Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:21
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2020-06-03 19:21:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1779.10 | 851.12 | 851.12 |
Net Site Energy | 1779.10 | 851.12 | 851.12 |
Total Source Energy | 5633.52 | 2695.05 | 2695.05 |
Net Source Energy | 5633.52 | 2695.05 | 2695.05 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 593.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 587.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 110.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 300.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 58.77 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1778.67 | 0.43 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 593.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 587.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 110.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 300.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 58.77 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 333.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 455.47 | 0.21 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 850.91 | 0.21 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 333.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 455.47 | 0.21 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 850.91 | 0.21 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1778.672 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1778.672 | 100.00 |
Total On-Site and Utility Electric Sources | 1778.672 | 100.00 |
Total Electricity End Uses | 1778.672 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 35.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1278.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 21.0784 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 22.5208 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.3680 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.3680 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.3680 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 15.8795 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 15.8795 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 15.8795 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 15.8795 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 15.8795 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 18.4215 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 18.4215 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 01-JUL-14:20 | 02-JAN-09:09 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 63785.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 87150.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 36581.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 17417.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7529.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 156768.41 | 63785.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 63785.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 87150.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 36581.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 17417.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7529.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.47 | 0.00 | 0.00 | 0.00 |
Cooling | 1878.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1859.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 350.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 950.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 186.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5633.05 | 0.47 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.22 | 0.00 | 0.00 | 0.00 |
Cooling | 898.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 889.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 167.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 454.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2694.83 | 0.22 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.22 | 0.00 | 0.00 | 0.00 |
Cooling | 898.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 889.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 167.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 454.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2694.83 | 0.22 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.62 |
SMSTORE1 DIRECT AIR | 1.37 |
SMSTORE2 DIRECT AIR | 1.37 |
SMSTORE3 DIRECT AIR | 1.37 |
SMSTORE4 DIRECT AIR | 1.37 |
LGSTORE2 DIRECT AIR | 2.49 |
SMSTORE5 DIRECT AIR | 1.32 |
SMSTORE6 DIRECT AIR | 1.31 |
SMSTORE7 DIRECT AIR | 1.31 |
SMSTORE8 DIRECT AIR | 1.42 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.62 | 2.62 | 2.62 | 2.62 | 2.62 | 2.62 | 1.00 | 1.00 | 2.62 |
PSZ-AC_2:2 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.00 | 1.00 | 1.37 |
PSZ-AC_3:3 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.00 | 1.00 | 1.37 |
PSZ-AC_4:4 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.00 | 1.00 | 1.37 |
PSZ-AC_5:5 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.00 | 1.00 | 1.37 |
PSZ-AC_6:6 | 2.49 | 2.49 | 2.49 | 2.49 | 2.49 | 2.49 | 1.00 | 1.00 | 2.49 |
PSZ-AC_7:7 | 1.32 | 1.32 | 1.32 | 1.32 | 1.32 | 1.32 | 1.00 | 1.00 | 1.32 |
PSZ-AC_8:8 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.00 | 1.00 | 1.31 |
PSZ-AC_9:9 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.00 | 1.00 | 1.31 |
PSZ-AC_10:10 | 1.42 | 1.42 | 1.42 | 1.42 | 1.42 | 1.42 | 1.00 | 1.00 | 1.42 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.62 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 1.37 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 1.37 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 1.37 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 1.37 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 2.49 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 1.32 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 1.31 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 1.31 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 1.42 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.62 | 2.62 | 2.62 | 2.62 | 53652.24 | 65614.05 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.37 | 1.37 | 1.37 | 1.37 | 27937.67 | 34220.05 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.37 | 1.37 | 1.37 | 1.37 | 27812.25 | 34062.11 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.37 | 1.37 | 1.37 | 1.37 | 27865.95 | 34128.98 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.37 | 1.37 | 1.37 | 1.37 | 27800.95 | 34047.51 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.49 | 2.49 | 2.49 | 2.49 | 51259.84 | 62610.90 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.32 | 1.32 | 1.32 | 1.32 | 26936.89 | 32964.00 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.31 | 1.31 | 1.31 | 1.31 | 26835.80 | 32837.47 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.31 | 1.31 | 1.31 | 1.31 | 26847.61 | 32852.10 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.42 | 1.42 | 1.42 | 1.42 | 28607.77 | 35184.59 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 2.62 | 1.31 | 2.62 | 43406.72 | 53652.24 | 26826.12 | 53652.24 | 0.728447 | 0.728450 | 0.728450 | 0.728450 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.37 | 0.687255 | 1.37 | 22753.02 | 27937.67 | 13968.83 | 27937.67 | 0.730426 | 0.730430 | 0.730430 | 0.730430 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.37 | 0.683710 | 1.37 | 22635.66 | 27812.25 | 13906.12 | 27812.25 | 0.730225 | 0.730230 | 0.730230 | 0.730230 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.37 | 0.685210 | 1.37 | 22685.32 | 27865.95 | 13932.98 | 27865.95 | 0.730303 | 0.730300 | 0.730300 | 0.730300 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.37 | 0.683385 | 1.37 | 22624.90 | 27800.95 | 13900.48 | 27800.95 | 0.730204 | 0.730200 | 0.730200 | 0.730200 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 2.49 | 1.24 | 2.49 | 41763.73 | 51259.84 | 25629.92 | 51259.84 | 0.726327 | 0.726330 | 0.726330 | 0.726330 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 1.32 | 0.659070 | 1.32 | 21847.52 | 26936.89 | 13468.44 | 26936.89 | 0.728815 | 0.728810 | 0.728810 | 0.728810 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 1.31 | 0.656230 | 1.31 | 21781.68 | 26835.80 | 13417.90 | 26835.80 | 0.728648 | 0.728650 | 0.728650 | 0.728650 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 1.31 | 0.656560 | 1.31 | 21789.59 | 26847.61 | 13423.81 | 26847.61 | 0.728667 | 0.728670 | 0.728670 | 0.728670 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.42 | 0.708900 | 1.42 | 23469.62 | 28607.77 | 14303.89 | 28607.77 | 0.732622 | 0.732620 | 0.732620 | 0.732620 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.62 | 2805.88 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.37 | 1521.80 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.37 | 1513.95 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.37 | 1517.27 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.37 | 1513.23 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.49 | 2661.66 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.32 | 1459.39 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.31 | 1453.10 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.31 | 1453.83 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.42 | 1517.11 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 65614.05 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 34220.05 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 34062.11 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 34128.98 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 34047.51 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 62610.90 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 32964.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 32837.47 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 32852.10 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 35184.59 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 21.078 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.378 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 22.521 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 26.821 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.368 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.668 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.368 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.668 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.368 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.668 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 5532.190 | 15.879 | 184.430 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5532.190 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 1811.251 | 5.199 | 60.383 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1811.251 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1156.875 | 6.641 | 77.135 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1156.875 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 5532.190 | 15.879 | 184.430 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5532.190 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.4678 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.903 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.37383775E-12 | 0.81582362E-15 | -0.12542534E-12 | 0.11541335E-15 |
23 | 6 | 0.32294454E-07 | 0.13597119E-09 | 0.73677206E-08 | -0.15476624E-12 |
24 | 5 | -0.20833553E-03 | 0.11386595E-05 | -0.10688959E-03 | 0.72710034E-08 |
25 | 4 | 0.31322919 | 0.54351077E-03 | 0.10727732 | -0.36571185E-04 |
26 | 3 | -7.6832781 | 0.16549290E-01 | -2.4626776 | 0.31053958E-01 |
27 | 2 | 42.245606 | 0.57933024E-01 | 15.771342 | -0.34865193 |
28 | 1 | -81.598353 | 0.25789083E-01 | -29.595166 | 1.1010509 |
29 | 0 | 46.824332 | 0.51189598E-03 | 16.280659 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 29 | 1 | VerySmooth | 2.843 | 0.252 | 0.162 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.16139 | 0.61114 | 0.61114 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.286 | 8.224E-004 | 4.530E-004 | 0.571 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 0.164 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.204 | 1.172E-003 | 5.440E-004 | 0.815 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 28946.21434 | 34735.45721 | 2.18517 | 2.62220 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 42.00000 | 9.11023E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 13297.51978 | 15957.02373 | 0.58810 | 0.70572 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 15173.02750 | 18207.63300 | 1.14543 | 1.37451 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 6889.00986 | 8266.81183 | 0.30467 | 0.36561 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 15094.79480 | 18113.75377 | 1.13952 | 1.36742 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 41.83833 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 6975.88327 | 8371.05993 | 0.30851 | 0.37022 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 15127.92604 | 18153.51125 | 1.14202 | 1.37042 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 41.83833 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 7041.21118 | 8449.45342 | 0.31140 | 0.37368 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 15087.56487 | 18105.07784 | 1.13897 | 1.36677 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 41.83833 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 7178.68231 | 8614.41877 | 0.31748 | 0.38098 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 27458.61861 | 32950.34233 | 2.07285 | 2.48742 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | 41.75750 | 9.11022E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 13506.72277 | 16208.06732 | 0.59735 | 0.71682 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 14550.84099 | 17461.00919 | 1.09845 | 1.31814 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | 41.75750 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 7350.47756 | 8820.57307 | 0.32508 | 0.39010 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 14488.15406 | 17385.78487 | 1.09372 | 1.31246 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | 41.75750 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 7344.78090 | 8813.73708 | 0.32483 | 0.38979 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 14495.40456 | 17394.48548 | 1.09426 | 1.31312 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | 41.75750 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 7508.22478 | 9009.86974 | 0.33206 | 0.39847 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 15651.51299 | 18781.81559 | 1.18150 | 1.41780 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 41.51500 | 9.11022E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 8243.77093 | 9892.52512 | 0.36459 | 0.43750 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 43082.10 | 2.62220 | 2.62220 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 22911.46 | 0.70572 | 0.70572 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 22368.76 | 1.37451 | 1.37451 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 11739.81 | 0.36561 | 0.36561 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 22271.89 | 1.36742 | 1.36742 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 11842.53 | 0.37022 | 0.37022 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 22309.73 | 1.37042 | 1.37042 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 11919.78 | 0.37368 | 0.37368 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 22261.43 | 1.36677 | 1.36677 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 12082.35 | 0.38098 | 0.38098 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 41294.44 | 2.48742 | 2.48742 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 23158.84 | 0.71682 | 0.71682 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 21616.88 | 1.31814 | 1.31814 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 12285.50 | 0.39010 | 0.39010 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 21542.51 | 1.31246 | 1.31246 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 12278.76 | 0.38979 | 0.38979 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 21550.51 | 1.31312 | 1.31312 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 12472.04 | 0.39847 | 0.39847 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 22845.94 | 1.41780 | 1.41780 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 13341.83 | 0.43750 | 0.43750 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.62220 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.37451 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.36742 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.37042 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.36677 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.48742 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.31814 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.31246 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.31312 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.41780 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.62220 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.62220 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.62220 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.62220 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.62220 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.62220 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.37451 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37451 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.37451 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.37451 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.37451 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.37451 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.36742 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36742 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.36742 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.36742 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.36742 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.36742 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.37042 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37042 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.37042 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.37042 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.37042 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.37042 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.36677 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36677 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.36677 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.36677 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.36677 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.36677 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.48742 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.48742 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.48742 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.48742 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.48742 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.48742 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.31814 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.31814 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.31814 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.31814 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.31814 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.31814 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.31246 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.31246 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.31246 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.31246 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.31246 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.31246 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.31312 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.31312 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.31312 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.31312 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.31312 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.31312 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.41780 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.41780 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.41780 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.41780 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.41780 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.41780 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.62220 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.37451 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.36742 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.37042 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.36677 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.48742 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.31814 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.31246 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.31312 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.41780 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.62220 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.62220 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.62220 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.62220 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.62220 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.62220 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.31110 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.62220 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 43406.72074 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 53652.24000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 26826.12000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 53652.24000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72845 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72845 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72845 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72845 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 53652.24000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 65614.05269 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.62220 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2805.87835 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 65614.05269 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.37451 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.37451 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.37451 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.37451 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.37451 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.37451 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68726 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.37451 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22753.02102 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 27937.67000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13968.83500 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 27937.67000 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73043 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73043 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73043 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73043 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27937.67000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34220.05388 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.37451 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1521.80093 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 34220.05388 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.36742 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.36742 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.36742 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.36742 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.36742 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.36742 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68371 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.36742 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22635.65635 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 27812.25000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13906.12500 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 27812.25000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73022 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73023 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73023 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73023 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27812.25000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34062.10922 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.36742 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1513.95172 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 34062.10922 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.37042 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.37042 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.37042 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.37042 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.37042 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.37042 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68521 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.37042 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22685.31700 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 27865.95000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13932.97500 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 27865.95000 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73030 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73030 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73030 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73030 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27865.95000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34128.98430 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.37042 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1517.27466 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 34128.98430 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.36677 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.36677 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.36677 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.36677 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.36677 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.36677 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68339 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.36677 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22624.89654 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 27800.95000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13900.47500 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 27800.95000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73020 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73020 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73020 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73020 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27800.95000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34047.50771 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.36677 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1513.22640 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 34047.50771 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.48742 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.48742 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.48742 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.48742 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.48742 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.48742 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.24371 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.48742 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 41763.72776 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 51259.84000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 25629.92000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 51259.84000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72633 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72633 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72633 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72633 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 51259.84000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 62610.90030 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.48742 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2661.65549 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 62610.90030 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.31814 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.31814 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.31814 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.31814 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.31814 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.31814 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65907 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.31814 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21847.52032 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26936.89000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13468.44500 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 26936.89000 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72881 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72881 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72881 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72881 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26936.89000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32964.00164 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.31814 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1459.38804 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32964.00164 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.31246 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.31246 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.31246 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.31246 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.31246 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.31246 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65623 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.31246 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21781.67937 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26835.80000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13417.90000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 26835.80000 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72865 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72865 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72865 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72865 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26835.80000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32837.46874 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.31246 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1453.10081 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32837.46874 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.31312 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.31312 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.31312 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.31312 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.31312 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.31312 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65656 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.31312 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21789.58764 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26847.61000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13423.80500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 26847.61000 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72867 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72867 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72867 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72867 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26847.61000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32852.09930 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.31312 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1453.82786 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32852.09930 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.41780 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.41780 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.41780 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.41780 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.41780 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.41780 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.70890 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.41780 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 23469.62423 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28607.77000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14303.88500 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 28607.77000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73262 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73262 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73262 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73262 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28607.77000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35184.59161 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.41780 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1517.10827 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 35184.59161 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 51590.8 | 10.94 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 26857.2 | 32.43 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 26737.3 | 43.68 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 26788.7 | 54.69 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 26726.5 | 65.92 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 49304.1 | 46.22 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 25900.6 | 100.33 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 25804.0 | 111.83 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 25815.3 | 122.89 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 27493.4 | 126.25 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 13 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 7.0135181185E-002 | 8.1279572370E-002 | Pass | Pass | 3.5915949710E-002 | 0.1130822385 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.4461193932E-002 | 8.5774162031E-002 | Pass | Pass | 5.5020667781E-002 | 0.1574204646 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 6.6882423608E-002 | 0.1042236942 | Pass | Pass | 6.0521876749E-002 | 0.2070230014 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 6.8310714020E-002 | 0.1393850801 | Pass | Pass | 0.1582797770 | 0.8425716873 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 6.9083969531E-002 | 0.1722731456 | Pass | Pass | 0.1793061124 | 1.0238376280 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 5.2509677705E-002 | 0.1535761585 | Pass | Pass | 0.4184388008 | 3.0786092094 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.9941250692E-002 | 0.1554361396 | Pass | Pass | 0.5719878629 | 4.0963783217 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.8541728616E-002 | 0.1587780751 | Pass | Pass | 0.3376679142 | 1.2009051342 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.7137989242E-002 | 0.1716376853 | Pass | Pass | 0.5327127261 | 2.9137508778 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 5.0351535684E-002 | 0.1961591061 | Pass | Pass | 0.3927002434 | 1.6008100803 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.843 | 0.252 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.843 | 0.252 | 0.251 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.843 | 0.252 | 0.251 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 15.8795 | 348.39 | 5532.19 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 102.16 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 5.1990 | 348.39 | 1811.25 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 33.45 |
SMSTORE1_LIGHTS | SMSTORE1 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 51.08 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 6.6413 | 174.19 | 1156.88 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 21.36 |
SMSTORE2_LIGHTS | SMSTORE2 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 40.48 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
SMSTORE3_LIGHTS | SMSTORE3 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 40.48 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
SMSTORE4_LIGHTS | SMSTORE4 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 40.48 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
LGSTORE2_LIGHTS | LGSTORE2 | 15.8795 | 348.39 | 5532.19 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 74.42 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.21 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.21 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.21 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.21 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 9.2108 | 4180.64 | 38506.89 | 587.06 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7048.38 | AstronomicalClock | - | 83.75 | 83.75 | 110.81 | |
Exterior Lighting Total | 7048.38 | 110.81 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 53652.24 | 39082.97 | 14569.27 | 0.73 | 3.73 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 27937.67 | 20406.51 | 7531.16 | 0.73 | 3.80 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 27812.25 | 20309.34 | 7502.91 | 0.73 | 3.80 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 27865.95 | 20350.50 | 7515.45 | 0.73 | 3.80 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 27800.95 | 20300.25 | 7500.70 | 0.73 | 3.80 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 51259.84 | 37231.56 | 14028.28 | 0.73 | 3.73 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26936.89 | 19631.87 | 7305.02 | 0.73 | 3.80 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26835.80 | 19553.91 | 7281.89 | 0.73 | 3.80 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26847.61 | 19563.05 | 7284.56 | 0.73 | 3.80 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28607.77 | 20958.62 | 7649.15 | 0.73 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 51590.8 | 10.94 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 26857.2 | 32.43 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 26737.3 | 43.68 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 26788.7 | 54.69 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 26726.5 | 65.92 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 49304.1 | 46.22 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 25900.6 | 100.33 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 25804.0 | 111.83 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 25815.3 | 122.89 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 27493.4 | 126.25 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 65614.05 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 34220.05 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 34062.11 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 34128.98 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 34047.51 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 62610.90 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32964.00 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32837.47 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32852.10 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 35184.59 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.62 | 2805.88 | 1070.05 | 1.00 | 1.28 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.37 | 1521.80 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.37 | 1513.95 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.37 | 1517.27 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.37 | 1513.23 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.49 | 2661.66 | 1070.05 | 1.00 | 1.29 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.32 | 1459.39 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.31 | 1453.10 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.31 | 1453.83 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.42 | 1517.11 | 1070.05 | 1.00 | 1.37 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 28946.21 | 34735.46 | 99.70 | 2.185 | 2.622 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 23.89 | 23.89 | 0.00750 | 42.00 | 0.00911 | 0.411 | 0.00 |
SMSTORE1 | 15173.03 | 18207.63 | 104.53 | 1.145 | 1.375 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00751 | 41.92 | 0.00911 | 0.206 | 0.00 |
SMSTORE2 | 15094.79 | 18113.75 | 103.99 | 1.140 | 1.367 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 23.89 | 23.89 | 0.00751 | 41.84 | 0.00911 | 0.206 | 0.00 |
SMSTORE3 | 15127.93 | 18153.51 | 104.21 | 1.142 | 1.370 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 23.89 | 23.89 | 0.00751 | 41.84 | 0.00911 | 0.206 | 0.00 |
SMSTORE4 | 15087.56 | 18105.08 | 103.94 | 1.139 | 1.367 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 23.89 | 23.89 | 0.00751 | 41.84 | 0.00911 | 0.206 | 0.00 |
LGSTORE2 | 27458.62 | 32950.34 | 94.58 | 2.073 | 2.487 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | 23.89 | 23.89 | 0.00752 | 41.76 | 0.00911 | 0.411 | 0.00 |
SMSTORE5 | 14550.84 | 17461.01 | 100.24 | 1.098 | 1.318 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | 23.89 | 23.89 | 0.00753 | 41.76 | 0.00911 | 0.206 | 0.00 |
SMSTORE6 | 14488.15 | 17385.78 | 99.81 | 1.094 | 1.312 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | 23.89 | 23.89 | 0.00753 | 41.76 | 0.00911 | 0.206 | 0.00 |
SMSTORE7 | 14495.40 | 17394.49 | 99.86 | 1.094 | 1.313 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | 23.89 | 23.89 | 0.00753 | 41.76 | 0.00911 | 0.206 | 0.00 |
SMSTORE8 | 15651.51 | 18781.82 | 107.82 | 1.181 | 1.418 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 23.89 | 23.89 | 0.00750 | 41.52 | 0.00911 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 13297.52 | 15957.02 | 45.80 | 0.588 | 0.706 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00732 | 6.30 | 0.00607 | 0.411 | 0.00 |
SMSTORE1 | 6889.01 | 8266.81 | 47.46 | 0.305 | 0.366 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00726 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE2 | 6975.88 | 8371.06 | 48.06 | 0.309 | 0.370 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00726 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE3 | 7041.21 | 8449.45 | 48.51 | 0.311 | 0.374 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00727 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE4 | 7178.68 | 8614.42 | 49.45 | 0.317 | 0.381 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00728 | 6.30 | 0.00607 | 0.206 | 0.00 |
LGSTORE2 | 13506.72 | 16208.07 | 46.52 | 0.597 | 0.717 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00732 | 6.30 | 0.00607 | 0.411 | 0.00 |
SMSTORE5 | 7350.48 | 8820.57 | 50.64 | 0.325 | 0.390 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00728 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE6 | 7344.78 | 8813.74 | 50.60 | 0.325 | 0.390 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00728 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE7 | 7508.22 | 9009.87 | 51.72 | 0.332 | 0.398 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00729 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE8 | 8243.77 | 9892.53 | 56.79 | 0.365 | 0.438 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00732 | 6.30 | 0.00607 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.62 | 2.62 | 0.71 | 0.71 | 2.6222 | 2.6222 | 2.6222 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.37 | 1.37 | 0.37 | 0.37 | 1.3745 | 1.3745 | 1.3745 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.37 | 1.37 | 0.37 | 0.37 | 1.3674 | 1.3674 | 1.3674 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.37 | 1.37 | 0.37 | 0.37 | 1.3704 | 1.3704 | 1.3704 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.37 | 1.37 | 0.38 | 0.38 | 1.3668 | 1.3668 | 1.3668 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.49 | 2.49 | 0.72 | 0.72 | 2.4874 | 2.4874 | 2.4874 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.32 | 1.32 | 0.39 | 0.39 | 1.3181 | 1.3181 | 1.3181 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.31 | 1.31 | 0.39 | 0.39 | 1.3125 | 1.3125 | 1.3125 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.31 | 1.31 | 0.40 | 0.40 | 1.3131 | 1.3131 | 1.3131 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.42 | 1.42 | 0.44 | 0.44 | 1.4178 | 1.4178 | 1.4178 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 53652.240 | 0.000 | 2.622200 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 53652.24 | 53652.24 | 2.622200 | 26.73 | 16.43 | 0.00775404 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 15.6912 | 23.89 | 0.00750164 | 39.6930 | 28946.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 65614.053 | 65614.053 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 65614.05 | 65614.05 | 2.622200 | 12.47 | 9.75 | 0.00659140 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.6912 | 21.11 | 0.00731717 | 45.8531 | 13297.52 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 27937.670 | 0.000 | 1.374510 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 27937.67 | 27937.67 | 1.374510 | 26.60 | 16.38 | 0.00774894 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 14.9673 | 23.89 | 0.00750924 | 39.7329 | 15171.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 34220.054 | 34220.054 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34220.05 | 34220.05 | 1.374510 | 12.78 | 9.89 | 0.00659239 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.9673 | 21.11 | 0.00726157 | 45.5091 | 6889.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 27812.250 | 0.000 | 1.367420 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 27812.25 | 27812.25 | 1.367420 | 26.61 | 16.39 | 0.00775225 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 15.0449 | 23.89 | 0.00751126 | 39.7434 | 15090.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 34062.109 | 34062.109 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34062.11 | 34062.11 | 1.367421 | 12.88 | 9.94 | 0.00660200 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.0449 | 21.11 | 0.00726444 | 45.5270 | 6975.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 27865.950 | 0.000 | 1.370420 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 27865.95 | 27865.95 | 1.370420 | 26.61 | 16.38 | 0.00775097 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 15.0119 | 23.89 | 0.00751032 | 39.7385 | 15121.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 34128.984 | 34128.984 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34128.98 | 34128.98 | 1.370422 | 12.96 | 9.98 | 0.00660975 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.0119 | 21.11 | 0.00726800 | 45.5490 | 7041.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 27800.950 | 0.000 | 1.366770 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 27800.95 | 27800.95 | 1.366770 | 26.61 | 16.39 | 0.00775261 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 15.0520 | 23.89 | 0.00751148 | 39.7446 | 15081.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 34047.508 | 34047.508 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34047.51 | 34047.51 | 1.366766 | 13.11 | 10.07 | 0.00662596 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.0521 | 21.11 | 0.00727584 | 45.5976 | 7178.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 51259.840 | 0.000 | 2.487420 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | 51259.84 | 51259.84 | 2.487420 | 26.89 | 16.51 | 0.00778461 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 16.5414 | 23.89 | 0.00752056 | 39.7919 | 27437.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 62610.900 | 62610.900 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 62610.90 | 62610.90 | 2.487419 | 12.61 | 9.83 | 0.00660502 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 16.5414 | 21.11 | 0.00732276 | 45.8878 | 13506.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 26936.890 | 0.000 | 1.318140 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | 26936.89 | 26936.89 | 1.318140 | 26.72 | 16.44 | 0.00777523 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 15.6073 | 23.89 | 0.00752692 | 39.8253 | 14537.10 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 32964.002 | 32964.002 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32964.00 | 32964.00 | 1.318138 | 13.30 | 10.17 | 0.00664506 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.6074 | 21.11 | 0.00728412 | 45.6489 | 7350.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 26835.800 | 0.000 | 1.312460 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | 26835.80 | 26835.80 | 1.312460 | 26.73 | 16.45 | 0.00777792 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 15.6749 | 23.89 | 0.00752883 | 39.8353 | 14474.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 32837.469 | 32837.469 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32837.47 | 32837.47 | 1.312459 | 13.29 | 10.17 | 0.00664445 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.6749 | 21.11 | 0.00728387 | 45.6474 | 7344.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 26847.610 | 0.000 | 1.313120 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | 26847.61 | 26847.61 | 1.313120 | 26.73 | 16.45 | 0.00777763 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00911023 | 22.20 | 15.6670 | 23.89 | 0.00752861 | 39.8341 | 14481.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 32852.099 | 32852.099 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32852.10 | 32852.10 | 1.313116 | 13.46 | 10.26 | 0.00666246 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.6671 | 21.11 | 0.00729233 | 45.6998 | 7508.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 28607.770 | 0.000 | 1.417800 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 28607.77 | 28607.77 | 1.417800 | 26.50 | 16.33 | 0.00773767 | 12.80 | 11.87 | 0.00850000 | 41.84 | 0.00911022 | 22.15 | 14.5103 | 23.89 | 0.00750320 | 39.7013 | 15565.35 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 35184.592 | 35184.592 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35184.59 | 35184.59 | 1.417796 | 14.15 | 10.63 | 0.00673469 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.5103 | 21.11 | 0.00732259 | 45.8874 | 8243.77 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 53652.240 | 0.000 | 2.622200 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2544 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 53652.24 | 53652.24 | 1.0000 | 3.07790023 | 2.622200 | 26.73 | 16.43 | 0.00775404 | 46636.6 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 53652.24 | 42.00 | 0.00911023 | 22.20 | 0.41145340 | 15.6912 | 23.89 | 0.00750164 | 23.89 | 0.00750164 | 39.6930 | 28946.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 65614.053 | 65614.053 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.622200 | 3.07790067 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 65614.05 | 65614.05 | 1.0000 | 3.07790067 | 2.622200 | 12.47 | 9.75 | 0.00659140 | 29172.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 65614.05 | 6.30 | 0.00607234 | 6.30 | 0.41145340 | 15.6912 | 21.11 | 0.00731717 | 21.11 | 0.00731717 | 45.8531 | 13297.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27937.670 | 0.000 | 1.374510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2449 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 27937.67 | 27937.67 | 1.0000 | 1.61337985 | 1.374510 | 26.60 | 16.38 | 0.00774894 | 46490.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27937.67 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 14.9673 | 23.89 | 0.00750930 | 23.89 | 0.00750924 | 39.7329 | 15171.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34220.054 | 34220.054 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.374510 | 1.61338003 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34220.05 | 34220.05 | 1.0000 | 1.61338003 | 1.374510 | 12.78 | 9.89 | 0.00659239 | 29481.5 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34220.05 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 14.9673 | 21.11 | 0.00726157 | 21.11 | 0.00726157 | 45.5091 | 6889.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27812.250 | 0.000 | 1.367420 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2510 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 27812.25 | 27812.25 | 1.0000 | 1.60505771 | 1.367420 | 26.61 | 16.39 | 0.00775225 | 46513.6 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27812.25 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 15.0449 | 23.89 | 0.00751167 | 23.89 | 0.00751126 | 39.7434 | 15090.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34062.109 | 34062.109 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.367421 | 1.60505848 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34062.11 | 34062.11 | 1.0000 | 1.60505848 | 1.367421 | 12.88 | 9.94 | 0.00660200 | 29611.3 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34062.11 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 15.0449 | 21.11 | 0.00726444 | 21.11 | 0.00726444 | 45.5270 | 6975.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27865.950 | 0.000 | 1.370420 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2487 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 27865.95 | 27865.95 | 1.0000 | 1.60857907 | 1.370420 | 26.61 | 16.38 | 0.00775097 | 46504.4 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27865.95 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 15.0119 | 23.89 | 0.00751076 | 23.89 | 0.00751032 | 39.7385 | 15121.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34128.984 | 34128.984 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.370422 | 1.60858138 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34128.98 | 34128.98 | 1.0000 | 1.60858138 | 1.370422 | 12.96 | 9.98 | 0.00660975 | 29708.5 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34128.98 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 15.0119 | 21.11 | 0.00726800 | 21.11 | 0.00726800 | 45.5490 | 7041.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27800.950 | 0.000 | 1.366770 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2517 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | 27800.95 | 27800.95 | 1.0000 | 1.60429475 | 1.366770 | 26.61 | 16.39 | 0.00775261 | 46516.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27800.95 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 15.0520 | 23.89 | 0.00751193 | 23.89 | 0.00751148 | 39.7446 | 15081.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34047.508 | 34047.508 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.366766 | 1.60428951 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34047.51 | 34047.51 | 1.0000 | 1.60428951 | 1.366766 | 13.11 | 10.07 | 0.00662596 | 29908.3 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34047.51 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 15.0521 | 21.11 | 0.00727584 | 21.11 | 0.00727584 | 45.5976 | 7178.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 51259.840 | 0.000 | 2.487420 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3112 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | 51259.84 | 51259.84 | 1.0000 | 2.91969743 | 2.487420 | 26.89 | 16.51 | 0.00778461 | 46873.9 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51259.84 | 42.00 | 0.00911023 | 22.20 | 0.41145340 | 16.5414 | 23.89 | 0.00752163 | 23.89 | 0.00752056 | 39.7919 | 27437.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 62610.900 | 62610.900 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.487419 | 2.91969579 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 62610.90 | 62610.90 | 1.0000 | 2.91969579 | 2.487419 | 12.61 | 9.83 | 0.00660502 | 29343.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62610.90 | 6.30 | 0.00607234 | 6.30 | 0.41145340 | 16.5414 | 21.11 | 0.00732276 | 21.11 | 0.00732276 | 45.8878 | 13506.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26936.890 | 0.000 | 1.318140 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2938 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | 26936.89 | 26936.89 | 1.0000 | 1.54721357 | 1.318140 | 26.72 | 16.44 | 0.00777523 | 46677.9 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26936.89 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 15.6073 | 23.89 | 0.00752806 | 23.89 | 0.00752692 | 39.8253 | 14537.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32964.002 | 32964.002 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.318138 | 1.54721126 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32964.00 | 32964.00 | 1.0000 | 1.54721126 | 1.318138 | 13.30 | 10.17 | 0.00664506 | 30146.6 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32964.00 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 15.6074 | 21.11 | 0.00728412 | 21.11 | 0.00728412 | 45.6489 | 7350.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26835.800 | 0.000 | 1.312460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2988 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | 26835.80 | 26835.80 | 1.0000 | 1.54054647 | 1.312460 | 26.73 | 16.45 | 0.00777792 | 46697.2 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26835.80 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 15.6749 | 23.89 | 0.00752999 | 23.89 | 0.00752883 | 39.8353 | 14474.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32837.469 | 32837.469 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.312459 | 1.54054567 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32837.47 | 32837.47 | 1.0000 | 1.54054567 | 1.312459 | 13.29 | 10.17 | 0.00664445 | 30138.9 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32837.47 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 15.6749 | 21.11 | 0.00728387 | 21.11 | 0.00728387 | 45.6474 | 7344.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26847.610 | 0.000 | 1.313120 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2982 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | 26847.61 | 26847.61 | 1.0000 | 1.54132116 | 1.313120 | 26.73 | 16.45 | 0.00777763 | 46695.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26847.61 | 42.00 | 0.00911023 | 22.20 | 0.20572670 | 15.6670 | 23.89 | 0.00752978 | 23.89 | 0.00752861 | 39.8341 | 14481.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32852.099 | 32852.099 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.313116 | 1.54131647 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32852.10 | 32852.10 | 1.0000 | 1.54131647 | 1.313116 | 13.46 | 10.26 | 0.00666246 | 30357.5 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32852.10 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 15.6671 | 21.11 | 0.00729233 | 21.11 | 0.00729233 | 45.6998 | 7508.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28607.770 | 0.000 | 1.417800 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2239 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 28607.77 | 28607.77 | 1.0000 | 1.66419303 | 1.417800 | 26.50 | 16.33 | 0.00773767 | 46360.3 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28607.77 | 41.84 | 0.00911022 | 22.15 | 0.20572670 | 14.5103 | 23.89 | 0.00750395 | 23.89 | 0.00750320 | 39.7013 | 15565.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35184.592 | 35184.592 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.417796 | 1.66418782 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35184.59 | 35184.59 | 1.0000 | 1.66418782 | 1.417796 | 14.15 | 10.63 | 0.00673469 | 31233.9 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35184.59 | 6.30 | 0.00607234 | 6.30 | 0.20572670 | 14.5103 | 21.11 | 0.00732259 | 21.11 | 0.00732259 | 45.8874 | 8243.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 4656.67 | 1297.67 | 1074.33 |
SMSTORE1 | 4561.67 | 1040.50 | 885.33 |
SMSTORE2 | 3485.17 | 1115.50 | 945.67 |
SMSTORE3 | 3460.83 | 1125.00 | 936.67 |
SMSTORE4 | 3405.67 | 1164.67 | 946.50 |
LGSTORE2 | 3020.33 | 1122.00 | 888.50 |
SMSTORE5 | 2899.00 | 1152.17 | 892.50 |
SMSTORE6 | 2873.33 | 1174.83 | 898.00 |
SMSTORE7 | 2843.83 | 1207.00 | 896.67 |
SMSTORE8 | 2851.67 | 1219.17 | 846.33 |
Facility | 4794.00 | 1795.33 | 1278.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 15.17 | 0.00 | 15.17 |
SMSTORE1 | 0.00 | 7.33 | 0.00 | 7.33 |
SMSTORE2 | 0.00 | 15.83 | 0.00 | 15.83 |
SMSTORE3 | 0.00 | 16.00 | 0.00 | 16.00 |
SMSTORE4 | 0.00 | 15.83 | 0.00 | 15.83 |
LGSTORE2 | 0.00 | 17.83 | 0.00 | 17.83 |
SMSTORE5 | 0.00 | 16.67 | 0.00 | 16.67 |
SMSTORE6 | 0.00 | 16.67 | 0.00 | 16.67 |
SMSTORE7 | 0.00 | 16.67 | 0.00 | 16.67 |
SMSTORE8 | 0.00 | 16.33 | 0.00 | 16.33 |
Facility | 0.00 | 35.67 | 0.00 | 35.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.848 | 0.340 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.688 | 0.379 | 0.000 | 0.000 |
SMSTORE2 | 3.77 | 15.00 | 902.60 | 0.848 | 0.499 | 0.000 | 0.000 |
SMSTORE3 | 3.77 | 15.00 | 902.60 | 0.848 | 0.499 | 0.000 | 0.000 |
SMSTORE4 | 3.77 | 15.00 | 902.60 | 0.848 | 0.499 | 0.000 | 0.000 |
LGSTORE2 | 13.20 | 30.00 | 1805.20 | 0.848 | 0.466 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 0.848 | 0.532 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 0.848 | 0.532 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 0.848 | 0.532 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 0.848 | 0.547 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.783 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.77 | 15.00 | 902.60 | 0.782 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.77 | 15.00 | 902.60 | 0.782 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.77 | 15.00 | 902.60 | 0.781 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.20 | 30.00 | 1805.20 | 0.782 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 0.782 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 0.782 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 0.781 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 0.780 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1778.67 | 3592.76 | 01-JAN-07:20 | 156768.41 | 01-JUL-14:20 |
Electricity:Building | 715.79 | 2374.76 | 01-JAN-00:10 | 44671.08 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 161.97 | 442.08 | 01-JAN-00:10 | 8324.52 | 01-JAN-10:10 |
InteriorLights:Electricity | 587.07 | 1925.34 | 01-JAN-00:10 | 36581.55 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 135.61 | 367.17 | 01-JAN-00:10 | 6976.27 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 587.07 | 1925.34 | 01-JAN-00:10 | 36581.55 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 85.62 | 233.60 | 01-JAN-00:10 | 4400.95 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 72.45 | 196.15 | 01-JAN-00:10 | 3726.82 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 62.39 | 214.85 | 01-JAN-00:10 | 4044.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 51.92 | 177.40 | 01-JAN-00:10 | 3370.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 62.39 | 214.85 | 01-JAN-00:10 | 4044.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 51.92 | 177.40 | 01-JAN-00:10 | 3370.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 62.39 | 214.85 | 01-JAN-00:10 | 4044.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 51.92 | 177.40 | 01-JAN-00:10 | 3370.57 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 93.68 | 351.51 | 01-JAN-00:10 | 6603.84 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 74.42 | 276.61 | 01-JAN-00:10 | 5255.58 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 46.84 | 175.76 | 01-JAN-00:10 | 3301.92 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 37.21 | 138.30 | 01-JAN-00:10 | 2627.79 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 46.84 | 175.76 | 01-JAN-00:10 | 3301.92 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 37.21 | 138.30 | 01-JAN-00:10 | 2627.79 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 46.84 | 175.76 | 01-JAN-00:10 | 3301.92 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 37.21 | 138.30 | 01-JAN-00:10 | 2627.79 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 46.84 | 175.76 | 01-JAN-00:10 | 3301.92 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 37.21 | 138.30 | 01-JAN-00:10 | 2627.79 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
Electricity:Plant | 58.77 | 1218.00 | 01-JAN-10:10 | 11816.20 | 11-JAN-13:50 |
WaterSystems:Electricity | 58.77 | 1218.00 | 01-JAN-10:10 | 11816.20 | 11-JAN-13:50 |
Water Heater:WaterSystems:Electricity | 58.77 | 1218.00 | 01-JAN-10:10 | 11816.20 | 11-JAN-13:50 |
ElectricityPurchased:Facility | 1778.67 | 3592.76 | 01-JAN-07:20 | 156768.41 | 01-JUL-14:20 |
ElectricityPurchased:Plant | 1778.67 | 3592.76 | 01-JAN-07:20 | 156768.41 | 01-JUL-14:20 |
Cogeneration:ElectricityPurchased | 1778.67 | 3592.76 | 01-JAN-07:20 | 156768.41 | 01-JUL-14:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1778.67 | 3592.76 | 01-JAN-07:20 | 156768.41 | 01-JUL-14:20 |
ElectricityNet:Plant | 1778.67 | 3592.76 | 01-JAN-07:20 | 156768.41 | 01-JUL-14:20 |
Cogeneration:ElectricityNet | 1778.67 | 3592.76 | 01-JAN-07:20 | 156768.41 | 01-JUL-14:20 |
Electricity:HVAC | 893.30 | 0.00 | 01-JAN-00:10 | 106812.00 | 10-JUN-16:00 |
Fans:Electricity | 300.06 | 0.00 | 01-JAN-00:10 | 17417.21 | 01-JAN-09:10 |
General:Fans:Electricity | 300.06 | 0.00 | 01-JAN-00:10 | 17417.21 | 01-JAN-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 593.24 | 0.00 | 01-JAN-00:10 | 89394.78 | 10-JUN-16:00 |
ExteriorLights:Electricity | 110.81 | 0.00 | 01-JAN-07:20 | 7048.38 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 110.81 | 0.00 | 01-JAN-07:20 | 7048.38 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 0.43 | 0.00 | 01-JAN-00:10 | 63785.83 | 02-JAN-09:10 |
Gas:HVAC | 0.43 | 0.00 | 01-JAN-00:10 | 63785.83 | 02-JAN-09:10 |
Heating:Gas | 0.43 | 0.00 | 01-JAN-00:10 | 63785.83 | 02-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 3178.62 | 0.00 | 01-JAN-00:10 | 451489.77 | 01-JUL-15:00 |
EnergyTransfer:Building | 1080.66 | 0.00 | 01-JAN-00:10 | 155397.64 | 12-JUN-14:20 |
EnergyTransfer:Zone:LGSTORE1 | 221.38 | 0.00 | 01-JAN-00:10 | 25246.94 | 08-JUN-16:10 |
Heating:EnergyTransfer | 11.32 | 0.00 | 01-JAN-00:10 | 42392.48 | 10-JUN-17:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.47 | 0.00 | 01-JAN-00:10 | 2892.53 | 11-APR-08:20 |
Cooling:EnergyTransfer | 1069.34 | 0.00 | 01-JAN-00:10 | 155397.64 | 12-JUN-14:20 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 220.91 | 0.00 | 01-JAN-00:10 | 25246.94 | 08-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 116.66 | 0.00 | 01-JAN-00:10 | 12930.11 | 08-JUN-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.24 | 0.00 | 01-JAN-00:10 | 1443.13 | 26-APR-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 116.42 | 0.00 | 01-JAN-00:10 | 12930.11 | 08-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE2 | 90.55 | 0.00 | 01-JAN-00:10 | 13114.61 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.85 | 0.00 | 01-JAN-00:10 | 4717.74 | 10-JUN-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 88.70 | 0.00 | 01-JAN-00:10 | 13114.61 | 12-JUN-14:00 |
EnergyTransfer:Zone:SMSTORE3 | 90.76 | 0.00 | 01-JAN-00:10 | 13271.32 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.83 | 0.00 | 01-JAN-00:10 | 4715.66 | 10-JUN-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 88.93 | 0.00 | 01-JAN-00:10 | 13271.32 | 12-JUN-14:00 |
EnergyTransfer:Zone:SMSTORE4 | 89.10 | 0.00 | 01-JAN-00:10 | 13260.05 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.88 | 0.00 | 01-JAN-00:10 | 5267.17 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 87.21 | 0.00 | 01-JAN-00:10 | 13260.05 | 12-JUN-14:00 |
EnergyTransfer:Zone:LGSTORE2 | 152.40 | 0.00 | 01-JAN-00:10 | 24711.10 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.51 | 0.00 | 01-JAN-00:10 | 11214.71 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 150.89 | 0.00 | 01-JAN-00:10 | 24711.10 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE5 | 79.39 | 0.00 | 01-JAN-00:10 | 13206.94 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.86 | 0.00 | 01-JAN-00:10 | 5747.12 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 78.53 | 0.00 | 01-JAN-00:10 | 13206.94 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE6 | 78.63 | 0.00 | 01-JAN-00:10 | 13157.61 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.87 | 0.00 | 01-JAN-00:10 | 6095.10 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 77.76 | 0.00 | 01-JAN-00:10 | 13157.61 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE7 | 77.90 | 0.00 | 01-JAN-00:10 | 13212.60 | 12-JUN-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.90 | 0.00 | 01-JAN-00:10 | 6775.96 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 76.99 | 0.00 | 01-JAN-00:10 | 13212.60 | 12-JUN-14:10 |
EnergyTransfer:Zone:SMSTORE8 | 83.90 | 0.00 | 01-JAN-00:10 | 14657.68 | 12-JUN-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.90 | 0.00 | 01-JAN-00:10 | 7340.63 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 82.99 | 0.00 | 01-JAN-00:10 | 14657.68 | 12-JUN-13:00 |
EnergyTransfer:HVAC | 2097.97 | 0.00 | 01-JAN-00:10 | 327259.08 | 01-JUL-16:00 |
HeatingCoils:EnergyTransfer | 0.34 | 0.00 | 01-JAN-00:10 | 51028.67 | 02-JAN-09:10 |
CoolingCoils:EnergyTransfer | 2097.62 | 0.00 | 01-JAN-00:10 | 327259.08 | 01-JUL-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.469 | -220.905 | 0.000 | 0.000 | 12.379 | 135.611 | 26.357 | 19.854 | 0.000 | 25.816 | 10.859 | 0.000 | -4.721 | 0.000 | -5.720 | -0.001 |
SMSTORE1 | 0.000 | 0.000 | 0.236 | -116.418 | 0.000 | 0.000 | 6.188 | 72.445 | 13.179 | 9.945 | 0.000 | 14.358 | 5.465 | 0.000 | -2.382 | 0.000 | -3.015 | -0.000 |
SMSTORE2 | 0.000 | 0.000 | 1.849 | -88.701 | 0.000 | 0.000 | 3.717 | 51.921 | 10.467 | 9.770 | 0.000 | 14.190 | 2.349 | 0.000 | -2.482 | 0.000 | -3.081 | -0.001 |
SMSTORE3 | 0.000 | 0.000 | 1.835 | -88.927 | 0.000 | 0.000 | 3.718 | 51.921 | 10.467 | 9.759 | 0.000 | 14.184 | 2.594 | 0.000 | -2.480 | 0.000 | -3.072 | -0.002 |
SMSTORE4 | 0.000 | 0.000 | 1.885 | -87.210 | 0.000 | 0.000 | 3.719 | 51.921 | 10.467 | 9.775 | 0.000 | 14.189 | 0.759 | 0.000 | -2.451 | 0.000 | -3.054 | -0.001 |
LGSTORE2 | 0.000 | 0.000 | 1.510 | -150.883 | 0.000 | 0.000 | 12.773 | 74.416 | 19.261 | 19.596 | 0.000 | 24.869 | 8.630 | 0.000 | -4.751 | 0.000 | -5.421 | -0.000 |
SMSTORE5 | 0.000 | 0.000 | 0.857 | -78.531 | 0.000 | 0.000 | 6.387 | 37.208 | 9.631 | 9.827 | 0.000 | 14.161 | 5.857 | 0.000 | -2.353 | 0.000 | -3.043 | -0.000 |
SMSTORE6 | 0.000 | 0.000 | 0.874 | -77.757 | 0.000 | 0.000 | 6.387 | 37.208 | 9.631 | 9.838 | 0.000 | 14.163 | 5.032 | 0.000 | -2.342 | 0.000 | -3.034 | -0.001 |
SMSTORE7 | 0.000 | 0.000 | 0.904 | -76.989 | 0.000 | 0.000 | 6.390 | 37.208 | 9.631 | 9.842 | 0.000 | 14.164 | 4.187 | 0.000 | -2.323 | 0.000 | -3.013 | -0.001 |
SMSTORE8 | 0.000 | 0.000 | 0.901 | -82.991 | 0.000 | 0.000 | 6.393 | 37.208 | 9.631 | 9.793 | 0.000 | 14.785 | 10.005 | 0.000 | -2.279 | 0.000 | -3.446 | -0.001 |
Total Facility | 0.000 | 0.000 | 11.320 | -1069.312 | 0.000 | 0.000 | 68.051 | 587.066 | 128.721 | 118.000 | 0.000 | 164.879 | 55.737 | 0.000 | -28.563 | 0.000 | -35.899 | -0.009 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 08-APR-08:61 | 0.00 | 0.00 | 0.00 | -46814.61 | 0.00 | 0.00 | 84.67 | 3671.72 | 749.03 | 389.96 | 0.00 | 28.76 | 41890.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 08-APR-08:61 | 0.00 | 0.00 | 0.00 | -24333.27 | 0.00 | 0.00 | 42.20 | 1961.49 | 374.52 | 191.75 | 0.00 | 15.42 | 21747.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 08-APR-07:01 | 0.00 | 0.00 | 0.00 | -24620.77 | 0.00 | 0.00 | 42.26 | 1773.99 | 374.52 | 30.01 | 0.00 | 0.00 | 22444.62 | 0.00 | -0.00 | 0.00 | -44.62 | 0.00 |
SMSTORE3 | 08-APR-07:01 | 0.00 | 0.00 | 0.00 | -24672.34 | 0.00 | 0.00 | 42.22 | 1773.99 | 374.52 | 29.26 | 0.00 | 0.00 | 22497.37 | 0.00 | -0.00 | 0.00 | -45.01 | 0.00 |
SMSTORE4 | 08-APR-07:01 | 0.00 | 0.00 | 0.00 | -24576.81 | 0.00 | 0.00 | 42.53 | 1773.99 | 374.52 | 31.48 | 0.00 | 0.00 | 22396.18 | 0.00 | -0.00 | 0.00 | -41.88 | 0.00 |
LGSTORE2 | 08-APR-08:61 | 0.00 | 0.00 | 0.00 | -44847.41 | 0.00 | 0.00 | 186.55 | 2766.09 | 749.03 | 385.52 | 0.00 | 26.00 | 40734.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 08-APR-08:61 | 0.00 | 0.00 | 0.00 | -23408.05 | 0.00 | 0.00 | 93.89 | 1383.05 | 374.52 | 194.43 | 0.00 | 19.08 | 21343.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 08-APR-08:61 | 0.00 | 0.00 | 0.00 | -23308.15 | 0.00 | 0.00 | 94.26 | 1383.05 | 374.52 | 195.36 | 0.00 | 20.54 | 21240.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 08-APR-08:61 | 0.00 | 0.00 | 0.00 | -23276.72 | 0.00 | 0.00 | 95.01 | 1383.05 | 374.52 | 196.93 | 0.00 | 23.90 | 21203.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 08-APR-08:61 | 0.00 | 0.00 | 0.00 | -24654.11 | 0.00 | 0.00 | 96.40 | 1383.05 | 374.52 | 200.92 | 0.00 | 34.79 | 22564.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JUN-07:01 | 0.00 | 0.00 | 0.00 | -244179.81 | 0.00 | 0.00 | 239.63 | 6715.10 | 1460.61 | 3636.44 | 0.00 | 4310.13 | 227817.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 02-JAN-09:01 | 0.00 | 0.00 | 10580.81 | 0.00 | 0.00 | 0.00 | 125.28 | 3671.72 | 749.03 | 688.39 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -871.77 | -14943.46 |
SMSTORE1 | 12-JUN-07:03 | 0.00 | 0.00 | 4302.36 | 0.00 | 0.00 | 0.00 | 38.21 | 196.15 | 37.45 | 315.03 | 0.00 | 385.69 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5274.89 |
SMSTORE2 | 02-JAN-08:62 | 0.00 | 0.00 | 11000.50 | 0.00 | 0.00 | 0.00 | 63.98 | 1773.99 | 374.52 | 4.05 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -545.77 | -12671.26 |
SMSTORE3 | 02-JAN-08:62 | 0.00 | 0.00 | 19634.66 | 0.00 | 0.00 | 0.00 | 65.50 | 1773.99 | 374.52 | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -543.99 | -21321.76 |
SMSTORE4 | 02-JAN-08:62 | 0.00 | 0.00 | 26225.17 | 0.00 | 0.00 | 0.00 | 66.62 | 1773.99 | 374.52 | 26.36 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -542.65 | -27924.00 |
LGSTORE2 | 01-JAN-10:01 | 0.00 | 0.00 | 57255.89 | 0.00 | 0.00 | 0.00 | 295.23 | 2766.09 | 749.03 | 1312.13 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -712.16 | -61666.21 |
SMSTORE5 | 01-JAN-10:01 | 0.00 | 0.00 | 30218.66 | 0.00 | 0.00 | 0.00 | 147.62 | 1383.05 | 374.52 | 656.14 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -407.90 | -32372.08 |
SMSTORE6 | 01-JAN-10:01 | 0.00 | 0.00 | 30124.80 | 0.00 | 0.00 | 0.00 | 148.19 | 1383.05 | 374.52 | 658.47 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -403.96 | -32285.06 |
SMSTORE7 | 01-JAN-10:01 | 0.00 | 0.00 | 30188.60 | 0.00 | 0.00 | 0.00 | 149.40 | 1383.05 | 374.52 | 663.16 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -395.82 | -32362.91 |
SMSTORE8 | 01-JAN-10:01 | 0.00 | 0.00 | 32358.34 | 0.00 | 0.00 | 0.00 | 151.33 | 1383.05 | 374.52 | 671.88 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -398.76 | -34540.36 |
Total Facility | 02-JAN-09:01 | -4043.03 | 4043.03 | 188670.01 | -4043.03 | 0.00 | 0.00 | 1462.79 | 24043.21 | 5393.02 | 4471.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5474.14 | -214523.44 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.6222 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.6222 | 0.1569 | 1.0000 | 0.4115 | 0.1569 | ||
PSZ-AC_2:2 | 1.3745 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3745 | 0.1497 | 1.0000 | 0.2057 | 0.1497 | ||
PSZ-AC_3:3 | 1.3674 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3674 | 0.1504 | 1.0000 | 0.2057 | 0.1504 | ||
PSZ-AC_4:4 | 1.3704 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3704 | 0.1501 | 1.0000 | 0.2057 | 0.1501 | ||
PSZ-AC_5:5 | 1.3668 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3668 | 0.1505 | 1.0000 | 0.2057 | 0.1505 | ||
PSZ-AC_6:6 | 2.4874 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.4874 | 0.1654 | 1.0000 | 0.4115 | 0.1654 | ||
PSZ-AC_7:7 | 1.3181 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3181 | 0.1561 | 1.0000 | 0.2057 | 0.1561 | ||
PSZ-AC_8:8 | 1.3125 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3125 | 0.1567 | 1.0000 | 0.2057 | 0.1567 | ||
PSZ-AC_9:9 | 1.3131 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3131 | 0.1567 | 1.0000 | 0.2057 | 0.1567 | ||
PSZ-AC_10:10 | 1.4178 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.4178 | 0.1451 | 1.0000 | 0.2057 | 0.1451 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.6222 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.6222 | 1.0000 | 1.0000 | 0.4115 | 0.1569 | ||
PSZ-AC_2:2 | 1.3745 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3745 | 1.0000 | 1.0000 | 0.2057 | 0.1497 | ||
PSZ-AC_3:3 | 1.3674 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3674 | 1.0000 | 1.0000 | 0.2057 | 0.1504 | ||
PSZ-AC_4:4 | 1.3704 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3704 | 1.0000 | 1.0000 | 0.2057 | 0.1501 | ||
PSZ-AC_5:5 | 1.3668 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3668 | 1.0000 | 1.0000 | 0.2057 | 0.1505 | ||
PSZ-AC_6:6 | 2.4874 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.4874 | 1.0000 | 1.0000 | 0.4115 | 0.1654 | ||
PSZ-AC_7:7 | 1.3181 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3181 | 1.0000 | 1.0000 | 0.2057 | 0.1561 | ||
PSZ-AC_8:8 | 1.3125 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3125 | 1.0000 | 1.0000 | 0.2057 | 0.1567 | ||
PSZ-AC_9:9 | 1.3131 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.3131 | 1.0000 | 1.0000 | 0.2057 | 0.1567 | ||
PSZ-AC_10:10 | 1.4178 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.4178 | 1.0000 | 1.0000 | 0.2057 | 0.1451 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.6222 | 2.6222 | 2.6222 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.3745 | 1.3745 | 1.3745 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.3674 | 1.3674 | 1.3674 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.3704 | 1.3704 | 1.3704 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.3668 | 1.3668 | 1.3668 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.4874 | 2.4874 | 2.4874 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.3181 | 1.3181 | 1.3181 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.3125 | 1.3125 | 1.3125 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.3131 | 1.3131 | 1.3131 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.4178 | 1.4178 | 1.4178 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.6222 | 2.6222 | 2.6222 | 2.6222 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.3745 | 1.3745 | 1.3745 | 1.3745 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.3674 | 1.3674 | 1.3674 | 1.3674 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.3704 | 1.3704 | 1.3704 | 1.3704 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3668 | 1.3668 | 1.3668 | 1.3668 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.4874 | 2.4874 | 2.4874 | 2.4874 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.3181 | 1.3181 | 1.3181 | 1.3181 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.3125 | 1.3125 | 1.3125 | 1.3125 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.3131 | 1.3131 | 1.3131 | 1.3131 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.4178 | 1.4178 | 1.4178 | 1.4178 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.6222 | 2.6222 | 2.6222 | 0.4115 | 0.5830 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.3745 | 1.3745 | 1.3745 | 0.2057 | 0.5627 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.3674 | 1.3674 | 1.3674 | 0.2057 | 0.5557 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.3704 | 1.3704 | 1.3704 | 0.2057 | 0.5505 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.3668 | 1.3668 | 1.3668 | 0.2057 | 0.5400 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.4874 | 2.4874 | 2.4874 | 0.4115 | 0.5740 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.3181 | 1.3181 | 1.3181 | 0.2057 | 0.5274 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.3125 | 1.3125 | 1.3125 | 0.2057 | 0.5278 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.3131 | 1.3131 | 1.3131 | 0.2057 | 0.5163 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.4178 | 1.4178 | 1.4178 | 0.2057 | 0.4702 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.6222 | 2.6222 | 2.6222 | 2.6222 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.3745 | 1.3745 | 1.3745 | 1.3745 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.3674 | 1.3674 | 1.3674 | 1.3674 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.3704 | 1.3704 | 1.3704 | 1.3704 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3668 | 1.3668 | 1.3668 | 1.3668 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.4874 | 2.4874 | 2.4874 | 2.4874 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.3181 | 1.3181 | 1.3181 | 1.3181 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.3125 | 1.3125 | 1.3125 | 1.3125 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.3131 | 1.3131 | 1.3131 | 1.3131 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.4178 | 1.4178 | 1.4178 | 1.4178 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:21:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 35.67 |
Number of hours not met | 35.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 0.43 | 63785.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 593.24 | 89394.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 587.07 | 36581.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 110.81 | 7048.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 300.06 | 17417.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 58.77 | 11816.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1778.67 |
Natural Gas | 0.00 | 0.43 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1779.10 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 280.85 |
Space Heating | 0.00 |
Space Cooling | 283.80 |
Fans (All) | 143.55 |
Service Water Heating | 28.12 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 850.91 |
Subtotal | 850.91 |
Natural Gas [MJ/m2] | |
Space Heating | 0.21 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.21 |
Subtotal | 0.21 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 33.00 |
Space Heating | 0.02 |
Space Cooling | 33.34 |
Fans (All) | 16.87 |
Service Water Heating | 3.30 |
Receptacle Equipment | 7.24 |
Miscellaneous | 6.23 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5131. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.426847E+09 |
February | 0.000 | 1114094.604 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 2793282.291 |
Annual Sum or Average | 0.430754E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.426847E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.426847E+09 |
February | 0.000 | 1114094.604 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 2793282.291 |
Annual Sum or Average | 0.430754E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.426847E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Meter
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.426847E+09 |
February | 0.000 | 1114094.604 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 2793282.291 |
Annual Sum or Average | 0.430754E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.426847E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.426847E+09 |
February | 0.000 | 1114094.604 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 2793282.291 |
Annual Sum or Average | 0.430754E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.426847E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.426847E+09 |
February | 0.000 | 1114094.604 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 2793282.291 |
Annual Sum or Average | 0.430754E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.426847E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.426847E+09 |
February | 0.000 | 1114094.604 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 2793282.291 |
Annual Sum or Average | 0.430754E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.426847E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.426847E+09 |
February | 0.000 | 1114094.604 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 2793282.291 |
Annual Sum or Average | 0.430754E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.426847E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Meter
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.426847E+09 |
February | 0.000 | 1114094.604 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 2793282.291 |
Annual Sum or Average | 0.430754E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.426847E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Meter
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.426847E+09 |
February | 0.000 | 1114094.604 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 2793282.291 |
Annual Sum or Average | 0.430754E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.426847E+09 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.794848E+10 | 8877.73 | 12-JAN-15:00 | 23.60 | 14.18 | 0.746737E+09 | 899.03 | 29-JAN-18:00 | 15.00 | 10.77 |
February | 0.973733E+10 | 14472.09 | 25-FEB-09:03 | 18.92 | 15.89 | 0.677435E+09 | 899.06 | 20-FEB-18:40 | 21.40 | 14.04 |
March | 0.152430E+11 | 40418.41 | 14-MAR-08:62 | 21.43 | 15.25 | 0.745291E+09 | 899.05 | 04-MAR-13:09 | 26.57 | 15.78 |
April | 0.206631E+11 | 46814.34 | 08-APR-08:61 | 26.02 | 15.25 | 0.727474E+09 | 899.08 | 14-APR-12:09 | 36.62 | 20.77 |
May | 0.252059E+11 | 44074.74 | 06-MAY-08:61 | 31.42 | 18.14 | 0.749008E+09 | 899.10 | 07-MAY-17:00 | 39.00 | 22.10 |
June | 0.252373E+11 | 41197.96 | 07-JUN-07:01 | 34.92 | 19.60 | 0.723578E+09 | 899.09 | 11-JUN-17:00 | 41.80 | 23.25 |
July | 0.250388E+11 | 35015.37 | 07-JUL-07:01 | 33.33 | 24.38 | 0.755034E+09 | 898.99 | 04-JUL-16:30 | 39.80 | 24.46 |
August | 0.240395E+11 | 30745.50 | 09-AUG-07:01 | 30.30 | 25.36 | 0.744715E+09 | 898.94 | 06-AUG-16:30 | 36.15 | 26.33 |
September | 0.221288E+11 | 36357.96 | 26-SEP-08:61 | 26.97 | 20.02 | 0.729564E+09 | 898.95 | 24-SEP-16:30 | 34.45 | 25.39 |
October | 0.207858E+11 | 42737.92 | 16-OCT-08:61 | 24.53 | 16.47 | 0.752791E+09 | 899.08 | 01-OCT-17:10 | 34.07 | 20.25 |
November | 0.151560E+11 | 37958.85 | 09-NOV-09:02 | 22.33 | 17.30 | 0.727137E+09 | 899.07 | 12-NOV-18:49 | 23.47 | 14.78 |
December | 0.972458E+10 | 10537.25 | 03-DEC-14:00 | 24.50 | 14.15 | 0.753548E+09 | 899.04 | 24-DEC-17:49 | 19.20 | 12.79 |
Annual Sum or Average | 0.220909E+12 | 0.883231E+10 | ||||||||
Minimum of Months | 0.794848E+10 | 8877.73 | 18.92 | 14.15 | 0.677435E+09 | 898.94 | 15.00 | 10.77 | ||
Maximum of Months | 0.252373E+11 | 46814.34 | 34.92 | 25.36 | 0.755034E+09 | 899.10 | 41.80 | 26.33 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.438382E+10 | 4838.06 | 12-JAN-15:00 | 23.60 | 14.18 | 0.374359E+09 | 449.52 | 07-JAN-13:00 | 20.90 | 13.27 |
February | 0.546656E+10 | 9628.46 | 25-FEB-09:03 | 18.92 | 15.89 | 0.339038E+09 | 449.53 | 20-FEB-18:19 | 22.20 | 14.15 |
March | 0.840083E+10 | 21739.40 | 14-MAR-08:62 | 21.43 | 15.25 | 0.372746E+09 | 449.54 | 05-MAR-13:50 | 28.68 | 17.15 |
April | 0.110388E+11 | 24333.16 | 08-APR-08:61 | 26.02 | 15.25 | 0.363785E+09 | 449.54 | 30-APR-17:40 | 35.90 | 17.51 |
May | 0.132515E+11 | 22896.95 | 06-MAY-08:61 | 31.42 | 18.14 | 0.374509E+09 | 449.56 | 07-MAY-17:49 | 39.42 | 22.06 |
June | 0.131066E+11 | 20819.63 | 07-JUN-08:61 | 36.23 | 19.94 | 0.361784E+09 | 449.53 | 02-JUN-12:09 | 37.00 | 21.29 |
July | 0.129108E+11 | 17425.54 | 05-JUL-07:01 | 33.75 | 24.50 | 0.377506E+09 | 449.49 | 04-JUL-16:30 | 39.80 | 24.46 |
August | 0.123125E+11 | 18486.33 | 20-AUG-07:01 | 26.57 | 26.13 | 0.372345E+09 | 449.47 | 06-AUG-16:30 | 36.15 | 26.33 |
September | 0.113826E+11 | 19785.48 | 26-SEP-08:61 | 26.97 | 20.02 | 0.364774E+09 | 449.47 | 24-SEP-16:30 | 34.45 | 25.39 |
October | 0.108285E+11 | 22985.50 | 16-OCT-08:61 | 24.53 | 16.47 | 0.376419E+09 | 449.54 | 01-OCT-17:10 | 34.07 | 20.25 |
November | 0.803764E+10 | 20716.85 | 09-NOV-09:02 | 22.33 | 17.30 | 0.363624E+09 | 449.53 | 03-NOV-12:20 | 26.97 | 16.22 |
December | 0.530007E+10 | 5687.35 | 02-DEC-14:00 | 24.10 | 13.12 | 0.377160E+09 | 449.52 | 24-DEC-17:49 | 19.20 | 12.79 |
Annual Sum or Average | 0.116420E+12 | 0.441805E+10 | ||||||||
Minimum of Months | 0.438382E+10 | 4838.06 | 18.92 | 13.12 | 0.339038E+09 | 449.47 | 19.20 | 12.79 | ||
Maximum of Months | 0.132515E+11 | 24333.16 | 36.23 | 26.13 | 0.377506E+09 | 449.56 | 39.80 | 26.33 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.276871E+10 | 4463.92 | 12-JAN-15:00 | 23.60 | 14.18 | 0.221277E+09 | 449.51 | 28-JAN-13:00 | 18.10 | 11.35 |
February | 0.373097E+10 | 9390.36 | 25-FEB-08:63 | 18.73 | 15.94 | 0.202998E+09 | 449.49 | 11-FEB-13:09 | 20.65 | 13.77 |
March | 0.625262E+10 | 20823.77 | 29-MAR-07:02 | 21.55 | 17.61 | 0.230358E+09 | 449.52 | 04-MAR-13:09 | 26.57 | 15.78 |
April | 0.856706E+10 | 24620.56 | 08-APR-07:01 | 24.45 | 14.69 | 0.219879E+09 | 449.50 | 29-APR-12:09 | 37.25 | 19.97 |
May | 0.106196E+11 | 23211.93 | 06-MAY-07:01 | 30.00 | 17.73 | 0.228256E+09 | 449.48 | 27-MAY-12:09 | 39.90 | 20.27 |
June | 0.105363E+11 | 20821.63 | 07-JUN-07:01 | 34.92 | 19.60 | 0.223375E+09 | 449.50 | 03-JUN-12:39 | 39.43 | 23.02 |
July | 0.100235E+11 | 15771.73 | 07-JUL-07:01 | 33.33 | 24.38 | 0.224903E+09 | 449.38 | 01-JUL-12:09 | 37.90 | 28.06 |
August | 0.972680E+10 | 15020.64 | 03-AUG-07:01 | 28.70 | 23.40 | 0.230945E+09 | 449.36 | 05-AUG-12:09 | 35.03 | 26.47 |
September | 0.875905E+10 | 18041.32 | 27-SEP-07:01 | 24.98 | 20.38 | 0.219792E+09 | 449.41 | 09-SEP-12:09 | 27.27 | 25.68 |
October | 0.827384E+10 | 23037.01 | 23-OCT-07:02 | 20.23 | 14.64 | 0.224768E+09 | 449.48 | 21-OCT-12:09 | 29.33 | 18.35 |
November | 0.594312E+10 | 18681.69 | 09-NOV-08:62 | 19.90 | 16.69 | 0.216604E+09 | 449.53 | 04-NOV-12:09 | 29.18 | 17.15 |
December | 0.350188E+10 | 5424.08 | 02-DEC-14:00 | 24.10 | 13.12 | 0.222690E+09 | 449.50 | 23-DEC-13:00 | 20.00 | 12.28 |
Annual Sum or Average | 0.887034E+11 | 0.266585E+10 | ||||||||
Minimum of Months | 0.276871E+10 | 4463.92 | 18.73 | 13.12 | 0.202998E+09 | 449.36 | 18.10 | 11.35 | ||
Maximum of Months | 0.106196E+11 | 24620.56 | 34.92 | 24.38 | 0.230945E+09 | 449.53 | 39.90 | 28.06 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261183E+10 | 4369.42 | 12-JAN-15:00 | 23.60 | 14.18 | 0.220731E+09 | 449.51 | 28-JAN-13:00 | 18.10 | 11.35 |
February | 0.365213E+10 | 9175.76 | 25-FEB-08:63 | 18.73 | 15.94 | 0.202934E+09 | 449.49 | 11-FEB-13:09 | 20.65 | 13.77 |
March | 0.623609E+10 | 20889.30 | 29-MAR-07:02 | 21.55 | 17.61 | 0.230354E+09 | 449.52 | 04-MAR-13:09 | 26.57 | 15.78 |
April | 0.861895E+10 | 24672.13 | 08-APR-07:01 | 24.45 | 14.69 | 0.219882E+09 | 449.50 | 29-APR-12:09 | 37.25 | 19.97 |
May | 0.107334E+11 | 23264.99 | 06-MAY-07:01 | 30.00 | 17.73 | 0.228261E+09 | 449.48 | 27-MAY-12:09 | 39.90 | 20.27 |
June | 0.106454E+11 | 20876.69 | 07-JUN-07:01 | 34.92 | 19.60 | 0.223379E+09 | 449.50 | 03-JUN-12:39 | 39.43 | 23.02 |
July | 0.101465E+11 | 16048.79 | 05-JUL-06:02 | 33.02 | 24.49 | 0.224908E+09 | 449.38 | 01-JUL-12:09 | 37.90 | 28.06 |
August | 0.981705E+10 | 15099.10 | 03-AUG-07:01 | 28.70 | 23.40 | 0.230949E+09 | 449.36 | 05-AUG-12:09 | 35.03 | 26.47 |
September | 0.883487E+10 | 18103.20 | 27-SEP-07:01 | 24.98 | 20.38 | 0.219796E+09 | 449.41 | 09-SEP-12:09 | 27.27 | 25.68 |
October | 0.832470E+10 | 23148.78 | 23-OCT-07:02 | 20.23 | 14.64 | 0.224772E+09 | 449.48 | 21-OCT-12:09 | 29.33 | 18.35 |
November | 0.591191E+10 | 18605.10 | 09-NOV-08:62 | 19.90 | 16.69 | 0.216596E+09 | 449.53 | 04-NOV-12:09 | 29.18 | 17.15 |
December | 0.339682E+10 | 5360.69 | 02-DEC-14:00 | 24.10 | 13.12 | 0.222570E+09 | 449.50 | 23-DEC-13:00 | 20.00 | 12.28 |
Annual Sum or Average | 0.889296E+11 | 0.266513E+10 | ||||||||
Minimum of Months | 0.261183E+10 | 4369.42 | 18.73 | 13.12 | 0.202934E+09 | 449.36 | 18.10 | 11.35 | ||
Maximum of Months | 0.107334E+11 | 24672.13 | 34.92 | 24.49 | 0.230949E+09 | 449.53 | 39.90 | 28.06 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239321E+10 | 4198.98 | 12-JAN-15:00 | 23.60 | 14.18 | 0.220080E+09 | 449.51 | 28-JAN-13:00 | 18.10 | 11.35 |
February | 0.347466E+10 | 8159.91 | 25-FEB-08:63 | 18.73 | 15.94 | 0.202790E+09 | 449.49 | 11-FEB-13:09 | 20.65 | 13.77 |
March | 0.605792E+10 | 20727.88 | 14-MAR-07:02 | 20.97 | 15.52 | 0.230329E+09 | 449.52 | 04-MAR-13:09 | 26.57 | 15.78 |
April | 0.848468E+10 | 24576.60 | 08-APR-07:01 | 24.45 | 14.69 | 0.219865E+09 | 449.50 | 29-APR-12:09 | 37.25 | 19.97 |
May | 0.106235E+11 | 23202.28 | 06-MAY-07:01 | 30.00 | 17.73 | 0.228249E+09 | 449.48 | 27-MAY-12:09 | 39.90 | 20.27 |
June | 0.105379E+11 | 20814.56 | 07-JUN-07:01 | 34.92 | 19.60 | 0.223369E+09 | 449.50 | 03-JUN-12:50 | 39.57 | 22.96 |
July | 0.100539E+11 | 15976.46 | 05-JUL-06:02 | 33.02 | 24.49 | 0.224897E+09 | 449.37 | 22-JUL-12:09 | 31.25 | 26.90 |
August | 0.970764E+10 | 14988.95 | 03-AUG-07:01 | 28.70 | 23.40 | 0.230937E+09 | 449.36 | 05-AUG-12:09 | 35.03 | 26.47 |
September | 0.872417E+10 | 18015.99 | 27-SEP-07:01 | 24.98 | 20.38 | 0.219783E+09 | 449.42 | 09-SEP-12:09 | 27.27 | 25.68 |
October | 0.819876E+10 | 23036.30 | 23-OCT-07:02 | 20.23 | 14.64 | 0.224755E+09 | 449.48 | 21-OCT-12:09 | 29.33 | 18.35 |
November | 0.575158E+10 | 17402.76 | 09-NOV-08:62 | 19.90 | 16.69 | 0.216571E+09 | 449.53 | 04-NOV-12:20 | 29.37 | 17.17 |
December | 0.320476E+10 | 5224.49 | 02-DEC-14:00 | 24.10 | 13.12 | 0.222347E+09 | 449.50 | 23-DEC-13:00 | 20.00 | 12.28 |
Annual Sum or Average | 0.872126E+11 | 0.266397E+10 | ||||||||
Minimum of Months | 0.239321E+10 | 4198.98 | 18.73 | 13.12 | 0.202790E+09 | 449.36 | 18.10 | 11.35 | ||
Maximum of Months | 0.106235E+11 | 24576.60 | 34.92 | 24.49 | 0.230937E+09 | 449.53 | 39.90 | 26.90 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.370300E+10 | 7315.46 | 12-JAN-15:10 | 23.55 | 14.23 | 0.750359E+09 | 1198.68 | 28-JAN-15:09 | 18.37 | 11.44 |
February | 0.571889E+10 | 11434.72 | 25-FEB-09:03 | 18.92 | 15.89 | 0.694050E+09 | 1198.65 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.104072E+11 | 38894.46 | 28-MAR-08:62 | 23.07 | 16.73 | 0.789488E+09 | 1198.73 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.147244E+11 | 44847.07 | 08-APR-08:61 | 26.02 | 15.25 | 0.753620E+09 | 1198.75 | 29-APR-14:00 | 32.00 | 18.74 |
May | 0.186163E+11 | 42737.60 | 29-MAY-08:61 | 32.12 | 19.76 | 0.779450E+09 | 1198.61 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.185164E+11 | 39534.66 | 07-JUN-07:01 | 34.92 | 19.60 | 0.764179E+09 | 1198.66 | 03-JUN-14:09 | 40.38 | 22.59 |
July | 0.176023E+11 | 33460.02 | 07-JUL-07:01 | 33.33 | 24.38 | 0.768940E+09 | 1198.31 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.170409E+11 | 29802.13 | 09-AUG-07:01 | 30.30 | 25.36 | 0.790667E+09 | 1198.33 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.152128E+11 | 34754.88 | 26-SEP-08:61 | 26.97 | 20.02 | 0.753448E+09 | 1198.42 | 09-SEP-14:09 | 26.78 | 25.72 |
October | 0.143435E+11 | 41464.90 | 23-OCT-08:62 | 21.77 | 15.30 | 0.766834E+09 | 1198.59 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.984368E+10 | 38575.06 | 11-NOV-10:02 | 23.18 | 16.66 | 0.737256E+09 | 1198.73 | 04-NOV-14:00 | 30.20 | 17.53 |
December | 0.515817E+10 | 9101.03 | 02-DEC-14:10 | 24.07 | 13.13 | 0.760962E+09 | 1198.69 | 23-DEC-15:50 | 19.33 | 12.10 |
Annual Sum or Average | 0.150887E+12 | 0.910925E+10 | ||||||||
Minimum of Months | 0.370300E+10 | 7315.46 | 18.92 | 13.13 | 0.694050E+09 | 1198.31 | 18.37 | 11.44 | ||
Maximum of Months | 0.186163E+11 | 44847.07 | 34.92 | 25.36 | 0.790667E+09 | 1198.75 | 41.70 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173903E+10 | 3763.81 | 12-JAN-15:10 | 23.55 | 14.23 | 0.374958E+09 | 599.34 | 28-JAN-15:09 | 18.37 | 11.44 |
February | 0.287038E+10 | 5789.85 | 25-FEB-09:03 | 18.92 | 15.89 | 0.347019E+09 | 599.32 | 04-FEB-15:00 | 23.60 | 13.13 |
March | 0.539212E+10 | 20398.79 | 28-MAR-08:62 | 23.07 | 16.73 | 0.394752E+09 | 599.36 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.774023E+10 | 23407.87 | 08-APR-08:61 | 26.02 | 15.25 | 0.376799E+09 | 599.37 | 29-APR-14:00 | 32.00 | 18.74 |
May | 0.981718E+10 | 22352.08 | 29-MAY-08:61 | 32.12 | 19.76 | 0.389713E+09 | 599.30 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.974107E+10 | 20491.65 | 12-JUN-07:01 | 35.90 | 20.10 | 0.382079E+09 | 599.33 | 03-JUN-14:09 | 40.38 | 22.59 |
July | 0.923910E+10 | 17499.27 | 07-JUL-07:01 | 33.33 | 24.38 | 0.384454E+09 | 599.14 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.891651E+10 | 15505.85 | 08-AUG-07:01 | 30.50 | 24.41 | 0.395322E+09 | 599.16 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.797038E+10 | 18256.00 | 26-SEP-08:61 | 26.97 | 20.02 | 0.376715E+09 | 599.20 | 09-SEP-14:09 | 26.78 | 25.72 |
October | 0.749722E+10 | 21732.49 | 23-OCT-08:62 | 21.77 | 15.30 | 0.383415E+09 | 599.29 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.507805E+10 | 20219.24 | 11-NOV-10:02 | 23.18 | 16.66 | 0.368635E+09 | 599.36 | 04-NOV-14:00 | 30.20 | 17.53 |
December | 0.253170E+10 | 4695.53 | 02-DEC-14:10 | 24.07 | 13.13 | 0.380438E+09 | 599.34 | 23-DEC-15:00 | 19.10 | 12.01 |
Annual Sum or Average | 0.785330E+11 | 0.455430E+10 | ||||||||
Minimum of Months | 0.173903E+10 | 3763.81 | 18.92 | 13.13 | 0.347019E+09 | 599.14 | 18.37 | 11.44 | ||
Maximum of Months | 0.981718E+10 | 23407.87 | 35.90 | 24.41 | 0.395322E+09 | 599.37 | 41.70 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167477E+10 | 3694.06 | 12-JAN-15:10 | 23.55 | 14.23 | 0.374524E+09 | 599.34 | 28-JAN-15:09 | 18.37 | 11.44 |
February | 0.280136E+10 | 5547.34 | 22-FEB-14:00 | 27.00 | 16.30 | 0.346905E+09 | 599.32 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.531401E+10 | 20281.88 | 28-MAR-08:62 | 23.07 | 16.73 | 0.394739E+09 | 599.36 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.767074E+10 | 23307.97 | 08-APR-08:61 | 26.02 | 15.25 | 0.376792E+09 | 599.37 | 29-APR-14:00 | 32.00 | 18.74 |
May | 0.974855E+10 | 22261.89 | 29-MAY-08:61 | 32.12 | 19.76 | 0.389711E+09 | 599.30 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.967518E+10 | 20394.20 | 12-JUN-07:01 | 35.90 | 20.10 | 0.382077E+09 | 599.33 | 03-JUN-14:09 | 40.38 | 22.59 |
July | 0.917910E+10 | 16842.21 | 07-JUL-07:01 | 33.33 | 24.38 | 0.384451E+09 | 599.14 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.885612E+10 | 15412.15 | 08-AUG-07:01 | 30.50 | 24.41 | 0.395318E+09 | 599.16 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.791569E+10 | 18176.92 | 26-SEP-08:61 | 26.97 | 20.02 | 0.376711E+09 | 599.20 | 09-SEP-14:09 | 26.78 | 25.72 |
October | 0.743737E+10 | 21631.25 | 23-OCT-08:62 | 21.77 | 15.30 | 0.383407E+09 | 599.29 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.501564E+10 | 20110.14 | 11-NOV-10:02 | 23.18 | 16.66 | 0.368624E+09 | 599.36 | 04-NOV-14:00 | 30.20 | 17.53 |
December | 0.247021E+10 | 4636.47 | 02-DEC-14:10 | 24.07 | 13.13 | 0.380241E+09 | 599.34 | 23-DEC-15:00 | 19.10 | 12.01 |
Annual Sum or Average | 0.777587E+11 | 0.455350E+10 | ||||||||
Minimum of Months | 0.167477E+10 | 3694.06 | 21.77 | 13.13 | 0.346905E+09 | 599.14 | 18.37 | 11.44 | ||
Maximum of Months | 0.974855E+10 | 23307.97 | 35.90 | 24.41 | 0.395318E+09 | 599.37 | 41.70 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152301E+10 | 3538.14 | 12-JAN-15:10 | 23.55 | 14.23 | 0.373461E+09 | 599.34 | 28-JAN-15:09 | 18.37 | 11.44 |
February | 0.263299E+10 | 5425.22 | 22-FEB-14:00 | 27.00 | 16.30 | 0.346535E+09 | 599.32 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.515210E+10 | 20172.59 | 28-MAR-08:62 | 23.07 | 16.73 | 0.394698E+09 | 599.36 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.758973E+10 | 23276.54 | 08-APR-08:61 | 26.02 | 15.25 | 0.376780E+09 | 599.37 | 29-APR-14:00 | 32.00 | 18.74 |
May | 0.972214E+10 | 22257.43 | 29-MAY-08:61 | 32.12 | 19.76 | 0.389709E+09 | 599.30 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.967330E+10 | 20418.86 | 12-JUN-07:01 | 35.90 | 20.10 | 0.382076E+09 | 599.33 | 03-JUN-14:09 | 40.38 | 22.59 |
July | 0.920630E+10 | 17033.62 | 07-JUL-07:01 | 33.33 | 24.38 | 0.384451E+09 | 599.14 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.889145E+10 | 15444.11 | 08-AUG-07:01 | 30.50 | 24.41 | 0.395318E+09 | 599.16 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.793188E+10 | 18181.13 | 26-SEP-08:61 | 26.97 | 20.02 | 0.376710E+09 | 599.21 | 09-SEP-14:09 | 26.78 | 25.72 |
October | 0.741527E+10 | 21610.12 | 23-OCT-08:62 | 21.77 | 15.30 | 0.383402E+09 | 599.29 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.492517E+10 | 20039.75 | 11-NOV-10:02 | 23.18 | 16.66 | 0.368600E+09 | 599.36 | 04-NOV-14:00 | 30.20 | 17.53 |
December | 0.232823E+10 | 4529.37 | 02-DEC-14:20 | 24.03 | 13.14 | 0.379752E+09 | 599.34 | 23-DEC-15:50 | 19.33 | 12.10 |
Annual Sum or Average | 0.769916E+11 | 0.455149E+10 | ||||||||
Minimum of Months | 0.152301E+10 | 3538.14 | 21.77 | 13.14 | 0.346535E+09 | 599.14 | 18.37 | 11.44 | ||
Maximum of Months | 0.972214E+10 | 23276.54 | 35.90 | 24.41 | 0.395318E+09 | 599.37 | 41.70 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133349E+10 | 3478.79 | 12-JAN-15:10 | 23.55 | 14.23 | 0.371953E+09 | 599.33 | 28-JAN-15:09 | 18.37 | 11.44 |
February | 0.244499E+10 | 5609.03 | 22-FEB-14:00 | 27.00 | 16.30 | 0.345489E+09 | 599.33 | 11-FEB-15:00 | 21.20 | 14.71 |
March | 0.511229E+10 | 20928.15 | 12-MAR-09:02 | 23.98 | 16.62 | 0.394577E+09 | 599.36 | 04-MAR-15:00 | 26.70 | 15.70 |
April | 0.805148E+10 | 24653.93 | 08-APR-08:61 | 26.02 | 15.25 | 0.376784E+09 | 599.37 | 29-APR-14:00 | 32.00 | 18.74 |
May | 0.105922E+11 | 23650.34 | 29-MAY-08:61 | 32.12 | 19.76 | 0.389733E+09 | 599.30 | 06-MAY-14:00 | 41.70 | 19.93 |
June | 0.106405E+11 | 22529.90 | 12-JUN-07:01 | 35.90 | 20.10 | 0.382099E+09 | 599.32 | 03-JUN-14:09 | 40.38 | 22.59 |
July | 0.102872E+11 | 18367.55 | 07-JUL-07:01 | 33.33 | 24.38 | 0.384498E+09 | 599.14 | 22-JUL-14:09 | 29.58 | 26.97 |
August | 0.100292E+11 | 15917.29 | 09-AUG-07:01 | 30.30 | 25.36 | 0.395356E+09 | 599.14 | 19-AUG-14:00 | 27.10 | 25.89 |
September | 0.888814E+10 | 19322.64 | 27-SEP-08:61 | 26.72 | 20.51 | 0.376758E+09 | 599.21 | 09-SEP-14:09 | 26.78 | 25.72 |
October | 0.818082E+10 | 22974.42 | 23-OCT-08:62 | 21.77 | 15.30 | 0.383452E+09 | 599.29 | 28-OCT-14:00 | 29.30 | 18.42 |
November | 0.520505E+10 | 21263.75 | 11-NOV-10:02 | 23.18 | 16.66 | 0.368587E+09 | 599.36 | 04-NOV-14:00 | 30.20 | 17.53 |
December | 0.222855E+10 | 4635.04 | 02-DEC-14:10 | 24.07 | 13.13 | 0.379035E+09 | 599.34 | 23-DEC-15:00 | 19.10 | 12.01 |
Annual Sum or Average | 0.829940E+11 | 0.454832E+10 | ||||||||
Minimum of Months | 0.133349E+10 | 3478.79 | 21.77 | 13.13 | 0.345489E+09 | 599.14 | 18.37 | 11.44 | ||
Maximum of Months | 0.106405E+11 | 24653.93 | 35.90 | 25.36 | 0.395356E+09 | 599.37 | 41.70 | 26.97 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2125908.01 | 10580.81 | 02-JAN-09:01 | 8.57 |
February | 215651.78 | 995.05 | 25-FEB-09:07 | 18.92 |
March | 53110494.24 | 3850.52 | 28-MAR-08:04 | 23.07 |
April | 0.157507E+09 | 7620.50 | 28-APR-08:04 | 31.13 |
May | 47151274.96 | 7675.78 | 31-MAY-08:06 | 33.03 |
June | 31005246.33 | 8169.29 | 12-JUN-07:03 | 35.90 |
July | 21035551.06 | 6908.94 | 07-JUL-07:03 | 33.33 |
August | 25353605.51 | 5874.55 | 06-AUG-07:06 | 29.23 |
September | 36861514.88 | 5639.74 | 25-SEP-08:06 | 28.03 |
October | 87080802.66 | 5075.70 | 04-OCT-08:06 | 27.45 |
November | 7378307.49 | 3262.93 | 10-NOV-09:05 | 21.28 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.468825E+09 | |||
Minimum of Months | 0.00 | 0.00 | 8.57 | |
Maximum of Months | 0.157507E+09 | 10580.81 | 35.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 476251.93 | 777.43 | 25-FEB-09:07 | 18.92 |
March | 28946891.94 | 2552.38 | 11-MAR-09:04 | 25.87 |
April | 71429938.90 | 3984.08 | 28-APR-08:04 | 31.13 |
May | 20752513.35 | 4006.79 | 06-MAY-08:04 | 31.42 |
June | 13832559.28 | 4302.66 | 12-JUN-07:03 | 35.90 |
July | 9992665.81 | 3739.21 | 04-JUL-07:06 | 31.77 |
August | 13969068.01 | 3175.07 | 05-AUG-08:06 | 29.27 |
September | 22108344.79 | 3168.01 | 22-SEP-08:06 | 29.38 |
October | 48888388.73 | 2662.07 | 03-OCT-08:04 | 26.33 |
November | 5203584.84 | 1910.98 | 10-NOV-09:05 | 21.28 |
December | 73303.73 | 187.91 | 16-DEC-09:10 | 18.95 |
Annual Sum or Average | 0.235674E+09 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 71429938.90 | 4302.66 | 35.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3812889.61 | 11000.66 | 02-JAN-08:62 | 7.38 |
February | 10538315.95 | 1188.19 | 20-FEB-17:12 | 24.07 |
March | 99372097.89 | 2665.92 | 12-MAR-16:11 | 31.07 |
April | 0.283073E+09 | 4429.19 | 16-APR-16:01 | 39.13 |
May | 0.289905E+09 | 5150.68 | 07-MAY-16:01 | 42.17 |
June | 0.306389E+09 | 5402.84 | 11-JUN-16:01 | 43.35 |
July | 0.247702E+09 | 4786.21 | 02-JUL-16:01 | 40.38 |
August | 0.222518E+09 | 3803.27 | 06-AUG-16:01 | 36.25 |
September | 0.201920E+09 | 3403.38 | 24-SEP-16:11 | 34.57 |
October | 0.154677E+09 | 3508.82 | 01-OCT-16:11 | 35.13 |
November | 28228528.21 | 1914.86 | 04-NOV-17:12 | 27.33 |
December | 764319.27 | 232.23 | 24-DEC-17:50 | 19.20 |
Annual Sum or Average | 0.184890E+10 | |||
Minimum of Months | 764319.27 | 232.23 | 7.38 | |
Maximum of Months | 0.306389E+09 | 11000.66 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9244846.41 | 19634.94 | 02-JAN-08:62 | 7.38 |
February | 10885347.43 | 1195.43 | 20-FEB-17:12 | 24.07 |
March | 99590940.06 | 2668.91 | 12-MAR-16:11 | 31.07 |
April | 0.277871E+09 | 4427.33 | 16-APR-16:01 | 39.13 |
May | 0.285948E+09 | 5147.74 | 07-MAY-16:01 | 42.17 |
June | 0.302808E+09 | 5398.98 | 11-JUN-16:01 | 43.35 |
July | 0.246320E+09 | 4783.27 | 02-JUL-16:01 | 40.38 |
August | 0.221308E+09 | 3800.52 | 06-AUG-16:01 | 36.25 |
September | 0.200214E+09 | 3404.53 | 24-SEP-16:11 | 34.57 |
October | 0.151144E+09 | 3509.75 | 01-OCT-16:11 | 35.13 |
November | 28370895.13 | 1919.04 | 04-NOV-17:12 | 27.33 |
December | 928665.37 | 253.85 | 24-DEC-17:50 | 19.20 |
Annual Sum or Average | 0.183463E+10 | |||
Minimum of Months | 928665.37 | 253.85 | 7.38 | |
Maximum of Months | 0.302808E+09 | 19634.94 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16037732.14 | 26225.54 | 02-JAN-08:62 | 7.38 |
February | 11466608.43 | 1200.02 | 20-FEB-17:12 | 24.07 |
March | 0.101888E+09 | 2670.20 | 12-MAR-16:11 | 31.07 |
April | 0.287049E+09 | 4429.68 | 16-APR-16:01 | 39.13 |
May | 0.293183E+09 | 5148.95 | 07-MAY-16:01 | 42.17 |
June | 0.308888E+09 | 5399.72 | 11-JUN-16:01 | 43.35 |
July | 0.248886E+09 | 4784.10 | 02-JUL-16:01 | 40.38 |
August | 0.224435E+09 | 3801.57 | 06-AUG-16:01 | 36.25 |
September | 0.205439E+09 | 3406.07 | 24-SEP-16:11 | 34.57 |
October | 0.157162E+09 | 3510.26 | 01-OCT-16:11 | 35.13 |
November | 28675433.02 | 1921.66 | 04-NOV-17:12 | 27.33 |
December | 1128279.84 | 274.84 | 24-DEC-17:50 | 19.20 |
Annual Sum or Average | 0.188424E+10 | |||
Minimum of Months | 1128279.84 | 274.84 | 7.38 | |
Maximum of Months | 0.308888E+09 | 26225.54 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38197094.52 | 57256.05 | 01-JAN-10:01 | 10.43 |
February | 13353622.27 | 2126.15 | 20-FEB-17:12 | 24.07 |
March | 0.116619E+09 | 5078.06 | 12-MAR-16:11 | 31.07 |
April | 0.290225E+09 | 8758.66 | 16-APR-16:01 | 39.13 |
May | 0.169446E+09 | 10193.22 | 07-MAY-16:01 | 42.17 |
June | 0.150693E+09 | 10705.81 | 11-JUN-16:01 | 43.35 |
July | 0.169535E+09 | 9453.15 | 02-JUL-16:01 | 40.38 |
August | 0.129378E+09 | 7478.98 | 06-AUG-16:01 | 36.25 |
September | 0.179220E+09 | 6647.01 | 24-SEP-16:01 | 34.68 |
October | 0.202542E+09 | 6865.42 | 01-OCT-16:01 | 35.32 |
November | 49757406.09 | 3562.10 | 04-NOV-17:12 | 27.33 |
December | 898760.09 | 428.68 | 24-DEC-17:05 | 20.40 |
Annual Sum or Average | 0.150986E+10 | |||
Minimum of Months | 898760.09 | 428.68 | 10.43 | |
Maximum of Months | 0.290225E+09 | 57256.05 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 25055392.66 | 30218.74 | 01-JAN-10:01 | 10.43 |
February | 9565178.20 | 1182.63 | 20-FEB-17:12 | 24.07 |
March | 69049509.64 | 2640.08 | 12-MAR-16:11 | 31.07 |
April | 0.163765E+09 | 4429.18 | 16-APR-16:01 | 39.13 |
May | 93420881.60 | 5145.09 | 07-MAY-16:01 | 42.17 |
June | 82446836.86 | 5396.34 | 11-JUN-16:01 | 43.35 |
July | 92346436.76 | 4777.89 | 02-JUL-16:01 | 40.38 |
August | 69475585.67 | 3796.09 | 06-AUG-16:01 | 36.25 |
September | 0.102400E+09 | 3378.32 | 24-SEP-16:01 | 34.68 |
October | 0.116514E+09 | 3485.12 | 01-OCT-16:01 | 35.32 |
November | 30780043.89 | 1905.86 | 04-NOV-17:12 | 27.33 |
December | 1653936.58 | 315.82 | 24-DEC-17:05 | 20.40 |
Annual Sum or Average | 0.856472E+09 | |||
Minimum of Months | 1653936.58 | 315.82 | 10.43 | |
Maximum of Months | 0.163765E+09 | 30218.74 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27995416.63 | 30124.88 | 01-JAN-10:01 | 10.43 |
February | 9667664.82 | 1182.46 | 20-FEB-17:12 | 24.07 |
March | 69650454.61 | 2636.87 | 12-MAR-16:11 | 31.07 |
April | 0.167119E+09 | 4429.49 | 16-APR-16:01 | 39.13 |
May | 96091515.45 | 5144.99 | 07-MAY-16:01 | 42.17 |
June | 84596389.76 | 5396.28 | 11-JUN-16:01 | 43.35 |
July | 93866494.28 | 4777.56 | 02-JUL-16:01 | 40.38 |
August | 70168507.66 | 3795.72 | 06-AUG-16:01 | 36.25 |
September | 0.105090E+09 | 3378.36 | 24-SEP-16:01 | 34.68 |
October | 0.117247E+09 | 3485.12 | 01-OCT-16:01 | 35.32 |
November | 30810435.72 | 1903.48 | 04-NOV-17:12 | 27.33 |
December | 1731953.95 | 323.37 | 24-DEC-17:05 | 20.40 |
Annual Sum or Average | 0.874034E+09 | |||
Minimum of Months | 1731953.95 | 323.37 | 10.43 | |
Maximum of Months | 0.167119E+09 | 30124.88 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35348034.97 | 30188.69 | 01-JAN-10:01 | 10.43 |
February | 10329137.13 | 1189.08 | 20-FEB-17:12 | 24.07 |
March | 72322221.93 | 2641.72 | 12-MAR-16:11 | 31.07 |
April | 0.175195E+09 | 4431.26 | 16-APR-16:01 | 39.13 |
May | 99074310.48 | 5145.05 | 07-MAY-16:01 | 42.17 |
June | 85283918.44 | 5395.12 | 11-JUN-16:01 | 43.35 |
July | 93617398.26 | 4775.86 | 02-JUL-16:01 | 40.38 |
August | 73088180.49 | 3793.53 | 06-AUG-16:01 | 36.25 |
September | 0.106312E+09 | 3376.73 | 24-SEP-16:01 | 34.68 |
October | 0.119385E+09 | 3484.00 | 01-OCT-16:01 | 35.32 |
November | 31851949.58 | 1906.59 | 04-NOV-17:12 | 27.33 |
December | 2240861.66 | 347.73 | 24-DEC-17:05 | 20.40 |
Annual Sum or Average | 0.904048E+09 | |||
Minimum of Months | 2240861.66 | 347.73 | 10.43 | |
Maximum of Months | 0.175195E+09 | 30188.69 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55733846.18 | 32358.45 | 01-JAN-10:01 | 10.43 |
February | 13314902.88 | 1303.74 | 02-FEB-09:05 | 10.37 |
March | 81108475.95 | 2692.49 | 11-MAR-09:04 | 25.87 |
April | 0.186354E+09 | 4398.65 | 16-APR-16:01 | 39.13 |
May | 95146015.46 | 5100.95 | 07-MAY-16:01 | 42.17 |
June | 80452387.07 | 5338.17 | 11-JUN-16:01 | 43.35 |
July | 84437978.53 | 4716.92 | 02-JUL-16:01 | 40.38 |
August | 61842333.27 | 3730.90 | 06-AUG-16:01 | 36.25 |
September | 87205033.88 | 3382.97 | 24-SEP-16:11 | 34.57 |
October | 0.116761E+09 | 3492.63 | 01-OCT-16:11 | 35.13 |
November | 33524382.61 | 2119.68 | 11-NOV-10:04 | 23.18 |
December | 5259477.92 | 1559.04 | 23-DEC-09:05 | 10.55 |
Annual Sum or Average | 0.901140E+09 | |||
Minimum of Months | 5259477.92 | 1303.74 | 10.37 | |
Maximum of Months | 0.186354E+09 | 32358.45 | 43.35 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.114998E+11 | 6976.27 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.104054E+11 | 6976.27 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.115236E+11 | 6976.27 | 01-MAR-10:09 | 0.223972E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.111588E+11 | 6976.27 | 01-APR-09:09 | 0.216880E+10 | 1348.26 | 01-APR-09:09 |
May | 0.114998E+11 | 6976.27 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.111588E+11 | 6976.27 | 01-JUN-09:09 | 0.216880E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.115236E+11 | 6976.27 | 01-JUL-09:09 | 0.223972E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.114998E+11 | 6976.27 | 01-AUG-09:09 | 0.223514E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.111826E+11 | 6976.27 | 01-SEP-09:09 | 0.217339E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.114998E+11 | 6976.27 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.111112E+11 | 6976.27 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.115474E+11 | 6976.27 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.135611E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.104054E+11 | 6976.27 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.115474E+11 | 6976.27 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.614337E+10 | 3726.82 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.555869E+10 | 3726.82 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.615608E+10 | 3726.82 | 01-MAR-10:09 | 0.111986E+10 | 674.13 | 01-MAR-10:09 |
April | 0.596119E+10 | 3726.82 | 01-APR-09:09 | 0.108440E+10 | 674.13 | 01-APR-09:09 |
May | 0.614337E+10 | 3726.82 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.596119E+10 | 3726.82 | 01-JUN-09:09 | 0.108440E+10 | 674.13 | 01-JUN-09:09 |
July | 0.615608E+10 | 3726.82 | 01-JUL-09:09 | 0.111986E+10 | 674.13 | 01-JUL-09:09 |
August | 0.614337E+10 | 3726.82 | 01-AUG-09:09 | 0.111757E+10 | 674.13 | 01-AUG-09:09 |
September | 0.597390E+10 | 3726.82 | 01-SEP-09:09 | 0.108669E+10 | 674.13 | 01-SEP-09:09 |
October | 0.614337E+10 | 3726.82 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.593577E+10 | 3726.82 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.616879E+10 | 3726.82 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.724452E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.555869E+10 | 3726.82 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.616879E+10 | 3726.82 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.438359E+10 | 3370.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.396975E+10 | 3370.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.447555E+10 | 3370.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.425331E+10 | 3370.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.442957E+10 | 3370.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.432228E+10 | 3370.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.436060E+10 | 3370.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.447555E+10 | 3370.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.425331E+10 | 3370.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.438359E+10 | 3370.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.425331E+10 | 3370.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.436060E+10 | 3370.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.519210E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.396975E+10 | 3370.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.447555E+10 | 3370.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.438359E+10 | 3370.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.396975E+10 | 3370.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.447555E+10 | 3370.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.425331E+10 | 3370.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.442957E+10 | 3370.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.432228E+10 | 3370.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.436060E+10 | 3370.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.447555E+10 | 3370.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.425331E+10 | 3370.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.438359E+10 | 3370.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.425331E+10 | 3370.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.436060E+10 | 3370.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.519210E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.396975E+10 | 3370.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.447555E+10 | 3370.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.438359E+10 | 3370.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.396975E+10 | 3370.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.447555E+10 | 3370.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.425331E+10 | 3370.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.442957E+10 | 3370.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.432228E+10 | 3370.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.436060E+10 | 3370.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.447555E+10 | 3370.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.425331E+10 | 3370.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.438359E+10 | 3370.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.425331E+10 | 3370.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.436060E+10 | 3370.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.519210E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.396975E+10 | 3370.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.447555E+10 | 3370.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.627948E+10 | 5255.58 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.568798E+10 | 5255.58 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.642287E+10 | 5255.58 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.609426E+10 | 5255.58 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.635118E+10 | 5255.58 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.620181E+10 | 5255.58 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.624363E+10 | 5255.58 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.642287E+10 | 5255.58 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.609426E+10 | 5255.58 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.627948E+10 | 5255.58 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.609426E+10 | 5255.58 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.624363E+10 | 5255.58 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.744157E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.568798E+10 | 5255.58 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.642287E+10 | 5255.58 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.313974E+10 | 2627.79 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.284399E+10 | 2627.79 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.321144E+10 | 2627.79 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.304713E+10 | 2627.79 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.317559E+10 | 2627.79 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.310090E+10 | 2627.79 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.312181E+10 | 2627.79 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.321144E+10 | 2627.79 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.304713E+10 | 2627.79 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.313974E+10 | 2627.79 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.304713E+10 | 2627.79 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.312181E+10 | 2627.79 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.372078E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.284399E+10 | 2627.79 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.321144E+10 | 2627.79 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.313974E+10 | 2627.79 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.284399E+10 | 2627.79 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.321144E+10 | 2627.79 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.304713E+10 | 2627.79 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.317559E+10 | 2627.79 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.310090E+10 | 2627.79 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.312181E+10 | 2627.79 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.321144E+10 | 2627.79 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.304713E+10 | 2627.79 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.313974E+10 | 2627.79 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.304713E+10 | 2627.79 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.312181E+10 | 2627.79 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.372078E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.284399E+10 | 2627.79 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.321144E+10 | 2627.79 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.313974E+10 | 2627.79 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.284399E+10 | 2627.79 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.321144E+10 | 2627.79 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.304713E+10 | 2627.79 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.317559E+10 | 2627.79 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.310090E+10 | 2627.79 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.312181E+10 | 2627.79 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.321144E+10 | 2627.79 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.304713E+10 | 2627.79 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.313974E+10 | 2627.79 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.304713E+10 | 2627.79 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.312181E+10 | 2627.79 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.372078E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.284399E+10 | 2627.79 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.321144E+10 | 2627.79 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.313974E+10 | 2627.79 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.284399E+10 | 2627.79 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.321144E+10 | 2627.79 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.304713E+10 | 2627.79 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.317559E+10 | 2627.79 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.310090E+10 | 2627.79 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.312181E+10 | 2627.79 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.321144E+10 | 2627.79 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.304713E+10 | 2627.79 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.313974E+10 | 2627.79 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.304713E+10 | 2627.79 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.312181E+10 | 2627.79 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.372078E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.284399E+10 | 2627.79 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.321144E+10 | 2627.79 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.114998E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219208E+10 |
February | 0.163016E+10 | 0.104054E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122267E+09 | 0.982578E+09 |
March | 0.178954E+10 | 0.115236E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124849E+10 | 0.287511E+09 |
April | 0.174484E+10 | 0.111588E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336024E+10 | 23794607.21 |
May | 0.179537E+10 | 0.114998E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479246E+10 | 8315688.94 |
June | 0.173447E+10 | 0.111588E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431932E+10 | 3539203.05 |
July | 0.181028E+10 | 0.115236E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351410E+10 | 2293767.59 |
August | 0.178501E+10 | 0.114998E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294572E+10 | 3811914.01 |
September | 0.174937E+10 | 0.111826E+11 | 0.217339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255546E+10 | 10248252.80 |
October | 0.180574E+10 | 0.114998E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220366E+10 | 57841245.51 |
November | 0.174613E+10 | 0.111112E+11 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749177E+09 | 0.294113E+09 |
December | 0.181481E+10 | 0.115474E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5270731.07 | 0.185395E+10 |
Annual Sum or Average | 0.212115E+11 | 0.135611E+12 | 0.263573E+11 | 0.258162E+11 | 0.572008E+10 | ||||
Minimum of Months | 0.163016E+10 | 0.104054E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2293767.59 |
Maximum of Months | 0.181481E+10 | 0.115474E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479246E+10 | 0.219208E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.614337E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119581E+10 |
February | 0.815075E+09 | 0.555869E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68876503.71 | 0.496688E+09 |
March | 0.894769E+09 | 0.615608E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700957E+09 | 0.121780E+09 |
April | 0.872416E+09 | 0.596119E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187320E+10 | 9935499.27 |
May | 0.897684E+09 | 0.614337E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264421E+10 | 2962174.19 |
June | 0.867232E+09 | 0.596119E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240046E+10 | 1129917.80 |
July | 0.905135E+09 | 0.615608E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192989E+10 | 669494.41 |
August | 0.892501E+09 | 0.614337E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163632E+10 | 1233288.38 |
September | 0.874683E+09 | 0.597390E+10 | 0.108669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143186E+10 | 3543374.36 |
October | 0.902868E+09 | 0.614337E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124492E+10 | 27986271.52 |
November | 0.873064E+09 | 0.593577E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424658E+09 | 0.150121E+09 |
December | 0.907403E+09 | 0.616879E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2978351.20 | 0.100350E+10 |
Annual Sum or Average | 0.106057E+11 | 0.724452E+11 | 0.131787E+11 | 0.143583E+11 | 0.301535E+10 | ||||
Minimum of Months | 0.815075E+09 | 0.555869E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 669494.41 |
Maximum of Months | 0.907403E+09 | 0.616879E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264421E+10 | 0.119581E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119721E+10 |
February | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68781984.06 | 0.522077E+09 |
March | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688321E+09 | 0.136549E+09 |
April | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185124E+10 | 9990865.16 |
May | 0.544247E+09 | 0.442957E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262243E+10 | 2891380.58 |
June | 0.532585E+09 | 0.432228E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238765E+10 | 1473876.91 |
July | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190274E+10 | 843991.83 |
August | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162010E+10 | 2416968.60 |
September | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141119E+10 | 4590426.74 |
October | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121558E+10 | 25001950.71 |
November | 0.518979E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419468E+09 | 0.161077E+09 |
December | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2978464.81 | 0.101712E+10 |
Annual Sum or Average | 0.638324E+10 | 0.519210E+11 | 0.104672E+11 | 0.141905E+11 | 0.308124E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 843991.83 |
Maximum of Months | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262243E+10 | 0.119721E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119006E+10 |
February | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68782325.08 | 0.520784E+09 |
March | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688267E+09 | 0.136523E+09 |
April | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185079E+10 | 10180141.64 |
May | 0.544247E+09 | 0.442957E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262076E+10 | 3103342.39 |
June | 0.532585E+09 | 0.432228E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238652E+10 | 1595151.65 |
July | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190076E+10 | 963607.97 |
August | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161914E+10 | 2584767.09 |
September | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141075E+10 | 4918822.26 |
October | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121532E+10 | 25150201.30 |
November | 0.518979E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419470E+09 | 0.160935E+09 |
December | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2978612.91 | 0.101504E+10 |
Annual Sum or Average | 0.638324E+10 | 0.519210E+11 | 0.104672E+11 | 0.141836E+11 | 0.307184E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 963607.97 |
Maximum of Months | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262076E+10 | 0.119006E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118183E+10 |
February | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68782988.44 | 0.518088E+09 |
March | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688434E+09 | 0.134975E+09 |
April | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185125E+10 | 9778642.76 |
May | 0.544247E+09 | 0.442957E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262192E+10 | 2883382.82 |
June | 0.532585E+09 | 0.432228E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238737E+10 | 1517647.82 |
July | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190208E+10 | 843489.77 |
August | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161999E+10 | 2353012.20 |
September | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141113E+10 | 4531066.16 |
October | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121557E+10 | 24891575.48 |
November | 0.518979E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419487E+09 | 0.160207E+09 |
December | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2978746.59 | 0.101165E+10 |
Annual Sum or Average | 0.638324E+10 | 0.519210E+11 | 0.104672E+11 | 0.141890E+11 | 0.305355E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 843489.77 |
Maximum of Months | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262192E+10 | 0.118183E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.627948E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206074E+10 |
February | 0.167188E+10 | 0.568798E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120606E+09 | 0.926769E+09 |
March | 0.189386E+10 | 0.642287E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120882E+10 | 0.255748E+09 |
April | 0.180380E+10 | 0.609426E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324331E+10 | 23032561.79 |
May | 0.186509E+10 | 0.635118E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460492E+10 | 6893335.22 |
June | 0.182945E+10 | 0.620181E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418610E+10 | 3360134.27 |
July | 0.183943E+10 | 0.624363E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334008E+10 | 1512252.37 |
August | 0.189386E+10 | 0.642287E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283375E+10 | 4527535.90 |
September | 0.180380E+10 | 0.609426E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246174E+10 | 11140236.45 |
October | 0.183632E+10 | 0.627948E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212914E+10 | 57623325.56 |
November | 0.176881E+10 | 0.609426E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.734964E+09 | 0.290685E+09 |
December | 0.183943E+10 | 0.624363E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5221615.38 | 0.177910E+10 |
Annual Sum or Average | 0.218821E+11 | 0.744157E+11 | 0.192612E+11 | 0.248687E+11 | 0.542113E+10 | ||||
Minimum of Months | 0.167188E+10 | 0.568798E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1512252.37 |
Maximum of Months | 0.189386E+10 | 0.642287E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460492E+10 | 0.206074E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116486E+10 |
February | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68791092.85 | 0.516274E+09 |
March | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689311E+09 | 0.136780E+09 |
April | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184728E+10 | 11900156.30 |
May | 0.932542E+09 | 0.317559E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261891E+10 | 3359826.95 |
June | 0.914724E+09 | 0.310090E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238283E+10 | 1632878.86 |
July | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189859E+10 | 666797.87 |
August | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161380E+10 | 2206152.01 |
September | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140349E+10 | 5448014.63 |
October | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121519E+10 | 31626845.24 |
November | 0.884402E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419574E+09 | 0.162703E+09 |
December | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2979802.29 | 0.100542E+10 |
Annual Sum or Average | 0.109410E+11 | 0.372078E+11 | 0.963059E+10 | 0.141607E+11 | 0.304287E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666797.87 |
Maximum of Months | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261891E+10 | 0.116486E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116155E+10 |
February | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68791260.19 | 0.514857E+09 |
March | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689403E+09 | 0.136032E+09 |
April | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184753E+10 | 11673809.86 |
May | 0.932542E+09 | 0.317559E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261936E+10 | 3287621.68 |
June | 0.914724E+09 | 0.310090E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238316E+10 | 1605278.42 |
July | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189907E+10 | 643370.55 |
August | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161411E+10 | 2158693.87 |
September | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140367E+10 | 5331590.61 |
October | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121533E+10 | 31437082.93 |
November | 0.884402E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419584E+09 | 0.162286E+09 |
December | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2979792.99 | 0.100360E+10 |
Annual Sum or Average | 0.109410E+11 | 0.372078E+11 | 0.963059E+10 | 0.141630E+11 | 0.303446E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643370.55 |
Maximum of Months | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261936E+10 | 0.116155E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115322E+10 |
February | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68792351.78 | 0.510421E+09 |
March | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689577E+09 | 0.133750E+09 |
April | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184797E+10 | 11093142.57 |
May | 0.932542E+09 | 0.317559E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261983E+10 | 3118307.73 |
June | 0.914724E+09 | 0.310090E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238338E+10 | 1568240.11 |
July | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189911E+10 | 614705.43 |
August | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161412E+10 | 2139259.18 |
September | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140370E+10 | 5199834.38 |
October | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121538E+10 | 31155559.82 |
November | 0.884402E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419595E+09 | 0.161354E+09 |
December | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2979773.96 | 0.998933E+09 |
Annual Sum or Average | 0.109410E+11 | 0.372078E+11 | 0.963059E+10 | 0.141644E+11 | 0.301257E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614705.43 |
Maximum of Months | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261983E+10 | 0.115322E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124601E+10 |
February | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70301130.22 | 0.621803E+09 |
March | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708081E+09 | 0.204837E+09 |
April | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192332E+10 | 17040110.26 |
May | 0.932542E+09 | 0.317559E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277193E+10 | 6200379.80 |
June | 0.914724E+09 | 0.310090E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249670E+10 | 3476393.98 |
July | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202191E+10 | 1744309.75 |
August | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168398E+10 | 4471686.04 |
September | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144497E+10 | 11419703.04 |
October | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123545E+10 | 41100785.64 |
November | 0.884402E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424851E+09 | 0.191226E+09 |
December | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3030821.38 | 0.109622E+10 |
Annual Sum or Average | 0.109410E+11 | 0.372078E+11 | 0.963059E+10 | 0.147845E+11 | 0.344555E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1744309.75 |
Maximum of Months | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277193E+10 | 0.124601E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 6976.27 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4748.44 | 15-JAN-18:00 |
February | 2159.72 | 03-FEB-13:09 | 6976.27 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1458.30 | 22-FEB-15:00 | 4355.56 | 10-FEB-18:00 |
March | 2159.72 | 03-MAR-13:09 | 6976.27 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.45 | 28-MAR-15:00 | 1703.61 | 25-MAR-00:10 |
April | 2159.72 | 01-APR-12:09 | 6976.27 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7535.40 | 15-APR-15:00 | 374.92 | 10-APR-07:10 |
May | 2159.72 | 05-MAY-12:09 | 6976.27 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8909.04 | 03-MAY-15:00 | 179.39 | 13-MAY-07:10 |
June | 2159.72 | 02-JUN-12:09 | 6976.27 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9076.61 | 06-JUN-15:00 | 163.78 | 18-JUN-05:00 |
July | 2159.72 | 01-JUL-12:09 | 6976.27 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7163.40 | 07-JUL-15:00 | 145.66 | 19-JUL-03:00 |
August | 2159.72 | 04-AUG-12:09 | 6976.27 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5962.33 | 07-AUG-15:00 | 165.52 | 16-AUG-07:06 |
September | 2159.72 | 01-SEP-12:09 | 6976.27 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5499.25 | 29-SEP-13:00 | 163.30 | 19-SEP-07:10 |
October | 2159.72 | 01-OCT-12:09 | 6976.27 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5550.73 | 02-OCT-14:00 | 541.90 | 31-OCT-07:03 |
November | 2159.72 | 03-NOV-12:09 | 6976.27 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2874.46 | 04-NOV-14:00 | 2243.94 | 30-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 6976.27 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 328.28 | 28-DEC-14:00 | 5517.28 | 31-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 6976.27 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.66 | |||||
Maximum of Months | 2159.72 | 6976.27 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9076.61 | 5517.28 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 3726.82 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2724.69 | 01-JAN-18:00 |
February | 1079.86 | 03-FEB-13:09 | 3726.82 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 826.32 | 22-FEB-15:00 | 2529.14 | 10-FEB-18:00 |
March | 1079.86 | 03-MAR-13:09 | 3726.82 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.56 | 28-MAR-15:00 | 900.28 | 18-MAR-17:00 |
April | 1079.86 | 01-APR-12:09 | 3726.82 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4149.32 | 15-APR-15:00 | 213.30 | 10-APR-07:10 |
May | 1079.86 | 05-MAY-12:09 | 3726.82 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5010.90 | 03-MAY-15:00 | 103.55 | 13-MAY-07:10 |
June | 1079.86 | 02-JUN-12:09 | 3726.82 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.33 | 07-JUN-16:00 | 64.27 | 24-JUN-08:00 |
July | 1079.86 | 01-JUL-12:09 | 3726.82 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4042.75 | 07-JUL-15:00 | 42.27 | 19-JUL-03:00 |
August | 1079.86 | 04-AUG-12:09 | 3726.82 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3349.79 | 07-AUG-15:00 | 90.07 | 16-AUG-07:50 |
September | 1079.86 | 01-SEP-12:09 | 3726.82 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3084.43 | 29-SEP-13:00 | 89.72 | 07-SEP-07:10 |
October | 1079.86 | 01-OCT-12:09 | 3726.82 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3139.79 | 02-OCT-14:00 | 313.74 | 31-OCT-07:03 |
November | 1079.86 | 03-NOV-12:09 | 3726.82 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1632.52 | 04-NOV-14:00 | 1275.88 | 30-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 3726.82 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.66 | 28-DEC-14:00 | 3138.04 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3726.82 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.27 | |||||
Maximum of Months | 1079.86 | 3726.82 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.33 | 3138.04 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3370.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2613.30 | 15-JAN-17:00 |
February | 1079.86 | 04-FEB-13:09 | 3370.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 826.32 | 22-FEB-15:00 | 2495.91 | 10-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3370.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.56 | 28-MAR-15:00 | 900.30 | 18-MAR-17:00 |
April | 1079.86 | 01-APR-12:09 | 3370.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4149.31 | 15-APR-15:00 | 269.70 | 22-APR-18:10 |
May | 1079.86 | 06-MAY-12:09 | 3370.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5010.89 | 03-MAY-15:00 | 87.54 | 13-MAY-07:01 |
June | 1079.86 | 03-JUN-12:09 | 3370.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.31 | 07-JUN-16:00 | 68.55 | 18-JUN-07:02 |
July | 1079.86 | 01-JUL-12:09 | 3370.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4042.74 | 07-JUL-15:00 | 45.95 | 19-JUL-03:00 |
August | 1079.86 | 05-AUG-12:09 | 3370.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3349.79 | 07-AUG-15:00 | 367.90 | 20-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3370.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3084.39 | 29-SEP-13:00 | 283.31 | 03-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 3370.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3139.79 | 02-OCT-14:00 | 305.89 | 29-OCT-07:03 |
November | 1079.86 | 04-NOV-12:09 | 3370.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1632.51 | 04-NOV-14:00 | 1275.88 | 30-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3370.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.65 | 28-DEC-14:00 | 3126.58 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.95 | |||||
Maximum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.31 | 3126.58 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3370.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2599.51 | 15-JAN-17:00 |
February | 1079.86 | 04-FEB-13:09 | 3370.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 826.32 | 22-FEB-15:00 | 2484.59 | 10-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3370.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.56 | 28-MAR-15:00 | 900.30 | 18-MAR-17:00 |
April | 1079.86 | 01-APR-12:09 | 3370.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4149.31 | 15-APR-15:00 | 270.43 | 22-APR-18:10 |
May | 1079.86 | 06-MAY-12:09 | 3370.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5010.89 | 03-MAY-15:00 | 87.54 | 13-MAY-07:01 |
June | 1079.86 | 03-JUN-12:09 | 3370.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.31 | 07-JUN-16:00 | 70.30 | 18-JUN-07:08 |
July | 1079.86 | 01-JUL-12:09 | 3370.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4042.74 | 07-JUL-15:00 | 46.99 | 19-JUL-03:00 |
August | 1079.86 | 05-AUG-12:09 | 3370.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3349.80 | 07-AUG-15:00 | 376.66 | 20-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3370.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3084.39 | 29-SEP-13:00 | 294.77 | 03-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 3370.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3139.79 | 02-OCT-14:00 | 306.77 | 29-OCT-07:03 |
November | 1079.86 | 04-NOV-12:09 | 3370.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1632.51 | 04-NOV-14:00 | 1275.88 | 30-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3370.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.66 | 28-DEC-14:00 | 3111.02 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.99 | |||||
Maximum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.31 | 3111.02 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3370.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2572.83 | 15-JAN-17:00 |
February | 1079.86 | 04-FEB-13:09 | 3370.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 826.32 | 22-FEB-15:00 | 2455.62 | 10-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3370.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.56 | 28-MAR-15:00 | 900.30 | 18-MAR-17:00 |
April | 1079.86 | 01-APR-12:09 | 3370.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4149.31 | 15-APR-15:00 | 266.00 | 22-APR-18:10 |
May | 1079.86 | 06-MAY-12:09 | 3370.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5010.89 | 03-MAY-15:00 | 87.31 | 13-MAY-07:01 |
June | 1079.86 | 03-JUN-12:09 | 3370.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.31 | 07-JUN-16:00 | 68.75 | 18-JUN-07:02 |
July | 1079.86 | 01-JUL-12:09 | 3370.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4042.74 | 07-JUL-15:00 | 45.52 | 19-JUL-03:00 |
August | 1079.86 | 05-AUG-12:09 | 3370.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3349.80 | 07-AUG-15:00 | 368.05 | 20-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 3370.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3084.39 | 29-SEP-13:00 | 287.09 | 03-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 3370.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3139.79 | 02-OCT-14:00 | 302.87 | 29-OCT-07:03 |
November | 1079.86 | 04-NOV-12:09 | 3370.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1632.51 | 04-NOV-14:00 | 1275.88 | 30-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3370.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.66 | 28-DEC-14:00 | 3074.80 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.52 | |||||
Maximum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.31 | 3074.80 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 5255.58 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4374.96 | 15-JAN-17:00 |
February | 2879.63 | 04-FEB-15:09 | 5255.58 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1447.91 | 22-FEB-15:00 | 4155.05 | 10-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 5255.58 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.50 | 28-MAR-15:00 | 1578.49 | 18-MAR-17:00 |
April | 2879.63 | 01-APR-14:09 | 5255.58 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7298.95 | 15-APR-15:00 | 473.46 | 22-APR-18:10 |
May | 2879.63 | 06-MAY-14:09 | 5255.58 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8787.00 | 03-MAY-15:00 | 168.58 | 13-MAY-07:10 |
June | 2879.63 | 03-JUN-14:09 | 5255.58 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8819.54 | 06-JUN-15:00 | 167.84 | 18-JUN-07:02 |
July | 2879.63 | 01-JUL-14:09 | 5255.58 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7085.82 | 07-JUL-15:00 | 85.07 | 19-JUL-03:00 |
August | 2879.63 | 05-AUG-14:09 | 5255.58 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5875.13 | 07-AUG-15:00 | 621.52 | 20-AUG-17:00 |
September | 2879.63 | 02-SEP-14:09 | 5255.58 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5410.92 | 29-SEP-13:00 | 485.28 | 03-SEP-17:00 |
October | 2879.63 | 07-OCT-14:09 | 5255.58 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5501.31 | 02-OCT-14:00 | 562.37 | 29-OCT-07:03 |
November | 2879.63 | 04-NOV-14:09 | 5255.58 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2858.66 | 04-NOV-14:00 | 2233.85 | 30-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 5255.58 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 324.25 | 28-DEC-14:00 | 5241.61 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 5255.58 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.07 | |||||
Maximum of Months | 2879.63 | 5255.58 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8819.54 | 5241.61 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2627.79 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2485.88 | 15-JAN-17:00 |
February | 1439.81 | 04-FEB-15:09 | 2627.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 826.32 | 22-FEB-15:00 | 2358.59 | 10-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2627.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.59 | 28-MAR-15:00 | 900.31 | 18-MAR-17:00 |
April | 1439.81 | 01-APR-14:09 | 2627.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4149.35 | 15-APR-15:00 | 249.01 | 22-APR-18:10 |
May | 1439.81 | 06-MAY-14:09 | 2627.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5010.92 | 03-MAY-15:00 | 93.78 | 13-MAY-07:10 |
June | 1439.81 | 03-JUN-14:09 | 2627.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.35 | 07-JUN-16:00 | 88.07 | 18-JUN-07:02 |
July | 1439.81 | 01-JUL-14:09 | 2627.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4042.84 | 07-JUL-15:00 | 41.15 | 19-JUL-03:00 |
August | 1439.81 | 05-AUG-14:09 | 2627.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3349.91 | 07-AUG-15:00 | 328.00 | 20-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2627.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3084.42 | 29-SEP-13:00 | 248.06 | 03-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 2627.79 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3139.82 | 02-OCT-14:00 | 315.06 | 29-OCT-07:03 |
November | 1439.81 | 04-NOV-14:09 | 2627.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1632.50 | 04-NOV-14:00 | 1275.90 | 30-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2627.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.91 | 28-DEC-14:00 | 2985.51 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.15 | |||||
Maximum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.35 | 2985.51 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2627.79 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2472.52 | 15-JAN-17:00 |
February | 1439.81 | 04-FEB-15:09 | 2627.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 826.32 | 22-FEB-15:00 | 2343.31 | 10-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2627.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.59 | 28-MAR-15:00 | 900.31 | 18-MAR-17:00 |
April | 1439.81 | 01-APR-14:09 | 2627.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4149.35 | 15-APR-15:00 | 247.05 | 22-APR-18:10 |
May | 1439.81 | 06-MAY-14:09 | 2627.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5010.92 | 03-MAY-15:00 | 92.31 | 13-MAY-07:10 |
June | 1439.81 | 03-JUN-14:09 | 2627.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.35 | 07-JUN-16:00 | 86.45 | 18-JUN-07:02 |
July | 1439.81 | 01-JUL-14:09 | 2627.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4042.84 | 07-JUL-15:00 | 40.77 | 19-JUL-03:00 |
August | 1439.81 | 05-AUG-14:09 | 2627.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3349.91 | 07-AUG-15:00 | 322.54 | 20-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2627.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3084.42 | 29-SEP-13:00 | 242.92 | 03-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 2627.79 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3139.82 | 02-OCT-14:00 | 313.72 | 29-OCT-07:03 |
November | 1439.81 | 04-NOV-14:09 | 2627.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1632.50 | 04-NOV-14:00 | 1275.90 | 30-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2627.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.91 | 28-DEC-14:00 | 2972.22 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.77 | |||||
Maximum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.35 | 2972.22 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2627.79 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2441.83 | 15-JAN-17:00 |
February | 1439.81 | 04-FEB-15:09 | 2627.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 826.37 | 22-FEB-15:00 | 2310.87 | 10-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 2627.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.59 | 28-MAR-15:00 | 900.31 | 18-MAR-17:00 |
April | 1439.81 | 01-APR-14:09 | 2627.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4149.35 | 15-APR-15:00 | 243.16 | 22-APR-18:10 |
May | 1439.81 | 06-MAY-14:09 | 2627.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5010.92 | 03-MAY-15:00 | 87.94 | 13-MAY-07:10 |
June | 1439.81 | 03-JUN-14:09 | 2627.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.35 | 07-JUN-16:00 | 84.00 | 18-JUN-07:02 |
July | 1439.81 | 01-JUL-14:09 | 2627.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4042.85 | 07-JUL-15:00 | 40.15 | 19-JUL-03:00 |
August | 1439.81 | 05-AUG-14:09 | 2627.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3349.40 | 07-AUG-15:00 | 323.19 | 20-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2627.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3084.42 | 29-SEP-13:00 | 244.30 | 03-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 2627.79 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3139.82 | 02-OCT-14:00 | 310.83 | 29-OCT-07:03 |
November | 1439.81 | 04-NOV-14:09 | 2627.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1632.50 | 04-NOV-14:00 | 1275.89 | 30-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2627.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.91 | 28-DEC-14:00 | 2937.15 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.15 | |||||
Maximum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.35 | 2937.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2627.79 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2433.04 | 15-JAN-17:00 |
February | 1439.81 | 04-FEB-15:09 | 2627.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 837.16 | 22-FEB-15:00 | 2237.60 | 10-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2627.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.59 | 28-MAR-15:00 | 1094.58 | 24-MAR-24:00 |
April | 1439.81 | 01-APR-14:09 | 2627.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.57 | 15-APR-15:00 | 386.62 | 22-APR-18:10 |
May | 1439.81 | 06-MAY-14:09 | 2627.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5132.86 | 03-MAY-15:00 | 107.54 | 15-MAY-03:00 |
June | 1439.81 | 03-JUN-14:09 | 2627.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5273.32 | 06-JUN-15:00 | 132.16 | 18-JUN-05:00 |
July | 1439.81 | 01-JUL-14:09 | 2627.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4120.47 | 07-JUL-15:00 | 100.66 | 19-JUL-03:00 |
August | 1439.81 | 05-AUG-14:09 | 2627.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3436.73 | 07-AUG-15:00 | 397.89 | 20-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 2627.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3172.65 | 29-SEP-13:00 | 311.40 | 03-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 2627.79 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3189.24 | 02-OCT-14:00 | 342.93 | 29-OCT-07:03 |
November | 1439.81 | 04-NOV-14:09 | 2627.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1648.27 | 04-NOV-14:00 | 1285.98 | 30-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2627.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.40 | 28-DEC-14:00 | 2924.85 | 21-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.66 | |||||
Maximum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5273.32 | 2924.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8877.73 | 12-JAN-15:00 | 1439.81 | 6976.27 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.13 |
February | 14472.09 | 25-FEB-09:03 | 539.93 | 11015.16 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.96 |
March | 40418.41 | 14-MAR-08:62 | 899.88 | 18358.60 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.04 |
April | 46814.34 | 08-APR-08:61 | 1259.84 | 25702.04 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 28.76 | 0.00 |
May | 44074.74 | 06-MAY-08:61 | 1259.84 | 25702.04 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 403.08 | 0.00 |
June | 41197.96 | 07-JUN-07:01 | 1259.84 | 2570.20 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 682.52 | 0.00 |
July | 35015.37 | 07-JUL-07:01 | 0.00 | 2570.20 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 506.07 | 0.00 |
August | 30745.50 | 09-AUG-07:01 | 1259.84 | 2570.20 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 250.03 | 0.00 |
September | 36357.96 | 26-SEP-08:61 | 1259.84 | 25702.04 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 76.68 | 0.00 |
October | 42737.92 | 16-OCT-08:61 | 1259.84 | 25702.04 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.91 |
November | 37958.85 | 09-NOV-09:02 | 899.88 | 18358.60 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.00 |
December | 10537.25 | 03-DEC-14:00 | 2159.72 | 6976.27 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 275.80 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8877.73 | 0.00 | 2570.20 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46814.34 | 2159.72 | 25702.04 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 682.52 | 394.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4838.06 | 12-JAN-15:00 | 719.90 | 3726.82 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.92 |
February | 9628.46 | 25-FEB-09:03 | 269.96 | 5884.46 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.87 |
March | 21739.40 | 14-MAR-08:62 | 449.94 | 9807.43 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.94 |
April | 24333.16 | 08-APR-08:61 | 629.92 | 13730.40 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 15.42 | 0.00 |
May | 22896.95 | 06-MAY-08:61 | 629.92 | 13730.40 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 218.83 | 0.00 |
June | 20819.63 | 07-JUN-08:61 | 629.92 | 13730.40 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 450.82 | 0.00 |
July | 17425.54 | 05-JUL-07:01 | 629.92 | 1373.04 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 267.24 | 0.00 |
August | 18486.33 | 20-AUG-07:01 | 629.92 | 1373.04 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 27.60 | 0.00 |
September | 19785.48 | 26-SEP-08:61 | 629.92 | 13730.40 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 44.06 | 0.00 |
October | 22985.50 | 16-OCT-08:61 | 629.92 | 13730.40 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.08 |
November | 20716.85 | 09-NOV-09:02 | 449.94 | 9807.43 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.11 |
December | 5687.35 | 02-DEC-14:00 | 1079.86 | 3726.82 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 53.06 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4838.06 | 269.96 | 1373.04 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24333.16 | 1079.86 | 13730.40 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 450.82 | 210.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4463.92 | 12-JAN-15:00 | 539.93 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.92 |
February | 9390.36 | 25-FEB-08:63 | 269.96 | 5321.96 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.81 |
March | 20823.77 | 29-MAR-07:02 | 539.93 | 10643.91 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.69 |
April | 24620.56 | 08-APR-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.62 |
May | 23211.93 | 06-MAY-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 164.86 | 0.00 |
June | 20821.63 | 07-JUN-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 379.99 | 0.00 |
July | 15771.73 | 07-JUL-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 293.61 | 0.00 |
August | 15020.64 | 03-AUG-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 107.01 | 0.00 |
September | 18041.32 | 27-SEP-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.54 |
October | 23037.01 | 23-OCT-07:02 | 539.93 | 10643.91 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.66 |
November | 18681.69 | 09-NOV-08:62 | 359.95 | 7095.94 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.92 |
December | 5424.08 | 02-DEC-14:00 | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 53.07 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4463.92 | 269.96 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24620.56 | 1079.86 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 379.99 | 217.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4369.42 | 12-JAN-15:00 | 539.93 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.92 |
February | 9175.76 | 25-FEB-08:63 | 269.96 | 5321.96 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.71 |
March | 20889.30 | 29-MAR-07:02 | 539.93 | 10643.91 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.60 |
April | 24672.13 | 08-APR-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.01 |
May | 23264.99 | 06-MAY-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 164.67 | 0.00 |
June | 20876.69 | 07-JUN-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 379.83 | 0.00 |
July | 16048.79 | 05-JUL-06:02 | 0.00 | 886.99 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 0.00 |
August | 15099.10 | 03-AUG-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 106.97 | 0.00 |
September | 18103.20 | 27-SEP-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.44 |
October | 23148.78 | 23-OCT-07:02 | 539.93 | 10643.91 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.41 |
November | 18605.10 | 09-NOV-08:62 | 359.95 | 7095.94 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.93 |
December | 5360.69 | 02-DEC-14:00 | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 53.07 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4369.42 | 0.00 | 886.99 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24672.13 | 1079.86 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 379.83 | 217.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4198.98 | 12-JAN-15:00 | 539.93 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.92 |
February | 8159.91 | 25-FEB-08:63 | 269.96 | 5321.96 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.09 |
March | 20727.88 | 14-MAR-07:02 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.55 |
April | 24576.60 | 08-APR-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.88 |
May | 23202.28 | 06-MAY-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 164.87 | 0.00 |
June | 20814.56 | 07-JUN-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 379.93 | 0.00 |
July | 15976.46 | 05-JUL-06:02 | 0.00 | 886.99 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 20.99 | 0.00 |
August | 14988.95 | 03-AUG-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 107.00 | 0.00 |
September | 18015.99 | 27-SEP-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.52 |
October | 23036.30 | 23-OCT-07:02 | 539.93 | 10643.91 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.99 |
November | 17402.76 | 09-NOV-08:62 | 359.95 | 7095.94 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.53 |
December | 5224.49 | 02-DEC-14:00 | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 53.07 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4198.98 | 0.00 | 886.99 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24576.60 | 1079.86 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 379.93 | 217.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7315.46 | 12-JAN-15:10 | 2483.68 | 5255.58 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.76 |
February | 11434.72 | 25-FEB-09:03 | 1187.85 | 8298.28 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.27 |
March | 38894.46 | 28-MAR-08:62 | 1979.74 | 13830.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.21 |
April | 44847.07 | 08-APR-08:61 | 2771.64 | 19362.66 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 0.00 |
May | 42737.60 | 29-MAY-08:61 | 0.00 | 1936.27 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 464.69 | 0.00 |
June | 39534.66 | 07-JUN-07:01 | 0.00 | 1936.27 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 611.38 | 0.00 |
July | 33460.02 | 07-JUL-07:01 | 0.00 | 1936.27 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 462.13 | 0.00 |
August | 29802.13 | 09-AUG-07:01 | 0.00 | 1936.27 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 242.66 | 0.00 |
September | 34754.88 | 26-SEP-08:61 | 2771.64 | 19362.66 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 70.97 | 0.00 |
October | 41464.90 | 23-OCT-08:62 | 1979.74 | 13830.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.29 |
November | 38575.06 | 11-NOV-10:02 | 1979.74 | 13830.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.25 |
December | 9101.03 | 02-DEC-14:10 | 2771.64 | 5255.58 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 77.67 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7315.46 | 0.00 | 1936.27 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44847.07 | 2771.64 | 19362.66 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 611.38 | 368.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3763.81 | 12-JAN-15:10 | 1241.83 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 |
February | 5789.85 | 25-FEB-09:03 | 593.92 | 4149.14 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.43 |
March | 20398.79 | 28-MAR-08:62 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.85 |
April | 23407.87 | 08-APR-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 19.08 | 0.00 |
May | 22352.08 | 29-MAY-08:61 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 261.00 | 0.00 |
June | 20491.65 | 12-JUN-07:01 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 337.95 | 0.00 |
July | 17499.27 | 07-JUL-07:01 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 267.14 | 0.00 |
August | 15505.85 | 08-AUG-07:01 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 150.00 | 0.00 |
September | 18256.00 | 26-SEP-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 41.62 | 0.00 |
October | 21732.49 | 23-OCT-08:62 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.88 |
November | 20219.24 | 11-NOV-10:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.22 |
December | 4695.53 | 02-DEC-14:10 | 1385.82 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 44.36 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3763.81 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23407.87 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 337.95 | 208.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3694.06 | 12-JAN-15:10 | 1241.83 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 |
February | 5547.34 | 22-FEB-14:00 | 1277.83 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 799.71 | 0.00 |
March | 20281.88 | 28-MAR-08:62 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.43 |
April | 23307.97 | 08-APR-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 20.54 | 0.00 |
May | 22261.89 | 29-MAY-08:61 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 262.01 | 0.00 |
June | 20394.20 | 12-JUN-07:01 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 338.55 | 0.00 |
July | 16842.21 | 07-JUL-07:01 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 267.25 | 0.00 |
August | 15412.15 | 08-AUG-07:01 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 150.84 | 0.00 |
September | 18176.92 | 26-SEP-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 41.47 | 0.00 |
October | 21631.25 | 23-OCT-08:62 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.07 |
November | 20110.14 | 11-NOV-10:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.15 |
December | 4636.47 | 02-DEC-14:10 | 1385.82 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 44.36 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3694.06 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23307.97 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 799.71 | 119.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3538.14 | 12-JAN-15:10 | 1241.83 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 |
February | 5425.22 | 22-FEB-14:00 | 1277.83 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 799.92 | 0.00 |
March | 20172.59 | 28-MAR-08:62 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.99 |
April | 23276.54 | 08-APR-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 23.90 | 0.00 |
May | 22257.43 | 29-MAY-08:61 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 263.55 | 0.00 |
June | 20418.86 | 12-JUN-07:01 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 337.92 | 0.00 |
July | 17033.62 | 07-JUL-07:01 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 267.21 | 0.00 |
August | 15444.11 | 08-AUG-07:01 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 150.24 | 0.00 |
September | 18181.13 | 26-SEP-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 41.57 | 0.00 |
October | 21610.12 | 23-OCT-08:62 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.71 |
November | 20039.75 | 11-NOV-10:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.30 |
December | 4529.37 | 02-DEC-14:20 | 1385.82 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 35.65 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3538.14 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23276.54 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 799.92 | 117.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3478.79 | 12-JAN-15:10 | 1241.83 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.09 |
February | 5609.03 | 22-FEB-14:00 | 1277.83 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 807.44 | 0.00 |
March | 20928.15 | 12-MAR-09:02 | 1187.84 | 8298.28 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.16 |
April | 24653.93 | 08-APR-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 34.79 | 0.00 |
May | 23650.34 | 29-MAY-08:61 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 351.91 | 0.00 |
June | 22529.90 | 12-JUN-07:01 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 386.37 | 0.00 |
July | 18367.55 | 07-JUL-07:01 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 293.82 | 0.00 |
August | 15917.29 | 09-AUG-07:01 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 140.78 | 0.00 |
September | 19322.64 | 27-SEP-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 40.53 | 0.00 |
October | 22974.42 | 23-OCT-08:62 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.62 |
November | 21263.75 | 11-NOV-10:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.66 |
December | 4635.04 | 02-DEC-14:10 | 1385.82 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 44.67 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3478.79 | 0.00 | 968.13 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24653.93 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 807.44 | 131.62 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.108792E+12 | 88350.60 | 26-JAN-13:30 | 0.426847E+09 | 63785.83 | 02-JAN-09:09 |
February | 0.106896E+12 | 96501.64 | 22-FEB-14:09 | 1114094.60 | 1856.82 | 02-FEB-09:09 |
March | 0.134825E+12 | 118939.15 | 28-MAR-16:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.150007E+12 | 137191.59 | 16-APR-13:39 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.176985E+12 | 149142.67 | 03-MAY-15:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.179280E+12 | 156380.00 | 10-JUN-16:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.182903E+12 | 156768.41 | 01-JUL-14:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.182960E+12 | 150296.41 | 27-AUG-13:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.166111E+12 | 141790.46 | 14-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.150087E+12 | 130292.28 | 04-OCT-12:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.126687E+12 | 109151.20 | 09-NOV-13:20 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.113140E+12 | 90153.49 | 28-DEC-18:10 | 2793282.29 | 2204.57 | 21-DEC-09:09 |
Annual Sum or Average | 0.177867E+13 | 0.430754E+09 | ||||
Minimum of Months | 0.106896E+12 | 88350.60 | 0.00 | 0.00 | ||
Maximum of Months | 0.182960E+12 | 156768.41 | 0.426847E+09 | 63785.83 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.496324E+11 | 0.106487E+11 | 0.108804E+11 | 0.00 | 0.252435E+11 | 0.00 | 0.00 | 0.715686E+10 | 0.00 | 0.00 | 0.00 | 0.522984E+10 | 0.00 |
February | 0.449372E+11 | 0.921506E+10 | 0.985143E+10 | 0.00 | 0.228775E+11 | 0.00 | 0.00 | 0.153121E+11 | 0.00 | 0.00 | 0.00 | 0.470276E+10 | 0.00 |
March | 0.503750E+11 | 0.954915E+10 | 0.110523E+11 | 0.00 | 0.257205E+11 | 0.00 | 0.00 | 0.329837E+11 | 0.00 | 0.00 | 0.00 | 0.514395E+10 | 0.00 |
April | 0.481627E+11 | 0.860185E+10 | 0.105581E+11 | 0.00 | 0.246038E+11 | 0.00 | 0.00 | 0.532428E+11 | 0.00 | 0.00 | 0.00 | 0.483735E+10 | 0.00 |
May | 0.499854E+11 | 0.832696E+10 | 0.109629E+11 | 0.00 | 0.256161E+11 | 0.00 | 0.00 | 0.772116E+11 | 0.00 | 0.00 | 0.00 | 0.488180E+10 | 0.00 |
June | 0.486922E+11 | 0.775604E+10 | 0.106818E+11 | 0.00 | 0.249934E+11 | 0.00 | 0.00 | 0.825091E+11 | 0.00 | 0.00 | 0.00 | 0.464711E+10 | 0.00 |
July | 0.494924E+11 | 0.817894E+10 | 0.108460E+11 | 0.00 | 0.253949E+11 | 0.00 | 0.00 | 0.842493E+11 | 0.00 | 0.00 | 0.00 | 0.474158E+10 | 0.00 |
August | 0.503385E+11 | 0.863145E+10 | 0.110454E+11 | 0.00 | 0.258606E+11 | 0.00 | 0.00 | 0.822882E+11 | 0.00 | 0.00 | 0.00 | 0.479624E+10 | 0.00 |
September | 0.481992E+11 | 0.896554E+10 | 0.105649E+11 | 0.00 | 0.246882E+11 | 0.00 | 0.00 | 0.689871E+11 | 0.00 | 0.00 | 0.00 | 0.470576E+10 | 0.00 |
October | 0.496324E+11 | 0.992976E+10 | 0.108804E+11 | 0.00 | 0.253569E+11 | 0.00 | 0.00 | 0.493177E+11 | 0.00 | 0.00 | 0.00 | 0.496994E+10 | 0.00 |
November | 0.480897E+11 | 0.101624E+11 | 0.105443E+11 | 0.00 | 0.245247E+11 | 0.00 | 0.00 | 0.284353E+11 | 0.00 | 0.00 | 0.00 | 0.493071E+10 | 0.00 |
December | 0.495289E+11 | 0.108475E+11 | 0.108529E+11 | 0.00 | 0.251754E+11 | 0.00 | 0.00 | 0.115478E+11 | 0.00 | 0.00 | 0.00 | 0.518751E+10 | 0.00 |
Annual Sum or Average | 0.587066E+12 | 0.110813E+12 | 0.128721E+12 | 0.300055E+12 | 0.00 | 0.593242E+12 | 0.587746E+11 | ||||||
Minimum of Months | 0.449372E+11 | 0.775604E+10 | 0.985143E+10 | 0.00 | 0.228775E+11 | 0.00 | 0.00 | 0.715686E+10 | 0.00 | 0.00 | 0.00 | 0.464711E+10 | 0.00 |
Maximum of Months | 0.503750E+11 | 0.108475E+11 | 0.110523E+11 | 0.00 | 0.258606E+11 | 0.00 | 0.00 | 0.842493E+11 | 0.00 | 0.00 | 0.00 | 0.522984E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.426847E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1114094.60 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 2793282.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.430754E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.426847E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 36581.55 | 01-JAN-11:09 | 7048.38 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 17417.21 | 01-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 36581.55 | 01-FEB-10:09 | 7048.38 | 01-FEB-00:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 17417.21 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 36581.55 | 01-MAR-10:09 | 7048.38 | 01-MAR-00:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 17417.21 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 36581.55 | 01-APR-09:09 | 7048.38 | 01-APR-00:10 | 8089.53 | 01-APR-09:09 | 0.00 | 17417.21 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 36581.55 | 01-MAY-09:09 | 7048.38 | 01-MAY-00:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 17417.21 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 36581.55 | 01-JUN-09:09 | 7048.38 | 01-JUN-00:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 17417.21 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 36581.55 | 01-JUL-09:09 | 7048.38 | 01-JUL-00:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 17417.21 | 01-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 36581.55 | 01-AUG-09:09 | 7048.38 | 01-AUG-00:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 17417.21 | 01-AUG-07:19 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 36581.55 | 01-SEP-09:09 | 7048.38 | 01-SEP-00:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 17417.21 | 01-SEP-07:19 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 36581.55 | 01-OCT-10:09 | 7048.38 | 01-OCT-00:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 17417.21 | 01-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 36581.55 | 01-NOV-09:09 | 7048.38 | 01-NOV-00:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 17417.21 | 01-NOV-07:19 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 36581.55 | 01-DEC-10:09 | 7048.38 | 01-DEC-00:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 17417.21 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 36581.55 | 7048.38 | 8089.53 | 0.00 | 17417.21 | 0.00 | 0.00 | |||||
Maximum of Months | 36581.55 | 7048.38 | 8089.53 | 0.00 | 17417.21 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 18458.26 | 12-JAN-15:09 | 0.00 | 0.00 | 0.00 | 11816.20 | 11-JAN-13:50 | 0.00 |
February | 29161.86 | 22-FEB-14:50 | 0.00 | 0.00 | 0.00 | 8906.70 | 03-FEB-12:50 | 0.00 |
March | 50899.85 | 28-MAR-14:00 | 0.00 | 0.00 | 0.00 | 7564.45 | 28-MAR-12:39 | 0.00 |
April | 69245.10 | 16-APR-14:00 | 0.00 | 0.00 | 0.00 | 9676.47 | 08-APR-12:09 | 0.00 |
May | 82123.86 | 03-MAY-14:00 | 0.00 | 0.00 | 0.00 | 9640.70 | 02-MAY-16:00 | 0.00 |
June | 89394.78 | 10-JUN-15:00 | 0.00 | 0.00 | 0.00 | 9461.44 | 17-JUN-13:00 | 0.00 |
July | 87246.78 | 01-JUL-14:50 | 0.00 | 0.00 | 0.00 | 9631.81 | 05-JUL-14:09 | 0.00 |
August | 83506.57 | 27-AUG-14:09 | 0.00 | 0.00 | 0.00 | 7539.82 | 16-AUG-12:09 | 0.00 |
September | 74364.71 | 14-SEP-16:10 | 0.00 | 0.00 | 0.00 | 7956.75 | 05-SEP-13:20 | 0.00 |
October | 63495.53 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 7557.60 | 25-OCT-13:39 | 0.00 |
November | 39597.51 | 09-NOV-13:30 | 0.00 | 0.00 | 0.00 | 7569.79 | 27-NOV-13:50 | 0.00 |
December | 22713.36 | 28-DEC-13:00 | 0.00 | 0.00 | 0.00 | 8974.34 | 11-DEC-12:20 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18458.26 | 0.00 | 0.00 | 0.00 | 7539.82 | 0.00 | ||
Maximum of Months | 89394.78 | 0.00 | 0.00 | 0.00 | 11816.20 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 88350.60 | 26-JAN-13:30 | 36581.55 | 8089.53 | 0.00 | 0.00 | 17417.21 | 0.00 | 0.00 | 16565.89 | 0.00 |
February | 96501.64 | 22-FEB-14:09 | 36581.55 | 8089.53 | 0.00 | 0.00 | 17417.21 | 0.00 | 0.00 | 28960.01 | 0.00 |
March | 118939.15 | 28-MAR-16:30 | 36581.55 | 8089.53 | 0.00 | 0.00 | 17417.21 | 0.00 | 0.00 | 49307.77 | 0.00 |
April | 137191.59 | 16-APR-13:39 | 36581.55 | 8089.53 | 0.00 | 0.00 | 17417.21 | 0.00 | 0.00 | 67904.80 | 0.00 |
May | 149142.67 | 03-MAY-15:20 | 36581.55 | 8089.53 | 0.00 | 0.00 | 17417.21 | 0.00 | 0.00 | 81627.68 | 0.00 |
June | 156380.00 | 10-JUN-16:19 | 36581.55 | 8089.53 | 0.00 | 0.00 | 17417.21 | 0.00 | 0.00 | 88867.58 | 0.00 |
July | 156768.41 | 01-JUL-14:20 | 36581.55 | 8089.53 | 0.00 | 0.00 | 17417.21 | 0.00 | 0.00 | 87150.94 | 0.00 |
August | 150296.41 | 27-AUG-13:30 | 36581.55 | 8089.53 | 0.00 | 0.00 | 17417.21 | 0.00 | 0.00 | 82792.93 | 0.00 |
September | 141790.46 | 14-SEP-14:00 | 36581.55 | 8089.53 | 0.00 | 0.00 | 17417.21 | 0.00 | 0.00 | 73928.74 | 0.00 |
October | 130292.28 | 04-OCT-12:39 | 36581.55 | 8089.53 | 0.00 | 0.00 | 17417.21 | 0.00 | 0.00 | 62763.05 | 0.00 |
November | 109151.20 | 09-NOV-13:20 | 36581.55 | 8089.53 | 0.00 | 0.00 | 17417.21 | 0.00 | 0.00 | 39567.91 | 0.00 |
December | 90153.49 | 28-DEC-18:10 | 36581.55 | 8089.53 | 7048.38 | 0.00 | 17417.21 | 0.00 | 0.00 | 16222.95 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 88350.60 | 36581.55 | 8089.53 | 0.00 | 0.00 | 17417.21 | 0.00 | 0.00 | 16222.95 | 0.00 | |
Maximum of Months | 156768.41 | 36581.55 | 8089.53 | 7048.38 | 0.00 | 17417.21 | 0.00 | 0.00 | 88867.58 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 63785.83 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1856.82 | 02-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 2204.57 | 21-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 63785.83 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.33 | 24.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.51 | 2.50 | 24.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.59 | 5.00 | 24.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.54 | 5.00 | 24.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.50 | 2.33 | 24.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.17 | 24.54 | 15.17 | 24.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.59 | 5.00 | 24.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.49 | 0.83 | 24.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.51 | 3.83 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.48 | 2.33 | 24.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.45 | 0.33 | 24.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.33 | 24.49 | 7.33 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.51 | 3.83 | 24.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.51 | 2.50 | 24.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.60 | 5.00 | 24.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.58 | 5.00 | 24.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.54 | 3.17 | 24.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.83 | 24.57 | 15.83 | 24.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.60 | 5.00 | 24.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.17 | 24.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.52 | 2.50 | 24.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.60 | 5.00 | 24.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.58 | 5.17 | 24.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.54 | 3.17 | 24.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.00 | 24.57 | 16.00 | 24.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.60 | 5.17 | 24.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.17 | 24.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.52 | 2.50 | 24.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.61 | 5.00 | 24.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.59 | 5.00 | 24.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.54 | 3.17 | 24.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.83 | 24.57 | 15.83 | 24.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.61 | 5.00 | 24.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.48 | 1.00 | 24.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.54 | 3.00 | 24.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.65 | 5.17 | 24.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.62 | 5.17 | 24.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.57 | 3.50 | 24.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.83 | 24.60 | 17.83 | 24.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.65 | 5.17 | 24.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.50 | 24.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.51 | 2.67 | 24.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.62 | 5.00 | 24.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.59 | 5.00 | 24.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.55 | 3.50 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.67 | 24.57 | 16.67 | 24.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.62 | 5.00 | 24.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.50 | 24.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.52 | 2.67 | 24.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.62 | 5.00 | 24.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.59 | 5.00 | 24.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.55 | 3.50 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.67 | 24.57 | 16.67 | 24.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.62 | 5.00 | 24.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.50 | 24.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.52 | 2.67 | 24.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.62 | 5.00 | 24.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.59 | 5.00 | 24.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.55 | 3.50 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.67 | 24.58 | 16.67 | 24.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.62 | 5.00 | 24.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.33 | 24.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.51 | 2.67 | 24.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.64 | 5.00 | 24.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.59 | 5.17 | 24.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.54 | 3.17 | 24.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.33 | 24.58 | 16.33 | 24.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.64 | 5.17 | 24.64 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 100.83 | 22.78 | 88.33 | 23.88 | 0.00 | 0.00 |
February | 42.00 | 23.11 | 203.67 | 23.89 | 0.00 | 0.00 |
March | 8.50 | 23.73 | 376.33 | 23.92 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 457.50 | 23.97 | 0.00 | 0.00 |
May | 26.67 | 24.63 | 496.00 | 23.99 | 26.67 | 24.63 |
June | 125.67 | 24.16 | 480.00 | 23.99 | 125.67 | 24.16 |
July | 324.67 | 24.04 | 496.00 | 23.99 | 324.67 | 24.04 |
August | 367.50 | 24.04 | 496.00 | 24.00 | 367.50 | 24.04 |
September | 226.00 | 24.05 | 480.00 | 23.98 | 226.00 | 24.05 |
October | 3.83 | 24.65 | 494.17 | 23.96 | 3.83 | 24.65 |
November | 3.50 | 23.57 | 406.00 | 23.91 | 0.00 | 0.00 |
December | 68.50 | 23.23 | 182.67 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 1297.67 | 23.89 | 4656.67 | 23.96 | 1074.33 | 24.07 |
Minimum of Months | 0.00 | 0.00 | 88.33 | 23.88 | 0.00 | 0.00 |
Maximum of Months | 367.50 | 24.65 | 496.00 | 24.00 | 367.50 | 24.65 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.17 | 22.87 | 79.50 | 23.89 | 0.00 | 0.00 |
February | 28.33 | 23.25 | 197.00 | 23.89 | 0.00 | 0.00 |
March | 1.17 | 23.85 | 371.50 | 23.93 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 444.33 | 23.98 | 0.00 | 0.00 |
May | 16.17 | 24.48 | 496.00 | 23.99 | 16.17 | 24.48 |
June | 101.83 | 24.14 | 480.00 | 23.99 | 101.83 | 24.14 |
July | 276.83 | 24.05 | 496.00 | 23.99 | 276.83 | 24.05 |
August | 308.00 | 24.05 | 496.00 | 24.00 | 308.00 | 24.05 |
September | 181.83 | 23.99 | 480.00 | 23.98 | 181.83 | 23.99 |
October | 0.67 | 24.65 | 491.33 | 23.96 | 0.67 | 24.65 |
November | 2.33 | 23.65 | 382.83 | 23.92 | 0.00 | 0.00 |
December | 51.17 | 23.38 | 147.17 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 1040.50 | 23.92 | 4561.67 | 23.97 | 885.33 | 24.05 |
Minimum of Months | 0.00 | 0.00 | 79.50 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 308.00 | 24.65 | 496.00 | 24.00 | 308.00 | 24.65 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 83.83 | 22.75 | 57.17 | 23.98 | 0.00 | 0.00 |
February | 28.83 | 23.14 | 160.00 | 24.07 | 0.00 | 0.00 |
March | 2.00 | 25.32 | 300.33 | 24.11 | 0.67 | 28.29 |
April | 7.83 | 28.74 | 339.33 | 24.19 | 7.83 | 28.74 |
May | 34.67 | 26.38 | 375.00 | 24.22 | 34.67 | 26.38 |
June | 118.67 | 24.73 | 366.00 | 24.22 | 118.67 | 24.73 |
July | 271.00 | 24.31 | 369.00 | 24.21 | 271.00 | 24.31 |
August | 304.00 | 24.23 | 379.00 | 24.18 | 304.00 | 24.23 |
September | 199.33 | 24.31 | 360.00 | 24.17 | 199.33 | 24.31 |
October | 9.33 | 26.67 | 371.00 | 24.13 | 9.33 | 26.67 |
November | 2.83 | 23.77 | 304.33 | 24.05 | 0.17 | 27.79 |
December | 53.17 | 23.26 | 104.00 | 24.04 | 0.00 | 0.00 |
Annual Sum or Average | 1115.50 | 24.25 | 3485.17 | 24.16 | 945.67 | 24.48 |
Minimum of Months | 2.00 | 22.75 | 57.17 | 23.98 | 0.00 | 0.00 |
Maximum of Months | 304.00 | 28.74 | 379.00 | 24.22 | 304.00 | 28.74 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 95.00 | 22.73 | 50.17 | 23.98 | 0.17 | 21.30 |
February | 30.33 | 23.10 | 154.00 | 24.07 | 0.00 | 0.00 |
March | 2.83 | 24.89 | 299.33 | 24.11 | 0.67 | 28.30 |
April | 8.17 | 28.73 | 340.67 | 24.19 | 8.17 | 28.73 |
May | 34.67 | 26.41 | 375.00 | 24.22 | 34.67 | 26.41 |
June | 118.00 | 24.74 | 366.00 | 24.23 | 118.00 | 24.74 |
July | 265.67 | 24.32 | 369.00 | 24.21 | 265.67 | 24.32 |
August | 302.00 | 24.24 | 379.00 | 24.18 | 302.00 | 24.24 |
September | 197.83 | 24.31 | 360.00 | 24.17 | 197.83 | 24.31 |
October | 9.33 | 26.68 | 371.00 | 24.13 | 9.33 | 26.68 |
November | 3.00 | 23.73 | 302.17 | 24.05 | 0.17 | 27.81 |
December | 58.17 | 23.25 | 94.50 | 24.03 | 0.00 | 0.00 |
Annual Sum or Average | 1125.00 | 24.23 | 3460.83 | 24.16 | 936.67 | 24.49 |
Minimum of Months | 2.83 | 22.73 | 50.17 | 23.98 | 0.00 | 0.00 |
Maximum of Months | 302.00 | 28.73 | 379.00 | 24.23 | 302.00 | 28.73 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 108.33 | 22.72 | 42.83 | 23.96 | 0.50 | 21.33 |
February | 34.33 | 23.07 | 136.67 | 24.08 | 0.00 | 0.00 |
March | 4.83 | 24.44 | 291.50 | 24.11 | 0.67 | 28.26 |
April | 7.83 | 28.72 | 338.50 | 24.19 | 7.83 | 28.72 |
May | 34.67 | 26.36 | 375.00 | 24.22 | 34.67 | 26.36 |
June | 119.83 | 24.73 | 366.00 | 24.22 | 119.83 | 24.73 |
July | 270.33 | 24.31 | 369.00 | 24.21 | 270.33 | 24.31 |
August | 304.17 | 24.23 | 379.00 | 24.17 | 304.17 | 24.23 |
September | 199.00 | 24.31 | 360.00 | 24.16 | 199.00 | 24.31 |
October | 9.33 | 26.60 | 370.83 | 24.12 | 9.33 | 26.60 |
November | 3.83 | 23.67 | 293.67 | 24.05 | 0.17 | 27.76 |
December | 68.17 | 23.24 | 82.67 | 24.02 | 0.00 | 0.00 |
Annual Sum or Average | 1164.67 | 24.19 | 3405.67 | 24.16 | 946.50 | 24.47 |
Minimum of Months | 3.83 | 22.72 | 42.83 | 23.96 | 0.00 | 0.00 |
Maximum of Months | 304.17 | 28.72 | 379.00 | 24.22 | 304.17 | 28.72 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 130.67 | 22.93 | 22.67 | 23.87 | 0.50 | 21.03 |
February | 31.50 | 23.18 | 97.00 | 23.97 | 0.00 | 0.00 |
March | 4.83 | 24.27 | 252.50 | 23.96 | 0.50 | 28.32 |
April | 4.00 | 28.98 | 305.83 | 24.01 | 4.00 | 28.98 |
May | 25.17 | 25.24 | 344.00 | 24.02 | 25.17 | 25.24 |
June | 110.67 | 24.19 | 336.00 | 24.00 | 110.67 | 24.19 |
July | 260.67 | 24.08 | 338.00 | 24.04 | 260.67 | 24.08 |
August | 294.67 | 24.01 | 348.00 | 23.99 | 294.67 | 24.01 |
September | 185.50 | 24.09 | 330.00 | 24.01 | 185.50 | 24.09 |
October | 6.83 | 26.30 | 339.17 | 23.99 | 6.83 | 26.30 |
November | 1.83 | 23.57 | 254.00 | 23.95 | 0.00 | 0.00 |
December | 65.67 | 23.23 | 53.17 | 23.94 | 0.00 | 0.00 |
Annual Sum or Average | 1122.00 | 23.92 | 3020.33 | 24.00 | 888.50 | 24.14 |
Minimum of Months | 1.83 | 22.93 | 22.67 | 23.87 | 0.00 | 0.00 |
Maximum of Months | 294.67 | 28.98 | 348.00 | 24.04 | 294.67 | 28.98 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 144.67 | 23.02 | 18.83 | 23.87 | 0.50 | 21.06 |
February | 36.00 | 23.27 | 75.50 | 23.98 | 0.00 | 0.00 |
March | 6.17 | 24.19 | 222.00 | 23.97 | 0.50 | 28.28 |
April | 3.67 | 28.97 | 287.00 | 24.02 | 3.67 | 28.97 |
May | 25.00 | 25.23 | 344.00 | 24.01 | 25.00 | 25.23 |
June | 110.67 | 24.18 | 336.00 | 24.00 | 110.67 | 24.18 |
July | 261.00 | 24.08 | 338.00 | 24.04 | 261.00 | 24.08 |
August | 300.00 | 24.00 | 348.00 | 23.99 | 300.00 | 24.00 |
September | 184.83 | 24.08 | 330.00 | 24.00 | 184.83 | 24.08 |
October | 6.33 | 26.27 | 337.50 | 23.99 | 6.33 | 26.27 |
November | 2.00 | 23.63 | 224.33 | 23.96 | 0.00 | 0.00 |
December | 71.83 | 23.30 | 37.83 | 23.95 | 0.00 | 0.00 |
Annual Sum or Average | 1152.17 | 23.92 | 2899.00 | 24.00 | 892.50 | 24.14 |
Minimum of Months | 2.00 | 23.02 | 18.83 | 23.87 | 0.00 | 0.00 |
Maximum of Months | 300.00 | 28.97 | 348.00 | 24.04 | 300.00 | 28.97 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 154.17 | 23.03 | 16.67 | 23.86 | 0.50 | 21.02 |
February | 39.00 | 23.26 | 67.33 | 23.98 | 0.00 | 0.00 |
March | 7.00 | 24.15 | 215.83 | 23.97 | 0.50 | 28.26 |
April | 3.67 | 28.96 | 284.67 | 24.02 | 3.67 | 28.96 |
May | 24.83 | 25.21 | 344.00 | 24.01 | 24.83 | 25.21 |
June | 111.67 | 24.18 | 336.00 | 24.00 | 111.67 | 24.18 |
July | 263.17 | 24.08 | 338.00 | 24.04 | 263.17 | 24.08 |
August | 301.83 | 24.00 | 348.00 | 23.99 | 301.83 | 24.00 |
September | 185.50 | 24.08 | 330.00 | 24.00 | 185.50 | 24.08 |
October | 6.33 | 26.25 | 337.17 | 23.99 | 6.33 | 26.25 |
November | 2.00 | 23.60 | 220.17 | 23.96 | 0.00 | 0.00 |
December | 75.67 | 23.29 | 35.50 | 23.95 | 0.00 | 0.00 |
Annual Sum or Average | 1174.83 | 23.90 | 2873.33 | 24.00 | 898.00 | 24.13 |
Minimum of Months | 2.00 | 23.03 | 16.67 | 23.86 | 0.00 | 0.00 |
Maximum of Months | 301.83 | 28.96 | 348.00 | 24.04 | 301.83 | 28.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 169.50 | 23.02 | 12.33 | 23.82 | 0.67 | 21.09 |
February | 49.33 | 23.23 | 59.17 | 23.99 | 0.00 | 0.00 |
March | 8.67 | 24.04 | 206.83 | 23.97 | 0.50 | 28.23 |
April | 3.50 | 28.99 | 283.00 | 24.02 | 3.50 | 28.99 |
May | 25.17 | 25.19 | 344.00 | 24.01 | 25.17 | 25.19 |
June | 112.00 | 24.18 | 336.00 | 24.00 | 112.00 | 24.18 |
July | 262.33 | 24.08 | 338.00 | 24.04 | 262.33 | 24.08 |
August | 300.50 | 24.00 | 348.00 | 23.99 | 300.50 | 24.00 |
September | 185.50 | 24.08 | 330.00 | 24.00 | 185.50 | 24.08 |
October | 6.50 | 26.20 | 337.17 | 23.99 | 6.50 | 26.20 |
November | 2.83 | 23.61 | 218.67 | 23.96 | 0.00 | 0.00 |
December | 81.17 | 23.24 | 30.67 | 23.95 | 0.00 | 0.00 |
Annual Sum or Average | 1207.00 | 23.88 | 2843.83 | 24.00 | 896.67 | 24.13 |
Minimum of Months | 2.83 | 23.02 | 12.33 | 23.82 | 0.00 | 0.00 |
Maximum of Months | 300.50 | 28.99 | 348.00 | 24.04 | 300.50 | 28.99 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 197.00 | 23.00 | 8.00 | 23.66 | 1.00 | 21.13 |
February | 66.17 | 23.12 | 50.33 | 23.99 | 0.00 | 0.00 |
March | 15.33 | 23.81 | 201.50 | 23.98 | 0.50 | 28.30 |
April | 4.33 | 28.92 | 292.17 | 24.02 | 4.33 | 28.92 |
May | 28.50 | 25.09 | 344.00 | 24.02 | 28.50 | 25.09 |
June | 105.00 | 24.21 | 336.00 | 24.00 | 105.00 | 24.21 |
July | 250.17 | 24.09 | 338.00 | 24.04 | 250.17 | 24.09 |
August | 273.83 | 24.02 | 348.00 | 23.99 | 273.83 | 24.02 |
September | 175.33 | 24.10 | 330.00 | 24.01 | 175.33 | 24.10 |
October | 7.50 | 26.32 | 338.17 | 24.00 | 7.50 | 26.32 |
November | 4.83 | 23.73 | 232.50 | 23.96 | 0.17 | 27.68 |
December | 91.17 | 23.16 | 33.00 | 23.95 | 0.00 | 0.00 |
Annual Sum or Average | 1219.17 | 23.84 | 2851.67 | 24.00 | 846.33 | 24.16 |
Minimum of Months | 4.33 | 23.00 | 8.00 | 23.66 | 0.00 | 0.00 |
Maximum of Months | 273.83 | 28.92 | 348.00 | 24.04 | 273.83 | 28.92 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.65077 | 37.82377 | 0.31866 | 7.61787 |
February | 448.00000 | 23.81138 | 39.86756 | 0.39756 | 8.51261 |
March | 496.00000 | 23.92018 | 41.06798 | 0.47231 | 9.76816 |
April | 480.00000 | 23.98382 | 41.32239 | 0.54114 | 11.28257 |
May | 496.00000 | 24.02256 | 50.34297 | -0.1663 | 5.90893 |
June | 480.00000 | 24.02440 | 56.67271 | -0.1011 | 5.58333 |
July | 496.00000 | 24.01935 | 63.62702 | -0.0579 | 5.48355 |
August | 496.00000 | 24.03414 | 65.09098 | -0.0520 | 5.46720 |
September | 480.00000 | 24.00973 | 61.60259 | -0.1020 | 5.51913 |
October | 496.00000 | 23.97969 | 47.20289 | 0.58879 | 12.39134 |
November | 480.00000 | 23.91478 | 40.67454 | 0.48017 | 9.89206 |
December | 496.00000 | 23.79401 | 37.09917 | 0.37030 | 8.11066 |
Annual Sum or Average | 5840.00000 | 23.93080 | 48.58728 | 0.22292 | 7.95574 |
Minimum of Months | 448.00000 | 23.65077 | 37.09917 | -0.1663 | 5.46720 |
Maximum of Months | 496.00000 | 24.03414 | 65.09098 | 0.58879 | 12.39134 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.73161 | 37.56318 | 0.33623 | 7.69634 |
February | 448.00000 | 23.85224 | 39.18799 | 0.40341 | 8.53074 |
March | 496.00000 | 23.93615 | 40.44150 | 0.46782 | 9.65823 |
April | 480.00000 | 23.99135 | 41.05363 | 0.52712 | 10.96244 |
May | 496.00000 | 24.02319 | 49.64288 | -0.2010 | 6.17107 |
June | 480.00000 | 24.02346 | 55.70733 | -0.1448 | 5.79402 |
July | 496.00000 | 24.01686 | 62.13314 | -0.1067 | 5.62336 |
August | 496.00000 | 24.03188 | 63.40887 | -0.1038 | 5.61685 |
September | 480.00000 | 24.00818 | 59.73510 | -0.1516 | 5.77555 |
October | 496.00000 | 23.98331 | 46.07749 | 0.56134 | 11.72343 |
November | 480.00000 | 23.92419 | 39.92400 | 0.46546 | 9.58417 |
December | 496.00000 | 23.83484 | 36.77386 | 0.37514 | 8.09545 |
Annual Sum or Average | 5840.00000 | 23.94677 | 47.69078 | 0.20105 | 7.93006 |
Minimum of Months | 448.00000 | 23.73161 | 36.77386 | -0.2010 | 5.61685 |
Maximum of Months | 496.00000 | 24.03188 | 63.40887 | 0.56134 | 11.72343 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.62827 | 37.19426 | 0.30074 | 7.48280 |
February | 336.00000 | 23.89122 | 39.03778 | 0.40508 | 8.67676 |
March | 379.00000 | 24.04074 | 40.26022 | 0.48860 | 10.20955 |
April | 360.00000 | 24.14594 | 40.63100 | 0.56202 | 12.03043 |
May | 375.00000 | 24.18704 | 50.05683 | -0.1379 | 6.35769 |
June | 366.00000 | 24.19139 | 56.58981 | -0.0780 | 6.16567 |
July | 369.00000 | 24.18372 | 64.07477 | -0.0337 | 6.06133 |
August | 379.00000 | 24.15052 | 65.99641 | -0.0410 | 5.87601 |
September | 360.00000 | 24.14396 | 62.28856 | -0.0848 | 5.90651 |
October | 371.00000 | 24.10380 | 46.94621 | 0.60118 | 12.87113 |
November | 360.00000 | 24.00220 | 39.82537 | 0.48461 | 10.04343 |
December | 369.00000 | 23.82846 | 36.17131 | 0.36506 | 8.03922 |
Annual Sum or Average | 4395.00000 | 24.04241 | 48.34272 | 0.23404 | 8.30033 |
Minimum of Months | 336.00000 | 23.62827 | 36.17131 | -0.1379 | 5.87601 |
Maximum of Months | 379.00000 | 24.19139 | 65.99641 | 0.60118 | 12.87113 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.58479 | 37.34728 | 0.28449 | 7.37939 |
February | 336.00000 | 23.88142 | 39.09265 | 0.39992 | 8.60780 |
March | 379.00000 | 24.04013 | 40.26483 | 0.48792 | 10.19676 |
April | 360.00000 | 24.14649 | 40.61014 | 0.56383 | 12.07707 |
May | 375.00000 | 24.18775 | 49.99844 | -0.1336 | 6.34525 |
June | 366.00000 | 24.19215 | 56.50414 | -0.0741 | 6.16664 |
July | 369.00000 | 24.18467 | 63.93570 | -0.0297 | 6.07229 |
August | 379.00000 | 24.15121 | 65.88016 | -0.0382 | 5.88288 |
September | 360.00000 | 24.14459 | 62.18823 | -0.0822 | 5.90790 |
October | 371.00000 | 24.10466 | 46.91049 | 0.60279 | 12.91529 |
November | 360.00000 | 24.00075 | 39.83880 | 0.48325 | 10.01748 |
December | 369.00000 | 23.81440 | 36.23184 | 0.35825 | 7.95832 |
Annual Sum or Average | 4395.00000 | 24.03707 | 48.31965 | 0.23331 | 8.28450 |
Minimum of Months | 336.00000 | 23.58479 | 36.23184 | -0.1336 | 5.88288 |
Maximum of Months | 379.00000 | 24.19215 | 65.88016 | 0.60279 | 12.91529 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.53076 | 37.54992 | 0.26557 | 7.25898 |
February | 336.00000 | 23.86224 | 39.22234 | 0.39094 | 8.48463 |
March | 379.00000 | 24.03544 | 40.34467 | 0.48311 | 10.09646 |
April | 360.00000 | 24.14344 | 40.65207 | 0.56054 | 11.99194 |
May | 375.00000 | 24.18592 | 50.06368 | -0.1360 | 6.33968 |
June | 366.00000 | 24.19034 | 56.60109 | -0.0761 | 6.15166 |
July | 369.00000 | 24.18290 | 64.05259 | -0.0309 | 6.05654 |
August | 379.00000 | 24.14950 | 66.02830 | -0.0398 | 5.86851 |
September | 360.00000 | 24.14245 | 62.33598 | -0.0843 | 5.89827 |
October | 371.00000 | 24.10155 | 46.99873 | 0.60025 | 12.84463 |
November | 360.00000 | 23.99565 | 39.91541 | 0.47878 | 9.92740 |
December | 369.00000 | 23.79055 | 36.34006 | 0.34814 | 7.84245 |
Annual Sum or Average | 4395.00000 | 24.02693 | 48.42813 | 0.22812 | 8.22115 |
Minimum of Months | 336.00000 | 23.53076 | 36.34006 | -0.1360 | 5.86851 |
Maximum of Months | 379.00000 | 24.19034 | 66.02830 | 0.60025 | 12.84463 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.48480 | 38.52826 | 0.24578 | 7.00451 |
February | 308.00000 | 23.81823 | 39.87324 | 0.37676 | 8.19268 |
March | 348.00000 | 23.94078 | 40.90051 | 0.46450 | 9.65712 |
April | 330.00000 | 24.02018 | 41.22955 | 0.54265 | 11.45665 |
May | 344.00000 | 24.03376 | 50.90713 | -0.1631 | 6.10747 |
June | 336.00000 | 24.02136 | 57.54162 | -0.1063 | 5.76184 |
July | 338.00000 | 24.05349 | 65.02919 | -0.0514 | 5.77546 |
August | 348.00000 | 24.01090 | 67.07969 | -0.0642 | 5.58141 |
September | 330.00000 | 24.02416 | 63.19474 | -0.1061 | 5.73554 |
October | 340.00000 | 24.00202 | 47.51284 | 0.58796 | 12.45111 |
November | 330.00000 | 23.93704 | 40.31306 | 0.46762 | 9.66818 |
December | 338.00000 | 23.75450 | 37.21575 | 0.33600 | 7.64957 |
Annual Sum or Average | 4030.00000 | 23.92567 | 49.20104 | 0.20882 | 7.91062 |
Minimum of Months | 308.00000 | 23.48480 | 37.21575 | -0.1631 | 5.58141 |
Maximum of Months | 348.00000 | 24.05349 | 67.07969 | 0.58796 | 12.45111 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.48699 | 38.47762 | 0.23443 | 6.89194 |
February | 308.00000 | 23.82200 | 39.85103 | 0.36429 | 7.99002 |
March | 348.00000 | 23.94175 | 40.91152 | 0.44823 | 9.33987 |
April | 330.00000 | 24.01935 | 41.21645 | 0.52184 | 10.98696 |
May | 344.00000 | 24.03292 | 50.92685 | -0.1956 | 6.35103 |
June | 336.00000 | 24.02049 | 57.61954 | -0.1395 | 5.93644 |
July | 338.00000 | 24.05230 | 65.19992 | -0.0828 | 5.86702 |
August | 348.00000 | 24.01013 | 67.29806 | -0.0943 | 5.68801 |
September | 330.00000 | 24.02375 | 63.35211 | -0.1350 | 5.88775 |
October | 340.00000 | 24.00226 | 47.57150 | 0.56805 | 11.96451 |
November | 330.00000 | 23.93795 | 40.33528 | 0.45141 | 9.35068 |
December | 338.00000 | 23.75892 | 37.18485 | 0.32481 | 7.48719 |
Annual Sum or Average | 4030.00000 | 23.92628 | 49.25337 | 0.18672 | 7.80380 |
Minimum of Months | 308.00000 | 23.48699 | 37.18485 | -0.1956 | 5.68801 |
Maximum of Months | 348.00000 | 24.05230 | 67.29806 | 0.56805 | 11.96451 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.46755 | 38.55101 | 0.22677 | 6.84471 |
February | 308.00000 | 23.81433 | 39.90563 | 0.35950 | 7.92823 |
March | 348.00000 | 23.94051 | 40.94408 | 0.44514 | 9.28211 |
April | 330.00000 | 24.01867 | 41.23552 | 0.51917 | 10.92705 |
May | 344.00000 | 24.03270 | 50.96485 | -0.1986 | 6.37407 |
June | 336.00000 | 24.02043 | 57.67546 | -0.1423 | 5.95112 |
July | 338.00000 | 24.05207 | 65.27319 | -0.0852 | 5.87281 |
August | 348.00000 | 24.00973 | 67.37827 | -0.0966 | 5.69442 |
September | 330.00000 | 24.02328 | 63.42588 | -0.1374 | 5.89770 |
October | 340.00000 | 24.00153 | 47.60931 | 0.56596 | 11.91330 |
November | 330.00000 | 23.93683 | 40.36293 | 0.44885 | 9.30225 |
December | 338.00000 | 23.74951 | 37.22823 | 0.32013 | 7.43874 |
Annual Sum or Average | 4030.00000 | 23.92284 | 49.30422 | 0.18335 | 7.77790 |
Minimum of Months | 308.00000 | 23.46755 | 37.22823 | -0.1986 | 5.69442 |
Maximum of Months | 348.00000 | 24.05207 | 67.37827 | 0.56596 | 11.91330 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.41765 | 38.72704 | 0.21033 | 6.76127 |
February | 308.00000 | 23.78873 | 40.05612 | 0.34846 | 7.80782 |
March | 348.00000 | 23.93640 | 41.02482 | 0.44050 | 9.20090 |
April | 330.00000 | 24.01738 | 41.26636 | 0.51788 | 10.89836 |
May | 344.00000 | 24.03254 | 50.99117 | -0.1970 | 6.36024 |
June | 336.00000 | 24.02024 | 57.69058 | -0.1397 | 5.93559 |
July | 338.00000 | 24.05215 | 65.24942 | -0.0816 | 5.86359 |
August | 348.00000 | 24.00982 | 67.34080 | -0.0928 | 5.68191 |
September | 330.00000 | 24.02331 | 63.41513 | -0.1341 | 5.88046 |
October | 340.00000 | 24.00095 | 47.63211 | 0.56707 | 11.94009 |
November | 330.00000 | 23.93426 | 40.41234 | 0.44705 | 9.27097 |
December | 338.00000 | 23.72374 | 37.33627 | 0.31073 | 7.36205 |
Annual Sum or Average | 4030.00000 | 23.91378 | 49.35250 | 0.18104 | 7.73982 |
Minimum of Months | 308.00000 | 23.41765 | 37.33627 | -0.1970 | 5.68191 |
Maximum of Months | 348.00000 | 24.05215 | 67.34080 | 0.56707 | 11.94009 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.33686 | 38.98845 | 0.18277 | 6.66768 |
February | 308.00000 | 23.72058 | 40.38775 | 0.32448 | 7.62219 |
March | 348.00000 | 23.92343 | 41.26271 | 0.43571 | 9.15645 |
April | 330.00000 | 24.01678 | 41.34186 | 0.53234 | 11.23501 |
May | 344.00000 | 24.03440 | 50.98405 | -0.1605 | 6.11103 |
June | 336.00000 | 24.02223 | 57.43991 | -0.0991 | 5.75894 |
July | 338.00000 | 24.05651 | 64.67510 | -0.0384 | 5.82039 |
August | 348.00000 | 24.01329 | 66.49626 | -0.0491 | 5.60060 |
September | 330.00000 | 24.02725 | 62.72540 | -0.0929 | 5.72922 |
October | 340.00000 | 24.00481 | 47.42486 | 0.59234 | 12.58044 |
November | 330.00000 | 23.93233 | 40.43253 | 0.45745 | 9.49371 |
December | 338.00000 | 23.67910 | 37.42849 | 0.29690 | 7.30585 |
Annual Sum or Average | 4030.00000 | 23.89832 | 49.21944 | 0.19674 | 7.74998 |
Minimum of Months | 308.00000 | 23.33686 | 37.42849 | -0.1605 | 5.60060 |
Maximum of Months | 348.00000 | 24.05651 | 66.49626 | 0.59234 | 12.58044 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.616252E+10 | 0.171619E+10 | 372.33 | 0.560868E+10 | 0.553838E+09 | 0.00 | 0.28 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 11910.33 | 12-JAN-15:00 | 11553.77 | 12-JAN-15:00 | 1984.79 | 17-JAN-18:10 | 3328.92 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.118222E+11 | 0.328643E+10 | 395.78 | 0.105462E+11 | 0.127593E+10 | 0.00 | 0.48 | 25-FEB-09:03 | 0.00 | 01-FEB-00:10 | 22654.85 | 25-FEB-09:03 | 16673.56 | 25-FEB-09:03 | 5981.29 | 25-FEB-09:03 | 5735.53 | 25-FEB-09:03 | 0.00 | 01-FEB-00:10 |
March | 0.234596E+11 | 0.673093E+10 | 473.91 | 0.208172E+11 | 0.264243E+10 | 0.00 | 1.00 | 10-MAR-09:02 | 0.00 | 01-MAR-00:05 | 56140.77 | 29-MAR-08:62 | 45693.80 | 11-MAR-09:01 | 13694.97 | 29-MAR-08:62 | 12736.21 | 11-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.349577E+11 | 0.108480E+11 | 471.42 | 0.318750E+11 | 0.308271E+10 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:05 | 56969.41 | 26-APR-08:61 | 52526.23 | 08-APR-08:61 | 16169.44 | 26-APR-08:03 | 13593.47 | 27-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.494419E+11 | 0.154647E+11 | 501.23 | 0.404072E+11 | 0.903475E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 60546.50 | 24-MAY-08:61 | 52134.14 | 06-MAY-08:61 | 29518.23 | 24-MAY-08:04 | 14582.68 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.556303E+11 | 0.166818E+11 | 487.81 | 0.404511E+11 | 0.151792E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 61490.67 | 26-JUN-08:61 | 50427.22 | 07-JUN-07:01 | 33026.10 | 26-JUN-08:06 | 15003.56 | 10-JUN-16:10 | 0.00 | 01-JUN-00:10 |
July | 0.634735E+11 | 0.174564E+11 | 504.20 | 0.388640E+11 | 0.246095E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 61569.24 | 18-JUL-08:61 | 43470.28 | 07-JUL-07:01 | 34534.85 | 25-JUL-08:04 | 14627.49 | 01-JUL-16:10 | 0.00 | 01-JUL-00:03 |
August | 0.628871E+11 | 0.166965E+11 | 502.80 | 0.363875E+11 | 0.264996E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 61561.97 | 10-AUG-07:01 | 37781.80 | 09-AUG-07:01 | 36236.52 | 12-AUG-08:06 | 13826.38 | 07-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.528914E+11 | 0.143052E+11 | 487.94 | 0.329867E+11 | 0.199047E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 61228.11 | 06-SEP-08:61 | 42136.68 | 26-SEP-08:61 | 32112.79 | 06-SEP-08:05 | 13505.62 | 22-SEP-08:61 | 0.00 | 01-SEP-00:10 |
October | 0.354019E+11 | 0.100875E+11 | 480.04 | 0.288650E+11 | 0.653692E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:03 | 59136.70 | 12-OCT-08:62 | 47687.41 | 16-OCT-08:61 | 25295.12 | 12-OCT-08:03 | 13162.26 | 04-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.208208E+11 | 0.583012E+10 | 458.33 | 0.184502E+11 | 0.237059E+10 | 0.00 | 1.00 | 09-NOV-09:02 | 0.00 | 01-NOV-00:10 | 55990.03 | 09-NOV-09:02 | 42915.71 | 09-NOV-09:02 | 13074.32 | 09-NOV-09:02 | 12215.76 | 09-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.919676E+10 | 0.255055E+10 | 423.33 | 0.825271E+10 | 0.944050E+09 | 0.00 | 0.34 | 28-DEC-15:00 | 0.00 | 01-DEC-01:05 | 14399.42 | 28-DEC-15:00 | 13650.96 | 03-DEC-14:00 | 2162.59 | 10-DEC-18:10 | 4024.97 | 28-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.426146E+12 | 0.121654E+12 | 5559.11 | 0.313512E+12 | 0.112634E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.616252E+10 | 0.171619E+10 | 372.33 | 0.560868E+10 | 0.553838E+09 | 0.00 | 0.28 | 0.00 | 11910.33 | 11553.77 | 1984.79 | 3328.92 | 0.00 | |||||||
Maximum of Months | 0.634735E+11 | 0.174564E+11 | 504.20 | 0.404511E+11 | 0.264996E+11 | 0.00 | 1.00 | 0.00 | 61569.24 | 52526.23 | 36236.52 | 15003.56 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.432007E+10 | 0.120362E+10 | 420.83 | 0.398673E+10 | 0.333337E+09 | 0.00 | 0.30 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 6464.82 | 12-JAN-15:00 | 6294.63 | 12-JAN-15:00 | 1139.55 | 17-JAN-18:10 | 1769.90 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.687875E+10 | 0.190104E+10 | 411.94 | 0.624078E+10 | 0.637975E+09 | 0.00 | 0.57 | 25-FEB-09:03 | 0.00 | 01-FEB-00:10 | 14283.69 | 25-FEB-09:03 | 11210.72 | 25-FEB-09:03 | 3072.97 | 25-FEB-09:03 | 3466.89 | 25-FEB-09:03 | 0.00 | 01-FEB-00:10 |
March | 0.122654E+11 | 0.349547E+10 | 475.43 | 0.110869E+11 | 0.117848E+10 | 0.00 | 1.00 | 10-MAR-09:02 | 0.00 | 01-MAR-00:05 | 29064.34 | 29-MAR-08:62 | 24499.70 | 11-MAR-09:01 | 6031.29 | 29-MAR-08:62 | 6493.73 | 11-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.173071E+11 | 0.535997E+10 | 473.91 | 0.159959E+11 | 0.131116E+10 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:05 | 29412.42 | 26-APR-08:61 | 27420.34 | 08-APR-08:61 | 7466.11 | 26-APR-08:03 | 6937.20 | 27-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.240640E+11 | 0.753418E+10 | 502.03 | 0.200077E+11 | 0.405628E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 31113.12 | 24-MAY-08:61 | 27176.09 | 06-MAY-08:61 | 13848.02 | 24-MAY-08:04 | 7461.49 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.267737E+11 | 0.804689E+10 | 488.02 | 0.198632E+11 | 0.691050E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 31594.13 | 24-JUN-08:61 | 26078.01 | 07-JUN-08:61 | 15549.38 | 24-JUN-08:05 | 7589.21 | 10-JUN-16:10 | 0.00 | 01-JUN-00:10 |
July | 0.303022E+11 | 0.837019E+10 | 504.41 | 0.190303E+11 | 0.112719E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 31842.31 | 25-JUL-08:61 | 22005.71 | 07-JUL-08:61 | 16425.75 | 25-JUL-08:13 | 7413.75 | 01-JUL-16:10 | 0.00 | 01-JUL-00:03 |
August | 0.301168E+11 | 0.801962E+10 | 502.74 | 0.178748E+11 | 0.122420E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 32010.91 | 12-AUG-08:61 | 21602.73 | 20-AUG-07:01 | 17290.92 | 12-AUG-08:06 | 7065.11 | 07-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.252575E+11 | 0.685716E+10 | 487.97 | 0.162120E+11 | 0.904551E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 31392.76 | 06-SEP-08:61 | 22934.23 | 26-SEP-08:61 | 15002.49 | 06-SEP-08:13 | 6902.89 | 22-SEP-08:61 | 0.00 | 01-SEP-00:10 |
October | 0.174694E+11 | 0.497354E+10 | 480.45 | 0.145733E+11 | 0.289606E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:03 | 30402.59 | 12-OCT-08:62 | 25711.75 | 16-OCT-08:61 | 11398.73 | 12-OCT-08:03 | 6714.89 | 04-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.110012E+11 | 0.306176E+10 | 459.78 | 0.993990E+10 | 0.106129E+10 | 0.00 | 1.00 | 09-NOV-09:02 | 0.00 | 01-NOV-00:10 | 28883.08 | 09-NOV-09:02 | 23497.90 | 09-NOV-09:02 | 5385.18 | 09-NOV-09:02 | 6210.42 | 09-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.582166E+10 | 0.161051E+10 | 448.92 | 0.532096E+10 | 0.500697E+09 | 0.00 | 0.34 | 28-DEC-14:40 | 0.00 | 01-DEC-01:05 | 7636.43 | 28-DEC-14:40 | 7355.84 | 03-DEC-14:00 | 1200.51 | 29-DEC-20:05 | 2095.20 | 28-DEC-14:40 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.211578E+12 | 0.604339E+11 | 5656.43 | 0.160133E+12 | 0.514451E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.432007E+10 | 0.120362E+10 | 411.94 | 0.398673E+10 | 0.333337E+09 | 0.00 | 0.30 | 0.00 | 6464.82 | 6294.63 | 1139.55 | 1769.90 | 0.00 | |||||||
Maximum of Months | 0.303022E+11 | 0.837019E+10 | 504.41 | 0.200077E+11 | 0.122420E+11 | 0.00 | 1.00 | 0.00 | 32010.91 | 27420.34 | 17290.92 | 7589.21 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.242277E+10 | 0.662279E+09 | 255.83 | 0.225022E+10 | 0.172553E+09 | 0.00 | 0.28 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 6064.24 | 12-JAN-15:00 | 5912.08 | 12-JAN-15:00 | 986.23 | 17-JAN-18:10 | 1667.34 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.477640E+10 | 0.130669E+10 | 276.39 | 0.433253E+10 | 0.443870E+09 | 0.00 | 0.58 | 25-FEB-08:63 | 0.00 | 01-FEB-00:10 | 14734.29 | 25-FEB-08:63 | 10925.23 | 25-FEB-08:63 | 3809.06 | 25-FEB-08:63 | 3555.57 | 25-FEB-08:63 | 0.00 | 01-FEB-00:10 |
March | 0.960422E+10 | 0.272207E+10 | 345.06 | 0.864440E+10 | 0.959820E+09 | 0.00 | 1.00 | 11-MAR-08:61 | 0.00 | 01-MAR-00:05 | 29274.96 | 11-MAR-08:61 | 23244.04 | 14-MAR-07:02 | 7030.22 | 11-MAR-08:03 | 6411.10 | 11-MAR-08:61 | 0.00 | 01-MAR-00:05 |
April | 0.140914E+11 | 0.430566E+10 | 343.54 | 0.129380E+11 | 0.115343E+10 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 29607.85 | 26-APR-07:01 | 27393.56 | 30-APR-08:61 | 8390.32 | 26-APR-07:03 | 6904.91 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.202204E+11 | 0.622033E+10 | 378.98 | 0.166101E+11 | 0.361033E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 31175.77 | 24-MAY-07:01 | 27131.22 | 06-MAY-07:01 | 14537.65 | 24-MAY-07:04 | 7269.81 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.226036E+11 | 0.662096E+10 | 370.69 | 0.164346E+11 | 0.616892E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 31968.44 | 25-JUN-08:61 | 25769.16 | 12-JUN-06:02 | 17945.06 | 26-JUN-07:04 | 7549.60 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.251218E+11 | 0.672028E+10 | 371.96 | 0.152432E+11 | 0.987856E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 31961.96 | 23-JUL-08:61 | 20369.06 | 05-JUL-06:02 | 18013.23 | 23-JUL-08:04 | 7368.27 | 01-JUL-14:00 | 0.00 | 01-JUL-00:03 |
August | 0.254830E+11 | 0.660784E+10 | 379.78 | 0.146100E+11 | 0.108730E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 32062.51 | 21-AUG-07:01 | 18396.65 | 03-AUG-07:01 | 19312.49 | 28-AUG-06:03 | 7048.80 | 27-AUG-14:00 | 0.00 | 01-AUG-00:10 |
September | 0.208829E+11 | 0.552580E+10 | 359.80 | 0.129676E+11 | 0.791523E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 32077.05 | 04-SEP-08:61 | 20783.88 | 26-SEP-07:01 | 18732.94 | 11-SEP-07:04 | 6820.48 | 24-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.140911E+11 | 0.397088E+10 | 344.21 | 0.116149E+11 | 0.247620E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 30708.74 | 12-OCT-07:01 | 25060.33 | 23-OCT-07:02 | 13216.73 | 13-OCT-07:03 | 6619.31 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.845956E+10 | 0.234341E+10 | 325.68 | 0.765739E+10 | 0.802163E+09 | 0.00 | 1.00 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 | 28995.93 | 09-NOV-08:62 | 21219.41 | 09-NOV-08:62 | 7776.53 | 09-NOV-08:62 | 6131.25 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.371458E+10 | 0.101136E+10 | 290.08 | 0.340948E+10 | 0.305101E+09 | 0.00 | 0.33 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 7274.62 | 28-DEC-14:00 | 6988.73 | 02-DEC-14:00 | 1113.00 | 29-DEC-18:10 | 2005.93 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.171472E+12 | 0.480176E+11 | 4042.00 | 0.126712E+12 | 0.447592E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.242277E+10 | 0.662279E+09 | 255.83 | 0.225022E+10 | 0.172553E+09 | 0.00 | 0.28 | 0.00 | 6064.24 | 5912.08 | 986.23 | 1667.34 | 0.00 | |||||||
Maximum of Months | 0.254830E+11 | 0.672028E+10 | 379.78 | 0.166101E+11 | 0.108730E+11 | 0.00 | 1.00 | 0.00 | 32077.05 | 27393.56 | 19312.49 | 7549.60 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.228220E+10 | 0.624546E+09 | 248.17 | 0.212086E+10 | 0.161343E+09 | 0.00 | 0.27 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 5970.82 | 12-JAN-15:00 | 5820.84 | 12-JAN-15:00 | 931.39 | 17-JAN-18:10 | 1643.65 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.469748E+10 | 0.128631E+10 | 274.06 | 0.426065E+10 | 0.436832E+09 | 0.00 | 0.57 | 25-FEB-08:63 | 0.00 | 01-FEB-00:10 | 14426.57 | 25-FEB-08:63 | 10690.57 | 25-FEB-08:63 | 3735.99 | 25-FEB-08:63 | 3492.92 | 25-FEB-08:63 | 0.00 | 01-FEB-00:10 |
March | 0.959137E+10 | 0.271926E+10 | 344.82 | 0.863252E+10 | 0.958847E+09 | 0.00 | 1.00 | 11-MAR-08:61 | 0.00 | 01-MAR-00:05 | 29333.89 | 11-MAR-08:61 | 23316.33 | 14-MAR-07:02 | 7038.28 | 11-MAR-08:03 | 6423.73 | 11-MAR-08:61 | 0.00 | 01-MAR-00:05 |
April | 0.141572E+11 | 0.432432E+10 | 344.89 | 0.129997E+11 | 0.115745E+10 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 29659.04 | 26-APR-07:01 | 27446.49 | 30-APR-08:61 | 8382.95 | 26-APR-07:03 | 6917.82 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.203575E+11 | 0.625889E+10 | 379.26 | 0.167339E+11 | 0.362363E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 31228.43 | 24-MAY-07:01 | 27183.13 | 06-MAY-07:01 | 14525.65 | 24-MAY-07:04 | 7283.51 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.227423E+11 | 0.665895E+10 | 370.70 | 0.165534E+11 | 0.618893E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 32030.17 | 25-JUN-08:61 | 26027.12 | 12-JUN-06:02 | 17815.63 | 26-JUN-07:04 | 7567.97 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.252863E+11 | 0.676177E+10 | 372.12 | 0.153737E+11 | 0.991257E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 32023.67 | 23-JUL-08:61 | 20626.45 | 05-JUL-06:02 | 17904.52 | 23-JUL-08:04 | 7385.44 | 01-JUL-14:00 | 0.00 | 01-JUL-00:03 |
August | 0.256099E+11 | 0.663981E+10 | 380.07 | 0.147078E+11 | 0.109021E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 32124.42 | 21-AUG-07:01 | 18477.42 | 03-AUG-07:01 | 19599.23 | 28-AUG-06:03 | 7074.94 | 27-AUG-14:00 | 0.00 | 01-AUG-00:10 |
September | 0.209901E+11 | 0.555310E+10 | 359.75 | 0.130512E+11 | 0.793895E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 32138.99 | 04-SEP-08:61 | 20866.80 | 26-SEP-07:01 | 18678.06 | 11-SEP-07:04 | 6833.57 | 24-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.141566E+11 | 0.398834E+10 | 344.86 | 0.116735E+11 | 0.248316E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 30771.39 | 12-OCT-07:01 | 25169.30 | 23-OCT-07:02 | 13224.99 | 13-OCT-07:03 | 6631.62 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.843104E+10 | 0.233653E+10 | 325.26 | 0.763112E+10 | 0.799925E+09 | 0.00 | 0.99 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 | 28897.50 | 09-NOV-08:62 | 21145.71 | 09-NOV-08:62 | 7751.80 | 09-NOV-08:62 | 6118.54 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.361182E+10 | 0.984406E+09 | 286.42 | 0.331418E+10 | 0.297643E+09 | 0.00 | 0.32 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 7188.57 | 28-DEC-14:00 | 6928.67 | 02-DEC-14:00 | 1099.19 | 29-DEC-18:10 | 1984.44 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.171914E+12 | 0.481362E+11 | 4030.37 | 0.127052E+12 | 0.448614E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.228220E+10 | 0.624546E+09 | 248.17 | 0.212086E+10 | 0.161343E+09 | 0.00 | 0.27 | 0.00 | 5970.82 | 5820.84 | 931.39 | 1643.65 | 0.00 | |||||||
Maximum of Months | 0.256099E+11 | 0.676177E+10 | 380.07 | 0.167339E+11 | 0.109021E+11 | 0.00 | 1.00 | 0.00 | 32138.99 | 27446.49 | 19599.23 | 7567.97 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.206706E+10 | 0.566596E+09 | 239.42 | 0.192283E+10 | 0.144230E+09 | 0.00 | 0.27 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 5793.76 | 12-JAN-15:00 | 5646.29 | 12-JAN-15:00 | 856.27 | 17-JAN-18:10 | 1597.91 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.450260E+10 | 0.123523E+10 | 270.22 | 0.408365E+10 | 0.418948E+09 | 0.00 | 0.52 | 25-FEB-08:63 | 0.00 | 01-FEB-00:10 | 12916.21 | 25-FEB-08:63 | 9529.93 | 25-FEB-08:63 | 3386.27 | 25-FEB-08:63 | 3173.90 | 25-FEB-08:63 | 0.00 | 01-FEB-00:10 |
March | 0.939302E+10 | 0.266764E+10 | 344.27 | 0.844938E+10 | 0.943644E+09 | 0.00 | 1.00 | 11-MAR-08:61 | 0.00 | 01-MAR-00:05 | 29249.05 | 11-MAR-08:61 | 23180.48 | 14-MAR-07:02 | 7102.81 | 11-MAR-08:03 | 6407.03 | 11-MAR-08:61 | 0.00 | 01-MAR-00:05 |
April | 0.140017E+11 | 0.428146E+10 | 343.15 | 0.128519E+11 | 0.114973E+10 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 29604.28 | 26-APR-07:01 | 27382.25 | 30-APR-08:61 | 8420.13 | 26-APR-07:03 | 6902.07 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.202188E+11 | 0.621953E+10 | 378.84 | 0.166100E+11 | 0.360881E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 31167.18 | 24-MAY-07:01 | 27120.28 | 06-MAY-07:01 | 14550.48 | 24-MAY-07:04 | 7266.99 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.225994E+11 | 0.661971E+10 | 370.24 | 0.164327E+11 | 0.616667E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 31955.42 | 25-JUN-08:61 | 25949.66 | 12-JUN-06:02 | 17858.15 | 26-JUN-07:04 | 7538.25 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.251551E+11 | 0.672787E+10 | 371.81 | 0.152719E+11 | 0.988318E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 31954.90 | 28-JUL-07:01 | 20549.56 | 05-JUL-06:02 | 17962.99 | 23-JUL-08:04 | 7352.50 | 01-JUL-14:00 | 0.00 | 01-JUL-00:03 |
August | 0.254523E+11 | 0.660030E+10 | 379.65 | 0.145879E+11 | 0.108645E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 32049.46 | 21-AUG-07:01 | 18364.46 | 03-AUG-07:01 | 19618.19 | 28-AUG-06:03 | 7051.35 | 27-AUG-14:00 | 0.00 | 01-AUG-00:10 |
September | 0.208322E+11 | 0.551335E+10 | 359.12 | 0.129282E+11 | 0.790396E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 32063.99 | 04-SEP-08:61 | 20778.32 | 26-SEP-07:01 | 18737.22 | 11-SEP-07:04 | 6817.69 | 24-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.140032E+11 | 0.394893E+10 | 343.64 | 0.115377E+11 | 0.246545E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 30690.44 | 12-OCT-07:01 | 25053.17 | 23-OCT-07:02 | 13278.32 | 13-OCT-07:03 | 6616.96 | 04-OCT-07:01 | 0.00 | 01-OCT-00:03 |
November | 0.825467E+10 | 0.229119E+10 | 324.93 | 0.746769E+10 | 0.786975E+09 | 0.00 | 0.95 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 | 27187.38 | 09-NOV-08:62 | 19812.77 | 09-NOV-08:62 | 7374.61 | 09-NOV-08:62 | 5839.19 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.340873E+10 | 0.930647E+09 | 281.08 | 0.312512E+10 | 0.283615E+09 | 0.00 | 0.32 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 7015.31 | 28-DEC-14:00 | 6788.43 | 02-DEC-14:00 | 1061.29 | 29-DEC-18:10 | 1940.02 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.169889E+12 | 0.476024E+11 | 4006.36 | 0.125269E+12 | 0.446197E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.206706E+10 | 0.566596E+09 | 239.42 | 0.192283E+10 | 0.144230E+09 | 0.00 | 0.27 | 0.00 | 5793.76 | 5646.29 | 856.27 | 1597.91 | 0.00 | |||||||
Maximum of Months | 0.254523E+11 | 0.672787E+10 | 379.65 | 0.166100E+11 | 0.108645E+11 | 0.00 | 1.00 | 0.00 | 32063.99 | 27382.25 | 19618.19 | 7538.25 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.300324E+10 | 0.840607E+09 | 215.58 | 0.277205E+10 | 0.231185E+09 | 0.00 | 0.26 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 10237.50 | 12-JAN-15:10 | 9824.82 | 12-JAN-15:10 | 1581.39 | 14-JAN-15:10 | 2879.38 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.758491E+10 | 0.212696E+10 | 263.03 | 0.681457E+10 | 0.770341E+09 | 0.00 | 0.40 | 25-FEB-09:03 | 0.00 | 01-FEB-00:10 | 17736.56 | 25-FEB-09:03 | 15006.74 | 22-FEB-14:00 | 4734.71 | 25-FEB-09:03 | 4624.48 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.167016E+11 | 0.484660E+10 | 336.29 | 0.148940E+11 | 0.180760E+10 | 0.00 | 1.00 | 10-MAR-09:02 | 0.00 | 01-MAR-00:05 | 53461.60 | 11-MAR-09:01 | 44017.79 | 28-MAR-08:62 | 12270.83 | 10-MAR-09:02 | 12198.45 | 11-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.251878E+11 | 0.788054E+10 | 333.22 | 0.230825E+11 | 0.210528E+10 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:05 | 54219.89 | 24-APR-08:61 | 50141.30 | 08-APR-08:61 | 14520.66 | 26-APR-08:03 | 13387.33 | 16-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.368122E+11 | 0.115466E+11 | 367.48 | 0.300824E+11 | 0.672972E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 57538.64 | 24-MAY-08:61 | 50324.06 | 29-MAY-08:61 | 27180.47 | 24-MAY-08:04 | 13943.82 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.412291E+11 | 0.123105E+11 | 359.61 | 0.298081E+11 | 0.114209E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 58773.74 | 25-JUN-09:01 | 48414.72 | 07-JUN-07:01 | 33163.66 | 26-JUN-08:04 | 14330.06 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.456444E+11 | 0.123899E+11 | 360.19 | 0.273536E+11 | 0.182908E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 58823.81 | 18-JUL-08:61 | 41551.19 | 07-JUL-07:01 | 33973.33 | 24-JUL-07:01 | 14007.45 | 01-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 0.464839E+11 | 0.122305E+11 | 371.01 | 0.262037E+11 | 0.202802E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 59029.06 | 21-AUG-08:61 | 36516.29 | 09-AUG-07:01 | 35834.59 | 28-AUG-07:02 | 13433.16 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.376254E+11 | 0.101273E+11 | 347.06 | 0.230599E+11 | 0.145655E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 59088.76 | 04-SEP-09:01 | 40149.73 | 26-SEP-08:61 | 34623.77 | 11-SEP-08:06 | 13015.28 | 24-SEP-09:13 | 0.00 | 01-SEP-00:10 |
October | 0.252401E+11 | 0.725784E+10 | 334.33 | 0.206081E+11 | 0.463202E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 56372.80 | 12-OCT-08:62 | 45952.08 | 15-OCT-09:01 | 24066.33 | 12-OCT-08:03 | 12567.74 | 04-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.145358E+11 | 0.411820E+10 | 318.32 | 0.130027E+11 | 0.153312E+10 | 0.00 | 1.00 | 09-NOV-09:02 | 0.00 | 01-NOV-00:10 | 53431.18 | 09-NOV-09:02 | 43550.99 | 11-NOV-10:02 | 12967.35 | 09-NOV-09:02 | 11666.83 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.540279E+10 | 0.150755E+10 | 270.75 | 0.487786E+10 | 0.524931E+09 | 0.00 | 0.31 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 12575.29 | 28-DEC-14:00 | 11847.57 | 02-DEC-14:10 | 1699.86 | 16-DEC-14:40 | 3546.73 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.305451E+12 | 0.871830E+11 | 3876.89 | 0.222560E+12 | 0.828916E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.300324E+10 | 0.840607E+09 | 215.58 | 0.277205E+10 | 0.231185E+09 | 0.00 | 0.26 | 0.00 | 10237.50 | 9824.82 | 1581.39 | 2879.38 | 0.00 | |||||||
Maximum of Months | 0.464839E+11 | 0.123899E+11 | 371.01 | 0.300824E+11 | 0.202802E+11 | 0.00 | 1.00 | 0.00 | 59088.76 | 50324.06 | 35834.59 | 14330.06 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.154944E+10 | 0.426298E+09 | 216.25 | 0.143557E+10 | 0.113871E+09 | 0.00 | 0.26 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 5339.34 | 12-JAN-15:10 | 5146.59 | 12-JAN-15:10 | 799.92 | 14-JAN-15:10 | 1476.11 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.395641E+10 | 0.109055E+10 | 264.53 | 0.356721E+10 | 0.389195E+09 | 0.00 | 0.40 | 25-FEB-09:03 | 0.00 | 01-FEB-00:10 | 9162.82 | 25-FEB-09:03 | 7857.54 | 22-FEB-14:00 | 2390.19 | 25-FEB-09:03 | 2372.79 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.871812E+10 | 0.248734E+10 | 337.31 | 0.779903E+10 | 0.919091E+09 | 0.00 | 1.00 | 10-MAR-09:02 | 0.00 | 01-MAR-00:05 | 28089.07 | 11-MAR-09:01 | 23272.62 | 28-MAR-08:62 | 6322.23 | 10-MAR-09:02 | 6297.39 | 11-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.131468E+11 | 0.404538E+10 | 332.49 | 0.120678E+11 | 0.107894E+10 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:05 | 28502.01 | 24-APR-08:61 | 26351.75 | 08-APR-08:61 | 7547.12 | 26-APR-08:03 | 6911.41 | 16-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.192012E+11 | 0.592666E+10 | 366.97 | 0.157191E+11 | 0.348208E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 30240.08 | 24-MAY-08:61 | 26436.98 | 29-MAY-08:61 | 14219.87 | 24-MAY-08:04 | 7197.88 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.214726E+11 | 0.631173E+10 | 359.55 | 0.155561E+11 | 0.591652E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 30885.42 | 25-JUN-09:01 | 25242.94 | 07-JUN-08:61 | 17377.71 | 26-JUN-08:04 | 7406.35 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.237783E+11 | 0.635349E+10 | 359.94 | 0.142896E+11 | 0.948864E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 30911.73 | 18-JUL-08:61 | 21829.56 | 07-JUL-07:01 | 18068.97 | 24-JUL-07:01 | 7231.10 | 01-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 0.241999E+11 | 0.626764E+10 | 370.82 | 0.136814E+11 | 0.105185E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 31019.58 | 21-AUG-08:61 | 19122.03 | 08-AUG-07:01 | 19099.72 | 28-AUG-07:02 | 6945.47 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.196152E+11 | 0.519471E+10 | 346.40 | 0.120571E+11 | 0.755807E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 31050.96 | 04-SEP-09:01 | 21211.96 | 26-SEP-08:61 | 18166.67 | 11-SEP-08:04 | 6719.69 | 24-SEP-09:13 | 0.00 | 01-SEP-00:10 |
October | 0.131718E+11 | 0.372507E+10 | 333.77 | 0.107876E+11 | 0.238418E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 29619.92 | 12-OCT-08:62 | 24250.76 | 23-OCT-08:62 | 12513.99 | 12-OCT-08:03 | 6488.24 | 04-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.759413E+10 | 0.211499E+10 | 318.60 | 0.681684E+10 | 0.777289E+09 | 0.00 | 1.00 | 09-NOV-09:02 | 0.00 | 01-NOV-00:10 | 28083.17 | 09-NOV-09:02 | 23018.17 | 11-NOV-10:02 | 6659.55 | 09-NOV-09:02 | 6024.64 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.282166E+10 | 0.773916E+09 | 271.83 | 0.255694E+10 | 0.264715E+09 | 0.00 | 0.31 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 6548.44 | 28-DEC-14:00 | 6197.42 | 02-DEC-14:10 | 864.30 | 16-DEC-14:40 | 1815.76 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.159225E+12 | 0.447178E+11 | 3878.46 | 0.116334E+12 | 0.428911E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.154944E+10 | 0.426298E+09 | 216.25 | 0.143557E+10 | 0.113871E+09 | 0.00 | 0.26 | 0.00 | 5339.34 | 5146.59 | 799.92 | 1476.11 | 0.00 | |||||||
Maximum of Months | 0.241999E+11 | 0.635349E+10 | 370.82 | 0.157191E+11 | 0.105185E+11 | 0.00 | 1.00 | 0.00 | 31050.96 | 26436.98 | 19099.72 | 7406.35 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.147850E+10 | 0.406996E+09 | 211.08 | 0.137041E+10 | 0.108097E+09 | 0.00 | 0.25 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 5262.08 | 12-JAN-15:10 | 5070.52 | 12-JAN-15:10 | 790.70 | 14-JAN-15:10 | 1455.75 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.387429E+10 | 0.106872E+10 | 262.19 | 0.349266E+10 | 0.381632E+09 | 0.00 | 0.38 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 | 8582.06 | 25-FEB-09:03 | 7783.79 | 22-FEB-14:00 | 2252.53 | 25-FEB-09:03 | 2352.50 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.862496E+10 | 0.246226E+10 | 336.58 | 0.771250E+10 | 0.912452E+09 | 0.00 | 1.00 | 10-MAR-09:02 | 0.00 | 01-MAR-00:05 | 27978.48 | 11-MAR-09:01 | 23141.44 | 28-MAR-08:62 | 6343.90 | 10-MAR-09:02 | 6273.24 | 11-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.130622E+11 | 0.402042E+10 | 332.46 | 0.119872E+11 | 0.107498E+10 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:05 | 28396.67 | 24-APR-08:61 | 26242.21 | 08-APR-08:61 | 7546.66 | 26-APR-08:03 | 6885.72 | 16-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.191117E+11 | 0.589894E+10 | 366.74 | 0.156390E+11 | 0.347272E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 30135.99 | 24-MAY-08:61 | 26333.45 | 29-MAY-08:61 | 14201.63 | 24-MAY-08:04 | 7171.13 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.213821E+11 | 0.628418E+10 | 359.46 | 0.154792E+11 | 0.590291E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 30769.51 | 25-JUN-09:01 | 25146.30 | 07-JUN-08:61 | 17353.78 | 26-JUN-08:04 | 7381.05 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.236879E+11 | 0.632757E+10 | 359.97 | 0.142191E+11 | 0.946884E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 30795.73 | 18-JUL-08:61 | 21121.80 | 07-JUL-07:01 | 18030.32 | 24-JUL-07:01 | 7206.22 | 01-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 0.241095E+11 | 0.624236E+10 | 370.88 | 0.136113E+11 | 0.104982E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 30903.18 | 21-AUG-08:61 | 19016.67 | 08-AUG-07:01 | 19055.36 | 28-AUG-07:02 | 6924.48 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.195323E+11 | 0.517168E+10 | 346.24 | 0.119916E+11 | 0.754070E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 30934.44 | 04-SEP-09:01 | 21114.68 | 26-SEP-08:61 | 18128.24 | 11-SEP-08:04 | 6694.43 | 24-SEP-09:13 | 0.00 | 01-SEP-00:10 |
October | 0.130950E+11 | 0.370409E+10 | 333.80 | 0.107190E+11 | 0.237609E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 29507.65 | 12-OCT-08:62 | 24133.38 | 15-OCT-09:01 | 12503.40 | 12-OCT-08:03 | 6464.26 | 04-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.751919E+10 | 0.209514E+10 | 318.40 | 0.674695E+10 | 0.772244E+09 | 0.00 | 1.00 | 09-NOV-09:02 | 0.00 | 01-NOV-00:10 | 27975.69 | 09-NOV-09:02 | 22893.00 | 11-NOV-10:02 | 6675.11 | 09-NOV-09:02 | 6001.48 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.274888E+10 | 0.754401E+09 | 269.08 | 0.249006E+10 | 0.258815E+09 | 0.00 | 0.30 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 6477.92 | 28-DEC-14:00 | 6132.08 | 02-DEC-14:10 | 856.33 | 16-DEC-14:40 | 1797.17 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.158227E+12 | 0.444368E+11 | 3866.89 | 0.115459E+12 | 0.427677E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.147850E+10 | 0.406996E+09 | 211.08 | 0.137041E+10 | 0.108097E+09 | 0.00 | 0.25 | 0.00 | 5262.08 | 5070.52 | 790.70 | 1455.75 | 0.00 | |||||||
Maximum of Months | 0.241095E+11 | 0.632757E+10 | 370.88 | 0.156390E+11 | 0.104982E+11 | 0.00 | 1.00 | 0.00 | 30934.44 | 26333.45 | 19055.36 | 7381.05 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.133394E+10 | 0.367691E+09 | 198.92 | 0.123791E+10 | 96026878.70 | 0.00 | 0.25 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 5102.21 | 12-JAN-15:10 | 4915.19 | 12-JAN-15:10 | 769.98 | 14-JAN-15:10 | 1414.27 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.369464E+10 | 0.102128E+10 | 257.78 | 0.333119E+10 | 0.363447E+09 | 0.00 | 0.38 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 | 8235.86 | 24-FEB-15:30 | 7663.55 | 22-FEB-14:00 | 1903.68 | 25-FEB-17:00 | 2320.38 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.844836E+10 | 0.241641E+10 | 334.82 | 0.755102E+10 | 0.897341E+09 | 0.00 | 1.00 | 10-MAR-09:02 | 0.00 | 01-MAR-00:05 | 27978.48 | 11-MAR-09:01 | 23058.08 | 28-MAR-08:62 | 6440.34 | 10-MAR-09:02 | 6274.74 | 11-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.129690E+11 | 0.399559E+10 | 330.85 | 0.118997E+11 | 0.106924E+10 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:05 | 28401.93 | 03-APR-08:61 | 26232.95 | 08-APR-08:61 | 7582.92 | 26-APR-08:03 | 6888.97 | 16-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.190767E+11 | 0.589031E+10 | 366.25 | 0.156101E+11 | 0.346659E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 30163.74 | 24-MAY-08:61 | 26338.20 | 29-MAY-08:61 | 14261.44 | 24-MAY-08:04 | 7174.31 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.213767E+11 | 0.628359E+10 | 359.43 | 0.154774E+11 | 0.589930E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 30783.04 | 25-JUN-09:01 | 25157.92 | 07-JUN-08:61 | 17420.20 | 26-JUN-08:04 | 7388.66 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.237225E+11 | 0.633624E+10 | 359.87 | 0.142476E+11 | 0.947491E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 30809.26 | 18-JUL-08:61 | 21329.44 | 07-JUL-07:01 | 18068.28 | 24-JUL-07:01 | 7217.88 | 10-JUL-13:00 | 0.00 | 01-JUL-00:03 |
August | 0.241530E+11 | 0.625252E+10 | 370.39 | 0.136448E+11 | 0.105082E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 30916.76 | 21-AUG-08:61 | 19051.54 | 08-AUG-07:01 | 19042.51 | 28-AUG-07:02 | 6936.38 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.195503E+11 | 0.517613E+10 | 346.10 | 0.120072E+11 | 0.754309E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 30948.03 | 04-SEP-09:01 | 21124.41 | 26-SEP-08:61 | 18185.01 | 11-SEP-08:06 | 6697.38 | 24-SEP-09:13 | 0.00 | 01-SEP-00:10 |
October | 0.130683E+11 | 0.369763E+10 | 333.78 | 0.106963E+11 | 0.237201E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 29515.63 | 12-OCT-08:62 | 24137.26 | 15-OCT-09:01 | 12544.15 | 12-OCT-08:03 | 6467.21 | 04-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.742179E+10 | 0.207019E+10 | 318.00 | 0.665770E+10 | 0.764093E+09 | 0.00 | 1.00 | 09-NOV-09:02 | 0.00 | 01-NOV-00:10 | 27980.57 | 09-NOV-09:02 | 22840.28 | 11-NOV-10:02 | 6735.04 | 09-NOV-09:02 | 6002.60 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.260187E+10 | 0.715074E+09 | 265.08 | 0.235618E+10 | 0.245689E+09 | 0.00 | 0.30 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 6355.83 | 28-DEC-14:00 | 6024.67 | 02-DEC-14:10 | 841.32 | 16-DEC-14:50 | 1765.87 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.157417E+12 | 0.442227E+11 | 3841.27 | 0.114717E+12 | 0.427000E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.133394E+10 | 0.367691E+09 | 198.92 | 0.123791E+10 | 96026878.70 | 0.00 | 0.25 | 0.00 | 5102.21 | 4915.19 | 769.98 | 1414.27 | 0.00 | |||||||
Maximum of Months | 0.241530E+11 | 0.633624E+10 | 370.39 | 0.156101E+11 | 0.105082E+11 | 0.00 | 1.00 | 0.00 | 30948.03 | 26338.20 | 19042.51 | 7388.66 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.123812E+10 | 0.342027E+09 | 186.00 | 0.115621E+10 | 81910786.67 | 0.00 | 0.23 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 5082.48 | 12-JAN-15:10 | 4918.33 | 12-JAN-15:10 | 743.73 | 14-JAN-15:10 | 1414.46 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.356199E+10 | 0.988930E+09 | 248.58 | 0.322968E+10 | 0.332309E+09 | 0.00 | 0.37 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 | 8406.72 | 22-FEB-14:00 | 7908.84 | 22-FEB-14:00 | 1837.05 | 25-FEB-17:00 | 2393.29 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.846700E+10 | 0.243577E+10 | 331.51 | 0.759047E+10 | 0.876524E+09 | 0.00 | 1.00 | 11-MAR-09:01 | 0.00 | 01-MAR-00:05 | 29828.50 | 30-MAR-08:62 | 23919.12 | 12-MAR-09:02 | 7174.36 | 30-MAR-08:62 | 6685.53 | 11-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.135224E+11 | 0.418148E+10 | 330.15 | 0.124321E+11 | 0.109027E+10 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:05 | 30338.09 | 03-APR-08:61 | 27939.85 | 08-APR-08:61 | 8290.63 | 03-APR-08:03 | 7339.58 | 16-APR-09:01 | 0.00 | 01-APR-00:05 |
May | 0.201817E+11 | 0.625151E+10 | 366.70 | 0.165745E+11 | 0.360722E+10 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 32550.32 | 24-MAY-08:61 | 27938.87 | 29-MAY-08:61 | 16625.45 | 24-MAY-08:04 | 7646.30 | 04-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.226757E+11 | 0.669080E+10 | 359.62 | 0.165413E+11 | 0.613442E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 32986.49 | 24-JUN-08:61 | 27460.85 | 12-JUN-07:01 | 18924.57 | 26-JUN-08:04 | 7790.34 | 10-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.254127E+11 | 0.680568E+10 | 360.76 | 0.154382E+11 | 0.997452E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 32948.63 | 26-JUL-08:61 | 22837.89 | 07-JUL-07:01 | 19384.61 | 24-JUL-07:01 | 7722.99 | 10-JUL-13:00 | 0.00 | 01-JUL-00:03 |
August | 0.259265E+11 | 0.673106E+10 | 371.65 | 0.148967E+11 | 0.110297E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 32943.70 | 21-AUG-08:61 | 19687.23 | 09-AUG-07:01 | 20424.38 | 27-AUG-08:62 | 7392.01 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.209557E+11 | 0.556275E+10 | 348.22 | 0.130740E+11 | 0.788167E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 33002.33 | 09-SEP-08:61 | 22459.56 | 27-SEP-08:61 | 19705.05 | 03-SEP-08:61 | 7136.74 | 24-SEP-09:13 | 0.00 | 01-SEP-00:10 |
October | 0.140039E+11 | 0.396379E+10 | 335.14 | 0.115480E+11 | 0.245588E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 31703.07 | 12-OCT-08:62 | 25958.68 | 15-OCT-09:01 | 14297.90 | 12-OCT-08:03 | 6890.93 | 04-OCT-08:61 | 0.00 | 01-OCT-00:03 |
November | 0.778243E+10 | 0.217380E+10 | 317.06 | 0.701595E+10 | 0.766482E+09 | 0.00 | 1.00 | 09-NOV-09:02 | 0.00 | 01-NOV-00:10 | 29800.48 | 09-NOV-09:02 | 24407.10 | 11-NOV-10:02 | 7023.33 | 09-NOV-09:02 | 6399.91 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.257686E+10 | 0.709415E+09 | 257.83 | 0.234779E+10 | 0.229066E+09 | 0.00 | 0.29 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 | 6532.20 | 28-DEC-14:00 | 6194.70 | 02-DEC-14:10 | 841.94 | 16-DEC-14:40 | 1819.74 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.166305E+12 | 0.468370E+11 | 3813.22 | 0.121845E+12 | 0.444600E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.123812E+10 | 0.342027E+09 | 186.00 | 0.115621E+10 | 81910786.67 | 0.00 | 0.23 | 0.00 | 5082.48 | 4918.33 | 743.73 | 1414.46 | 0.00 | |||||||
Maximum of Months | 0.259265E+11 | 0.680568E+10 | 371.65 | 0.165745E+11 | 0.110297E+11 | 0.00 | 1.00 | 0.00 | 33002.33 | 27939.85 | 20424.38 | 7790.34 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 102.64 | 61.42 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.58 | 48.04 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.74 | 28.25 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 84.45 | 9.63 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 84.35 | 1.68 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 86.22 | 1.29 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 80.78 | 0.47 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 73.92 | 1.36 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 82.29 | 4.93 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 127.07 | 22.52 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 144.92 | 42.87 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.70 | 59.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.42 | 23.41 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 73.92 | 0.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 144.92 | 61.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 102.64 | 61.42 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.58 | 48.04 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.74 | 28.25 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 84.45 | 9.63 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 84.35 | 1.68 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 86.22 | 1.29 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 80.78 | 0.47 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 73.92 | 1.36 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 82.29 | 4.93 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 127.07 | 22.52 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 144.92 | 42.87 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.70 | 59.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.42 | 23.41 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 73.92 | 0.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 144.92 | 61.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 102.64 | 61.42 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.58 | 48.04 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.74 | 28.25 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 84.45 | 9.63 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 84.35 | 1.68 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 86.22 | 1.29 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 80.78 | 0.47 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 73.92 | 1.36 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 82.29 | 4.93 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 127.07 | 22.52 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 144.92 | 42.87 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.70 | 59.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.42 | 23.41 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 73.92 | 0.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 144.92 | 61.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 102.64 | 61.42 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.58 | 48.04 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.74 | 28.25 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 84.45 | 9.63 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 84.35 | 1.68 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 86.22 | 1.29 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 80.78 | 0.47 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 73.92 | 1.36 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 82.29 | 4.93 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 127.07 | 22.52 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 144.92 | 42.87 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.70 | 59.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.42 | 23.41 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 73.92 | 0.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 144.92 | 61.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.66 | 56.31 | 36.35 | 123.39 | 73.43 | 0.00 | 0.00 | 744.00 |
February | 88.09 | 48.93 | 39.16 | 124.47 | 57.45 | 0.00 | 0.00 | 672.00 |
March | 75.30 | 33.25 | 42.05 | 116.11 | 33.85 | 0.00 | 0.00 | 744.00 |
April | 52.88 | 14.91 | 37.97 | 101.08 | 11.55 | 0.00 | 0.00 | 720.00 |
May | 38.02 | 2.79 | 35.23 | 100.69 | 2.03 | 0.00 | 0.00 | 744.00 |
June | 34.79 | 0.58 | 34.21 | 102.93 | 1.54 | 0.00 | 0.00 | 720.00 |
July | 36.29 | 0.49 | 35.80 | 96.46 | 0.56 | 0.00 | 0.00 | 744.00 |
August | 38.50 | 2.05 | 36.45 | 88.36 | 1.64 | 0.00 | 0.00 | 744.00 |
September | 51.61 | 13.39 | 38.22 | 98.51 | 5.92 | 0.00 | 0.00 | 720.00 |
October | 88.80 | 49.59 | 39.22 | 152.40 | 27.00 | 0.00 | 0.00 | 744.00 |
November | 110.95 | 73.35 | 37.61 | 173.99 | 51.34 | 0.00 | 0.00 | 720.00 |
December | 99.02 | 62.06 | 36.96 | 137.84 | 71.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.12 | 29.70 | 37.42 | 117.95 | 28.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.79 | 0.49 | 34.21 | 88.36 | 0.56 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.95 | 73.35 | 42.05 | 173.99 | 73.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.66 | 56.31 | 36.35 | 123.39 | 73.43 | 0.00 | 0.00 | 744.00 |
February | 88.09 | 48.93 | 39.16 | 124.47 | 57.45 | 0.00 | 0.00 | 672.00 |
March | 75.30 | 33.25 | 42.05 | 116.11 | 33.85 | 0.00 | 0.00 | 744.00 |
April | 52.88 | 14.91 | 37.97 | 101.08 | 11.55 | 0.00 | 0.00 | 720.00 |
May | 38.02 | 2.79 | 35.23 | 100.69 | 2.03 | 0.00 | 0.00 | 744.00 |
June | 34.79 | 0.58 | 34.21 | 102.93 | 1.54 | 0.00 | 0.00 | 720.00 |
July | 36.29 | 0.49 | 35.80 | 96.46 | 0.56 | 0.00 | 0.00 | 744.00 |
August | 38.50 | 2.05 | 36.45 | 88.36 | 1.64 | 0.00 | 0.00 | 744.00 |
September | 51.61 | 13.39 | 38.22 | 98.51 | 5.92 | 0.00 | 0.00 | 720.00 |
October | 88.80 | 49.59 | 39.22 | 152.40 | 27.00 | 0.00 | 0.00 | 744.00 |
November | 110.95 | 73.35 | 37.61 | 173.99 | 51.34 | 0.00 | 0.00 | 720.00 |
December | 99.02 | 62.06 | 36.96 | 137.84 | 71.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.12 | 29.70 | 37.42 | 117.95 | 28.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.79 | 0.49 | 34.21 | 88.36 | 0.56 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.95 | 73.35 | 42.05 | 173.99 | 73.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 102.02 | 62.30 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.04 | 48.82 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.47 | 28.77 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 84.62 | 9.83 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 84.96 | 1.69 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 87.07 | 1.28 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 81.71 | 0.43 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 74.73 | 1.24 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 82.82 | 4.69 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 127.24 | 22.39 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 144.74 | 43.01 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.23 | 60.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.59 | 23.63 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 74.73 | 0.43 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 144.74 | 62.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 102.02 | 62.30 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.04 | 48.82 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.47 | 28.77 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 84.62 | 9.83 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 84.96 | 1.69 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 87.07 | 1.28 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 81.71 | 0.43 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 74.73 | 1.24 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 82.82 | 4.69 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 127.24 | 22.39 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 144.74 | 43.01 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.23 | 60.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 98.59 | 23.63 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 74.73 | 0.43 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 144.74 | 62.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.66 | 56.31 | 36.35 | 122.66 | 74.47 | 0.00 | 0.00 | 744.00 |
February | 88.09 | 48.93 | 39.16 | 123.83 | 58.38 | 0.00 | 0.00 | 672.00 |
March | 75.30 | 33.25 | 42.05 | 115.79 | 34.46 | 0.00 | 0.00 | 744.00 |
April | 52.88 | 14.91 | 37.97 | 101.28 | 11.80 | 0.00 | 0.00 | 720.00 |
May | 38.02 | 2.79 | 35.23 | 101.41 | 2.04 | 0.00 | 0.00 | 744.00 |
June | 34.79 | 0.58 | 34.21 | 103.95 | 1.54 | 0.00 | 0.00 | 720.00 |
July | 36.29 | 0.49 | 35.80 | 97.57 | 0.52 | 0.00 | 0.00 | 744.00 |
August | 38.50 | 2.05 | 36.45 | 89.34 | 1.50 | 0.00 | 0.00 | 744.00 |
September | 51.61 | 13.39 | 38.22 | 99.16 | 5.63 | 0.00 | 0.00 | 720.00 |
October | 88.80 | 49.59 | 39.22 | 152.62 | 26.85 | 0.00 | 0.00 | 744.00 |
November | 110.95 | 73.35 | 37.61 | 173.80 | 51.50 | 0.00 | 0.00 | 720.00 |
December | 99.02 | 62.06 | 36.96 | 137.29 | 72.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.12 | 29.70 | 37.42 | 118.16 | 28.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.79 | 0.49 | 34.21 | 89.34 | 0.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.95 | 73.35 | 42.05 | 173.80 | 74.47 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 102.48 | 61.76 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.17 | 49.52 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.30 | 30.46 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 82.75 | 11.50 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.21 | 2.44 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 83.14 | 1.93 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.25 | 0.73 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 71.78 | 2.10 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.11 | 6.67 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.79 | 25.06 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 144.79 | 44.63 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.49 | 60.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.05 | 24.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 71.78 | 0.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 144.79 | 61.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 102.48 | 61.76 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.17 | 49.52 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.30 | 30.46 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 82.75 | 11.50 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.21 | 2.44 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 83.14 | 1.93 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.25 | 0.73 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 71.78 | 2.10 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.11 | 6.67 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.79 | 25.06 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 144.79 | 44.63 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.49 | 60.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.05 | 24.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 71.78 | 0.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 144.79 | 61.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 122.54 | 73.39 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 123.31 | 58.85 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 114.96 | 36.25 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 98.55 | 13.69 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 96.49 | 2.92 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 98.78 | 2.29 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 91.83 | 0.88 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 85.41 | 2.51 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 96.63 | 7.94 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 151.26 | 29.83 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 172.90 | 53.09 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 136.85 | 72.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 115.72 | 29.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 85.41 | 0.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 172.90 | 73.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 102.74 | 61.01 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.27 | 49.21 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.31 | 30.44 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 82.64 | 11.70 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 80.86 | 2.62 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 82.72 | 2.05 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 76.76 | 0.81 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 71.50 | 2.25 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.01 | 6.96 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.74 | 25.28 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 144.82 | 44.55 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.62 | 60.25 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 96.94 | 24.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 71.50 | 0.81 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 144.82 | 61.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 102.74 | 61.01 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.27 | 49.21 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.31 | 30.44 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 82.64 | 11.70 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 80.86 | 2.62 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 82.72 | 2.05 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 76.76 | 0.81 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 71.50 | 2.25 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.01 | 6.96 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.74 | 25.28 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 144.82 | 44.55 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.62 | 60.25 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 96.94 | 24.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 71.50 | 0.81 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 144.82 | 61.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 122.86 | 72.50 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 123.43 | 58.48 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 114.97 | 36.22 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 98.42 | 13.93 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 96.07 | 3.14 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 98.28 | 2.44 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 91.25 | 0.98 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 85.07 | 2.69 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 96.51 | 8.29 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 151.20 | 30.09 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 172.93 | 53.00 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 137.01 | 71.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 115.59 | 29.32 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 85.07 | 0.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 172.93 | 72.50 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.05 | 60.30 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.43 | 48.76 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.42 | 30.09 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 82.77 | 11.45 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.04 | 2.51 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 82.95 | 1.99 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 76.94 | 0.75 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 71.65 | 2.14 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.08 | 6.73 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.80 | 25.02 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 144.92 | 44.24 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.81 | 59.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.10 | 24.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 71.65 | 0.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 144.92 | 60.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.05 | 60.30 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.43 | 48.76 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.42 | 30.09 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 82.77 | 11.45 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.04 | 2.51 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 82.95 | 1.99 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 76.94 | 0.75 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 71.65 | 2.14 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.08 | 6.73 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.80 | 25.02 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 144.92 | 44.24 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 114.81 | 59.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.10 | 24.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 71.65 | 0.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 144.92 | 60.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 123.22 | 71.66 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 123.63 | 57.95 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 115.11 | 35.80 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 98.58 | 13.63 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 96.29 | 3.01 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 98.56 | 2.36 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 91.46 | 0.91 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 85.26 | 2.55 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 96.59 | 8.02 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 151.27 | 29.78 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 173.06 | 52.62 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 137.24 | 71.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 115.78 | 28.99 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 85.26 | 0.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 173.06 | 71.66 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.77 | 58.92 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.91 | 47.61 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.62 | 28.98 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 82.90 | 10.64 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.27 | 2.20 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 83.42 | 1.81 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.01 | 0.58 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 71.78 | 1.77 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 80.92 | 5.98 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.62 | 24.07 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.05 | 43.34 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.31 | 58.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.32 | 23.62 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 71.78 | 0.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.05 | 58.92 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.77 | 58.92 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.91 | 47.61 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.62 | 28.98 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 82.90 | 10.64 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.27 | 2.20 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 83.42 | 1.81 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.01 | 0.58 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 71.78 | 1.77 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 80.92 | 5.98 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.62 | 24.07 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.05 | 43.34 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.31 | 58.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.32 | 23.62 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 71.78 | 0.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.05 | 58.92 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.77 | 58.92 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.91 | 47.61 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.62 | 28.98 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 82.90 | 10.64 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.27 | 2.20 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 83.42 | 1.81 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.01 | 0.58 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 71.78 | 1.77 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 80.92 | 5.98 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.62 | 24.07 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.05 | 43.34 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.31 | 58.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.32 | 23.62 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 71.78 | 0.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.05 | 58.92 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.77 | 58.92 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.91 | 47.61 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.62 | 28.98 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 82.90 | 10.64 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.27 | 2.20 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 83.42 | 1.81 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.01 | 0.58 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 71.78 | 1.77 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 80.92 | 5.98 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.62 | 24.07 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.05 | 43.34 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.31 | 58.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.32 | 23.62 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 71.78 | 0.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.05 | 58.92 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 124.09 | 70.02 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 124.20 | 56.59 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 115.35 | 34.49 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 98.75 | 12.67 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 96.57 | 2.63 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 99.12 | 2.15 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 91.56 | 0.70 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 85.42 | 2.12 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 96.41 | 7.13 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 151.07 | 28.66 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 173.22 | 51.56 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 137.83 | 69.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 116.06 | 28.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 85.42 | 0.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 173.22 | 70.02 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 124.09 | 70.02 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 124.20 | 56.59 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 115.35 | 34.49 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 98.75 | 12.67 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 96.57 | 2.63 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 99.12 | 2.15 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 91.56 | 0.70 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 85.42 | 2.12 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 96.41 | 7.13 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 151.07 | 28.66 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 173.22 | 51.56 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 137.83 | 69.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 116.06 | 28.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 85.42 | 0.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 173.22 | 70.02 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.63 | 58.81 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.78 | 47.46 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.64 | 28.68 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.29 | 10.33 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 82.07 | 2.02 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 84.30 | 1.70 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.83 | 0.49 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.37 | 1.58 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.22 | 5.59 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.71 | 23.67 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 144.99 | 43.06 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.18 | 58.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.61 | 23.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.37 | 0.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 144.99 | 58.81 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.63 | 58.81 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.78 | 47.46 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.64 | 28.68 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.29 | 10.33 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 82.07 | 2.02 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 84.30 | 1.70 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.83 | 0.49 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.37 | 1.58 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.22 | 5.59 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.71 | 23.67 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 144.99 | 43.06 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.18 | 58.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.61 | 23.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.37 | 0.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 144.99 | 58.81 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 123.93 | 69.88 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 124.06 | 56.41 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 115.39 | 34.13 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 99.21 | 12.30 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 97.51 | 2.42 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 100.17 | 2.02 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 92.53 | 0.59 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 86.12 | 1.88 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 96.78 | 6.66 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 151.19 | 28.18 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 173.17 | 51.23 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 137.69 | 69.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 116.41 | 27.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 86.12 | 0.59 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 173.17 | 69.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.76 | 58.55 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.88 | 47.26 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.72 | 28.52 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.39 | 10.22 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 82.20 | 1.98 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 84.45 | 1.67 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.96 | 0.47 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.47 | 1.54 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.29 | 5.51 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.77 | 23.57 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.06 | 42.94 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.27 | 58.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.71 | 23.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.47 | 0.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.06 | 58.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 103.76 | 58.55 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 103.88 | 47.26 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.72 | 28.52 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.39 | 10.22 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 82.20 | 1.98 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 84.45 | 1.67 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.96 | 0.47 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.47 | 1.54 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.29 | 5.51 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.77 | 23.57 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.06 | 42.94 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.27 | 58.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.71 | 23.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.47 | 0.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.06 | 58.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 124.09 | 69.57 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 124.18 | 56.17 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 115.49 | 33.94 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 99.33 | 12.18 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 97.67 | 2.37 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 100.35 | 1.99 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 92.69 | 0.57 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 86.25 | 1.84 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 96.86 | 6.57 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 151.26 | 28.06 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 173.24 | 51.08 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 137.80 | 69.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 116.53 | 27.69 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 86.25 | 0.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 173.24 | 69.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 104.05 | 57.91 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.12 | 46.71 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.87 | 28.16 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.46 | 10.07 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 82.18 | 1.95 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 84.36 | 1.66 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.79 | 0.48 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.32 | 1.57 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.21 | 5.57 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.75 | 23.55 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.13 | 42.75 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.48 | 58.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.75 | 23.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.32 | 0.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.13 | 58.04 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 104.05 | 57.91 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.12 | 46.71 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 96.87 | 28.16 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.46 | 10.07 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 82.18 | 1.95 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 84.36 | 1.66 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 77.79 | 0.48 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 72.32 | 1.57 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 81.21 | 5.57 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.75 | 23.55 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.13 | 42.75 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.48 | 58.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.75 | 23.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 72.32 | 0.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.13 | 58.04 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 124.43 | 68.82 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 124.47 | 55.52 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 115.66 | 33.52 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 99.42 | 11.99 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 97.65 | 2.34 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 100.24 | 1.98 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 92.48 | 0.58 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 86.07 | 1.88 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 96.77 | 6.64 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 151.24 | 28.03 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 173.33 | 50.86 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 138.05 | 68.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 116.58 | 27.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 86.07 | 0.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 173.33 | 68.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 104.61 | 56.08 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.68 | 44.82 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 97.12 | 26.86 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.21 | 9.64 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.26 | 1.98 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 82.99 | 1.73 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 75.96 | 0.60 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 70.76 | 1.95 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 80.26 | 6.34 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.23 | 23.97 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.07 | 42.34 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.89 | 56.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.27 | 22.66 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 70.76 | 0.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.07 | 56.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.96 | 46.77 | 30.19 | 104.61 | 56.08 | 0.00 | 0.00 | 744.00 |
February | 73.17 | 40.64 | 32.53 | 104.68 | 44.82 | 0.00 | 0.00 | 672.00 |
March | 62.54 | 27.62 | 34.93 | 97.12 | 26.86 | 0.00 | 0.00 | 744.00 |
April | 43.92 | 12.38 | 31.54 | 83.21 | 9.64 | 0.00 | 0.00 | 720.00 |
May | 31.58 | 2.32 | 29.26 | 81.26 | 1.98 | 0.00 | 0.00 | 744.00 |
June | 28.89 | 0.48 | 28.41 | 82.99 | 1.73 | 0.00 | 0.00 | 720.00 |
July | 30.14 | 0.41 | 29.74 | 75.96 | 0.60 | 0.00 | 0.00 | 744.00 |
August | 31.98 | 1.70 | 30.27 | 70.76 | 1.95 | 0.00 | 0.00 | 744.00 |
September | 42.87 | 11.12 | 31.75 | 80.26 | 6.34 | 0.00 | 0.00 | 720.00 |
October | 73.76 | 41.19 | 32.57 | 126.23 | 23.97 | 0.00 | 0.00 | 744.00 |
November | 92.16 | 60.92 | 31.23 | 145.07 | 42.34 | 0.00 | 0.00 | 720.00 |
December | 82.25 | 51.55 | 30.70 | 115.89 | 56.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.75 | 24.67 | 31.09 | 97.27 | 22.66 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.89 | 0.41 | 28.41 | 70.76 | 0.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 92.16 | 60.92 | 34.93 | 145.07 | 56.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.15 | 56.00 | 36.15 | 125.10 | 66.64 | 0.00 | 0.00 | 744.00 |
February | 87.61 | 48.67 | 38.95 | 125.14 | 53.27 | 0.00 | 0.00 | 672.00 |
March | 74.88 | 33.07 | 41.82 | 115.96 | 31.98 | 0.00 | 0.00 | 744.00 |
April | 52.59 | 14.82 | 37.76 | 99.11 | 11.49 | 0.00 | 0.00 | 720.00 |
May | 37.81 | 2.78 | 35.03 | 96.54 | 2.38 | 0.00 | 0.00 | 744.00 |
June | 34.60 | 0.58 | 34.02 | 98.59 | 2.06 | 0.00 | 0.00 | 720.00 |
July | 36.09 | 0.49 | 35.60 | 90.29 | 0.73 | 0.00 | 0.00 | 744.00 |
August | 38.29 | 2.04 | 36.25 | 84.19 | 2.34 | 0.00 | 0.00 | 744.00 |
September | 51.33 | 13.32 | 38.01 | 95.62 | 7.55 | 0.00 | 0.00 | 720.00 |
October | 88.32 | 49.31 | 39.00 | 150.60 | 28.54 | 0.00 | 0.00 | 744.00 |
November | 110.35 | 72.95 | 37.40 | 173.25 | 50.37 | 0.00 | 0.00 | 720.00 |
December | 98.48 | 61.72 | 36.76 | 138.53 | 67.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.76 | 29.54 | 37.22 | 116.00 | 26.95 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.60 | 0.49 | 34.02 | 84.19 | 0.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.35 | 72.95 | 41.82 | 173.25 | 67.41 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.274909E+09 | 0.164511E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.250578E+09 | 0.116210E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259108E+09 | 75666376.08 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.218882E+09 | 24956344.33 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.225929E+09 | 4497814.35 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.223492E+09 | 3331635.32 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.216366E+09 | 1245709.03 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.197975E+09 | 3635510.09 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.213293E+09 | 12777025.18 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340342E+09 | 60309222.23 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375623E+09 | 0.111128E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.307217E+09 | 0.160079E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.310371E+10 | 0.738348E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.197975E+09 | 1245709.03 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375623E+09 | 0.164511E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.274909E+09 | 0.164511E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.250578E+09 | 0.116210E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259108E+09 | 75666376.08 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.218882E+09 | 24956344.33 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.225929E+09 | 4497814.35 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.223492E+09 | 3331635.32 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.216366E+09 | 1245709.03 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.197975E+09 | 3635510.09 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.213293E+09 | 12777025.18 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340342E+09 | 60309222.23 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375623E+09 | 0.111128E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.307217E+09 | 0.160079E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.310371E+10 | 0.738348E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.197975E+09 | 1245709.03 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375623E+09 | 0.164511E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.274909E+09 | 0.164511E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.250578E+09 | 0.116210E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259108E+09 | 75666376.08 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.218882E+09 | 24956344.33 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.225929E+09 | 4497814.35 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.223492E+09 | 3331635.32 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.216366E+09 | 1245709.03 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.197975E+09 | 3635510.09 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.213293E+09 | 12777025.18 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340342E+09 | 60309222.23 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375623E+09 | 0.111128E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.307217E+09 | 0.160079E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.310371E+10 | 0.738348E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.197975E+09 | 1245709.03 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375623E+09 | 0.164511E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.274909E+09 | 0.164511E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.250578E+09 | 0.116210E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259108E+09 | 75666376.08 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.218882E+09 | 24956344.33 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.225929E+09 | 4497814.35 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.223492E+09 | 3331635.32 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.216366E+09 | 1245709.03 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.197975E+09 | 3635510.09 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.213293E+09 | 12777025.18 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340342E+09 | 60309222.23 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375623E+09 | 0.111128E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.307217E+09 | 0.160079E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.310371E+10 | 0.738348E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.197975E+09 | 1245709.03 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375623E+09 | 0.164511E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248181E+09 | 0.150827E+09 | 97354518.97 | 0.330485E+09 | 0.196680E+09 |
February | 0.213112E+09 | 0.118378E+09 | 94734419.52 | 0.301111E+09 | 0.138987E+09 |
March | 0.201672E+09 | 89050731.45 | 0.112622E+09 | 0.310982E+09 | 90660911.10 |
April | 0.137055E+09 | 38635516.98 | 98419012.29 | 0.261990E+09 | 29937248.28 |
May | 0.101831E+09 | 7480702.62 | 94349914.59 | 0.269694E+09 | 5427549.17 |
June | 90170610.98 | 1510838.69 | 88659772.29 | 0.266798E+09 | 4002634.43 |
July | 97206536.27 | 1321397.98 | 95885138.30 | 0.258360E+09 | 1507182.36 |
August | 0.103116E+09 | 5491590.03 | 97624287.37 | 0.236659E+09 | 4384408.26 |
September | 0.133773E+09 | 34703279.05 | 99069922.65 | 0.255332E+09 | 15356338.98 |
October | 0.237848E+09 | 0.132810E+09 | 0.105039E+09 | 0.408192E+09 | 72324255.51 |
November | 0.287593E+09 | 0.190121E+09 | 97472814.23 | 0.450986E+09 | 0.133072E+09 |
December | 0.265225E+09 | 0.166225E+09 | 98999985.37 | 0.369185E+09 | 0.191456E+09 |
Annual Sum or Average | 0.211678E+10 | 0.936554E+09 | 0.118023E+10 | 0.371977E+10 | 0.883795E+09 |
Minimum of Months | 90170610.98 | 1321397.98 | 88659772.29 | 0.236659E+09 | 1507182.36 |
Maximum of Months | 0.287593E+09 | 0.190121E+09 | 0.112622E+09 | 0.450986E+09 | 0.196680E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248181E+09 | 0.150827E+09 | 97354518.97 | 0.330485E+09 | 0.196680E+09 |
February | 0.213112E+09 | 0.118378E+09 | 94734419.52 | 0.301111E+09 | 0.138987E+09 |
March | 0.201672E+09 | 89050731.45 | 0.112622E+09 | 0.310982E+09 | 90660911.10 |
April | 0.137055E+09 | 38635516.98 | 98419012.29 | 0.261990E+09 | 29937248.28 |
May | 0.101831E+09 | 7480702.62 | 94349914.59 | 0.269694E+09 | 5427549.17 |
June | 90170610.98 | 1510838.69 | 88659772.29 | 0.266798E+09 | 4002634.43 |
July | 97206536.27 | 1321397.98 | 95885138.30 | 0.258360E+09 | 1507182.36 |
August | 0.103116E+09 | 5491590.03 | 97624287.37 | 0.236659E+09 | 4384408.26 |
September | 0.133773E+09 | 34703279.05 | 99069922.65 | 0.255332E+09 | 15356338.98 |
October | 0.237848E+09 | 0.132810E+09 | 0.105039E+09 | 0.408192E+09 | 72324255.51 |
November | 0.287593E+09 | 0.190121E+09 | 97472814.23 | 0.450986E+09 | 0.133072E+09 |
December | 0.265225E+09 | 0.166225E+09 | 98999985.37 | 0.369185E+09 | 0.191456E+09 |
Annual Sum or Average | 0.211678E+10 | 0.936554E+09 | 0.118023E+10 | 0.371977E+10 | 0.883795E+09 |
Minimum of Months | 90170610.98 | 1321397.98 | 88659772.29 | 0.236659E+09 | 1507182.36 |
Maximum of Months | 0.287593E+09 | 0.190121E+09 | 0.112622E+09 | 0.450986E+09 | 0.196680E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.273247E+09 | 0.166859E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.249265E+09 | 0.118105E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258377E+09 | 77054019.86 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.219325E+09 | 25491566.92 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.227555E+09 | 4528563.23 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.225692E+09 | 3328992.00 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.218843E+09 | 1146025.33 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.200158E+09 | 3327121.95 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.214671E+09 | 12146697.94 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340793E+09 | 59978207.52 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375167E+09 | 0.111489E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.305956E+09 | 0.161593E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.310905E+10 | 0.745048E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.200158E+09 | 1146025.33 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375167E+09 | 0.166859E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.273247E+09 | 0.166859E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.249265E+09 | 0.118105E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258377E+09 | 77054019.86 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.219325E+09 | 25491566.92 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.227555E+09 | 4528563.23 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.225692E+09 | 3328992.00 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.218843E+09 | 1146025.33 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.200158E+09 | 3327121.95 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.214671E+09 | 12146697.94 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.340793E+09 | 59978207.52 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375167E+09 | 0.111489E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.305956E+09 | 0.161593E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.310905E+10 | 0.745048E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.200158E+09 | 1146025.33 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375167E+09 | 0.166859E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248181E+09 | 0.150827E+09 | 97354518.97 | 0.328529E+09 | 0.199461E+09 |
February | 0.213112E+09 | 0.118378E+09 | 94734419.52 | 0.299565E+09 | 0.141233E+09 |
March | 0.201672E+09 | 89050731.45 | 0.112622E+09 | 0.310119E+09 | 92304786.45 |
April | 0.137055E+09 | 38635516.98 | 98419012.29 | 0.262522E+09 | 30575661.14 |
May | 0.101831E+09 | 7480702.62 | 94349914.59 | 0.271629E+09 | 5465856.29 |
June | 90170610.98 | 1510838.69 | 88659772.29 | 0.269438E+09 | 3998854.35 |
July | 97206536.27 | 1321397.98 | 95885138.30 | 0.261334E+09 | 1387454.12 |
August | 0.103116E+09 | 5491590.03 | 97624287.37 | 0.239299E+09 | 4013500.34 |
September | 0.133773E+09 | 34703279.05 | 99069922.65 | 0.257022E+09 | 14597023.49 |
October | 0.237848E+09 | 0.132810E+09 | 0.105039E+09 | 0.408768E+09 | 71912558.82 |
November | 0.287593E+09 | 0.190121E+09 | 97472814.23 | 0.450477E+09 | 0.133487E+09 |
December | 0.265225E+09 | 0.166225E+09 | 98999985.37 | 0.367708E+09 | 0.193241E+09 |
Annual Sum or Average | 0.211678E+10 | 0.936554E+09 | 0.118023E+10 | 0.372641E+10 | 0.891677E+09 |
Minimum of Months | 90170610.98 | 1321397.98 | 88659772.29 | 0.239299E+09 | 1387454.12 |
Maximum of Months | 0.287593E+09 | 0.190121E+09 | 0.112622E+09 | 0.450477E+09 | 0.199461E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.274471E+09 | 0.165410E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.249590E+09 | 0.119798E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.257933E+09 | 81596759.36 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.214485E+09 | 29800785.17 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.217511E+09 | 6522445.06 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.215492E+09 | 4996744.40 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.206908E+09 | 1961963.79 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.192249E+09 | 5637410.65 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210240E+09 | 17276679.00 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339595E+09 | 67120126.97 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375297E+09 | 0.115680E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.306656E+09 | 0.162441E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.306042E+10 | 0.778241E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.192249E+09 | 1961963.79 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375297E+09 | 0.165410E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.274471E+09 | 0.165410E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.249590E+09 | 0.119798E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.257933E+09 | 81596759.36 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.214485E+09 | 29800785.17 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.217511E+09 | 6522445.06 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.215492E+09 | 4996744.40 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.206908E+09 | 1961963.79 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.192249E+09 | 5637410.65 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210240E+09 | 17276679.00 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339595E+09 | 67120126.97 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375297E+09 | 0.115680E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.306656E+09 | 0.162441E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.306042E+10 | 0.778241E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.192249E+09 | 1961963.79 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375297E+09 | 0.165410E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.328206E+09 | 0.196566E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.298322E+09 | 0.142375E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.307907E+09 | 97083177.11 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.255444E+09 | 35480562.31 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.258431E+09 | 7820128.54 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.256039E+09 | 5944580.83 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.245968E+09 | 2360065.01 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.228764E+09 | 6731773.73 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.250473E+09 | 20575953.52 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.405128E+09 | 79885978.34 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.448167E+09 | 0.137611E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.366541E+09 | 0.193090E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.364939E+10 | 0.925525E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.228764E+09 | 2360065.01 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.448167E+09 | 0.196566E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.275188E+09 | 0.163408E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.249824E+09 | 0.119039E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.257963E+09 | 81540643.49 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.214195E+09 | 30327677.90 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.216575E+09 | 7025758.70 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.214406E+09 | 5322756.96 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.205598E+09 | 2178850.14 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.191492E+09 | 6030945.16 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.209973E+09 | 18046258.97 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339463E+09 | 67718320.50 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375363E+09 | 0.115476E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.307010E+09 | 0.161365E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.305705E+10 | 0.777480E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.191492E+09 | 2178850.14 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375363E+09 | 0.163408E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.275188E+09 | 0.163408E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.249824E+09 | 0.119039E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.257963E+09 | 81540643.49 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.214195E+09 | 30327677.90 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.216575E+09 | 7025758.70 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.214406E+09 | 5322756.96 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.205598E+09 | 2178850.14 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.191492E+09 | 6030945.16 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.209973E+09 | 18046258.97 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339463E+09 | 67718320.50 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375363E+09 | 0.115476E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.307010E+09 | 0.161365E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.305705E+10 | 0.777480E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.191492E+09 | 2178850.14 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375363E+09 | 0.163408E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.329068E+09 | 0.194186E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.298605E+09 | 0.141473E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.307945E+09 | 97015958.92 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.255096E+09 | 36107252.12 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.257316E+09 | 8422131.43 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.254743E+09 | 6332383.08 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.244408E+09 | 2621755.72 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.227861E+09 | 7200508.96 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.250153E+09 | 21492863.77 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.404969E+09 | 80598716.53 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.448247E+09 | 0.137369E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.366968E+09 | 0.191811E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.364538E+10 | 0.924631E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.227861E+09 | 2621755.72 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.448247E+09 | 0.194186E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.275998E+09 | 0.161517E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.250229E+09 | 0.117948E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258257E+09 | 80590979.23 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.214542E+09 | 29677782.16 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.217063E+09 | 6720699.25 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.215019E+09 | 5145871.21 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.206064E+09 | 2013833.02 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.191915E+09 | 5719633.05 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210155E+09 | 17448384.01 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339624E+09 | 67011433.65 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375623E+09 | 0.114658E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.307520E+09 | 0.160168E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.306201E+10 | 0.768620E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.191915E+09 | 2013833.02 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375623E+09 | 0.161517E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.275998E+09 | 0.161517E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.250229E+09 | 0.117948E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258257E+09 | 80590979.23 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.214542E+09 | 29677782.16 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.217063E+09 | 6720699.25 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.215019E+09 | 5145871.21 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.206064E+09 | 2013833.02 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.191915E+09 | 5719633.05 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210155E+09 | 17448384.01 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339624E+09 | 67011433.65 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375623E+09 | 0.114658E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.307520E+09 | 0.160168E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.306201E+10 | 0.768620E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.191915E+09 | 2013833.02 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375623E+09 | 0.161517E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.330042E+09 | 0.191943E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.299092E+09 | 0.140182E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.308300E+09 | 95893743.53 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.255513E+09 | 35339796.75 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.257894E+09 | 8060029.94 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.255470E+09 | 6123975.36 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.244959E+09 | 2425935.12 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.228362E+09 | 6832978.88 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.250372E+09 | 20789506.75 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.405165E+09 | 79762917.62 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.448562E+09 | 0.136400E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.367581E+09 | 0.190393E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.365131E+10 | 0.914147E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.228362E+09 | 2425935.12 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.448562E+09 | 0.191943E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.277950E+09 | 0.157808E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251381E+09 | 0.115176E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258789E+09 | 77620191.50 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.214883E+09 | 27574835.06 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.217679E+09 | 5890258.83 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.216212E+09 | 4696517.69 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.206261E+09 | 1554264.22 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.192251E+09 | 4744222.58 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.209740E+09 | 15509795.03 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339147E+09 | 64474180.16 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375967E+09 | 0.112334E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.308856E+09 | 0.157365E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.306912E+10 | 0.744748E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.192251E+09 | 1554264.22 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375967E+09 | 0.157808E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.277950E+09 | 0.157808E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251381E+09 | 0.115176E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258789E+09 | 77620191.50 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.214883E+09 | 27574835.06 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.217679E+09 | 5890258.83 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.216212E+09 | 4696517.69 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.206261E+09 | 1554264.22 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.192251E+09 | 4744222.58 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.209740E+09 | 15509795.03 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339147E+09 | 64474180.16 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375967E+09 | 0.112334E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.308856E+09 | 0.157365E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.306912E+10 | 0.744748E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.192251E+09 | 1554264.22 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375967E+09 | 0.157808E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.277950E+09 | 0.157808E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251381E+09 | 0.115176E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258789E+09 | 77620191.50 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.214883E+09 | 27574835.06 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.217679E+09 | 5890258.83 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.216212E+09 | 4696517.69 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.206261E+09 | 1554264.22 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.192251E+09 | 4744222.58 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.209740E+09 | 15509795.03 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339147E+09 | 64474180.16 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375967E+09 | 0.112334E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.308856E+09 | 0.157365E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.306912E+10 | 0.744748E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.192251E+09 | 1554264.22 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375967E+09 | 0.157808E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.277950E+09 | 0.157808E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251381E+09 | 0.115176E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258789E+09 | 77620191.50 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.214883E+09 | 27574835.06 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.217679E+09 | 5890258.83 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.216212E+09 | 4696517.69 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.206261E+09 | 1554264.22 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.192251E+09 | 4744222.58 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.209740E+09 | 15509795.03 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339147E+09 | 64474180.16 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375967E+09 | 0.112334E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.308856E+09 | 0.157365E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.306912E+10 | 0.744748E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.192251E+09 | 1554264.22 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375967E+09 | 0.157808E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.332354E+09 | 0.187536E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.300459E+09 | 0.136901E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.308953E+09 | 92378198.24 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.255957E+09 | 32839886.77 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.258666E+09 | 7057418.63 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.256924E+09 | 5582958.40 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.245234E+09 | 1870469.73 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.228790E+09 | 5665997.85 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.249902E+09 | 18478911.76 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.404620E+09 | 76758596.42 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.448976E+09 | 0.133645E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.369168E+09 | 0.187065E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.366000E+10 | 0.885780E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.228790E+09 | 1870469.73 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.448976E+09 | 0.187536E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.332354E+09 | 0.187536E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.300459E+09 | 0.136901E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.308953E+09 | 92378198.24 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.255957E+09 | 32839886.77 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.258666E+09 | 7057418.63 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.256924E+09 | 5582958.40 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.245234E+09 | 1870469.73 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.228790E+09 | 5665997.85 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.249902E+09 | 18478911.76 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.404620E+09 | 76758596.42 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.448976E+09 | 0.133645E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.369168E+09 | 0.187065E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.366000E+10 | 0.885780E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.228790E+09 | 1870469.73 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.448976E+09 | 0.187536E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.277567E+09 | 0.157507E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251063E+09 | 0.114824E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258853E+09 | 76806668.04 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.215875E+09 | 26766884.58 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.219803E+09 | 5407173.91 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.218504E+09 | 4407639.15 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.208457E+09 | 1310943.98 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.193828E+09 | 4221643.75 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210521E+09 | 14494900.78 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339393E+09 | 63402201.12 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375824E+09 | 0.111621E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.308493E+09 | 0.157050E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.307818E+10 | 0.737820E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.193828E+09 | 1310943.98 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375824E+09 | 0.157507E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.277567E+09 | 0.157507E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251063E+09 | 0.114824E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.258853E+09 | 76806668.04 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.215875E+09 | 26766884.58 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.219803E+09 | 5407173.91 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.218504E+09 | 4407639.15 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.208457E+09 | 1310943.98 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.193828E+09 | 4221643.75 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210521E+09 | 14494900.78 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339393E+09 | 63402201.12 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375824E+09 | 0.111621E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.308493E+09 | 0.157050E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.307818E+10 | 0.737820E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.193828E+09 | 1310943.98 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375824E+09 | 0.157507E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.331945E+09 | 0.187158E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.300123E+09 | 0.136465E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.309061E+09 | 91404163.05 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.257144E+09 | 31879210.50 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.261177E+09 | 6483873.99 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.259646E+09 | 5238692.26 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.247837E+09 | 1580579.09 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.230675E+09 | 5045213.96 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.250855E+09 | 17271082.70 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.404949E+09 | 75477538.85 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.448850E+09 | 0.132787E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.368780E+09 | 0.186674E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.367104E+10 | 0.877465E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.230675E+09 | 1580579.09 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.448850E+09 | 0.187158E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.277911E+09 | 0.156819E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251304E+09 | 0.114340E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259067E+09 | 76393005.04 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.216135E+09 | 26497819.04 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.220158E+09 | 5289917.91 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.218882E+09 | 4334534.43 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.208810E+09 | 1265915.06 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.194111E+09 | 4122889.76 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210694E+09 | 14287658.02 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339537E+09 | 63124969.68 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375984E+09 | 0.111297E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.308744E+09 | 0.156592E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.308134E+10 | 0.734364E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.194111E+09 | 1265915.06 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375984E+09 | 0.156819E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.277911E+09 | 0.156819E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251304E+09 | 0.114340E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259067E+09 | 76393005.04 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.216135E+09 | 26497819.04 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.220158E+09 | 5289917.91 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.218882E+09 | 4334534.43 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.208810E+09 | 1265915.06 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.194111E+09 | 4122889.76 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210694E+09 | 14287658.02 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339537E+09 | 63124969.68 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.375984E+09 | 0.111297E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.308744E+09 | 0.156592E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.308134E+10 | 0.734364E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.194111E+09 | 1265915.06 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.375984E+09 | 0.156819E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.332357E+09 | 0.186340E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.300414E+09 | 0.135890E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.309320E+09 | 90912480.68 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.257457E+09 | 31558581.44 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.261602E+09 | 6343324.90 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.260098E+09 | 5151237.46 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.248260E+09 | 1526536.37 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.231013E+09 | 4927836.92 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.251065E+09 | 17024295.60 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.405124E+09 | 75146513.91 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.449044E+09 | 0.132400E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.369081E+09 | 0.186128E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.367483E+10 | 0.873349E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.231013E+09 | 1526536.37 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.449044E+09 | 0.186340E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.278685E+09 | 0.155119E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251890E+09 | 0.113009E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259448E+09 | 75429752.43 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.216328E+09 | 26092120.93 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.220112E+09 | 5225433.70 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.218663E+09 | 4313183.35 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.208340E+09 | 1282795.37 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.193703E+09 | 4203922.02 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210492E+09 | 14429849.08 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339498E+09 | 63070137.35 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376180E+09 | 0.110805E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.309310E+09 | 0.155453E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.308265E+10 | 0.728433E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.193703E+09 | 1282795.37 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376180E+09 | 0.155453E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.278685E+09 | 0.155119E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.251890E+09 | 0.113009E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.259448E+09 | 75429752.43 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.216328E+09 | 26092120.93 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.220112E+09 | 5225433.70 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.218663E+09 | 4313183.35 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.208340E+09 | 1282795.37 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.193703E+09 | 4203922.02 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.210492E+09 | 14429849.08 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.339498E+09 | 63070137.35 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376180E+09 | 0.110805E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.309310E+09 | 0.155453E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.308265E+10 | 0.728433E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.193703E+09 | 1282795.37 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376180E+09 | 0.155453E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.333284E+09 | 0.184324E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.301118E+09 | 0.134313E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.309780E+09 | 89774960.39 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.257687E+09 | 31081636.44 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.261541E+09 | 6269167.94 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.259829E+09 | 5127497.60 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.247692E+09 | 1548058.43 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.230521E+09 | 5025881.31 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.250820E+09 | 17201092.96 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.405076E+09 | 75088712.22 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.449279E+09 | 0.131821E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.369759E+09 | 0.184779E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.367639E+10 | 0.866354E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.230521E+09 | 1548058.43 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.449279E+09 | 0.184779E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.280176E+09 | 0.150197E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.253250E+09 | 0.108423E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.260120E+09 | 71944905.56 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.215672E+09 | 24989096.56 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.217635E+09 | 5304689.74 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.215101E+09 | 4484602.86 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.203453E+09 | 1614568.75 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.189526E+09 | 5235651.13 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.208040E+09 | 16426034.09 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.338094E+09 | 64209675.24 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376016E+09 | 0.109737E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.310387E+09 | 0.151886E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.306747E+10 | 0.714452E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.189526E+09 | 1614568.75 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376016E+09 | 0.151886E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206140E+09 | 0.125277E+09 | 80862769.86 | 0.280176E+09 | 0.150197E+09 |
February | 0.177011E+09 | 98324877.05 | 78686512.39 | 0.253250E+09 | 0.108423E+09 |
March | 0.167509E+09 | 73965634.87 | 93543734.09 | 0.260120E+09 | 71944905.56 |
April | 0.113838E+09 | 32090702.63 | 81746939.17 | 0.215672E+09 | 24989096.56 |
May | 84580621.94 | 6213479.77 | 78367142.18 | 0.217635E+09 | 5304689.74 |
June | 74895808.02 | 1254904.26 | 73640903.76 | 0.215101E+09 | 4484602.86 |
July | 80739855.26 | 1097554.60 | 79642300.66 | 0.203453E+09 | 1614568.75 |
August | 85648160.46 | 4561320.68 | 81086839.78 | 0.189526E+09 | 5235651.13 |
September | 0.111112E+09 | 28824581.51 | 82287586.02 | 0.208040E+09 | 16426034.09 |
October | 0.197557E+09 | 0.110312E+09 | 87245272.99 | 0.338094E+09 | 64209675.24 |
November | 0.238875E+09 | 0.157914E+09 | 80961026.03 | 0.376016E+09 | 0.109737E+09 |
December | 0.220296E+09 | 0.138066E+09 | 82229496.04 | 0.310387E+09 | 0.151886E+09 |
Annual Sum or Average | 0.175820E+10 | 0.777902E+09 | 0.980301E+09 | 0.306747E+10 | 0.714452E+09 |
Minimum of Months | 74895808.02 | 1097554.60 | 73640903.76 | 0.189526E+09 | 1614568.75 |
Maximum of Months | 0.238875E+09 | 0.157914E+09 | 93543734.09 | 0.376016E+09 | 0.151886E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246825E+09 | 0.150002E+09 | 96822527.06 | 0.335069E+09 | 0.178481E+09 |
February | 0.211948E+09 | 0.117731E+09 | 94216745.09 | 0.302745E+09 | 0.128876E+09 |
March | 0.200570E+09 | 88564115.43 | 0.112006E+09 | 0.310587E+09 | 85644194.31 |
April | 0.136306E+09 | 38424393.94 | 97881203.48 | 0.256890E+09 | 29769710.68 |
May | 0.101274E+09 | 7439824.46 | 93834341.29 | 0.258565E+09 | 6364797.59 |
June | 89677875.40 | 1502582.74 | 88175292.66 | 0.255556E+09 | 5331977.15 |
July | 96675353.01 | 1314177.22 | 95361175.79 | 0.241846E+09 | 1947343.39 |
August | 0.102552E+09 | 5461581.34 | 97090821.32 | 0.225507E+09 | 6259275.25 |
September | 0.133042E+09 | 34513643.65 | 98528556.95 | 0.247856E+09 | 19576234.89 |
October | 0.236549E+09 | 0.132084E+09 | 0.104465E+09 | 0.403370E+09 | 76449306.92 |
November | 0.286022E+09 | 0.189082E+09 | 96940175.90 | 0.449072E+09 | 0.130553E+09 |
December | 0.263775E+09 | 0.165316E+09 | 98459001.84 | 0.371045E+09 | 0.180546E+09 |
Annual Sum or Average | 0.210522E+10 | 0.931436E+09 | 0.117378E+10 | 0.365811E+10 | 0.849799E+09 |
Minimum of Months | 89677875.40 | 1314177.22 | 88175292.66 | 0.225507E+09 | 1947343.39 |
Maximum of Months | 0.286022E+09 | 0.189082E+09 | 0.112006E+09 | 0.449072E+09 | 0.180546E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 657.33 | 392.55 | 493.18 | 299.72 | 193.46 | 0.00 | 0.00 |
February | 663.25 | 307.05 | 468.86 | 260.44 | 208.42 | 0.00 | 0.00 |
March | 619.17 | 180.70 | 400.76 | 176.96 | 223.80 | 0.00 | 0.00 |
April | 539.93 | 61.61 | 281.43 | 79.33 | 202.09 | 0.00 | 0.00 |
May | 538.79 | 10.77 | 202.35 | 14.87 | 187.49 | 0.00 | 0.00 |
June | 550.76 | 8.23 | 185.16 | 3.10 | 182.05 | 0.00 | 0.00 |
July | 516.05 | 2.99 | 193.16 | 2.63 | 190.54 | 0.00 | 0.00 |
August | 472.38 | 8.70 | 204.91 | 10.91 | 193.99 | 0.00 | 0.00 |
September | 526.17 | 31.57 | 274.69 | 71.26 | 203.43 | 0.00 | 0.00 |
October | 813.08 | 144.07 | 472.64 | 263.91 | 208.73 | 0.00 | 0.00 |
November | 927.65 | 274.17 | 590.54 | 390.39 | 200.15 | 0.00 | 0.00 |
December | 734.48 | 382.03 | 527.04 | 330.31 | 196.73 | 0.00 | 0.00 |
Annual Sum or Average | 629.58 | 149.70 | 357.25 | 158.06 | 199.19 | 0.00 | 0.00 |
Minimum of Months | 472.38 | 2.99 | 185.16 | 2.63 | 182.05 | 0.00 | 0.00 |
Maximum of Months | 927.65 | 392.55 | 590.54 | 390.39 | 223.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 326.70 | 199.07 | 246.59 | 149.86 | 96.73 | 0.00 | 0.00 |
February | 329.90 | 156.02 | 234.43 | 130.22 | 104.21 | 0.00 | 0.00 |
March | 308.72 | 92.00 | 200.38 | 88.48 | 111.90 | 0.00 | 0.00 |
April | 270.51 | 31.47 | 140.71 | 39.67 | 101.05 | 0.00 | 0.00 |
May | 271.33 | 5.42 | 101.18 | 7.43 | 93.74 | 0.00 | 0.00 |
June | 278.09 | 4.11 | 92.58 | 1.55 | 91.03 | 0.00 | 0.00 |
July | 260.98 | 1.37 | 96.58 | 1.31 | 95.27 | 0.00 | 0.00 |
August | 238.80 | 3.98 | 102.45 | 5.46 | 97.00 | 0.00 | 0.00 |
September | 264.80 | 15.00 | 137.34 | 35.63 | 101.71 | 0.00 | 0.00 |
October | 407.09 | 71.64 | 236.32 | 131.96 | 104.36 | 0.00 | 0.00 |
November | 463.28 | 137.53 | 295.27 | 195.20 | 100.08 | 0.00 | 0.00 |
December | 365.75 | 192.81 | 263.52 | 165.16 | 98.36 | 0.00 | 0.00 |
Annual Sum or Average | 315.34 | 75.53 | 178.63 | 79.03 | 99.60 | 0.00 | 0.00 |
Minimum of Months | 238.80 | 1.37 | 92.58 | 1.31 | 91.03 | 0.00 | 0.00 |
Maximum of Months | 463.28 | 199.07 | 295.27 | 195.20 | 111.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 327.49 | 196.90 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 329.66 | 157.89 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 307.56 | 97.18 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 264.05 | 36.68 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 258.91 | 7.79 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 265.05 | 6.15 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 246.33 | 2.35 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 228.97 | 6.72 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 258.85 | 21.27 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 404.84 | 79.95 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 462.48 | 142.35 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 365.83 | 193.39 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 309.81 | 78.70 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 228.97 | 2.35 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 462.48 | 196.90 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 328.35 | 194.52 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 329.97 | 156.89 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 307.60 | 97.11 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 263.69 | 37.33 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 257.79 | 8.39 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 263.72 | 6.55 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 244.77 | 2.61 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 228.06 | 7.19 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 258.53 | 22.22 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 404.68 | 80.66 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 462.57 | 142.10 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 366.26 | 192.11 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 309.47 | 78.63 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 228.06 | 2.61 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 462.57 | 194.52 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 329.32 | 192.27 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 330.50 | 155.46 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 307.95 | 95.98 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 264.12 | 36.53 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 258.37 | 8.03 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 264.47 | 6.33 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 245.33 | 2.41 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 228.57 | 6.82 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 258.75 | 21.48 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 404.87 | 79.82 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 462.89 | 141.09 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 366.87 | 190.68 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 309.97 | 77.73 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 228.57 | 2.41 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 462.89 | 192.27 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 663.27 | 375.71 | 492.16 | 299.10 | 193.06 | 0.00 | 0.00 |
February | 664.04 | 303.62 | 467.90 | 259.90 | 207.99 | 0.00 | 0.00 |
March | 617.18 | 184.90 | 399.93 | 176.59 | 223.34 | 0.00 | 0.00 |
April | 529.11 | 67.89 | 280.85 | 79.17 | 201.68 | 0.00 | 0.00 |
May | 518.24 | 14.07 | 201.94 | 14.83 | 187.10 | 0.00 | 0.00 |
June | 531.90 | 11.56 | 184.78 | 3.10 | 181.68 | 0.00 | 0.00 |
July | 491.15 | 3.72 | 192.77 | 2.62 | 190.15 | 0.00 | 0.00 |
August | 457.95 | 11.32 | 204.49 | 10.89 | 193.60 | 0.00 | 0.00 |
September | 516.50 | 38.19 | 274.13 | 71.11 | 203.01 | 0.00 | 0.00 |
October | 808.63 | 153.60 | 471.67 | 263.37 | 208.30 | 0.00 | 0.00 |
November | 926.63 | 276.48 | 589.33 | 389.59 | 199.74 | 0.00 | 0.00 |
December | 736.92 | 374.70 | 525.96 | 329.64 | 196.32 | 0.00 | 0.00 |
Annual Sum or Average | 621.40 | 150.64 | 356.52 | 157.74 | 198.78 | 0.00 | 0.00 |
Minimum of Months | 457.95 | 3.72 | 184.78 | 2.62 | 181.68 | 0.00 | 0.00 |
Maximum of Months | 926.63 | 375.71 | 589.33 | 389.59 | 223.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 331.20 | 187.49 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 331.62 | 151.34 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 308.68 | 91.48 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 265.78 | 32.95 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 261.64 | 6.46 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 268.77 | 5.42 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 248.19 | 1.57 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 230.86 | 5.04 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 259.22 | 17.85 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 404.62 | 75.52 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 463.15 | 137.36 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 368.04 | 186.97 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 311.63 | 74.62 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 230.86 | 1.57 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 463.15 | 187.49 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 331.61 | 186.67 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 331.94 | 150.70 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 308.94 | 90.99 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 266.10 | 32.62 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 262.07 | 6.32 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 269.24 | 5.33 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 248.61 | 1.52 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 231.20 | 4.92 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 259.43 | 17.59 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 404.79 | 75.19 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 463.35 | 136.96 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 368.34 | 186.42 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 311.95 | 74.27 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 231.20 | 1.52 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 463.35 | 186.67 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 332.53 | 184.65 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 332.71 | 148.95 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 309.39 | 89.84 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 266.34 | 32.12 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 262.01 | 6.24 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 268.96 | 5.31 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 248.05 | 1.54 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 230.71 | 5.02 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 259.18 | 17.77 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 404.75 | 75.13 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 463.60 | 136.35 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 369.02 | 185.07 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 312.08 | 73.67 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 230.71 | 1.54 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 463.60 | 185.07 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 334.31 | 178.79 | 246.08 | 149.55 | 96.53 | 0.00 | 0.00 |
February | 334.51 | 142.91 | 233.95 | 129.95 | 104.00 | 0.00 | 0.00 |
March | 310.20 | 85.70 | 199.97 | 88.30 | 111.67 | 0.00 | 0.00 |
April | 265.52 | 30.77 | 140.42 | 39.59 | 100.84 | 0.00 | 0.00 |
May | 259.05 | 6.34 | 100.97 | 7.42 | 93.55 | 0.00 | 0.00 |
June | 264.57 | 5.52 | 92.39 | 1.55 | 90.84 | 0.00 | 0.00 |
July | 242.22 | 1.93 | 96.38 | 1.31 | 95.07 | 0.00 | 0.00 |
August | 225.72 | 6.25 | 102.24 | 5.45 | 96.80 | 0.00 | 0.00 |
September | 256.15 | 20.23 | 137.06 | 35.56 | 101.51 | 0.00 | 0.00 |
October | 403.06 | 76.49 | 235.84 | 131.69 | 104.15 | 0.00 | 0.00 |
November | 463.39 | 135.04 | 294.67 | 194.80 | 99.87 | 0.00 | 0.00 |
December | 370.30 | 180.82 | 262.98 | 164.82 | 98.16 | 0.00 | 0.00 |
Annual Sum or Average | 310.54 | 72.26 | 178.26 | 78.87 | 99.39 | 0.00 | 0.00 |
Minimum of Months | 225.72 | 1.93 | 92.39 | 1.31 | 90.84 | 0.00 | 0.00 |
Maximum of Months | 463.39 | 180.82 | 294.67 | 194.80 | 111.67 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.176060E+10 | 0.105140E+10 | 0.132092E+10 | 0.802760E+09 | 0.518160E+09 | 0.00 | 0.00 |
February | 0.160454E+10 | 0.742814E+09 | 0.113427E+10 | 0.630055E+09 | 0.504215E+09 | 0.00 | 0.00 |
March | 0.165840E+10 | 0.483987E+09 | 0.107338E+10 | 0.473964E+09 | 0.599418E+09 | 0.00 | 0.00 |
April | 0.139951E+10 | 0.159699E+09 | 0.729460E+09 | 0.205634E+09 | 0.523826E+09 | 0.00 | 0.00 |
May | 0.144310E+10 | 28846190.14 | 0.541984E+09 | 39815324.31 | 0.502168E+09 | 0.00 | 0.00 |
June | 0.142756E+10 | 21331759.34 | 0.479924E+09 | 8041294.43 | 0.471883E+09 | 0.00 | 0.00 |
July | 0.138218E+10 | 7997097.25 | 0.517372E+09 | 7033014.36 | 0.510339E+09 | 0.00 | 0.00 |
August | 0.126522E+10 | 23310677.06 | 0.548824E+09 | 29228462.76 | 0.519596E+09 | 0.00 | 0.00 |
September | 0.136383E+10 | 81819770.50 | 0.711995E+09 | 0.184705E+09 | 0.527290E+09 | 0.00 | 0.00 |
October | 0.217775E+10 | 0.385885E+09 | 0.126592E+10 | 0.706866E+09 | 0.559059E+09 | 0.00 | 0.00 |
November | 0.240447E+10 | 0.710656E+09 | 0.153069E+10 | 0.101190E+10 | 0.518790E+09 | 0.00 | 0.00 |
December | 0.196724E+10 | 0.102323E+10 | 0.141163E+10 | 0.884714E+09 | 0.526918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.198544E+11 | 0.472098E+10 | 0.112664E+11 | 0.498472E+10 | 0.628166E+10 | 0.00 | 0.00 |
Minimum of Months | 0.126522E+10 | 7997097.25 | 0.479924E+09 | 7033014.36 | 0.471883E+09 | 0.00 | 0.00 |
Maximum of Months | 0.240447E+10 | 0.105140E+10 | 0.153069E+10 | 0.101190E+10 | 0.599418E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.875024E+09 | 0.533180E+09 | 0.660460E+09 | 0.401380E+09 | 0.259080E+09 | 0.00 | 0.00 |
February | 0.798095E+09 | 0.377443E+09 | 0.567135E+09 | 0.315028E+09 | 0.252107E+09 | 0.00 | 0.00 |
March | 0.826873E+09 | 0.246413E+09 | 0.536691E+09 | 0.236982E+09 | 0.299709E+09 | 0.00 | 0.00 |
April | 0.701172E+09 | 81558506.18 | 0.364730E+09 | 0.102817E+09 | 0.261913E+09 | 0.00 | 0.00 |
May | 0.726739E+09 | 14522855.90 | 0.270992E+09 | 19907662.15 | 0.251084E+09 | 0.00 | 0.00 |
June | 0.720822E+09 | 10656813.38 | 0.239962E+09 | 4020647.22 | 0.235942E+09 | 0.00 | 0.00 |
July | 0.699020E+09 | 3679458.96 | 0.258686E+09 | 3516507.18 | 0.255170E+09 | 0.00 | 0.00 |
August | 0.639614E+09 | 10667632.33 | 0.274412E+09 | 14614231.38 | 0.259798E+09 | 0.00 | 0.00 |
September | 0.686364E+09 | 38890103.08 | 0.355998E+09 | 92352442.07 | 0.263645E+09 | 0.00 | 0.00 |
October | 0.109035E+10 | 0.191869E+09 | 0.632962E+09 | 0.353433E+09 | 0.279529E+09 | 0.00 | 0.00 |
November | 0.120081E+10 | 0.356465E+09 | 0.765344E+09 | 0.505950E+09 | 0.259395E+09 | 0.00 | 0.00 |
December | 0.979620E+09 | 0.516428E+09 | 0.705816E+09 | 0.442357E+09 | 0.263459E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.994451E+10 | 0.238177E+10 | 0.563319E+10 | 0.249236E+10 | 0.314083E+10 | 0.00 | 0.00 |
Minimum of Months | 0.639614E+09 | 3679458.96 | 0.239962E+09 | 3516507.18 | 0.235942E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120081E+10 | 0.533180E+09 | 0.765344E+09 | 0.505950E+09 | 0.299709E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.877147E+09 | 0.527386E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.797501E+09 | 0.381970E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.823772E+09 | 0.260277E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.684413E+09 | 95082119.71 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.693452E+09 | 20864762.20 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.687022E+09 | 15938015.07 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.659783E+09 | 6283869.11 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.613262E+09 | 18006458.20 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.670952E+09 | 55129147.38 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.108432E+10 | 0.214126E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.119876E+10 | 0.368971E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.979852E+09 | 0.517972E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.977024E+10 | 0.248201E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.613262E+09 | 6283869.11 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119876E+10 | 0.527386E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.879443E+09 | 0.521003E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.798253E+09 | 0.379551E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.823871E+09 | 0.260097E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.683485E+09 | 96762538.13 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.690465E+09 | 22473520.53 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.683555E+09 | 16977884.27 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.655605E+09 | 6979455.99 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.610845E+09 | 19262307.73 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.670099E+09 | 57585256.98 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.108389E+10 | 0.216035E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.119897E+10 | 0.368321E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.980989E+09 | 0.514542E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.975948E+10 | 0.247959E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.610845E+09 | 6979455.99 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119897E+10 | 0.521003E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.882038E+09 | 0.514978E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.799549E+09 | 0.376079E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.824813E+09 | 0.257076E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.684598E+09 | 94695341.94 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.692020E+09 | 21501150.35 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.685508E+09 | 16415707.64 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.657088E+09 | 6453498.76 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.612192E+09 | 18272212.52 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.670682E+09 | 55686210.95 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.108441E+10 | 0.213786E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.119981E+10 | 0.365715E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.982621E+09 | 0.510728E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.977533E+10 | 0.245139E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.612192E+09 | 6453498.76 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119981E+10 | 0.514978E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.177651E+10 | 0.100630E+10 | 0.131821E+10 | 0.801112E+09 | 0.517096E+09 | 0.00 | 0.00 |
February | 0.160644E+10 | 0.734508E+09 | 0.113194E+10 | 0.628762E+09 | 0.503180E+09 | 0.00 | 0.00 |
March | 0.165306E+10 | 0.495237E+09 | 0.107118E+10 | 0.472991E+09 | 0.598188E+09 | 0.00 | 0.00 |
April | 0.137145E+10 | 0.175979E+09 | 0.727962E+09 | 0.205212E+09 | 0.522750E+09 | 0.00 | 0.00 |
May | 0.138805E+10 | 37675426.54 | 0.540871E+09 | 39733568.00 | 0.501137E+09 | 0.00 | 0.00 |
June | 0.137870E+10 | 29951836.08 | 0.478939E+09 | 8024782.53 | 0.470914E+09 | 0.00 | 0.00 |
July | 0.131551E+10 | 9957636.51 | 0.516310E+09 | 7018572.86 | 0.509292E+09 | 0.00 | 0.00 |
August | 0.122658E+10 | 30308815.00 | 0.547697E+09 | 29168445.38 | 0.518529E+09 | 0.00 | 0.00 |
September | 0.133876E+10 | 98996796.51 | 0.710533E+09 | 0.184326E+09 | 0.526207E+09 | 0.00 | 0.00 |
October | 0.216583E+10 | 0.411414E+09 | 0.126333E+10 | 0.705415E+09 | 0.557911E+09 | 0.00 | 0.00 |
November | 0.240182E+10 | 0.716626E+09 | 0.152755E+10 | 0.100982E+10 | 0.517724E+09 | 0.00 | 0.00 |
December | 0.197376E+10 | 0.100359E+10 | 0.140873E+10 | 0.882898E+09 | 0.525836E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.195965E+11 | 0.475055E+10 | 0.112432E+11 | 0.497448E+10 | 0.626876E+10 | 0.00 | 0.00 |
Minimum of Months | 0.122658E+10 | 9957636.51 | 0.478939E+09 | 7018572.86 | 0.470914E+09 | 0.00 | 0.00 |
Maximum of Months | 0.240182E+10 | 0.100630E+10 | 0.152755E+10 | 0.100982E+10 | 0.598188E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.887079E+09 | 0.502172E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.802250E+09 | 0.366112E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.826768E+09 | 0.245017E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.688894E+09 | 85412932.51 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.700784E+09 | 17298073.44 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.696655E+09 | 14053786.69 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.664752E+09 | 4202357.91 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.618332E+09 | 13488417.34 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.671896E+09 | 46260884.26 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.108374E+10 | 0.202282E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.120050E+10 | 0.356029E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.985766E+09 | 0.500775E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.982741E+10 | 0.235310E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.618332E+09 | 4202357.91 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120050E+10 | 0.502172E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.888179E+09 | 0.499978E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.803022E+09 | 0.364569E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.827454E+09 | 0.243698E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.689728E+09 | 84554123.75 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.701918E+09 | 16923010.49 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.697861E+09 | 13820248.23 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.665880E+09 | 4058282.50 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.619235E+09 | 13173555.34 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.672452E+09 | 45599584.47 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.108420E+10 | 0.201396E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.120101E+10 | 0.354995E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.986568E+09 | 0.499311E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.983751E+10 | 0.234208E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.619235E+09 | 4058282.50 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120101E+10 | 0.499978E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.890655E+09 | 0.494561E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.804899E+09 | 0.360330E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.828675E+09 | 0.240634E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.690342E+09 | 83265810.32 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.701765E+09 | 16719686.13 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.697156E+09 | 13753735.39 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.664371E+09 | 4113536.99 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.617928E+09 | 13433622.44 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.671805E+09 | 46060700.43 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.108407E+10 | 0.201229E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.120164E+10 | 0.353431E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.988380E+09 | 0.495686E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.984169E+10 | 0.232322E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.617928E+09 | 4113536.99 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120164E+10 | 0.495686E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.895422E+09 | 0.478875E+09 | 0.659104E+09 | 0.400556E+09 | 0.258548E+09 | 0.00 | 0.00 |
February | 0.809245E+09 | 0.345721E+09 | 0.565971E+09 | 0.314381E+09 | 0.251590E+09 | 0.00 | 0.00 |
March | 0.830827E+09 | 0.229534E+09 | 0.535589E+09 | 0.236495E+09 | 0.299094E+09 | 0.00 | 0.00 |
April | 0.688233E+09 | 79747839.38 | 0.363981E+09 | 0.102606E+09 | 0.261375E+09 | 0.00 | 0.00 |
May | 0.693834E+09 | 16974004.55 | 0.270435E+09 | 19866784.00 | 0.250569E+09 | 0.00 | 0.00 |
June | 0.685757E+09 | 14301074.14 | 0.239469E+09 | 4012391.27 | 0.235457E+09 | 0.00 | 0.00 |
July | 0.648751E+09 | 5176318.87 | 0.258155E+09 | 3509286.43 | 0.254646E+09 | 0.00 | 0.00 |
August | 0.604558E+09 | 16730486.16 | 0.273849E+09 | 14584222.69 | 0.259265E+09 | 0.00 | 0.00 |
September | 0.663935E+09 | 52428303.07 | 0.355267E+09 | 92162806.66 | 0.263104E+09 | 0.00 | 0.00 |
October | 0.107956E+10 | 0.204869E+09 | 0.631663E+09 | 0.352707E+09 | 0.278955E+09 | 0.00 | 0.00 |
November | 0.120110E+10 | 0.350026E+09 | 0.763773E+09 | 0.504911E+09 | 0.258862E+09 | 0.00 | 0.00 |
December | 0.991820E+09 | 0.484318E+09 | 0.704367E+09 | 0.441449E+09 | 0.262918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.979304E+10 | 0.227870E+10 | 0.562162E+10 | 0.248724E+10 | 0.313438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.604558E+09 | 5176318.87 | 0.239469E+09 | 3509286.43 | 0.235457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120110E+10 | 0.484318E+09 | 0.763773E+09 | 0.504911E+09 | 0.299094E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.37 | 7.87 | 1.20 | 0.37 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.77 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.59 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.31 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.95 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.37 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.28 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.69 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.73 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.45 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.87 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.75 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.37 | 7.87 | 0.66 | 0.37 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.18 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.17 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.47 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.63 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.60 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.49 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.34 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.56 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.67 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.02 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.14 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.28 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.18 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.67 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.55 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.57 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.73 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.61 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.36 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.40 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.17 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.16 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.05 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.91 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.61 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.17 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.47 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.24 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.03 | 0.00 | 15.60 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.69 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.40 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.58 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.47 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.301086E+09 | -186921586.7 | 0.00 | 0.00 | 744.00 | 0.00 | -114164510.6 | 58.99 | 0.00 | 0.00 |
February | 0.268447E+09 | -166091623.5 | 0.00 | 0.00 | 672.00 | 0.00 | -102355734.4 | 58.99 | 0.00 | 0.00 |
March | 0.286716E+09 | -174339501.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112376491.1 | 58.99 | 0.00 | 0.00 |
April | 0.257388E+09 | -149650693.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107737712.6 | 58.99 | 0.00 | 0.00 |
May | 0.247039E+09 | -136556816.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110481752.5 | 58.99 | 0.00 | 0.00 |
June | 0.226398E+09 | -119766993.5 | 0.00 | 0.00 | 720.00 | 0.00 | -106631099.8 | 58.99 | 0.00 | 0.00 |
July | 0.225828E+09 | -115765022.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110062898.2 | 58.99 | 0.00 | 0.00 |
August | 0.232338E+09 | -122192521.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110145640.2 | 58.99 | 0.00 | 0.00 |
September | 0.236367E+09 | -129448063.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106918673.9 | 58.99 | 0.00 | 0.00 |
October | 0.261338E+09 | -150070007.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111268242.8 | 58.99 | 0.00 | 0.00 |
November | 0.270795E+09 | -162148755.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108646496.8 | 58.99 | 0.00 | 0.00 |
December | 0.295162E+09 | -181752360.8 | 0.00 | 0.00 | 744.00 | 0.00 | -113410055.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.310890E+10 | -.179470E+10 | 8760.00 | -.131420E+10 | 58.99 | |||||
Minimum of Months | 0.225828E+09 | -186921586.7 | 0.00 | 0.00 | 672.00 | 0.00 | -114164510.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.301086E+09 | -115765022.2 | 0.00 | 0.00 | 744.00 | 0.00 | -102355734.4 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.300588E+09 | -186918284.5 | 0.00 | 0.00 | 744.00 | 0.00 | -113669420.4 | 58.99 | 0.00 | 0.00 |
February | 0.268095E+09 | -166091318.7 | 0.00 | 0.00 | 672.00 | 0.00 | -102003805.0 | 58.99 | 0.00 | 0.00 |
March | 0.286421E+09 | -174344422.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112076731.1 | 58.99 | 0.00 | 0.00 |
April | 0.257247E+09 | -149649200.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107597773.1 | 58.99 | 0.00 | 0.00 |
May | 0.247021E+09 | -136560246.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110460725.7 | 58.99 | 0.00 | 0.00 |
June | 0.226450E+09 | -119764865.4 | 0.00 | 0.00 | 720.00 | 0.00 | -106685135.0 | 58.99 | 0.00 | 0.00 |
July | 0.225930E+09 | -115767273.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110163216.7 | 58.99 | 0.00 | 0.00 |
August | 0.232448E+09 | -122185925.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110262151.9 | 58.99 | 0.00 | 0.00 |
September | 0.236445E+09 | -129445210.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106999331.7 | 58.99 | 0.00 | 0.00 |
October | 0.261317E+09 | -150065111.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111252096.2 | 58.99 | 0.00 | 0.00 |
November | 0.270675E+09 | -162150568.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108524765.2 | 58.99 | 0.00 | 0.00 |
December | 0.294835E+09 | -181753614.0 | 0.00 | 0.00 | 744.00 | 0.00 | -113081654.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.310747E+10 | -.179470E+10 | 8760.00 | -.131278E+10 | 58.99 | |||||
Minimum of Months | 0.225930E+09 | -186918284.5 | 0.00 | 0.00 | 672.00 | 0.00 | -113669420.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.300588E+09 | -115767273.5 | 0.00 | 0.00 | 744.00 | 0.00 | -102003805.0 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.278358E+09 | -164369615.4 | 0.00 | 0.00 | 744.00 | 0.00 | -113988041.8 | 58.99 | 0.00 | 0.00 |
February | 0.247693E+09 | -146191745.8 | 0.00 | 0.00 | 672.00 | 0.00 | -101500872.4 | 58.99 | 0.00 | 0.00 |
March | 0.266388E+09 | -155702854.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110685338.3 | 58.99 | 0.00 | 0.00 |
April | 0.236747E+09 | -131505514.2 | 0.00 | 0.00 | 720.00 | 0.00 | -105241766.8 | 58.99 | 0.00 | 0.00 |
May | 0.228749E+09 | -121163308.7 | 0.00 | 0.00 | 744.00 | 0.00 | -107585674.6 | 58.99 | 0.00 | 0.00 |
June | 0.210608E+09 | -106755816.7 | 0.00 | 0.00 | 720.00 | 0.00 | -103852296.2 | 58.98 | 0.00 | 0.00 |
July | 0.208228E+09 | -101099308.8 | 0.00 | 0.00 | 744.00 | 0.00 | -107128221.5 | 59.00 | 0.00 | 0.00 |
August | 0.216907E+09 | -109232544.3 | 0.00 | 0.00 | 744.00 | 0.00 | -107674802.1 | 58.98 | 0.00 | 0.00 |
September | 0.218264E+09 | -113737104.7 | 0.00 | 0.00 | 720.00 | 0.00 | -104526714.2 | 58.99 | 0.00 | 0.00 |
October | 0.241057E+09 | -131994126.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109062385.6 | 58.99 | 0.00 | 0.00 |
November | 0.250592E+09 | -143139284.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107452685.4 | 59.00 | 0.00 | 0.00 |
December | 0.271539E+09 | -158639793.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112898797.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.287513E+10 | -.158353E+10 | 8760.00 | -.129160E+10 | 58.99 | |||||
Minimum of Months | 0.208228E+09 | -164369615.4 | 0.00 | 0.00 | 672.00 | 0.00 | -113988041.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.278358E+09 | -101099308.8 | 0.00 | 0.00 | 744.00 | 0.00 | -101500872.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.278722E+09 | -164373703.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114348178.6 | 58.99 | 0.00 | 0.00 |
February | 0.247823E+09 | -146187321.9 | 0.00 | 0.00 | 672.00 | 0.00 | -101635814.6 | 58.99 | 0.00 | 0.00 |
March | 0.266403E+09 | -155695611.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110706960.7 | 58.99 | 0.00 | 0.00 |
April | 0.236620E+09 | -131514783.2 | 0.00 | 0.00 | 720.00 | 0.00 | -105104719.6 | 58.99 | 0.00 | 0.00 |
May | 0.228551E+09 | -121157221.8 | 0.00 | 0.00 | 744.00 | 0.00 | -107394249.2 | 58.99 | 0.00 | 0.00 |
June | 0.210410E+09 | -106746689.0 | 0.00 | 0.00 | 720.00 | 0.00 | -103663774.9 | 58.98 | 0.00 | 0.00 |
July | 0.208016E+09 | -101131962.9 | 0.00 | 0.00 | 744.00 | 0.00 | -106884294.0 | 58.99 | 0.00 | 0.00 |
August | 0.216733E+09 | -109180453.6 | 0.00 | 0.00 | 744.00 | 0.00 | -107552660.6 | 59.00 | 0.00 | 0.00 |
September | 0.218102E+09 | -113738543.5 | 0.00 | 0.00 | 720.00 | 0.00 | -104363583.0 | 58.99 | 0.00 | 0.00 |
October | 0.240951E+09 | -131999114.5 | 0.00 | 0.00 | 744.00 | 0.00 | -108952197.0 | 58.99 | 0.00 | 0.00 |
November | 0.250624E+09 | -143186130.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107437798.7 | 58.98 | 0.00 | 0.00 |
December | 0.271728E+09 | -158658644.4 | 0.00 | 0.00 | 744.00 | 0.00 | -113069356.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.287468E+10 | -.158357E+10 | 8760.00 | -.129111E+10 | 58.99 | |||||
Minimum of Months | 0.208016E+09 | -164373703.1 | 0.00 | 0.00 | 672.00 | 0.00 | -114348178.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.278722E+09 | -101131962.9 | 0.00 | 0.00 | 744.00 | 0.00 | -101635814.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.270844E+09 | -155340396.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115503492.6 | 59.00 | 0.00 | 0.00 |
February | 0.240633E+09 | -138247298.0 | 0.00 | 0.00 | 672.00 | 0.00 | -102385258.9 | 58.99 | 0.00 | 0.00 |
March | 0.258845E+09 | -147280509.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111564427.8 | 59.00 | 0.00 | 0.00 |
April | 0.230308E+09 | -124450425.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105857721.4 | 58.99 | 0.00 | 0.00 |
May | 0.222632E+09 | -114597331.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108034437.0 | 58.99 | 0.00 | 0.00 |
June | 0.205356E+09 | -101019422.3 | 0.00 | 0.00 | 720.00 | 0.00 | -104336445.0 | 58.98 | 0.00 | 0.00 |
July | 0.202957E+09 | -95643505.7 | 0.00 | 0.00 | 744.00 | 0.00 | -107313402.0 | 58.99 | 0.00 | 0.00 |
August | 0.211414E+09 | -103350863.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108062659.7 | 58.99 | 0.00 | 0.00 |
September | 0.212526E+09 | -107642680.4 | 0.00 | 0.00 | 720.00 | 0.00 | -104883720.8 | 58.99 | 0.00 | 0.00 |
October | 0.234297E+09 | -124768922.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109528371.3 | 58.99 | 0.00 | 0.00 |
November | 0.243244E+09 | -135236907.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108006984.7 | 58.98 | 0.00 | 0.00 |
December | 0.263901E+09 | -150034015.8 | 0.00 | 0.00 | 744.00 | 0.00 | -113867361.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.279696E+10 | -.149761E+10 | 8760.00 | -.129934E+10 | 58.99 | |||||
Minimum of Months | 0.202957E+09 | -155340396.1 | 0.00 | 0.00 | 672.00 | 0.00 | -115503492.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.270844E+09 | -95643505.7 | 0.00 | 0.00 | 744.00 | 0.00 | -102385258.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.270893E+09 | -155341546.6 | 0.00 | 0.00 | 744.00 | 0.00 | -115551560.5 | 59.00 | 0.00 | 0.00 |
February | 0.240682E+09 | -138244708.5 | 0.00 | 0.00 | 672.00 | 0.00 | -102437509.4 | 58.99 | 0.00 | 0.00 |
March | 0.258948E+09 | -147305367.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111642455.3 | 59.00 | 0.00 | 0.00 |
April | 0.230474E+09 | -124464701.5 | 0.00 | 0.00 | 720.00 | 0.00 | -106008857.8 | 58.99 | 0.00 | 0.00 |
May | 0.222829E+09 | -114602707.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108226278.8 | 58.99 | 0.00 | 0.00 |
June | 0.205547E+09 | -100970934.0 | 0.00 | 0.00 | 720.00 | 0.00 | -104575768.5 | 58.99 | 0.00 | 0.00 |
July | 0.203162E+09 | -95613566.4 | 0.00 | 0.00 | 744.00 | 0.00 | -107548655.7 | 59.00 | 0.00 | 0.00 |
August | 0.211620E+09 | -103372630.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108247276.8 | 58.98 | 0.00 | 0.00 |
September | 0.212701E+09 | -107634153.8 | 0.00 | 0.00 | 720.00 | 0.00 | -105067215.8 | 58.99 | 0.00 | 0.00 |
October | 0.234455E+09 | -124757750.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109697310.8 | 58.99 | 0.00 | 0.00 |
November | 0.243349E+09 | -135208135.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108140742.1 | 58.99 | 0.00 | 0.00 |
December | 0.263942E+09 | -150038078.4 | 0.00 | 0.00 | 744.00 | 0.00 | -113903701.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.279860E+10 | -.149755E+10 | 8760.00 | -.130105E+10 | 58.99 | |||||
Minimum of Months | 0.203162E+09 | -155341546.6 | 0.00 | 0.00 | 672.00 | 0.00 | -115551560.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.270893E+09 | -95613566.4 | 0.00 | 0.00 | 744.00 | 0.00 | -102437509.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.271024E+09 | -155349507.6 | 0.00 | 0.00 | 744.00 | 0.00 | -115674550.6 | 58.99 | 0.00 | 0.00 |
February | 0.240771E+09 | -138241350.2 | 0.00 | 0.00 | 672.00 | 0.00 | -102529899.9 | 58.99 | 0.00 | 0.00 |
March | 0.259014E+09 | -147360675.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111653208.6 | 58.98 | 0.00 | 0.00 |
April | 0.230532E+09 | -124440259.2 | 0.00 | 0.00 | 720.00 | 0.00 | -106091867.9 | 58.99 | 0.00 | 0.00 |
May | 0.222875E+09 | -114565401.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108309412.8 | 59.00 | 0.00 | 0.00 |
June | 0.205603E+09 | -101003931.3 | 0.00 | 0.00 | 720.00 | 0.00 | -104599373.5 | 58.98 | 0.00 | 0.00 |
July | 0.203213E+09 | -95660714.9 | 0.00 | 0.00 | 744.00 | 0.00 | -107551970.1 | 58.98 | 0.00 | 0.00 |
August | 0.211648E+09 | -103317230.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108331092.9 | 58.99 | 0.00 | 0.00 |
September | 0.212740E+09 | -107620178.0 | 0.00 | 0.00 | 720.00 | 0.00 | -105119927.4 | 58.99 | 0.00 | 0.00 |
October | 0.234509E+09 | -124758550.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109750386.6 | 58.99 | 0.00 | 0.00 |
November | 0.243405E+09 | -135205896.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108199308.5 | 58.99 | 0.00 | 0.00 |
December | 0.264036E+09 | -150042337.9 | 0.00 | 0.00 | 744.00 | 0.00 | -113994008.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.279937E+10 | -.149757E+10 | 8760.00 | -.130181E+10 | 58.99 | |||||
Minimum of Months | 0.203213E+09 | -155349507.6 | 0.00 | 0.00 | 672.00 | 0.00 | -115674550.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.271024E+09 | -95660714.9 | 0.00 | 0.00 | 744.00 | 0.00 | -102529899.9 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 319.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 364.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 372.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 317.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 315.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | ||||||||||
Minimum of Months | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3249809.34 | 14738.29 | 02-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3249809.34 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3249809.34 | 14738.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 10318990.32 | 13825.81 | 02-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10318990.32 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10318990.32 | 13825.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 22037503.05 | 23115.37 | 02-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22037503.05 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22037503.05 | 23115.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 34835107.46 | 30204.07 | 02-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34835107.46 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34835107.46 | 30204.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 71466443.25 | 62610.90 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 71466443.25 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71466443.25 | 62610.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 37641222.14 | 32964.00 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37641222.14 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37641222.14 | 32964.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 41258671.45 | 32837.47 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41258671.45 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41258671.45 | 32837.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 50035489.28 | 32852.10 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50035489.28 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50035489.28 | 32852.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 70634369.88 | 35184.59 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 891275.68 | 2970.92 | 02-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2234625.83 | 3527.31 | 21-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73760271.40 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 70634369.88 | 35184.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.616252E+10 | 0.560868E+10 | 11910.33 | 12-JAN-15:00 | 11553.77 | 0.00 |
February | 0.00 | 0.00 | 0.118222E+11 | 0.105462E+11 | 22654.85 | 25-FEB-09:03 | 16673.56 | 0.00 |
March | 0.00 | 0.00 | 0.234596E+11 | 0.208172E+11 | 56140.77 | 29-MAR-08:62 | 42445.80 | 0.00 |
April | 0.00 | 0.00 | 0.349577E+11 | 0.318750E+11 | 56969.41 | 26-APR-08:61 | 41430.69 | 0.00 |
May | 0.00 | 0.00 | 0.494419E+11 | 0.404072E+11 | 60546.50 | 24-MAY-08:61 | 31533.05 | 0.00 |
June | 0.00 | 0.00 | 0.556303E+11 | 0.404511E+11 | 61490.67 | 26-JUN-08:61 | 28826.67 | 0.00 |
July | 0.00 | 0.00 | 0.634735E+11 | 0.388640E+11 | 61569.24 | 18-JUL-08:61 | 28177.23 | 0.00 |
August | 0.00 | 0.00 | 0.628871E+11 | 0.363875E+11 | 61561.97 | 10-AUG-07:01 | 29612.56 | 0.00 |
September | 0.00 | 0.00 | 0.528914E+11 | 0.329867E+11 | 61228.11 | 06-SEP-08:61 | 29673.24 | 0.00 |
October | 0.00 | 0.00 | 0.354019E+11 | 0.288650E+11 | 59136.70 | 12-OCT-08:62 | 34244.47 | 0.00 |
November | 0.00 | 0.00 | 0.208208E+11 | 0.184502E+11 | 55990.03 | 09-NOV-09:02 | 42915.71 | 0.00 |
December | 0.00 | 0.00 | 0.919676E+10 | 0.825271E+10 | 14399.42 | 28-DEC-15:00 | 13366.62 | 0.00 |
Annual Sum or Average | 0.426146E+12 | 0.313512E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.616252E+10 | 0.560868E+10 | 11910.33 | 11553.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.634735E+11 | 0.404511E+11 | 61569.24 | 42915.71 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.432007E+10 | 0.398673E+10 | 6464.82 | 12-JAN-15:00 | 6294.63 | 0.00 |
February | 0.00 | 0.00 | 0.687875E+10 | 0.624078E+10 | 14283.69 | 25-FEB-09:03 | 11210.72 | 0.00 |
March | 0.00 | 0.00 | 0.122654E+11 | 0.110869E+11 | 29064.34 | 29-MAR-08:62 | 23033.05 | 0.00 |
April | 0.00 | 0.00 | 0.173071E+11 | 0.159959E+11 | 29412.42 | 26-APR-08:61 | 22330.56 | 0.00 |
May | 0.00 | 0.00 | 0.240640E+11 | 0.200077E+11 | 31113.12 | 24-MAY-08:61 | 17730.60 | 0.00 |
June | 0.00 | 0.00 | 0.267737E+11 | 0.198632E+11 | 31594.13 | 24-JUN-08:61 | 16606.20 | 0.00 |
July | 0.00 | 0.00 | 0.303022E+11 | 0.190303E+11 | 31842.31 | 25-JUL-08:61 | 15680.35 | 0.00 |
August | 0.00 | 0.00 | 0.301168E+11 | 0.178748E+11 | 32010.91 | 12-AUG-08:61 | 15226.00 | 0.00 |
September | 0.00 | 0.00 | 0.252575E+11 | 0.162120E+11 | 31392.76 | 06-SEP-08:61 | 16974.02 | 0.00 |
October | 0.00 | 0.00 | 0.174694E+11 | 0.145733E+11 | 30402.59 | 12-OCT-08:62 | 19311.80 | 0.00 |
November | 0.00 | 0.00 | 0.110012E+11 | 0.993990E+10 | 28883.08 | 09-NOV-09:02 | 23497.90 | 0.00 |
December | 0.00 | 0.00 | 0.582166E+10 | 0.532096E+10 | 7636.43 | 28-DEC-14:40 | 7139.29 | 0.00 |
Annual Sum or Average | 0.211578E+12 | 0.160133E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.432007E+10 | 0.398673E+10 | 6464.82 | 6294.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.303022E+11 | 0.200077E+11 | 32010.91 | 23497.90 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.242277E+10 | 0.225022E+10 | 6064.24 | 12-JAN-15:00 | 5912.08 | 0.00 |
February | 0.00 | 0.00 | 0.477640E+10 | 0.433253E+10 | 14734.29 | 25-FEB-08:63 | 10925.23 | 0.00 |
March | 0.00 | 0.00 | 0.960422E+10 | 0.864440E+10 | 29274.96 | 11-MAR-08:61 | 22635.29 | 0.00 |
April | 0.00 | 0.00 | 0.140914E+11 | 0.129380E+11 | 29607.85 | 26-APR-07:01 | 21584.20 | 0.00 |
May | 0.00 | 0.00 | 0.202204E+11 | 0.166101E+11 | 31175.77 | 24-MAY-07:01 | 17018.60 | 0.00 |
June | 0.00 | 0.00 | 0.226036E+11 | 0.164346E+11 | 31968.44 | 25-JUN-08:61 | 14689.14 | 0.00 |
July | 0.00 | 0.00 | 0.251218E+11 | 0.152432E+11 | 31961.96 | 23-JUL-08:61 | 14103.42 | 0.00 |
August | 0.00 | 0.00 | 0.254830E+11 | 0.146100E+11 | 32062.51 | 21-AUG-07:01 | 13242.86 | 0.00 |
September | 0.00 | 0.00 | 0.208829E+11 | 0.129676E+11 | 32077.05 | 04-SEP-08:61 | 13988.96 | 0.00 |
October | 0.00 | 0.00 | 0.140911E+11 | 0.116149E+11 | 30708.74 | 12-OCT-07:01 | 17742.27 | 0.00 |
November | 0.00 | 0.00 | 0.845956E+10 | 0.765739E+10 | 28995.93 | 09-NOV-08:62 | 21219.41 | 0.00 |
December | 0.00 | 0.00 | 0.371458E+10 | 0.340948E+10 | 7274.62 | 28-DEC-14:00 | 6857.37 | 0.00 |
Annual Sum or Average | 0.171472E+12 | 0.126712E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.242277E+10 | 0.225022E+10 | 6064.24 | 5912.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.254830E+11 | 0.166101E+11 | 32077.05 | 22635.29 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.228220E+10 | 0.212086E+10 | 5970.82 | 12-JAN-15:00 | 5820.84 | 0.00 |
February | 0.00 | 0.00 | 0.469748E+10 | 0.426065E+10 | 14426.57 | 25-FEB-08:63 | 10690.57 | 0.00 |
March | 0.00 | 0.00 | 0.959137E+10 | 0.863252E+10 | 29333.89 | 11-MAR-08:61 | 22688.39 | 0.00 |
April | 0.00 | 0.00 | 0.141572E+11 | 0.129997E+11 | 29659.04 | 26-APR-07:01 | 21644.87 | 0.00 |
May | 0.00 | 0.00 | 0.203575E+11 | 0.167339E+11 | 31228.43 | 24-MAY-07:01 | 17097.83 | 0.00 |
June | 0.00 | 0.00 | 0.227423E+11 | 0.165534E+11 | 32030.17 | 25-JUN-08:61 | 14792.72 | 0.00 |
July | 0.00 | 0.00 | 0.252863E+11 | 0.153737E+11 | 32023.67 | 23-JUL-08:61 | 14247.68 | 0.00 |
August | 0.00 | 0.00 | 0.256099E+11 | 0.147078E+11 | 32124.42 | 21-AUG-07:01 | 13377.73 | 0.00 |
September | 0.00 | 0.00 | 0.209901E+11 | 0.130512E+11 | 32138.99 | 04-SEP-08:61 | 14158.75 | 0.00 |
October | 0.00 | 0.00 | 0.141566E+11 | 0.116735E+11 | 30771.39 | 12-OCT-07:01 | 17811.40 | 0.00 |
November | 0.00 | 0.00 | 0.843104E+10 | 0.763112E+10 | 28897.50 | 09-NOV-08:62 | 21145.71 | 0.00 |
December | 0.00 | 0.00 | 0.361182E+10 | 0.331418E+10 | 7188.57 | 28-DEC-14:00 | 6775.49 | 0.00 |
Annual Sum or Average | 0.171914E+12 | 0.127052E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.228220E+10 | 0.212086E+10 | 5970.82 | 5820.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.256099E+11 | 0.167339E+11 | 32138.99 | 22688.39 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.206706E+10 | 0.192283E+10 | 5793.76 | 12-JAN-15:00 | 5646.29 | 0.00 |
February | 0.00 | 0.00 | 0.450260E+10 | 0.408365E+10 | 12916.21 | 25-FEB-08:63 | 9529.93 | 0.00 |
March | 0.00 | 0.00 | 0.939302E+10 | 0.844938E+10 | 29249.05 | 11-MAR-08:61 | 22531.03 | 0.00 |
April | 0.00 | 0.00 | 0.140017E+11 | 0.128519E+11 | 29604.28 | 26-APR-07:01 | 21550.32 | 0.00 |
May | 0.00 | 0.00 | 0.202188E+11 | 0.166100E+11 | 31167.18 | 24-MAY-07:01 | 16996.67 | 0.00 |
June | 0.00 | 0.00 | 0.225994E+11 | 0.164327E+11 | 31955.42 | 25-JUN-08:61 | 14656.40 | 0.00 |
July | 0.00 | 0.00 | 0.251551E+11 | 0.152719E+11 | 31954.90 | 28-JUL-07:01 | 14857.58 | 0.00 |
August | 0.00 | 0.00 | 0.254523E+11 | 0.145879E+11 | 32049.46 | 21-AUG-07:01 | 13269.34 | 0.00 |
September | 0.00 | 0.00 | 0.208322E+11 | 0.129282E+11 | 32063.99 | 04-SEP-08:61 | 14060.63 | 0.00 |
October | 0.00 | 0.00 | 0.140032E+11 | 0.115377E+11 | 30690.44 | 12-OCT-07:01 | 17678.71 | 0.00 |
November | 0.00 | 0.00 | 0.825467E+10 | 0.746769E+10 | 27187.38 | 09-NOV-08:62 | 19812.77 | 0.00 |
December | 0.00 | 0.00 | 0.340873E+10 | 0.312512E+10 | 7015.31 | 28-DEC-14:00 | 6608.49 | 0.00 |
Annual Sum or Average | 0.169889E+12 | 0.125269E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.206706E+10 | 0.192283E+10 | 5793.76 | 5646.29 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.254523E+11 | 0.166100E+11 | 32063.99 | 22531.03 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.300324E+10 | 0.277205E+10 | 10237.50 | 12-JAN-15:10 | 9824.82 | 0.00 |
February | 0.00 | 0.00 | 0.758491E+10 | 0.681457E+10 | 17736.56 | 25-FEB-09:03 | 13001.84 | 0.00 |
March | 0.00 | 0.00 | 0.167016E+11 | 0.148940E+11 | 53461.60 | 11-MAR-09:01 | 42557.23 | 0.00 |
April | 0.00 | 0.00 | 0.251878E+11 | 0.230825E+11 | 54219.89 | 24-APR-08:61 | 40489.29 | 0.00 |
May | 0.00 | 0.00 | 0.368122E+11 | 0.300824E+11 | 57538.64 | 24-MAY-08:61 | 30942.59 | 0.00 |
June | 0.00 | 0.00 | 0.412291E+11 | 0.298081E+11 | 58773.74 | 25-JUN-09:01 | 27274.14 | 0.00 |
July | 0.00 | 0.00 | 0.456444E+11 | 0.273536E+11 | 58823.81 | 18-JUL-08:61 | 27293.58 | 0.00 |
August | 0.00 | 0.00 | 0.464839E+11 | 0.262037E+11 | 59029.06 | 21-AUG-08:61 | 24214.69 | 0.00 |
September | 0.00 | 0.00 | 0.376254E+11 | 0.230599E+11 | 59088.76 | 04-SEP-09:01 | 25361.93 | 0.00 |
October | 0.00 | 0.00 | 0.252401E+11 | 0.206081E+11 | 56372.80 | 12-OCT-08:62 | 32667.94 | 0.00 |
November | 0.00 | 0.00 | 0.145358E+11 | 0.130027E+11 | 53431.18 | 09-NOV-09:02 | 40463.82 | 0.00 |
December | 0.00 | 0.00 | 0.540279E+10 | 0.487786E+10 | 12575.29 | 28-DEC-14:00 | 11664.32 | 0.00 |
Annual Sum or Average | 0.305451E+12 | 0.222560E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.300324E+10 | 0.277205E+10 | 10237.50 | 9824.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.464839E+11 | 0.300824E+11 | 59088.76 | 42557.23 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.154944E+10 | 0.143557E+10 | 5339.34 | 12-JAN-15:10 | 5146.59 | 0.00 |
February | 0.00 | 0.00 | 0.395641E+10 | 0.356721E+10 | 9162.82 | 25-FEB-09:03 | 6772.64 | 0.00 |
March | 0.00 | 0.00 | 0.871812E+10 | 0.779903E+10 | 28089.07 | 11-MAR-09:01 | 22419.07 | 0.00 |
April | 0.00 | 0.00 | 0.131468E+11 | 0.120678E+11 | 28502.01 | 24-APR-08:61 | 21357.36 | 0.00 |
May | 0.00 | 0.00 | 0.192012E+11 | 0.157191E+11 | 30240.08 | 24-MAY-08:61 | 16347.94 | 0.00 |
June | 0.00 | 0.00 | 0.214726E+11 | 0.155561E+11 | 30885.42 | 25-JUN-09:01 | 14336.30 | 0.00 |
July | 0.00 | 0.00 | 0.237783E+11 | 0.142896E+11 | 30911.73 | 18-JUL-08:61 | 14453.43 | 0.00 |
August | 0.00 | 0.00 | 0.241999E+11 | 0.136814E+11 | 31019.58 | 21-AUG-08:61 | 12751.20 | 0.00 |
September | 0.00 | 0.00 | 0.196152E+11 | 0.120571E+11 | 31050.96 | 04-SEP-09:01 | 13376.05 | 0.00 |
October | 0.00 | 0.00 | 0.131718E+11 | 0.107876E+11 | 29619.92 | 12-OCT-08:62 | 17314.47 | 0.00 |
November | 0.00 | 0.00 | 0.759413E+10 | 0.681684E+10 | 28083.17 | 09-NOV-09:02 | 21423.63 | 0.00 |
December | 0.00 | 0.00 | 0.282166E+10 | 0.255694E+10 | 6548.44 | 28-DEC-14:00 | 6096.96 | 0.00 |
Annual Sum or Average | 0.159225E+12 | 0.116334E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.154944E+10 | 0.143557E+10 | 5339.34 | 5146.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.241999E+11 | 0.157191E+11 | 31050.96 | 22419.07 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.147850E+10 | 0.137041E+10 | 5262.08 | 12-JAN-15:10 | 5070.52 | 0.00 |
February | 0.00 | 0.00 | 0.387429E+10 | 0.349266E+10 | 8582.06 | 25-FEB-09:03 | 6329.53 | 0.00 |
March | 0.00 | 0.00 | 0.862496E+10 | 0.771250E+10 | 27978.48 | 11-MAR-09:01 | 22290.16 | 0.00 |
April | 0.00 | 0.00 | 0.130622E+11 | 0.119872E+11 | 28396.67 | 24-APR-08:61 | 21253.57 | 0.00 |
May | 0.00 | 0.00 | 0.191117E+11 | 0.156390E+11 | 30135.99 | 24-MAY-08:61 | 16255.26 | 0.00 |
June | 0.00 | 0.00 | 0.213821E+11 | 0.154792E+11 | 30769.51 | 25-JUN-09:01 | 14241.44 | 0.00 |
July | 0.00 | 0.00 | 0.236879E+11 | 0.142191E+11 | 30795.73 | 18-JUL-08:61 | 14368.03 | 0.00 |
August | 0.00 | 0.00 | 0.241095E+11 | 0.136113E+11 | 30903.18 | 21-AUG-08:61 | 12674.77 | 0.00 |
September | 0.00 | 0.00 | 0.195323E+11 | 0.119916E+11 | 30934.44 | 04-SEP-09:01 | 13297.23 | 0.00 |
October | 0.00 | 0.00 | 0.130950E+11 | 0.107190E+11 | 29507.65 | 12-OCT-08:62 | 17208.24 | 0.00 |
November | 0.00 | 0.00 | 0.751919E+10 | 0.674695E+10 | 27975.69 | 09-NOV-09:02 | 21300.58 | 0.00 |
December | 0.00 | 0.00 | 0.274888E+10 | 0.249006E+10 | 6477.92 | 28-DEC-14:00 | 6028.91 | 0.00 |
Annual Sum or Average | 0.158227E+12 | 0.115459E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.147850E+10 | 0.137041E+10 | 5262.08 | 5070.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.241095E+11 | 0.156390E+11 | 30934.44 | 22290.16 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.133394E+10 | 0.123791E+10 | 5102.21 | 12-JAN-15:10 | 4915.19 | 0.00 |
February | 0.00 | 0.00 | 0.369464E+10 | 0.333119E+10 | 8235.86 | 24-FEB-15:30 | 7023.58 | 0.00 |
March | 0.00 | 0.00 | 0.844836E+10 | 0.755102E+10 | 27978.48 | 11-MAR-09:01 | 22212.57 | 0.00 |
April | 0.00 | 0.00 | 0.129690E+11 | 0.118997E+11 | 28401.93 | 03-APR-08:61 | 21372.66 | 0.00 |
May | 0.00 | 0.00 | 0.190767E+11 | 0.156101E+11 | 30163.74 | 24-MAY-08:61 | 16219.87 | 0.00 |
June | 0.00 | 0.00 | 0.213767E+11 | 0.154774E+11 | 30783.04 | 25-JUN-09:01 | 14179.62 | 0.00 |
July | 0.00 | 0.00 | 0.237225E+11 | 0.142476E+11 | 30809.26 | 18-JUL-08:61 | 14378.26 | 0.00 |
August | 0.00 | 0.00 | 0.241530E+11 | 0.136448E+11 | 30916.76 | 21-AUG-08:61 | 12627.06 | 0.00 |
September | 0.00 | 0.00 | 0.195503E+11 | 0.120072E+11 | 30948.03 | 04-SEP-09:01 | 13295.35 | 0.00 |
October | 0.00 | 0.00 | 0.130683E+11 | 0.106963E+11 | 29515.63 | 12-OCT-08:62 | 17173.71 | 0.00 |
November | 0.00 | 0.00 | 0.742179E+10 | 0.665770E+10 | 27980.57 | 09-NOV-09:02 | 21245.52 | 0.00 |
December | 0.00 | 0.00 | 0.260187E+10 | 0.235618E+10 | 6355.83 | 28-DEC-14:00 | 5913.05 | 0.00 |
Annual Sum or Average | 0.157417E+12 | 0.114717E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.133394E+10 | 0.123791E+10 | 5102.21 | 4915.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.241530E+11 | 0.156101E+11 | 30948.03 | 22212.57 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.123812E+10 | 0.115621E+10 | 5082.48 | 12-JAN-15:10 | 4918.33 | 0.00 |
February | 0.00 | 0.00 | 0.356199E+10 | 0.322968E+10 | 8406.72 | 22-FEB-14:00 | 7908.84 | 0.00 |
March | 0.00 | 0.00 | 0.846700E+10 | 0.759047E+10 | 29828.50 | 30-MAR-08:62 | 22654.14 | 0.00 |
April | 0.00 | 0.00 | 0.135224E+11 | 0.124321E+11 | 30338.09 | 03-APR-08:61 | 22436.86 | 0.00 |
May | 0.00 | 0.00 | 0.201817E+11 | 0.165745E+11 | 32550.32 | 24-MAY-08:61 | 16112.21 | 0.00 |
June | 0.00 | 0.00 | 0.226757E+11 | 0.165413E+11 | 32986.49 | 24-JUN-08:61 | 14798.10 | 0.00 |
July | 0.00 | 0.00 | 0.254127E+11 | 0.154382E+11 | 32948.63 | 26-JUL-08:61 | 14666.85 | 0.00 |
August | 0.00 | 0.00 | 0.259265E+11 | 0.148967E+11 | 32943.70 | 21-AUG-08:61 | 13696.61 | 0.00 |
September | 0.00 | 0.00 | 0.209557E+11 | 0.130740E+11 | 33002.33 | 09-SEP-08:61 | 14406.75 | 0.00 |
October | 0.00 | 0.00 | 0.140039E+11 | 0.115480E+11 | 31703.07 | 12-OCT-08:62 | 17597.89 | 0.00 |
November | 0.00 | 0.00 | 0.778243E+10 | 0.701595E+10 | 29800.48 | 09-NOV-09:02 | 22777.15 | 0.00 |
December | 0.00 | 0.00 | 0.257686E+10 | 0.234779E+10 | 6532.20 | 28-DEC-14:00 | 6105.07 | 0.00 |
Annual Sum or Average | 0.166305E+12 | 0.121845E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.123812E+10 | 0.115621E+10 | 5082.48 | 4918.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.259265E+11 | 0.165745E+11 | 33002.33 | 22777.15 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.509099E+10 | 0.61 | 2805.88 | 01-JAN-09:02 | 0.90 |
February | 0.460613E+10 | 0.61 | 2805.88 | 15-FEB-16:30 | 0.89 |
March | 0.510109E+10 | 0.61 | 2805.88 | 09-MAR-20:17 | 0.89 |
April | 0.493947E+10 | 0.61 | 2805.88 | 01-APR-09:00 | 0.89 |
May | 0.509099E+10 | 0.60 | 2805.88 | 21-MAY-08:00 | 0.89 |
June | 0.493947E+10 | 0.60 | 2805.88 | 01-JUN-07:04 | 0.89 |
July | 0.510109E+10 | 0.60 | 2805.88 | 01-JUL-07:50 | 0.88 |
August | 0.509099E+10 | 0.60 | 2805.88 | 01-AUG-07:04 | 0.88 |
September | 0.494957E+10 | 0.60 | 2805.88 | 01-SEP-07:09 | 0.88 |
October | 0.509099E+10 | 0.60 | 2805.88 | 08-OCT-22:40 | 0.89 |
November | 0.491927E+10 | 0.60 | 2805.88 | 29-NOV-11:50 | 0.90 |
December | 0.511119E+10 | 0.61 | 2805.88 | 16-DEC-15:00 | 0.89 |
Annual Sum or Average | 0.600312E+11 | 0.60 | |||
Minimum of Months | 0.460613E+10 | 0.60 | 2805.88 | 0.88 | |
Maximum of Months | 0.511119E+10 | 0.61 | 2805.88 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.216294E+10 | 0.67 | 1521.80 | 02-JAN-18:50 | 0.92 |
February | 0.198014E+10 | 0.67 | 1521.80 | 01-FEB-12:00 | 0.93 |
March | 0.225288E+10 | 0.67 | 1521.80 | 01-MAR-10:10 | 0.93 |
April | 0.220954E+10 | 0.66 | 1521.80 | 01-APR-08:09 | 0.92 |
May | 0.234710E+10 | 0.66 | 1521.80 | 01-MAY-08:06 | 0.92 |
June | 0.231637E+10 | 0.65 | 1521.80 | 01-JUN-07:10 | 0.92 |
July | 0.239848E+10 | 0.65 | 1521.80 | 01-JUL-07:10 | 0.92 |
August | 0.240307E+10 | 0.65 | 1521.80 | 01-AUG-08:07 | 0.91 |
September | 0.228377E+10 | 0.66 | 1521.80 | 01-SEP-08:09 | 0.91 |
October | 0.227641E+10 | 0.66 | 1521.80 | 01-OCT-08:00 | 0.92 |
November | 0.215059E+10 | 0.67 | 1521.80 | 01-NOV-10:10 | 0.93 |
December | 0.216893E+10 | 0.68 | 1521.80 | 01-DEC-12:40 | 0.93 |
Annual Sum or Average | 0.269502E+11 | 0.66 | |||
Minimum of Months | 0.198014E+10 | 0.65 | 1521.80 | 0.91 | |
Maximum of Months | 0.240307E+10 | 0.68 | 1521.80 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.219099E+10 | 0.50 | 1513.95 | 02-JAN-08:30 | 0.93 |
February | 0.198388E+10 | 0.50 | 1513.95 | 01-FEB-11:50 | 0.93 |
March | 0.223459E+10 | 0.51 | 1513.95 | 01-MAR-12:20 | 0.93 |
April | 0.212559E+10 | 0.50 | 1513.95 | 01-APR-09:10 | 0.92 |
May | 0.221279E+10 | 0.50 | 1513.95 | 01-MAY-07:20 | 0.93 |
June | 0.215829E+10 | 0.51 | 1513.95 | 01-JUN-06:45 | 0.92 |
July | 0.218009E+10 | 0.49 | 1513.95 | 01-JUL-08:06 | 0.92 |
August | 0.223459E+10 | 0.50 | 1513.95 | 01-AUG-07:20 | 0.91 |
September | 0.212559E+10 | 0.50 | 1513.95 | 01-SEP-07:07 | 0.91 |
October | 0.219099E+10 | 0.50 | 1513.95 | 01-OCT-08:09 | 0.92 |
November | 0.212559E+10 | 0.50 | 1513.95 | 01-NOV-07:03 | 0.92 |
December | 0.218009E+10 | 0.50 | 1513.95 | 01-DEC-08:50 | 0.93 |
Annual Sum or Average | 0.259431E+11 | 0.50 | |||
Minimum of Months | 0.198388E+10 | 0.49 | 1513.95 | 0.91 | |
Maximum of Months | 0.223459E+10 | 0.51 | 1513.95 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.219580E+10 | 0.50 | 1517.27 | 04-JAN-13:00 | 0.93 |
February | 0.198824E+10 | 0.50 | 1517.27 | 01-FEB-11:20 | 0.93 |
March | 0.223950E+10 | 0.51 | 1517.27 | 01-MAR-09:50 | 0.93 |
April | 0.213025E+10 | 0.50 | 1517.27 | 01-APR-07:15 | 0.92 |
May | 0.221765E+10 | 0.50 | 1517.27 | 01-MAY-13:30 | 0.92 |
June | 0.216303E+10 | 0.51 | 1517.27 | 01-JUN-09:10 | 0.92 |
July | 0.218488E+10 | 0.49 | 1517.27 | 01-JUL-07:10 | 0.92 |
August | 0.223950E+10 | 0.50 | 1517.27 | 01-AUG-06:30 | 0.91 |
September | 0.213025E+10 | 0.50 | 1517.27 | 01-SEP-07:00 | 0.91 |
October | 0.219580E+10 | 0.50 | 1517.27 | 01-OCT-07:05 | 0.92 |
November | 0.213025E+10 | 0.50 | 1517.27 | 01-NOV-08:00 | 0.92 |
December | 0.218488E+10 | 0.50 | 1517.27 | 01-DEC-11:10 | 0.93 |
Annual Sum or Average | 0.260000E+11 | 0.50 | |||
Minimum of Months | 0.198824E+10 | 0.49 | 1517.27 | 0.91 | |
Maximum of Months | 0.223950E+10 | 0.51 | 1517.27 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.218994E+10 | 0.50 | 1513.23 | 04-JAN-16:00 | 0.93 |
February | 0.198293E+10 | 0.50 | 1513.23 | 02-FEB-16:30 | 0.93 |
March | 0.223352E+10 | 0.51 | 1513.23 | 01-MAR-19:30 | 0.93 |
April | 0.212457E+10 | 0.50 | 1513.23 | 01-APR-08:06 | 0.92 |
May | 0.221173E+10 | 0.50 | 1513.23 | 07-MAY-08:04 | 0.92 |
June | 0.215726E+10 | 0.51 | 1513.23 | 04-JUN-07:08 | 0.92 |
July | 0.217905E+10 | 0.49 | 1513.23 | 06-JUL-07:00 | 0.91 |
August | 0.223352E+10 | 0.50 | 1513.23 | 06-AUG-13:50 | 0.92 |
September | 0.212457E+10 | 0.50 | 1513.23 | 05-SEP-06:10 | 0.91 |
October | 0.218994E+10 | 0.50 | 1513.23 | 05-OCT-07:06 | 0.92 |
November | 0.212457E+10 | 0.50 | 1513.23 | 01-NOV-10:20 | 0.93 |
December | 0.217905E+10 | 0.50 | 1513.23 | 02-DEC-13:30 | 0.93 |
Annual Sum or Average | 0.259306E+11 | 0.50 | |||
Minimum of Months | 0.198293E+10 | 0.49 | 1513.23 | 0.91 | |
Maximum of Months | 0.223352E+10 | 0.51 | 1513.23 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.355491E+10 | 0.45 | 2661.66 | 06-JAN-12:00 | 0.90 |
February | 0.321954E+10 | 0.45 | 2661.66 | 04-FEB-15:40 | 0.90 |
March | 0.363156E+10 | 0.46 | 2661.66 | 02-MAR-15:40 | 0.90 |
April | 0.344951E+10 | 0.45 | 2661.66 | 10-APR-10:40 | 0.90 |
May | 0.359323E+10 | 0.45 | 2661.66 | 02-MAY-13:00 | 0.89 |
June | 0.350700E+10 | 0.45 | 2661.66 | 01-JUN-08:50 | 0.89 |
July | 0.353574E+10 | 0.44 | 2661.66 | 15-JUL-07:13 | 0.88 |
August | 0.363156E+10 | 0.45 | 2661.66 | 09-AUG-07:20 | 0.88 |
September | 0.344951E+10 | 0.44 | 2661.66 | 14-SEP-12:30 | 0.88 |
October | 0.355491E+10 | 0.44 | 2661.66 | 11-OCT-08:09 | 0.89 |
November | 0.344951E+10 | 0.45 | 2661.66 | 01-NOV-09:40 | 0.89 |
December | 0.353574E+10 | 0.44 | 2661.66 | 04-DEC-20:20 | 0.89 |
Annual Sum or Average | 0.421127E+11 | 0.45 | |||
Minimum of Months | 0.321954E+10 | 0.44 | 2661.66 | 0.88 | |
Maximum of Months | 0.363156E+10 | 0.46 | 2661.66 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.194916E+10 | 0.46 | 1459.39 | 03-JAN-09:07 | 0.93 |
February | 0.176528E+10 | 0.46 | 1459.39 | 01-FEB-14:40 | 0.93 |
March | 0.199119E+10 | 0.47 | 1459.39 | 01-MAR-13:00 | 0.93 |
April | 0.189137E+10 | 0.46 | 1459.39 | 01-APR-08:03 | 0.92 |
May | 0.197017E+10 | 0.46 | 1459.39 | 01-MAY-09:00 | 0.92 |
June | 0.192289E+10 | 0.47 | 1459.39 | 01-JUN-12:50 | 0.92 |
July | 0.193865E+10 | 0.45 | 1459.39 | 01-JUL-08:06 | 0.91 |
August | 0.199119E+10 | 0.47 | 1459.39 | 01-AUG-08:17 | 0.91 |
September | 0.189137E+10 | 0.46 | 1459.39 | 01-SEP-07:50 | 0.91 |
October | 0.194916E+10 | 0.46 | 1459.39 | 01-OCT-09:40 | 0.92 |
November | 0.189137E+10 | 0.46 | 1459.39 | 01-NOV-09:30 | 0.93 |
December | 0.193865E+10 | 0.46 | 1459.39 | 01-DEC-11:20 | 0.93 |
Annual Sum or Average | 0.230904E+11 | 0.46 | |||
Minimum of Months | 0.176528E+10 | 0.45 | 1459.39 | 0.91 | |
Maximum of Months | 0.199119E+10 | 0.47 | 1459.39 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.194076E+10 | 0.46 | 1453.10 | 01-JAN-10:40 | 0.93 |
February | 0.175767E+10 | 0.46 | 1453.10 | 01-FEB-12:00 | 0.93 |
March | 0.198261E+10 | 0.47 | 1453.10 | 01-MAR-10:10 | 0.93 |
April | 0.188322E+10 | 0.46 | 1453.10 | 01-APR-08:30 | 0.92 |
May | 0.196169E+10 | 0.46 | 1453.10 | 01-MAY-07:04 | 0.93 |
June | 0.191461E+10 | 0.47 | 1453.10 | 01-JUN-07:04 | 0.92 |
July | 0.193030E+10 | 0.45 | 1453.10 | 01-JUL-07:01 | 0.92 |
August | 0.198261E+10 | 0.47 | 1453.10 | 01-AUG-07:06 | 0.91 |
September | 0.188322E+10 | 0.46 | 1453.10 | 01-SEP-08:07 | 0.91 |
October | 0.194076E+10 | 0.46 | 1453.10 | 01-OCT-08:08 | 0.92 |
November | 0.188322E+10 | 0.46 | 1453.10 | 01-NOV-08:20 | 0.92 |
December | 0.193030E+10 | 0.46 | 1453.10 | 01-DEC-10:20 | 0.93 |
Annual Sum or Average | 0.229910E+11 | 0.46 | |||
Minimum of Months | 0.175767E+10 | 0.45 | 1453.10 | 0.91 | |
Maximum of Months | 0.198261E+10 | 0.47 | 1453.10 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.194173E+10 | 0.46 | 1453.83 | 01-JAN-11:30 | 0.93 |
February | 0.175855E+10 | 0.46 | 1453.83 | 01-FEB-11:40 | 0.93 |
March | 0.198360E+10 | 0.47 | 1453.83 | 01-MAR-20:25 | 0.93 |
April | 0.188416E+10 | 0.46 | 1453.83 | 02-APR-09:06 | 0.92 |
May | 0.196267E+10 | 0.46 | 1453.83 | 05-MAY-07:40 | 0.92 |
June | 0.191556E+10 | 0.47 | 1453.83 | 01-JUN-07:15 | 0.92 |
July | 0.193126E+10 | 0.45 | 1453.83 | 01-JUL-11:30 | 0.92 |
August | 0.198360E+10 | 0.47 | 1453.83 | 01-AUG-07:40 | 0.91 |
September | 0.188416E+10 | 0.46 | 1453.83 | 01-SEP-07:04 | 0.91 |
October | 0.194173E+10 | 0.46 | 1453.83 | 01-OCT-08:08 | 0.92 |
November | 0.188416E+10 | 0.46 | 1453.83 | 23-NOV-13:30 | 0.93 |
December | 0.193126E+10 | 0.46 | 1453.83 | 25-DEC-14:40 | 0.93 |
Annual Sum or Average | 0.230025E+11 | 0.46 | |||
Minimum of Months | 0.175855E+10 | 0.45 | 1453.83 | 0.91 | |
Maximum of Months | 0.198360E+10 | 0.47 | 1453.83 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.202625E+10 | 0.45 | 1517.11 | 23-JAN-14:00 | 0.90 |
February | 0.183509E+10 | 0.45 | 1517.11 | 06-FEB-13:30 | 0.90 |
March | 0.206994E+10 | 0.46 | 1517.11 | 01-MAR-12:10 | 0.90 |
April | 0.196617E+10 | 0.45 | 1517.11 | 01-APR-08:03 | 0.89 |
May | 0.204810E+10 | 0.45 | 1517.11 | 01-MAY-07:06 | 0.89 |
June | 0.199894E+10 | 0.45 | 1517.11 | 01-JUN-07:20 | 0.89 |
July | 0.201533E+10 | 0.44 | 1517.11 | 01-JUL-07:06 | 0.88 |
August | 0.206994E+10 | 0.45 | 1517.11 | 01-AUG-07:13 | 0.88 |
September | 0.196617E+10 | 0.44 | 1517.11 | 01-SEP-07:04 | 0.88 |
October | 0.202625E+10 | 0.44 | 1517.11 | 01-OCT-08:10 | 0.89 |
November | 0.196617E+10 | 0.45 | 1517.11 | 01-NOV-08:20 | 0.89 |
December | 0.201533E+10 | 0.44 | 1517.11 | 01-DEC-13:10 | 0.90 |
Annual Sum or Average | 0.240037E+11 | 0.45 | |||
Minimum of Months | 0.183509E+10 | 0.44 | 1517.11 | 0.88 | |
Maximum of Months | 0.206994E+10 | 0.46 | 1517.11 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 1.50 |
February | 0.00 | 0.00 |
March | 0.14 | 0.00 |
April | 0.44 | 0.00 |
May | 0.83 | 0.00 |
June | 1.75 | 0.00 |
July | 1.75 | 0.00 |
August | 2.25 | 0.00 |
September | 1.33 | 0.00 |
October | 1.00 | 0.25 |
November | 0.00 | 0.00 |
December | 0.17 | 1.50 |
Annual Sum or Average | 9.83 | 0.08 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.25 | 1.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 0.75 |
February | 0.00 | 0.00 |
March | 0.14 | 0.00 |
April | 0.69 | 0.00 |
May | 0.00 | 0.00 |
June | 1.00 | 0.00 |
July | 0.75 | 0.00 |
August | 0.75 | 0.00 |
September | 0.00 | 0.00 |
October | 0.83 | 0.00 |
November | 0.00 | 0.00 |
December | 0.22 | 0.75 |
Annual Sum or Average | 4.56 | 0.06 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.00 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.60 | 0.75 |
March | 3.55 | 0.75 |
April | 5.52 | 0.71 |
May | 5.34 | 0.68 |
June | 5.52 | 0.67 |
July | 5.99 | 0.66 |
August | 6.28 | 0.67 |
September | 5.74 | 0.71 |
October | 4.71 | 0.74 |
November | 1.73 | 0.75 |
December | 0.08 | 0.00 |
Annual Sum or Average | 45.06 | 0.70 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 6.28 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.75 |
February | 0.60 | 0.75 |
March | 3.55 | 0.75 |
April | 5.52 | 0.71 |
May | 5.34 | 0.68 |
June | 5.52 | 0.67 |
July | 5.99 | 0.66 |
August | 6.11 | 0.69 |
September | 5.57 | 0.73 |
October | 4.71 | 0.74 |
November | 1.73 | 0.75 |
December | 0.08 | 0.00 |
Annual Sum or Average | 44.81 | 0.70 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 6.11 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.75 |
February | 0.46 | 0.75 |
March | 3.47 | 0.75 |
April | 5.52 | 0.71 |
May | 5.34 | 0.68 |
June | 5.58 | 0.67 |
July | 5.99 | 0.66 |
August | 6.11 | 0.69 |
September | 5.66 | 0.72 |
October | 4.71 | 0.74 |
November | 1.53 | 0.75 |
December | 0.00 | 0.00 |
Annual Sum or Average | 44.45 | 0.70 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 6.11 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 1.65 |
February | 0.12 | 3.30 |
March | 1.47 | 2.67 |
April | 2.52 | 1.95 |
May | 2.29 | 1.29 |
June | 1.64 | 1.70 |
July | 2.52 | 2.04 |
August | 2.06 | 2.03 |
September | 2.65 | 2.09 |
October | 2.16 | 2.83 |
November | 0.51 | 3.30 |
December | 0.08 | 0.00 |
Annual Sum or Average | 18.17 | 2.09 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 2.65 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 0.82 |
February | 0.12 | 1.65 |
March | 1.47 | 1.34 |
April | 2.14 | 1.05 |
May | 1.45 | 1.02 |
June | 1.36 | 1.13 |
July | 2.10 | 1.22 |
August | 1.72 | 1.21 |
September | 2.24 | 1.36 |
October | 1.83 | 1.60 |
November | 0.51 | 1.65 |
December | 0.00 | 0.00 |
Annual Sum or Average | 15.10 | 1.26 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.24 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 0.82 |
February | 0.12 | 1.65 |
March | 1.38 | 1.42 |
April | 2.10 | 1.10 |
May | 1.45 | 1.02 |
June | 1.36 | 1.13 |
July | 2.10 | 1.22 |
August | 1.72 | 1.21 |
September | 2.24 | 1.36 |
October | 1.83 | 1.60 |
November | 0.51 | 1.65 |
December | 0.00 | 0.00 |
Annual Sum or Average | 14.98 | 1.27 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.24 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 0.82 |
February | 0.12 | 1.65 |
March | 1.30 | 1.51 |
April | 2.02 | 1.15 |
May | 1.45 | 1.02 |
June | 1.36 | 1.13 |
July | 2.10 | 1.22 |
August | 1.72 | 1.21 |
September | 2.15 | 1.42 |
October | 1.83 | 1.60 |
November | 0.42 | 1.65 |
December | 0.00 | 0.00 |
Annual Sum or Average | 14.65 | 1.29 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.15 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.25 | 1.65 |
February | 0.12 | 1.65 |
March | 1.30 | 1.40 |
April | 1.98 | 1.07 |
May | 1.54 | 0.87 |
June | 1.39 | 1.00 |
July | 2.02 | 1.13 |
August | 1.64 | 1.19 |
September | 2.32 | 1.20 |
October | 1.91 | 1.53 |
November | 0.51 | 1.65 |
December | 0.00 | 0.00 |
Annual Sum or Average | 14.96 | 1.21 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.32 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.680718E+10 | 4062261.68 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.789255E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.118320E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.157875E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.205557E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.216213E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.225575E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.217875E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.192547E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.151785E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.107494E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.766174E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.181685E+12 | 4062261.68 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.680718E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.225575E+11 | 4062261.68 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.336656E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.388119E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.574835E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.756950E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.988128E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.103633E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.107687E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.104227E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.914093E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.724994E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.521235E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.377944E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.873842E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.336656E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.107687E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.285327E+10 | 12898737.90 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.329058E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.495666E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.643124E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.843313E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.877925E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.890037E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.884243E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.765138E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.616187E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.446900E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.319145E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.739606E+11 | 12898737.90 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.285327E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.890037E+10 | 12898737.90 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.282035E+10 | 27546878.81 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.327454E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.495875E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.645457E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.847654E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.882198E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.894665E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.887931E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.768336E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.618414E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.446678E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.316928E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.741363E+11 | 27546878.81 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.282035E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.894665E+10 | 27546878.81 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.275654E+10 | 43543884.32 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.321816E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.490116E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.640603E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.843126E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.877696E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.890692E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.883383E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.763792E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.613887E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.441576E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.310969E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.735331E+11 | 43543884.32 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.275654E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.890692E+10 | 43543884.32 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.439551E+10 | 89333054.06 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.534650E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.847816E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.113300E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.151398E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.158175E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.159256E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.158621E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.135768E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.108127E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.756771E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.504329E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.129296E+12 | 89333054.06 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.439551E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.159256E+11 | 89333054.06 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.237546E+10 | 47051527.67 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.285582E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.447853E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.593675E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.789684E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.823462E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.829215E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.825882E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.708608E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.567423E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.400636E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.271257E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.678082E+11 | 47051527.67 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.237546E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.829215E+10 | 47051527.67 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.234776E+10 | 51573339.31 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.282639E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.444488E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.590364E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.786062E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.819879E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.825786E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.822497E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.705490E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.564485E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.397836E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.268470E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.674277E+11 | 51573339.31 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.234776E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.825786E+10 | 51573339.31 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.230942E+10 | 62544361.60 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.277983E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.440001E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.587975E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.785298E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.819916E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.826750E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.823612E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.706029E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.563936E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.395435E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.264634E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.672251E+11 | 62544361.60 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.230942E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.826750E+10 | 62544361.60 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.236828E+10 | 88292962.35 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.282402E+10 | 1114094.60 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.450571E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.614766E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.829961E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.868974E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.882101E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.880100E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.752892E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.599004E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.413998E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.272474E+10 | 2793282.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.708407E+11 | 92200339.25 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.236828E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.882101E+10 | 88292962.35 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.509099E+10 | 0.616252E+10 | 3249809.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.460613E+10 | 0.118222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.510109E+10 | 0.234596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.493947E+10 | 0.349577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.509099E+10 | 0.494419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.493947E+10 | 0.556303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.510109E+10 | 0.634735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.509099E+10 | 0.628871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.494957E+10 | 0.528914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.509099E+10 | 0.354019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.491927E+10 | 0.208208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.511119E+10 | 0.919676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.600312E+11 | 0.426146E+12 | 3249809.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.460613E+10 | 0.616252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511119E+10 | 0.634735E+11 | 3249809.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.216294E+10 | 0.432007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198014E+10 | 0.687875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225288E+10 | 0.122654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.220954E+10 | 0.173071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.234710E+10 | 0.240640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.231637E+10 | 0.267737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.239848E+10 | 0.303022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.240307E+10 | 0.301168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.228377E+10 | 0.252575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.227641E+10 | 0.174694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215059E+10 | 0.110012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216893E+10 | 0.582166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269502E+11 | 0.211578E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.198014E+10 | 0.432007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.240307E+10 | 0.303022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.219099E+10 | 0.242277E+10 | 10318990.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198388E+10 | 0.477640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.223459E+10 | 0.960422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212559E+10 | 0.140914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.221279E+10 | 0.202204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.215829E+10 | 0.226036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.218009E+10 | 0.251218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.223459E+10 | 0.254830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212559E+10 | 0.208829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.219099E+10 | 0.140911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.212559E+10 | 0.845956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218009E+10 | 0.371458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259431E+11 | 0.171472E+12 | 10318990.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.198388E+10 | 0.242277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.223459E+10 | 0.254830E+11 | 10318990.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.219580E+10 | 0.228220E+10 | 22037503.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198824E+10 | 0.469748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.223950E+10 | 0.959137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.213025E+10 | 0.141572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.221765E+10 | 0.203575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.216303E+10 | 0.227423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.218488E+10 | 0.252863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.223950E+10 | 0.256099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.213025E+10 | 0.209901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.219580E+10 | 0.141566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213025E+10 | 0.843104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218488E+10 | 0.361182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260000E+11 | 0.171914E+12 | 22037503.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.198824E+10 | 0.228220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.223950E+10 | 0.256099E+11 | 22037503.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.218994E+10 | 0.206706E+10 | 34835107.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198293E+10 | 0.450260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.223352E+10 | 0.939302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212457E+10 | 0.140017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.221173E+10 | 0.202188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.215726E+10 | 0.225994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.217905E+10 | 0.251551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.223352E+10 | 0.254523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212457E+10 | 0.208322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.218994E+10 | 0.140032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.212457E+10 | 0.825467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.217905E+10 | 0.340873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259306E+11 | 0.169889E+12 | 34835107.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.198293E+10 | 0.206706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.223352E+10 | 0.254523E+11 | 34835107.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.355491E+10 | 0.300324E+10 | 71466443.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.321954E+10 | 0.758491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.363156E+10 | 0.167016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.344951E+10 | 0.251878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.359323E+10 | 0.368122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.350700E+10 | 0.412291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.353574E+10 | 0.456444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.363156E+10 | 0.464839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.344951E+10 | 0.376254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.355491E+10 | 0.252401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.344951E+10 | 0.145358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.353574E+10 | 0.540279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421127E+11 | 0.305451E+12 | 71466443.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.321954E+10 | 0.300324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.363156E+10 | 0.464839E+11 | 71466443.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.194916E+10 | 0.154944E+10 | 37641222.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176528E+10 | 0.395641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199119E+10 | 0.871812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189137E+10 | 0.131468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197017E+10 | 0.192012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.192289E+10 | 0.214726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193865E+10 | 0.237783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.199119E+10 | 0.241999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189137E+10 | 0.196152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194916E+10 | 0.131718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189137E+10 | 0.759413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193865E+10 | 0.282166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230904E+11 | 0.159225E+12 | 37641222.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176528E+10 | 0.154944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.199119E+10 | 0.241999E+11 | 37641222.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.194076E+10 | 0.147850E+10 | 41258671.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175767E+10 | 0.387429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198261E+10 | 0.862496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188322E+10 | 0.130622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196169E+10 | 0.191117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.191461E+10 | 0.213821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193030E+10 | 0.236879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198261E+10 | 0.241095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.188322E+10 | 0.195323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194076E+10 | 0.130950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188322E+10 | 0.751919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193030E+10 | 0.274888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229910E+11 | 0.158227E+12 | 41258671.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.175767E+10 | 0.147850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.198261E+10 | 0.241095E+11 | 41258671.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.194173E+10 | 0.133394E+10 | 50035489.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175855E+10 | 0.369464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198360E+10 | 0.844836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188416E+10 | 0.129690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196267E+10 | 0.190767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.191556E+10 | 0.213767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193126E+10 | 0.237225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198360E+10 | 0.241530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.188416E+10 | 0.195503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194173E+10 | 0.130683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188416E+10 | 0.742179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193126E+10 | 0.260187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230025E+11 | 0.157417E+12 | 50035489.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.175855E+10 | 0.133394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.198360E+10 | 0.241530E+11 | 50035489.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.202625E+10 | 0.123812E+10 | 70634369.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183509E+10 | 0.356199E+10 | 891275.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206994E+10 | 0.846700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196617E+10 | 0.135224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.204810E+10 | 0.201817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.199894E+10 | 0.226757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.201533E+10 | 0.254127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.206994E+10 | 0.259265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196617E+10 | 0.209557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202625E+10 | 0.140039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.196617E+10 | 0.778243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201533E+10 | 0.257686E+10 | 2234625.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240037E+11 | 0.166305E+12 | 73760271.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.183509E+10 | 0.123812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.206994E+10 | 0.259265E+11 | 70634369.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.509099E+10 | 0.00 | 0.00 | 0.00 | 0.171619E+10 | 0.00 | 4062261.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.460613E+10 | 0.00 | 0.00 | 0.00 | 0.328643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.510109E+10 | 0.00 | 0.00 | 0.00 | 0.673093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.493947E+10 | 0.00 | 0.00 | 0.00 | 0.108480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.509099E+10 | 0.00 | 0.00 | 0.00 | 0.154647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.493947E+10 | 0.00 | 0.00 | 0.00 | 0.166818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.510109E+10 | 0.00 | 0.00 | 0.00 | 0.174564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.509099E+10 | 0.00 | 0.00 | 0.00 | 0.166965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.494957E+10 | 0.00 | 0.00 | 0.00 | 0.143052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.509099E+10 | 0.00 | 0.00 | 0.00 | 0.100875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.491927E+10 | 0.00 | 0.00 | 0.00 | 0.583012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.511119E+10 | 0.00 | 0.00 | 0.00 | 0.255055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.600312E+11 | 0.00 | 0.00 | 0.00 | 0.121654E+12 | 0.00 | 4062261.68 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.460613E+10 | 0.00 | 0.00 | 0.00 | 0.171619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511119E+10 | 0.00 | 0.00 | 0.00 | 0.174564E+11 | 0.00 | 4062261.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.216294E+10 | 0.00 | 0.00 | 0.00 | 0.120362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198014E+10 | 0.00 | 0.00 | 0.00 | 0.190104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225288E+10 | 0.00 | 0.00 | 0.00 | 0.349547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.220954E+10 | 0.00 | 0.00 | 0.00 | 0.535997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.234710E+10 | 0.00 | 0.00 | 0.00 | 0.753418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.231637E+10 | 0.00 | 0.00 | 0.00 | 0.804689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.239848E+10 | 0.00 | 0.00 | 0.00 | 0.837019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.240307E+10 | 0.00 | 0.00 | 0.00 | 0.801962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.228377E+10 | 0.00 | 0.00 | 0.00 | 0.685716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.227641E+10 | 0.00 | 0.00 | 0.00 | 0.497354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215059E+10 | 0.00 | 0.00 | 0.00 | 0.306176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216893E+10 | 0.00 | 0.00 | 0.00 | 0.161051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269502E+11 | 0.00 | 0.00 | 0.00 | 0.604339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.198014E+10 | 0.00 | 0.00 | 0.00 | 0.120362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.240307E+10 | 0.00 | 0.00 | 0.00 | 0.837019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.219099E+10 | 0.00 | 0.00 | 0.00 | 0.662279E+09 | 0.00 | 12898737.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198388E+10 | 0.00 | 0.00 | 0.00 | 0.130669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.223459E+10 | 0.00 | 0.00 | 0.00 | 0.272207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212559E+10 | 0.00 | 0.00 | 0.00 | 0.430566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.221279E+10 | 0.00 | 0.00 | 0.00 | 0.622033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.215829E+10 | 0.00 | 0.00 | 0.00 | 0.662096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.218009E+10 | 0.00 | 0.00 | 0.00 | 0.672028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.223459E+10 | 0.00 | 0.00 | 0.00 | 0.660784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212559E+10 | 0.00 | 0.00 | 0.00 | 0.552580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.219099E+10 | 0.00 | 0.00 | 0.00 | 0.397088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.212559E+10 | 0.00 | 0.00 | 0.00 | 0.234341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218009E+10 | 0.00 | 0.00 | 0.00 | 0.101136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259431E+11 | 0.00 | 0.00 | 0.00 | 0.480176E+11 | 0.00 | 12898737.90 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.198388E+10 | 0.00 | 0.00 | 0.00 | 0.662279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.223459E+10 | 0.00 | 0.00 | 0.00 | 0.672028E+10 | 0.00 | 12898737.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.219580E+10 | 0.00 | 0.00 | 0.00 | 0.624546E+09 | 0.00 | 27546878.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198824E+10 | 0.00 | 0.00 | 0.00 | 0.128631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.223950E+10 | 0.00 | 0.00 | 0.00 | 0.271926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.213025E+10 | 0.00 | 0.00 | 0.00 | 0.432432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.221765E+10 | 0.00 | 0.00 | 0.00 | 0.625889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.216303E+10 | 0.00 | 0.00 | 0.00 | 0.665895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.218488E+10 | 0.00 | 0.00 | 0.00 | 0.676177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.223950E+10 | 0.00 | 0.00 | 0.00 | 0.663981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.213025E+10 | 0.00 | 0.00 | 0.00 | 0.555310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.219580E+10 | 0.00 | 0.00 | 0.00 | 0.398834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213025E+10 | 0.00 | 0.00 | 0.00 | 0.233653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218488E+10 | 0.00 | 0.00 | 0.00 | 0.984406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260000E+11 | 0.00 | 0.00 | 0.00 | 0.481362E+11 | 0.00 | 27546878.81 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.198824E+10 | 0.00 | 0.00 | 0.00 | 0.624546E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.223950E+10 | 0.00 | 0.00 | 0.00 | 0.676177E+10 | 0.00 | 27546878.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.218994E+10 | 0.00 | 0.00 | 0.00 | 0.566596E+09 | 0.00 | 43543884.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198293E+10 | 0.00 | 0.00 | 0.00 | 0.123523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.223352E+10 | 0.00 | 0.00 | 0.00 | 0.266764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212457E+10 | 0.00 | 0.00 | 0.00 | 0.428146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.221173E+10 | 0.00 | 0.00 | 0.00 | 0.621953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.215726E+10 | 0.00 | 0.00 | 0.00 | 0.661971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.217905E+10 | 0.00 | 0.00 | 0.00 | 0.672787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.223352E+10 | 0.00 | 0.00 | 0.00 | 0.660030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212457E+10 | 0.00 | 0.00 | 0.00 | 0.551335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.218994E+10 | 0.00 | 0.00 | 0.00 | 0.394893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.212457E+10 | 0.00 | 0.00 | 0.00 | 0.229119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.217905E+10 | 0.00 | 0.00 | 0.00 | 0.930647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259306E+11 | 0.00 | 0.00 | 0.00 | 0.476024E+11 | 0.00 | 43543884.32 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.198293E+10 | 0.00 | 0.00 | 0.00 | 0.566596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.223352E+10 | 0.00 | 0.00 | 0.00 | 0.672787E+10 | 0.00 | 43543884.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.355491E+10 | 0.00 | 0.00 | 0.00 | 0.840607E+09 | 0.00 | 89333054.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.321954E+10 | 0.00 | 0.00 | 0.00 | 0.212696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.363156E+10 | 0.00 | 0.00 | 0.00 | 0.484660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.344951E+10 | 0.00 | 0.00 | 0.00 | 0.788054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.359323E+10 | 0.00 | 0.00 | 0.00 | 0.115466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.350700E+10 | 0.00 | 0.00 | 0.00 | 0.123105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.353574E+10 | 0.00 | 0.00 | 0.00 | 0.123899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.363156E+10 | 0.00 | 0.00 | 0.00 | 0.122305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.344951E+10 | 0.00 | 0.00 | 0.00 | 0.101273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.355491E+10 | 0.00 | 0.00 | 0.00 | 0.725784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.344951E+10 | 0.00 | 0.00 | 0.00 | 0.411820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.353574E+10 | 0.00 | 0.00 | 0.00 | 0.150755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421127E+11 | 0.00 | 0.00 | 0.00 | 0.871830E+11 | 0.00 | 89333054.06 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.321954E+10 | 0.00 | 0.00 | 0.00 | 0.840607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.363156E+10 | 0.00 | 0.00 | 0.00 | 0.123899E+11 | 0.00 | 89333054.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.194916E+10 | 0.00 | 0.00 | 0.00 | 0.426298E+09 | 0.00 | 47051527.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176528E+10 | 0.00 | 0.00 | 0.00 | 0.109055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199119E+10 | 0.00 | 0.00 | 0.00 | 0.248734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189137E+10 | 0.00 | 0.00 | 0.00 | 0.404538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197017E+10 | 0.00 | 0.00 | 0.00 | 0.592666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.192289E+10 | 0.00 | 0.00 | 0.00 | 0.631173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.635349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.199119E+10 | 0.00 | 0.00 | 0.00 | 0.626764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189137E+10 | 0.00 | 0.00 | 0.00 | 0.519471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194916E+10 | 0.00 | 0.00 | 0.00 | 0.372507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189137E+10 | 0.00 | 0.00 | 0.00 | 0.211499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193865E+10 | 0.00 | 0.00 | 0.00 | 0.773916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230904E+11 | 0.00 | 0.00 | 0.00 | 0.447178E+11 | 0.00 | 47051527.67 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.176528E+10 | 0.00 | 0.00 | 0.00 | 0.426298E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.199119E+10 | 0.00 | 0.00 | 0.00 | 0.635349E+10 | 0.00 | 47051527.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.194076E+10 | 0.00 | 0.00 | 0.00 | 0.406996E+09 | 0.00 | 51573339.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175767E+10 | 0.00 | 0.00 | 0.00 | 0.106872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198261E+10 | 0.00 | 0.00 | 0.00 | 0.246226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188322E+10 | 0.00 | 0.00 | 0.00 | 0.402042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196169E+10 | 0.00 | 0.00 | 0.00 | 0.589894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.191461E+10 | 0.00 | 0.00 | 0.00 | 0.628418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193030E+10 | 0.00 | 0.00 | 0.00 | 0.632757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198261E+10 | 0.00 | 0.00 | 0.00 | 0.624236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.188322E+10 | 0.00 | 0.00 | 0.00 | 0.517168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194076E+10 | 0.00 | 0.00 | 0.00 | 0.370409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188322E+10 | 0.00 | 0.00 | 0.00 | 0.209514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193030E+10 | 0.00 | 0.00 | 0.00 | 0.754401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229910E+11 | 0.00 | 0.00 | 0.00 | 0.444368E+11 | 0.00 | 51573339.31 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.175767E+10 | 0.00 | 0.00 | 0.00 | 0.406996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.198261E+10 | 0.00 | 0.00 | 0.00 | 0.632757E+10 | 0.00 | 51573339.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.194173E+10 | 0.00 | 0.00 | 0.00 | 0.367691E+09 | 0.00 | 62544361.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175855E+10 | 0.00 | 0.00 | 0.00 | 0.102128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198360E+10 | 0.00 | 0.00 | 0.00 | 0.241641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188416E+10 | 0.00 | 0.00 | 0.00 | 0.399559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196267E+10 | 0.00 | 0.00 | 0.00 | 0.589031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.191556E+10 | 0.00 | 0.00 | 0.00 | 0.628359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193126E+10 | 0.00 | 0.00 | 0.00 | 0.633624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198360E+10 | 0.00 | 0.00 | 0.00 | 0.625252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.188416E+10 | 0.00 | 0.00 | 0.00 | 0.517613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194173E+10 | 0.00 | 0.00 | 0.00 | 0.369763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188416E+10 | 0.00 | 0.00 | 0.00 | 0.207019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193126E+10 | 0.00 | 0.00 | 0.00 | 0.715074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230025E+11 | 0.00 | 0.00 | 0.00 | 0.442227E+11 | 0.00 | 62544361.60 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.175855E+10 | 0.00 | 0.00 | 0.00 | 0.367691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.198360E+10 | 0.00 | 0.00 | 0.00 | 0.633624E+10 | 0.00 | 62544361.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.202625E+10 | 0.00 | 0.00 | 0.00 | 0.342027E+09 | 0.00 | 88292962.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183509E+10 | 0.00 | 0.00 | 0.00 | 0.988930E+09 | 0.00 | 1114094.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206994E+10 | 0.00 | 0.00 | 0.00 | 0.243577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196617E+10 | 0.00 | 0.00 | 0.00 | 0.418148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.204810E+10 | 0.00 | 0.00 | 0.00 | 0.625151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.199894E+10 | 0.00 | 0.00 | 0.00 | 0.669080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.201533E+10 | 0.00 | 0.00 | 0.00 | 0.680568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.206994E+10 | 0.00 | 0.00 | 0.00 | 0.673106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196617E+10 | 0.00 | 0.00 | 0.00 | 0.556275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202625E+10 | 0.00 | 0.00 | 0.00 | 0.396379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.196617E+10 | 0.00 | 0.00 | 0.00 | 0.217380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201533E+10 | 0.00 | 0.00 | 0.00 | 0.709415E+09 | 0.00 | 2793282.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240037E+11 | 0.00 | 0.00 | 0.00 | 0.468370E+11 | 0.00 | 92200339.25 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.183509E+10 | 0.00 | 0.00 | 0.00 | 0.342027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.206994E+10 | 0.00 | 0.00 | 0.00 | 0.680568E+10 | 0.00 | 88292962.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199734E+10 | 221065.09 | 0.00 | 11452401.61 | 0.00 | 1801109.26 | 0.555727E+10 | 0.00 | 0.57 |
February | 0.839532E+09 | 0.214208E+09 | 0.00 | 11841927.85 | 0.00 | 0.00 | 0.267460E+10 | 0.00 | 0.57 |
March | 0.238705E+09 | 0.283692E+10 | 0.00 | 6372798.93 | 5713599.58 | 0.00 | 0.600207E+09 | 0.00 | 0.57 |
April | 17820986.34 | 0.819682E+10 | 0.00 | 611725.04 | 0.171809E+09 | 0.00 | 15594686.44 | 0.00 | 0.58 |
May | 257264.98 | 0.160465E+11 | 0.00 | 29739.70 | 0.117602E+09 | 0.00 | 323242.87 | 0.00 | 0.58 |
June | 0.00 | 0.206375E+11 | 0.00 | 0.00 | 0.126347E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.253002E+11 | 0.00 | 0.00 | 92028421.87 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.252304E+11 | 0.00 | 0.00 | 0.155223E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.194210E+11 | 0.00 | 0.00 | 0.256702E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 89930911.83 | 0.748757E+10 | 0.00 | 1284795.21 | 0.116997E+09 | 0.00 | 28702651.97 | 0.00 | 0.57 |
November | 0.344261E+09 | 0.146079E+10 | 0.00 | 10318031.61 | 17194.31 | 0.00 | 0.145953E+10 | 0.00 | 0.57 |
December | 0.126961E+10 | 10780023.64 | 0.00 | 14772119.08 | 0.00 | 0.00 | 0.519543E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.479746E+10 | 0.126843E+12 | 0.00 | 56683539.04 | 0.104244E+10 | 1801109.26 | 0.155317E+11 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 221065.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.199734E+10 | 0.253002E+11 | 0.00 | 14772119.08 | 0.256702E+09 | 1801109.26 | 0.555727E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.764601E+09 | 97804.03 | 0.00 | 6763465.70 | 0.00 | 0.00 | 0.180326E+10 | 0.00 | 0.44 |
February | 0.309879E+09 | 0.110798E+09 | 0.00 | 6761871.51 | 0.00 | 0.00 | 0.792208E+09 | 0.00 | 0.45 |
March | 94245447.59 | 0.127315E+10 | 0.00 | 3443131.78 | 8965536.90 | 0.00 | 0.164250E+09 | 0.00 | 0.46 |
April | 9160568.18 | 0.343013E+10 | 0.00 | 390577.09 | 90499061.57 | 0.00 | 5270115.56 | 0.00 | 0.47 |
May | 16177.23 | 0.684096E+10 | 0.00 | 10298.08 | 62779235.28 | 0.00 | 54163.99 | 0.00 | 0.48 |
June | 0.00 | 0.880696E+10 | 0.00 | 0.00 | 68733876.74 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.107950E+11 | 0.00 | 0.00 | 59716714.90 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.00 | 0.108650E+11 | 0.00 | 0.00 | 0.119809E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.813086E+10 | 0.00 | 0.00 | 0.215492E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 22984686.30 | 0.321815E+10 | 0.00 | 308146.93 | 97065379.73 | 0.00 | 2526535.42 | 0.00 | 0.46 |
November | 0.130824E+09 | 0.724747E+09 | 0.00 | 5152124.72 | 855686.78 | 0.00 | 0.328007E+09 | 0.00 | 0.45 |
December | 0.506329E+09 | 5618576.67 | 0.00 | 8239769.93 | 0.00 | 0.00 | 0.156770E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.183804E+10 | 0.542015E+11 | 0.00 | 31069385.73 | 0.723917E+09 | 0.00 | 0.466328E+10 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 97804.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.764601E+09 | 0.108650E+11 | 0.00 | 8239769.93 | 0.215492E+09 | 0.00 | 0.180326E+10 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.138783E+10 | 149845.39 | 0.00 | 3562475.40 | 0.00 | 3764348.91 | 0.134461E+10 | 0.00 | 0.45 |
February | 0.613316E+09 | 0.108332E+09 | 0.00 | 3607067.87 | 561002.54 | 0.00 | 0.682767E+09 | 0.00 | 0.46 |
March | 0.191339E+09 | 0.112855E+10 | 0.00 | 2189932.10 | 56002860.05 | 0.00 | 0.210840E+09 | 0.00 | 0.46 |
April | 17150308.19 | 0.302588E+10 | 0.00 | 418966.73 | 0.242496E+09 | 0.00 | 2514919.35 | 0.00 | 0.46 |
May | 2593626.12 | 0.590828E+10 | 0.00 | 95255.63 | 0.434837E+09 | 0.00 | 1348029.48 | 0.00 | 0.47 |
June | 133010.94 | 0.737654E+10 | 0.00 | 3415.50 | 0.579580E+09 | 0.00 | 468821.41 | 0.00 | 0.47 |
July | 0.00 | 0.874937E+10 | 0.00 | 0.00 | 0.642589E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.897240E+10 | 0.00 | 0.00 | 0.655124E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.664936E+10 | 0.00 | 6500.18 | 0.545551E+09 | 0.00 | 130236.38 | 0.00 | 0.46 |
October | 86863429.88 | 0.276719E+10 | 0.00 | 1115472.14 | 0.189526E+09 | 0.00 | 24327493.35 | 0.00 | 0.46 |
November | 0.332978E+09 | 0.679632E+09 | 0.00 | 2660967.78 | 10884568.64 | 0.00 | 0.343841E+09 | 0.00 | 0.46 |
December | 0.101488E+10 | 5973743.25 | 0.00 | 4811185.89 | 0.00 | 0.00 | 0.123117E+10 | 0.00 | 0.45 |
Annual Sum or Average | 0.364708E+10 | 0.453717E+11 | 0.00 | 18471239.21 | 0.335715E+10 | 3764348.91 | 0.384202E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 149845.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.138783E+10 | 0.897240E+10 | 0.00 | 4811185.89 | 0.655124E+09 | 3764348.91 | 0.134461E+10 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.141569E+10 | 144437.47 | 0.00 | 3320749.15 | 0.00 | 11760364.95 | 0.129725E+10 | 0.00 | 0.45 |
February | 0.625557E+09 | 0.107597E+09 | 0.00 | 3508797.43 | 559871.28 | 0.00 | 0.669732E+09 | 0.00 | 0.46 |
March | 0.191952E+09 | 0.112838E+10 | 0.00 | 2187597.28 | 55980468.46 | 0.00 | 0.210184E+09 | 0.00 | 0.46 |
April | 17380915.25 | 0.303842E+10 | 0.00 | 424709.33 | 0.232671E+09 | 0.00 | 2639281.55 | 0.00 | 0.46 |
May | 2443524.12 | 0.593134E+10 | 0.00 | 92242.64 | 0.421557E+09 | 0.00 | 1487541.83 | 0.00 | 0.47 |
June | 151926.07 | 0.740217E+10 | 0.00 | 8828.97 | 0.568891E+09 | 0.00 | 350715.82 | 0.00 | 0.47 |
July | 0.00 | 0.878041E+10 | 0.00 | 0.00 | 0.637192E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.899898E+10 | 0.00 | 0.00 | 0.650650E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.667749E+10 | 0.00 | 5810.57 | 0.534702E+09 | 0.00 | 94029.06 | 0.00 | 0.46 |
October | 85630390.28 | 0.277293E+10 | 0.00 | 1130622.72 | 0.188471E+09 | 0.00 | 25892292.98 | 0.00 | 0.46 |
November | 0.335226E+09 | 0.679048E+09 | 0.00 | 2644940.61 | 10873871.10 | 0.00 | 0.341672E+09 | 0.00 | 0.46 |
December | 0.103941E+10 | 5871844.16 | 0.00 | 4646360.42 | 0.00 | 0.00 | 0.120461E+10 | 0.00 | 0.45 |
Annual Sum or Average | 0.371344E+10 | 0.455228E+11 | 0.00 | 17970659.13 | 0.330155E+10 | 11760364.95 | 0.375391E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 144437.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.141569E+10 | 0.899898E+10 | 0.00 | 4646360.42 | 0.650650E+09 | 11760364.95 | 0.129725E+10 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145807E+10 | 136447.03 | 0.00 | 2964350.22 | 0.00 | 20266360.14 | 0.123461E+10 | 0.00 | 0.45 |
February | 0.661324E+09 | 0.105634E+09 | 0.00 | 3284064.76 | 552050.45 | 0.00 | 0.635204E+09 | 0.00 | 0.46 |
March | 0.193367E+09 | 0.112124E+10 | 0.00 | 2086307.85 | 56266105.39 | 0.00 | 0.208870E+09 | 0.00 | 0.46 |
April | 16590057.54 | 0.301829E+10 | 0.00 | 398977.63 | 0.248882E+09 | 0.00 | 2481554.08 | 0.00 | 0.46 |
May | 2556600.28 | 0.590100E+10 | 0.00 | 97042.74 | 0.441798E+09 | 0.00 | 1354151.41 | 0.00 | 0.47 |
June | 163710.32 | 0.736934E+10 | 0.00 | 5089.71 | 0.585547E+09 | 0.00 | 391485.65 | 0.00 | 0.47 |
July | 0.00 | 0.874918E+10 | 0.00 | 0.00 | 0.647642E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.895146E+10 | 0.00 | 0.00 | 0.671312E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.663258E+10 | 0.00 | 7113.02 | 0.555613E+09 | 0.00 | 131448.85 | 0.00 | 0.46 |
October | 84823339.51 | 0.276091E+10 | 0.00 | 1114862.42 | 0.189850E+09 | 0.00 | 26432718.38 | 0.00 | 0.46 |
November | 0.333985E+09 | 0.674139E+09 | 0.00 | 2534618.25 | 10886697.35 | 0.00 | 0.344109E+09 | 0.00 | 0.46 |
December | 0.109386E+10 | 5715343.82 | 0.00 | 4347410.79 | 0.00 | 0.00 | 0.114821E+10 | 0.00 | 0.45 |
Annual Sum or Average | 0.384473E+10 | 0.452896E+11 | 0.00 | 16839837.39 | 0.340835E+10 | 20266360.14 | 0.360179E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 136447.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.145807E+10 | 0.895146E+10 | 0.00 | 4347410.79 | 0.671312E+09 | 20266360.14 | 0.123461E+10 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.227429E+10 | 0.00 | 0.00 | 4635799.55 | 0.00 | 48682614.39 | 0.247920E+10 | 0.00 | 0.42 |
February | 0.907847E+09 | 0.163509E+09 | 0.00 | 5941158.06 | 428823.67 | 0.00 | 0.124418E+10 | 0.00 | 0.42 |
March | 0.248019E+09 | 0.219540E+10 | 0.00 | 3699507.11 | 46907168.32 | 0.00 | 0.292075E+09 | 0.00 | 0.43 |
April | 11113334.88 | 0.592743E+10 | 0.00 | 237319.94 | 0.301081E+09 | 0.00 | 5081887.36 | 0.00 | 0.42 |
May | 812088.38 | 0.117198E+11 | 0.00 | 61259.79 | 0.264618E+09 | 0.00 | 353265.16 | 0.00 | 0.43 |
June | 57418.24 | 0.146066E+11 | 0.00 | 12753.37 | 0.332396E+09 | 0.00 | 157864.52 | 0.00 | 0.44 |
July | 0.00 | 0.169656E+11 | 0.00 | 0.00 | 0.468816E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.176665E+11 | 0.00 | 0.00 | 0.447266E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 438.53 | 0.128539E+11 | 0.00 | 21284.64 | 0.628350E+09 | 0.00 | 17224.00 | 0.00 | 0.43 |
October | 90773608.76 | 0.542208E+10 | 0.00 | 1131399.17 | 0.245695E+09 | 0.00 | 18207304.35 | 0.00 | 0.42 |
November | 0.383509E+09 | 0.124047E+10 | 0.00 | 4684413.67 | 16728660.97 | 0.00 | 0.552403E+09 | 0.00 | 0.42 |
December | 0.164629E+10 | 7214108.22 | 0.00 | 7265531.06 | 0.00 | 0.00 | 0.231811E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.556272E+10 | 0.887685E+11 | 0.00 | 27690426.37 | 0.275229E+10 | 48682614.39 | 0.690978E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.227429E+10 | 0.176665E+11 | 0.00 | 7265531.06 | 0.628350E+09 | 48682614.39 | 0.247920E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114625E+10 | 0.00 | 0.00 | 2238824.93 | 0.00 | 31715253.90 | 0.121734E+10 | 0.00 | 0.42 |
February | 0.456637E+09 | 81102067.12 | 0.00 | 2993167.38 | 210109.76 | 0.00 | 0.618417E+09 | 0.00 | 0.42 |
March | 0.124291E+09 | 0.109562E+10 | 0.00 | 1872938.13 | 23151556.42 | 0.00 | 0.145415E+09 | 0.00 | 0.43 |
April | 5524105.03 | 0.296063E+10 | 0.00 | 116771.06 | 0.156217E+09 | 0.00 | 2554195.14 | 0.00 | 0.42 |
May | 327345.44 | 0.583484E+10 | 0.00 | 25312.20 | 0.154396E+09 | 0.00 | 213159.43 | 0.00 | 0.43 |
June | 19844.40 | 0.727333E+10 | 0.00 | 4305.54 | 0.183980E+09 | 0.00 | 131530.86 | 0.00 | 0.44 |
July | 0.00 | 0.843694E+10 | 0.00 | 0.00 | 0.253251E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.878525E+10 | 0.00 | 0.00 | 0.236744E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 13654.76 | 0.638718E+10 | 0.00 | 10538.56 | 0.330146E+09 | 0.00 | 18973.21 | 0.00 | 0.43 |
October | 45475129.85 | 0.270341E+10 | 0.00 | 571699.48 | 0.121920E+09 | 0.00 | 9119590.45 | 0.00 | 0.42 |
November | 0.190609E+09 | 0.616892E+09 | 0.00 | 2373423.32 | 8114875.54 | 0.00 | 0.277097E+09 | 0.00 | 0.42 |
December | 0.851049E+09 | 3593070.05 | 0.00 | 3609237.99 | 0.00 | 0.00 | 0.112988E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.282019E+10 | 0.441788E+11 | 0.00 | 13816218.60 | 0.146813E+10 | 31715253.90 | 0.340018E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.114625E+10 | 0.878525E+10 | 0.00 | 3609237.99 | 0.330146E+09 | 31715253.90 | 0.121734E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117436E+10 | 0.00 | 0.00 | 2124691.85 | 0.00 | 32849263.64 | 0.118405E+10 | 0.00 | 0.42 |
February | 0.466051E+09 | 80320574.40 | 0.00 | 2909318.21 | 211892.35 | 0.00 | 0.609631E+09 | 0.00 | 0.42 |
March | 0.124943E+09 | 0.109248E+10 | 0.00 | 1833150.57 | 23284236.39 | 0.00 | 0.144854E+09 | 0.00 | 0.43 |
April | 5986906.45 | 0.295680E+10 | 0.00 | 114387.11 | 0.158162E+09 | 0.00 | 2008726.00 | 0.00 | 0.42 |
May | 317932.20 | 0.581892E+10 | 0.00 | 23723.82 | 0.164221E+09 | 0.00 | 217999.21 | 0.00 | 0.43 |
June | 20582.72 | 0.726082E+10 | 0.00 | 3392.62 | 0.187284E+09 | 0.00 | 142120.36 | 0.00 | 0.44 |
July | 0.00 | 0.842360E+10 | 0.00 | 0.00 | 0.254497E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.876297E+10 | 0.00 | 0.00 | 0.245573E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 14023.33 | 0.637130E+10 | 0.00 | 10164.04 | 0.334450E+09 | 0.00 | 21944.63 | 0.00 | 0.43 |
October | 45279978.42 | 0.269853E+10 | 0.00 | 564178.78 | 0.121956E+09 | 0.00 | 9245227.68 | 0.00 | 0.42 |
November | 0.190946E+09 | 0.614766E+09 | 0.00 | 2334927.14 | 8253613.26 | 0.00 | 0.277472E+09 | 0.00 | 0.42 |
December | 0.857945E+09 | 3567636.29 | 0.00 | 3506262.36 | 0.00 | 0.00 | 0.112273E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.286586E+10 | 0.440841E+11 | 0.00 | 13424196.50 | 0.149789E+10 | 32849263.64 | 0.335037E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.117436E+10 | 0.876297E+10 | 0.00 | 3506262.36 | 0.334450E+09 | 32849263.64 | 0.118405E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122495E+10 | 0.00 | 0.00 | 1870949.45 | 0.00 | 44544884.88 | 0.110899E+10 | 0.00 | 0.42 |
February | 0.492622E+09 | 78617428.64 | 0.00 | 2704507.00 | 216365.46 | 0.00 | 0.581462E+09 | 0.00 | 0.42 |
March | 0.129637E+09 | 0.108530E+10 | 0.00 | 1722165.92 | 23791462.97 | 0.00 | 0.139591E+09 | 0.00 | 0.43 |
April | 6753099.95 | 0.295037E+10 | 0.00 | 109046.95 | 0.162478E+09 | 0.00 | 1048469.76 | 0.00 | 0.42 |
May | 288386.82 | 0.581004E+10 | 0.00 | 20995.93 | 0.168760E+09 | 0.00 | 215600.17 | 0.00 | 0.43 |
June | 21577.57 | 0.725566E+10 | 0.00 | 1798.68 | 0.189577E+09 | 0.00 | 156771.80 | 0.00 | 0.44 |
July | 0.00 | 0.842459E+10 | 0.00 | 0.00 | 0.256855E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.875943E+10 | 0.00 | 0.00 | 0.254448E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 13394.29 | 0.637122E+10 | 0.00 | 10476.46 | 0.335975E+09 | 0.00 | 20682.26 | 0.00 | 0.43 |
October | 44791286.71 | 0.269456E+10 | 0.00 | 550898.36 | 0.123467E+09 | 0.00 | 9381320.63 | 0.00 | 0.42 |
November | 0.190269E+09 | 0.611450E+09 | 0.00 | 2267923.97 | 8424792.68 | 0.00 | 0.278557E+09 | 0.00 | 0.42 |
December | 0.880783E+09 | 3512709.70 | 0.00 | 3277743.47 | 0.00 | 0.00 | 0.109668E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.297013E+10 | 0.440447E+11 | 0.00 | 12536506.19 | 0.152399E+10 | 44544884.88 | 0.321610E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.122495E+10 | 0.875943E+10 | 0.00 | 3277743.47 | 0.335975E+09 | 44544884.88 | 0.110899E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129422E+10 | 0.00 | 0.00 | 1613062.73 | 0.00 | 55090059.88 | 0.999604E+09 | 0.00 | 0.42 |
February | 0.538270E+09 | 75936571.98 | 0.00 | 2461129.96 | 225809.63 | 672461.95 | 0.521079E+09 | 0.00 | 0.42 |
March | 0.144928E+09 | 0.106836E+10 | 0.00 | 1596253.75 | 23302691.79 | 0.00 | 0.131282E+09 | 0.00 | 0.43 |
April | 7211995.00 | 0.294460E+10 | 0.00 | 127227.29 | 0.151970E+09 | 0.00 | 1811555.64 | 0.00 | 0.42 |
May | 1823521.45 | 0.579706E+10 | 0.00 | 70056.26 | 0.142027E+09 | 0.00 | 121702.97 | 0.00 | 0.43 |
June | 89603.57 | 0.726004E+10 | 0.00 | 1883.08 | 0.175490E+09 | 0.00 | 585882.72 | 0.00 | 0.44 |
July | 0.00 | 0.847342E+10 | 0.00 | 730.60 | 0.216088E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.888668E+10 | 0.00 | 0.00 | 0.194299E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 128062.44 | 0.652272E+10 | 0.00 | 29291.73 | 0.247325E+09 | 0.00 | 175290.17 | 0.00 | 0.43 |
October | 43605764.20 | 0.272858E+10 | 0.00 | 558808.71 | 0.110457E+09 | 0.00 | 9890572.91 | 0.00 | 0.42 |
November | 0.194887E+09 | 0.612855E+09 | 0.00 | 2281363.00 | 8093890.50 | 0.00 | 0.272323E+09 | 0.00 | 0.42 |
December | 0.883472E+09 | 3490025.01 | 0.00 | 3147210.41 | 0.00 | 1781975.86 | 0.106150E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.310863E+10 | 0.443737E+11 | 0.00 | 11887017.52 | 0.126928E+10 | 57544497.69 | 0.299837E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.129422E+10 | 0.888668E+10 | 0.00 | 3147210.41 | 0.247325E+09 | 55090059.88 | 0.106150E+10 | 0.00 | 0.44 |