 | 0.00 | 01-MAY-00:10 |
June | 0.136461E+11 | 0.359413E+10 | 336.80 | 0.921563E+10 | 0.443048E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 25562.80 | 14-JUN-08:61 | 16339.89 | 06-JUN-08:61 | 11354.23 | 14-JUN-08:05 | 5576.11 | 18-JUN-09:01 | 0.00 | 01-JUN-00:10 |
July | 0.155536E+11 | 0.409851E+10 | 345.18 | 0.103561E+11 | 0.519742E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 26168.48 | 20-JUL-08:61 | 16684.57 | 18-JUL-08:61 | 13390.54 | 20-JUL-08:04 | 5659.13 | 09-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.162524E+11 | 0.431430E+10 | 353.01 | 0.109271E+11 | 0.532530E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 25703.54 | 28-AUG-08:61 | 16362.66 | 23-AUG-08:61 | 11738.14 | 28-AUG-08:05 | 5710.84 | 27-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.156111E+11 | 0.405821E+10 | 333.14 | 0.100633E+11 | 0.554780E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 26169.62 | 30-SEP-08:61 | 16178.35 | 27-SEP-08:61 | 13851.21 | 30-SEP-08:04 | 5699.37 | 03-SEP-09:13 | 0.00 | 01-SEP-00:10 |
October | 0.157294E+11 | 0.413395E+10 | 339.62 | 0.104304E+11 | 0.529900E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 25902.90 | 10-OCT-08:61 | 15885.39 | 27-OCT-08:61 | 12582.22 | 23-OCT-08:04 | 5713.07 | 01-OCT-09:13 | 0.00 | 01-OCT-00:03 |
November | 0.132448E+11 | 0.345091E+10 | 330.53 | 0.880198E+10 | 0.444285E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 25725.23 | 01-NOV-08:61 | 17286.06 | 15-NOV-09:01 | 12010.87 | 01-NOV-08:05 | 5621.22 | 06-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.119618E+11 | 0.310781E+10 | 329.81 | 0.801788E+10 | 0.394391E+10 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 25954.93 | 03-DEC-10:01 | 18693.67 | 25-DEC-10:01 | 12795.06 | 03-DEC-10:05 | 5500.85 | 06-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.157985E+12 | 0.414891E+11 | 3991.50 | 0.106162E+12 | 0.518228E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.101273E+11 | 0.266204E+10 | 298.47 | 0.674875E+10 | 0.297612E+10 | 0.00 | 1.00 | 0.00 | 25349.53 | 15885.39 | 11000.17 | 5490.49 | 0.00 | |||||||
Maximum of Months | 0.162524E+11 | 0.431430E+10 | 353.01 | 0.109271E+11 | 0.554780E+10 | 0.00 | 1.00 | 0.00 | 26334.85 | 19806.09 | 14225.10 | 5713.07 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.100354E+11 | 0.263893E+10 | 329.44 | 0.707612E+10 | 0.295931E+10 | 0.00 | 1.00 | 01-JAN-10:01 | 0.00 | 01-JAN-00:05 | 25350.61 | 02-JAN-09:01 | 19689.77 | 20-JAN-09:02 | 11132.55 | 31-JAN-09:02 | 5514.40 | 08-JAN-10:01 | 0.00 | 01-JAN-00:05 |
February | 0.104929E+11 | 0.270280E+10 | 298.27 | 0.667886E+10 | 0.381403E+10 | 0.00 | 1.00 | 01-FEB-09:02 | 0.00 | 01-FEB-00:05 | 26222.91 | 18-FEB-09:01 | 16599.82 | 09-FEB-09:02 | 14195.82 | 18-FEB-09:01 | 5506.79 | 19-FEB-10:13 | 0.00 | 01-FEB-00:05 |
March | 0.111764E+11 | 0.294865E+10 | 338.08 | 0.769920E+10 | 0.347718E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 25697.35 | 13-MAR-08:61 | 18182.69 | 07-MAR-09:02 | 13041.50 | 03-MAR-09:03 | 5467.47 | 12-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.104182E+11 | 0.277339E+10 | 318.42 | 0.736843E+10 | 0.304972E+10 | 0.00 | 1.00 | 02-APR-09:02 | 0.00 | 01-APR-00:05 | 25239.97 | 24-APR-08:61 | 18209.90 | 30-APR-09:01 | 10974.96 | 24-APR-08:04 | 5504.30 | 09-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.134061E+11 | 0.355186E+10 | 338.07 | 0.915846E+10 | 0.424765E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 25722.07 | 15-MAY-08:61 | 17497.90 | 31-MAY-08:61 | 12453.99 | 10-MAY-08:05 | 5560.49 | 21-MAY-09:01 | 0.00 | 01-MAY-00:10 |
June | 0.135563E+11 | 0.357083E+10 | 335.93 | 0.914281E+10 | 0.441348E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 25459.02 | 14-JUN-08:61 | 16236.43 | 06-JUN-08:61 | 11327.77 | 14-JUN-08:05 | 5553.25 | 18-JUN-09:01 | 0.00 | 01-JUN-00:10 |
July | 0.154646E+11 | 0.407492E+10 | 344.20 | 0.102839E+11 | 0.518070E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 26068.31 | 20-JUL-08:61 | 16595.75 | 18-JUL-08:61 | 13370.79 | 20-JUL-08:04 | 5635.50 | 09-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.161634E+11 | 0.429034E+10 | 352.19 | 0.108542E+11 | 0.530914E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 25647.33 | 28-AUG-08:61 | 16274.59 | 23-AUG-08:61 | 11699.26 | 28-AUG-08:05 | 5687.07 | 27-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.155229E+11 | 0.403510E+10 | 332.50 | 0.999284E+10 | 0.553009E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 26058.27 | 30-SEP-08:61 | 16092.23 | 27-SEP-08:61 | 13819.19 | 30-SEP-08:04 | 5675.62 | 03-SEP-09:13 | 0.00 | 01-SEP-00:10 |
October | 0.156415E+11 | 0.411070E+10 | 338.99 | 0.103588E+11 | 0.528274E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 25798.68 | 10-OCT-08:61 | 15784.39 | 27-OCT-08:61 | 12549.19 | 23-OCT-08:04 | 5689.44 | 01-OCT-09:13 | 0.00 | 01-OCT-00:03 |
November | 0.131536E+11 | 0.342760E+10 | 329.82 | 0.872883E+10 | 0.442472E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 25623.05 | 01-NOV-08:61 | 17181.13 | 15-NOV-09:01 | 11985.44 | 01-NOV-08:05 | 5597.72 | 06-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.118692E+11 | 0.308460E+10 | 329.95 | 0.794336E+10 | 0.392584E+10 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 25847.83 | 03-DEC-10:01 | 18582.13 | 25-DEC-10:01 | 12750.82 | 03-DEC-10:05 | 5477.88 | 06-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.156900E+12 | 0.412097E+11 | 3985.86 | 0.105286E+12 | 0.516146E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.100354E+11 | 0.263893E+10 | 298.27 | 0.667886E+10 | 0.295931E+10 | 0.00 | 1.00 | 0.00 | 25239.97 | 15784.39 | 10974.96 | 5467.47 | 0.00 | |||||||
Maximum of Months | 0.161634E+11 | 0.429034E+10 | 352.19 | 0.108542E+11 | 0.553009E+10 | 0.00 | 1.00 | 0.00 | 26222.91 | 19689.77 | 14195.82 | 5689.44 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.991526E+10 | 0.261000E+10 | 328.75 | 0.698170E+10 | 0.293357E+10 | 0.00 | 1.00 | 01-JAN-10:01 | 0.00 | 01-JAN-00:05 | 25333.13 | 02-JAN-09:01 | 19621.99 | 20-JAN-09:02 | 11168.85 | 31-JAN-09:02 | 5510.96 | 08-JAN-10:01 | 0.00 | 01-JAN-00:05 |
February | 0.103678E+11 | 0.267341E+10 | 298.06 | 0.658583E+10 | 0.378201E+10 | 0.00 | 1.00 | 01-FEB-09:02 | 0.00 | 01-FEB-00:05 | 26200.49 | 18-FEB-09:01 | 16519.08 | 09-FEB-09:02 | 14230.09 | 18-FEB-09:01 | 5503.19 | 19-FEB-10:13 | 0.00 | 01-FEB-00:05 |
March | 0.110482E+11 | 0.291796E+10 | 338.39 | 0.759990E+10 | 0.344830E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 25672.60 | 13-MAR-08:61 | 18111.87 | 07-MAR-09:02 | 13086.00 | 03-MAR-09:03 | 5463.73 | 12-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.103166E+11 | 0.274887E+10 | 318.35 | 0.728852E+10 | 0.302813E+10 | 0.00 | 1.00 | 02-APR-09:02 | 0.00 | 01-APR-00:05 | 25215.15 | 24-APR-08:61 | 18150.01 | 30-APR-09:01 | 11002.64 | 24-APR-08:04 | 5500.87 | 09-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.133312E+11 | 0.353387E+10 | 337.25 | 0.909997E+10 | 0.423122E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 25698.31 | 15-MAY-08:61 | 17441.05 | 31-MAY-08:61 | 12476.56 | 10-MAY-08:05 | 5557.12 | 21-MAY-09:01 | 0.00 | 01-MAY-00:10 |
June | 0.134904E+11 | 0.355498E+10 | 334.18 | 0.909197E+10 | 0.439848E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 25439.95 | 14-JUN-08:61 | 16181.04 | 06-JUN-08:61 | 11346.99 | 14-JUN-08:05 | 5549.43 | 18-JUN-09:01 | 0.00 | 01-JUN-00:10 |
July | 0.154157E+11 | 0.406252E+10 | 342.76 | 0.102466E+11 | 0.516906E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 26061.80 | 20-JUL-08:61 | 16565.88 | 18-JUL-08:61 | 13400.36 | 20-JUL-08:04 | 5631.88 | 09-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.161286E+11 | 0.428137E+10 | 351.38 | 0.108275E+11 | 0.530117E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 25593.16 | 28-AUG-08:61 | 16247.22 | 23-AUG-08:61 | 11731.53 | 28-AUG-08:05 | 5683.51 | 27-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.154767E+11 | 0.402361E+10 | 331.48 | 0.995789E+10 | 0.551883E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 26039.36 | 25-SEP-08:61 | 16066.04 | 27-SEP-08:61 | 13839.05 | 30-SEP-08:04 | 5671.98 | 03-SEP-09:13 | 0.00 | 01-SEP-00:10 |
October | 0.155952E+11 | 0.409915E+10 | 338.10 | 0.103230E+11 | 0.527221E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 25785.50 | 10-OCT-08:61 | 15739.52 | 27-OCT-08:61 | 12570.03 | 23-OCT-08:04 | 5685.86 | 01-OCT-09:13 | 0.00 | 01-OCT-00:03 |
November | 0.130694E+11 | 0.340738E+10 | 328.48 | 0.866472E+10 | 0.440473E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 25610.24 | 01-NOV-08:61 | 17131.35 | 15-NOV-09:01 | 12003.19 | 01-NOV-08:05 | 5594.11 | 06-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.117684E+11 | 0.306075E+10 | 329.56 | 0.786531E+10 | 0.390307E+10 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 25841.96 | 03-DEC-10:01 | 18518.38 | 25-DEC-10:01 | 12781.94 | 03-DEC-10:05 | 5474.38 | 06-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.155924E+12 | 0.409739E+11 | 3976.74 | 0.104533E+12 | 0.513908E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.991526E+10 | 0.261000E+10 | 298.06 | 0.658583E+10 | 0.293357E+10 | 0.00 | 1.00 | 0.00 | 25215.15 | 15739.52 | 11002.64 | 5463.73 | 0.00 | |||||||
Maximum of Months | 0.161286E+11 | 0.428137E+10 | 351.38 | 0.108275E+11 | 0.551883E+10 | 0.00 | 1.00 | 0.00 | 26200.49 | 19621.99 | 14230.09 | 5685.86 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.104822E+11 | 0.276242E+10 | 329.71 | 0.746208E+10 | 0.302011E+10 | 0.00 | 1.00 | 01-JAN-10:01 | 0.00 | 01-JAN-00:05 | 27051.20 | 03-JAN-09:01 | 21084.04 | 20-JAN-09:02 | 12557.42 | 31-JAN-09:02 | 5867.77 | 08-JAN-10:01 | 0.00 | 01-JAN-00:05 |
February | 0.108224E+11 | 0.279837E+10 | 298.15 | 0.694432E+10 | 0.387809E+10 | 0.00 | 1.00 | 01-FEB-09:02 | 0.00 | 01-FEB-00:05 | 28092.75 | 18-FEB-09:01 | 17789.23 | 06-FEB-09:01 | 15912.19 | 18-FEB-09:01 | 5857.37 | 19-FEB-10:13 | 0.00 | 01-FEB-00:05 |
March | 0.116099E+11 | 0.307245E+10 | 338.64 | 0.806613E+10 | 0.354376E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 27365.24 | 13-MAR-08:61 | 19405.80 | 26-MAR-09:02 | 14464.35 | 03-MAR-09:02 | 5815.95 | 12-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.110275E+11 | 0.293899E+10 | 319.10 | 0.787637E+10 | 0.315113E+10 | 0.00 | 1.00 | 02-APR-09:02 | 0.00 | 01-APR-00:05 | 26856.51 | 24-APR-08:61 | 19414.65 | 30-APR-09:01 | 11529.49 | 24-APR-08:03 | 5858.81 | 09-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.143838E+11 | 0.381089E+10 | 338.68 | 0.993841E+10 | 0.444543E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 27579.10 | 10-MAY-08:61 | 18619.41 | 31-MAY-08:61 | 14033.89 | 10-MAY-08:04 | 5916.60 | 21-MAY-09:01 | 0.00 | 01-MAY-00:10 |
June | 0.145927E+11 | 0.384204E+10 | 337.41 | 0.994656E+10 | 0.464618E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 27263.29 | 14-JUN-08:61 | 17353.96 | 11-JUN-09:01 | 12539.70 | 14-JUN-08:05 | 5906.98 | 18-JUN-09:01 | 0.00 | 01-JUN-00:10 |
July | 0.167121E+11 | 0.440059E+10 | 344.81 | 0.112456E+11 | 0.546651E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 27899.01 | 20-JUL-08:61 | 17627.36 | 18-JUL-08:61 | 14726.83 | 20-JUL-08:02 | 5995.97 | 09-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.175790E+11 | 0.465843E+10 | 352.83 | 0.119513E+11 | 0.562765E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 27387.24 | 01-AUG-08:61 | 17010.64 | 23-AUG-08:61 | 13061.86 | 25-AUG-08:04 | 6048.67 | 27-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.166524E+11 | 0.432876E+10 | 332.53 | 0.108414E+11 | 0.581095E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 27921.34 | 30-SEP-08:61 | 17195.66 | 27-SEP-08:61 | 15388.11 | 30-SEP-08:61 | 6037.87 | 03-SEP-09:13 | 0.00 | 01-SEP-00:10 |
October | 0.168577E+11 | 0.442827E+10 | 339.17 | 0.113093E+11 | 0.554841E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 27471.69 | 10-OCT-08:61 | 16584.36 | 17-OCT-08:61 | 13293.41 | 10-OCT-08:05 | 6051.83 | 01-OCT-09:13 | 0.00 | 01-OCT-00:03 |
November | 0.139383E+11 | 0.363637E+10 | 330.16 | 0.933743E+10 | 0.460090E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 27451.88 | 01-NOV-08:61 | 18411.34 | 15-NOV-09:01 | 13300.48 | 01-NOV-08:05 | 5955.33 | 06-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.124698E+11 | 0.324723E+10 | 330.21 | 0.842457E+10 | 0.404523E+10 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 27509.96 | 03-DEC-10:01 | 19973.84 | 25-DEC-10:01 | 13531.29 | 03-DEC-10:05 | 5829.87 | 06-DEC-09:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.167128E+12 | 0.439248E+11 | 3991.40 | 0.113343E+12 | 0.537844E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.104822E+11 | 0.276242E+10 | 298.15 | 0.694432E+10 | 0.302011E+10 | 0.00 | 1.00 | 0.00 | 26856.51 | 16584.36 | 11529.49 | 5815.95 | 0.00 | |||||||
Maximum of Months | 0.175790E+11 | 0.465843E+10 | 352.83 | 0.119513E+11 | 0.581095E+10 | 0.00 | 1.00 | 0.00 | 28092.75 | 21084.04 | 15912.19 | 6051.83 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 122.03 | 24.38 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.37 | 23.08 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.69 | 22.69 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.91 | 19.00 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.19 | 13.81 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.67 | 10.67 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.89 | 7.84 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.84 | 9.01 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.95 | 8.15 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.42 | 13.31 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 122.01 | 15.87 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.67 | 18.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.46 | 15.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.67 | 7.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.67 | 24.38 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 122.03 | 24.38 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.37 | 23.08 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.69 | 22.69 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.91 | 19.00 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.19 | 13.81 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.67 | 10.67 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.89 | 7.84 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.84 | 9.01 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.95 | 8.15 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.42 | 13.31 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 122.01 | 15.87 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.67 | 18.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.46 | 15.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.67 | 7.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.67 | 24.38 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 122.03 | 24.38 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.37 | 23.08 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.69 | 22.69 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.91 | 19.00 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.19 | 13.81 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.67 | 10.67 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.89 | 7.84 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.84 | 9.01 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.95 | 8.15 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.42 | 13.31 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 122.01 | 15.87 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.67 | 18.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.46 | 15.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.67 | 7.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.67 | 24.38 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 122.03 | 24.38 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.37 | 23.08 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.69 | 22.69 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.91 | 19.00 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.19 | 13.81 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.67 | 10.67 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.89 | 7.84 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.84 | 9.01 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.95 | 8.15 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.42 | 13.31 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 122.01 | 15.87 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.67 | 18.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.46 | 15.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.67 | 7.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.67 | 24.38 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.84 | 57.67 | 34.17 | 146.54 | 29.25 | 0.00 | 0.00 | 744.00 |
February | 77.79 | 41.47 | 36.32 | 121.73 | 27.68 | 0.00 | 0.00 | 672.00 |
March | 56.44 | 19.34 | 37.10 | 84.84 | 27.21 | 0.00 | 0.00 | 744.00 |
April | 36.49 | 3.51 | 32.98 | 52.65 | 22.81 | 0.00 | 0.00 | 720.00 |
May | 30.89 | 0.08 | 30.81 | 52.90 | 16.60 | 0.00 | 0.00 | 744.00 |
June | 30.55 | 0.00 | 30.55 | 52.28 | 12.86 | 0.00 | 0.00 | 720.00 |
July | 29.63 | 0.08 | 29.55 | 56.08 | 9.47 | 0.00 | 0.00 | 744.00 |
August | 32.41 | 1.99 | 30.42 | 59.62 | 10.87 | 0.00 | 0.00 | 744.00 |
September | 48.98 | 11.89 | 37.09 | 82.61 | 9.84 | 0.00 | 0.00 | 720.00 |
October | 69.44 | 33.53 | 35.91 | 120.43 | 16.02 | 0.00 | 0.00 | 744.00 |
November | 87.68 | 50.26 | 37.42 | 146.46 | 19.10 | 0.00 | 0.00 | 720.00 |
December | 94.88 | 61.13 | 33.75 | 154.51 | 22.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 57.15 | 23.34 | 33.81 | 94.11 | 18.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.63 | 0.00 | 29.55 | 52.28 | 9.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.88 | 61.13 | 37.42 | 154.51 | 29.25 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.84 | 57.67 | 34.17 | 146.54 | 29.25 | 0.00 | 0.00 | 744.00 |
February | 77.79 | 41.47 | 36.32 | 121.73 | 27.68 | 0.00 | 0.00 | 672.00 |
March | 56.44 | 19.34 | 37.10 | 84.84 | 27.21 | 0.00 | 0.00 | 744.00 |
April | 36.49 | 3.51 | 32.98 | 52.65 | 22.81 | 0.00 | 0.00 | 720.00 |
May | 30.89 | 0.08 | 30.81 | 52.90 | 16.60 | 0.00 | 0.00 | 744.00 |
June | 30.55 | 0.00 | 30.55 | 52.28 | 12.86 | 0.00 | 0.00 | 720.00 |
July | 29.63 | 0.08 | 29.55 | 56.08 | 9.47 | 0.00 | 0.00 | 744.00 |
August | 32.41 | 1.99 | 30.42 | 59.62 | 10.87 | 0.00 | 0.00 | 744.00 |
September | 48.98 | 11.89 | 37.09 | 82.61 | 9.84 | 0.00 | 0.00 | 720.00 |
October | 69.44 | 33.53 | 35.91 | 120.43 | 16.02 | 0.00 | 0.00 | 744.00 |
November | 87.68 | 50.26 | 37.42 | 146.46 | 19.10 | 0.00 | 0.00 | 720.00 |
December | 94.88 | 61.13 | 33.75 | 154.51 | 22.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 57.15 | 23.34 | 33.81 | 94.11 | 18.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.63 | 0.00 | 29.55 | 52.28 | 9.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.88 | 61.13 | 37.42 | 154.51 | 29.25 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 121.78 | 24.54 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.20 | 23.20 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.64 | 22.84 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.92 | 19.10 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.30 | 13.85 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.83 | 10.61 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 47.15 | 7.74 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 50.14 | 8.87 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 69.23 | 7.96 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.51 | 13.25 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.92 | 15.84 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.47 | 18.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.50 | 15.51 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.83 | 7.74 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.47 | 24.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 121.78 | 24.54 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.20 | 23.20 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.64 | 22.84 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.92 | 19.10 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.30 | 13.85 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.83 | 10.61 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 47.15 | 7.74 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 50.14 | 8.87 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 69.23 | 7.96 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.51 | 13.25 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.92 | 15.84 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.47 | 18.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.50 | 15.51 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.83 | 7.74 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.47 | 24.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.84 | 57.67 | 34.17 | 146.26 | 29.44 | 0.00 | 0.00 | 744.00 |
February | 77.79 | 41.47 | 36.32 | 121.54 | 27.82 | 0.00 | 0.00 | 672.00 |
March | 56.44 | 19.34 | 37.10 | 84.78 | 27.38 | 0.00 | 0.00 | 744.00 |
April | 36.49 | 3.51 | 32.98 | 52.66 | 22.93 | 0.00 | 0.00 | 720.00 |
May | 30.89 | 0.08 | 30.81 | 53.04 | 16.64 | 0.00 | 0.00 | 744.00 |
June | 30.55 | 0.00 | 30.55 | 52.48 | 12.79 | 0.00 | 0.00 | 720.00 |
July | 29.63 | 0.08 | 29.55 | 56.40 | 9.35 | 0.00 | 0.00 | 744.00 |
August | 32.41 | 1.99 | 30.42 | 59.99 | 10.70 | 0.00 | 0.00 | 744.00 |
September | 48.98 | 11.89 | 37.09 | 82.96 | 9.61 | 0.00 | 0.00 | 720.00 |
October | 69.44 | 33.53 | 35.91 | 120.55 | 15.94 | 0.00 | 0.00 | 744.00 |
November | 87.68 | 50.26 | 37.42 | 146.37 | 19.05 | 0.00 | 0.00 | 720.00 |
December | 94.88 | 61.13 | 33.75 | 154.29 | 22.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 57.15 | 23.34 | 33.81 | 94.17 | 18.63 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.63 | 0.00 | 29.55 | 52.48 | 9.35 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.88 | 61.13 | 37.42 | 154.29 | 29.44 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 121.90 | 26.39 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.24 | 25.09 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.56 | 24.65 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.89 | 20.96 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.15 | 15.99 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.69 | 12.84 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.71 | 10.23 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.95 | 11.34 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.70 | 10.53 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.27 | 15.86 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.98 | 18.11 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.57 | 20.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.38 | 17.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.69 | 10.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.57 | 26.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 121.90 | 26.39 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.24 | 25.09 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.56 | 24.65 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.89 | 20.96 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.15 | 15.99 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.69 | 12.84 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.71 | 10.23 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.95 | 11.34 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.70 | 10.53 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.27 | 15.86 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.98 | 18.11 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.57 | 20.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.38 | 17.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.69 | 10.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.57 | 26.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 145.60 | 31.43 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 120.92 | 29.86 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 84.23 | 29.34 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 52.34 | 24.97 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 52.58 | 19.05 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 52.02 | 15.31 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 55.57 | 12.21 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 59.42 | 13.54 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 81.88 | 12.57 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 119.61 | 18.91 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 145.63 | 21.60 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 153.56 | 24.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 93.51 | 21.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 52.02 | 12.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 153.56 | 31.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 121.91 | 26.38 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.25 | 25.10 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.57 | 24.68 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.90 | 20.97 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.13 | 16.09 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.67 | 12.95 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.66 | 10.42 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.91 | 11.52 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.65 | 10.75 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.23 | 16.05 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.96 | 18.20 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.57 | 20.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.36 | 17.80 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.67 | 10.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.57 | 26.38 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 121.91 | 26.38 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.25 | 25.10 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.57 | 24.68 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.90 | 20.97 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.13 | 16.09 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.67 | 12.95 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.66 | 10.42 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.91 | 11.52 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.65 | 10.75 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.23 | 16.05 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.96 | 18.20 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.57 | 20.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.36 | 17.80 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.67 | 10.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.57 | 26.38 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 145.61 | 31.41 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 120.93 | 29.87 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 84.23 | 29.37 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 52.35 | 24.98 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 52.55 | 19.17 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 51.99 | 15.45 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 55.51 | 12.43 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 59.38 | 13.75 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 81.82 | 12.83 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 119.56 | 19.13 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 145.60 | 21.71 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 153.55 | 24.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 93.48 | 21.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 51.99 | 12.43 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 153.55 | 31.41 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 122.00 | 26.12 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.33 | 24.82 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.65 | 24.38 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.99 | 20.69 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.22 | 15.84 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.75 | 12.70 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.73 | 10.18 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.98 | 11.26 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.70 | 10.50 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.29 | 15.79 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 122.03 | 17.96 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.65 | 20.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.44 | 17.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.75 | 10.18 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.65 | 26.12 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 122.00 | 26.12 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.33 | 24.82 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.65 | 24.38 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.99 | 20.69 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.22 | 15.84 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.75 | 12.70 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.73 | 10.18 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.98 | 11.26 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.70 | 10.50 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.29 | 15.79 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 122.03 | 17.96 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.65 | 20.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.44 | 17.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.75 | 10.18 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.65 | 26.12 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 145.72 | 31.11 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 121.03 | 29.54 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 84.33 | 29.02 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 52.45 | 24.64 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 52.65 | 18.87 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 52.09 | 15.16 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 55.60 | 12.15 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 59.46 | 13.44 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 81.89 | 12.53 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 119.63 | 18.83 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 145.70 | 21.42 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 153.65 | 24.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 93.58 | 20.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 52.09 | 12.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 153.65 | 31.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 121.96 | 25.34 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.34 | 23.97 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.65 | 23.47 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.87 | 19.83 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 43.94 | 14.99 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.44 | 11.82 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.33 | 9.36 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.58 | 10.31 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.34 | 9.60 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.01 | 14.91 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.84 | 17.16 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.57 | 19.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.23 | 16.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.44 | 9.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.57 | 25.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 121.96 | 25.34 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.34 | 23.97 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.65 | 23.47 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.87 | 19.83 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 43.94 | 14.99 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.44 | 11.82 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.33 | 9.36 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.58 | 10.31 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.34 | 9.60 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.01 | 14.91 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.84 | 17.16 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.57 | 19.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.23 | 16.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.44 | 9.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.57 | 25.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 121.96 | 25.34 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.34 | 23.97 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.65 | 23.47 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.87 | 19.83 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 43.94 | 14.99 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.44 | 11.82 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.33 | 9.36 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.58 | 10.31 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.34 | 9.60 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.01 | 14.91 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.84 | 17.16 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.57 | 19.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.23 | 16.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.44 | 9.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.57 | 25.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 121.96 | 25.34 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.34 | 23.97 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.65 | 23.47 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.87 | 19.83 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 43.94 | 14.99 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.44 | 11.82 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.33 | 9.36 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.58 | 10.31 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.34 | 9.60 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.01 | 14.91 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.84 | 17.16 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.57 | 19.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.23 | 16.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.44 | 9.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.57 | 25.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 145.68 | 30.18 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 121.04 | 28.55 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 84.35 | 27.94 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 52.33 | 23.62 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 52.34 | 17.88 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 51.74 | 14.12 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 55.14 | 11.18 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 59.01 | 12.32 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 81.48 | 11.47 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 119.32 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 145.48 | 20.48 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 153.56 | 23.72 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 93.35 | 19.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 51.74 | 11.18 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 153.56 | 30.18 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 145.68 | 30.18 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 121.04 | 28.55 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 84.35 | 27.94 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 52.33 | 23.62 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 52.34 | 17.88 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 51.74 | 14.12 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 55.14 | 11.18 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 59.01 | 12.32 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 81.48 | 11.47 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 119.32 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 145.48 | 20.48 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 153.56 | 23.72 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 93.35 | 19.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 51.74 | 11.18 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 153.56 | 30.18 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 121.89 | 25.02 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.29 | 23.64 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.69 | 23.12 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.98 | 19.48 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.13 | 14.63 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.65 | 11.42 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.58 | 8.94 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.84 | 9.88 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.54 | 9.15 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.11 | 14.49 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.84 | 16.76 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.50 | 19.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.33 | 16.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.65 | 8.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.50 | 25.02 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 121.89 | 25.02 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.29 | 23.64 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.69 | 23.12 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.98 | 19.48 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.13 | 14.63 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.65 | 11.42 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.58 | 8.94 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.84 | 9.88 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.54 | 9.15 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.11 | 14.49 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.84 | 16.76 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.50 | 19.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.33 | 16.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.65 | 8.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.50 | 25.02 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 145.61 | 29.80 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 121.00 | 28.14 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 84.41 | 27.53 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 52.47 | 23.21 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 52.57 | 17.44 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 52.00 | 13.64 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 55.45 | 10.69 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 59.32 | 11.80 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 81.71 | 10.94 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 119.44 | 17.28 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 145.49 | 20.00 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 153.50 | 23.27 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 93.47 | 19.43 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 52.00 | 10.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 153.50 | 29.80 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 121.95 | 24.89 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.36 | 23.51 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.76 | 22.99 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.05 | 19.36 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.20 | 14.52 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.72 | 11.31 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.65 | 8.84 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.91 | 9.78 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.60 | 9.05 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.17 | 14.38 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.90 | 16.65 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.56 | 19.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.40 | 16.19 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.72 | 8.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.56 | 24.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 121.95 | 24.89 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.36 | 23.51 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.76 | 22.99 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.05 | 19.36 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.20 | 14.52 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.72 | 11.31 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.65 | 8.84 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.91 | 9.78 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.60 | 9.05 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.17 | 14.38 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.90 | 16.65 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.56 | 19.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.40 | 16.19 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.72 | 8.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.56 | 24.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 145.69 | 29.66 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 121.09 | 27.99 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 84.48 | 27.37 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 52.55 | 23.06 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 52.66 | 17.31 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 52.08 | 13.52 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 55.53 | 10.57 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 59.40 | 11.69 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 81.79 | 10.81 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 119.51 | 17.16 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 145.57 | 19.87 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 153.58 | 23.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 93.55 | 19.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 52.08 | 10.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 153.58 | 29.66 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 122.04 | 24.70 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.45 | 23.30 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.82 | 22.78 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.11 | 19.18 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.24 | 14.40 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.75 | 11.22 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.66 | 8.77 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.90 | 9.73 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.59 | 8.99 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.17 | 14.32 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.95 | 16.53 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.63 | 19.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.44 | 16.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.75 | 8.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.63 | 24.70 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 122.04 | 24.70 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.45 | 23.30 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.82 | 22.78 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 44.11 | 19.18 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 44.24 | 14.40 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.75 | 11.22 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.66 | 8.77 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.90 | 9.73 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.59 | 8.99 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 100.17 | 14.32 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.95 | 16.53 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.63 | 19.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.44 | 16.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.75 | 8.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.63 | 24.70 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 145.79 | 29.43 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 121.19 | 27.74 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 84.56 | 27.13 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 52.62 | 22.85 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 52.70 | 17.17 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 52.12 | 13.40 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 55.54 | 10.49 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 59.39 | 11.63 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 81.78 | 10.75 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 119.52 | 17.08 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 145.63 | 19.73 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 153.66 | 22.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 93.60 | 19.15 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 52.12 | 10.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 153.66 | 29.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 121.92 | 24.17 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.38 | 22.72 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.66 | 22.19 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.84 | 18.68 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 43.77 | 14.22 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.26 | 11.12 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.06 | 8.86 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.21 | 9.92 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.05 | 9.21 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 99.62 | 14.48 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.64 | 16.39 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.42 | 18.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.06 | 15.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.26 | 8.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.42 | 24.17 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.28 | 47.90 | 28.38 | 121.92 | 24.17 | 0.00 | 0.00 | 744.00 |
February | 64.61 | 34.44 | 30.17 | 101.38 | 22.72 | 0.00 | 0.00 | 672.00 |
March | 46.88 | 16.06 | 30.82 | 70.66 | 22.19 | 0.00 | 0.00 | 744.00 |
April | 30.31 | 2.92 | 27.39 | 43.84 | 18.68 | 0.00 | 0.00 | 720.00 |
May | 25.66 | 0.07 | 25.59 | 43.77 | 14.22 | 0.00 | 0.00 | 744.00 |
June | 25.38 | 0.00 | 25.38 | 43.26 | 11.12 | 0.00 | 0.00 | 720.00 |
July | 24.61 | 0.07 | 24.54 | 46.06 | 8.86 | 0.00 | 0.00 | 744.00 |
August | 26.92 | 1.65 | 25.27 | 49.21 | 9.92 | 0.00 | 0.00 | 744.00 |
September | 40.68 | 9.87 | 30.81 | 68.05 | 9.21 | 0.00 | 0.00 | 720.00 |
October | 57.68 | 27.85 | 29.82 | 99.62 | 14.48 | 0.00 | 0.00 | 744.00 |
November | 72.83 | 41.75 | 31.08 | 121.64 | 16.39 | 0.00 | 0.00 | 720.00 |
December | 78.81 | 50.78 | 28.03 | 128.42 | 18.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 19.39 | 28.08 | 78.06 | 15.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.61 | 0.00 | 24.54 | 43.26 | 8.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 78.81 | 50.78 | 31.08 | 128.42 | 24.17 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.34 | 57.36 | 33.98 | 145.64 | 28.80 | 0.00 | 0.00 | 744.00 |
February | 77.37 | 41.24 | 36.13 | 121.10 | 27.06 | 0.00 | 0.00 | 672.00 |
March | 56.13 | 19.23 | 36.90 | 84.36 | 26.43 | 0.00 | 0.00 | 744.00 |
April | 36.29 | 3.50 | 32.80 | 52.29 | 22.27 | 0.00 | 0.00 | 720.00 |
May | 30.72 | 0.08 | 30.64 | 52.13 | 16.96 | 0.00 | 0.00 | 744.00 |
June | 30.39 | 0.00 | 30.39 | 51.52 | 13.29 | 0.00 | 0.00 | 720.00 |
July | 29.46 | 0.08 | 29.38 | 54.81 | 10.59 | 0.00 | 0.00 | 744.00 |
August | 32.23 | 1.98 | 30.25 | 58.56 | 11.86 | 0.00 | 0.00 | 744.00 |
September | 48.71 | 11.82 | 36.89 | 81.13 | 11.01 | 0.00 | 0.00 | 720.00 |
October | 69.06 | 33.35 | 35.71 | 118.84 | 17.28 | 0.00 | 0.00 | 744.00 |
November | 87.20 | 49.99 | 37.21 | 145.25 | 19.57 | 0.00 | 0.00 | 720.00 |
December | 94.36 | 60.80 | 33.56 | 153.39 | 22.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.84 | 23.21 | 33.63 | 93.14 | 18.94 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.46 | 0.00 | 29.38 | 51.52 | 10.59 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 94.36 | 60.80 | 37.21 | 153.39 | 28.80 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326845E+09 | 65288040.04 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245244E+09 | 55829064.91 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189342E+09 | 60765403.78 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.113820E+09 | 49248735.03 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118360E+09 | 36988599.11 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113201E+09 | 27645598.88 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.125588E+09 | 20996949.48 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.133487E+09 | 24127656.09 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.178711E+09 | 21116561.14 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.268965E+09 | 35644724.63 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.316238E+09 | 41139095.31 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344624E+09 | 50098782.64 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247442E+10 | 0.488889E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113201E+09 | 20996949.48 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344624E+09 | 65288040.04 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326845E+09 | 65288040.04 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245244E+09 | 55829064.91 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189342E+09 | 60765403.78 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.113820E+09 | 49248735.03 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118360E+09 | 36988599.11 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113201E+09 | 27645598.88 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.125588E+09 | 20996949.48 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.133487E+09 | 24127656.09 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.178711E+09 | 21116561.14 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.268965E+09 | 35644724.63 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.316238E+09 | 41139095.31 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344624E+09 | 50098782.64 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247442E+10 | 0.488889E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113201E+09 | 20996949.48 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344624E+09 | 65288040.04 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326845E+09 | 65288040.04 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245244E+09 | 55829064.91 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189342E+09 | 60765403.78 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.113820E+09 | 49248735.03 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118360E+09 | 36988599.11 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113201E+09 | 27645598.88 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.125588E+09 | 20996949.48 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.133487E+09 | 24127656.09 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.178711E+09 | 21116561.14 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.268965E+09 | 35644724.63 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.316238E+09 | 41139095.31 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344624E+09 | 50098782.64 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247442E+10 | 0.488889E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113201E+09 | 20996949.48 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344624E+09 | 65288040.04 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326845E+09 | 65288040.04 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245244E+09 | 55829064.91 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189342E+09 | 60765403.78 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.113820E+09 | 49248735.03 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118360E+09 | 36988599.11 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113201E+09 | 27645598.88 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.125588E+09 | 20996949.48 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.133487E+09 | 24127656.09 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.178711E+09 | 21116561.14 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.268965E+09 | 35644724.63 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.316238E+09 | 41139095.31 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344624E+09 | 50098782.64 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247442E+10 | 0.488889E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113201E+09 | 20996949.48 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344624E+09 | 65288040.04 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245987E+09 | 0.154472E+09 | 91515107.98 | 0.392506E+09 | 78342929.39 |
February | 0.188197E+09 | 0.100323E+09 | 87874414.35 | 0.294494E+09 | 66958198.40 |
March | 0.151158E+09 | 51789298.46 | 99368896.28 | 0.227230E+09 | 72869108.40 |
April | 94588372.98 | 9109605.43 | 85478767.55 | 0.136462E+09 | 59126300.02 |
May | 82733628.79 | 213615.15 | 82520013.64 | 0.141697E+09 | 44463163.84 |
June | 79197287.84 | 0.00 | 79197287.84 | 0.135510E+09 | 33323820.53 |
July | 79352611.83 | 216935.24 | 79135676.59 | 0.150205E+09 | 25365208.95 |
August | 86805029.55 | 5330716.79 | 81474312.76 | 0.159677E+09 | 29124996.50 |
September | 0.126953E+09 | 30810433.11 | 96142796.74 | 0.214120E+09 | 25497478.31 |
October | 0.185985E+09 | 89814394.78 | 96170710.31 | 0.322563E+09 | 42903205.50 |
November | 0.227268E+09 | 0.130278E+09 | 96989683.65 | 0.379613E+09 | 49500758.73 |
December | 0.254120E+09 | 0.163736E+09 | 90383919.63 | 0.413838E+09 | 60212714.29 |
Annual Sum or Average | 0.180234E+10 | 0.736093E+09 | 0.106625E+10 | 0.296791E+10 | 0.587688E+09 |
Minimum of Months | 79197287.84 | 0.00 | 79135676.59 | 0.135510E+09 | 25365208.95 |
Maximum of Months | 0.254120E+09 | 0.163736E+09 | 99368896.28 | 0.413838E+09 | 78342929.39 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245987E+09 | 0.154472E+09 | 91515107.98 | 0.392506E+09 | 78342929.39 |
February | 0.188197E+09 | 0.100323E+09 | 87874414.35 | 0.294494E+09 | 66958198.40 |
March | 0.151158E+09 | 51789298.46 | 99368896.28 | 0.227230E+09 | 72869108.40 |
April | 94588372.98 | 9109605.43 | 85478767.55 | 0.136462E+09 | 59126300.02 |
May | 82733628.79 | 213615.15 | 82520013.64 | 0.141697E+09 | 44463163.84 |
June | 79197287.84 | 0.00 | 79197287.84 | 0.135510E+09 | 33323820.53 |
July | 79352611.83 | 216935.24 | 79135676.59 | 0.150205E+09 | 25365208.95 |
August | 86805029.55 | 5330716.79 | 81474312.76 | 0.159677E+09 | 29124996.50 |
September | 0.126953E+09 | 30810433.11 | 96142796.74 | 0.214120E+09 | 25497478.31 |
October | 0.185985E+09 | 89814394.78 | 96170710.31 | 0.322563E+09 | 42903205.50 |
November | 0.227268E+09 | 0.130278E+09 | 96989683.65 | 0.379613E+09 | 49500758.73 |
December | 0.254120E+09 | 0.163736E+09 | 90383919.63 | 0.413838E+09 | 60212714.29 |
Annual Sum or Average | 0.180234E+10 | 0.736093E+09 | 0.106625E+10 | 0.296791E+10 | 0.587688E+09 |
Minimum of Months | 79197287.84 | 0.00 | 79135676.59 | 0.135510E+09 | 25365208.95 |
Maximum of Months | 0.254120E+09 | 0.163736E+09 | 99368896.28 | 0.413838E+09 | 78342929.39 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326177E+09 | 65727982.45 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.244818E+09 | 56121947.54 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189189E+09 | 61170423.17 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.113831E+09 | 49510217.52 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118645E+09 | 37086944.40 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113620E+09 | 27505808.66 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.126284E+09 | 20729794.06 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.134308E+09 | 23747483.06 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.179446E+09 | 20639297.38 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.269204E+09 | 35476553.41 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.316025E+09 | 41047167.66 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344091E+09 | 50221616.66 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247564E+10 | 0.488985E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113620E+09 | 20639297.38 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344091E+09 | 65727982.45 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326177E+09 | 65727982.45 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.244818E+09 | 56121947.54 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189189E+09 | 61170423.17 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.113831E+09 | 49510217.52 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118645E+09 | 37086944.40 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113620E+09 | 27505808.66 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.126284E+09 | 20729794.06 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.134308E+09 | 23747483.06 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.179446E+09 | 20639297.38 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.269204E+09 | 35476553.41 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.316025E+09 | 41047167.66 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344091E+09 | 50221616.66 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247564E+10 | 0.488985E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113620E+09 | 20639297.38 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344091E+09 | 65727982.45 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245987E+09 | 0.154472E+09 | 91515107.98 | 0.391753E+09 | 78851604.65 |
February | 0.188197E+09 | 0.100323E+09 | 87874414.35 | 0.294022E+09 | 67292359.56 |
March | 0.151158E+09 | 51789298.46 | 99368896.28 | 0.227072E+09 | 73332840.31 |
April | 94588372.98 | 9109605.43 | 85478767.55 | 0.136489E+09 | 59423268.16 |
May | 82733628.79 | 213615.15 | 82520013.64 | 0.142053E+09 | 44567593.82 |
June | 79197287.84 | 0.00 | 79197287.84 | 0.136024E+09 | 33149067.12 |
July | 79352611.83 | 216935.24 | 79135676.59 | 0.151051E+09 | 25038258.50 |
August | 86805029.55 | 5330716.79 | 81474312.76 | 0.160665E+09 | 28661301.66 |
September | 0.126953E+09 | 30810433.11 | 96142796.74 | 0.215021E+09 | 24913977.76 |
October | 0.185985E+09 | 89814394.78 | 96170710.31 | 0.322880E+09 | 42691261.63 |
November | 0.227268E+09 | 0.130278E+09 | 96989683.65 | 0.379401E+09 | 49379469.80 |
December | 0.254120E+09 | 0.163736E+09 | 90383919.63 | 0.413250E+09 | 60344603.44 |
Annual Sum or Average | 0.180234E+10 | 0.736093E+09 | 0.106625E+10 | 0.296968E+10 | 0.587646E+09 |
Minimum of Months | 79197287.84 | 0.00 | 79135676.59 | 0.136024E+09 | 24913977.76 |
Maximum of Months | 0.254120E+09 | 0.163736E+09 | 99368896.28 | 0.413250E+09 | 78851604.65 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326505E+09 | 70678015.20 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.244920E+09 | 60694936.64 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.188996E+09 | 66035936.47 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.113771E+09 | 54331418.22 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118262E+09 | 42828349.58 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113250E+09 | 33270112.59 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.125107E+09 | 27398662.23 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.133775E+09 | 30385627.02 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.178063E+09 | 27292868.29 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.268562E+09 | 42477188.49 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.316160E+09 | 46948620.35 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344367E+09 | 55949430.11 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247174E+10 | 0.558291E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113250E+09 | 27292868.29 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344367E+09 | 70678015.20 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326505E+09 | 70678015.20 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.244920E+09 | 60694936.64 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.188996E+09 | 66035936.47 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.113771E+09 | 54331418.22 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118262E+09 | 42828349.58 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113250E+09 | 33270112.59 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.125107E+09 | 27398662.23 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.133775E+09 | 30385627.02 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.178063E+09 | 27292868.29 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.268562E+09 | 42477188.49 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.316160E+09 | 46948620.35 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344367E+09 | 55949430.11 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247174E+10 | 0.558291E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113250E+09 | 27292868.29 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344367E+09 | 70678015.20 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.389985E+09 | 84169082.19 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.292526E+09 | 72238356.83 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.225600E+09 | 78588607.06 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.135669E+09 | 64709876.05 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.140818E+09 | 51021234.60 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.134838E+09 | 39693110.80 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.148847E+09 | 32701004.17 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.159154E+09 | 36258760.15 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.212234E+09 | 32569431.87 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.320354E+09 | 50641197.25 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.377468E+09 | 55984961.26 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.411300E+09 | 66679002.66 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.294879E+10 | 0.665255E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.134838E+09 | 32569431.87 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.411300E+09 | 84169082.19 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326528E+09 | 70651882.22 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.244935E+09 | 60710933.44 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189006E+09 | 66091110.79 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.113787E+09 | 54364041.92 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118209E+09 | 43097155.94 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113185E+09 | 33573332.67 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.124976E+09 | 27903202.57 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.133674E+09 | 30858690.68 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.177928E+09 | 27868051.96 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.268451E+09 | 42983481.22 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.316109E+09 | 47185587.84 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344349E+09 | 56065011.07 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247114E+10 | 0.561352E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113185E+09 | 27868051.96 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344349E+09 | 70651882.22 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326528E+09 | 70651882.22 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.244935E+09 | 60710933.44 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189006E+09 | 66091110.79 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.113787E+09 | 54364041.92 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118209E+09 | 43097155.94 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113185E+09 | 33573332.67 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.124976E+09 | 27903202.57 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.133674E+09 | 30858690.68 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.177928E+09 | 27868051.96 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.268451E+09 | 42983481.22 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.316109E+09 | 47185587.84 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344349E+09 | 56065011.07 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247114E+10 | 0.561352E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113185E+09 | 27868051.96 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344349E+09 | 70651882.22 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.390012E+09 | 84138078.68 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.292544E+09 | 72256752.24 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.225613E+09 | 78654842.50 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.135688E+09 | 64746688.45 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.140754E+09 | 51341223.78 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.134760E+09 | 40054100.73 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.148689E+09 | 33299718.56 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.159031E+09 | 36820268.35 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.212071E+09 | 33252777.87 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.320221E+09 | 51242444.76 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.377406E+09 | 56266857.56 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.411277E+09 | 66815480.70 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.294807E+10 | 0.668889E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.134760E+09 | 33252777.87 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.411277E+09 | 84138078.68 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326756E+09 | 69955592.10 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245145E+09 | 60035956.35 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189227E+09 | 65294461.98 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114014E+09 | 53626364.27 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118429E+09 | 42413441.61 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113397E+09 | 32920611.89 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.125163E+09 | 27268401.08 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.133863E+09 | 30159777.85 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.178075E+09 | 27219794.17 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.268620E+09 | 42299925.85 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.316307E+09 | 46552999.42 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344568E+09 | 55378896.10 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247356E+10 | 0.553126E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113397E+09 | 27219794.17 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344568E+09 | 69955592.10 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326756E+09 | 69955592.10 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245145E+09 | 60035956.35 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189227E+09 | 65294461.98 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114014E+09 | 53626364.27 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118429E+09 | 42413441.61 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113397E+09 | 32920611.89 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.125163E+09 | 27268401.08 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.133863E+09 | 30159777.85 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.178075E+09 | 27219794.17 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.268620E+09 | 42299925.85 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.316307E+09 | 46552999.42 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344568E+09 | 55378896.10 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247356E+10 | 0.553126E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113397E+09 | 27219794.17 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344568E+09 | 69955592.10 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.390286E+09 | 83317798.26 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.292799E+09 | 71461799.34 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.225880E+09 | 77716248.91 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.135963E+09 | 63876203.06 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.141019E+09 | 50534699.69 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.135015E+09 | 39284036.75 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.148915E+09 | 32552895.16 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.159259E+09 | 35996894.30 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.212249E+09 | 32490090.25 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.320424E+09 | 50437406.26 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.377644E+09 | 55521848.33 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.411540E+09 | 66007098.65 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.295099E+10 | 0.659197E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.135015E+09 | 32490090.25 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.411540E+09 | 83317798.26 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326662E+09 | 67864504.21 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245155E+09 | 57999861.62 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189238E+09 | 62858411.12 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.113705E+09 | 51388080.39 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.117694E+09 | 40161644.13 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.112603E+09 | 30645555.16 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.124083E+09 | 25058883.91 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.132796E+09 | 27612787.61 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.177148E+09 | 24878475.87 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.267878E+09 | 39937946.70 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.315815E+09 | 44489191.17 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344355E+09 | 53281192.52 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.246713E+10 | 0.526177E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.112603E+09 | 24878475.87 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344355E+09 | 67864504.21 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326662E+09 | 67864504.21 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245155E+09 | 57999861.62 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189238E+09 | 62858411.12 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.113705E+09 | 51388080.39 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.117694E+09 | 40161644.13 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.112603E+09 | 30645555.16 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.124083E+09 | 25058883.91 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.132796E+09 | 27612787.61 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.177148E+09 | 24878475.87 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.267878E+09 | 39937946.70 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.315815E+09 | 44489191.17 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344355E+09 | 53281192.52 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.246713E+10 | 0.526177E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.112603E+09 | 24878475.87 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344355E+09 | 67864504.21 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326662E+09 | 67864504.21 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245155E+09 | 57999861.62 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189238E+09 | 62858411.12 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.113705E+09 | 51388080.39 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.117694E+09 | 40161644.13 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.112603E+09 | 30645555.16 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.124083E+09 | 25058883.91 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.132796E+09 | 27612787.61 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.177148E+09 | 24878475.87 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.267878E+09 | 39937946.70 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.315815E+09 | 44489191.17 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344355E+09 | 53281192.52 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.246713E+10 | 0.526177E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.112603E+09 | 24878475.87 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344355E+09 | 67864504.21 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326662E+09 | 67864504.21 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245155E+09 | 57999861.62 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189238E+09 | 62858411.12 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.113705E+09 | 51388080.39 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.117694E+09 | 40161644.13 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.112603E+09 | 30645555.16 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.124083E+09 | 25058883.91 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.132796E+09 | 27612787.61 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.177148E+09 | 24878475.87 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.267878E+09 | 39937946.70 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.315815E+09 | 44489191.17 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344355E+09 | 53281192.52 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.246713E+10 | 0.526177E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.112603E+09 | 24878475.87 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344355E+09 | 67864504.21 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.390185E+09 | 80846702.98 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.292825E+09 | 69056407.50 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.225915E+09 | 74840245.84 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.135629E+09 | 61231846.79 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.140189E+09 | 47877006.83 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.134116E+09 | 36594472.59 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.147683E+09 | 29940872.05 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.158049E+09 | 32988379.95 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.211188E+09 | 29722618.33 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.319574E+09 | 47644952.68 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.377083E+09 | 53081759.37 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.411296E+09 | 63527495.76 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.294373E+10 | 0.627353E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.134116E+09 | 29722618.33 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.411296E+09 | 80846702.98 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.390185E+09 | 80846702.98 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.292825E+09 | 69056407.50 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.225915E+09 | 74840245.84 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.135629E+09 | 61231846.79 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.140189E+09 | 47877006.83 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.134116E+09 | 36594472.59 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.147683E+09 | 29940872.05 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.158049E+09 | 32988379.95 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.211188E+09 | 29722618.33 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.319574E+09 | 47644952.68 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.377083E+09 | 53081759.37 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.411296E+09 | 63527495.76 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.294373E+10 | 0.627353E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.134116E+09 | 29722618.33 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.411296E+09 | 80846702.98 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326458E+09 | 67013014.41 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245040E+09 | 57182668.91 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189344E+09 | 61926174.74 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114005E+09 | 50490706.90 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118206E+09 | 39181170.10 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113147E+09 | 29598461.28 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.124768E+09 | 23948050.27 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.133502E+09 | 26454433.72 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.177644E+09 | 23719812.52 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.268134E+09 | 38802088.42 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.315801E+09 | 43451444.33 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344163E+09 | 52269417.39 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247021E+10 | 0.514037E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113147E+09 | 23719812.52 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344163E+09 | 67013014.41 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326458E+09 | 67013014.41 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245040E+09 | 57182668.91 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189344E+09 | 61926174.74 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114005E+09 | 50490706.90 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118206E+09 | 39181170.10 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113147E+09 | 29598461.28 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.124768E+09 | 23948050.27 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.133502E+09 | 26454433.72 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.177644E+09 | 23719812.52 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.268134E+09 | 38802088.42 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.315801E+09 | 43451444.33 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344163E+09 | 52269417.39 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247021E+10 | 0.514037E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113147E+09 | 23719812.52 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344163E+09 | 67013014.41 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.389993E+09 | 79828508.00 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.292729E+09 | 68079181.81 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.226071E+09 | 73724875.13 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.136006E+09 | 60160091.96 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.140816E+09 | 46708400.37 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.134780E+09 | 35353784.42 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.148513E+09 | 28623873.24 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.158896E+09 | 31614024.84 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.211799E+09 | 28346412.84 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.319912E+09 | 46293834.86 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.377110E+09 | 51844620.61 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.411122E+09 | 62320219.81 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.294775E+10 | 0.612898E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.134780E+09 | 28346412.84 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.411122E+09 | 79828508.00 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326644E+09 | 66678482.03 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245214E+09 | 56866885.20 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189520E+09 | 61577024.70 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114181E+09 | 50174950.32 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118398E+09 | 38889770.78 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113332E+09 | 29328053.02 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.124956E+09 | 23678049.92 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.133675E+09 | 26189140.67 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.177806E+09 | 23446888.96 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.268294E+09 | 38515208.95 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.315976E+09 | 43153853.27 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344348E+09 | 51943539.11 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247234E+10 | 0.510442E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113332E+09 | 23446888.96 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344348E+09 | 66678482.03 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326644E+09 | 66678482.03 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245214E+09 | 56866885.20 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189520E+09 | 61577024.70 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114181E+09 | 50174950.32 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118398E+09 | 38889770.78 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113332E+09 | 29328053.02 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.124956E+09 | 23678049.92 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.133675E+09 | 26189140.67 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.177806E+09 | 23446888.96 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.268294E+09 | 38515208.95 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.315976E+09 | 43153853.27 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344348E+09 | 51943539.11 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247234E+10 | 0.510442E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113332E+09 | 23446888.96 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344348E+09 | 66678482.03 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.390218E+09 | 79430802.19 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.292939E+09 | 67704055.94 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.226284E+09 | 73309683.25 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.136219E+09 | 59784433.89 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.141047E+09 | 46361059.11 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.135003E+09 | 35031775.11 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.148739E+09 | 28302808.38 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.159105E+09 | 31298407.56 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.211995E+09 | 28021613.64 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.320104E+09 | 45952167.42 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.377320E+09 | 51490844.44 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.411345E+09 | 61933000.94 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.295032E+10 | 0.608621E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.135003E+09 | 28021613.64 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.411345E+09 | 79430802.19 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326874E+09 | 66156631.48 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245420E+09 | 56358086.79 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189692E+09 | 61022358.70 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114336E+09 | 49703392.85 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118491E+09 | 38574491.35 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113403E+09 | 29071774.27 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.124967E+09 | 23499740.71 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.133648E+09 | 26058576.70 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.177792E+09 | 23308469.77 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.268301E+09 | 38342741.77 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.316098E+09 | 42849897.05 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344522E+09 | 51533337.98 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247354E+10 | 0.506479E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113403E+09 | 23308469.77 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344522E+09 | 66156631.48 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326874E+09 | 66156631.48 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245420E+09 | 56358086.79 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189692E+09 | 61022358.70 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.114336E+09 | 49703392.85 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.118491E+09 | 38574491.35 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.113403E+09 | 29071774.27 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.124967E+09 | 23499740.71 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.133648E+09 | 26058576.70 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.177792E+09 | 23308469.77 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.268301E+09 | 38342741.77 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.316098E+09 | 42849897.05 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.344522E+09 | 51533337.98 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.247354E+10 | 0.506479E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.113403E+09 | 23308469.77 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.344522E+09 | 66156631.48 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.390491E+09 | 78817217.04 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.293187E+09 | 67106361.04 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.226491E+09 | 72657408.94 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.136403E+09 | 59229980.76 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.141157E+09 | 45993912.74 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.135086E+09 | 34733319.75 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.148751E+09 | 28098072.92 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.159070E+09 | 31149483.74 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.211977E+09 | 27865353.87 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.320111E+09 | 45755040.90 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.377465E+09 | 51134702.70 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.411550E+09 | 61451119.51 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.295174E+10 | 0.603992E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.135086E+09 | 27865353.87 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.411550E+09 | 78817217.04 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326548E+09 | 64735177.57 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245253E+09 | 54958582.40 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189255E+09 | 59429579.85 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.113621E+09 | 48424631.73 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.117228E+09 | 38083291.61 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.112120E+09 | 28830181.17 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.123355E+09 | 23726468.27 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.131815E+09 | 26571819.22 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.176398E+09 | 23871436.94 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.266815E+09 | 38777992.63 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.315294E+09 | 42486588.72 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.343951E+09 | 50714719.05 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.246165E+10 | 0.500610E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.112120E+09 | 23726468.27 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.343951E+09 | 64735177.57 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.204317E+09 | 0.128304E+09 | 76012548.70 | 0.326548E+09 | 64735177.57 |
February | 0.156317E+09 | 83327985.17 | 72988584.60 | 0.245253E+09 | 54958582.40 |
March | 0.125552E+09 | 43016247.90 | 82535913.85 | 0.189255E+09 | 59429579.85 |
April | 78565205.98 | 7566448.23 | 70998757.75 | 0.113621E+09 | 48424631.73 |
May | 68718642.49 | 177428.98 | 68541213.52 | 0.117228E+09 | 38083291.61 |
June | 65781353.84 | 0.00 | 65781353.84 | 0.112120E+09 | 28830181.17 |
July | 65910366.11 | 180186.65 | 65730179.46 | 0.123355E+09 | 23726468.27 |
August | 72100352.41 | 4427699.19 | 67672653.22 | 0.131815E+09 | 26571819.22 |
September | 0.105447E+09 | 25591179.41 | 79856312.04 | 0.176398E+09 | 23871436.94 |
October | 0.154479E+09 | 74599934.46 | 79879497.09 | 0.266815E+09 | 38777992.63 |
November | 0.188769E+09 | 0.108209E+09 | 80559737.24 | 0.315294E+09 | 42486588.72 |
December | 0.211072E+09 | 0.135999E+09 | 75072982.42 | 0.343951E+09 | 50714719.05 |
Annual Sum or Average | 0.149703E+10 | 0.611400E+09 | 0.885630E+09 | 0.246165E+10 | 0.500610E+09 |
Minimum of Months | 65781353.84 | 0.00 | 65730179.46 | 0.112120E+09 | 23726468.27 |
Maximum of Months | 0.211072E+09 | 0.135999E+09 | 82535913.85 | 0.343951E+09 | 64735177.57 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244643E+09 | 0.153628E+09 | 91015025.42 | 0.390084E+09 | 77146844.17 |
February | 0.187169E+09 | 99774298.03 | 87394226.29 | 0.292976E+09 | 65458847.64 |
March | 0.150332E+09 | 51506296.83 | 98825896.85 | 0.225957E+09 | 70784438.30 |
April | 94071496.63 | 9059826.17 | 85011670.46 | 0.135533E+09 | 57727281.34 |
May | 82281532.46 | 212447.85 | 82069084.61 | 0.139625E+09 | 45423150.04 |
June | 78764515.78 | 0.00 | 78764515.78 | 0.133531E+09 | 34456753.65 |
July | 78918991.00 | 215749.80 | 78703241.20 | 0.146797E+09 | 28376573.84 |
August | 86330685.12 | 5301587.19 | 81029097.94 | 0.156852E+09 | 31768756.61 |
September | 0.126259E+09 | 30642070.08 | 95617426.26 | 0.210291E+09 | 28543542.83 |
October | 0.184969E+09 | 89323605.73 | 95645187.31 | 0.318309E+09 | 46282012.94 |
November | 0.226026E+09 | 0.129566E+09 | 96459685.38 | 0.376483E+09 | 50716982.84 |
December | 0.252731E+09 | 0.162841E+09 | 89890018.43 | 0.410851E+09 | 60494759.01 |
Annual Sum or Average | 0.179250E+10 | 0.732071E+09 | 0.106043E+10 | 0.293729E+10 | 0.597180E+09 |
Minimum of Months | 78764515.78 | 0.00 | 78703241.20 | 0.133531E+09 | 28376573.84 |
Maximum of Months | 0.252731E+09 | 0.162841E+09 | 98825896.85 | 0.410851E+09 | 77146844.17 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 781.21 | 156.00 | 488.81 | 306.96 | 181.85 | 0.00 | 0.00 |
February | 648.96 | 147.67 | 414.05 | 220.72 | 193.33 | 0.00 | 0.00 |
March | 452.44 | 145.16 | 300.38 | 102.91 | 197.46 | 0.00 | 0.00 |
April | 280.94 | 121.62 | 194.23 | 18.71 | 175.52 | 0.00 | 0.00 |
May | 282.57 | 88.44 | 164.40 | 0.42 | 163.98 | 0.00 | 0.00 |
June | 279.25 | 68.38 | 162.62 | 0.00 | 162.62 | 0.00 | 0.00 |
July | 299.72 | 50.30 | 157.69 | 0.43 | 157.26 | 0.00 | 0.00 |
August | 318.59 | 57.78 | 172.50 | 10.59 | 161.90 | 0.00 | 0.00 |
September | 441.00 | 52.26 | 260.69 | 63.27 | 197.42 | 0.00 | 0.00 |
October | 642.54 | 85.27 | 369.58 | 178.48 | 191.11 | 0.00 | 0.00 |
November | 780.93 | 101.68 | 466.67 | 267.51 | 199.16 | 0.00 | 0.00 |
December | 823.69 | 119.78 | 504.98 | 325.37 | 179.61 | 0.00 | 0.00 |
Annual Sum or Average | 502.08 | 99.28 | 304.19 | 124.23 | 179.95 | 0.00 | 0.00 |
Minimum of Months | 279.25 | 50.30 | 157.69 | 0.00 | 157.26 | 0.00 | 0.00 |
Maximum of Months | 823.69 | 156.00 | 504.98 | 325.37 | 199.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 389.82 | 78.52 | 244.41 | 153.48 | 90.93 | 0.00 | 0.00 |
February | 323.93 | 74.21 | 207.02 | 110.36 | 96.66 | 0.00 | 0.00 |
March | 226.05 | 73.06 | 150.19 | 51.46 | 98.73 | 0.00 | 0.00 |
April | 140.49 | 61.13 | 97.11 | 9.35 | 87.76 | 0.00 | 0.00 |
May | 141.63 | 44.33 | 82.20 | 0.21 | 81.99 | 0.00 | 0.00 |
June | 140.15 | 34.01 | 81.31 | 0.00 | 81.31 | 0.00 | 0.00 |
July | 150.69 | 24.83 | 78.84 | 0.22 | 78.63 | 0.00 | 0.00 |
August | 160.27 | 28.43 | 86.25 | 5.30 | 80.95 | 0.00 | 0.00 |
September | 221.42 | 25.54 | 130.34 | 31.63 | 98.71 | 0.00 | 0.00 |
October | 321.57 | 42.43 | 184.79 | 89.24 | 95.55 | 0.00 | 0.00 |
November | 390.22 | 50.72 | 233.34 | 133.76 | 99.58 | 0.00 | 0.00 |
December | 411.23 | 60.03 | 252.49 | 162.68 | 89.80 | 0.00 | 0.00 |
Annual Sum or Average | 251.17 | 49.65 | 152.09 | 62.12 | 89.98 | 0.00 | 0.00 |
Minimum of Months | 140.15 | 24.83 | 78.84 | 0.00 | 78.63 | 0.00 | 0.00 |
Maximum of Months | 411.23 | 78.52 | 252.49 | 162.68 | 99.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 389.41 | 84.20 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 323.40 | 80.04 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 225.36 | 78.65 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 140.13 | 66.89 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 140.88 | 51.03 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 139.41 | 40.99 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 148.99 | 32.67 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 159.31 | 36.23 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 219.27 | 33.62 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 320.15 | 50.63 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 389.58 | 57.82 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 410.71 | 66.67 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 250.26 | 56.50 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 139.41 | 32.67 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 410.71 | 84.20 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 389.44 | 84.17 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 323.42 | 80.06 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 225.37 | 78.72 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 140.15 | 66.93 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 140.82 | 51.35 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 139.32 | 41.36 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 148.84 | 33.27 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 159.19 | 36.79 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 219.11 | 34.33 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 320.01 | 51.23 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 389.52 | 58.12 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 410.68 | 66.81 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 250.20 | 56.81 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 139.32 | 33.27 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 410.68 | 84.17 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 389.71 | 83.34 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 323.70 | 79.17 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 225.63 | 77.77 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 140.43 | 66.02 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 141.08 | 50.54 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 139.59 | 40.56 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 149.06 | 32.52 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 159.42 | 35.96 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 219.29 | 33.54 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 320.21 | 50.42 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 389.76 | 57.34 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 410.95 | 66.00 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 250.45 | 55.98 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 139.59 | 32.52 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 410.95 | 83.34 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 779.20 | 161.72 | 487.81 | 306.33 | 181.48 | 0.00 | 0.00 |
February | 647.43 | 152.99 | 413.20 | 220.26 | 192.93 | 0.00 | 0.00 |
March | 451.31 | 149.76 | 299.76 | 102.70 | 197.06 | 0.00 | 0.00 |
April | 280.12 | 126.55 | 193.83 | 18.67 | 175.16 | 0.00 | 0.00 |
May | 280.45 | 95.73 | 164.07 | 0.42 | 163.64 | 0.00 | 0.00 |
June | 277.25 | 75.53 | 162.29 | 0.00 | 162.29 | 0.00 | 0.00 |
July | 295.59 | 59.78 | 157.36 | 0.43 | 156.93 | 0.00 | 0.00 |
August | 316.34 | 65.87 | 172.14 | 10.57 | 161.57 | 0.00 | 0.00 |
September | 436.33 | 61.33 | 260.15 | 63.14 | 197.01 | 0.00 | 0.00 |
October | 638.69 | 95.22 | 368.82 | 178.11 | 190.71 | 0.00 | 0.00 |
November | 778.33 | 109.61 | 465.71 | 266.96 | 198.75 | 0.00 | 0.00 |
December | 821.39 | 127.01 | 503.94 | 324.70 | 179.24 | 0.00 | 0.00 |
Annual Sum or Average | 499.62 | 106.53 | 303.56 | 123.98 | 179.58 | 0.00 | 0.00 |
Minimum of Months | 277.25 | 59.78 | 157.36 | 0.00 | 156.93 | 0.00 | 0.00 |
Maximum of Months | 821.39 | 161.72 | 503.94 | 324.70 | 198.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 389.38 | 79.84 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 323.58 | 75.42 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 225.79 | 73.77 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 140.44 | 62.17 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 140.84 | 46.70 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 139.30 | 36.48 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 148.61 | 28.57 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 159.01 | 31.56 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 218.78 | 29.24 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 319.66 | 46.26 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 389.16 | 53.53 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 410.49 | 62.30 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 250.13 | 52.03 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 139.30 | 28.57 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 410.49 | 79.84 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 389.60 | 79.45 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 323.81 | 75.00 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 226.00 | 73.35 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 140.66 | 61.78 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 141.07 | 46.35 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 139.53 | 36.14 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 148.84 | 28.25 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 159.22 | 31.24 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 218.98 | 28.90 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 319.85 | 45.92 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 389.38 | 53.16 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 410.71 | 61.91 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 250.35 | 51.67 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 139.53 | 28.25 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 410.71 | 79.45 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 389.87 | 78.83 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 324.09 | 74.33 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 226.21 | 72.69 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 140.85 | 61.20 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 141.18 | 45.98 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 139.62 | 35.83 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 148.85 | 28.04 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 159.19 | 31.09 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 218.97 | 28.74 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 319.86 | 45.71 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 389.53 | 52.79 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 410.91 | 61.42 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 250.47 | 51.27 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 139.62 | 28.04 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 410.91 | 78.83 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 389.48 | 77.14 | 243.91 | 153.16 | 90.74 | 0.00 | 0.00 |
February | 323.86 | 72.49 | 206.60 | 110.13 | 96.47 | 0.00 | 0.00 |
March | 225.68 | 70.80 | 149.88 | 51.35 | 98.53 | 0.00 | 0.00 |
April | 139.96 | 59.64 | 96.91 | 9.33 | 87.58 | 0.00 | 0.00 |
May | 139.67 | 45.40 | 82.03 | 0.21 | 81.82 | 0.00 | 0.00 |
June | 138.03 | 35.54 | 81.14 | 0.00 | 81.14 | 0.00 | 0.00 |
July | 146.92 | 28.31 | 78.68 | 0.22 | 78.47 | 0.00 | 0.00 |
August | 156.99 | 31.70 | 86.07 | 5.29 | 80.78 | 0.00 | 0.00 |
September | 217.24 | 29.43 | 130.08 | 31.57 | 98.51 | 0.00 | 0.00 |
October | 318.08 | 46.24 | 184.41 | 89.05 | 95.36 | 0.00 | 0.00 |
November | 388.53 | 52.35 | 232.86 | 133.48 | 99.37 | 0.00 | 0.00 |
December | 410.23 | 60.46 | 251.97 | 162.35 | 89.62 | 0.00 | 0.00 |
Annual Sum or Average | 249.26 | 50.68 | 151.78 | 61.99 | 89.79 | 0.00 | 0.00 |
Minimum of Months | 138.03 | 28.31 | 78.68 | 0.00 | 78.47 | 0.00 | 0.00 |
Maximum of Months | 410.23 | 77.14 | 251.97 | 162.35 | 99.37 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.209239E+10 | 0.417838E+09 | 0.130924E+10 | 0.822161E+09 | 0.487080E+09 | 0.00 | 0.00 |
February | 0.156996E+10 | 0.357233E+09 | 0.100166E+10 | 0.533957E+09 | 0.467703E+09 | 0.00 | 0.00 |
March | 0.121183E+10 | 0.388800E+09 | 0.804525E+09 | 0.275644E+09 | 0.528881E+09 | 0.00 | 0.00 |
April | 0.728201E+09 | 0.315247E+09 | 0.503438E+09 | 48485003.77 | 0.454953E+09 | 0.00 | 0.00 |
May | 0.756832E+09 | 0.236880E+09 | 0.440342E+09 | 1136946.20 | 0.439205E+09 | 0.00 | 0.00 |
June | 0.723822E+09 | 0.177229E+09 | 0.421520E+09 | 0.00 | 0.421520E+09 | 0.00 | 0.00 |
July | 0.802760E+09 | 0.134717E+09 | 0.422347E+09 | 1154617.08 | 0.421192E+09 | 0.00 | 0.00 |
August | 0.853302E+09 | 0.154760E+09 | 0.462011E+09 | 28372230.32 | 0.433639E+09 | 0.00 | 0.00 |
September | 0.114308E+10 | 0.135458E+09 | 0.675696E+09 | 0.163986E+09 | 0.511711E+09 | 0.00 | 0.00 |
October | 0.172099E+10 | 0.228385E+09 | 0.989888E+09 | 0.478029E+09 | 0.511859E+09 | 0.00 | 0.00 |
November | 0.202418E+10 | 0.263558E+09 | 0.120961E+10 | 0.693393E+09 | 0.516218E+09 | 0.00 | 0.00 |
December | 0.220617E+10 | 0.320820E+09 | 0.135253E+10 | 0.871468E+09 | 0.481060E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.158335E+11 | 0.313093E+10 | 0.959281E+10 | 0.391779E+10 | 0.567502E+10 | 0.00 | 0.00 |
Minimum of Months | 0.723822E+09 | 0.134717E+09 | 0.421520E+09 | 0.00 | 0.421192E+09 | 0.00 | 0.00 |
Maximum of Months | 0.220617E+10 | 0.417838E+09 | 0.135253E+10 | 0.871468E+09 | 0.528881E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104411E+10 | 0.210308E+09 | 0.654621E+09 | 0.411081E+09 | 0.243540E+09 | 0.00 | 0.00 |
February | 0.783658E+09 | 0.179536E+09 | 0.500830E+09 | 0.266978E+09 | 0.233852E+09 | 0.00 | 0.00 |
March | 0.605450E+09 | 0.195674E+09 | 0.402263E+09 | 0.137822E+09 | 0.264441E+09 | 0.00 | 0.00 |
April | 0.364151E+09 | 0.158444E+09 | 0.251719E+09 | 24242501.89 | 0.227476E+09 | 0.00 | 0.00 |
May | 0.379343E+09 | 0.118741E+09 | 0.220171E+09 | 568473.10 | 0.219602E+09 | 0.00 | 0.00 |
June | 0.363264E+09 | 88160620.32 | 0.210760E+09 | 0.00 | 0.210760E+09 | 0.00 | 0.00 |
July | 0.403619E+09 | 66497695.65 | 0.211173E+09 | 577308.54 | 0.210596E+09 | 0.00 | 0.00 |
August | 0.429280E+09 | 76155945.13 | 0.231006E+09 | 14186115.16 | 0.216820E+09 | 0.00 | 0.00 |
September | 0.573912E+09 | 66192271.60 | 0.337848E+09 | 81992791.92 | 0.255855E+09 | 0.00 | 0.00 |
October | 0.861288E+09 | 0.113644E+09 | 0.494944E+09 | 0.239014E+09 | 0.255930E+09 | 0.00 | 0.00 |
November | 0.101145E+10 | 0.131474E+09 | 0.604806E+09 | 0.346697E+09 | 0.258109E+09 | 0.00 | 0.00 |
December | 0.110143E+10 | 0.160788E+09 | 0.676264E+09 | 0.435734E+09 | 0.240530E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.792096E+10 | 0.156561E+10 | 0.479640E+10 | 0.195889E+10 | 0.283751E+10 | 0.00 | 0.00 |
Minimum of Months | 0.363264E+09 | 66192271.60 | 0.210760E+09 | 0.00 | 0.210596E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110143E+10 | 0.210308E+09 | 0.676264E+09 | 0.435734E+09 | 0.264441E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104299E+10 | 0.225525E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.782365E+09 | 0.193628E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.603592E+09 | 0.210660E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.363211E+09 | 0.173373E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.377342E+09 | 0.136678E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.361338E+09 | 0.106233E+09 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.399060E+09 | 87498214.68 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.426703E+09 | 97029634.46 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.568359E+09 | 87155050.60 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.857477E+09 | 0.135595E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.100979E+10 | 0.149882E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.110003E+10 | 0.178578E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.789226E+10 | 0.178184E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.361338E+09 | 87155050.60 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110003E+10 | 0.225525E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104307E+10 | 0.225442E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.782413E+09 | 0.193679E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.603624E+09 | 0.210837E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.363262E+09 | 0.173475E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.377172E+09 | 0.137535E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.361130E+09 | 0.107201E+09 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.398642E+09 | 89106015.10 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.426378E+09 | 98537272.25 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.567927E+09 | 88988739.68 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.857123E+09 | 0.137209E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.100962E+10 | 0.150638E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.109997E+10 | 0.178945E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.789034E+10 | 0.179159E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.361130E+09 | 88988739.68 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109997E+10 | 0.225442E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104380E+10 | 0.223229E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.783089E+09 | 0.191534E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.604335E+09 | 0.208305E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.363990E+09 | 0.171129E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.377876E+09 | 0.135361E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.361809E+09 | 0.105125E+09 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.399241E+09 | 87089532.36 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.426984E+09 | 96316021.05 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.568399E+09 | 86929559.46 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.857663E+09 | 0.135037E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.101026E+10 | 0.148628E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.110068E+10 | 0.176765E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.789812E+10 | 0.176545E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.361809E+09 | 86929559.46 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110068E+10 | 0.223229E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.208702E+10 | 0.433151E+09 | 0.130655E+10 | 0.820473E+09 | 0.486080E+09 | 0.00 | 0.00 |
February | 0.156627E+10 | 0.370112E+09 | 0.999603E+09 | 0.532861E+09 | 0.466743E+09 | 0.00 | 0.00 |
March | 0.120878E+10 | 0.401114E+09 | 0.802873E+09 | 0.275078E+09 | 0.527795E+09 | 0.00 | 0.00 |
April | 0.726080E+09 | 0.328016E+09 | 0.502404E+09 | 48385445.24 | 0.454018E+09 | 0.00 | 0.00 |
May | 0.751153E+09 | 0.256400E+09 | 0.439438E+09 | 1134611.60 | 0.438303E+09 | 0.00 | 0.00 |
June | 0.718644E+09 | 0.195771E+09 | 0.420654E+09 | 0.00 | 0.420654E+09 | 0.00 | 0.00 |
July | 0.791700E+09 | 0.160117E+09 | 0.421479E+09 | 1152246.21 | 0.420327E+09 | 0.00 | 0.00 |
August | 0.847280E+09 | 0.176428E+09 | 0.461063E+09 | 28313971.12 | 0.432749E+09 | 0.00 | 0.00 |
September | 0.113097E+10 | 0.158958E+09 | 0.674309E+09 | 0.163649E+09 | 0.510660E+09 | 0.00 | 0.00 |
October | 0.171066E+10 | 0.255041E+09 | 0.987855E+09 | 0.477047E+09 | 0.510808E+09 | 0.00 | 0.00 |
November | 0.201742E+10 | 0.284120E+09 | 0.120713E+10 | 0.691970E+09 | 0.515158E+09 | 0.00 | 0.00 |
December | 0.220001E+10 | 0.340180E+09 | 0.134975E+10 | 0.869679E+09 | 0.480072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.157560E+11 | 0.335941E+10 | 0.957311E+10 | 0.390974E+10 | 0.566337E+10 | 0.00 | 0.00 |
Minimum of Months | 0.718644E+09 | 0.158958E+09 | 0.420654E+09 | 0.00 | 0.420327E+09 | 0.00 | 0.00 |
Maximum of Months | 0.220001E+10 | 0.433151E+09 | 0.134975E+10 | 0.869679E+09 | 0.527795E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104291E+10 | 0.213855E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.782808E+09 | 0.182445E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.604758E+09 | 0.197577E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.364017E+09 | 0.161141E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.377227E+09 | 0.125071E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.361074E+09 | 94550666.37 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.398050E+09 | 76519972.00 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.425899E+09 | 84522643.95 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.567087E+09 | 75785899.41 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.856180E+09 | 0.123898E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.100871E+10 | 0.138748E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.109945E+10 | 0.166859E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.788817E+10 | 0.164097E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.361074E+09 | 75785899.41 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109945E+10 | 0.213855E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104351E+10 | 0.212788E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.783366E+09 | 0.181438E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.605323E+09 | 0.196464E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.364581E+09 | 0.160134E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.377842E+09 | 0.124140E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.361667E+09 | 93687665.35 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.398652E+09 | 75658639.12 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.426456E+09 | 83676597.96 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.567607E+09 | 74915205.27 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.856692E+09 | 0.122982E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.100927E+10 | 0.137798E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.110004E+10 | 0.165820E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.789500E+10 | 0.162950E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.361667E+09 | 74915205.27 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110004E+10 | 0.212788E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104424E+10 | 0.211130E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.784027E+09 | 0.179822E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.605875E+09 | 0.194702E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.365075E+09 | 0.158637E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.378140E+09 | 0.123143E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.361892E+09 | 92876667.17 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.398685E+09 | 75097410.66 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.426366E+09 | 83266485.19 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.567562E+09 | 74482197.03 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.856712E+09 | 0.122440E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.100966E+10 | 0.136834E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.110059E+10 | 0.164518E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.789883E+10 | 0.161695E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.361892E+09 | 74482197.03 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110059E+10 | 0.211130E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104318E+10 | 0.206617E+09 | 0.653277E+09 | 0.410236E+09 | 0.243040E+09 | 0.00 | 0.00 |
February | 0.783482E+09 | 0.175376E+09 | 0.499802E+09 | 0.266430E+09 | 0.233371E+09 | 0.00 | 0.00 |
March | 0.604466E+09 | 0.189644E+09 | 0.401437E+09 | 0.137539E+09 | 0.263898E+09 | 0.00 | 0.00 |
April | 0.362776E+09 | 0.154577E+09 | 0.251202E+09 | 24192722.62 | 0.227009E+09 | 0.00 | 0.00 |
May | 0.374081E+09 | 0.121590E+09 | 0.219719E+09 | 567305.80 | 0.219152E+09 | 0.00 | 0.00 |
June | 0.357771E+09 | 92117114.03 | 0.210327E+09 | 0.00 | 0.210327E+09 | 0.00 | 0.00 |
July | 0.393507E+09 | 75829262.90 | 0.210740E+09 | 576123.10 | 0.210164E+09 | 0.00 | 0.00 |
August | 0.420481E+09 | 84912324.39 | 0.230531E+09 | 14156985.56 | 0.216374E+09 | 0.00 | 0.00 |
September | 0.563087E+09 | 76285651.18 | 0.337154E+09 | 81824428.90 | 0.255330E+09 | 0.00 | 0.00 |
October | 0.851939E+09 | 0.123838E+09 | 0.493928E+09 | 0.238523E+09 | 0.255404E+09 | 0.00 | 0.00 |
November | 0.100707E+10 | 0.135690E+09 | 0.603564E+09 | 0.345985E+09 | 0.257579E+09 | 0.00 | 0.00 |
December | 0.109875E+10 | 0.161924E+09 | 0.674875E+09 | 0.434839E+09 | 0.240036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.786059E+10 | 0.159840E+10 | 0.478656E+10 | 0.195487E+10 | 0.283168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.357771E+09 | 75829262.90 | 0.210327E+09 | 0.00 | 0.210164E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109875E+10 | 0.206617E+09 | 0.674875E+09 | 0.434839E+09 | 0.263898E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 22.49 | 18.25 | 15.90 | 4.15 | 13.31 | 59.87 | 181.51 | 0.00 |
February | 22.80 | 19.74 | 18.20 | 3.70 | 14.21 | 74.30 | 182.84 | 0.03 |
March | 23.17 | 18.99 | 16.85 | 4.23 | 14.23 | 89.51 | 186.76 | 0.02 |
April | 23.76 | 19.01 | 16.50 | 4.83 | 14.94 | 95.22 | 199.35 | 0.00 |
May | 25.23 | 20.49 | 18.23 | 4.38 | 17.08 | 98.73 | 213.00 | 0.00 |
June | 25.87 | 20.89 | 18.70 | 5.87 | 17.20 | 99.16 | 227.55 | 0.00 |
July | 26.90 | 21.77 | 19.49 | 5.98 | 18.80 | 89.26 | 241.04 | 0.00 |
August | 27.06 | 21.88 | 19.61 | 5.21 | 18.26 | 83.09 | 253.22 | 0.00 |
September | 26.87 | 22.30 | 20.37 | 5.44 | 18.71 | 93.82 | 214.78 | 0.00 |
October | 26.22 | 21.67 | 19.68 | 3.78 | 17.26 | 74.41 | 199.79 | 0.00 |
November | 24.76 | 20.57 | 18.62 | 5.17 | 16.20 | 67.97 | 175.93 | 0.00 |
December | 23.69 | 19.64 | 17.67 | 4.42 | 14.96 | 56.37 | 177.80 | 0.00 |
Annual Sum or Average | 24.91 | 20.44 | 18.32 | 4.77 | 16.27 | 81.79 | 204.64 | 0.00 |
Minimum of Months | 22.49 | 18.25 | 15.90 | 3.70 | 13.31 | 56.37 | 175.93 | 0.00 |
Maximum of Months | 27.06 | 22.30 | 20.37 | 5.98 | 18.80 | 99.16 | 253.22 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.40 | 03-JAN-12:00 | 22.05 | 18.90 | 3.60 | 19.35 | 145.50 | 575.00 |
February | 28.90 | 19-FEB-10:00 | 22.34 | 19.40 | 3.10 | 18.28 | 204.00 | 595.50 |
March | 30.00 | 29-MAR-12:00 | 20.05 | 15.00 | 6.70 | 20.22 | 350.50 | 543.50 |
April | 30.00 | 09-APR-13:00 | 20.06 | 15.00 | 7.20 | 17.39 | 126.00 | 778.50 |
May | 31.10 | 17-MAY-13:20 | 21.31 | 16.70 | 7.87 | 22.12 | 283.17 | 716.50 |
June | 30.60 | 26-JUN-13:00 | 21.72 | 17.80 | 6.70 | 20.40 | 162.00 | 756.50 |
July | 32.20 | 09-JUL-11:00 | 23.42 | 20.00 | 6.20 | 23.49 | 235.00 | 733.00 |
August | 32.80 | 11-AUG-13:00 | 23.28 | 19.40 | 6.20 | 23.99 | 228.00 | 563.00 |
September | 33.30 | 02-SEP-12:00 | 23.47 | 19.40 | 5.70 | 23.32 | 185.00 | 789.00 |
October | 33.30 | 01-OCT-12:00 | 23.04 | 18.90 | 6.20 | 23.15 | 143.50 | 854.50 |
November | 30.60 | 03-NOV-12:00 | 22.49 | 18.90 | 7.70 | 20.57 | 148.00 | 798.50 |
December | 30.60 | 13-DEC-13:00 | 22.11 | 18.30 | 5.70 | 18.64 | 59.00 | 832.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 20.05 | 15.00 | 3.10 | 17.39 | 59.00 | 543.50 | |
Maximum of Months | 33.30 | 23.47 | 20.00 | 7.87 | 23.99 | 350.50 | 854.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.20 | 07-JAN-06:00 | 15.82 | 15.00 | 1.50 | 3.89 | 0.00 | 0.00 |
February | 13.30 | 12-FEB-06:00 | 12.64 | 12.20 | 3.10 | 0.73 | 0.00 | 0.00 |
March | 15.00 | 08-MAR-03:00 | 13.29 | 12.20 | 0.00 | 1.16 | 0.00 | 0.00 |
April | 17.80 | 22-APR-02:00 | 16.39 | 15.60 | 0.00 | 6.75 | 0.00 | 0.00 |
May | 18.90 | 23-MAY-05:00 | 17.45 | 16.70 | 2.10 | 9.33 | 110.00 | 159.50 |
June | 21.10 | 06-JUN-04:00 | 19.20 | 18.30 | 2.60 | 9.52 | 0.00 | 0.00 |
July | 22.20 | 09-JUL-03:00 | 20.00 | 18.90 | 1.50 | 11.84 | 0.00 | 0.00 |
August | 21.10 | 18-AUG-05:00 | 19.93 | 19.40 | 2.10 | 8.54 | 0.00 | 0.00 |
September | 22.20 | 19-SEP-04:00 | 20.25 | 19.40 | 2.60 | 11.84 | 0.00 | 0.00 |
October | 19.40 | 19-OCT-05:00 | 17.58 | 16.70 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 16.10 | 27-NOV-06:00 | 15.39 | 15.00 | 2.60 | 5.74 | 50.00 | 566.00 |
December | 16.70 | 26-DEC-01:00 | 15.01 | 13.90 | 2.60 | 4.31 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 12.64 | 12.20 | 0.00 | 0.73 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 20.25 | 19.40 | 3.10 | 11.84 | 110.00 | 566.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.03 | 01-JAN-15:00 | 27.80 | 21.10 | 4.10 | 20.92 | 91.00 | 199.00 |
February | 24.57 | 18-FEB-13:00 | 27.80 | 23.30 | 4.10 | 21.44 | 268.00 | 307.00 |
March | 23.81 | 13-MAR-12:00 | 27.80 | 22.20 | 5.70 | 22.47 | 468.50 | 259.00 |
April | 22.82 | 24-APR-11:00 | 28.30 | 20.60 | 4.60 | 19.87 | 357.00 | 446.00 |
May | 23.35 | 08-MAY-15:00 | 28.90 | 21.10 | 6.20 | 22.13 | 182.00 | 323.50 |
June | 23.02 | 20-JUN-13:00 | 28.90 | 20.60 | 7.70 | 21.96 | 370.50 | 346.50 |
July | 24.68 | 20-JUL-13:00 | 26.70 | 23.90 | 8.20 | 25.33 | 309.00 | 14.00 |
August | 25.47 | 19-AUG-14:00 | 31.70 | 23.30 | 5.20 | 25.33 | 229.00 | 409.00 |
September | 25.16 | 23-SEP-14:00 | 27.20 | 24.40 | 4.10 | 23.82 | 288.00 | 450.00 |
October | 24.72 | 15-OCT-13:00 | 31.70 | 22.20 | 5.20 | 22.98 | 151.50 | 527.00 |
November | 23.46 | 02-NOV-09:00 | 29.40 | 21.10 | 6.20 | 20.57 | 236.50 | 546.50 |
December | 23.69 | 03-DEC-10:00 | 26.10 | 22.80 | 6.70 | 24.50 | 251.50 | 3.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.82 | 26.10 | 20.60 | 4.10 | 19.87 | 91.00 | 3.00 | |
Maximum of Months | 25.47 | 31.70 | 24.40 | 8.20 | 25.33 | 468.50 | 546.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 01-JAN-15:00 | 27.80 | 23.03 | 4.10 | 20.92 | 91.00 | 199.00 |
February | 23.30 | 16-FEB-17:00 | 24.40 | 23.65 | 3.10 | 22.98 | 29.50 | 4.00 |
March | 22.20 | 13-MAR-10:00 | 27.20 | 23.57 | 4.60 | 21.78 | 336.00 | 148.00 |
April | 21.10 | 24-APR-23:00 | 22.80 | 21.58 | 1.50 | 18.82 | 0.00 | 0.00 |
May | 22.20 | 09-MAY-23:00 | 24.40 | 22.88 | 1.50 | 22.64 | 0.00 | 0.00 |
June | 20.80 | 09-JUN-00:10 | 22.15 | 21.03 | 3.78 | 18.14 | 0.00 | 0.00 |
July | 23.90 | 20-JUL-13:00 | 26.70 | 24.68 | 8.20 | 25.33 | 309.00 | 14.00 |
August | 23.30 | 19-AUG-14:00 | 31.70 | 25.47 | 5.20 | 25.33 | 229.00 | 409.00 |
September | 24.40 | 23-SEP-14:00 | 27.20 | 25.16 | 4.10 | 23.82 | 288.00 | 450.00 |
October | 22.80 | 24-OCT-12:00 | 26.10 | 23.69 | 4.10 | 19.70 | 259.00 | 474.50 |
November | 21.70 | 29-NOV-17:00 | 26.10 | 22.98 | 3.10 | 22.13 | 0.00 | 0.00 |
December | 22.80 | 03-DEC-10:00 | 26.10 | 23.69 | 6.70 | 24.50 | 251.50 | 3.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.80 | 22.15 | 21.03 | 1.50 | 18.14 | 0.00 | 0.00 | |
Maximum of Months | 24.40 | 31.70 | 25.47 | 8.20 | 25.33 | 336.00 | 474.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 26.59 | 31.34 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 26.78 | 37.09 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 27.35 | 43.34 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 28.17 | 47.38 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.01 | 50.82 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.64 | 52.70 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.90 | 53.08 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.71 | 53.00 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.13 | 48.47 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.31 | 39.62 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.47 | 33.78 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 26.84 | 30.10 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.25 | 43.42 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 26.59 | 30.10 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.90 | 53.08 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.270877E+09 | -159036624.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111840115.3 | 58.99 | 0.00 | 0.00 |
February | 0.244538E+09 | -143588680.3 | 0.00 | 0.00 | 672.00 | 0.00 | -100949423.1 | 58.99 | 0.00 | 0.00 |
March | 0.270457E+09 | -158618661.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111838561.1 | 58.99 | 0.00 | 0.00 |
April | 0.255983E+09 | -147827926.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108154728.1 | 58.99 | 0.00 | 0.00 |
May | 0.260165E+09 | -148723212.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111441346.7 | 58.99 | 0.00 | 0.00 |
June | 0.249879E+09 | -142216595.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107662117.4 | 58.99 | 0.00 | 0.00 |
July | 0.253953E+09 | -142894253.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111058250.3 | 58.99 | 0.00 | 0.00 |
August | 0.257675E+09 | -146659869.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111014690.8 | 58.99 | 0.00 | 0.00 |
September | 0.250695E+09 | -143349368.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107345934.1 | 58.99 | 0.00 | 0.00 |
October | 0.261858E+09 | -150647767.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111210320.1 | 58.99 | 0.00 | 0.00 |
November | 0.257087E+09 | -149368842.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107717798.4 | 58.99 | 0.00 | 0.00 |
December | 0.269592E+09 | -158048458.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111543492.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.310276E+10 | -.179098E+10 | 8760.00 | -.131178E+10 | 58.99 | |||||
Minimum of Months | 0.244538E+09 | -159036624.3 | 0.00 | 0.00 | 672.00 | 0.00 | -111840115.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.270877E+09 | -142216595.6 | 0.00 | 0.00 | 744.00 | 0.00 | -100949423.1 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.270691E+09 | -159044440.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111647008.4 | 58.99 | 0.00 | 0.00 |
February | 0.244392E+09 | -143594589.2 | 0.00 | 0.00 | 672.00 | 0.00 | -100797147.8 | 58.99 | 0.00 | 0.00 |
March | 0.270270E+09 | -158636585.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111633576.3 | 58.99 | 0.00 | 0.00 |
April | 0.255823E+09 | -147845095.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107977514.2 | 58.99 | 0.00 | 0.00 |
May | 0.260040E+09 | -148734788.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111305619.4 | 58.99 | 0.00 | 0.00 |
June | 0.249771E+09 | -142213977.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107557486.4 | 58.99 | 0.00 | 0.00 |
July | 0.253889E+09 | -142900858.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110987759.9 | 58.99 | 0.00 | 0.00 |
August | 0.257614E+09 | -146660490.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110953087.4 | 58.99 | 0.00 | 0.00 |
September | 0.250667E+09 | -143353302.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107314065.8 | 58.99 | 0.00 | 0.00 |
October | 0.261786E+09 | -150659653.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111126386.4 | 58.99 | 0.00 | 0.00 |
November | 0.256980E+09 | -149375947.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107603936.3 | 58.99 | 0.00 | 0.00 |
December | 0.269451E+09 | -158046607.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111404744.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.310137E+10 | -.179107E+10 | 8760.00 | -.131031E+10 | 58.99 | |||||
Minimum of Months | 0.244392E+09 | -159044440.6 | 0.00 | 0.00 | 672.00 | 0.00 | -111647008.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.270691E+09 | -142213977.1 | 0.00 | 0.00 | 744.00 | 0.00 | -100797147.8 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.250196E+09 | -139862155.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110333403.0 | 58.99 | 0.00 | 0.00 |
February | 0.225910E+09 | -126375044.5 | 0.00 | 0.00 | 672.00 | 0.00 | -99535290.0 | 58.99 | 0.00 | 0.00 |
March | 0.251926E+09 | -141672498.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110253153.4 | 58.99 | 0.00 | 0.00 |
April | 0.236506E+09 | -129914142.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106592169.1 | 58.99 | 0.00 | 0.00 |
May | 0.241461E+09 | -131890511.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109570104.1 | 58.99 | 0.00 | 0.00 |
June | 0.232592E+09 | -126763261.7 | 0.00 | 0.00 | 720.00 | 0.00 | -105828584.0 | 58.99 | 0.00 | 0.00 |
July | 0.233666E+09 | -124837743.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108828026.2 | 58.99 | 0.00 | 0.00 |
August | 0.240074E+09 | -131094264.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108979613.1 | 58.99 | 0.00 | 0.00 |
September | 0.231051E+09 | -125901906.9 | 0.00 | 0.00 | 720.00 | 0.00 | -105149273.1 | 58.99 | 0.00 | 0.00 |
October | 0.241519E+09 | -132492000.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109027000.8 | 58.99 | 0.00 | 0.00 |
November | 0.237859E+09 | -131866327.4 | 0.00 | 0.00 | 720.00 | 0.00 | -105993118.6 | 58.99 | 0.00 | 0.00 |
December | 0.247799E+09 | -137961387.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109837670.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.287056E+10 | -.158063E+10 | 8760.00 | -.128993E+10 | 58.99 | |||||
Minimum of Months | 0.225910E+09 | -141672498.9 | 0.00 | 0.00 | 672.00 | 0.00 | -110333403.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.251926E+09 | -124837743.0 | 0.00 | 0.00 | 744.00 | 0.00 | -99535290.0 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.250198E+09 | -139862357.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110335848.9 | 58.99 | 0.00 | 0.00 |
February | 0.225906E+09 | -126375114.1 | 0.00 | 0.00 | 672.00 | 0.00 | -99530949.4 | 58.99 | 0.00 | 0.00 |
March | 0.251916E+09 | -141671531.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110244164.0 | 58.99 | 0.00 | 0.00 |
April | 0.236499E+09 | -129913194.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106586052.7 | 58.99 | 0.00 | 0.00 |
May | 0.241415E+09 | -131889683.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109524966.6 | 58.99 | 0.00 | 0.00 |
June | 0.232538E+09 | -126754140.8 | 0.00 | 0.00 | 720.00 | 0.00 | -105783779.6 | 58.99 | 0.00 | 0.00 |
July | 0.233575E+09 | -124843060.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108731930.3 | 58.99 | 0.00 | 0.00 |
August | 0.239996E+09 | -131092368.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108903868.3 | 58.99 | 0.00 | 0.00 |
September | 0.230950E+09 | -125890737.2 | 0.00 | 0.00 | 720.00 | 0.00 | -105059542.3 | 58.99 | 0.00 | 0.00 |
October | 0.241434E+09 | -132488483.5 | 0.00 | 0.00 | 744.00 | 0.00 | -108945628.1 | 58.99 | 0.00 | 0.00 |
November | 0.237810E+09 | -131880837.6 | 0.00 | 0.00 | 720.00 | 0.00 | -105929509.2 | 58.99 | 0.00 | 0.00 |
December | 0.247784E+09 | -137992837.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109791476.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.287002E+10 | -.158065E+10 | 8760.00 | -.128937E+10 | 58.99 | |||||
Minimum of Months | 0.225906E+09 | -141671531.3 | 0.00 | 0.00 | 672.00 | 0.00 | -110335848.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.251916E+09 | -124843060.0 | 0.00 | 0.00 | 744.00 | 0.00 | -99530949.4 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.242960E+09 | -132178749.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110780985.3 | 58.99 | 0.00 | 0.00 |
February | 0.219458E+09 | -119502803.2 | 0.00 | 0.00 | 672.00 | 0.00 | -99955479.8 | 58.99 | 0.00 | 0.00 |
March | 0.244854E+09 | -134065616.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110788742.0 | 58.99 | 0.00 | 0.00 |
April | 0.230024E+09 | -122911909.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107111933.0 | 59.00 | 0.00 | 0.00 |
May | 0.234747E+09 | -124732009.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110015413.0 | 58.99 | 0.00 | 0.00 |
June | 0.226235E+09 | -119937109.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106298078.6 | 58.99 | 0.00 | 0.00 |
July | 0.227288E+09 | -118070581.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109217130.6 | 58.99 | 0.00 | 0.00 |
August | 0.233519E+09 | -124048827.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109469756.1 | 58.99 | 0.00 | 0.00 |
September | 0.224676E+09 | -119130157.7 | 0.00 | 0.00 | 720.00 | 0.00 | -105545927.0 | 58.99 | 0.00 | 0.00 |
October | 0.234692E+09 | -125239948.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109451838.1 | 58.99 | 0.00 | 0.00 |
November | 0.230921E+09 | -124552841.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106367804.6 | 58.99 | 0.00 | 0.00 |
December | 0.240729E+09 | -130505940.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110222725.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.279010E+10 | -.149488E+10 | 8760.00 | -.129523E+10 | 58.99 | |||||
Minimum of Months | 0.219458E+09 | -134065616.7 | 0.00 | 0.00 | 672.00 | 0.00 | -110788742.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.244854E+09 | -118070581.1 | 0.00 | 0.00 | 744.00 | 0.00 | -99955479.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.243070E+09 | -132176542.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110893212.0 | 59.00 | 0.00 | 0.00 |
February | 0.219568E+09 | -119495948.8 | 0.00 | 0.00 | 672.00 | 0.00 | -100072489.1 | 58.99 | 0.00 | 0.00 |
March | 0.244976E+09 | -134057465.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110918180.4 | 58.99 | 0.00 | 0.00 |
April | 0.230135E+09 | -122943936.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107190718.7 | 58.99 | 0.00 | 0.00 |
May | 0.234892E+09 | -124732115.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110159625.2 | 58.99 | 0.00 | 0.00 |
June | 0.226367E+09 | -119956245.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106411209.6 | 58.99 | 0.00 | 0.00 |
July | 0.227426E+09 | -118070480.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109355266.4 | 58.99 | 0.00 | 0.00 |
August | 0.233671E+09 | -124047034.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109624458.6 | 58.99 | 0.00 | 0.00 |
September | 0.224827E+09 | -119122245.3 | 0.00 | 0.00 | 720.00 | 0.00 | -105704328.1 | 58.99 | 0.00 | 0.00 |
October | 0.234836E+09 | -125240465.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109595346.9 | 58.99 | 0.00 | 0.00 |
November | 0.231053E+09 | -124556018.2 | 0.00 | 0.00 | 720.00 | 0.00 | -106496562.9 | 58.99 | 0.00 | 0.00 |
December | 0.240858E+09 | -130486929.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110370624.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.279168E+10 | -.149489E+10 | 8760.00 | -.129679E+10 | 58.99 | |||||
Minimum of Months | 0.219568E+09 | -134057465.4 | 0.00 | 0.00 | 672.00 | 0.00 | -110918180.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.244976E+09 | -118070480.1 | 0.00 | 0.00 | 744.00 | 0.00 | -100072489.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.243128E+09 | -132175502.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110952095.1 | 59.00 | 0.00 | 0.00 |
February | 0.219627E+09 | -119495191.2 | 0.00 | 0.00 | 672.00 | 0.00 | -100131657.2 | 58.99 | 0.00 | 0.00 |
March | 0.245031E+09 | -134050692.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110979949.0 | 58.99 | 0.00 | 0.00 |
April | 0.230194E+09 | -122951044.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107242840.4 | 58.99 | 0.00 | 0.00 |
May | 0.234941E+09 | -124735187.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110205363.8 | 58.99 | 0.00 | 0.00 |
June | 0.226419E+09 | -119942413.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106476702.2 | 58.99 | 0.00 | 0.00 |
July | 0.227479E+09 | -118073168.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109405973.9 | 58.99 | 0.00 | 0.00 |
August | 0.233710E+09 | -124042355.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109668004.9 | 58.99 | 0.00 | 0.00 |
September | 0.224885E+09 | -119157079.0 | 0.00 | 0.00 | 720.00 | 0.00 | -105727944.1 | 58.98 | 0.00 | 0.00 |
October | 0.234877E+09 | -125200754.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109676106.4 | 59.00 | 0.00 | 0.00 |
November | 0.231103E+09 | -124541080.5 | 0.00 | 0.00 | 720.00 | 0.00 | -106561894.4 | 58.99 | 0.00 | 0.00 |
December | 0.240919E+09 | -130493827.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110425294.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.279231E+10 | -.149486E+10 | 8760.00 | -.129745E+10 | 58.99 | |||||
Minimum of Months | 0.219627E+09 | -134050692.5 | 0.00 | 0.00 | 672.00 | 0.00 | -110979949.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.245031E+09 | -118073168.2 | 0.00 | 0.00 | 744.00 | 0.00 | -100131657.2 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 326.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 285.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 336.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 360.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 384.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 392.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 398.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 382.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 346.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 316.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 318.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4207.17 | ||||||||||
Minimum of Months | 285.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 398.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.278156E+11 | 0.198992E+11 | 50432.44 | 02-JAN-09:01 | 29790.16 | 0.00 |
February | 0.00 | 0.00 | 0.290395E+11 | 0.188732E+11 | 52433.08 | 18-FEB-09:01 | 24472.45 | 0.00 |
March | 0.00 | 0.00 | 0.305030E+11 | 0.213512E+11 | 51220.72 | 03-MAR-09:02 | 25104.47 | 0.00 |
April | 0.00 | 0.00 | 0.291509E+11 | 0.209336E+11 | 50083.62 | 25-APR-08:61 | 30770.61 | 0.00 |
May | 0.00 | 0.00 | 0.361898E+11 | 0.250145E+11 | 51604.90 | 10-MAY-08:61 | 26408.65 | 0.00 |
June | 0.00 | 0.00 | 0.365633E+11 | 0.250817E+11 | 50995.84 | 14-JUN-08:61 | 28562.27 | 0.00 |
July | 0.00 | 0.00 | 0.422282E+11 | 0.284480E+11 | 52201.22 | 20-JUL-08:61 | 25304.35 | 0.00 |
August | 0.00 | 0.00 | 0.428468E+11 | 0.290490E+11 | 51176.84 | 01-AUG-08:61 | 28086.63 | 0.00 |
September | 0.00 | 0.00 | 0.427983E+11 | 0.279368E+11 | 52241.93 | 30-SEP-08:61 | 24541.57 | 0.00 |
October | 0.00 | 0.00 | 0.419910E+11 | 0.280809E+11 | 51036.23 | 13-OCT-08:61 | 28623.20 | 0.00 |
November | 0.00 | 0.00 | 0.356067E+11 | 0.239842E+11 | 51363.90 | 01-NOV-08:61 | 27311.97 | 0.00 |
December | 0.00 | 0.00 | 0.329251E+11 | 0.224133E+11 | 51149.51 | 03-DEC-08:61 | 27632.33 | 0.00 |
Annual Sum or Average | 0.427658E+12 | 0.291066E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.278156E+11 | 0.188732E+11 | 50083.62 | 24472.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.428468E+11 | 0.290490E+11 | 52433.08 | 30770.61 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.143017E+11 | 0.105312E+11 | 26121.69 | 02-JAN-09:01 | 16481.48 | 0.00 |
February | 0.00 | 0.00 | 0.146845E+11 | 0.987437E+10 | 27022.86 | 18-FEB-09:01 | 13994.78 | 0.00 |
March | 0.00 | 0.00 | 0.154600E+11 | 0.111288E+11 | 26512.76 | 03-MAR-09:02 | 14213.94 | 0.00 |
April | 0.00 | 0.00 | 0.146976E+11 | 0.108445E+11 | 25838.87 | 25-APR-08:61 | 17175.52 | 0.00 |
May | 0.00 | 0.00 | 0.180149E+11 | 0.127987E+11 | 26649.95 | 10-MAY-08:61 | 14910.51 | 0.00 |
June | 0.00 | 0.00 | 0.180683E+11 | 0.127133E+11 | 26421.90 | 14-JUN-08:61 | 15706.49 | 0.00 |
July | 0.00 | 0.00 | 0.206874E+11 | 0.143133E+11 | 27033.80 | 20-JUL-08:61 | 14030.74 | 0.00 |
August | 0.00 | 0.00 | 0.210106E+11 | 0.146111E+11 | 26471.83 | 01-AUG-08:61 | 15564.38 | 0.00 |
September | 0.00 | 0.00 | 0.207782E+11 | 0.139414E+11 | 27014.64 | 30-SEP-08:61 | 13862.59 | 0.00 |
October | 0.00 | 0.00 | 0.207166E+11 | 0.142501E+11 | 26393.53 | 13-OCT-08:61 | 15834.91 | 0.00 |
November | 0.00 | 0.00 | 0.177473E+11 | 0.123004E+11 | 26608.28 | 01-NOV-08:61 | 15089.82 | 0.00 |
December | 0.00 | 0.00 | 0.165731E+11 | 0.116355E+11 | 26413.42 | 03-DEC-08:61 | 15488.40 | 0.00 |
Annual Sum or Average | 0.212740E+12 | 0.148943E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.143017E+11 | 0.987437E+10 | 25838.87 | 13862.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.210106E+11 | 0.146111E+11 | 27033.80 | 17175.52 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.112173E+11 | 0.806623E+10 | 26411.90 | 01-JAN-09:01 | 15036.05 | 0.00 |
February | 0.00 | 0.00 | 0.116193E+11 | 0.757988E+10 | 27406.11 | 18-FEB-08:61 | 12333.53 | 0.00 |
March | 0.00 | 0.00 | 0.123343E+11 | 0.866657E+10 | 26671.16 | 13-MAR-07:02 | 13748.87 | 0.00 |
April | 0.00 | 0.00 | 0.115796E+11 | 0.834199E+10 | 26291.73 | 24-APR-07:02 | 14549.09 | 0.00 |
May | 0.00 | 0.00 | 0.146162E+11 | 0.101521E+11 | 26840.61 | 10-MAY-07:01 | 13927.47 | 0.00 |
June | 0.00 | 0.00 | 0.147845E+11 | 0.101425E+11 | 26511.54 | 14-JUN-07:01 | 15023.84 | 0.00 |
July | 0.00 | 0.00 | 0.167343E+11 | 0.113121E+11 | 27075.94 | 21-JUL-07:01 | 13475.88 | 0.00 |
August | 0.00 | 0.00 | 0.173842E+11 | 0.118499E+11 | 26754.76 | 19-AUG-07:01 | 14367.13 | 0.00 |
September | 0.00 | 0.00 | 0.167675E+11 | 0.109691E+11 | 27121.53 | 25-SEP-07:01 | 13209.65 | 0.00 |
October | 0.00 | 0.00 | 0.168183E+11 | 0.113144E+11 | 26705.34 | 01-OCT-08:61 | 14645.76 | 0.00 |
November | 0.00 | 0.00 | 0.143837E+11 | 0.972315E+10 | 26680.80 | 24-NOV-08:61 | 14477.98 | 0.00 |
December | 0.00 | 0.00 | 0.131302E+11 | 0.896382E+10 | 26739.05 | 03-DEC-09:01 | 14379.18 | 0.00 |
Annual Sum or Average | 0.171369E+12 | 0.117082E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.112173E+11 | 0.757988E+10 | 26291.73 | 12333.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.173842E+11 | 0.118499E+11 | 27406.11 | 15036.05 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.112019E+11 | 0.805564E+10 | 26476.43 | 01-JAN-09:01 | 15110.77 | 0.00 |
February | 0.00 | 0.00 | 0.116075E+11 | 0.757279E+10 | 27467.26 | 18-FEB-08:61 | 12366.42 | 0.00 |
March | 0.00 | 0.00 | 0.123271E+11 | 0.866270E+10 | 26733.73 | 13-MAR-07:02 | 13802.92 | 0.00 |
April | 0.00 | 0.00 | 0.115697E+11 | 0.833562E+10 | 26351.25 | 24-APR-07:02 | 14593.51 | 0.00 |
May | 0.00 | 0.00 | 0.146353E+11 | 0.101691E+11 | 26895.36 | 10-MAY-07:01 | 13976.19 | 0.00 |
June | 0.00 | 0.00 | 0.148092E+11 | 0.101641E+11 | 26567.05 | 14-JUN-07:01 | 15069.95 | 0.00 |
July | 0.00 | 0.00 | 0.167888E+11 | 0.113570E+11 | 27130.38 | 21-JUL-07:01 | 13523.21 | 0.00 |
August | 0.00 | 0.00 | 0.174294E+11 | 0.118880E+11 | 26811.59 | 19-AUG-07:01 | 14412.98 | 0.00 |
September | 0.00 | 0.00 | 0.168332E+11 | 0.110217E+11 | 27162.63 | 24-SEP-08:61 | 13474.87 | 0.00 |
October | 0.00 | 0.00 | 0.168720E+11 | 0.113587E+11 | 26759.98 | 10-OCT-07:01 | 13683.96 | 0.00 |
November | 0.00 | 0.00 | 0.144010E+11 | 0.973909E+10 | 26732.52 | 24-NOV-08:61 | 14536.38 | 0.00 |
December | 0.00 | 0.00 | 0.131315E+11 | 0.896668E+10 | 26792.28 | 03-DEC-09:01 | 14429.20 | 0.00 |
Annual Sum or Average | 0.171607E+12 | 0.117291E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.112019E+11 | 0.757279E+10 | 26351.25 | 12366.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.174294E+11 | 0.118880E+11 | 27467.26 | 15110.77 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.110268E+11 | 0.791293E+10 | 26386.41 | 01-JAN-09:01 | 15020.44 | 0.00 |
February | 0.00 | 0.00 | 0.114336E+11 | 0.743823E+10 | 27371.31 | 18-FEB-08:61 | 12251.06 | 0.00 |
March | 0.00 | 0.00 | 0.121314E+11 | 0.850546E+10 | 26639.86 | 13-MAR-07:02 | 13698.22 | 0.00 |
April | 0.00 | 0.00 | 0.113874E+11 | 0.818747E+10 | 26258.31 | 24-APR-07:02 | 14483.28 | 0.00 |
May | 0.00 | 0.00 | 0.144613E+11 | 0.100288E+11 | 26817.24 | 10-MAY-07:01 | 13874.18 | 0.00 |
June | 0.00 | 0.00 | 0.146397E+11 | 0.100284E+11 | 26492.47 | 14-JUN-07:01 | 14976.58 | 0.00 |
July | 0.00 | 0.00 | 0.166290E+11 | 0.112293E+11 | 27068.36 | 21-JUL-07:01 | 13406.12 | 0.00 |
August | 0.00 | 0.00 | 0.172592E+11 | 0.117512E+11 | 26727.92 | 19-AUG-07:01 | 14300.65 | 0.00 |
September | 0.00 | 0.00 | 0.166718E+11 | 0.108951E+11 | 27095.87 | 24-SEP-08:61 | 13373.24 | 0.00 |
October | 0.00 | 0.00 | 0.167091E+11 | 0.112280E+11 | 26682.24 | 01-OCT-08:61 | 14620.29 | 0.00 |
November | 0.00 | 0.00 | 0.142385E+11 | 0.961025E+10 | 26656.80 | 24-NOV-08:61 | 14452.44 | 0.00 |
December | 0.00 | 0.00 | 0.129588E+11 | 0.882889E+10 | 26723.05 | 03-DEC-09:01 | 14334.53 | 0.00 |
Annual Sum or Average | 0.169547E+12 | 0.115644E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.110268E+11 | 0.743823E+10 | 26258.31 | 12251.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.172592E+11 | 0.117512E+11 | 27371.31 | 15020.44 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.194781E+11 | 0.137263E+11 | 48725.35 | 02-JAN-09:01 | 27999.79 | 0.00 |
February | 0.00 | 0.00 | 0.203749E+11 | 0.129676E+11 | 50439.81 | 18-FEB-09:01 | 23165.56 | 0.00 |
March | 0.00 | 0.00 | 0.217013E+11 | 0.149468E+11 | 49389.30 | 13-MAR-08:61 | 25182.82 | 0.00 |
April | 0.00 | 0.00 | 0.202158E+11 | 0.142921E+11 | 48522.38 | 24-APR-08:61 | 27721.65 | 0.00 |
May | 0.00 | 0.00 | 0.259611E+11 | 0.177315E+11 | 49429.00 | 15-MAY-08:61 | 26137.23 | 0.00 |
June | 0.00 | 0.00 | 0.262739E+11 | 0.177136E+11 | 48933.52 | 14-JUN-08:61 | 27584.29 | 0.00 |
July | 0.00 | 0.00 | 0.299176E+11 | 0.198888E+11 | 50078.96 | 20-JUL-08:61 | 24537.72 | 0.00 |
August | 0.00 | 0.00 | 0.312608E+11 | 0.209860E+11 | 49234.05 | 28-AUG-08:61 | 27025.12 | 0.00 |
September | 0.00 | 0.00 | 0.300425E+11 | 0.193352E+11 | 50118.10 | 30-SEP-08:61 | 23576.33 | 0.00 |
October | 0.00 | 0.00 | 0.302271E+11 | 0.200129E+11 | 49575.88 | 10-OCT-08:61 | 25752.32 | 0.00 |
November | 0.00 | 0.00 | 0.254824E+11 | 0.169015E+11 | 49242.62 | 01-NOV-08:61 | 26511.49 | 0.00 |
December | 0.00 | 0.00 | 0.230140E+11 | 0.153946E+11 | 49679.09 | 03-DEC-10:01 | 25380.96 | 0.00 |
Annual Sum or Average | 0.303950E+12 | 0.203897E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.194781E+11 | 0.129676E+11 | 48522.38 | 23165.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.312608E+11 | 0.209860E+11 | 50439.81 | 27999.79 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.101273E+11 | 0.715118E+10 | 25455.30 | 02-JAN-09:01 | 14667.27 | 0.00 |
February | 0.00 | 0.00 | 0.105831E+11 | 0.674875E+10 | 26334.85 | 18-FEB-09:01 | 12109.75 | 0.00 |
March | 0.00 | 0.00 | 0.112725E+11 | 0.777679E+10 | 25808.71 | 13-MAR-08:61 | 13180.78 | 0.00 |
April | 0.00 | 0.00 | 0.105055E+11 | 0.744004E+10 | 25349.53 | 24-APR-08:61 | 14489.69 | 0.00 |
May | 0.00 | 0.00 | 0.134973E+11 | 0.923289E+10 | 25832.82 | 15-MAY-08:61 | 13648.68 | 0.00 |
June | 0.00 | 0.00 | 0.136461E+11 | 0.921563E+10 | 25562.80 | 14-JUN-08:61 | 14432.59 | 0.00 |
July | 0.00 | 0.00 | 0.155536E+11 | 0.103561E+11 | 26168.48 | 20-JUL-08:61 | 12818.77 | 0.00 |
August | 0.00 | 0.00 | 0.162524E+11 | 0.109271E+11 | 25703.54 | 28-AUG-08:61 | 14141.51 | 0.00 |
September | 0.00 | 0.00 | 0.156111E+11 | 0.100633E+11 | 26169.62 | 30-SEP-08:61 | 12346.32 | 0.00 |
October | 0.00 | 0.00 | 0.157294E+11 | 0.104304E+11 | 25902.90 | 10-OCT-08:61 | 13468.39 | 0.00 |
November | 0.00 | 0.00 | 0.132448E+11 | 0.880198E+10 | 25725.23 | 01-NOV-08:61 | 13881.68 | 0.00 |
December | 0.00 | 0.00 | 0.119618E+11 | 0.801788E+10 | 25954.93 | 03-DEC-10:01 | 13279.66 | 0.00 |
Annual Sum or Average | 0.157985E+12 | 0.106162E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.101273E+11 | 0.674875E+10 | 25349.53 | 12109.75 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.162524E+11 | 0.109271E+11 | 26334.85 | 14667.27 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.100354E+11 | 0.707612E+10 | 25350.61 | 02-JAN-09:01 | 14585.33 | 0.00 |
February | 0.00 | 0.00 | 0.104929E+11 | 0.667886E+10 | 26222.91 | 18-FEB-09:01 | 12027.09 | 0.00 |
March | 0.00 | 0.00 | 0.111764E+11 | 0.769920E+10 | 25697.35 | 13-MAR-08:61 | 13097.01 | 0.00 |
April | 0.00 | 0.00 | 0.104182E+11 | 0.736843E+10 | 25239.97 | 24-APR-08:61 | 14400.38 | 0.00 |
May | 0.00 | 0.00 | 0.134061E+11 | 0.915846E+10 | 25722.07 | 15-MAY-08:61 | 13565.42 | 0.00 |
June | 0.00 | 0.00 | 0.135563E+11 | 0.914281E+10 | 25459.02 | 14-JUN-08:61 | 14349.94 | 0.00 |
July | 0.00 | 0.00 | 0.154646E+11 | 0.102839E+11 | 26068.31 | 20-JUL-08:61 | 12735.25 | 0.00 |
August | 0.00 | 0.00 | 0.161634E+11 | 0.108542E+11 | 25647.33 | 28-AUG-08:61 | 14125.73 | 0.00 |
September | 0.00 | 0.00 | 0.155229E+11 | 0.999284E+10 | 26058.27 | 30-SEP-08:61 | 12263.56 | 0.00 |
October | 0.00 | 0.00 | 0.156415E+11 | 0.103588E+11 | 25798.68 | 10-OCT-08:61 | 13393.38 | 0.00 |
November | 0.00 | 0.00 | 0.131536E+11 | 0.872883E+10 | 25623.05 | 01-NOV-08:61 | 13799.36 | 0.00 |
December | 0.00 | 0.00 | 0.118692E+11 | 0.794336E+10 | 25847.83 | 03-DEC-10:01 | 13211.94 | 0.00 |
Annual Sum or Average | 0.156900E+12 | 0.105286E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.100354E+11 | 0.667886E+10 | 25239.97 | 12027.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.161634E+11 | 0.108542E+11 | 26222.91 | 14585.33 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.991526E+10 | 0.698170E+10 | 25333.13 | 02-JAN-09:01 | 14537.61 | 0.00 |
February | 0.00 | 0.00 | 0.103678E+11 | 0.658583E+10 | 26200.49 | 18-FEB-09:01 | 11970.41 | 0.00 |
March | 0.00 | 0.00 | 0.110482E+11 | 0.759990E+10 | 25672.60 | 13-MAR-08:61 | 13039.30 | 0.00 |
April | 0.00 | 0.00 | 0.103166E+11 | 0.728852E+10 | 25215.15 | 24-APR-08:61 | 14343.04 | 0.00 |
May | 0.00 | 0.00 | 0.133312E+11 | 0.909997E+10 | 25698.31 | 15-MAY-08:61 | 13515.65 | 0.00 |
June | 0.00 | 0.00 | 0.134904E+11 | 0.909197E+10 | 25439.95 | 14-JUN-08:61 | 14307.41 | 0.00 |
July | 0.00 | 0.00 | 0.154157E+11 | 0.102466E+11 | 26061.80 | 20-JUL-08:61 | 12697.41 | 0.00 |
August | 0.00 | 0.00 | 0.161286E+11 | 0.108275E+11 | 25593.16 | 28-AUG-08:61 | 14029.53 | 0.00 |
September | 0.00 | 0.00 | 0.154767E+11 | 0.995789E+10 | 26039.36 | 25-SEP-08:61 | 12846.87 | 0.00 |
October | 0.00 | 0.00 | 0.155952E+11 | 0.103230E+11 | 25785.50 | 10-OCT-08:61 | 13361.91 | 0.00 |
November | 0.00 | 0.00 | 0.130694E+11 | 0.866472E+10 | 25610.24 | 01-NOV-08:61 | 13766.73 | 0.00 |
December | 0.00 | 0.00 | 0.117684E+11 | 0.786531E+10 | 25841.96 | 03-DEC-10:01 | 13172.14 | 0.00 |
Annual Sum or Average | 0.155924E+12 | 0.104533E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.991526E+10 | 0.658583E+10 | 25215.15 | 11970.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.161286E+11 | 0.108275E+11 | 26200.49 | 14537.61 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.104822E+11 | 0.746208E+10 | 27051.20 | 03-JAN-09:01 | 15353.79 | 0.00 |
February | 0.00 | 0.00 | 0.108224E+11 | 0.694432E+10 | 28092.75 | 18-FEB-09:01 | 12180.57 | 0.00 |
March | 0.00 | 0.00 | 0.116099E+11 | 0.806613E+10 | 27365.24 | 13-MAR-08:61 | 13861.32 | 0.00 |
April | 0.00 | 0.00 | 0.110275E+11 | 0.787637E+10 | 26856.51 | 24-APR-08:61 | 15410.45 | 0.00 |
May | 0.00 | 0.00 | 0.143838E+11 | 0.993841E+10 | 27579.10 | 10-MAY-08:61 | 13596.22 | 0.00 |
June | 0.00 | 0.00 | 0.145927E+11 | 0.994656E+10 | 27263.29 | 14-JUN-08:61 | 14908.88 | 0.00 |
July | 0.00 | 0.00 | 0.167121E+11 | 0.112456E+11 | 27899.01 | 20-JUL-08:61 | 13182.89 | 0.00 |
August | 0.00 | 0.00 | 0.175790E+11 | 0.119513E+11 | 27387.24 | 01-AUG-08:61 | 14590.29 | 0.00 |
September | 0.00 | 0.00 | 0.166524E+11 | 0.108414E+11 | 27921.34 | 30-SEP-08:61 | 12533.23 | 0.00 |
October | 0.00 | 0.00 | 0.168577E+11 | 0.113093E+11 | 27471.69 | 10-OCT-08:61 | 14284.53 | 0.00 |
November | 0.00 | 0.00 | 0.139383E+11 | 0.933743E+10 | 27451.88 | 01-NOV-08:61 | 14271.34 | 0.00 |
December | 0.00 | 0.00 | 0.124698E+11 | 0.842457E+10 | 27509.96 | 03-DEC-10:01 | 14130.85 | 0.00 |
Annual Sum or Average | 0.167128E+12 | 0.113343E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.104822E+11 | 0.694432E+10 | 26856.51 | 12180.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.175790E+11 | 0.119513E+11 | 28092.75 | 15410.45 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.385041E+10 | 0.59 | 2122.14 | 01-JAN-09:10 | 0.87 |
February | 0.348370E+10 | 0.59 | 2122.14 | 01-FEB-10:40 | 0.87 |
March | 0.385805E+10 | 0.59 | 2122.14 | 01-MAR-11:00 | 0.87 |
April | 0.373581E+10 | 0.59 | 2122.14 | 01-APR-17:50 | 0.87 |
May | 0.385041E+10 | 0.59 | 2122.14 | 01-MAY-08:07 | 0.87 |
June | 0.373581E+10 | 0.59 | 2122.14 | 01-JUN-19:45 | 0.87 |
July | 0.385805E+10 | 0.59 | 2122.14 | 01-JUL-09:50 | 0.87 |
August | 0.385041E+10 | 0.59 | 2122.14 | 01-AUG-15:40 | 0.87 |
September | 0.374345E+10 | 0.59 | 2122.14 | 01-SEP-07:20 | 0.86 |
October | 0.385041E+10 | 0.59 | 2122.14 | 01-OCT-08:04 | 0.86 |
November | 0.372053E+10 | 0.59 | 2122.14 | 01-NOV-08:40 | 0.86 |
December | 0.386569E+10 | 0.59 | 2122.14 | 01-DEC-00:10 | 0.87 |
Annual Sum or Average | 0.454027E+11 | 0.59 | |||
Minimum of Months | 0.348370E+10 | 0.59 | 2122.14 | 0.86 | |
Maximum of Months | 0.386569E+10 | 0.59 | 2122.14 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.173069E+10 | 0.64 | 1155.46 | 01-JAN-09:03 | 0.90 |
February | 0.157758E+10 | 0.64 | 1155.46 | 01-FEB-09:08 | 0.90 |
March | 0.175662E+10 | 0.64 | 1155.46 | 01-MAR-09:09 | 0.90 |
April | 0.168236E+10 | 0.65 | 1155.46 | 01-APR-09:50 | 0.90 |
May | 0.176421E+10 | 0.64 | 1155.46 | 01-MAY-09:10 | 0.90 |
June | 0.172026E+10 | 0.64 | 1155.46 | 01-JUN-08:40 | 0.90 |
July | 0.177436E+10 | 0.64 | 1155.46 | 01-JUL-08:05 | 0.90 |
August | 0.179199E+10 | 0.64 | 1155.46 | 01-AUG-10:10 | 0.90 |
September | 0.173682E+10 | 0.64 | 1155.46 | 01-SEP-07:09 | 0.89 |
October | 0.177683E+10 | 0.64 | 1155.46 | 01-OCT-11:20 | 0.90 |
November | 0.170348E+10 | 0.64 | 1155.46 | 01-NOV-18:10 | 0.90 |
December | 0.174474E+10 | 0.65 | 1155.46 | 01-DEC-14:00 | 0.90 |
Annual Sum or Average | 0.207599E+11 | 0.64 | |||
Minimum of Months | 0.157758E+10 | 0.64 | 1155.46 | 0.89 | |
Maximum of Months | 0.179199E+10 | 0.65 | 1155.46 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166325E+10 | 0.49 | 1149.29 | 01-JAN-10:17 | 0.90 |
February | 0.150603E+10 | 0.49 | 1149.29 | 01-FEB-08:20 | 0.90 |
March | 0.169635E+10 | 0.49 | 1149.29 | 01-MAR-09:15 | 0.90 |
April | 0.161361E+10 | 0.49 | 1149.29 | 02-APR-09:06 | 0.90 |
May | 0.167980E+10 | 0.49 | 1149.29 | 01-MAY-08:03 | 0.90 |
June | 0.163843E+10 | 0.49 | 1149.29 | 01-JUN-07:20 | 0.89 |
July | 0.165498E+10 | 0.48 | 1149.29 | 03-JUL-06:30 | 0.89 |
August | 0.169635E+10 | 0.49 | 1149.29 | 01-AUG-06:40 | 0.89 |
September | 0.161361E+10 | 0.49 | 1149.29 | 01-SEP-10:40 | 0.90 |
October | 0.166325E+10 | 0.48 | 1149.29 | 01-OCT-07:50 | 0.89 |
November | 0.161361E+10 | 0.49 | 1149.29 | 01-NOV-06:40 | 0.89 |
December | 0.165498E+10 | 0.48 | 1149.29 | 01-DEC-19:00 | 0.90 |
Annual Sum or Average | 0.196943E+11 | 0.49 | |||
Minimum of Months | 0.150603E+10 | 0.48 | 1149.29 | 0.89 | |
Maximum of Months | 0.169635E+10 | 0.49 | 1149.29 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166811E+10 | 0.49 | 1152.65 | 15-JAN-09:20 | 0.90 |
February | 0.151043E+10 | 0.49 | 1152.65 | 01-FEB-07:10 | 0.90 |
March | 0.170131E+10 | 0.49 | 1152.65 | 01-MAR-07:10 | 0.89 |
April | 0.161832E+10 | 0.49 | 1152.65 | 01-APR-16:40 | 0.90 |
May | 0.168471E+10 | 0.49 | 1152.65 | 01-MAY-06:10 | 0.90 |
June | 0.164322E+10 | 0.49 | 1152.65 | 01-JUN-06:10 | 0.89 |
July | 0.165981E+10 | 0.48 | 1152.65 | 01-JUL-06:10 | 0.89 |
August | 0.170131E+10 | 0.49 | 1152.65 | 01-AUG-06:10 | 0.89 |
September | 0.161832E+10 | 0.49 | 1152.65 | 27-SEP-06:20 | 0.89 |
October | 0.166811E+10 | 0.48 | 1152.65 | 01-OCT-07:02 | 0.89 |
November | 0.161832E+10 | 0.49 | 1152.65 | 01-NOV-06:10 | 0.89 |
December | 0.165981E+10 | 0.48 | 1152.65 | 01-DEC-07:10 | 0.89 |
Annual Sum or Average | 0.197518E+11 | 0.49 | |||
Minimum of Months | 0.151043E+10 | 0.48 | 1152.65 | 0.89 | |
Maximum of Months | 0.170131E+10 | 0.49 | 1152.65 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166095E+10 | 0.49 | 1147.70 | 01-JAN-08:62 | 0.89 |
February | 0.150395E+10 | 0.49 | 1147.70 | 01-FEB-07:10 | 0.90 |
March | 0.169400E+10 | 0.49 | 1147.70 | 01-MAR-07:10 | 0.89 |
April | 0.161137E+10 | 0.49 | 1147.70 | 01-APR-06:10 | 0.90 |
May | 0.167748E+10 | 0.49 | 1147.70 | 01-MAY-06:10 | 0.90 |
June | 0.163616E+10 | 0.49 | 1147.70 | 01-JUN-06:10 | 0.89 |
July | 0.165269E+10 | 0.48 | 1147.70 | 17-JUL-06:50 | 0.89 |
August | 0.169400E+10 | 0.49 | 1147.70 | 01-AUG-06:10 | 0.89 |
September | 0.161137E+10 | 0.49 | 1147.70 | 06-SEP-07:00 | 0.89 |
October | 0.166095E+10 | 0.48 | 1147.70 | 30-OCT-06:30 | 0.89 |
November | 0.161137E+10 | 0.49 | 1147.70 | 01-NOV-06:10 | 0.89 |
December | 0.165269E+10 | 0.48 | 1147.70 | 02-DEC-08:00 | 0.89 |
Annual Sum or Average | 0.196670E+11 | 0.49 | |||
Minimum of Months | 0.150395E+10 | 0.48 | 1147.70 | 0.89 | |
Maximum of Months | 0.169400E+10 | 0.49 | 1147.70 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.269398E+10 | 0.43 | 2017.05 | 02-JAN-17:50 | 0.87 |
February | 0.243983E+10 | 0.43 | 2017.05 | 01-FEB-11:30 | 0.87 |
March | 0.275207E+10 | 0.44 | 2017.05 | 02-MAR-12:20 | 0.87 |
April | 0.261410E+10 | 0.43 | 2017.05 | 02-APR-12:10 | 0.87 |
May | 0.272302E+10 | 0.44 | 2017.05 | 01-MAY-10:20 | 0.87 |
June | 0.265767E+10 | 0.44 | 2017.05 | 04-JUN-09:00 | 0.86 |
July | 0.267945E+10 | 0.43 | 2017.05 | 01-JUL-13:50 | 0.87 |
August | 0.275207E+10 | 0.44 | 2017.05 | 02-AUG-12:50 | 0.87 |
September | 0.261410E+10 | 0.43 | 2017.05 | 06-SEP-17:50 | 0.87 |
October | 0.269398E+10 | 0.43 | 2017.05 | 01-OCT-08:17 | 0.86 |
November | 0.261410E+10 | 0.43 | 2017.05 | 02-NOV-08:50 | 0.86 |
December | 0.267945E+10 | 0.43 | 2017.05 | 01-DEC-19:50 | 0.87 |
Annual Sum or Average | 0.319138E+11 | 0.43 | |||
Minimum of Months | 0.243983E+10 | 0.43 | 2017.05 | 0.86 | |
Maximum of Months | 0.275207E+10 | 0.44 | 2017.05 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.145943E+10 | 0.45 | 1092.71 | 04-JAN-20:25 | 0.90 |
February | 0.132175E+10 | 0.45 | 1092.71 | 02-FEB-19:40 | 0.90 |
March | 0.149090E+10 | 0.46 | 1092.71 | 02-MAR-09:20 | 0.89 |
April | 0.141616E+10 | 0.45 | 1092.71 | 04-APR-08:08 | 0.90 |
May | 0.147516E+10 | 0.45 | 1092.71 | 03-MAY-19:25 | 0.90 |
June | 0.143976E+10 | 0.46 | 1092.71 | 01-JUN-16:00 | 0.90 |
July | 0.145156E+10 | 0.44 | 1092.71 | 09-JUL-08:09 | 0.89 |
August | 0.149090E+10 | 0.46 | 1092.71 | 04-AUG-17:10 | 0.90 |
September | 0.141616E+10 | 0.45 | 1092.71 | 05-SEP-07:40 | 0.89 |
October | 0.145943E+10 | 0.45 | 1092.71 | 03-OCT-19:05 | 0.90 |
November | 0.141616E+10 | 0.45 | 1092.71 | 02-NOV-08:17 | 0.89 |
December | 0.145156E+10 | 0.44 | 1092.71 | 01-DEC-08:40 | 0.89 |
Annual Sum or Average | 0.172889E+11 | 0.45 | |||
Minimum of Months | 0.132175E+10 | 0.44 | 1092.71 | 0.89 | |
Maximum of Months | 0.149090E+10 | 0.46 | 1092.71 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.145115E+10 | 0.45 | 1086.52 | 04-JAN-10:50 | 0.90 |
February | 0.131425E+10 | 0.45 | 1086.52 | 03-FEB-18:40 | 0.90 |
March | 0.148244E+10 | 0.46 | 1086.52 | 10-MAR-09:03 | 0.90 |
April | 0.140812E+10 | 0.45 | 1086.52 | 04-APR-20:00 | 0.90 |
May | 0.146680E+10 | 0.45 | 1086.52 | 04-MAY-19:12 | 0.90 |
June | 0.143159E+10 | 0.46 | 1086.52 | 06-JUN-12:00 | 0.90 |
July | 0.144333E+10 | 0.44 | 1086.52 | 02-JUL-09:50 | 0.90 |
August | 0.148244E+10 | 0.46 | 1086.52 | 11-AUG-08:00 | 0.89 |
September | 0.140812E+10 | 0.45 | 1086.52 | 07-SEP-10:00 | 0.90 |
October | 0.145115E+10 | 0.45 | 1086.52 | 03-OCT-18:00 | 0.90 |
November | 0.140812E+10 | 0.45 | 1086.52 | 01-NOV-19:17 | 0.90 |
December | 0.144333E+10 | 0.44 | 1086.52 | 02-DEC-10:50 | 0.90 |
Annual Sum or Average | 0.171909E+11 | 0.45 | |||
Minimum of Months | 0.131425E+10 | 0.44 | 1086.52 | 0.89 | |
Maximum of Months | 0.148244E+10 | 0.46 | 1086.52 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144976E+10 | 0.45 | 1085.48 | 02-JAN-10:40 | 0.90 |
February | 0.131299E+10 | 0.45 | 1085.48 | 03-FEB-17:50 | 0.90 |
March | 0.148103E+10 | 0.46 | 1085.48 | 13-MAR-09:30 | 0.89 |
April | 0.140678E+10 | 0.45 | 1085.48 | 01-APR-14:40 | 0.90 |
May | 0.146540E+10 | 0.45 | 1085.48 | 01-MAY-14:00 | 0.90 |
June | 0.143023E+10 | 0.46 | 1085.48 | 06-JUN-08:05 | 0.90 |
July | 0.144195E+10 | 0.44 | 1085.48 | 02-JUL-08:20 | 0.89 |
August | 0.148103E+10 | 0.46 | 1085.48 | 04-AUG-18:00 | 0.90 |
September | 0.140678E+10 | 0.45 | 1085.48 | 01-SEP-08:08 | 0.89 |
October | 0.144976E+10 | 0.45 | 1085.48 | 03-OCT-18:10 | 0.90 |
November | 0.140678E+10 | 0.45 | 1085.48 | 01-NOV-19:50 | 0.90 |
December | 0.144195E+10 | 0.44 | 1085.48 | 01-DEC-09:30 | 0.89 |
Annual Sum or Average | 0.171744E+11 | 0.45 | |||
Minimum of Months | 0.131299E+10 | 0.44 | 1085.48 | 0.89 | |
Maximum of Months | 0.148103E+10 | 0.46 | 1085.48 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158186E+10 | 0.45 | 1184.38 | 02-JAN-10:10 | 0.90 |
February | 0.143263E+10 | 0.45 | 1184.38 | 05-FEB-16:10 | 0.89 |
March | 0.161597E+10 | 0.46 | 1184.38 | 01-MAR-12:40 | 0.90 |
April | 0.153496E+10 | 0.45 | 1184.38 | 01-APR-10:30 | 0.90 |
May | 0.159892E+10 | 0.45 | 1184.38 | 01-MAY-11:10 | 0.90 |
June | 0.156054E+10 | 0.46 | 1184.38 | 01-JUN-10:30 | 0.90 |
July | 0.157334E+10 | 0.44 | 1184.38 | 06-JUL-19:05 | 0.90 |
August | 0.161597E+10 | 0.46 | 1184.38 | 03-AUG-10:50 | 0.90 |
September | 0.153496E+10 | 0.45 | 1184.38 | 01-SEP-10:20 | 0.89 |
October | 0.158186E+10 | 0.45 | 1184.38 | 04-OCT-19:08 | 0.90 |
November | 0.153496E+10 | 0.45 | 1184.38 | 02-NOV-19:08 | 0.90 |
December | 0.157334E+10 | 0.44 | 1184.38 | 04-DEC-14:40 | 0.90 |
Annual Sum or Average | 0.187393E+11 | 0.45 | |||
Minimum of Months | 0.143263E+10 | 0.44 | 1184.38 | 0.89 | |
Maximum of Months | 0.161597E+10 | 0.46 | 1184.38 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.47 | 0.00 |
February | 0.17 | 0.00 |
March | 0.72 | 0.00 |
April | 0.00 | 0.00 |
May | 1.50 | 0.00 |
June | 1.06 | 0.00 |
July | 0.28 | 0.00 |
August | 0.28 | 0.00 |
September | 0.00 | 0.00 |
October | 0.67 | 0.00 |
November | 0.61 | 0.00 |
December | 0.61 | 0.00 |
Annual Sum or Average | 6.36 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.50 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.81 | 0.00 |
February | 0.33 | 0.00 |
March | 0.97 | 0.00 |
April | 0.00 | 0.00 |
May | 2.08 | 0.00 |
June | 1.39 | 0.00 |
July | 0.28 | 0.00 |
August | 0.28 | 0.00 |
September | 0.00 | 0.00 |
October | 0.83 | 0.00 |
November | 1.03 | 0.00 |
December | 1.11 | 0.00 |
Annual Sum or Average | 9.11 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.08 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.88 | 0.75 |
February | 1.93 | 0.75 |
March | 2.34 | 0.75 |
April | 2.16 | 0.75 |
May | 3.21 | 0.75 |
June | 2.97 | 0.75 |
July | 3.59 | 0.75 |
August | 3.12 | 0.75 |
September | 3.84 | 0.73 |
October | 3.67 | 0.75 |
November | 2.71 | 0.75 |
December | 2.76 | 0.75 |
Annual Sum or Average | 34.18 | 0.75 |
Minimum of Months | 1.88 | 0.73 |
Maximum of Months | 3.84 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.88 | 0.75 |
February | 1.93 | 0.75 |
March | 2.34 | 0.75 |
April | 2.16 | 0.75 |
May | 3.21 | 0.75 |
June | 2.97 | 0.75 |
July | 3.59 | 0.75 |
August | 3.12 | 0.75 |
September | 3.84 | 0.73 |
October | 3.67 | 0.75 |
November | 2.71 | 0.75 |
December | 2.76 | 0.75 |
Annual Sum or Average | 34.18 | 0.75 |
Minimum of Months | 1.88 | 0.73 |
Maximum of Months | 3.84 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.74 | 0.75 |
February | 1.93 | 0.75 |
March | 2.34 | 0.75 |
April | 2.07 | 0.75 |
May | 3.21 | 0.75 |
June | 2.97 | 0.75 |
July | 3.59 | 0.75 |
August | 3.12 | 0.75 |
September | 3.84 | 0.73 |
October | 3.67 | 0.75 |
November | 2.66 | 0.75 |
December | 2.59 | 0.75 |
Annual Sum or Average | 33.73 | 0.75 |
Minimum of Months | 1.74 | 0.73 |
Maximum of Months | 3.84 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.57 | 2.50 |
February | 0.39 | 3.30 |
March | 0.72 | 3.30 |
April | 0.70 | 3.30 |
May | 1.46 | 2.36 |
June | 2.40 | 1.58 |
July | 2.81 | 2.32 |
August | 1.53 | 2.70 |
September | 2.35 | 2.60 |
October | 2.22 | 2.47 |
November | 1.39 | 1.33 |
December | 1.23 | 2.18 |
Annual Sum or Average | 17.78 | 2.33 |
Minimum of Months | 0.39 | 1.33 |
Maximum of Months | 2.81 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.52 | 1.21 |
February | 0.22 | 1.65 |
March | 0.64 | 1.65 |
April | 0.59 | 1.65 |
May | 1.38 | 1.25 |
June | 1.90 | 1.00 |
July | 2.72 | 1.20 |
August | 1.53 | 1.35 |
September | 2.26 | 1.29 |
October | 1.92 | 1.39 |
November | 1.26 | 0.66 |
December | 0.98 | 1.37 |
Annual Sum or Average | 15.92 | 1.24 |
Minimum of Months | 0.22 | 0.66 |
Maximum of Months | 2.72 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.35 | 1.39 |
February | 0.14 | 1.65 |
March | 0.64 | 1.65 |
April | 0.59 | 1.65 |
May | 1.29 | 1.33 |
June | 1.90 | 1.00 |
July | 2.64 | 1.23 |
August | 1.45 | 1.43 |
September | 2.10 | 1.32 |
October | 1.83 | 1.45 |
November | 1.17 | 0.71 |
December | 0.98 | 1.37 |
Annual Sum or Average | 15.08 | 1.28 |
Minimum of Months | 0.14 | 0.71 |
Maximum of Months | 2.64 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.35 | 1.39 |
February | 0.00 | 0.00 |
March | 0.64 | 1.65 |
April | 0.59 | 1.65 |
May | 1.29 | 1.33 |
June | 1.73 | 1.09 |
July | 2.47 | 1.32 |
August | 1.37 | 1.52 |
September | 2.10 | 1.39 |
October | 1.83 | 1.45 |
November | 0.95 | 0.78 |
December | 0.89 | 1.34 |
Annual Sum or Average | 14.22 | 1.33 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.47 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.49 | 1.46 |
February | 0.39 | 1.65 |
March | 0.72 | 1.65 |
April | 0.70 | 1.65 |
May | 1.43 | 1.27 |
June | 2.31 | 0.82 |
July | 2.81 | 1.16 |
August | 1.53 | 1.35 |
September | 2.18 | 1.33 |
October | 2.22 | 1.24 |
November | 1.26 | 0.66 |
December | 1.06 | 1.26 |
Annual Sum or Average | 17.11 | 1.20 |
Minimum of Months | 0.39 | 0.66 |
Maximum of Months | 2.81 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.112650E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.110815E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.120013E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.115844E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.135700E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.135204E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.151695E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.153817E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.150666E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.150659E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.131489E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.125616E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.159417E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.110815E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.153817E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.552916E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.541278E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.587268E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.563152E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.659837E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.655377E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.732607E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.745265E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.725234E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.731458E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.639837E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.611551E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.774578E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.541278E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.745265E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.460595E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.449749E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.494325E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.468804E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.554841E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.552925E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.606729E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.631007E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.597516E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.608538E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.535967E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.506144E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.646714E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.449749E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.631007E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.460792E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.450005E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.494745E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.469125E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.555904E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.554135E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.608692E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.632765E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.599703E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.610440E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.536991E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.506758E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.648005E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.450005E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.632765E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.455817E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.445205E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.489265E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.463962E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.550937E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.549262E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.603993E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.627803E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.595014E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.605711E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.532335E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.501895E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.642120E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.445205E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.627803E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.790247E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.777634E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.857346E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.808608E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.971715E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.969509E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.106985E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.111923E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.105569E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.107747E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.936732E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.876134E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.113102E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.777634E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.111923E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.412147E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.404694E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.446386E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.421189E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.505056E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.503389E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.555007E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.580520E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.547437E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.559338E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.486706E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.455937E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.587780E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.404694E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.580520E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.409008E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.401705E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.443109E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.418151E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.501866E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.500242E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.551825E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.577279E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.544323E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.556185E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.483572E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.452793E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.584006E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.401705E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.577279E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.405977E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.398641E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.439898E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.415565E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.499926E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.498520E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.550447E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.576239E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.543039E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.554892E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.481416E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.450270E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.581483E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.398641E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.576239E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.434429E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.423100E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.468842E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.447396E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.540981E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.540258E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.597393E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.627440E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.586372E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.601014E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.517133E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.482057E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.626641E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.423100E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.627440E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.385041E+10 | 0.278156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.348370E+10 | 0.290395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.385805E+10 | 0.305030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373581E+10 | 0.291509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.385041E+10 | 0.361898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.373581E+10 | 0.365633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.385805E+10 | 0.422282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.385041E+10 | 0.428468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.374345E+10 | 0.427983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.385041E+10 | 0.419910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.372053E+10 | 0.356067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386569E+10 | 0.329251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.454027E+11 | 0.427658E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.348370E+10 | 0.278156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.386569E+10 | 0.428468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.173069E+10 | 0.143017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157758E+10 | 0.146845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175662E+10 | 0.154600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168236E+10 | 0.146976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176421E+10 | 0.180149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172026E+10 | 0.180683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.177436E+10 | 0.206874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179199E+10 | 0.210106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173682E+10 | 0.207782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177683E+10 | 0.207166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170348E+10 | 0.177473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174474E+10 | 0.165731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207599E+11 | 0.212740E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157758E+10 | 0.143017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179199E+10 | 0.210106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166325E+10 | 0.112173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150603E+10 | 0.116193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169635E+10 | 0.123343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161361E+10 | 0.115796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167980E+10 | 0.146162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163843E+10 | 0.147845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165498E+10 | 0.167343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169635E+10 | 0.173842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161361E+10 | 0.167675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166325E+10 | 0.168183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161361E+10 | 0.143837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165498E+10 | 0.131302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196943E+11 | 0.171369E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150603E+10 | 0.112173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169635E+10 | 0.173842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166811E+10 | 0.112019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151043E+10 | 0.116075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170131E+10 | 0.123271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161832E+10 | 0.115697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168471E+10 | 0.146353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164322E+10 | 0.148092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165981E+10 | 0.167888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170131E+10 | 0.174294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161832E+10 | 0.168332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166811E+10 | 0.168720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161832E+10 | 0.144010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165981E+10 | 0.131315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197518E+11 | 0.171607E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151043E+10 | 0.112019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170131E+10 | 0.174294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166095E+10 | 0.110268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150395E+10 | 0.114336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169400E+10 | 0.121314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161137E+10 | 0.113874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167748E+10 | 0.144613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163616E+10 | 0.146397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165269E+10 | 0.166290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169400E+10 | 0.172592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161137E+10 | 0.166718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166095E+10 | 0.167091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161137E+10 | 0.142385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165269E+10 | 0.129588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196670E+11 | 0.169547E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150395E+10 | 0.110268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169400E+10 | 0.172592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.269398E+10 | 0.194781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.243983E+10 | 0.203749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.275207E+10 | 0.217013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.261410E+10 | 0.202158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.272302E+10 | 0.259611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.265767E+10 | 0.262739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.267945E+10 | 0.299176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.275207E+10 | 0.312608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.261410E+10 | 0.300425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.269398E+10 | 0.302271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.261410E+10 | 0.254824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.267945E+10 | 0.230140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319138E+11 | 0.303950E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.243983E+10 | 0.194781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.275207E+10 | 0.312608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.145943E+10 | 0.101273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132175E+10 | 0.105831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149090E+10 | 0.112725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141616E+10 | 0.105055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147516E+10 | 0.134973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143976E+10 | 0.136461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145156E+10 | 0.155536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149090E+10 | 0.162524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141616E+10 | 0.156111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145943E+10 | 0.157294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141616E+10 | 0.132448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145156E+10 | 0.119618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172889E+11 | 0.157985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132175E+10 | 0.101273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149090E+10 | 0.162524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.145115E+10 | 0.100354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131425E+10 | 0.104929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148244E+10 | 0.111764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140812E+10 | 0.104182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146680E+10 | 0.134061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143159E+10 | 0.135563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144333E+10 | 0.154646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148244E+10 | 0.161634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140812E+10 | 0.155229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145115E+10 | 0.156415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140812E+10 | 0.131536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144333E+10 | 0.118692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171909E+11 | 0.156900E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131425E+10 | 0.100354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148244E+10 | 0.161634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144976E+10 | 0.991526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131299E+10 | 0.103678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148103E+10 | 0.110482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140678E+10 | 0.103166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146540E+10 | 0.133312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143023E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144195E+10 | 0.154157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148103E+10 | 0.161286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140678E+10 | 0.154767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144976E+10 | 0.155952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140678E+10 | 0.130694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144195E+10 | 0.117684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171744E+11 | 0.155924E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131299E+10 | 0.991526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148103E+10 | 0.161286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158186E+10 | 0.104822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143263E+10 | 0.108224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161597E+10 | 0.116099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153496E+10 | 0.110275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159892E+10 | 0.143838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156054E+10 | 0.145927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157334E+10 | 0.167121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161597E+10 | 0.175790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153496E+10 | 0.166524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158186E+10 | 0.168577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153496E+10 | 0.139383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157334E+10 | 0.124698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187393E+11 | 0.167128E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143263E+10 | 0.104822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161597E+10 | 0.175790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.385041E+10 | 0.00 | 0.00 | 0.00 | 0.741463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.348370E+10 | 0.00 | 0.00 | 0.00 | 0.759780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.385805E+10 | 0.00 | 0.00 | 0.00 | 0.814327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373581E+10 | 0.00 | 0.00 | 0.00 | 0.784860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.385041E+10 | 0.00 | 0.00 | 0.00 | 0.971960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.373581E+10 | 0.00 | 0.00 | 0.00 | 0.978462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.385805E+10 | 0.00 | 0.00 | 0.00 | 0.113115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.385041E+10 | 0.00 | 0.00 | 0.00 | 0.115313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.374345E+10 | 0.00 | 0.00 | 0.00 | 0.113232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.385041E+10 | 0.00 | 0.00 | 0.00 | 0.112155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.372053E+10 | 0.00 | 0.00 | 0.00 | 0.942834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386569E+10 | 0.00 | 0.00 | 0.00 | 0.869595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.454027E+11 | 0.00 | 0.00 | 0.00 | 0.114014E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.348370E+10 | 0.00 | 0.00 | 0.00 | 0.741463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.386569E+10 | 0.00 | 0.00 | 0.00 | 0.115313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.173069E+10 | 0.00 | 0.00 | 0.00 | 0.379847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157758E+10 | 0.00 | 0.00 | 0.00 | 0.383521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175662E+10 | 0.00 | 0.00 | 0.00 | 0.411606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168236E+10 | 0.00 | 0.00 | 0.00 | 0.394916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176421E+10 | 0.00 | 0.00 | 0.00 | 0.483416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172026E+10 | 0.00 | 0.00 | 0.00 | 0.483351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.177436E+10 | 0.00 | 0.00 | 0.00 | 0.555170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179199E+10 | 0.00 | 0.00 | 0.00 | 0.566066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173682E+10 | 0.00 | 0.00 | 0.00 | 0.551551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177683E+10 | 0.00 | 0.00 | 0.00 | 0.553775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170348E+10 | 0.00 | 0.00 | 0.00 | 0.469489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174474E+10 | 0.00 | 0.00 | 0.00 | 0.437077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207599E+11 | 0.00 | 0.00 | 0.00 | 0.566978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.157758E+10 | 0.00 | 0.00 | 0.00 | 0.379847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179199E+10 | 0.00 | 0.00 | 0.00 | 0.566066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.166325E+10 | 0.00 | 0.00 | 0.00 | 0.294270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150603E+10 | 0.00 | 0.00 | 0.00 | 0.299146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169635E+10 | 0.00 | 0.00 | 0.00 | 0.324690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161361E+10 | 0.00 | 0.00 | 0.00 | 0.307443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167980E+10 | 0.00 | 0.00 | 0.00 | 0.386861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163843E+10 | 0.00 | 0.00 | 0.00 | 0.389082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165498E+10 | 0.00 | 0.00 | 0.00 | 0.441231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169635E+10 | 0.00 | 0.00 | 0.00 | 0.461371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161361E+10 | 0.00 | 0.00 | 0.00 | 0.436156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166325E+10 | 0.00 | 0.00 | 0.00 | 0.442213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161361E+10 | 0.00 | 0.00 | 0.00 | 0.374607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165498E+10 | 0.00 | 0.00 | 0.00 | 0.340646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196943E+11 | 0.00 | 0.00 | 0.00 | 0.449771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.150603E+10 | 0.00 | 0.00 | 0.00 | 0.294270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169635E+10 | 0.00 | 0.00 | 0.00 | 0.461371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.166811E+10 | 0.00 | 0.00 | 0.00 | 0.293981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151043E+10 | 0.00 | 0.00 | 0.00 | 0.298962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170131E+10 | 0.00 | 0.00 | 0.00 | 0.324614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161832E+10 | 0.00 | 0.00 | 0.00 | 0.307293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168471E+10 | 0.00 | 0.00 | 0.00 | 0.387433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164322E+10 | 0.00 | 0.00 | 0.00 | 0.389814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165981E+10 | 0.00 | 0.00 | 0.00 | 0.442710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170131E+10 | 0.00 | 0.00 | 0.00 | 0.462634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161832E+10 | 0.00 | 0.00 | 0.00 | 0.437872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166811E+10 | 0.00 | 0.00 | 0.00 | 0.443628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161832E+10 | 0.00 | 0.00 | 0.00 | 0.375159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165981E+10 | 0.00 | 0.00 | 0.00 | 0.340777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197518E+11 | 0.00 | 0.00 | 0.00 | 0.450488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.151043E+10 | 0.00 | 0.00 | 0.00 | 0.293981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170131E+10 | 0.00 | 0.00 | 0.00 | 0.462634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.166095E+10 | 0.00 | 0.00 | 0.00 | 0.289722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150395E+10 | 0.00 | 0.00 | 0.00 | 0.294810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169400E+10 | 0.00 | 0.00 | 0.00 | 0.319864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161137E+10 | 0.00 | 0.00 | 0.00 | 0.302825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167748E+10 | 0.00 | 0.00 | 0.00 | 0.383189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163616E+10 | 0.00 | 0.00 | 0.00 | 0.385646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165269E+10 | 0.00 | 0.00 | 0.00 | 0.438724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169400E+10 | 0.00 | 0.00 | 0.00 | 0.458402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161137E+10 | 0.00 | 0.00 | 0.00 | 0.433877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166095E+10 | 0.00 | 0.00 | 0.00 | 0.439616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161137E+10 | 0.00 | 0.00 | 0.00 | 0.371198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165269E+10 | 0.00 | 0.00 | 0.00 | 0.336626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196670E+11 | 0.00 | 0.00 | 0.00 | 0.445450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.150395E+10 | 0.00 | 0.00 | 0.00 | 0.289722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169400E+10 | 0.00 | 0.00 | 0.00 | 0.458402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.269398E+10 | 0.00 | 0.00 | 0.00 | 0.520850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.243983E+10 | 0.00 | 0.00 | 0.00 | 0.533652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.275207E+10 | 0.00 | 0.00 | 0.00 | 0.582139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.261410E+10 | 0.00 | 0.00 | 0.00 | 0.547198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.272302E+10 | 0.00 | 0.00 | 0.00 | 0.699412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.265767E+10 | 0.00 | 0.00 | 0.00 | 0.703742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.267945E+10 | 0.00 | 0.00 | 0.00 | 0.801900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.275207E+10 | 0.00 | 0.00 | 0.00 | 0.844020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.261410E+10 | 0.00 | 0.00 | 0.00 | 0.794283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.269398E+10 | 0.00 | 0.00 | 0.00 | 0.808076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.261410E+10 | 0.00 | 0.00 | 0.00 | 0.675322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.267945E+10 | 0.00 | 0.00 | 0.00 | 0.608189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319138E+11 | 0.00 | 0.00 | 0.00 | 0.811878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.243983E+10 | 0.00 | 0.00 | 0.00 | 0.520850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.275207E+10 | 0.00 | 0.00 | 0.00 | 0.844020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.145943E+10 | 0.00 | 0.00 | 0.00 | 0.266204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132175E+10 | 0.00 | 0.00 | 0.00 | 0.272519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149090E+10 | 0.00 | 0.00 | 0.00 | 0.297296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141616E+10 | 0.00 | 0.00 | 0.00 | 0.279573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147516E+10 | 0.00 | 0.00 | 0.00 | 0.357539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143976E+10 | 0.00 | 0.00 | 0.00 | 0.359413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145156E+10 | 0.00 | 0.00 | 0.00 | 0.409851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149090E+10 | 0.00 | 0.00 | 0.00 | 0.431430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141616E+10 | 0.00 | 0.00 | 0.00 | 0.405821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145943E+10 | 0.00 | 0.00 | 0.00 | 0.413395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141616E+10 | 0.00 | 0.00 | 0.00 | 0.345091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145156E+10 | 0.00 | 0.00 | 0.00 | 0.310781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172889E+11 | 0.00 | 0.00 | 0.00 | 0.414891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.132175E+10 | 0.00 | 0.00 | 0.00 | 0.266204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149090E+10 | 0.00 | 0.00 | 0.00 | 0.431430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.145115E+10 | 0.00 | 0.00 | 0.00 | 0.263893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131425E+10 | 0.00 | 0.00 | 0.00 | 0.270280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148244E+10 | 0.00 | 0.00 | 0.00 | 0.294865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140812E+10 | 0.00 | 0.00 | 0.00 | 0.277339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146680E+10 | 0.00 | 0.00 | 0.00 | 0.355186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143159E+10 | 0.00 | 0.00 | 0.00 | 0.357083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144333E+10 | 0.00 | 0.00 | 0.00 | 0.407492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148244E+10 | 0.00 | 0.00 | 0.00 | 0.429034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140812E+10 | 0.00 | 0.00 | 0.00 | 0.403510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145115E+10 | 0.00 | 0.00 | 0.00 | 0.411070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140812E+10 | 0.00 | 0.00 | 0.00 | 0.342760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144333E+10 | 0.00 | 0.00 | 0.00 | 0.308460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171909E+11 | 0.00 | 0.00 | 0.00 | 0.412097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.131425E+10 | 0.00 | 0.00 | 0.00 | 0.263893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148244E+10 | 0.00 | 0.00 | 0.00 | 0.429034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.144976E+10 | 0.00 | 0.00 | 0.00 | 0.261000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131299E+10 | 0.00 | 0.00 | 0.00 | 0.267341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148103E+10 | 0.00 | 0.00 | 0.00 | 0.291796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140678E+10 | 0.00 | 0.00 | 0.00 | 0.274887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146540E+10 | 0.00 | 0.00 | 0.00 | 0.353387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143023E+10 | 0.00 | 0.00 | 0.00 | 0.355498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144195E+10 | 0.00 | 0.00 | 0.00 | 0.406252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148103E+10 | 0.00 | 0.00 | 0.00 | 0.428137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140678E+10 | 0.00 | 0.00 | 0.00 | 0.402361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144976E+10 | 0.00 | 0.00 | 0.00 | 0.409915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140678E+10 | 0.00 | 0.00 | 0.00 | 0.340738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144195E+10 | 0.00 | 0.00 | 0.00 | 0.306075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171744E+11 | 0.00 | 0.00 | 0.00 | 0.409739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.131299E+10 | 0.00 | 0.00 | 0.00 | 0.261000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148103E+10 | 0.00 | 0.00 | 0.00 | 0.428137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.158186E+10 | 0.00 | 0.00 | 0.00 | 0.276242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143263E+10 | 0.00 | 0.00 | 0.00 | 0.279837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161597E+10 | 0.00 | 0.00 | 0.00 | 0.307245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153496E+10 | 0.00 | 0.00 | 0.00 | 0.293899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159892E+10 | 0.00 | 0.00 | 0.00 | 0.381089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156054E+10 | 0.00 | 0.00 | 0.00 | 0.384204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157334E+10 | 0.00 | 0.00 | 0.00 | 0.440059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161597E+10 | 0.00 | 0.00 | 0.00 | 0.465843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153496E+10 | 0.00 | 0.00 | 0.00 | 0.432876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158186E+10 | 0.00 | 0.00 | 0.00 | 0.442827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153496E+10 | 0.00 | 0.00 | 0.00 | 0.363637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157334E+10 | 0.00 | 0.00 | 0.00 | 0.324723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187393E+11 | 0.00 | 0.00 | 0.00 | 0.439248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.143263E+10 | 0.00 | 0.00 | 0.00 | 0.276242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161597E+10 | 0.00 | 0.00 | 0.00 | 0.465843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 82116409.95 | 0.474853E+10 | 0.00 | 3624583.32 | 39537175.50 | 0.00 | 0.101672E+09 | 0.00 | 0.57 |
February | 51430275.75 | 0.681519E+10 | 0.00 | 2094964.64 | 0.107094E+09 | 0.00 | 99810928.76 | 0.00 | 0.57 |
March | 75325700.77 | 0.641007E+10 | 0.00 | 1773288.69 | 51081456.90 | 0.00 | 49395822.17 | 0.00 | 0.57 |
April | 47762280.71 | 0.607429E+10 | 0.00 | 882030.59 | 64064496.68 | 0.00 | 3187373.97 | 0.00 | 0.57 |
May | 8037294.44 | 0.947848E+10 | 0.00 | 223129.24 | 0.140137E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 2748061.74 | 0.968491E+10 | 0.00 | 93302.30 | 0.123266E+09 | 0.00 | 365711.18 | 0.00 | 0.57 |
July | 15471052.32 | 0.123780E+11 | 0.00 | 157769.44 | 0.110799E+09 | 0.00 | 414260.95 | 0.00 | 0.57 |
August | 69364.64 | 0.128374E+11 | 0.00 | 0.00 | 0.151054E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 714936.41 | 0.130393E+11 | 0.00 | 4516.70 | 0.164768E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 4351324.21 | 0.125238E+11 | 0.00 | 60273.78 | 0.200264E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
November | 9930518.23 | 0.898099E+10 | 0.00 | 305803.64 | 0.116579E+09 | 0.00 | 81762.39 | 0.00 | 0.57 |
December | 40783678.49 | 0.740609E+10 | 0.00 | 1467531.73 | 81323901.94 | 0.00 | 6011123.64 | 0.00 | 0.57 |
Annual Sum or Average | 0.338741E+09 | 0.110377E+12 | 0.00 | 10687194.08 | 0.134997E+10 | 0.00 | 0.260939E+09 | 0.00 | 0.57 |
Minimum of Months | 69364.64 | 0.474853E+10 | 0.00 | 0.00 | 39537175.50 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 82116409.95 | 0.130393E+11 | 0.00 | 3624583.32 | 0.200264E+09 | 0.00 | 0.101672E+09 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 21045245.29 | 0.221519E+10 | 0.00 | 1323789.78 | 58897825.59 | 0.00 | 21025457.01 | 0.00 | 0.46 |
February | 13560327.13 | 0.304493E+10 | 0.00 | 937978.33 | 0.118666E+09 | 0.00 | 13322257.92 | 0.00 | 0.47 |
March | 12737359.77 | 0.289733E+10 | 0.00 | 410042.75 | 77722816.22 | 0.00 | 5452532.45 | 0.00 | 0.47 |
April | 8962245.04 | 0.271188E+10 | 0.00 | 195928.41 | 77399704.18 | 0.00 | 639619.81 | 0.00 | 0.46 |
May | 131696.85 | 0.415007E+10 | 0.00 | 9086.36 | 0.149137E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.420174E+10 | 0.00 | 0.00 | 0.138425E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 2666639.61 | 0.532244E+10 | 0.00 | 90.57 | 0.127921E+09 | 0.00 | 460.94 | 0.00 | 0.47 |
August | 0.00 | 0.556695E+10 | 0.00 | 0.00 | 0.172914E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.553570E+10 | 0.00 | 0.00 | 0.172809E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.542953E+10 | 0.00 | 0.00 | 0.194369E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
November | 329283.80 | 0.397327E+10 | 0.00 | 12067.56 | 0.120992E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
December | 6048354.39 | 0.328268E+10 | 0.00 | 391497.48 | 97522704.25 | 0.00 | 581058.72 | 0.00 | 0.47 |
Annual Sum or Average | 65481151.88 | 0.483317E+11 | 0.00 | 3280481.25 | 0.150678E+10 | 0.00 | 41021386.85 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.221519E+10 | 0.00 | 0.00 | 58897825.59 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 21045245.29 | 0.556695E+10 | 0.00 | 1323789.78 | 0.194369E+09 | 0.00 | 21025457.01 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132689E+09 | 0.192992E+10 | 0.00 | 1340328.00 | 57470027.32 | 0.00 | 27942600.65 | 0.00 | 0.45 |
February | 89838991.90 | 0.259497E+10 | 0.00 | 822829.06 | 0.124040E+09 | 0.00 | 19083385.20 | 0.00 | 0.46 |
March | 0.119725E+09 | 0.251576E+10 | 0.00 | 1039901.06 | 0.103456E+09 | 0.00 | 17605621.38 | 0.00 | 0.46 |
April | 78301473.77 | 0.234028E+10 | 0.00 | 867101.62 | 94818340.96 | 0.00 | 5187686.38 | 0.00 | 0.46 |
May | 34842943.16 | 0.356239E+10 | 0.00 | 837253.73 | 0.202126E+09 | 0.00 | 142760.65 | 0.00 | 0.46 |
June | 7854721.41 | 0.364659E+10 | 0.00 | 235397.77 | 0.231852E+09 | 0.00 | 52289.64 | 0.00 | 0.46 |
July | 13333805.82 | 0.449976E+10 | 0.00 | 331664.67 | 0.281219E+09 | 0.00 | 851081.20 | 0.00 | 0.45 |
August | 12200205.75 | 0.478469E+10 | 0.00 | 190584.73 | 0.296875E+09 | 0.00 | 226148.97 | 0.00 | 0.47 |
September | 12818633.65 | 0.457777E+10 | 0.00 | 256921.70 | 0.310973E+09 | 0.00 | 927000.63 | 0.00 | 0.46 |
October | 41977224.45 | 0.455845E+10 | 0.00 | 799730.04 | 0.272864E+09 | 0.00 | 524783.20 | 0.00 | 0.46 |
November | 28178416.76 | 0.342856E+10 | 0.00 | 363142.01 | 0.172570E+09 | 0.00 | 981740.92 | 0.00 | 0.46 |
December | 70449955.41 | 0.279290E+10 | 0.00 | 1324443.47 | 0.142419E+09 | 0.00 | 4828844.95 | 0.00 | 0.45 |
Annual Sum or Average | 0.642210E+09 | 0.412320E+11 | 0.00 | 8409297.87 | 0.229068E+10 | 0.00 | 78353943.76 | 0.00 | 0.46 |
Minimum of Months | 7854721.41 | 0.192992E+10 | 0.00 | 190584.73 | 57470027.32 | 0.00 | 52289.64 | 0.00 | 0.45 |
Maximum of Months | 0.132689E+09 | 0.478469E+10 | 0.00 | 1340328.00 | 0.310973E+09 | 0.00 | 27942600.65 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133279E+09 | 0.192810E+10 | 0.00 | 1338825.51 | 57263179.61 | 0.00 | 27812860.03 | 0.00 | 0.45 |
February | 89988727.62 | 0.259328E+10 | 0.00 | 830717.11 | 0.123467E+09 | 0.00 | 19218243.03 | 0.00 | 0.46 |
March | 0.119935E+09 | 0.251452E+10 | 0.00 | 1048556.42 | 0.103253E+09 | 0.00 | 17668289.01 | 0.00 | 0.46 |
April | 78420067.04 | 0.233882E+10 | 0.00 | 870454.91 | 94466032.52 | 0.00 | 5202340.99 | 0.00 | 0.46 |
May | 35245648.98 | 0.356482E+10 | 0.00 | 851225.29 | 0.201464E+09 | 0.00 | 143494.98 | 0.00 | 0.46 |
June | 7921319.34 | 0.365033E+10 | 0.00 | 232233.18 | 0.230555E+09 | 0.00 | 50271.31 | 0.00 | 0.46 |
July | 12819596.62 | 0.450954E+10 | 0.00 | 324073.27 | 0.278422E+09 | 0.00 | 1310532.77 | 0.00 | 0.45 |
August | 12060543.96 | 0.479130E+10 | 0.00 | 186158.76 | 0.295989E+09 | 0.00 | 444435.36 | 0.00 | 0.47 |
September | 11265002.20 | 0.458767E+10 | 0.00 | 243628.01 | 0.310626E+09 | 0.00 | 2442175.76 | 0.00 | 0.46 |
October | 42535154.61 | 0.456701E+10 | 0.00 | 813791.66 | 0.271623E+09 | 0.00 | 580398.46 | 0.00 | 0.46 |
November | 28100093.98 | 0.343166E+10 | 0.00 | 359335.23 | 0.171273E+09 | 0.00 | 1251969.18 | 0.00 | 0.46 |
December | 70690900.12 | 0.279274E+10 | 0.00 | 1334115.26 | 0.142153E+09 | 0.00 | 4857312.49 | 0.00 | 0.45 |
Annual Sum or Average | 0.642260E+09 | 0.412698E+11 | 0.00 | 8433114.61 | 0.228056E+10 | 0.00 | 80982323.38 | 0.00 | 0.46 |
Minimum of Months | 7921319.34 | 0.192810E+10 | 0.00 | 186158.76 | 57263179.61 | 0.00 | 50271.31 | 0.00 | 0.45 |
Maximum of Months | 0.133279E+09 | 0.479130E+10 | 0.00 | 1338825.51 | 0.310626E+09 | 0.00 | 27812860.03 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131481E+09 | 0.190901E+10 | 0.00 | 1261684.90 | 57563838.41 | 0.00 | 28931375.18 | 0.00 | 0.45 |
February | 88540588.89 | 0.256930E+10 | 0.00 | 799303.59 | 0.123026E+09 | 0.00 | 19901144.79 | 0.00 | 0.46 |
March | 0.117244E+09 | 0.249034E+10 | 0.00 | 980238.07 | 0.102988E+09 | 0.00 | 18989081.37 | 0.00 | 0.46 |
April | 76071946.21 | 0.231667E+10 | 0.00 | 796320.83 | 95030357.00 | 0.00 | 5638792.48 | 0.00 | 0.46 |
May | 33843392.53 | 0.354357E+10 | 0.00 | 798105.26 | 0.202374E+09 | 0.00 | 142874.48 | 0.00 | 0.46 |
June | 7564373.88 | 0.362909E+10 | 0.00 | 228913.45 | 0.231790E+09 | 0.00 | 53278.96 | 0.00 | 0.46 |
July | 13273944.74 | 0.448756E+10 | 0.00 | 335088.63 | 0.281164E+09 | 0.00 | 869553.02 | 0.00 | 0.45 |
August | 12009533.16 | 0.476924E+10 | 0.00 | 194651.26 | 0.297511E+09 | 0.00 | 272108.58 | 0.00 | 0.47 |
September | 12717382.82 | 0.456644E+10 | 0.00 | 266146.90 | 0.310070E+09 | 0.00 | 913731.44 | 0.00 | 0.46 |
October | 41477861.92 | 0.454593E+10 | 0.00 | 788448.47 | 0.272054E+09 | 0.00 | 522795.51 | 0.00 | 0.46 |
November | 27390128.51 | 0.341015E+10 | 0.00 | 356913.38 | 0.172515E+09 | 0.00 | 1067760.50 | 0.00 | 0.46 |
December | 69425292.35 | 0.277131E+10 | 0.00 | 1272977.78 | 0.142013E+09 | 0.00 | 4805739.28 | 0.00 | 0.45 |
Annual Sum or Average | 0.631039E+09 | 0.410086E+11 | 0.00 | 8078792.51 | 0.228810E+10 | 0.00 | 82108235.58 | 0.00 | 0.46 |
Minimum of Months | 7564373.88 | 0.190901E+10 | 0.00 | 194651.26 | 57563838.41 | 0.00 | 53278.96 | 0.00 | 0.45 |
Maximum of Months | 0.131481E+09 | 0.476924E+10 | 0.00 | 1272977.78 | 0.310070E+09 | 0.00 | 28931375.18 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116085E+09 | 0.348798E+10 | 0.00 | 2381847.92 | 73043645.21 | 0.00 | 62617724.80 | 0.00 | 0.42 |
February | 71188656.98 | 0.478667E+10 | 0.00 | 1258527.54 | 0.162705E+09 | 0.00 | 30121738.97 | 0.00 | 0.42 |
March | 95608831.93 | 0.469596E+10 | 0.00 | 1291020.71 | 0.112306E+09 | 0.00 | 15376601.73 | 0.00 | 0.43 |
April | 61227927.20 | 0.433477E+10 | 0.00 | 870749.46 | 0.115544E+09 | 0.00 | 4210454.38 | 0.00 | 0.42 |
May | 18346108.26 | 0.676088E+10 | 0.00 | 312517.08 | 0.228471E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 5049672.71 | 0.691771E+10 | 0.00 | 78315.53 | 0.228473E+09 | 0.00 | 471600.56 | 0.00 | 0.43 |
July | 15075944.02 | 0.858088E+10 | 0.00 | 176358.20 | 0.292612E+09 | 0.00 | 641626.32 | 0.00 | 0.42 |
August | 1901020.63 | 0.922909E+10 | 0.00 | 343.35 | 0.303678E+09 | 0.00 | 15209.98 | 0.00 | 0.43 |
September | 7145430.46 | 0.872799E+10 | 0.00 | 22524.74 | 0.339662E+09 | 0.00 | 410178.34 | 0.00 | 0.42 |
October | 13259970.31 | 0.875007E+10 | 0.00 | 51183.37 | 0.344816E+09 | 0.00 | 492212.39 | 0.00 | 0.42 |
November | 16519376.29 | 0.642586E+10 | 0.00 | 307904.65 | 0.182552E+09 | 0.00 | 327602.70 | 0.00 | 0.42 |
December | 71895262.16 | 0.520296E+10 | 0.00 | 1746049.36 | 0.147023E+09 | 0.00 | 3627749.37 | 0.00 | 0.42 |
Annual Sum or Average | 0.493304E+09 | 0.779008E+11 | 0.00 | 8497341.92 | 0.253089E+10 | 0.00 | 0.118313E+09 | 0.00 | 0.42 |
Minimum of Months | 1901020.63 | 0.348798E+10 | 0.00 | 343.35 | 73043645.21 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.116085E+09 | 0.922909E+10 | 0.00 | 2381847.92 | 0.344816E+09 | 0.00 | 62617724.80 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 57976238.42 | 0.173625E+10 | 0.00 | 1195502.88 | 35881714.08 | 0.00 | 31220710.32 | 0.00 | 0.42 |
February | 35463465.69 | 0.237993E+10 | 0.00 | 638878.41 | 81309505.64 | 0.00 | 14852498.74 | 0.00 | 0.42 |
March | 47411641.83 | 0.233695E+10 | 0.00 | 625227.34 | 55793426.25 | 0.00 | 7494022.14 | 0.00 | 0.43 |
April | 30146421.19 | 0.216062E+10 | 0.00 | 423400.57 | 57107064.13 | 0.00 | 2003330.22 | 0.00 | 0.42 |
May | 9255663.07 | 0.337039E+10 | 0.00 | 154728.08 | 0.113982E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 2741409.87 | 0.344795E+10 | 0.00 | 37780.90 | 0.114797E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 7699573.02 | 0.427308E+10 | 0.00 | 88586.84 | 0.151508E+09 | 0.00 | 95236.65 | 0.00 | 0.42 |
August | 1005916.63 | 0.460139E+10 | 0.00 | 163.23 | 0.155236E+09 | 0.00 | 8950.56 | 0.00 | 0.43 |
September | 3802806.66 | 0.434943E+10 | 0.00 | 11893.72 | 0.169659E+09 | 0.00 | 155846.85 | 0.00 | 0.42 |
October | 7006668.64 | 0.436265E+10 | 0.00 | 24036.86 | 0.172684E+09 | 0.00 | 68211.73 | 0.00 | 0.42 |
November | 8399277.84 | 0.319812E+10 | 0.00 | 150471.17 | 94608914.64 | 0.00 | 77826.77 | 0.00 | 0.42 |
December | 35992389.44 | 0.258852E+10 | 0.00 | 874304.90 | 74883658.45 | 0.00 | 1679618.93 | 0.00 | 0.42 |
Annual Sum or Average | 0.246901E+09 | 0.388053E+11 | 0.00 | 4224974.89 | 0.127745E+10 | 0.00 | 57656252.89 | 0.00 | 0.42 |
Minimum of Months | 1005916.63 | 0.173625E+10 | 0.00 | 163.23 | 35881714.08 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 57976238.42 | 0.460139E+10 | 0.00 | 1195502.88 | 0.172684E+09 | 0.00 | 31220710.32 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 57558617.25 | 0.172723E+10 | 0.00 | 1175156.37 | 35988412.55 | 0.00 | 31913342.49 | 0.00 | 0.42 |
February | 35204556.80 | 0.236783E+10 | 0.00 | 632281.56 | 81796189.63 | 0.00 | 15165044.23 | 0.00 | 0.42 |
March | 46973534.96 | 0.232602E+10 | 0.00 | 611948.52 | 56037209.35 | 0.00 | 7684113.49 | 0.00 | 0.43 |
April | 29698763.56 | 0.215150E+10 | 0.00 | 407561.98 | 57020662.81 | 0.00 | 2057289.38 | 0.00 | 0.42 |
May | 9083227.99 | 0.336002E+10 | 0.00 | 151124.65 | 0.114879E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 2718788.87 | 0.343758E+10 | 0.00 | 39252.38 | 0.115391E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 7697156.65 | 0.426389E+10 | 0.00 | 92129.91 | 0.151277E+09 | 0.00 | 101167.58 | 0.00 | 0.42 |
August | 1004312.85 | 0.459058E+10 | 0.00 | 179.26 | 0.156644E+09 | 0.00 | 9026.47 | 0.00 | 0.43 |
September | 3795774.33 | 0.433991E+10 | 0.00 | 12612.22 | 0.168877E+09 | 0.00 | 157328.59 | 0.00 | 0.42 |
October | 6924708.98 | 0.435115E+10 | 0.00 | 24487.71 | 0.174448E+09 | 0.00 | 70777.73 | 0.00 | 0.42 |
November | 8278572.92 | 0.318635E+10 | 0.00 | 146351.14 | 95876944.33 | 0.00 | 77093.29 | 0.00 | 0.42 |
December | 35673462.73 | 0.257876E+10 | 0.00 | 856734.06 | 74195180.59 | 0.00 | 1583422.79 | 0.00 | 0.42 |
Annual Sum or Average | 0.244611E+09 | 0.386808E+11 | 0.00 | 4149819.76 | 0.128243E+10 | 0.00 | 58818606.03 | 0.00 | 0.42 |
Minimum of Months | 1004312.85 | 0.172723E+10 | 0.00 | 179.26 | 35988412.55 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 57558617.25 | 0.459058E+10 | 0.00 | 1175156.37 | 0.174448E+09 | 0.00 | 31913342.49 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 55975541.99 | 0.171313E+10 | 0.00 | 1115552.75 | 36016236.82 | 0.00 | 33266821.69 | 0.00 | 0.42 |
February | 34312500.08 | 0.234833E+10 | 0.00 | 606676.58 | 82891989.21 | 0.00 | 15766543.77 | 0.00 | 0.42 |
March | 45413776.19 | 0.230776E+10 | 0.00 | 566319.32 | 56646011.00 | 0.00 | 8109727.29 | 0.00 | 0.43 |
April | 28316198.10 | 0.213776E+10 | 0.00 | 367517.31 | 57750595.83 | 0.00 | 2196611.22 | 0.00 | 0.42 |
May | 8547753.55 | 0.334972E+10 | 0.00 | 140197.40 | 0.116435E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 2542001.36 | 0.342827E+10 | 0.00 | 40882.66 | 0.117132E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 7663992.94 | 0.425262E+10 | 0.00 | 95309.45 | 0.156349E+09 | 0.00 | 51910.17 | 0.00 | 0.42 |
August | 976254.92 | 0.458280E+10 | 0.00 | 227.43 | 0.160313E+09 | 0.00 | 9931.31 | 0.00 | 0.43 |
September | 3743457.65 | 0.432966E+10 | 0.00 | 13342.20 | 0.172753E+09 | 0.00 | 161558.76 | 0.00 | 0.42 |
October | 6689040.66 | 0.434281E+10 | 0.00 | 25085.84 | 0.176891E+09 | 0.00 | 74595.85 | 0.00 | 0.42 |
November | 7937277.51 | 0.317304E+10 | 0.00 | 136824.87 | 97983266.47 | 0.00 | 74643.43 | 0.00 | 0.42 |
December | 34407374.78 | 0.256335E+10 | 0.00 | 813666.73 | 76098484.68 | 0.00 | 1674081.65 | 0.00 | 0.42 |
Annual Sum or Average | 0.236525E+09 | 0.385293E+11 | 0.00 | 3921602.55 | 0.130726E+10 | 0.00 | 61386425.13 | 0.00 | 0.42 |
Minimum of Months | 976254.92 | 0.171313E+10 | 0.00 | 227.43 | 36016236.82 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 55975541.99 | 0.458280E+10 | 0.00 | 1115552.75 | 0.176891E+09 | 0.00 | 33266821.69 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 67908253.20 | 0.171121E+10 | 0.00 | 1292928.01 | 26232164.63 | 0.00 | 37573461.55 | 0.00 | 0.42 |
February | 41157893.33 | 0.232711E+10 | 0.00 | 647641.62 | 60408787.28 | 0.00 | 18813466.46 | 0.00 | 0.42 |
March | 60169662.91 | 0.227920E+10 | 0.00 | 743574.43 | 43453242.42 | 0.00 | 11084322.20 | 0.00 | 0.43 |
April | 37670887.40 | 0.213883E+10 | 0.00 | 544968.96 | 42045333.78 | 0.00 | 2461544.31 | 0.00 | 0.42 |
May | 16230170.91 | 0.336957E+10 | 0.00 | 362271.97 | 79701648.72 | 0.00 | 356143.62 | 0.00 | 0.43 |
June | 8484704.31 | 0.344533E+10 | 0.00 | 231752.67 | 70525392.22 | 0.00 | 205580.44 | 0.00 | 0.43 |
July | 14149293.94 | 0.428760E+10 | 0.00 | 209350.59 | 0.106027E+09 | 0.00 | 440143.49 | 0.00 | 0.42 |
August | 7345488.59 | 0.462758E+10 | 0.00 | 65928.11 | 99787608.63 | 0.00 | 113850.15 | 0.00 | 0.43 |
September | 7506910.86 | 0.433774E+10 | 0.00 | 46607.73 | 0.122978E+09 | 0.00 | 276865.06 | 0.00 | 0.42 |
October | 11254032.39 | 0.438128E+10 | 0.00 | 81593.60 | 0.129211E+09 | 0.00 | 106085.00 | 0.00 | 0.42 |
November | 14741354.35 | 0.317037E+10 | 0.00 | 315945.66 | 62351720.57 | 0.00 | 289820.92 | 0.00 | 0.42 |
December | 43595671.01 | 0.256562E+10 | 0.00 | 926557.10 | 47873334.60 | 0.00 | 3502173.13 | 0.00 | 0.42 |
Annual Sum or Average | 0.330214E+09 | 0.386414E+11 | 0.00 | 5469120.44 | 0.890596E+09 | 0.00 | 75223456.33 | 0.00 | 0.42 |
Minimum of Months | 7345488.59 | 0.171121E+10 | 0.00 | 46607.73 | 26232164.63 | 0.00 | 106085.00 | 0.00 | 0.42 |
Maximum of Months | 67908253.20 | 0.462758E+10 | 0.00 | 1292928.01 | 0.129211E+09 | 0.00 | 37573461.55 | 0.00 | 0.43 |