Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:19
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2020-06-03 19:19:24
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1694.81 | 810.79 | 810.79 |
Net Site Energy | 1694.81 | 810.79 | 810.79 |
Total Source Energy | 4332.01 | 2072.42 | 2072.42 |
Net Source Energy | 4332.01 | 2072.42 | 2072.42 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 497.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 66.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 587.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 110.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 239.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 65.95 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1197.71 | 497.10 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 497.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 66.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 587.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 110.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 239.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 65.95 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 333.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 177.66 | 237.81 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 572.98 | 237.81 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 333.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 177.66 | 237.81 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 572.98 | 237.81 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1197.711 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1197.711 | 100.00 |
Total On-Site and Utility Electric Sources | 1197.711 | 100.00 |
Total Electricity End Uses | 1197.711 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2119.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 21.0784 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 22.5208 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.3680 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.3680 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.3680 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 15.8795 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 15.8795 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 15.8795 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 15.8795 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 15.8795 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 18.4215 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 18.4215 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-13:00 | 09-JAN-09:09 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 307809.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 43908.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 36581.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5465.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 107930.00 | 307809.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 307809.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 43908.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 36581.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5465.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 538.86 | 0.00 | 0.00 | 0.00 |
Cooling | 210.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1859.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 350.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 757.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 208.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3793.15 | 538.86 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 257.79 | 0.00 | 0.00 | 0.00 |
Cooling | 100.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 889.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 167.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 362.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 99.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1814.63 | 257.79 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 257.79 | 0.00 | 0.00 | 0.00 |
Cooling | 100.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 889.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 167.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 362.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 99.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1814.63 | 257.79 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.06 |
SMSTORE1 DIRECT AIR | 1.11 |
SMSTORE2 DIRECT AIR | 1.11 |
SMSTORE3 DIRECT AIR | 1.10 |
SMSTORE4 DIRECT AIR | 1.11 |
LGSTORE2 DIRECT AIR | 2.02 |
SMSTORE5 DIRECT AIR | 1.04 |
SMSTORE6 DIRECT AIR | 1.03 |
SMSTORE7 DIRECT AIR | 1.02 |
SMSTORE8 DIRECT AIR | 1.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.06 | 2.06 | 2.06 | 2.06 | 2.06 | 2.06 | 1.00 | 1.00 | 2.06 |
PSZ-AC_2:2 | 1.11 | 1.11 | 1.11 | 1.11 | 1.11 | 1.11 | 1.00 | 1.00 | 1.11 |
PSZ-AC_3:3 | 1.11 | 1.11 | 1.11 | 1.11 | 1.11 | 1.11 | 1.00 | 0.997191 | 1.11 |
PSZ-AC_4:4 | 1.10 | 1.10 | 1.10 | 1.10 | 1.11 | 1.11 | 1.00 | 0.987403 | 1.11 |
PSZ-AC_5:5 | 1.11 | 1.11 | 1.11 | 1.11 | 1.11 | 1.11 | 1.00 | 0.998304 | 1.11 |
PSZ-AC_6:6 | 2.02 | 2.02 | 2.02 | 2.02 | 2.02 | 2.02 | 1.00 | 1.00 | 2.02 |
PSZ-AC_7:7 | 1.04 | 1.04 | 1.04 | 1.04 | 1.05 | 1.05 | 1.00 | 0.995887 | 1.05 |
PSZ-AC_8:8 | 1.03 | 1.03 | 1.03 | 1.03 | 1.04 | 1.04 | 1.00 | 0.995534 | 1.04 |
PSZ-AC_9:9 | 1.02 | 1.02 | 1.02 | 1.02 | 1.03 | 1.03 | 1.00 | 0.989673 | 1.03 |
PSZ-AC_10:10 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.05 | 1.00 | 1.00 | 1.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.06 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 1.11 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 1.11 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 1.11 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 1.11 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 2.02 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 1.05 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 1.04 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 1.03 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 1.05 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.06 | 2.06 | 2.06 | 2.06 | 34244.90 | 62375.17 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.11 | 1.11 | 1.11 | 1.11 | 18396.10 | 32824.32 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.11 | 1.11 | 1.11 | 1.11 | 18351.47 | 32708.15 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.11 | 1.11 | 1.11 | 1.11 | 18415.14 | 32567.12 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.11 | 1.11 | 1.11 | 1.11 | 18325.44 | 32701.44 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.02 | 2.02 | 2.02 | 2.02 | 33619.80 | 61530.12 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 1.05 | 17370.31 | 31430.36 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 1.04 | 17253.97 | 31266.66 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 1.03 | 17127.01 | 30975.46 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 1.05 | 17384.52 | 31593.37 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 2.06 | 1.03 | 2.06 | 34082.44 | 34244.90 | 17122.45 | 34244.90 | 0.796911 | 0.796910 | 0.796910 | 0.796910 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.11 | 0.555655 | 1.11 | 18396.13 | 18396.10 | 9198.05 | 18396.10 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.11 | 0.554305 | 1.11 | 18351.43 | 18351.47 | 9175.74 | 18351.47 | 0.798654 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.11 | 0.556230 | 1.11 | 18415.16 | 18415.14 | 9207.57 | 18415.14 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.11 | 0.553520 | 1.11 | 18325.44 | 18325.44 | 9162.72 | 18325.44 | 0.798655 | 0.798660 | 0.798660 | 0.798660 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 2.02 | 1.01 | 2.02 | 33383.05 | 33619.80 | 16809.90 | 33619.80 | 0.796066 | 0.796070 | 0.796070 | 0.796070 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 1.05 | 0.522950 | 1.05 | 17313.36 | 17370.31 | 8685.16 | 17370.31 | 0.797450 | 0.797450 | 0.797450 | 0.797450 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 1.04 | 0.519020 | 1.04 | 17183.25 | 17253.97 | 8626.99 | 17253.97 | 0.797148 | 0.797150 | 0.797150 | 0.797150 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 1.03 | 0.514735 | 1.03 | 17041.38 | 17127.01 | 8563.50 | 17127.01 | 0.796817 | 0.796820 | 0.796820 | 0.796820 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.05 | 0.524870 | 1.05 | 17376.92 | 17384.52 | 8692.26 | 17384.52 | 0.798495 | 0.798490 | 0.798490 | 0.798490 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.06 | 2203.14 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.11 | 1230.39 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.11 | 1227.41 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.11 | 1231.67 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.11 | 1225.67 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.02 | 2157.93 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1157.97 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1149.28 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1139.79 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1162.23 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 62375.17 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 32824.32 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 32708.15 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 32567.12 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 32701.44 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 61530.12 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 31430.36 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 31266.66 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 30975.46 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 31593.37 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 21.078 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.378 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 22.521 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 26.821 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.368 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.668 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.368 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.668 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.368 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.668 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 5532.190 | 15.879 | 184.430 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5532.190 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 1811.251 | 5.199 | 60.383 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1811.251 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1156.875 | 6.641 | 77.135 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1156.875 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 5532.190 | 15.879 | 184.430 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5532.190 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1464 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2111 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.756 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.659 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009596 | 2.1009596 | 2.1009596 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
23 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
24 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
25 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
26 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
27 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
28 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
29 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
30 | 7 | -0.28997596E-08 | -0.17578320E-14 | 0.22751757E-14 | -0.53829073E-16 |
31 | 6 | 0.41991781E-05 | 0.27986603E-08 | 0.31940183E-02 | -0.26794102E-04 |
32 | 5 | -0.29588474E-03 | 0.16552611E-05 | -0.22396035 | 0.19582313E-02 |
33 | 4 | 0.67666006E-02 | 0.75295852E-04 | 4.8334724 | -0.45302727E-01 |
34 | 3 | -0.59297736E-01 | 0.59838054E-03 | -38.043598 | 0.39889893 |
35 | 2 | 0.21038411 | 0.99492606E-03 | 116.52712 | -1.4185167 |
36 | 1 | -0.30354941 | 0.30287292E-03 | -143.93272 | 2.0494576 |
37 | 0 | 0.14796861 | 0.73483799E-05 | 60.838472 | |
38 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
39 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
40 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
41 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
42 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
43 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
44 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
45 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
46 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
47 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
48 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
49 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
50 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
51 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
52 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
53 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
54 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789911E-14 | -0.32998980E-16 |
55 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
56 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
57 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
58 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
59 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
60 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
61 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
62 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
63 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
64 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
65 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
66 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
67 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
68 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
69 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
70 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
71 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
72 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
73 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
74 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
75 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
76 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
77 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
78 | 7 | -0.51571905E-08 | -0.97500957E-14 | 0.15789917E-14 | -0.32998991E-16 |
79 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
80 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
81 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
82 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
83 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
84 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
85 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
86 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
87 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
88 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
89 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
90 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
91 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
92 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
93 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
94 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
95 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
96 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
97 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
98 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
99 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
100 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
101 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
102 | 7 | -0.19967951E-08 | -0.58252365E-15 | 0.72897552E-14 | -0.10630581E-15 |
103 | 6 | 0.59274927E-05 | 0.40433693E-08 | 0.31889525E-02 | -0.26751606E-04 |
104 | 5 | -0.42514865E-03 | 0.23948505E-05 | -0.22367243 | 0.19556901E-02 |
105 | 4 | 0.97725356E-02 | 0.10900143E-03 | 4.8286774 | -0.45256634E-01 |
106 | 3 | -0.85796444E-01 | 0.86675557E-03 | -38.016512 | 0.39859954 |
107 | 2 | 0.30461848 | 0.14417950E-02 | 116.47440 | -1.4178116 |
108 | 1 | -0.43965446 | 0.43929230E-03 | -143.90169 | 2.0489476 |
109 | 0 | 0.21434897 | 0.10616597E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 29 | 1 | VerySmooth | 2.045 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.159 | 4.569E-004 | 2.517E-004 | 0.317 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 4.561E-002 | 2.619E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 9.122E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.113 | 6.514E-004 | 3.022E-004 | 0.453 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 20395.34684 | 24474.41621 | 1.71577 | 2.05892 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.40000 | 6.26594E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 29465.42443 | 35358.50932 | 1.45220 | 1.74264 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 11008.49775 | 13210.19730 | 0.92609 | 1.11131 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.26594E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 14628.73554 | 17554.48265 | 0.72097 | 0.86516 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 11252.40951 | 13502.89141 | 0.92125 | 1.10550 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.60000 | 6.26593E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 14795.22113 | 17754.26536 | 0.72917 | 0.87501 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 11182.68644 | 13419.22373 | 0.91537 | 1.09844 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.60000 | 6.26593E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 14867.31912 | 17840.78295 | 0.73273 | 0.87927 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 11249.17337 | 13499.00805 | 0.92097 | 1.10516 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.60000 | 6.26593E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 15007.73665 | 18009.28398 | 0.73965 | 0.88758 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 19976.70991 | 23972.05189 | 1.68056 | 2.01667 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.13333 | 6.26594E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 28539.27679 | 34247.13215 | 1.40656 | 1.68788 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 10614.68162 | 12737.61794 | 0.86800 | 1.04159 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.32000 | 6.26593E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 15342.47217 | 18410.96660 | 0.75614 | 0.90737 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 10533.11334 | 12639.73601 | 0.86117 | 1.03341 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.32000 | 6.26593E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 15325.97607 | 18391.17128 | 0.75533 | 0.90640 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 10387.94808 | 12465.53769 | 0.84904 | 1.01884 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.32000 | 6.26593E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 15521.28131 | 18625.53757 | 0.76496 | 0.91795 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 10398.40952 | 12478.09142 | 0.87478 | 1.04974 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 32.73333 | 6.26593E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 17723.30111 | 21267.96133 | 0.87347 | 1.04817 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60000 | 3.41898E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 28303.18 | 2.05892 | 2.05892 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 56051.24 | 1.74264 | 1.74264 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 15111.42 | 1.11131 | 1.11131 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 27902.61 | 0.86516 | 0.86516 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 15075.90 | 1.10861 | 1.10861 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 28099.49 | 0.87501 | 0.87501 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 15120.25 | 1.11246 | 1.11246 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 28184.75 | 0.87927 | 0.87927 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 15056.62 | 1.10704 | 1.10704 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 28350.79 | 0.88758 | 0.88758 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 27793.24 | 2.01667 | 2.01667 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 54956.10 | 1.68788 | 1.68788 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 14336.07 | 1.04590 | 1.04590 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 28746.63 | 0.90737 | 0.90737 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 14244.29 | 1.03804 | 1.03804 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 28727.13 | 0.90640 | 0.90640 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14144.23 | 1.02947 | 1.02947 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 28958.08 | 0.91795 | 0.91795 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 14312.51 | 1.04974 | 1.04974 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 31561.97 | 1.04817 | 1.04817 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.05892 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.11131 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.10550 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09844 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.10516 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.01667 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04159 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03341 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01884 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04974 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05892 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05892 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05892 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05892 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05892 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.05892 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.11131 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.11131 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.11131 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.11131 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.11131 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.11131 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.10550 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.10550 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.10550 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.10550 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10861 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.10861 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.99719 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.09844 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.09844 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.09844 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.09844 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.11246 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.11246 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 0.98740 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.10516 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.10516 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.10516 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.10516 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10704 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.10704 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.99830 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.01667 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.01667 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.01667 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.01667 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.01667 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.01667 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04159 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04159 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04159 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04159 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04590 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04590 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.99589 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03341 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03341 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03341 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03341 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03804 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.03804 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.99553 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.01884 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.01884 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.01884 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.01884 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02947 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02947 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.98967 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04974 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04974 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04974 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04974 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04974 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04974 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.05892 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.11131 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.10861 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.11246 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.10704 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.01667 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.04590 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.03804 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.02947 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.04974 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05892 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.05892 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.05892 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.05892 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.05892 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.05892 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.02946 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.05892 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 34082.43668 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 34244.90000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 17122.45000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 34244.90000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79691 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79691 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79691 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79691 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34244.90000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 62375.17112 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.05892 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2203.14305 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 62375.17112 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.11131 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.11131 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.11131 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.11131 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.11131 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.11131 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55566 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.11131 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18396.12647 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18396.10000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9198.05000 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 18396.10000 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18396.10000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32824.32029 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.11131 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1230.39452 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32824.32029 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10861 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10861 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10861 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10861 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10861 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10861 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55431 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.10861 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18351.43188 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18351.47000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9175.73500 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 18351.47000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79865 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18351.47000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32708.14767 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10861 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1227.40980 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32708.14767 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.11246 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.11246 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.11246 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.11246 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.11246 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.11246 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55623 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.11246 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18415.16305 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18415.14000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9207.57000 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 18415.14000 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18415.14000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32567.11553 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.11246 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1231.66859 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32567.11553 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10704 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10704 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10704 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10704 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10704 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10704 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55352 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.10704 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18325.44281 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18325.44000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9162.72000 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 18325.44000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79866 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79866 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79866 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79866 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18325.44000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32701.43528 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10704 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1225.66906 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32701.43528 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.01667 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.01667 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.01667 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.01667 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.01667 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.01667 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.00834 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.01667 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 33383.04916 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 33619.80000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16809.90000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 33619.80000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79607 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79607 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79607 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79607 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33619.80000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 61530.11851 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.01667 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2157.92973 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 61530.11851 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04590 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04590 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04590 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04590 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.04590 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04590 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52295 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.04590 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17313.35872 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17370.31000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8685.15500 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 17370.31000 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79745 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79745 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79745 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79745 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17370.31000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31430.36424 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04590 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1157.97302 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31430.36424 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03804 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03804 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03804 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03804 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.03804 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03804 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51902 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.03804 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17183.24781 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17253.97000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8626.98500 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 17253.97000 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79715 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79715 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79715 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79715 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17253.97000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31266.66068 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03804 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1149.27819 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31266.66068 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02947 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02947 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02947 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02947 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02947 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02947 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51474 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.02947 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17041.38388 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17127.01000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8563.50500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 17127.01000 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79682 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79682 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79682 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79682 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17127.01000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30975.46302 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02947 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1139.79166 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 30975.46302 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04974 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04974 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04974 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04974 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.04974 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04974 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52487 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.04974 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17376.92435 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17384.52000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8692.26000 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 17384.52000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79849 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79849 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79849 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79849 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17384.52000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31593.36871 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04974 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1162.22628 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31593.36871 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 32631.2 | 10.75 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 17525.2 | 31.49 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 17482.6 | 42.56 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 17543.3 | 53.42 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 17457.8 | 64.68 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 32039.2 | 45.20 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 16550.6 | 100.59 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 16440.4 | 112.29 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 16320.2 | 124.14 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 16561.8 | 133.23 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.146 | 0.141 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.211 | 0.201 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 11 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.4638126998E-002 | 6.8307806349E-002 | Pass | Pass | 0.1678913173 | 0.4396327384 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 6.6991602001E-002 | 0.1150194642 | Pass | Pass | 7.1973532968E-002 | 0.2686939631 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 2.8973321625E-002 | 5.0433557277E-002 | Pass | Pass | 0.2238641807 | 0.7002985204 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 2.6660396747E-002 | 7.6182221184E-002 | Pass | Pass | 0.1521012926 | 0.4581213499 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.2519216773E-002 | 0.1031031800 | Pass | Pass | 0.5280889507 | 2.9987206473 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 3.9556245348E-002 | 0.1237549307 | Pass | Pass | 0.1669953016 | 0.5024692861 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.1737771439E-002 | 0.1280540154 | Pass | Pass | 0.2345117525 | 0.6724794409 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.3553275457E-002 | 0.1358296882 | Pass | Pass | 0.4561110395 | 2.6216179216 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.8352114171E-002 | 0.1790663008 | Pass | Pass | 0.2232112467 | 1.2529958027 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 7.3805317805E-002 | 0.3011615409 | Pass | Pass | 9.0328784416E-002 | 0.3224454184 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.146 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.083 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.211 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.045 | 0.394 | 0.401 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.045 | 0.394 | 0.401 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.045 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.36_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.045 | 0.394 | 0.401 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.045 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.045 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 15.8795 | 348.39 | 5532.19 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 102.16 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 5.1990 | 348.39 | 1811.25 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 33.45 |
SMSTORE1_LIGHTS | SMSTORE1 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 51.08 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 6.6413 | 174.19 | 1156.88 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 21.36 |
SMSTORE2_LIGHTS | SMSTORE2 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 40.48 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
SMSTORE3_LIGHTS | SMSTORE3 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 40.48 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
SMSTORE4_LIGHTS | SMSTORE4 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 40.48 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
LGSTORE2_LIGHTS | LGSTORE2 | 15.8795 | 348.39 | 5532.19 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 74.42 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.21 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.21 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.21 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.21 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 9.2108 | 4180.64 | 38506.89 | 587.06 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7048.38 | AstronomicalClock | - | 83.57 | 83.57 | 110.57 | |
Exterior Lighting Total | 7048.38 | 110.57 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 34244.90 | 27290.10 | 6954.80 | 0.80 | 3.80 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 18396.10 | 14692.23 | 3703.87 | 0.80 | 3.91 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 18351.47 | 14656.59 | 3694.88 | 0.80 | 3.91 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 18415.14 | 14707.44 | 3707.70 | 0.80 | 3.91 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 18325.44 | 14635.80 | 3689.64 | 0.80 | 3.91 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 33619.80 | 26763.71 | 6856.09 | 0.80 | 3.80 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17370.31 | 13851.95 | 3518.36 | 0.80 | 3.91 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17253.97 | 13754.00 | 3499.97 | 0.80 | 3.91 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17127.01 | 13647.14 | 3479.87 | 0.80 | 3.91 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17384.52 | 13881.37 | 3503.15 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 32631.2 | 10.75 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 17525.2 | 31.49 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 17482.6 | 42.56 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 17543.3 | 53.42 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 17457.8 | 64.68 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 32039.2 | 45.20 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 16550.6 | 100.59 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 16440.4 | 112.29 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 16320.2 | 124.14 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 16561.8 | 133.23 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 62375.17 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32824.32 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32708.15 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32567.12 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32701.44 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 61530.12 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31430.36 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31266.66 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 30975.46 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31593.37 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.06 | 2203.14 | 1070.05 | 1.00 | 1.31 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.11 | 1230.39 | 1107.16 | 1.00 | 1.38 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.11 | 1227.41 | 1107.16 | 1.00 | 1.38 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.11 | 1231.67 | 1107.16 | 1.00 | 1.38 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.11 | 1225.67 | 1107.16 | 1.00 | 1.38 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.02 | 2157.93 | 1070.05 | 1.00 | 1.31 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1157.97 | 1107.16 | 1.00 | 1.39 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1149.28 | 1107.16 | 1.00 | 1.39 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1139.79 | 1107.16 | 1.00 | 1.40 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1162.23 | 1107.16 | 1.00 | 1.39 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 20395.35 | 24474.42 | 70.25 | 1.716 | 2.059 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 23.89 | 23.89 | 0.00720 | 33.40 | 0.00627 | 0.411 | 0.00 |
SMSTORE1 | 11008.50 | 13210.20 | 75.84 | 0.926 | 1.111 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00717 | 33.27 | 0.00627 | 0.206 | 0.00 |
SMSTORE2 | 11252.41 | 13502.89 | 77.52 | 0.921 | 1.105 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00755 | 24.60 | 0.00627 | 0.206 | 0.00 |
SMSTORE3 | 11182.69 | 13419.22 | 77.04 | 0.915 | 1.098 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00753 | 24.60 | 0.00627 | 0.206 | 0.00 |
SMSTORE4 | 11249.17 | 13499.01 | 77.49 | 0.921 | 1.105 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00755 | 24.60 | 0.00627 | 0.206 | 0.00 |
LGSTORE2 | 19976.71 | 23972.05 | 68.81 | 1.681 | 2.017 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00720 | 33.13 | 0.00627 | 0.411 | 0.00 |
SMSTORE5 | 10614.68 | 12737.62 | 73.12 | 0.868 | 1.042 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00743 | 27.32 | 0.00627 | 0.206 | 0.00 |
SMSTORE6 | 10533.11 | 12639.74 | 72.56 | 0.861 | 1.033 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00745 | 27.32 | 0.00627 | 0.206 | 0.00 |
SMSTORE7 | 10387.95 | 12465.54 | 71.56 | 0.849 | 1.019 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00747 | 27.32 | 0.00627 | 0.206 | 0.00 |
SMSTORE8 | 10398.41 | 12478.09 | 71.63 | 0.875 | 1.050 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 23.89 | 23.89 | 0.00718 | 32.73 | 0.00627 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 29465.42 | 35358.51 | 101.49 | 1.452 | 1.743 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00675 | -27.60 | 0.00034 | 0.411 | 0.00 |
SMSTORE1 | 14628.74 | 17554.48 | 100.78 | 0.721 | 0.865 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00664 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE2 | 14795.22 | 17754.27 | 101.92 | 0.729 | 0.875 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00665 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE3 | 14867.32 | 17840.78 | 102.42 | 0.733 | 0.879 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00666 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE4 | 15007.74 | 18009.28 | 103.39 | 0.740 | 0.888 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00666 | -27.60 | 0.00034 | 0.206 | 0.00 |
LGSTORE2 | 28539.28 | 34247.13 | 98.30 | 1.407 | 1.688 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00674 | -27.60 | 0.00034 | 0.411 | 0.00 |
SMSTORE5 | 15342.47 | 18410.97 | 105.69 | 0.756 | 0.907 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00669 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE6 | 15325.98 | 18391.17 | 105.58 | 0.755 | 0.906 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00668 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE7 | 15521.28 | 18625.54 | 106.92 | 0.765 | 0.918 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00670 | -27.60 | 0.00034 | 0.206 | 0.00 |
SMSTORE8 | 17723.30 | 21267.96 | 122.09 | 0.873 | 1.048 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00680 | -27.60 | 0.00034 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.06 | 2.06 | 1.74 | 1.74 | 2.0589 | 2.0589 | 2.0589 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.11 | 1.11 | 0.87 | 0.87 | 1.1113 | 1.1113 | 1.1113 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.11 | 1.11 | 0.88 | 0.88 | 1.1086 | 1.1055 | 1.1086 | 0.9972 | 1.0000 |
PSZ-AC_4:4 | 1.11 | 1.11 | 0.88 | 0.88 | 1.1125 | 1.0984 | 1.1125 | 0.9874 | 1.0000 |
PSZ-AC_5:5 | 1.11 | 1.11 | 0.89 | 0.89 | 1.1070 | 1.1052 | 1.1070 | 0.9983 | 1.0000 |
PSZ-AC_6:6 | 2.02 | 2.02 | 1.69 | 1.69 | 2.0167 | 2.0167 | 2.0167 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.05 | 1.05 | 0.91 | 0.91 | 1.0459 | 1.0416 | 1.0459 | 0.9959 | 1.0000 |
PSZ-AC_8:8 | 1.04 | 1.04 | 0.91 | 0.91 | 1.0380 | 1.0334 | 1.0380 | 0.9955 | 1.0000 |
PSZ-AC_9:9 | 1.03 | 1.03 | 0.92 | 0.92 | 1.0295 | 1.0188 | 1.0295 | 0.9897 | 1.0000 |
PSZ-AC_10:10 | 1.05 | 1.05 | 1.05 | 1.05 | 1.0497 | 1.0497 | 1.0497 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 34244.900 | 0.000 | 2.058920 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34244.90 | 34244.90 | 2.058920 | 25.79 | 14.36 | 0.00700978 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 19.9839 | 23.89 | 0.00719555 | 34.1731 | 20395.35 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 62375.171 | 62375.171 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 62375.17 | 62375.17 | 2.058921 | 9.61 | 6.08 | 0.00523894 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 19.9839 | 21.10 | 0.00675255 | 38.0114 | 29465.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 18396.100 | 0.000 | 1.111310 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 18396.10 | 18396.10 | 1.111310 | 25.65 | 14.31 | 0.00700556 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 18.5121 | 23.89 | 0.00717369 | 34.0704 | 11007.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 32824.320 | 32824.320 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32824.32 | 32824.32 | 1.111308 | 9.52 | 5.93 | 0.00514216 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 18.5121 | 21.10 | 0.00663972 | 37.3838 | 14628.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 18351.470 | 0.000 | 1.108610 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 18351.47 | 18351.47 | 1.108610 | 25.65 | 14.31 | 0.00700545 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 18.5572 | 23.89 | 0.00755201 | 35.8500 | 10977.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 32708.148 | 32708.148 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32708.15 | 32708.15 | 1.108612 | 9.65 | 6.02 | 0.00516747 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 18.5571 | 21.10 | 0.00665078 | 37.4455 | 14795.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 18415.140 | 0.000 | 1.112460 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 18415.14 | 18415.14 | 1.112460 | 25.65 | 14.31 | 0.00700560 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 18.4930 | 23.89 | 0.00753430 | 35.7666 | 11015.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 32567.116 | 32567.116 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32567.12 | 32567.12 | 1.112459 | 9.71 | 6.06 | 0.00517827 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 18.4930 | 21.10 | 0.00665549 | 37.4717 | 14867.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 18325.440 | 0.000 | 1.107040 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 18325.44 | 18325.44 | 1.107040 | 25.66 | 14.31 | 0.00700538 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 18.5835 | 23.89 | 0.00754758 | 35.8291 | 10961.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 32701.435 | 32701.435 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32701.44 | 32701.44 | 1.107040 | 9.82 | 6.13 | 0.00519911 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 18.5835 | 21.10 | 0.00666463 | 37.5226 | 15007.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 33619.800 | 0.000 | 2.016670 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33619.80 | 33619.80 | 2.016670 | 25.83 | 14.37 | 0.00701077 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 20.4026 | 23.89 | 0.00720219 | 34.2043 | 19964.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 61530.119 | 61530.119 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 61530.12 | 61530.12 | 2.016668 | 9.23 | 5.83 | 0.00517880 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 20.4026 | 21.10 | 0.00673797 | 37.9299 | 28539.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 17370.310 | 0.000 | 1.045900 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 17370.31 | 17370.31 | 1.045900 | 25.76 | 14.34 | 0.00700264 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 19.6698 | 23.89 | 0.00743334 | 35.2922 | 10353.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 31430.364 | 31430.364 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31430.36 | 31430.36 | 1.045896 | 10.06 | 6.30 | 0.00524749 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 19.6699 | 21.10 | 0.00668584 | 37.6408 | 15342.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 17253.970 | 0.000 | 1.038040 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 17253.97 | 17253.97 | 1.038040 | 25.78 | 14.35 | 0.00700225 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 19.8188 | 23.89 | 0.00744528 | 35.3484 | 10275.93 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 31266.661 | 31266.661 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31266.66 | 31266.66 | 1.038043 | 10.05 | 6.29 | 0.00524515 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 19.8187 | 21.10 | 0.00668481 | 37.6350 | 15325.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 17127.010 | 0.000 | 1.029470 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 17127.01 | 17127.01 | 1.029470 | 25.79 | 14.35 | 0.00700181 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00626594 | 16.30 | 19.9837 | 23.89 | 0.00747342 | 35.4807 | 10191.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 30975.463 | 30975.463 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30975.46 | 30975.46 | 1.029474 | 10.19 | 6.39 | 0.00527263 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 19.9837 | 21.10 | 0.00669689 | 37.7023 | 15521.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 17384.520 | 0.000 | 1.049740 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 17384.52 | 17384.52 | 1.049740 | 25.73 | 14.33 | 0.00699907 | 12.80 | 10.89 | 0.00850000 | 33.27 | 0.00626594 | 16.26 | 19.5979 | 23.89 | 0.00717976 | 34.0989 | 10333.40 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 31593.369 | 31593.369 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31593.37 | 31593.37 | 1.049738 | 11.55 | 7.29 | 0.00552966 | 40.00 | 19.60 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 19.5979 | 21.10 | 0.00679652 | 38.2578 | 17723.30 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34244.900 | 0.000 | 2.058920 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8708 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34244.90 | 34244.90 | 1.0000 | 2.16833076 | 2.058920 | 25.79 | 14.36 | 0.00700978 | 43781.8 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34244.90 | 33.40 | 0.00626594 | 16.30 | 0.41145340 | 19.9839 | 23.89 | 0.00719555 | 23.89 | 0.00719555 | 34.1731 | 20395.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 62375.171 | 62375.171 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.058921 | 2.16833206 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 62375.17 | 62375.17 | 1.0000 | 2.16833206 | 2.058921 | 9.61 | 6.08 | 0.00523894 | 22848.4 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62375.17 | -27.60 | 0.00034190 | -27.60 | 0.41145340 | 19.9839 | 21.11 | 0.00675255 | 21.10 | 0.00675255 | 38.0114 | 29465.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18396.100 | 0.000 | 1.111310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8630 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 18396.10 | 18396.10 | 1.0000 | 1.17036488 | 1.111310 | 25.65 | 14.31 | 0.00700556 | 43628.7 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18396.10 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 18.5121 | 23.89 | 0.00717360 | 23.89 | 0.00717369 | 34.0704 | 11007.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32824.320 | 32824.320 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.111308 | 1.17036293 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32824.32 | 32824.32 | 1.0000 | 1.17036293 | 1.111308 | 9.52 | 5.93 | 0.00514216 | 22521.4 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32824.32 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 18.5121 | 21.11 | 0.00663972 | 21.10 | 0.00663972 | 37.3838 | 14628.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18351.470 | 0.000 | 1.108610 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8628 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 18351.47 | 18351.47 | 1.0000 | 1.16752140 | 1.108610 | 25.65 | 14.31 | 0.00700545 | 43633.3 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18351.47 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 18.5572 | 23.89 | 0.00717402 | 23.89 | 0.00755201 | 35.8500 | 10977.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32708.148 | 32708.148 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.108612 | 1.16752383 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32708.15 | 32708.15 | 1.0000 | 1.16752383 | 1.108612 | 9.65 | 6.02 | 0.00516747 | 22717.4 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32708.15 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 18.5571 | 21.11 | 0.00665078 | 21.10 | 0.00665078 | 37.4455 | 14795.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18415.140 | 0.000 | 1.112460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8631 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 18415.14 | 18415.14 | 1.0000 | 1.17157599 | 1.112460 | 25.65 | 14.31 | 0.00700560 | 43627.6 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18415.14 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 18.4930 | 23.89 | 0.00717350 | 23.89 | 0.00753430 | 35.7666 | 11015.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32567.116 | 32567.116 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.112459 | 1.17157483 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32567.12 | 32567.12 | 1.0000 | 1.17157483 | 1.112459 | 9.71 | 6.06 | 0.00517827 | 22800.9 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32567.12 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 18.4930 | 21.11 | 0.00665549 | 21.10 | 0.00665549 | 37.4717 | 14867.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18325.440 | 0.000 | 1.107040 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8627 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 18325.44 | 18325.44 | 1.0000 | 1.16586797 | 1.107040 | 25.66 | 14.31 | 0.00700538 | 43635.8 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18325.44 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 18.5835 | 23.89 | 0.00717425 | 23.89 | 0.00754758 | 35.8291 | 10961.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32701.435 | 32701.435 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.107040 | 1.16586802 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32701.44 | 32701.44 | 1.0000 | 1.16586802 | 1.107040 | 9.82 | 6.13 | 0.00519911 | 22961.6 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32701.44 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 18.5835 | 21.11 | 0.00666463 | 21.10 | 0.00666463 | 37.5226 | 15007.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33619.800 | 0.000 | 2.016670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8727 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33619.80 | 33619.80 | 1.0000 | 2.12383560 | 2.016670 | 25.83 | 14.37 | 0.00701077 | 43826.0 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33619.80 | 33.40 | 0.00626594 | 16.30 | 0.41145340 | 20.4026 | 23.89 | 0.00720183 | 23.89 | 0.00720219 | 34.2043 | 19964.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61530.119 | 61530.119 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.016668 | 2.12383314 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 61530.12 | 61530.12 | 1.0000 | 2.12383314 | 2.016668 | 9.23 | 5.83 | 0.00517880 | 22318.5 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61530.12 | -27.60 | 0.00034190 | -27.60 | 0.41145340 | 20.4026 | 21.11 | 0.00673797 | 21.10 | 0.00673797 | 37.9299 | 28539.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17370.310 | 0.000 | 1.045900 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8576 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 17370.31 | 17370.31 | 1.0000 | 1.10147900 | 1.045900 | 25.76 | 14.34 | 0.00700264 | 43734.6 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17370.31 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 19.6698 | 23.89 | 0.00718319 | 23.89 | 0.00743334 | 35.2922 | 10353.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31430.364 | 31430.364 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.045896 | 1.10147491 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31430.36 | 31430.36 | 1.0000 | 1.10147491 | 1.045896 | 10.06 | 6.30 | 0.00524749 | 23333.4 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31430.36 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 19.6699 | 21.11 | 0.00668584 | 21.10 | 0.00668584 | 37.6408 | 15342.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17253.970 | 0.000 | 1.038040 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8568 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 17253.97 | 17253.97 | 1.0000 | 1.09320132 | 1.038040 | 25.78 | 14.35 | 0.00700225 | 43747.9 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17253.97 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 19.8188 | 23.89 | 0.00718440 | 23.89 | 0.00744528 | 35.3484 | 10275.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31266.661 | 31266.661 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.038043 | 1.09320430 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31266.66 | 31266.66 | 1.0000 | 1.09320430 | 1.038043 | 10.05 | 6.29 | 0.00524515 | 23315.4 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31266.66 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 19.8187 | 21.11 | 0.00668481 | 21.10 | 0.00668481 | 37.6350 | 15325.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17127.010 | 0.000 | 1.029470 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8560 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 17127.01 | 17127.01 | 1.0000 | 1.08417591 | 1.029470 | 25.79 | 14.35 | 0.00700181 | 43762.7 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17127.01 | 33.40 | 0.00626594 | 16.30 | 0.20572670 | 19.9837 | 23.89 | 0.00718573 | 23.89 | 0.00747342 | 35.4807 | 10191.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30975.463 | 30975.463 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.029474 | 1.08418063 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30975.46 | 30975.46 | 1.0000 | 1.08418063 | 1.029474 | 10.19 | 6.39 | 0.00527263 | 23525.8 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30975.46 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 19.9837 | 21.11 | 0.00669689 | 21.10 | 0.00669689 | 37.7023 | 15521.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17384.520 | 0.000 | 1.049740 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8509 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 17384.52 | 17384.52 | 1.0000 | 1.10552306 | 1.049740 | 25.73 | 14.33 | 0.00699907 | 43697.9 | 12.80 | 10.89 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17384.52 | 33.27 | 0.00626594 | 16.26 | 0.20572670 | 19.5979 | 23.89 | 0.00717865 | 23.89 | 0.00717976 | 34.0989 | 10333.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31593.369 | 31593.369 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.049738 | 1.10552065 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31593.37 | 31593.37 | 1.0000 | 1.10552065 | 1.049738 | 11.55 | 7.29 | 0.00552966 | 25550.0 | 40.00 | 19.60 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31593.37 | -27.60 | 0.00034190 | -27.60 | 0.20572670 | 19.5979 | 21.11 | 0.00679652 | 21.10 | 0.00679652 | 38.2578 | 17723.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.06 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.11 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.11 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.11 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.11 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.02 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.05 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.04 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.03 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 2028.17 | 3748.00 | 1128.17 |
SMSTORE1 | 1489.83 | 3587.17 | 621.33 |
SMSTORE2 | 1428.67 | 2738.00 | 678.00 |
SMSTORE3 | 1504.17 | 2770.83 | 752.83 |
SMSTORE4 | 1562.67 | 2817.50 | 836.00 |
LGSTORE2 | 1580.00 | 2679.17 | 964.00 |
SMSTORE5 | 1510.67 | 2734.33 | 1001.67 |
SMSTORE6 | 1534.17 | 2767.00 | 1048.17 |
SMSTORE7 | 1631.17 | 2845.50 | 1188.17 |
SMSTORE8 | 2038.17 | 3008.17 | 1653.83 |
Facility | 3143.50 | 4344.83 | 2119.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 3.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 24.00 | 0.00 | 0.00 | 0.00 |
Facility | 28.17 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 1.164 | 0.241 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 1.052 | 0.253 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 1.227 | 0.329 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 1.222 | 0.329 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 1.205 | 0.329 | 0.000 | 0.000 |
LGSTORE2 | 13.21 | 30.00 | 1805.20 | 1.151 | 0.316 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 1.164 | 0.351 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 1.153 | 0.351 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 1.129 | 0.351 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 1.096 | 0.377 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.21 | 30.00 | 1805.20 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1197.71 | 3592.76 | 12-FEB-07:50 | 107930.00 | 17-JUL-14:00 |
Electricity:Building | 715.79 | 2374.76 | 01-JAN-00:10 | 44671.08 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 161.97 | 442.08 | 01-JAN-00:10 | 8324.52 | 01-JAN-10:10 |
InteriorLights:Electricity | 587.07 | 1925.34 | 01-JAN-00:10 | 36581.55 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 135.61 | 367.17 | 01-JAN-00:10 | 6976.27 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 587.07 | 1925.34 | 01-JAN-00:10 | 36581.55 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 85.62 | 233.60 | 01-JAN-00:10 | 4400.95 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 72.45 | 196.15 | 01-JAN-00:10 | 3726.82 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 62.39 | 214.85 | 01-JAN-00:10 | 4044.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 51.92 | 177.40 | 01-JAN-00:10 | 3370.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 62.39 | 214.85 | 01-JAN-00:10 | 4044.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 51.92 | 177.40 | 01-JAN-00:10 | 3370.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 62.39 | 214.85 | 01-JAN-00:10 | 4044.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 51.92 | 177.40 | 01-JAN-00:10 | 3370.57 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 93.68 | 351.51 | 01-JAN-00:10 | 6603.84 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 74.42 | 276.61 | 01-JAN-00:10 | 5255.58 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 46.84 | 175.76 | 01-JAN-00:10 | 3301.92 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 37.21 | 138.30 | 01-JAN-00:10 | 2627.79 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 46.84 | 175.76 | 01-JAN-00:10 | 3301.92 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 37.21 | 138.30 | 01-JAN-00:10 | 2627.79 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 46.84 | 175.76 | 01-JAN-00:10 | 3301.92 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 37.21 | 138.30 | 01-JAN-00:10 | 2627.79 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 46.84 | 175.76 | 01-JAN-00:10 | 3301.92 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 37.21 | 138.30 | 01-JAN-00:10 | 2627.79 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
Electricity:Plant | 65.95 | 1218.00 | 06-JAN-00:10 | 11898.64 | 21-JAN-14:20 |
WaterSystems:Electricity | 65.95 | 1218.00 | 06-JAN-00:10 | 11898.64 | 21-JAN-14:20 |
Water Heater:WaterSystems:Electricity | 65.95 | 1218.00 | 06-JAN-00:10 | 11898.64 | 21-JAN-14:20 |
ElectricityPurchased:Facility | 1197.71 | 3592.76 | 12-FEB-07:50 | 107930.00 | 17-JUL-14:00 |
ElectricityPurchased:Plant | 1197.71 | 3592.76 | 12-FEB-07:50 | 107930.00 | 17-JUL-14:00 |
Cogeneration:ElectricityPurchased | 1197.71 | 3592.76 | 12-FEB-07:50 | 107930.00 | 17-JUL-14:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1197.71 | 3592.76 | 12-FEB-07:50 | 107930.00 | 17-JUL-14:00 |
ElectricityNet:Plant | 1197.71 | 3592.76 | 12-FEB-07:50 | 107930.00 | 17-JUL-14:00 |
Cogeneration:ElectricityNet | 1197.71 | 3592.76 | 12-FEB-07:50 | 107930.00 | 17-JUL-14:00 |
Electricity:HVAC | 305.40 | 0.00 | 01-JAN-00:10 | 58904.60 | 17-JUL-16:10 |
Fans:Electricity | 239.05 | 0.00 | 01-JAN-00:10 | 13885.48 | 06-OCT-09:40 |
General:Fans:Electricity | 239.05 | 0.00 | 01-JAN-00:10 | 13885.48 | 06-OCT-09:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 66.36 | 0.00 | 01-JAN-00:10 | 45019.12 | 17-JUL-16:10 |
ExteriorLights:Electricity | 110.57 | 0.00 | 01-JAN-08:20 | 7048.38 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 110.57 | 0.00 | 01-JAN-08:20 | 7048.38 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 497.10 | 0.00 | 01-JAN-00:10 | 307809.02 | 09-JAN-09:10 |
Gas:HVAC | 497.10 | 0.00 | 01-JAN-00:10 | 307809.02 | 09-JAN-09:10 |
Heating:Gas | 497.10 | 0.00 | 01-JAN-00:10 | 307809.02 | 09-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1142.34 | 0.00 | 01-JAN-00:10 | 380247.53 | 09-JAN-09:10 |
EnergyTransfer:Building | 500.93 | 0.00 | 01-JAN-00:10 | 134000.32 | 09-JAN-09:10 |
EnergyTransfer:Zone:LGSTORE1 | 103.38 | 0.00 | 01-JAN-00:10 | 23489.03 | 29-JAN-09:10 |
Heating:EnergyTransfer | 144.76 | 0.00 | 01-JAN-00:10 | 133733.39 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 20.42 | 0.00 | 01-JAN-00:10 | 22535.26 | 09-JAN-09:10 |
Cooling:EnergyTransfer | 356.18 | 0.00 | 01-JAN-00:10 | 97425.92 | 17-JUL-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 82.97 | 0.00 | 01-JAN-00:10 | 17531.57 | 28-JAN-00:10 |
EnergyTransfer:Zone:SMSTORE1 | 53.42 | 0.00 | 01-JAN-00:10 | 11147.31 | 27-JUL-20:20 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 7.27 | 0.00 | 01-JAN-00:10 | 10312.98 | 11-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 46.14 | 0.00 | 01-JAN-00:10 | 11147.31 | 27-JUL-20:20 |
EnergyTransfer:Zone:SMSTORE2 | 41.68 | 0.00 | 01-JAN-00:10 | 12147.53 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 9.17 | 0.00 | 01-JAN-00:10 | 12075.88 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 32.51 | 0.00 | 01-JAN-00:10 | 8455.01 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 41.44 | 0.00 | 01-JAN-00:10 | 12578.82 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 9.92 | 0.00 | 01-JAN-00:10 | 12578.82 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 31.52 | 0.00 | 01-JAN-00:10 | 8517.67 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE4 | 40.65 | 0.00 | 01-JAN-00:10 | 13071.24 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 11.00 | 0.00 | 01-JAN-00:10 | 13071.24 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 29.65 | 0.00 | 01-JAN-00:10 | 8450.79 | 17-JUL-16:10 |
EnergyTransfer:Zone:LGSTORE2 | 69.86 | 0.00 | 01-JAN-00:10 | 25125.44 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 21.74 | 0.00 | 01-JAN-00:10 | 24869.84 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 48.12 | 0.00 | 01-JAN-00:10 | 15429.49 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE5 | 36.32 | 0.00 | 01-JAN-00:10 | 13355.81 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 12.45 | 0.00 | 01-JAN-00:10 | 13355.81 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 23.87 | 0.00 | 01-JAN-00:10 | 8083.29 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE6 | 35.92 | 0.00 | 01-JAN-00:10 | 13401.81 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 12.88 | 0.00 | 01-JAN-00:10 | 13401.81 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 23.04 | 0.00 | 01-JAN-00:10 | 8012.94 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE7 | 35.66 | 0.00 | 01-JAN-00:10 | 13729.49 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 14.70 | 0.00 | 01-JAN-00:10 | 13729.49 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 20.97 | 0.00 | 01-JAN-00:10 | 7916.00 | 17-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE8 | 42.60 | 0.00 | 01-JAN-00:10 | 16174.75 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 25.22 | 0.00 | 01-JAN-00:10 | 16174.75 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 17.39 | 0.00 | 01-JAN-00:10 | 8181.17 | 17-JUL-13:00 |
EnergyTransfer:HVAC | 641.41 | 0.00 | 01-JAN-00:10 | 246247.21 | 09-JAN-09:10 |
HeatingCoils:EnergyTransfer | 397.68 | 0.00 | 01-JAN-00:10 | 246247.21 | 09-JAN-09:10 |
CoolingCoils:EnergyTransfer | 243.73 | 0.00 | 01-JAN-00:10 | 145960.96 | 17-JUL-16:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 20.418 | -82.966 | 0.000 | 0.000 | 13.447 | 135.611 | 26.357 | 23.037 | 0.000 | 1.726 | 0.004 | 0.000 | -12.769 | 0.000 | -44.199 | -80.663 |
SMSTORE1 | 0.000 | 0.000 | 7.274 | -46.142 | 0.000 | 0.000 | 6.612 | 72.445 | 13.179 | 11.418 | 0.000 | 0.931 | 0.001 | 0.000 | -6.658 | 0.000 | -21.251 | -37.808 |
SMSTORE2 | 0.000 | 0.000 | 9.171 | -32.511 | 0.000 | 0.000 | 4.030 | 51.921 | 10.467 | 11.405 | 0.000 | 0.912 | 0.001 | 0.000 | -6.578 | 0.000 | -21.875 | -26.941 |
SMSTORE3 | 0.000 | 0.000 | 9.924 | -31.518 | 0.000 | 0.000 | 4.038 | 51.921 | 10.467 | 11.421 | 0.000 | 0.911 | 0.001 | 0.000 | -6.516 | 0.000 | -21.783 | -28.865 |
SMSTORE4 | 0.000 | 0.000 | 10.999 | -29.654 | 0.000 | 0.000 | 4.047 | 51.921 | 10.467 | 11.443 | 0.000 | 0.912 | 0.002 | 0.000 | -6.456 | 0.000 | -21.680 | -31.999 |
LGSTORE2 | 0.000 | 0.000 | 21.737 | -48.119 | 0.000 | 0.000 | 13.939 | 74.416 | 19.261 | 23.000 | 0.000 | 1.642 | 0.000 | 0.000 | -12.601 | 0.000 | -39.963 | -53.313 |
SMSTORE5 | 0.000 | 0.000 | 12.445 | -23.875 | 0.000 | 0.000 | 6.973 | 37.208 | 9.631 | 11.489 | 0.000 | 0.913 | 0.003 | 0.000 | -6.305 | 0.000 | -21.694 | -26.785 |
SMSTORE6 | 0.000 | 0.000 | 12.877 | -23.038 | 0.000 | 0.000 | 6.981 | 37.208 | 9.631 | 11.503 | 0.000 | 0.913 | 0.002 | 0.000 | -6.274 | 0.000 | -21.643 | -28.158 |
SMSTORE7 | 0.000 | 0.000 | 14.695 | -20.965 | 0.000 | 0.000 | 7.000 | 37.208 | 9.631 | 11.539 | 0.000 | 0.913 | 0.002 | 0.000 | -6.179 | 0.000 | -21.494 | -32.349 |
SMSTORE8 | 0.000 | 0.000 | 25.218 | -17.386 | 0.000 | 0.000 | 7.037 | 37.208 | 9.631 | 11.641 | 0.000 | 0.964 | 0.004 | 0.000 | -5.834 | 0.000 | -27.784 | -40.694 |
Total Facility | 0.000 | 0.000 | 144.759 | -356.174 | 0.000 | 0.000 | 74.104 | 587.066 | 128.721 | 137.897 | 0.000 | 10.736 | 0.020 | 0.000 | -76.169 | 0.000 | -263.365 | -387.575 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 26-AUG-08:62 | 0.00 | 0.00 | 0.00 | -41635.50 | 0.00 | 0.00 | 91.41 | 3671.72 | 749.03 | 486.33 | 0.00 | 0.00 | 36981.56 | 0.00 | -0.00 | 0.00 | -344.54 | 0.00 |
SMSTORE1 | 14-MAY-17:16 | 0.00 | 0.00 | 0.00 | -23753.59 | 0.00 | 0.00 | 630.36 | 3726.82 | 674.13 | 115.64 | 0.00 | 0.00 | 18874.39 | 0.00 | -0.00 | 0.00 | -267.74 | 0.00 |
SMSTORE2 | 20-OCT-07:01 | 0.00 | 0.00 | 0.00 | -29940.21 | 0.00 | 0.00 | 48.55 | 1773.99 | 374.52 | 0.00 | 0.00 | 0.00 | 28467.43 | 0.00 | -268.04 | 0.00 | -456.23 | 0.00 |
SMSTORE3 | 20-OCT-07:01 | 0.00 | 0.00 | 0.00 | -29708.48 | 0.00 | 0.00 | 48.71 | 1773.99 | 374.52 | 0.00 | 0.00 | 0.00 | 28233.91 | 0.00 | -267.24 | 0.00 | -455.40 | 0.00 |
SMSTORE4 | 28-SEP-07:01 | 0.00 | 0.00 | 0.00 | -27660.40 | 0.00 | 0.00 | 47.33 | 1773.99 | 374.52 | 0.00 | 0.00 | 0.00 | 26031.44 | 0.00 | -186.41 | 0.00 | -380.46 | 0.00 |
LGSTORE2 | 02-AUG-08:62 | 0.00 | 0.00 | 0.00 | -41424.31 | 0.00 | 0.00 | 207.58 | 2766.09 | 749.03 | 331.47 | 0.00 | 0.00 | 37837.69 | 0.00 | -0.00 | 0.00 | -467.56 | 0.00 |
SMSTORE5 | 26-AUG-08:62 | 0.00 | 0.00 | 0.00 | -20948.44 | 0.00 | 0.00 | 101.17 | 1383.05 | 374.52 | 241.02 | 0.00 | 0.00 | 19022.96 | 0.00 | -0.00 | 0.00 | -174.27 | 0.00 |
SMSTORE6 | 26-AUG-08:62 | 0.00 | 0.00 | 0.00 | -20742.62 | 0.00 | 0.00 | 101.77 | 1383.05 | 374.52 | 242.22 | 0.00 | 0.00 | 18814.09 | 0.00 | -0.00 | 0.00 | -173.02 | 0.00 |
SMSTORE7 | 26-AUG-08:62 | 0.00 | 0.00 | 0.00 | -20410.16 | 0.00 | 0.00 | 103.45 | 1383.05 | 374.52 | 245.32 | 0.00 | 0.00 | 18472.94 | 0.00 | -0.00 | 0.00 | -169.11 | 0.00 |
SMSTORE8 | 27-JUL-08:61 | 0.00 | 0.00 | 0.00 | -19929.78 | 0.00 | 0.00 | 105.78 | 1383.05 | 374.52 | 204.34 | 0.00 | 0.00 | 18081.62 | 0.00 | -0.00 | 0.00 | -219.52 | 0.00 |
Total Facility | 27-JUL-08:61 | 0.00 | 0.00 | 0.00 | -195111.55 | 0.00 | 0.00 | 1047.62 | 24043.21 | 5393.02 | 2346.98 | 0.00 | 0.00 | 164734.72 | 0.00 | 0.00 | 0.00 | -2454.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 11-JAN-08:61 | 0.00 | 0.00 | 62492.88 | 0.00 | 0.00 | 0.00 | 152.28 | 367.17 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1203.60 | 0.00 | -1995.10 | -59888.53 |
SMSTORE1 | 28-JAN-08:61 | 0.00 | 0.00 | 32833.28 | 0.00 | 0.00 | 0.00 | 0.00 | 196.15 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -724.32 | 0.00 | -1083.72 | -31258.83 |
SMSTORE2 | 29-JAN-08:61 | 0.00 | 0.00 | 32602.15 | 0.00 | 0.00 | 0.00 | 0.00 | 177.40 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -790.79 | 0.00 | -1152.93 | -30873.28 |
SMSTORE3 | 29-JAN-08:61 | 0.00 | 0.00 | 32467.17 | 0.00 | 0.00 | 0.00 | 0.00 | 177.40 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -785.09 | 0.00 | -1145.56 | -30751.37 |
SMSTORE4 | 29-JAN-08:61 | 0.00 | 0.00 | 32597.50 | 0.00 | 0.00 | 0.00 | 0.00 | 177.40 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -780.16 | 0.00 | -1138.96 | -30893.24 |
LGSTORE2 | 11-JAN-08:61 | 0.00 | 0.00 | 61678.50 | 0.00 | 0.00 | 0.00 | 0.00 | 276.61 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1194.36 | 0.00 | -1694.82 | -59140.84 |
SMSTORE5 | 28-JAN-08:61 | 0.00 | 0.00 | 31493.15 | 0.00 | 0.00 | 0.00 | 0.00 | 138.30 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -696.93 | 0.00 | -1047.77 | -29924.21 |
SMSTORE6 | 11-JAN-08:61 | 0.00 | 0.00 | 31364.30 | 0.00 | 0.00 | 0.00 | 0.00 | 138.30 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -600.48 | 0.00 | -922.39 | -30017.19 |
SMSTORE7 | 28-JAN-08:61 | 0.00 | 0.00 | 31111.49 | 0.00 | 0.00 | 0.00 | 0.00 | 138.30 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -694.49 | 0.00 | -1051.74 | -29541.02 |
SMSTORE8 | 30-JAN-08:61 | 0.00 | 0.00 | 31706.99 | 0.00 | 0.00 | 0.00 | 0.00 | 138.30 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -498.78 | 0.00 | -1125.63 | -30258.34 |
Total Facility | 30-JAN-08:61 | 0.00 | 0.00 | 359077.44 | 0.00 | 0.00 | 0.00 | 434.38 | 6715.10 | 1460.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6271.19 | 0.00 | -10665.25 | -350751.10 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0589 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.0589 | 0.1998 | 1.0000 | 0.4115 | 0.1998 | ||
PSZ-AC_2:2 | 1.1113 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1113 | 0.1851 | 1.0000 | 0.2057 | 0.1851 | ||
PSZ-AC_3:3 | 1.1055 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1086 | 0.1856 | 1.0000 | 0.2057 | 0.1856 | ||
PSZ-AC_4:4 | 1.0984 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1125 | 0.1849 | 1.0000 | 0.2057 | 0.1849 | ||
PSZ-AC_5:5 | 1.1052 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1070 | 0.1858 | 1.0000 | 0.2057 | 0.1858 | ||
PSZ-AC_6:6 | 2.0167 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.0167 | 0.2040 | 1.0000 | 0.4115 | 0.2040 | ||
PSZ-AC_7:7 | 1.0416 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0459 | 0.1967 | 1.0000 | 0.2057 | 0.1967 | ||
PSZ-AC_8:8 | 1.0334 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0380 | 0.1982 | 1.0000 | 0.2057 | 0.1982 | ||
PSZ-AC_9:9 | 1.0188 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0295 | 0.1998 | 1.0000 | 0.2057 | 0.1998 | ||
PSZ-AC_10:10 | 1.0497 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0497 | 0.1960 | 1.0000 | 0.2057 | 0.1960 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0589 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.0589 | 1.0000 | 1.0000 | 0.4115 | 0.1998 | ||
PSZ-AC_2:2 | 1.1113 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1113 | 1.0000 | 1.0000 | 0.2057 | 0.1851 | ||
PSZ-AC_3:3 | 1.1055 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1055 | 1.0000 | 1.0000 | 0.2057 | 0.1861 | ||
PSZ-AC_4:4 | 1.0984 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0984 | 1.0000 | 1.0000 | 0.2057 | 0.1873 | ||
PSZ-AC_5:5 | 1.1052 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1052 | 1.0000 | 1.0000 | 0.2057 | 0.1862 | ||
PSZ-AC_6:6 | 2.0167 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.0167 | 1.0000 | 1.0000 | 0.4115 | 0.2040 | ||
PSZ-AC_7:7 | 1.0416 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0416 | 1.0000 | 1.0000 | 0.2057 | 0.1975 | ||
PSZ-AC_8:8 | 1.0334 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0334 | 1.0000 | 1.0000 | 0.2057 | 0.1991 | ||
PSZ-AC_9:9 | 1.0188 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0188 | 1.0000 | 1.0000 | 0.2057 | 0.2019 | ||
PSZ-AC_10:10 | 1.0497 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0497 | 1.0000 | 1.0000 | 0.2057 | 0.1960 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.0589 | 2.0589 | 2.0589 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.1113 | 1.1113 | 1.1113 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.1055 | 1.1055 | 1.1055 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.0984 | 1.0984 | 1.0984 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.1052 | 1.1052 | 1.1052 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.0167 | 2.0167 | 2.0167 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.0416 | 1.0416 | 1.0416 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.0334 | 1.0334 | 1.0334 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.0188 | 1.0188 | 1.0188 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0497 | 1.0497 | 1.0497 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0589 | 2.0589 | 2.0589 | 2.0589 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1113 | 1.1113 | 1.1113 | 1.1113 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1055 | 1.1086 | 1.1055 | 1.1055 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0984 | 1.1125 | 1.0984 | 1.0984 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1052 | 1.1070 | 1.1052 | 1.1052 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.0167 | 2.0167 | 2.0167 | 2.0167 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0416 | 1.0459 | 1.0416 | 1.0416 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0334 | 1.0380 | 1.0334 | 1.0334 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0188 | 1.0295 | 1.0188 | 1.0188 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0497 | 1.0497 | 1.0497 | 1.0497 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.0589 | 2.0589 | 2.0589 | 0.4115 | 0.2361 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.1113 | 1.1113 | 1.1113 | 0.2057 | 0.2378 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.1055 | 1.1055 | 1.1055 | 0.2057 | 0.2351 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.0984 | 1.0984 | 1.0984 | 0.2057 | 0.2340 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.1052 | 1.1052 | 1.1052 | 0.2057 | 0.2318 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.0167 | 2.0167 | 2.0167 | 0.4115 | 0.2438 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.0416 | 1.0416 | 1.0416 | 0.2057 | 0.2267 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.0334 | 1.0334 | 1.0334 | 0.2057 | 0.2270 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.0188 | 1.0188 | 1.0188 | 0.2057 | 0.2241 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0497 | 1.0497 | 1.0497 | 0.2057 | 0.1963 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0589 | 2.0589 | 2.0589 | 2.0589 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1113 | 1.1113 | 1.1113 | 1.1113 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1055 | 1.1055 | 1.1055 | 1.1055 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0984 | 1.0984 | 1.0984 | 1.0984 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1052 | 1.1052 | 1.1052 | 1.1052 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.0167 | 2.0167 | 2.0167 | 2.0167 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0416 | 1.0416 | 1.0416 | 1.0416 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0334 | 1.0334 | 1.0334 | 1.0334 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0188 | 1.0188 | 1.0188 | 1.0188 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0497 | 1.0497 | 1.0497 | 1.0497 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:24
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 497.10 | 307809.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 66.36 | 45019.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 587.07 | 36581.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 110.57 | 7048.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 239.05 | 13885.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 65.95 | 11898.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1197.71 |
Natural Gas | 0.00 | 497.10 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1694.81 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 280.85 |
Space Heating | 0.00 |
Space Cooling | 31.75 |
Fans (All) | 114.36 |
Service Water Heating | 31.55 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 572.98 |
Subtotal | 572.98 |
Natural Gas [MJ/m2] | |
Space Heating | 237.81 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 237.81 |
Subtotal | 237.81 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 34.64 |
Space Heating | 29.33 |
Space Cooling | 3.92 |
Fans (All) | 14.10 |
Service Water Heating | 3.89 |
Receptacle Equipment | 7.60 |
Miscellaneous | 6.52 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5131. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159033E+12 |
February | 0.000 | 0.850801E+11 |
March | 0.000 | 0.623882E+11 |
April | 0.000 | 0.199611E+11 |
May | 0.000 | 0.126608E+11 |
June | 0.000 | 0.112006E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.800325E+09 |
October | 0.000 | 0.624954E+10 |
November | 0.000 | 0.413937E+11 |
December | 0.000 | 0.109421E+12 |
Annual Sum or Average | 0.497100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.159033E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159033E+12 |
February | 0.000 | 0.850801E+11 |
March | 0.000 | 0.623882E+11 |
April | 0.000 | 0.199611E+11 |
May | 0.000 | 0.126608E+11 |
June | 0.000 | 0.112006E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.800325E+09 |
October | 0.000 | 0.624954E+10 |
November | 0.000 | 0.413937E+11 |
December | 0.000 | 0.109421E+12 |
Annual Sum or Average | 0.497100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.159033E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Meter
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159033E+12 |
February | 0.000 | 0.850801E+11 |
March | 0.000 | 0.623882E+11 |
April | 0.000 | 0.199611E+11 |
May | 0.000 | 0.126608E+11 |
June | 0.000 | 0.112006E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.800325E+09 |
October | 0.000 | 0.624954E+10 |
November | 0.000 | 0.413937E+11 |
December | 0.000 | 0.109421E+12 |
Annual Sum or Average | 0.497100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.159033E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159033E+12 |
February | 0.000 | 0.850801E+11 |
March | 0.000 | 0.623882E+11 |
April | 0.000 | 0.199611E+11 |
May | 0.000 | 0.126608E+11 |
June | 0.000 | 0.112006E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.800325E+09 |
October | 0.000 | 0.624954E+10 |
November | 0.000 | 0.413937E+11 |
December | 0.000 | 0.109421E+12 |
Annual Sum or Average | 0.497100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.159033E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159033E+12 |
February | 0.000 | 0.850801E+11 |
March | 0.000 | 0.623882E+11 |
April | 0.000 | 0.199611E+11 |
May | 0.000 | 0.126608E+11 |
June | 0.000 | 0.112006E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.800325E+09 |
October | 0.000 | 0.624954E+10 |
November | 0.000 | 0.413937E+11 |
December | 0.000 | 0.109421E+12 |
Annual Sum or Average | 0.497100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.159033E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159033E+12 |
February | 0.000 | 0.850801E+11 |
March | 0.000 | 0.623882E+11 |
April | 0.000 | 0.199611E+11 |
May | 0.000 | 0.126608E+11 |
June | 0.000 | 0.112006E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.800325E+09 |
October | 0.000 | 0.624954E+10 |
November | 0.000 | 0.413937E+11 |
December | 0.000 | 0.109421E+12 |
Annual Sum or Average | 0.497100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.159033E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159033E+12 |
February | 0.000 | 0.850801E+11 |
March | 0.000 | 0.623882E+11 |
April | 0.000 | 0.199611E+11 |
May | 0.000 | 0.126608E+11 |
June | 0.000 | 0.112006E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.800325E+09 |
October | 0.000 | 0.624954E+10 |
November | 0.000 | 0.413937E+11 |
December | 0.000 | 0.109421E+12 |
Annual Sum or Average | 0.497100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.159033E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Meter
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159033E+12 |
February | 0.000 | 0.850801E+11 |
March | 0.000 | 0.623882E+11 |
April | 0.000 | 0.199611E+11 |
May | 0.000 | 0.126608E+11 |
June | 0.000 | 0.112006E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.800325E+09 |
October | 0.000 | 0.624954E+10 |
November | 0.000 | 0.413937E+11 |
December | 0.000 | 0.109421E+12 |
Annual Sum or Average | 0.497100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.159033E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Meter
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159033E+12 |
February | 0.000 | 0.850801E+11 |
March | 0.000 | 0.623882E+11 |
April | 0.000 | 0.199611E+11 |
May | 0.000 | 0.126608E+11 |
June | 0.000 | 0.112006E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.800325E+09 |
October | 0.000 | 0.624954E+10 |
November | 0.000 | 0.413937E+11 |
December | 0.000 | 0.109421E+12 |
Annual Sum or Average | 0.497100E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.159033E+12 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128864E+10 | 18687.43 | 28-JAN-00:01 | -29.2 | -29.5 | 0.567143E+09 | 680.94 | 14-JAN-13:20 | 10.20 | 4.86 |
February | 0.224347E+10 | 15242.90 | 04-FEB-00:01 | -21.0 | -21.3 | 0.528571E+09 | 898.99 | 26-FEB-17:19 | 14.10 | 5.33 |
March | 0.317272E+10 | 13608.18 | 04-MAR-00:02 | -17.2 | -17.7 | 0.570929E+09 | 730.02 | 26-MAR-17:00 | 8.90 | 1.04 |
April | 0.435028E+10 | 9137.27 | 30-APR-08:03 | -2.8 | -4.0 | 0.622993E+09 | 898.99 | 16-APR-17:19 | 19.80 | 8.87 |
May | 0.653161E+10 | 34772.45 | 20-MAY-08:62 | 20.10 | 12.38 | 0.682540E+09 | 899.01 | 19-MAY-12:09 | 24.27 | 14.49 |
June | 0.108548E+11 | 37845.84 | 30-JUN-08:62 | 16.47 | 11.67 | 0.717229E+09 | 899.05 | 04-JUN-12:09 | 23.12 | 14.05 |
July | 0.148551E+11 | 40531.36 | 27-JUL-08:61 | 14.68 | 10.38 | 0.754313E+09 | 899.06 | 01-JUL-12:00 | 26.70 | 16.71 |
August | 0.141762E+11 | 41636.17 | 26-AUG-08:62 | 16.28 | 9.48 | 0.741587E+09 | 899.03 | 20-AUG-17:10 | 23.22 | 14.10 |
September | 0.112684E+11 | 40425.23 | 09-SEP-08:62 | 17.15 | 9.14 | 0.710628E+09 | 899.08 | 10-SEP-12:50 | 18.77 | 13.26 |
October | 0.795723E+10 | 32623.76 | 19-OCT-08:62 | 14.37 | 6.91 | 0.697578E+09 | 898.99 | 29-OCT-17:19 | 10.20 | 4.47 |
November | 0.428897E+10 | 12814.58 | 27-NOV-09:04 | -11.7 | -12.7 | 0.599138E+09 | 898.99 | 05-NOV-17:19 | 12.73 | 5.65 |
December | 0.197859E+10 | 16252.60 | 29-DEC-00:01 | -23.6 | -23.9 | 0.571322E+09 | 680.12 | 09-DEC-13:09 | 3.95 | 0.92 |
Annual Sum or Average | 0.829659E+11 | 0.776397E+10 | ||||||||
Minimum of Months | 0.128864E+10 | 9137.27 | -29.2 | -29.5 | 0.528571E+09 | 680.12 | 3.95 | 0.92 | ||
Maximum of Months | 0.148551E+11 | 41636.17 | 20.10 | 12.38 | 0.754313E+09 | 899.08 | 26.70 | 16.71 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.592114E+09 | 8741.16 | 27-JAN-20:01 | -26.9 | -27.2 | 0.292335E+09 | 420.55 | 01-JAN-18:00 | 2.80 | -0.1 |
February | 0.103987E+10 | 16830.17 | 26-FEB-18:15 | 10.17 | 3.54 | 0.278136E+09 | 449.50 | 26-FEB-17:40 | 12.60 | 4.70 |
March | 0.155441E+10 | 7400.57 | 05-MAR-09:04 | -16.9 | -17.9 | 0.305563E+09 | 444.49 | 26-MAR-17:00 | 8.90 | 1.04 |
April | 0.236217E+10 | 19690.68 | 25-APR-20:01 | 12.12 | 5.44 | 0.330827E+09 | 449.50 | 08-APR-12:09 | 12.80 | 6.16 |
May | 0.385496E+10 | 23753.53 | 14-MAY-17:16 | 13.87 | 4.87 | 0.351124E+09 | 449.51 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.644914E+10 | 21867.89 | 20-JUN-08:62 | 16.47 | 9.92 | 0.357753E+09 | 449.52 | 04-JUN-12:09 | 23.12 | 14.05 |
July | 0.841400E+10 | 22225.12 | 27-JUL-08:61 | 14.68 | 10.38 | 0.375416E+09 | 449.53 | 09-JUL-17:49 | 27.88 | 13.09 |
August | 0.807687E+10 | 22986.45 | 02-AUG-08:62 | 11.88 | 8.37 | 0.369386E+09 | 449.51 | 20-AUG-12:09 | 18.98 | 12.62 |
September | 0.636000E+10 | 23309.28 | 26-SEP-08:62 | 8.58 | 6.50 | 0.357779E+09 | 449.54 | 10-SEP-12:50 | 18.77 | 13.26 |
October | 0.433127E+10 | 22885.14 | 19-OCT-08:62 | 14.37 | 6.91 | 0.359758E+09 | 449.49 | 29-OCT-17:19 | 10.20 | 4.47 |
November | 0.217715E+10 | 19801.71 | 05-NOV-17:01 | 13.02 | 5.76 | 0.317673E+09 | 449.49 | 05-NOV-17:19 | 12.73 | 5.65 |
December | 0.929767E+09 | 7718.29 | 30-DEC-09:04 | -18.7 | -19.2 | 0.297920E+09 | 413.53 | 10-DEC-18:00 | 0.00 | -3.2 |
Annual Sum or Average | 0.461417E+11 | 0.399367E+10 | ||||||||
Minimum of Months | 0.592114E+09 | 7400.57 | -26.9 | -27.2 | 0.278136E+09 | 413.53 | 0.00 | -3.2 | ||
Maximum of Months | 0.841400E+10 | 23753.53 | 16.47 | 10.38 | 0.375416E+09 | 449.54 | 27.88 | 14.05 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.311983E+09 | 7316.42 | 19-JAN-08:03 | -17.3 | -17.7 | 0.169192E+09 | 353.42 | 14-JAN-13:20 | 10.20 | 4.86 |
February | 0.681589E+09 | 7688.68 | 10-FEB-08:04 | -18.8 | -19.2 | 0.159836E+09 | 432.46 | 25-FEB-13:00 | 15.00 | 5.03 |
March | 0.122584E+10 | 6094.97 | 05-MAR-09:04 | -16.9 | -17.9 | 0.179174E+09 | 375.09 | 18-MAR-12:00 | 11.70 | 3.92 |
April | 0.170218E+10 | 10400.29 | 08-APR-07:01 | 8.40 | 5.02 | 0.190056E+09 | 449.49 | 08-APR-12:30 | 12.80 | 6.12 |
May | 0.253487E+10 | 21590.29 | 21-MAY-08:62 | 12.88 | 9.34 | 0.207585E+09 | 449.50 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.450813E+10 | 26869.85 | 08-JUN-07:01 | 8.98 | 5.10 | 0.220907E+09 | 449.51 | 24-JUN-12:09 | 27.07 | 16.02 |
July | 0.597939E+10 | 23580.33 | 12-JUL-07:02 | 14.37 | 8.07 | 0.224298E+09 | 449.53 | 01-JUL-12:00 | 26.70 | 16.71 |
August | 0.586637E+10 | 25868.88 | 28-AUG-07:01 | 10.33 | 6.39 | 0.229838E+09 | 449.49 | 12-AUG-12:00 | 30.00 | 14.95 |
September | 0.446226E+10 | 27832.07 | 28-SEP-07:01 | 7.95 | 4.26 | 0.213568E+09 | 449.50 | 23-SEP-12:09 | 21.28 | 11.86 |
October | 0.305752E+10 | 29942.16 | 20-OCT-07:01 | 4.18 | 1.89 | 0.208892E+09 | 449.49 | 28-OCT-12:09 | 18.12 | 9.55 |
November | 0.157530E+10 | 11019.54 | 05-NOV-08:61 | 8.43 | 3.51 | 0.180272E+09 | 449.49 | 04-NOV-12:09 | 16.20 | 7.85 |
December | 0.606297E+09 | 6138.22 | 15-DEC-08:02 | -11.8 | -12.0 | 0.169465E+09 | 351.70 | 02-DEC-13:00 | 9.40 | 4.25 |
Annual Sum or Average | 0.325117E+11 | 0.235308E+10 | ||||||||
Minimum of Months | 0.311983E+09 | 6094.97 | -18.8 | -19.2 | 0.159836E+09 | 351.70 | 9.40 | 3.92 | ||
Maximum of Months | 0.597939E+10 | 29942.16 | 14.37 | 9.34 | 0.229838E+09 | 449.53 | 30.00 | 16.71 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239717E+09 | 7371.21 | 19-JAN-08:03 | -17.3 | -17.7 | 0.169114E+09 | 348.14 | 14-JAN-13:20 | 10.20 | 4.86 |
February | 0.592443E+09 | 7281.39 | 03-FEB-08:04 | -17.1 | -17.4 | 0.159139E+09 | 426.64 | 25-FEB-13:00 | 15.00 | 5.03 |
March | 0.109334E+10 | 5851.21 | 04-MAR-08:04 | -19.9 | -20.6 | 0.178142E+09 | 370.64 | 18-MAR-12:00 | 11.70 | 3.92 |
April | 0.154460E+10 | 6572.30 | 08-APR-07:01 | 8.40 | 5.02 | 0.188487E+09 | 447.52 | 08-APR-12:39 | 12.80 | 6.10 |
May | 0.240510E+10 | 21660.84 | 21-MAY-08:62 | 12.88 | 9.34 | 0.206654E+09 | 449.50 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.447751E+10 | 26135.02 | 08-JUN-07:01 | 8.98 | 5.10 | 0.220852E+09 | 449.51 | 24-JUN-12:09 | 27.07 | 16.02 |
July | 0.600513E+10 | 23657.67 | 12-JUL-07:02 | 14.37 | 8.07 | 0.224299E+09 | 449.53 | 01-JUL-12:00 | 26.70 | 16.71 |
August | 0.588420E+10 | 25996.29 | 28-AUG-07:01 | 10.33 | 6.39 | 0.229827E+09 | 449.49 | 12-AUG-12:00 | 30.00 | 14.95 |
September | 0.442270E+10 | 27924.23 | 28-SEP-07:01 | 7.95 | 4.26 | 0.213241E+09 | 449.50 | 23-SEP-12:09 | 21.28 | 11.86 |
October | 0.292209E+10 | 29710.40 | 20-OCT-07:01 | 4.18 | 1.89 | 0.207974E+09 | 449.49 | 28-OCT-12:09 | 18.12 | 9.55 |
November | 0.142866E+10 | 6993.35 | 05-NOV-08:61 | 8.43 | 3.51 | 0.178713E+09 | 449.49 | 04-NOV-12:09 | 16.20 | 7.85 |
December | 0.503228E+09 | 6401.43 | 14-DEC-08:03 | -13.2 | -13.3 | 0.169243E+09 | 347.19 | 02-DEC-13:00 | 9.40 | 4.25 |
Annual Sum or Average | 0.315187E+11 | 0.234569E+10 | ||||||||
Minimum of Months | 0.239717E+09 | 5851.21 | -19.9 | -20.6 | 0.159139E+09 | 347.19 | 9.40 | 3.92 | ||
Maximum of Months | 0.600513E+10 | 29710.40 | 14.37 | 9.34 | 0.229827E+09 | 449.53 | 30.00 | 16.71 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172364E+09 | 6059.12 | 28-JAN-08:04 | -25.1 | -25.5 | 0.169055E+09 | 341.98 | 14-JAN-13:20 | 10.20 | 4.86 |
February | 0.497275E+09 | 7494.05 | 09-FEB-08:04 | -18.3 | -18.6 | 0.158396E+09 | 419.06 | 25-FEB-13:00 | 15.00 | 5.03 |
March | 0.934745E+09 | 7796.37 | 04-MAR-08:04 | -19.9 | -20.6 | 0.177083E+09 | 365.28 | 18-MAR-12:00 | 11.70 | 3.92 |
April | 0.134452E+10 | 4630.02 | 29-APR-07:03 | -4.5 | -6.1 | 0.186473E+09 | 439.29 | 08-APR-12:39 | 12.80 | 6.10 |
May | 0.219823E+10 | 19629.98 | 21-MAY-08:62 | 12.88 | 9.34 | 0.205372E+09 | 449.50 | 13-MAY-12:09 | 23.40 | 10.96 |
June | 0.429415E+10 | 25129.84 | 07-JUN-07:01 | 9.68 | 6.15 | 0.220686E+09 | 449.51 | 24-JUN-12:09 | 27.07 | 16.02 |
July | 0.584595E+10 | 23444.54 | 12-JUL-07:02 | 14.37 | 8.07 | 0.224269E+09 | 449.53 | 01-JUL-12:00 | 26.70 | 16.71 |
August | 0.571541E+10 | 25772.52 | 28-AUG-07:01 | 10.33 | 6.39 | 0.229716E+09 | 449.49 | 12-AUG-12:00 | 30.00 | 14.95 |
September | 0.425473E+10 | 27662.28 | 28-SEP-07:01 | 7.95 | 4.26 | 0.212700E+09 | 449.50 | 23-SEP-12:09 | 21.28 | 11.86 |
October | 0.273235E+10 | 25973.04 | 19-OCT-07:01 | 11.57 | 5.30 | 0.206633E+09 | 449.49 | 28-OCT-12:09 | 18.12 | 9.55 |
November | 0.127192E+10 | 6434.74 | 27-NOV-08:04 | -12.7 | -13.5 | 0.176660E+09 | 449.49 | 04-NOV-12:09 | 16.20 | 7.85 |
December | 0.392242E+09 | 6528.85 | 14-DEC-08:03 | -13.2 | -13.3 | 0.169078E+09 | 342.20 | 02-DEC-13:00 | 9.40 | 4.25 |
Annual Sum or Average | 0.296539E+11 | 0.233612E+10 | ||||||||
Minimum of Months | 0.172364E+09 | 4630.02 | -25.1 | -25.5 | 0.158396E+09 | 341.98 | 9.40 | 3.92 | ||
Maximum of Months | 0.584595E+10 | 27662.28 | 14.37 | 9.34 | 0.229716E+09 | 449.53 | 30.00 | 16.71 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143030E+09 | 12248.14 | 18-JAN-09:04 | -10.1 | -10.8 | 0.577737E+09 | 906.82 | 14-JAN-15:09 | 10.50 | 5.05 |
February | 0.669696E+09 | 10112.97 | 23-FEB-09:04 | -6.7 | -7.4 | 0.539483E+09 | 1117.97 | 25-FEB-15:00 | 15.00 | 5.18 |
March | 0.130939E+10 | 9851.95 | 07-MAR-09:04 | -4.0 | -5.7 | 0.601941E+09 | 997.91 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.197593E+10 | 8593.69 | 29-APR-08:02 | -1.8 | -4.3 | 0.628888E+09 | 1136.30 | 01-APR-14:00 | 18.30 | 6.98 |
May | 0.339878E+10 | 33955.61 | 20-MAY-08:62 | 20.10 | 12.38 | 0.693447E+09 | 1198.64 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.713882E+10 | 38298.54 | 27-JUN-08:62 | 17.30 | 10.28 | 0.755717E+09 | 1198.67 | 03-JUN-14:09 | 24.18 | 14.31 |
July | 0.997529E+10 | 40588.80 | 27-JUL-08:61 | 14.68 | 10.38 | 0.767568E+09 | 1198.67 | 15-JUL-14:09 | 32.20 | 18.27 |
August | 0.975889E+10 | 41431.76 | 02-AUG-08:62 | 11.88 | 8.37 | 0.786447E+09 | 1198.64 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.707167E+10 | 39830.62 | 09-SEP-08:62 | 17.15 | 9.14 | 0.726498E+09 | 1198.66 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.435366E+10 | 31023.97 | 19-OCT-08:62 | 14.37 | 6.91 | 0.696905E+09 | 1198.63 | 28-OCT-14:00 | 20.00 | 9.78 |
November | 0.192423E+10 | 13887.04 | 26-NOV-10:04 | -15.1 | -15.9 | 0.589333E+09 | 1198.65 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 0.400083E+09 | 12840.12 | 14-DEC-09:04 | -12.3 | -12.4 | 0.579052E+09 | 906.82 | 02-DEC-15:00 | 3.90 | 1.29 |
Annual Sum or Average | 0.481195E+11 | 0.794302E+10 | ||||||||
Minimum of Months | 0.143030E+09 | 8593.69 | -15.1 | -15.9 | 0.539483E+09 | 906.82 | 3.90 | 1.29 | ||
Maximum of Months | 0.997529E+10 | 41431.76 | 20.10 | 12.38 | 0.786447E+09 | 1198.67 | 32.20 | 18.27 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57229024.58 | 6056.17 | 18-JAN-09:04 | -10.1 | -10.8 | 0.288859E+09 | 453.41 | 14-JAN-15:09 | 10.50 | 5.05 |
February | 0.300051E+09 | 4996.93 | 23-FEB-09:04 | -6.7 | -7.4 | 0.269478E+09 | 555.87 | 25-FEB-15:00 | 15.00 | 5.18 |
March | 0.592535E+09 | 5290.28 | 03-MAR-09:04 | -13.4 | -14.2 | 0.300749E+09 | 495.82 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.885238E+09 | 4270.98 | 28-APR-08:02 | -2.7 | -4.0 | 0.313393E+09 | 561.86 | 01-APR-14:00 | 18.30 | 6.98 |
May | 0.161686E+10 | 17399.03 | 20-MAY-08:62 | 20.10 | 12.38 | 0.346105E+09 | 599.32 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.359993E+10 | 19536.83 | 25-JUN-09:02 | 17.15 | 11.94 | 0.377802E+09 | 599.33 | 03-JUN-14:09 | 24.18 | 14.31 |
July | 0.511635E+10 | 20848.13 | 27-JUL-08:61 | 14.68 | 10.38 | 0.383764E+09 | 599.34 | 15-JUL-14:09 | 32.20 | 18.27 |
August | 0.498558E+10 | 20949.29 | 26-AUG-08:62 | 16.28 | 9.48 | 0.393201E+09 | 599.32 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.355835E+10 | 20450.56 | 09-SEP-08:62 | 17.15 | 9.14 | 0.363092E+09 | 599.33 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.210574E+10 | 14484.76 | 19-OCT-08:62 | 14.37 | 6.91 | 0.348110E+09 | 599.32 | 21-OCT-14:00 | 16.10 | 8.09 |
November | 0.882407E+09 | 6891.69 | 26-NOV-10:04 | -15.1 | -15.9 | 0.293964E+09 | 599.32 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 0.174681E+09 | 6352.20 | 14-DEC-09:04 | -12.3 | -12.4 | 0.289513E+09 | 453.41 | 02-DEC-15:50 | 4.45 | 1.59 |
Annual Sum or Average | 0.238749E+11 | 0.396803E+10 | ||||||||
Minimum of Months | 57229024.58 | 4270.98 | -15.1 | -15.9 | 0.269478E+09 | 453.41 | 4.45 | 1.59 | ||
Maximum of Months | 0.511635E+10 | 20949.29 | 20.10 | 12.38 | 0.393201E+09 | 599.34 | 32.20 | 18.27 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 48863056.12 | 6027.28 | 18-JAN-09:04 | -10.1 | -10.8 | 0.288858E+09 | 453.41 | 14-JAN-15:09 | 10.50 | 5.05 |
February | 0.271126E+09 | 5092.97 | 23-FEB-09:04 | -6.7 | -7.4 | 0.268914E+09 | 550.49 | 25-FEB-15:00 | 15.00 | 5.18 |
March | 0.539931E+09 | 6455.01 | 03-MAR-09:04 | -13.4 | -14.2 | 0.300279E+09 | 491.40 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.805652E+09 | 4372.25 | 28-APR-08:02 | -2.7 | -4.0 | 0.311620E+09 | 557.04 | 01-APR-14:00 | 18.30 | 6.98 |
May | 0.151244E+10 | 15930.59 | 20-MAY-08:62 | 20.10 | 12.38 | 0.344972E+09 | 599.32 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.348913E+10 | 19330.44 | 25-JUN-09:02 | 17.15 | 11.94 | 0.377583E+09 | 599.33 | 03-JUN-14:09 | 24.18 | 14.31 |
July | 0.502050E+10 | 20645.26 | 27-JUL-08:61 | 14.68 | 10.38 | 0.383738E+09 | 599.34 | 15-JUL-14:09 | 32.20 | 18.27 |
August | 0.488831E+10 | 20743.47 | 26-AUG-08:62 | 16.28 | 9.48 | 0.393091E+09 | 599.32 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.346622E+10 | 20268.38 | 09-SEP-08:62 | 17.15 | 9.14 | 0.362551E+09 | 599.33 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.201739E+10 | 13234.53 | 19-OCT-08:62 | 14.37 | 6.91 | 0.346756E+09 | 599.32 | 21-OCT-14:00 | 16.10 | 8.09 |
November | 0.824842E+09 | 6971.32 | 26-NOV-10:04 | -15.1 | -15.9 | 0.292458E+09 | 599.32 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 0.153575E+09 | 6417.10 | 15-DEC-09:04 | -12.1 | -12.3 | 0.289458E+09 | 453.41 | 02-DEC-15:39 | 5.00 | 1.88 |
Annual Sum or Average | 0.230380E+11 | 0.396028E+10 | ||||||||
Minimum of Months | 48863056.12 | 4372.25 | -15.1 | -15.9 | 0.268914E+09 | 453.41 | 5.00 | 1.88 | ||
Maximum of Months | 0.502050E+10 | 20743.47 | 20.10 | 12.38 | 0.393091E+09 | 599.34 | 32.20 | 18.27 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26723368.89 | 5909.98 | 05-JAN-09:04 | -9.3 | -9.4 | 0.288828E+09 | 453.41 | 14-JAN-15:09 | 10.50 | 5.05 |
February | 0.198338E+09 | 5362.37 | 23-FEB-09:04 | -6.7 | -7.4 | 0.267598E+09 | 536.11 | 25-FEB-15:00 | 15.00 | 5.18 |
March | 0.384117E+09 | 6700.67 | 03-MAR-09:04 | -13.4 | -14.2 | 0.299206E+09 | 479.33 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.609590E+09 | 4260.48 | 30-APR-09:04 | -2.3 | -3.7 | 0.307266E+09 | 543.21 | 22-APR-14:00 | 16.70 | 9.27 |
May | 0.125062E+10 | 10689.35 | 20-MAY-08:62 | 20.10 | 12.38 | 0.342030E+09 | 599.32 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.319944E+10 | 18978.47 | 25-JUN-09:02 | 17.15 | 11.94 | 0.376876E+09 | 599.33 | 03-JUN-14:09 | 24.18 | 14.31 |
July | 0.481436E+10 | 20327.88 | 27-JUL-08:61 | 14.68 | 10.38 | 0.383649E+09 | 599.34 | 15-JUL-14:09 | 32.20 | 18.27 |
August | 0.467597E+10 | 20411.02 | 26-AUG-08:62 | 16.28 | 9.48 | 0.392761E+09 | 599.32 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.324666E+10 | 19970.42 | 09-SEP-08:62 | 17.15 | 9.14 | 0.361149E+09 | 599.33 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.179160E+10 | 9381.64 | 19-OCT-08:62 | 14.37 | 6.91 | 0.343228E+09 | 599.32 | 21-OCT-14:00 | 16.10 | 8.09 |
November | 0.675342E+09 | 7021.10 | 26-NOV-10:04 | -15.1 | -15.9 | 0.289415E+09 | 599.32 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 92363252.67 | 6501.95 | 14-DEC-09:04 | -12.3 | -12.4 | 0.289366E+09 | 453.41 | 02-DEC-15:20 | 6.10 | 2.44 |
Annual Sum or Average | 0.209651E+11 | 0.394137E+10 | ||||||||
Minimum of Months | 26723368.89 | 4260.48 | -15.1 | -15.9 | 0.267598E+09 | 453.41 | 6.10 | 2.44 | ||
Maximum of Months | 0.481436E+10 | 20411.02 | 20.10 | 12.38 | 0.392761E+09 | 599.34 | 32.20 | 18.27 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5615294.15 | 4638.61 | 04-JAN-09:04 | -4.1 | -6.5 | 0.288813E+09 | 453.41 | 14-JAN-15:00 | 10.00 | 4.55 |
February | 74451435.18 | 4676.13 | 22-FEB-09:04 | -4.0 | -5.5 | 0.265477E+09 | 504.13 | 27-FEB-15:00 | 18.90 | 7.03 |
March | 85886163.78 | 4665.69 | 25-MAR-08:04 | -3.8 | -5.0 | 0.298005E+09 | 453.41 | 18-MAR-14:00 | 12.20 | 4.15 |
April | 0.231948E+09 | 4538.35 | 28-APR-08:04 | -2.7 | -4.0 | 0.299484E+09 | 531.90 | 06-APR-16:10 | 22.02 | 10.90 |
May | 0.772107E+09 | 4210.55 | 20-MAY-16:00 | 30.00 | 15.19 | 0.335533E+09 | 599.32 | 27-MAY-14:00 | 23.30 | 12.28 |
June | 0.267953E+10 | 18899.14 | 25-JUN-09:02 | 17.15 | 11.94 | 0.374308E+09 | 599.33 | 03-JUN-14:09 | 24.18 | 14.31 |
July | 0.462150E+10 | 19930.34 | 27-JUL-08:61 | 14.68 | 10.38 | 0.383262E+09 | 599.34 | 15-JUL-14:09 | 32.20 | 18.27 |
August | 0.442614E+10 | 19650.92 | 13-AUG-09:01 | 17.98 | 10.96 | 0.391644E+09 | 599.32 | 19-AUG-14:09 | 21.28 | 11.33 |
September | 0.282736E+10 | 19276.74 | 05-SEP-08:61 | 19.03 | 12.19 | 0.358057E+09 | 599.33 | 09-SEP-14:09 | 27.70 | 13.65 |
October | 0.130450E+10 | 4723.91 | 10-OCT-08:04 | -3.7 | -4.5 | 0.335436E+09 | 599.32 | 21-OCT-14:00 | 16.10 | 8.09 |
November | 0.344436E+09 | 5380.38 | 11-NOV-10:04 | -6.7 | -7.8 | 0.284589E+09 | 598.96 | 04-NOV-14:00 | 16.70 | 7.95 |
December | 12989216.71 | 5274.81 | 22-DEC-09:04 | -6.7 | -7.1 | 0.289302E+09 | 453.41 | 09-DEC-15:09 | 8.27 | 3.16 |
Annual Sum or Average | 0.173865E+11 | 0.390391E+10 | ||||||||
Minimum of Months | 5615294.15 | 4210.55 | -6.7 | -7.8 | 0.265477E+09 | 453.41 | 8.27 | 3.16 | ||
Maximum of Months | 0.462150E+10 | 19930.34 | 30.00 | 15.19 | 0.391644E+09 | 599.34 | 32.20 | 18.27 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.767225E+10 | 62492.84 | 11-JAN-08:61 | -17.3 |
February | 0.339921E+10 | 61944.48 | 04-FEB-08:61 | -20.0 |
March | 0.213923E+10 | 62143.64 | 06-MAR-08:61 | -16.9 |
April | 0.560606E+09 | 53008.19 | 29-APR-08:61 | -1.8 |
May | 0.395763E+09 | 54366.79 | 09-MAY-08:61 | 2.07 |
June | 0.188750E+09 | 2720.02 | 23-JUN-08:04 | 23.27 |
July | 0.182833E+09 | 3870.54 | 18-JUL-08:05 | 26.57 |
August | 0.195318E+09 | 3624.03 | 07-AUG-08:05 | 25.97 |
September | 0.190027E+09 | 3369.48 | 04-SEP-07:04 | 20.02 |
October | 0.222259E+09 | 23452.54 | 10-OCT-08:61 | -3.7 |
November | 0.112614E+10 | 54029.99 | 30-NOV-09:01 | 1.10 |
December | 0.414557E+10 | 62170.53 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.204179E+11 | |||
Minimum of Months | 0.182833E+09 | 2720.02 | -27.6 | |
Maximum of Months | 0.767225E+10 | 62492.84 | 26.57 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285280E+10 | 32833.30 | 28-JAN-08:61 | -25.1 |
February | 0.114285E+10 | 28691.22 | 06-FEB-09:01 | 1.10 |
March | 0.610801E+09 | 27549.80 | 07-MAR-09:01 | -4.0 |
April | 0.151156E+09 | 9241.23 | 29-APR-08:61 | -1.8 |
May | 0.129380E+09 | 2881.11 | 09-MAY-08:50 | 3.53 |
June | 0.104420E+09 | 1648.19 | 25-JUN-07:03 | 14.18 |
July | 0.100350E+09 | 2105.10 | 18-JUL-08:05 | 26.57 |
August | 0.108074E+09 | 1972.95 | 07-AUG-08:05 | 25.97 |
September | 0.104911E+09 | 1915.16 | 04-SEP-07:04 | 20.02 |
October | 0.113856E+09 | 1290.79 | 29-OCT-07:02 | 9.32 |
November | 0.392013E+09 | 27488.01 | 28-NOV-09:01 | -4.2 |
December | 0.146316E+10 | 32698.12 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.727378E+10 | |||
Minimum of Months | 0.100350E+09 | 1290.79 | -27.6 | |
Maximum of Months | 0.285280E+10 | 32833.30 | 26.57 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.335115E+10 | 32602.16 | 29-JAN-08:61 | -29.8 |
February | 0.142415E+10 | 32282.23 | 05-FEB-08:61 | -20.1 |
March | 0.809683E+09 | 32191.64 | 06-MAR-07:01 | -19.7 |
April | 0.199605E+09 | 13326.90 | 30-APR-08:61 | -2.8 |
May | 0.196456E+09 | 10895.27 | 08-MAY-07:01 | -2.1 |
June | 0.144277E+09 | 1587.18 | 24-JUN-17:12 | 27.23 |
July | 0.192482E+09 | 2769.50 | 17-JUL-19:02 | 33.48 |
August | 0.173647E+09 | 3229.43 | 06-AUG-16:01 | 35.50 |
September | 0.142629E+09 | 2939.75 | 02-SEP-17:02 | 34.03 |
October | 0.128455E+09 | 2254.91 | 10-OCT-07:05 | -5.7 |
November | 0.542616E+09 | 27407.28 | 28-NOV-08:61 | -4.4 |
December | 0.186591E+10 | 32595.05 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.917106E+10 | |||
Minimum of Months | 0.128455E+09 | 1587.18 | -29.8 | |
Maximum of Months | 0.335115E+10 | 32602.16 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.356945E+10 | 32467.18 | 29-JAN-08:61 | -29.8 |
February | 0.155633E+10 | 32147.68 | 05-FEB-08:61 | -20.1 |
March | 0.920771E+09 | 32057.98 | 06-MAR-07:01 | -19.7 |
April | 0.225056E+09 | 18968.75 | 30-APR-08:61 | -2.8 |
May | 0.221541E+09 | 20311.94 | 08-MAY-07:01 | -2.1 |
June | 0.144742E+09 | 1595.69 | 24-JUN-17:12 | 27.23 |
July | 0.190723E+09 | 2769.08 | 17-JUL-19:02 | 33.48 |
August | 0.171856E+09 | 3229.72 | 06-AUG-16:01 | 35.50 |
September | 0.141297E+09 | 2942.08 | 02-SEP-17:02 | 34.03 |
October | 0.138713E+09 | 5392.08 | 05-OCT-07:10 | -2.5 |
November | 0.613172E+09 | 27338.98 | 28-NOV-08:61 | -4.4 |
December | 0.203018E+10 | 32460.14 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.992383E+10 | |||
Minimum of Months | 0.138713E+09 | 1595.69 | -29.8 | |
Maximum of Months | 0.356945E+10 | 32467.18 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388050E+10 | 32597.51 | 29-JAN-08:61 | -29.8 |
February | 0.175506E+10 | 32278.41 | 05-FEB-08:61 | -20.1 |
March | 0.107526E+10 | 32189.57 | 06-MAR-07:01 | -19.7 |
April | 0.264273E+09 | 23921.79 | 30-APR-08:61 | -2.8 |
May | 0.253444E+09 | 27807.70 | 08-MAY-07:01 | -2.1 |
June | 0.145149E+09 | 1590.77 | 24-JUN-17:12 | 27.23 |
July | 0.193855E+09 | 2770.68 | 17-JUL-19:02 | 33.48 |
August | 0.174486E+09 | 3231.06 | 06-AUG-16:01 | 35.50 |
September | 0.142118E+09 | 2944.52 | 02-SEP-17:02 | 34.03 |
October | 0.148914E+09 | 6754.31 | 10-OCT-07:03 | -5.7 |
November | 0.706936E+09 | 27938.21 | 29-NOV-08:61 | -1.1 |
December | 0.225916E+10 | 32590.60 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.109991E+11 | |||
Minimum of Months | 0.142118E+09 | 1590.77 | -29.8 | |
Maximum of Months | 0.388050E+10 | 32597.51 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.767791E+10 | 61678.48 | 11-JAN-08:61 | -17.3 |
February | 0.351148E+10 | 61663.11 | 05-FEB-09:01 | -20.4 |
March | 0.218024E+10 | 61350.64 | 06-MAR-08:61 | -16.9 |
April | 0.564218E+09 | 52060.46 | 29-APR-08:61 | -1.8 |
May | 0.491864E+09 | 53687.01 | 09-MAY-08:61 | 2.07 |
June | 0.227213E+09 | 2947.53 | 24-JUN-17:12 | 27.23 |
July | 0.281178E+09 | 5190.30 | 16-JUL-16:02 | 32.88 |
August | 0.258909E+09 | 6341.20 | 06-AUG-16:01 | 35.50 |
September | 0.253229E+09 | 5763.43 | 02-SEP-17:02 | 34.03 |
October | 0.286705E+09 | 51205.94 | 10-OCT-08:61 | -3.7 |
November | 0.146136E+10 | 61104.12 | 27-NOV-08:61 | -12.7 |
December | 0.454290E+10 | 61156.10 | 31-DEC-09:01 | -26.2 |
Annual Sum or Average | 0.217372E+11 | |||
Minimum of Months | 0.227213E+09 | 2947.53 | -26.2 | |
Maximum of Months | 0.767791E+10 | 61678.48 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.429768E+10 | 31493.16 | 28-JAN-08:61 | -25.1 |
February | 0.201780E+10 | 31481.34 | 05-FEB-09:01 | -20.4 |
March | 0.130230E+10 | 31356.31 | 06-MAR-08:61 | -16.9 |
April | 0.354642E+09 | 27070.77 | 01-APR-08:61 | 8.30 |
May | 0.297210E+09 | 27543.40 | 09-MAY-08:61 | 2.07 |
June | 0.124598E+09 | 1555.95 | 24-JUN-17:12 | 27.23 |
July | 0.152967E+09 | 2645.44 | 16-JUL-16:11 | 32.97 |
August | 0.141263E+09 | 3217.16 | 06-AUG-16:01 | 35.50 |
September | 0.137621E+09 | 2936.00 | 02-SEP-17:02 | 34.03 |
October | 0.165750E+09 | 26296.08 | 10-OCT-08:61 | -3.7 |
November | 0.859683E+09 | 31226.54 | 27-NOV-08:61 | -12.7 |
December | 0.259365E+10 | 31248.88 | 29-DEC-08:61 | -27.9 |
Annual Sum or Average | 0.124452E+11 | |||
Minimum of Months | 0.124598E+09 | 1555.95 | -27.9 | |
Maximum of Months | 0.429768E+10 | 31493.16 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.438875E+10 | 31364.29 | 11-JAN-08:61 | -17.3 |
February | 0.208366E+10 | 31343.08 | 05-FEB-09:01 | -20.4 |
March | 0.137665E+10 | 31199.50 | 06-MAR-08:61 | -16.9 |
April | 0.396728E+09 | 28633.27 | 01-APR-08:61 | 8.30 |
May | 0.317613E+09 | 27417.07 | 09-MAY-08:61 | 2.07 |
June | 0.124129E+09 | 1551.75 | 24-JUN-17:12 | 27.23 |
July | 0.152921E+09 | 2640.87 | 16-JUL-16:02 | 32.88 |
August | 0.141123E+09 | 3215.69 | 06-AUG-16:01 | 35.50 |
September | 0.137622E+09 | 2934.60 | 02-SEP-17:02 | 34.03 |
October | 0.171915E+09 | 26168.04 | 10-OCT-08:61 | -3.7 |
November | 0.904633E+09 | 31070.99 | 27-NOV-08:61 | -12.7 |
December | 0.268147E+10 | 31093.00 | 29-DEC-08:61 | -27.9 |
Annual Sum or Average | 0.128772E+11 | |||
Minimum of Months | 0.124129E+09 | 1551.75 | -27.9 | |
Maximum of Months | 0.438875E+10 | 31364.29 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.481829E+10 | 31111.49 | 28-JAN-08:61 | -25.1 |
February | 0.238689E+10 | 31091.19 | 05-FEB-09:01 | -20.4 |
March | 0.165847E+10 | 30935.42 | 06-MAR-08:61 | -16.9 |
April | 0.558483E+09 | 28464.65 | 01-APR-08:61 | 8.30 |
May | 0.408096E+09 | 27240.43 | 09-MAY-08:61 | 2.07 |
June | 0.123778E+09 | 1552.04 | 24-JUN-17:12 | 27.23 |
July | 0.153396E+09 | 2641.43 | 16-JUL-16:02 | 32.88 |
August | 0.141760E+09 | 3215.38 | 06-AUG-16:01 | 35.50 |
September | 0.139479E+09 | 2934.32 | 02-SEP-17:02 | 34.03 |
October | 0.195302E+09 | 25981.51 | 10-OCT-08:61 | -3.7 |
November | 0.106971E+10 | 30795.61 | 27-NOV-08:61 | -12.7 |
December | 0.304162E+10 | 30833.20 | 31-DEC-09:01 | -26.2 |
Annual Sum or Average | 0.146953E+11 | |||
Minimum of Months | 0.123778E+09 | 1552.04 | -26.2 | |
Maximum of Months | 0.481829E+10 | 31111.49 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.769964E+10 | 31706.99 | 30-JAN-08:61 | -14.1 |
February | 0.415691E+10 | 31651.56 | 05-FEB-09:01 | -20.4 |
March | 0.331762E+10 | 31619.81 | 06-MAR-08:61 | -16.9 |
April | 0.138745E+10 | 31476.50 | 03-APR-07:01 | 2.35 |
May | 0.854185E+09 | 31349.67 | 08-MAY-07:01 | -2.1 |
June | 0.127338E+09 | 1600.78 | 16-JUN-08:07 | 2.70 |
July | 0.153257E+09 | 2660.10 | 16-JUL-16:11 | 32.97 |
August | 0.141928E+09 | 3218.55 | 06-AUG-16:01 | 35.50 |
September | 0.169425E+09 | 16122.85 | 20-SEP-08:62 | 7.07 |
October | 0.329086E+09 | 27816.33 | 11-OCT-08:61 | 2.57 |
November | 0.189785E+10 | 31487.89 | 26-NOV-09:01 | -15.8 |
December | 0.498274E+10 | 31513.29 | 31-DEC-09:01 | -26.2 |
Annual Sum or Average | 0.252174E+11 | |||
Minimum of Months | 0.127338E+09 | 1600.78 | -26.2 | |
Maximum of Months | 0.769964E+10 | 31706.99 | 35.50 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.114998E+11 | 6976.27 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.104054E+11 | 6976.27 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.115236E+11 | 6976.27 | 01-MAR-10:09 | 0.223972E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.111588E+11 | 6976.27 | 01-APR-09:09 | 0.216880E+10 | 1348.26 | 01-APR-09:09 |
May | 0.114998E+11 | 6976.27 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.111588E+11 | 6976.27 | 01-JUN-09:09 | 0.216880E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.115236E+11 | 6976.27 | 01-JUL-09:09 | 0.223972E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.114998E+11 | 6976.27 | 01-AUG-09:09 | 0.223514E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.111826E+11 | 6976.27 | 01-SEP-09:09 | 0.217339E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.114998E+11 | 6976.27 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.111112E+11 | 6976.27 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.115474E+11 | 6976.27 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.135611E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.104054E+11 | 6976.27 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.115474E+11 | 6976.27 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.614337E+10 | 3726.82 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.555869E+10 | 3726.82 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.615608E+10 | 3726.82 | 01-MAR-10:09 | 0.111986E+10 | 674.13 | 01-MAR-10:09 |
April | 0.596119E+10 | 3726.82 | 01-APR-09:09 | 0.108440E+10 | 674.13 | 01-APR-09:09 |
May | 0.614337E+10 | 3726.82 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.596119E+10 | 3726.82 | 01-JUN-09:09 | 0.108440E+10 | 674.13 | 01-JUN-09:09 |
July | 0.615608E+10 | 3726.82 | 01-JUL-09:09 | 0.111986E+10 | 674.13 | 01-JUL-09:09 |
August | 0.614337E+10 | 3726.82 | 01-AUG-09:09 | 0.111757E+10 | 674.13 | 01-AUG-09:09 |
September | 0.597390E+10 | 3726.82 | 01-SEP-09:09 | 0.108669E+10 | 674.13 | 01-SEP-09:09 |
October | 0.614337E+10 | 3726.82 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.593577E+10 | 3726.82 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.616879E+10 | 3726.82 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.724452E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.555869E+10 | 3726.82 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.616879E+10 | 3726.82 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.438359E+10 | 3370.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.396975E+10 | 3370.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.447555E+10 | 3370.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.425331E+10 | 3370.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.442957E+10 | 3370.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.432228E+10 | 3370.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.436060E+10 | 3370.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.447555E+10 | 3370.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.425331E+10 | 3370.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.438359E+10 | 3370.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.425331E+10 | 3370.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.436060E+10 | 3370.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.519210E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.396975E+10 | 3370.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.447555E+10 | 3370.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.438359E+10 | 3370.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.396975E+10 | 3370.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.447555E+10 | 3370.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.425331E+10 | 3370.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.442957E+10 | 3370.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.432228E+10 | 3370.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.436060E+10 | 3370.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.447555E+10 | 3370.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.425331E+10 | 3370.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.438359E+10 | 3370.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.425331E+10 | 3370.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.436060E+10 | 3370.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.519210E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.396975E+10 | 3370.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.447555E+10 | 3370.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.438359E+10 | 3370.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.396975E+10 | 3370.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.447555E+10 | 3370.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.425331E+10 | 3370.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.442957E+10 | 3370.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.432228E+10 | 3370.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.436060E+10 | 3370.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.447555E+10 | 3370.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.425331E+10 | 3370.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.438359E+10 | 3370.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.425331E+10 | 3370.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.436060E+10 | 3370.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.519210E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.396975E+10 | 3370.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.447555E+10 | 3370.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.627948E+10 | 5255.58 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.568798E+10 | 5255.58 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.642287E+10 | 5255.58 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.609426E+10 | 5255.58 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.635118E+10 | 5255.58 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.620181E+10 | 5255.58 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.624363E+10 | 5255.58 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.642287E+10 | 5255.58 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.609426E+10 | 5255.58 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.627948E+10 | 5255.58 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.609426E+10 | 5255.58 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.624363E+10 | 5255.58 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.744157E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.568798E+10 | 5255.58 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.642287E+10 | 5255.58 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.313974E+10 | 2627.79 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.284399E+10 | 2627.79 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.321144E+10 | 2627.79 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.304713E+10 | 2627.79 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.317559E+10 | 2627.79 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.310090E+10 | 2627.79 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.312181E+10 | 2627.79 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.321144E+10 | 2627.79 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.304713E+10 | 2627.79 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.313974E+10 | 2627.79 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.304713E+10 | 2627.79 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.312181E+10 | 2627.79 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.372078E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.284399E+10 | 2627.79 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.321144E+10 | 2627.79 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.313974E+10 | 2627.79 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.284399E+10 | 2627.79 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.321144E+10 | 2627.79 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.304713E+10 | 2627.79 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.317559E+10 | 2627.79 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.310090E+10 | 2627.79 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.312181E+10 | 2627.79 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.321144E+10 | 2627.79 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.304713E+10 | 2627.79 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.313974E+10 | 2627.79 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.304713E+10 | 2627.79 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.312181E+10 | 2627.79 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.372078E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.284399E+10 | 2627.79 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.321144E+10 | 2627.79 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.313974E+10 | 2627.79 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.284399E+10 | 2627.79 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.321144E+10 | 2627.79 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.304713E+10 | 2627.79 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.317559E+10 | 2627.79 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.310090E+10 | 2627.79 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.312181E+10 | 2627.79 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.321144E+10 | 2627.79 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.304713E+10 | 2627.79 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.313974E+10 | 2627.79 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.304713E+10 | 2627.79 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.312181E+10 | 2627.79 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.372078E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.284399E+10 | 2627.79 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.321144E+10 | 2627.79 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.313974E+10 | 2627.79 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.284399E+10 | 2627.79 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.321144E+10 | 2627.79 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.304713E+10 | 2627.79 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.317559E+10 | 2627.79 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.310090E+10 | 2627.79 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.312181E+10 | 2627.79 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.321144E+10 | 2627.79 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.304713E+10 | 2627.79 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.313974E+10 | 2627.79 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.304713E+10 | 2627.79 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.312181E+10 | 2627.79 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.372078E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.284399E+10 | 2627.79 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.321144E+10 | 2627.79 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.114998E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820928E+10 |
February | 0.163016E+10 | 0.104054E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551706E+10 |
March | 0.178954E+10 | 0.115236E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506530E+10 |
April | 0.174484E+10 | 0.111588E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328798E+10 |
May | 0.179537E+10 | 0.114998E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40073357.50 | 0.286106E+10 |
June | 0.173447E+10 | 0.111588E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249750E+09 | 0.129792E+10 |
July | 0.181028E+10 | 0.115236E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677114E+09 | 0.622852E+09 |
August | 0.178501E+10 | 0.114998E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518077E+09 | 0.903170E+09 |
September | 0.174937E+10 | 0.111826E+11 | 0.217339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237879E+09 | 0.190014E+10 |
October | 0.180574E+10 | 0.114998E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2821082.58 | 0.320272E+10 |
November | 0.174613E+10 | 0.111112E+11 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475183E+10 |
December | 0.181481E+10 | 0.115474E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657946E+10 |
Annual Sum or Average | 0.212115E+11 | 0.135611E+12 | 0.263573E+11 | 0.172571E+10 | 0.441988E+11 | ||||
Minimum of Months | 0.163016E+10 | 0.104054E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622852E+09 |
Maximum of Months | 0.181481E+10 | 0.115474E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677114E+09 | 0.820928E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.614337E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401695E+10 |
February | 0.815075E+09 | 0.555869E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267918E+10 |
March | 0.894769E+09 | 0.615608E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248071E+10 |
April | 0.872416E+09 | 0.596119E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161843E+10 |
May | 0.897684E+09 | 0.614337E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21470225.99 | 0.135129E+10 |
June | 0.867232E+09 | 0.596119E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134785E+09 | 0.568209E+09 |
July | 0.905135E+09 | 0.615608E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365785E+09 | 0.246254E+09 |
August | 0.892501E+09 | 0.614337E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279189E+09 | 0.384842E+09 |
September | 0.874683E+09 | 0.597390E+10 | 0.108669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128211E+09 | 0.856719E+09 |
October | 0.902868E+09 | 0.614337E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1515572.10 | 0.152156E+10 |
November | 0.873064E+09 | 0.593577E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229993E+10 |
December | 0.907403E+09 | 0.616879E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322660E+10 |
Annual Sum or Average | 0.106057E+11 | 0.724452E+11 | 0.131787E+11 | 0.930956E+09 | 0.212507E+11 | ||||
Minimum of Months | 0.815075E+09 | 0.555869E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246254E+09 |
Maximum of Months | 0.907403E+09 | 0.616879E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365785E+09 | 0.401695E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411946E+10 |
February | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275471E+10 |
March | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253894E+10 |
April | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165586E+10 |
May | 0.544247E+09 | 0.442957E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21312791.84 | 0.138978E+10 |
June | 0.532585E+09 | 0.432228E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133356E+09 | 0.603000E+09 |
July | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357360E+09 | 0.276449E+09 |
August | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275835E+09 | 0.411834E+09 |
September | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122190E+09 | 0.894873E+09 |
October | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515539.38 | 0.156289E+10 |
November | 0.518979E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235137E+10 |
December | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331587E+10 |
Annual Sum or Average | 0.638324E+10 | 0.519210E+11 | 0.104672E+11 | 0.911570E+09 | 0.218750E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276449E+09 |
Maximum of Months | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357360E+09 | 0.411946E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411154E+10 |
February | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274325E+10 |
March | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252725E+10 |
April | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164170E+10 |
May | 0.544247E+09 | 0.442957E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21313111.70 | 0.138070E+10 |
June | 0.532585E+09 | 0.432228E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133358E+09 | 0.602294E+09 |
July | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357274E+09 | 0.276951E+09 |
August | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275768E+09 | 0.411982E+09 |
September | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122107E+09 | 0.891693E+09 |
October | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515539.28 | 0.155346E+10 |
November | 0.518979E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233478E+10 |
December | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330725E+10 |
Annual Sum or Average | 0.638324E+10 | 0.519210E+11 | 0.104672E+11 | 0.911335E+09 | 0.217828E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276951E+09 |
Maximum of Months | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357274E+09 | 0.411154E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410589E+10 |
February | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273347E+10 |
March | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251695E+10 |
April | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162563E+10 |
May | 0.544247E+09 | 0.442957E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21314708.63 | 0.136934E+10 |
June | 0.532585E+09 | 0.432228E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133362E+09 | 0.599350E+09 |
July | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357421E+09 | 0.275032E+09 |
August | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275824E+09 | 0.409633E+09 |
September | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122166E+09 | 0.885913E+09 |
October | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515539.64 | 0.154160E+10 |
November | 0.518979E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231624E+10 |
December | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330121E+10 |
Annual Sum or Average | 0.638324E+10 | 0.519210E+11 | 0.104672E+11 | 0.911603E+09 | 0.216803E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275032E+09 |
Maximum of Months | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357421E+09 | 0.410589E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.627948E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754951E+10 |
February | 0.167188E+10 | 0.568798E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502634E+10 |
March | 0.189386E+10 | 0.642287E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462545E+10 |
April | 0.180380E+10 | 0.609426E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296581E+10 |
May | 0.186509E+10 | 0.635118E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38420814.63 | 0.252894E+10 |
June | 0.182945E+10 | 0.620181E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240263E+09 | 0.113199E+10 |
July | 0.183943E+10 | 0.624363E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644191E+09 | 0.533530E+09 |
August | 0.189386E+10 | 0.642287E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497022E+09 | 0.780916E+09 |
September | 0.180380E+10 | 0.609426E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219815E+09 | 0.166047E+10 |
October | 0.183632E+10 | 0.627948E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2730339.75 | 0.284260E+10 |
November | 0.176881E+10 | 0.609426E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424653E+10 |
December | 0.183943E+10 | 0.624363E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607113E+10 |
Annual Sum or Average | 0.218821E+11 | 0.744157E+11 | 0.192612E+11 | 0.164244E+10 | 0.399632E+11 | ||||
Minimum of Months | 0.167188E+10 | 0.568798E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533530E+09 |
Maximum of Months | 0.189386E+10 | 0.642287E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644191E+09 | 0.754951E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412377E+10 |
February | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273568E+10 |
March | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251807E+10 |
April | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160704E+10 |
May | 0.932542E+09 | 0.317559E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21321585.73 | 0.136438E+10 |
June | 0.914724E+09 | 0.310090E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133464E+09 | 0.604740E+09 |
July | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358051E+09 | 0.279462E+09 |
August | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276097E+09 | 0.415043E+09 |
September | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122217E+09 | 0.890500E+09 |
October | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515721.01 | 0.153727E+10 |
November | 0.884402E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230401E+10 |
December | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331398E+10 |
Annual Sum or Average | 0.109410E+11 | 0.372078E+11 | 0.963059E+10 | 0.912666E+09 | 0.216939E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279462E+09 |
Maximum of Months | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358051E+09 | 0.412377E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412192E+10 |
February | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273119E+10 |
March | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251414E+10 |
April | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159800E+10 |
May | 0.932542E+09 | 0.317559E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21322642.74 | 0.135797E+10 |
June | 0.914724E+09 | 0.310090E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133471E+09 | 0.602659E+09 |
July | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358147E+09 | 0.278338E+09 |
August | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276136E+09 | 0.413643E+09 |
September | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122266E+09 | 0.887118E+09 |
October | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515720.44 | 0.153025E+10 |
November | 0.884402E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229584E+10 |
December | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331158E+10 |
Annual Sum or Average | 0.109410E+11 | 0.372078E+11 | 0.963059E+10 | 0.912858E+09 | 0.216427E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278338E+09 |
Maximum of Months | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358147E+09 | 0.412192E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411379E+10 |
February | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271690E+10 |
March | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250202E+10 |
April | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157387E+10 |
May | 0.932542E+09 | 0.317559E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21325076.80 | 0.133944E+10 |
June | 0.914724E+09 | 0.310090E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133491E+09 | 0.595886E+09 |
July | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358353E+09 | 0.274948E+09 |
August | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276204E+09 | 0.409450E+09 |
September | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122343E+09 | 0.877680E+09 |
October | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515717.04 | 0.151118E+10 |
November | 0.884402E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227596E+10 |
December | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330248E+10 |
Annual Sum or Average | 0.109410E+11 | 0.372078E+11 | 0.963059E+10 | 0.913233E+09 | 0.214936E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274948E+09 |
Maximum of Months | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358353E+09 | 0.411379E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515028E+10 |
February | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346006E+10 |
March | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318105E+10 |
April | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199183E+10 |
May | 0.932542E+09 | 0.317559E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22706759.31 | 0.176861E+10 |
June | 0.914724E+09 | 0.310090E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140665E+09 | 0.858499E+09 |
July | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377862E+09 | 0.454271E+09 |
August | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292117E+09 | 0.616966E+09 |
September | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129057E+09 | 0.124424E+10 |
October | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1606619.45 | 0.198916E+10 |
November | 0.884402E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293672E+10 |
December | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413198E+10 |
Annual Sum or Average | 0.109410E+11 | 0.372078E+11 | 0.963059E+10 | 0.964015E+09 | 0.277837E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454271E+09 |
Maximum of Months | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377862E+09 | 0.515028E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 6976.27 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 15364.07 | 10-JAN-18:00 |
February | 2159.72 | 03-FEB-13:09 | 6976.27 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 12414.04 | 09-FEB-18:00 |
March | 2159.72 | 03-MAR-13:09 | 6976.27 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 11849.64 | 04-MAR-18:00 |
April | 2159.72 | 01-APR-12:09 | 6976.27 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 7152.79 | 27-APR-11:10 |
May | 2159.72 | 05-MAY-12:09 | 6976.27 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1606.60 | 20-MAY-16:00 | 6558.07 | 22-MAY-16:00 |
June | 2159.72 | 02-JUN-12:09 | 6976.27 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2254.15 | 29-JUN-15:00 | 4450.40 | 16-JUN-11:05 |
July | 2159.72 | 01-JUL-12:09 | 6976.27 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3402.24 | 17-JUL-16:00 | 2701.03 | 05-JUL-11:10 |
August | 2159.72 | 04-AUG-12:09 | 6976.27 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3014.11 | 05-AUG-16:00 | 4417.12 | 17-AUG-11:05 |
September | 2159.72 | 01-SEP-12:09 | 6976.27 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2770.65 | 02-SEP-15:00 | 5159.26 | 12-SEP-11:05 |
October | 2159.72 | 01-OCT-12:09 | 6976.27 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 300.31 | 18-OCT-14:00 | 6168.47 | 10-OCT-11:10 |
November | 2159.72 | 03-NOV-12:09 | 6976.27 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10834.03 | 26-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 6976.27 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13286.18 | 28-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 6976.27 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2701.03 | |||||
Maximum of Months | 2159.72 | 6976.27 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3402.24 | 15364.07 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 3726.82 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.71 | 10-JAN-18:00 |
February | 1079.86 | 03-FEB-13:09 | 3726.82 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6783.34 | 09-FEB-18:00 |
March | 1079.86 | 03-MAR-13:09 | 3726.82 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6558.56 | 04-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3726.82 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3838.45 | 27-APR-11:10 |
May | 1079.86 | 05-MAY-12:09 | 3726.82 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.13 | 20-MAY-16:00 | 3450.85 | 22-MAY-16:00 |
June | 1079.86 | 02-JUN-12:09 | 3726.82 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.98 | 29-JUN-15:00 | 2579.34 | 16-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 3726.82 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.59 | 17-JUL-16:00 | 1485.06 | 05-JUL-11:10 |
August | 1079.86 | 04-AUG-12:09 | 3726.82 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.32 | 05-AUG-16:00 | 2423.10 | 17-AUG-11:05 |
September | 1079.86 | 01-SEP-12:09 | 3726.82 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.52 | 02-SEP-15:00 | 2877.33 | 12-SEP-11:05 |
October | 1079.86 | 01-OCT-12:09 | 3726.82 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.34 | 18-OCT-14:00 | 3337.71 | 10-OCT-11:10 |
November | 1079.86 | 03-NOV-12:09 | 3726.82 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.64 | 26-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 3726.82 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.57 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3726.82 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.06 | |||||
Maximum of Months | 1079.86 | 3726.82 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.59 | 8415.71 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3370.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.69 | 10-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 3370.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6783.33 | 09-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3370.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6558.56 | 04-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3370.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3838.42 | 27-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 3370.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.13 | 20-MAY-16:00 | 3450.83 | 22-MAY-16:00 |
June | 1079.86 | 03-JUN-12:09 | 3370.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.97 | 29-JUN-15:00 | 2565.83 | 16-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 3370.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 17-JUL-16:00 | 1485.06 | 05-JUL-11:10 |
August | 1079.86 | 05-AUG-12:09 | 3370.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.32 | 05-AUG-16:00 | 2425.28 | 17-AUG-11:05 |
September | 1079.86 | 02-SEP-12:09 | 3370.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.52 | 02-SEP-15:00 | 2864.57 | 12-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 3370.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.34 | 18-OCT-14:00 | 3337.08 | 10-OCT-11:10 |
November | 1079.86 | 04-NOV-12:09 | 3370.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.64 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3370.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.06 | |||||
Maximum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 8415.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3370.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.69 | 10-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 3370.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6783.33 | 09-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3370.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6558.56 | 04-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3370.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3838.42 | 27-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 3370.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.13 | 20-MAY-16:00 | 3450.83 | 22-MAY-16:00 |
June | 1079.86 | 03-JUN-12:09 | 3370.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.97 | 29-JUN-15:00 | 2558.16 | 16-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 3370.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 17-JUL-16:00 | 1485.06 | 05-JUL-11:10 |
August | 1079.86 | 05-AUG-12:09 | 3370.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.32 | 05-AUG-16:00 | 2424.16 | 17-AUG-11:05 |
September | 1079.86 | 02-SEP-12:09 | 3370.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.52 | 02-SEP-15:00 | 2857.22 | 12-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 3370.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.34 | 18-OCT-14:00 | 3337.08 | 10-OCT-11:10 |
November | 1079.86 | 04-NOV-12:09 | 3370.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.64 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3370.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.06 | |||||
Maximum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 8415.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3370.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.69 | 10-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 3370.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6783.33 | 09-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3370.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6558.56 | 04-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3370.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3838.42 | 27-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 3370.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.13 | 20-MAY-16:00 | 3450.84 | 22-MAY-16:00 |
June | 1079.86 | 03-JUN-12:09 | 3370.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.97 | 29-JUN-15:00 | 2536.73 | 16-JUN-11:05 |
July | 1079.86 | 01-JUL-12:09 | 3370.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 17-JUL-16:00 | 1485.06 | 05-JUL-11:10 |
August | 1079.86 | 05-AUG-12:09 | 3370.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.32 | 05-AUG-16:00 | 2403.65 | 17-AUG-11:05 |
September | 1079.86 | 02-SEP-12:09 | 3370.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.52 | 02-SEP-15:00 | 2833.01 | 12-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 3370.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.34 | 18-OCT-14:00 | 3337.08 | 10-OCT-11:10 |
November | 1079.86 | 04-NOV-12:09 | 3370.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.64 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3370.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.06 | |||||
Maximum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.58 | 8415.69 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 5255.58 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 15122.71 | 10-JAN-18:00 |
February | 2879.63 | 04-FEB-15:09 | 5255.58 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 12193.07 | 09-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 5255.58 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 11770.37 | 04-MAR-18:00 |
April | 2879.63 | 01-APR-14:09 | 5255.58 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6915.21 | 27-APR-11:10 |
May | 2879.63 | 06-MAY-14:09 | 5255.58 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1561.13 | 20-MAY-16:00 | 6232.53 | 22-MAY-16:00 |
June | 2879.63 | 03-JUN-14:09 | 5255.58 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2159.37 | 29-JUN-15:00 | 4444.57 | 16-JUN-11:05 |
July | 2879.63 | 01-JUL-14:09 | 5255.58 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3334.69 | 17-JUL-16:00 | 2667.35 | 05-JUL-11:10 |
August | 2879.63 | 05-AUG-14:09 | 5255.58 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2946.89 | 05-AUG-16:00 | 4222.07 | 17-AUG-11:05 |
September | 2879.63 | 02-SEP-14:09 | 5255.58 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2681.37 | 02-SEP-15:00 | 4977.81 | 12-SEP-11:05 |
October | 2879.63 | 07-OCT-14:09 | 5255.58 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 290.65 | 18-OCT-14:00 | 6005.90 | 10-OCT-11:10 |
November | 2879.63 | 04-NOV-14:09 | 5255.58 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10596.59 | 26-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 5255.58 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13191.80 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 5255.58 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2667.35 | |||||
Maximum of Months | 2879.63 | 5255.58 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3334.69 | 15122.71 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2627.79 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.69 | 10-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2627.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6783.32 | 09-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2627.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6558.55 | 04-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2627.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3838.41 | 27-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2627.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.15 | 20-MAY-16:00 | 3450.84 | 22-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 2627.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.99 | 29-JUN-15:00 | 2481.66 | 16-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 2627.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 17-JUL-16:00 | 1485.06 | 05-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 2627.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.35 | 05-AUG-16:00 | 2339.95 | 17-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 2627.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.55 | 02-SEP-15:00 | 2766.74 | 12-SEP-11:05 |
October | 1439.81 | 07-OCT-14:09 | 2627.79 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.35 | 18-OCT-14:00 | 3337.07 | 10-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 2627.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.63 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2627.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.06 | |||||
Maximum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 8415.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2627.79 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.69 | 10-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2627.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6783.32 | 09-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2627.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6558.55 | 04-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2627.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3838.41 | 27-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2627.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.15 | 20-MAY-16:00 | 3450.83 | 22-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 2627.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.99 | 29-JUN-15:00 | 2467.67 | 16-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 2627.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 17-JUL-16:00 | 1485.06 | 05-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 2627.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.35 | 05-AUG-16:00 | 2329.23 | 17-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 2627.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.55 | 02-SEP-15:00 | 2749.85 | 12-SEP-11:05 |
October | 1439.81 | 07-OCT-14:09 | 2627.79 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.35 | 18-OCT-14:00 | 3337.07 | 10-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 2627.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.63 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2627.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.06 | |||||
Maximum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 8415.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2627.79 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8415.69 | 10-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2627.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6783.32 | 09-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2627.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6558.55 | 04-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2627.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3838.42 | 27-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2627.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 867.15 | 20-MAY-16:00 | 3450.82 | 22-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 2627.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.99 | 29-JUN-15:00 | 2427.06 | 16-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 2627.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 17-JUL-16:00 | 1476.76 | 05-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 2627.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1638.35 | 05-AUG-16:00 | 2294.68 | 17-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 2627.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.55 | 02-SEP-15:00 | 2705.39 | 12-SEP-11:05 |
October | 1439.81 | 07-OCT-14:09 | 2627.79 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.35 | 18-OCT-14:00 | 3337.07 | 10-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 2627.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5891.63 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2627.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7350.58 | 31-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1476.76 | |||||
Maximum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.61 | 8415.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2627.79 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8656.72 | 10-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 2627.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 7003.99 | 09-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2627.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6689.31 | 04-MAR-14:00 |
April | 1439.81 | 01-APR-14:09 | 2627.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4075.67 | 27-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 2627.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 912.62 | 20-MAY-16:00 | 3775.95 | 22-MAY-16:00 |
June | 1439.81 | 03-JUN-14:09 | 2627.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1291.68 | 29-JUN-15:00 | 2462.91 | 16-JUN-11:05 |
July | 1439.81 | 01-JUL-14:09 | 2627.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1922.12 | 17-JUL-16:00 | 1449.46 | 05-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 2627.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1705.55 | 05-AUG-16:00 | 2373.23 | 17-AUG-11:05 |
September | 1439.81 | 02-SEP-14:09 | 2627.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1577.78 | 02-SEP-15:00 | 2891.97 | 12-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 2627.79 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 171.02 | 18-OCT-14:00 | 3499.42 | 10-OCT-11:10 |
November | 1439.81 | 04-NOV-14:09 | 2627.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6128.78 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2627.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7465.45 | 28-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1449.46 | |||||
Maximum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1922.12 | 8656.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18687.43 | 28-JAN-00:01 | 1439.81 | 29373.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.88 |
February | 15242.90 | 04-FEB-00:01 | 1259.84 | 25702.04 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.88 |
March | 13608.18 | 04-MAR-00:02 | 1079.86 | 22030.32 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.22 |
April | 9137.27 | 30-APR-08:03 | 1259.84 | 25702.04 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.42 |
May | 34772.45 | 20-MAY-08:62 | 899.88 | 18358.60 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.10 |
June | 37845.84 | 30-JUN-08:62 | 1079.86 | 22030.32 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.86 |
July | 40531.36 | 27-JUL-08:61 | 1259.84 | 25702.04 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.63 |
August | 41636.17 | 26-AUG-08:62 | 1079.86 | 22030.32 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.54 |
September | 40425.23 | 09-SEP-08:62 | 1079.86 | 22030.32 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.47 |
October | 32623.76 | 19-OCT-08:62 | 899.88 | 18358.60 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.15 |
November | 12814.58 | 27-NOV-09:04 | 1439.81 | 29373.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1780.98 |
December | 16252.60 | 29-DEC-00:01 | 1259.84 | 25702.04 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.30 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9137.27 | 899.88 | 18358.60 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.30 | |
Maximum of Months | 41636.17 | 1439.81 | 29373.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1780.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8741.16 | 27-JAN-20:01 | 3779.50 | 26087.75 | 4718.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.47 |
February | 16830.17 | 26-FEB-18:15 | 2159.71 | 7453.64 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.19 |
March | 7400.57 | 05-MAR-09:04 | 719.90 | 15691.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 915.92 |
April | 19690.68 | 25-APR-20:01 | 5399.28 | 37268.22 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23753.53 | 14-MAY-17:16 | 10798.56 | 37268.22 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.74 |
June | 21867.89 | 20-JUN-08:62 | 449.94 | 9807.43 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.11 |
July | 22225.12 | 27-JUL-08:61 | 629.92 | 13730.40 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.21 |
August | 22986.45 | 02-AUG-08:62 | 449.94 | 9807.43 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.47 |
September | 23309.28 | 26-SEP-08:62 | 449.94 | 9807.43 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.74 |
October | 22885.14 | 19-OCT-08:62 | 449.94 | 9807.43 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.18 |
November | 19801.71 | 05-NOV-17:01 | 10798.56 | 37268.22 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.28 |
December | 7718.29 | 30-DEC-09:04 | 719.90 | 15691.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 849.57 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7400.57 | 449.94 | 7453.64 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23753.53 | 10798.56 | 37268.22 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 915.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7316.42 | 19-JAN-08:03 | 809.89 | 15965.87 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 921.79 |
February | 7688.68 | 10-FEB-08:04 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 957.36 |
March | 6094.97 | 05-MAR-09:04 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 911.06 |
April | 10400.29 | 08-APR-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.73 |
May | 21590.29 | 21-MAY-08:62 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.41 |
June | 26869.85 | 08-JUN-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.35 |
July | 23580.33 | 12-JUL-07:02 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.82 |
August | 25868.88 | 28-AUG-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.76 |
September | 27832.07 | 28-SEP-07:01 | 809.89 | 15965.87 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.63 |
October | 29942.16 | 20-OCT-07:01 | 899.88 | 17739.85 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.23 |
November | 11019.54 | 05-NOV-08:61 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.24 |
December | 6138.22 | 15-DEC-08:02 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 834.11 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6094.97 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.82 | |
Maximum of Months | 29942.16 | 899.88 | 17739.85 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 957.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7371.21 | 19-JAN-08:03 | 809.89 | 15965.87 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 920.86 |
February | 7281.39 | 03-FEB-08:04 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 874.81 |
March | 5851.21 | 04-MAR-08:04 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901.45 |
April | 6572.30 | 08-APR-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.55 |
May | 21660.84 | 21-MAY-08:62 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.32 |
June | 26135.02 | 08-JUN-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.17 |
July | 23657.67 | 12-JUL-07:02 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.75 |
August | 25996.29 | 28-AUG-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.61 |
September | 27924.23 | 28-SEP-07:01 | 809.89 | 15965.87 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.54 |
October | 29710.40 | 20-OCT-07:01 | 899.88 | 17739.85 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.40 |
November | 6993.35 | 05-NOV-08:61 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.01 |
December | 6401.43 | 14-DEC-08:03 | 539.93 | 10643.91 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 770.61 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5851.21 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.75 | |
Maximum of Months | 29710.40 | 899.88 | 17739.85 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 920.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6059.12 | 28-JAN-08:04 | 899.88 | 17739.85 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1166.15 |
February | 7494.05 | 09-FEB-08:04 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 932.96 |
March | 7796.37 | 04-MAR-08:04 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.09 |
April | 4630.02 | 29-APR-07:03 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 641.13 |
May | 19629.98 | 21-MAY-08:62 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.84 |
June | 25129.84 | 07-JUN-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.68 |
July | 23444.54 | 12-JUL-07:02 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.13 |
August | 25772.52 | 28-AUG-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.42 |
September | 27662.28 | 28-SEP-07:01 | 809.89 | 15965.87 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.46 |
October | 25973.04 | 19-OCT-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.14 |
November | 6434.74 | 27-NOV-08:04 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 849.92 |
December | 6528.85 | 14-DEC-08:03 | 539.93 | 10643.91 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 772.70 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4630.02 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.13 | |
Maximum of Months | 27662.28 | 899.88 | 17739.85 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1166.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12248.14 | 18-JAN-09:04 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1420.45 |
February | 10112.97 | 23-FEB-09:04 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1174.72 |
March | 9851.95 | 07-MAR-09:04 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 947.73 |
April | 8593.69 | 29-APR-08:02 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 993.67 |
May | 33955.61 | 20-MAY-08:62 | 1979.74 | 13830.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.09 |
June | 38298.54 | 27-JUN-08:62 | 1979.74 | 13830.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.31 |
July | 40588.80 | 27-JUL-08:61 | 2771.64 | 19362.66 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.26 |
August | 41431.76 | 02-AUG-08:62 | 1979.74 | 13830.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.56 |
September | 39830.62 | 09-SEP-08:62 | 2375.69 | 16596.57 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.59 |
October | 31023.97 | 19-OCT-08:62 | 1979.74 | 13830.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.44 |
November | 13887.04 | 26-NOV-10:04 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1727.72 |
December | 12840.12 | 14-DEC-09:04 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1393.70 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8593.69 | 1979.74 | 13830.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.09 | |
Maximum of Months | 41431.76 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1727.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6056.17 | 18-JAN-09:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 779.16 |
February | 4996.93 | 23-FEB-09:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.59 |
March | 5290.28 | 03-MAR-09:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 915.07 |
April | 4270.98 | 28-APR-08:02 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.65 |
May | 17399.03 | 20-MAY-08:62 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.75 |
June | 19536.83 | 25-JUN-09:02 | 1187.84 | 8298.28 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.68 |
July | 20848.13 | 27-JUL-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.14 |
August | 20949.29 | 26-AUG-08:62 | 1187.84 | 8298.28 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.27 |
September | 20450.56 | 09-SEP-08:62 | 1187.84 | 8298.28 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.80 |
October | 14484.76 | 19-OCT-08:62 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.08 |
November | 6891.69 | 26-NOV-10:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 945.15 |
December | 6352.20 | 14-DEC-09:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769.67 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4270.98 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.75 | |
Maximum of Months | 20949.29 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 945.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6027.28 | 18-JAN-09:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 776.31 |
February | 5092.97 | 23-FEB-09:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.33 |
March | 6455.01 | 03-MAR-09:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 915.94 |
April | 4372.25 | 28-APR-08:02 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.39 |
May | 15930.59 | 20-MAY-08:62 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.01 |
June | 19330.44 | 25-JUN-09:02 | 1187.84 | 8298.28 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.20 |
July | 20645.26 | 27-JUL-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.96 |
August | 20743.47 | 26-AUG-08:62 | 1187.84 | 8298.28 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.02 |
September | 20268.38 | 09-SEP-08:62 | 1187.84 | 8298.28 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.48 |
October | 13234.53 | 19-OCT-08:62 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.93 |
November | 6971.32 | 26-NOV-10:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 946.75 |
December | 6417.10 | 15-DEC-09:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 828.46 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4372.25 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.01 | |
Maximum of Months | 20743.47 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 946.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5909.98 | 05-JAN-09:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 850.40 |
February | 5362.37 | 23-FEB-09:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.52 |
March | 6700.67 | 03-MAR-09:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 919.75 |
April | 4260.48 | 30-APR-09:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552.25 |
May | 10689.35 | 20-MAY-08:62 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.48 |
June | 18978.47 | 25-JUN-09:02 | 1187.84 | 8298.28 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.67 |
July | 20327.88 | 27-JUL-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.44 |
August | 20411.02 | 26-AUG-08:62 | 1187.84 | 8298.28 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.11 |
September | 19970.42 | 09-SEP-08:62 | 1187.84 | 8298.28 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.04 |
October | 9381.64 | 19-OCT-08:62 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.49 |
November | 7021.10 | 26-NOV-10:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 942.93 |
December | 6501.95 | 14-DEC-09:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769.46 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4260.48 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.48 | |
Maximum of Months | 20411.02 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 942.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4638.61 | 04-JAN-09:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 707.97 |
February | 4676.13 | 22-FEB-09:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.31 |
March | 4665.69 | 25-MAR-08:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 595.71 |
April | 4538.35 | 28-APR-08:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 581.46 |
May | 4210.55 | 20-MAY-16:00 | 1331.82 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 912.62 | 0.00 |
June | 18899.14 | 25-JUN-09:02 | 1187.84 | 8298.28 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.20 |
July | 19930.34 | 27-JUL-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.52 |
August | 19650.92 | 13-AUG-09:01 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.46 |
September | 19276.74 | 05-SEP-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.34 |
October | 4723.91 | 10-OCT-08:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 773.21 |
November | 5380.38 | 11-NOV-10:04 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 682.95 |
December | 5274.81 | 22-DEC-09:04 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 707.74 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4210.55 | 989.87 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19930.34 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 912.62 | 844.31 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.983872E+11 | 76680.86 | 14-JAN-17:30 | 0.159033E+12 | 307809.02 | 09-JAN-09:09 |
February | 0.881218E+11 | 77437.52 | 02-FEB-17:00 | 0.850801E+11 | 251177.02 | 04-FEB-09:09 |
March | 0.973286E+11 | 73100.08 | 01-MAR-18:00 | 0.623882E+11 | 225901.22 | 04-MAR-09:09 |
April | 0.920172E+11 | 72078.18 | 07-APR-13:39 | 0.199611E+11 | 114425.46 | 29-APR-08:09 |
May | 0.968348E+11 | 91072.45 | 20-MAY-14:00 | 0.126608E+11 | 125606.22 | 08-MAY-08:09 |
June | 0.102554E+12 | 98578.02 | 29-JUN-12:39 | 0.112006E+09 | 10437.73 | 16-JUN-08:50 |
July | 0.115568E+12 | 107930.00 | 17-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.113904E+12 | 104454.79 | 06-AUG-15:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.101953E+12 | 103477.91 | 02-SEP-14:39 | 0.800325E+09 | 22609.19 | 19-SEP-08:20 |
October | 0.978084E+11 | 85815.61 | 18-OCT-13:39 | 0.624954E+10 | 103960.28 | 10-OCT-08:09 |
November | 0.948361E+11 | 73180.99 | 29-NOV-18:40 | 0.413937E+11 | 196001.11 | 27-NOV-09:09 |
December | 0.983982E+11 | 75014.39 | 13-DEC-17:40 | 0.109421E+12 | 287215.01 | 29-DEC-09:09 |
Annual Sum or Average | 0.119771E+13 | 0.497100E+12 | ||||
Minimum of Months | 0.881218E+11 | 72078.18 | 0.00 | 0.00 | ||
Maximum of Months | 0.115568E+12 | 107930.00 | 0.159033E+12 | 307809.02 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.496324E+11 | 0.119935E+11 | 0.108804E+11 | 0.00 | 0.200931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578770E+10 | 0.00 |
February | 0.449372E+11 | 0.990862E+10 | 0.985143E+10 | 0.00 | 0.181657E+11 | 0.00 | 0.00 | 2848463.85 | 0.00 | 0.00 | 0.00 | 0.525589E+10 | 0.00 |
March | 0.503750E+11 | 0.967602E+10 | 0.110523E+11 | 0.00 | 0.203878E+11 | 0.00 | 0.00 | 303730.31 | 0.00 | 0.00 | 0.00 | 0.583714E+10 | 0.00 |
April | 0.481627E+11 | 0.805630E+10 | 0.105581E+11 | 0.00 | 0.195628E+11 | 0.00 | 0.00 | 0.144242E+09 | 0.00 | 0.00 | 0.00 | 0.553317E+10 | 0.00 |
May | 0.499854E+11 | 0.716398E+10 | 0.109629E+11 | 0.00 | 0.204198E+11 | 0.00 | 0.00 | 0.268752E+10 | 0.00 | 0.00 | 0.00 | 0.561513E+10 | 0.00 |
June | 0.486922E+11 | 0.632663E+10 | 0.106818E+11 | 0.00 | 0.199966E+11 | 0.00 | 0.00 | 0.115243E+11 | 0.00 | 0.00 | 0.00 | 0.533199E+10 | 0.00 |
July | 0.494924E+11 | 0.681720E+10 | 0.108460E+11 | 0.00 | 0.202522E+11 | 0.00 | 0.00 | 0.227815E+11 | 0.00 | 0.00 | 0.00 | 0.537841E+10 | 0.00 |
August | 0.503385E+11 | 0.780256E+10 | 0.110454E+11 | 0.00 | 0.206501E+11 | 0.00 | 0.00 | 0.186692E+11 | 0.00 | 0.00 | 0.00 | 0.539861E+10 | 0.00 |
September | 0.481992E+11 | 0.879215E+10 | 0.105649E+11 | 0.00 | 0.197610E+11 | 0.00 | 0.00 | 0.940966E+10 | 0.00 | 0.00 | 0.00 | 0.522634E+10 | 0.00 |
October | 0.496324E+11 | 0.104288E+11 | 0.108804E+11 | 0.00 | 0.202673E+11 | 0.00 | 0.00 | 0.113150E+10 | 0.00 | 0.00 | 0.00 | 0.546799E+10 | 0.00 |
November | 0.480897E+11 | 0.112746E+11 | 0.105443E+11 | 0.00 | 0.195085E+11 | 0.00 | 0.00 | 6218386.63 | 0.00 | 0.00 | 0.00 | 0.541276E+10 | 0.00 |
December | 0.495289E+11 | 0.123276E+11 | 0.108529E+11 | 0.00 | 0.199825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570629E+10 | 0.00 |
Annual Sum or Average | 0.587066E+12 | 0.110568E+12 | 0.128721E+12 | 0.239047E+12 | 0.00 | 0.663574E+11 | 0.659514E+11 | ||||||
Minimum of Months | 0.449372E+11 | 0.632663E+10 | 0.985143E+10 | 0.00 | 0.181657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522634E+10 | 0.00 |
Maximum of Months | 0.503750E+11 | 0.123276E+11 | 0.110523E+11 | 0.00 | 0.206501E+11 | 0.00 | 0.00 | 0.227815E+11 | 0.00 | 0.00 | 0.00 | 0.583714E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.159033E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.850801E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.623882E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.199611E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.126608E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.112006E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.800325E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.624954E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.413937E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.109421E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.497100E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.159033E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 36581.55 | 01-JAN-11:09 | 7048.38 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 13885.48 | 01-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 36581.55 | 01-FEB-10:09 | 7048.38 | 01-FEB-00:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 13885.48 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 36581.55 | 01-MAR-10:09 | 7048.38 | 01-MAR-00:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 13885.48 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 36581.55 | 01-APR-09:09 | 7048.38 | 01-APR-00:10 | 8089.53 | 01-APR-09:09 | 0.00 | 13885.48 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 36581.55 | 01-MAY-09:09 | 7048.38 | 01-MAY-00:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 13885.48 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 36581.55 | 01-JUN-09:09 | 7048.38 | 01-JUN-00:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 13885.48 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 36581.55 | 01-JUL-09:09 | 7048.38 | 01-JUL-00:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 13885.48 | 01-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 36581.55 | 01-AUG-09:09 | 7048.38 | 01-AUG-00:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 13885.48 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 36581.55 | 01-SEP-09:09 | 7048.38 | 01-SEP-00:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 13885.48 | 01-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 36581.55 | 01-OCT-10:09 | 7048.38 | 01-OCT-00:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 13885.48 | 06-OCT-09:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 36581.55 | 01-NOV-09:09 | 7048.38 | 01-NOV-00:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 13885.48 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 36581.55 | 01-DEC-10:09 | 7048.38 | 01-DEC-00:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 13885.48 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 36581.55 | 7048.38 | 8089.53 | 0.00 | 13885.48 | 0.00 | 0.00 | |||||
Maximum of Months | 36581.55 | 7048.38 | 8089.53 | 0.00 | 13885.48 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 11898.64 | 21-JAN-14:20 | 0.00 |
February | 1779.81 | 26-FEB-18:19 | 0.00 | 0.00 | 0.00 | 11893.23 | 02-FEB-13:00 | 0.00 |
March | 63.20 | 29-MAR-22:10 | 0.00 | 0.00 | 0.00 | 9754.17 | 18-MAR-12:09 | 0.00 |
April | 9272.70 | 07-APR-13:00 | 0.00 | 0.00 | 0.00 | 9750.04 | 06-APR-12:20 | 0.00 |
May | 26057.18 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 10793.28 | 24-MAY-10:39 | 0.00 |
June | 32053.88 | 29-JUN-14:00 | 0.00 | 0.00 | 0.00 | 11779.81 | 01-JUN-10:00 | 0.00 |
July | 45019.12 | 17-JUL-16:10 | 0.00 | 0.00 | 0.00 | 9719.30 | 05-JUL-12:50 | 0.00 |
August | 40787.78 | 06-AUG-15:00 | 0.00 | 0.00 | 0.00 | 9713.63 | 05-AUG-12:30 | 0.00 |
September | 39636.88 | 02-SEP-14:00 | 0.00 | 0.00 | 0.00 | 9717.37 | 27-SEP-12:30 | 0.00 |
October | 20704.92 | 18-OCT-14:30 | 0.00 | 0.00 | 0.00 | 9700.13 | 28-OCT-14:30 | 0.00 |
November | 423.60 | 05-NOV-22:19 | 0.00 | 0.00 | 0.00 | 9627.71 | 30-NOV-13:30 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 9751.16 | 22-DEC-13:39 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9627.71 | 0.00 | ||
Maximum of Months | 45019.12 | 0.00 | 0.00 | 0.00 | 11898.64 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 76680.86 | 14-JAN-17:30 | 36581.55 | 8089.53 | 7048.38 | 0.00 | 13885.48 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 77437.52 | 02-FEB-17:00 | 36581.55 | 8089.53 | 7048.38 | 0.00 | 13885.48 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 73100.08 | 01-MAR-18:00 | 36581.55 | 8089.53 | 7048.38 | 0.00 | 13885.48 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72078.18 | 07-APR-13:39 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13885.48 | 0.00 | 0.00 | 8040.25 | 0.00 |
May | 91072.45 | 20-MAY-14:00 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13885.48 | 0.00 | 0.00 | 23717.48 | 0.00 |
June | 98578.02 | 29-JUN-12:39 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13885.48 | 0.00 | 0.00 | 30444.60 | 0.00 |
July | 107930.00 | 17-JUL-13:00 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13885.48 | 0.00 | 0.00 | 43908.00 | 0.00 |
August | 104454.79 | 06-AUG-15:50 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13885.48 | 0.00 | 0.00 | 40466.02 | 0.00 |
September | 103477.91 | 02-SEP-14:39 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13885.48 | 0.00 | 0.00 | 39467.98 | 0.00 |
October | 85815.61 | 18-OCT-13:39 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13885.48 | 0.00 | 0.00 | 20085.75 | 0.00 |
November | 73180.99 | 29-NOV-18:40 | 36581.55 | 8089.53 | 7048.38 | 0.00 | 13885.48 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 75014.39 | 13-DEC-17:40 | 36581.55 | 8089.53 | 7048.38 | 0.00 | 13885.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 72078.18 | 36581.55 | 8089.53 | 0.00 | 0.00 | 13885.48 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 107930.00 | 36581.55 | 8089.53 | 7048.38 | 0.00 | 13885.48 | 0.00 | 0.00 | 43908.00 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 307809.02 | 09-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 251177.02 | 04-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 225901.22 | 04-MAR-09:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 114425.46 | 29-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 125606.22 | 08-MAY-08:09 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 10437.73 | 16-JUN-08:50 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 22609.19 | 19-SEP-08:20 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 103960.28 | 10-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 196001.11 | 27-NOV-09:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 287215.01 | 29-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 307809.02 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 20.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.00 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.67 | 20.38 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 20.37 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 15.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 15.00 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 15.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 14.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 14.89 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 14.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 14.98 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 14.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 14.92 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 14.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.17 | 14.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.33 | 14.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.00 | 14.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 14.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 14.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.00 | 14.85 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.17 | 14.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 20.96 | 352.50 | 20.90 | 352.50 | 20.90 |
February | 448.00 | 21.21 | 189.50 | 20.83 | 189.50 | 20.83 |
March | 496.00 | 21.11 | 152.67 | 20.81 | 152.67 | 20.81 |
April | 467.50 | 22.02 | 38.67 | 20.82 | 38.67 | 20.82 |
May | 334.50 | 22.21 | 41.83 | 22.33 | 20.33 | 20.67 |
June | 67.83 | 23.18 | 167.33 | 23.93 | 0.00 | 0.00 |
July | 11.50 | 24.04 | 323.50 | 23.95 | 2.67 | 24.73 |
August | 29.17 | 23.36 | 225.83 | 23.95 | 0.00 | 0.00 |
September | 127.17 | 22.60 | 170.00 | 23.92 | 5.50 | 23.80 |
October | 303.83 | 22.40 | 4.33 | 20.81 | 4.33 | 20.81 |
November | 470.50 | 21.74 | 88.00 | 20.90 | 88.00 | 20.90 |
December | 496.00 | 21.01 | 274.00 | 20.89 | 274.00 | 20.89 |
Annual Sum or Average | 3748.00 | 21.60 | 2028.17 | 22.24 | 1128.17 | 20.89 |
Minimum of Months | 11.50 | 20.96 | 4.33 | 20.81 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 24.04 | 352.50 | 23.95 | 352.50 | 24.73 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.32 | 253.67 | 20.99 | 253.67 | 20.99 |
February | 445.83 | 21.78 | 127.17 | 20.99 | 127.17 | 20.99 |
March | 496.00 | 21.85 | 63.83 | 20.99 | 63.83 | 20.99 |
April | 438.33 | 22.72 | 4.33 | 21.06 | 4.33 | 21.06 |
May | 305.83 | 22.73 | 24.33 | 23.43 | 3.67 | 20.92 |
June | 50.50 | 23.34 | 164.17 | 23.95 | 0.00 | 0.00 |
July | 12.83 | 23.37 | 307.83 | 23.96 | 0.00 | 0.00 |
August | 25.83 | 23.29 | 211.00 | 23.99 | 0.00 | 0.00 |
September | 108.17 | 23.06 | 170.17 | 23.93 | 5.33 | 23.89 |
October | 263.50 | 22.96 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 448.33 | 22.35 | 31.33 | 20.93 | 31.33 | 20.93 |
December | 496.00 | 21.50 | 132.00 | 20.98 | 132.00 | 20.98 |
Annual Sum or Average | 3587.17 | 22.12 | 1489.83 | 22.73 | 621.33 | 21.01 |
Minimum of Months | 12.83 | 21.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.37 | 307.83 | 23.99 | 253.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 237.67 | 21.11 | 237.67 | 21.11 |
February | 336.00 | 21.41 | 124.00 | 21.11 | 124.00 | 21.11 |
March | 379.00 | 21.33 | 81.83 | 21.11 | 81.83 | 21.11 |
April | 339.17 | 22.19 | 9.50 | 21.11 | 9.50 | 21.11 |
May | 243.33 | 22.27 | 30.17 | 23.71 | 7.00 | 21.11 |
June | 36.67 | 23.06 | 145.33 | 24.16 | 0.00 | 0.00 |
July | 4.33 | 25.09 | 259.50 | 24.15 | 1.17 | 28.53 |
August | 16.33 | 23.62 | 192.67 | 24.20 | 0.83 | 29.02 |
September | 89.67 | 22.75 | 137.50 | 24.13 | 6.67 | 24.84 |
October | 207.00 | 22.38 | 2.17 | 23.51 | 1.00 | 21.11 |
November | 346.50 | 21.85 | 46.00 | 21.11 | 46.00 | 21.11 |
December | 369.00 | 21.14 | 162.33 | 21.11 | 162.33 | 21.11 |
Annual Sum or Average | 2738.00 | 21.71 | 1428.67 | 22.74 | 678.00 | 21.17 |
Minimum of Months | 4.33 | 21.11 | 2.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 25.09 | 259.50 | 24.20 | 237.67 | 29.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 248.50 | 21.11 | 248.50 | 21.11 |
February | 336.00 | 21.38 | 133.17 | 21.11 | 133.17 | 21.11 |
March | 379.00 | 21.29 | 97.50 | 21.11 | 97.50 | 21.11 |
April | 350.33 | 22.16 | 12.83 | 21.11 | 12.83 | 21.11 |
May | 249.17 | 22.24 | 32.50 | 23.40 | 10.33 | 21.11 |
June | 37.67 | 23.04 | 144.17 | 24.16 | 0.00 | 0.00 |
July | 4.67 | 24.98 | 260.67 | 24.15 | 1.17 | 28.56 |
August | 16.67 | 23.61 | 195.33 | 24.19 | 0.83 | 29.04 |
September | 91.33 | 22.70 | 136.67 | 24.13 | 6.83 | 24.83 |
October | 216.50 | 22.36 | 3.50 | 22.58 | 2.33 | 21.11 |
November | 349.50 | 21.79 | 58.33 | 21.11 | 58.33 | 21.11 |
December | 369.00 | 21.13 | 181.00 | 21.11 | 181.00 | 21.11 |
Annual Sum or Average | 2770.83 | 21.69 | 1504.17 | 22.66 | 752.83 | 21.16 |
Minimum of Months | 4.67 | 21.11 | 3.50 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 24.98 | 260.67 | 24.19 | 248.50 | 29.04 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 265.67 | 21.11 | 265.67 | 21.11 |
February | 336.00 | 21.34 | 146.67 | 21.11 | 146.67 | 21.11 |
March | 379.00 | 21.24 | 112.67 | 21.11 | 112.67 | 21.11 |
April | 356.00 | 22.08 | 19.33 | 21.11 | 19.33 | 21.11 |
May | 256.33 | 22.18 | 34.50 | 23.13 | 13.50 | 21.11 |
June | 43.50 | 23.07 | 139.67 | 24.16 | 0.00 | 0.00 |
July | 5.33 | 24.52 | 255.50 | 24.15 | 0.83 | 28.67 |
August | 20.00 | 23.56 | 186.67 | 24.20 | 0.83 | 29.00 |
September | 95.83 | 22.63 | 131.33 | 24.13 | 6.67 | 24.84 |
October | 231.00 | 22.34 | 3.67 | 22.11 | 2.83 | 21.11 |
November | 354.50 | 21.71 | 67.50 | 21.11 | 67.50 | 21.11 |
December | 369.00 | 21.12 | 199.50 | 21.11 | 199.50 | 21.11 |
Annual Sum or Average | 2817.50 | 21.66 | 1562.67 | 22.55 | 836.00 | 21.15 |
Minimum of Months | 5.33 | 21.11 | 3.67 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 24.52 | 265.67 | 24.20 | 265.67 | 29.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 291.00 | 21.11 | 291.00 | 21.11 |
February | 308.00 | 21.28 | 174.17 | 21.11 | 174.17 | 21.11 |
March | 348.00 | 21.18 | 129.17 | 21.11 | 129.17 | 21.11 |
April | 330.00 | 21.95 | 30.50 | 21.11 | 30.50 | 21.11 |
May | 256.17 | 22.17 | 33.83 | 22.50 | 18.67 | 21.11 |
June | 50.17 | 23.11 | 113.00 | 23.99 | 0.00 | 0.00 |
July | 5.50 | 24.45 | 223.83 | 24.01 | 0.83 | 28.58 |
August | 21.83 | 23.37 | 156.67 | 24.00 | 0.83 | 28.94 |
September | 108.33 | 22.65 | 115.33 | 24.04 | 6.83 | 24.70 |
October | 243.50 | 22.36 | 3.67 | 21.69 | 3.17 | 21.11 |
November | 329.67 | 21.55 | 84.83 | 21.11 | 84.83 | 21.11 |
December | 338.00 | 21.11 | 224.00 | 21.11 | 224.00 | 21.11 |
Annual Sum or Average | 2679.17 | 21.64 | 1580.00 | 22.26 | 964.00 | 21.15 |
Minimum of Months | 5.50 | 21.11 | 3.67 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 24.45 | 291.00 | 24.04 | 291.00 | 28.94 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 292.50 | 21.11 | 292.50 | 21.11 |
February | 308.00 | 21.28 | 179.33 | 21.11 | 179.33 | 21.11 |
March | 348.00 | 21.17 | 136.67 | 21.11 | 136.67 | 21.11 |
April | 330.00 | 21.92 | 36.17 | 21.11 | 36.17 | 21.11 |
May | 262.00 | 22.19 | 32.33 | 22.15 | 22.00 | 21.11 |
June | 68.67 | 23.32 | 96.17 | 24.00 | 0.00 | 0.00 |
July | 7.50 | 24.28 | 185.50 | 24.03 | 0.83 | 28.45 |
August | 23.83 | 23.37 | 122.83 | 24.02 | 0.67 | 28.89 |
September | 118.83 | 22.74 | 102.17 | 24.06 | 6.67 | 24.60 |
October | 259.50 | 22.45 | 4.33 | 21.27 | 4.17 | 21.11 |
November | 330.00 | 21.54 | 91.33 | 21.11 | 91.33 | 21.11 |
December | 338.00 | 21.11 | 231.33 | 21.11 | 231.33 | 21.11 |
Annual Sum or Average | 2734.33 | 21.67 | 1510.67 | 22.11 | 1001.67 | 21.14 |
Minimum of Months | 7.50 | 21.11 | 4.33 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 24.28 | 292.50 | 24.06 | 292.50 | 28.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 296.33 | 21.11 | 296.33 | 21.11 |
February | 308.00 | 21.26 | 189.33 | 21.11 | 189.33 | 21.11 |
March | 348.00 | 21.16 | 144.33 | 21.11 | 144.33 | 21.11 |
April | 330.00 | 21.87 | 40.17 | 21.11 | 40.17 | 21.11 |
May | 268.00 | 22.18 | 35.33 | 21.93 | 26.50 | 21.11 |
June | 75.17 | 23.33 | 91.33 | 24.01 | 0.00 | 0.00 |
July | 8.33 | 24.22 | 178.67 | 24.03 | 0.83 | 28.42 |
August | 25.67 | 23.37 | 116.83 | 24.03 | 0.67 | 28.87 |
September | 125.17 | 22.75 | 98.67 | 24.07 | 6.83 | 24.57 |
October | 270.67 | 22.46 | 5.00 | 21.11 | 5.00 | 21.11 |
November | 330.00 | 21.49 | 97.17 | 21.11 | 97.17 | 21.11 |
December | 338.00 | 21.11 | 241.00 | 21.11 | 241.00 | 21.11 |
Annual Sum or Average | 2767.00 | 21.67 | 1534.17 | 22.05 | 1048.17 | 21.14 |
Minimum of Months | 8.33 | 21.11 | 5.00 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 24.22 | 296.33 | 24.07 | 296.33 | 28.87 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 309.83 | 21.11 | 309.83 | 21.11 |
February | 308.00 | 21.22 | 221.83 | 21.11 | 221.83 | 21.11 |
March | 348.00 | 21.14 | 173.00 | 21.11 | 173.00 | 21.11 |
April | 330.00 | 21.75 | 57.17 | 21.11 | 57.17 | 21.11 |
May | 284.33 | 22.17 | 42.67 | 21.46 | 38.33 | 21.11 |
June | 93.33 | 23.34 | 78.83 | 24.01 | 0.00 | 0.00 |
July | 11.17 | 24.00 | 166.17 | 24.03 | 0.67 | 28.53 |
August | 31.67 | 23.32 | 109.50 | 24.03 | 0.50 | 28.90 |
September | 141.00 | 22.74 | 92.33 | 24.07 | 7.00 | 24.49 |
October | 290.00 | 22.42 | 7.33 | 21.11 | 7.33 | 21.11 |
November | 330.00 | 21.40 | 114.33 | 21.11 | 114.33 | 21.11 |
December | 338.00 | 21.11 | 258.17 | 21.11 | 258.17 | 21.11 |
Annual Sum or Average | 2845.50 | 21.66 | 1631.17 | 21.92 | 1188.17 | 21.13 |
Minimum of Months | 11.17 | 21.11 | 7.33 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 24.00 | 309.83 | 24.07 | 309.83 | 28.90 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 333.00 | 21.11 | 333.00 | 21.11 |
February | 308.00 | 21.17 | 275.67 | 21.11 | 275.67 | 21.11 |
March | 348.00 | 21.11 | 284.17 | 21.11 | 284.17 | 21.11 |
April | 330.00 | 21.53 | 157.17 | 21.11 | 157.17 | 21.11 |
May | 320.67 | 22.14 | 82.33 | 21.16 | 81.50 | 21.11 |
June | 139.83 | 23.28 | 58.17 | 24.02 | 0.00 | 0.00 |
July | 23.00 | 23.72 | 150.33 | 24.04 | 0.67 | 28.54 |
August | 48.17 | 23.24 | 100.17 | 24.03 | 0.67 | 28.88 |
September | 159.33 | 22.62 | 85.67 | 23.99 | 9.50 | 23.70 |
October | 323.17 | 22.30 | 21.67 | 21.11 | 21.67 | 21.11 |
November | 330.00 | 21.27 | 174.50 | 21.11 | 174.50 | 21.11 |
December | 338.00 | 21.11 | 315.33 | 21.11 | 315.33 | 21.11 |
Annual Sum or Average | 3008.17 | 21.65 | 2038.17 | 21.67 | 1653.83 | 21.13 |
Minimum of Months | 23.00 | 21.11 | 21.67 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.72 | 333.00 | 24.04 | 333.00 | 28.88 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 20.94042 | 10.67329 | -0.6736 | 15.37383 |
February | 448.00000 | 21.19807 | 13.79754 | -0.5378 | 12.32655 |
March | 496.00000 | 21.10127 | 15.56685 | -0.5202 | 11.30789 |
April | 480.00000 | 22.06325 | 20.17606 | -0.2371 | 7.76836 |
May | 496.00000 | 22.74824 | 23.69787 | -1.0316 | 30.86103 |
June | 480.00000 | 23.81841 | 30.79163 | -0.5454 | 11.98794 |
July | 496.00000 | 23.95036 | 33.60943 | -0.4248 | 8.98364 |
August | 496.00000 | 23.91073 | 30.07182 | -0.4699 | 9.94741 |
September | 480.00000 | 23.57095 | 30.95549 | -0.6115 | 14.89218 |
October | 496.00000 | 22.97541 | 22.18498 | 0.05349 | 6.54389 |
November | 480.00000 | 21.77366 | 16.60747 | -0.3176 | 8.83667 |
December | 496.00000 | 20.99224 | 12.94698 | -0.5977 | 13.10914 |
Annual Sum or Average | 5840.00000 | 22.42606 | 21.79052 | -0.4932 | 12.68392 |
Minimum of Months | 448.00000 | 20.94042 | 10.67329 | -1.0316 | 6.54389 |
Maximum of Months | 496.00000 | 23.95036 | 33.60943 | 0.05349 | 30.86103 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.29119 | 11.71956 | -0.5472 | 12.34585 |
February | 448.00000 | 21.76239 | 14.40834 | -0.3819 | 9.66419 |
March | 496.00000 | 21.82254 | 16.30847 | -0.3351 | 8.35367 |
April | 480.00000 | 22.80364 | 20.06400 | -0.0585 | 6.39999 |
May | 496.00000 | 23.15535 | 23.63079 | -0.8881 | 24.27268 |
June | 480.00000 | 23.84577 | 30.64732 | -0.5257 | 11.24873 |
July | 496.00000 | 23.90531 | 33.59213 | -0.4392 | 9.30243 |
August | 496.00000 | 23.89017 | 30.16909 | -0.4751 | 10.00525 |
September | 480.00000 | 23.70911 | 30.78038 | -0.5665 | 12.88825 |
October | 496.00000 | 23.39012 | 21.97241 | 0.14567 | 6.36206 |
November | 480.00000 | 22.43197 | 16.92533 | -0.1628 | 7.29985 |
December | 496.00000 | 21.48025 | 13.94465 | -0.4578 | 10.20593 |
Annual Sum or Average | 5840.00000 | 22.79464 | 22.04766 | -0.3918 | 10.71777 |
Minimum of Months | 448.00000 | 21.29119 | 11.71956 | -0.8881 | 6.36206 |
Maximum of Months | 496.00000 | 23.90531 | 33.59213 | 0.14567 | 24.27268 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.09081 | 10.31241 | -0.6172 | 13.40396 |
February | 336.00000 | 21.40150 | 13.11844 | -0.4750 | 10.79110 |
March | 379.00000 | 21.32498 | 15.26547 | -0.4439 | 9.63780 |
April | 360.00000 | 22.28694 | 19.55485 | -0.1696 | 7.12630 |
May | 375.00000 | 22.88167 | 22.98832 | -0.9825 | 28.84266 |
June | 366.00000 | 23.92726 | 30.29513 | -0.5068 | 11.15892 |
July | 369.00000 | 24.07432 | 33.04295 | -0.3913 | 8.67246 |
August | 379.00000 | 24.02312 | 29.79215 | -0.4358 | 9.46236 |
September | 360.00000 | 23.68105 | 30.72615 | -0.5773 | 14.02413 |
October | 371.00000 | 23.07630 | 21.84241 | 0.07930 | 6.54919 |
November | 360.00000 | 21.93202 | 16.35346 | -0.2726 | 8.15715 |
December | 369.00000 | 21.12362 | 12.76499 | -0.5488 | 11.64437 |
Annual Sum or Average | 4395.00000 | 22.57654 | 21.39118 | -0.4461 | 11.65306 |
Minimum of Months | 336.00000 | 21.09081 | 10.31241 | -0.9825 | 6.54919 |
Maximum of Months | 379.00000 | 24.07432 | 33.04295 | 0.07930 | 28.84266 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.08565 | 10.31211 | -0.6313 | 13.76843 |
February | 336.00000 | 21.36275 | 13.14564 | -0.4954 | 11.12506 |
March | 379.00000 | 21.27796 | 15.30453 | -0.4655 | 9.99992 |
April | 360.00000 | 22.20084 | 19.65673 | -0.1978 | 7.30748 |
May | 375.00000 | 22.83043 | 23.05120 | -1.0088 | 29.99711 |
June | 366.00000 | 23.92266 | 30.30537 | -0.5100 | 11.25337 |
July | 369.00000 | 24.07460 | 33.04012 | -0.3900 | 8.65728 |
August | 379.00000 | 24.02268 | 29.79157 | -0.4352 | 9.45870 |
September | 360.00000 | 23.65971 | 30.76040 | -0.5866 | 14.41595 |
October | 371.00000 | 23.02433 | 21.91185 | 0.06190 | 6.58191 |
November | 360.00000 | 21.84872 | 16.44291 | -0.3014 | 8.42070 |
December | 369.00000 | 21.11038 | 12.77411 | -0.5643 | 12.00079 |
Annual Sum or Average | 4395.00000 | 22.54319 | 21.42764 | -0.4612 | 11.94657 |
Minimum of Months | 336.00000 | 21.08565 | 10.31211 | -1.0088 | 6.58191 |
Maximum of Months | 379.00000 | 24.07460 | 33.04012 | 0.06190 | 29.99711 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.08147 | 10.32282 | -0.6460 | 14.17028 |
February | 336.00000 | 21.32303 | 13.18519 | -0.5168 | 11.50922 |
March | 379.00000 | 21.23146 | 15.35184 | -0.4876 | 10.40039 |
April | 360.00000 | 22.09355 | 19.79079 | -0.2310 | 7.54169 |
May | 375.00000 | 22.75568 | 23.15354 | -1.0440 | 31.50319 |
June | 366.00000 | 23.90594 | 30.34061 | -0.5220 | 11.56593 |
July | 369.00000 | 24.06921 | 33.05584 | -0.3968 | 8.76164 |
August | 379.00000 | 24.01326 | 29.81059 | -0.4436 | 9.63007 |
September | 360.00000 | 23.62037 | 30.84215 | -0.6053 | 15.08046 |
October | 371.00000 | 22.94685 | 22.02022 | 0.03851 | 6.60993 |
November | 360.00000 | 21.73959 | 16.57236 | -0.3354 | 8.72613 |
December | 369.00000 | 21.09988 | 12.79184 | -0.5795 | 12.37003 |
Annual Sum or Average | 4395.00000 | 22.49839 | 21.48919 | -0.4816 | 12.35447 |
Minimum of Months | 336.00000 | 21.08147 | 10.32282 | -1.0440 | 6.60993 |
Maximum of Months | 379.00000 | 24.06921 | 33.05584 | 0.03851 | 31.50319 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.07205 | 11.08909 | -0.6842 | 15.24270 |
February | 308.00000 | 21.25604 | 13.97848 | -0.5600 | 12.38250 |
March | 348.00000 | 21.15525 | 16.24613 | -0.5266 | 11.16466 |
April | 330.00000 | 21.93821 | 20.69539 | -0.2820 | 7.94412 |
May | 344.00000 | 22.62459 | 23.89268 | -1.1062 | 34.08971 |
June | 336.00000 | 23.82085 | 30.92725 | -0.5547 | 12.28956 |
July | 338.00000 | 23.98042 | 33.62469 | -0.4218 | 9.06411 |
August | 348.00000 | 23.91045 | 30.48082 | -0.4730 | 10.14124 |
September | 330.00000 | 23.52190 | 31.67304 | -0.6397 | 16.23594 |
October | 340.00000 | 22.80471 | 22.89573 | 0.00055 | 6.64259 |
November | 330.00000 | 21.54745 | 17.59535 | -0.3952 | 9.37085 |
December | 338.00000 | 21.08228 | 13.59501 | -0.6147 | 13.26672 |
Annual Sum or Average | 4030.00000 | 22.40153 | 22.27795 | -0.5222 | 13.18735 |
Minimum of Months | 308.00000 | 21.07205 | 11.08909 | -1.1062 | 6.64259 |
Maximum of Months | 348.00000 | 23.98042 | 33.62469 | 0.00055 | 34.08971 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.07162 | 11.03360 | -0.6829 | 15.18574 |
February | 308.00000 | 21.24935 | 13.93139 | -0.5655 | 12.46601 |
March | 348.00000 | 21.15052 | 16.19631 | -0.5360 | 11.35651 |
April | 330.00000 | 21.91280 | 20.67483 | -0.2992 | 8.12597 |
May | 344.00000 | 22.60828 | 23.87732 | -1.1290 | 35.00641 |
June | 336.00000 | 23.81872 | 30.89992 | -0.5774 | 12.81084 |
July | 338.00000 | 23.97836 | 33.58518 | -0.4477 | 9.52162 |
August | 348.00000 | 23.90882 | 30.43712 | -0.4984 | 10.64063 |
September | 330.00000 | 23.51880 | 31.64328 | -0.6629 | 16.82315 |
October | 340.00000 | 22.80048 | 22.85240 | -0.0135 | 6.63924 |
November | 330.00000 | 21.52986 | 17.56167 | -0.4084 | 9.53039 |
December | 338.00000 | 21.08147 | 13.53894 | -0.6173 | 13.32012 |
Annual Sum or Average | 4030.00000 | 22.39449 | 22.23945 | -0.5374 | 13.48894 |
Minimum of Months | 308.00000 | 21.07162 | 11.03360 | -1.1290 | 6.63924 |
Maximum of Months | 348.00000 | 23.97836 | 33.58518 | -0.0135 | 35.00641 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.07071 | 11.03425 | -0.6879 | 15.32651 |
February | 308.00000 | 21.23172 | 13.94772 | -0.5751 | 12.65056 |
March | 348.00000 | 21.13753 | 16.20845 | -0.5457 | 11.56559 |
April | 330.00000 | 21.85993 | 20.74470 | -0.3184 | 8.33818 |
May | 344.00000 | 22.57017 | 23.94183 | -1.1504 | 35.93157 |
June | 336.00000 | 23.80835 | 30.92930 | -0.5873 | 13.09055 |
July | 338.00000 | 23.97576 | 33.59063 | -0.4537 | 9.63410 |
August | 348.00000 | 23.90391 | 30.44738 | -0.5052 | 10.79990 |
September | 330.00000 | 23.49685 | 31.69154 | -0.6755 | 17.26560 |
October | 340.00000 | 22.75554 | 22.91983 | -0.0282 | 6.66802 |
November | 330.00000 | 21.48357 | 17.61777 | -0.4245 | 9.73307 |
December | 338.00000 | 21.07884 | 13.54171 | -0.6236 | 13.48370 |
Annual Sum or Average | 4030.00000 | 22.37326 | 22.27129 | -0.5488 | 13.74481 |
Minimum of Months | 308.00000 | 21.07071 | 11.03425 | -1.1504 | 6.66802 |
Maximum of Months | 348.00000 | 23.97576 | 33.59063 | -0.0282 | 35.93157 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06728 | 11.03249 | -0.7048 | 15.82534 |
February | 308.00000 | 21.18987 | 13.98244 | -0.6027 | 13.25578 |
March | 348.00000 | 21.10680 | 16.23437 | -0.5723 | 12.18664 |
April | 330.00000 | 21.73109 | 20.91173 | -0.3664 | 8.95716 |
May | 344.00000 | 22.46866 | 24.11581 | -1.2052 | 38.35636 |
June | 336.00000 | 23.77351 | 31.02150 | -0.6128 | 13.86812 |
July | 338.00000 | 23.96779 | 33.60819 | -0.4646 | 9.85209 |
August | 348.00000 | 23.88914 | 30.47586 | -0.5186 | 11.15493 |
September | 330.00000 | 23.43911 | 31.81532 | -0.7046 | 18.34906 |
October | 340.00000 | 22.63617 | 23.09798 | -0.0649 | 6.77905 |
November | 330.00000 | 21.38884 | 17.73166 | -0.4602 | 10.27358 |
December | 338.00000 | 21.07267 | 13.54307 | -0.6431 | 14.01368 |
Annual Sum or Average | 4030.00000 | 22.31998 | 22.35079 | -0.5774 | 14.44501 |
Minimum of Months | 308.00000 | 21.06728 | 11.03249 | -1.2052 | 6.77905 |
Maximum of Months | 348.00000 | 23.96779 | 33.60819 | -0.0649 | 38.35636 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06313 | 10.93452 | -0.7779 | 18.15916 |
February | 308.00000 | 21.12736 | 13.95435 | -0.6890 | 15.55209 |
March | 348.00000 | 21.06864 | 16.13094 | -0.6565 | 14.42656 |
April | 330.00000 | 21.49715 | 21.08274 | -0.4849 | 11.01717 |
May | 344.00000 | 22.24081 | 24.47740 | -1.3462 | 44.79277 |
June | 336.00000 | 23.65654 | 31.28992 | -0.6885 | 16.42655 |
July | 338.00000 | 23.94190 | 33.71852 | -0.4856 | 10.37564 |
August | 348.00000 | 23.83924 | 30.54122 | -0.5498 | 12.20042 |
September | 330.00000 | 23.30866 | 31.98011 | -0.7734 | 21.09314 |
October | 340.00000 | 22.36808 | 23.37054 | -0.1539 | 7.31110 |
November | 330.00000 | 21.24048 | 17.83373 | -0.5450 | 11.96829 |
December | 338.00000 | 21.06440 | 13.47565 | -0.7155 | 16.14932 |
Annual Sum or Average | 4030.00000 | 22.21058 | 22.45278 | -0.6562 | 16.66391 |
Minimum of Months | 308.00000 | 21.06313 | 10.93452 | -1.3462 | 7.31110 |
Maximum of Months | 348.00000 | 23.94190 | 33.71852 | -0.1539 | 44.79277 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 2582.98 | 729.14 | 5.33 | 2582.98 | 0.00 | 0.00 | 0.00 | 27-FEB-15:30 | 0.00 | 01-FEB-00:05 | 0.32 | 27-FEB-15:30 | 0.32 | 27-FEB-15:30 | 0.00 | 27-FEB-12:50 | 0.09 | 27-FEB-15:30 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 97718874.51 | 27013167.02 | 40.75 | 97718874.51 | 0.00 | 0.00 | 0.24 | 07-APR-14:00 | 0.00 | 01-APR-00:10 | 6219.84 | 07-APR-14:00 | 6219.84 | 07-APR-14:00 | 0.00 | 06-APR-16:30 | 1716.30 | 07-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.205346E+10 | 0.560618E+09 | 153.09 | 0.204500E+10 | 8461588.85 | 0.00 | 1.00 | 20-MAY-08:62 | 0.00 | 01-MAY-00:10 | 32542.70 | 20-MAY-08:62 | 31432.39 | 20-MAY-08:62 | 3261.93 | 30-MAY-08:62 | 6903.48 | 20-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.814835E+10 | 0.223387E+10 | 329.01 | 0.779845E+10 | 0.349901E+09 | 0.00 | 1.00 | 06-JUN-08:62 | 0.00 | 01-JUN-00:10 | 34227.21 | 22-JUN-08:61 | 32563.81 | 23-JUN-08:61 | 7449.42 | 13-JUN-08:62 | 7385.28 | 22-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.161250E+11 | 0.450586E+10 | 429.16 | 0.157077E+11 | 0.417357E+09 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 35411.73 | 19-JUL-08:61 | 33503.49 | 18-JUL-08:61 | 9479.79 | 19-JUL-08:04 | 7816.71 | 18-JUL-08:61 | 0.00 | 01-JUL-00:03 |
August | 0.130341E+11 | 0.363713E+10 | 398.43 | 0.129643E+11 | 69843251.90 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 33526.95 | 09-AUG-08:61 | 33526.95 | 09-AUG-08:61 | 6428.10 | 22-AUG-08:62 | 7658.50 | 07-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.703486E+10 | 0.192513E+10 | 271.24 | 0.668132E+10 | 0.353536E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 33655.18 | 07-SEP-08:61 | 32718.76 | 02-SEP-08:61 | 12366.74 | 07-SEP-08:03 | 7166.12 | 07-SEP-08:61 | 0.00 | 01-SEP-00:10 |
October | 0.830360E+09 | 0.222174E+09 | 124.22 | 0.830232E+09 | 127587.91 | 0.00 | 0.79 | 16-OCT-08:62 | 0.00 | 01-OCT-00:05 | 23643.04 | 16-OCT-08:62 | 23643.04 | 16-OCT-08:62 | 850.41 | 25-OCT-08:62 | 5362.68 | 16-OCT-08:62 | 0.00 | 01-OCT-00:05 |
November | 10830.88 | 3057.40 | 19.58 | 10830.88 | 0.00 | 0.00 | 0.00 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.45 | 03-NOV-14:00 | 0.45 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.13 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.473239E+11 | 0.131118E+11 | 1770.82 | 0.461247E+11 | 0.119923E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.161250E+11 | 0.450586E+10 | 429.16 | 0.157077E+11 | 0.417357E+09 | 0.00 | 1.00 | 0.00 | 35411.73 | 33526.95 | 12366.74 | 7816.71 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 11315094.12 | 2844511.02 | 12.83 | 11315094.12 | 0.00 | 0.00 | 1.00 | 26-FEB-18:15 | 0.00 | 01-FEB-00:05 | 17312.25 | 26-FEB-18:15 | 17312.25 | 26-FEB-18:15 | 0.00 | 26-FEB-18:15 | 3559.62 | 26-FEB-18:15 | 0.00 | 01-FEB-00:05 |
March | 1031269.27 | 303730.31 | 2.83 | 1031269.27 | 0.00 | 0.00 | 0.02 | 29-MAR-22:10 | 0.00 | 01-MAR-00:05 | 214.99 | 29-MAR-22:10 | 214.99 | 29-MAR-22:10 | 0.00 | 01-MAR-00:05 | 63.20 | 29-MAR-22:10 | 0.00 | 01-MAR-00:05 |
April | 0.126798E+09 | 31965987.15 | 60.33 | 0.126798E+09 | 0.00 | 0.00 | 1.00 | 06-APR-20:02 | 0.00 | 01-APR-00:10 | 17312.25 | 06-APR-20:02 | 17312.25 | 06-APR-20:02 | 0.00 | 07-APR-16:20 | 3559.62 | 06-APR-20:02 | 0.00 | 01-APR-00:10 |
May | 0.149851E+10 | 0.373209E+09 | 145.66 | 0.148717E+10 | 11341218.53 | 0.00 | 1.00 | 12-MAY-20:11 | 0.00 | 01-MAY-00:10 | 17647.52 | 20-MAY-18:17 | 17647.52 | 20-MAY-18:17 | 2818.87 | 20-MAY-21:10 | 3820.04 | 20-MAY-18:17 | 0.00 | 01-MAY-00:10 |
June | 0.506172E+10 | 0.129876E+10 | 292.40 | 0.484231E+10 | 0.219415E+09 | 0.00 | 1.00 | 03-JUN-08:62 | 0.00 | 01-JUN-00:10 | 18465.49 | 21-JUN-20:02 | 17684.38 | 23-JUN-08:61 | 5792.84 | 21-JUN-22:49 | 3925.41 | 18-JUN-19:11 | 0.00 | 01-JUN-00:10 |
July | 0.926473E+10 | 0.245563E+10 | 372.17 | 0.899255E+10 | 0.272179E+09 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 19024.31 | 18-JUL-21:56 | 18027.02 | 18-JUL-08:61 | 8130.34 | 18-JUL-21:56 | 4082.60 | 18-JUL-08:61 | 0.00 | 01-JUL-00:03 |
August | 0.762491E+10 | 0.201250E+10 | 346.78 | 0.756465E+10 | 60252274.31 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 18022.87 | 09-AUG-08:61 | 18022.87 | 09-AUG-08:61 | 3770.36 | 15-AUG-20:50 | 4001.48 | 07-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.414087E+10 | 0.107438E+10 | 239.19 | 0.392901E+10 | 0.211861E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 18761.03 | 06-SEP-20:02 | 17623.09 | 24-SEP-17:11 | 6555.72 | 06-SEP-22:49 | 3886.20 | 06-SEP-20:02 | 0.00 | 01-SEP-00:10 |
October | 0.578003E+09 | 0.146498E+09 | 123.05 | 0.577835E+09 | 167340.56 | 0.00 | 1.00 | 02-OCT-20:02 | 0.00 | 01-OCT-00:05 | 17312.25 | 02-OCT-20:02 | 17312.25 | 02-OCT-20:02 | 1064.88 | 25-OCT-08:62 | 3559.62 | 02-OCT-20:02 | 0.00 | 01-OCT-00:05 |
November | 22837288.57 | 6209381.97 | 31.60 | 22837288.57 | 0.00 | 0.00 | 1.00 | 03-NOV-20:02 | 0.00 | 01-NOV-00:10 | 17312.25 | 03-NOV-20:02 | 17312.25 | 03-NOV-20:02 | 0.00 | 05-NOV-17:01 | 3559.62 | 03-NOV-20:02 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.283307E+11 | 0.740231E+10 | 1626.83 | 0.275555E+11 | 0.775217E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.926473E+10 | 0.245563E+10 | 372.17 | 0.899255E+10 | 0.272179E+09 | 0.00 | 1.00 | 0.00 | 19024.31 | 18027.02 | 8130.34 | 4082.60 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 1917.11 | 525.57 | 7.00 | 1917.11 | 0.00 | 0.00 | 0.00 | 27-FEB-15:30 | 0.00 | 01-FEB-00:05 | 0.17 | 27-FEB-15:30 | 0.17 | 27-FEB-15:30 | 0.00 | 01-FEB-00:05 | 0.05 | 27-FEB-15:30 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 68804558.63 | 18343264.29 | 41.53 | 68804558.63 | 0.00 | 0.00 | 0.27 | 07-APR-14:00 | 0.00 | 01-APR-00:10 | 3775.19 | 07-APR-14:00 | 3775.19 | 07-APR-14:00 | 0.00 | 07-APR-15:00 | 1003.57 | 07-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.914901E+09 | 0.242357E+09 | 119.38 | 0.909727E+09 | 5174547.71 | 0.00 | 1.00 | 20-MAY-07:02 | 0.00 | 01-MAY-00:10 | 17354.62 | 20-MAY-07:02 | 16206.39 | 20-MAY-07:02 | 3168.31 | 21-MAY-08:62 | 3572.06 | 20-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.367462E+10 | 0.981149E+09 | 256.25 | 0.353323E+10 | 0.141384E+09 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 18251.63 | 22-JUN-07:01 | 17270.26 | 29-JUN-07:02 | 4800.61 | 04-JUN-08:62 | 3774.55 | 22-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.692802E+10 | 0.188537E+10 | 307.87 | 0.676444E+10 | 0.163582E+09 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 18875.22 | 19-JUL-07:01 | 17859.99 | 18-JUL-07:01 | 6369.71 | 04-JUL-08:62 | 3901.80 | 19-JUL-07:01 | 0.00 | 01-JUL-00:03 |
August | 0.574212E+10 | 0.155815E+10 | 292.54 | 0.570691E+10 | 35213402.95 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 17797.90 | 09-AUG-07:01 | 17770.23 | 06-AUG-08:61 | 4050.85 | 14-AUG-07:02 | 3851.06 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.298558E+10 | 0.791158E+09 | 206.00 | 0.282978E+10 | 0.155800E+09 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 18004.47 | 07-SEP-07:01 | 17833.43 | 04-SEP-08:61 | 6381.87 | 07-SEP-07:03 | 3994.27 | 04-SEP-08:61 | 0.00 | 01-SEP-00:10 |
October | 0.439017E+09 | 0.113735E+09 | 103.99 | 0.438172E+09 | 845321.99 | 0.00 | 1.00 | 19-OCT-07:01 | 0.00 | 01-OCT-00:05 | 17270.26 | 25-OCT-07:02 | 17270.26 | 19-OCT-07:01 | 3116.42 | 01-OCT-08:61 | 3550.98 | 19-OCT-07:01 | 0.00 | 01-OCT-00:05 |
November | 5306.36 | 1454.73 | 16.71 | 5304.74 | 1.62 | 0.00 | 0.00 | 05-NOV-08:61 | 0.00 | 01-NOV-00:10 | 3.30 | 05-NOV-08:61 | 3.28 | 05-NOV-08:61 | 0.02 | 05-NOV-08:61 | 0.91 | 05-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.207531E+11 | 0.559026E+10 | 1351.29 | 0.202511E+11 | 0.502000E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.692802E+10 | 0.188537E+10 | 307.87 | 0.676444E+10 | 0.163582E+09 | 0.00 | 1.00 | 0.00 | 18875.22 | 17859.99 | 6381.87 | 3994.27 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 1914.33 | 524.81 | 6.50 | 1914.33 | 0.00 | 0.00 | 0.00 | 27-FEB-11:40 | 0.00 | 01-FEB-00:05 | 0.18 | 27-FEB-11:40 | 0.18 | 27-FEB-11:40 | 0.00 | 26-FEB-15:50 | 0.05 | 27-FEB-11:40 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 60808481.26 | 16266186.60 | 36.17 | 60808481.26 | 0.00 | 0.00 | 0.26 | 07-APR-14:00 | 0.00 | 01-APR-00:10 | 3588.31 | 07-APR-14:00 | 3588.31 | 07-APR-14:00 | 0.00 | 07-APR-17:10 | 957.36 | 07-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.889108E+09 | 0.235967E+09 | 116.36 | 0.884213E+09 | 4894760.72 | 0.00 | 1.00 | 20-MAY-07:02 | 0.00 | 01-MAY-00:10 | 17413.47 | 20-MAY-07:02 | 16256.88 | 20-MAY-07:02 | 3179.02 | 21-MAY-08:62 | 3584.11 | 20-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.365885E+10 | 0.977655E+09 | 255.94 | 0.351804E+10 | 0.140811E+09 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 18315.72 | 22-JUN-07:01 | 17330.17 | 29-JUN-07:02 | 4821.76 | 04-JUN-08:62 | 3787.80 | 22-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.695606E+10 | 0.189290E+10 | 308.20 | 0.679097E+10 | 0.165085E+09 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 18942.66 | 19-JUL-07:01 | 17925.27 | 18-JUL-07:01 | 6388.80 | 04-JUL-08:62 | 3915.66 | 19-JUL-07:01 | 0.00 | 01-JUL-00:03 |
August | 0.575830E+10 | 0.156271E+10 | 291.99 | 0.572289E+10 | 35412631.01 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 17859.88 | 09-AUG-07:01 | 17833.05 | 06-AUG-08:61 | 4057.58 | 14-AUG-07:02 | 3864.64 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.298289E+10 | 0.790650E+09 | 204.21 | 0.282606E+10 | 0.156826E+09 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 18068.87 | 07-SEP-07:01 | 17897.40 | 04-SEP-08:61 | 6398.24 | 07-SEP-07:03 | 4008.44 | 04-SEP-08:61 | 0.00 | 01-SEP-00:10 |
October | 0.415356E+09 | 0.107843E+09 | 101.31 | 0.414624E+09 | 731550.80 | 0.00 | 1.00 | 19-OCT-07:01 | 0.00 | 01-OCT-00:05 | 17330.17 | 25-OCT-07:02 | 17330.17 | 19-OCT-07:01 | 2852.83 | 01-OCT-08:61 | 3563.30 | 19-OCT-07:01 | 0.00 | 01-OCT-00:05 |
November | 6501.68 | 1782.37 | 12.69 | 6501.68 | 0.00 | 0.00 | 0.00 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 4.54 | 05-NOV-15:00 | 4.54 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 1.24 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.207214E+11 | 0.558399E+10 | 1333.37 | 0.202176E+11 | 0.503762E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.695606E+10 | 0.189290E+10 | 308.20 | 0.679097E+10 | 0.165085E+09 | 0.00 | 1.00 | 0.00 | 18942.66 | 17925.27 | 6398.24 | 4008.44 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 1430.14 | 392.07 | 5.83 | 1430.14 | 0.00 | 0.00 | 0.00 | 27-FEB-15:30 | 0.00 | 01-FEB-00:05 | 0.15 | 27-FEB-15:30 | 0.15 | 27-FEB-15:30 | 0.00 | 26-FEB-16:40 | 0.04 | 27-FEB-15:30 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 49993031.61 | 13434389.20 | 31.83 | 49993031.61 | 0.00 | 0.00 | 0.24 | 07-APR-14:00 | 0.00 | 01-APR-00:10 | 3296.91 | 07-APR-14:00 | 3296.91 | 07-APR-14:00 | 0.00 | 06-APR-15:50 | 884.04 | 07-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.836061E+09 | 0.222677E+09 | 111.40 | 0.831858E+09 | 4202990.46 | 0.00 | 1.00 | 20-MAY-07:02 | 0.00 | 01-MAY-00:10 | 17321.57 | 20-MAY-07:02 | 16143.36 | 20-MAY-07:02 | 2825.83 | 30-MAY-07:02 | 3564.90 | 20-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.354818E+10 | 0.950280E+09 | 253.25 | 0.341252E+10 | 0.135655E+09 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 18221.65 | 22-JUN-07:01 | 17245.76 | 29-JUN-07:02 | 4820.48 | 04-JUN-08:62 | 3768.37 | 22-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.681984E+10 | 0.185903E+10 | 306.81 | 0.665918E+10 | 0.160657E+09 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 18846.52 | 19-JUL-07:01 | 17833.90 | 18-JUL-07:01 | 6374.39 | 04-JUL-08:62 | 3895.96 | 19-JUL-07:01 | 0.00 | 01-JUL-00:03 |
August | 0.563390E+10 | 0.153176E+10 | 290.37 | 0.560013E+10 | 33770192.41 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 17772.21 | 09-AUG-07:01 | 17745.06 | 06-AUG-08:61 | 4054.59 | 14-AUG-07:02 | 3845.60 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.290499E+10 | 0.771304E+09 | 198.91 | 0.275196E+10 | 0.153026E+09 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 17977.16 | 07-SEP-07:01 | 17809.10 | 04-SEP-08:61 | 6383.40 | 07-SEP-07:03 | 3988.75 | 04-SEP-08:61 | 0.00 | 01-SEP-00:10 |
October | 0.381380E+09 | 99354755.18 | 93.11 | 0.380887E+09 | 492867.93 | 0.00 | 1.00 | 19-OCT-07:01 | 0.00 | 01-OCT-00:05 | 17245.76 | 19-OCT-07:01 | 17245.76 | 19-OCT-07:01 | 1815.95 | 01-OCT-08:61 | 3545.94 | 19-OCT-07:01 | 0.00 | 01-OCT-00:05 |
November | 2899.15 | 794.80 | 10.00 | 2899.15 | 0.00 | 0.00 | 0.00 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.21 | 04-NOV-14:00 | 0.21 | 04-NOV-14:00 | 0.00 | 04-NOV-11:50 | 0.06 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.201743E+11 | 0.544784E+10 | 1301.51 | 0.196865E+11 | 0.487804E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.681984E+10 | 0.185903E+10 | 306.81 | 0.665918E+10 | 0.160657E+09 | 0.00 | 1.00 | 0.00 | 18846.52 | 17833.90 | 6383.40 | 3988.75 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 1359.68 | 383.82 | 2.50 | 1359.68 | 0.00 | 0.00 | 0.00 | 27-FEB-15:10 | 0.00 | 01-FEB-00:05 | 0.30 | 27-FEB-15:10 | 0.30 | 27-FEB-15:10 | 0.00 | 01-FEB-00:05 | 0.08 | 27-FEB-15:10 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 61963208.21 | 17271321.78 | 24.75 | 61963208.21 | 0.00 | 0.00 | 0.20 | 07-APR-14:00 | 0.00 | 01-APR-00:10 | 5070.76 | 07-APR-14:00 | 5070.76 | 07-APR-14:00 | 0.00 | 07-APR-12:30 | 1413.86 | 07-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.138427E+10 | 0.382229E+09 | 100.73 | 0.137800E+10 | 6263576.49 | 0.00 | 1.00 | 20-MAY-08:62 | 0.00 | 01-MAY-00:10 | 31974.06 | 20-MAY-08:62 | 30714.23 | 20-MAY-08:62 | 2864.74 | 21-MAY-09:02 | 6783.84 | 20-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.634586E+10 | 0.175737E+10 | 246.51 | 0.607835E+10 | 0.267511E+09 | 0.00 | 1.00 | 04-JUN-09:02 | 0.00 | 01-JUN-00:10 | 33528.42 | 22-JUN-08:61 | 31658.79 | 23-JUN-08:61 | 6984.11 | 13-JUN-08:62 | 7247.60 | 23-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.122340E+11 | 0.344798E+10 | 299.26 | 0.119435E+11 | 0.290526E+09 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 34620.39 | 19-JUL-08:61 | 32897.10 | 18-JUL-08:61 | 13122.69 | 04-JUL-09:02 | 7674.48 | 18-JUL-08:61 | 0.00 | 01-JUL-00:03 |
August | 0.101054E+11 | 0.284083E+10 | 292.88 | 0.100461E+11 | 59296202.46 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 32884.85 | 09-AUG-08:61 | 32884.85 | 09-AUG-08:61 | 6355.20 | 22-AUG-08:62 | 7777.73 | 06-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.506649E+10 | 0.138787E+10 | 181.64 | 0.477078E+10 | 0.295710E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 32978.45 | 07-SEP-08:61 | 32722.51 | 04-SEP-09:01 | 11826.36 | 07-SEP-08:03 | 7697.23 | 04-SEP-09:01 | 0.00 | 01-SEP-00:10 |
October | 0.604087E+09 | 0.162996E+09 | 79.04 | 0.604028E+09 | 58934.93 | 0.00 | 0.68 | 19-OCT-08:62 | 0.00 | 01-OCT-00:05 | 19414.02 | 19-OCT-08:62 | 19414.02 | 19-OCT-08:62 | 392.90 | 25-OCT-08:62 | 4549.72 | 19-OCT-08:62 | 0.00 | 01-OCT-00:05 |
November | 2146.34 | 605.88 | 4.67 | 2146.34 | 0.00 | 0.00 | 0.00 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.35 | 04-NOV-14:00 | 0.35 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.10 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.358021E+11 | 0.999653E+10 | 1231.98 | 0.348828E+11 | 0.919365E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.122340E+11 | 0.344798E+10 | 299.26 | 0.119435E+11 | 0.295710E+09 | 0.00 | 1.00 | 0.00 | 34620.39 | 32897.10 | 13122.69 | 7777.73 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 4100.06 | 1123.92 | 2.50 | 4100.06 | 0.00 | 0.00 | 0.00 | 27-FEB-13:20 | 0.00 | 01-FEB-00:05 | 5.73 | 27-FEB-13:20 | 5.73 | 27-FEB-13:20 | 0.00 | 27-FEB-15:10 | 1.57 | 27-FEB-13:20 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 28969249.01 | 7854582.76 | 24.58 | 28969249.01 | 0.00 | 0.00 | 0.20 | 07-APR-14:00 | 0.00 | 01-APR-00:10 | 2551.41 | 07-APR-14:00 | 2551.41 | 07-APR-14:00 | 0.00 | 07-APR-15:50 | 691.82 | 07-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.704000E+09 | 0.188980E+09 | 99.48 | 0.701315E+09 | 2685367.75 | 0.00 | 1.00 | 20-MAY-08:62 | 0.00 | 01-MAY-00:10 | 16518.69 | 20-MAY-08:62 | 15895.68 | 20-MAY-08:62 | 1122.33 | 21-MAY-09:02 | 3403.66 | 20-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.326085E+10 | 0.877510E+09 | 245.68 | 0.312719E+10 | 0.133667E+09 | 0.00 | 1.00 | 04-JUN-09:02 | 0.00 | 01-JUN-00:10 | 17322.54 | 22-JUN-08:61 | 16384.91 | 23-JUN-08:61 | 3588.23 | 13-JUN-08:62 | 3636.49 | 23-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.631254E+10 | 0.172829E+10 | 299.14 | 0.616751E+10 | 0.145027E+09 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 17888.96 | 19-JUL-08:61 | 16998.75 | 18-JUL-08:61 | 6765.43 | 04-JUL-09:02 | 3851.89 | 18-JUL-08:61 | 0.00 | 01-JUL-00:03 |
August | 0.521024E+10 | 0.142294E+10 | 292.58 | 0.518157E+10 | 28666367.01 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 16994.00 | 09-AUG-08:61 | 16994.00 | 09-AUG-08:61 | 3260.84 | 22-AUG-08:62 | 3904.73 | 06-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.261168E+10 | 0.694869E+09 | 180.40 | 0.246209E+10 | 0.149588E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 17039.28 | 07-SEP-08:61 | 16917.60 | 04-SEP-09:01 | 6099.49 | 07-SEP-08:03 | 3864.46 | 04-SEP-09:01 | 0.00 | 01-SEP-00:10 |
October | 0.307149E+09 | 80507109.25 | 79.32 | 0.307139E+09 | 10147.55 | 0.00 | 0.59 | 19-OCT-08:62 | 0.00 | 01-OCT-00:05 | 8480.68 | 19-OCT-08:62 | 8480.68 | 19-OCT-08:62 | 67.65 | 25-OCT-08:62 | 1982.19 | 19-OCT-08:62 | 0.00 | 01-OCT-00:05 |
November | 1105.41 | 303.05 | 4.50 | 1105.41 | 0.00 | 0.00 | 0.00 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.18 | 04-NOV-14:00 | 0.18 | 04-NOV-14:00 | 0.00 | 04-NOV-15:50 | 0.05 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.184354E+11 | 0.500096E+10 | 1228.18 | 0.179758E+11 | 0.459643E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.631254E+10 | 0.172829E+10 | 299.14 | 0.616751E+10 | 0.149588E+09 | 0.00 | 1.00 | 0.00 | 17888.96 | 16998.75 | 6765.43 | 3904.73 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 568.73 | 155.92 | 2.17 | 568.73 | 0.00 | 0.00 | 0.00 | 27-FEB-15:10 | 0.00 | 01-FEB-00:05 | 0.14 | 27-FEB-15:10 | 0.14 | 27-FEB-15:10 | 0.00 | 27-FEB-14:30 | 0.04 | 27-FEB-15:10 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 24745943.98 | 6727239.51 | 23.25 | 24745943.98 | 0.00 | 0.00 | 0.19 | 07-APR-14:00 | 0.00 | 01-APR-00:10 | 2387.25 | 07-APR-14:00 | 2387.25 | 07-APR-14:00 | 0.00 | 06-APR-15:40 | 649.19 | 07-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.673173E+09 | 0.181131E+09 | 98.06 | 0.670800E+09 | 2372950.33 | 0.00 | 0.94 | 20-MAY-08:62 | 0.00 | 01-MAY-00:10 | 15025.44 | 20-MAY-08:62 | 14433.84 | 20-MAY-08:62 | 844.41 | 21-MAY-09:02 | 3162.22 | 20-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.319114E+10 | 0.859868E+09 | 243.57 | 0.305978E+10 | 0.131365E+09 | 0.00 | 1.00 | 04-JUN-09:02 | 0.00 | 01-JUN-00:10 | 17204.04 | 22-JUN-08:61 | 16250.87 | 23-JUN-08:61 | 3582.88 | 13-JUN-08:62 | 3611.65 | 23-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.622361E+10 | 0.170541E+10 | 297.83 | 0.608025E+10 | 0.143361E+09 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 17767.00 | 19-JUL-08:61 | 16877.92 | 18-JUL-08:61 | 6733.68 | 04-JUL-09:02 | 3825.11 | 18-JUL-08:61 | 0.00 | 01-JUL-00:03 |
August | 0.513121E+10 | 0.140265E+10 | 290.80 | 0.510316E+10 | 28051504.48 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 16876.35 | 09-AUG-08:61 | 16876.35 | 09-AUG-08:61 | 3257.99 | 22-AUG-08:62 | 3878.50 | 06-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.256562E+10 | 0.683199E+09 | 177.29 | 0.241812E+10 | 0.147506E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 16923.27 | 07-SEP-08:61 | 16802.86 | 04-SEP-09:01 | 6001.32 | 07-SEP-08:61 | 3838.28 | 04-SEP-09:01 | 0.00 | 01-SEP-00:10 |
October | 0.291109E+09 | 76412382.38 | 77.11 | 0.291109E+09 | 0.00 | 0.00 | 0.52 | 19-OCT-08:62 | 0.00 | 01-OCT-00:05 | 7253.24 | 19-OCT-08:62 | 7253.24 | 19-OCT-08:62 | 0.00 | 18-OCT-12:00 | 1730.77 | 19-OCT-08:62 | 0.00 | 01-OCT-00:05 |
November | 1027.87 | 281.79 | 4.17 | 1027.87 | 0.00 | 0.00 | 0.00 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 0.16 | 04-NOV-14:00 | 0.16 | 04-NOV-14:00 | 0.00 | 04-NOV-14:40 | 0.04 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.181006E+11 | 0.491540E+10 | 1214.24 | 0.176480E+11 | 0.452656E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.622361E+10 | 0.170541E+10 | 297.83 | 0.608025E+10 | 0.147506E+09 | 0.00 | 1.00 | 0.00 | 17767.00 | 16877.92 | 6733.68 | 3878.50 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 428.90 | 117.58 | 1.83 | 428.90 | 0.00 | 0.00 | 0.00 | 27-FEB-14:30 | 0.00 | 01-FEB-00:05 | 0.14 | 27-FEB-14:30 | 0.14 | 27-FEB-14:30 | 0.00 | 01-FEB-00:05 | 0.04 | 27-FEB-14:30 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 15497284.67 | 4243477.32 | 16.42 | 15497284.67 | 0.00 | 0.00 | 0.16 | 07-APR-14:00 | 0.00 | 01-APR-00:10 | 1983.05 | 07-APR-14:00 | 1983.05 | 07-APR-14:00 | 0.00 | 07-APR-15:30 | 543.46 | 07-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.601839E+09 | 0.162946E+09 | 86.51 | 0.600153E+09 | 1686603.89 | 0.00 | 0.65 | 20-MAY-08:62 | 0.00 | 01-MAY-00:10 | 9521.33 | 20-MAY-08:62 | 9111.40 | 20-MAY-08:62 | 409.93 | 20-MAY-08:62 | 2188.39 | 20-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.302759E+10 | 0.819116E+09 | 234.11 | 0.290243E+10 | 0.125165E+09 | 0.00 | 1.00 | 21-JUN-08:61 | 0.00 | 01-JUN-00:10 | 17070.83 | 22-JUN-08:61 | 16117.95 | 29-JUN-08:62 | 3208.10 | 21-JUN-08:61 | 3583.80 | 23-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.604655E+10 | 0.166106E+10 | 295.36 | 0.590771E+10 | 0.138843E+09 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 17631.01 | 19-JUL-08:61 | 16736.50 | 18-JUL-08:61 | 6164.11 | 04-JUL-09:02 | 3794.52 | 18-JUL-08:61 | 0.00 | 01-JUL-00:03 |
August | 0.497143E+10 | 0.136261E+10 | 288.66 | 0.494530E+10 | 26129573.51 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 16743.62 | 09-AUG-08:61 | 16743.62 | 09-AUG-08:61 | 3140.20 | 14-AUG-08:62 | 3851.06 | 06-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.246910E+10 | 0.659107E+09 | 170.73 | 0.232664E+10 | 0.142458E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 16793.69 | 07-SEP-08:61 | 16670.55 | 04-SEP-09:01 | 5990.58 | 07-SEP-08:61 | 3808.84 | 04-SEP-09:01 | 0.00 | 01-SEP-00:10 |
October | 0.255304E+09 | 67277675.83 | 69.45 | 0.255304E+09 | 0.00 | 0.00 | 0.45 | 18-OCT-14:30 | 0.00 | 01-OCT-00:05 | 6094.08 | 18-OCT-14:40 | 6094.08 | 18-OCT-14:40 | 0.00 | 18-OCT-12:40 | 1595.69 | 18-OCT-14:40 | 0.00 | 01-OCT-00:05 |
November | 2643.42 | 724.65 | 3.17 | 2643.42 | 0.00 | 0.00 | 0.00 | 04-NOV-16:20 | 0.00 | 01-NOV-00:10 | 3.41 | 04-NOV-16:20 | 3.41 | 04-NOV-16:20 | 0.00 | 04-NOV-14:50 | 0.93 | 04-NOV-16:20 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.173873E+11 | 0.473636E+10 | 1166.23 | 0.169530E+11 | 0.434282E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.604655E+10 | 0.166106E+10 | 295.36 | 0.590771E+10 | 0.142458E+09 | 0.00 | 1.00 | 0.00 | 17631.01 | 16743.62 | 6164.11 | 3851.06 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 4026988.63 | 1121948.61 | 5.33 | 4026988.63 | 0.00 | 0.00 | 0.09 | 07-APR-14:00 | 0.00 | 01-APR-00:10 | 1117.52 | 07-APR-14:00 | 1117.52 | 07-APR-14:00 | 0.00 | 01-APR-00:10 | 311.77 | 07-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.501539E+09 | 0.137406E+09 | 67.25 | 0.500458E+09 | 1081648.17 | 0.00 | 0.48 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 | 6717.33 | 20-MAY-16:00 | 6717.33 | 20-MAY-16:00 | 101.35 | 19-MAY-11:30 | 1925.68 | 20-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.281996E+10 | 0.768732E+09 | 214.29 | 0.270596E+10 | 0.114002E+09 | 0.00 | 1.00 | 21-JUN-08:61 | 0.00 | 01-JUN-00:10 | 17308.59 | 22-JUN-08:61 | 16495.50 | 23-JUN-08:61 | 3078.60 | 24-JUN-08:61 | 3628.54 | 22-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.594862E+10 | 0.164002E+10 | 290.14 | 0.581996E+10 | 0.128662E+09 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 17911.19 | 19-JUL-08:61 | 16974.33 | 17-JUL-08:61 | 4604.81 | 19-JUL-08:02 | 3837.12 | 18-JUL-08:61 | 0.00 | 01-JUL-00:03 |
August | 0.486277E+10 | 0.133796E+10 | 280.14 | 0.484083E+10 | 21934454.70 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 16982.57 | 09-AUG-08:61 | 16982.57 | 09-AUG-08:61 | 2344.87 | 01-AUG-08:61 | 3906.87 | 06-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.235663E+10 | 0.631992E+09 | 154.07 | 0.222715E+10 | 0.129477E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 17029.27 | 07-SEP-08:61 | 16927.64 | 04-SEP-09:01 | 6147.84 | 07-SEP-08:61 | 3867.37 | 04-SEP-09:01 | 0.00 | 01-SEP-00:10 |
October | 0.206147E+09 | 54701570.62 | 51.58 | 0.206147E+09 | 0.00 | 0.00 | 0.42 | 18-OCT-14:30 | 0.00 | 01-OCT-00:05 | 5744.73 | 18-OCT-14:40 | 5744.73 | 18-OCT-14:40 | 0.00 | 18-OCT-11:40 | 1516.47 | 18-OCT-14:40 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.166997E+11 | 0.457194E+10 | 1062.81 | 0.163045E+11 | 0.395157E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.594862E+10 | 0.164002E+10 | 290.14 | 0.581996E+10 | 0.129477E+09 | 0.00 | 1.00 | 0.00 | 17911.19 | 16982.57 | 6147.84 | 3906.87 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.15 | 118.96 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 147.95 | 88.86 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.81 | 78.24 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.65 | 58.36 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.06 | 46.75 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.03 | 32.80 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.67 | 25.72 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.15 | 29.35 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.47 | 42.45 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.48 | 61.28 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 130.11 | 76.59 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.11 | 102.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.98 | 63.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.06 | 25.72 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 147.95 | 118.96 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.15 | 118.96 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 147.95 | 88.86 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.81 | 78.24 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.65 | 58.36 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.06 | 46.75 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.03 | 32.80 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.67 | 25.72 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.15 | 29.35 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.47 | 42.45 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.48 | 61.28 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 130.11 | 76.59 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.11 | 102.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.98 | 63.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.06 | 25.72 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 147.95 | 118.96 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.15 | 118.96 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 147.95 | 88.86 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.81 | 78.24 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.65 | 58.36 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.06 | 46.75 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.03 | 32.80 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.67 | 25.72 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.15 | 29.35 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.47 | 42.45 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.48 | 61.28 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 130.11 | 76.59 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.11 | 102.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.98 | 63.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.06 | 25.72 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 147.95 | 118.96 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.15 | 118.96 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 147.95 | 88.86 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.81 | 78.24 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.65 | 58.36 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.06 | 46.75 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.03 | 32.80 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.67 | 25.72 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.15 | 29.35 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.47 | 42.45 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.48 | 61.28 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 130.11 | 76.59 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.11 | 102.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.98 | 63.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.06 | 25.72 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 147.95 | 118.96 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.04 | 101.44 | 40.61 | 131.64 | 141.92 | 0.00 | 0.00 | 744.00 |
February | 180.96 | 130.15 | 50.80 | 178.32 | 106.09 | 0.00 | 0.00 | 672.00 |
March | 161.82 | 90.90 | 70.92 | 149.24 | 93.42 | 0.00 | 0.00 | 744.00 |
April | 130.03 | 62.20 | 67.83 | 109.24 | 69.75 | 0.00 | 0.00 | 720.00 |
May | 115.50 | 38.35 | 77.15 | 88.05 | 55.87 | 0.00 | 0.00 | 744.00 |
June | 114.76 | 33.45 | 81.30 | 95.13 | 39.24 | 0.00 | 0.00 | 720.00 |
July | 123.72 | 45.68 | 78.03 | 116.24 | 30.83 | 0.00 | 0.00 | 744.00 |
August | 147.05 | 74.14 | 72.92 | 148.14 | 35.17 | 0.00 | 0.00 | 744.00 |
September | 163.17 | 100.00 | 63.17 | 171.47 | 50.80 | 0.00 | 0.00 | 720.00 |
October | 170.57 | 117.96 | 52.61 | 177.60 | 73.29 | 0.00 | 0.00 | 744.00 |
November | 155.43 | 112.58 | 42.85 | 156.76 | 91.50 | 0.00 | 0.00 | 720.00 |
December | 135.07 | 97.52 | 37.55 | 129.15 | 121.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 144.76 | 83.39 | 61.37 | 137.29 | 75.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.76 | 33.45 | 37.55 | 88.05 | 30.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 180.96 | 130.15 | 81.30 | 178.32 | 141.92 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.04 | 101.44 | 40.61 | 131.64 | 141.92 | 0.00 | 0.00 | 744.00 |
February | 180.96 | 130.15 | 50.80 | 178.32 | 106.09 | 0.00 | 0.00 | 672.00 |
March | 161.82 | 90.90 | 70.92 | 149.24 | 93.42 | 0.00 | 0.00 | 744.00 |
April | 130.03 | 62.20 | 67.83 | 109.24 | 69.75 | 0.00 | 0.00 | 720.00 |
May | 115.50 | 38.35 | 77.15 | 88.05 | 55.87 | 0.00 | 0.00 | 744.00 |
June | 114.76 | 33.45 | 81.30 | 95.13 | 39.24 | 0.00 | 0.00 | 720.00 |
July | 123.72 | 45.68 | 78.03 | 116.24 | 30.83 | 0.00 | 0.00 | 744.00 |
August | 147.05 | 74.14 | 72.92 | 148.14 | 35.17 | 0.00 | 0.00 | 744.00 |
September | 163.17 | 100.00 | 63.17 | 171.47 | 50.80 | 0.00 | 0.00 | 720.00 |
October | 170.57 | 117.96 | 52.61 | 177.60 | 73.29 | 0.00 | 0.00 | 744.00 |
November | 155.43 | 112.58 | 42.85 | 156.76 | 91.50 | 0.00 | 0.00 | 720.00 |
December | 135.07 | 97.52 | 37.55 | 129.15 | 121.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 144.76 | 83.39 | 61.37 | 137.29 | 75.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.76 | 33.45 | 37.55 | 88.05 | 30.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 180.96 | 130.15 | 81.30 | 178.32 | 141.92 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 108.06 | 123.31 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 146.40 | 93.10 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 122.28 | 82.96 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.11 | 62.49 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 71.89 | 49.35 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.46 | 33.65 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.49 | 26.01 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.89 | 29.74 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.86 | 43.63 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 146.46 | 63.56 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 128.68 | 80.21 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 105.95 | 106.26 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 112.98 | 66.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 71.89 | 26.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 146.46 | 123.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 108.06 | 123.31 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 146.40 | 93.10 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 122.28 | 82.96 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.11 | 62.49 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 71.89 | 49.35 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.46 | 33.65 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.49 | 26.01 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.89 | 29.74 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.86 | 43.63 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 146.46 | 63.56 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 128.68 | 80.21 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 105.95 | 106.26 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 112.98 | 66.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 71.89 | 26.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 146.46 | 123.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.04 | 101.44 | 40.61 | 130.32 | 147.10 | 0.00 | 0.00 | 744.00 |
February | 180.96 | 130.15 | 50.80 | 176.47 | 111.11 | 0.00 | 0.00 | 672.00 |
March | 161.82 | 90.90 | 70.92 | 147.41 | 99.02 | 0.00 | 0.00 | 744.00 |
April | 130.03 | 62.20 | 67.83 | 107.39 | 74.64 | 0.00 | 0.00 | 720.00 |
May | 115.50 | 38.35 | 77.15 | 86.64 | 58.95 | 0.00 | 0.00 | 744.00 |
June | 114.76 | 33.45 | 81.30 | 94.44 | 40.25 | 0.00 | 0.00 | 720.00 |
July | 123.72 | 45.68 | 78.03 | 116.02 | 31.17 | 0.00 | 0.00 | 744.00 |
August | 147.05 | 74.14 | 72.92 | 147.83 | 35.63 | 0.00 | 0.00 | 744.00 |
September | 163.17 | 100.00 | 63.17 | 170.75 | 52.19 | 0.00 | 0.00 | 720.00 |
October | 170.57 | 117.96 | 52.61 | 176.38 | 75.99 | 0.00 | 0.00 | 744.00 |
November | 155.43 | 112.58 | 42.85 | 155.05 | 95.79 | 0.00 | 0.00 | 720.00 |
December | 135.07 | 97.52 | 37.55 | 127.76 | 126.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 144.76 | 83.39 | 61.37 | 136.09 | 78.94 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.76 | 33.45 | 37.55 | 86.64 | 31.17 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 180.96 | 130.15 | 81.30 | 176.47 | 147.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 108.26 | 120.71 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 146.80 | 90.89 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 122.63 | 80.78 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.49 | 60.96 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 72.05 | 48.83 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.22 | 34.83 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.95 | 27.87 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.56 | 31.53 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.71 | 44.65 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 146.74 | 63.07 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 129.18 | 78.39 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 106.26 | 103.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.09 | 65.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 72.05 | 27.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 146.80 | 120.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 108.26 | 120.71 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 146.80 | 90.89 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 122.63 | 80.78 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.49 | 60.96 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 72.05 | 48.83 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.22 | 34.83 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.95 | 27.87 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.56 | 31.53 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.71 | 44.65 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 146.74 | 63.07 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 129.18 | 78.39 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 106.26 | 103.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.09 | 65.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 72.05 | 27.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 146.80 | 120.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 129.86 | 143.20 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 175.98 | 107.89 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 147.02 | 95.90 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 107.26 | 72.42 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 86.37 | 58.00 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 93.64 | 41.40 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 114.76 | 33.18 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.62 | 37.52 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 169.63 | 53.09 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 175.76 | 74.97 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 154.80 | 93.10 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 127.44 | 123.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 135.48 | 77.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 86.37 | 33.18 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 175.98 | 143.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 108.41 | 119.63 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 147.06 | 89.88 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 122.87 | 79.77 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.80 | 60.01 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 72.27 | 48.19 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.25 | 34.74 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.92 | 27.96 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.54 | 31.59 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.77 | 44.47 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 146.93 | 62.44 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 129.48 | 77.35 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 106.45 | 102.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.24 | 64.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 72.27 | 27.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 147.06 | 119.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 108.41 | 119.63 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 147.06 | 89.88 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 122.87 | 79.77 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 89.80 | 60.01 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 72.27 | 48.19 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.25 | 34.74 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.92 | 27.96 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.54 | 31.59 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.77 | 44.47 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 146.93 | 62.44 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 129.48 | 77.35 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 106.45 | 102.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.24 | 64.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 72.27 | 27.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 147.06 | 119.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 130.05 | 141.92 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 176.30 | 106.68 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 147.31 | 94.69 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 107.63 | 71.29 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 86.63 | 57.24 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 93.68 | 41.30 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 114.73 | 33.28 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.60 | 37.59 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 169.70 | 52.88 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 175.98 | 74.22 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 155.17 | 91.87 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 127.66 | 122.07 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 135.67 | 76.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 86.63 | 33.28 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 176.30 | 141.92 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 108.57 | 118.86 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 147.33 | 89.12 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.12 | 79.00 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.15 | 59.17 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 72.58 | 47.54 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.40 | 34.43 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.02 | 27.71 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.63 | 31.31 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.91 | 44.08 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.17 | 61.82 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 129.83 | 76.47 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 106.63 | 102.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.46 | 64.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 72.58 | 27.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 147.33 | 118.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 108.57 | 118.86 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 147.33 | 89.12 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.12 | 79.00 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.15 | 59.17 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 72.58 | 47.54 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.40 | 34.43 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.02 | 27.71 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.63 | 31.31 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 141.91 | 44.08 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.17 | 61.82 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 129.83 | 76.47 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 106.63 | 102.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.46 | 64.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 72.58 | 27.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 147.33 | 118.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 130.24 | 141.01 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 176.62 | 105.78 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 147.62 | 93.79 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 108.05 | 70.29 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 87.00 | 56.47 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 93.86 | 40.93 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 114.84 | 33.00 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.72 | 37.27 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 169.88 | 52.42 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 176.27 | 73.49 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 155.59 | 90.82 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 127.89 | 121.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 135.93 | 76.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 87.00 | 33.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 176.62 | 141.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.41 | 116.39 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.37 | 87.04 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.97 | 77.11 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.92 | 57.44 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.21 | 46.10 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.60 | 33.49 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.93 | 26.88 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.64 | 30.39 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.19 | 43.11 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.80 | 60.51 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 130.73 | 74.53 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.46 | 100.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.03 | 62.67 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.21 | 26.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.37 | 116.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.41 | 116.39 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.37 | 87.04 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.97 | 77.11 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.92 | 57.44 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.21 | 46.10 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.60 | 33.49 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.93 | 26.88 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.64 | 30.39 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.19 | 43.11 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.80 | 60.51 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 130.73 | 74.53 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.46 | 100.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.03 | 62.67 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.21 | 26.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.37 | 116.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.41 | 116.39 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.37 | 87.04 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.97 | 77.11 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.92 | 57.44 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.21 | 46.10 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.60 | 33.49 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.93 | 26.88 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.64 | 30.39 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.19 | 43.11 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.80 | 60.51 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 130.73 | 74.53 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.46 | 100.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.03 | 62.67 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.21 | 26.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.37 | 116.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.41 | 116.39 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.37 | 87.04 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.97 | 77.11 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.92 | 57.44 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.21 | 46.10 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.60 | 33.49 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 95.93 | 26.88 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.64 | 30.39 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.19 | 43.11 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.80 | 60.51 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 130.73 | 74.53 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.46 | 100.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.03 | 62.67 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.21 | 26.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.37 | 116.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 131.23 | 138.10 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 177.85 | 103.33 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 148.62 | 91.55 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 108.97 | 68.24 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 87.77 | 54.77 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 94.11 | 39.83 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 114.75 | 32.02 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.73 | 36.18 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 170.21 | 51.27 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 177.02 | 71.94 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 156.65 | 88.53 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 128.88 | 118.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 136.61 | 74.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 87.77 | 32.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 177.85 | 138.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 131.23 | 138.10 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 177.85 | 103.33 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 148.62 | 91.55 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 108.97 | 68.24 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 87.77 | 54.77 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 94.11 | 39.83 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 114.75 | 32.02 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.73 | 36.18 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 170.21 | 51.27 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 177.02 | 71.94 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 156.65 | 88.53 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 128.88 | 118.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 136.61 | 74.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 87.77 | 32.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 177.85 | 138.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.04 | 117.03 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.02 | 87.37 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.70 | 77.27 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.88 | 57.34 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.23 | 46.01 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.71 | 33.34 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.14 | 26.64 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.74 | 30.15 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.13 | 42.96 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.61 | 60.44 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 130.52 | 74.60 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.13 | 100.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.92 | 62.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.23 | 26.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.02 | 117.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.04 | 117.03 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.02 | 87.37 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.70 | 77.27 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 90.88 | 57.34 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.23 | 46.01 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.71 | 33.34 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.14 | 26.64 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.74 | 30.15 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.13 | 42.96 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.61 | 60.44 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 130.52 | 74.60 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.13 | 100.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 113.92 | 62.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.23 | 26.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.02 | 117.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 130.81 | 138.83 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 177.45 | 103.70 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 148.32 | 91.73 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 108.94 | 68.12 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 87.79 | 54.65 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 94.24 | 39.64 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 115.00 | 31.72 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.86 | 35.89 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 170.15 | 51.09 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 176.81 | 71.85 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 156.42 | 88.60 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 128.50 | 119.25 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 136.49 | 74.49 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 87.79 | 31.72 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 177.45 | 138.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.10 | 116.78 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.15 | 87.05 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.83 | 76.91 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 91.11 | 56.83 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.45 | 45.62 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.86 | 33.13 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.24 | 26.50 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.84 | 29.99 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.25 | 42.71 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.78 | 60.08 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 130.70 | 74.17 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.22 | 100.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.05 | 62.41 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.45 | 26.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.15 | 116.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.10 | 116.78 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.15 | 87.05 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 123.83 | 76.91 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 91.11 | 56.83 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 73.45 | 45.62 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 78.86 | 33.13 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.24 | 26.50 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 122.84 | 29.99 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.25 | 42.71 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 147.78 | 60.08 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 130.70 | 74.17 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.22 | 100.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.05 | 62.41 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 73.45 | 26.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.15 | 116.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 130.88 | 138.52 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 177.61 | 103.32 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 148.47 | 91.29 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 109.21 | 67.51 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 88.06 | 54.19 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 94.42 | 39.39 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 115.12 | 31.55 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 146.98 | 35.70 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 170.29 | 50.80 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 177.01 | 71.42 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 156.64 | 88.09 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 128.60 | 118.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 136.65 | 74.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 88.06 | 31.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 177.61 | 138.52 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.31 | 115.72 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.55 | 85.85 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 124.19 | 75.65 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 91.69 | 55.35 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 74.02 | 44.48 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.24 | 32.52 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.45 | 26.14 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.03 | 29.59 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.51 | 42.07 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 148.20 | 59.10 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 131.14 | 73.02 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.49 | 99.05 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.41 | 61.46 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 74.02 | 26.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.55 | 115.72 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 109.31 | 115.72 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 148.55 | 85.85 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 124.19 | 75.65 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 91.69 | 55.35 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 74.02 | 44.48 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 79.24 | 32.52 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.45 | 26.14 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.03 | 29.59 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 142.51 | 42.07 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 148.20 | 59.10 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 131.14 | 73.02 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 107.49 | 99.05 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 114.41 | 61.46 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 74.02 | 26.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 148.55 | 115.72 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 131.13 | 137.26 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 178.09 | 101.89 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 148.91 | 89.80 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 109.90 | 65.75 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 88.74 | 52.84 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 94.88 | 38.66 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 115.37 | 31.13 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 147.21 | 35.23 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 170.61 | 50.03 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 177.51 | 70.25 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 157.17 | 86.72 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 128.93 | 117.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 137.08 | 73.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 88.74 | 31.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 178.09 | 137.26 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 110.10 | 111.31 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 149.80 | 81.19 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 125.33 | 70.90 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 93.20 | 50.52 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 75.55 | 40.69 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 80.37 | 30.14 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.93 | 24.76 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.49 | 28.08 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 143.17 | 39.87 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 149.24 | 55.98 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 132.31 | 69.25 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 108.41 | 94.60 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 115.42 | 58.03 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 75.55 | 24.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 149.80 | 111.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.98 | 84.25 | 33.73 | 110.10 | 111.31 | 0.00 | 0.00 | 744.00 |
February | 150.30 | 108.10 | 42.20 | 149.80 | 81.19 | 0.00 | 0.00 | 672.00 |
March | 134.40 | 75.50 | 58.90 | 125.33 | 70.90 | 0.00 | 0.00 | 744.00 |
April | 108.00 | 51.66 | 56.34 | 93.20 | 50.52 | 0.00 | 0.00 | 720.00 |
May | 95.93 | 31.85 | 64.08 | 75.55 | 40.69 | 0.00 | 0.00 | 744.00 |
June | 95.32 | 27.79 | 67.53 | 80.37 | 30.14 | 0.00 | 0.00 | 720.00 |
July | 102.76 | 37.95 | 64.81 | 96.93 | 24.76 | 0.00 | 0.00 | 744.00 |
August | 122.14 | 61.58 | 60.56 | 123.49 | 28.08 | 0.00 | 0.00 | 744.00 |
September | 135.53 | 83.06 | 52.47 | 143.17 | 39.87 | 0.00 | 0.00 | 720.00 |
October | 141.68 | 97.98 | 43.70 | 149.24 | 55.98 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 93.51 | 35.59 | 132.31 | 69.25 | 0.00 | 0.00 | 720.00 |
December | 112.19 | 81.00 | 31.19 | 108.41 | 94.60 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 120.24 | 69.26 | 50.97 | 115.42 | 58.03 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.32 | 27.79 | 31.19 | 75.55 | 24.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.30 | 108.10 | 67.53 | 149.80 | 111.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.27 | 100.88 | 40.39 | 132.10 | 132.00 | 0.00 | 0.00 | 744.00 |
February | 179.97 | 129.44 | 50.53 | 179.61 | 96.35 | 0.00 | 0.00 | 672.00 |
March | 160.93 | 90.40 | 70.53 | 150.30 | 84.15 | 0.00 | 0.00 | 744.00 |
April | 129.32 | 61.86 | 67.46 | 111.73 | 60.01 | 0.00 | 0.00 | 720.00 |
May | 114.87 | 38.14 | 76.73 | 90.59 | 48.34 | 0.00 | 0.00 | 744.00 |
June | 114.13 | 33.27 | 80.86 | 96.24 | 35.85 | 0.00 | 0.00 | 720.00 |
July | 123.04 | 45.43 | 77.61 | 115.95 | 29.50 | 0.00 | 0.00 | 744.00 |
August | 146.25 | 73.73 | 72.52 | 147.76 | 33.43 | 0.00 | 0.00 | 744.00 |
September | 162.28 | 99.46 | 62.82 | 171.40 | 47.43 | 0.00 | 0.00 | 720.00 |
October | 169.64 | 117.32 | 52.32 | 178.76 | 66.56 | 0.00 | 0.00 | 744.00 |
November | 154.58 | 111.96 | 42.62 | 158.58 | 82.25 | 0.00 | 0.00 | 720.00 |
December | 134.33 | 96.99 | 37.35 | 130.05 | 112.27 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 143.97 | 82.93 | 61.04 | 138.30 | 68.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.13 | 33.27 | 37.35 | 90.59 | 29.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 179.97 | 129.44 | 80.86 | 179.61 | 132.00 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292350E+09 | 0.318615E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.357919E+09 | 0.214981E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.331606E+09 | 0.209552E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.234958E+09 | 0.151281E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.195671E+09 | 0.125223E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.204843E+09 | 85012277.96 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258912E+09 | 68897930.95 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329847E+09 | 78618814.20 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369279E+09 | 0.110037E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.395005E+09 | 0.164141E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.337238E+09 | 0.198515E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.286883E+09 | 0.273564E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.359451E+10 | 0.199844E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.195671E+09 | 68897930.95 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.395005E+09 | 0.318615E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292350E+09 | 0.318615E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.357919E+09 | 0.214981E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.331606E+09 | 0.209552E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.234958E+09 | 0.151281E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.195671E+09 | 0.125223E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.204843E+09 | 85012277.96 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258912E+09 | 68897930.95 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329847E+09 | 78618814.20 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369279E+09 | 0.110037E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.395005E+09 | 0.164141E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.337238E+09 | 0.198515E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.286883E+09 | 0.273564E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.359451E+10 | 0.199844E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.195671E+09 | 68897930.95 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.395005E+09 | 0.318615E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292350E+09 | 0.318615E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.357919E+09 | 0.214981E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.331606E+09 | 0.209552E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.234958E+09 | 0.151281E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.195671E+09 | 0.125223E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.204843E+09 | 85012277.96 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258912E+09 | 68897930.95 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329847E+09 | 78618814.20 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369279E+09 | 0.110037E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.395005E+09 | 0.164141E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.337238E+09 | 0.198515E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.286883E+09 | 0.273564E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.359451E+10 | 0.199844E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.195671E+09 | 68897930.95 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.395005E+09 | 0.318615E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292350E+09 | 0.318615E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.357919E+09 | 0.214981E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.331606E+09 | 0.209552E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.234958E+09 | 0.151281E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.195671E+09 | 0.125223E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.204843E+09 | 85012277.96 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258912E+09 | 68897930.95 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329847E+09 | 78618814.20 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369279E+09 | 0.110037E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.395005E+09 | 0.164141E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.337238E+09 | 0.198515E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.286883E+09 | 0.273564E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.359451E+10 | 0.199844E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.195671E+09 | 68897930.95 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.395005E+09 | 0.318615E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380453E+09 | 0.271690E+09 | 0.108762E+09 | 0.352577E+09 | 0.380128E+09 |
February | 0.437770E+09 | 0.314863E+09 | 0.122907E+09 | 0.431391E+09 | 0.256647E+09 |
March | 0.433407E+09 | 0.243461E+09 | 0.189946E+09 | 0.399718E+09 | 0.250217E+09 |
April | 0.337031E+09 | 0.161216E+09 | 0.175815E+09 | 0.283145E+09 | 0.180785E+09 |
May | 0.309355E+09 | 0.102713E+09 | 0.206642E+09 | 0.235823E+09 | 0.149652E+09 |
June | 0.297452E+09 | 86712993.89 | 0.210739E+09 | 0.246572E+09 | 0.101707E+09 |
July | 0.331364E+09 | 0.122361E+09 | 0.209003E+09 | 0.311348E+09 | 82584142.00 |
August | 0.393866E+09 | 0.198570E+09 | 0.195296E+09 | 0.396777E+09 | 94191550.03 |
September | 0.422938E+09 | 0.259211E+09 | 0.163727E+09 | 0.444448E+09 | 0.131679E+09 |
October | 0.456854E+09 | 0.315950E+09 | 0.140904E+09 | 0.475672E+09 | 0.196304E+09 |
November | 0.402876E+09 | 0.291803E+09 | 0.111073E+09 | 0.406320E+09 | 0.237172E+09 |
December | 0.361772E+09 | 0.261197E+09 | 0.100575E+09 | 0.345911E+09 | 0.326606E+09 |
Annual Sum or Average | 0.456514E+10 | 0.262975E+10 | 0.193539E+10 | 0.432970E+10 | 0.238767E+10 |
Minimum of Months | 0.297452E+09 | 86712993.89 | 0.100575E+09 | 0.235823E+09 | 82584142.00 |
Maximum of Months | 0.456854E+09 | 0.315950E+09 | 0.210739E+09 | 0.475672E+09 | 0.380128E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380453E+09 | 0.271690E+09 | 0.108762E+09 | 0.352577E+09 | 0.380128E+09 |
February | 0.437770E+09 | 0.314863E+09 | 0.122907E+09 | 0.431391E+09 | 0.256647E+09 |
March | 0.433407E+09 | 0.243461E+09 | 0.189946E+09 | 0.399718E+09 | 0.250217E+09 |
April | 0.337031E+09 | 0.161216E+09 | 0.175815E+09 | 0.283145E+09 | 0.180785E+09 |
May | 0.309355E+09 | 0.102713E+09 | 0.206642E+09 | 0.235823E+09 | 0.149652E+09 |
June | 0.297452E+09 | 86712993.89 | 0.210739E+09 | 0.246572E+09 | 0.101707E+09 |
July | 0.331364E+09 | 0.122361E+09 | 0.209003E+09 | 0.311348E+09 | 82584142.00 |
August | 0.393866E+09 | 0.198570E+09 | 0.195296E+09 | 0.396777E+09 | 94191550.03 |
September | 0.422938E+09 | 0.259211E+09 | 0.163727E+09 | 0.444448E+09 | 0.131679E+09 |
October | 0.456854E+09 | 0.315950E+09 | 0.140904E+09 | 0.475672E+09 | 0.196304E+09 |
November | 0.402876E+09 | 0.291803E+09 | 0.111073E+09 | 0.406320E+09 | 0.237172E+09 |
December | 0.361772E+09 | 0.261197E+09 | 0.100575E+09 | 0.345911E+09 | 0.326606E+09 |
Annual Sum or Average | 0.456514E+10 | 0.262975E+10 | 0.193539E+10 | 0.432970E+10 | 0.238767E+10 |
Minimum of Months | 0.297452E+09 | 86712993.89 | 0.100575E+09 | 0.235823E+09 | 82584142.00 |
Maximum of Months | 0.456854E+09 | 0.315950E+09 | 0.210739E+09 | 0.475672E+09 | 0.380128E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.289421E+09 | 0.330286E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.354182E+09 | 0.225228E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.327524E+09 | 0.222204E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.230978E+09 | 0.161966E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.192551E+09 | 0.132180E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.203366E+09 | 87231808.02 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258431E+09 | 69653268.98 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329150E+09 | 79665655.74 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367711E+09 | 0.113087E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.392277E+09 | 0.170246E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.333531E+09 | 0.207903E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.283779E+09 | 0.284617E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.356290E+10 | 0.208427E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.192551E+09 | 69653268.98 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.392277E+09 | 0.330286E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.289421E+09 | 0.330286E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.354182E+09 | 0.225228E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.327524E+09 | 0.222204E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.230978E+09 | 0.161966E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.192551E+09 | 0.132180E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.203366E+09 | 87231808.02 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258431E+09 | 69653268.98 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329150E+09 | 79665655.74 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367711E+09 | 0.113087E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.392277E+09 | 0.170246E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.333531E+09 | 0.207903E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.283779E+09 | 0.284617E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.356290E+10 | 0.208427E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.192551E+09 | 69653268.98 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.392277E+09 | 0.330286E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380453E+09 | 0.271690E+09 | 0.108762E+09 | 0.349061E+09 | 0.393989E+09 |
February | 0.437770E+09 | 0.314863E+09 | 0.122907E+09 | 0.426921E+09 | 0.268797E+09 |
March | 0.433407E+09 | 0.243461E+09 | 0.189946E+09 | 0.394821E+09 | 0.265217E+09 |
April | 0.337031E+09 | 0.161216E+09 | 0.175815E+09 | 0.278360E+09 | 0.193460E+09 |
May | 0.309355E+09 | 0.102713E+09 | 0.206642E+09 | 0.232067E+09 | 0.157892E+09 |
June | 0.297452E+09 | 86712993.89 | 0.210739E+09 | 0.244788E+09 | 0.104336E+09 |
July | 0.331364E+09 | 0.122361E+09 | 0.209003E+09 | 0.310761E+09 | 83479964.84 |
August | 0.393866E+09 | 0.198570E+09 | 0.195296E+09 | 0.395939E+09 | 95428764.65 |
September | 0.422938E+09 | 0.259211E+09 | 0.163727E+09 | 0.442579E+09 | 0.135281E+09 |
October | 0.456854E+09 | 0.315950E+09 | 0.140904E+09 | 0.472428E+09 | 0.203520E+09 |
November | 0.402876E+09 | 0.291803E+09 | 0.111073E+09 | 0.401902E+09 | 0.248282E+09 |
December | 0.361772E+09 | 0.261197E+09 | 0.100575E+09 | 0.342196E+09 | 0.339709E+09 |
Annual Sum or Average | 0.456514E+10 | 0.262975E+10 | 0.193539E+10 | 0.429182E+10 | 0.248939E+10 |
Minimum of Months | 0.297452E+09 | 86712993.89 | 0.100575E+09 | 0.232067E+09 | 83479964.84 |
Maximum of Months | 0.456854E+09 | 0.315950E+09 | 0.210739E+09 | 0.472428E+09 | 0.393989E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.289958E+09 | 0.323299E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.355133E+09 | 0.219893E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.328453E+09 | 0.216349E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.231960E+09 | 0.158008E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.192979E+09 | 0.130788E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.202739E+09 | 90275818.08 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257003E+09 | 74644458.34 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328260E+09 | 84446059.07 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367308E+09 | 0.115735E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.393035E+09 | 0.168930E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.334824E+09 | 0.203183E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.284613E+09 | 0.278150E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.356627E+10 | 0.206370E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.192979E+09 | 74644458.34 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.393035E+09 | 0.323299E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.289958E+09 | 0.323299E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.355133E+09 | 0.219893E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.328453E+09 | 0.216349E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.231960E+09 | 0.158008E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.192979E+09 | 0.130788E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.202739E+09 | 90275818.08 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257003E+09 | 74644458.34 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328260E+09 | 84446059.07 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367308E+09 | 0.115735E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.393035E+09 | 0.168930E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.334824E+09 | 0.203183E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.284613E+09 | 0.278150E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.356627E+10 | 0.206370E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.192979E+09 | 74644458.34 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.393035E+09 | 0.323299E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.347813E+09 | 0.383552E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.425736E+09 | 0.261013E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.393784E+09 | 0.256846E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.278018E+09 | 0.187707E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.231322E+09 | 0.155345E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.242709E+09 | 0.107307E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.307381E+09 | 88864667.40 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.392718E+09 | 0.100496E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.439690E+09 | 0.137620E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.470752E+09 | 0.200807E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.401253E+09 | 0.241326E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.341336E+09 | 0.330197E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.427251E+10 | 0.245108E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.231322E+09 | 88864667.40 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.470752E+09 | 0.383552E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.290372E+09 | 0.320411E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.355765E+09 | 0.217436E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.329102E+09 | 0.213646E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.232759E+09 | 0.155544E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.193576E+09 | 0.129082E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.202830E+09 | 90054340.85 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256920E+09 | 74880661.22 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328208E+09 | 84603143.99 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367459E+09 | 0.115263E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.393531E+09 | 0.167241E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.335622E+09 | 0.200501E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.285107E+09 | 0.275435E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.357125E+10 | 0.204410E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.193576E+09 | 74880661.22 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.393531E+09 | 0.320411E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.290372E+09 | 0.320411E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.355765E+09 | 0.217436E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.329102E+09 | 0.213646E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.232759E+09 | 0.155544E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.193576E+09 | 0.129082E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.202830E+09 | 90054340.85 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256920E+09 | 74880661.22 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328208E+09 | 84603143.99 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367459E+09 | 0.115263E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.393531E+09 | 0.167241E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.335622E+09 | 0.200501E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.285107E+09 | 0.275435E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.357125E+10 | 0.204410E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.193576E+09 | 74880661.22 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.393531E+09 | 0.320411E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.348317E+09 | 0.380111E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.426498E+09 | 0.258090E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.394567E+09 | 0.253629E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.278977E+09 | 0.184778E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.232040E+09 | 0.153316E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.242819E+09 | 0.107044E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.307281E+09 | 89145302.73 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.392655E+09 | 0.100683E+09 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.439870E+09 | 0.137060E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.471347E+09 | 0.198799E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.402211E+09 | 0.238135E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.341935E+09 | 0.326963E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.427852E+10 | 0.242775E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.232040E+09 | 89145302.73 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.471347E+09 | 0.380111E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.290802E+09 | 0.318365E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.356411E+09 | 0.215591E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.329770E+09 | 0.211598E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.233671E+09 | 0.153356E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.194399E+09 | 0.127342E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.203225E+09 | 89243709.34 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257186E+09 | 74230645.59 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328464E+09 | 83867497.19 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367843E+09 | 0.114259E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.394174E+09 | 0.165588E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.336527E+09 | 0.198212E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.285596E+09 | 0.273525E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.357807E+10 | 0.202518E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.194399E+09 | 74230645.59 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.394174E+09 | 0.318365E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.290802E+09 | 0.318365E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.356411E+09 | 0.215591E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.329770E+09 | 0.211598E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.233671E+09 | 0.153356E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.194399E+09 | 0.127342E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.203225E+09 | 89243709.34 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257186E+09 | 74230645.59 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328464E+09 | 83867497.19 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.367843E+09 | 0.114259E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.394174E+09 | 0.165588E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.336527E+09 | 0.198212E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.285596E+09 | 0.273525E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.357807E+10 | 0.202518E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.194399E+09 | 74230645.59 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.394174E+09 | 0.318365E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.348842E+09 | 0.377671E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.427275E+09 | 0.255894E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.395373E+09 | 0.251194E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.280072E+09 | 0.182180E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.233029E+09 | 0.151255E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.243295E+09 | 0.106088E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.307601E+09 | 88377811.79 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.392966E+09 | 99814470.53 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.440333E+09 | 0.135873E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.472118E+09 | 0.196839E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.403293E+09 | 0.235417E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.342527E+09 | 0.324689E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.428672E+10 | 0.240529E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.233029E+09 | 88377811.79 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.472118E+09 | 0.377671E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.293033E+09 | 0.311750E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.358931E+09 | 0.210563E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.332029E+09 | 0.206526E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.235664E+09 | 0.148872E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.196088E+09 | 0.123467E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.203730E+09 | 86818883.32 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256950E+09 | 72003421.14 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328477E+09 | 81393614.79 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.368545E+09 | 0.111736E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.395867E+09 | 0.162069E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.338844E+09 | 0.193176E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.287832E+09 | 0.267940E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.359599E+10 | 0.197632E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.196088E+09 | 72003421.14 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.395867E+09 | 0.311750E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.293033E+09 | 0.311750E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.358931E+09 | 0.210563E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.332029E+09 | 0.206526E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.235664E+09 | 0.148872E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.196088E+09 | 0.123467E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.203730E+09 | 86818883.32 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256950E+09 | 72003421.14 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328477E+09 | 81393614.79 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.368545E+09 | 0.111736E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.395867E+09 | 0.162069E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.338844E+09 | 0.193176E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.287832E+09 | 0.267940E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.359599E+10 | 0.197632E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.196088E+09 | 72003421.14 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.395867E+09 | 0.311750E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.293033E+09 | 0.311750E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.358931E+09 | 0.210563E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.332029E+09 | 0.206526E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.235664E+09 | 0.148872E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.196088E+09 | 0.123467E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.203730E+09 | 86818883.32 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256950E+09 | 72003421.14 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328477E+09 | 81393614.79 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.368545E+09 | 0.111736E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.395867E+09 | 0.162069E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.338844E+09 | 0.193176E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.287832E+09 | 0.267940E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.359599E+10 | 0.197632E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.196088E+09 | 72003421.14 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.395867E+09 | 0.311750E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.293033E+09 | 0.311750E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.358931E+09 | 0.210563E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.332029E+09 | 0.206526E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.235664E+09 | 0.148872E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.196088E+09 | 0.123467E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.203730E+09 | 86818883.32 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.256950E+09 | 72003421.14 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328477E+09 | 81393614.79 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.368545E+09 | 0.111736E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.395867E+09 | 0.162069E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.338844E+09 | 0.193176E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.287832E+09 | 0.267940E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.359599E+10 | 0.197632E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.196088E+09 | 72003421.14 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.395867E+09 | 0.311750E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.351490E+09 | 0.369878E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.430262E+09 | 0.249968E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.398064E+09 | 0.245219E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.282459E+09 | 0.176884E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.235070E+09 | 0.146692E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.243926E+09 | 0.103231E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.307358E+09 | 85749880.36 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.393011E+09 | 96897705.13 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.441178E+09 | 0.132899E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.474124E+09 | 0.192690E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.406041E+09 | 0.229478E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.345181E+09 | 0.318104E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.430816E+10 | 0.234769E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.235070E+09 | 85749880.36 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.474124E+09 | 0.369878E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.351490E+09 | 0.369878E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.430262E+09 | 0.249968E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.398064E+09 | 0.245219E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.282459E+09 | 0.176884E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.235070E+09 | 0.146692E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.243926E+09 | 0.103231E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.307358E+09 | 85749880.36 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.393011E+09 | 96897705.13 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.441178E+09 | 0.132899E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.474124E+09 | 0.192690E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.406041E+09 | 0.229478E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.345181E+09 | 0.318104E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.430816E+10 | 0.234769E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.235070E+09 | 85749880.36 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.474124E+09 | 0.369878E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292058E+09 | 0.313463E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.358083E+09 | 0.211365E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.331323E+09 | 0.206970E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.235569E+09 | 0.148635E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.196137E+09 | 0.123225E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.204019E+09 | 86424650.19 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257494E+09 | 71349852.70 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328755E+09 | 80756599.55 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.368394E+09 | 0.111351E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.395363E+09 | 0.161894E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.338314E+09 | 0.193355E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.286941E+09 | 0.269087E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.359245E+10 | 0.197788E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.196137E+09 | 71349852.70 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.395363E+09 | 0.313463E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292058E+09 | 0.313463E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.358083E+09 | 0.211365E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.331323E+09 | 0.206970E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.235569E+09 | 0.148635E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.196137E+09 | 0.123225E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.204019E+09 | 86424650.19 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257494E+09 | 71349852.70 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.328755E+09 | 80756599.55 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.368394E+09 | 0.111351E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.395363E+09 | 0.161894E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.338314E+09 | 0.193355E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.286941E+09 | 0.269087E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.359245E+10 | 0.197788E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.196137E+09 | 71349852.70 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.395363E+09 | 0.313463E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.350370E+09 | 0.371831E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.429295E+09 | 0.250865E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.397266E+09 | 0.245691E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.282368E+09 | 0.176565E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.235145E+09 | 0.146371E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.244280E+09 | 0.102746E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.308011E+09 | 84965704.37 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.393356E+09 | 96129984.49 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.441026E+09 | 0.132417E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.473565E+09 | 0.192446E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.405450E+09 | 0.229640E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.344162E+09 | 0.319401E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.430429E+10 | 0.234907E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.235145E+09 | 84965704.37 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.473565E+09 | 0.371831E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292215E+09 | 0.312777E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.358397E+09 | 0.210588E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.331656E+09 | 0.205986E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.236153E+09 | 0.147310E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.196725E+09 | 0.122184E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.204398E+09 | 85885542.03 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257767E+09 | 70965843.51 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329008E+09 | 80328430.38 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.368700E+09 | 0.110715E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.395811E+09 | 0.160930E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.338784E+09 | 0.192256E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.287172E+09 | 0.268304E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.359679E+10 | 0.196823E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.196725E+09 | 70965843.51 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.395811E+09 | 0.312777E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292215E+09 | 0.312777E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.358397E+09 | 0.210588E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.331656E+09 | 0.205986E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.236153E+09 | 0.147310E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.196725E+09 | 0.122184E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.204398E+09 | 85885542.03 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.257767E+09 | 70965843.51 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329008E+09 | 80328430.38 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.368700E+09 | 0.110715E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.395811E+09 | 0.160930E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.338784E+09 | 0.192256E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.287172E+09 | 0.268304E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.359679E+10 | 0.196823E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.196725E+09 | 70965843.51 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.395811E+09 | 0.312777E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.350560E+09 | 0.371012E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.429673E+09 | 0.249940E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.397670E+09 | 0.244520E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.283072E+09 | 0.174989E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.235853E+09 | 0.145135E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.244737E+09 | 0.102105E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.308340E+09 | 84509179.51 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.393660E+09 | 95619879.32 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.441394E+09 | 0.131661E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.474102E+09 | 0.191300E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.406015E+09 | 0.228333E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.344441E+09 | 0.318468E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.430952E+10 | 0.233759E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.235853E+09 | 84509179.51 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.474102E+09 | 0.371012E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292763E+09 | 0.309940E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.359365E+09 | 0.207683E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.332619E+09 | 0.202632E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.237651E+09 | 0.143474E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.198247E+09 | 0.119135E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.205393E+09 | 84279236.80 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258319E+09 | 70010125.23 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329520E+09 | 79258034.56 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369396E+09 | 0.109051E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.396938E+09 | 0.158290E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.339925E+09 | 0.189267E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.287908E+09 | 0.265289E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.360804E+10 | 0.193831E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.198247E+09 | 70010125.23 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.396938E+09 | 0.309940E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.292763E+09 | 0.309940E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.359365E+09 | 0.207683E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.332619E+09 | 0.202632E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.237651E+09 | 0.143474E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.198247E+09 | 0.119135E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.205393E+09 | 84279236.80 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.258319E+09 | 70010125.23 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.329520E+09 | 79258034.56 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.369396E+09 | 0.109051E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.396938E+09 | 0.158290E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.339925E+09 | 0.189267E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.287908E+09 | 0.265289E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.360804E+10 | 0.193831E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.198247E+09 | 70010125.23 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.396938E+09 | 0.309940E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.351226E+09 | 0.367629E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.430840E+09 | 0.246484E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.398837E+09 | 0.240531E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.284871E+09 | 0.170430E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.237686E+09 | 0.141519E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.245930E+09 | 0.100200E+09 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.309003E+09 | 83378315.32 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.394278E+09 | 94354223.43 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.442232E+09 | 0.129690E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.475452E+09 | 0.188167E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.407387E+09 | 0.224784E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.345332E+09 | 0.314878E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.432307E+10 | 0.230205E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.237686E+09 | 83378315.32 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.475452E+09 | 0.367629E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.294900E+09 | 0.298136E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.362393E+09 | 0.196413E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.335696E+09 | 0.189891E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.241569E+09 | 0.130944E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.202363E+09 | 0.108980E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.208323E+09 | 78132383.82 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.259622E+09 | 66317490.87 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.330762E+09 | 75200344.86 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.371089E+09 | 0.103344E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.399734E+09 | 0.149941E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.342958E+09 | 0.179488E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.290374E+09 | 0.253377E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.363978E+10 | 0.183017E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.202363E+09 | 66317490.87 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.399734E+09 | 0.298136E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316004E+09 | 0.225666E+09 | 90338001.12 | 0.294900E+09 | 0.298136E+09 |
February | 0.363612E+09 | 0.261526E+09 | 0.102086E+09 | 0.362393E+09 | 0.196413E+09 |
March | 0.359988E+09 | 0.202219E+09 | 0.157769E+09 | 0.335696E+09 | 0.189891E+09 |
April | 0.279938E+09 | 0.133906E+09 | 0.146032E+09 | 0.241569E+09 | 0.130944E+09 |
May | 0.256951E+09 | 85313868.24 | 0.171637E+09 | 0.202363E+09 | 0.108980E+09 |
June | 0.247064E+09 | 72023907.49 | 0.175040E+09 | 0.208323E+09 | 78132383.82 |
July | 0.275231E+09 | 0.101633E+09 | 0.173598E+09 | 0.259622E+09 | 66317490.87 |
August | 0.327145E+09 | 0.164932E+09 | 0.162213E+09 | 0.330762E+09 | 75200344.86 |
September | 0.351293E+09 | 0.215301E+09 | 0.135992E+09 | 0.371089E+09 | 0.103344E+09 |
October | 0.379464E+09 | 0.262428E+09 | 0.117035E+09 | 0.399734E+09 | 0.149941E+09 |
November | 0.334629E+09 | 0.242372E+09 | 92257076.27 | 0.342958E+09 | 0.179488E+09 |
December | 0.300488E+09 | 0.216951E+09 | 83537300.00 | 0.290374E+09 | 0.253377E+09 |
Annual Sum or Average | 0.379181E+10 | 0.218427E+10 | 0.160754E+10 | 0.363978E+10 | 0.183017E+10 |
Minimum of Months | 0.247064E+09 | 72023907.49 | 83537300.00 | 0.202363E+09 | 66317490.87 |
Maximum of Months | 0.379464E+09 | 0.262428E+09 | 0.175040E+09 | 0.399734E+09 | 0.298136E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378374E+09 | 0.270206E+09 | 0.108168E+09 | 0.353821E+09 | 0.353541E+09 |
February | 0.435378E+09 | 0.313143E+09 | 0.122235E+09 | 0.434502E+09 | 0.233088E+09 |
March | 0.431038E+09 | 0.242130E+09 | 0.188908E+09 | 0.402577E+09 | 0.225386E+09 |
April | 0.335189E+09 | 0.160335E+09 | 0.174854E+09 | 0.289602E+09 | 0.155556E+09 |
May | 0.307665E+09 | 0.102152E+09 | 0.205513E+09 | 0.242642E+09 | 0.129486E+09 |
June | 0.295827E+09 | 86239152.39 | 0.209588E+09 | 0.249444E+09 | 92919759.44 |
July | 0.329553E+09 | 0.121693E+09 | 0.207861E+09 | 0.310564E+09 | 79006104.80 |
August | 0.391714E+09 | 0.197485E+09 | 0.194229E+09 | 0.395771E+09 | 89552189.77 |
September | 0.420627E+09 | 0.257795E+09 | 0.162832E+09 | 0.444263E+09 | 0.122937E+09 |
October | 0.454358E+09 | 0.314223E+09 | 0.140134E+09 | 0.478803E+09 | 0.178278E+09 |
November | 0.400674E+09 | 0.290209E+09 | 0.110466E+09 | 0.411043E+09 | 0.213190E+09 |
December | 0.359795E+09 | 0.259770E+09 | 0.100025E+09 | 0.348323E+09 | 0.300708E+09 |
Annual Sum or Average | 0.454019E+10 | 0.261538E+10 | 0.192481E+10 | 0.436135E+10 | 0.217365E+10 |
Minimum of Months | 0.295827E+09 | 86239152.39 | 0.100025E+09 | 0.242642E+09 | 79006104.80 |
Maximum of Months | 0.454358E+09 | 0.314223E+09 | 0.209588E+09 | 0.478803E+09 | 0.353541E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 699.88 | 759.68 | 756.02 | 539.89 | 216.13 | 0.00 | 0.00 |
February | 948.44 | 567.63 | 963.12 | 692.72 | 270.40 | 0.00 | 0.00 |
March | 793.70 | 499.79 | 861.25 | 483.79 | 377.45 | 0.00 | 0.00 |
April | 581.06 | 372.95 | 692.06 | 331.04 | 361.02 | 0.00 | 0.00 |
May | 468.31 | 298.76 | 614.74 | 204.11 | 410.63 | 0.00 | 0.00 |
June | 506.37 | 209.67 | 610.79 | 178.06 | 432.73 | 0.00 | 0.00 |
July | 619.15 | 164.56 | 658.47 | 243.15 | 415.32 | 0.00 | 0.00 |
August | 788.88 | 187.75 | 782.67 | 394.59 | 388.08 | 0.00 | 0.00 |
September | 912.81 | 271.41 | 868.46 | 532.26 | 336.20 | 0.00 | 0.00 |
October | 945.10 | 391.72 | 907.84 | 627.84 | 280.00 | 0.00 | 0.00 |
November | 833.95 | 489.35 | 827.26 | 599.19 | 228.08 | 0.00 | 0.00 |
December | 686.74 | 652.43 | 718.90 | 519.04 | 199.86 | 0.00 | 0.00 |
Annual Sum or Average | 730.51 | 404.91 | 770.47 | 443.83 | 326.64 | 0.00 | 0.00 |
Minimum of Months | 468.31 | 164.56 | 610.79 | 178.06 | 199.86 | 0.00 | 0.00 |
Maximum of Months | 948.44 | 759.68 | 963.12 | 692.72 | 432.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 346.44 | 393.73 | 378.01 | 269.95 | 108.06 | 0.00 | 0.00 |
February | 469.28 | 297.31 | 481.56 | 346.36 | 135.20 | 0.00 | 0.00 |
March | 391.98 | 264.94 | 430.62 | 241.90 | 188.73 | 0.00 | 0.00 |
April | 285.62 | 199.61 | 346.03 | 165.52 | 180.51 | 0.00 | 0.00 |
May | 230.42 | 157.65 | 307.37 | 102.05 | 205.32 | 0.00 | 0.00 |
June | 251.36 | 107.56 | 305.39 | 89.03 | 216.37 | 0.00 | 0.00 |
July | 309.00 | 83.18 | 329.24 | 121.58 | 207.66 | 0.00 | 0.00 |
August | 393.61 | 95.12 | 391.34 | 197.29 | 194.04 | 0.00 | 0.00 |
September | 454.48 | 139.45 | 434.23 | 266.13 | 168.10 | 0.00 | 0.00 |
October | 469.30 | 203.11 | 453.92 | 313.92 | 140.00 | 0.00 | 0.00 |
November | 412.41 | 256.21 | 413.63 | 299.59 | 114.04 | 0.00 | 0.00 |
December | 339.66 | 339.36 | 359.45 | 259.52 | 99.93 | 0.00 | 0.00 |
Annual Sum or Average | 362.05 | 211.12 | 385.23 | 221.91 | 163.32 | 0.00 | 0.00 |
Minimum of Months | 230.42 | 83.18 | 305.39 | 89.03 | 99.93 | 0.00 | 0.00 |
Maximum of Months | 469.30 | 393.73 | 481.56 | 346.36 | 216.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 346.37 | 384.61 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 469.58 | 289.68 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 392.28 | 257.45 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 286.24 | 194.34 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 230.47 | 155.66 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 250.07 | 111.06 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 306.67 | 88.92 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 391.74 | 100.58 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 453.05 | 142.40 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 469.24 | 201.12 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 413.16 | 249.88 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 339.96 | 330.98 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 361.65 | 208.60 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 230.47 | 88.92 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 469.58 | 384.61 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 346.87 | 381.17 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 470.42 | 286.44 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 393.06 | 254.23 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 287.23 | 191.31 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 231.18 | 153.63 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 250.18 | 110.78 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 306.57 | 89.20 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 391.68 | 100.77 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 453.24 | 141.82 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 469.84 | 199.10 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 414.14 | 246.58 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 340.56 | 327.75 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 362.16 | 206.62 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 231.18 | 89.20 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 470.42 | 381.17 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 347.39 | 378.73 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 471.27 | 284.01 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 393.86 | 251.79 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 288.35 | 188.62 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 232.16 | 151.56 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 250.67 | 109.79 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 306.89 | 88.43 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 391.99 | 99.89 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 453.71 | 140.58 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 470.60 | 197.14 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 415.26 | 243.77 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 341.14 | 325.47 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 362.85 | 204.71 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 232.16 | 88.43 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 471.27 | 378.73 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 700.09 | 741.77 | 754.47 | 538.78 | 215.68 | 0.00 | 0.00 |
February | 949.18 | 554.81 | 961.15 | 691.30 | 269.85 | 0.00 | 0.00 |
March | 793.10 | 491.54 | 859.48 | 482.80 | 376.68 | 0.00 | 0.00 |
April | 581.63 | 366.22 | 690.64 | 330.36 | 360.28 | 0.00 | 0.00 |
May | 468.37 | 293.93 | 613.48 | 203.69 | 409.79 | 0.00 | 0.00 |
June | 502.61 | 213.63 | 609.53 | 177.69 | 431.84 | 0.00 | 0.00 |
July | 613.24 | 171.56 | 657.12 | 242.65 | 414.47 | 0.00 | 0.00 |
August | 784.02 | 193.91 | 781.07 | 393.78 | 387.29 | 0.00 | 0.00 |
September | 909.16 | 274.98 | 866.68 | 531.17 | 335.51 | 0.00 | 0.00 |
October | 945.23 | 385.92 | 905.98 | 626.55 | 279.42 | 0.00 | 0.00 |
November | 836.21 | 475.18 | 825.57 | 597.96 | 227.61 | 0.00 | 0.00 |
December | 687.61 | 637.68 | 717.42 | 517.97 | 199.45 | 0.00 | 0.00 |
Annual Sum or Average | 729.33 | 399.56 | 768.89 | 442.92 | 325.97 | 0.00 | 0.00 |
Minimum of Months | 468.37 | 171.56 | 609.53 | 177.69 | 199.45 | 0.00 | 0.00 |
Maximum of Months | 949.18 | 741.77 | 961.15 | 691.30 | 431.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 348.90 | 372.89 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 473.49 | 278.44 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 395.73 | 246.28 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 290.70 | 182.81 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 234.25 | 146.66 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 251.67 | 106.33 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 307.27 | 85.00 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 392.35 | 96.19 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 454.40 | 137.01 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 472.03 | 192.74 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 417.47 | 237.79 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 342.76 | 320.18 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 364.32 | 199.92 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 234.25 | 85.00 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 473.49 | 372.89 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 349.09 | 372.07 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 473.90 | 277.41 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 396.12 | 245.11 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 291.43 | 181.18 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 234.95 | 145.42 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 252.13 | 105.66 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 307.60 | 84.54 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 392.65 | 95.68 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 454.78 | 136.22 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 472.57 | 191.59 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 418.05 | 236.44 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 343.03 | 319.25 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 364.76 | 198.95 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 234.95 | 84.54 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 473.90 | 372.07 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 349.74 | 368.69 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 475.19 | 273.58 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 397.28 | 241.11 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 293.28 | 176.46 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 236.78 | 141.80 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 253.36 | 103.69 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 308.26 | 83.41 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 393.26 | 94.41 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 455.64 | 134.18 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 473.91 | 188.45 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 419.46 | 232.76 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 343.92 | 315.66 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 365.90 | 195.92 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 236.78 | 83.41 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 475.19 | 368.69 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 352.31 | 354.62 | 377.23 | 269.39 | 107.84 | 0.00 | 0.00 |
February | 479.20 | 258.73 | 480.57 | 345.65 | 134.92 | 0.00 | 0.00 |
March | 400.97 | 225.94 | 429.74 | 241.40 | 188.34 | 0.00 | 0.00 |
April | 298.12 | 161.05 | 345.32 | 165.18 | 180.14 | 0.00 | 0.00 |
May | 241.70 | 129.72 | 306.74 | 101.84 | 204.89 | 0.00 | 0.00 |
June | 256.98 | 96.14 | 304.77 | 88.85 | 215.92 | 0.00 | 0.00 |
July | 309.81 | 79.02 | 328.56 | 121.33 | 207.23 | 0.00 | 0.00 |
August | 394.75 | 89.59 | 390.53 | 196.89 | 193.64 | 0.00 | 0.00 |
September | 457.73 | 127.17 | 433.34 | 265.59 | 167.75 | 0.00 | 0.00 |
October | 477.25 | 178.52 | 452.99 | 313.28 | 139.71 | 0.00 | 0.00 |
November | 423.21 | 220.74 | 412.78 | 298.98 | 113.80 | 0.00 | 0.00 |
December | 346.88 | 301.47 | 358.71 | 258.99 | 99.72 | 0.00 | 0.00 |
Annual Sum or Average | 369.13 | 184.99 | 384.44 | 221.46 | 162.98 | 0.00 | 0.00 |
Minimum of Months | 241.70 | 79.02 | 304.77 | 88.85 | 99.72 | 0.00 | 0.00 |
Maximum of Months | 479.20 | 354.62 | 480.57 | 345.65 | 215.92 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.187455E+10 | 0.203472E+10 | 0.202492E+10 | 0.144605E+10 | 0.578876E+09 | 0.00 | 0.00 |
February | 0.229446E+10 | 0.137322E+10 | 0.232999E+10 | 0.167583E+10 | 0.654159E+09 | 0.00 | 0.00 |
March | 0.212586E+10 | 0.133864E+10 | 0.230677E+10 | 0.129580E+10 | 0.101097E+10 | 0.00 | 0.00 |
April | 0.150612E+10 | 0.966691E+09 | 0.179381E+10 | 0.858059E+09 | 0.935756E+09 | 0.00 | 0.00 |
May | 0.125433E+10 | 0.800194E+09 | 0.164651E+10 | 0.546682E+09 | 0.109983E+10 | 0.00 | 0.00 |
June | 0.131252E+10 | 0.543463E+09 | 0.158316E+10 | 0.461522E+09 | 0.112164E+10 | 0.00 | 0.00 |
July | 0.165834E+10 | 0.440760E+09 | 0.176365E+10 | 0.651256E+09 | 0.111240E+10 | 0.00 | 0.00 |
August | 0.211294E+10 | 0.502858E+09 | 0.209631E+10 | 0.105687E+10 | 0.103944E+10 | 0.00 | 0.00 |
September | 0.236601E+10 | 0.703504E+09 | 0.225105E+10 | 0.137963E+10 | 0.871421E+09 | 0.00 | 0.00 |
October | 0.253136E+10 | 0.104917E+10 | 0.243156E+10 | 0.168161E+10 | 0.749950E+09 | 0.00 | 0.00 |
November | 0.216159E+10 | 0.126840E+10 | 0.214427E+10 | 0.155309E+10 | 0.591174E+09 | 0.00 | 0.00 |
December | 0.183935E+10 | 0.174747E+10 | 0.192550E+10 | 0.139020E+10 | 0.535298E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.230374E+11 | 0.127691E+11 | 0.242975E+11 | 0.139966E+11 | 0.103009E+11 | 0.00 | 0.00 |
Minimum of Months | 0.125433E+10 | 0.440760E+09 | 0.158316E+10 | 0.461522E+09 | 0.535298E+09 | 0.00 | 0.00 |
Maximum of Months | 0.253136E+10 | 0.203472E+10 | 0.243156E+10 | 0.168161E+10 | 0.112164E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.927902E+09 | 0.105456E+10 | 0.101246E+10 | 0.723023E+09 | 0.289438E+09 | 0.00 | 0.00 |
February | 0.113528E+10 | 0.719252E+09 | 0.116499E+10 | 0.837915E+09 | 0.327080E+09 | 0.00 | 0.00 |
March | 0.104987E+10 | 0.709623E+09 | 0.115338E+10 | 0.647898E+09 | 0.505485E+09 | 0.00 | 0.00 |
April | 0.740315E+09 | 0.517393E+09 | 0.896907E+09 | 0.429029E+09 | 0.467878E+09 | 0.00 | 0.00 |
May | 0.617168E+09 | 0.422251E+09 | 0.823257E+09 | 0.273341E+09 | 0.549916E+09 | 0.00 | 0.00 |
June | 0.651519E+09 | 0.278799E+09 | 0.791580E+09 | 0.230761E+09 | 0.560820E+09 | 0.00 | 0.00 |
July | 0.827622E+09 | 0.222786E+09 | 0.881826E+09 | 0.325628E+09 | 0.556198E+09 | 0.00 | 0.00 |
August | 0.105424E+10 | 0.254760E+09 | 0.104816E+10 | 0.528435E+09 | 0.519722E+09 | 0.00 | 0.00 |
September | 0.117800E+10 | 0.361454E+09 | 0.112552E+10 | 0.689814E+09 | 0.435711E+09 | 0.00 | 0.00 |
October | 0.125698E+10 | 0.544011E+09 | 0.121578E+10 | 0.840807E+09 | 0.374975E+09 | 0.00 | 0.00 |
November | 0.106896E+10 | 0.664087E+09 | 0.107213E+10 | 0.776547E+09 | 0.295587E+09 | 0.00 | 0.00 |
December | 0.909754E+09 | 0.908942E+09 | 0.962748E+09 | 0.695099E+09 | 0.267649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114176E+11 | 0.665792E+10 | 0.121488E+11 | 0.699830E+10 | 0.515046E+10 | 0.00 | 0.00 |
Minimum of Months | 0.617168E+09 | 0.222786E+09 | 0.791580E+09 | 0.230761E+09 | 0.267649E+09 | 0.00 | 0.00 |
Maximum of Months | 0.125698E+10 | 0.105456E+10 | 0.121578E+10 | 0.840807E+09 | 0.560820E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.927726E+09 | 0.103015E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.113600E+10 | 0.700799E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.105069E+10 | 0.689544E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.741938E+09 | 0.503721E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.617281E+09 | 0.416920E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.648186E+09 | 0.287858E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.821386E+09 | 0.238154E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.104924E+10 | 0.269389E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.117431E+10 | 0.369090E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.125682E+10 | 0.538668E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.107090E+10 | 0.647692E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.910562E+09 | 0.886498E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114050E+11 | 0.657848E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.617281E+09 | 0.238154E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.125682E+10 | 0.103015E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.929059E+09 | 0.102093E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.113803E+10 | 0.692963E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.105277E+10 | 0.680921E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.744494E+09 | 0.495866E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.619192E+09 | 0.411479E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.648479E+09 | 0.287152E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.821121E+09 | 0.238907E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.104907E+10 | 0.269889E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.117479E+10 | 0.367587E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.125841E+10 | 0.533282E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.107346E+10 | 0.639136E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.912149E+09 | 0.877832E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114210E+11 | 0.651595E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.619192E+09 | 0.238907E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.125841E+10 | 0.102093E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.930445E+09 | 0.101440E+10 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.114010E+10 | 0.687076E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.105491E+10 | 0.674390E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.747414E+09 | 0.488891E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.621825E+09 | 0.405937E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.649745E+09 | 0.284575E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.821973E+09 | 0.236839E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.104989E+10 | 0.267549E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.117602E+10 | 0.364391E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.126047E+10 | 0.528015E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.107635E+10 | 0.631841E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.913718E+09 | 0.871739E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114429E+11 | 0.645564E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.621825E+09 | 0.236839E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.126047E+10 | 0.101440E+10 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.187511E+10 | 0.198676E+10 | 0.202076E+10 | 0.144308E+10 | 0.577688E+09 | 0.00 | 0.00 |
February | 0.229625E+10 | 0.134219E+10 | 0.232520E+10 | 0.167239E+10 | 0.652816E+09 | 0.00 | 0.00 |
March | 0.212424E+10 | 0.131654E+10 | 0.230203E+10 | 0.129314E+10 | 0.100889E+10 | 0.00 | 0.00 |
April | 0.150758E+10 | 0.949255E+09 | 0.179013E+10 | 0.856297E+09 | 0.933834E+09 | 0.00 | 0.00 |
May | 0.125449E+10 | 0.787252E+09 | 0.164313E+10 | 0.545560E+09 | 0.109757E+10 | 0.00 | 0.00 |
June | 0.130277E+10 | 0.553737E+09 | 0.157991E+10 | 0.460574E+09 | 0.111934E+10 | 0.00 | 0.00 |
July | 0.164251E+10 | 0.459513E+09 | 0.176003E+10 | 0.649918E+09 | 0.111011E+10 | 0.00 | 0.00 |
August | 0.209993E+10 | 0.519370E+09 | 0.209201E+10 | 0.105470E+10 | 0.103731E+10 | 0.00 | 0.00 |
September | 0.235654E+10 | 0.712740E+09 | 0.224643E+10 | 0.137680E+10 | 0.869632E+09 | 0.00 | 0.00 |
October | 0.253172E+10 | 0.103366E+10 | 0.242657E+10 | 0.167816E+10 | 0.748410E+09 | 0.00 | 0.00 |
November | 0.216745E+10 | 0.123166E+10 | 0.213986E+10 | 0.154990E+10 | 0.589960E+09 | 0.00 | 0.00 |
December | 0.184169E+10 | 0.170797E+10 | 0.192154E+10 | 0.138734E+10 | 0.534199E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.230003E+11 | 0.126006E+11 | 0.242476E+11 | 0.139679E+11 | 0.102798E+11 | 0.00 | 0.00 |
Minimum of Months | 0.125449E+10 | 0.459513E+09 | 0.157991E+10 | 0.460574E+09 | 0.534199E+09 | 0.00 | 0.00 |
Maximum of Months | 0.253172E+10 | 0.198676E+10 | 0.242657E+10 | 0.167816E+10 | 0.111934E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.934486E+09 | 0.998755E+09 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.114546E+10 | 0.673595E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.105991E+10 | 0.659629E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.753505E+09 | 0.473834E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.627418E+09 | 0.392820E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.652319E+09 | 0.275595E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.822999E+09 | 0.227665E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105087E+10 | 0.257643E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.117781E+10 | 0.355117E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.126429E+10 | 0.516235E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.108208E+10 | 0.616349E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.918044E+09 | 0.857573E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114892E+11 | 0.630481E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.627418E+09 | 0.227665E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.126429E+10 | 0.998755E+09 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.934990E+09 | 0.996564E+09 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.114647E+10 | 0.671115E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.106098E+10 | 0.656491E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.755378E+09 | 0.469609E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.629300E+09 | 0.389501E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.653533E+09 | 0.273876E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.823874E+09 | 0.226441E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105168E+10 | 0.256277E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.117879E+10 | 0.353091E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.126572E+10 | 0.513159E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.108358E+10 | 0.612845E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.918784E+09 | 0.855076E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115031E+11 | 0.627404E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.629300E+09 | 0.226441E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.126572E+10 | 0.996564E+09 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.936750E+09 | 0.987507E+09 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.114957E+10 | 0.661851E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.106407E+10 | 0.645795E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.760172E+09 | 0.457378E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.634178E+09 | 0.379787E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.656716E+09 | 0.268758E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.825640E+09 | 0.223398E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105332E+10 | 0.252870E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.118102E+10 | 0.347793E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.126933E+10 | 0.504747E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.108724E+10 | 0.603316E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.921146E+09 | 0.845455E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115392E+11 | 0.617866E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.634178E+09 | 0.223398E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.126933E+10 | 0.987507E+09 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.943620E+09 | 0.949813E+09 | 0.101038E+10 | 0.721538E+09 | 0.288844E+09 | 0.00 | 0.00 |
February | 0.115929E+10 | 0.625914E+09 | 0.116260E+10 | 0.836194E+09 | 0.326408E+09 | 0.00 | 0.00 |
March | 0.107397E+10 | 0.605167E+09 | 0.115101E+10 | 0.646568E+09 | 0.504447E+09 | 0.00 | 0.00 |
April | 0.772739E+09 | 0.417443E+09 | 0.895066E+09 | 0.428148E+09 | 0.466917E+09 | 0.00 | 0.00 |
May | 0.647368E+09 | 0.347446E+09 | 0.821566E+09 | 0.272780E+09 | 0.548787E+09 | 0.00 | 0.00 |
June | 0.666090E+09 | 0.249185E+09 | 0.789955E+09 | 0.230287E+09 | 0.559668E+09 | 0.00 | 0.00 |
July | 0.829808E+09 | 0.211641E+09 | 0.880015E+09 | 0.324959E+09 | 0.555056E+09 | 0.00 | 0.00 |
August | 0.105729E+10 | 0.239953E+09 | 0.104600E+10 | 0.527350E+09 | 0.518655E+09 | 0.00 | 0.00 |
September | 0.118644E+10 | 0.329625E+09 | 0.112321E+10 | 0.688398E+09 | 0.434816E+09 | 0.00 | 0.00 |
October | 0.127827E+10 | 0.478160E+09 | 0.121329E+10 | 0.839080E+09 | 0.374205E+09 | 0.00 | 0.00 |
November | 0.109695E+10 | 0.572163E+09 | 0.106993E+10 | 0.774952E+09 | 0.294980E+09 | 0.00 | 0.00 |
December | 0.929071E+09 | 0.807462E+09 | 0.960771E+09 | 0.693672E+09 | 0.267100E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.116409E+11 | 0.583397E+10 | 0.121238E+11 | 0.698393E+10 | 0.513988E+10 | 0.00 | 0.00 |
Minimum of Months | 0.647368E+09 | 0.211641E+09 | 0.789955E+09 | 0.230287E+09 | 0.267100E+09 | 0.00 | 0.00 |
Maximum of Months | 0.127827E+10 | 0.949813E+09 | 0.121329E+10 | 0.839080E+09 | 0.559668E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.8 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -4.9 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.8 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.37 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.04 | 4.91 | 4.56 | 5.04 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.44 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.02 | 4.61 | 4.29 | 7.18 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.07 | 4.37 | 5.43 | 3.41 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.8 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.4 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.40 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.8 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.44 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.15 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.20 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.65 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.64 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.19 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.36 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.25 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.61 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.25 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.37 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.15 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.47 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.15 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.61 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.0 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.6 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.4 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.98 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.5 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.5 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.0 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.17 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.20 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.92 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.00 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.19 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.18 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.19 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.61 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.11 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.58 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.87 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.61 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.17 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.11 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.47 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.15 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.49 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.84 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.60 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.75 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.73 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.09 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.77 | 2.10 | 4.06 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.87 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.80 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.15 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.09 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.388661E+09 | -263102560.7 | 0.00 | 0.00 | 744.00 | 0.00 | -125558750.7 | 59.00 | 0.00 | 0.00 |
February | 0.355278E+09 | -243114445.2 | 0.00 | 0.00 | 672.00 | 0.00 | -112163778.5 | 58.99 | 0.00 | 0.00 |
March | 0.394487E+09 | -270545496.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123941684.3 | 58.99 | 0.00 | 0.00 |
April | 0.365838E+09 | -249339620.1 | 0.00 | 0.00 | 720.00 | 0.00 | -116498641.0 | 58.99 | 0.00 | 0.00 |
May | 0.361410E+09 | -243581763.5 | 0.00 | 0.00 | 744.00 | 0.00 | -117828617.0 | 58.99 | 0.00 | 0.00 |
June | 0.333076E+09 | -223297543.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109778300.5 | 58.99 | 0.00 | 0.00 |
July | 0.327284E+09 | -214917742.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112366335.1 | 58.99 | 0.00 | 0.00 |
August | 0.326612E+09 | -214077315.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112534400.2 | 58.99 | 0.00 | 0.00 |
September | 0.318308E+09 | -207988475.6 | 0.00 | 0.00 | 720.00 | 0.00 | -110319785.7 | 58.99 | 0.00 | 0.00 |
October | 0.339128E+09 | -222692495.0 | 0.00 | 0.00 | 744.00 | 0.00 | -116435250.0 | 58.99 | 0.00 | 0.00 |
November | 0.345756E+09 | -228639463.9 | 0.00 | 0.00 | 720.00 | 0.00 | -117116930.1 | 58.99 | 0.00 | 0.00 |
December | 0.376548E+09 | -251969362.6 | 0.00 | 0.00 | 744.00 | 0.00 | -124578845.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.423239E+10 | -.283327E+10 | 8760.00 | -.139912E+10 | 58.99 | |||||
Minimum of Months | 0.318308E+09 | -270545496.4 | 0.00 | 0.00 | 672.00 | 0.00 | -125558750.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.394487E+09 | -207988475.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109778300.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.386612E+09 | -263103562.5 | 0.00 | 0.00 | 744.00 | 0.00 | -123508332.9 | 58.99 | 0.00 | 0.00 |
February | 0.352963E+09 | -243117468.9 | 0.00 | 0.00 | 672.00 | 0.00 | -109845892.1 | 58.99 | 0.00 | 0.00 |
March | 0.391445E+09 | -270552420.6 | 0.00 | 0.00 | 744.00 | 0.00 | -120892502.4 | 58.99 | 0.00 | 0.00 |
April | 0.362948E+09 | -249348695.6 | 0.00 | 0.00 | 720.00 | 0.00 | -113599341.7 | 58.99 | 0.00 | 0.00 |
May | 0.359521E+09 | -243585345.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115935267.7 | 58.99 | 0.00 | 0.00 |
June | 0.332539E+09 | -223292110.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109246728.7 | 58.99 | 0.00 | 0.00 |
July | 0.327139E+09 | -214926046.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112212536.8 | 58.99 | 0.00 | 0.00 |
August | 0.326382E+09 | -214076213.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112305411.8 | 58.99 | 0.00 | 0.00 |
September | 0.317531E+09 | -207991192.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109539358.9 | 58.99 | 0.00 | 0.00 |
October | 0.337420E+09 | -222698484.5 | 0.00 | 0.00 | 744.00 | 0.00 | -114721839.3 | 58.99 | 0.00 | 0.00 |
November | 0.343283E+09 | -228633065.6 | 0.00 | 0.00 | 720.00 | 0.00 | -114649437.6 | 58.99 | 0.00 | 0.00 |
December | 0.374250E+09 | -251954018.6 | 0.00 | 0.00 | 744.00 | 0.00 | -122296430.4 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421203E+10 | -.283328E+10 | 8760.00 | -.137875E+10 | 58.99 | |||||
Minimum of Months | 0.317531E+09 | -270552420.6 | 0.00 | 0.00 | 672.00 | 0.00 | -123508332.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.391445E+09 | -207991192.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109246728.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.356912E+09 | -231369508.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125542350.1 | 58.99 | 0.00 | 0.00 |
February | 0.325541E+09 | -213957227.9 | 0.00 | 0.00 | 672.00 | 0.00 | -111584117.3 | 58.99 | 0.00 | 0.00 |
March | 0.364534E+09 | -241639617.7 | 0.00 | 0.00 | 744.00 | 0.00 | -122894610.9 | 58.99 | 0.00 | 0.00 |
April | 0.334215E+09 | -219126831.5 | 0.00 | 0.00 | 720.00 | 0.00 | -115088362.7 | 58.99 | 0.00 | 0.00 |
May | 0.332479E+09 | -216028582.7 | 0.00 | 0.00 | 744.00 | 0.00 | -116450221.7 | 59.01 | 0.00 | 0.00 |
June | 0.307167E+09 | -199007314.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108160048.2 | 58.99 | 0.00 | 0.00 |
July | 0.298008E+09 | -187738462.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110269713.7 | 58.99 | 0.00 | 0.00 |
August | 0.301998E+09 | -191356076.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110642225.0 | 58.99 | 0.00 | 0.00 |
September | 0.291318E+09 | -182666811.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108651577.1 | 58.99 | 0.00 | 0.00 |
October | 0.311208E+09 | -195848347.4 | 0.00 | 0.00 | 744.00 | 0.00 | -115359212.6 | 58.99 | 0.00 | 0.00 |
November | 0.318189E+09 | -201865532.3 | 0.00 | 0.00 | 720.00 | 0.00 | -116323119.5 | 58.99 | 0.00 | 0.00 |
December | 0.344246E+09 | -219929907.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124315893.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.388582E+10 | -.250053E+10 | 8760.00 | -.138528E+10 | 58.99 | |||||
Minimum of Months | 0.291318E+09 | -241639617.7 | 0.00 | 0.00 | 672.00 | 0.00 | -125542350.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.364534E+09 | -182666811.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108160048.2 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.357419E+09 | -231344631.0 | 0.00 | 0.00 | 744.00 | 0.00 | -126074000.4 | 59.00 | 0.00 | 0.00 |
February | 0.326050E+09 | -213942538.5 | 0.00 | 0.00 | 672.00 | 0.00 | -112107050.2 | 59.00 | 0.00 | 0.00 |
March | 0.365088E+09 | -241641237.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123447048.6 | 58.99 | 0.00 | 0.00 |
April | 0.334805E+09 | -219123275.1 | 0.00 | 0.00 | 720.00 | 0.00 | -115682105.5 | 58.99 | 0.00 | 0.00 |
May | 0.332872E+09 | -216025589.6 | 0.00 | 0.00 | 744.00 | 0.00 | -116846053.7 | 59.01 | 0.00 | 0.00 |
June | 0.307220E+09 | -199003311.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108217015.2 | 58.99 | 0.00 | 0.00 |
July | 0.297951E+09 | -187740879.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110210051.3 | 58.99 | 0.00 | 0.00 |
August | 0.301963E+09 | -191357007.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110605691.3 | 58.99 | 0.00 | 0.00 |
September | 0.291428E+09 | -182666806.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108761220.4 | 58.99 | 0.00 | 0.00 |
October | 0.311600E+09 | -195838048.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115761835.6 | 59.00 | 0.00 | 0.00 |
November | 0.318776E+09 | -201873793.7 | 0.00 | 0.00 | 720.00 | 0.00 | -116901829.3 | 58.99 | 0.00 | 0.00 |
December | 0.344754E+09 | -219924049.0 | 0.00 | 0.00 | 744.00 | 0.00 | -124830429.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.388993E+10 | -.250048E+10 | 8760.00 | -.138944E+10 | 58.99 | |||||
Minimum of Months | 0.291428E+09 | -241641237.7 | 0.00 | 0.00 | 672.00 | 0.00 | -126074000.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.365088E+09 | -182666806.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108217015.2 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.346309E+09 | -218673565.9 | 0.00 | 0.00 | 744.00 | 0.00 | -127635802.6 | 58.99 | 0.00 | 0.00 |
February | 0.315942E+09 | -202331600.9 | 0.00 | 0.00 | 672.00 | 0.00 | -113610577.4 | 58.99 | 0.00 | 0.00 |
March | 0.353648E+09 | -228642341.5 | 0.00 | 0.00 | 744.00 | 0.00 | -125005887.7 | 58.99 | 0.00 | 0.00 |
April | 0.324784E+09 | -207361414.6 | 0.00 | 0.00 | 720.00 | 0.00 | -117422576.8 | 58.99 | 0.00 | 0.00 |
May | 0.322621E+09 | -204327678.8 | 0.00 | 0.00 | 744.00 | 0.00 | -118293363.4 | 58.99 | 0.00 | 0.00 |
June | 0.297361E+09 | -188307799.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109053383.0 | 58.99 | 0.00 | 0.00 |
July | 0.288490E+09 | -177551159.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110938721.0 | 58.99 | 0.00 | 0.00 |
August | 0.292486E+09 | -181018906.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111467036.8 | 59.01 | 0.00 | 0.00 |
September | 0.282471E+09 | -172847562.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109623074.0 | 59.00 | 0.00 | 0.00 |
October | 0.302162E+09 | -185114322.1 | 0.00 | 0.00 | 744.00 | 0.00 | -117047372.8 | 58.99 | 0.00 | 0.00 |
November | 0.309345E+09 | -190662421.1 | 0.00 | 0.00 | 720.00 | 0.00 | -118682549.8 | 58.99 | 0.00 | 0.00 |
December | 0.334282E+09 | -207988926.1 | 0.00 | 0.00 | 744.00 | 0.00 | -126292622.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.376990E+10 | -.236483E+10 | 8760.00 | -.140507E+10 | 58.99 | |||||
Minimum of Months | 0.282471E+09 | -228642341.5 | 0.00 | 0.00 | 672.00 | 0.00 | -127635802.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.353648E+09 | -172847562.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109053383.0 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.346241E+09 | -218673340.6 | 0.00 | 0.00 | 744.00 | 0.00 | -127567782.3 | 58.99 | 0.00 | 0.00 |
February | 0.315937E+09 | -202329897.2 | 0.00 | 0.00 | 672.00 | 0.00 | -113607093.0 | 58.99 | 0.00 | 0.00 |
March | 0.353688E+09 | -228641359.5 | 0.00 | 0.00 | 744.00 | 0.00 | -125046875.6 | 58.99 | 0.00 | 0.00 |
April | 0.324916E+09 | -207358688.1 | 0.00 | 0.00 | 720.00 | 0.00 | -117557246.6 | 58.99 | 0.00 | 0.00 |
May | 0.322735E+09 | -204329932.1 | 0.00 | 0.00 | 744.00 | 0.00 | -118404743.7 | 58.99 | 0.00 | 0.00 |
June | 0.297466E+09 | -188309112.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109157032.0 | 58.99 | 0.00 | 0.00 |
July | 0.288639E+09 | -177556834.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111082184.8 | 58.99 | 0.00 | 0.00 |
August | 0.292593E+09 | -181097807.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111495204.1 | 58.98 | 0.00 | 0.00 |
September | 0.282579E+09 | -172833689.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109745451.7 | 59.00 | 0.00 | 0.00 |
October | 0.302259E+09 | -185107735.8 | 0.00 | 0.00 | 744.00 | 0.00 | -117151369.3 | 58.99 | 0.00 | 0.00 |
November | 0.309465E+09 | -190657934.3 | 0.00 | 0.00 | 720.00 | 0.00 | -118807089.4 | 58.99 | 0.00 | 0.00 |
December | 0.334245E+09 | -207989452.5 | 0.00 | 0.00 | 744.00 | 0.00 | -126255636.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.377076E+10 | -.236489E+10 | 8760.00 | -.140588E+10 | 58.99 | |||||
Minimum of Months | 0.282579E+09 | -228641359.5 | 0.00 | 0.00 | 672.00 | 0.00 | -127567782.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.353688E+09 | -172833689.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109157032.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.346355E+09 | -218674554.8 | 0.00 | 0.00 | 744.00 | 0.00 | -127680592.4 | 58.99 | 0.00 | 0.00 |
February | 0.316100E+09 | -202332421.2 | 0.00 | 0.00 | 672.00 | 0.00 | -113767883.0 | 58.99 | 0.00 | 0.00 |
March | 0.353876E+09 | -228641677.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125234380.7 | 58.99 | 0.00 | 0.00 |
April | 0.325234E+09 | -207354296.8 | 0.00 | 0.00 | 720.00 | 0.00 | -117879286.8 | 58.99 | 0.00 | 0.00 |
May | 0.323001E+09 | -204328689.6 | 0.00 | 0.00 | 744.00 | 0.00 | -118672225.7 | 58.99 | 0.00 | 0.00 |
June | 0.297600E+09 | -188307272.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109293030.2 | 58.99 | 0.00 | 0.00 |
July | 0.288740E+09 | -177552548.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111186995.1 | 58.99 | 0.00 | 0.00 |
August | 0.292682E+09 | -181123804.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111558300.3 | 58.97 | 0.00 | 0.00 |
September | 0.282728E+09 | -172882575.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109845430.9 | 58.98 | 0.00 | 0.00 |
October | 0.302499E+09 | -185116380.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117383114.0 | 58.99 | 0.00 | 0.00 |
November | 0.309717E+09 | -190656314.2 | 0.00 | 0.00 | 720.00 | 0.00 | -119061116.1 | 58.99 | 0.00 | 0.00 |
December | 0.334381E+09 | -207998006.2 | 0.00 | 0.00 | 744.00 | 0.00 | -126383123.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.377291E+10 | -.236497E+10 | 8760.00 | -.140795E+10 | 58.99 | |||||
Minimum of Months | 0.282728E+09 | -228641677.9 | 0.00 | 0.00 | 672.00 | 0.00 | -127680592.4 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.353876E+09 | -172882575.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109293030.2 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | ||||||||||
Minimum of Months | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.239968E+11 | 62375.17 | 04-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125773E+11 | 62375.17 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.929042E+10 | 62375.17 | 03-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.271668E+10 | 62375.17 | 29-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166135E+10 | 62375.17 | 08-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5161130.27 | 2243.88 | 16-JUN-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 51118953.21 | 4796.51 | 20-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.649667E+09 | 32898.98 | 10-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.582844E+10 | 62375.17 | 26-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163586E+11 | 62375.17 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.731355E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.239968E+11 | 62375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.836627E+10 | 32824.32 | 06-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.411470E+10 | 32824.32 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251225E+10 | 32824.32 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.578764E+09 | 13360.12 | 29-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.369596E+09 | 5760.99 | 09-MAY-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121002E+09 | 5340.23 | 10-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164675E+10 | 32824.32 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.530940E+10 | 32824.32 | 16-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230187E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.836627E+10 | 32824.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.960806E+10 | 32708.15 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.498133E+10 | 32708.15 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.333207E+10 | 32708.15 | 04-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.858773E+09 | 17885.86 | 30-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.574594E+09 | 15134.51 | 08-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2279981.14 | 1077.47 | 19-SEP-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.257146E+09 | 6877.01 | 10-OCT-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.221216E+10 | 32708.15 | 26-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.644207E+10 | 32708.15 | 16-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.282685E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.960806E+10 | 32708.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.989258E+10 | 32567.12 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.517790E+10 | 32567.12 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.355669E+10 | 32567.12 | 04-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.964050E+09 | 23772.32 | 30-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.643470E+09 | 24913.34 | 08-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5497735.82 | 1229.97 | 19-SEP-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.307619E+09 | 9607.40 | 05-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.238082E+10 | 32567.12 | 26-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.670117E+10 | 32567.12 | 15-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296298E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.989258E+10 | 32567.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102795E+11 | 32701.44 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.546011E+10 | 32701.44 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.386592E+10 | 32701.44 | 04-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112529E+10 | 28941.61 | 30-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.735680E+09 | 32701.44 | 08-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14529445.53 | 3450.09 | 19-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.364304E+09 | 11797.01 | 10-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.258851E+10 | 32701.44 | 26-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.704815E+10 | 32701.44 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.314820E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102795E+11 | 32701.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.198336E+11 | 61530.12 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106901E+11 | 61530.12 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.782782E+10 | 61530.12 | 03-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.251281E+10 | 61530.12 | 29-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161134E+10 | 61530.12 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2671430.97 | 1147.68 | 16-JUN-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87971103.25 | 5936.78 | 20-SEP-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.859678E+09 | 61530.12 | 10-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.535559E+10 | 61530.12 | 13-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138314E+11 | 61530.12 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.626129E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.198336E+11 | 61530.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102847E+11 | 31430.36 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.554420E+10 | 31430.36 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.407949E+10 | 31430.36 | 03-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131750E+10 | 31430.36 | 29-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.845685E+09 | 31430.36 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 920043.13 | 458.51 | 16-JUN-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 46470171.69 | 3134.54 | 19-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.443053E+09 | 31430.36 | 10-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.277953E+10 | 31430.36 | 13-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.715836E+10 | 31430.36 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.324999E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102847E+11 | 31430.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103953E+11 | 31266.66 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.564279E+10 | 31266.66 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.421512E+10 | 31266.66 | 03-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141480E+10 | 31266.66 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.901575E+09 | 31266.66 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2463546.56 | 795.08 | 16-JUN-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59578681.11 | 3318.35 | 19-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.477159E+09 | 31266.66 | 10-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.287851E+10 | 31266.66 | 12-NOV-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.727818E+10 | 31266.66 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.332654E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103953E+11 | 31266.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108573E+11 | 30975.46 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.601514E+10 | 30975.46 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.465778E+10 | 30975.46 | 03-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170812E+10 | 30975.46 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108393E+10 | 30975.46 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11809371.18 | 1989.85 | 16-JUN-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101937E+09 | 4283.56 | 20-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.578224E+09 | 30975.46 | 10-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.317659E+10 | 30975.46 | 12-NOV-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.771086E+10 | 30975.46 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.359017E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108573E+11 | 30975.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137126E+11 | 31593.37 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.786056E+10 | 31593.37 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.657296E+10 | 31593.37 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.277207E+10 | 31593.37 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170144E+10 | 31593.37 | 01-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 66579551.67 | 4456.24 | 16-JUN-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.270877E+09 | 19119.90 | 20-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.941784E+09 | 31593.37 | 10-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.426804E+10 | 31593.37 | 11-NOV-10:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.969837E+10 | 31593.37 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.478653E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137126E+11 | 31593.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2582.98 | 2582.98 | 0.32 | 27-FEB-15:30 | 0.32 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 97718874.51 | 97718874.51 | 6219.84 | 07-APR-14:00 | 6219.84 | 0.00 |
May | 0.00 | 0.00 | 0.205346E+10 | 0.204500E+10 | 32542.70 | 20-MAY-08:62 | 31432.39 | 0.00 |
June | 0.00 | 0.00 | 0.814835E+10 | 0.779845E+10 | 34227.21 | 22-JUN-08:61 | 28826.02 | 0.00 |
July | 0.00 | 0.00 | 0.161250E+11 | 0.157077E+11 | 35411.73 | 19-JUL-08:61 | 26222.87 | 0.00 |
August | 0.00 | 0.00 | 0.130341E+11 | 0.129643E+11 | 33526.95 | 09-AUG-08:61 | 33526.95 | 0.00 |
September | 0.00 | 0.00 | 0.703486E+10 | 0.668132E+10 | 33655.18 | 07-SEP-08:61 | 21414.17 | 0.00 |
October | 0.00 | 0.00 | 0.830360E+09 | 0.830232E+09 | 23643.04 | 16-OCT-08:62 | 23643.04 | 0.00 |
November | 0.00 | 0.00 | 10830.88 | 10830.88 | 0.45 | 03-NOV-14:00 | 0.45 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.473239E+11 | 0.461247E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.161250E+11 | 0.157077E+11 | 35411.73 | 33526.95 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 11315094.12 | 11315094.12 | 17312.25 | 26-FEB-18:15 | 17312.25 | 0.00 |
March | 0.00 | 0.00 | 1031269.27 | 1031269.27 | 214.99 | 29-MAR-22:10 | 214.99 | 0.00 |
April | 0.00 | 0.00 | 0.126798E+09 | 0.126798E+09 | 17312.25 | 06-APR-20:02 | 17312.25 | 0.00 |
May | 0.00 | 0.00 | 0.149851E+10 | 0.148717E+10 | 17647.52 | 20-MAY-18:17 | 17647.52 | 0.00 |
June | 0.00 | 0.00 | 0.506172E+10 | 0.484231E+10 | 18465.49 | 21-JUN-20:02 | 14968.01 | 0.00 |
July | 0.00 | 0.00 | 0.926473E+10 | 0.899255E+10 | 19024.31 | 18-JUL-21:56 | 10893.97 | 0.00 |
August | 0.00 | 0.00 | 0.762491E+10 | 0.756465E+10 | 18022.87 | 09-AUG-08:61 | 18022.87 | 0.00 |
September | 0.00 | 0.00 | 0.414087E+10 | 0.392901E+10 | 18761.03 | 06-SEP-20:02 | 13192.22 | 0.00 |
October | 0.00 | 0.00 | 0.578003E+09 | 0.577835E+09 | 17312.25 | 02-OCT-20:02 | 17312.25 | 0.00 |
November | 0.00 | 0.00 | 22837288.57 | 22837288.57 | 17312.25 | 03-NOV-20:02 | 17312.25 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.283307E+11 | 0.275555E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.926473E+10 | 0.899255E+10 | 19024.31 | 18022.87 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1917.11 | 1917.11 | 0.17 | 27-FEB-15:30 | 0.17 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 68804558.63 | 68804558.63 | 3775.19 | 07-APR-14:00 | 3775.19 | 0.00 |
May | 0.00 | 0.00 | 0.914901E+09 | 0.909727E+09 | 17354.62 | 20-MAY-07:02 | 16206.39 | 0.00 |
June | 0.00 | 0.00 | 0.367462E+10 | 0.353323E+10 | 18251.63 | 22-JUN-07:01 | 14108.98 | 0.00 |
July | 0.00 | 0.00 | 0.692802E+10 | 0.676444E+10 | 18875.22 | 19-JUL-07:01 | 13518.18 | 0.00 |
August | 0.00 | 0.00 | 0.574212E+10 | 0.570691E+10 | 17797.90 | 09-AUG-07:01 | 16748.10 | 0.00 |
September | 0.00 | 0.00 | 0.298558E+10 | 0.282978E+10 | 18004.47 | 07-SEP-07:01 | 11706.19 | 0.00 |
October | 0.00 | 0.00 | 0.439017E+09 | 0.438172E+09 | 17270.26 | 25-OCT-07:02 | 15306.16 | 0.00 |
November | 0.00 | 0.00 | 5306.36 | 5304.74 | 3.30 | 05-NOV-08:61 | 3.28 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.207531E+11 | 0.202511E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.692802E+10 | 0.676444E+10 | 18875.22 | 16748.10 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1914.33 | 1914.33 | 0.18 | 27-FEB-11:40 | 0.18 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 60808481.26 | 60808481.26 | 3588.31 | 07-APR-14:00 | 3588.31 | 0.00 |
May | 0.00 | 0.00 | 0.889108E+09 | 0.884213E+09 | 17413.47 | 20-MAY-07:02 | 16256.88 | 0.00 |
June | 0.00 | 0.00 | 0.365885E+10 | 0.351804E+10 | 18315.72 | 22-JUN-07:01 | 14159.71 | 0.00 |
July | 0.00 | 0.00 | 0.695606E+10 | 0.679097E+10 | 18942.66 | 19-JUL-07:01 | 13558.72 | 0.00 |
August | 0.00 | 0.00 | 0.575830E+10 | 0.572289E+10 | 17859.88 | 09-AUG-07:01 | 16805.81 | 0.00 |
September | 0.00 | 0.00 | 0.298289E+10 | 0.282606E+10 | 18068.87 | 07-SEP-07:01 | 11755.13 | 0.00 |
October | 0.00 | 0.00 | 0.415356E+09 | 0.414624E+09 | 17330.17 | 25-OCT-07:02 | 15347.80 | 0.00 |
November | 0.00 | 0.00 | 6501.68 | 6501.68 | 4.54 | 05-NOV-15:00 | 4.54 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.207214E+11 | 0.202176E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.695606E+10 | 0.679097E+10 | 18942.66 | 16805.81 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1430.14 | 1430.14 | 0.15 | 27-FEB-15:30 | 0.15 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 49993031.61 | 49993031.61 | 3296.91 | 07-APR-14:00 | 3296.91 | 0.00 |
May | 0.00 | 0.00 | 0.836061E+09 | 0.831858E+09 | 17321.57 | 20-MAY-07:02 | 16143.36 | 0.00 |
June | 0.00 | 0.00 | 0.354818E+10 | 0.341252E+10 | 18221.65 | 22-JUN-07:01 | 14061.93 | 0.00 |
July | 0.00 | 0.00 | 0.681984E+10 | 0.665918E+10 | 18846.52 | 19-JUL-07:01 | 13505.14 | 0.00 |
August | 0.00 | 0.00 | 0.563390E+10 | 0.560013E+10 | 17772.21 | 09-AUG-07:01 | 16724.85 | 0.00 |
September | 0.00 | 0.00 | 0.290499E+10 | 0.275196E+10 | 17977.16 | 07-SEP-07:01 | 11676.54 | 0.00 |
October | 0.00 | 0.00 | 0.381380E+09 | 0.380887E+09 | 17245.76 | 19-OCT-07:01 | 17245.76 | 0.00 |
November | 0.00 | 0.00 | 2899.15 | 2899.15 | 0.21 | 04-NOV-14:00 | 0.21 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.201743E+11 | 0.196865E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.681984E+10 | 0.665918E+10 | 18846.52 | 17245.76 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1359.68 | 1359.68 | 0.30 | 27-FEB-15:10 | 0.30 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 61963208.21 | 61963208.21 | 5070.76 | 07-APR-14:00 | 5070.76 | 0.00 |
May | 0.00 | 0.00 | 0.138427E+10 | 0.137800E+10 | 31974.06 | 20-MAY-08:62 | 30714.23 | 0.00 |
June | 0.00 | 0.00 | 0.634586E+10 | 0.607835E+10 | 33528.42 | 22-JUN-08:61 | 28550.73 | 0.00 |
July | 0.00 | 0.00 | 0.122340E+11 | 0.119435E+11 | 34620.39 | 19-JUL-08:61 | 26272.08 | 0.00 |
August | 0.00 | 0.00 | 0.101054E+11 | 0.100461E+11 | 32884.85 | 09-AUG-08:61 | 32884.85 | 0.00 |
September | 0.00 | 0.00 | 0.506649E+10 | 0.477078E+10 | 32978.45 | 07-SEP-08:61 | 21289.16 | 0.00 |
October | 0.00 | 0.00 | 0.604087E+09 | 0.604028E+09 | 19414.02 | 19-OCT-08:62 | 19414.02 | 0.00 |
November | 0.00 | 0.00 | 2146.34 | 2146.34 | 0.35 | 04-NOV-14:00 | 0.35 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.358021E+11 | 0.348828E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.122340E+11 | 0.119435E+11 | 34620.39 | 32884.85 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 4100.06 | 4100.06 | 5.73 | 27-FEB-13:20 | 5.73 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 28969249.01 | 28969249.01 | 2551.41 | 07-APR-14:00 | 2551.41 | 0.00 |
May | 0.00 | 0.00 | 0.704000E+09 | 0.701315E+09 | 16518.69 | 20-MAY-08:62 | 15895.68 | 0.00 |
June | 0.00 | 0.00 | 0.326085E+10 | 0.312719E+10 | 17322.54 | 22-JUN-08:61 | 14773.30 | 0.00 |
July | 0.00 | 0.00 | 0.631254E+10 | 0.616751E+10 | 17888.96 | 19-JUL-08:61 | 13593.75 | 0.00 |
August | 0.00 | 0.00 | 0.521024E+10 | 0.518157E+10 | 16994.00 | 09-AUG-08:61 | 16994.00 | 0.00 |
September | 0.00 | 0.00 | 0.261168E+10 | 0.246209E+10 | 17039.28 | 07-SEP-08:61 | 11012.29 | 0.00 |
October | 0.00 | 0.00 | 0.307149E+09 | 0.307139E+09 | 8480.68 | 19-OCT-08:62 | 8480.68 | 0.00 |
November | 0.00 | 0.00 | 1105.41 | 1105.41 | 0.18 | 04-NOV-14:00 | 0.18 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.184354E+11 | 0.179758E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.631254E+10 | 0.616751E+10 | 17888.96 | 16994.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 568.73 | 568.73 | 0.14 | 27-FEB-15:10 | 0.14 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 24745943.98 | 24745943.98 | 2387.25 | 07-APR-14:00 | 2387.25 | 0.00 |
May | 0.00 | 0.00 | 0.673173E+09 | 0.670800E+09 | 15025.44 | 20-MAY-08:62 | 14433.84 | 0.00 |
June | 0.00 | 0.00 | 0.319114E+10 | 0.305978E+10 | 17204.04 | 22-JUN-08:61 | 14650.58 | 0.00 |
July | 0.00 | 0.00 | 0.622361E+10 | 0.608025E+10 | 17767.00 | 19-JUL-08:61 | 13483.28 | 0.00 |
August | 0.00 | 0.00 | 0.513121E+10 | 0.510316E+10 | 16876.35 | 09-AUG-08:61 | 16876.35 | 0.00 |
September | 0.00 | 0.00 | 0.256562E+10 | 0.241812E+10 | 16923.27 | 07-SEP-08:61 | 10921.95 | 0.00 |
October | 0.00 | 0.00 | 0.291109E+09 | 0.291109E+09 | 7253.24 | 19-OCT-08:62 | 7253.24 | 0.00 |
November | 0.00 | 0.00 | 1027.87 | 1027.87 | 0.16 | 04-NOV-14:00 | 0.16 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.181006E+11 | 0.176480E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.622361E+10 | 0.608025E+10 | 17767.00 | 16876.35 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 428.90 | 428.90 | 0.14 | 27-FEB-14:30 | 0.14 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 15497284.67 | 15497284.67 | 1983.05 | 07-APR-14:00 | 1983.05 | 0.00 |
May | 0.00 | 0.00 | 0.601839E+09 | 0.600153E+09 | 9521.33 | 20-MAY-08:62 | 9111.40 | 0.00 |
June | 0.00 | 0.00 | 0.302759E+10 | 0.290243E+10 | 17070.83 | 22-JUN-08:61 | 14492.08 | 0.00 |
July | 0.00 | 0.00 | 0.604655E+10 | 0.590771E+10 | 17631.01 | 19-JUL-08:61 | 13343.58 | 0.00 |
August | 0.00 | 0.00 | 0.497143E+10 | 0.494530E+10 | 16743.62 | 09-AUG-08:61 | 16743.62 | 0.00 |
September | 0.00 | 0.00 | 0.246910E+10 | 0.232664E+10 | 16793.69 | 07-SEP-08:61 | 10803.11 | 0.00 |
October | 0.00 | 0.00 | 0.255304E+09 | 0.255304E+09 | 6094.08 | 18-OCT-14:40 | 6094.08 | 0.00 |
November | 0.00 | 0.00 | 2643.42 | 2643.42 | 3.41 | 04-NOV-16:20 | 3.41 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.173873E+11 | 0.169530E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.604655E+10 | 0.590771E+10 | 17631.01 | 16743.62 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 4026988.63 | 4026988.63 | 1117.52 | 07-APR-14:00 | 1117.52 | 0.00 |
May | 0.00 | 0.00 | 0.501539E+09 | 0.500458E+09 | 6717.33 | 20-MAY-16:00 | 6717.33 | 0.00 |
June | 0.00 | 0.00 | 0.281996E+10 | 0.270596E+10 | 17308.59 | 22-JUN-08:61 | 14661.91 | 0.00 |
July | 0.00 | 0.00 | 0.594862E+10 | 0.581996E+10 | 17911.19 | 19-JUL-08:61 | 13372.09 | 0.00 |
August | 0.00 | 0.00 | 0.486277E+10 | 0.484083E+10 | 16982.57 | 09-AUG-08:61 | 16982.57 | 0.00 |
September | 0.00 | 0.00 | 0.235663E+10 | 0.222715E+10 | 17029.27 | 07-SEP-08:61 | 10881.43 | 0.00 |
October | 0.00 | 0.00 | 0.206147E+09 | 0.206147E+09 | 5744.73 | 18-OCT-14:40 | 5744.73 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.166997E+11 | 0.163045E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.594862E+10 | 0.581996E+10 | 17911.19 | 16982.57 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.400563E+10 | 0.69 | 2203.14 | 01-JAN-11:40 | 1.01 |
February | 0.362000E+10 | 0.69 | 2203.14 | 02-FEB-10:30 | 1.01 |
March | 0.400760E+10 | 0.69 | 2203.14 | 01-MAR-11:30 | 1.00 |
April | 0.387841E+10 | 0.68 | 2203.14 | 03-APR-08:10 | 1.01 |
May | 0.399753E+10 | 0.68 | 2203.14 | 01-MAY-10:30 | 1.01 |
June | 0.387841E+10 | 0.68 | 2203.14 | 02-JUN-10:20 | 1.00 |
July | 0.400531E+10 | 0.68 | 2203.14 | 01-JUL-13:50 | 0.99 |
August | 0.399738E+10 | 0.68 | 2203.14 | 01-AUG-22:02 | 1.00 |
September | 0.388634E+10 | 0.68 | 2203.14 | 01-SEP-11:40 | 1.00 |
October | 0.399738E+10 | 0.68 | 2203.14 | 05-OCT-12:40 | 1.00 |
November | 0.386413E+10 | 0.68 | 2203.14 | 02-NOV-09:30 | 1.01 |
December | 0.401548E+10 | 0.69 | 2203.14 | 01-DEC-12:40 | 1.01 |
Annual Sum or Average | 0.471536E+11 | 0.68 | |||
Minimum of Months | 0.362000E+10 | 0.68 | 2203.14 | 0.99 | |
Maximum of Months | 0.401548E+10 | 0.69 | 2203.14 | 1.01 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.167695E+10 | 0.59 | 1230.39 | 01-JAN-09:08 | 1.04 |
February | 0.152388E+10 | 0.58 | 1230.39 | 01-FEB-11:30 | 1.04 |
March | 0.170219E+10 | 0.58 | 1230.39 | 03-MAR-09:10 | 1.04 |
April | 0.174068E+10 | 0.65 | 1230.39 | 01-APR-08:09 | 1.04 |
May | 0.190090E+10 | 0.66 | 1230.39 | 01-MAY-08:09 | 1.04 |
June | 0.194879E+10 | 0.66 | 1230.39 | 01-JUN-13:40 | 1.03 |
July | 0.195132E+10 | 0.65 | 1230.39 | 01-JUL-08:30 | 1.03 |
August | 0.198082E+10 | 0.65 | 1230.39 | 01-AUG-08:40 | 1.03 |
September | 0.193098E+10 | 0.68 | 1230.39 | 01-SEP-08:40 | 1.03 |
October | 0.189911E+10 | 0.69 | 1230.39 | 02-OCT-10:30 | 1.04 |
November | 0.169944E+10 | 0.63 | 1230.39 | 02-NOV-08:15 | 1.04 |
December | 0.166315E+10 | 0.55 | 1230.39 | 01-DEC-09:04 | 1.04 |
Annual Sum or Average | 0.216182E+11 | 0.63 | |||
Minimum of Months | 0.152388E+10 | 0.55 | 1230.39 | 1.03 | |
Maximum of Months | 0.198082E+10 | 0.69 | 1230.39 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.177631E+10 | 0.56 | 1227.41 | 01-JAN-09:50 | 1.04 |
February | 0.160840E+10 | 0.56 | 1227.41 | 01-FEB-14:50 | 1.04 |
March | 0.181166E+10 | 0.57 | 1227.41 | 01-MAR-09:40 | 1.04 |
April | 0.172328E+10 | 0.56 | 1227.41 | 01-APR-07:04 | 1.04 |
May | 0.179398E+10 | 0.57 | 1227.41 | 01-MAY-07:40 | 1.04 |
June | 0.174980E+10 | 0.57 | 1227.41 | 01-JUN-14:10 | 1.03 |
July | 0.176747E+10 | 0.56 | 1227.41 | 01-JUL-08:07 | 1.03 |
August | 0.181166E+10 | 0.57 | 1227.41 | 01-AUG-07:03 | 1.03 |
September | 0.172328E+10 | 0.56 | 1227.41 | 01-SEP-07:30 | 1.03 |
October | 0.177631E+10 | 0.56 | 1227.41 | 04-OCT-08:00 | 1.04 |
November | 0.172328E+10 | 0.56 | 1227.41 | 02-NOV-08:00 | 1.04 |
December | 0.176747E+10 | 0.56 | 1227.41 | 01-DEC-08:10 | 1.04 |
Annual Sum or Average | 0.210329E+11 | 0.56 | |||
Minimum of Months | 0.160840E+10 | 0.56 | 1227.41 | 1.03 | |
Maximum of Months | 0.181166E+10 | 0.57 | 1227.41 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.178256E+10 | 0.56 | 1231.67 | 01-JAN-10:30 | 1.04 |
February | 0.161398E+10 | 0.56 | 1231.67 | 01-FEB-10:10 | 1.04 |
March | 0.181794E+10 | 0.57 | 1231.67 | 02-MAR-08:09 | 1.04 |
April | 0.172926E+10 | 0.56 | 1231.67 | 01-APR-07:50 | 1.04 |
May | 0.180021E+10 | 0.57 | 1231.67 | 01-MAY-11:00 | 1.04 |
June | 0.175587E+10 | 0.57 | 1231.67 | 01-JUN-13:50 | 1.03 |
July | 0.177360E+10 | 0.56 | 1231.67 | 01-JUL-07:10 | 1.03 |
August | 0.181794E+10 | 0.57 | 1231.67 | 01-AUG-08:50 | 1.03 |
September | 0.172926E+10 | 0.56 | 1231.67 | 01-SEP-08:09 | 1.03 |
October | 0.178247E+10 | 0.56 | 1231.67 | 02-OCT-18:40 | 1.04 |
November | 0.172926E+10 | 0.56 | 1231.67 | 02-NOV-08:00 | 1.04 |
December | 0.177360E+10 | 0.56 | 1231.67 | 01-DEC-09:08 | 1.04 |
Annual Sum or Average | 0.211060E+11 | 0.56 | |||
Minimum of Months | 0.161398E+10 | 0.56 | 1231.67 | 1.03 | |
Maximum of Months | 0.181794E+10 | 0.57 | 1231.67 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.177398E+10 | 0.56 | 1225.67 | 14-JAN-08:20 | 1.04 |
February | 0.160612E+10 | 0.56 | 1225.67 | 11-FEB-18:10 | 1.04 |
March | 0.180909E+10 | 0.57 | 1225.67 | 13-MAR-12:30 | 1.04 |
April | 0.172084E+10 | 0.56 | 1225.67 | 23-APR-16:00 | 1.04 |
May | 0.179144E+10 | 0.57 | 1225.67 | 12-MAY-13:10 | 1.04 |
June | 0.174731E+10 | 0.57 | 1225.67 | 01-JUN-13:40 | 1.03 |
July | 0.176496E+10 | 0.56 | 1225.67 | 08-JUL-16:10 | 1.04 |
August | 0.180909E+10 | 0.57 | 1225.67 | 08-AUG-07:40 | 1.03 |
September | 0.172084E+10 | 0.56 | 1225.67 | 20-SEP-16:00 | 1.04 |
October | 0.177379E+10 | 0.56 | 1225.67 | 06-OCT-09:40 | 1.04 |
November | 0.172084E+10 | 0.56 | 1225.67 | 22-NOV-14:40 | 1.04 |
December | 0.176496E+10 | 0.56 | 1225.67 | 28-DEC-08:00 | 1.04 |
Annual Sum or Average | 0.210033E+11 | 0.56 | |||
Minimum of Months | 0.160612E+10 | 0.56 | 1225.67 | 1.03 | |
Maximum of Months | 0.180909E+10 | 0.57 | 1225.67 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.288557E+10 | 0.51 | 2157.93 | 01-JAN-09:02 | 1.01 |
February | 0.261036E+10 | 0.50 | 2157.93 | 12-FEB-16:00 | 1.01 |
March | 0.294428E+10 | 0.51 | 2157.93 | 01-MAR-08:62 | 1.00 |
April | 0.279668E+10 | 0.50 | 2157.93 | 01-APR-07:02 | 1.01 |
May | 0.291321E+10 | 0.51 | 2157.93 | 02-MAY-14:30 | 1.00 |
June | 0.284329E+10 | 0.51 | 2157.93 | 06-JUN-10:20 | 1.00 |
July | 0.286659E+10 | 0.50 | 2157.93 | 01-JUL-07:01 | 1.00 |
August | 0.294428E+10 | 0.51 | 2157.93 | 01-AUG-07:01 | 1.00 |
September | 0.279668E+10 | 0.50 | 2157.93 | 12-SEP-15:20 | 1.00 |
October | 0.288213E+10 | 0.50 | 2157.93 | 05-OCT-15:10 | 1.00 |
November | 0.279668E+10 | 0.50 | 2157.93 | 15-NOV-11:20 | 1.01 |
December | 0.286705E+10 | 0.50 | 2157.93 | 07-DEC-10:50 | 1.00 |
Annual Sum or Average | 0.341468E+11 | 0.50 | |||
Minimum of Months | 0.261036E+10 | 0.50 | 2157.93 | 1.00 | |
Maximum of Months | 0.294428E+10 | 0.51 | 2157.93 | 1.01 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154819E+10 | 0.53 | 1157.97 | 01-JAN-11:10 | 1.04 |
February | 0.140068E+10 | 0.52 | 1157.97 | 18-FEB-16:00 | 1.04 |
March | 0.157994E+10 | 0.53 | 1157.97 | 01-MAR-10:10 | 1.04 |
April | 0.150073E+10 | 0.52 | 1157.97 | 19-APR-13:50 | 1.04 |
May | 0.156326E+10 | 0.52 | 1157.97 | 10-MAY-10:50 | 1.04 |
June | 0.152575E+10 | 0.53 | 1157.97 | 01-JUN-13:30 | 1.03 |
July | 0.153825E+10 | 0.51 | 1157.97 | 01-JUL-10:00 | 1.03 |
August | 0.157994E+10 | 0.53 | 1157.97 | 01-AUG-09:40 | 1.03 |
September | 0.150073E+10 | 0.52 | 1157.97 | 01-SEP-13:50 | 1.03 |
October | 0.154659E+10 | 0.52 | 1157.97 | 17-OCT-12:40 | 1.04 |
November | 0.150073E+10 | 0.52 | 1157.97 | 15-NOV-10:10 | 1.04 |
December | 0.153844E+10 | 0.52 | 1157.97 | 06-DEC-11:10 | 1.04 |
Annual Sum or Average | 0.183232E+11 | 0.52 | |||
Minimum of Months | 0.140068E+10 | 0.51 | 1157.97 | 1.03 | |
Maximum of Months | 0.157994E+10 | 0.53 | 1157.97 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153674E+10 | 0.53 | 1149.28 | 01-JAN-10:30 | 1.04 |
February | 0.139024E+10 | 0.52 | 1149.28 | 02-FEB-08:40 | 1.04 |
March | 0.156808E+10 | 0.53 | 1149.28 | 01-MAR-18:20 | 1.04 |
April | 0.148946E+10 | 0.52 | 1149.28 | 01-APR-10:20 | 1.04 |
May | 0.155153E+10 | 0.52 | 1149.28 | 01-MAY-10:40 | 1.04 |
June | 0.151429E+10 | 0.53 | 1149.28 | 01-JUN-19:20 | 1.03 |
July | 0.152670E+10 | 0.51 | 1149.28 | 01-JUL-08:10 | 1.03 |
August | 0.156808E+10 | 0.53 | 1149.28 | 01-AUG-11:30 | 1.03 |
September | 0.148946E+10 | 0.52 | 1149.28 | 05-SEP-19:03 | 1.03 |
October | 0.153498E+10 | 0.52 | 1149.28 | 02-OCT-14:10 | 1.04 |
November | 0.148946E+10 | 0.52 | 1149.28 | 02-NOV-10:00 | 1.04 |
December | 0.152689E+10 | 0.52 | 1149.28 | 01-DEC-10:50 | 1.04 |
Annual Sum or Average | 0.181859E+11 | 0.52 | |||
Minimum of Months | 0.139024E+10 | 0.51 | 1149.28 | 1.03 | |
Maximum of Months | 0.156808E+10 | 0.53 | 1149.28 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.152549E+10 | 0.54 | 1139.79 | 03-JAN-09:17 | 1.04 |
February | 0.137889E+10 | 0.52 | 1139.79 | 01-FEB-08:08 | 1.04 |
March | 0.155533E+10 | 0.53 | 1139.79 | 01-MAR-14:00 | 1.04 |
April | 0.147717E+10 | 0.52 | 1139.79 | 01-APR-08:02 | 1.04 |
May | 0.153872E+10 | 0.52 | 1139.79 | 02-MAY-08:40 | 1.04 |
June | 0.150179E+10 | 0.53 | 1139.79 | 01-JUN-14:50 | 1.03 |
July | 0.151410E+10 | 0.51 | 1139.79 | 02-JUL-09:06 | 1.03 |
August | 0.155513E+10 | 0.53 | 1139.79 | 01-AUG-18:20 | 1.03 |
September | 0.147717E+10 | 0.52 | 1139.79 | 05-SEP-19:13 | 1.03 |
October | 0.152231E+10 | 0.52 | 1139.79 | 02-OCT-14:00 | 1.04 |
November | 0.147717E+10 | 0.52 | 1139.79 | 02-NOV-11:20 | 1.04 |
December | 0.151447E+10 | 0.52 | 1139.79 | 02-DEC-09:04 | 1.04 |
Annual Sum or Average | 0.180377E+11 | 0.52 | |||
Minimum of Months | 0.137889E+10 | 0.51 | 1139.79 | 1.03 | |
Maximum of Months | 0.155533E+10 | 0.54 | 1139.79 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158170E+10 | 0.62 | 1162.23 | 14-JAN-11:50 | 1.04 |
February | 0.141319E+10 | 0.56 | 1162.23 | 01-FEB-08:20 | 1.04 |
March | 0.159173E+10 | 0.55 | 1162.23 | 01-MAR-09:09 | 1.04 |
April | 0.150625E+10 | 0.52 | 1162.23 | 11-APR-09:20 | 1.04 |
May | 0.156901E+10 | 0.52 | 1162.23 | 17-MAY-16:10 | 1.04 |
June | 0.153135E+10 | 0.53 | 1162.23 | 03-JUN-10:50 | 1.03 |
July | 0.154390E+10 | 0.51 | 1162.23 | 03-JUL-08:50 | 1.03 |
August | 0.158574E+10 | 0.53 | 1162.23 | 29-AUG-20:00 | 1.03 |
September | 0.150625E+10 | 0.52 | 1162.23 | 01-SEP-08:30 | 1.03 |
October | 0.155227E+10 | 0.52 | 1162.23 | 03-OCT-08:13 | 1.04 |
November | 0.150751E+10 | 0.53 | 1162.23 | 14-NOV-20:00 | 1.04 |
December | 0.155094E+10 | 0.55 | 1162.23 | 07-DEC-12:20 | 1.04 |
Annual Sum or Average | 0.184398E+11 | 0.54 | |||
Minimum of Months | 0.141319E+10 | 0.51 | 1162.23 | 1.03 | |
Maximum of Months | 0.159173E+10 | 0.62 | 1162.23 | 1.04 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.28 | 0.56 |
February | 1.62 | 0.78 |
March | 1.15 | 0.49 |
April | 0.29 | 1.50 |
May | 0.22 | 1.50 |
June | 0.54 | 1.04 |
July | 0.25 | 0.50 |
August | 0.25 | 0.00 |
September | 0.72 | 1.21 |
October | 0.90 | 1.50 |
November | 0.49 | 0.39 |
December | 1.02 | 1.01 |
Annual Sum or Average | 9.73 | 0.82 |
Minimum of Months | 0.22 | 0.00 |
Maximum of Months | 2.28 | 1.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.46 | 3.27 |
February | 1.19 | 5.83 |
March | 1.79 | 4.87 |
April | 2.02 | 3.73 |
May | 3.49 | 3.65 |
June | 4.32 | 3.54 |
July | 4.28 | 2.65 |
August | 5.69 | 3.16 |
September | 3.88 | 3.04 |
October | 1.39 | 2.90 |
November | 1.12 | 3.43 |
December | 0.76 | 4.58 |
Annual Sum or Average | 30.40 | 3.46 |
Minimum of Months | 0.46 | 2.65 |
Maximum of Months | 5.69 | 5.83 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.48 | 0.00 |
February | 0.31 | 0.14 |
March | 0.07 | 0.00 |
April | 1.03 | 0.75 |
May | 1.10 | 0.69 |
June | 1.91 | 0.75 |
July | 2.48 | 0.72 |
August | 2.64 | 0.73 |
September | 1.79 | 0.71 |
October | 1.29 | 0.70 |
November | 0.67 | 0.56 |
December | 0.08 | 0.00 |
Annual Sum or Average | 13.85 | 0.67 |
Minimum of Months | 0.07 | 0.00 |
Maximum of Months | 2.64 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.57 | 0.00 |
February | 0.25 | 0.00 |
March | 0.15 | 0.00 |
April | 0.72 | 0.75 |
May | 0.96 | 0.69 |
June | 1.91 | 0.75 |
July | 2.48 | 0.72 |
August | 2.64 | 0.73 |
September | 1.79 | 0.71 |
October | 1.25 | 0.70 |
November | 0.47 | 0.49 |
December | 0.17 | 0.00 |
Annual Sum or Average | 13.36 | 0.65 |
Minimum of Months | 0.15 | 0.00 |
Maximum of Months | 2.64 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.61 | 0.00 |
February | 0.25 | 0.00 |
March | 0.15 | 0.00 |
April | 0.50 | 0.75 |
May | 0.96 | 0.69 |
June | 1.66 | 0.75 |
July | 2.40 | 0.72 |
August | 2.72 | 0.73 |
September | 1.87 | 0.72 |
October | 0.92 | 0.68 |
November | 0.33 | 0.37 |
December | 0.17 | 0.00 |
Annual Sum or Average | 12.55 | 0.64 |
Minimum of Months | 0.15 | 0.00 |
Maximum of Months | 2.72 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.54 | 0.00 |
February | 0.55 | 0.00 |
March | 0.22 | 0.00 |
April | 0.08 | 3.30 |
May | 0.51 | 2.76 |
June | 0.77 | 3.30 |
July | 1.41 | 3.10 |
August | 0.94 | 3.01 |
September | 1.37 | 3.10 |
October | 0.86 | 2.98 |
November | 0.07 | 1.83 |
December | 0.40 | 0.00 |
Annual Sum or Average | 8.73 | 2.10 |
Minimum of Months | 0.07 | 0.00 |
Maximum of Months | 1.54 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.92 | 0.00 |
February | 0.38 | 0.00 |
March | 0.22 | 0.00 |
April | 0.00 | 0.00 |
May | 0.51 | 1.38 |
June | 0.77 | 1.65 |
July | 1.41 | 1.55 |
August | 0.94 | 1.50 |
September | 1.12 | 1.65 |
October | 0.69 | 1.45 |
November | 0.07 | 0.92 |
December | 0.32 | 0.00 |
Annual Sum or Average | 7.35 | 1.16 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.41 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.92 | 0.00 |
February | 0.30 | 0.00 |
March | 0.22 | 0.00 |
April | 0.00 | 0.00 |
May | 0.42 | 1.32 |
June | 0.69 | 1.65 |
July | 1.24 | 1.54 |
August | 0.69 | 1.45 |
September | 1.12 | 1.65 |
October | 0.64 | 1.43 |
November | 0.07 | 0.00 |
December | 0.32 | 0.00 |
Annual Sum or Average | 6.63 | 1.11 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.24 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.57 | 0.00 |
February | 0.55 | 0.00 |
March | 0.27 | 0.00 |
April | 0.00 | 0.00 |
May | 0.34 | 1.24 |
June | 0.69 | 1.65 |
July | 1.08 | 1.65 |
August | 0.78 | 1.65 |
September | 0.79 | 1.65 |
October | 0.56 | 1.40 |
November | 0.13 | 0.00 |
December | 0.57 | 0.00 |
Annual Sum or Average | 7.31 | 0.91 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.57 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.80 | 0.00 |
February | 2.15 | 0.00 |
March | 1.16 | 0.00 |
April | 0.31 | 0.00 |
May | 0.42 | 0.67 |
June | 0.51 | 1.65 |
July | 0.99 | 1.51 |
August | 0.69 | 1.45 |
September | 0.90 | 1.50 |
October | 0.00 | 0.00 |
November | 1.13 | 0.00 |
December | 2.34 | 0.00 |
Annual Sum or Average | 14.40 | 0.34 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.80 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.400563E+10 | 0.299960E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.362000E+10 | 0.157216E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.400760E+10 | 0.116130E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.390543E+10 | 0.339585E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.455815E+10 | 0.207668E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.611228E+10 | 6451412.84 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.851117E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.763451E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.581148E+10 | 63898691.51 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.421956E+10 | 0.812083E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.386414E+10 | 0.728556E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.401548E+10 | 0.204482E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.602654E+11 | 0.914193E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.362000E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.851117E+10 | 0.299960E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.167695E+10 | 0.104578E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.152672E+10 | 0.514337E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.170249E+10 | 0.314031E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.177265E+10 | 0.723455E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.227411E+10 | 0.461996E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.324755E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.440696E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.399333E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.300536E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.204561E+10 | 0.151253E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.170565E+10 | 0.205844E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.166315E+10 | 0.663675E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.290205E+11 | 0.287734E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.152672E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.440696E+10 | 0.104578E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.177631E+10 | 0.120101E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.160840E+10 | 0.622666E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.181166E+10 | 0.416509E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.174163E+10 | 0.107347E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.203634E+10 | 0.718243E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.273094E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.365284E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.336980E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.251444E+10 | 2849976.42 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.189004E+10 | 0.321432E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.172328E+10 | 0.276520E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.176747E+10 | 0.805259E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.266231E+11 | 0.353356E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.160840E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.365284E+10 | 0.120101E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.178256E+10 | 0.123657E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.161398E+10 | 0.647237E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.181794E+10 | 0.444586E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.174553E+10 | 0.120506E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.203617E+10 | 0.804337E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.273352E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.366650E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.338065E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.251991E+10 | 6872169.78 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.189031E+10 | 0.384524E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.172926E+10 | 0.297603E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.177360E+10 | 0.837647E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.266900E+11 | 0.370372E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.161398E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.366650E+10 | 0.123657E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.177398E+10 | 0.128494E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.160612E+10 | 0.682513E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.180909E+10 | 0.483241E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.173427E+10 | 0.140661E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.201411E+10 | 0.919600E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.269759E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.362399E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.334085E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.249214E+10 | 18161806.91 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.187314E+10 | 0.455380E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.172084E+10 | 0.323564E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.176496E+10 | 0.881019E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.264511E+11 | 0.393525E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.160612E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.362399E+10 | 0.128494E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.288557E+10 | 0.247920E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.261036E+10 | 0.133626E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.294428E+10 | 0.978477E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.281395E+10 | 0.314101E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.329543E+10 | 0.201418E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.460065E+10 | 3339288.71 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.631457E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.578511E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.418454E+10 | 0.109964E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.304513E+10 | 0.107460E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.279668E+10 | 0.669449E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.286705E+10 | 0.172892E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.441433E+11 | 0.782661E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.261036E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.631457E+10 | 0.247920E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.154819E+10 | 0.128558E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.140069E+10 | 0.693025E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.157994E+10 | 0.509937E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.150859E+10 | 0.164688E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.175224E+10 | 0.105711E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.240326E+10 | 1150053.91 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.326654E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.300288E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.219560E+10 | 58087714.61 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.162710E+10 | 0.553816E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.150073E+10 | 0.347441E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.153844E+10 | 0.894795E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.233242E+11 | 0.406248E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.140069E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.326654E+10 | 0.128558E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.153674E+10 | 0.129941E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.139024E+10 | 0.705348E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.156808E+10 | 0.526890E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.149619E+10 | 0.176850E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.173266E+10 | 0.112697E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.237416E+10 | 3079433.20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.323211E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.297073E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.217266E+10 | 74473351.39 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.161139E+10 | 0.596449E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.148946E+10 | 0.359814E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.152689E+10 | 0.909773E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.231013E+11 | 0.415818E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.139024E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.323211E+10 | 0.129941E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.152549E+10 | 0.135716E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.137889E+10 | 0.751893E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.155533E+10 | 0.582223E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.148141E+10 | 0.213516E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.170167E+10 | 0.135492E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.232091E+10 | 14761713.97 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.317516E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.291774E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.213628E+10 | 0.127421E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.158958E+10 | 0.722780E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.147717E+10 | 0.397074E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.151447E+10 | 0.963857E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.227741E+11 | 0.448771E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.137889E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.317516E+10 | 0.135716E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.158170E+10 | 0.171408E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.141319E+10 | 0.982570E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159173E+10 | 0.821620E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.150737E+10 | 0.346508E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.170641E+10 | 0.212680E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.230008E+10 | 83224439.59 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.318392E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.292371E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.213824E+10 | 0.338596E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.160697E+10 | 0.117723E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.150751E+10 | 0.533504E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.155094E+10 | 0.121230E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.230118E+11 | 0.598316E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.141319E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.318392E+10 | 0.171408E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.400563E+10 | 0.00 | 0.239968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.362000E+10 | 2582.98 | 0.125773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.400760E+10 | 0.00 | 0.929042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.387841E+10 | 97718874.51 | 0.271668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.399753E+10 | 0.205346E+10 | 0.166135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.387841E+10 | 0.814835E+10 | 5161130.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.400531E+10 | 0.161250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.399738E+10 | 0.130341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.388634E+10 | 0.703486E+10 | 51118953.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.399738E+10 | 0.830360E+09 | 0.649667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.386413E+10 | 10830.88 | 0.582844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.401548E+10 | 0.00 | 0.163586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471536E+11 | 0.473239E+11 | 0.731355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.362000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.401548E+10 | 0.161250E+11 | 0.239968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.167695E+10 | 0.00 | 0.836627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152388E+10 | 11315094.12 | 0.411470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170219E+10 | 1031269.27 | 0.251225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174068E+10 | 0.126798E+09 | 0.578764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.190090E+10 | 0.149851E+10 | 0.369596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.194879E+10 | 0.506172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195132E+10 | 0.926473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198082E+10 | 0.762491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.193098E+10 | 0.414087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189911E+10 | 0.578003E+09 | 0.121002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169944E+10 | 22837288.57 | 0.164675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166315E+10 | 0.00 | 0.530940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216182E+11 | 0.283307E+11 | 0.230187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.198082E+10 | 0.926473E+10 | 0.836627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.177631E+10 | 0.00 | 0.960806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160840E+10 | 1917.11 | 0.498133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181166E+10 | 0.00 | 0.333207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172328E+10 | 68804558.63 | 0.858773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179398E+10 | 0.914901E+09 | 0.574594E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174980E+10 | 0.367462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176747E+10 | 0.692802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181166E+10 | 0.574212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172328E+10 | 0.298558E+10 | 2279981.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177631E+10 | 0.439017E+09 | 0.257146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172328E+10 | 5306.36 | 0.221216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176747E+10 | 0.00 | 0.644207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210329E+11 | 0.207531E+11 | 0.282685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181166E+10 | 0.692802E+10 | 0.960806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.178256E+10 | 0.00 | 0.989258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161398E+10 | 1914.33 | 0.517790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181794E+10 | 0.00 | 0.355669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172926E+10 | 60808481.26 | 0.964050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180021E+10 | 0.889108E+09 | 0.643470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.175587E+10 | 0.365885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.177360E+10 | 0.695606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181794E+10 | 0.575830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172926E+10 | 0.298289E+10 | 5497735.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178247E+10 | 0.415356E+09 | 0.307619E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172926E+10 | 6501.68 | 0.238082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177360E+10 | 0.00 | 0.670117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211060E+11 | 0.207214E+11 | 0.296298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181794E+10 | 0.695606E+10 | 0.989258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.177398E+10 | 0.00 | 0.102795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160612E+10 | 1430.14 | 0.546011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180909E+10 | 0.00 | 0.386592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172084E+10 | 49993031.61 | 0.112529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179144E+10 | 0.836061E+09 | 0.735680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174731E+10 | 0.354818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176496E+10 | 0.681984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180909E+10 | 0.563390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172084E+10 | 0.290499E+10 | 14529445.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177379E+10 | 0.381380E+09 | 0.364304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172084E+10 | 2899.15 | 0.258851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176496E+10 | 0.00 | 0.704815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210033E+11 | 0.201743E+11 | 0.314820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180909E+10 | 0.681984E+10 | 0.102795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.288557E+10 | 0.00 | 0.198336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.261036E+10 | 1359.68 | 0.106901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.294428E+10 | 0.00 | 0.782782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.279668E+10 | 61963208.21 | 0.251281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.291321E+10 | 0.138427E+10 | 0.161134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.284329E+10 | 0.634586E+10 | 2671430.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.286659E+10 | 0.122340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.294428E+10 | 0.101054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.279668E+10 | 0.506649E+10 | 87971103.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288213E+10 | 0.604087E+09 | 0.859678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279668E+10 | 2146.34 | 0.535559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.286705E+10 | 0.00 | 0.138314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.341468E+11 | 0.358021E+11 | 0.626129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.261036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.294428E+10 | 0.122340E+11 | 0.198336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154819E+10 | 0.00 | 0.102847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140068E+10 | 4100.06 | 0.554420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157994E+10 | 0.00 | 0.407949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150073E+10 | 28969249.01 | 0.131750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156326E+10 | 0.704000E+09 | 0.845685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152575E+10 | 0.326085E+10 | 920043.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153825E+10 | 0.631254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157994E+10 | 0.521024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150073E+10 | 0.261168E+10 | 46470171.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154659E+10 | 0.307149E+09 | 0.443053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150073E+10 | 1105.41 | 0.277953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153844E+10 | 0.00 | 0.715836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183232E+11 | 0.184354E+11 | 0.324999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157994E+10 | 0.631254E+10 | 0.102847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153674E+10 | 0.00 | 0.103953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139024E+10 | 568.73 | 0.564279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156808E+10 | 0.00 | 0.421512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148946E+10 | 24745943.98 | 0.141480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155153E+10 | 0.673173E+09 | 0.901575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151429E+10 | 0.319114E+10 | 2463546.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152670E+10 | 0.622361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156808E+10 | 0.513121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148946E+10 | 0.256562E+10 | 59578681.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153498E+10 | 0.291109E+09 | 0.477159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148946E+10 | 1027.87 | 0.287851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152689E+10 | 0.00 | 0.727818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181859E+11 | 0.181006E+11 | 0.332654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.156808E+10 | 0.622361E+10 | 0.103953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.152549E+10 | 0.00 | 0.108573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137889E+10 | 428.90 | 0.601514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155533E+10 | 0.00 | 0.465778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147717E+10 | 15497284.67 | 0.170812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153872E+10 | 0.601839E+09 | 0.108393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150179E+10 | 0.302759E+10 | 11809371.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151410E+10 | 0.604655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155513E+10 | 0.497143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147717E+10 | 0.246910E+10 | 0.101937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152231E+10 | 0.255304E+09 | 0.578224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147717E+10 | 2643.42 | 0.317659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151447E+10 | 0.00 | 0.771086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180377E+11 | 0.173873E+11 | 0.359017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155533E+10 | 0.604655E+10 | 0.108573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158170E+10 | 0.00 | 0.137126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141319E+10 | 0.00 | 0.786056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159173E+10 | 0.00 | 0.657296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150625E+10 | 4026988.63 | 0.277207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156901E+10 | 0.501539E+09 | 0.170144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153135E+10 | 0.281996E+10 | 66579551.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154390E+10 | 0.594862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158574E+10 | 0.486277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150625E+10 | 0.235663E+10 | 0.270877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155227E+10 | 0.206147E+09 | 0.941784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150751E+10 | 0.00 | 0.426804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155094E+10 | 0.00 | 0.969837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184398E+11 | 0.166997E+11 | 0.478653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159173E+10 | 0.594862E+10 | 0.137126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.400563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.362000E+10 | 0.00 | 0.00 | 0.00 | 729.14 | 0.00 | 0.157216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.400760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.387841E+10 | 0.00 | 0.00 | 0.00 | 27013167.02 | 0.00 | 0.339585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.399753E+10 | 0.00 | 0.00 | 0.00 | 0.560618E+09 | 0.00 | 0.207668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.387841E+10 | 0.00 | 0.00 | 0.00 | 0.223387E+10 | 0.00 | 6451412.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.400531E+10 | 0.00 | 0.00 | 0.00 | 0.450586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.399738E+10 | 0.00 | 0.00 | 0.00 | 0.363713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.388634E+10 | 0.00 | 0.00 | 0.00 | 0.192513E+10 | 0.00 | 63898691.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.399738E+10 | 0.00 | 0.00 | 0.00 | 0.222174E+09 | 0.00 | 0.812083E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.386413E+10 | 0.00 | 0.00 | 0.00 | 3057.40 | 0.00 | 0.728556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.401548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471536E+11 | 0.00 | 0.00 | 0.00 | 0.131118E+11 | 0.00 | 0.914193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.362000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.401548E+10 | 0.00 | 0.00 | 0.00 | 0.450586E+10 | 0.00 | 0.299960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.167695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152388E+10 | 0.00 | 0.00 | 0.00 | 2844511.02 | 0.00 | 0.514337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170219E+10 | 0.00 | 0.00 | 0.00 | 303730.31 | 0.00 | 0.314031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174068E+10 | 0.00 | 0.00 | 0.00 | 31965987.15 | 0.00 | 0.723455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.190090E+10 | 0.00 | 0.00 | 0.00 | 0.373209E+09 | 0.00 | 0.461996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.194879E+10 | 0.00 | 0.00 | 0.00 | 0.129876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195132E+10 | 0.00 | 0.00 | 0.00 | 0.245563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198082E+10 | 0.00 | 0.00 | 0.00 | 0.201250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.193098E+10 | 0.00 | 0.00 | 0.00 | 0.107438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189911E+10 | 0.00 | 0.00 | 0.00 | 0.146498E+09 | 0.00 | 0.151253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169944E+10 | 0.00 | 0.00 | 0.00 | 6209381.97 | 0.00 | 0.205844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216182E+11 | 0.00 | 0.00 | 0.00 | 0.740231E+10 | 0.00 | 0.287734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.152388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.198082E+10 | 0.00 | 0.00 | 0.00 | 0.245563E+10 | 0.00 | 0.104578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.177631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160840E+10 | 0.00 | 0.00 | 0.00 | 525.57 | 0.00 | 0.622666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172328E+10 | 0.00 | 0.00 | 0.00 | 18343264.29 | 0.00 | 0.107347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179398E+10 | 0.00 | 0.00 | 0.00 | 0.242357E+09 | 0.00 | 0.718243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174980E+10 | 0.00 | 0.00 | 0.00 | 0.981149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176747E+10 | 0.00 | 0.00 | 0.00 | 0.188537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181166E+10 | 0.00 | 0.00 | 0.00 | 0.155815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172328E+10 | 0.00 | 0.00 | 0.00 | 0.791158E+09 | 0.00 | 2849976.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177631E+10 | 0.00 | 0.00 | 0.00 | 0.113735E+09 | 0.00 | 0.321432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172328E+10 | 0.00 | 0.00 | 0.00 | 1454.73 | 0.00 | 0.276520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210329E+11 | 0.00 | 0.00 | 0.00 | 0.559026E+10 | 0.00 | 0.353356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.160840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181166E+10 | 0.00 | 0.00 | 0.00 | 0.188537E+10 | 0.00 | 0.120101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.178256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161398E+10 | 0.00 | 0.00 | 0.00 | 524.81 | 0.00 | 0.647237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172926E+10 | 0.00 | 0.00 | 0.00 | 16266186.60 | 0.00 | 0.120506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180021E+10 | 0.00 | 0.00 | 0.00 | 0.235967E+09 | 0.00 | 0.804337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.175587E+10 | 0.00 | 0.00 | 0.00 | 0.977655E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.177360E+10 | 0.00 | 0.00 | 0.00 | 0.189290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181794E+10 | 0.00 | 0.00 | 0.00 | 0.156271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172926E+10 | 0.00 | 0.00 | 0.00 | 0.790650E+09 | 0.00 | 6872169.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178247E+10 | 0.00 | 0.00 | 0.00 | 0.107843E+09 | 0.00 | 0.384524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172926E+10 | 0.00 | 0.00 | 0.00 | 1782.37 | 0.00 | 0.297603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211060E+11 | 0.00 | 0.00 | 0.00 | 0.558399E+10 | 0.00 | 0.370372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.161398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181794E+10 | 0.00 | 0.00 | 0.00 | 0.189290E+10 | 0.00 | 0.123657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.177398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160612E+10 | 0.00 | 0.00 | 0.00 | 392.07 | 0.00 | 0.682513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172084E+10 | 0.00 | 0.00 | 0.00 | 13434389.20 | 0.00 | 0.140661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179144E+10 | 0.00 | 0.00 | 0.00 | 0.222677E+09 | 0.00 | 0.919600E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174731E+10 | 0.00 | 0.00 | 0.00 | 0.950280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176496E+10 | 0.00 | 0.00 | 0.00 | 0.185903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180909E+10 | 0.00 | 0.00 | 0.00 | 0.153176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172084E+10 | 0.00 | 0.00 | 0.00 | 0.771304E+09 | 0.00 | 18161806.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177379E+10 | 0.00 | 0.00 | 0.00 | 99354755.18 | 0.00 | 0.455380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172084E+10 | 0.00 | 0.00 | 0.00 | 794.80 | 0.00 | 0.323564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210033E+11 | 0.00 | 0.00 | 0.00 | 0.544784E+10 | 0.00 | 0.393525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.160612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180909E+10 | 0.00 | 0.00 | 0.00 | 0.185903E+10 | 0.00 | 0.128494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.288557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.261036E+10 | 0.00 | 0.00 | 0.00 | 383.82 | 0.00 | 0.133626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.294428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.978477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.279668E+10 | 0.00 | 0.00 | 0.00 | 17271321.78 | 0.00 | 0.314101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.291321E+10 | 0.00 | 0.00 | 0.00 | 0.382229E+09 | 0.00 | 0.201418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.284329E+10 | 0.00 | 0.00 | 0.00 | 0.175737E+10 | 0.00 | 3339288.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.286659E+10 | 0.00 | 0.00 | 0.00 | 0.344798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.294428E+10 | 0.00 | 0.00 | 0.00 | 0.284083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.279668E+10 | 0.00 | 0.00 | 0.00 | 0.138787E+10 | 0.00 | 0.109964E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288213E+10 | 0.00 | 0.00 | 0.00 | 0.162996E+09 | 0.00 | 0.107460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279668E+10 | 0.00 | 0.00 | 0.00 | 605.88 | 0.00 | 0.669449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.286705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.341468E+11 | 0.00 | 0.00 | 0.00 | 0.999653E+10 | 0.00 | 0.782661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.261036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.294428E+10 | 0.00 | 0.00 | 0.00 | 0.344798E+10 | 0.00 | 0.247920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.154819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140068E+10 | 0.00 | 0.00 | 0.00 | 1123.92 | 0.00 | 0.693025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150073E+10 | 0.00 | 0.00 | 0.00 | 7854582.76 | 0.00 | 0.164688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156326E+10 | 0.00 | 0.00 | 0.00 | 0.188980E+09 | 0.00 | 0.105711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152575E+10 | 0.00 | 0.00 | 0.00 | 0.877510E+09 | 0.00 | 1150053.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153825E+10 | 0.00 | 0.00 | 0.00 | 0.172829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157994E+10 | 0.00 | 0.00 | 0.00 | 0.142294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150073E+10 | 0.00 | 0.00 | 0.00 | 0.694869E+09 | 0.00 | 58087714.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154659E+10 | 0.00 | 0.00 | 0.00 | 80507109.25 | 0.00 | 0.553816E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150073E+10 | 0.00 | 0.00 | 0.00 | 303.05 | 0.00 | 0.347441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183232E+11 | 0.00 | 0.00 | 0.00 | 0.500096E+10 | 0.00 | 0.406248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.140068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157994E+10 | 0.00 | 0.00 | 0.00 | 0.172829E+10 | 0.00 | 0.128558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.153674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139024E+10 | 0.00 | 0.00 | 0.00 | 155.92 | 0.00 | 0.705348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148946E+10 | 0.00 | 0.00 | 0.00 | 6727239.51 | 0.00 | 0.176850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155153E+10 | 0.00 | 0.00 | 0.00 | 0.181131E+09 | 0.00 | 0.112697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151429E+10 | 0.00 | 0.00 | 0.00 | 0.859868E+09 | 0.00 | 3079433.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152670E+10 | 0.00 | 0.00 | 0.00 | 0.170541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156808E+10 | 0.00 | 0.00 | 0.00 | 0.140265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148946E+10 | 0.00 | 0.00 | 0.00 | 0.683199E+09 | 0.00 | 74473351.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153498E+10 | 0.00 | 0.00 | 0.00 | 76412382.38 | 0.00 | 0.596449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148946E+10 | 0.00 | 0.00 | 0.00 | 281.79 | 0.00 | 0.359814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.909773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181859E+11 | 0.00 | 0.00 | 0.00 | 0.491540E+10 | 0.00 | 0.415818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.139024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.156808E+10 | 0.00 | 0.00 | 0.00 | 0.170541E+10 | 0.00 | 0.129941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.152549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137889E+10 | 0.00 | 0.00 | 0.00 | 117.58 | 0.00 | 0.751893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147717E+10 | 0.00 | 0.00 | 0.00 | 4243477.32 | 0.00 | 0.213516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153872E+10 | 0.00 | 0.00 | 0.00 | 0.162946E+09 | 0.00 | 0.135492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150179E+10 | 0.00 | 0.00 | 0.00 | 0.819116E+09 | 0.00 | 14761713.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151410E+10 | 0.00 | 0.00 | 0.00 | 0.166106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155513E+10 | 0.00 | 0.00 | 0.00 | 0.136261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147717E+10 | 0.00 | 0.00 | 0.00 | 0.659107E+09 | 0.00 | 0.127421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152231E+10 | 0.00 | 0.00 | 0.00 | 67277675.83 | 0.00 | 0.722780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147717E+10 | 0.00 | 0.00 | 0.00 | 724.65 | 0.00 | 0.397074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180377E+11 | 0.00 | 0.00 | 0.00 | 0.473636E+10 | 0.00 | 0.448771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.137889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155533E+10 | 0.00 | 0.00 | 0.00 | 0.166106E+10 | 0.00 | 0.135716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.158170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150625E+10 | 0.00 | 0.00 | 0.00 | 1121948.61 | 0.00 | 0.346508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156901E+10 | 0.00 | 0.00 | 0.00 | 0.137406E+09 | 0.00 | 0.212680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153135E+10 | 0.00 | 0.00 | 0.00 | 0.768732E+09 | 0.00 | 83224439.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154390E+10 | 0.00 | 0.00 | 0.00 | 0.164002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158574E+10 | 0.00 | 0.00 | 0.00 | 0.133796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150625E+10 | 0.00 | 0.00 | 0.00 | 0.631992E+09 | 0.00 | 0.338596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155227E+10 | 0.00 | 0.00 | 0.00 | 54701570.62 | 0.00 | 0.117723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184398E+11 | 0.00 | 0.00 | 0.00 | 0.457194E+10 | 0.00 | 0.598316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.141319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159173E+10 | 0.00 | 0.00 | 0.00 | 0.164002E+10 | 0.00 | 0.171408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.523294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168030E+11 | 0.00 | 0.00 | 0.52 |
February | 0.640066E+10 | 0.00 | 0.00 | 132865.60 | 0.00 | 0.884516E+10 | 0.167392E+09 | 0.00 | 0.53 |
March | 0.882532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590932E+10 | 0.00 | 0.00 | 0.53 |
April | 0.754913E+10 | 0.00 | 0.00 | 1832829.72 | 0.00 | 0.144917E+10 | 0.172572E+10 | 0.00 | 0.62 |
May | 0.502378E+10 | 44772349.27 | 0.00 | 11561437.60 | 2746082.82 | 0.879693E+09 | 0.434807E+10 | 0.00 | 0.86 |
June | 0.755842E+09 | 0.574749E+09 | 0.00 | 24037165.49 | 0.00 | 0.00 | 0.678174E+10 | 0.00 | 1.12 |
July | 58387532.46 | 0.147176E+10 | 0.00 | 30510343.73 | 3320470.58 | 0.00 | 0.455558E+10 | 0.00 | 1.06 |
August | 0.303197E+09 | 0.103599E+10 | 0.00 | 31152944.89 | 1821988.64 | 0.00 | 0.623266E+10 | 0.00 | 1.17 |
September | 0.203250E+10 | 0.546955E+09 | 0.00 | 20574969.01 | 729164.73 | 2745011.87 | 0.707523E+10 | 0.00 | 1.04 |
October | 0.575671E+10 | 4352085.95 | 0.00 | 8533491.91 | 0.00 | 0.109317E+09 | 0.623124E+10 | 0.00 | 0.78 |
November | 0.934750E+10 | 0.00 | 0.00 | 909958.54 | 0.00 | 0.293104E+10 | 0.101327E+10 | 0.00 | 0.54 |
December | 0.824463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103833E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.595306E+11 | 0.367857E+10 | 0.00 | 0.129246E+09 | 8617706.77 | 0.473128E+11 | 0.381309E+11 | 0.00 | 0.78 |
Minimum of Months | 58387532.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.934750E+10 | 0.147176E+10 | 0.00 | 31152944.89 | 3320470.58 | 0.168030E+11 | 0.707523E+10 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.220771E+10 | 0.00 | 0.00 | 8552.73 | 0.00 | 0.575301E+10 | 6704471.23 | 0.00 | 0.39 |
February | 0.263499E+10 | 0.00 | 0.00 | 345048.36 | 0.00 | 0.271656E+10 | 0.341216E+09 | 0.00 | 0.41 |
March | 0.367509E+10 | 0.00 | 0.00 | 64623.52 | 0.00 | 0.161589E+10 | 53333493.84 | 0.00 | 0.40 |
April | 0.250428E+10 | 0.00 | 0.00 | 1981233.32 | 0.00 | 0.345431E+09 | 0.176804E+10 | 0.00 | 0.58 |
May | 0.172133E+10 | 23095880.88 | 0.00 | 5393364.09 | 31113.47 | 0.223164E+09 | 0.283531E+10 | 0.00 | 0.84 |
June | 0.209105E+09 | 0.285825E+09 | 0.00 | 9706928.89 | 0.00 | 0.00 | 0.363205E+10 | 0.00 | 1.10 |
July | 15805351.23 | 0.716356E+09 | 0.00 | 10076371.82 | 2607188.96 | 0.00 | 0.204954E+10 | 0.00 | 0.94 |
August | 0.110303E+09 | 0.498719E+09 | 0.00 | 11603161.57 | 984860.67 | 0.00 | 0.303898E+10 | 0.00 | 1.09 |
September | 0.720911E+09 | 0.266132E+09 | 0.00 | 9045524.25 | 611255.45 | 0.00 | 0.391356E+10 | 0.00 | 1.03 |
October | 0.176554E+10 | 2223218.84 | 0.00 | 5908980.67 | 0.00 | 6094646.45 | 0.416180E+10 | 0.00 | 0.80 |
November | 0.322157E+10 | 0.00 | 0.00 | 1220603.45 | 0.00 | 0.948595E+09 | 0.114701E+10 | 0.00 | 0.45 |
December | 0.308888E+10 | 0.00 | 0.00 | 7778.42 | 0.00 | 0.353021E+10 | 6631081.87 | 0.00 | 0.38 |
Annual Sum or Average | 0.218755E+11 | 0.179235E+10 | 0.00 | 55362171.09 | 4234418.55 | 0.151390E+11 | 0.229542E+11 | 0.00 | 0.70 |
Minimum of Months | 15805351.23 | 0.00 | 0.00 | 7778.42 | 0.00 | 0.00 | 6631081.87 | 0.00 | 0.38 |
Maximum of Months | 0.367509E+10 | 0.716356E+09 | 0.00 | 11603161.57 | 2607188.96 | 0.575301E+10 | 0.416180E+10 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.148154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695895E+10 | 0.00 | 0.00 | 0.41 |
February | 0.211216E+10 | 0.00 | 0.00 | 95059.30 | 0.00 | 0.369706E+10 | 0.125874E+09 | 0.00 | 0.42 |
March | 0.337646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227520E+10 | 0.00 | 0.00 | 0.42 |
April | 0.281077E+10 | 0.00 | 0.00 | 722280.00 | 0.00 | 0.531307E+09 | 0.771932E+09 | 0.00 | 0.51 |
May | 0.205678E+10 | 21579912.16 | 0.00 | 2385172.06 | 1312186.81 | 0.315038E+09 | 0.155118E+10 | 0.00 | 0.69 |
June | 0.409195E+09 | 0.265864E+09 | 0.00 | 5719607.86 | 5475359.60 | 0.00 | 0.244088E+10 | 0.00 | 0.91 |
July | 98427582.96 | 0.637384E+09 | 0.00 | 5981429.34 | 29404754.59 | 0.00 | 0.133618E+10 | 0.00 | 0.77 |
August | 0.249838E+09 | 0.459571E+09 | 0.00 | 6963785.78 | 16939311.72 | 0.00 | 0.210670E+10 | 0.00 | 0.91 |
September | 0.101694E+10 | 0.227661E+09 | 0.00 | 5378268.16 | 13766765.47 | 0.00 | 0.243152E+10 | 0.00 | 0.84 |
October | 0.231858E+10 | 2407168.20 | 0.00 | 3150000.67 | 0.00 | 54361606.93 | 0.228203E+10 | 0.00 | 0.66 |
November | 0.331843E+10 | 0.00 | 0.00 | 306849.19 | 0.00 | 0.138028E+10 | 0.371664E+09 | 0.00 | 0.43 |
December | 0.243955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460280E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.216887E+11 | 0.161447E+10 | 0.00 | 30702452.36 | 66898378.19 | 0.198150E+11 | 0.134180E+11 | 0.00 | 0.62 |
Minimum of Months | 98427582.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.337646E+10 | 0.637384E+09 | 0.00 | 6963785.78 | 29404754.59 | 0.695895E+10 | 0.244088E+10 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711934E+10 | 0.00 | 0.00 | 0.41 |
February | 0.193105E+10 | 0.00 | 0.00 | 67882.08 | 0.00 | 0.389391E+10 | 89289094.67 | 0.00 | 0.42 |
March | 0.316961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246762E+10 | 0.00 | 0.00 | 0.42 |
April | 0.280823E+10 | 0.00 | 0.00 | 585477.89 | 0.00 | 0.596424E+09 | 0.643018E+09 | 0.00 | 0.50 |
May | 0.204930E+10 | 21321157.88 | 0.00 | 2230681.95 | 1885043.49 | 0.359489E+09 | 0.145914E+10 | 0.00 | 0.68 |
June | 0.411241E+09 | 0.265767E+09 | 0.00 | 5661878.84 | 5457598.41 | 0.00 | 0.242889E+10 | 0.00 | 0.90 |
July | 99456393.01 | 0.637827E+09 | 0.00 | 6030901.54 | 29326928.68 | 0.00 | 0.134068E+10 | 0.00 | 0.78 |
August | 0.250709E+09 | 0.459843E+09 | 0.00 | 6995489.70 | 16843551.66 | 0.00 | 0.211509E+10 | 0.00 | 0.92 |
September | 0.102573E+10 | 0.227729E+09 | 0.00 | 5306446.09 | 13708588.18 | 0.00 | 0.239585E+10 | 0.00 | 0.83 |
October | 0.227765E+10 | 2407633.50 | 0.00 | 2914710.06 | 0.00 | 0.154519E+09 | 0.215624E+10 | 0.00 | 0.65 |
November | 0.317522E+10 | 0.00 | 0.00 | 218018.69 | 0.00 | 0.155753E+10 | 0.292536E+09 | 0.00 | 0.42 |
December | 0.226513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477333E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.207829E+11 | 0.161489E+10 | 0.00 | 30011486.84 | 67221710.43 | 0.209222E+11 | 0.129207E+11 | 0.00 | 0.61 |
Minimum of Months | 99456393.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.317522E+10 | 0.637827E+09 | 0.00 | 6995489.70 | 29326928.68 | 0.711934E+10 | 0.242889E+10 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732271E+10 | 0.00 | 0.00 | 0.41 |
February | 0.171663E+10 | 0.00 | 0.00 | 46083.93 | 0.00 | 0.411160E+10 | 66339024.73 | 0.00 | 0.42 |
March | 0.289739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272662E+10 | 0.00 | 0.00 | 0.42 |
April | 0.279104E+10 | 0.00 | 0.00 | 432653.80 | 0.00 | 0.699556E+09 | 0.479788E+09 | 0.00 | 0.49 |
May | 0.202497E+10 | 20808399.34 | 0.00 | 1951488.70 | 2548439.50 | 0.437518E+09 | 0.130202E+10 | 0.00 | 0.66 |
June | 0.430994E+09 | 0.264609E+09 | 0.00 | 5272473.31 | 5495249.61 | 0.00 | 0.232568E+10 | 0.00 | 0.89 |
July | 0.100338E+09 | 0.636892E+09 | 0.00 | 5746884.27 | 29709399.77 | 0.00 | 0.130484E+10 | 0.00 | 0.77 |
August | 0.258239E+09 | 0.459426E+09 | 0.00 | 6661203.62 | 17042846.70 | 0.00 | 0.205250E+10 | 0.00 | 0.91 |
September | 0.105695E+10 | 0.227048E+09 | 0.00 | 4932038.01 | 13791972.30 | 519672.48 | 0.227281E+10 | 0.00 | 0.82 |
October | 0.234843E+10 | 2406530.01 | 0.00 | 2536552.76 | 0.00 | 0.194288E+09 | 0.192661E+10 | 0.00 | 0.64 |
November | 0.300145E+10 | 0.00 | 0.00 | 130039.86 | 0.00 | 0.180035E+10 | 0.170686E+09 | 0.00 | 0.42 |
December | 0.197980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505696E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.197226E+11 | 0.161119E+10 | 0.00 | 27709418.26 | 68587907.89 | 0.223501E+11 | 0.119013E+11 | 0.00 | 0.60 |
Minimum of Months | 0.100338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.300145E+10 | 0.636892E+09 | 0.00 | 6661203.62 | 29709399.77 | 0.732271E+10 | 0.232568E+10 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.115646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143755E+11 | 0.00 | 0.00 | 0.38 |
February | 0.268371E+10 | 0.00 | 0.00 | 42621.89 | 0.00 | 0.802467E+10 | 73808500.86 | 0.00 | 0.38 |
March | 0.464481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560976E+10 | 0.00 | 0.00 | 0.39 |
April | 0.483136E+10 | 0.00 | 0.00 | 553994.40 | 0.00 | 0.151254E+10 | 0.691957E+09 | 0.00 | 0.43 |
May | 0.355133E+10 | 28260811.90 | 0.00 | 3020960.32 | 4335486.04 | 0.911944E+09 | 0.205833E+10 | 0.00 | 0.57 |
June | 0.590455E+09 | 0.489855E+09 | 0.00 | 8341639.46 | 150944.19 | 0.00 | 0.387379E+10 | 0.00 | 0.76 |
July | 97231865.58 | 0.122287E+10 | 0.00 | 8982383.73 | 27872229.41 | 0.00 | 0.204306E+10 | 0.00 | 0.66 |
August | 0.375389E+09 | 0.852769E+09 | 0.00 | 10166908.72 | 27112423.34 | 0.00 | 0.338684E+10 | 0.00 | 0.79 |
September | 0.178043E+10 | 0.409339E+09 | 0.00 | 7279575.24 | 27782290.92 | 2765005.38 | 0.382902E+10 | 0.00 | 0.71 |
October | 0.422560E+10 | 2425529.69 | 0.00 | 3543465.16 | 0.00 | 0.422711E+09 | 0.303134E+10 | 0.00 | 0.55 |
November | 0.506908E+10 | 0.00 | 0.00 | 87988.02 | 0.00 | 0.377015E+10 | 0.138290E+09 | 0.00 | 0.38 |
December | 0.290429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100001E+11 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.319101E+11 | 0.300553E+10 | 0.00 | 42019536.93 | 87253373.91 | 0.446301E+11 | 0.191264E+11 | 0.00 | 0.53 |
Minimum of Months | 97231865.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.506908E+10 | 0.122287E+10 | 0.00 | 10166908.72 | 27872229.41 | 0.143755E+11 | 0.387379E+10 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.432675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732660E+10 | 0.00 | 0.00 | 0.38 |
February | 0.123545E+10 | 0.00 | 0.00 | 16625.22 | 0.00 | 0.411900E+10 | 28005658.19 | 0.00 | 0.38 |
March | 0.216584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295357E+10 | 0.00 | 0.00 | 0.39 |
April | 0.225813E+10 | 0.00 | 0.00 | 246746.78 | 0.00 | 0.910222E+09 | 0.331192E+09 | 0.00 | 0.43 |
May | 0.167286E+10 | 14590185.91 | 0.00 | 1443614.39 | 2331034.07 | 0.571897E+09 | 0.100934E+10 | 0.00 | 0.57 |
June | 0.307334E+09 | 0.246296E+09 | 0.00 | 4098911.42 | 84025.06 | 0.00 | 0.195662E+10 | 0.00 | 0.77 |
July | 49884799.70 | 0.616271E+09 | 0.00 | 4390894.70 | 13879654.43 | 0.00 | 0.104432E+10 | 0.00 | 0.67 |
August | 0.187972E+09 | 0.430635E+09 | 0.00 | 5042201.10 | 13571663.91 | 0.00 | 0.173499E+10 | 0.00 | 0.81 |
September | 0.900184E+09 | 0.206334E+09 | 0.00 | 3609105.76 | 14158397.33 | 2162739.43 | 0.193946E+10 | 0.00 | 0.72 |
October | 0.209808E+10 | 1261333.12 | 0.00 | 1730377.11 | 0.00 | 0.230765E+09 | 0.152349E+10 | 0.00 | 0.55 |
November | 0.239534E+10 | 0.00 | 0.00 | 37792.55 | 0.00 | 0.202653E+10 | 54458735.08 | 0.00 | 0.38 |
December | 0.127456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517080E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.149783E+11 | 0.151539E+10 | 0.00 | 20616269.04 | 44024774.81 | 0.233115E+11 | 0.962187E+10 | 0.00 | 0.54 |
Minimum of Months | 49884799.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.239534E+10 | 0.616271E+09 | 0.00 | 5042201.10 | 14158397.33 | 0.732660E+10 | 0.195662E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.382708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737650E+10 | 0.00 | 0.00 | 0.38 |
February | 0.112536E+10 | 0.00 | 0.00 | 12686.89 | 0.00 | 0.422580E+10 | 24659484.44 | 0.00 | 0.38 |
March | 0.207295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304303E+10 | 0.00 | 0.00 | 0.39 |
April | 0.212518E+10 | 0.00 | 0.00 | 207634.21 | 0.00 | 0.104548E+10 | 0.295903E+09 | 0.00 | 0.42 |
May | 0.161863E+10 | 14591641.83 | 0.00 | 1317222.90 | 2473504.41 | 0.646245E+09 | 0.937379E+09 | 0.00 | 0.56 |
June | 0.320163E+09 | 0.245710E+09 | 0.00 | 3898295.91 | 85190.04 | 0.00 | 0.189105E+10 | 0.00 | 0.76 |
July | 52405710.27 | 0.616354E+09 | 0.00 | 4231799.68 | 13691962.65 | 0.00 | 0.102307E+10 | 0.00 | 0.66 |
August | 0.185647E+09 | 0.430885E+09 | 0.00 | 4874737.00 | 13608636.87 | 0.00 | 0.170733E+10 | 0.00 | 0.80 |
September | 0.925183E+09 | 0.205937E+09 | 0.00 | 3454294.58 | 14083585.51 | 2629673.28 | 0.186807E+10 | 0.00 | 0.71 |
October | 0.214848E+10 | 1256112.44 | 0.00 | 1588556.38 | 0.00 | 0.240384E+09 | 0.140550E+10 | 0.00 | 0.54 |
November | 0.232558E+10 | 0.00 | 0.00 | 31651.43 | 0.00 | 0.208914E+10 | 45543375.84 | 0.00 | 0.38 |
December | 0.112226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532264E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.144045E+11 | 0.151473E+10 | 0.00 | 19616878.98 | 43942879.48 | 0.239919E+11 | 0.919851E+10 | 0.00 | 0.53 |
Minimum of Months | 52405710.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.232558E+10 | 0.616354E+09 | 0.00 | 4874737.00 | 14083585.51 | 0.737650E+10 | 0.189105E+10 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.227349E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753094E+10 | 0.00 | 0.00 | 0.38 |
February | 0.824127E+09 | 0.00 | 0.00 | 4442.22 | 0.00 | 0.452232E+10 | 14313857.93 | 0.00 | 0.38 |
March | 0.169254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341540E+10 | 0.00 | 0.00 | 0.39 |
April | 0.183306E+10 | 0.00 | 0.00 | 125183.24 | 0.00 | 0.136305E+10 | 0.198762E+09 | 0.00 | 0.41 |
May | 0.155250E+10 | 14617768.21 | 0.00 | 1008238.77 | 2873423.25 | 0.793744E+09 | 0.739061E+09 | 0.00 | 0.54 |
June | 0.371005E+09 | 0.244385E+09 | 0.00 | 3332388.85 | 87861.77 | 0.00 | 0.170500E+10 | 0.00 | 0.73 |
July | 62670395.80 | 0.616490E+09 | 0.00 | 3807448.10 | 12800377.38 | 0.00 | 0.968754E+09 | 0.00 | 0.65 |
August | 0.188149E+09 | 0.431266E+09 | 0.00 | 4452818.37 | 13927579.92 | 0.00 | 0.163769E+10 | 0.00 | 0.78 |
September | 0.100063E+10 | 0.204912E+09 | 0.00 | 3091310.80 | 14313475.76 | 9958966.10 | 0.168563E+10 | 0.00 | 0.69 |
October | 0.216612E+10 | 1251315.77 | 0.00 | 1267288.59 | 0.00 | 0.325875E+09 | 0.117128E+10 | 0.00 | 0.53 |
November | 0.207412E+10 | 0.00 | 0.00 | 19868.47 | 0.00 | 0.231949E+10 | 34976581.62 | 0.00 | 0.38 |
December | 0.716889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572669E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.127091E+11 | 0.151292E+10 | 0.00 | 17108987.41 | 44002718.07 | 0.260075E+11 | 0.815547E+10 | 0.00 | 0.52 |
Minimum of Months | 62670395.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.216612E+10 | 0.616490E+09 | 0.00 | 4452818.37 | 14313475.76 | 0.753094E+10 | 0.170500E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 14586581.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773151E+10 | 0.00 | 0.00 | 0.38 |
February | 0.321556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501255E+10 | 0.00 | 0.00 | 0.38 |
March | 0.605184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447721E+10 | 0.00 | 0.00 | 0.39 |
April | 0.109869E+10 | 0.00 | 0.00 | 17307.46 | 0.00 | 0.211338E+10 | 59501068.52 | 0.00 | 0.40 |
May | 0.109748E+10 | 14755168.06 | 0.00 | 588917.38 | 3413034.09 | 0.132527E+10 | 0.466595E+09 | 0.00 | 0.50 |
June | 0.529743E+09 | 0.243404E+09 | 0.00 | 2282363.94 | 102650.46 | 44978215.35 | 0.125093E+10 | 0.00 | 0.68 |
July | 0.103469E+09 | 0.610872E+09 | 0.00 | 3138593.71 | 12860082.72 | 0.00 | 0.860832E+09 | 0.00 | 0.64 |
August | 0.219019E+09 | 0.432953E+09 | 0.00 | 3612856.06 | 13388110.18 | 0.00 | 0.148615E+10 | 0.00 | 0.76 |
September | 0.912343E+09 | 0.202195E+09 | 0.00 | 2426582.27 | 13975385.79 | 0.207709E+09 | 0.140287E+10 | 0.00 | 0.67 |
October | 0.203728E+10 | 1276667.24 | 0.00 | 802101.32 | 0.00 | 0.627959E+09 | 0.785580E+09 | 0.00 | 0.50 |
November | 0.131277E+10 | 0.00 | 0.00 | 2358.84 | 0.00 | 0.304938E+10 | 11484003.59 | 0.00 | 0.38 |
December | 77033967.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635701E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.832915E+10 | 0.150546E+10 | 0.00 | 12871080.98 | 43739263.23 | 0.309470E+11 | 0.632394E+10 | 0.00 | 0.50 |
Minimum of Months | 14586581.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.203728E+10 | 0.610872E+09 | 0.00 | 3612856.06 | 13975385.79 | 0.773151E+10 | 0.148615E+10 | 0.00 | 0.76 |