Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:19
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2020-06-03 19:19:21
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1965.78 | 940.42 | 940.42 |
Net Site Energy | 1965.78 | 940.42 | 940.42 |
Total Source Energy | 6225.64 | 2978.32 | 2978.32 |
Net Source Energy | 6225.64 | 2978.32 | 2978.32 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 830.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 587.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 110.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 250.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 57.67 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1965.78 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 830.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 587.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 110.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 250.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 57.67 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 333.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 544.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 940.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 333.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 544.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 940.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1965.784 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1965.784 | 100.00 |
Total On-Site and Utility Electric Sources | 1965.784 | 100.00 |
Total Electricity End Uses | 1965.784 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 106.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2426.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 21.0784 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 22.5208 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.3680 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.3680 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 20.3680 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 15.8795 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 15.8795 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 15.8795 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 15.8795 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 15.8795 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 18.4215 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 18.4215 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 14-JUN-14:09 | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 78717.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 36581.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 14505.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 9641.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 147535.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 78717.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 36581.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 14505.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 9641.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2631.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1859.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 351.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 793.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 182.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6225.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1258.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 889.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 379.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2978.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1258.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 889.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 168.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 379.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2978.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.19 |
SMSTORE1 DIRECT AIR | 1.14 |
SMSTORE2 DIRECT AIR | 1.14 |
SMSTORE3 DIRECT AIR | 1.14 |
SMSTORE4 DIRECT AIR | 1.14 |
LGSTORE2 DIRECT AIR | 2.07 |
SMSTORE5 DIRECT AIR | 1.09 |
SMSTORE6 DIRECT AIR | 1.08 |
SMSTORE7 DIRECT AIR | 1.08 |
SMSTORE8 DIRECT AIR | 1.17 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.19 | 2.19 | 2.19 | 2.19 | 2.19 | 2.19 | 1.00 | 1.00 | 2.19 |
PSZ-AC_2:2 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-AC_3:3 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-AC_4:4 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-AC_5:5 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-AC_6:6 | 2.07 | 2.07 | 2.07 | 2.07 | 2.07 | 2.07 | 1.00 | 1.00 | 2.07 |
PSZ-AC_7:7 | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.00 | 1.00 | 1.09 |
PSZ-AC_8:8 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.00 | 1.08 |
PSZ-AC_9:9 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.00 | 1.08 |
PSZ-AC_10:10 | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.00 | 1.00 | 1.17 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.19 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 1.14 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 1.14 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 1.14 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 1.14 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 2.07 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 1.09 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 1.08 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 1.08 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 1.17 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.19 | 2.19 | 2.19 | 2.19 | 54273.92 | 50434.19 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 1.14 | 28414.76 | 26392.66 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 1.14 | 28266.71 | 26310.74 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 1.14 | 28343.45 | 26326.64 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 1.14 | 28240.65 | 26232.10 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.07 | 2.07 | 2.07 | 2.07 | 51383.09 | 48078.98 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.09 | 1.09 | 1.09 | 1.09 | 27043.86 | 25131.15 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 1.08 | 26907.99 | 25006.16 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 1.08 | 26906.61 | 25384.68 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.17 | 1.17 | 1.17 | 1.17 | 29094.93 | 27017.99 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 2.19 | 1.09 | 2.19 | 53609.71 | 54273.92 | 27136.96 | 54273.92 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.14 | 0.572130 | 1.14 | 27973.08 | 28414.76 | 14207.38 | 28414.76 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.14 | 0.569150 | 1.14 | 27881.65 | 28266.71 | 14133.35 | 28266.71 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.14 | 0.570695 | 1.14 | 27934.96 | 28343.45 | 14171.73 | 28343.45 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.14 | 0.568625 | 1.14 | 27866.75 | 28240.65 | 14120.33 | 28240.65 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 2.07 | 1.03 | 2.07 | 51383.16 | 51383.09 | 25691.54 | 51383.09 | 0.676084 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 1.09 | 0.544530 | 1.09 | 27032.42 | 27043.86 | 13521.93 | 27043.86 | 0.676084 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 1.08 | 0.541790 | 1.08 | 26907.87 | 26907.99 | 13454.00 | 26907.99 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 1.08 | 0.541765 | 1.08 | 26906.63 | 26906.61 | 13453.31 | 26906.61 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.17 | 0.585825 | 1.17 | 28327.12 | 29094.93 | 14547.47 | 29094.93 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.19 | 2338.71 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1266.88 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1260.28 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1263.70 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1259.12 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.07 | 2214.14 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.09 | 1205.76 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.08 | 1199.70 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.08 | 1199.64 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.17 | 1297.21 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 50434.19 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 26392.66 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 26310.74 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 26326.64 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 26232.10 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 48078.98 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 25131.15 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 25006.16 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 25384.68 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 27017.99 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 21.078 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.378 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 22.521 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 26.821 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.368 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.668 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.368 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.668 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 20.368 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.668 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 15.879 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.179 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 5532.190 | 15.879 | 184.430 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5532.190 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 1811.251 | 5.199 | 60.383 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1811.251 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1156.875 | 6.641 | 77.135 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1156.875 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 781.875 | 4.489 | 52.132 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 781.875 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 5532.190 | 15.879 | 184.430 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5532.190 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 2766.095 | 15.879 | 184.431 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.095 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.4678 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.903 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.37383775E-12 | 0.81582362E-15 | -0.12542534E-12 | 0.11541335E-15 |
23 | 6 | 0.32294454E-07 | 0.13597119E-09 | 0.73677206E-08 | -0.15476624E-12 |
24 | 5 | -0.20833553E-03 | 0.11386595E-05 | -0.10688959E-03 | 0.72710034E-08 |
25 | 4 | 0.31322919 | 0.54351077E-03 | 0.10727732 | -0.36571185E-04 |
26 | 3 | -7.6832781 | 0.16549290E-01 | -2.4626776 | 0.31053958E-01 |
27 | 2 | 42.245606 | 0.57933024E-01 | 15.771342 | -0.34865193 |
28 | 1 | -81.598353 | 0.25789083E-01 | -29.595166 | 1.1010509 |
29 | 0 | 46.824332 | 0.51189598E-03 | 16.280659 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 29 | 1 | VerySmooth | 2.843 | 0.252 | 0.162 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.16139 | 0.61114 | 0.61114 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.286 | 8.224E-004 | 4.530E-004 | 0.571 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 0.164 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 8.210E-002 | 4.713E-004 | 3.194E-004 | 0.327 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.204 | 1.172E-003 | 5.440E-004 | 0.815 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 24796.79543 | 29756.15451 | 1.82134 | 2.18561 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 35.20000 | 1.71339E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 1649.42835 | 1979.31402 | 6.97893E-002 | 0.41145 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 12983.15341 | 15579.78409 | 0.95355 | 1.14426 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 34.91667 | 1.71339E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 834.19065 | 1001.02878 | 3.53727E-002 | 0.20573 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 12916.42693 | 15499.71232 | 0.94858 | 1.13830 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 34.84583 | 1.71339E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 915.94400 | 1099.13279 | 3.88289E-002 | 0.20573 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 12951.49338 | 15541.79205 | 0.95116 | 1.14139 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 34.84583 | 1.71339E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 951.86773 | 1142.24128 | 4.03206E-002 | 0.20573 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 12904.52315 | 15485.42778 | 0.94771 | 1.13725 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 34.84583 | 1.71339E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 1096.27949 | 1315.53539 | 4.63207E-002 | 0.20573 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 23481.79887 | 28178.15864 | 1.72433 | 2.06920 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 34.77500 | 1.71339E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 2072.27490 | 2486.72988 | 8.72739E-002 | 0.41145 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 12358.60801 | 14830.32962 | 0.90755 | 1.08906 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 34.77500 | 1.71339E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 1025.44723 | 1230.53668 | 4.33773E-002 | 0.20573 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 12296.51832 | 14755.82199 | 0.90299 | 1.08358 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 34.77500 | 1.71339E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 1011.97426 | 1214.36911 | 4.28156E-002 | 0.20573 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 12295.89433 | 14755.07320 | 0.90294 | 1.08353 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 34.77500 | 1.71339E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 1102.55056 | 1323.06067 | 4.65533E-002 | 0.20573 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 13295.62462 | 15954.74954 | 0.97638 | 1.17165 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 34.77500 | 1.71339E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 1027.69926 | 1233.23912 | 4.34991E-002 | 0.20573 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 34927.78 | 2.18561 | 2.18561 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 9902.82 | 0.41145 | 0.41145 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 18132.81 | 1.14426 | 1.14426 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 4951.41 | 0.20573 | 0.20573 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 18039.87 | 1.13830 | 1.13830 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 4951.41 | 0.20573 | 0.20573 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:20:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 18078.19 | 1.14139 | 1.14139 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 4951.41 | 0.20573 | 0.20573 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 18021.46 | 1.13725 | 1.13725 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 4951.41 | 0.20573 | 0.20573 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 33268.89 | 2.06920 | 2.06920 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 9902.82 | 0.41145 | 0.41145 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:10:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 17354.65 | 1.08906 | 1.08906 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 4951.41 | 0.20573 | 0.20573 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 17280.92 | 1.08358 | 1.08358 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 4951.41 | 0.20573 | 0.20573 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 17276.57 | 1.08353 | 1.08353 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 4951.41 | 0.20573 | 0.20573 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:30:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 18417.61 | 1.17165 | 1.17165 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 4951.41 | 0.20573 | 0.20573 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.18561 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14426 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.13830 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14139 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.13725 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.06920 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08906 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08358 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08353 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.17165 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.18561 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.18561 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.18561 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.18561 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.18561 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.18561 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14426 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14426 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14426 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14426 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14426 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14426 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.13830 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.13830 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.13830 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.13830 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.13830 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.13830 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14139 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14139 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14139 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14139 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14139 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14139 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.13725 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.13725 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.13725 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.13725 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.13725 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.13725 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.06920 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.06920 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.06920 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.06920 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.06920 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.06920 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.08906 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08906 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.08906 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.08906 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.08906 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.08906 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.08358 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08358 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.08358 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.08358 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.08358 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.08358 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.08353 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08353 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.08353 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.08353 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.08353 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.08353 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.17165 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.17165 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.17165 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.17165 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.17165 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.17165 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.18561 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.14426 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.13830 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.14139 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.13725 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.06920 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.08906 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.08358 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.08353 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.17165 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.18561 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.18561 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.18561 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.18561 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.18561 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.18561 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.09281 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.18561 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 53609.71048 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 54273.92000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 27136.96000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 54273.92000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 54273.92000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 50434.19196 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.18561 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2338.70662 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 50434.19196 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14426 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14426 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14426 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14426 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.14426 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14426 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57213 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.14426 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27973.07738 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28414.76000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14207.38000 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 28414.76000 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28414.76000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26392.66107 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14426 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1266.88019 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 26392.66107 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.13830 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.13830 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.13830 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.13830 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.13830 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.13830 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56915 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.13830 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27881.65278 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28266.71000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14133.35500 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 28266.71000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28266.71000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26310.74458 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.13830 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1260.27909 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 26310.74458 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14139 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14139 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14139 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14139 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.14139 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14139 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57070 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.14139 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27934.95726 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28343.45000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14171.72500 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 28343.45000 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28343.45000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26326.64121 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14139 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1263.70075 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 26326.64121 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.13725 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.13725 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.13725 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.13725 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.13725 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.13725 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56863 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.13725 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27866.75241 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28240.65000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14120.32500 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 28240.65000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28240.65000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26232.09798 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.13725 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1259.11721 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 26232.09798 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.06920 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.06920 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.06920 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.06920 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.06920 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.06920 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.03460 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.06920 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 51383.16365 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 51383.09000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 25691.54500 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 51383.09000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 51383.09000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 48078.98401 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.06920 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2214.13879 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 48078.98401 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.08906 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.08906 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.08906 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.08906 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.08906 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.08906 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54453 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.08906 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27032.42291 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 27043.86000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13521.93000 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 27043.86000 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27043.86000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25131.15010 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.08906 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1205.75809 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25131.15010 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.08358 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.08358 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.08358 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.08358 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.08358 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.08358 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54179 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.08358 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 26907.87186 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26907.99000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13453.99500 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 26907.99000 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26907.99000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25006.16271 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.08358 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1199.70016 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25006.16271 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.08353 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.08353 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.08353 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.08353 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.08353 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.08353 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54177 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.08353 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 26906.63025 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26906.61000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13453.30500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 26906.61000 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26906.61000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25384.68103 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.08353 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1199.63901 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25384.68103 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.17165 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.17165 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.17165 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.17165 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.17165 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.17165 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58583 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.17165 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 28327.12274 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 29094.93000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14547.46500 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 29094.93000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29094.93000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27017.99222 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.17165 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1297.20578 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 27017.99222 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 52549.7 | 11.23 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 27512.0 | 33.18 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 27368.7 | 44.76 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 27443.0 | 56.04 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 27343.5 | 67.65 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 49750.7 | 47.83 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 26184.7 | 103.71 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 26053.1 | 115.64 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 26051.8 | 127.05 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 28170.6 | 128.90 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 8 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 3.2618540322E-002 | 0.1783506540 | Pass | Pass | 3.2165115266E-002 | 0.1606284679 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 3.3645403704E-002 | 0.1988969643 | Pass | Pass | 0.1802054390 | 1.8324904075 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 5.2070485327E-002 | 0.2272584287 | Pass | Pass | 7.1034188435E-002 | 0.4099882961 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.2674962822E-002 | 0.2294054337 | Pass | Pass | 7.3592993063E-002 | 0.4191880377 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 5.1486432883E-002 | 0.2272036293 | Pass | Pass | 7.9120475706E-002 | 0.4342901962 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 5.0871586305E-002 | 0.2209710921 | Pass | Pass | 7.2525025314E-002 | 0.4253671355 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 5.2627009116E-002 | 0.2239184436 | Pass | Pass | 9.2421408932E-002 | 0.5163113335 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 5.1033766817E-002 | 0.2239815937 | Pass | Pass | 0.1747394044 | 1.0232209350 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.3688062032E-002 | 0.2281088130 | Pass | Pass | 0.1400750421 | 0.6602085663 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 5.6546015307E-002 | 0.2313640642 | Pass | Pass | 0.1473850354 | 0.9322489091 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.843 | 0.252 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.843 | 0.252 | 0.251 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.843 | 0.252 | 0.251 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 15.8795 | 348.39 | 5532.19 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 102.16 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 5.1990 | 348.39 | 1811.25 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 33.45 |
SMSTORE1_LIGHTS | SMSTORE1 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 51.08 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 6.6413 | 174.19 | 1156.88 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 21.36 |
SMSTORE2_LIGHTS | SMSTORE2 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 40.48 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
SMSTORE3_LIGHTS | SMSTORE3 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 40.48 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
SMSTORE4_LIGHTS | SMSTORE4 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 40.48 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 4.4886 | 174.19 | 781.88 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 11.44 |
LGSTORE2_LIGHTS | LGSTORE2 | 15.8795 | 348.39 | 5532.19 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 74.42 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.21 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.21 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.21 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 15.8795 | 174.19 | 2766.09 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 37.21 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 9.2108 | 4180.64 | 38506.89 | 587.06 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7048.38 | AstronomicalClock | - | 83.83 | 83.83 | 110.92 | |
Exterior Lighting Total | 7048.38 | 110.92 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 54273.92 | 36693.51 | 17580.41 | 0.68 | 3.73 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28414.76 | 19210.65 | 9204.11 | 0.68 | 3.80 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28266.71 | 19110.56 | 9156.15 | 0.68 | 3.80 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28343.45 | 19162.44 | 9181.01 | 0.68 | 3.80 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28240.65 | 19092.94 | 9147.71 | 0.68 | 3.80 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 51383.09 | 34739.08 | 16644.01 | 0.68 | 3.73 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 27043.86 | 18283.81 | 8760.05 | 0.68 | 3.80 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26907.99 | 18191.95 | 8716.04 | 0.68 | 3.80 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26906.61 | 18191.02 | 8715.59 | 0.68 | 3.80 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 29094.93 | 19670.50 | 9424.43 | 0.68 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 52549.7 | 11.23 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 27512.0 | 33.18 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 27368.7 | 44.76 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 27443.0 | 56.04 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 27343.5 | 67.65 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 49750.7 | 47.83 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 26184.7 | 103.71 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 26053.1 | 115.64 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 26051.8 | 127.05 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 28170.6 | 128.90 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 50434.19 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 26392.66 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 26310.74 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 26326.64 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 26232.10 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 48078.98 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25131.15 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25006.16 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25384.68 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 27017.99 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.19 | 2338.71 | 1070.05 | 1.00 | 1.30 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1266.88 | 1107.16 | 1.00 | 1.37 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1260.28 | 1107.16 | 1.00 | 1.37 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1263.70 | 1107.16 | 1.00 | 1.37 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1259.12 | 1107.16 | 1.00 | 1.37 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.07 | 2214.14 | 1070.05 | 1.00 | 1.31 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.09 | 1205.76 | 1107.16 | 1.00 | 1.38 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.08 | 1199.70 | 1107.16 | 1.00 | 1.38 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.08 | 1199.64 | 1107.16 | 1.00 | 1.38 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.17 | 1297.21 | 1107.16 | 1.00 | 1.37 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 24796.80 | 29756.15 | 85.41 | 1.821 | 2.186 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 23.89 | 23.88 | 0.01020 | 35.20 | 0.01713 | 0.411 | 0.00 |
SMSTORE1 | 12983.15 | 15579.78 | 89.44 | 0.954 | 1.144 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 23.89 | 23.88 | 0.01026 | 34.92 | 0.01713 | 0.206 | 0.00 |
SMSTORE2 | 12916.43 | 15499.71 | 88.98 | 0.949 | 1.138 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 23.89 | 23.88 | 0.01027 | 34.85 | 0.01713 | 0.206 | 0.00 |
SMSTORE3 | 12951.49 | 15541.79 | 89.22 | 0.951 | 1.141 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 23.89 | 23.88 | 0.01027 | 34.85 | 0.01713 | 0.206 | 0.00 |
SMSTORE4 | 12904.52 | 15485.43 | 88.90 | 0.948 | 1.137 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 23.89 | 23.88 | 0.01027 | 34.85 | 0.01713 | 0.206 | 0.00 |
LGSTORE2 | 23481.80 | 28178.16 | 80.88 | 1.724 | 2.069 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 23.89 | 23.88 | 0.01024 | 34.78 | 0.01713 | 0.411 | 0.00 |
SMSTORE5 | 12358.61 | 14830.33 | 85.14 | 0.908 | 1.089 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 23.89 | 23.88 | 0.01033 | 34.78 | 0.01713 | 0.206 | 0.00 |
SMSTORE6 | 12296.52 | 14755.82 | 84.71 | 0.903 | 1.084 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 23.89 | 23.88 | 0.01034 | 34.78 | 0.01713 | 0.206 | 0.00 |
SMSTORE7 | 12295.89 | 14755.07 | 84.71 | 0.903 | 1.084 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 23.89 | 23.88 | 0.01034 | 34.78 | 0.01713 | 0.206 | 0.00 |
SMSTORE8 | 13295.62 | 15954.75 | 91.59 | 0.976 | 1.172 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 23.89 | 23.88 | 0.01028 | 34.78 | 0.01713 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 1649.43 | 1979.31 | 5.68 | 0.070 | 0.411 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01264 | 20.10 | 0.01480 | 0.411 | 0.00 |
SMSTORE1 | 834.19 | 1001.03 | 5.75 | 0.035 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01232 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE2 | 915.94 | 1099.13 | 6.31 | 0.039 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.11 | 21.11 | 0.01306 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE3 | 951.87 | 1142.24 | 6.56 | 0.040 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.11 | 21.11 | 0.01302 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE4 | 1096.28 | 1315.54 | 7.55 | 0.046 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.11 | 21.11 | 0.01283 | 20.10 | 0.01480 | 0.206 | 0.00 |
LGSTORE2 | 2072.27 | 2486.73 | 7.14 | 0.087 | 0.411 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01293 | 20.10 | 0.01480 | 0.411 | 0.00 |
SMSTORE5 | 1025.45 | 1230.54 | 7.06 | 0.043 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01304 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE6 | 1011.97 | 1214.37 | 6.97 | 0.043 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01306 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE7 | 1102.55 | 1323.06 | 7.60 | 0.047 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01294 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE8 | 1027.70 | 1233.24 | 7.08 | 0.043 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01354 | 20.10 | 0.01480 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.19 | 2.19 | 0.41 | 0.41 | 2.1856 | 2.1856 | 2.1856 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.14 | 1.14 | 0.21 | 0.21 | 1.1443 | 1.1443 | 1.1443 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.14 | 1.14 | 0.21 | 0.21 | 1.1383 | 1.1383 | 1.1383 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.14 | 1.14 | 0.21 | 0.21 | 1.1414 | 1.1414 | 1.1414 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.14 | 1.14 | 0.21 | 0.21 | 1.1373 | 1.1373 | 1.1373 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.07 | 2.07 | 0.41 | 0.41 | 2.0692 | 2.0692 | 2.0692 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.09 | 1.09 | 0.21 | 0.21 | 1.0891 | 1.0891 | 1.0891 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.08 | 1.08 | 0.21 | 0.21 | 1.0836 | 1.0836 | 1.0836 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.08 | 1.08 | 0.21 | 0.21 | 1.0835 | 1.0835 | 1.0835 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.17 | 1.17 | 0.21 | 0.21 | 1.1717 | 1.1717 | 1.1717 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 54273.920 | 0.000 | 2.185610 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 54273.92 | 35683.36 | 2.185610 | 26.01 | 19.48 | 0.01150820 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01713393 | 25.80 | 18.8256 | 23.88 | 0.01020351 | 55.1393 | 24796.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 50434.192 | 50434.192 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 50434.19 | 50434.19 | 2.185611 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 18.8256 | 21.11 | 0.01263721 | 80.5083 | 880.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28414.760 | 0.000 | 1.144260 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 28414.76 | 18637.91 | 1.144260 | 25.92 | 19.45 | 0.01150949 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01713393 | 25.80 | 17.9790 | 23.88 | 0.01026436 | 55.4637 | 12964.52 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 26392.661 | 26392.661 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 26392.66 | 26392.66 | 1.144262 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 17.9790 | 21.11 | 0.01231659 | 78.5060 | 449.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 28266.710 | 0.000 | 1.138300 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 28266.71 | 18514.89 | 1.138300 | 25.93 | 19.47 | 0.01152433 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01713393 | 25.80 | 18.0732 | 23.88 | 0.01027138 | 55.5008 | 12885.86 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 26310.745 | 26310.745 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:20:00 | 26310.74 | 26310.74 | 1.138300 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 18.0731 | 21.11 | 0.01305857 | 83.1365 | 703.77 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 28343.450 | 0.000 | 1.141390 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 28343.45 | 18575.79 | 1.141390 | 25.93 | 19.46 | 0.01151823 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01713393 | 25.80 | 18.0242 | 23.88 | 0.01026755 | 55.4804 | 12918.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 26326.641 | 26326.641 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | 26326.64 | 26326.64 | 1.141391 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 18.0242 | 21.11 | 0.01301733 | 82.8793 | 608.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 28240.650 | 0.000 | 1.137250 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 28240.65 | 18492.66 | 1.137250 | 25.93 | 19.47 | 0.01152729 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01713393 | 25.80 | 18.0898 | 23.88 | 0.01027271 | 55.5079 | 12870.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 26232.098 | 26232.098 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:30:00 | 26232.10 | 26232.10 | 1.137251 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 18.0898 | 21.11 | 0.01283390 | 81.7344 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 51383.090 | 0.000 | 2.069200 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 51383.09 | 33407.03 | 2.069200 | 26.14 | 19.61 | 0.01163426 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01713393 | 25.80 | 19.8847 | 23.88 | 0.01023534 | 55.3069 | 23392.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 48078.984 | 48078.984 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:10:00 | 48078.98 | 48078.98 | 2.069197 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 19.8847 | 21.11 | 0.01293223 | 82.3478 | 1078.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 27043.860 | 0.000 | 1.089060 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 27043.86 | 17528.61 | 1.089060 | 26.01 | 19.57 | 0.01163435 | 12.80 | 12.09 | 0.00850000 | 35.13 | 0.01713393 | 25.78 | 18.8903 | 23.88 | 0.01032991 | 55.8111 | 12320.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 25131.150 | 25131.150 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 14:00:00 | 25131.15 | 25131.15 | 1.089056 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 18.8904 | 21.11 | 0.01304129 | 83.0282 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 26907.990 | 0.000 | 1.083580 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 26907.99 | 17420.30 | 1.083580 | 26.02 | 19.59 | 0.01164704 | 12.80 | 12.09 | 0.00850000 | 35.13 | 0.01713393 | 25.78 | 18.9858 | 23.88 | 0.01033692 | 55.8483 | 12258.40 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 25006.163 | 25006.163 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 25006.16 | 25006.16 | 1.083585 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 18.9858 | 21.11 | 0.01305905 | 83.1390 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 26906.610 | 0.000 | 1.083530 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 26906.61 | 17418.18 | 1.083530 | 26.02 | 19.59 | 0.01164781 | 12.80 | 12.09 | 0.00850000 | 35.13 | 0.01713393 | 25.78 | 18.9867 | 23.88 | 0.01033700 | 55.8487 | 12254.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 25384.681 | 25384.681 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:30:00 | 25384.68 | 25384.68 | 1.083529 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 18.9867 | 21.11 | 0.01294386 | 82.4203 | 605.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 29094.930 | 0.000 | 1.171650 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 29094.93 | 19094.06 | 1.171650 | 25.80 | 19.39 | 0.01147940 | 12.80 | 12.09 | 0.00850000 | 34.78 | 0.01713393 | 25.69 | 17.5587 | 23.88 | 0.01027508 | 55.5204 | 13295.62 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 27017.992 | 27017.992 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 27017.99 | 27017.99 | 1.171653 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 17.5587 | 21.11 | 0.01354257 | 86.1508 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 54273.920 | 0.000 | 2.185610 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2332 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 54273.92 | 35683.36 | 1.0000 | 2.63058923 | 2.185610 | 26.01 | 19.48 | 0.01150820 | 55477.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54273.92 | 35.20 | 0.01713393 | 25.80 | 0.41145340 | 18.8256 | 23.88 | 0.01020351 | 23.88 | 0.01020351 | 55.1393 | 24796.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 50434.192 | 50434.192 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.185611 | 2.63058990 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 50434.19 | 50434.19 | 1.0000 | 2.63058990 | 2.185611 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50434.19 | 20.10 | 0.01479830 | 20.10 | 0.41145340 | 18.8256 | 21.11 | 0.01198134 | 21.11 | 0.01263721 | 80.5083 | 880.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28414.760 | 0.000 | 1.144260 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2356 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 28414.76 | 18637.91 | 1.0000 | 1.37722559 | 1.144260 | 25.92 | 19.45 | 0.01150949 | 55384.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28414.76 | 35.20 | 0.01713393 | 25.80 | 0.20572670 | 17.9790 | 23.88 | 0.01027460 | 23.88 | 0.01026436 | 55.4637 | 12964.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26392.661 | 26392.661 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.144262 | 1.37722857 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 26392.66 | 26392.66 | 1.0000 | 1.37722857 | 1.144262 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26392.66 | 20.10 | 0.01479830 | 20.10 | 0.20572670 | 17.9790 | 21.11 | 0.01198012 | 21.11 | 0.01231659 | 78.5060 | 449.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28266.710 | 0.000 | 1.138300 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2631 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 28266.71 | 18514.89 | 1.0000 | 1.37005217 | 1.138300 | 25.93 | 19.47 | 0.01152433 | 55435.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28266.71 | 35.20 | 0.01713393 | 25.80 | 0.20572670 | 18.0732 | 23.88 | 0.01028351 | 23.88 | 0.01027138 | 55.5008 | 12885.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26310.745 | 26310.745 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.138300 | 1.37005249 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:20:00 | 26310.74 | 26310.74 | 1.0000 | 1.37005249 | 1.138300 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26310.74 | 20.10 | 0.01479830 | 20.10 | 0.20572670 | 18.0731 | 21.06 | 0.01296367 | 21.11 | 0.01305857 | 83.1365 | 703.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28343.450 | 0.000 | 1.141390 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2518 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 28343.45 | 18575.79 | 1.0000 | 1.37377128 | 1.141390 | 25.93 | 19.46 | 0.01151823 | 55414.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28343.45 | 35.20 | 0.01713393 | 25.80 | 0.20572670 | 18.0242 | 23.88 | 0.01027988 | 23.88 | 0.01026755 | 55.4804 | 12918.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26326.641 | 26326.641 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.141391 | 1.37377219 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | 26326.64 | 26326.64 | 1.0000 | 1.37377219 | 1.141391 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26326.64 | 20.10 | 0.01479830 | 20.10 | 0.20572670 | 18.0242 | 21.11 | 0.01246504 | 21.11 | 0.01301733 | 82.8793 | 608.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28240.650 | 0.000 | 1.137250 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2687 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 28240.65 | 18492.66 | 1.0000 | 1.36878839 | 1.137250 | 25.93 | 19.47 | 0.01152729 | 55445.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28240.65 | 35.20 | 0.01713393 | 25.80 | 0.20572670 | 18.0898 | 23.88 | 0.01028530 | 23.88 | 0.01027271 | 55.5079 | 12870.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26232.098 | 26232.098 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.137251 | 1.36878941 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:30:00 | 26232.10 | 26232.10 | 1.0000 | 1.36878941 | 1.137251 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26232.10 | 20.10 | 0.01479830 | 20.10 | 0.20572670 | 18.0898 | 21.11 | 0.00000000 | 21.11 | 0.01283390 | 81.7344 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 51383.090 | 0.000 | 2.069200 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.4675 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 51383.09 | 33407.03 | 1.0000 | 2.49047874 | 2.069200 | 26.14 | 19.61 | 0.01163426 | 55929.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51383.09 | 35.20 | 0.01713393 | 25.80 | 0.41145340 | 19.8847 | 23.88 | 0.01026314 | 23.88 | 0.01023534 | 55.3069 | 23392.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 48078.984 | 48078.984 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.069197 | 2.49047534 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:10:00 | 48078.98 | 48078.98 | 1.0000 | 2.49047534 | 2.069197 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48078.98 | 20.10 | 0.01479830 | 20.10 | 0.41145340 | 19.8847 | 20.96 | 0.00449986 | 21.11 | 0.01293223 | 82.3478 | 1078.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27043.860 | 0.000 | 1.089060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.4677 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 27043.86 | 17528.61 | 1.0000 | 1.31078715 | 1.089060 | 26.01 | 19.57 | 0.01163435 | 55798.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27043.86 | 35.13 | 0.01713393 | 25.78 | 0.20572670 | 18.8903 | 23.88 | 0.01034903 | 23.88 | 0.01032991 | 55.8111 | 12320.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25131.150 | 25131.150 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.089056 | 1.31078258 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 14:00:00 | 25131.15 | 25131.15 | 1.0000 | 1.31078258 | 1.089056 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25131.15 | 20.10 | 0.01479830 | 20.10 | 0.20572670 | 18.8904 | 21.11 | 0.00000000 | 21.11 | 0.01304129 | 83.0282 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26907.990 | 0.000 | 1.083580 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.4913 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 26907.99 | 17420.30 | 1.0000 | 1.30419145 | 1.083580 | 26.02 | 19.59 | 0.01164704 | 55842.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26907.99 | 35.13 | 0.01713393 | 25.78 | 0.20572670 | 18.9858 | 23.88 | 0.01035663 | 23.88 | 0.01033692 | 55.8483 | 12258.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25006.163 | 25006.163 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.083585 | 1.30419699 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 25006.16 | 25006.16 | 1.0000 | 1.30419699 | 1.083585 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25006.16 | 20.10 | 0.01479830 | 20.10 | 0.20572670 | 18.9858 | 21.11 | 0.00000000 | 21.11 | 0.01305905 | 83.1390 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26906.610 | 0.000 | 1.083530 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.4927 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 26906.61 | 17418.18 | 1.0000 | 1.30413127 | 1.083530 | 26.02 | 19.59 | 0.01164781 | 55844.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26906.61 | 35.13 | 0.01713393 | 25.78 | 0.20572670 | 18.9867 | 23.88 | 0.01035710 | 23.88 | 0.01033700 | 55.8487 | 12254.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25384.681 | 25384.681 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.083529 | 1.30413051 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:30:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:30:00 | 25384.68 | 25384.68 | 1.0000 | 1.30413051 | 1.083529 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25384.68 | 20.10 | 0.01479830 | 20.10 | 0.20572670 | 18.9867 | 20.75 | 0.00651021 | 21.11 | 0.01294386 | 82.4203 | 605.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29094.930 | 0.000 | 1.171650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1796 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 29094.93 | 19094.06 | 1.0000 | 1.41019206 | 1.171650 | 25.80 | 19.39 | 0.01147940 | 55181.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29094.93 | 34.78 | 0.01713393 | 25.69 | 0.20572670 | 17.5587 | 23.89 | 0.01027508 | 23.88 | 0.01027508 | 55.5204 | 13295.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27017.992 | 27017.992 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.171653 | 1.41019559 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 27017.99 | 27017.99 | 1.0000 | 1.41019559 | 1.171653 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27017.99 | 20.10 | 0.01479830 | 20.10 | 0.20572670 | 17.5587 | 21.11 | 0.00000000 | 21.11 | 0.01354257 | 86.1508 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 5840.00 | 1665.33 | 1665.33 |
SMSTORE1 | 5839.67 | 1436.17 | 1436.17 |
SMSTORE2 | 4395.00 | 1743.33 | 1743.33 |
SMSTORE3 | 4395.00 | 1723.83 | 1723.83 |
SMSTORE4 | 4395.00 | 1767.33 | 1767.33 |
LGSTORE2 | 4030.00 | 1797.33 | 1797.33 |
SMSTORE5 | 4030.00 | 1827.83 | 1827.83 |
SMSTORE6 | 4030.00 | 1858.67 | 1858.67 |
SMSTORE7 | 4030.00 | 1869.83 | 1869.83 |
SMSTORE8 | 4030.00 | 1625.67 | 1625.67 |
Facility | 5943.00 | 2426.83 | 2426.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 39.17 | 0.00 | 39.17 |
SMSTORE1 | 0.00 | 22.00 | 0.00 | 22.00 |
SMSTORE2 | 0.00 | 49.00 | 0.00 | 49.00 |
SMSTORE3 | 0.00 | 48.17 | 0.00 | 48.17 |
SMSTORE4 | 0.00 | 49.17 | 0.00 | 49.17 |
LGSTORE2 | 0.00 | 52.67 | 0.00 | 52.67 |
SMSTORE5 | 0.00 | 51.00 | 0.00 | 51.00 |
SMSTORE6 | 0.00 | 51.33 | 0.00 | 51.33 |
SMSTORE7 | 0.00 | 51.17 | 0.00 | 51.17 |
SMSTORE8 | 0.00 | 48.00 | 0.00 | 48.00 |
Facility | 0.00 | 106.00 | 0.00 | 106.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.02 | 30.00 | 1805.20 | 0.849 | 0.347 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.704 | 0.381 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.850 | 0.499 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.850 | 0.499 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.850 | 0.499 | 0.000 | 0.000 |
LGSTORE2 | 13.23 | 30.00 | 1805.20 | 0.850 | 0.467 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 0.850 | 0.532 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 0.850 | 0.532 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 0.850 | 0.532 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 0.850 | 0.556 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.02 | 30.00 | 1805.20 | 0.831 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.143 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.829 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.829 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.829 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.23 | 30.00 | 1805.20 | 0.833 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.61 | 15.00 | 902.60 | 0.833 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.61 | 15.00 | 902.60 | 0.833 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.61 | 15.00 | 902.60 | 0.833 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.61 | 15.00 | 902.60 | 0.833 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1965.78 | 3592.76 | 01-JAN-06:20 | 147535.24 | 14-JUN-14:10 |
Electricity:Building | 715.79 | 2374.76 | 01-JAN-00:10 | 44671.08 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 161.97 | 442.08 | 01-JAN-00:10 | 8324.52 | 01-JAN-10:10 |
InteriorLights:Electricity | 587.07 | 1925.34 | 01-JAN-00:10 | 36581.55 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 135.61 | 367.17 | 01-JAN-00:10 | 6976.27 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 587.07 | 1925.34 | 01-JAN-00:10 | 36581.55 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 85.62 | 233.60 | 01-JAN-00:10 | 4400.95 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 72.45 | 196.15 | 01-JAN-00:10 | 3726.82 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 62.39 | 214.85 | 01-JAN-00:10 | 4044.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 51.92 | 177.40 | 01-JAN-00:10 | 3370.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 62.39 | 214.85 | 01-JAN-00:10 | 4044.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 51.92 | 177.40 | 01-JAN-00:10 | 3370.57 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 62.39 | 214.85 | 01-JAN-00:10 | 4044.70 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 51.92 | 177.40 | 01-JAN-00:10 | 3370.57 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 93.68 | 351.51 | 01-JAN-00:10 | 6603.84 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 74.42 | 276.61 | 01-JAN-00:10 | 5255.58 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 46.84 | 175.76 | 01-JAN-00:10 | 3301.92 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 37.21 | 138.30 | 01-JAN-00:10 | 2627.79 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 46.84 | 175.76 | 01-JAN-00:10 | 3301.92 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 37.21 | 138.30 | 01-JAN-00:10 | 2627.79 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 46.84 | 175.76 | 01-JAN-00:10 | 3301.92 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 37.21 | 138.30 | 01-JAN-00:10 | 2627.79 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 46.84 | 175.76 | 01-JAN-00:10 | 3301.92 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 37.21 | 138.30 | 01-JAN-00:10 | 2627.79 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
Electricity:Plant | 57.67 | 1218.00 | 01-JAN-09:10 | 11776.24 | 31-JAN-13:20 |
WaterSystems:Electricity | 57.67 | 1218.00 | 01-JAN-09:10 | 11776.24 | 31-JAN-13:20 |
Water Heater:WaterSystems:Electricity | 57.67 | 1218.00 | 01-JAN-09:10 | 11776.24 | 31-JAN-13:20 |
ElectricityPurchased:Facility | 1965.78 | 3592.76 | 01-JAN-06:20 | 147535.24 | 14-JUN-14:10 |
ElectricityPurchased:Plant | 1965.78 | 3592.76 | 01-JAN-06:20 | 147535.24 | 14-JUN-14:10 |
Cogeneration:ElectricityPurchased | 1965.78 | 3592.76 | 01-JAN-06:20 | 147535.24 | 14-JUN-14:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1965.78 | 3592.76 | 01-JAN-06:20 | 147535.24 | 14-JUN-14:10 |
ElectricityNet:Plant | 1965.78 | 3592.76 | 01-JAN-06:20 | 147535.24 | 14-JUN-14:10 |
Cogeneration:ElectricityNet | 1965.78 | 3592.76 | 01-JAN-06:20 | 147535.24 | 14-JUN-14:10 |
Electricity:HVAC | 1081.40 | 0.00 | 01-JAN-00:10 | 98630.56 | 16-JUN-13:00 |
Fans:Electricity | 250.43 | 0.00 | 01-JAN-00:10 | 14505.13 | 01-JAN-09:10 |
General:Fans:Electricity | 250.43 | 0.00 | 01-JAN-00:10 | 14505.13 | 01-JAN-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 830.97 | 0.00 | 01-JAN-00:10 | 84125.44 | 16-JUN-13:00 |
ExteriorLights:Electricity | 110.92 | 0.00 | 01-JAN-06:20 | 7048.38 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 110.92 | 0.00 | 01-JAN-06:20 | 7048.38 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Gas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 4449.83 | 0.00 | 01-JAN-00:10 | 444136.16 | 16-JUN-13:00 |
EnergyTransfer:Building | 1272.17 | 0.00 | 01-JAN-00:10 | 127856.87 | 06-MAY-13:00 |
EnergyTransfer:Zone:LGSTORE1 | 257.79 | 0.00 | 01-JAN-00:10 | 21302.39 | 06-MAY-13:00 |
Heating:EnergyTransfer | 11.64 | 0.00 | 01-JAN-00:10 | 25095.23 | 29-MAY-16:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.53 | 0.00 | 01-JAN-00:10 | 2247.61 | 04-MAR-08:10 |
Cooling:EnergyTransfer | 1260.53 | 0.00 | 01-JAN-00:10 | 127856.87 | 06-MAY-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 257.26 | 0.00 | 01-JAN-00:10 | 21302.39 | 06-MAY-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 133.66 | 0.00 | 01-JAN-00:10 | 11070.28 | 06-MAY-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.28 | 0.00 | 01-JAN-00:10 | 1188.53 | 22-SEP-08:00 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 133.38 | 0.00 | 01-JAN-00:10 | 11070.28 | 06-MAY-13:00 |
EnergyTransfer:Zone:SMSTORE2 | 104.98 | 0.00 | 01-JAN-00:10 | 11037.38 | 06-MAY-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.74 | 0.00 | 01-JAN-00:10 | 2801.93 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 103.23 | 0.00 | 01-JAN-00:10 | 11037.38 | 06-MAY-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 105.54 | 0.00 | 01-JAN-00:10 | 11066.32 | 06-MAY-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.71 | 0.00 | 01-JAN-00:10 | 2798.26 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 103.83 | 0.00 | 01-JAN-00:10 | 11066.32 | 06-MAY-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 104.35 | 0.00 | 01-JAN-00:10 | 10970.93 | 06-MAY-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.81 | 0.00 | 01-JAN-00:10 | 2800.90 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 102.54 | 0.00 | 01-JAN-00:10 | 10970.93 | 06-MAY-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 180.49 | 0.00 | 01-JAN-00:10 | 19661.44 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.62 | 0.00 | 01-JAN-00:10 | 5508.30 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 178.87 | 0.00 | 01-JAN-00:10 | 19661.44 | 06-MAY-13:10 |
EnergyTransfer:Zone:SMSTORE5 | 94.53 | 0.00 | 01-JAN-00:10 | 10418.48 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.96 | 0.00 | 01-JAN-00:10 | 2802.78 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 93.57 | 0.00 | 01-JAN-00:10 | 10418.48 | 06-MAY-13:10 |
EnergyTransfer:Zone:SMSTORE6 | 93.83 | 0.00 | 01-JAN-00:10 | 10363.27 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.99 | 0.00 | 01-JAN-00:10 | 2803.79 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 92.84 | 0.00 | 01-JAN-00:10 | 10363.27 | 06-MAY-13:10 |
EnergyTransfer:Zone:SMSTORE7 | 93.65 | 0.00 | 01-JAN-00:10 | 10394.06 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 1.03 | 0.00 | 01-JAN-00:10 | 2803.72 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 92.62 | 0.00 | 01-JAN-00:10 | 10394.06 | 06-MAY-13:10 |
EnergyTransfer:Zone:SMSTORE8 | 103.35 | 0.00 | 01-JAN-00:10 | 11616.55 | 06-MAY-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.96 | 0.00 | 01-JAN-00:10 | 2775.55 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 102.39 | 0.00 | 01-JAN-00:10 | 11616.55 | 06-MAY-13:00 |
EnergyTransfer:HVAC | 3177.66 | 0.00 | 01-JAN-00:10 | 322450.94 | 16-JUN-13:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 3177.66 | 0.00 | 01-JAN-00:10 | 322450.94 | 16-JUN-13:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.533 | -257.249 | 0.000 | 0.000 | 12.365 | 135.611 | 26.357 | 15.448 | 0.000 | 29.040 | 39.614 | 0.000 | -1.221 | 0.000 | -0.498 | -0.001 |
SMSTORE1 | 0.000 | 0.000 | 0.284 | -133.372 | 0.000 | 0.000 | 6.182 | 72.445 | 13.179 | 7.766 | 0.000 | 16.045 | 18.228 | 0.000 | -0.597 | 0.000 | -0.160 | -0.001 |
SMSTORE2 | 0.000 | 0.000 | 1.744 | -103.229 | 0.000 | 0.000 | 3.712 | 51.921 | 10.467 | 7.649 | 0.000 | 15.794 | 12.995 | 0.000 | -0.806 | 0.000 | -0.248 | -0.000 |
SMSTORE3 | 0.000 | 0.000 | 1.714 | -103.826 | 0.000 | 0.000 | 3.712 | 51.921 | 10.467 | 7.641 | 0.000 | 15.786 | 13.669 | 0.000 | -0.827 | 0.000 | -0.258 | -0.001 |
SMSTORE4 | 0.000 | 0.000 | 1.811 | -102.535 | 0.000 | 0.000 | 3.712 | 51.921 | 10.467 | 7.649 | 0.000 | 15.794 | 12.228 | 0.000 | -0.805 | 0.000 | -0.243 | -0.002 |
LGSTORE2 | 0.000 | 0.000 | 1.621 | -178.863 | 0.000 | 0.000 | 12.747 | 74.416 | 19.261 | 15.242 | 0.000 | 27.633 | 29.883 | 0.000 | -1.465 | 0.000 | -0.476 | -0.002 |
SMSTORE5 | 0.000 | 0.000 | 0.959 | -93.566 | 0.000 | 0.000 | 6.374 | 37.208 | 9.631 | 7.652 | 0.000 | 15.730 | 16.938 | 0.000 | -0.694 | 0.000 | -0.232 | -0.001 |
SMSTORE6 | 0.000 | 0.000 | 0.988 | -92.835 | 0.000 | 0.000 | 6.374 | 37.208 | 9.631 | 7.660 | 0.000 | 15.734 | 16.153 | 0.000 | -0.685 | 0.000 | -0.228 | -0.001 |
SMSTORE7 | 0.000 | 0.000 | 1.030 | -92.615 | 0.000 | 0.000 | 6.374 | 37.208 | 9.631 | 7.658 | 0.000 | 15.737 | 15.879 | 0.000 | -0.683 | 0.000 | -0.220 | -0.002 |
SMSTORE8 | 0.000 | 0.000 | 0.958 | -102.386 | 0.000 | 0.000 | 6.373 | 37.208 | 9.631 | 7.587 | 0.000 | 16.508 | 25.321 | 0.000 | -0.714 | 0.000 | -0.485 | -0.000 |
Total Facility | 0.000 | 0.000 | 11.644 | -1260.474 | 0.000 | 0.000 | 67.926 | 587.066 | 128.721 | 91.954 | 0.000 | 183.802 | 200.907 | 0.000 | -8.497 | 0.000 | -3.048 | -0.012 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 24-FEB-09:01 | 0.00 | 0.00 | 0.00 | -36088.15 | 0.00 | 0.00 | 84.36 | 3671.72 | 749.03 | 1292.73 | 0.00 | 0.00 | 30328.53 | 0.00 | -0.00 | 0.00 | -38.22 | 0.00 |
SMSTORE1 | 24-FEB-09:01 | 0.00 | 0.00 | 0.00 | -20027.27 | 0.00 | 0.00 | 42.18 | 1961.49 | 374.52 | 645.90 | 0.00 | 0.00 | 17020.55 | 0.00 | -0.00 | 0.00 | -17.36 | 0.00 |
SMSTORE2 | 24-FEB-08:61 | 0.00 | 0.00 | 0.00 | -17852.05 | 0.00 | 0.00 | 42.42 | 1773.99 | 374.52 | 383.25 | 0.00 | 0.00 | 15380.20 | 0.00 | -0.00 | 0.00 | -102.32 | 0.00 |
SMSTORE3 | 24-FEB-08:61 | 0.00 | 0.00 | 0.00 | -17931.53 | 0.00 | 0.00 | 42.29 | 1773.99 | 374.52 | 382.14 | 0.00 | 0.00 | 15462.21 | 0.00 | -0.00 | 0.00 | -103.60 | 0.00 |
SMSTORE4 | 25-FEB-08:61 | 0.00 | 0.00 | 0.00 | -17780.61 | 0.00 | 0.00 | 42.17 | 1773.99 | 374.52 | 387.62 | 0.00 | 30.13 | 15172.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 25-FEB-09:01 | 0.00 | 0.00 | 0.00 | -33783.27 | 0.00 | 0.00 | 185.53 | 2766.09 | 749.03 | 972.84 | 0.00 | 0.00 | 29174.34 | 0.00 | -0.00 | 0.00 | -64.57 | 0.00 |
SMSTORE5 | 25-FEB-09:01 | 0.00 | 0.00 | 0.00 | -17721.25 | 0.00 | 0.00 | 92.77 | 1383.05 | 374.52 | 486.83 | 0.00 | 0.00 | 15419.13 | 0.00 | -0.00 | 0.00 | -35.04 | 0.00 |
SMSTORE6 | 25-FEB-09:01 | 0.00 | 0.00 | 0.00 | -17617.86 | 0.00 | 0.00 | 92.77 | 1383.05 | 374.52 | 487.33 | 0.00 | 0.00 | 15315.38 | 0.00 | -0.00 | 0.00 | -35.18 | 0.00 |
SMSTORE7 | 25-FEB-09:01 | 0.00 | 0.00 | 0.00 | -17598.31 | 0.00 | 0.00 | 92.77 | 1383.05 | 374.52 | 487.35 | 0.00 | 0.00 | 15295.78 | 0.00 | -0.00 | 0.00 | -35.15 | 0.00 |
SMSTORE8 | 24-FEB-09:01 | 0.00 | 0.00 | 0.00 | -18524.80 | 0.00 | 0.00 | 92.81 | 1383.05 | 374.52 | 640.49 | 0.00 | 0.00 | 16055.99 | 0.00 | -0.00 | 0.00 | -22.04 | 0.00 |
Total Facility | 24-FEB-09:01 | 0.00 | 0.00 | 0.00 | -176619.59 | 0.00 | 0.00 | 998.74 | 24043.21 | 5393.02 | 7824.46 | 0.00 | 204.00 | 138334.04 | 0.00 | 0.00 | 0.00 | -177.88 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 29-MAR-08:06 | 0.00 | 0.00 | 5541.50 | 0.00 | 0.00 | 0.00 | 84.33 | 3671.72 | 749.03 | 634.38 | 0.00 | 496.44 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -11177.40 |
SMSTORE1 | 04-MAR-09:05 | 0.00 | 0.00 | 3000.08 | 0.00 | 0.00 | 0.00 | 42.17 | 1961.49 | 374.52 | 459.59 | 0.00 | 265.54 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6103.37 |
SMSTORE2 | 29-MAY-16:01 | 0.00 | 0.00 | 3312.53 | 0.00 | 0.00 | 0.00 | 52.55 | 1773.99 | 374.52 | 397.73 | 0.00 | 2605.09 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8516.40 |
SMSTORE3 | 29-MAY-16:01 | 0.00 | 0.00 | 3310.71 | 0.00 | 0.00 | 0.00 | 52.55 | 1773.99 | 374.52 | 397.30 | 0.00 | 2604.47 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8513.53 |
SMSTORE4 | 29-MAY-16:01 | 0.00 | 0.00 | 3311.30 | 0.00 | 0.00 | 0.00 | 52.55 | 1773.99 | 374.52 | 397.33 | 0.00 | 2604.96 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8514.65 |
LGSTORE2 | 29-MAY-16:01 | 0.00 | 0.00 | 6521.68 | 0.00 | 0.00 | 0.00 | 231.21 | 2766.09 | 749.03 | 790.44 | 0.00 | 4576.16 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -15634.61 |
SMSTORE5 | 29-MAY-16:01 | 0.00 | 0.00 | 3302.78 | 0.00 | 0.00 | 0.00 | 115.61 | 1383.05 | 374.52 | 398.36 | 0.00 | 2608.14 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8182.45 |
SMSTORE6 | 29-MAY-16:01 | 0.00 | 0.00 | 3302.26 | 0.00 | 0.00 | 0.00 | 115.61 | 1383.05 | 374.52 | 398.67 | 0.00 | 2608.60 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8182.69 |
SMSTORE7 | 29-MAY-16:01 | 0.00 | 0.00 | 3301.89 | 0.00 | 0.00 | 0.00 | 115.61 | 1383.05 | 374.52 | 398.33 | 0.00 | 2608.53 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8181.93 |
SMSTORE8 | 29-MAY-16:01 | 0.00 | 0.00 | 3301.74 | 0.00 | 0.00 | 0.00 | 115.61 | 1383.05 | 374.52 | 393.14 | 0.00 | 2626.80 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8194.85 |
Total Facility | 29-MAY-16:01 | -28121.37 | 28121.37 | 29664.89 | -28121.37 | 0.00 | 0.00 | 2743.01 | 24323.33 | 5393.02 | 4791.89 | 0.00 | 30376.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -69170.79 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.1856 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.1856 | 0.1883 | 1.0000 | 0.4115 | 0.1883 | ||
PSZ-AC_2:2 | 1.1443 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1443 | 0.1798 | 1.0000 | 0.2057 | 0.1798 | ||
PSZ-AC_3:3 | 1.1383 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1383 | 0.1807 | 1.0000 | 0.2057 | 0.1807 | ||
PSZ-AC_4:4 | 1.1414 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1414 | 0.1802 | 1.0000 | 0.2057 | 0.1802 | ||
PSZ-AC_5:5 | 1.1373 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1373 | 0.1809 | 1.0000 | 0.2057 | 0.1809 | ||
PSZ-AC_6:6 | 2.0692 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.0692 | 0.1988 | 1.0000 | 0.4115 | 0.1988 | ||
PSZ-AC_7:7 | 1.0891 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0891 | 0.1889 | 1.0000 | 0.2057 | 0.1889 | ||
PSZ-AC_8:8 | 1.0836 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0836 | 0.1899 | 1.0000 | 0.2057 | 0.1899 | ||
PSZ-AC_9:9 | 1.0835 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0835 | 0.1899 | 1.0000 | 0.2057 | 0.1899 | ||
PSZ-AC_10:10 | 1.1717 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1717 | 0.1756 | 1.0000 | 0.2057 | 0.1756 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.1856 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.1856 | 1.0000 | 1.0000 | 0.4115 | 0.1883 | ||
PSZ-AC_2:2 | 1.1443 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1443 | 1.0000 | 1.0000 | 0.2057 | 0.1798 | ||
PSZ-AC_3:3 | 1.1383 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1383 | 1.0000 | 1.0000 | 0.2057 | 0.1807 | ||
PSZ-AC_4:4 | 1.1414 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1414 | 1.0000 | 1.0000 | 0.2057 | 0.1802 | ||
PSZ-AC_5:5 | 1.1373 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1373 | 1.0000 | 1.0000 | 0.2057 | 0.1809 | ||
PSZ-AC_6:6 | 2.0692 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 2.0692 | 1.0000 | 1.0000 | 0.4115 | 0.1988 | ||
PSZ-AC_7:7 | 1.0891 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0891 | 1.0000 | 1.0000 | 0.2057 | 0.1889 | ||
PSZ-AC_8:8 | 1.0836 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0836 | 1.0000 | 1.0000 | 0.2057 | 0.1899 | ||
PSZ-AC_9:9 | 1.0835 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0835 | 1.0000 | 1.0000 | 0.2057 | 0.1899 | ||
PSZ-AC_10:10 | 1.1717 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.1717 | 1.0000 | 1.0000 | 0.2057 | 0.1756 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.1856 | 2.1856 | 2.1856 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.1443 | 1.1443 | 1.1443 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.1383 | 1.1383 | 1.1383 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.1414 | 1.1414 | 1.1414 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.1373 | 1.1373 | 1.1373 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.0692 | 2.0692 | 2.0692 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.0891 | 1.0891 | 1.0891 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.0836 | 1.0836 | 1.0836 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.0835 | 1.0835 | 1.0835 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.1717 | 1.1717 | 1.1717 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.1856 | 2.1856 | 2.1856 | 2.1856 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1443 | 1.1443 | 1.1443 | 1.1443 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1383 | 1.1383 | 1.1383 | 1.1383 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1414 | 1.1414 | 1.1414 | 1.1414 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1373 | 1.1373 | 1.1373 | 1.1373 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.0692 | 2.0692 | 2.0692 | 2.0692 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0891 | 1.0891 | 1.0891 | 1.0891 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0836 | 1.0836 | 1.0836 | 1.0836 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0835 | 1.0835 | 1.0835 | 1.0835 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.1717 | 1.1717 | 1.1717 | 1.1717 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 2.1856 | 2.1856 | 2.1856 | 0.4115 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.1443 | 1.1443 | 1.1443 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.1383 | 1.1383 | 1.1383 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.1414 | 1.1414 | 1.1414 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.1373 | 1.1373 | 1.1373 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 2.0692 | 2.0692 | 2.0692 | 0.4115 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 1.0891 | 1.0891 | 1.0891 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 1.0836 | 1.0836 | 1.0836 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 1.0835 | 1.0835 | 1.0835 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.1717 | 1.1717 | 1.1717 | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.1856 | 2.1856 | 2.1856 | 2.1856 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1443 | 1.1443 | 1.1443 | 1.1443 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1383 | 1.1383 | 1.1383 | 1.1383 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1414 | 1.1414 | 1.1414 | 1.1414 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1373 | 1.1373 | 1.1373 | 1.1373 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.0692 | 2.0692 | 2.0692 | 2.0692 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0891 | 1.0891 | 1.0891 | 1.0891 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0836 | 1.0836 | 1.0836 | 1.0836 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0835 | 1.0835 | 1.0835 | 1.0835 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.1717 | 1.1717 | 1.1717 | 1.1717 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:21
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 2090.32 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 106.00 |
Number of hours not met | 106.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 830.97 | 84125.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 587.07 | 36581.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 110.92 | 7048.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 250.43 | 14505.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 57.67 | 11776.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1965.78 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1965.78 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 280.85 |
Space Heating | 0.00 |
Space Cooling | 397.53 |
Fans (All) | 119.81 |
Service Water Heating | 27.59 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 940.42 |
Subtotal | 940.42 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 29.86 |
Space Heating | 0.00 |
Space Cooling | 42.27 |
Fans (All) | 12.74 |
Service Water Heating | 2.93 |
Receptacle Equipment | 6.55 |
Miscellaneous | 5.64 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5131. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Meter
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Meter
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Meter
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213785E+11 | 34718.56 | 23-JAN-09:01 | 24.37 | 19.54 | 0.753053E+09 | 898.96 | 15-JAN-17:30 | 29.85 | 21.39 |
February | 0.201177E+11 | 36096.24 | 24-FEB-09:01 | 25.53 | 19.48 | 0.679869E+09 | 898.95 | 26-FEB-17:30 | 29.90 | 23.54 |
March | 0.225944E+11 | 33659.00 | 04-MAR-09:01 | 29.40 | 20.97 | 0.746478E+09 | 898.94 | 19-MAR-16:30 | 33.35 | 24.64 |
April | 0.222902E+11 | 27984.70 | 23-APR-07:02 | 25.42 | 24.10 | 0.727709E+09 | 898.94 | 23-APR-16:30 | 32.60 | 24.72 |
May | 0.229271E+11 | 25459.85 | 14-MAY-07:01 | 27.50 | 26.58 | 0.748890E+09 | 898.93 | 28-MAY-16:19 | 28.07 | 26.23 |
June | 0.227662E+11 | 28337.12 | 25-JUN-07:01 | 25.75 | 24.65 | 0.723447E+09 | 898.92 | 04-JUN-16:30 | 32.10 | 27.83 |
July | 0.216293E+11 | 32521.69 | 09-JUL-07:01 | 26.50 | 23.81 | 0.754959E+09 | 898.94 | 09-JUL-16:30 | 30.65 | 23.82 |
August | 0.211711E+11 | 27238.99 | 27-AUG-07:01 | 26.67 | 25.88 | 0.744635E+09 | 898.94 | 20-AUG-16:30 | 26.00 | 24.82 |
September | 0.208998E+11 | 29296.50 | 10-SEP-07:02 | 26.50 | 25.49 | 0.729503E+09 | 898.92 | 04-SEP-16:30 | 32.50 | 26.80 |
October | 0.204336E+11 | 29239.65 | 08-OCT-07:02 | 25.75 | 24.25 | 0.753108E+09 | 898.94 | 22-OCT-16:19 | 25.17 | 24.36 |
November | 0.200929E+11 | 33107.61 | 25-NOV-09:01 | 23.67 | 20.23 | 0.728317E+09 | 898.95 | 26-NOV-17:30 | 24.25 | 22.67 |
December | 0.209564E+11 | 33845.93 | 27-DEC-09:01 | 26.40 | 20.68 | 0.756726E+09 | 898.95 | 25-DEC-17:30 | 28.00 | 24.45 |
Annual Sum or Average | 0.257257E+12 | 0.884669E+10 | ||||||||
Minimum of Months | 0.200929E+11 | 25459.85 | 23.67 | 19.48 | 0.679869E+09 | 898.92 | 24.25 | 21.39 | ||
Maximum of Months | 0.229271E+11 | 36096.24 | 29.40 | 26.58 | 0.756726E+09 | 898.96 | 33.35 | 27.83 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111508E+11 | 19911.98 | 16-JAN-08:62 | 22.05 | 20.00 | 0.376533E+09 | 449.48 | 15-JAN-17:30 | 29.85 | 21.39 |
February | 0.104402E+11 | 20030.88 | 24-FEB-09:01 | 25.53 | 19.48 | 0.339935E+09 | 449.47 | 26-FEB-17:30 | 29.90 | 23.54 |
March | 0.116636E+11 | 18469.68 | 03-MAR-09:01 | 27.33 | 20.99 | 0.373235E+09 | 449.47 | 19-MAR-16:30 | 33.35 | 24.64 |
April | 0.115005E+11 | 17579.28 | 23-APR-07:02 | 25.42 | 24.10 | 0.363845E+09 | 449.47 | 23-APR-16:30 | 32.60 | 24.72 |
May | 0.118660E+11 | 16475.30 | 14-MAY-07:01 | 27.50 | 26.58 | 0.374433E+09 | 449.46 | 28-MAY-16:19 | 28.07 | 26.23 |
June | 0.117257E+11 | 18057.79 | 25-JUN-07:01 | 25.75 | 24.65 | 0.361710E+09 | 449.46 | 04-JUN-16:30 | 32.10 | 27.83 |
July | 0.111785E+11 | 19613.51 | 16-JUL-07:01 | 24.92 | 23.77 | 0.377470E+09 | 449.47 | 09-JUL-16:30 | 30.65 | 23.82 |
August | 0.109554E+11 | 17111.98 | 20-AUG-07:02 | 24.33 | 23.26 | 0.372307E+09 | 449.46 | 27-AUG-16:30 | 32.50 | 26.16 |
September | 0.108120E+11 | 18157.41 | 10-SEP-07:02 | 26.50 | 25.49 | 0.364740E+09 | 449.46 | 10-SEP-16:30 | 28.00 | 25.78 |
October | 0.106775E+11 | 18221.52 | 08-OCT-07:02 | 25.75 | 24.25 | 0.376547E+09 | 449.47 | 22-OCT-16:19 | 25.17 | 24.36 |
November | 0.104709E+11 | 18476.73 | 25-NOV-09:01 | 23.67 | 20.23 | 0.364151E+09 | 449.47 | 26-NOV-17:30 | 24.25 | 22.67 |
December | 0.109366E+11 | 18892.66 | 27-DEC-09:01 | 26.40 | 20.68 | 0.378364E+09 | 449.47 | 25-DEC-17:30 | 28.00 | 24.45 |
Annual Sum or Average | 0.133378E+12 | 0.442327E+10 | ||||||||
Minimum of Months | 0.104402E+11 | 16475.30 | 22.05 | 19.48 | 0.339935E+09 | 449.46 | 24.25 | 21.39 | ||
Maximum of Months | 0.118660E+11 | 20030.88 | 27.50 | 26.58 | 0.378364E+09 | 449.48 | 33.35 | 27.83 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.860786E+10 | 17351.23 | 24-JAN-08:62 | 19.83 | 17.92 | 0.224727E+09 | 449.40 | 21-JAN-13:09 | 31.15 | 22.93 |
February | 0.811692E+10 | 17858.15 | 24-FEB-08:61 | 23.33 | 18.56 | 0.204165E+09 | 449.42 | 25-FEB-13:09 | 31.70 | 22.30 |
March | 0.920248E+10 | 16946.31 | 04-MAR-08:61 | 26.50 | 20.57 | 0.230731E+09 | 449.42 | 04-MAR-13:09 | 33.25 | 22.11 |
April | 0.892703E+10 | 13614.03 | 27-APR-07:01 | 27.08 | 24.31 | 0.219690E+09 | 449.35 | 22-APR-12:09 | 32.68 | 25.44 |
May | 0.930064E+10 | 12200.37 | 09-MAY-07:01 | 24.50 | 24.40 | 0.227799E+09 | 449.33 | 06-MAY-12:09 | 37.10 | 26.02 |
June | 0.925783E+10 | 12567.24 | 27-JUN-07:01 | 25.75 | 24.54 | 0.222916E+09 | 449.30 | 03-JUN-12:00 | 27.40 | 26.46 |
July | 0.847419E+10 | 14299.85 | 06-JUL-07:01 | 25.92 | 23.26 | 0.224512E+09 | 449.38 | 22-JUL-12:09 | 30.43 | 24.41 |
August | 0.854492E+10 | 12809.15 | 30-AUG-07:01 | 25.50 | 24.07 | 0.230650E+09 | 449.36 | 19-AUG-12:09 | 29.12 | 25.92 |
September | 0.827129E+10 | 12652.25 | 16-SEP-07:01 | 24.75 | 24.21 | 0.219582E+09 | 449.39 | 16-SEP-12:00 | 24.40 | 24.15 |
October | 0.813394E+10 | 12837.70 | 27-OCT-07:01 | 24.92 | 23.62 | 0.224702E+09 | 449.35 | 21-OCT-12:09 | 30.90 | 25.77 |
November | 0.805646E+10 | 16729.71 | 25-NOV-08:61 | 22.25 | 19.44 | 0.217075E+09 | 449.43 | 25-NOV-13:09 | 26.53 | 21.45 |
December | 0.834041E+10 | 17045.14 | 21-DEC-08:62 | 21.33 | 19.10 | 0.224403E+09 | 449.39 | 16-DEC-13:09 | 29.25 | 24.38 |
Annual Sum or Average | 0.103234E+12 | 0.267095E+10 | ||||||||
Minimum of Months | 0.805646E+10 | 12200.37 | 19.83 | 17.92 | 0.204165E+09 | 449.30 | 24.40 | 21.45 | ||
Maximum of Months | 0.930064E+10 | 17858.15 | 27.08 | 24.54 | 0.230731E+09 | 449.43 | 37.10 | 26.46 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.864972E+10 | 17430.58 | 24-JAN-08:62 | 19.83 | 17.92 | 0.224729E+09 | 449.40 | 21-JAN-13:09 | 31.15 | 22.93 |
February | 0.816011E+10 | 17937.65 | 24-FEB-08:61 | 23.33 | 18.56 | 0.204167E+09 | 449.42 | 25-FEB-13:09 | 31.70 | 22.30 |
March | 0.924208E+10 | 17003.85 | 04-MAR-08:61 | 26.50 | 20.57 | 0.230730E+09 | 449.42 | 04-MAR-13:09 | 33.25 | 22.11 |
April | 0.898835E+10 | 13678.73 | 27-APR-07:01 | 27.08 | 24.31 | 0.219693E+09 | 449.35 | 22-APR-12:09 | 32.68 | 25.44 |
May | 0.937488E+10 | 12318.63 | 09-MAY-07:01 | 24.50 | 24.40 | 0.227802E+09 | 449.33 | 06-MAY-12:09 | 37.10 | 26.02 |
June | 0.932420E+10 | 12644.19 | 27-JUN-07:01 | 25.75 | 24.54 | 0.222918E+09 | 449.30 | 03-JUN-12:00 | 27.40 | 26.46 |
July | 0.853697E+10 | 14390.60 | 06-JUL-07:01 | 25.92 | 23.26 | 0.224515E+09 | 449.38 | 22-JUL-12:09 | 30.43 | 24.41 |
August | 0.858779E+10 | 12883.02 | 30-AUG-07:01 | 25.50 | 24.07 | 0.230651E+09 | 449.36 | 19-AUG-12:09 | 29.12 | 25.92 |
September | 0.832180E+10 | 12785.92 | 13-SEP-07:01 | 26.50 | 25.09 | 0.219585E+09 | 449.39 | 16-SEP-12:00 | 24.40 | 24.15 |
October | 0.817835E+10 | 12887.70 | 27-OCT-07:01 | 24.92 | 23.62 | 0.224704E+09 | 449.35 | 21-OCT-12:09 | 30.90 | 25.77 |
November | 0.809399E+10 | 16804.60 | 25-NOV-08:61 | 22.25 | 19.44 | 0.217076E+09 | 449.43 | 25-NOV-13:09 | 26.53 | 21.45 |
December | 0.837252E+10 | 17102.22 | 27-DEC-08:61 | 23.50 | 19.74 | 0.224405E+09 | 449.39 | 16-DEC-13:09 | 29.25 | 24.38 |
Annual Sum or Average | 0.103831E+12 | 0.267097E+10 | ||||||||
Minimum of Months | 0.809399E+10 | 12318.63 | 19.83 | 17.92 | 0.204167E+09 | 449.30 | 24.40 | 21.45 | ||
Maximum of Months | 0.937488E+10 | 17937.65 | 27.08 | 25.09 | 0.230730E+09 | 449.43 | 37.10 | 26.46 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.854124E+10 | 17298.88 | 24-JAN-08:62 | 19.83 | 17.92 | 0.224714E+09 | 449.40 | 21-JAN-13:09 | 31.15 | 22.93 |
February | 0.806165E+10 | 17786.30 | 24-FEB-08:61 | 23.33 | 18.56 | 0.204155E+09 | 449.42 | 25-FEB-13:09 | 31.70 | 22.30 |
March | 0.913224E+10 | 16889.15 | 04-MAR-08:61 | 26.50 | 20.57 | 0.230718E+09 | 449.42 | 04-MAR-13:09 | 33.25 | 22.11 |
April | 0.887961E+10 | 13553.50 | 27-APR-07:01 | 27.08 | 24.31 | 0.219681E+09 | 449.35 | 22-APR-12:09 | 32.68 | 25.44 |
May | 0.927221E+10 | 12197.05 | 09-MAY-07:01 | 24.50 | 24.40 | 0.227790E+09 | 449.33 | 06-MAY-12:09 | 37.10 | 26.02 |
June | 0.921687E+10 | 12527.77 | 27-JUN-07:01 | 25.75 | 24.54 | 0.222906E+09 | 449.31 | 03-JUN-12:00 | 27.40 | 26.46 |
July | 0.843322E+10 | 14268.45 | 06-JUL-07:01 | 25.92 | 23.26 | 0.224503E+09 | 449.38 | 22-JUL-12:09 | 30.43 | 24.41 |
August | 0.847467E+10 | 12750.97 | 30-AUG-07:01 | 25.50 | 24.07 | 0.230638E+09 | 449.37 | 19-AUG-12:09 | 29.12 | 25.92 |
September | 0.821621E+10 | 12577.69 | 13-SEP-07:01 | 26.50 | 25.09 | 0.219573E+09 | 449.40 | 16-SEP-12:00 | 24.40 | 24.15 |
October | 0.807030E+10 | 12745.09 | 27-OCT-07:01 | 24.92 | 23.62 | 0.224692E+09 | 449.35 | 21-OCT-12:09 | 30.90 | 25.77 |
November | 0.798387E+10 | 16659.23 | 25-NOV-08:61 | 22.25 | 19.44 | 0.217063E+09 | 449.43 | 25-NOV-13:09 | 26.53 | 21.45 |
December | 0.825817E+10 | 16968.78 | 27-DEC-08:61 | 23.50 | 19.74 | 0.224390E+09 | 449.39 | 16-DEC-13:09 | 29.25 | 24.38 |
Annual Sum or Average | 0.102540E+12 | 0.267082E+10 | ||||||||
Minimum of Months | 0.798387E+10 | 12197.05 | 19.83 | 17.92 | 0.204155E+09 | 449.31 | 24.40 | 21.45 | ||
Maximum of Months | 0.927221E+10 | 17786.30 | 27.08 | 25.09 | 0.230718E+09 | 449.43 | 37.10 | 26.46 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149117E+11 | 32435.08 | 24-JAN-09:02 | 19.07 | 17.34 | 0.766566E+09 | 1198.51 | 28-JAN-15:20 | 32.03 | 21.32 |
February | 0.140827E+11 | 33790.78 | 25-FEB-09:01 | 25.22 | 19.83 | 0.698067E+09 | 1198.42 | 25-FEB-15:09 | 31.83 | 22.02 |
March | 0.159790E+11 | 31800.15 | 04-MAR-09:01 | 29.40 | 20.97 | 0.790440E+09 | 1198.45 | 04-MAR-15:00 | 33.20 | 22.29 |
April | 0.154820E+11 | 25268.97 | 27-APR-08:61 | 28.25 | 24.47 | 0.753254E+09 | 1198.26 | 22-APR-14:00 | 31.90 | 25.99 |
May | 0.162474E+11 | 22010.94 | 11-MAY-08:61 | 28.17 | 26.54 | 0.778679E+09 | 1198.21 | 13-MAY-14:00 | 31.50 | 26.16 |
June | 0.161858E+11 | 23775.75 | 21-JUN-08:61 | 28.17 | 24.45 | 0.763571E+09 | 1198.20 | 03-JUN-14:00 | 28.00 | 27.19 |
July | 0.147015E+11 | 26393.42 | 06-JUL-08:61 | 26.75 | 24.00 | 0.768250E+09 | 1198.34 | 01-JUL-14:00 | 30.30 | 24.75 |
August | 0.147756E+11 | 23220.67 | 30-AUG-08:61 | 27.33 | 25.50 | 0.790219E+09 | 1198.42 | 19-AUG-14:00 | 24.00 | 24.00 |
September | 0.142862E+11 | 23494.53 | 13-SEP-08:61 | 28.75 | 25.91 | 0.753037E+09 | 1198.42 | 16-SEP-14:09 | 25.75 | 24.54 |
October | 0.140000E+11 | 25178.63 | 20-OCT-08:61 | 27.67 | 23.83 | 0.766587E+09 | 1198.28 | 21-OCT-14:00 | 29.50 | 25.83 |
November | 0.138845E+11 | 30873.56 | 25-NOV-09:01 | 23.67 | 20.23 | 0.738170E+09 | 1198.47 | 25-NOV-15:00 | 25.40 | 22.47 |
December | 0.143350E+11 | 32240.14 | 27-DEC-09:01 | 26.40 | 20.68 | 0.767934E+09 | 1198.39 | 16-DEC-15:00 | 28.60 | 24.85 |
Annual Sum or Average | 0.178871E+12 | 0.913478E+10 | ||||||||
Minimum of Months | 0.138845E+11 | 22010.94 | 19.07 | 17.34 | 0.698067E+09 | 1198.20 | 24.00 | 21.32 | ||
Maximum of Months | 0.162474E+11 | 33790.78 | 29.40 | 26.54 | 0.790440E+09 | 1198.51 | 33.20 | 27.19 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.780358E+10 | 16983.17 | 24-JAN-09:02 | 19.07 | 17.34 | 0.383277E+09 | 599.25 | 28-JAN-15:20 | 32.03 | 21.32 |
February | 0.737759E+10 | 17725.39 | 25-FEB-09:01 | 25.22 | 19.83 | 0.349023E+09 | 599.20 | 25-FEB-15:00 | 31.00 | 21.02 |
March | 0.837570E+10 | 16680.16 | 04-MAR-09:01 | 29.40 | 20.97 | 0.395208E+09 | 599.22 | 04-MAR-15:00 | 33.20 | 22.29 |
April | 0.811667E+10 | 13279.95 | 27-APR-08:61 | 28.25 | 24.47 | 0.376612E+09 | 599.11 | 22-APR-14:00 | 31.90 | 25.99 |
May | 0.851125E+10 | 11543.23 | 11-MAY-08:61 | 28.17 | 26.54 | 0.389323E+09 | 599.09 | 13-MAY-14:00 | 31.50 | 26.16 |
June | 0.846656E+10 | 12480.43 | 21-JUN-08:61 | 28.17 | 24.45 | 0.381768E+09 | 599.08 | 03-JUN-14:00 | 28.00 | 27.19 |
July | 0.767918E+10 | 13884.83 | 06-JUL-08:61 | 26.75 | 24.00 | 0.384110E+09 | 599.16 | 01-JUL-14:00 | 30.30 | 24.75 |
August | 0.771897E+10 | 12202.04 | 30-AUG-08:61 | 27.33 | 25.50 | 0.395094E+09 | 599.20 | 19-AUG-14:00 | 24.00 | 24.00 |
September | 0.746831E+10 | 12398.52 | 13-SEP-08:61 | 28.75 | 25.91 | 0.376505E+09 | 599.20 | 16-SEP-14:09 | 25.75 | 24.54 |
October | 0.731414E+10 | 13205.71 | 20-OCT-08:61 | 27.67 | 23.83 | 0.383284E+09 | 599.12 | 21-OCT-14:00 | 29.50 | 25.83 |
November | 0.724795E+10 | 16196.69 | 25-NOV-09:01 | 23.67 | 20.23 | 0.369076E+09 | 599.23 | 25-NOV-15:00 | 25.40 | 22.47 |
December | 0.749080E+10 | 16930.73 | 27-DEC-09:01 | 26.40 | 20.68 | 0.383958E+09 | 599.19 | 16-DEC-15:00 | 28.60 | 24.85 |
Annual Sum or Average | 0.935707E+11 | 0.456724E+10 | ||||||||
Minimum of Months | 0.724795E+10 | 11543.23 | 19.07 | 17.34 | 0.349023E+09 | 599.08 | 24.00 | 21.02 | ||
Maximum of Months | 0.851125E+10 | 17725.39 | 29.40 | 26.54 | 0.395208E+09 | 599.25 | 33.20 | 27.19 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.773664E+10 | 16871.68 | 24-JAN-09:02 | 19.07 | 17.34 | 0.383271E+09 | 599.25 | 28-JAN-15:20 | 32.03 | 21.32 |
February | 0.732102E+10 | 17621.97 | 25-FEB-09:01 | 25.22 | 19.83 | 0.349019E+09 | 599.20 | 25-FEB-15:00 | 31.00 | 21.02 |
March | 0.831320E+10 | 16580.93 | 04-MAR-09:01 | 29.40 | 20.97 | 0.395205E+09 | 599.22 | 04-MAR-15:00 | 33.20 | 22.29 |
April | 0.806063E+10 | 13190.14 | 27-APR-08:61 | 28.25 | 24.47 | 0.376611E+09 | 599.11 | 22-APR-14:00 | 31.90 | 25.99 |
May | 0.845027E+10 | 11447.62 | 11-MAY-08:61 | 28.17 | 26.54 | 0.389319E+09 | 599.09 | 13-MAY-14:00 | 31.50 | 26.16 |
June | 0.840465E+10 | 12391.10 | 21-JUN-08:61 | 28.17 | 24.45 | 0.381767E+09 | 599.08 | 03-JUN-14:00 | 28.00 | 27.19 |
July | 0.761808E+10 | 13792.19 | 06-JUL-08:61 | 26.75 | 24.00 | 0.384104E+09 | 599.16 | 01-JUL-14:00 | 30.30 | 24.75 |
August | 0.765764E+10 | 12107.32 | 30-AUG-08:61 | 27.33 | 25.50 | 0.395091E+09 | 599.20 | 19-AUG-14:00 | 24.00 | 24.00 |
September | 0.741031E+10 | 12267.03 | 13-SEP-08:61 | 28.75 | 25.91 | 0.376501E+09 | 599.20 | 16-SEP-14:09 | 25.75 | 24.54 |
October | 0.725310E+10 | 13108.29 | 20-OCT-08:61 | 27.67 | 23.83 | 0.383279E+09 | 599.12 | 21-OCT-14:00 | 29.50 | 25.83 |
November | 0.718740E+10 | 16084.90 | 25-NOV-09:01 | 23.67 | 20.23 | 0.369075E+09 | 599.23 | 25-NOV-15:00 | 25.40 | 22.47 |
December | 0.742633E+10 | 16830.07 | 27-DEC-09:01 | 26.40 | 20.68 | 0.383952E+09 | 599.19 | 16-DEC-15:00 | 28.60 | 24.85 |
Annual Sum or Average | 0.928393E+11 | 0.456719E+10 | ||||||||
Minimum of Months | 0.718740E+10 | 11447.62 | 19.07 | 17.34 | 0.349019E+09 | 599.08 | 24.00 | 21.02 | ||
Maximum of Months | 0.845027E+10 | 17621.97 | 29.40 | 26.54 | 0.395205E+09 | 599.25 | 33.20 | 27.19 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.769853E+10 | 16818.08 | 24-JAN-09:02 | 19.07 | 17.34 | 0.383268E+09 | 599.25 | 28-JAN-15:20 | 32.03 | 21.32 |
February | 0.729960E+10 | 17602.44 | 25-FEB-09:01 | 25.22 | 19.83 | 0.349017E+09 | 599.20 | 25-FEB-15:00 | 31.00 | 21.02 |
March | 0.829461E+10 | 16555.27 | 04-MAR-09:01 | 29.40 | 20.97 | 0.395201E+09 | 599.22 | 04-MAR-15:00 | 33.20 | 22.29 |
April | 0.805440E+10 | 13168.35 | 27-APR-08:61 | 28.25 | 24.47 | 0.376606E+09 | 599.11 | 22-APR-14:00 | 31.90 | 25.99 |
May | 0.844600E+10 | 11414.88 | 11-MAY-08:61 | 28.17 | 26.54 | 0.389318E+09 | 599.09 | 13-MAY-14:00 | 31.50 | 26.16 |
June | 0.840795E+10 | 12363.01 | 21-JUN-08:61 | 28.17 | 24.45 | 0.381765E+09 | 599.08 | 03-JUN-14:00 | 28.00 | 27.19 |
July | 0.761136E+10 | 13772.37 | 06-JUL-08:61 | 26.75 | 24.00 | 0.384103E+09 | 599.16 | 01-JUL-14:00 | 30.30 | 24.75 |
August | 0.764539E+10 | 12081.25 | 30-AUG-08:61 | 27.33 | 25.50 | 0.395089E+09 | 599.21 | 19-AUG-14:00 | 24.00 | 24.00 |
September | 0.740345E+10 | 12245.05 | 13-SEP-08:61 | 28.75 | 25.91 | 0.376499E+09 | 599.20 | 16-SEP-14:09 | 25.75 | 24.54 |
October | 0.721978E+10 | 13068.24 | 20-OCT-08:61 | 27.67 | 23.83 | 0.383275E+09 | 599.13 | 21-OCT-14:00 | 29.50 | 25.83 |
November | 0.715388E+10 | 16031.02 | 25-NOV-09:01 | 23.67 | 20.23 | 0.369068E+09 | 599.23 | 25-NOV-15:00 | 25.40 | 22.47 |
December | 0.738394E+10 | 16803.56 | 27-DEC-09:01 | 26.40 | 20.68 | 0.383948E+09 | 599.19 | 16-DEC-15:00 | 28.60 | 24.85 |
Annual Sum or Average | 0.926189E+11 | 0.456716E+10 | ||||||||
Minimum of Months | 0.715388E+10 | 11414.88 | 19.07 | 17.34 | 0.349017E+09 | 599.08 | 24.00 | 21.02 | ||
Maximum of Months | 0.844600E+10 | 17602.44 | 29.40 | 26.54 | 0.395201E+09 | 599.25 | 33.20 | 27.19 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.837657E+10 | 17786.99 | 24-JAN-09:02 | 19.07 | 17.34 | 0.383309E+09 | 599.25 | 28-JAN-15:20 | 32.03 | 21.32 |
February | 0.804720E+10 | 18529.81 | 24-FEB-09:01 | 25.53 | 19.48 | 0.349059E+09 | 599.20 | 25-FEB-15:00 | 31.00 | 21.02 |
March | 0.920228E+10 | 17432.96 | 04-MAR-09:01 | 29.40 | 20.97 | 0.395243E+09 | 599.21 | 04-MAR-15:00 | 33.20 | 22.29 |
April | 0.900502E+10 | 13407.68 | 27-APR-08:61 | 28.25 | 24.47 | 0.376653E+09 | 599.10 | 22-APR-14:00 | 31.90 | 25.99 |
May | 0.940007E+10 | 11867.70 | 06-MAY-08:61 | 32.17 | 26.11 | 0.389360E+09 | 599.07 | 13-MAY-14:00 | 31.50 | 26.16 |
June | 0.943407E+10 | 12614.17 | 21-JUN-08:61 | 28.17 | 24.45 | 0.381800E+09 | 599.07 | 03-JUN-14:00 | 28.00 | 27.19 |
July | 0.846828E+10 | 14902.26 | 19-JUL-08:61 | 26.70 | 24.35 | 0.384162E+09 | 599.14 | 01-JUL-14:00 | 30.30 | 24.75 |
August | 0.851390E+10 | 12396.65 | 30-AUG-08:61 | 27.33 | 25.50 | 0.395120E+09 | 599.20 | 19-AUG-14:00 | 24.00 | 24.00 |
September | 0.825168E+10 | 12605.66 | 13-SEP-08:61 | 28.75 | 25.91 | 0.376546E+09 | 599.20 | 16-SEP-14:09 | 25.75 | 24.54 |
October | 0.786260E+10 | 13425.01 | 20-OCT-08:61 | 27.67 | 23.83 | 0.383319E+09 | 599.11 | 21-OCT-14:00 | 29.50 | 25.83 |
November | 0.780343E+10 | 16965.33 | 25-NOV-09:01 | 23.67 | 20.23 | 0.369100E+09 | 599.23 | 25-NOV-15:00 | 25.40 | 22.47 |
December | 0.802678E+10 | 17592.22 | 27-DEC-09:01 | 26.40 | 20.68 | 0.383989E+09 | 599.18 | 16-DEC-15:00 | 28.60 | 24.85 |
Annual Sum or Average | 0.102392E+12 | 0.456766E+10 | ||||||||
Minimum of Months | 0.780343E+10 | 11867.70 | 19.07 | 17.34 | 0.349059E+09 | 599.07 | 24.00 | 21.02 | ||
Maximum of Months | 0.943407E+10 | 18529.81 | 32.17 | 26.11 | 0.395243E+09 | 599.25 | 33.20 | 27.19 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55970866.06 | 4689.94 | 20-JAN-09:06 | 28.27 |
February | 57093469.93 | 5215.60 | 28-FEB-09:06 | 28.33 |
March | 51714368.47 | 5542.67 | 29-MAR-08:06 | 29.33 |
April | 23189221.94 | 5493.12 | 19-APR-08:07 | 29.67 |
May | 26064511.94 | 5414.23 | 07-MAY-07:08 | 29.67 |
June | 22174827.26 | 4662.60 | 18-JUN-07:08 | 28.00 |
July | 54671809.63 | 4883.78 | 29-JUL-08:06 | 28.13 |
August | 38883559.43 | 4701.39 | 12-AUG-08:09 | 28.33 |
September | 37412950.90 | 5281.67 | 06-SEP-08:07 | 29.17 |
October | 61211028.42 | 4860.44 | 30-OCT-08:07 | 28.25 |
November | 41435796.54 | 4888.29 | 20-NOV-09:06 | 28.23 |
December | 63350968.72 | 4625.35 | 06-DEC-09:06 | 28.03 |
Annual Sum or Average | 0.533173E+09 | |||
Minimum of Months | 22174827.26 | 4625.35 | 28.00 | |
Maximum of Months | 63350968.72 | 5542.67 | 29.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28331539.07 | 2959.20 | 03-JAN-09:06 | 29.27 |
February | 30225081.18 | 2655.02 | 28-FEB-09:06 | 28.33 |
March | 27823123.50 | 3000.45 | 04-MAR-09:05 | 29.40 |
April | 13443095.03 | 2677.28 | 27-APR-08:06 | 28.25 |
May | 15169830.55 | 2855.42 | 07-MAY-07:06 | 29.67 |
June | 9986182.10 | 2806.71 | 23-JUN-08:06 | 29.33 |
July | 25568207.91 | 2473.08 | 09-JUL-07:04 | 26.50 |
August | 24759743.49 | 2757.79 | 14-AUG-08:07 | 29.33 |
September | 21461333.80 | 2727.35 | 27-SEP-08:06 | 29.00 |
October | 34245777.48 | 2775.01 | 05-OCT-08:06 | 29.17 |
November | 19459255.96 | 2691.53 | 22-NOV-09:06 | 28.22 |
December | 33673126.28 | 2907.68 | 08-DEC-09:06 | 29.03 |
Annual Sum or Average | 0.284146E+09 | |||
Minimum of Months | 9986182.10 | 2473.08 | 26.50 | |
Maximum of Months | 34245777.48 | 3000.45 | 29.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138518E+09 | 2408.16 | 29-JAN-17:11 | 30.67 |
February | 0.141071E+09 | 2464.61 | 26-FEB-09:06 | 27.45 |
March | 0.165856E+09 | 3243.59 | 19-MAR-16:01 | 34.25 |
April | 0.172093E+09 | 3027.01 | 02-APR-16:01 | 33.25 |
May | 0.162675E+09 | 3311.51 | 29-MAY-16:01 | 34.50 |
June | 0.156924E+09 | 3247.20 | 11-JUN-16:01 | 34.25 |
July | 0.145121E+09 | 2958.89 | 15-JUL-17:12 | 32.67 |
August | 0.138964E+09 | 2852.36 | 27-AUG-16:11 | 32.67 |
September | 0.140956E+09 | 2859.90 | 04-SEP-16:11 | 32.67 |
October | 0.139186E+09 | 2503.67 | 08-OCT-08:07 | 28.25 |
November | 0.118544E+09 | 2432.62 | 11-NOV-09:07 | 28.23 |
December | 0.123814E+09 | 2180.57 | 09-DEC-08:07 | 27.33 |
Annual Sum or Average | 0.174372E+10 | |||
Minimum of Months | 0.118544E+09 | 2180.57 | 27.33 | |
Maximum of Months | 0.172093E+09 | 3311.51 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134446E+09 | 2410.68 | 29-JAN-17:11 | 30.67 |
February | 0.139155E+09 | 2448.42 | 26-FEB-09:06 | 27.45 |
March | 0.157237E+09 | 3243.12 | 19-MAR-16:01 | 34.25 |
April | 0.172585E+09 | 3026.11 | 02-APR-16:01 | 33.25 |
May | 0.161493E+09 | 3309.69 | 29-MAY-16:01 | 34.50 |
June | 0.156037E+09 | 3245.72 | 11-JUN-16:01 | 34.25 |
July | 0.142828E+09 | 2961.77 | 15-JUL-17:12 | 32.67 |
August | 0.136624E+09 | 2853.96 | 27-AUG-16:11 | 32.67 |
September | 0.139824E+09 | 2861.10 | 04-SEP-16:11 | 32.67 |
October | 0.135055E+09 | 2504.67 | 08-OCT-08:07 | 28.25 |
November | 0.116775E+09 | 2435.05 | 11-NOV-09:07 | 28.23 |
December | 0.121482E+09 | 2107.46 | 09-DEC-08:07 | 27.33 |
Annual Sum or Average | 0.171354E+10 | |||
Minimum of Months | 0.116775E+09 | 2107.46 | 27.33 | |
Maximum of Months | 0.172585E+09 | 3309.69 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141624E+09 | 2410.70 | 29-JAN-17:11 | 30.67 |
February | 0.147297E+09 | 2458.45 | 26-FEB-09:06 | 27.45 |
March | 0.170914E+09 | 3244.54 | 19-MAR-16:01 | 34.25 |
April | 0.178326E+09 | 3027.29 | 02-APR-16:01 | 33.25 |
May | 0.167415E+09 | 3310.28 | 29-MAY-16:01 | 34.50 |
June | 0.159535E+09 | 3246.63 | 11-JUN-16:01 | 34.25 |
July | 0.151382E+09 | 2962.80 | 15-JUL-17:12 | 32.67 |
August | 0.146567E+09 | 2853.52 | 27-AUG-16:11 | 32.67 |
September | 0.149376E+09 | 2860.19 | 04-SEP-16:11 | 32.67 |
October | 0.144940E+09 | 2508.74 | 08-OCT-08:07 | 28.25 |
November | 0.124101E+09 | 2437.83 | 11-NOV-09:07 | 28.23 |
December | 0.128697E+09 | 2234.69 | 09-DEC-08:07 | 27.33 |
Annual Sum or Average | 0.181017E+10 | |||
Minimum of Months | 0.124101E+09 | 2234.69 | 27.33 | |
Maximum of Months | 0.178326E+09 | 3310.28 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126549E+09 | 4775.37 | 20-JAN-09:06 | 28.27 |
February | 0.143297E+09 | 4956.58 | 18-FEB-09:06 | 28.72 |
March | 0.142400E+09 | 6389.76 | 19-MAR-16:01 | 34.25 |
April | 0.138883E+09 | 5947.90 | 02-APR-16:01 | 33.25 |
May | 0.139863E+09 | 6519.79 | 29-MAY-16:01 | 34.50 |
June | 0.107208E+09 | 6394.73 | 11-JUN-16:01 | 34.25 |
July | 0.170312E+09 | 5703.75 | 15-JUL-17:12 | 32.67 |
August | 0.124576E+09 | 5606.13 | 27-AUG-16:02 | 32.83 |
September | 0.138089E+09 | 5617.84 | 04-SEP-16:02 | 32.83 |
October | 0.145624E+09 | 5051.33 | 05-OCT-08:08 | 29.17 |
November | 0.102704E+09 | 4895.14 | 07-NOV-09:07 | 28.67 |
December | 0.141462E+09 | 5041.49 | 03-DEC-10:06 | 29.17 |
Annual Sum or Average | 0.162097E+10 | |||
Minimum of Months | 0.102704E+09 | 4775.37 | 28.27 | |
Maximum of Months | 0.170312E+09 | 6519.79 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76732395.47 | 2404.46 | 29-JAN-17:02 | 30.83 |
February | 83265590.19 | 2849.54 | 26-FEB-10:06 | 29.92 |
March | 87079218.39 | 3239.45 | 19-MAR-16:01 | 34.25 |
April | 80922439.32 | 3020.54 | 02-APR-16:01 | 33.25 |
May | 77932618.40 | 3301.78 | 29-MAY-16:01 | 34.50 |
June | 60774658.78 | 3240.87 | 11-JUN-16:01 | 34.25 |
July | 97751846.74 | 2927.55 | 15-JUL-17:12 | 32.67 |
August | 76822150.72 | 2845.36 | 27-AUG-16:02 | 32.83 |
September | 82856700.12 | 2850.44 | 04-SEP-16:02 | 32.83 |
October | 87401334.04 | 2309.89 | 20-OCT-08:06 | 27.67 |
November | 62832832.37 | 2654.32 | 23-NOV-10:06 | 29.13 |
December | 84623275.68 | 2625.32 | 03-DEC-10:06 | 29.17 |
Annual Sum or Average | 0.958995E+09 | |||
Minimum of Months | 60774658.78 | 2309.89 | 27.67 | |
Maximum of Months | 97751846.74 | 3301.78 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 77816763.46 | 2404.48 | 29-JAN-17:02 | 30.83 |
February | 85813761.82 | 2851.22 | 26-FEB-10:06 | 29.92 |
March | 89892907.10 | 3239.10 | 19-MAR-16:01 | 34.25 |
April | 85956180.73 | 3020.04 | 02-APR-16:01 | 33.25 |
May | 80041331.74 | 3301.25 | 29-MAY-16:01 | 34.50 |
June | 62680818.78 | 3240.60 | 11-JUN-16:01 | 34.25 |
July | 98533165.48 | 2923.73 | 15-JUL-17:12 | 32.67 |
August | 78303829.69 | 2845.46 | 27-AUG-16:02 | 32.83 |
September | 85256573.26 | 2850.32 | 04-SEP-16:02 | 32.83 |
October | 89901388.90 | 2471.39 | 06-OCT-08:08 | 28.67 |
November | 66824163.69 | 2656.04 | 23-NOV-10:06 | 29.13 |
December | 87000858.12 | 2627.41 | 03-DEC-10:06 | 29.17 |
Annual Sum or Average | 0.988022E+09 | |||
Minimum of Months | 62680818.78 | 2404.48 | 28.67 | |
Maximum of Months | 98533165.48 | 3301.25 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 83682082.33 | 2405.98 | 29-JAN-17:02 | 30.83 |
February | 89588589.41 | 2852.00 | 26-FEB-10:06 | 29.92 |
March | 94242462.80 | 3239.07 | 19-MAR-16:01 | 34.25 |
April | 86589476.80 | 3019.62 | 02-APR-16:01 | 33.25 |
May | 82955358.08 | 3300.89 | 29-MAY-16:01 | 34.50 |
June | 64908438.06 | 3239.48 | 11-JUN-16:01 | 34.25 |
July | 0.102368E+09 | 2926.10 | 15-JUL-17:12 | 32.67 |
August | 81707312.52 | 2844.79 | 27-AUG-16:02 | 32.83 |
September | 87514976.09 | 2849.78 | 04-SEP-16:02 | 32.83 |
October | 94407846.63 | 2288.15 | 20-OCT-08:06 | 27.67 |
November | 70758989.79 | 2652.56 | 23-NOV-10:06 | 29.13 |
December | 91271512.06 | 2628.57 | 03-DEC-10:06 | 29.17 |
Annual Sum or Average | 0.102999E+10 | |||
Minimum of Months | 64908438.06 | 2288.15 | 27.67 | |
Maximum of Months | 0.102368E+09 | 3300.89 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 82649351.00 | 2500.22 | 20-JAN-09:06 | 28.27 |
February | 83615738.42 | 2882.05 | 26-FEB-10:06 | 29.92 |
March | 84618548.97 | 3235.79 | 19-MAR-16:01 | 34.25 |
April | 76287668.26 | 3020.85 | 02-APR-16:01 | 33.25 |
May | 77598650.10 | 3300.70 | 29-MAY-16:01 | 34.50 |
June | 58917743.71 | 3232.78 | 11-JUN-16:01 | 34.25 |
July | 94625762.94 | 2974.84 | 15-JUL-17:12 | 32.67 |
August | 73505837.99 | 2870.91 | 27-AUG-16:11 | 32.67 |
September | 78853061.40 | 2877.10 | 04-SEP-16:11 | 32.67 |
October | 91407994.93 | 2504.22 | 05-OCT-08:08 | 29.17 |
November | 65908051.79 | 2636.98 | 14-NOV-09:07 | 28.67 |
December | 89468043.45 | 2420.72 | 06-DEC-09:06 | 28.03 |
Annual Sum or Average | 0.957456E+09 | |||
Minimum of Months | 58917743.71 | 2420.72 | 28.03 | |
Maximum of Months | 94625762.94 | 3300.70 | 34.50 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.114998E+11 | 6976.27 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.104054E+11 | 6976.27 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.115236E+11 | 6976.27 | 01-MAR-10:09 | 0.223972E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.111588E+11 | 6976.27 | 01-APR-09:09 | 0.216880E+10 | 1348.26 | 01-APR-09:09 |
May | 0.114998E+11 | 6976.27 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.111588E+11 | 6976.27 | 01-JUN-09:09 | 0.216880E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.115236E+11 | 6976.27 | 01-JUL-09:09 | 0.223972E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.114998E+11 | 6976.27 | 01-AUG-09:09 | 0.223514E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.111826E+11 | 6976.27 | 01-SEP-09:09 | 0.217339E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.114998E+11 | 6976.27 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.111112E+11 | 6976.27 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.115474E+11 | 6976.27 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.135611E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.104054E+11 | 6976.27 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.115474E+11 | 6976.27 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.614337E+10 | 3726.82 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.555869E+10 | 3726.82 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.615608E+10 | 3726.82 | 01-MAR-10:09 | 0.111986E+10 | 674.13 | 01-MAR-10:09 |
April | 0.596119E+10 | 3726.82 | 01-APR-09:09 | 0.108440E+10 | 674.13 | 01-APR-09:09 |
May | 0.614337E+10 | 3726.82 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.596119E+10 | 3726.82 | 01-JUN-09:09 | 0.108440E+10 | 674.13 | 01-JUN-09:09 |
July | 0.615608E+10 | 3726.82 | 01-JUL-09:09 | 0.111986E+10 | 674.13 | 01-JUL-09:09 |
August | 0.614337E+10 | 3726.82 | 01-AUG-09:09 | 0.111757E+10 | 674.13 | 01-AUG-09:09 |
September | 0.597390E+10 | 3726.82 | 01-SEP-09:09 | 0.108669E+10 | 674.13 | 01-SEP-09:09 |
October | 0.614337E+10 | 3726.82 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.593577E+10 | 3726.82 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.616879E+10 | 3726.82 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.724452E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.555869E+10 | 3726.82 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.616879E+10 | 3726.82 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.438359E+10 | 3370.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.396975E+10 | 3370.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.447555E+10 | 3370.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.425331E+10 | 3370.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.442957E+10 | 3370.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.432228E+10 | 3370.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.436060E+10 | 3370.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.447555E+10 | 3370.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.425331E+10 | 3370.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.438359E+10 | 3370.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.425331E+10 | 3370.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.436060E+10 | 3370.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.519210E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.396975E+10 | 3370.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.447555E+10 | 3370.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.438359E+10 | 3370.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.396975E+10 | 3370.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.447555E+10 | 3370.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.425331E+10 | 3370.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.442957E+10 | 3370.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.432228E+10 | 3370.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.436060E+10 | 3370.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.447555E+10 | 3370.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.425331E+10 | 3370.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.438359E+10 | 3370.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.425331E+10 | 3370.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.436060E+10 | 3370.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.519210E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.396975E+10 | 3370.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.447555E+10 | 3370.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.438359E+10 | 3370.57 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.396975E+10 | 3370.57 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.447555E+10 | 3370.57 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.425331E+10 | 3370.57 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.442957E+10 | 3370.57 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.432228E+10 | 3370.57 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.436060E+10 | 3370.57 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.447555E+10 | 3370.57 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.425331E+10 | 3370.57 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.438359E+10 | 3370.57 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.425331E+10 | 3370.57 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.436060E+10 | 3370.57 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.519210E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.396975E+10 | 3370.57 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.447555E+10 | 3370.57 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.627948E+10 | 5255.58 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.568798E+10 | 5255.58 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.642287E+10 | 5255.58 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.609426E+10 | 5255.58 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.635118E+10 | 5255.58 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.620181E+10 | 5255.58 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.624363E+10 | 5255.58 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.642287E+10 | 5255.58 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.609426E+10 | 5255.58 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.627948E+10 | 5255.58 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.609426E+10 | 5255.58 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.624363E+10 | 5255.58 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.744157E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.568798E+10 | 5255.58 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.642287E+10 | 5255.58 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.313974E+10 | 2627.79 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.284399E+10 | 2627.79 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.321144E+10 | 2627.79 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.304713E+10 | 2627.79 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.317559E+10 | 2627.79 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.310090E+10 | 2627.79 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.312181E+10 | 2627.79 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.321144E+10 | 2627.79 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.304713E+10 | 2627.79 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.313974E+10 | 2627.79 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.304713E+10 | 2627.79 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.312181E+10 | 2627.79 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.372078E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.284399E+10 | 2627.79 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.321144E+10 | 2627.79 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.313974E+10 | 2627.79 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.284399E+10 | 2627.79 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.321144E+10 | 2627.79 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.304713E+10 | 2627.79 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.317559E+10 | 2627.79 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.310090E+10 | 2627.79 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.312181E+10 | 2627.79 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.321144E+10 | 2627.79 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.304713E+10 | 2627.79 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.313974E+10 | 2627.79 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.304713E+10 | 2627.79 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.312181E+10 | 2627.79 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.372078E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.284399E+10 | 2627.79 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.321144E+10 | 2627.79 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.313974E+10 | 2627.79 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.284399E+10 | 2627.79 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.321144E+10 | 2627.79 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.304713E+10 | 2627.79 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.317559E+10 | 2627.79 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.310090E+10 | 2627.79 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.312181E+10 | 2627.79 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.321144E+10 | 2627.79 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.304713E+10 | 2627.79 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.313974E+10 | 2627.79 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.304713E+10 | 2627.79 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.312181E+10 | 2627.79 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.372078E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.284399E+10 | 2627.79 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.321144E+10 | 2627.79 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.313974E+10 | 2627.79 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.284399E+10 | 2627.79 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.321144E+10 | 2627.79 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.304713E+10 | 2627.79 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.317559E+10 | 2627.79 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.310090E+10 | 2627.79 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.312181E+10 | 2627.79 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.321144E+10 | 2627.79 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.304713E+10 | 2627.79 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.313974E+10 | 2627.79 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.304713E+10 | 2627.79 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.312181E+10 | 2627.79 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.372078E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.284399E+10 | 2627.79 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.321144E+10 | 2627.79 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.114998E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226710E+10 | 0.100450E+09 |
February | 0.163016E+10 | 0.104054E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246037E+10 | 31050487.44 |
March | 0.178954E+10 | 0.115236E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299245E+10 | 42994414.73 |
April | 0.174484E+10 | 0.111588E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296915E+10 | 7854423.39 |
May | 0.179537E+10 | 0.114998E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301800E+10 | 19991164.36 |
June | 0.173447E+10 | 0.111588E+11 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293719E+10 | 19752027.18 |
July | 0.181028E+10 | 0.115236E+11 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219675E+10 | 23248582.87 |
August | 0.178501E+10 | 0.114998E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223791E+10 | 38403958.88 |
September | 0.174937E+10 | 0.111826E+11 | 0.217339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218552E+10 | 21154507.90 |
October | 0.180574E+10 | 0.114998E+11 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192253E+10 | 39590002.32 |
November | 0.174613E+10 | 0.111112E+11 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184545E+10 | 50644393.11 |
December | 0.181481E+10 | 0.115474E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200798E+10 | 0.103103E+09 |
Annual Sum or Average | 0.212115E+11 | 0.135611E+12 | 0.263573E+11 | 0.290404E+11 | 0.498237E+09 | ||||
Minimum of Months | 0.163016E+10 | 0.104054E+11 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184545E+10 | 7854423.39 |
Maximum of Months | 0.181481E+10 | 0.115474E+11 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301800E+10 | 0.103103E+09 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.614337E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126528E+10 | 33274214.11 |
February | 0.815075E+09 | 0.555869E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136560E+10 | 10966443.80 |
March | 0.894769E+09 | 0.615608E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164343E+10 | 12820057.17 |
April | 0.872416E+09 | 0.596119E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163252E+10 | 2505810.13 |
May | 0.897684E+09 | 0.614337E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165047E+10 | 6173562.27 |
June | 0.867232E+09 | 0.596119E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161199E+10 | 5898684.21 |
July | 0.905135E+09 | 0.615608E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121344E+10 | 8367674.44 |
August | 0.892501E+09 | 0.614337E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122768E+10 | 12254980.46 |
September | 0.874683E+09 | 0.597390E+10 | 0.108669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121176E+10 | 6846874.76 |
October | 0.902868E+09 | 0.614337E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106795E+10 | 13253744.05 |
November | 0.873064E+09 | 0.593577E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103062E+10 | 15886345.77 |
December | 0.907403E+09 | 0.616879E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112421E+10 | 32117803.66 |
Annual Sum or Average | 0.106057E+11 | 0.724452E+11 | 0.131787E+11 | 0.160450E+11 | 0.160366E+09 | ||||
Minimum of Months | 0.815075E+09 | 0.555869E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103062E+10 | 2505810.13 |
Maximum of Months | 0.907403E+09 | 0.616879E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165047E+10 | 33274214.11 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124172E+10 | 43851882.34 |
February | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134024E+10 | 13731589.03 |
March | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162176E+10 | 20080874.74 |
April | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160870E+10 | 4996664.25 |
May | 0.544247E+09 | 0.442957E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162727E+10 | 9838047.32 |
June | 0.532585E+09 | 0.432228E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159269E+10 | 11339361.24 |
July | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118711E+10 | 13045730.50 |
August | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121331E+10 | 22373262.00 |
September | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119289E+10 | 13999547.56 |
October | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104873E+10 | 24177574.44 |
November | 0.518979E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101518E+10 | 25569910.39 |
December | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110414E+10 | 45054224.63 |
Annual Sum or Average | 0.638324E+10 | 0.519210E+11 | 0.104672E+11 | 0.157937E+11 | 0.248059E+09 | ||||
Minimum of Months | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101518E+10 | 4996664.25 |
Maximum of Months | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162727E+10 | 45054224.63 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124159E+10 | 44955059.50 |
February | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133990E+10 | 14470106.23 |
March | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162096E+10 | 21363161.29 |
April | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160714E+10 | 5407910.43 |
May | 0.544247E+09 | 0.442957E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162561E+10 | 10409015.68 |
June | 0.532585E+09 | 0.432228E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159140E+10 | 12145770.39 |
July | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118654E+10 | 13746453.04 |
August | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121286E+10 | 23353806.58 |
September | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119243E+10 | 14663311.59 |
October | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104851E+10 | 25052112.80 |
November | 0.518979E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101503E+10 | 26236642.67 |
December | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110407E+10 | 45823611.22 |
Annual Sum or Average | 0.638324E+10 | 0.519210E+11 | 0.104672E+11 | 0.157860E+11 | 0.257627E+09 | ||||
Minimum of Months | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101503E+10 | 5407910.43 |
Maximum of Months | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162561E+10 | 45823611.22 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124180E+10 | 43223923.76 |
February | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134027E+10 | 13352310.71 |
March | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162194E+10 | 19347008.11 |
April | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160892E+10 | 4862102.21 |
May | 0.544247E+09 | 0.442957E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162701E+10 | 9606306.05 |
June | 0.532585E+09 | 0.432228E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159274E+10 | 11278501.64 |
July | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118709E+10 | 12867289.53 |
August | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121339E+10 | 21538434.57 |
September | 0.524810E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119292E+10 | 13597197.89 |
October | 0.537120E+09 | 0.438359E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104881E+10 | 23706001.46 |
November | 0.518979E+09 | 0.425331E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101527E+10 | 24902473.87 |
December | 0.536472E+09 | 0.436060E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110420E+10 | 44226922.78 |
Annual Sum or Average | 0.638324E+10 | 0.519210E+11 | 0.104672E+11 | 0.157944E+11 | 0.242508E+09 | ||||
Minimum of Months | 0.487879E+09 | 0.396975E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101527E+10 | 4862102.21 |
Maximum of Months | 0.551374E+09 | 0.447555E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162701E+10 | 44226922.78 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.627948E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217377E+10 | 90678568.88 |
February | 0.167188E+10 | 0.568798E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234595E+10 | 29829473.41 |
March | 0.189386E+10 | 0.642287E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284298E+10 | 33469294.06 |
April | 0.180380E+10 | 0.609426E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282342E+10 | 8576744.03 |
May | 0.186509E+10 | 0.635118E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285530E+10 | 17549350.20 |
June | 0.182945E+10 | 0.620181E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279358E+10 | 21001846.11 |
July | 0.183943E+10 | 0.624363E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207548E+10 | 27667157.06 |
August | 0.189386E+10 | 0.642287E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212007E+10 | 36592401.14 |
September | 0.180380E+10 | 0.609426E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208228E+10 | 25650266.72 |
October | 0.183632E+10 | 0.627948E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182793E+10 | 46349834.15 |
November | 0.176881E+10 | 0.609426E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176759E+10 | 49001273.62 |
December | 0.183943E+10 | 0.624363E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192459E+10 | 90100681.52 |
Annual Sum or Average | 0.218821E+11 | 0.744157E+11 | 0.192612E+11 | 0.276329E+11 | 0.476467E+09 | ||||
Minimum of Months | 0.167188E+10 | 0.568798E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176759E+10 | 8576744.03 |
Maximum of Months | 0.189386E+10 | 0.642287E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285530E+10 | 90678568.88 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123872E+10 | 45293078.96 |
February | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133625E+10 | 14503763.91 |
March | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161742E+10 | 15319457.67 |
April | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160666E+10 | 4053564.02 |
May | 0.932542E+09 | 0.317559E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162321E+10 | 8174446.94 |
June | 0.914724E+09 | 0.310090E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158922E+10 | 9974181.00 |
July | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118153E+10 | 13652915.94 |
August | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120571E+10 | 17320432.74 |
September | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118588E+10 | 12369284.32 |
October | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104118E+10 | 22882531.82 |
November | 0.884402E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100754E+10 | 24196635.77 |
December | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109717E+10 | 44389816.12 |
Annual Sum or Average | 0.109410E+11 | 0.372078E+11 | 0.963059E+10 | 0.157305E+11 | 0.232130E+09 | ||||
Minimum of Months | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100754E+10 | 4053564.02 |
Maximum of Months | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162321E+10 | 45293078.96 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123888E+10 | 44688353.45 |
February | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133647E+10 | 14183511.61 |
March | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161785E+10 | 14828185.72 |
April | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160723E+10 | 3918868.02 |
May | 0.932542E+09 | 0.317559E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162374E+10 | 7983041.17 |
June | 0.914724E+09 | 0.310090E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158970E+10 | 9769052.27 |
July | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118181E+10 | 13381515.28 |
August | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120597E+10 | 16869297.80 |
September | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118611E+10 | 12082312.52 |
October | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104134E+10 | 22436408.44 |
November | 0.884402E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100768E+10 | 23774804.62 |
December | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109727E+10 | 43808207.92 |
Annual Sum or Average | 0.109410E+11 | 0.372078E+11 | 0.963059E+10 | 0.157340E+11 | 0.227724E+09 | ||||
Minimum of Months | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100768E+10 | 3918868.02 |
Maximum of Months | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162374E+10 | 44688353.45 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123902E+10 | 43592300.16 |
February | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133667E+10 | 13598785.42 |
March | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161839E+10 | 13917777.29 |
April | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160787E+10 | 3678980.18 |
May | 0.932542E+09 | 0.317559E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162416E+10 | 7662437.11 |
June | 0.914724E+09 | 0.310090E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159005E+10 | 9479218.65 |
July | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118194E+10 | 13001490.94 |
August | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120624E+10 | 16109285.09 |
September | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118629E+10 | 11630693.03 |
October | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104156E+10 | 21628671.56 |
November | 0.884402E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100791E+10 | 22957037.90 |
December | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109739E+10 | 42754904.60 |
Annual Sum or Average | 0.109410E+11 | 0.372078E+11 | 0.963059E+10 | 0.157375E+11 | 0.220012E+09 | ||||
Minimum of Months | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100791E+10 | 3678980.18 |
Maximum of Months | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162416E+10 | 43592300.16 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128058E+10 | 90784225.64 |
February | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139082E+10 | 29155485.81 |
March | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171036E+10 | 35569548.68 |
April | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170143E+10 | 7931940.24 |
May | 0.932542E+09 | 0.317559E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173179E+10 | 19142796.67 |
June | 0.914724E+09 | 0.310090E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168496E+10 | 23302634.02 |
July | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123890E+10 | 27121384.90 |
August | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127737E+10 | 37294461.61 |
September | 0.901896E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123790E+10 | 26185594.07 |
October | 0.918158E+09 | 0.313974E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108344E+10 | 44386585.46 |
November | 0.884402E+09 | 0.304713E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104118E+10 | 48206604.63 |
December | 0.919713E+09 | 0.312181E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112906E+10 | 95502531.97 |
Annual Sum or Average | 0.109410E+11 | 0.372078E+11 | 0.963059E+10 | 0.165078E+11 | 0.484584E+09 | ||||
Minimum of Months | 0.835938E+09 | 0.284399E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104118E+10 | 7931940.24 |
Maximum of Months | 0.946926E+09 | 0.321144E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173179E+10 | 95502531.97 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 6976.27 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4854.60 | 04-JAN-13:00 | 1326.85 | 07-JAN-05:00 |
February | 2159.72 | 03-FEB-13:09 | 6976.27 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5340.18 | 28-FEB-15:00 | 330.02 | 01-FEB-07:00 |
March | 2159.72 | 03-MAR-13:09 | 6976.27 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5878.49 | 21-MAR-13:00 | 257.77 | 03-MAR-05:30 |
April | 2159.72 | 01-APR-12:09 | 6976.27 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5322.45 | 01-APR-14:00 | 479.99 | 14-APR-16:00 |
May | 2159.72 | 05-MAY-12:09 | 6976.27 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6360.43 | 06-MAY-13:00 | 248.85 | 17-MAY-02:00 |
June | 2159.72 | 02-JUN-12:09 | 6976.27 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5711.70 | 13-JUN-15:00 | 305.86 | 20-JUN-23:20 |
July | 2159.72 | 01-JUL-12:09 | 6976.27 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4343.88 | 28-JUL-13:00 | 350.56 | 03-JUL-13:00 |
August | 2159.72 | 04-AUG-12:09 | 6976.27 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4803.18 | 27-AUG-14:00 | 855.58 | 20-AUG-11:10 |
September | 2159.72 | 01-SEP-12:09 | 6976.27 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4751.49 | 06-SEP-14:00 | 460.46 | 15-SEP-17:00 |
October | 2159.72 | 01-OCT-12:09 | 6976.27 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4299.55 | 04-OCT-14:00 | 436.15 | 30-OCT-17:00 |
November | 2159.72 | 03-NOV-12:09 | 6976.27 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4834.46 | 18-NOV-13:00 | 319.27 | 25-NOV-08:10 |
December | 2159.72 | 01-DEC-13:09 | 6976.27 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4241.05 | 07-DEC-14:00 | 496.26 | 21-DEC-05:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 6976.27 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4241.05 | 248.85 | |||||
Maximum of Months | 2159.72 | 6976.27 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6360.43 | 1326.85 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 3726.82 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2697.56 | 04-JAN-13:00 | 409.22 | 07-JAN-05:00 |
February | 1079.86 | 03-FEB-13:09 | 3726.82 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2948.34 | 28-FEB-15:00 | 151.41 | 21-FEB-10:00 |
March | 1079.86 | 03-MAR-13:09 | 3726.82 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3266.50 | 21-MAR-13:00 | 111.11 | 15-MAR-08:00 |
April | 1079.86 | 01-APR-12:09 | 3726.82 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2998.75 | 01-APR-14:00 | 269.63 | 14-APR-16:00 |
May | 1079.86 | 05-MAY-12:09 | 3726.82 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3553.67 | 06-MAY-13:00 | 133.72 | 21-MAY-13:00 |
June | 1079.86 | 02-JUN-12:09 | 3726.82 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3173.82 | 13-JUN-15:00 | 132.16 | 30-JUN-13:00 |
July | 1079.86 | 01-JUL-12:09 | 3726.82 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2414.51 | 15-JUL-16:00 | 192.73 | 03-JUL-13:00 |
August | 1079.86 | 04-AUG-12:09 | 3726.82 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2669.00 | 27-AUG-14:00 | 475.42 | 20-AUG-11:10 |
September | 1079.86 | 01-SEP-12:09 | 3726.82 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2654.74 | 06-SEP-14:00 | 250.54 | 15-SEP-17:00 |
October | 1079.86 | 01-OCT-12:09 | 3726.82 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2402.23 | 04-OCT-14:00 | 243.64 | 30-OCT-17:00 |
November | 1079.86 | 03-NOV-12:09 | 3726.82 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2716.16 | 18-NOV-13:00 | 170.05 | 25-NOV-08:10 |
December | 1079.86 | 01-DEC-13:09 | 3726.82 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2382.74 | 07-DEC-14:00 | 192.59 | 21-DEC-08:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3726.82 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2382.74 | 111.11 | |||||
Maximum of Months | 1079.86 | 3726.82 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3553.67 | 475.42 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3370.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2697.55 | 04-JAN-13:00 | 431.18 | 07-JAN-05:00 |
February | 1079.86 | 04-FEB-13:09 | 3370.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2948.30 | 28-FEB-15:00 | 257.28 | 05-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3370.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3266.49 | 21-MAR-13:00 | 212.31 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3370.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2998.74 | 01-APR-14:00 | 339.70 | 09-APR-17:00 |
May | 1079.86 | 06-MAY-12:09 | 3370.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3553.67 | 06-MAY-13:00 | 175.84 | 08-MAY-22:00 |
June | 1079.86 | 03-JUN-12:09 | 3370.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3173.80 | 13-JUN-15:00 | 243.52 | 25-JUN-19:00 |
July | 1079.86 | 01-JUL-12:09 | 3370.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2414.51 | 15-JUL-16:00 | 581.58 | 16-JUL-17:00 |
August | 1079.86 | 05-AUG-12:09 | 3370.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2668.99 | 27-AUG-14:00 | 475.41 | 20-AUG-11:10 |
September | 1079.86 | 02-SEP-12:09 | 3370.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2654.71 | 06-SEP-14:00 | 611.47 | 03-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 3370.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2402.19 | 04-OCT-14:00 | 518.37 | 29-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3370.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2716.20 | 18-NOV-13:00 | 694.18 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3370.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2382.73 | 07-DEC-14:00 | 541.59 | 17-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2382.73 | 175.84 | |||||
Maximum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3553.67 | 694.18 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3370.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2697.55 | 04-JAN-13:00 | 435.90 | 07-JAN-05:00 |
February | 1079.86 | 04-FEB-13:09 | 3370.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2948.30 | 28-FEB-15:00 | 264.31 | 05-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3370.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3266.49 | 21-MAR-13:00 | 217.64 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3370.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2998.73 | 01-APR-14:00 | 346.25 | 09-APR-17:00 |
May | 1079.86 | 06-MAY-12:09 | 3370.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3553.67 | 06-MAY-13:00 | 180.92 | 08-MAY-22:00 |
June | 1079.86 | 03-JUN-12:09 | 3370.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3173.80 | 13-JUN-15:00 | 250.19 | 25-JUN-19:00 |
July | 1079.86 | 01-JUL-12:09 | 3370.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2414.51 | 15-JUL-16:00 | 588.05 | 16-JUL-17:00 |
August | 1079.86 | 05-AUG-12:09 | 3370.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2669.00 | 27-AUG-14:00 | 475.41 | 20-AUG-11:10 |
September | 1079.86 | 02-SEP-12:09 | 3370.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2654.71 | 06-SEP-14:00 | 617.76 | 03-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 3370.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2402.18 | 04-OCT-14:00 | 526.19 | 29-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3370.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2716.20 | 18-NOV-13:00 | 696.22 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3370.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2382.73 | 07-DEC-14:00 | 544.28 | 17-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2382.73 | 180.92 | |||||
Maximum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3553.67 | 696.22 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 3370.57 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2697.55 | 04-JAN-13:00 | 424.29 | 07-JAN-05:00 |
February | 1079.86 | 04-FEB-13:09 | 3370.57 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2948.30 | 28-FEB-15:00 | 255.32 | 05-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 3370.57 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3266.49 | 21-MAR-13:00 | 207.97 | 05-MAR-18:00 |
April | 1079.86 | 01-APR-12:09 | 3370.57 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2998.72 | 01-APR-14:00 | 336.96 | 09-APR-17:00 |
May | 1079.86 | 06-MAY-12:09 | 3370.57 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3553.66 | 06-MAY-13:00 | 173.93 | 08-MAY-22:00 |
June | 1079.86 | 03-JUN-12:09 | 3370.57 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3173.80 | 13-JUN-15:00 | 246.32 | 25-JUN-19:00 |
July | 1079.86 | 01-JUL-12:09 | 3370.57 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2414.50 | 15-JUL-16:00 | 578.90 | 16-JUL-17:00 |
August | 1079.86 | 05-AUG-12:09 | 3370.57 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2668.99 | 27-AUG-14:00 | 475.41 | 20-AUG-11:10 |
September | 1079.86 | 02-SEP-12:09 | 3370.57 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2654.70 | 06-SEP-14:00 | 607.79 | 03-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 3370.57 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2402.17 | 04-OCT-14:00 | 516.76 | 29-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 3370.57 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2716.19 | 18-NOV-13:00 | 685.12 | 26-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 3370.57 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2382.72 | 07-DEC-14:00 | 532.79 | 17-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2382.72 | 173.93 | |||||
Maximum of Months | 1079.86 | 3370.57 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3553.66 | 685.12 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 5255.58 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4738.74 | 04-JAN-13:00 | 795.02 | 07-JAN-05:00 |
February | 2879.63 | 04-FEB-15:09 | 5255.58 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5184.10 | 28-FEB-15:00 | 415.23 | 05-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 5255.58 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5738.23 | 21-MAR-13:00 | 330.06 | 05-MAR-18:00 |
April | 2879.63 | 01-APR-14:09 | 5255.58 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5257.10 | 01-APR-14:00 | 550.16 | 09-APR-17:00 |
May | 2879.63 | 06-MAY-14:09 | 5255.58 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6237.53 | 06-MAY-13:00 | 312.57 | 08-MAY-22:00 |
June | 2879.63 | 03-JUN-14:09 | 5255.58 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5575.39 | 13-JUN-15:00 | 452.95 | 25-JUN-19:00 |
July | 2879.63 | 01-JUL-14:09 | 5255.58 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4240.06 | 28-JUL-13:00 | 982.34 | 16-JUL-17:00 |
August | 2879.63 | 05-AUG-14:09 | 5255.58 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4688.46 | 27-AUG-14:00 | 835.13 | 20-AUG-11:10 |
September | 2879.63 | 02-SEP-14:09 | 5255.58 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4659.63 | 06-SEP-14:00 | 1035.04 | 03-SEP-17:00 |
October | 2879.63 | 07-OCT-14:09 | 5255.58 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4216.36 | 04-OCT-14:00 | 884.64 | 29-OCT-17:00 |
November | 2879.63 | 04-NOV-14:09 | 5255.58 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4763.76 | 18-NOV-13:00 | 1161.39 | 26-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 5255.58 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4178.93 | 07-DEC-14:00 | 887.14 | 17-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 5255.58 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4178.93 | 312.57 | |||||
Maximum of Months | 2879.63 | 5255.58 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6237.53 | 1161.39 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2627.79 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2697.58 | 04-JAN-13:00 | 387.85 | 07-JAN-05:00 |
February | 1439.81 | 04-FEB-15:09 | 2627.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2948.32 | 28-FEB-15:00 | 214.05 | 05-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2627.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3266.54 | 21-MAR-13:00 | 167.42 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2627.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2998.78 | 01-APR-14:00 | 300.15 | 09-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 2627.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3553.66 | 06-MAY-13:00 | 148.42 | 08-MAY-22:00 |
June | 1439.81 | 03-JUN-14:09 | 2627.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3173.92 | 13-JUN-15:00 | 238.82 | 25-JUN-19:00 |
July | 1439.81 | 01-JUL-14:09 | 2627.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2414.56 | 15-JUL-16:00 | 544.08 | 16-JUL-17:00 |
August | 1439.81 | 05-AUG-14:09 | 2627.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2669.02 | 27-AUG-14:00 | 475.40 | 20-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 2627.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2654.72 | 06-SEP-14:00 | 573.65 | 03-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 2627.79 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2402.18 | 04-OCT-14:00 | 479.18 | 29-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2627.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2716.24 | 18-NOV-13:00 | 650.14 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2627.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2382.76 | 07-DEC-14:00 | 497.17 | 17-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2382.76 | 148.42 | |||||
Maximum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3553.66 | 650.14 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2627.79 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2697.58 | 04-JAN-13:00 | 384.14 | 07-JAN-05:00 |
February | 1439.81 | 04-FEB-15:09 | 2627.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2948.32 | 28-FEB-15:00 | 208.44 | 05-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2627.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3266.53 | 21-MAR-13:00 | 161.84 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2627.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2998.78 | 01-APR-14:00 | 295.05 | 09-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 2627.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3553.66 | 06-MAY-13:00 | 147.24 | 08-MAY-22:00 |
June | 1439.81 | 03-JUN-14:09 | 2627.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3173.92 | 13-JUN-15:00 | 237.04 | 25-JUN-19:00 |
July | 1439.81 | 01-JUL-14:09 | 2627.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2414.56 | 15-JUL-16:00 | 539.48 | 16-JUL-17:00 |
August | 1439.81 | 05-AUG-14:09 | 2627.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2669.02 | 27-AUG-14:00 | 475.40 | 20-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 2627.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2654.72 | 06-SEP-14:00 | 569.11 | 03-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 2627.79 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2402.18 | 04-OCT-14:00 | 473.31 | 29-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2627.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2716.24 | 18-NOV-13:00 | 645.37 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2627.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2382.76 | 07-DEC-14:00 | 491.61 | 17-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2382.76 | 147.24 | |||||
Maximum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3553.66 | 645.37 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2627.79 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2697.58 | 04-JAN-13:00 | 378.45 | 07-JAN-05:00 |
February | 1439.81 | 04-FEB-15:09 | 2627.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2948.31 | 28-FEB-15:00 | 206.50 | 05-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2627.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3266.53 | 21-MAR-13:00 | 158.81 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2627.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2998.78 | 01-APR-14:00 | 291.24 | 09-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 2627.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3553.67 | 06-MAY-13:00 | 145.71 | 08-MAY-22:00 |
June | 1439.81 | 03-JUN-14:09 | 2627.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3173.83 | 13-JUN-15:00 | 235.81 | 25-JUN-19:00 |
July | 1439.81 | 01-JUL-14:09 | 2627.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2414.56 | 15-JUL-16:00 | 536.70 | 16-JUL-17:00 |
August | 1439.81 | 05-AUG-14:09 | 2627.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2669.02 | 27-AUG-14:00 | 475.41 | 20-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 2627.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2654.72 | 06-SEP-14:00 | 567.25 | 03-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 2627.79 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2402.17 | 04-OCT-14:00 | 470.29 | 29-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2627.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2716.23 | 18-NOV-13:00 | 637.37 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2627.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2382.75 | 07-DEC-14:00 | 485.20 | 17-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2382.75 | 145.71 | |||||
Maximum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3553.67 | 637.37 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 2627.79 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2813.36 | 04-JAN-13:00 | 837.23 | 07-JAN-05:00 |
February | 1439.81 | 04-FEB-15:09 | 2627.79 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3104.14 | 28-FEB-15:00 | 288.16 | 05-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 2627.79 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3406.73 | 21-MAR-13:00 | 222.70 | 05-MAR-18:00 |
April | 1439.81 | 01-APR-14:09 | 2627.79 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3064.10 | 01-APR-14:00 | 327.38 | 09-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 2627.79 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3676.43 | 06-MAY-13:00 | 364.24 | 08-MAY-22:00 |
June | 1439.81 | 03-JUN-14:09 | 2627.79 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3310.21 | 13-JUN-15:00 | 389.85 | 25-JUN-19:00 |
July | 1439.81 | 01-JUL-14:09 | 2627.79 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2517.39 | 28-JUL-13:00 | 604.38 | 16-JUL-17:00 |
August | 1439.81 | 05-AUG-14:09 | 2627.79 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2783.64 | 27-AUG-14:00 | 495.79 | 20-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 2627.79 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2746.45 | 06-SEP-14:00 | 654.58 | 03-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 2627.79 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2485.16 | 04-OCT-14:00 | 553.84 | 29-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 2627.79 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2787.00 | 18-NOV-13:00 | 684.11 | 26-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 2627.79 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2444.83 | 07-DEC-14:00 | 527.62 | 17-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2444.83 | 222.70 | |||||
Maximum of Months | 1439.81 | 2627.79 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3676.43 | 837.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 34718.56 | 23-JAN-09:01 | 1259.84 | 25702.04 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.65 |
February | 36096.24 | 24-FEB-09:01 | 1439.81 | 29373.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.22 |
March | 33659.00 | 04-MAR-09:01 | 1439.81 | 29373.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 324.20 | 0.00 |
April | 27984.70 | 23-APR-07:02 | 1079.86 | 2203.03 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 |
May | 25459.85 | 14-MAY-07:01 | 1259.84 | 2570.20 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 119.18 | 0.00 |
June | 28337.12 | 25-JUN-07:01 | 1259.84 | 2570.20 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 |
July | 32521.69 | 09-JUL-07:01 | 1259.84 | 2570.20 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 50.88 | 0.00 |
August | 27238.99 | 27-AUG-07:01 | 1259.84 | 2570.20 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 59.07 | 0.00 |
September | 29296.50 | 10-SEP-07:02 | 1079.86 | 2203.03 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 65.23 | 0.00 |
October | 29239.65 | 08-OCT-07:02 | 1079.86 | 2203.03 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 22.27 | 0.00 |
November | 33107.61 | 25-NOV-09:01 | 1259.84 | 25702.04 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.30 |
December | 33845.93 | 27-DEC-09:01 | 1439.81 | 29373.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.79 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 25459.85 | 1079.86 | 2203.03 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36096.24 | 1439.81 | 29373.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 324.20 | 175.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19911.98 | 16-JAN-08:62 | 539.93 | 1176.89 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.80 |
February | 20030.88 | 24-FEB-09:01 | 719.90 | 15691.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 |
March | 18469.68 | 03-MAR-09:01 | 719.90 | 15691.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 54.41 | 0.00 |
April | 17579.28 | 23-APR-07:02 | 539.93 | 1176.89 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 | 0.00 |
May | 16475.30 | 14-MAY-07:01 | 629.92 | 1373.04 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 69.79 | 0.00 |
June | 18057.79 | 25-JUN-07:01 | 629.92 | 1373.04 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 0.00 |
July | 19613.51 | 16-JUL-07:01 | 629.92 | 1373.04 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.18 |
August | 17111.98 | 20-AUG-07:02 | 539.93 | 1176.89 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.48 |
September | 18157.41 | 10-SEP-07:02 | 539.93 | 1176.89 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 41.90 | 0.00 |
October | 18221.52 | 08-OCT-07:02 | 539.93 | 1176.89 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 0.00 |
November | 18476.73 | 25-NOV-09:01 | 629.92 | 13730.40 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.78 |
December | 18892.66 | 27-DEC-09:01 | 719.90 | 15691.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 16475.30 | 539.93 | 1176.89 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20030.88 | 719.90 | 15691.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 69.79 | 119.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17351.23 | 24-JAN-08:62 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.57 |
February | 17858.15 | 24-FEB-08:61 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.32 |
March | 16946.31 | 04-MAR-08:61 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 24.12 | 0.00 |
April | 13614.03 | 27-APR-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 40.11 | 0.00 |
May | 12200.37 | 09-MAY-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.73 |
June | 12567.24 | 27-JUN-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.40 |
July | 14299.85 | 06-JUL-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 |
August | 12809.15 | 30-AUG-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.63 |
September | 12652.25 | 16-SEP-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.73 |
October | 12837.70 | 27-OCT-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.64 |
November | 16729.71 | 25-NOV-08:61 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.46 |
December | 17045.14 | 21-DEC-08:62 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.13 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12200.37 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17858.15 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 40.11 | 207.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17430.58 | 24-JAN-08:62 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.08 |
February | 17937.65 | 24-FEB-08:61 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.60 |
March | 17003.85 | 04-MAR-08:61 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 24.20 | 0.00 |
April | 13678.73 | 27-APR-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 0.00 |
May | 12318.63 | 09-MAY-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.76 |
June | 12644.19 | 27-JUN-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 |
July | 14390.60 | 06-JUL-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 |
August | 12883.02 | 30-AUG-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.52 |
September | 12785.92 | 13-SEP-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 0.00 |
October | 12887.70 | 27-OCT-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.59 |
November | 16804.60 | 25-NOV-08:61 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.82 |
December | 17102.22 | 27-DEC-08:61 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.42 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12318.63 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17937.65 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 209.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17298.88 | 24-JAN-08:62 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.00 |
February | 17786.30 | 24-FEB-08:61 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.22 |
March | 16889.15 | 04-MAR-08:61 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 24.14 | 0.00 |
April | 13553.50 | 27-APR-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 40.12 | 0.00 |
May | 12197.05 | 09-MAY-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.80 |
June | 12527.77 | 27-JUN-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.39 |
July | 14268.45 | 06-JUL-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 |
August | 12750.97 | 30-AUG-07:01 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.65 |
September | 12577.69 | 13-SEP-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 11.02 | 0.00 |
October | 12745.09 | 27-OCT-07:01 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.56 |
November | 16659.23 | 25-NOV-08:61 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.11 |
December | 16968.78 | 27-DEC-08:61 | 629.92 | 12417.90 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.25 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12197.05 | 449.94 | 8869.93 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17786.30 | 719.90 | 14191.88 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 40.12 | 206.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32435.08 | 24-JAN-09:02 | 1979.74 | 13830.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.71 |
February | 33790.78 | 25-FEB-09:01 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.57 |
March | 31800.15 | 04-MAR-09:01 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 276.84 | 0.00 |
April | 25268.97 | 27-APR-08:61 | 2771.64 | 19362.66 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 163.09 | 0.00 |
May | 22010.94 | 11-MAY-08:61 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 125.78 | 0.00 |
June | 23775.75 | 21-JUN-08:61 | 2771.64 | 19362.66 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 137.12 | 0.00 |
July | 26393.42 | 06-JUL-08:61 | 2771.64 | 19362.66 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 44.47 | 0.00 |
August | 23220.67 | 30-AUG-08:61 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 78.92 | 0.00 |
September | 23494.53 | 13-SEP-08:61 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 183.01 | 0.00 |
October | 25178.63 | 20-OCT-08:61 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 108.42 | 0.00 |
November | 30873.56 | 25-NOV-09:01 | 2771.64 | 19362.66 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.05 |
December | 32240.14 | 27-DEC-09:01 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.19 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 22010.94 | 1979.74 | 13830.47 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33790.78 | 3167.59 | 22128.76 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 276.84 | 396.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16983.17 | 24-JAN-09:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.05 |
February | 17725.39 | 25-FEB-09:01 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 |
March | 16680.16 | 04-MAR-09:01 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 155.37 | 0.00 |
April | 13279.95 | 27-APR-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 92.50 | 0.00 |
May | 11543.23 | 11-MAY-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 75.21 | 0.00 |
June | 12480.43 | 21-JUN-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 78.76 | 0.00 |
July | 13884.83 | 06-JUL-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 26.21 | 0.00 |
August | 12202.04 | 30-AUG-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 45.53 | 0.00 |
September | 12398.52 | 13-SEP-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 100.08 | 0.00 |
October | 13205.71 | 20-OCT-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 62.09 | 0.00 |
November | 16196.69 | 25-NOV-09:01 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.89 |
December | 16930.73 | 27-DEC-09:01 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14.91 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11543.23 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17725.39 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 155.37 | 223.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16871.68 | 24-JAN-09:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.89 |
February | 17621.97 | 25-FEB-09:01 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.18 |
March | 16580.93 | 04-MAR-09:01 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 155.24 | 0.00 |
April | 13190.14 | 27-APR-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 92.33 | 0.00 |
May | 11447.62 | 11-MAY-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 75.10 | 0.00 |
June | 12391.10 | 21-JUN-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 78.61 | 0.00 |
July | 13792.19 | 06-JUL-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 26.05 | 0.00 |
August | 12107.32 | 30-AUG-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 45.43 | 0.00 |
September | 12267.03 | 13-SEP-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 104.09 | 0.00 |
October | 13108.29 | 20-OCT-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 61.96 | 0.00 |
November | 16084.90 | 25-NOV-09:01 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.71 |
December | 16830.07 | 27-DEC-09:01 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11447.62 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17621.97 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 155.24 | 221.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16818.08 | 24-JAN-09:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.56 |
February | 17602.44 | 25-FEB-09:01 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.15 |
March | 16555.27 | 04-MAR-09:01 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 155.29 | 0.00 |
April | 13168.35 | 27-APR-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 92.36 | 0.00 |
May | 11414.88 | 11-MAY-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 75.12 | 0.00 |
June | 12363.01 | 21-JUN-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 78.63 | 0.00 |
July | 13772.37 | 06-JUL-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 26.08 | 0.00 |
August | 12081.25 | 30-AUG-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 45.47 | 0.00 |
September | 12245.05 | 13-SEP-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 104.11 | 0.00 |
October | 13068.24 | 20-OCT-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 61.96 | 0.00 |
November | 16031.02 | 25-NOV-09:01 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.41 |
December | 16803.56 | 27-DEC-09:01 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11414.88 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17602.44 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 155.29 | 219.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17786.99 | 24-JAN-09:02 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.09 |
February | 18529.81 | 24-FEB-09:01 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.04 |
March | 17432.96 | 04-MAR-09:01 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 201.33 | 0.00 |
April | 13407.68 | 27-APR-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 111.48 | 0.00 |
May | 11867.70 | 06-MAY-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 355.74 | 0.00 |
June | 12614.17 | 21-JUN-08:61 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 84.23 | 0.00 |
July | 14902.26 | 19-JUL-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 23.28 | 0.00 |
August | 12396.65 | 30-AUG-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 51.63 | 0.00 |
September | 12605.66 | 13-SEP-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 118.39 | 0.00 |
October | 13425.01 | 20-OCT-08:61 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 72.20 | 0.00 |
November | 16965.33 | 25-NOV-09:01 | 1385.82 | 9681.33 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.53 |
December | 17592.22 | 27-DEC-09:01 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11867.70 | 989.87 | 6915.24 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18529.81 | 1583.79 | 11064.38 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 355.74 | 239.09 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.157943E+12 | 131562.98 | 04-JAN-12:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.146722E+12 | 135711.72 | 13-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.167347E+12 | 136234.65 | 28-MAR-13:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.166768E+12 | 139504.03 | 01-APR-12:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.177548E+12 | 145506.62 | 06-MAY-14:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.174259E+12 | 147535.24 | 14-JUN-14:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.162037E+12 | 132018.77 | 28-JUL-12:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.171350E+12 | 143311.21 | 13-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.163327E+12 | 137400.26 | 30-SEP-11:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.164087E+12 | 134700.20 | 28-OCT-13:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.156782E+12 | 132939.29 | 10-NOV-13:39 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.157613E+12 | 132842.62 | 10-DEC-13:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.196578E+13 | 0.00 | ||||
Minimum of Months | 0.146722E+12 | 131562.98 | 0.00 | 0.00 | ||
Maximum of Months | 0.177548E+12 | 147535.24 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.496324E+11 | 0.987901E+10 | 0.108804E+11 | 0.00 | 0.211472E+11 | 0.00 | 0.00 | 0.614800E+11 | 0.00 | 0.00 | 0.00 | 0.492407E+10 | 0.00 |
February | 0.449372E+11 | 0.878369E+10 | 0.985143E+10 | 0.00 | 0.191493E+11 | 0.00 | 0.00 | 0.595494E+11 | 0.00 | 0.00 | 0.00 | 0.445079E+10 | 0.00 |
March | 0.503750E+11 | 0.942651E+10 | 0.110523E+11 | 0.00 | 0.214992E+11 | 0.00 | 0.00 | 0.700573E+11 | 0.00 | 0.00 | 0.00 | 0.493658E+10 | 0.00 |
April | 0.481627E+11 | 0.890634E+10 | 0.105581E+11 | 0.00 | 0.205505E+11 | 0.00 | 0.00 | 0.738528E+11 | 0.00 | 0.00 | 0.00 | 0.473770E+10 | 0.00 |
May | 0.499854E+11 | 0.904589E+10 | 0.109629E+11 | 0.00 | 0.213599E+11 | 0.00 | 0.00 | 0.813135E+11 | 0.00 | 0.00 | 0.00 | 0.488051E+10 | 0.00 |
June | 0.486922E+11 | 0.865259E+10 | 0.106818E+11 | 0.00 | 0.208093E+11 | 0.00 | 0.00 | 0.807025E+11 | 0.00 | 0.00 | 0.00 | 0.472096E+10 | 0.00 |
July | 0.494924E+11 | 0.901206E+10 | 0.108460E+11 | 0.00 | 0.210950E+11 | 0.00 | 0.00 | 0.667433E+11 | 0.00 | 0.00 | 0.00 | 0.484862E+10 | 0.00 |
August | 0.503385E+11 | 0.912625E+10 | 0.110454E+11 | 0.00 | 0.215056E+11 | 0.00 | 0.00 | 0.744495E+11 | 0.00 | 0.00 | 0.00 | 0.488425E+10 | 0.00 |
September | 0.481992E+11 | 0.905858E+10 | 0.105649E+11 | 0.00 | 0.205547E+11 | 0.00 | 0.00 | 0.702288E+11 | 0.00 | 0.00 | 0.00 | 0.472112E+10 | 0.00 |
October | 0.496324E+11 | 0.960413E+10 | 0.108804E+11 | 0.00 | 0.211661E+11 | 0.00 | 0.00 | 0.679116E+11 | 0.00 | 0.00 | 0.00 | 0.489196E+10 | 0.00 |
November | 0.480897E+11 | 0.948148E+10 | 0.105443E+11 | 0.00 | 0.205109E+11 | 0.00 | 0.00 | 0.634026E+11 | 0.00 | 0.00 | 0.00 | 0.475301E+10 | 0.00 |
December | 0.495289E+11 | 0.994245E+10 | 0.108529E+11 | 0.00 | 0.210851E+11 | 0.00 | 0.00 | 0.612799E+11 | 0.00 | 0.00 | 0.00 | 0.492387E+10 | 0.00 |
Annual Sum or Average | 0.587066E+12 | 0.110919E+12 | 0.128721E+12 | 0.250433E+12 | 0.00 | 0.830971E+12 | 0.576734E+11 | ||||||
Minimum of Months | 0.449372E+11 | 0.865259E+10 | 0.985143E+10 | 0.00 | 0.191493E+11 | 0.00 | 0.00 | 0.595494E+11 | 0.00 | 0.00 | 0.00 | 0.445079E+10 | 0.00 |
Maximum of Months | 0.503750E+11 | 0.994245E+10 | 0.110523E+11 | 0.00 | 0.215056E+11 | 0.00 | 0.00 | 0.813135E+11 | 0.00 | 0.00 | 0.00 | 0.493658E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 36581.55 | 01-JAN-11:09 | 7048.38 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 14505.13 | 01-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 36581.55 | 01-FEB-10:09 | 7048.38 | 01-FEB-00:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 14505.13 | 01-FEB-08:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 36581.55 | 01-MAR-10:09 | 7048.38 | 01-MAR-00:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 14505.13 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 36581.55 | 01-APR-09:09 | 7048.38 | 01-APR-00:10 | 8089.53 | 01-APR-09:09 | 0.00 | 14505.13 | 01-APR-07:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 36581.55 | 01-MAY-09:09 | 7048.38 | 01-MAY-00:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 14505.13 | 01-MAY-07:19 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 36581.55 | 01-JUN-09:09 | 7048.38 | 01-JUN-00:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 14505.13 | 01-JUN-07:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 36581.55 | 01-JUL-09:09 | 7048.38 | 01-JUL-00:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 14505.13 | 01-JUL-07:19 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 36581.55 | 01-AUG-09:09 | 7048.38 | 01-AUG-00:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 14505.13 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 36581.55 | 01-SEP-09:09 | 7048.38 | 01-SEP-00:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 14505.13 | 01-SEP-07:19 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 36581.55 | 01-OCT-10:09 | 7048.38 | 01-OCT-00:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 14505.13 | 01-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 36581.55 | 01-NOV-09:09 | 7048.38 | 01-NOV-00:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 14505.13 | 01-NOV-07:19 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 36581.55 | 01-DEC-10:09 | 7048.38 | 01-DEC-00:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 14505.13 | 01-DEC-08:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 36581.55 | 7048.38 | 8089.53 | 0.00 | 14505.13 | 0.00 | 0.00 | |||||
Maximum of Months | 36581.55 | 7048.38 | 8089.53 | 0.00 | 14505.13 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 64502.69 | 04-JAN-13:09 | 0.00 | 0.00 | 0.00 | 11776.24 | 31-JAN-13:20 | 0.00 |
February | 69879.46 | 13-FEB-14:00 | 0.00 | 0.00 | 0.00 | 10816.68 | 06-FEB-14:39 | 0.00 |
March | 72296.63 | 27-MAR-12:00 | 0.00 | 0.00 | 0.00 | 7746.73 | 28-MAR-13:09 | 0.00 |
April | 76106.87 | 01-APR-13:00 | 0.00 | 0.00 | 0.00 | 8631.03 | 03-APR-13:00 | 0.00 |
May | 83273.45 | 04-MAY-12:00 | 0.00 | 0.00 | 0.00 | 9660.77 | 12-MAY-12:09 | 0.00 |
June | 84125.44 | 16-JUN-12:00 | 0.00 | 0.00 | 0.00 | 9653.73 | 03-JUN-13:30 | 0.00 |
July | 68378.27 | 28-JUL-12:00 | 0.00 | 0.00 | 0.00 | 11015.64 | 18-JUL-16:30 | 0.00 |
August | 78957.74 | 13-AUG-14:09 | 0.00 | 0.00 | 0.00 | 9654.80 | 25-AUG-13:00 | 0.00 |
September | 74898.87 | 30-SEP-11:39 | 0.00 | 0.00 | 0.00 | 7546.73 | 14-SEP-13:30 | 0.00 |
October | 70425.43 | 28-OCT-12:00 | 0.00 | 0.00 | 0.00 | 8160.15 | 17-OCT-12:20 | 0.00 |
November | 68958.03 | 18-NOV-12:00 | 0.00 | 0.00 | 0.00 | 8760.02 | 24-NOV-11:30 | 0.00 |
December | 64863.91 | 30-DEC-13:00 | 0.00 | 0.00 | 0.00 | 11540.08 | 16-DEC-13:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 64502.69 | 0.00 | 0.00 | 0.00 | 7546.73 | 0.00 | ||
Maximum of Months | 84125.44 | 0.00 | 0.00 | 0.00 | 11776.24 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 131562.98 | 04-JAN-12:20 | 36581.55 | 8089.53 | 0.00 | 0.00 | 14505.13 | 0.00 | 0.00 | 61254.74 | 0.00 |
February | 135711.72 | 13-FEB-15:30 | 36581.55 | 8089.53 | 0.00 | 0.00 | 14505.13 | 0.00 | 0.00 | 68997.97 | 0.00 |
March | 136234.65 | 28-MAR-13:09 | 36581.55 | 8089.53 | 0.00 | 0.00 | 14505.13 | 0.00 | 0.00 | 69311.71 | 0.00 |
April | 139504.03 | 01-APR-12:30 | 36581.55 | 8089.53 | 0.00 | 0.00 | 14505.13 | 0.00 | 0.00 | 72777.22 | 0.00 |
May | 145506.62 | 06-MAY-14:20 | 36581.55 | 8089.53 | 0.00 | 0.00 | 14505.13 | 0.00 | 0.00 | 81763.80 | 0.00 |
June | 147535.24 | 14-JUN-14:09 | 36581.55 | 8089.53 | 0.00 | 0.00 | 14505.13 | 0.00 | 0.00 | 78717.30 | 0.00 |
July | 132018.77 | 28-JUL-12:50 | 36581.55 | 8089.53 | 0.00 | 0.00 | 14505.13 | 0.00 | 0.00 | 67405.53 | 0.00 |
August | 143311.21 | 13-AUG-13:00 | 36581.55 | 8089.53 | 0.00 | 0.00 | 14505.13 | 0.00 | 0.00 | 78717.91 | 0.00 |
September | 137400.26 | 30-SEP-11:39 | 36581.55 | 8089.53 | 0.00 | 0.00 | 14505.13 | 0.00 | 0.00 | 74898.87 | 0.00 |
October | 134700.20 | 28-OCT-13:09 | 36581.55 | 8089.53 | 0.00 | 0.00 | 14505.13 | 0.00 | 0.00 | 69320.29 | 0.00 |
November | 132939.29 | 10-NOV-13:39 | 36581.55 | 8089.53 | 0.00 | 0.00 | 14505.13 | 0.00 | 0.00 | 67380.23 | 0.00 |
December | 132842.62 | 10-DEC-13:00 | 36581.55 | 8089.53 | 0.00 | 0.00 | 14505.13 | 0.00 | 0.00 | 64762.95 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 131562.98 | 36581.55 | 8089.53 | 0.00 | 0.00 | 14505.13 | 0.00 | 0.00 | 61254.74 | 0.00 | |
Maximum of Months | 147535.24 | 36581.55 | 8089.53 | 0.00 | 0.00 | 14505.13 | 0.00 | 0.00 | 81763.80 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.48 | 1.00 | 24.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.49 | 0.33 | 24.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.48 | 3.50 | 24.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.55 | 4.67 | 24.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.68 | 4.83 | 24.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.70 | 4.67 | 24.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.48 | 2.50 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.67 | 4.67 | 24.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.57 | 4.33 | 24.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.54 | 4.17 | 24.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.51 | 3.00 | 24.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.48 | 1.50 | 24.48 |
Annual Sum or Average | 0.00 | 0.00 | 39.17 | 24.58 | 39.17 | 24.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.33 | 24.48 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.70 | 4.83 | 24.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.46 | 0.50 | 24.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.48 | 3.00 | 24.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.55 | 4.67 | 24.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.56 | 4.33 | 24.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.55 | 4.17 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.50 | 2.33 | 24.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.47 | 2.00 | 24.47 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.45 | 0.83 | 24.45 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.17 | 24.48 |
Annual Sum or Average | 0.00 | 0.00 | 22.00 | 24.52 | 22.00 | 24.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.56 | 4.67 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.49 | 1.50 | 24.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.48 | 1.50 | 24.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.51 | 3.67 | 24.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.55 | 5.00 | 24.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.71 | 4.83 | 24.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.70 | 5.00 | 24.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.50 | 5.00 | 24.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.63 | 5.17 | 24.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.59 | 5.00 | 24.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.56 | 5.17 | 24.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.51 | 4.50 | 24.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.50 | 2.67 | 24.50 |
Annual Sum or Average | 0.00 | 0.00 | 49.00 | 24.57 | 49.00 | 24.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.48 | 1.50 | 24.48 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.71 | 5.17 | 24.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.49 | 1.17 | 24.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.48 | 1.33 | 24.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.49 | 3.17 | 24.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.55 | 5.00 | 24.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.71 | 5.00 | 24.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.70 | 5.00 | 24.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.50 | 5.00 | 24.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.62 | 5.17 | 24.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.59 | 5.00 | 24.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.55 | 5.17 | 24.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.51 | 4.50 | 24.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.51 | 2.67 | 24.51 |
Annual Sum or Average | 0.00 | 0.00 | 48.17 | 24.58 | 48.17 | 24.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.48 | 1.17 | 24.48 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.71 | 5.17 | 24.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.49 | 1.50 | 24.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.48 | 1.50 | 24.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.50 | 3.67 | 24.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.56 | 5.00 | 24.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.72 | 5.00 | 24.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.70 | 5.00 | 24.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.51 | 5.00 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.63 | 5.17 | 24.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.60 | 5.00 | 24.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.57 | 5.17 | 24.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.51 | 4.33 | 24.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.51 | 2.83 | 24.51 |
Annual Sum or Average | 0.00 | 0.00 | 49.17 | 24.58 | 49.17 | 24.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.48 | 1.50 | 24.48 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.72 | 5.17 | 24.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.50 | 2.67 | 24.50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.51 | 2.33 | 24.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.52 | 4.83 | 24.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.63 | 5.00 | 24.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.80 | 5.00 | 24.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.78 | 4.50 | 24.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.55 | 5.17 | 24.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.76 | 4.83 | 24.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.65 | 4.67 | 24.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.63 | 5.17 | 24.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.56 | 4.83 | 24.56 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.53 | 3.67 | 24.53 |
Annual Sum or Average | 0.00 | 0.00 | 52.67 | 24.63 | 52.67 | 24.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.50 | 2.33 | 24.50 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.80 | 5.17 | 24.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.49 | 2.00 | 24.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.50 | 1.83 | 24.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.50 | 4.33 | 24.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.59 | 5.00 | 24.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.76 | 5.17 | 24.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.73 | 4.83 | 24.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.53 | 4.83 | 24.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.72 | 5.17 | 24.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.64 | 5.00 | 24.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.60 | 5.17 | 24.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.53 | 4.83 | 24.53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.53 | 2.83 | 24.53 |
Annual Sum or Average | 0.00 | 0.00 | 51.00 | 24.61 | 51.00 | 24.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.49 | 1.83 | 24.49 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.76 | 5.17 | 24.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.48 | 2.00 | 24.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.50 | 1.83 | 24.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.50 | 4.33 | 24.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.61 | 5.00 | 24.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.76 | 5.17 | 24.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.74 | 4.83 | 24.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.52 | 5.00 | 24.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.73 | 5.17 | 24.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.64 | 5.00 | 24.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.60 | 5.17 | 24.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.54 | 4.83 | 24.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.53 | 3.00 | 24.53 |
Annual Sum or Average | 0.00 | 0.00 | 51.33 | 24.61 | 51.33 | 24.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.48 | 1.83 | 24.48 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.76 | 5.17 | 24.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.49 | 2.17 | 24.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.50 | 1.83 | 24.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.50 | 4.33 | 24.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.60 | 5.00 | 24.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.76 | 5.17 | 24.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.74 | 4.83 | 24.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.53 | 5.00 | 24.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.73 | 5.17 | 24.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.64 | 5.00 | 24.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.60 | 5.17 | 24.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.53 | 4.50 | 24.53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.53 | 3.00 | 24.53 |
Annual Sum or Average | 0.00 | 0.00 | 51.17 | 24.61 | 51.17 | 24.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.49 | 1.83 | 24.49 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.76 | 5.17 | 24.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.47 | 1.67 | 24.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.49 | 1.67 | 24.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.49 | 4.00 | 24.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.60 | 5.00 | 24.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.77 | 5.00 | 24.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.76 | 5.00 | 24.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.53 | 3.67 | 24.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.72 | 5.17 | 24.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.63 | 5.00 | 24.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.59 | 5.17 | 24.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.53 | 4.17 | 24.53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.51 | 2.50 | 24.51 |
Annual Sum or Average | 0.00 | 0.00 | 48.00 | 24.62 | 48.00 | 24.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.47 | 1.67 | 24.47 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.77 | 5.17 | 24.77 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.17 | 25.18 | 496.00 | 23.98 | 28.17 | 25.18 |
February | 17.00 | 25.16 | 448.00 | 23.98 | 17.00 | 25.16 |
March | 43.17 | 25.11 | 496.00 | 23.99 | 43.17 | 25.11 |
April | 96.33 | 24.39 | 480.00 | 23.99 | 96.33 | 24.39 |
May | 241.67 | 24.12 | 496.00 | 24.00 | 241.67 | 24.12 |
June | 238.67 | 24.11 | 480.00 | 24.00 | 238.67 | 24.11 |
July | 81.17 | 24.42 | 496.00 | 23.98 | 81.17 | 24.42 |
August | 289.67 | 24.08 | 496.00 | 24.00 | 289.67 | 24.08 |
September | 224.83 | 24.09 | 480.00 | 23.98 | 224.83 | 24.09 |
October | 235.67 | 24.10 | 496.00 | 23.99 | 235.67 | 24.10 |
November | 116.83 | 24.31 | 480.00 | 23.99 | 116.83 | 24.31 |
December | 52.17 | 24.54 | 496.00 | 23.97 | 52.17 | 24.54 |
Annual Sum or Average | 1665.33 | 24.21 | 5840.00 | 23.99 | 1665.33 | 24.21 |
Minimum of Months | 17.00 | 24.08 | 448.00 | 23.97 | 17.00 | 24.08 |
Maximum of Months | 289.67 | 25.18 | 496.00 | 24.00 | 289.67 | 25.18 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.67 | 24.86 | 496.00 | 23.98 | 7.67 | 24.86 |
February | 4.00 | 24.85 | 448.00 | 23.98 | 4.00 | 24.85 |
March | 25.33 | 25.39 | 496.00 | 23.99 | 25.33 | 25.39 |
April | 81.67 | 24.39 | 480.00 | 23.99 | 81.67 | 24.39 |
May | 218.83 | 24.11 | 496.00 | 24.00 | 218.83 | 24.11 |
June | 228.17 | 24.08 | 480.00 | 23.99 | 228.17 | 24.08 |
July | 60.00 | 24.08 | 496.00 | 23.98 | 60.00 | 24.08 |
August | 272.83 | 24.05 | 496.00 | 24.00 | 272.83 | 24.05 |
September | 208.00 | 24.03 | 480.00 | 23.98 | 208.00 | 24.03 |
October | 203.83 | 24.03 | 496.00 | 23.99 | 203.83 | 24.03 |
November | 96.00 | 24.09 | 480.00 | 23.99 | 96.00 | 24.09 |
December | 29.83 | 24.07 | 495.67 | 23.97 | 29.83 | 24.07 |
Annual Sum or Average | 1436.17 | 24.11 | 5839.67 | 23.99 | 1436.17 | 24.11 |
Minimum of Months | 4.00 | 24.03 | 448.00 | 23.97 | 4.00 | 24.03 |
Maximum of Months | 272.83 | 25.39 | 496.00 | 24.00 | 272.83 | 25.39 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.83 | 25.06 | 371.00 | 24.12 | 32.83 | 25.06 |
February | 30.00 | 25.34 | 336.00 | 24.13 | 30.00 | 25.34 |
March | 39.83 | 25.14 | 379.00 | 24.13 | 39.83 | 25.14 |
April | 102.67 | 24.64 | 360.00 | 24.15 | 102.67 | 24.64 |
May | 230.33 | 24.29 | 375.00 | 24.15 | 230.33 | 24.29 |
June | 241.17 | 24.26 | 366.00 | 24.15 | 241.17 | 24.26 |
July | 101.83 | 24.56 | 369.00 | 24.14 | 101.83 | 24.56 |
August | 295.00 | 24.17 | 379.00 | 24.12 | 295.00 | 24.17 |
September | 235.83 | 24.23 | 360.00 | 24.13 | 235.83 | 24.23 |
October | 238.83 | 24.22 | 371.00 | 24.12 | 238.83 | 24.22 |
November | 130.00 | 24.40 | 360.00 | 24.11 | 130.00 | 24.40 |
December | 65.00 | 24.71 | 369.00 | 24.11 | 65.00 | 24.71 |
Annual Sum or Average | 1743.33 | 24.36 | 4395.00 | 24.13 | 1743.33 | 24.36 |
Minimum of Months | 30.00 | 24.17 | 336.00 | 24.11 | 30.00 | 24.17 |
Maximum of Months | 295.00 | 25.34 | 379.00 | 24.15 | 295.00 | 25.34 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.33 | 25.10 | 371.00 | 24.12 | 32.33 | 25.10 |
February | 29.50 | 25.36 | 336.00 | 24.13 | 29.50 | 25.36 |
March | 39.50 | 25.15 | 379.00 | 24.13 | 39.50 | 25.15 |
April | 100.83 | 24.65 | 360.00 | 24.15 | 100.83 | 24.65 |
May | 227.33 | 24.30 | 375.00 | 24.15 | 227.33 | 24.30 |
June | 238.33 | 24.26 | 366.00 | 24.15 | 238.33 | 24.26 |
July | 99.00 | 24.59 | 369.00 | 24.14 | 99.00 | 24.59 |
August | 293.00 | 24.17 | 379.00 | 24.12 | 293.00 | 24.17 |
September | 233.67 | 24.24 | 360.00 | 24.13 | 233.67 | 24.24 |
October | 237.00 | 24.23 | 371.00 | 24.12 | 237.00 | 24.23 |
November | 129.67 | 24.41 | 360.00 | 24.11 | 129.67 | 24.41 |
December | 63.67 | 24.73 | 369.00 | 24.11 | 63.67 | 24.73 |
Annual Sum or Average | 1723.83 | 24.37 | 4395.00 | 24.13 | 1723.83 | 24.37 |
Minimum of Months | 29.50 | 24.17 | 336.00 | 24.11 | 29.50 | 24.17 |
Maximum of Months | 293.00 | 25.36 | 379.00 | 24.15 | 293.00 | 25.36 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.50 | 25.05 | 371.00 | 24.12 | 33.50 | 25.05 |
February | 30.17 | 25.26 | 336.00 | 24.13 | 30.17 | 25.26 |
March | 39.83 | 25.12 | 379.00 | 24.13 | 39.83 | 25.12 |
April | 104.33 | 24.62 | 360.00 | 24.15 | 104.33 | 24.62 |
May | 231.50 | 24.28 | 375.00 | 24.15 | 231.50 | 24.28 |
June | 242.83 | 24.25 | 366.00 | 24.15 | 242.83 | 24.25 |
July | 103.33 | 24.56 | 369.00 | 24.13 | 103.33 | 24.56 |
August | 300.00 | 24.16 | 379.00 | 24.12 | 300.00 | 24.16 |
September | 237.67 | 24.23 | 360.00 | 24.13 | 237.67 | 24.23 |
October | 242.67 | 24.22 | 371.00 | 24.12 | 242.67 | 24.22 |
November | 135.33 | 24.38 | 360.00 | 24.11 | 135.33 | 24.38 |
December | 66.17 | 24.69 | 369.00 | 24.11 | 66.17 | 24.69 |
Annual Sum or Average | 1767.33 | 24.35 | 4395.00 | 24.13 | 1767.33 | 24.35 |
Minimum of Months | 30.17 | 24.16 | 336.00 | 24.11 | 30.17 | 24.16 |
Maximum of Months | 300.00 | 25.26 | 379.00 | 24.15 | 300.00 | 25.26 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.50 | 24.75 | 340.00 | 23.98 | 25.50 | 24.75 |
February | 23.67 | 24.89 | 308.00 | 23.99 | 23.67 | 24.89 |
March | 29.33 | 24.67 | 348.00 | 23.97 | 29.33 | 24.67 |
April | 104.67 | 24.24 | 330.00 | 24.00 | 104.67 | 24.24 |
May | 239.67 | 24.04 | 344.00 | 24.00 | 239.67 | 24.04 |
June | 253.50 | 24.02 | 336.00 | 23.99 | 253.50 | 24.02 |
July | 109.17 | 24.21 | 338.00 | 24.00 | 109.17 | 24.21 |
August | 307.83 | 23.98 | 348.00 | 23.97 | 307.83 | 23.98 |
September | 254.33 | 24.02 | 330.00 | 23.99 | 254.33 | 24.02 |
October | 251.33 | 24.02 | 340.00 | 23.99 | 251.33 | 24.02 |
November | 140.17 | 24.08 | 330.00 | 23.97 | 140.17 | 24.08 |
December | 58.17 | 24.39 | 338.00 | 23.99 | 58.17 | 24.39 |
Annual Sum or Average | 1797.33 | 24.09 | 4030.00 | 23.99 | 1797.33 | 24.09 |
Minimum of Months | 23.67 | 23.98 | 308.00 | 23.97 | 23.67 | 23.98 |
Maximum of Months | 307.83 | 24.89 | 348.00 | 24.00 | 307.83 | 24.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.83 | 24.70 | 340.00 | 23.98 | 25.83 | 24.70 |
February | 26.17 | 24.78 | 308.00 | 23.99 | 26.17 | 24.78 |
March | 29.50 | 24.63 | 348.00 | 23.97 | 29.50 | 24.63 |
April | 110.50 | 24.21 | 330.00 | 24.00 | 110.50 | 24.21 |
May | 241.33 | 24.04 | 344.00 | 23.99 | 241.33 | 24.04 |
June | 256.67 | 24.01 | 336.00 | 23.98 | 256.67 | 24.01 |
July | 116.67 | 24.18 | 338.00 | 24.00 | 116.67 | 24.18 |
August | 304.50 | 23.98 | 348.00 | 23.97 | 304.50 | 23.98 |
September | 254.83 | 24.02 | 330.00 | 23.99 | 254.83 | 24.02 |
October | 255.67 | 24.02 | 340.00 | 23.99 | 255.67 | 24.02 |
November | 146.00 | 24.07 | 330.00 | 23.97 | 146.00 | 24.07 |
December | 60.17 | 24.38 | 338.00 | 23.99 | 60.17 | 24.38 |
Annual Sum or Average | 1827.83 | 24.08 | 4030.00 | 23.99 | 1827.83 | 24.08 |
Minimum of Months | 25.83 | 23.98 | 308.00 | 23.97 | 25.83 | 23.98 |
Maximum of Months | 304.50 | 24.78 | 348.00 | 24.00 | 304.50 | 24.78 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.33 | 24.68 | 340.00 | 23.98 | 26.33 | 24.68 |
February | 27.00 | 24.75 | 308.00 | 23.99 | 27.00 | 24.75 |
March | 30.00 | 24.62 | 348.00 | 23.97 | 30.00 | 24.62 |
April | 112.67 | 24.21 | 330.00 | 24.00 | 112.67 | 24.21 |
May | 245.00 | 24.04 | 344.00 | 23.99 | 245.00 | 24.04 |
June | 260.33 | 24.01 | 336.00 | 23.98 | 260.33 | 24.01 |
July | 120.17 | 24.18 | 338.00 | 24.00 | 120.17 | 24.18 |
August | 307.67 | 23.98 | 348.00 | 23.97 | 307.67 | 23.98 |
September | 259.67 | 24.02 | 330.00 | 23.99 | 259.67 | 24.02 |
October | 258.33 | 24.02 | 340.00 | 23.99 | 258.33 | 24.02 |
November | 150.17 | 24.07 | 330.00 | 23.97 | 150.17 | 24.07 |
December | 61.33 | 24.36 | 338.00 | 23.98 | 61.33 | 24.36 |
Annual Sum or Average | 1858.67 | 24.08 | 4030.00 | 23.98 | 1858.67 | 24.08 |
Minimum of Months | 26.33 | 23.98 | 308.00 | 23.97 | 26.33 | 23.98 |
Maximum of Months | 307.67 | 24.75 | 348.00 | 24.00 | 307.67 | 24.75 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.50 | 24.67 | 340.00 | 23.98 | 26.50 | 24.67 |
February | 27.67 | 24.72 | 308.00 | 23.99 | 27.67 | 24.72 |
March | 30.33 | 24.61 | 348.00 | 23.97 | 30.33 | 24.61 |
April | 113.00 | 24.21 | 330.00 | 24.00 | 113.00 | 24.21 |
May | 245.00 | 24.04 | 344.00 | 23.99 | 245.00 | 24.04 |
June | 260.67 | 24.01 | 336.00 | 23.98 | 260.67 | 24.01 |
July | 120.67 | 24.18 | 338.00 | 24.00 | 120.67 | 24.18 |
August | 309.00 | 23.98 | 348.00 | 23.97 | 309.00 | 23.98 |
September | 261.00 | 24.02 | 330.00 | 23.99 | 261.00 | 24.02 |
October | 261.00 | 24.02 | 340.00 | 23.99 | 261.00 | 24.02 |
November | 152.83 | 24.06 | 330.00 | 23.97 | 152.83 | 24.06 |
December | 62.17 | 24.36 | 338.00 | 23.98 | 62.17 | 24.36 |
Annual Sum or Average | 1869.83 | 24.08 | 4030.00 | 23.98 | 1869.83 | 24.08 |
Minimum of Months | 26.50 | 23.98 | 308.00 | 23.97 | 26.50 | 23.98 |
Maximum of Months | 309.00 | 24.72 | 348.00 | 24.00 | 309.00 | 24.72 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.50 | 24.73 | 340.00 | 23.98 | 27.50 | 24.73 |
February | 22.83 | 24.97 | 308.00 | 23.99 | 22.83 | 24.97 |
March | 30.33 | 24.66 | 348.00 | 23.98 | 30.33 | 24.66 |
April | 92.50 | 24.30 | 330.00 | 24.01 | 92.50 | 24.30 |
May | 214.67 | 24.06 | 344.00 | 24.00 | 214.67 | 24.06 |
June | 221.50 | 24.04 | 336.00 | 23.99 | 221.50 | 24.04 |
July | 90.17 | 24.29 | 338.00 | 24.01 | 90.17 | 24.29 |
August | 279.33 | 23.99 | 348.00 | 23.97 | 279.33 | 23.99 |
September | 221.67 | 24.05 | 330.00 | 24.00 | 221.67 | 24.05 |
October | 236.00 | 24.03 | 340.00 | 23.99 | 236.00 | 24.03 |
November | 130.67 | 24.10 | 330.00 | 23.97 | 130.67 | 24.10 |
December | 58.50 | 24.41 | 338.00 | 23.99 | 58.50 | 24.41 |
Annual Sum or Average | 1625.67 | 24.12 | 4030.00 | 23.99 | 1625.67 | 24.12 |
Minimum of Months | 22.83 | 23.99 | 308.00 | 23.97 | 22.83 | 23.99 |
Maximum of Months | 279.33 | 24.97 | 348.00 | 24.01 | 279.33 | 24.97 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 24.00622 | 55.82962 | 0.66298 | 14.42066 |
February | 448.00000 | 24.01030 | 55.95317 | 0.67039 | 14.62863 |
March | 496.00000 | 24.02125 | 57.44667 | 0.68477 | 15.10881 |
April | 480.00000 | 24.01688 | 61.65357 | 0.71822 | 16.09694 |
May | 496.00000 | 24.02782 | 65.28672 | -0.0738 | 5.60178 |
June | 480.00000 | 24.02547 | 65.09924 | -0.0652 | 5.57257 |
July | 496.00000 | 24.01068 | 60.44487 | -0.1229 | 5.63547 |
August | 496.00000 | 24.03043 | 65.98492 | -0.0874 | 5.62150 |
September | 480.00000 | 24.00987 | 64.61001 | -0.0959 | 5.56809 |
October | 496.00000 | 24.01495 | 64.44367 | 0.71569 | 15.99353 |
November | 480.00000 | 24.01866 | 61.60921 | 0.70184 | 15.58578 |
December | 496.00000 | 23.99908 | 57.99620 | 0.67315 | 14.70343 |
Annual Sum or Average | 5840.00000 | 24.01599 | 61.38702 | 0.36320 | 11.18889 |
Minimum of Months | 448.00000 | 23.99908 | 55.82962 | -0.1229 | 5.56809 |
Maximum of Months | 496.00000 | 24.03043 | 65.98492 | 0.71822 | 16.09694 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 24.00763 | 53.23976 | 0.62450 | 13.37813 |
February | 448.00000 | 24.01086 | 53.53992 | 0.63095 | 13.55071 |
March | 496.00000 | 24.02094 | 55.09895 | 0.64415 | 13.96060 |
April | 480.00000 | 24.01541 | 59.05676 | 0.67504 | 14.82187 |
May | 496.00000 | 24.02515 | 62.49025 | -0.1274 | 5.79981 |
June | 480.00000 | 24.02282 | 62.39665 | -0.1209 | 5.77120 |
July | 496.00000 | 24.00979 | 57.78013 | -0.1743 | 5.95762 |
August | 496.00000 | 24.02855 | 63.07572 | -0.1396 | 5.85239 |
September | 480.00000 | 24.00805 | 61.66022 | -0.1494 | 5.84398 |
October | 496.00000 | 24.01420 | 61.27481 | 0.67394 | 14.77839 |
November | 480.00000 | 24.01817 | 58.66697 | 0.66073 | 14.40563 |
December | 496.00000 | 23.99991 | 55.04707 | 0.63248 | 13.59186 |
Annual Sum or Average | 5840.00000 | 24.01515 | 58.63217 | 0.31721 | 10.62351 |
Minimum of Months | 448.00000 | 23.99991 | 53.23976 | -0.1743 | 5.77120 |
Maximum of Months | 496.00000 | 24.02855 | 63.07572 | 0.67504 | 14.82187 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.10756 | 56.11990 | 0.67540 | 14.87574 |
February | 336.00000 | 24.11589 | 56.51545 | 0.68367 | 15.13840 |
March | 379.00000 | 24.11632 | 57.61897 | 0.68962 | 15.32484 |
April | 360.00000 | 24.13175 | 62.17948 | 0.72954 | 16.57794 |
May | 375.00000 | 24.13234 | 65.91747 | -0.0607 | 5.81088 |
June | 366.00000 | 24.13248 | 65.99453 | -0.0522 | 5.78102 |
July | 369.00000 | 24.12139 | 61.89045 | -0.1031 | 5.83705 |
August | 379.00000 | 24.11088 | 67.22869 | -0.0781 | 5.71669 |
September | 360.00000 | 24.11701 | 66.08469 | -0.0776 | 5.74213 |
October | 371.00000 | 24.11053 | 65.81493 | 0.73310 | 16.62818 |
November | 360.00000 | 24.10056 | 62.41117 | 0.71309 | 15.99153 |
December | 369.00000 | 24.10319 | 58.33750 | 0.68604 | 15.19775 |
Annual Sum or Average | 4395.00000 | 24.11665 | 62.21264 | 0.37512 | 11.51266 |
Minimum of Months | 336.00000 | 24.10056 | 56.11990 | -0.1031 | 5.71669 |
Maximum of Months | 379.00000 | 24.13248 | 67.22869 | 0.73310 | 16.62818 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.10785 | 56.05050 | 0.67644 | 14.90821 |
February | 336.00000 | 24.11634 | 56.44677 | 0.68477 | 15.17367 |
March | 379.00000 | 24.11581 | 57.55083 | 0.69043 | 15.34989 |
April | 360.00000 | 24.13227 | 62.08145 | 0.73072 | 16.61848 |
May | 375.00000 | 24.13292 | 65.79124 | -0.0585 | 5.81570 |
June | 366.00000 | 24.13296 | 65.87880 | -0.0502 | 5.78620 |
July | 369.00000 | 24.12193 | 61.78171 | -0.1010 | 5.83678 |
August | 379.00000 | 24.11092 | 67.14694 | -0.0769 | 5.71872 |
September | 360.00000 | 24.11752 | 65.98943 | -0.0760 | 5.74545 |
October | 371.00000 | 24.11071 | 65.72280 | 0.73395 | 16.65756 |
November | 360.00000 | 24.10075 | 62.34560 | 0.71380 | 16.01528 |
December | 369.00000 | 24.10357 | 58.28149 | 0.68674 | 15.22131 |
Annual Sum or Average | 4395.00000 | 24.11696 | 62.12539 | 0.37641 | 11.53125 |
Minimum of Months | 336.00000 | 24.10075 | 56.05050 | -0.1010 | 5.71872 |
Maximum of Months | 379.00000 | 24.13296 | 67.14694 | 0.73395 | 16.65756 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.10537 | 56.20564 | 0.67508 | 14.86212 |
February | 336.00000 | 24.11399 | 56.60319 | 0.68345 | 15.12822 |
March | 379.00000 | 24.11408 | 57.71595 | 0.68923 | 15.30859 |
April | 360.00000 | 24.13044 | 62.26191 | 0.72978 | 16.58292 |
May | 375.00000 | 24.13106 | 65.97506 | -0.0599 | 5.80446 |
June | 366.00000 | 24.13096 | 66.06804 | -0.0517 | 5.77353 |
July | 369.00000 | 24.12011 | 61.96306 | -0.1027 | 5.83032 |
August | 379.00000 | 24.10901 | 67.37332 | -0.0787 | 5.71061 |
September | 360.00000 | 24.11556 | 66.20410 | -0.0777 | 5.73685 |
October | 371.00000 | 24.10892 | 65.94010 | 0.73315 | 16.62691 |
November | 360.00000 | 24.09836 | 62.54416 | 0.71274 | 15.97620 |
December | 369.00000 | 24.10090 | 58.46021 | 0.68531 | 15.17270 |
Annual Sum or Average | 4395.00000 | 24.11489 | 62.31285 | 0.37507 | 11.50358 |
Minimum of Months | 336.00000 | 24.09836 | 56.20564 | -0.1027 | 5.71061 |
Maximum of Months | 379.00000 | 24.13106 | 67.37332 | 0.73315 | 16.62691 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 24.00189 | 57.04793 | 0.66334 | 14.43854 |
February | 308.00000 | 24.01044 | 57.51070 | 0.67242 | 14.72928 |
March | 348.00000 | 23.99825 | 58.63540 | 0.67567 | 14.81305 |
April | 330.00000 | 24.02101 | 63.25842 | 0.71790 | 16.10728 |
May | 344.00000 | 24.01765 | 66.96062 | -0.0792 | 5.64150 |
June | 336.00000 | 24.00845 | 67.08945 | -0.0722 | 5.58482 |
July | 338.00000 | 24.02270 | 62.95715 | -0.1183 | 5.73741 |
August | 348.00000 | 23.99855 | 68.58582 | -0.0988 | 5.60969 |
September | 330.00000 | 24.01370 | 67.29907 | -0.0954 | 5.62298 |
October | 340.00000 | 24.01077 | 67.06744 | 0.72204 | 16.20233 |
November | 330.00000 | 23.99679 | 63.64893 | 0.70095 | 15.53038 |
December | 338.00000 | 24.00851 | 59.31890 | 0.67429 | 14.78090 |
Annual Sum or Average | 4030.00000 | 24.00900 | 63.31996 | 0.36031 | 11.19355 |
Minimum of Months | 308.00000 | 23.99679 | 57.04793 | -0.1183 | 5.58482 |
Maximum of Months | 348.00000 | 24.02270 | 68.58582 | 0.72204 | 16.20233 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 24.00156 | 57.11083 | 0.64304 | 13.88230 |
February | 308.00000 | 24.00967 | 57.58427 | 0.65157 | 14.14961 |
March | 348.00000 | 23.99751 | 58.70270 | 0.65476 | 14.22815 |
April | 330.00000 | 24.01981 | 63.38540 | 0.69700 | 15.48718 |
May | 344.00000 | 24.01627 | 67.13309 | -0.1086 | 5.76250 |
June | 336.00000 | 24.00685 | 67.29759 | -0.1026 | 5.70032 |
July | 338.00000 | 24.02164 | 63.09653 | -0.1471 | 5.90158 |
August | 348.00000 | 23.99702 | 68.79128 | -0.1263 | 5.74007 |
September | 330.00000 | 24.01260 | 67.49684 | -0.1233 | 5.75585 |
October | 340.00000 | 24.00995 | 67.25155 | 0.70345 | 15.64624 |
November | 330.00000 | 23.99589 | 63.80318 | 0.68170 | 14.97135 |
December | 338.00000 | 24.00784 | 59.42283 | 0.65461 | 14.23221 |
Annual Sum or Average | 4030.00000 | 24.00799 | 63.46168 | 0.33657 | 10.91819 |
Minimum of Months | 308.00000 | 23.99589 | 57.11083 | -0.1471 | 5.70032 |
Maximum of Months | 348.00000 | 24.02164 | 68.79128 | 0.70345 | 15.64624 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 24.00100 | 57.20454 | 0.64123 | 13.83133 |
February | 308.00000 | 24.00936 | 57.67441 | 0.64987 | 14.10153 |
March | 348.00000 | 23.99724 | 58.79276 | 0.65314 | 14.18195 |
April | 330.00000 | 24.02019 | 63.48498 | 0.69559 | 15.44619 |
May | 344.00000 | 24.01602 | 67.24209 | -0.1109 | 5.77029 |
June | 336.00000 | 24.00690 | 67.40757 | -0.1049 | 5.70876 |
July | 338.00000 | 24.02108 | 63.20119 | -0.1495 | 5.91261 |
August | 348.00000 | 23.99691 | 68.91005 | -0.1286 | 5.74997 |
September | 330.00000 | 24.01230 | 67.61202 | -0.1256 | 5.76493 |
October | 340.00000 | 24.00964 | 67.37443 | 0.70200 | 15.60158 |
November | 330.00000 | 23.99602 | 63.91779 | 0.68021 | 14.92803 |
December | 338.00000 | 24.00735 | 59.52592 | 0.65286 | 14.18247 |
Annual Sum or Average | 4030.00000 | 24.00777 | 63.56775 | 0.33467 | 10.89527 |
Minimum of Months | 308.00000 | 23.99602 | 57.20454 | -0.1495 | 5.70876 |
Maximum of Months | 348.00000 | 24.02108 | 68.91005 | 0.70200 | 15.60158 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 24.00075 | 57.26818 | 0.64213 | 13.85485 |
February | 308.00000 | 24.00914 | 57.71471 | 0.65119 | 14.13704 |
March | 348.00000 | 23.99691 | 58.82697 | 0.65460 | 14.22210 |
April | 330.00000 | 24.01942 | 63.50045 | 0.69736 | 15.49684 |
May | 344.00000 | 24.01597 | 67.26252 | -0.1083 | 5.75988 |
June | 336.00000 | 24.00670 | 67.41171 | -0.1021 | 5.69731 |
July | 338.00000 | 24.02112 | 63.22271 | -0.1470 | 5.89825 |
August | 348.00000 | 23.99669 | 68.94580 | -0.1263 | 5.73816 |
September | 330.00000 | 24.01216 | 67.63793 | -0.1232 | 5.75263 |
October | 340.00000 | 24.00917 | 67.45103 | 0.70320 | 15.63622 |
November | 330.00000 | 23.99519 | 63.98829 | 0.68126 | 14.95667 |
December | 338.00000 | 24.00692 | 59.60008 | 0.65370 | 14.20485 |
Annual Sum or Average | 4030.00000 | 24.00745 | 63.60797 | 0.33643 | 10.90966 |
Minimum of Months | 308.00000 | 23.99519 | 57.26818 | -0.1470 | 5.69731 |
Maximum of Months | 348.00000 | 24.02112 | 68.94580 | 0.70320 | 15.63622 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 24.00410 | 56.80092 | 0.66181 | 14.41721 |
February | 308.00000 | 24.01287 | 57.10561 | 0.67405 | 14.79946 |
March | 348.00000 | 24.00035 | 58.27741 | 0.67921 | 14.94436 |
April | 330.00000 | 24.02380 | 62.68780 | 0.72330 | 16.30449 |
May | 344.00000 | 24.02000 | 66.48716 | -0.0723 | 5.68663 |
June | 336.00000 | 24.01059 | 66.45554 | -0.0628 | 5.62028 |
July | 338.00000 | 24.02576 | 62.39365 | -0.1119 | 5.75922 |
August | 348.00000 | 23.99961 | 68.14567 | -0.0931 | 5.64332 |
September | 330.00000 | 24.01627 | 66.71413 | -0.0884 | 5.65442 |
October | 340.00000 | 24.01272 | 66.86070 | 0.72095 | 16.19757 |
November | 330.00000 | 23.99778 | 63.33322 | 0.69916 | 15.49984 |
December | 338.00000 | 24.01005 | 59.06599 | 0.67207 | 14.73813 |
Annual Sum or Average | 4030.00000 | 24.01109 | 62.89958 | 0.36361 | 11.23223 |
Minimum of Months | 308.00000 | 23.99778 | 56.80092 | -0.1119 | 5.62028 |
Maximum of Months | 348.00000 | 24.02576 | 68.14567 | 0.72330 | 16.30449 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.462030E+11 | 0.125528E+11 | 492.04 | 0.298422E+11 | 0.163608E+11 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:03 | 61749.09 | 10-JAN-09:01 | 38441.54 | 23-JAN-09:01 | 32108.20 | 10-JAN-09:04 | 13643.29 | 03-JAN-09:01 | 0.00 | 01-JAN-00:03 |
February | 0.443918E+11 | 0.121295E+11 | 447.90 | 0.286260E+11 | 0.157658E+11 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:03 | 61578.73 | 16-FEB-09:01 | 40003.96 | 24-FEB-09:01 | 31576.31 | 16-FEB-09:05 | 13555.06 | 18-FEB-09:03 | 0.00 | 01-FEB-00:03 |
March | 0.515426E+11 | 0.141195E+11 | 500.79 | 0.327253E+11 | 0.188173E+11 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:03 | 62038.40 | 27-MAR-08:61 | 39433.42 | 04-MAR-09:01 | 32998.38 | 27-MAR-08:61 | 13800.97 | 09-MAR-09:01 | 0.00 | 01-MAR-00:03 |
April | 0.564964E+11 | 0.151327E+11 | 487.59 | 0.329069E+11 | 0.235895E+11 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:03 | 62221.79 | 20-APR-08:61 | 32581.79 | 23-APR-07:02 | 33650.58 | 20-APR-08:61 | 13929.21 | 15-APR-08:05 | 0.00 | 01-APR-00:03 |
May | 0.628531E+11 | 0.164550E+11 | 501.90 | 0.339511E+11 | 0.289020E+11 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 62654.45 | 17-MAY-08:61 | 31150.71 | 06-MAY-13:00 | 38274.36 | 19-MAY-08:04 | 14154.79 | 06-MAY-08:13 | 0.00 | 01-MAY-00:10 |
June | 0.621978E+11 | 0.161829E+11 | 487.19 | 0.334156E+11 | 0.287822E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 62569.23 | 01-JUN-08:61 | 32742.19 | 25-JUN-07:01 | 37648.84 | 10-JUN-08:04 | 14111.76 | 16-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 0.521802E+11 | 0.138157E+11 | 499.44 | 0.305657E+11 | 0.216145E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 61939.28 | 01-JUL-08:61 | 37328.11 | 09-JUL-07:01 | 32678.33 | 01-JUL-08:02 | 13498.74 | 29-JUL-08:13 | 0.00 | 01-JUL-00:03 |
August | 0.583329E+11 | 0.150000E+11 | 500.70 | 0.305760E+11 | 0.277570E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 62500.23 | 19-AUG-08:61 | 32124.22 | 27-AUG-07:01 | 38919.29 | 11-AUG-08:06 | 13804.48 | 28-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.555654E+11 | 0.143944E+11 | 486.17 | 0.300052E+11 | 0.255602E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 62576.89 | 21-SEP-08:61 | 34402.99 | 10-SEP-07:02 | 35687.96 | 25-SEP-08:04 | 13650.85 | 14-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.537031E+11 | 0.139039E+11 | 496.93 | 0.290634E+11 | 0.246397E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:03 | 62589.59 | 23-OCT-08:61 | 34006.92 | 08-OCT-07:02 | 35761.80 | 23-OCT-08:61 | 13632.11 | 05-OCT-08:13 | 0.00 | 01-OCT-00:03 |
November | 0.493746E+11 | 0.129676E+11 | 481.54 | 0.282792E+11 | 0.210954E+11 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 62005.28 | 03-NOV-08:61 | 36395.37 | 25-NOV-09:01 | 32919.35 | 03-NOV-08:04 | 13573.70 | 07-NOV-09:13 | 0.00 | 01-NOV-00:10 |
December | 0.471797E+11 | 0.126277E+11 | 495.33 | 0.291098E+11 | 0.180699E+11 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-01:05 | 61442.87 | 18-DEC-09:01 | 38168.42 | 27-DEC-09:01 | 31220.05 | 18-DEC-09:05 | 13621.42 | 09-DEC-09:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.640021E+12 | 0.169282E+12 | 5877.53 | 0.369066E+12 | 0.270954E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.443918E+11 | 0.121295E+11 | 447.90 | 0.282792E+11 | 0.157658E+11 | 0.00 | 1.00 | 0.00 | 61442.87 | 31150.71 | 31220.05 | 13498.74 | 0.00 | |||||||
Maximum of Months | 0.628531E+11 | 0.164550E+11 | 501.90 | 0.339511E+11 | 0.289020E+11 | 0.00 | 1.00 | 0.00 | 62654.45 | 40003.96 | 38919.29 | 14154.79 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.225248E+11 | 0.613289E+10 | 494.21 | 0.149924E+11 | 0.753238E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:03 | 31790.35 | 10-JAN-09:01 | 21736.72 | 16-JAN-08:62 | 15066.92 | 10-JAN-09:13 | 7012.94 | 03-JAN-09:01 | 0.00 | 01-JAN-00:03 |
February | 0.215371E+11 | 0.589874E+10 | 448.82 | 0.142705E+11 | 0.726657E+10 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:03 | 31723.88 | 16-FEB-09:01 | 22191.50 | 24-FEB-09:01 | 14829.73 | 16-FEB-09:04 | 6970.30 | 18-FEB-09:01 | 0.00 | 01-FEB-00:03 |
March | 0.249271E+11 | 0.684959E+10 | 501.09 | 0.162608E+11 | 0.866636E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:03 | 31955.55 | 27-MAR-08:61 | 21523.17 | 04-MAR-09:01 | 15576.87 | 27-MAR-08:04 | 7092.64 | 09-MAR-09:01 | 0.00 | 01-MAR-00:03 |
April | 0.270766E+11 | 0.729030E+10 | 487.33 | 0.162479E+11 | 0.108288E+11 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:03 | 32087.80 | 20-APR-08:61 | 20144.44 | 23-APR-07:02 | 16045.29 | 20-APR-08:04 | 7167.90 | 15-APR-08:04 | 0.00 | 01-APR-00:03 |
May | 0.302137E+11 | 0.794899E+10 | 502.25 | 0.168432E+11 | 0.133706E+11 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 32614.25 | 16-MAY-08:61 | 19332.65 | 14-MAY-07:01 | 18599.00 | 19-MAY-08:04 | 7289.24 | 06-MAY-08:13 | 0.00 | 01-MAY-00:10 |
June | 0.299716E+11 | 0.782990E+10 | 487.68 | 0.165831E+11 | 0.133885E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 32641.85 | 02-JUN-08:61 | 20501.84 | 25-JUN-07:01 | 18449.49 | 10-JUN-08:04 | 7207.87 | 16-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 0.251316E+11 | 0.667822E+10 | 500.80 | 0.151607E+11 | 0.997085E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 31813.82 | 01-JUL-08:61 | 21978.55 | 09-JUL-07:01 | 15219.76 | 14-JUL-08:13 | 6926.27 | 03-JUL-08:13 | 0.00 | 01-JUL-00:03 |
August | 0.281815E+11 | 0.726610E+10 | 500.42 | 0.152291E+11 | 0.129524E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 32674.50 | 04-AUG-08:61 | 19746.82 | 27-AUG-07:01 | 19026.40 | 11-AUG-08:04 | 7108.68 | 28-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.267504E+11 | 0.695524E+10 | 486.65 | 0.149047E+11 | 0.118457E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 32347.68 | 01-SEP-08:61 | 20995.09 | 10-SEP-07:02 | 16835.68 | 01-SEP-08:04 | 7023.10 | 06-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.260350E+11 | 0.675701E+10 | 498.14 | 0.145682E+11 | 0.114668E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:03 | 32158.17 | 23-OCT-08:61 | 20886.61 | 08-OCT-07:02 | 16525.43 | 23-OCT-08:04 | 7022.73 | 05-OCT-08:13 | 0.00 | 01-OCT-00:03 |
November | 0.239645E+11 | 0.630945E+10 | 482.51 | 0.141836E+11 | 0.978090E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 31903.53 | 03-NOV-08:61 | 20681.52 | 23-NOV-08:61 | 15490.95 | 03-NOV-08:13 | 6981.77 | 14-NOV-09:13 | 0.00 | 01-NOV-00:10 |
December | 0.229560E+11 | 0.616327E+10 | 496.38 | 0.146612E+11 | 0.829484E+10 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-01:05 | 31509.19 | 18-DEC-09:01 | 21232.13 | 27-DEC-09:01 | 14125.89 | 18-DEC-09:04 | 7000.92 | 09-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.309270E+12 | 0.820797E+11 | 5886.29 | 0.183905E+12 | 0.125365E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.215371E+11 | 0.589874E+10 | 448.82 | 0.141836E+11 | 0.726657E+10 | 0.00 | 1.00 | 0.00 | 31509.19 | 19332.65 | 14125.89 | 6926.27 | 0.00 | |||||||
Maximum of Months | 0.302137E+11 | 0.794899E+10 | 502.25 | 0.168432E+11 | 0.133885E+11 | 0.00 | 1.00 | 0.00 | 32674.50 | 22191.50 | 19026.40 | 7289.24 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.185729E+11 | 0.496818E+10 | 354.10 | 0.120468E+11 | 0.652602E+10 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:03 | 32450.61 | 02-JAN-08:61 | 18723.24 | 24-JAN-08:62 | 17905.07 | 02-JAN-08:61 | 6985.41 | 11-JAN-08:04 | 0.00 | 01-JAN-00:03 |
February | 0.178967E+11 | 0.481196E+10 | 325.25 | 0.115482E+11 | 0.634851E+10 | 0.00 | 1.00 | 01-FEB-08:61 | 0.00 | 01-FEB-00:03 | 32327.30 | 16-FEB-08:61 | 20344.24 | 25-FEB-08:61 | 17345.35 | 16-FEB-08:03 | 6915.13 | 20-FEB-09:13 | 0.00 | 01-FEB-00:03 |
March | 0.210303E+11 | 0.568375E+10 | 374.04 | 0.133828E+11 | 0.764750E+10 | 0.00 | 1.00 | 01-MAR-08:61 | 0.00 | 01-MAR-00:03 | 32524.37 | 28-MAR-07:01 | 19411.77 | 04-MAR-08:61 | 17941.51 | 28-MAR-07:01 | 7014.29 | 26-MAR-08:13 | 0.00 | 01-MAR-00:03 |
April | 0.226132E+11 | 0.595313E+10 | 359.31 | 0.131512E+11 | 0.946205E+10 | 0.00 | 1.00 | 01-APR-07:01 | 0.00 | 01-APR-00:03 | 32587.04 | 24-APR-07:01 | 16222.08 | 27-APR-07:01 | 18556.62 | 03-APR-07:03 | 6984.08 | 30-APR-08:13 | 0.00 | 01-APR-00:03 |
May | 0.256057E+11 | 0.657689E+10 | 374.22 | 0.137574E+11 | 0.118483E+11 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 32628.16 | 17-MAY-07:01 | 16061.30 | 06-MAY-13:00 | 20840.75 | 22-MAY-07:02 | 7136.25 | 07-MAY-08:13 | 0.00 | 01-MAY-00:10 |
June | 0.255854E+11 | 0.653507E+10 | 365.30 | 0.136416E+11 | 0.119438E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 32602.57 | 01-JUN-07:01 | 15163.91 | 15-JUN-13:00 | 20684.02 | 11-JUN-07:01 | 7117.71 | 16-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 0.207619E+11 | 0.537557E+10 | 365.96 | 0.119901E+11 | 0.877177E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 32533.65 | 02-JUL-08:61 | 16621.81 | 06-JUL-07:01 | 18106.33 | 01-JUL-07:01 | 6865.67 | 30-JUL-08:13 | 0.00 | 01-JUL-00:03 |
August | 0.240213E+11 | 0.605161E+10 | 375.49 | 0.124285E+11 | 0.115929E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 32603.71 | 04-AUG-07:01 | 15019.97 | 30-AUG-07:01 | 19887.24 | 21-AUG-07:04 | 6974.60 | 13-AUG-08:15 | 0.00 | 01-AUG-00:10 |
September | 0.224082E+11 | 0.568040E+10 | 358.01 | 0.119324E+11 | 0.104758E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 32632.78 | 18-SEP-07:01 | 15017.52 | 13-SEP-07:01 | 20177.39 | 25-SEP-07:03 | 6939.16 | 10-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.217501E+11 | 0.550807E+10 | 365.73 | 0.116263E+11 | 0.101239E+11 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 32632.35 | 23-OCT-07:01 | 15035.82 | 08-OCT-08:61 | 19405.65 | 23-OCT-07:03 | 6919.99 | 29-OCT-08:13 | 0.00 | 01-OCT-00:03 |
November | 0.199315E+11 | 0.513999E+10 | 353.50 | 0.114057E+11 | 0.852578E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 32541.96 | 05-NOV-08:61 | 18228.22 | 25-NOV-08:61 | 19116.16 | 12-NOV-09:04 | 6923.73 | 23-NOV-09:04 | 0.00 | 01-NOV-00:10 |
December | 0.188132E+11 | 0.496365E+10 | 353.25 | 0.117004E+11 | 0.711278E+10 | 0.00 | 1.00 | 01-DEC-08:61 | 0.00 | 01-DEC-00:10 | 32580.65 | 11-DEC-08:61 | 18810.14 | 27-DEC-08:61 | 18792.88 | 11-DEC-08:03 | 6953.37 | 31-DEC-09:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.258990E+12 | 0.672483E+11 | 4324.15 | 0.148611E+12 | 0.110379E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.178967E+11 | 0.481196E+10 | 325.25 | 0.114057E+11 | 0.634851E+10 | 0.00 | 1.00 | 0.00 | 32327.30 | 15017.52 | 17345.35 | 6865.67 | 0.00 | |||||||
Maximum of Months | 0.256057E+11 | 0.657689E+10 | 375.49 | 0.137574E+11 | 0.119438E+11 | 0.00 | 1.00 | 0.00 | 32632.78 | 20344.24 | 20840.75 | 7136.25 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.186384E+11 | 0.498626E+10 | 356.27 | 0.120981E+11 | 0.654032E+10 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:03 | 32513.51 | 02-JAN-08:61 | 18805.74 | 24-JAN-08:62 | 17859.56 | 02-JAN-08:61 | 7004.51 | 11-JAN-08:04 | 0.00 | 01-JAN-00:03 |
February | 0.179603E+11 | 0.482957E+10 | 325.97 | 0.115981E+11 | 0.636212E+10 | 0.00 | 1.00 | 01-FEB-08:61 | 0.00 | 01-FEB-00:03 | 32403.96 | 16-FEB-08:61 | 20415.00 | 25-FEB-08:61 | 17353.78 | 16-FEB-08:03 | 6933.60 | 20-FEB-09:13 | 0.00 | 01-FEB-00:03 |
March | 0.211025E+11 | 0.570481E+10 | 376.49 | 0.134381E+11 | 0.766444E+10 | 0.00 | 1.00 | 01-MAR-08:61 | 0.00 | 01-MAR-00:03 | 32602.37 | 28-MAR-07:01 | 19478.21 | 04-MAR-08:61 | 17949.38 | 28-MAR-07:01 | 7033.47 | 26-MAR-08:13 | 0.00 | 01-MAR-00:03 |
April | 0.227037E+11 | 0.597761E+10 | 359.06 | 0.132179E+11 | 0.948580E+10 | 0.00 | 1.00 | 01-APR-07:01 | 0.00 | 01-APR-00:03 | 32663.64 | 24-APR-07:01 | 16289.78 | 27-APR-07:01 | 18493.55 | 10-APR-07:03 | 7004.65 | 30-APR-08:13 | 0.00 | 01-APR-00:03 |
May | 0.257195E+11 | 0.660674E+10 | 374.51 | 0.138392E+11 | 0.118803E+11 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 32716.74 | 17-MAY-07:01 | 16093.87 | 06-MAY-13:00 | 21657.92 | 29-MAY-07:01 | 7211.40 | 28-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.256873E+11 | 0.656230E+10 | 365.49 | 0.137152E+11 | 0.119720E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 32683.57 | 01-JUN-07:01 | 15221.55 | 13-JUN-14:00 | 20659.11 | 11-JUN-07:01 | 7131.85 | 16-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 0.208595E+11 | 0.540112E+10 | 366.18 | 0.120613E+11 | 0.879823E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 32607.47 | 01-JUL-07:01 | 16717.65 | 06-JUL-07:01 | 18142.88 | 01-JUL-07:01 | 6884.09 | 30-JUL-08:13 | 0.00 | 01-JUL-00:03 |
August | 0.240929E+11 | 0.607163E+10 | 375.67 | 0.124800E+11 | 0.116129E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 32692.23 | 04-AUG-07:01 | 15101.92 | 30-AUG-07:01 | 19897.34 | 21-AUG-07:04 | 6995.83 | 13-AUG-08:15 | 0.00 | 01-AUG-00:10 |
September | 0.224876E+11 | 0.570172E+10 | 357.76 | 0.119897E+11 | 0.104979E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 32721.38 | 18-SEP-07:01 | 15147.49 | 13-SEP-07:01 | 20128.59 | 25-SEP-07:03 | 6959.35 | 10-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.218253E+11 | 0.552861E+10 | 366.60 | 0.116808E+11 | 0.101445E+11 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 32720.95 | 23-OCT-07:01 | 15121.94 | 08-OCT-08:61 | 19415.68 | 23-OCT-07:03 | 6939.71 | 29-OCT-08:13 | 0.00 | 01-OCT-00:03 |
November | 0.199926E+11 | 0.515694E+10 | 354.21 | 0.114506E+11 | 0.854194E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 32610.24 | 05-NOV-08:61 | 18305.49 | 25-NOV-08:61 | 19112.94 | 12-NOV-09:04 | 6942.48 | 23-NOV-09:04 | 0.00 | 01-NOV-00:10 |
December | 0.188654E+11 | 0.497834E+10 | 353.88 | 0.117401E+11 | 0.712534E+10 | 0.00 | 1.00 | 01-DEC-08:61 | 0.00 | 01-DEC-00:10 | 32669.10 | 11-DEC-08:61 | 18896.05 | 27-DEC-08:61 | 18760.20 | 11-DEC-08:03 | 6972.14 | 31-DEC-09:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.259935E+12 | 0.675057E+11 | 4332.09 | 0.149309E+12 | 0.110626E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.179603E+11 | 0.482957E+10 | 325.97 | 0.114506E+11 | 0.636212E+10 | 0.00 | 1.00 | 0.00 | 32403.96 | 15101.92 | 17353.78 | 6884.09 | 0.00 | |||||||
Maximum of Months | 0.257195E+11 | 0.660674E+10 | 376.49 | 0.138392E+11 | 0.119720E+11 | 0.00 | 1.00 | 0.00 | 32721.38 | 20415.00 | 21657.92 | 7211.40 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.184812E+11 | 0.494564E+10 | 353.55 | 0.119763E+11 | 0.650489E+10 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:03 | 32414.30 | 02-JAN-08:61 | 18673.23 | 24-JAN-08:62 | 17865.43 | 02-JAN-08:61 | 6978.76 | 11-JAN-08:04 | 0.00 | 01-JAN-00:03 |
February | 0.178151E+11 | 0.479167E+10 | 323.31 | 0.114857E+11 | 0.632944E+10 | 0.00 | 1.00 | 01-FEB-08:61 | 0.00 | 01-FEB-00:03 | 32323.31 | 16-FEB-08:61 | 20298.24 | 25-FEB-08:61 | 17419.30 | 16-FEB-08:61 | 6908.63 | 20-FEB-09:13 | 0.00 | 01-FEB-00:03 |
March | 0.209304E+11 | 0.565880E+10 | 373.99 | 0.133063E+11 | 0.762413E+10 | 0.00 | 1.00 | 01-MAR-08:61 | 0.00 | 01-MAR-00:03 | 32494.39 | 28-MAR-07:01 | 19354.19 | 04-MAR-08:61 | 17949.45 | 28-MAR-07:01 | 7007.83 | 26-MAR-08:13 | 0.00 | 01-MAR-00:03 |
April | 0.225374E+11 | 0.593386E+10 | 358.52 | 0.130952E+11 | 0.944222E+10 | 0.00 | 1.00 | 01-APR-07:01 | 0.00 | 01-APR-00:03 | 32557.00 | 24-APR-07:01 | 16161.91 | 27-APR-07:01 | 18513.16 | 10-APR-07:03 | 6978.01 | 30-APR-08:13 | 0.00 | 01-APR-00:03 |
May | 0.255562E+11 | 0.656392E+10 | 373.74 | 0.137225E+11 | 0.118338E+11 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 32598.08 | 17-MAY-07:01 | 15993.64 | 06-MAY-13:00 | 21507.12 | 29-MAY-07:01 | 7130.73 | 07-MAY-08:13 | 0.00 | 01-MAY-00:10 |
June | 0.255212E+11 | 0.651903E+10 | 365.10 | 0.135963E+11 | 0.119249E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 32576.08 | 01-JUN-07:01 | 15149.86 | 13-JUN-14:00 | 20651.10 | 11-JUN-07:01 | 7096.32 | 16-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 0.206954E+11 | 0.535886E+10 | 364.76 | 0.119410E+11 | 0.875447E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 32522.41 | 01-JUL-07:01 | 16586.64 | 06-JUL-07:01 | 18199.53 | 01-JUL-07:01 | 6859.31 | 30-JUL-08:13 | 0.00 | 01-JUL-00:03 |
August | 0.239056E+11 | 0.602394E+10 | 374.38 | 0.123484E+11 | 0.115572E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 32591.68 | 19-AUG-07:01 | 14961.15 | 30-AUG-07:01 | 19915.78 | 21-AUG-07:04 | 6968.48 | 13-AUG-08:15 | 0.00 | 01-AUG-00:10 |
September | 0.223142E+11 | 0.565733E+10 | 356.44 | 0.118665E+11 | 0.104477E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 32602.70 | 18-SEP-07:01 | 14953.86 | 13-SEP-07:01 | 20132.29 | 25-SEP-07:03 | 6932.84 | 10-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.216477E+11 | 0.548347E+10 | 364.19 | 0.115549E+11 | 0.100928E+11 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:03 | 32602.27 | 23-OCT-07:01 | 15006.49 | 08-OCT-08:61 | 19402.28 | 23-OCT-07:03 | 6913.49 | 29-OCT-08:13 | 0.00 | 01-OCT-00:03 |
November | 0.198206E+11 | 0.511330E+10 | 352.35 | 0.113261E+11 | 0.849452E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 32518.12 | 05-NOV-08:61 | 18168.19 | 25-NOV-08:61 | 19130.50 | 12-NOV-09:04 | 6917.42 | 23-NOV-09:04 | 0.00 | 01-NOV-00:10 |
December | 0.186970E+11 | 0.493541E+10 | 350.84 | 0.116124E+11 | 0.708465E+10 | 0.00 | 1.00 | 01-DEC-08:61 | 0.00 | 01-DEC-00:10 | 32550.62 | 11-DEC-08:61 | 18766.71 | 27-DEC-08:61 | 18761.62 | 11-DEC-08:03 | 6946.99 | 31-DEC-09:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.257922E+12 | 0.669852E+11 | 4311.17 | 0.147831E+12 | 0.110091E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.178151E+11 | 0.479167E+10 | 323.31 | 0.113261E+11 | 0.632944E+10 | 0.00 | 1.00 | 0.00 | 32323.31 | 14953.86 | 17419.30 | 6859.31 | 0.00 | |||||||
Maximum of Months | 0.255562E+11 | 0.656392E+10 | 374.38 | 0.137225E+11 | 0.119249E+11 | 0.00 | 1.00 | 0.00 | 32602.70 | 20298.24 | 21507.12 | 7130.73 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.333907E+11 | 0.906967E+10 | 347.48 | 0.213909E+11 | 0.119998E+11 | 0.00 | 1.00 | 01-JAN-10:01 | 0.00 | 01-JAN-00:03 | 58887.72 | 02-JAN-09:01 | 35352.48 | 21-JAN-09:01 | 31906.79 | 02-JAN-09:01 | 12916.58 | 03-JAN-09:01 | 0.00 | 01-JAN-00:03 |
February | 0.322266E+11 | 0.879105E+10 | 318.14 | 0.205359E+11 | 0.116907E+11 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:03 | 58415.40 | 16-FEB-09:01 | 37306.47 | 24-FEB-09:01 | 30240.70 | 16-FEB-09:04 | 13045.51 | 26-FEB-10:13 | 0.00 | 01-FEB-00:03 |
March | 0.379277E+11 | 0.103946E+11 | 365.92 | 0.238437E+11 | 0.140839E+11 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:03 | 58952.84 | 27-MAR-08:61 | 37269.47 | 04-MAR-09:01 | 31957.22 | 27-MAR-08:61 | 13291.83 | 26-MAR-09:13 | 0.00 | 01-MAR-00:03 |
April | 0.408275E+11 | 0.108812E+11 | 348.20 | 0.234062E+11 | 0.174213E+11 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:03 | 59077.15 | 03-APR-07:01 | 30395.77 | 27-APR-08:61 | 35627.50 | 03-APR-07:01 | 13186.37 | 09-APR-09:13 | 0.00 | 01-APR-00:03 |
May | 0.464549E+11 | 0.120540E+11 | 363.97 | 0.245575E+11 | 0.218974E+11 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 59317.22 | 17-MAY-08:61 | 29355.79 | 06-MAY-13:00 | 38396.04 | 29-MAY-08:62 | 13439.80 | 07-MAY-09:25 | 0.00 | 01-MAY-00:10 |
June | 0.465875E+11 | 0.120224E+11 | 356.94 | 0.244320E+11 | 0.221555E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 59236.54 | 01-JUN-08:61 | 28858.84 | 21-JUN-08:61 | 37612.15 | 11-JUN-08:62 | 13372.62 | 16-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 0.372471E+11 | 0.976947E+10 | 351.56 | 0.211813E+11 | 0.160658E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 59055.20 | 24-JUL-08:61 | 30790.78 | 06-JUL-08:61 | 32711.10 | 24-JUL-08:61 | 12886.05 | 04-JUL-09:13 | 0.00 | 01-JUL-00:03 |
August | 0.433957E+11 | 0.110514E+11 | 366.32 | 0.219821E+11 | 0.214136E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 59160.40 | 19-AUG-08:61 | 27778.89 | 30-AUG-08:61 | 37501.84 | 21-AUG-08:03 | 13166.18 | 27-AUG-09:25 | 0.00 | 01-AUG-00:10 |
September | 0.402865E+11 | 0.103328E+11 | 345.10 | 0.210601E+11 | 0.192264E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 59317.22 | 18-SEP-08:61 | 28746.12 | 13-SEP-08:61 | 36714.76 | 25-SEP-08:03 | 13013.43 | 03-SEP-09:15 | 0.00 | 01-SEP-00:10 |
October | 0.390098E+11 | 0.100008E+11 | 353.60 | 0.204383E+11 | 0.185715E+11 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 59299.65 | 23-OCT-08:61 | 29863.28 | 20-OCT-08:61 | 36149.16 | 23-OCT-08:04 | 13003.49 | 29-OCT-09:07 | 0.00 | 01-OCT-00:03 |
November | 0.357665E+11 | 0.934486E+10 | 344.64 | 0.200721E+11 | 0.156944E+11 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 59090.36 | 13-NOV-09:01 | 33824.93 | 25-NOV-09:01 | 34069.41 | 12-NOV-10:04 | 13079.18 | 19-NOV-10:13 | 0.00 | 01-NOV-00:10 |
December | 0.335587E+11 | 0.898500E+10 | 346.48 | 0.205668E+11 | 0.129918E+11 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 59153.70 | 18-DEC-09:01 | 36245.34 | 27-DEC-09:01 | 32885.77 | 18-DEC-09:01 | 13170.37 | 31-DEC-10:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.466679E+12 | 0.122697E+12 | 4208.37 | 0.263467E+12 | 0.203212E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.322266E+11 | 0.879105E+10 | 318.14 | 0.200721E+11 | 0.116907E+11 | 0.00 | 1.00 | 0.00 | 58415.40 | 27778.89 | 30240.70 | 12886.05 | 0.00 | |||||||
Maximum of Months | 0.465875E+11 | 0.120540E+11 | 366.32 | 0.245575E+11 | 0.221555E+11 | 0.00 | 1.00 | 0.00 | 59317.22 | 37306.47 | 38396.04 | 13439.80 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.174060E+11 | 0.465275E+10 | 346.12 | 0.111688E+11 | 0.623727E+10 | 0.00 | 1.00 | 01-JAN-10:01 | 0.00 | 01-JAN-00:03 | 31025.05 | 02-JAN-09:01 | 18644.37 | 21-JAN-09:01 | 16818.25 | 02-JAN-09:01 | 6679.09 | 03-JAN-09:01 | 0.00 | 01-JAN-00:03 |
February | 0.167996E+11 | 0.451038E+10 | 317.37 | 0.107194E+11 | 0.608020E+10 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:03 | 30746.23 | 16-FEB-09:01 | 19672.51 | 24-FEB-09:01 | 15888.44 | 16-FEB-09:04 | 6745.36 | 26-FEB-10:13 | 0.00 | 01-FEB-00:03 |
March | 0.197524E+11 | 0.532877E+10 | 364.43 | 0.124353E+11 | 0.731710E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:03 | 31024.06 | 27-MAR-08:61 | 19603.26 | 04-MAR-09:01 | 16789.82 | 27-MAR-08:61 | 6873.37 | 26-MAR-09:13 | 0.00 | 01-MAR-00:03 |
April | 0.212544E+11 | 0.557776E+10 | 347.57 | 0.122060E+11 | 0.904841E+10 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:03 | 31093.37 | 03-APR-07:01 | 16029.02 | 27-APR-08:61 | 18838.34 | 03-APR-07:01 | 6819.55 | 09-APR-09:13 | 0.00 | 01-APR-00:03 |
May | 0.241687E+11 | 0.617715E+10 | 363.70 | 0.128048E+11 | 0.113638E+11 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 31219.73 | 17-MAY-08:61 | 15377.84 | 06-MAY-13:00 | 20384.57 | 29-MAY-08:62 | 6951.97 | 07-MAY-09:25 | 0.00 | 01-MAY-00:10 |
June | 0.242189E+11 | 0.615694E+10 | 356.51 | 0.127258E+11 | 0.114932E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 31177.26 | 01-JUN-08:61 | 15205.62 | 21-JUN-08:61 | 19883.97 | 11-JUN-08:62 | 6903.81 | 16-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 0.193911E+11 | 0.500675E+10 | 350.45 | 0.110478E+11 | 0.834331E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 31093.93 | 24-JUL-08:61 | 16269.86 | 06-JUL-08:61 | 17212.89 | 24-JUL-08:61 | 6663.27 | 04-JUL-09:13 | 0.00 | 01-JUL-00:03 |
August | 0.225622E+11 | 0.565815E+10 | 365.00 | 0.114555E+11 | 0.111067E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 31144.60 | 19-AUG-08:61 | 14661.66 | 30-AUG-08:61 | 19759.24 | 21-AUG-08:03 | 6810.89 | 27-AUG-09:25 | 0.00 | 01-AUG-00:10 |
September | 0.209633E+11 | 0.529381E+10 | 344.25 | 0.109813E+11 | 0.998204E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 31219.73 | 18-SEP-08:61 | 15192.02 | 13-SEP-08:61 | 19303.42 | 25-SEP-08:03 | 6730.93 | 03-SEP-09:15 | 0.00 | 01-SEP-00:10 |
October | 0.203053E+11 | 0.512416E+10 | 352.34 | 0.106621E+11 | 0.964311E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 31210.48 | 23-OCT-08:61 | 15731.16 | 20-OCT-08:61 | 19004.47 | 23-OCT-08:04 | 6722.33 | 29-OCT-09:13 | 0.00 | 01-OCT-00:03 |
November | 0.186156E+11 | 0.478718E+10 | 343.67 | 0.104681E+11 | 0.814751E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 31100.32 | 13-NOV-09:01 | 17870.86 | 25-NOV-09:01 | 17956.72 | 12-NOV-10:04 | 6763.18 | 19-NOV-10:13 | 0.00 | 01-NOV-00:10 |
December | 0.174812E+11 | 0.460622E+10 | 344.78 | 0.107320E+11 | 0.674924E+10 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 31156.18 | 18-DEC-09:01 | 19121.84 | 27-DEC-09:01 | 17346.94 | 18-DEC-09:01 | 6810.49 | 31-DEC-10:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.242919E+12 | 0.628800E+11 | 4196.19 | 0.137407E+12 | 0.105512E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.167996E+11 | 0.451038E+10 | 317.37 | 0.104681E+11 | 0.608020E+10 | 0.00 | 1.00 | 0.00 | 30746.23 | 14661.66 | 15888.44 | 6663.27 | 0.00 | |||||||
Maximum of Months | 0.242189E+11 | 0.617715E+10 | 365.00 | 0.128048E+11 | 0.114932E+11 | 0.00 | 1.00 | 0.00 | 31219.73 | 19672.51 | 20384.57 | 6951.97 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.173065E+11 | 0.462537E+10 | 345.67 | 0.110925E+11 | 0.621407E+10 | 0.00 | 1.00 | 01-JAN-10:01 | 0.00 | 01-JAN-00:03 | 30858.42 | 02-JAN-09:01 | 18529.52 | 21-JAN-09:01 | 16741.37 | 02-JAN-09:01 | 6645.52 | 03-JAN-09:01 | 0.00 | 01-JAN-00:03 |
February | 0.167133E+11 | 0.448587E+10 | 316.39 | 0.106525E+11 | 0.606075E+10 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:03 | 30604.57 | 16-FEB-09:01 | 19555.63 | 24-FEB-09:01 | 15849.85 | 16-FEB-09:04 | 6711.67 | 26-FEB-10:13 | 0.00 | 01-FEB-00:03 |
March | 0.196558E+11 | 0.530085E+10 | 364.29 | 0.123613E+11 | 0.729445E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:03 | 30877.28 | 27-MAR-08:61 | 19489.96 | 04-MAR-09:01 | 16734.83 | 27-MAR-08:61 | 6838.75 | 26-MAR-09:13 | 0.00 | 01-MAR-00:03 |
April | 0.211599E+11 | 0.554992E+10 | 346.77 | 0.121359E+11 | 0.902402E+10 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:03 | 30899.74 | 24-APR-08:61 | 15923.64 | 27-APR-08:61 | 18577.82 | 03-APR-07:01 | 6784.86 | 09-APR-09:13 | 0.00 | 01-APR-00:03 |
May | 0.240695E+11 | 0.614832E+10 | 363.34 | 0.127328E+11 | 0.113367E+11 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 31062.93 | 17-MAY-08:61 | 15316.09 | 06-MAY-13:00 | 20303.02 | 29-MAY-08:62 | 6916.55 | 07-MAY-09:25 | 0.00 | 01-MAY-00:10 |
June | 0.241185E+11 | 0.612763E+10 | 356.24 | 0.126530E+11 | 0.114655E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 31020.67 | 01-JUN-08:61 | 15101.12 | 21-JUN-08:61 | 19805.33 | 11-JUN-08:62 | 6876.99 | 16-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 0.192951E+11 | 0.498030E+10 | 350.08 | 0.109775E+11 | 0.831762E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 30945.09 | 24-JUL-08:61 | 16161.54 | 06-JUL-08:61 | 17154.03 | 24-JUL-08:61 | 6629.80 | 04-JUL-09:13 | 0.00 | 01-JUL-00:03 |
August | 0.224606E+11 | 0.562976E+10 | 365.10 | 0.113837E+11 | 0.110769E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 30998.39 | 19-AUG-08:61 | 14554.31 | 30-AUG-08:61 | 19704.35 | 21-AUG-08:61 | 6775.92 | 27-AUG-09:25 | 0.00 | 01-AUG-00:10 |
September | 0.208664E+11 | 0.526672E+10 | 343.78 | 0.109123E+11 | 0.995412E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 31062.93 | 18-SEP-08:61 | 15057.60 | 13-SEP-08:61 | 19234.73 | 25-SEP-08:03 | 6696.31 | 03-SEP-09:15 | 0.00 | 01-SEP-00:10 |
October | 0.202038E+11 | 0.509647E+10 | 351.52 | 0.105899E+11 | 0.961393E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 31053.72 | 23-OCT-08:61 | 15620.01 | 20-OCT-08:61 | 18938.32 | 23-OCT-08:04 | 6688.00 | 29-OCT-09:13 | 0.00 | 01-OCT-00:03 |
November | 0.185143E+11 | 0.475944E+10 | 343.07 | 0.103945E+11 | 0.811976E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 30944.12 | 13-NOV-09:01 | 17749.43 | 25-NOV-09:01 | 17897.88 | 12-NOV-10:04 | 6729.18 | 19-NOV-10:13 | 0.00 | 01-NOV-00:10 |
December | 0.173812E+11 | 0.457883E+10 | 344.65 | 0.106566E+11 | 0.672458E+10 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 31011.22 | 18-DEC-09:01 | 19006.89 | 27-DEC-09:01 | 17301.87 | 18-DEC-09:01 | 6776.19 | 31-DEC-10:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.241745E+12 | 0.625495E+11 | 4190.90 | 0.136543E+12 | 0.105202E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.167133E+11 | 0.448587E+10 | 316.39 | 0.103945E+11 | 0.606075E+10 | 0.00 | 1.00 | 0.00 | 30604.57 | 14554.31 | 15849.85 | 6629.80 | 0.00 | |||||||
Maximum of Months | 0.241185E+11 | 0.614832E+10 | 365.10 | 0.127328E+11 | 0.114655E+11 | 0.00 | 1.00 | 0.00 | 31062.93 | 19555.63 | 20303.02 | 6916.55 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.172467E+11 | 0.461057E+10 | 343.95 | 0.110479E+11 | 0.619879E+10 | 0.00 | 1.00 | 01-JAN-10:01 | 0.00 | 01-JAN-00:03 | 30877.04 | 02-JAN-09:01 | 18504.97 | 21-JAN-09:01 | 16813.04 | 02-JAN-09:01 | 6645.15 | 03-JAN-09:01 | 0.00 | 01-JAN-00:03 |
February | 0.166785E+11 | 0.447713E+10 | 315.76 | 0.106270E+11 | 0.605153E+10 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:03 | 30615.82 | 16-FEB-09:01 | 19539.41 | 24-FEB-09:01 | 15892.16 | 16-FEB-09:04 | 6711.47 | 26-FEB-10:13 | 0.00 | 01-FEB-00:03 |
March | 0.196229E+11 | 0.529243E+10 | 363.39 | 0.123379E+11 | 0.728501E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:03 | 30889.00 | 27-MAR-08:61 | 19466.36 | 04-MAR-09:01 | 16780.12 | 27-MAR-08:61 | 6838.32 | 26-MAR-09:13 | 0.00 | 01-MAR-00:03 |
April | 0.211489E+11 | 0.554713E+10 | 346.55 | 0.121292E+11 | 0.901971E+10 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:03 | 30898.13 | 24-APR-08:61 | 15903.66 | 27-APR-08:61 | 17560.72 | 03-APR-08:03 | 6784.32 | 09-APR-09:13 | 0.00 | 01-APR-00:03 |
May | 0.240561E+11 | 0.614462E+10 | 362.29 | 0.127253E+11 | 0.113309E+11 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 31061.30 | 17-MAY-08:61 | 15347.30 | 06-MAY-13:00 | 20324.01 | 29-MAY-08:62 | 6916.34 | 07-MAY-09:25 | 0.00 | 01-MAY-00:10 |
June | 0.241182E+11 | 0.612691E+10 | 355.91 | 0.126539E+11 | 0.114644E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 31019.05 | 01-JUN-08:61 | 15074.84 | 21-JUN-08:61 | 19811.72 | 11-JUN-08:62 | 6884.75 | 16-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 0.192785E+11 | 0.497580E+10 | 349.15 | 0.109662E+11 | 0.831226E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 30954.61 | 24-JUL-08:61 | 16143.54 | 06-JUL-08:61 | 17193.46 | 24-JUL-08:61 | 6629.46 | 04-JUL-09:13 | 0.00 | 01-JUL-00:03 |
August | 0.224347E+11 | 0.562326E+10 | 363.67 | 0.113676E+11 | 0.110671E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 31004.09 | 19-AUG-08:61 | 14530.24 | 30-AUG-08:61 | 19769.54 | 21-AUG-08:61 | 6775.29 | 27-AUG-09:25 | 0.00 | 01-AUG-00:10 |
September | 0.208520E+11 | 0.526291E+10 | 343.39 | 0.109028E+11 | 0.994914E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 31061.30 | 18-SEP-08:61 | 15037.08 | 13-SEP-08:61 | 19272.59 | 25-SEP-08:03 | 6695.72 | 03-SEP-09:15 | 0.00 | 01-SEP-00:10 |
October | 0.201456E+11 | 0.508249E+10 | 350.32 | 0.105514E+11 | 0.959414E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 31052.10 | 23-OCT-08:61 | 15581.41 | 20-OCT-08:61 | 18979.14 | 23-OCT-08:04 | 6687.13 | 29-OCT-09:13 | 0.00 | 01-OCT-00:03 |
November | 0.184603E+11 | 0.474645E+10 | 342.12 | 0.103569E+11 | 0.810341E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 30942.50 | 13-NOV-09:01 | 17708.47 | 25-NOV-09:01 | 17952.46 | 12-NOV-10:04 | 6728.79 | 19-NOV-10:13 | 0.00 | 01-NOV-00:10 |
December | 0.173165E+11 | 0.456311E+10 | 343.54 | 0.106094E+11 | 0.670702E+10 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 31010.43 | 18-DEC-09:01 | 18983.90 | 27-DEC-09:01 | 17356.14 | 18-DEC-09:01 | 6775.76 | 31-DEC-10:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.241359E+12 | 0.624528E+11 | 4180.06 | 0.136275E+12 | 0.105083E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.166785E+11 | 0.447713E+10 | 315.76 | 0.103569E+11 | 0.605153E+10 | 0.00 | 1.00 | 0.00 | 30615.82 | 14530.24 | 15892.16 | 6629.46 | 0.00 | |||||||
Maximum of Months | 0.241182E+11 | 0.614462E+10 | 363.67 | 0.127253E+11 | 0.114644E+11 | 0.00 | 1.00 | 0.00 | 31061.30 | 19539.41 | 20324.01 | 6916.34 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.183867E+11 | 0.493582E+10 | 345.44 | 0.118647E+11 | 0.652199E+10 | 0.00 | 1.00 | 01-JAN-10:01 | 0.00 | 01-JAN-00:03 | 33460.99 | 02-JAN-09:01 | 19778.87 | 23-JAN-09:01 | 18434.74 | 02-JAN-09:01 | 7185.57 | 03-JAN-09:03 | 0.00 | 01-JAN-00:03 |
February | 0.178968E+11 | 0.482357E+10 | 317.75 | 0.115067E+11 | 0.639019E+10 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:03 | 33408.61 | 16-FEB-09:01 | 20733.34 | 24-FEB-09:01 | 18230.48 | 16-FEB-09:01 | 7258.47 | 26-FEB-10:13 | 0.00 | 01-FEB-00:03 |
March | 0.211564E+11 | 0.572421E+10 | 364.95 | 0.134014E+11 | 0.775491E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:03 | 33411.10 | 24-MAR-08:61 | 20572.61 | 04-MAR-09:01 | 18622.12 | 24-MAR-08:02 | 7394.81 | 26-MAR-09:13 | 0.00 | 01-MAR-00:03 |
April | 0.228124E+11 | 0.600920E+10 | 348.41 | 0.132321E+11 | 0.958028E+10 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:03 | 33535.28 | 21-APR-08:61 | 16375.02 | 27-APR-08:61 | 20551.78 | 03-APR-07:01 | 7339.95 | 09-APR-09:13 | 0.00 | 01-APR-00:03 |
May | 0.258417E+11 | 0.663781E+10 | 363.57 | 0.138368E+11 | 0.120049E+11 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 33587.54 | 17-MAY-08:61 | 16682.64 | 06-MAY-13:00 | 22693.30 | 30-MAY-07:02 | 7483.70 | 07-MAY-09:25 | 0.00 | 01-MAY-00:10 |
June | 0.259941E+11 | 0.663943E+10 | 356.45 | 0.138349E+11 | 0.121592E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 33541.86 | 01-JUN-08:61 | 16153.41 | 12-JUN-15:00 | 22108.72 | 11-JUN-08:62 | 7421.75 | 16-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 0.207710E+11 | 0.538154E+10 | 351.30 | 0.119729E+11 | 0.879818E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 33533.00 | 24-JUL-08:61 | 17420.37 | 19-JUL-08:61 | 18796.09 | 24-JUL-08:61 | 7168.54 | 04-JUL-09:13 | 0.00 | 01-JUL-00:03 |
August | 0.241084E+11 | 0.607372E+10 | 365.32 | 0.123967E+11 | 0.117117E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 33563.90 | 19-AUG-08:61 | 15073.24 | 30-AUG-08:61 | 21919.31 | 13-AUG-08:62 | 7332.89 | 27-AUG-09:25 | 0.00 | 01-AUG-00:10 |
September | 0.224027E+11 | 0.568350E+10 | 344.74 | 0.119014E+11 | 0.105013E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 33587.54 | 18-SEP-08:61 | 15621.96 | 13-SEP-08:61 | 21527.99 | 05-SEP-07:01 | 7246.63 | 03-SEP-09:15 | 0.00 | 01-SEP-00:10 |
October | 0.213831E+11 | 0.542662E+10 | 351.74 | 0.113401E+11 | 0.100429E+11 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:03 | 33577.59 | 23-OCT-08:61 | 16168.34 | 20-OCT-08:61 | 20587.18 | 23-OCT-08:04 | 7232.94 | 29-OCT-09:13 | 0.00 | 01-OCT-00:03 |
November | 0.196407E+11 | 0.507730E+10 | 343.35 | 0.111492E+11 | 0.849150E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 33459.09 | 13-NOV-09:01 | 18871.38 | 25-NOV-09:01 | 19397.54 | 12-NOV-10:04 | 7276.15 | 19-NOV-10:13 | 0.00 | 01-NOV-00:10 |
December | 0.184255E+11 | 0.487830E+10 | 344.91 | 0.113918E+11 | 0.703368E+10 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 33532.54 | 18-DEC-09:01 | 20007.72 | 27-DEC-09:01 | 18972.27 | 18-DEC-09:03 | 7327.35 | 31-DEC-10:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.258820E+12 | 0.672910E+11 | 4197.94 | 0.147829E+12 | 0.110991E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.178968E+11 | 0.482357E+10 | 317.75 | 0.111492E+11 | 0.639019E+10 | 0.00 | 1.00 | 0.00 | 33408.61 | 15073.24 | 18230.48 | 7168.54 | 0.00 | |||||||
Maximum of Months | 0.259941E+11 | 0.663943E+10 | 365.32 | 0.138368E+11 | 0.121592E+11 | 0.00 | 1.00 | 0.00 | 33587.54 | 20733.34 | 22693.30 | 7483.70 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.63 | 9.96 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.83 | 7.69 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.84 | 5.43 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 62.02 | 2.69 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 63.89 | 3.17 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 62.89 | 3.45 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 57.11 | 5.90 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.97 | 4.79 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 60.65 | 4.81 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 71.23 | 5.97 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 93.00 | 7.17 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.37 | 11.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 76.61 | 6.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.97 | 2.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.63 | 11.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.63 | 9.96 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.83 | 7.69 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.84 | 5.43 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 62.02 | 2.69 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 63.89 | 3.17 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 62.89 | 3.45 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 57.11 | 5.90 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.97 | 4.79 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 60.65 | 4.81 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 71.23 | 5.97 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 93.00 | 7.17 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.37 | 11.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 76.61 | 6.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.97 | 2.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.63 | 11.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.63 | 9.96 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.83 | 7.69 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.84 | 5.43 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 62.02 | 2.69 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 63.89 | 3.17 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 62.89 | 3.45 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 57.11 | 5.90 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.97 | 4.79 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 60.65 | 4.81 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 71.23 | 5.97 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 93.00 | 7.17 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.37 | 11.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 76.61 | 6.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.97 | 2.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.63 | 11.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.63 | 9.96 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.83 | 7.69 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.84 | 5.43 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 62.02 | 2.69 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 63.89 | 3.17 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 62.89 | 3.45 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 57.11 | 5.90 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.97 | 4.79 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 60.65 | 4.81 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 71.23 | 5.97 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 93.00 | 7.17 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.37 | 11.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 76.61 | 6.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.97 | 2.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.63 | 11.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.91 | 32.50 | 45.41 | 136.26 | 11.99 | 0.00 | 0.00 | 744.00 |
February | 66.15 | 21.56 | 44.59 | 117.23 | 9.28 | 0.00 | 0.00 | 672.00 |
March | 45.13 | 6.04 | 39.09 | 83.54 | 6.58 | 0.00 | 0.00 | 744.00 |
April | 33.66 | 0.01 | 33.65 | 74.06 | 3.25 | 0.00 | 0.00 | 720.00 |
May | 33.69 | 0.00 | 33.69 | 76.31 | 3.83 | 0.00 | 0.00 | 744.00 |
June | 33.57 | 0.00 | 33.57 | 75.11 | 4.16 | 0.00 | 0.00 | 720.00 |
July | 34.58 | 0.00 | 34.58 | 68.32 | 7.11 | 0.00 | 0.00 | 744.00 |
August | 33.66 | 0.05 | 33.61 | 65.73 | 5.78 | 0.00 | 0.00 | 744.00 |
September | 37.26 | 1.21 | 36.05 | 72.56 | 5.80 | 0.00 | 0.00 | 720.00 |
October | 48.75 | 7.76 | 40.98 | 85.33 | 7.20 | 0.00 | 0.00 | 744.00 |
November | 63.39 | 19.33 | 44.06 | 111.48 | 8.64 | 0.00 | 0.00 | 720.00 |
December | 77.87 | 33.13 | 44.75 | 135.96 | 13.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.73 | 10.09 | 38.64 | 91.71 | 7.28 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 33.57 | 0.00 | 33.57 | 65.73 | 3.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 77.91 | 33.13 | 45.41 | 136.26 | 13.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.91 | 32.50 | 45.41 | 136.26 | 11.99 | 0.00 | 0.00 | 744.00 |
February | 66.15 | 21.56 | 44.59 | 117.23 | 9.28 | 0.00 | 0.00 | 672.00 |
March | 45.13 | 6.04 | 39.09 | 83.54 | 6.58 | 0.00 | 0.00 | 744.00 |
April | 33.66 | 0.01 | 33.65 | 74.06 | 3.25 | 0.00 | 0.00 | 720.00 |
May | 33.69 | 0.00 | 33.69 | 76.31 | 3.83 | 0.00 | 0.00 | 744.00 |
June | 33.57 | 0.00 | 33.57 | 75.11 | 4.16 | 0.00 | 0.00 | 720.00 |
July | 34.58 | 0.00 | 34.58 | 68.32 | 7.11 | 0.00 | 0.00 | 744.00 |
August | 33.66 | 0.05 | 33.61 | 65.73 | 5.78 | 0.00 | 0.00 | 744.00 |
September | 37.26 | 1.21 | 36.05 | 72.56 | 5.80 | 0.00 | 0.00 | 720.00 |
October | 48.75 | 7.76 | 40.98 | 85.33 | 7.20 | 0.00 | 0.00 | 744.00 |
November | 63.39 | 19.33 | 44.06 | 111.48 | 8.64 | 0.00 | 0.00 | 720.00 |
December | 77.87 | 33.13 | 44.75 | 135.96 | 13.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.73 | 10.09 | 38.64 | 91.71 | 7.28 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 33.57 | 0.00 | 33.57 | 65.73 | 3.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 77.91 | 33.13 | 45.41 | 136.26 | 13.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.83 | 9.87 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 98.19 | 7.55 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 70.39 | 5.26 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 62.67 | 2.54 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 64.49 | 3.06 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 63.55 | 3.30 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 57.53 | 5.74 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 55.44 | 4.63 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 61.09 | 4.66 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 71.51 | 5.87 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 93.26 | 7.08 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.53 | 11.31 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 77.03 | 5.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 55.44 | 2.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.83 | 11.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.83 | 9.87 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 98.19 | 7.55 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 70.39 | 5.26 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 62.67 | 2.54 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 64.49 | 3.06 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 63.55 | 3.30 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 57.53 | 5.74 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 55.44 | 4.63 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 61.09 | 4.66 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 71.51 | 5.87 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 93.26 | 7.08 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.53 | 11.31 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 77.03 | 5.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 55.44 | 2.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.83 | 11.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.91 | 32.50 | 45.41 | 136.51 | 11.88 | 0.00 | 0.00 | 744.00 |
February | 66.15 | 21.56 | 44.59 | 117.67 | 9.11 | 0.00 | 0.00 | 672.00 |
March | 45.13 | 6.04 | 39.09 | 84.18 | 6.37 | 0.00 | 0.00 | 744.00 |
April | 33.66 | 0.01 | 33.65 | 74.84 | 3.08 | 0.00 | 0.00 | 720.00 |
May | 33.69 | 0.00 | 33.69 | 77.04 | 3.70 | 0.00 | 0.00 | 744.00 |
June | 33.57 | 0.00 | 33.57 | 75.90 | 3.98 | 0.00 | 0.00 | 720.00 |
July | 34.58 | 0.00 | 34.58 | 68.82 | 6.91 | 0.00 | 0.00 | 744.00 |
August | 33.66 | 0.05 | 33.61 | 66.29 | 5.59 | 0.00 | 0.00 | 744.00 |
September | 37.26 | 1.21 | 36.05 | 73.09 | 5.61 | 0.00 | 0.00 | 720.00 |
October | 48.75 | 7.76 | 40.98 | 85.67 | 7.08 | 0.00 | 0.00 | 744.00 |
November | 63.39 | 19.33 | 44.06 | 111.80 | 8.53 | 0.00 | 0.00 | 720.00 |
December | 77.87 | 33.13 | 44.75 | 136.17 | 13.60 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.73 | 10.09 | 38.64 | 92.22 | 7.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 33.57 | 0.00 | 33.57 | 66.29 | 3.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 77.91 | 33.13 | 45.41 | 136.51 | 13.60 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.48 | 12.48 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.71 | 10.11 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.70 | 7.59 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 60.56 | 3.89 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 62.33 | 4.43 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 61.64 | 4.80 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 56.20 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.70 | 6.75 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 59.94 | 6.66 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.84 | 8.21 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.81 | 9.38 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.34 | 13.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 76.01 | 8.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.70 | 3.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.48 | 13.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.48 | 12.48 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.71 | 10.11 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.70 | 7.59 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 60.56 | 3.89 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 62.33 | 4.43 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 61.64 | 4.80 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 56.20 | 7.82 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.70 | 6.75 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 59.94 | 6.66 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.84 | 8.21 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.81 | 9.38 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.34 | 13.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 76.01 | 8.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.70 | 3.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.48 | 13.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.48 | 32.32 | 45.16 | 135.36 | 14.87 | 0.00 | 0.00 | 744.00 |
February | 65.79 | 21.44 | 44.35 | 116.48 | 12.07 | 0.00 | 0.00 | 672.00 |
March | 44.88 | 6.00 | 38.88 | 82.96 | 9.09 | 0.00 | 0.00 | 744.00 |
April | 33.48 | 0.01 | 33.47 | 72.00 | 4.67 | 0.00 | 0.00 | 720.00 |
May | 33.50 | 0.00 | 33.50 | 74.11 | 5.29 | 0.00 | 0.00 | 744.00 |
June | 33.38 | 0.00 | 33.38 | 73.28 | 5.74 | 0.00 | 0.00 | 720.00 |
July | 34.39 | 0.00 | 34.39 | 66.91 | 9.32 | 0.00 | 0.00 | 744.00 |
August | 33.48 | 0.05 | 33.43 | 65.08 | 8.06 | 0.00 | 0.00 | 744.00 |
September | 37.05 | 1.20 | 35.85 | 71.37 | 7.94 | 0.00 | 0.00 | 720.00 |
October | 48.48 | 7.72 | 40.76 | 84.43 | 9.78 | 0.00 | 0.00 | 744.00 |
November | 63.04 | 19.23 | 43.82 | 110.68 | 11.18 | 0.00 | 0.00 | 720.00 |
December | 77.45 | 32.95 | 44.50 | 135.20 | 16.55 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.47 | 10.04 | 38.43 | 90.54 | 9.55 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 33.38 | 0.00 | 33.38 | 65.08 | 4.67 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 77.48 | 32.95 | 45.16 | 135.36 | 16.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.42 | 12.68 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.64 | 10.32 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.65 | 7.81 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 60.45 | 4.12 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 62.16 | 4.64 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 61.53 | 5.05 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 56.12 | 8.07 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.64 | 6.95 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 59.87 | 6.88 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.78 | 8.42 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.76 | 9.55 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.29 | 14.05 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 75.93 | 8.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.64 | 4.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.42 | 14.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.42 | 12.68 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.64 | 10.32 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.65 | 7.81 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 60.45 | 4.12 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 62.16 | 4.64 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 61.53 | 5.05 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 56.12 | 8.07 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.64 | 6.95 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 59.87 | 6.88 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.78 | 8.42 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.76 | 9.55 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.29 | 14.05 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 75.93 | 8.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.64 | 4.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.42 | 14.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.48 | 32.32 | 45.16 | 135.28 | 15.11 | 0.00 | 0.00 | 744.00 |
February | 65.79 | 21.44 | 44.35 | 116.39 | 12.32 | 0.00 | 0.00 | 672.00 |
March | 44.88 | 6.00 | 38.88 | 82.89 | 9.35 | 0.00 | 0.00 | 744.00 |
April | 33.48 | 0.01 | 33.47 | 71.87 | 4.95 | 0.00 | 0.00 | 720.00 |
May | 33.50 | 0.00 | 33.50 | 73.91 | 5.54 | 0.00 | 0.00 | 744.00 |
June | 33.38 | 0.00 | 33.38 | 73.15 | 6.03 | 0.00 | 0.00 | 720.00 |
July | 34.39 | 0.00 | 34.39 | 66.81 | 9.62 | 0.00 | 0.00 | 744.00 |
August | 33.48 | 0.05 | 33.43 | 65.01 | 8.30 | 0.00 | 0.00 | 744.00 |
September | 37.05 | 1.20 | 35.85 | 71.28 | 8.20 | 0.00 | 0.00 | 720.00 |
October | 48.48 | 7.72 | 40.76 | 84.36 | 10.03 | 0.00 | 0.00 | 744.00 |
November | 63.04 | 19.23 | 43.82 | 110.62 | 11.39 | 0.00 | 0.00 | 720.00 |
December | 77.45 | 32.95 | 44.50 | 135.14 | 16.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.47 | 10.04 | 38.43 | 90.44 | 9.80 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 33.38 | 0.00 | 33.38 | 65.01 | 4.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 77.48 | 32.95 | 45.16 | 135.28 | 16.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.50 | 12.45 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.72 | 10.10 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.71 | 7.56 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 60.54 | 3.91 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 62.26 | 4.46 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 61.63 | 4.86 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 56.18 | 7.85 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.72 | 6.71 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 59.94 | 6.65 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.85 | 8.19 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.84 | 9.33 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.37 | 13.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 76.01 | 7.99 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.72 | 3.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.50 | 13.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.50 | 12.45 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.72 | 10.10 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.71 | 7.56 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 60.54 | 3.91 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 62.26 | 4.46 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 61.63 | 4.86 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 56.18 | 7.85 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.72 | 6.71 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 59.94 | 6.65 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.85 | 8.19 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.84 | 9.33 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.37 | 13.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 76.01 | 7.99 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.72 | 3.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.50 | 13.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.48 | 32.32 | 45.16 | 135.38 | 14.85 | 0.00 | 0.00 | 744.00 |
February | 65.79 | 21.44 | 44.35 | 116.49 | 12.05 | 0.00 | 0.00 | 672.00 |
March | 44.88 | 6.00 | 38.88 | 82.97 | 9.06 | 0.00 | 0.00 | 744.00 |
April | 33.48 | 0.01 | 33.47 | 71.98 | 4.70 | 0.00 | 0.00 | 720.00 |
May | 33.50 | 0.00 | 33.50 | 74.03 | 5.33 | 0.00 | 0.00 | 744.00 |
June | 33.38 | 0.00 | 33.38 | 73.26 | 5.80 | 0.00 | 0.00 | 720.00 |
July | 34.39 | 0.00 | 34.39 | 66.89 | 9.36 | 0.00 | 0.00 | 744.00 |
August | 33.48 | 0.05 | 33.43 | 65.10 | 8.02 | 0.00 | 0.00 | 744.00 |
September | 37.05 | 1.20 | 35.85 | 71.37 | 7.94 | 0.00 | 0.00 | 720.00 |
October | 48.48 | 7.72 | 40.76 | 84.45 | 9.76 | 0.00 | 0.00 | 744.00 |
November | 63.04 | 19.23 | 43.82 | 110.71 | 11.13 | 0.00 | 0.00 | 720.00 |
December | 77.45 | 32.95 | 44.50 | 135.25 | 16.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.47 | 10.04 | 38.43 | 90.54 | 9.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 33.38 | 0.00 | 33.38 | 65.10 | 4.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 77.48 | 32.95 | 45.16 | 135.38 | 16.47 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.19 | 11.65 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.32 | 9.27 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.33 | 6.73 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 60.37 | 3.37 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 62.02 | 3.89 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 61.44 | 4.28 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 55.86 | 7.14 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.40 | 5.89 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 59.71 | 5.96 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.58 | 7.42 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.54 | 8.57 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.08 | 13.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 75.72 | 7.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.40 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.19 | 13.04 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.19 | 11.65 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.32 | 9.27 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.33 | 6.73 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 60.37 | 3.37 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 62.02 | 3.89 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 61.44 | 4.28 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 55.86 | 7.14 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.40 | 5.89 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 59.71 | 5.96 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.58 | 7.42 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.54 | 8.57 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.08 | 13.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 75.72 | 7.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.40 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.19 | 13.04 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.19 | 11.65 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.32 | 9.27 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.33 | 6.73 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 60.37 | 3.37 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 62.02 | 3.89 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 61.44 | 4.28 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 55.86 | 7.14 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.40 | 5.89 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 59.71 | 5.96 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.58 | 7.42 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.54 | 8.57 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.08 | 13.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 75.72 | 7.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.40 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.19 | 13.04 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.19 | 11.65 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.32 | 9.27 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.33 | 6.73 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 60.37 | 3.37 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 62.02 | 3.89 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 61.44 | 4.28 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 55.86 | 7.14 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.40 | 5.89 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 59.71 | 5.96 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.58 | 7.42 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.54 | 8.57 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.08 | 13.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 75.72 | 7.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.40 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.19 | 13.04 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.48 | 32.32 | 45.16 | 135.02 | 13.90 | 0.00 | 0.00 | 744.00 |
February | 65.79 | 21.44 | 44.35 | 116.02 | 11.07 | 0.00 | 0.00 | 672.00 |
March | 44.88 | 6.00 | 38.88 | 82.53 | 8.07 | 0.00 | 0.00 | 744.00 |
April | 33.48 | 0.01 | 33.47 | 71.78 | 4.05 | 0.00 | 0.00 | 720.00 |
May | 33.50 | 0.00 | 33.50 | 73.76 | 4.66 | 0.00 | 0.00 | 744.00 |
June | 33.38 | 0.00 | 33.38 | 73.05 | 5.12 | 0.00 | 0.00 | 720.00 |
July | 34.39 | 0.00 | 34.39 | 66.51 | 8.52 | 0.00 | 0.00 | 744.00 |
August | 33.48 | 0.05 | 33.43 | 64.75 | 7.04 | 0.00 | 0.00 | 744.00 |
September | 37.05 | 1.20 | 35.85 | 71.11 | 7.11 | 0.00 | 0.00 | 720.00 |
October | 48.48 | 7.72 | 40.76 | 84.14 | 8.84 | 0.00 | 0.00 | 744.00 |
November | 63.04 | 19.23 | 43.82 | 110.37 | 10.22 | 0.00 | 0.00 | 720.00 |
December | 77.45 | 32.95 | 44.50 | 134.92 | 15.55 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.47 | 10.04 | 38.43 | 90.21 | 8.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 33.38 | 0.00 | 33.38 | 64.75 | 4.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 77.48 | 32.95 | 45.16 | 135.02 | 15.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.48 | 32.32 | 45.16 | 135.02 | 13.90 | 0.00 | 0.00 | 744.00 |
February | 65.79 | 21.44 | 44.35 | 116.02 | 11.07 | 0.00 | 0.00 | 672.00 |
March | 44.88 | 6.00 | 38.88 | 82.53 | 8.07 | 0.00 | 0.00 | 744.00 |
April | 33.48 | 0.01 | 33.47 | 71.78 | 4.05 | 0.00 | 0.00 | 720.00 |
May | 33.50 | 0.00 | 33.50 | 73.76 | 4.66 | 0.00 | 0.00 | 744.00 |
June | 33.38 | 0.00 | 33.38 | 73.05 | 5.12 | 0.00 | 0.00 | 720.00 |
July | 34.39 | 0.00 | 34.39 | 66.51 | 8.52 | 0.00 | 0.00 | 744.00 |
August | 33.48 | 0.05 | 33.43 | 64.75 | 7.04 | 0.00 | 0.00 | 744.00 |
September | 37.05 | 1.20 | 35.85 | 71.11 | 7.11 | 0.00 | 0.00 | 720.00 |
October | 48.48 | 7.72 | 40.76 | 84.14 | 8.84 | 0.00 | 0.00 | 744.00 |
November | 63.04 | 19.23 | 43.82 | 110.37 | 10.22 | 0.00 | 0.00 | 720.00 |
December | 77.45 | 32.95 | 44.50 | 134.92 | 15.55 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.47 | 10.04 | 38.43 | 90.21 | 8.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 33.38 | 0.00 | 33.38 | 64.75 | 4.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 77.48 | 32.95 | 45.16 | 135.02 | 15.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.36 | 11.26 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.57 | 8.84 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.69 | 6.27 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 60.86 | 3.02 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 62.52 | 3.59 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 61.94 | 3.94 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 56.13 | 6.76 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.71 | 5.48 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 60.01 | 5.58 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.81 | 7.02 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.73 | 8.19 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.23 | 12.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 76.03 | 6.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.71 | 3.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.36 | 12.67 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.36 | 11.26 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.57 | 8.84 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.69 | 6.27 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 60.86 | 3.02 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 62.52 | 3.59 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 61.94 | 3.94 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 56.13 | 6.76 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.71 | 5.48 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 60.01 | 5.58 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.81 | 7.02 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.73 | 8.19 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.23 | 12.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 76.03 | 6.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.71 | 3.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.36 | 12.67 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.48 | 32.32 | 45.16 | 135.23 | 13.43 | 0.00 | 0.00 | 744.00 |
February | 65.79 | 21.44 | 44.35 | 116.33 | 10.57 | 0.00 | 0.00 | 672.00 |
March | 44.88 | 6.00 | 38.88 | 82.95 | 7.53 | 0.00 | 0.00 | 744.00 |
April | 33.48 | 0.01 | 33.47 | 72.37 | 3.63 | 0.00 | 0.00 | 720.00 |
May | 33.50 | 0.00 | 33.50 | 74.35 | 4.29 | 0.00 | 0.00 | 744.00 |
June | 33.38 | 0.00 | 33.38 | 73.65 | 4.71 | 0.00 | 0.00 | 720.00 |
July | 34.39 | 0.00 | 34.39 | 66.85 | 8.06 | 0.00 | 0.00 | 744.00 |
August | 33.48 | 0.05 | 33.43 | 65.12 | 6.55 | 0.00 | 0.00 | 744.00 |
September | 37.05 | 1.20 | 35.85 | 71.47 | 6.66 | 0.00 | 0.00 | 720.00 |
October | 48.48 | 7.72 | 40.76 | 84.42 | 8.38 | 0.00 | 0.00 | 744.00 |
November | 63.04 | 19.23 | 43.82 | 110.61 | 9.77 | 0.00 | 0.00 | 720.00 |
December | 77.45 | 32.95 | 44.50 | 135.10 | 15.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.47 | 10.04 | 38.43 | 90.59 | 8.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 33.38 | 0.00 | 33.38 | 65.12 | 3.63 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 77.48 | 32.95 | 45.16 | 135.23 | 15.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.44 | 11.16 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.64 | 8.75 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.76 | 6.18 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 60.95 | 2.95 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 62.62 | 3.52 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 62.03 | 3.86 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 56.21 | 6.67 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.79 | 5.39 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 60.08 | 5.50 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.88 | 6.93 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.81 | 8.10 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.31 | 12.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 76.11 | 6.80 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.79 | 2.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.44 | 12.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.44 | 11.16 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.64 | 8.75 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.76 | 6.18 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 60.95 | 2.95 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 62.62 | 3.52 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 62.03 | 3.86 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 56.21 | 6.67 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.79 | 5.39 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 60.08 | 5.50 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.88 | 6.93 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.81 | 8.10 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.31 | 12.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 76.11 | 6.80 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.79 | 2.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.44 | 12.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.48 | 32.32 | 45.16 | 135.33 | 13.31 | 0.00 | 0.00 | 744.00 |
February | 65.79 | 21.44 | 44.35 | 116.42 | 10.46 | 0.00 | 0.00 | 672.00 |
March | 44.88 | 6.00 | 38.88 | 83.04 | 7.42 | 0.00 | 0.00 | 744.00 |
April | 33.48 | 0.01 | 33.47 | 72.47 | 3.55 | 0.00 | 0.00 | 720.00 |
May | 33.50 | 0.00 | 33.50 | 74.47 | 4.22 | 0.00 | 0.00 | 744.00 |
June | 33.38 | 0.00 | 33.38 | 73.76 | 4.62 | 0.00 | 0.00 | 720.00 |
July | 34.39 | 0.00 | 34.39 | 66.94 | 7.96 | 0.00 | 0.00 | 744.00 |
August | 33.48 | 0.05 | 33.43 | 65.21 | 6.45 | 0.00 | 0.00 | 744.00 |
September | 37.05 | 1.20 | 35.85 | 71.56 | 6.56 | 0.00 | 0.00 | 720.00 |
October | 48.48 | 7.72 | 40.76 | 84.51 | 8.26 | 0.00 | 0.00 | 744.00 |
November | 63.04 | 19.23 | 43.82 | 110.70 | 9.66 | 0.00 | 0.00 | 720.00 |
December | 77.45 | 32.95 | 44.50 | 135.20 | 14.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.47 | 10.04 | 38.43 | 90.68 | 8.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 33.38 | 0.00 | 33.38 | 65.21 | 3.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 77.48 | 32.95 | 45.16 | 135.33 | 14.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.46 | 11.10 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.64 | 8.71 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.74 | 6.16 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 60.90 | 2.95 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 62.56 | 3.52 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 61.97 | 3.87 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 56.17 | 6.67 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.75 | 5.38 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 60.05 | 5.49 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.88 | 6.88 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.82 | 8.05 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.33 | 12.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 76.09 | 6.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.75 | 2.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.46 | 12.51 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 113.46 | 11.10 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.64 | 8.71 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.74 | 6.16 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 60.90 | 2.95 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 62.56 | 3.52 | 0.00 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 61.97 | 3.87 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 56.17 | 6.67 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.75 | 5.38 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 60.05 | 5.49 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.88 | 6.88 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.82 | 8.05 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 113.33 | 12.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 76.09 | 6.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.75 | 2.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 113.46 | 12.51 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.48 | 32.32 | 45.16 | 135.35 | 13.24 | 0.00 | 0.00 | 744.00 |
February | 65.79 | 21.44 | 44.35 | 116.41 | 10.42 | 0.00 | 0.00 | 672.00 |
March | 44.88 | 6.00 | 38.88 | 83.02 | 7.39 | 0.00 | 0.00 | 744.00 |
April | 33.48 | 0.01 | 33.47 | 72.41 | 3.54 | 0.00 | 0.00 | 720.00 |
May | 33.50 | 0.00 | 33.50 | 74.40 | 4.22 | 0.00 | 0.00 | 744.00 |
June | 33.38 | 0.00 | 33.38 | 73.68 | 4.63 | 0.00 | 0.00 | 720.00 |
July | 34.39 | 0.00 | 34.39 | 66.89 | 7.96 | 0.00 | 0.00 | 744.00 |
August | 33.48 | 0.05 | 33.43 | 65.17 | 6.44 | 0.00 | 0.00 | 744.00 |
September | 37.05 | 1.20 | 35.85 | 71.51 | 6.56 | 0.00 | 0.00 | 720.00 |
October | 48.48 | 7.72 | 40.76 | 84.50 | 8.20 | 0.00 | 0.00 | 744.00 |
November | 63.04 | 19.23 | 43.82 | 110.72 | 9.61 | 0.00 | 0.00 | 720.00 |
December | 77.45 | 32.95 | 44.50 | 135.23 | 14.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.47 | 10.04 | 38.43 | 90.66 | 8.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 33.38 | 0.00 | 33.38 | 65.17 | 3.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 77.48 | 32.95 | 45.16 | 135.35 | 14.91 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 112.99 | 11.26 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.01 | 9.00 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.04 | 6.47 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 59.95 | 3.29 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 61.57 | 3.83 | 4.67 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 60.96 | 4.28 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 55.40 | 7.16 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.02 | 5.79 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 59.26 | 5.94 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.36 | 7.14 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.31 | 8.27 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 112.91 | 12.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 75.39 | 7.09 | 4.67 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.02 | 3.29 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 112.99 | 12.65 | 4.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.71 | 26.99 | 37.72 | 112.99 | 11.26 | 0.00 | 0.00 | 744.00 |
February | 54.95 | 17.91 | 37.04 | 97.01 | 9.00 | 0.00 | 0.00 | 672.00 |
March | 37.48 | 5.01 | 32.47 | 69.04 | 6.47 | 0.00 | 0.00 | 744.00 |
April | 27.96 | 0.01 | 27.95 | 59.95 | 3.29 | 0.00 | 0.00 | 720.00 |
May | 27.98 | 0.00 | 27.98 | 61.57 | 3.83 | 4.67 | 0.00 | 744.00 |
June | 27.88 | 0.00 | 27.88 | 60.96 | 4.28 | 0.00 | 0.00 | 720.00 |
July | 28.72 | 0.00 | 28.72 | 55.40 | 7.16 | 0.00 | 0.00 | 744.00 |
August | 27.96 | 0.04 | 27.92 | 54.02 | 5.79 | 0.00 | 0.00 | 744.00 |
September | 30.95 | 1.00 | 29.94 | 59.26 | 5.94 | 0.00 | 0.00 | 720.00 |
October | 40.49 | 6.45 | 34.04 | 70.36 | 7.14 | 0.00 | 0.00 | 744.00 |
November | 52.65 | 16.06 | 36.59 | 92.31 | 8.27 | 0.00 | 0.00 | 720.00 |
December | 64.68 | 27.51 | 37.17 | 112.91 | 12.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.48 | 8.38 | 32.09 | 75.39 | 7.09 | 4.67 | 0.00 | 8760.00 |
Minimum of Months | 27.88 | 0.00 | 27.88 | 54.02 | 3.29 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 64.71 | 27.51 | 37.72 | 112.99 | 12.65 | 4.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.48 | 32.32 | 45.16 | 134.79 | 13.43 | 0.00 | 0.00 | 744.00 |
February | 65.79 | 21.44 | 44.35 | 115.65 | 10.76 | 0.00 | 0.00 | 672.00 |
March | 44.88 | 6.00 | 38.88 | 82.18 | 7.76 | 0.00 | 0.00 | 744.00 |
April | 33.48 | 0.01 | 33.47 | 71.27 | 3.96 | 0.00 | 0.00 | 720.00 |
May | 33.50 | 0.00 | 33.50 | 73.21 | 4.58 | 4.67 | 0.00 | 744.00 |
June | 33.38 | 0.00 | 33.38 | 72.47 | 5.12 | 0.00 | 0.00 | 720.00 |
July | 34.39 | 0.00 | 34.39 | 65.96 | 8.55 | 0.00 | 0.00 | 744.00 |
August | 33.48 | 0.05 | 33.43 | 64.29 | 6.93 | 0.00 | 0.00 | 744.00 |
September | 37.05 | 1.20 | 35.85 | 70.57 | 7.09 | 0.00 | 0.00 | 720.00 |
October | 48.48 | 7.72 | 40.76 | 83.88 | 8.51 | 0.00 | 0.00 | 744.00 |
November | 63.04 | 19.23 | 43.82 | 110.09 | 9.87 | 0.00 | 0.00 | 720.00 |
December | 77.45 | 32.95 | 44.50 | 134.71 | 15.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.47 | 10.04 | 38.43 | 89.81 | 8.47 | 4.67 | 0.00 | 8760.00 |
Minimum of Months | 33.38 | 0.00 | 33.38 | 64.29 | 3.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 77.48 | 32.95 | 45.16 | 134.79 | 15.09 | 4.67 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.304352E+09 | 26671585.10 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.236674E+09 | 18593762.41 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.187066E+09 | 14544697.48 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.160758E+09 | 6960000.52 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.171123E+09 | 8502200.40 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.163014E+09 | 8947306.34 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.152973E+09 | 15811945.47 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.147244E+09 | 12829087.39 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.157200E+09 | 12473927.98 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.190777E+09 | 15988033.30 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.241051E+09 | 18582212.89 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.303638E+09 | 30517567.71 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.241587E+10 | 0.190422E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.147244E+09 | 6960000.52 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.304352E+09 | 30517567.71 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.304352E+09 | 26671585.10 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.236674E+09 | 18593762.41 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.187066E+09 | 14544697.48 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.160758E+09 | 6960000.52 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.171123E+09 | 8502200.40 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.163014E+09 | 8947306.34 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.152973E+09 | 15811945.47 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.147244E+09 | 12829087.39 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.157200E+09 | 12473927.98 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.190777E+09 | 15988033.30 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.241051E+09 | 18582212.89 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.303638E+09 | 30517567.71 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.241587E+10 | 0.190422E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.147244E+09 | 6960000.52 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.304352E+09 | 30517567.71 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.304352E+09 | 26671585.10 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.236674E+09 | 18593762.41 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.187066E+09 | 14544697.48 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.160758E+09 | 6960000.52 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.171123E+09 | 8502200.40 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.163014E+09 | 8947306.34 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.152973E+09 | 15811945.47 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.147244E+09 | 12829087.39 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.157200E+09 | 12473927.98 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.190777E+09 | 15988033.30 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.241051E+09 | 18582212.89 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.303638E+09 | 30517567.71 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.241587E+10 | 0.190422E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.147244E+09 | 6960000.52 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.304352E+09 | 30517567.71 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.304352E+09 | 26671585.10 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.236674E+09 | 18593762.41 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.187066E+09 | 14544697.48 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.160758E+09 | 6960000.52 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.171123E+09 | 8502200.40 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.163014E+09 | 8947306.34 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.152973E+09 | 15811945.47 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.147244E+09 | 12829087.39 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.157200E+09 | 12473927.98 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.190777E+09 | 15988033.30 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.241051E+09 | 18582212.89 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.303638E+09 | 30517567.71 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.241587E+10 | 0.190422E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.147244E+09 | 6960000.52 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.304352E+09 | 30517567.71 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208666E+09 | 87038661.22 | 0.121628E+09 | 0.364955E+09 | 32117890.42 |
February | 0.160032E+09 | 52152796.71 | 0.107879E+09 | 0.283608E+09 | 22454128.43 |
March | 0.120869E+09 | 16170523.79 | 0.104698E+09 | 0.223744E+09 | 17622432.09 |
April | 87257009.42 | 37570.35 | 87219439.07 | 0.191954E+09 | 8425476.52 |
May | 90228797.30 | 0.00 | 90228797.30 | 0.204399E+09 | 10254617.59 |
June | 87003851.23 | 0.00 | 87003851.23 | 0.194691E+09 | 10789538.98 |
July | 92614653.21 | 0.00 | 92614653.21 | 0.182984E+09 | 19035782.42 |
August | 90158792.68 | 137072.17 | 90021720.51 | 0.176040E+09 | 15488771.07 |
September | 96571592.00 | 3131542.89 | 93440049.11 | 0.188068E+09 | 15036888.33 |
October | 0.130561E+09 | 20795394.03 | 0.109766E+09 | 0.228546E+09 | 19273708.01 |
November | 0.164303E+09 | 50109508.94 | 0.114194E+09 | 0.288962E+09 | 22390553.33 |
December | 0.208570E+09 | 88725030.59 | 0.119845E+09 | 0.364157E+09 | 36714360.06 |
Annual Sum or Average | 0.153684E+10 | 0.318298E+09 | 0.121854E+10 | 0.289211E+10 | 0.229604E+09 |
Minimum of Months | 87003851.23 | 0.00 | 87003851.23 | 0.176040E+09 | 8425476.52 |
Maximum of Months | 0.208666E+09 | 88725030.59 | 0.121628E+09 | 0.364955E+09 | 36714360.06 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208666E+09 | 87038661.22 | 0.121628E+09 | 0.364955E+09 | 32117890.42 |
February | 0.160032E+09 | 52152796.71 | 0.107879E+09 | 0.283608E+09 | 22454128.43 |
March | 0.120869E+09 | 16170523.79 | 0.104698E+09 | 0.223744E+09 | 17622432.09 |
April | 87257009.42 | 37570.35 | 87219439.07 | 0.191954E+09 | 8425476.52 |
May | 90228797.30 | 0.00 | 90228797.30 | 0.204399E+09 | 10254617.59 |
June | 87003851.23 | 0.00 | 87003851.23 | 0.194691E+09 | 10789538.98 |
July | 92614653.21 | 0.00 | 92614653.21 | 0.182984E+09 | 19035782.42 |
August | 90158792.68 | 137072.17 | 90021720.51 | 0.176040E+09 | 15488771.07 |
September | 96571592.00 | 3131542.89 | 93440049.11 | 0.188068E+09 | 15036888.33 |
October | 0.130561E+09 | 20795394.03 | 0.109766E+09 | 0.228546E+09 | 19273708.01 |
November | 0.164303E+09 | 50109508.94 | 0.114194E+09 | 0.288962E+09 | 22390553.33 |
December | 0.208570E+09 | 88725030.59 | 0.119845E+09 | 0.364157E+09 | 36714360.06 |
Annual Sum or Average | 0.153684E+10 | 0.318298E+09 | 0.121854E+10 | 0.289211E+10 | 0.229604E+09 |
Minimum of Months | 87003851.23 | 0.00 | 87003851.23 | 0.176040E+09 | 8425476.52 |
Maximum of Months | 0.208666E+09 | 88725030.59 | 0.121628E+09 | 0.364955E+09 | 36714360.06 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.304880E+09 | 26430858.94 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.237547E+09 | 18255656.42 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.188521E+09 | 14096578.69 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.162448E+09 | 6591693.04 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.172728E+09 | 8207046.65 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.164717E+09 | 8564417.61 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.154075E+09 | 15378946.18 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.148489E+09 | 12400097.06 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.158347E+09 | 12074304.67 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.191525E+09 | 15734640.02 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.241717E+09 | 18346003.84 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.304081E+09 | 30299569.19 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.242907E+10 | 0.186380E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.148489E+09 | 6591693.04 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.304880E+09 | 30299569.19 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.304880E+09 | 26430858.94 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.237547E+09 | 18255656.42 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.188521E+09 | 14096578.69 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.162448E+09 | 6591693.04 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.172728E+09 | 8207046.65 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.164717E+09 | 8564417.61 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.154075E+09 | 15378946.18 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.148489E+09 | 12400097.06 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.158347E+09 | 12074304.67 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.191525E+09 | 15734640.02 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.241717E+09 | 18346003.84 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.304081E+09 | 30299569.19 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.242907E+10 | 0.186380E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.148489E+09 | 6591693.04 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.304880E+09 | 30299569.19 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208666E+09 | 87038661.22 | 0.121628E+09 | 0.365618E+09 | 31815881.89 |
February | 0.160032E+09 | 52152796.71 | 0.107879E+09 | 0.284664E+09 | 22033396.39 |
March | 0.120869E+09 | 16170523.79 | 0.104698E+09 | 0.225478E+09 | 17068063.03 |
April | 87257009.42 | 37570.35 | 87219439.07 | 0.193991E+09 | 7986434.67 |
May | 90228797.30 | 0.00 | 90228797.30 | 0.206335E+09 | 9898206.44 |
June | 87003851.23 | 0.00 | 87003851.23 | 0.196742E+09 | 10326350.63 |
July | 92614653.21 | 0.00 | 92614653.21 | 0.184325E+09 | 18507667.20 |
August | 90158792.68 | 137072.17 | 90021720.51 | 0.177546E+09 | 14968057.92 |
September | 96571592.00 | 3131542.89 | 93440049.11 | 0.189462E+09 | 14553115.58 |
October | 0.130561E+09 | 20795394.03 | 0.109766E+09 | 0.229472E+09 | 18959380.62 |
November | 0.164303E+09 | 50109508.94 | 0.114194E+09 | 0.289794E+09 | 22098560.31 |
December | 0.208570E+09 | 88725030.59 | 0.119845E+09 | 0.364722E+09 | 36437404.11 |
Annual Sum or Average | 0.153684E+10 | 0.318298E+09 | 0.121854E+10 | 0.290815E+10 | 0.224653E+09 |
Minimum of Months | 87003851.23 | 0.00 | 87003851.23 | 0.177546E+09 | 7986434.67 |
Maximum of Months | 0.208666E+09 | 88725030.59 | 0.121628E+09 | 0.365618E+09 | 36437404.11 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.303956E+09 | 33415502.66 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.236390E+09 | 24467834.45 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.186685E+09 | 20320422.36 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.156973E+09 | 10083053.37 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.166943E+09 | 11858752.21 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.159781E+09 | 12453727.07 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.150538E+09 | 20947560.47 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.146509E+09 | 18077762.09 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.155363E+09 | 17257728.98 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.189732E+09 | 21977231.56 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.240573E+09 | 24320785.13 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.303563E+09 | 37204686.92 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.239701E+10 | 0.252385E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.146509E+09 | 10083053.37 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.303956E+09 | 37204686.92 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.303956E+09 | 33415502.66 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.236390E+09 | 24467834.45 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.186685E+09 | 20320422.36 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.156973E+09 | 10083053.37 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.166943E+09 | 11858752.21 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.159781E+09 | 12453727.07 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.150538E+09 | 20947560.47 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.146509E+09 | 18077762.09 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.155363E+09 | 17257728.98 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.189732E+09 | 21977231.56 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.240573E+09 | 24320785.13 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.303563E+09 | 37204686.92 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.239701E+10 | 0.252385E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.146509E+09 | 10083053.37 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.303956E+09 | 37204686.92 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207526E+09 | 86563040.12 | 0.120963E+09 | 0.362547E+09 | 39824140.69 |
February | 0.159158E+09 | 51867808.75 | 0.107290E+09 | 0.281784E+09 | 29208436.61 |
March | 0.120208E+09 | 16082160.27 | 0.104126E+09 | 0.222190E+09 | 24337676.74 |
April | 86780195.16 | 37365.05 | 86742830.12 | 0.186620E+09 | 12109440.21 |
May | 89735743.77 | 0.00 | 89735743.77 | 0.198500E+09 | 14168504.94 |
June | 86528420.35 | 0.00 | 86528420.35 | 0.189954E+09 | 14876927.30 |
July | 92108562.21 | 0.00 | 92108562.21 | 0.179222E+09 | 24964125.88 |
August | 89666121.68 | 136323.14 | 89529798.54 | 0.174321E+09 | 21585808.20 |
September | 96043878.38 | 3114430.63 | 92929447.75 | 0.184984E+09 | 20579337.71 |
October | 0.129848E+09 | 20681758.00 | 0.109166E+09 | 0.226141E+09 | 26181700.55 |
November | 0.163406E+09 | 49835686.49 | 0.113570E+09 | 0.286890E+09 | 28987506.28 |
December | 0.207430E+09 | 88240194.36 | 0.119190E+09 | 0.362129E+09 | 44322558.61 |
Annual Sum or Average | 0.152844E+10 | 0.316559E+09 | 0.121188E+10 | 0.285528E+10 | 0.301146E+09 |
Minimum of Months | 86528420.35 | 0.00 | 86528420.35 | 0.174321E+09 | 12109440.21 |
Maximum of Months | 0.207526E+09 | 88240194.36 | 0.120963E+09 | 0.362547E+09 | 44322558.61 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.303783E+09 | 33955149.06 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.236222E+09 | 24977927.05 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.186538E+09 | 20919190.74 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.156689E+09 | 10678842.74 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.166500E+09 | 12420999.61 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.159490E+09 | 13089857.79 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.150300E+09 | 21612519.66 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.146352E+09 | 18623288.98 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.155175E+09 | 17828202.60 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.189573E+09 | 22555150.77 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.240428E+09 | 24765488.93 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.303428E+09 | 37631083.21 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.239448E+10 | 0.259058E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.146352E+09 | 10678842.74 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.303783E+09 | 37631083.21 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.303783E+09 | 33955149.06 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.236222E+09 | 24977927.05 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.186538E+09 | 20919190.74 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.156689E+09 | 10678842.74 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.166500E+09 | 12420999.61 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.159490E+09 | 13089857.79 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.150300E+09 | 21612519.66 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.146352E+09 | 18623288.98 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.155175E+09 | 17828202.60 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.189573E+09 | 22555150.77 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.240428E+09 | 24765488.93 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.303428E+09 | 37631083.21 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.239448E+10 | 0.259058E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.146352E+09 | 10678842.74 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.303783E+09 | 37631083.21 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207526E+09 | 86563040.12 | 0.120963E+09 | 0.362339E+09 | 40464966.13 |
February | 0.159158E+09 | 51867808.75 | 0.107290E+09 | 0.281581E+09 | 29814645.42 |
March | 0.120208E+09 | 16082160.27 | 0.104126E+09 | 0.222012E+09 | 25048022.85 |
April | 86780195.16 | 37365.05 | 86742830.12 | 0.186280E+09 | 12818369.88 |
May | 89735743.77 | 0.00 | 89735743.77 | 0.197970E+09 | 14837612.55 |
June | 86528420.35 | 0.00 | 86528420.35 | 0.189606E+09 | 15633887.81 |
July | 92108562.21 | 0.00 | 92108562.21 | 0.178937E+09 | 25754190.07 |
August | 89666121.68 | 136323.14 | 89529798.54 | 0.174131E+09 | 22232962.59 |
September | 96043878.38 | 3114430.63 | 92929447.75 | 0.184759E+09 | 21256028.67 |
October | 0.129848E+09 | 20681758.00 | 0.109166E+09 | 0.225950E+09 | 26867492.45 |
November | 0.163406E+09 | 49835686.49 | 0.113570E+09 | 0.286715E+09 | 29516401.08 |
December | 0.207430E+09 | 88240194.36 | 0.119190E+09 | 0.361966E+09 | 44828679.49 |
Annual Sum or Average | 0.152844E+10 | 0.316559E+09 | 0.121188E+10 | 0.285225E+10 | 0.309073E+09 |
Minimum of Months | 86528420.35 | 0.00 | 86528420.35 | 0.174131E+09 | 12818369.88 |
Maximum of Months | 0.207526E+09 | 88240194.36 | 0.120963E+09 | 0.362339E+09 | 44828679.49 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.303993E+09 | 33358107.55 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.236406E+09 | 24424493.42 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.186723E+09 | 20253539.96 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.156925E+09 | 10143757.12 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.166757E+09 | 11950890.46 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.159733E+09 | 12586817.87 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.150475E+09 | 21032467.84 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.146552E+09 | 17978517.67 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.155372E+09 | 17244065.76 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.189765E+09 | 21926903.44 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.240642E+09 | 24188653.21 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.303663E+09 | 37031071.68 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.239701E+10 | 0.252119E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.146552E+09 | 10143757.12 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.303993E+09 | 37031071.68 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.303993E+09 | 33358107.55 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.236406E+09 | 24424493.42 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.186723E+09 | 20253539.96 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.156925E+09 | 10143757.12 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.166757E+09 | 11950890.46 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.159733E+09 | 12586817.87 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.150475E+09 | 21032467.84 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.146552E+09 | 17978517.67 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.155372E+09 | 17244065.76 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.189765E+09 | 21926903.44 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.240642E+09 | 24188653.21 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.303663E+09 | 37031071.68 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.239701E+10 | 0.252119E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.146552E+09 | 10143757.12 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.303993E+09 | 37031071.68 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207526E+09 | 86563040.12 | 0.120963E+09 | 0.362592E+09 | 39762915.42 |
February | 0.159158E+09 | 51867808.75 | 0.107290E+09 | 0.281803E+09 | 29162382.49 |
March | 0.120208E+09 | 16082160.27 | 0.104126E+09 | 0.222235E+09 | 24265278.36 |
April | 86780195.16 | 37365.05 | 86742830.12 | 0.186562E+09 | 12187101.91 |
May | 89735743.77 | 0.00 | 89735743.77 | 0.198276E+09 | 14283044.37 |
June | 86528420.35 | 0.00 | 86528420.35 | 0.189896E+09 | 15041262.49 |
July | 92108562.21 | 0.00 | 92108562.21 | 0.179147E+09 | 25071287.33 |
August | 89666121.68 | 136323.14 | 89529798.54 | 0.174372E+09 | 21475727.93 |
September | 96043878.38 | 3114430.63 | 92929447.75 | 0.184996E+09 | 20569570.75 |
October | 0.129848E+09 | 20681758.00 | 0.109166E+09 | 0.226181E+09 | 26128852.19 |
November | 0.163406E+09 | 49835686.49 | 0.113570E+09 | 0.286973E+09 | 28837862.98 |
December | 0.207430E+09 | 88240194.36 | 0.119190E+09 | 0.362248E+09 | 44121545.58 |
Annual Sum or Average | 0.152844E+10 | 0.316559E+09 | 0.121188E+10 | 0.285528E+10 | 0.300907E+09 |
Minimum of Months | 86528420.35 | 0.00 | 86528420.35 | 0.174372E+09 | 12187101.91 |
Maximum of Months | 0.207526E+09 | 88240194.36 | 0.120963E+09 | 0.362592E+09 | 44121545.58 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.303168E+09 | 31206299.17 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.235427E+09 | 22417996.65 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.185685E+09 | 18025283.22 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.156482E+09 | 8736621.58 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.166117E+09 | 10428937.45 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.159247E+09 | 11098749.78 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.149604E+09 | 19123344.42 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.145708E+09 | 15769238.20 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.154775E+09 | 15437077.88 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.189054E+09 | 19861940.59 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.239857E+09 | 22210645.42 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.302887E+09 | 34937160.65 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.238801E+10 | 0.229253E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.145708E+09 | 8736621.58 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.303168E+09 | 34937160.65 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.303168E+09 | 31206299.17 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.235427E+09 | 22417996.65 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.185685E+09 | 18025283.22 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.156482E+09 | 8736621.58 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.166117E+09 | 10428937.45 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.159247E+09 | 11098749.78 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.149604E+09 | 19123344.42 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.145708E+09 | 15769238.20 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.154775E+09 | 15437077.88 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.189054E+09 | 19861940.59 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.239857E+09 | 22210645.42 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.302887E+09 | 34937160.65 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.238801E+10 | 0.229253E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.145708E+09 | 8736621.58 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.303168E+09 | 34937160.65 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.303168E+09 | 31206299.17 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.235427E+09 | 22417996.65 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.185685E+09 | 18025283.22 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.156482E+09 | 8736621.58 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.166117E+09 | 10428937.45 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.159247E+09 | 11098749.78 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.149604E+09 | 19123344.42 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.145708E+09 | 15769238.20 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.154775E+09 | 15437077.88 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.189054E+09 | 19861940.59 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.239857E+09 | 22210645.42 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.302887E+09 | 34937160.65 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.238801E+10 | 0.229253E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.145708E+09 | 8736621.58 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.303168E+09 | 34937160.65 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.303168E+09 | 31206299.17 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.235427E+09 | 22417996.65 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.185685E+09 | 18025283.22 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.156482E+09 | 8736621.58 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.166117E+09 | 10428937.45 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.159247E+09 | 11098749.78 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.149604E+09 | 19123344.42 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.145708E+09 | 15769238.20 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.154775E+09 | 15437077.88 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.189054E+09 | 19861940.59 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.239857E+09 | 22210645.42 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.302887E+09 | 34937160.65 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.238801E+10 | 0.229253E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.145708E+09 | 8736621.58 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.303168E+09 | 34937160.65 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207526E+09 | 86563040.12 | 0.120963E+09 | 0.361640E+09 | 37217483.34 |
February | 0.159158E+09 | 51867808.75 | 0.107290E+09 | 0.280678E+09 | 26787330.49 |
March | 0.120208E+09 | 16082160.27 | 0.104126E+09 | 0.221042E+09 | 21612953.96 |
April | 86780195.16 | 37365.05 | 86742830.12 | 0.186062E+09 | 10492087.05 |
May | 89735743.77 | 0.00 | 89735743.77 | 0.197551E+09 | 12468772.31 |
June | 86528420.35 | 0.00 | 86528420.35 | 0.189348E+09 | 13262580.11 |
July | 92108562.21 | 0.00 | 92108562.21 | 0.178147E+09 | 22807882.94 |
August | 89666121.68 | 136323.14 | 89529798.54 | 0.173413E+09 | 18855122.70 |
September | 96043878.38 | 3114430.63 | 92929447.75 | 0.184316E+09 | 18421647.04 |
October | 0.129848E+09 | 20681758.00 | 0.109166E+09 | 0.225367E+09 | 23682810.32 |
November | 0.163406E+09 | 49835686.49 | 0.113570E+09 | 0.286071E+09 | 26494685.63 |
December | 0.207430E+09 | 88240194.36 | 0.119190E+09 | 0.361358E+09 | 41647879.00 |
Annual Sum or Average | 0.152844E+10 | 0.316559E+09 | 0.121188E+10 | 0.284499E+10 | 0.273751E+09 |
Minimum of Months | 86528420.35 | 0.00 | 86528420.35 | 0.173413E+09 | 10492087.05 |
Maximum of Months | 0.207526E+09 | 88240194.36 | 0.120963E+09 | 0.361640E+09 | 41647879.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207526E+09 | 86563040.12 | 0.120963E+09 | 0.361640E+09 | 37217483.34 |
February | 0.159158E+09 | 51867808.75 | 0.107290E+09 | 0.280678E+09 | 26787330.49 |
March | 0.120208E+09 | 16082160.27 | 0.104126E+09 | 0.221042E+09 | 21612953.96 |
April | 86780195.16 | 37365.05 | 86742830.12 | 0.186062E+09 | 10492087.05 |
May | 89735743.77 | 0.00 | 89735743.77 | 0.197551E+09 | 12468772.31 |
June | 86528420.35 | 0.00 | 86528420.35 | 0.189348E+09 | 13262580.11 |
July | 92108562.21 | 0.00 | 92108562.21 | 0.178147E+09 | 22807882.94 |
August | 89666121.68 | 136323.14 | 89529798.54 | 0.173413E+09 | 18855122.70 |
September | 96043878.38 | 3114430.63 | 92929447.75 | 0.184316E+09 | 18421647.04 |
October | 0.129848E+09 | 20681758.00 | 0.109166E+09 | 0.225367E+09 | 23682810.32 |
November | 0.163406E+09 | 49835686.49 | 0.113570E+09 | 0.286071E+09 | 26494685.63 |
December | 0.207430E+09 | 88240194.36 | 0.119190E+09 | 0.361358E+09 | 41647879.00 |
Annual Sum or Average | 0.152844E+10 | 0.316559E+09 | 0.121188E+10 | 0.284499E+10 | 0.273751E+09 |
Minimum of Months | 86528420.35 | 0.00 | 86528420.35 | 0.173413E+09 | 10492087.05 |
Maximum of Months | 0.207526E+09 | 88240194.36 | 0.120963E+09 | 0.361640E+09 | 41647879.00 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.303621E+09 | 30156112.43 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.236031E+09 | 21393017.54 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.186645E+09 | 16803438.54 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.157754E+09 | 7829898.36 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.167459E+09 | 9611489.92 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.160548E+09 | 10204868.63 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.150348E+09 | 18097637.73 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.146543E+09 | 14672001.67 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.155547E+09 | 14464904.24 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.189649E+09 | 18811966.38 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.240365E+09 | 21237203.15 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.303275E+09 | 33924583.76 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.239779E+10 | 0.217207E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.146543E+09 | 7829898.36 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.303621E+09 | 33924583.76 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.303621E+09 | 30156112.43 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.236031E+09 | 21393017.54 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.186645E+09 | 16803438.54 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.157754E+09 | 7829898.36 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.167459E+09 | 9611489.92 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.160548E+09 | 10204868.63 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.150348E+09 | 18097637.73 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.146543E+09 | 14672001.67 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.155547E+09 | 14464904.24 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.189649E+09 | 18811966.38 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.240365E+09 | 21237203.15 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.303275E+09 | 33924583.76 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.239779E+10 | 0.217207E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.146543E+09 | 7829898.36 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.303621E+09 | 33924583.76 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207526E+09 | 86563040.12 | 0.120963E+09 | 0.362212E+09 | 35966659.09 |
February | 0.159158E+09 | 51867808.75 | 0.107290E+09 | 0.281416E+09 | 25570084.80 |
March | 0.120208E+09 | 16082160.27 | 0.104126E+09 | 0.222182E+09 | 20163072.08 |
April | 86780195.16 | 37365.05 | 86742830.12 | 0.187573E+09 | 9413979.33 |
May | 89735743.77 | 0.00 | 89735743.77 | 0.199152E+09 | 11496009.32 |
June | 86528420.35 | 0.00 | 86528420.35 | 0.190895E+09 | 12197721.88 |
July | 92108562.21 | 0.00 | 92108562.21 | 0.179049E+09 | 21588680.98 |
August | 89666121.68 | 136323.14 | 89529798.54 | 0.174420E+09 | 17552169.86 |
September | 96043878.38 | 3114430.63 | 92929447.75 | 0.185249E+09 | 17265953.35 |
October | 0.129848E+09 | 20681758.00 | 0.109166E+09 | 0.226103E+09 | 22431672.67 |
November | 0.163406E+09 | 49835686.49 | 0.113570E+09 | 0.286707E+09 | 25333512.58 |
December | 0.207430E+09 | 88240194.36 | 0.119190E+09 | 0.361858E+09 | 40440759.60 |
Annual Sum or Average | 0.152844E+10 | 0.316559E+09 | 0.121188E+10 | 0.285682E+10 | 0.259420E+09 |
Minimum of Months | 86528420.35 | 0.00 | 86528420.35 | 0.174420E+09 | 9413979.33 |
Maximum of Months | 0.207526E+09 | 88240194.36 | 0.120963E+09 | 0.362212E+09 | 40440759.60 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.303834E+09 | 29898003.46 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.236212E+09 | 21170324.66 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.186840E+09 | 16557471.23 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.157988E+09 | 7644286.56 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.167716E+09 | 9439504.26 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.160781E+09 | 10016219.86 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.150541E+09 | 17866930.29 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.146740E+09 | 14436347.59 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.155737E+09 | 14245164.58 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.189846E+09 | 18549267.19 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.240564E+09 | 20996807.96 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.303482E+09 | 33664650.01 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.240028E+10 | 0.214485E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.146740E+09 | 7644286.56 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.303834E+09 | 33664650.01 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.303834E+09 | 29898003.46 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.236212E+09 | 21170324.66 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.186840E+09 | 16557471.23 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.157988E+09 | 7644286.56 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.167716E+09 | 9439504.26 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.160781E+09 | 10016219.86 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.150541E+09 | 17866930.29 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.146740E+09 | 14436347.59 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.155737E+09 | 14245164.58 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.189846E+09 | 18549267.19 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.240564E+09 | 20996807.96 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.303482E+09 | 33664650.01 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.240028E+10 | 0.214485E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.146740E+09 | 7644286.56 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.303834E+09 | 33664650.01 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207526E+09 | 86563040.12 | 0.120963E+09 | 0.362467E+09 | 35659190.32 |
February | 0.159158E+09 | 51867808.75 | 0.107290E+09 | 0.281634E+09 | 25304362.50 |
March | 0.120208E+09 | 16082160.27 | 0.104126E+09 | 0.222417E+09 | 19870082.59 |
April | 86780195.16 | 37365.05 | 86742830.12 | 0.187852E+09 | 9191635.09 |
May | 89735743.77 | 0.00 | 89735743.77 | 0.199461E+09 | 11291198.21 |
June | 86528420.35 | 0.00 | 86528420.35 | 0.191176E+09 | 11973018.02 |
July | 92108562.21 | 0.00 | 92108562.21 | 0.179282E+09 | 21313715.69 |
August | 89666121.68 | 136323.14 | 89529798.54 | 0.174657E+09 | 17271541.16 |
September | 96043878.38 | 3114430.63 | 92929447.75 | 0.185478E+09 | 17004086.57 |
October | 0.129848E+09 | 20681758.00 | 0.109166E+09 | 0.226340E+09 | 22117863.45 |
November | 0.163406E+09 | 49835686.49 | 0.113570E+09 | 0.286947E+09 | 25047780.08 |
December | 0.207430E+09 | 88240194.36 | 0.119190E+09 | 0.362107E+09 | 40131811.20 |
Annual Sum or Average | 0.152844E+10 | 0.316559E+09 | 0.121188E+10 | 0.285982E+10 | 0.256176E+09 |
Minimum of Months | 86528420.35 | 0.00 | 86528420.35 | 0.174657E+09 | 9191635.09 |
Maximum of Months | 0.207526E+09 | 88240194.36 | 0.120963E+09 | 0.362467E+09 | 40131811.20 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.303889E+09 | 29736491.09 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.236201E+09 | 21083204.36 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.186792E+09 | 16485586.55 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.157861E+09 | 7634814.72 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.167563E+09 | 9434760.01 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.160623E+09 | 10038478.07 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.150438E+09 | 17877677.57 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.146656E+09 | 14405677.35 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.155638E+09 | 14233800.88 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.189842E+09 | 18423738.66 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.240591E+09 | 20869586.22 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.303554E+09 | 33498835.85 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.239965E+10 | 0.213723E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.146656E+09 | 7634814.72 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.303889E+09 | 33498835.85 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.303889E+09 | 29736491.09 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.236201E+09 | 21083204.36 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.186792E+09 | 16485586.55 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.157861E+09 | 7634814.72 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.167563E+09 | 9434760.01 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.160623E+09 | 10038478.07 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.150438E+09 | 17877677.57 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.146656E+09 | 14405677.35 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.155638E+09 | 14233800.88 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.189842E+09 | 18423738.66 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.240591E+09 | 20869586.22 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.303554E+09 | 33498835.85 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.239965E+10 | 0.213723E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.146656E+09 | 7634814.72 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.303889E+09 | 33498835.85 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207526E+09 | 86563040.12 | 0.120963E+09 | 0.362531E+09 | 35473734.02 |
February | 0.159158E+09 | 51867808.75 | 0.107290E+09 | 0.281617E+09 | 25207327.94 |
March | 0.120208E+09 | 16082160.27 | 0.104126E+09 | 0.222357E+09 | 19791417.60 |
April | 86780195.16 | 37365.05 | 86742830.12 | 0.187697E+09 | 9186012.71 |
May | 89735743.77 | 0.00 | 89735743.77 | 0.199274E+09 | 11290734.79 |
June | 86528420.35 | 0.00 | 86528420.35 | 0.190983E+09 | 12004321.03 |
July | 92108562.21 | 0.00 | 92108562.21 | 0.179156E+09 | 21331525.73 |
August | 89666121.68 | 136323.14 | 89529798.54 | 0.174553E+09 | 17242269.00 |
September | 96043878.38 | 3114430.63 | 92929447.75 | 0.185356E+09 | 16997484.70 |
October | 0.129848E+09 | 20681758.00 | 0.109166E+09 | 0.226333E+09 | 21975795.49 |
November | 0.163406E+09 | 49835686.49 | 0.113570E+09 | 0.286976E+09 | 24903060.85 |
December | 0.207430E+09 | 88240194.36 | 0.119190E+09 | 0.362191E+09 | 39940635.07 |
Annual Sum or Average | 0.152844E+10 | 0.316559E+09 | 0.121188E+10 | 0.285902E+10 | 0.255344E+09 |
Minimum of Months | 86528420.35 | 0.00 | 86528420.35 | 0.174553E+09 | 9186012.71 |
Maximum of Months | 0.207526E+09 | 88240194.36 | 0.120963E+09 | 0.362531E+09 | 39940635.07 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.302636E+09 | 30149324.74 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.234677E+09 | 21768756.05 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.184930E+09 | 17323382.94 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.155388E+09 | 8531248.38 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.164910E+09 | 10253944.58 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.158009E+09 | 11088734.42 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.148384E+09 | 19182639.42 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.144695E+09 | 15509537.00 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.153609E+09 | 15389953.49 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.188455E+09 | 19110831.59 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.239256E+09 | 21429983.71 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.302410E+09 | 33889397.75 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.237736E+10 | 0.223628E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.144695E+09 | 8531248.38 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.302636E+09 | 33889397.75 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173319E+09 | 72294407.13 | 0.101024E+09 | 0.302636E+09 | 30149324.74 |
February | 0.132923E+09 | 43318169.94 | 89604780.35 | 0.234677E+09 | 21768756.05 |
March | 0.100394E+09 | 13431254.73 | 86962606.10 | 0.184930E+09 | 17323382.94 |
April | 72475767.39 | 31205.97 | 72444561.42 | 0.155388E+09 | 8531248.38 |
May | 74944137.65 | 0.00 | 74944137.65 | 0.164910E+09 | 10253944.58 |
June | 72265493.92 | 0.00 | 72265493.92 | 0.158009E+09 | 11088734.42 |
July | 76925832.18 | 0.00 | 76925832.18 | 0.148384E+09 | 19182639.42 |
August | 74885991.74 | 113852.29 | 74772139.44 | 0.144695E+09 | 15509537.00 |
September | 80212469.86 | 2601062.95 | 77611406.91 | 0.153609E+09 | 15389953.49 |
October | 0.108444E+09 | 17272677.01 | 91171580.30 | 0.188455E+09 | 19110831.59 |
November | 0.136471E+09 | 41621012.89 | 94849564.15 | 0.239256E+09 | 21429983.71 |
December | 0.173239E+09 | 73695107.37 | 99543532.43 | 0.302410E+09 | 33889397.75 |
Annual Sum or Average | 0.127650E+10 | 0.264379E+09 | 0.101212E+10 | 0.237736E+10 | 0.223628E+09 |
Minimum of Months | 72265493.92 | 0.00 | 72265493.92 | 0.144695E+09 | 8531248.38 |
Maximum of Months | 0.173319E+09 | 73695107.37 | 0.101024E+09 | 0.302636E+09 | 33889397.75 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207526E+09 | 86563040.12 | 0.120963E+09 | 0.361012E+09 | 35973215.37 |
February | 0.159158E+09 | 51867808.75 | 0.107290E+09 | 0.279776E+09 | 26028598.40 |
March | 0.120208E+09 | 16082160.27 | 0.104126E+09 | 0.220113E+09 | 20795815.27 |
April | 86780195.16 | 37365.05 | 86742830.12 | 0.184724E+09 | 10260847.90 |
May | 89735743.77 | 0.00 | 89735743.77 | 0.196090E+09 | 12274449.98 |
June | 86528420.35 | 0.00 | 86528420.35 | 0.187840E+09 | 13261714.41 |
July | 92108562.21 | 0.00 | 92108562.21 | 0.176679E+09 | 22887544.12 |
August | 89666121.68 | 136323.14 | 89529798.54 | 0.172188E+09 | 18559488.10 |
September | 96043878.38 | 3114430.63 | 92929447.75 | 0.182911E+09 | 18376686.40 |
October | 0.129848E+09 | 20681758.00 | 0.109166E+09 | 0.224656E+09 | 22799179.63 |
November | 0.163406E+09 | 49835686.49 | 0.113570E+09 | 0.285357E+09 | 25575384.99 |
December | 0.207430E+09 | 88240194.36 | 0.119190E+09 | 0.360802E+09 | 40413656.20 |
Annual Sum or Average | 0.152844E+10 | 0.316559E+09 | 0.121188E+10 | 0.283215E+10 | 0.267207E+09 |
Minimum of Months | 86528420.35 | 0.00 | 86528420.35 | 0.172188E+09 | 10260847.90 |
Maximum of Months | 0.207526E+09 | 88240194.36 | 0.120963E+09 | 0.361012E+09 | 40413656.20 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 727.04 | 63.81 | 414.65 | 172.96 | 241.69 | 0.00 | 0.00 |
February | 625.79 | 49.30 | 352.08 | 114.74 | 237.34 | 0.00 | 0.00 |
March | 446.44 | 34.88 | 240.19 | 32.13 | 208.05 | 0.00 | 0.00 |
April | 396.20 | 17.24 | 179.17 | 0.08 | 179.10 | 0.00 | 0.00 |
May | 408.19 | 20.35 | 179.30 | 0.00 | 179.30 | 0.00 | 0.00 |
June | 401.79 | 22.13 | 178.65 | 0.00 | 178.65 | 0.00 | 0.00 |
July | 365.09 | 37.83 | 184.04 | 0.00 | 184.04 | 0.00 | 0.00 |
August | 351.35 | 30.72 | 179.16 | 0.27 | 178.89 | 0.00 | 0.00 |
September | 387.71 | 30.85 | 198.30 | 6.43 | 191.87 | 0.00 | 0.00 |
October | 455.57 | 38.27 | 259.45 | 41.32 | 218.12 | 0.00 | 0.00 |
November | 594.96 | 45.95 | 337.38 | 102.89 | 234.49 | 0.00 | 0.00 |
December | 725.38 | 72.99 | 414.46 | 176.31 | 238.15 | 0.00 | 0.00 |
Annual Sum or Average | 489.84 | 38.71 | 259.38 | 53.72 | 205.66 | 0.00 | 0.00 |
Minimum of Months | 351.35 | 17.24 | 178.65 | 0.00 | 178.65 | 0.00 | 0.00 |
Maximum of Months | 727.04 | 72.99 | 414.65 | 176.31 | 241.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 364.16 | 31.61 | 207.33 | 86.48 | 120.85 | 0.00 | 0.00 |
February | 314.05 | 24.20 | 176.04 | 57.37 | 118.67 | 0.00 | 0.00 |
March | 224.95 | 16.90 | 120.09 | 16.07 | 104.03 | 0.00 | 0.00 |
April | 200.19 | 8.17 | 89.59 | 0.04 | 89.55 | 0.00 | 0.00 |
May | 206.01 | 9.82 | 89.65 | 0.00 | 89.65 | 0.00 | 0.00 |
June | 203.00 | 10.59 | 89.33 | 0.00 | 89.33 | 0.00 | 0.00 |
July | 183.87 | 18.39 | 92.02 | 0.00 | 92.02 | 0.00 | 0.00 |
August | 177.17 | 14.85 | 89.58 | 0.14 | 89.44 | 0.00 | 0.00 |
September | 195.28 | 14.93 | 99.15 | 3.22 | 95.93 | 0.00 | 0.00 |
October | 228.69 | 18.83 | 129.72 | 20.66 | 109.06 | 0.00 | 0.00 |
November | 298.31 | 22.68 | 168.69 | 51.45 | 117.24 | 0.00 | 0.00 |
December | 363.23 | 36.23 | 207.23 | 88.16 | 119.08 | 0.00 | 0.00 |
Annual Sum or Average | 246.27 | 18.94 | 129.69 | 26.86 | 102.83 | 0.00 | 0.00 |
Minimum of Months | 177.17 | 8.17 | 89.33 | 0.00 | 89.33 | 0.00 | 0.00 |
Maximum of Months | 364.16 | 36.23 | 207.33 | 88.16 | 120.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 362.33 | 39.82 | 206.90 | 86.30 | 120.60 | 0.00 | 0.00 |
February | 311.91 | 32.30 | 175.68 | 57.25 | 118.43 | 0.00 | 0.00 |
March | 222.36 | 24.26 | 119.85 | 16.03 | 103.81 | 0.00 | 0.00 |
April | 193.12 | 12.45 | 89.40 | 0.04 | 89.36 | 0.00 | 0.00 |
May | 198.77 | 14.14 | 89.47 | 0.00 | 89.47 | 0.00 | 0.00 |
June | 196.57 | 15.35 | 89.14 | 0.00 | 89.14 | 0.00 | 0.00 |
July | 179.32 | 24.96 | 91.83 | 0.00 | 91.83 | 0.00 | 0.00 |
August | 174.48 | 21.56 | 89.40 | 0.14 | 89.26 | 0.00 | 0.00 |
September | 191.25 | 21.26 | 98.95 | 3.21 | 95.74 | 0.00 | 0.00 |
October | 226.11 | 26.19 | 129.46 | 20.62 | 108.84 | 0.00 | 0.00 |
November | 296.31 | 29.95 | 168.34 | 51.34 | 117.00 | 0.00 | 0.00 |
December | 361.88 | 44.33 | 206.81 | 87.97 | 118.83 | 0.00 | 0.00 |
Annual Sum or Average | 242.56 | 25.56 | 129.42 | 26.80 | 102.62 | 0.00 | 0.00 |
Minimum of Months | 174.48 | 12.45 | 89.14 | 0.00 | 89.14 | 0.00 | 0.00 |
Maximum of Months | 362.33 | 44.33 | 206.90 | 87.97 | 120.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 362.12 | 40.46 | 206.90 | 86.30 | 120.60 | 0.00 | 0.00 |
February | 311.68 | 32.97 | 175.68 | 57.25 | 118.43 | 0.00 | 0.00 |
March | 222.18 | 24.97 | 119.85 | 16.03 | 103.81 | 0.00 | 0.00 |
April | 192.77 | 13.19 | 89.40 | 0.04 | 89.36 | 0.00 | 0.00 |
May | 198.24 | 14.81 | 89.47 | 0.00 | 89.47 | 0.00 | 0.00 |
June | 196.21 | 16.13 | 89.14 | 0.00 | 89.14 | 0.00 | 0.00 |
July | 179.04 | 25.75 | 91.83 | 0.00 | 91.83 | 0.00 | 0.00 |
August | 174.30 | 22.21 | 89.40 | 0.14 | 89.26 | 0.00 | 0.00 |
September | 191.01 | 21.96 | 98.95 | 3.21 | 95.74 | 0.00 | 0.00 |
October | 225.92 | 26.87 | 129.46 | 20.62 | 108.84 | 0.00 | 0.00 |
November | 296.13 | 30.50 | 168.34 | 51.34 | 117.00 | 0.00 | 0.00 |
December | 361.72 | 44.84 | 206.81 | 87.97 | 118.83 | 0.00 | 0.00 |
Annual Sum or Average | 242.30 | 26.23 | 129.42 | 26.80 | 102.62 | 0.00 | 0.00 |
Minimum of Months | 174.30 | 13.19 | 89.14 | 0.00 | 89.14 | 0.00 | 0.00 |
Maximum of Months | 362.12 | 44.84 | 206.90 | 87.97 | 120.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 362.37 | 39.75 | 206.90 | 86.30 | 120.60 | 0.00 | 0.00 |
February | 311.93 | 32.25 | 175.68 | 57.25 | 118.43 | 0.00 | 0.00 |
March | 222.40 | 24.18 | 119.85 | 16.03 | 103.81 | 0.00 | 0.00 |
April | 193.06 | 12.53 | 89.40 | 0.04 | 89.36 | 0.00 | 0.00 |
May | 198.55 | 14.26 | 89.47 | 0.00 | 89.47 | 0.00 | 0.00 |
June | 196.51 | 15.51 | 89.14 | 0.00 | 89.14 | 0.00 | 0.00 |
July | 179.25 | 25.07 | 91.83 | 0.00 | 91.83 | 0.00 | 0.00 |
August | 174.54 | 21.44 | 89.40 | 0.14 | 89.26 | 0.00 | 0.00 |
September | 191.26 | 21.24 | 98.95 | 3.21 | 95.74 | 0.00 | 0.00 |
October | 226.15 | 26.13 | 129.46 | 20.62 | 108.84 | 0.00 | 0.00 |
November | 296.40 | 29.79 | 168.34 | 51.34 | 117.00 | 0.00 | 0.00 |
December | 362.00 | 44.12 | 206.81 | 87.97 | 118.83 | 0.00 | 0.00 |
Annual Sum or Average | 242.56 | 25.53 | 129.42 | 26.80 | 102.62 | 0.00 | 0.00 |
Minimum of Months | 174.54 | 12.53 | 89.14 | 0.00 | 89.14 | 0.00 | 0.00 |
Maximum of Months | 362.37 | 44.12 | 206.90 | 87.97 | 120.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 722.80 | 74.39 | 413.80 | 172.60 | 241.20 | 0.00 | 0.00 |
February | 621.31 | 59.21 | 351.36 | 114.50 | 236.85 | 0.00 | 0.00 |
March | 442.36 | 43.06 | 239.69 | 32.07 | 207.63 | 0.00 | 0.00 |
April | 385.05 | 21.58 | 178.81 | 0.08 | 178.73 | 0.00 | 0.00 |
May | 395.60 | 24.89 | 178.93 | 0.00 | 178.93 | 0.00 | 0.00 |
June | 391.85 | 27.36 | 178.29 | 0.00 | 178.29 | 0.00 | 0.00 |
July | 356.45 | 45.59 | 183.66 | 0.00 | 183.66 | 0.00 | 0.00 |
August | 347.09 | 37.63 | 178.79 | 0.27 | 178.52 | 0.00 | 0.00 |
September | 381.07 | 38.04 | 197.89 | 6.42 | 191.48 | 0.00 | 0.00 |
October | 450.62 | 47.35 | 258.91 | 41.24 | 217.67 | 0.00 | 0.00 |
November | 590.88 | 54.72 | 336.69 | 102.68 | 234.00 | 0.00 | 0.00 |
December | 722.17 | 83.27 | 413.61 | 175.95 | 237.66 | 0.00 | 0.00 |
Annual Sum or Average | 483.32 | 46.44 | 258.84 | 53.61 | 205.23 | 0.00 | 0.00 |
Minimum of Months | 347.09 | 21.58 | 178.29 | 0.00 | 178.29 | 0.00 | 0.00 |
Maximum of Months | 722.80 | 83.27 | 413.80 | 175.95 | 241.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 361.95 | 35.95 | 206.90 | 86.30 | 120.60 | 0.00 | 0.00 |
February | 311.46 | 28.26 | 175.68 | 57.25 | 118.43 | 0.00 | 0.00 |
March | 222.32 | 20.08 | 119.85 | 16.03 | 103.81 | 0.00 | 0.00 |
April | 194.09 | 9.67 | 89.40 | 0.04 | 89.36 | 0.00 | 0.00 |
May | 199.40 | 11.47 | 89.47 | 0.00 | 89.47 | 0.00 | 0.00 |
June | 197.53 | 12.58 | 89.14 | 0.00 | 89.14 | 0.00 | 0.00 |
July | 179.12 | 21.57 | 91.83 | 0.00 | 91.83 | 0.00 | 0.00 |
August | 174.55 | 17.51 | 89.40 | 0.14 | 89.26 | 0.00 | 0.00 |
September | 191.49 | 17.82 | 98.95 | 3.21 | 95.74 | 0.00 | 0.00 |
October | 226.03 | 22.42 | 129.46 | 20.62 | 108.84 | 0.00 | 0.00 |
November | 296.08 | 26.16 | 168.34 | 51.34 | 117.00 | 0.00 | 0.00 |
December | 361.56 | 40.43 | 206.81 | 87.97 | 118.83 | 0.00 | 0.00 |
Annual Sum or Average | 242.66 | 22.00 | 129.42 | 26.80 | 102.62 | 0.00 | 0.00 |
Minimum of Months | 174.55 | 9.67 | 89.14 | 0.00 | 89.14 | 0.00 | 0.00 |
Maximum of Months | 361.95 | 40.43 | 206.90 | 87.97 | 120.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 362.21 | 35.64 | 206.90 | 86.30 | 120.60 | 0.00 | 0.00 |
February | 311.70 | 27.96 | 175.68 | 57.25 | 118.43 | 0.00 | 0.00 |
March | 222.56 | 19.78 | 119.85 | 16.03 | 103.81 | 0.00 | 0.00 |
April | 194.38 | 9.44 | 89.40 | 0.04 | 89.36 | 0.00 | 0.00 |
May | 199.71 | 11.26 | 89.47 | 0.00 | 89.47 | 0.00 | 0.00 |
June | 197.82 | 12.35 | 89.14 | 0.00 | 89.14 | 0.00 | 0.00 |
July | 179.35 | 21.30 | 91.83 | 0.00 | 91.83 | 0.00 | 0.00 |
August | 174.78 | 17.23 | 89.40 | 0.14 | 89.26 | 0.00 | 0.00 |
September | 191.73 | 17.55 | 98.95 | 3.21 | 95.74 | 0.00 | 0.00 |
October | 226.27 | 22.11 | 129.46 | 20.62 | 108.84 | 0.00 | 0.00 |
November | 296.33 | 25.86 | 168.34 | 51.34 | 117.00 | 0.00 | 0.00 |
December | 361.81 | 40.12 | 206.81 | 87.97 | 118.83 | 0.00 | 0.00 |
Annual Sum or Average | 242.91 | 21.73 | 129.42 | 26.80 | 102.62 | 0.00 | 0.00 |
Minimum of Months | 174.78 | 9.44 | 89.14 | 0.00 | 89.14 | 0.00 | 0.00 |
Maximum of Months | 362.21 | 40.12 | 206.90 | 87.97 | 120.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 362.27 | 35.45 | 206.90 | 86.30 | 120.60 | 0.00 | 0.00 |
February | 311.68 | 27.85 | 175.68 | 57.25 | 118.43 | 0.00 | 0.00 |
March | 222.50 | 19.70 | 119.85 | 16.03 | 103.81 | 0.00 | 0.00 |
April | 194.22 | 9.43 | 89.40 | 0.04 | 89.36 | 0.00 | 0.00 |
May | 199.52 | 11.26 | 89.47 | 0.00 | 89.47 | 0.00 | 0.00 |
June | 197.62 | 12.38 | 89.14 | 0.00 | 89.14 | 0.00 | 0.00 |
July | 179.22 | 21.31 | 91.83 | 0.00 | 91.83 | 0.00 | 0.00 |
August | 174.68 | 17.19 | 89.40 | 0.14 | 89.26 | 0.00 | 0.00 |
September | 191.60 | 17.54 | 98.95 | 3.21 | 95.74 | 0.00 | 0.00 |
October | 226.26 | 21.96 | 129.46 | 20.62 | 108.84 | 0.00 | 0.00 |
November | 296.36 | 25.71 | 168.34 | 51.34 | 117.00 | 0.00 | 0.00 |
December | 361.89 | 39.93 | 206.81 | 87.97 | 118.83 | 0.00 | 0.00 |
Annual Sum or Average | 242.84 | 21.65 | 129.42 | 26.80 | 102.62 | 0.00 | 0.00 |
Minimum of Months | 174.68 | 9.43 | 89.14 | 0.00 | 89.14 | 0.00 | 0.00 |
Maximum of Months | 362.27 | 39.93 | 206.90 | 87.97 | 120.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 360.77 | 35.94 | 206.90 | 86.30 | 120.60 | 0.00 | 0.00 |
February | 309.66 | 28.76 | 175.68 | 57.25 | 118.43 | 0.00 | 0.00 |
March | 220.27 | 20.70 | 119.85 | 16.03 | 103.81 | 0.00 | 0.00 |
April | 191.16 | 10.54 | 89.40 | 0.04 | 89.36 | 0.00 | 0.00 |
May | 196.35 | 12.24 | 89.47 | 0.00 | 89.47 | 0.00 | 0.00 |
June | 194.39 | 13.67 | 89.14 | 0.00 | 89.14 | 0.00 | 0.00 |
July | 176.76 | 22.87 | 91.83 | 0.00 | 91.83 | 0.00 | 0.00 |
August | 172.33 | 18.51 | 89.40 | 0.14 | 89.26 | 0.00 | 0.00 |
September | 189.09 | 18.96 | 98.95 | 3.21 | 95.74 | 0.00 | 0.00 |
October | 224.60 | 22.78 | 129.46 | 20.62 | 108.84 | 0.00 | 0.00 |
November | 294.70 | 26.40 | 168.34 | 51.34 | 117.00 | 0.00 | 0.00 |
December | 360.52 | 40.39 | 206.81 | 87.97 | 118.83 | 0.00 | 0.00 |
Annual Sum or Average | 240.58 | 22.66 | 129.42 | 26.80 | 102.62 | 0.00 | 0.00 |
Minimum of Months | 172.33 | 10.54 | 89.14 | 0.00 | 89.14 | 0.00 | 0.00 |
Maximum of Months | 360.77 | 40.39 | 206.90 | 87.97 | 120.60 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.194732E+10 | 0.170919E+09 | 0.111061E+10 | 0.463255E+09 | 0.647352E+09 | 0.00 | 0.00 |
February | 0.151391E+10 | 0.119276E+09 | 0.851756E+09 | 0.277578E+09 | 0.574178E+09 | 0.00 | 0.00 |
March | 0.119574E+10 | 93414499.19 | 0.643313E+09 | 86066066.50 | 0.557247E+09 | 0.00 | 0.00 |
April | 0.102694E+10 | 44690005.93 | 0.464417E+09 | 199964.58 | 0.464217E+09 | 0.00 | 0.00 |
May | 0.109329E+10 | 54517530.72 | 0.480234E+09 | 0.00 | 0.480234E+09 | 0.00 | 0.00 |
June | 0.104144E+10 | 57366508.03 | 0.463070E+09 | 0.00 | 0.463070E+09 | 0.00 | 0.00 |
July | 0.977858E+09 | 0.101318E+09 | 0.492933E+09 | 0.00 | 0.492933E+09 | 0.00 | 0.00 |
August | 0.941055E+09 | 82292207.36 | 0.479862E+09 | 729553.52 | 0.479132E+09 | 0.00 | 0.00 |
September | 0.100493E+10 | 79967843.92 | 0.513993E+09 | 16667337.56 | 0.497326E+09 | 0.00 | 0.00 |
October | 0.122020E+10 | 0.102498E+09 | 0.694899E+09 | 0.110681E+09 | 0.584218E+09 | 0.00 | 0.00 |
November | 0.154213E+10 | 0.119109E+09 | 0.874489E+09 | 0.266703E+09 | 0.607786E+09 | 0.00 | 0.00 |
December | 0.194286E+10 | 0.195496E+09 | 0.111009E+10 | 0.472230E+09 | 0.637864E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.154477E+11 | 0.122086E+10 | 0.817967E+10 | 0.169411E+10 | 0.648556E+10 | 0.00 | 0.00 |
Minimum of Months | 0.941055E+09 | 44690005.93 | 0.463070E+09 | 0.00 | 0.463070E+09 | 0.00 | 0.00 |
Maximum of Months | 0.194732E+10 | 0.195496E+09 | 0.111061E+10 | 0.472230E+09 | 0.647352E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.975378E+09 | 84676953.23 | 0.555304E+09 | 0.231627E+09 | 0.323676E+09 | 0.00 | 0.00 |
February | 0.759757E+09 | 58543312.27 | 0.425878E+09 | 0.138789E+09 | 0.287089E+09 | 0.00 | 0.00 |
March | 0.602517E+09 | 45258264.62 | 0.321657E+09 | 43033033.25 | 0.278624E+09 | 0.00 | 0.00 |
April | 0.518886E+09 | 21169505.29 | 0.232209E+09 | 99982.29 | 0.232109E+09 | 0.00 | 0.00 |
May | 0.551789E+09 | 26311402.97 | 0.240117E+09 | 0.00 | 0.240117E+09 | 0.00 | 0.00 |
June | 0.526175E+09 | 27454947.03 | 0.231535E+09 | 0.00 | 0.231535E+09 | 0.00 | 0.00 |
July | 0.492476E+09 | 49265265.24 | 0.246466E+09 | 0.00 | 0.246466E+09 | 0.00 | 0.00 |
August | 0.474523E+09 | 39767307.47 | 0.239931E+09 | 364776.76 | 0.239566E+09 | 0.00 | 0.00 |
September | 0.506155E+09 | 38701169.93 | 0.256997E+09 | 8333668.78 | 0.248663E+09 | 0.00 | 0.00 |
October | 0.612522E+09 | 50427540.54 | 0.347450E+09 | 55340748.04 | 0.292109E+09 | 0.00 | 0.00 |
November | 0.773227E+09 | 58789905.73 | 0.437245E+09 | 0.133352E+09 | 0.303893E+09 | 0.00 | 0.00 |
December | 0.972882E+09 | 97035538.34 | 0.555047E+09 | 0.236115E+09 | 0.318932E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.776629E+10 | 0.597401E+09 | 0.408983E+10 | 0.847056E+09 | 0.324278E+10 | 0.00 | 0.00 |
Minimum of Months | 0.474523E+09 | 21169505.29 | 0.231535E+09 | 0.00 | 0.231535E+09 | 0.00 | 0.00 |
Maximum of Months | 0.975378E+09 | 97035538.34 | 0.555304E+09 | 0.236115E+09 | 0.323676E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.970458E+09 | 0.106654E+09 | 0.554163E+09 | 0.231152E+09 | 0.323012E+09 | 0.00 | 0.00 |
February | 0.754564E+09 | 78143619.40 | 0.425004E+09 | 0.138504E+09 | 0.286499E+09 | 0.00 | 0.00 |
March | 0.595560E+09 | 64978145.08 | 0.320996E+09 | 42944669.73 | 0.278051E+09 | 0.00 | 0.00 |
April | 0.500566E+09 | 32275336.44 | 0.231732E+09 | 99776.99 | 0.231632E+09 | 0.00 | 0.00 |
May | 0.532386E+09 | 37885817.30 | 0.239624E+09 | 0.00 | 0.239624E+09 | 0.00 | 0.00 |
June | 0.509516E+09 | 39784201.04 | 0.231059E+09 | 0.00 | 0.231059E+09 | 0.00 | 0.00 |
July | 0.480298E+09 | 66859210.43 | 0.245960E+09 | 0.00 | 0.245960E+09 | 0.00 | 0.00 |
August | 0.467339E+09 | 57741321.11 | 0.239438E+09 | 364027.73 | 0.239074E+09 | 0.00 | 0.00 |
September | 0.495710E+09 | 55094662.81 | 0.256469E+09 | 8316556.52 | 0.248152E+09 | 0.00 | 0.00 |
October | 0.605604E+09 | 70135868.17 | 0.346736E+09 | 55227112.01 | 0.291509E+09 | 0.00 | 0.00 |
November | 0.768037E+09 | 77628895.74 | 0.436347E+09 | 0.133078E+09 | 0.303269E+09 | 0.00 | 0.00 |
December | 0.969255E+09 | 0.118732E+09 | 0.553908E+09 | 0.235630E+09 | 0.318277E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.764929E+10 | 0.805913E+09 | 0.408144E+10 | 0.845316E+09 | 0.323612E+10 | 0.00 | 0.00 |
Minimum of Months | 0.467339E+09 | 32275336.44 | 0.231059E+09 | 0.00 | 0.231059E+09 | 0.00 | 0.00 |
Maximum of Months | 0.970458E+09 | 0.118732E+09 | 0.554163E+09 | 0.235630E+09 | 0.323012E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.969904E+09 | 0.108375E+09 | 0.554163E+09 | 0.231152E+09 | 0.323012E+09 | 0.00 | 0.00 |
February | 0.754025E+09 | 79770047.23 | 0.425004E+09 | 0.138504E+09 | 0.286499E+09 | 0.00 | 0.00 |
March | 0.595087E+09 | 66885995.52 | 0.320996E+09 | 42944669.73 | 0.278051E+09 | 0.00 | 0.00 |
April | 0.499658E+09 | 34175801.55 | 0.231732E+09 | 99776.99 | 0.231632E+09 | 0.00 | 0.00 |
May | 0.530970E+09 | 39679411.52 | 0.239624E+09 | 0.00 | 0.239624E+09 | 0.00 | 0.00 |
June | 0.508585E+09 | 41813481.23 | 0.231059E+09 | 0.00 | 0.231059E+09 | 0.00 | 0.00 |
July | 0.479536E+09 | 68979204.24 | 0.245960E+09 | 0.00 | 0.245960E+09 | 0.00 | 0.00 |
August | 0.466834E+09 | 59479526.45 | 0.239438E+09 | 364027.73 | 0.239074E+09 | 0.00 | 0.00 |
September | 0.495109E+09 | 56912333.31 | 0.256469E+09 | 8316556.52 | 0.248152E+09 | 0.00 | 0.00 |
October | 0.605096E+09 | 71977418.66 | 0.346736E+09 | 55227112.01 | 0.291509E+09 | 0.00 | 0.00 |
November | 0.767572E+09 | 79047166.97 | 0.436347E+09 | 0.133078E+09 | 0.303269E+09 | 0.00 | 0.00 |
December | 0.968821E+09 | 0.120091E+09 | 0.553908E+09 | 0.235630E+09 | 0.318277E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.764120E+10 | 0.827185E+09 | 0.408144E+10 | 0.845316E+09 | 0.323612E+10 | 0.00 | 0.00 |
Minimum of Months | 0.466834E+09 | 34175801.55 | 0.231059E+09 | 0.00 | 0.231059E+09 | 0.00 | 0.00 |
Maximum of Months | 0.969904E+09 | 0.120091E+09 | 0.554163E+09 | 0.235630E+09 | 0.323012E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.970578E+09 | 0.106479E+09 | 0.554163E+09 | 0.231152E+09 | 0.323012E+09 | 0.00 | 0.00 |
February | 0.754615E+09 | 78010630.50 | 0.425004E+09 | 0.138504E+09 | 0.286499E+09 | 0.00 | 0.00 |
March | 0.595681E+09 | 64772012.34 | 0.320996E+09 | 42944669.73 | 0.278051E+09 | 0.00 | 0.00 |
April | 0.500413E+09 | 32474441.62 | 0.231732E+09 | 99776.99 | 0.231632E+09 | 0.00 | 0.00 |
May | 0.531789E+09 | 38184529.79 | 0.239624E+09 | 0.00 | 0.239624E+09 | 0.00 | 0.00 |
June | 0.509362E+09 | 40214842.22 | 0.231059E+09 | 0.00 | 0.231059E+09 | 0.00 | 0.00 |
July | 0.480097E+09 | 67136010.10 | 0.245960E+09 | 0.00 | 0.245960E+09 | 0.00 | 0.00 |
August | 0.467476E+09 | 57432572.90 | 0.239438E+09 | 364027.73 | 0.239074E+09 | 0.00 | 0.00 |
September | 0.495740E+09 | 55057665.64 | 0.256469E+09 | 8316556.52 | 0.248152E+09 | 0.00 | 0.00 |
October | 0.605712E+09 | 69982394.89 | 0.346736E+09 | 55227112.01 | 0.291509E+09 | 0.00 | 0.00 |
November | 0.768256E+09 | 77214984.62 | 0.436347E+09 | 0.133078E+09 | 0.303269E+09 | 0.00 | 0.00 |
December | 0.969574E+09 | 0.118184E+09 | 0.553908E+09 | 0.235630E+09 | 0.318277E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.764929E+10 | 0.805142E+09 | 0.408144E+10 | 0.845316E+09 | 0.323612E+10 | 0.00 | 0.00 |
Minimum of Months | 0.467476E+09 | 32474441.62 | 0.231059E+09 | 0.00 | 0.231059E+09 | 0.00 | 0.00 |
Maximum of Months | 0.970578E+09 | 0.118184E+09 | 0.554163E+09 | 0.235630E+09 | 0.323012E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.193595E+10 | 0.199258E+09 | 0.110833E+10 | 0.462304E+09 | 0.646023E+09 | 0.00 | 0.00 |
February | 0.150306E+10 | 0.143245E+09 | 0.850007E+09 | 0.277008E+09 | 0.572999E+09 | 0.00 | 0.00 |
March | 0.118482E+10 | 0.115326E+09 | 0.641992E+09 | 85889339.47 | 0.556103E+09 | 0.00 | 0.00 |
April | 0.998051E+09 | 55930328.16 | 0.463463E+09 | 199553.98 | 0.463264E+09 | 0.00 | 0.00 |
May | 0.105957E+10 | 66652419.70 | 0.479248E+09 | 0.00 | 0.479248E+09 | 0.00 | 0.00 |
June | 0.101568E+10 | 70919372.56 | 0.462119E+09 | 0.00 | 0.462119E+09 | 0.00 | 0.00 |
July | 0.954711E+09 | 0.122109E+09 | 0.491920E+09 | 0.00 | 0.491920E+09 | 0.00 | 0.00 |
August | 0.929657E+09 | 0.100787E+09 | 0.478876E+09 | 728055.46 | 0.478148E+09 | 0.00 | 0.00 |
September | 0.987730E+09 | 98591467.95 | 0.512938E+09 | 16633113.05 | 0.496305E+09 | 0.00 | 0.00 |
October | 0.120695E+10 | 0.126813E+09 | 0.693472E+09 | 0.110454E+09 | 0.583018E+09 | 0.00 | 0.00 |
November | 0.153157E+10 | 0.141832E+09 | 0.872693E+09 | 0.266155E+09 | 0.606538E+09 | 0.00 | 0.00 |
December | 0.193426E+10 | 0.223044E+09 | 0.110782E+10 | 0.471261E+09 | 0.636555E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.152420E+11 | 0.146451E+10 | 0.816287E+10 | 0.169063E+10 | 0.647224E+10 | 0.00 | 0.00 |
Minimum of Months | 0.929657E+09 | 55930328.16 | 0.462119E+09 | 0.00 | 0.462119E+09 | 0.00 | 0.00 |
Maximum of Months | 0.193595E+10 | 0.223044E+09 | 0.110833E+10 | 0.471261E+09 | 0.646023E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.969454E+09 | 96277988.07 | 0.554163E+09 | 0.231152E+09 | 0.323012E+09 | 0.00 | 0.00 |
February | 0.753477E+09 | 68355141.94 | 0.425004E+09 | 0.138504E+09 | 0.286499E+09 | 0.00 | 0.00 |
March | 0.595471E+09 | 53769201.09 | 0.320996E+09 | 42944669.73 | 0.278051E+09 | 0.00 | 0.00 |
April | 0.503080E+09 | 25073372.03 | 0.231732E+09 | 99776.99 | 0.231632E+09 | 0.00 | 0.00 |
May | 0.534069E+09 | 30718703.76 | 0.239624E+09 | 0.00 | 0.239624E+09 | 0.00 | 0.00 |
June | 0.511990E+09 | 32607286.79 | 0.231059E+09 | 0.00 | 0.231059E+09 | 0.00 | 0.00 |
July | 0.479746E+09 | 57783940.46 | 0.245960E+09 | 0.00 | 0.245960E+09 | 0.00 | 0.00 |
August | 0.467507E+09 | 46896052.85 | 0.239438E+09 | 364027.73 | 0.239074E+09 | 0.00 | 0.00 |
September | 0.496342E+09 | 46195596.41 | 0.256469E+09 | 8316556.52 | 0.248152E+09 | 0.00 | 0.00 |
October | 0.605401E+09 | 60055291.20 | 0.346736E+09 | 55227112.01 | 0.291509E+09 | 0.00 | 0.00 |
November | 0.767437E+09 | 67807830.67 | 0.436347E+09 | 0.133078E+09 | 0.303269E+09 | 0.00 | 0.00 |
December | 0.968407E+09 | 0.108290E+09 | 0.553908E+09 | 0.235630E+09 | 0.318277E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.765238E+10 | 0.693830E+09 | 0.408144E+10 | 0.845316E+09 | 0.323612E+10 | 0.00 | 0.00 |
Minimum of Months | 0.467507E+09 | 25073372.03 | 0.231059E+09 | 0.00 | 0.231059E+09 | 0.00 | 0.00 |
Maximum of Months | 0.969454E+09 | 0.108290E+09 | 0.554163E+09 | 0.235630E+09 | 0.323012E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.970134E+09 | 95454776.40 | 0.554163E+09 | 0.231152E+09 | 0.323012E+09 | 0.00 | 0.00 |
February | 0.754058E+09 | 67644040.77 | 0.425004E+09 | 0.138504E+09 | 0.286499E+09 | 0.00 | 0.00 |
March | 0.596096E+09 | 52984352.58 | 0.320996E+09 | 42944669.73 | 0.278051E+09 | 0.00 | 0.00 |
April | 0.503828E+09 | 24479994.80 | 0.231732E+09 | 99776.99 | 0.231632E+09 | 0.00 | 0.00 |
May | 0.534893E+09 | 30170078.76 | 0.239624E+09 | 0.00 | 0.239624E+09 | 0.00 | 0.00 |
June | 0.512739E+09 | 32005449.56 | 0.231059E+09 | 0.00 | 0.231059E+09 | 0.00 | 0.00 |
July | 0.480365E+09 | 57047466.14 | 0.245960E+09 | 0.00 | 0.245960E+09 | 0.00 | 0.00 |
August | 0.468137E+09 | 46144102.42 | 0.239438E+09 | 364027.73 | 0.239074E+09 | 0.00 | 0.00 |
September | 0.496952E+09 | 45494388.16 | 0.256469E+09 | 8316556.52 | 0.248152E+09 | 0.00 | 0.00 |
October | 0.606033E+09 | 59216107.88 | 0.346736E+09 | 55227112.01 | 0.291509E+09 | 0.00 | 0.00 |
November | 0.768075E+09 | 67041166.33 | 0.436347E+09 | 0.133078E+09 | 0.303269E+09 | 0.00 | 0.00 |
December | 0.969071E+09 | 0.107461E+09 | 0.553908E+09 | 0.235630E+09 | 0.318277E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.766038E+10 | 0.685143E+09 | 0.408144E+10 | 0.845316E+09 | 0.323612E+10 | 0.00 | 0.00 |
Minimum of Months | 0.468137E+09 | 24479994.80 | 0.231059E+09 | 0.00 | 0.231059E+09 | 0.00 | 0.00 |
Maximum of Months | 0.970134E+09 | 0.107461E+09 | 0.554163E+09 | 0.235630E+09 | 0.323012E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.970309E+09 | 94946179.38 | 0.554163E+09 | 0.231152E+09 | 0.323012E+09 | 0.00 | 0.00 |
February | 0.754018E+09 | 67372718.35 | 0.425004E+09 | 0.138504E+09 | 0.286499E+09 | 0.00 | 0.00 |
March | 0.595939E+09 | 52761808.54 | 0.320996E+09 | 42944669.73 | 0.278051E+09 | 0.00 | 0.00 |
April | 0.503418E+09 | 24455201.95 | 0.231732E+09 | 99776.99 | 0.231632E+09 | 0.00 | 0.00 |
May | 0.534399E+09 | 30160016.46 | 0.239624E+09 | 0.00 | 0.239624E+09 | 0.00 | 0.00 |
June | 0.512228E+09 | 32081155.45 | 0.231059E+09 | 0.00 | 0.231059E+09 | 0.00 | 0.00 |
July | 0.480032E+09 | 57086819.91 | 0.245960E+09 | 0.00 | 0.245960E+09 | 0.00 | 0.00 |
August | 0.467864E+09 | 46053545.42 | 0.239438E+09 | 364027.73 | 0.239074E+09 | 0.00 | 0.00 |
September | 0.496632E+09 | 45464943.14 | 0.256469E+09 | 8316556.52 | 0.248152E+09 | 0.00 | 0.00 |
October | 0.606017E+09 | 58823033.11 | 0.346736E+09 | 55227112.01 | 0.291509E+09 | 0.00 | 0.00 |
November | 0.768157E+09 | 66641965.99 | 0.436347E+09 | 0.133078E+09 | 0.303269E+09 | 0.00 | 0.00 |
December | 0.969298E+09 | 0.106938E+09 | 0.553908E+09 | 0.235630E+09 | 0.318277E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.765831E+10 | 0.682785E+09 | 0.408144E+10 | 0.845316E+09 | 0.323612E+10 | 0.00 | 0.00 |
Minimum of Months | 0.467864E+09 | 24455201.95 | 0.231059E+09 | 0.00 | 0.231059E+09 | 0.00 | 0.00 |
Maximum of Months | 0.970309E+09 | 0.106938E+09 | 0.554163E+09 | 0.235630E+09 | 0.323012E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.966284E+09 | 96271175.17 | 0.554163E+09 | 0.231152E+09 | 0.323012E+09 | 0.00 | 0.00 |
February | 0.749130E+09 | 69565306.27 | 0.425004E+09 | 0.138504E+09 | 0.286499E+09 | 0.00 | 0.00 |
March | 0.589972E+09 | 55441500.05 | 0.320996E+09 | 42944669.73 | 0.278051E+09 | 0.00 | 0.00 |
April | 0.495499E+09 | 27323019.69 | 0.231732E+09 | 99776.99 | 0.231632E+09 | 0.00 | 0.00 |
May | 0.525910E+09 | 32781956.32 | 0.239624E+09 | 0.00 | 0.239624E+09 | 0.00 | 0.00 |
June | 0.503858E+09 | 35438945.21 | 0.231059E+09 | 0.00 | 0.231059E+09 | 0.00 | 0.00 |
July | 0.473446E+09 | 61252788.81 | 0.245960E+09 | 0.00 | 0.245960E+09 | 0.00 | 0.00 |
August | 0.461578E+09 | 49578264.39 | 0.239438E+09 | 364027.73 | 0.239074E+09 | 0.00 | 0.00 |
September | 0.490130E+09 | 49156531.13 | 0.256469E+09 | 8316556.52 | 0.248152E+09 | 0.00 | 0.00 |
October | 0.601566E+09 | 61020477.76 | 0.346736E+09 | 55227112.01 | 0.291509E+09 | 0.00 | 0.00 |
November | 0.763870E+09 | 68435258.25 | 0.436347E+09 | 0.133078E+09 | 0.303269E+09 | 0.00 | 0.00 |
December | 0.965623E+09 | 0.108192E+09 | 0.553908E+09 | 0.235630E+09 | 0.318277E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.758686E+10 | 0.714457E+09 | 0.408144E+10 | 0.845316E+09 | 0.323612E+10 | 0.00 | 0.00 |
Minimum of Months | 0.461578E+09 | 27323019.69 | 0.231059E+09 | 0.00 | 0.231059E+09 | 0.00 | 0.00 |
Maximum of Months | 0.966284E+09 | 0.108192E+09 | 0.554163E+09 | 0.235630E+09 | 0.323012E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.65 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.90 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.36 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 22.99 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.54 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.00 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.13 | 23.20 | 1.94 | 20.28 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.59 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 22.99 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.66 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.00 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 22.99 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.95 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.41 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.58 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.62 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.85 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.50 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.22 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.33 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.21 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.00 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.85 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.93 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.52 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.16 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.27 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.92 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.69 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.10 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.42 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.05 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.55 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.52 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.86 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.10 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.05 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.03 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.55 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.10 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.254786E+09 | -143753214.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111033072.8 | 58.99 | 0.00 | 0.00 |
February | 0.229855E+09 | -129691880.8 | 0.00 | 0.00 | 672.00 | 0.00 | -100163200.7 | 58.99 | 0.00 | 0.00 |
March | 0.254316E+09 | -143573061.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110742698.8 | 58.99 | 0.00 | 0.00 |
April | 0.241367E+09 | -134366700.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107000704.5 | 58.99 | 0.00 | 0.00 |
May | 0.246442E+09 | -135933701.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110508011.5 | 58.99 | 0.00 | 0.00 |
June | 0.237592E+09 | -130705173.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106887188.4 | 58.99 | 0.00 | 0.00 |
July | 0.242521E+09 | -131812155.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110709053.9 | 58.99 | 0.00 | 0.00 |
August | 0.246028E+09 | -135365621.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110661918.6 | 58.99 | 0.00 | 0.00 |
September | 0.239074E+09 | -131977604.3 | 0.00 | 0.00 | 720.00 | 0.00 | -107096040.4 | 58.99 | 0.00 | 0.00 |
October | 0.248862E+09 | -138050661.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110811581.8 | 58.99 | 0.00 | 0.00 |
November | 0.243379E+09 | -136105828.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107273361.7 | 58.99 | 0.00 | 0.00 |
December | 0.254409E+09 | -143314446.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111094713.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.293863E+10 | -.163465E+10 | 8760.00 | -.130398E+10 | 58.99 | |||||
Minimum of Months | 0.229855E+09 | -143753214.2 | 0.00 | 0.00 | 672.00 | 0.00 | -111094713.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.254786E+09 | -129691880.8 | 0.00 | 0.00 | 744.00 | 0.00 | -100163200.7 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.254730E+09 | -143752937.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110977560.5 | 58.99 | 0.00 | 0.00 |
February | 0.229841E+09 | -129697120.3 | 0.00 | 0.00 | 672.00 | 0.00 | -100144284.8 | 58.99 | 0.00 | 0.00 |
March | 0.254308E+09 | -143566616.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110741222.0 | 58.99 | 0.00 | 0.00 |
April | 0.241397E+09 | -134368491.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107028608.0 | 58.99 | 0.00 | 0.00 |
May | 0.246472E+09 | -135934351.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110537748.1 | 58.99 | 0.00 | 0.00 |
June | 0.237632E+09 | -130705188.1 | 0.00 | 0.00 | 720.00 | 0.00 | -106926991.7 | 58.99 | 0.00 | 0.00 |
July | 0.242541E+09 | -131814696.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110726032.7 | 58.99 | 0.00 | 0.00 |
August | 0.246048E+09 | -135363273.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110684280.4 | 58.99 | 0.00 | 0.00 |
September | 0.239099E+09 | -131981163.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107118138.1 | 58.99 | 0.00 | 0.00 |
October | 0.248844E+09 | -138052163.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110791947.6 | 58.99 | 0.00 | 0.00 |
November | 0.243356E+09 | -136103782.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107252453.9 | 58.99 | 0.00 | 0.00 |
December | 0.254359E+09 | -143321600.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111037236.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.293863E+10 | -.163466E+10 | 8760.00 | -.130397E+10 | 58.99 | |||||
Minimum of Months | 0.229841E+09 | -143752937.6 | 0.00 | 0.00 | 672.00 | 0.00 | -111037236.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.254730E+09 | -129697120.3 | 0.00 | 0.00 | 744.00 | 0.00 | -100144284.8 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.235219E+09 | -126410475.6 | 0.00 | 0.00 | 744.00 | 0.00 | -108808061.8 | 58.99 | 0.00 | 0.00 |
February | 0.212277E+09 | -114159343.1 | 0.00 | 0.00 | 672.00 | 0.00 | -98117954.1 | 58.99 | 0.00 | 0.00 |
March | 0.236807E+09 | -128235097.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108572231.0 | 58.99 | 0.00 | 0.00 |
April | 0.222754E+09 | -118094976.7 | 0.00 | 0.00 | 720.00 | 0.00 | -104659144.9 | 58.99 | 0.00 | 0.00 |
May | 0.228673E+09 | -120542947.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108130308.8 | 58.99 | 0.00 | 0.00 |
June | 0.221149E+09 | -116502134.6 | 0.00 | 0.00 | 720.00 | 0.00 | -104647356.1 | 58.99 | 0.00 | 0.00 |
July | 0.223467E+09 | -115164001.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108302743.2 | 58.99 | 0.00 | 0.00 |
August | 0.229590E+09 | -120974702.5 | 0.00 | 0.00 | 744.00 | 0.00 | -108615043.9 | 59.00 | 0.00 | 0.00 |
September | 0.220809E+09 | -115906575.4 | 0.00 | 0.00 | 720.00 | 0.00 | -104902587.2 | 58.99 | 0.00 | 0.00 |
October | 0.230002E+09 | -121396147.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108605509.7 | 58.99 | 0.00 | 0.00 |
November | 0.225427E+09 | -120181498.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105245821.5 | 58.99 | 0.00 | 0.00 |
December | 0.234050E+09 | -125123583.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108926667.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.272022E+10 | -.144269E+10 | 8760.00 | -.127753E+10 | 58.99 | |||||
Minimum of Months | 0.212277E+09 | -128235097.1 | 0.00 | 0.00 | 672.00 | 0.00 | -108926667.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.236807E+09 | -114159343.1 | 0.00 | 0.00 | 744.00 | 0.00 | -98117954.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.235118E+09 | -126408771.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108709702.1 | 58.99 | 0.00 | 0.00 |
February | 0.212174E+09 | -114160506.0 | 0.00 | 0.00 | 672.00 | 0.00 | -98013567.7 | 58.99 | 0.00 | 0.00 |
March | 0.236701E+09 | -128227983.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108473483.7 | 58.99 | 0.00 | 0.00 |
April | 0.222626E+09 | -118079699.3 | 0.00 | 0.00 | 720.00 | 0.00 | -104546633.8 | 58.99 | 0.00 | 0.00 |
May | 0.228545E+09 | -120550837.7 | 0.00 | 0.00 | 744.00 | 0.00 | -107993929.3 | 58.99 | 0.00 | 0.00 |
June | 0.221003E+09 | -116500860.2 | 0.00 | 0.00 | 720.00 | 0.00 | -104501817.2 | 58.99 | 0.00 | 0.00 |
July | 0.223344E+09 | -115153668.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108190588.8 | 58.99 | 0.00 | 0.00 |
August | 0.229486E+09 | -120991182.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108494583.8 | 58.99 | 0.00 | 0.00 |
September | 0.220704E+09 | -115906736.8 | 0.00 | 0.00 | 720.00 | 0.00 | -104797146.5 | 58.99 | 0.00 | 0.00 |
October | 0.229891E+09 | -121388512.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108502156.9 | 58.99 | 0.00 | 0.00 |
November | 0.225340E+09 | -120182099.4 | 0.00 | 0.00 | 720.00 | 0.00 | -105158210.6 | 58.99 | 0.00 | 0.00 |
December | 0.233968E+09 | -125125980.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108842268.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.271890E+10 | -.144268E+10 | 8760.00 | -.127622E+10 | 58.99 | |||||
Minimum of Months | 0.212174E+09 | -128227983.3 | 0.00 | 0.00 | 672.00 | 0.00 | -108842268.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.236701E+09 | -114160506.0 | 0.00 | 0.00 | 744.00 | 0.00 | -98013567.7 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.228691E+09 | -119483953.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109207406.3 | 58.99 | 0.00 | 0.00 |
February | 0.206432E+09 | -107949148.5 | 0.00 | 0.00 | 672.00 | 0.00 | -98482984.3 | 58.99 | 0.00 | 0.00 |
March | 0.230361E+09 | -121321728.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109038947.0 | 58.99 | 0.00 | 0.00 |
April | 0.216763E+09 | -111738510.4 | 0.00 | 0.00 | 720.00 | 0.00 | -105024693.3 | 58.99 | 0.00 | 0.00 |
May | 0.222454E+09 | -114047674.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108406723.7 | 58.98 | 0.00 | 0.00 |
June | 0.215251E+09 | -110222872.7 | 0.00 | 0.00 | 720.00 | 0.00 | -105028224.4 | 58.99 | 0.00 | 0.00 |
July | 0.217522E+09 | -108919853.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108601873.9 | 58.99 | 0.00 | 0.00 |
August | 0.223513E+09 | -114507419.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109005861.0 | 58.98 | 0.00 | 0.00 |
September | 0.214955E+09 | -109695941.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105259140.9 | 58.99 | 0.00 | 0.00 |
October | 0.223706E+09 | -114746139.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108959867.1 | 58.99 | 0.00 | 0.00 |
November | 0.219139E+09 | -113493625.3 | 0.00 | 0.00 | 720.00 | 0.00 | -105645161.7 | 58.99 | 0.00 | 0.00 |
December | 0.227650E+09 | -118329527.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109320744.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.264644E+10 | -.136446E+10 | 8760.00 | -.128198E+10 | 58.99 | |||||
Minimum of Months | 0.206432E+09 | -121321728.2 | 0.00 | 0.00 | 672.00 | 0.00 | -109320744.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.230361E+09 | -107949148.5 | 0.00 | 0.00 | 744.00 | 0.00 | -98482984.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.228844E+09 | -119487308.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109356482.9 | 58.99 | 0.00 | 0.00 |
February | 0.206577E+09 | -107951890.3 | 0.00 | 0.00 | 672.00 | 0.00 | -98624739.4 | 58.99 | 0.00 | 0.00 |
March | 0.230516E+09 | -121303744.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109211816.6 | 59.00 | 0.00 | 0.00 |
April | 0.216934E+09 | -111750278.0 | 0.00 | 0.00 | 720.00 | 0.00 | -105184049.0 | 58.99 | 0.00 | 0.00 |
May | 0.222615E+09 | -113974215.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108640377.6 | 58.99 | 0.00 | 0.00 |
June | 0.215437E+09 | -110250121.8 | 0.00 | 0.00 | 720.00 | 0.00 | -105186646.1 | 58.99 | 0.00 | 0.00 |
July | 0.217695E+09 | -108908758.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108786516.2 | 58.99 | 0.00 | 0.00 |
August | 0.223676E+09 | -114512298.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109164086.3 | 58.98 | 0.00 | 0.00 |
September | 0.215117E+09 | -109700194.1 | 0.00 | 0.00 | 720.00 | 0.00 | -105417167.3 | 58.98 | 0.00 | 0.00 |
October | 0.223870E+09 | -114748793.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109121026.1 | 58.99 | 0.00 | 0.00 |
November | 0.219292E+09 | -113509973.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105781989.0 | 58.99 | 0.00 | 0.00 |
December | 0.227814E+09 | -118330739.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109483735.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.264839E+10 | -.136443E+10 | 8760.00 | -.128396E+10 | 58.99 | |||||
Minimum of Months | 0.206577E+09 | -121303744.1 | 0.00 | 0.00 | 672.00 | 0.00 | -109483735.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.230516E+09 | -107951890.3 | 0.00 | 0.00 | 744.00 | 0.00 | -98624739.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.228896E+09 | -119487839.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109407694.8 | 58.99 | 0.00 | 0.00 |
February | 0.206620E+09 | -107951653.8 | 0.00 | 0.00 | 672.00 | 0.00 | -98668071.0 | 58.99 | 0.00 | 0.00 |
March | 0.230562E+09 | -121312995.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109249444.8 | 58.99 | 0.00 | 0.00 |
April | 0.216983E+09 | -111747825.8 | 0.00 | 0.00 | 720.00 | 0.00 | -105235313.7 | 58.99 | 0.00 | 0.00 |
May | 0.222661E+09 | -113989285.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108672179.2 | 58.99 | 0.00 | 0.00 |
June | 0.215478E+09 | -110233748.2 | 0.00 | 0.00 | 720.00 | 0.00 | -105244278.0 | 58.99 | 0.00 | 0.00 |
July | 0.217744E+09 | -108925497.4 | 0.00 | 0.00 | 744.00 | 0.00 | -108818910.0 | 58.99 | 0.00 | 0.00 |
August | 0.223721E+09 | -114543418.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109177355.0 | 58.97 | 0.00 | 0.00 |
September | 0.215158E+09 | -109681584.7 | 0.00 | 0.00 | 720.00 | 0.00 | -105476463.3 | 58.99 | 0.00 | 0.00 |
October | 0.223918E+09 | -114731494.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109186766.9 | 58.99 | 0.00 | 0.00 |
November | 0.219338E+09 | -113507912.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105830019.8 | 58.99 | 0.00 | 0.00 |
December | 0.227864E+09 | -118325228.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109538522.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.264894E+10 | -.136444E+10 | 8760.00 | -.128451E+10 | 58.99 | |||||
Minimum of Months | 0.206620E+09 | -121312995.4 | 0.00 | 0.00 | 672.00 | 0.00 | -109538522.7 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.230562E+09 | -107951653.8 | 0.00 | 0.00 | 744.00 | 0.00 | -98668071.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 350.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 361.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 376.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 370.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 357.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 356.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 349.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4292.33 | ||||||||||
Minimum of Months | 321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.462030E+11 | 0.298422E+11 | 61749.09 | 10-JAN-09:01 | 29703.44 | 0.00 |
February | 0.00 | 0.00 | 0.443918E+11 | 0.286260E+11 | 61578.73 | 16-FEB-09:01 | 30129.99 | 0.00 |
March | 0.00 | 0.00 | 0.515426E+11 | 0.327253E+11 | 62038.40 | 27-MAR-08:61 | 29040.01 | 0.00 |
April | 0.00 | 0.00 | 0.564964E+11 | 0.329069E+11 | 62221.79 | 20-APR-08:61 | 28571.21 | 0.00 |
May | 0.00 | 0.00 | 0.628531E+11 | 0.339511E+11 | 62654.45 | 17-MAY-08:61 | 26115.25 | 0.00 |
June | 0.00 | 0.00 | 0.621978E+11 | 0.334156E+11 | 62569.23 | 01-JUN-08:61 | 26208.81 | 0.00 |
July | 0.00 | 0.00 | 0.521802E+11 | 0.305657E+11 | 61939.28 | 01-JUL-08:61 | 29268.91 | 0.00 |
August | 0.00 | 0.00 | 0.583329E+11 | 0.305760E+11 | 62500.23 | 19-AUG-08:61 | 27253.57 | 0.00 |
September | 0.00 | 0.00 | 0.555654E+11 | 0.300052E+11 | 62576.89 | 21-SEP-08:61 | 26970.73 | 0.00 |
October | 0.00 | 0.00 | 0.537031E+11 | 0.290634E+11 | 62589.59 | 23-OCT-08:61 | 26827.79 | 0.00 |
November | 0.00 | 0.00 | 0.493746E+11 | 0.282792E+11 | 62005.28 | 03-NOV-08:61 | 29144.97 | 0.00 |
December | 0.00 | 0.00 | 0.471797E+11 | 0.291098E+11 | 61442.87 | 18-DEC-09:01 | 30442.54 | 0.00 |
Annual Sum or Average | 0.640021E+12 | 0.369066E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.443918E+11 | 0.282792E+11 | 61442.87 | 26115.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.628531E+11 | 0.339511E+11 | 62654.45 | 30442.54 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.225248E+11 | 0.149924E+11 | 31790.35 | 10-JAN-09:01 | 16954.97 | 0.00 |
February | 0.00 | 0.00 | 0.215371E+11 | 0.142705E+11 | 31723.88 | 16-FEB-09:01 | 17097.79 | 0.00 |
March | 0.00 | 0.00 | 0.249271E+11 | 0.162608E+11 | 31955.55 | 27-MAR-08:61 | 16510.08 | 0.00 |
April | 0.00 | 0.00 | 0.270766E+11 | 0.162479E+11 | 32087.80 | 20-APR-08:61 | 16178.64 | 0.00 |
May | 0.00 | 0.00 | 0.302137E+11 | 0.168432E+11 | 32614.25 | 16-MAY-08:61 | 14673.45 | 0.00 |
June | 0.00 | 0.00 | 0.299716E+11 | 0.165831E+11 | 32641.85 | 02-JUN-08:61 | 14783.51 | 0.00 |
July | 0.00 | 0.00 | 0.251316E+11 | 0.151607E+11 | 31813.82 | 01-JUL-08:61 | 16878.80 | 0.00 |
August | 0.00 | 0.00 | 0.281815E+11 | 0.152291E+11 | 32674.50 | 04-AUG-08:61 | 14912.87 | 0.00 |
September | 0.00 | 0.00 | 0.267504E+11 | 0.149047E+11 | 32347.68 | 01-SEP-08:61 | 15593.32 | 0.00 |
October | 0.00 | 0.00 | 0.260350E+11 | 0.145682E+11 | 32158.17 | 23-OCT-08:61 | 15759.97 | 0.00 |
November | 0.00 | 0.00 | 0.239645E+11 | 0.141836E+11 | 31903.53 | 03-NOV-08:61 | 16658.08 | 0.00 |
December | 0.00 | 0.00 | 0.229560E+11 | 0.146612E+11 | 31509.19 | 18-DEC-09:01 | 17669.55 | 0.00 |
Annual Sum or Average | 0.309270E+12 | 0.183905E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.215371E+11 | 0.141836E+11 | 31509.19 | 14673.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.302137E+11 | 0.168432E+11 | 32674.50 | 17669.55 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.185729E+11 | 0.120468E+11 | 32450.61 | 02-JAN-08:61 | 14545.53 | 0.00 |
February | 0.00 | 0.00 | 0.178967E+11 | 0.115482E+11 | 32327.30 | 16-FEB-08:61 | 14984.97 | 0.00 |
March | 0.00 | 0.00 | 0.210303E+11 | 0.133828E+11 | 32524.37 | 28-MAR-07:01 | 14582.86 | 0.00 |
April | 0.00 | 0.00 | 0.226132E+11 | 0.131512E+11 | 32587.04 | 24-APR-07:01 | 14228.20 | 0.00 |
May | 0.00 | 0.00 | 0.256057E+11 | 0.137574E+11 | 32628.16 | 17-MAY-07:01 | 13166.00 | 0.00 |
June | 0.00 | 0.00 | 0.255854E+11 | 0.136416E+11 | 32602.57 | 01-JUN-07:01 | 14107.23 | 0.00 |
July | 0.00 | 0.00 | 0.207619E+11 | 0.119901E+11 | 32533.65 | 02-JUL-08:61 | 14510.75 | 0.00 |
August | 0.00 | 0.00 | 0.240213E+11 | 0.124285E+11 | 32603.71 | 04-AUG-07:01 | 13957.05 | 0.00 |
September | 0.00 | 0.00 | 0.224082E+11 | 0.119324E+11 | 32632.78 | 18-SEP-07:01 | 13042.07 | 0.00 |
October | 0.00 | 0.00 | 0.217501E+11 | 0.116263E+11 | 32632.35 | 23-OCT-07:01 | 13263.82 | 0.00 |
November | 0.00 | 0.00 | 0.199315E+11 | 0.114057E+11 | 32541.96 | 05-NOV-08:61 | 14307.75 | 0.00 |
December | 0.00 | 0.00 | 0.188132E+11 | 0.117004E+11 | 32580.65 | 11-DEC-08:61 | 13845.10 | 0.00 |
Annual Sum or Average | 0.258990E+12 | 0.148611E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.178967E+11 | 0.114057E+11 | 32327.30 | 13042.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.256057E+11 | 0.137574E+11 | 32632.78 | 14984.97 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.186384E+11 | 0.120981E+11 | 32513.51 | 02-JAN-08:61 | 14653.94 | 0.00 |
February | 0.00 | 0.00 | 0.179603E+11 | 0.115981E+11 | 32403.96 | 16-FEB-08:61 | 15054.80 | 0.00 |
March | 0.00 | 0.00 | 0.211025E+11 | 0.134381E+11 | 32602.37 | 28-MAR-07:01 | 14652.99 | 0.00 |
April | 0.00 | 0.00 | 0.227037E+11 | 0.132179E+11 | 32663.64 | 24-APR-07:01 | 14359.70 | 0.00 |
May | 0.00 | 0.00 | 0.257195E+11 | 0.138392E+11 | 32716.74 | 17-MAY-07:01 | 13242.32 | 0.00 |
June | 0.00 | 0.00 | 0.256873E+11 | 0.137152E+11 | 32683.57 | 01-JUN-07:01 | 14177.89 | 0.00 |
July | 0.00 | 0.00 | 0.208595E+11 | 0.120613E+11 | 32607.47 | 01-JUL-07:01 | 14464.59 | 0.00 |
August | 0.00 | 0.00 | 0.240929E+11 | 0.124800E+11 | 32692.23 | 04-AUG-07:01 | 14027.34 | 0.00 |
September | 0.00 | 0.00 | 0.224876E+11 | 0.119897E+11 | 32721.38 | 18-SEP-07:01 | 13122.40 | 0.00 |
October | 0.00 | 0.00 | 0.218253E+11 | 0.116808E+11 | 32720.95 | 23-OCT-07:01 | 13343.66 | 0.00 |
November | 0.00 | 0.00 | 0.199926E+11 | 0.114506E+11 | 32610.24 | 05-NOV-08:61 | 14400.65 | 0.00 |
December | 0.00 | 0.00 | 0.188654E+11 | 0.117401E+11 | 32669.10 | 11-DEC-08:61 | 13964.13 | 0.00 |
Annual Sum or Average | 0.259935E+12 | 0.149309E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.179603E+11 | 0.114506E+11 | 32403.96 | 13122.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.257195E+11 | 0.138392E+11 | 32721.38 | 15054.80 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.184812E+11 | 0.119763E+11 | 32414.30 | 02-JAN-08:61 | 14548.88 | 0.00 |
February | 0.00 | 0.00 | 0.178151E+11 | 0.114857E+11 | 32323.31 | 16-FEB-08:61 | 14904.02 | 0.00 |
March | 0.00 | 0.00 | 0.209304E+11 | 0.133063E+11 | 32494.39 | 28-MAR-07:01 | 14544.94 | 0.00 |
April | 0.00 | 0.00 | 0.225374E+11 | 0.130952E+11 | 32557.00 | 24-APR-07:01 | 14242.39 | 0.00 |
May | 0.00 | 0.00 | 0.255562E+11 | 0.137225E+11 | 32598.08 | 17-MAY-07:01 | 13094.86 | 0.00 |
June | 0.00 | 0.00 | 0.255212E+11 | 0.135963E+11 | 32576.08 | 01-JUN-07:01 | 14052.35 | 0.00 |
July | 0.00 | 0.00 | 0.206954E+11 | 0.119410E+11 | 32522.41 | 01-JUL-07:01 | 14322.88 | 0.00 |
August | 0.00 | 0.00 | 0.239056E+11 | 0.123484E+11 | 32591.68 | 19-AUG-07:01 | 13937.73 | 0.00 |
September | 0.00 | 0.00 | 0.223142E+11 | 0.118665E+11 | 32602.70 | 18-SEP-07:01 | 13005.47 | 0.00 |
October | 0.00 | 0.00 | 0.216477E+11 | 0.115549E+11 | 32602.27 | 23-OCT-07:01 | 13237.04 | 0.00 |
November | 0.00 | 0.00 | 0.198206E+11 | 0.113261E+11 | 32518.12 | 05-NOV-08:61 | 14277.97 | 0.00 |
December | 0.00 | 0.00 | 0.186970E+11 | 0.116124E+11 | 32550.62 | 11-DEC-08:61 | 13843.09 | 0.00 |
Annual Sum or Average | 0.257922E+12 | 0.147831E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.178151E+11 | 0.113261E+11 | 32323.31 | 13005.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.255562E+11 | 0.137225E+11 | 32602.70 | 14904.02 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.333907E+11 | 0.213909E+11 | 58887.72 | 02-JAN-09:01 | 26980.93 | 0.00 |
February | 0.00 | 0.00 | 0.322266E+11 | 0.205359E+11 | 58415.40 | 16-FEB-09:01 | 28246.64 | 0.00 |
March | 0.00 | 0.00 | 0.379277E+11 | 0.238437E+11 | 58952.84 | 27-MAR-08:61 | 26995.62 | 0.00 |
April | 0.00 | 0.00 | 0.408275E+11 | 0.234062E+11 | 59077.15 | 03-APR-07:01 | 23449.66 | 0.00 |
May | 0.00 | 0.00 | 0.464549E+11 | 0.245575E+11 | 59317.22 | 17-MAY-08:61 | 24428.09 | 0.00 |
June | 0.00 | 0.00 | 0.465875E+11 | 0.244320E+11 | 59236.54 | 01-JUN-08:61 | 25005.08 | 0.00 |
July | 0.00 | 0.00 | 0.372471E+11 | 0.211813E+11 | 59055.20 | 24-JUL-08:61 | 26344.09 | 0.00 |
August | 0.00 | 0.00 | 0.433957E+11 | 0.219821E+11 | 59160.40 | 19-AUG-08:61 | 25794.00 | 0.00 |
September | 0.00 | 0.00 | 0.402865E+11 | 0.210601E+11 | 59317.22 | 18-SEP-08:61 | 23062.40 | 0.00 |
October | 0.00 | 0.00 | 0.390098E+11 | 0.204383E+11 | 59299.65 | 23-OCT-08:61 | 23219.94 | 0.00 |
November | 0.00 | 0.00 | 0.357665E+11 | 0.200721E+11 | 59090.36 | 13-NOV-09:01 | 25363.90 | 0.00 |
December | 0.00 | 0.00 | 0.335587E+11 | 0.205668E+11 | 59153.70 | 18-DEC-09:01 | 26267.93 | 0.00 |
Annual Sum or Average | 0.466679E+12 | 0.263467E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.322266E+11 | 0.200721E+11 | 58415.40 | 23062.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.465875E+11 | 0.245575E+11 | 59317.22 | 28246.64 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.174060E+11 | 0.111688E+11 | 31025.05 | 02-JAN-09:01 | 14206.80 | 0.00 |
February | 0.00 | 0.00 | 0.167996E+11 | 0.107194E+11 | 30746.23 | 16-FEB-09:01 | 14893.45 | 0.00 |
March | 0.00 | 0.00 | 0.197524E+11 | 0.124353E+11 | 31024.06 | 27-MAR-08:61 | 14234.24 | 0.00 |
April | 0.00 | 0.00 | 0.212544E+11 | 0.122060E+11 | 31093.37 | 03-APR-07:01 | 12255.04 | 0.00 |
May | 0.00 | 0.00 | 0.241687E+11 | 0.128048E+11 | 31219.73 | 17-MAY-08:61 | 12896.12 | 0.00 |
June | 0.00 | 0.00 | 0.242189E+11 | 0.127258E+11 | 31177.26 | 01-JUN-08:61 | 13214.03 | 0.00 |
July | 0.00 | 0.00 | 0.193911E+11 | 0.110478E+11 | 31093.93 | 24-JUL-08:61 | 13881.04 | 0.00 |
August | 0.00 | 0.00 | 0.225622E+11 | 0.114555E+11 | 31144.60 | 19-AUG-08:61 | 13607.64 | 0.00 |
September | 0.00 | 0.00 | 0.209633E+11 | 0.109813E+11 | 31219.73 | 18-SEP-08:61 | 12126.16 | 0.00 |
October | 0.00 | 0.00 | 0.203053E+11 | 0.106621E+11 | 31210.48 | 23-OCT-08:61 | 12238.95 | 0.00 |
November | 0.00 | 0.00 | 0.186156E+11 | 0.104681E+11 | 31100.32 | 13-NOV-09:01 | 13355.69 | 0.00 |
December | 0.00 | 0.00 | 0.174812E+11 | 0.107320E+11 | 31156.18 | 18-DEC-09:01 | 13809.24 | 0.00 |
Annual Sum or Average | 0.242919E+12 | 0.137407E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.167996E+11 | 0.104681E+11 | 30746.23 | 12126.16 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.242189E+11 | 0.128048E+11 | 31219.73 | 14893.45 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.173065E+11 | 0.110925E+11 | 30858.42 | 02-JAN-09:01 | 14117.06 | 0.00 |
February | 0.00 | 0.00 | 0.167133E+11 | 0.106525E+11 | 30604.57 | 16-FEB-09:01 | 14787.22 | 0.00 |
March | 0.00 | 0.00 | 0.196558E+11 | 0.123613E+11 | 30877.28 | 27-MAR-08:61 | 14142.45 | 0.00 |
April | 0.00 | 0.00 | 0.211599E+11 | 0.121359E+11 | 30899.74 | 24-APR-08:61 | 13634.79 | 0.00 |
May | 0.00 | 0.00 | 0.240695E+11 | 0.127328E+11 | 31062.93 | 17-MAY-08:61 | 12795.73 | 0.00 |
June | 0.00 | 0.00 | 0.241185E+11 | 0.126530E+11 | 31020.67 | 01-JUN-08:61 | 13106.70 | 0.00 |
July | 0.00 | 0.00 | 0.192951E+11 | 0.109775E+11 | 30945.09 | 24-JUL-08:61 | 13791.06 | 0.00 |
August | 0.00 | 0.00 | 0.224606E+11 | 0.113837E+11 | 30998.39 | 19-AUG-08:61 | 13508.81 | 0.00 |
September | 0.00 | 0.00 | 0.208664E+11 | 0.109123E+11 | 31062.93 | 18-SEP-08:61 | 12033.44 | 0.00 |
October | 0.00 | 0.00 | 0.202038E+11 | 0.105899E+11 | 31053.72 | 23-OCT-08:61 | 12145.65 | 0.00 |
November | 0.00 | 0.00 | 0.185143E+11 | 0.103945E+11 | 30944.12 | 13-NOV-09:01 | 13260.22 | 0.00 |
December | 0.00 | 0.00 | 0.173812E+11 | 0.106566E+11 | 31011.22 | 18-DEC-09:01 | 13709.35 | 0.00 |
Annual Sum or Average | 0.241745E+12 | 0.136543E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.167133E+11 | 0.103945E+11 | 30604.57 | 12033.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.241185E+11 | 0.127328E+11 | 31062.93 | 14787.22 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.172467E+11 | 0.110479E+11 | 30877.04 | 02-JAN-09:01 | 14064.00 | 0.00 |
February | 0.00 | 0.00 | 0.166785E+11 | 0.106270E+11 | 30615.82 | 16-FEB-09:01 | 14754.08 | 0.00 |
March | 0.00 | 0.00 | 0.196229E+11 | 0.123379E+11 | 30889.00 | 27-MAR-08:61 | 14108.87 | 0.00 |
April | 0.00 | 0.00 | 0.211489E+11 | 0.121292E+11 | 30898.13 | 24-APR-08:61 | 13591.08 | 0.00 |
May | 0.00 | 0.00 | 0.240561E+11 | 0.127253E+11 | 31061.30 | 17-MAY-08:61 | 12765.95 | 0.00 |
June | 0.00 | 0.00 | 0.241182E+11 | 0.126539E+11 | 31019.05 | 01-JUN-08:61 | 13069.13 | 0.00 |
July | 0.00 | 0.00 | 0.192785E+11 | 0.109662E+11 | 30954.61 | 24-JUL-08:61 | 13761.15 | 0.00 |
August | 0.00 | 0.00 | 0.224347E+11 | 0.113676E+11 | 31004.09 | 19-AUG-08:61 | 13484.61 | 0.00 |
September | 0.00 | 0.00 | 0.208520E+11 | 0.109028E+11 | 31061.30 | 18-SEP-08:61 | 11989.64 | 0.00 |
October | 0.00 | 0.00 | 0.201456E+11 | 0.105514E+11 | 31052.10 | 23-OCT-08:61 | 12100.84 | 0.00 |
November | 0.00 | 0.00 | 0.184603E+11 | 0.103569E+11 | 30942.50 | 13-NOV-09:01 | 13210.74 | 0.00 |
December | 0.00 | 0.00 | 0.173165E+11 | 0.106094E+11 | 31010.43 | 18-DEC-09:01 | 13654.29 | 0.00 |
Annual Sum or Average | 0.241359E+12 | 0.136275E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.166785E+11 | 0.103569E+11 | 30615.82 | 11989.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.241182E+11 | 0.127253E+11 | 31061.30 | 14754.08 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.183867E+11 | 0.118647E+11 | 33460.99 | 02-JAN-09:01 | 15026.25 | 0.00 |
February | 0.00 | 0.00 | 0.178968E+11 | 0.115067E+11 | 33408.61 | 16-FEB-09:01 | 15178.12 | 0.00 |
March | 0.00 | 0.00 | 0.211564E+11 | 0.134014E+11 | 33411.10 | 24-MAR-08:61 | 14839.29 | 0.00 |
April | 0.00 | 0.00 | 0.228124E+11 | 0.132321E+11 | 33535.28 | 21-APR-08:61 | 14531.55 | 0.00 |
May | 0.00 | 0.00 | 0.258417E+11 | 0.138368E+11 | 33587.54 | 17-MAY-08:61 | 12856.59 | 0.00 |
June | 0.00 | 0.00 | 0.259941E+11 | 0.138349E+11 | 33541.86 | 01-JUN-08:61 | 13126.85 | 0.00 |
July | 0.00 | 0.00 | 0.207710E+11 | 0.119729E+11 | 33533.00 | 24-JUL-08:61 | 14736.91 | 0.00 |
August | 0.00 | 0.00 | 0.241084E+11 | 0.123967E+11 | 33563.90 | 19-AUG-08:61 | 13544.05 | 0.00 |
September | 0.00 | 0.00 | 0.224027E+11 | 0.119014E+11 | 33587.54 | 18-SEP-08:61 | 12940.79 | 0.00 |
October | 0.00 | 0.00 | 0.213831E+11 | 0.113401E+11 | 33577.59 | 23-OCT-08:61 | 13010.93 | 0.00 |
November | 0.00 | 0.00 | 0.196407E+11 | 0.111492E+11 | 33459.09 | 13-NOV-09:01 | 14507.05 | 0.00 |
December | 0.00 | 0.00 | 0.184255E+11 | 0.113918E+11 | 33532.54 | 18-DEC-09:01 | 14581.47 | 0.00 |
Annual Sum or Average | 0.258820E+12 | 0.147829E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.178968E+11 | 0.111492E+11 | 33408.61 | 12856.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.259941E+11 | 0.138368E+11 | 33587.54 | 15178.12 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.424335E+10 | 0.59 | 2338.71 | 01-JAN-08:07 | 0.86 |
February | 0.383922E+10 | 0.59 | 2338.71 | 01-FEB-09:00 | 0.87 |
March | 0.425177E+10 | 0.59 | 2338.71 | 01-MAR-08:06 | 0.86 |
April | 0.411706E+10 | 0.59 | 2338.71 | 01-APR-07:04 | 0.86 |
May | 0.424335E+10 | 0.58 | 2338.71 | 01-MAY-07:17 | 0.86 |
June | 0.411706E+10 | 0.59 | 2338.71 | 01-JUN-07:09 | 0.86 |
July | 0.425177E+10 | 0.59 | 2338.71 | 01-JUL-07:17 | 0.86 |
August | 0.424335E+10 | 0.58 | 2338.71 | 01-AUG-07:10 | 0.86 |
September | 0.412548E+10 | 0.59 | 2338.71 | 01-SEP-07:03 | 0.86 |
October | 0.424335E+10 | 0.58 | 2338.71 | 01-OCT-07:07 | 0.86 |
November | 0.410022E+10 | 0.58 | 2338.71 | 01-NOV-08:10 | 0.86 |
December | 0.426019E+10 | 0.59 | 2338.71 | 01-DEC-00:10 | 0.86 |
Annual Sum or Average | 0.500362E+11 | 0.59 | |||
Minimum of Months | 0.383922E+10 | 0.58 | 2338.71 | 0.86 | |
Maximum of Months | 0.426019E+10 | 0.59 | 2338.71 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.192420E+10 | 0.64 | 1266.88 | 02-JAN-08:50 | 0.89 |
February | 0.174469E+10 | 0.64 | 1266.88 | 08-FEB-09:20 | 0.90 |
March | 0.195392E+10 | 0.64 | 1266.88 | 09-MAR-08:04 | 0.90 |
April | 0.189911E+10 | 0.64 | 1266.88 | 01-APR-07:09 | 0.89 |
May | 0.198000E+10 | 0.63 | 1266.88 | 01-MAY-07:10 | 0.89 |
June | 0.192239E+10 | 0.63 | 1266.88 | 03-JUN-07:30 | 0.89 |
July | 0.194206E+10 | 0.64 | 1266.88 | 03-JUL-07:06 | 0.90 |
August | 0.196870E+10 | 0.63 | 1266.88 | 01-AUG-07:04 | 0.89 |
September | 0.189483E+10 | 0.64 | 1266.88 | 02-SEP-16:30 | 0.89 |
October | 0.194311E+10 | 0.64 | 1266.88 | 01-OCT-07:07 | 0.90 |
November | 0.187632E+10 | 0.64 | 1266.88 | 01-NOV-07:10 | 0.89 |
December | 0.192376E+10 | 0.64 | 1266.88 | 03-DEC-08:20 | 0.90 |
Annual Sum or Average | 0.229731E+11 | 0.64 | |||
Minimum of Months | 0.174469E+10 | 0.63 | 1266.88 | 0.89 | |
Maximum of Months | 0.198000E+10 | 0.64 | 1266.88 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.182388E+10 | 0.48 | 1260.28 | 13-JAN-08:00 | 0.89 |
February | 0.165147E+10 | 0.49 | 1260.28 | 10-FEB-08:00 | 0.89 |
March | 0.186017E+10 | 0.49 | 1260.28 | 01-MAR-07:30 | 0.89 |
April | 0.176943E+10 | 0.48 | 1260.28 | 01-APR-06:10 | 0.89 |
May | 0.184202E+10 | 0.49 | 1260.28 | 16-MAY-06:20 | 0.89 |
June | 0.179665E+10 | 0.49 | 1260.28 | 20-JUN-06:50 | 0.89 |
July | 0.181480E+10 | 0.48 | 1260.28 | 02-JUL-07:06 | 0.89 |
August | 0.186017E+10 | 0.49 | 1260.28 | 20-AUG-11:50 | 0.89 |
September | 0.176943E+10 | 0.48 | 1260.28 | 01-SEP-06:10 | 0.89 |
October | 0.182388E+10 | 0.48 | 1260.28 | 26-OCT-06:40 | 0.89 |
November | 0.176943E+10 | 0.48 | 1260.28 | 14-NOV-07:20 | 0.89 |
December | 0.181480E+10 | 0.48 | 1260.28 | 21-DEC-08:40 | 0.90 |
Annual Sum or Average | 0.215961E+11 | 0.49 | |||
Minimum of Months | 0.165147E+10 | 0.48 | 1260.28 | 0.89 | |
Maximum of Months | 0.186017E+10 | 0.49 | 1260.28 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.182883E+10 | 0.48 | 1263.70 | 01-JAN-08:20 | 0.89 |
February | 0.165595E+10 | 0.49 | 1263.70 | 01-FEB-08:07 | 0.90 |
March | 0.186522E+10 | 0.49 | 1263.70 | 02-MAR-07:20 | 0.89 |
April | 0.177424E+10 | 0.48 | 1263.70 | 03-APR-13:20 | 0.89 |
May | 0.184703E+10 | 0.49 | 1263.70 | 01-MAY-15:00 | 0.89 |
June | 0.180153E+10 | 0.49 | 1263.70 | 02-JUN-07:00 | 0.89 |
July | 0.181973E+10 | 0.48 | 1263.70 | 01-JUL-06:10 | 0.89 |
August | 0.186522E+10 | 0.49 | 1263.70 | 01-AUG-12:10 | 0.89 |
September | 0.177424E+10 | 0.48 | 1263.70 | 03-SEP-07:01 | 0.88 |
October | 0.182883E+10 | 0.48 | 1263.70 | 01-OCT-07:06 | 0.89 |
November | 0.177424E+10 | 0.48 | 1263.70 | 01-NOV-06:50 | 0.89 |
December | 0.181973E+10 | 0.48 | 1263.70 | 02-DEC-07:40 | 0.89 |
Annual Sum or Average | 0.216548E+11 | 0.49 | |||
Minimum of Months | 0.165595E+10 | 0.48 | 1263.70 | 0.88 | |
Maximum of Months | 0.186522E+10 | 0.49 | 1263.70 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.182219E+10 | 0.48 | 1259.12 | 01-JAN-08:08 | 0.89 |
February | 0.164995E+10 | 0.49 | 1259.12 | 01-FEB-09:03 | 0.90 |
March | 0.185846E+10 | 0.49 | 1259.12 | 01-MAR-07:40 | 0.89 |
April | 0.176780E+10 | 0.48 | 1259.12 | 01-APR-08:10 | 0.89 |
May | 0.184033E+10 | 0.49 | 1259.12 | 01-MAY-06:10 | 0.88 |
June | 0.179500E+10 | 0.49 | 1259.12 | 26-JUN-07:00 | 0.88 |
July | 0.181313E+10 | 0.48 | 1259.12 | 01-JUL-06:20 | 0.89 |
August | 0.185846E+10 | 0.49 | 1259.12 | 01-AUG-06:20 | 0.89 |
September | 0.176780E+10 | 0.48 | 1259.12 | 01-SEP-12:20 | 0.89 |
October | 0.182219E+10 | 0.48 | 1259.12 | 01-OCT-07:04 | 0.89 |
November | 0.176780E+10 | 0.48 | 1259.12 | 13-NOV-07:40 | 0.89 |
December | 0.181313E+10 | 0.48 | 1259.12 | 01-DEC-08:15 | 0.89 |
Annual Sum or Average | 0.215762E+11 | 0.49 | |||
Minimum of Months | 0.164995E+10 | 0.48 | 1259.12 | 0.88 | |
Maximum of Months | 0.185846E+10 | 0.49 | 1259.12 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.295720E+10 | 0.43 | 2214.14 | 01-JAN-11:40 | 0.87 |
February | 0.267822E+10 | 0.43 | 2214.14 | 02-FEB-20:08 | 0.87 |
March | 0.302097E+10 | 0.44 | 2214.14 | 01-MAR-11:10 | 0.87 |
April | 0.286952E+10 | 0.43 | 2214.14 | 04-APR-16:20 | 0.87 |
May | 0.298909E+10 | 0.43 | 2214.14 | 01-MAY-12:10 | 0.86 |
June | 0.291735E+10 | 0.44 | 2214.14 | 02-JUN-07:04 | 0.86 |
July | 0.294126E+10 | 0.43 | 2214.14 | 01-JUL-08:40 | 0.86 |
August | 0.302097E+10 | 0.44 | 2214.14 | 02-AUG-07:09 | 0.86 |
September | 0.286952E+10 | 0.43 | 2214.14 | 01-SEP-15:10 | 0.86 |
October | 0.295720E+10 | 0.43 | 2214.14 | 01-OCT-09:00 | 0.86 |
November | 0.286952E+10 | 0.43 | 2214.14 | 01-NOV-08:09 | 0.86 |
December | 0.294126E+10 | 0.43 | 2214.14 | 03-DEC-09:01 | 0.86 |
Annual Sum or Average | 0.350321E+11 | 0.43 | |||
Minimum of Months | 0.267822E+10 | 0.43 | 2214.14 | 0.86 | |
Maximum of Months | 0.302097E+10 | 0.44 | 2214.14 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.161041E+10 | 0.45 | 1205.76 | 03-JAN-20:10 | 0.90 |
February | 0.145848E+10 | 0.45 | 1205.76 | 01-FEB-20:03 | 0.90 |
March | 0.164514E+10 | 0.46 | 1205.76 | 05-MAR-10:15 | 0.89 |
April | 0.156266E+10 | 0.45 | 1205.76 | 09-APR-08:40 | 0.89 |
May | 0.162777E+10 | 0.45 | 1205.76 | 01-MAY-13:40 | 0.89 |
June | 0.158871E+10 | 0.45 | 1205.76 | 03-JUN-07:30 | 0.89 |
July | 0.160173E+10 | 0.44 | 1205.76 | 05-JUL-08:08 | 0.89 |
August | 0.164514E+10 | 0.45 | 1205.76 | 04-AUG-07:30 | 0.89 |
September | 0.156266E+10 | 0.45 | 1205.76 | 02-SEP-15:00 | 0.89 |
October | 0.161041E+10 | 0.44 | 1205.76 | 03-OCT-07:17 | 0.89 |
November | 0.156266E+10 | 0.45 | 1205.76 | 08-NOV-09:00 | 0.89 |
December | 0.160173E+10 | 0.44 | 1205.76 | 04-DEC-11:20 | 0.90 |
Annual Sum or Average | 0.190775E+11 | 0.45 | |||
Minimum of Months | 0.145848E+10 | 0.44 | 1205.76 | 0.89 | |
Maximum of Months | 0.164514E+10 | 0.46 | 1205.76 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.160232E+10 | 0.45 | 1199.70 | 01-JAN-09:40 | 0.89 |
February | 0.145116E+10 | 0.45 | 1199.70 | 05-FEB-09:04 | 0.89 |
March | 0.163687E+10 | 0.46 | 1199.70 | 01-MAR-08:20 | 0.89 |
April | 0.155481E+10 | 0.45 | 1199.70 | 05-APR-07:10 | 0.89 |
May | 0.161960E+10 | 0.45 | 1199.70 | 02-MAY-07:03 | 0.89 |
June | 0.158072E+10 | 0.45 | 1199.70 | 03-JUN-07:06 | 0.89 |
July | 0.159368E+10 | 0.44 | 1199.70 | 03-JUL-07:20 | 0.89 |
August | 0.163687E+10 | 0.45 | 1199.70 | 01-AUG-07:13 | 0.89 |
September | 0.155481E+10 | 0.45 | 1199.70 | 01-SEP-07:09 | 0.89 |
October | 0.160232E+10 | 0.44 | 1199.70 | 01-OCT-08:30 | 0.89 |
November | 0.155481E+10 | 0.45 | 1199.70 | 03-NOV-19:30 | 0.89 |
December | 0.159368E+10 | 0.44 | 1199.70 | 01-DEC-08:40 | 0.89 |
Annual Sum or Average | 0.189817E+11 | 0.45 | |||
Minimum of Months | 0.145116E+10 | 0.44 | 1199.70 | 0.89 | |
Maximum of Months | 0.163687E+10 | 0.46 | 1199.70 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.160224E+10 | 0.45 | 1199.64 | 03-JAN-08:50 | 0.89 |
February | 0.145108E+10 | 0.45 | 1199.64 | 03-FEB-09:20 | 0.90 |
March | 0.163679E+10 | 0.46 | 1199.64 | 02-MAR-08:50 | 0.89 |
April | 0.155473E+10 | 0.45 | 1199.64 | 01-APR-07:50 | 0.89 |
May | 0.161951E+10 | 0.45 | 1199.64 | 01-MAY-14:30 | 0.89 |
June | 0.158064E+10 | 0.45 | 1199.64 | 05-JUN-08:18 | 0.89 |
July | 0.159360E+10 | 0.44 | 1199.64 | 05-JUL-08:00 | 0.89 |
August | 0.163679E+10 | 0.45 | 1199.64 | 02-AUG-07:40 | 0.89 |
September | 0.155473E+10 | 0.45 | 1199.64 | 01-SEP-07:50 | 0.89 |
October | 0.160224E+10 | 0.44 | 1199.64 | 01-OCT-08:30 | 0.89 |
November | 0.155473E+10 | 0.45 | 1199.64 | 03-NOV-07:50 | 0.89 |
December | 0.159360E+10 | 0.44 | 1199.64 | 02-DEC-09:00 | 0.89 |
Annual Sum or Average | 0.189807E+11 | 0.45 | |||
Minimum of Months | 0.145108E+10 | 0.44 | 1199.64 | 0.89 | |
Maximum of Months | 0.163679E+10 | 0.46 | 1199.64 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.173255E+10 | 0.45 | 1297.21 | 12-JAN-09:20 | 0.89 |
February | 0.156910E+10 | 0.45 | 1297.21 | 01-FEB-09:06 | 0.90 |
March | 0.176991E+10 | 0.46 | 1297.21 | 20-MAR-07:10 | 0.89 |
April | 0.168118E+10 | 0.45 | 1297.21 | 01-APR-07:09 | 0.89 |
May | 0.175123E+10 | 0.45 | 1297.21 | 01-MAY-07:15 | 0.88 |
June | 0.170920E+10 | 0.45 | 1297.21 | 09-JUN-07:05 | 0.88 |
July | 0.172321E+10 | 0.44 | 1297.21 | 01-JUL-07:30 | 0.89 |
August | 0.176991E+10 | 0.45 | 1297.21 | 01-AUG-07:10 | 0.89 |
September | 0.168118E+10 | 0.45 | 1297.21 | 06-SEP-08:00 | 0.89 |
October | 0.173255E+10 | 0.44 | 1297.21 | 04-OCT-19:03 | 0.89 |
November | 0.168118E+10 | 0.45 | 1297.21 | 09-NOV-09:00 | 0.89 |
December | 0.172321E+10 | 0.44 | 1297.21 | 18-DEC-18:50 | 0.89 |
Annual Sum or Average | 0.205244E+11 | 0.45 | |||
Minimum of Months | 0.156910E+10 | 0.44 | 1297.21 | 0.88 | |
Maximum of Months | 0.176991E+10 | 0.46 | 1297.21 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.14 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.92 | 0.00 |
May | 1.00 | 0.00 |
June | 1.33 | 0.00 |
July | 0.00 | 0.00 |
August | 0.44 | 0.00 |
September | 0.42 | 0.00 |
October | 0.00 | 0.00 |
November | 0.56 | 0.00 |
December | 0.69 | 0.00 |
Annual Sum or Average | 5.50 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.33 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.14 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.28 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.56 | 0.00 |
December | 0.69 | 0.00 |
Annual Sum or Average | 1.67 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.69 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.75 | 0.75 |
February | 4.43 | 0.75 |
March | 4.98 | 0.74 |
April | 4.90 | 0.72 |
May | 4.89 | 0.75 |
June | 4.65 | 0.74 |
July | 4.32 | 0.75 |
August | 4.43 | 0.75 |
September | 4.36 | 0.72 |
October | 4.53 | 0.75 |
November | 4.23 | 0.75 |
December | 3.91 | 0.75 |
Annual Sum or Average | 54.38 | 0.74 |
Minimum of Months | 3.91 | 0.72 |
Maximum of Months | 4.98 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.75 | 0.75 |
February | 4.51 | 0.75 |
March | 5.06 | 0.74 |
April | 4.90 | 0.72 |
May | 4.80 | 0.75 |
June | 4.65 | 0.74 |
July | 4.32 | 0.75 |
August | 4.60 | 0.72 |
September | 4.36 | 0.72 |
October | 4.53 | 0.75 |
November | 4.23 | 0.75 |
December | 3.91 | 0.75 |
Annual Sum or Average | 54.63 | 0.74 |
Minimum of Months | 3.91 | 0.72 |
Maximum of Months | 5.06 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.75 | 0.75 |
February | 4.51 | 0.75 |
March | 5.06 | 0.74 |
April | 4.90 | 0.72 |
May | 5.10 | 0.73 |
June | 4.65 | 0.74 |
July | 4.32 | 0.75 |
August | 4.43 | 0.75 |
September | 4.36 | 0.72 |
October | 4.53 | 0.75 |
November | 4.23 | 0.75 |
December | 3.91 | 0.75 |
Annual Sum or Average | 54.75 | 0.74 |
Minimum of Months | 3.91 | 0.72 |
Maximum of Months | 5.10 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.98 | 2.84 |
February | 1.64 | 3.13 |
March | 1.62 | 2.79 |
April | 2.51 | 2.24 |
May | 3.12 | 2.26 |
June | 2.77 | 1.99 |
July | 2.09 | 3.04 |
August | 1.86 | 2.12 |
September | 2.59 | 1.95 |
October | 2.56 | 1.76 |
November | 2.07 | 2.19 |
December | 2.45 | 2.18 |
Annual Sum or Average | 27.25 | 2.32 |
Minimum of Months | 1.62 | 1.76 |
Maximum of Months | 3.12 | 3.13 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.98 | 1.42 |
February | 1.39 | 1.65 |
March | 1.37 | 1.55 |
April | 1.84 | 1.38 |
May | 2.12 | 1.34 |
June | 1.81 | 1.49 |
July | 1.70 | 1.65 |
August | 1.57 | 1.21 |
September | 2.17 | 1.16 |
October | 2.31 | 0.98 |
November | 1.99 | 1.14 |
December | 2.20 | 1.21 |
Annual Sum or Average | 22.44 | 1.32 |
Minimum of Months | 1.37 | 0.98 |
Maximum of Months | 2.31 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.98 | 1.42 |
February | 1.39 | 1.65 |
March | 1.37 | 1.55 |
April | 1.67 | 1.43 |
May | 2.12 | 1.34 |
June | 1.73 | 1.48 |
July | 1.70 | 1.65 |
August | 1.57 | 1.21 |
September | 2.17 | 1.16 |
October | 2.31 | 0.98 |
November | 1.82 | 1.25 |
December | 1.97 | 1.30 |
Annual Sum or Average | 21.80 | 1.35 |
Minimum of Months | 1.37 | 0.98 |
Maximum of Months | 2.31 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.90 | 1.48 |
February | 1.39 | 1.65 |
March | 1.37 | 1.55 |
April | 1.76 | 1.44 |
May | 2.16 | 1.34 |
June | 1.81 | 1.49 |
July | 1.70 | 1.65 |
August | 1.40 | 1.36 |
September | 2.09 | 1.21 |
October | 2.14 | 1.05 |
November | 1.74 | 1.31 |
December | 1.89 | 1.36 |
Annual Sum or Average | 21.34 | 1.39 |
Minimum of Months | 1.37 | 1.05 |
Maximum of Months | 2.16 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.98 | 1.42 |
February | 1.56 | 1.65 |
March | 1.45 | 1.55 |
April | 1.67 | 1.51 |
May | 2.33 | 1.25 |
June | 2.06 | 1.17 |
July | 1.92 | 1.65 |
August | 1.73 | 1.10 |
September | 2.26 | 1.12 |
October | 2.39 | 0.94 |
November | 1.99 | 1.14 |
December | 2.45 | 1.09 |
Annual Sum or Average | 23.79 | 1.27 |
Minimum of Months | 1.45 | 0.94 |
Maximum of Months | 2.45 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.167962E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.159687E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.183712E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.192498E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.206983E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.203000E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.180675E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.192434E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.185199E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.181473E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.170679E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.168879E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.219318E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.159687E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.206983E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.805709E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.764342E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.880350E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.918941E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.992899E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.975228E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.862028E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.923480E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.885007E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.870012E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.818577E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.808703E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.105053E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.764342E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.992899E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.679205E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.646343E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.754392E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.772256E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.841892E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.833172E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.719037E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.791178E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.744984E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.733195E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.690942E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.677845E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.888444E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.646343E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.841892E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.681509E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.648553E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.757003E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.775185E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.845377E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.836383E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.722085E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.793686E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.747596E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.735743E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.693118E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.679807E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.891604E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.648553E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.845377E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.676784E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.644162E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.751726E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.770167E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.840425E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.831403E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.717198E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.788240E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.742513E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.730566E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.688110E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.674854E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.885615E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.644162E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.840425E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.120269E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.114693E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.134156E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.137507E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.150431E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.149397E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.127107E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.140723E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.132023E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.129580E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.122144E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.119263E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.157729E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.114693E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.150431E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.626316E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.596886E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.697391E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.714043E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.780492E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.774565E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.660848E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.730329E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.685647E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.673457E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.634985E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.620795E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.819575E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.596886E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.780492E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.622769E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.593703E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.693773E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.710473E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.776791E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.770836E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.657398E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.726663E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.682153E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.669879E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.631425E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.617251E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.815311E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.593703E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.776791E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.621280E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.592821E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.692921E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.710186E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.776413E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.770756E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.656940E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.726005E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.681764E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.668473E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.630118E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.615671E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.814335E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.592821E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.776413E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.666837E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.639267E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.749411E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.769038E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.838904E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.834863E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.710474E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.784363E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.736468E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.715916E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.675848E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.660151E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.878154E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.639267E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.838904E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.424335E+10 | 0.462030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.383922E+10 | 0.443918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.425177E+10 | 0.515426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.411706E+10 | 0.564964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.424335E+10 | 0.628531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.411706E+10 | 0.621978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.425177E+10 | 0.521802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.424335E+10 | 0.583329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.412548E+10 | 0.555654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.424335E+10 | 0.537031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.410022E+10 | 0.493746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.426019E+10 | 0.471797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.500362E+11 | 0.640021E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.383922E+10 | 0.443918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.426019E+10 | 0.628531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.192420E+10 | 0.225248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174469E+10 | 0.215371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195392E+10 | 0.249271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189911E+10 | 0.270766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198000E+10 | 0.302137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.192239E+10 | 0.299716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.194206E+10 | 0.251316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196870E+10 | 0.281815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189483E+10 | 0.267504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194311E+10 | 0.260350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187632E+10 | 0.239645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192376E+10 | 0.229560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229731E+11 | 0.309270E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.174469E+10 | 0.215371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.198000E+10 | 0.302137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.182388E+10 | 0.185729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165147E+10 | 0.178967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186017E+10 | 0.210303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176943E+10 | 0.226132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.184202E+10 | 0.256057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179665E+10 | 0.255854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181480E+10 | 0.207619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.186017E+10 | 0.240213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176943E+10 | 0.224082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182388E+10 | 0.217501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176943E+10 | 0.199315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181480E+10 | 0.188132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215961E+11 | 0.258990E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.165147E+10 | 0.178967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.186017E+10 | 0.256057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.182883E+10 | 0.186384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165595E+10 | 0.179603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186522E+10 | 0.211025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177424E+10 | 0.227037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.184703E+10 | 0.257195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.180153E+10 | 0.256873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181973E+10 | 0.208595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.186522E+10 | 0.240929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.177424E+10 | 0.224876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182883E+10 | 0.218253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177424E+10 | 0.199926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181973E+10 | 0.188654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216548E+11 | 0.259935E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.165595E+10 | 0.179603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.186522E+10 | 0.257195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.182219E+10 | 0.184812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164995E+10 | 0.178151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185846E+10 | 0.209304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176780E+10 | 0.225374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.184033E+10 | 0.255562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179500E+10 | 0.255212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181313E+10 | 0.206954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.185846E+10 | 0.239056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176780E+10 | 0.223142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182219E+10 | 0.216477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176780E+10 | 0.198206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181313E+10 | 0.186970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215762E+11 | 0.257922E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.164995E+10 | 0.178151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.185846E+10 | 0.255562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.295720E+10 | 0.333907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.267822E+10 | 0.322266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.302097E+10 | 0.379277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.286952E+10 | 0.408275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.298909E+10 | 0.464549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.291735E+10 | 0.465875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.294126E+10 | 0.372471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.302097E+10 | 0.433957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.286952E+10 | 0.402865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.295720E+10 | 0.390098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286952E+10 | 0.357665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.294126E+10 | 0.335587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.350321E+11 | 0.466679E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.267822E+10 | 0.322266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.302097E+10 | 0.465875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.161041E+10 | 0.174060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145848E+10 | 0.167996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164514E+10 | 0.197524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156266E+10 | 0.212544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162777E+10 | 0.241687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158871E+10 | 0.242189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160173E+10 | 0.193911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164514E+10 | 0.225622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156266E+10 | 0.209633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161041E+10 | 0.203053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156266E+10 | 0.186156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160173E+10 | 0.174812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190775E+11 | 0.242919E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145848E+10 | 0.167996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164514E+10 | 0.242189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.160232E+10 | 0.173065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145116E+10 | 0.167133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163687E+10 | 0.196558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155481E+10 | 0.211599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161960E+10 | 0.240695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158072E+10 | 0.241185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159368E+10 | 0.192951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.163687E+10 | 0.224606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155481E+10 | 0.208664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160232E+10 | 0.202038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155481E+10 | 0.185143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159368E+10 | 0.173812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189817E+11 | 0.241745E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145116E+10 | 0.167133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163687E+10 | 0.241185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.160224E+10 | 0.172467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145108E+10 | 0.166785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163679E+10 | 0.196229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155473E+10 | 0.211489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161951E+10 | 0.240561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158064E+10 | 0.241182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159360E+10 | 0.192785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.163679E+10 | 0.224347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155473E+10 | 0.208520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160224E+10 | 0.201456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155473E+10 | 0.184603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159360E+10 | 0.173165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189807E+11 | 0.241359E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145108E+10 | 0.166785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163679E+10 | 0.241182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.173255E+10 | 0.183867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156910E+10 | 0.178968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176991E+10 | 0.211564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168118E+10 | 0.228124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.175123E+10 | 0.258417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.170920E+10 | 0.259941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.172321E+10 | 0.207710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176991E+10 | 0.241084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168118E+10 | 0.224027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173255E+10 | 0.213831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168118E+10 | 0.196407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172321E+10 | 0.184255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205244E+11 | 0.258820E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156910E+10 | 0.178968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176991E+10 | 0.259941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.424335E+10 | 0.00 | 0.00 | 0.00 | 0.125528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.383922E+10 | 0.00 | 0.00 | 0.00 | 0.121295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.425177E+10 | 0.00 | 0.00 | 0.00 | 0.141195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.411706E+10 | 0.00 | 0.00 | 0.00 | 0.151327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.424335E+10 | 0.00 | 0.00 | 0.00 | 0.164550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.411706E+10 | 0.00 | 0.00 | 0.00 | 0.161829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.425177E+10 | 0.00 | 0.00 | 0.00 | 0.138157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.424335E+10 | 0.00 | 0.00 | 0.00 | 0.150000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.412548E+10 | 0.00 | 0.00 | 0.00 | 0.143944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.424335E+10 | 0.00 | 0.00 | 0.00 | 0.139039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.410022E+10 | 0.00 | 0.00 | 0.00 | 0.129676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.426019E+10 | 0.00 | 0.00 | 0.00 | 0.126277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.500362E+11 | 0.00 | 0.00 | 0.00 | 0.169282E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.383922E+10 | 0.00 | 0.00 | 0.00 | 0.121295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.426019E+10 | 0.00 | 0.00 | 0.00 | 0.164550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.192420E+10 | 0.00 | 0.00 | 0.00 | 0.613289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174469E+10 | 0.00 | 0.00 | 0.00 | 0.589874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195392E+10 | 0.00 | 0.00 | 0.00 | 0.684959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189911E+10 | 0.00 | 0.00 | 0.00 | 0.729030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198000E+10 | 0.00 | 0.00 | 0.00 | 0.794899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.192239E+10 | 0.00 | 0.00 | 0.00 | 0.782990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.194206E+10 | 0.00 | 0.00 | 0.00 | 0.667822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196870E+10 | 0.00 | 0.00 | 0.00 | 0.726610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189483E+10 | 0.00 | 0.00 | 0.00 | 0.695524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194311E+10 | 0.00 | 0.00 | 0.00 | 0.675701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187632E+10 | 0.00 | 0.00 | 0.00 | 0.630945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192376E+10 | 0.00 | 0.00 | 0.00 | 0.616327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229731E+11 | 0.00 | 0.00 | 0.00 | 0.820797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.174469E+10 | 0.00 | 0.00 | 0.00 | 0.589874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.198000E+10 | 0.00 | 0.00 | 0.00 | 0.794899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.182388E+10 | 0.00 | 0.00 | 0.00 | 0.496818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165147E+10 | 0.00 | 0.00 | 0.00 | 0.481196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186017E+10 | 0.00 | 0.00 | 0.00 | 0.568375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176943E+10 | 0.00 | 0.00 | 0.00 | 0.595313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.184202E+10 | 0.00 | 0.00 | 0.00 | 0.657689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179665E+10 | 0.00 | 0.00 | 0.00 | 0.653507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181480E+10 | 0.00 | 0.00 | 0.00 | 0.537557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.186017E+10 | 0.00 | 0.00 | 0.00 | 0.605161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176943E+10 | 0.00 | 0.00 | 0.00 | 0.568040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182388E+10 | 0.00 | 0.00 | 0.00 | 0.550807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176943E+10 | 0.00 | 0.00 | 0.00 | 0.513999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181480E+10 | 0.00 | 0.00 | 0.00 | 0.496365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215961E+11 | 0.00 | 0.00 | 0.00 | 0.672483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.165147E+10 | 0.00 | 0.00 | 0.00 | 0.481196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.186017E+10 | 0.00 | 0.00 | 0.00 | 0.657689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.182883E+10 | 0.00 | 0.00 | 0.00 | 0.498626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165595E+10 | 0.00 | 0.00 | 0.00 | 0.482957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186522E+10 | 0.00 | 0.00 | 0.00 | 0.570481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177424E+10 | 0.00 | 0.00 | 0.00 | 0.597761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.184703E+10 | 0.00 | 0.00 | 0.00 | 0.660674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.180153E+10 | 0.00 | 0.00 | 0.00 | 0.656230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181973E+10 | 0.00 | 0.00 | 0.00 | 0.540112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.186522E+10 | 0.00 | 0.00 | 0.00 | 0.607163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.177424E+10 | 0.00 | 0.00 | 0.00 | 0.570172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182883E+10 | 0.00 | 0.00 | 0.00 | 0.552861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177424E+10 | 0.00 | 0.00 | 0.00 | 0.515694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181973E+10 | 0.00 | 0.00 | 0.00 | 0.497834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216548E+11 | 0.00 | 0.00 | 0.00 | 0.675057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.165595E+10 | 0.00 | 0.00 | 0.00 | 0.482957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.186522E+10 | 0.00 | 0.00 | 0.00 | 0.660674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.182219E+10 | 0.00 | 0.00 | 0.00 | 0.494564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164995E+10 | 0.00 | 0.00 | 0.00 | 0.479167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185846E+10 | 0.00 | 0.00 | 0.00 | 0.565880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176780E+10 | 0.00 | 0.00 | 0.00 | 0.593386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.184033E+10 | 0.00 | 0.00 | 0.00 | 0.656392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179500E+10 | 0.00 | 0.00 | 0.00 | 0.651903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181313E+10 | 0.00 | 0.00 | 0.00 | 0.535886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.185846E+10 | 0.00 | 0.00 | 0.00 | 0.602394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176780E+10 | 0.00 | 0.00 | 0.00 | 0.565733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182219E+10 | 0.00 | 0.00 | 0.00 | 0.548347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176780E+10 | 0.00 | 0.00 | 0.00 | 0.511330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181313E+10 | 0.00 | 0.00 | 0.00 | 0.493541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215762E+11 | 0.00 | 0.00 | 0.00 | 0.669852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.164995E+10 | 0.00 | 0.00 | 0.00 | 0.479167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.185846E+10 | 0.00 | 0.00 | 0.00 | 0.656392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.295720E+10 | 0.00 | 0.00 | 0.00 | 0.906967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.267822E+10 | 0.00 | 0.00 | 0.00 | 0.879105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.302097E+10 | 0.00 | 0.00 | 0.00 | 0.103946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.286952E+10 | 0.00 | 0.00 | 0.00 | 0.108812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.298909E+10 | 0.00 | 0.00 | 0.00 | 0.120540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.291735E+10 | 0.00 | 0.00 | 0.00 | 0.120224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.294126E+10 | 0.00 | 0.00 | 0.00 | 0.976947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.302097E+10 | 0.00 | 0.00 | 0.00 | 0.110514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.286952E+10 | 0.00 | 0.00 | 0.00 | 0.103328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.295720E+10 | 0.00 | 0.00 | 0.00 | 0.100008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286952E+10 | 0.00 | 0.00 | 0.00 | 0.934486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.294126E+10 | 0.00 | 0.00 | 0.00 | 0.898500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.350321E+11 | 0.00 | 0.00 | 0.00 | 0.122697E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.267822E+10 | 0.00 | 0.00 | 0.00 | 0.879105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.302097E+10 | 0.00 | 0.00 | 0.00 | 0.120540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.161041E+10 | 0.00 | 0.00 | 0.00 | 0.465275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145848E+10 | 0.00 | 0.00 | 0.00 | 0.451038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164514E+10 | 0.00 | 0.00 | 0.00 | 0.532877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156266E+10 | 0.00 | 0.00 | 0.00 | 0.557776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162777E+10 | 0.00 | 0.00 | 0.00 | 0.617715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158871E+10 | 0.00 | 0.00 | 0.00 | 0.615694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160173E+10 | 0.00 | 0.00 | 0.00 | 0.500675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164514E+10 | 0.00 | 0.00 | 0.00 | 0.565815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156266E+10 | 0.00 | 0.00 | 0.00 | 0.529381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161041E+10 | 0.00 | 0.00 | 0.00 | 0.512416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156266E+10 | 0.00 | 0.00 | 0.00 | 0.478718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160173E+10 | 0.00 | 0.00 | 0.00 | 0.460622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190775E+11 | 0.00 | 0.00 | 0.00 | 0.628800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.145848E+10 | 0.00 | 0.00 | 0.00 | 0.451038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164514E+10 | 0.00 | 0.00 | 0.00 | 0.617715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.160232E+10 | 0.00 | 0.00 | 0.00 | 0.462537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145116E+10 | 0.00 | 0.00 | 0.00 | 0.448587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163687E+10 | 0.00 | 0.00 | 0.00 | 0.530085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155481E+10 | 0.00 | 0.00 | 0.00 | 0.554992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161960E+10 | 0.00 | 0.00 | 0.00 | 0.614832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158072E+10 | 0.00 | 0.00 | 0.00 | 0.612763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159368E+10 | 0.00 | 0.00 | 0.00 | 0.498030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.163687E+10 | 0.00 | 0.00 | 0.00 | 0.562976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155481E+10 | 0.00 | 0.00 | 0.00 | 0.526672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160232E+10 | 0.00 | 0.00 | 0.00 | 0.509647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155481E+10 | 0.00 | 0.00 | 0.00 | 0.475944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159368E+10 | 0.00 | 0.00 | 0.00 | 0.457883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189817E+11 | 0.00 | 0.00 | 0.00 | 0.625495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.145116E+10 | 0.00 | 0.00 | 0.00 | 0.448587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163687E+10 | 0.00 | 0.00 | 0.00 | 0.614832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.160224E+10 | 0.00 | 0.00 | 0.00 | 0.461057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145108E+10 | 0.00 | 0.00 | 0.00 | 0.447713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163679E+10 | 0.00 | 0.00 | 0.00 | 0.529243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155473E+10 | 0.00 | 0.00 | 0.00 | 0.554713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161951E+10 | 0.00 | 0.00 | 0.00 | 0.614462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158064E+10 | 0.00 | 0.00 | 0.00 | 0.612691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159360E+10 | 0.00 | 0.00 | 0.00 | 0.497580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.163679E+10 | 0.00 | 0.00 | 0.00 | 0.562326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155473E+10 | 0.00 | 0.00 | 0.00 | 0.526291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160224E+10 | 0.00 | 0.00 | 0.00 | 0.508249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155473E+10 | 0.00 | 0.00 | 0.00 | 0.474645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159360E+10 | 0.00 | 0.00 | 0.00 | 0.456311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189807E+11 | 0.00 | 0.00 | 0.00 | 0.624528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.145108E+10 | 0.00 | 0.00 | 0.00 | 0.447713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163679E+10 | 0.00 | 0.00 | 0.00 | 0.614462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.173255E+10 | 0.00 | 0.00 | 0.00 | 0.493582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156910E+10 | 0.00 | 0.00 | 0.00 | 0.482357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176991E+10 | 0.00 | 0.00 | 0.00 | 0.572421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168118E+10 | 0.00 | 0.00 | 0.00 | 0.600920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.175123E+10 | 0.00 | 0.00 | 0.00 | 0.663781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.170920E+10 | 0.00 | 0.00 | 0.00 | 0.663943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.172321E+10 | 0.00 | 0.00 | 0.00 | 0.538154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176991E+10 | 0.00 | 0.00 | 0.00 | 0.607372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168118E+10 | 0.00 | 0.00 | 0.00 | 0.568350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173255E+10 | 0.00 | 0.00 | 0.00 | 0.542662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168118E+10 | 0.00 | 0.00 | 0.00 | 0.507730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172321E+10 | 0.00 | 0.00 | 0.00 | 0.487830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205244E+11 | 0.00 | 0.00 | 0.00 | 0.672910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.156910E+10 | 0.00 | 0.00 | 0.00 | 0.482357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176991E+10 | 0.00 | 0.00 | 0.00 | 0.663943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8875536.96 | 0.149093E+11 | 0.00 | 97989.29 | 0.190247E+09 | 0.00 | 2061820.04 | 0.00 | 0.57 |
February | 4242109.53 | 0.149757E+11 | 0.00 | 7090.58 | 0.213684E+09 | 0.00 | 1079245.90 | 0.00 | 0.57 |
March | 0.00 | 0.177474E+11 | 0.00 | 0.00 | 0.176347E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
April | 0.00 | 0.219836E+11 | 0.00 | 0.00 | 0.126579E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
May | 0.00 | 0.256929E+11 | 0.00 | 0.00 | 0.193901E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.254077E+11 | 0.00 | 0.00 | 0.137496E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.189095E+11 | 0.00 | 0.00 | 0.375750E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.232037E+11 | 0.00 | 0.00 | 0.271151E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.219070E+11 | 0.00 | 0.00 | 0.288232E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 0.00 | 0.205214E+11 | 0.00 | 0.00 | 0.371482E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
November | 0.00 | 0.180392E+11 | 0.00 | 0.00 | 0.174142E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
December | 6280075.58 | 0.158419E+11 | 0.00 | 279727.40 | 0.209986E+09 | 0.00 | 829471.77 | 0.00 | 0.58 |
Annual Sum or Average | 19397722.07 | 0.239139E+12 | 0.00 | 384807.26 | 0.272900E+10 | 0.00 | 3970537.70 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.149093E+11 | 0.00 | 0.00 | 0.126579E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 8875536.96 | 0.256929E+11 | 0.00 | 279727.40 | 0.375750E+09 | 0.00 | 2061820.04 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 485729.82 | 0.639247E+10 | 0.00 | 30469.86 | 0.180717E+09 | 0.00 | 62503.04 | 0.00 | 0.47 |
February | 0.00 | 0.642523E+10 | 0.00 | 0.00 | 0.184780E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
March | 0.00 | 0.764102E+10 | 0.00 | 0.00 | 0.177911E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
April | 0.00 | 0.942928E+10 | 0.00 | 0.00 | 0.120771E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
May | 0.00 | 0.111513E+11 | 0.00 | 0.00 | 0.153390E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.111642E+11 | 0.00 | 0.00 | 96389022.96 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.802956E+10 | 0.00 | 0.00 | 0.308709E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.100952E+11 | 0.00 | 0.00 | 0.254780E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.941482E+10 | 0.00 | 0.00 | 0.255324E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.879852E+10 | 0.00 | 0.00 | 0.341603E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
November | 0.00 | 0.780620E+10 | 0.00 | 0.00 | 0.147157E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
December | 827894.31 | 0.679580E+10 | 0.00 | 109507.11 | 0.193942E+09 | 0.00 | 10929.34 | 0.00 | 0.47 |
Annual Sum or Average | 1313624.13 | 0.103144E+12 | 0.00 | 139976.97 | 0.241547E+10 | 0.00 | 73432.38 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.639247E+10 | 0.00 | 0.00 | 96389022.96 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 827894.31 | 0.111642E+11 | 0.00 | 109507.11 | 0.341603E+09 | 0.00 | 62503.04 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 36628339.41 | 0.532491E+10 | 0.00 | 840862.25 | 0.382191E+09 | 0.00 | 2937905.94 | 0.00 | 0.46 |
February | 19398816.16 | 0.536617E+10 | 0.00 | 412286.21 | 0.383540E+09 | 0.00 | 1429092.62 | 0.00 | 0.46 |
March | 1123624.73 | 0.656122E+10 | 0.00 | 28937.90 | 0.463401E+09 | 0.00 | 768337.18 | 0.00 | 0.47 |
April | 0.00 | 0.780791E+10 | 0.00 | 0.00 | 0.553806E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 6741.48 | 0.931656E+10 | 0.00 | 48.28 | 0.640954E+09 | 0.00 | 3308.00 | 0.00 | 0.47 |
June | 132405.47 | 0.942731E+10 | 0.00 | 0.00 | 0.610172E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.667121E+10 | 0.00 | 0.00 | 0.510687E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 165754.24 | 0.865147E+10 | 0.00 | 36.23 | 0.587949E+09 | 0.00 | 104702.50 | 0.00 | 0.47 |
September | 1766225.98 | 0.785301E+10 | 0.00 | 61976.24 | 0.584009E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 2086792.33 | 0.739876E+10 | 0.00 | 21815.00 | 0.559908E+09 | 0.00 | 636315.34 | 0.00 | 0.46 |
November | 9924406.33 | 0.644738E+10 | 0.00 | 328581.59 | 0.457479E+09 | 0.00 | 4434989.16 | 0.00 | 0.46 |
December | 15695893.27 | 0.557330E+10 | 0.00 | 516046.52 | 0.391783E+09 | 0.00 | 3818043.93 | 0.00 | 0.46 |
Annual Sum or Average | 86928999.40 | 0.863992E+11 | 0.00 | 2210590.23 | 0.612588E+10 | 0.00 | 14132694.67 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.532491E+10 | 0.00 | 0.00 | 0.382191E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 36628339.41 | 0.942731E+10 | 0.00 | 840862.25 | 0.640954E+09 | 0.00 | 4434989.16 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 35913437.11 | 0.534491E+10 | 0.00 | 851032.03 | 0.373346E+09 | 0.00 | 3838242.11 | 0.00 | 0.46 |
February | 19482326.88 | 0.538430E+10 | 0.00 | 410318.30 | 0.375395E+09 | 0.00 | 1434567.52 | 0.00 | 0.46 |
March | 1142090.58 | 0.658210E+10 | 0.00 | 27432.62 | 0.455846E+09 | 0.00 | 750130.97 | 0.00 | 0.47 |
April | 0.00 | 0.783296E+10 | 0.00 | 0.00 | 0.545522E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 14532.45 | 0.936079E+10 | 0.00 | 0.00 | 0.620672E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.946127E+10 | 0.00 | 16.08 | 0.597469E+09 | 0.00 | 146911.66 | 0.00 | 0.47 |
July | 0.00 | 0.671487E+10 | 0.00 | 0.00 | 0.485857E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 178876.44 | 0.867888E+10 | 0.00 | 48.49 | 0.575760E+09 | 0.00 | 89276.47 | 0.00 | 0.47 |
September | 832504.73 | 0.788806E+10 | 0.00 | 61279.08 | 0.565437E+09 | 0.00 | 967280.17 | 0.00 | 0.46 |
October | 1332409.79 | 0.742761E+10 | 0.00 | 14364.62 | 0.547448E+09 | 0.00 | 1289255.04 | 0.00 | 0.46 |
November | 7668558.00 | 0.646421E+10 | 0.00 | 331535.32 | 0.451580E+09 | 0.00 | 6607058.45 | 0.00 | 0.46 |
December | 15018268.41 | 0.559112E+10 | 0.00 | 513665.66 | 0.382976E+09 | 0.00 | 4526402.79 | 0.00 | 0.46 |
Annual Sum or Average | 81583004.39 | 0.867311E+11 | 0.00 | 2209692.21 | 0.597731E+10 | 0.00 | 19649125.19 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.534491E+10 | 0.00 | 0.00 | 0.373346E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 35913437.11 | 0.946127E+10 | 0.00 | 851032.03 | 0.620672E+09 | 0.00 | 6607058.45 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 36516854.26 | 0.530595E+10 | 0.00 | 830011.99 | 0.389183E+09 | 0.00 | 2997244.24 | 0.00 | 0.46 |
February | 19278541.54 | 0.534722E+10 | 0.00 | 401313.18 | 0.390667E+09 | 0.00 | 1395282.06 | 0.00 | 0.46 |
March | 1131756.58 | 0.652844E+10 | 0.00 | 33313.41 | 0.481462E+09 | 0.00 | 758363.67 | 0.00 | 0.47 |
April | 0.00 | 0.777208E+10 | 0.00 | 0.00 | 0.575828E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 1753.93 | 0.929087E+10 | 0.00 | 44.58 | 0.657169E+09 | 0.00 | 15516.19 | 0.00 | 0.47 |
June | 138413.45 | 0.939130E+10 | 0.00 | 0.00 | 0.634447E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.664524E+10 | 0.00 | 0.00 | 0.525216E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 165741.82 | 0.860300E+10 | 0.00 | 47.96 | 0.611913E+09 | 0.00 | 105676.99 | 0.00 | 0.47 |
September | 1809785.32 | 0.782685E+10 | 0.00 | 64901.70 | 0.590835E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 2067140.09 | 0.737026E+10 | 0.00 | 21781.54 | 0.568423E+09 | 0.00 | 662785.05 | 0.00 | 0.46 |
November | 10582411.88 | 0.641425E+10 | 0.00 | 327931.41 | 0.470270E+09 | 0.00 | 3785957.07 | 0.00 | 0.46 |
December | 14761282.67 | 0.555034E+10 | 0.00 | 514689.40 | 0.397042E+09 | 0.00 | 4529610.36 | 0.00 | 0.46 |
Annual Sum or Average | 86453681.54 | 0.860458E+11 | 0.00 | 2194035.18 | 0.629245E+10 | 0.00 | 14250435.63 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.530595E+10 | 0.00 | 0.00 | 0.389183E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 36516854.26 | 0.939130E+10 | 0.00 | 830011.99 | 0.657169E+09 | 0.00 | 4529610.36 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 43944419.56 | 0.103612E+11 | 0.00 | 876875.40 | 0.345774E+09 | 0.00 | 6357033.02 | 0.00 | 0.42 |
February | 8579076.55 | 0.104224E+11 | 0.00 | 40867.51 | 0.398147E+09 | 0.00 | 332093.14 | 0.00 | 0.42 |
March | 0.00 | 0.126381E+11 | 0.00 | 0.00 | 0.426121E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.150741E+11 | 0.00 | 0.00 | 0.470378E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.179360E+11 | 0.00 | 0.00 | 0.538491E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.183045E+11 | 0.00 | 0.00 | 0.446277E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.127496E+11 | 0.00 | 0.00 | 0.610623E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.165838E+11 | 0.00 | 0.00 | 0.630685E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 3779626.69 | 0.150884E+11 | 0.00 | 65356.19 | 0.619624E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 566425.18 | 0.141680E+11 | 0.00 | 62.72 | 0.626999E+09 | 0.00 | 131330.31 | 0.00 | 0.43 |
November | 6292555.26 | 0.125018E+11 | 0.00 | 296088.63 | 0.362265E+09 | 0.00 | 8134601.92 | 0.00 | 0.43 |
December | 6375800.78 | 0.107059E+11 | 0.00 | 451635.17 | 0.419784E+09 | 0.00 | 8707862.63 | 0.00 | 0.42 |
Annual Sum or Average | 69537904.02 | 0.166534E+12 | 0.00 | 1730885.62 | 0.589517E+10 | 0.00 | 23662921.02 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.103612E+11 | 0.00 | 0.00 | 0.345774E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 43944419.56 | 0.183045E+11 | 0.00 | 876875.40 | 0.630685E+09 | 0.00 | 8707862.63 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22733525.53 | 0.515390E+10 | 0.00 | 441332.86 | 0.190597E+09 | 0.00 | 2687909.22 | 0.00 | 0.42 |
February | 4087605.25 | 0.519315E+10 | 0.00 | 18217.52 | 0.208085E+09 | 0.00 | 238637.20 | 0.00 | 0.42 |
March | 0.00 | 0.628633E+10 | 0.00 | 0.00 | 0.235939E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.747911E+10 | 0.00 | 0.00 | 0.274319E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.891665E+10 | 0.00 | 0.00 | 0.294164E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.908705E+10 | 0.00 | 0.00 | 0.257259E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.633477E+10 | 0.00 | 0.00 | 0.324945E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.822053E+10 | 0.00 | 0.00 | 0.355781E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 2163447.03 | 0.747664E+10 | 0.00 | 39758.16 | 0.348778E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 361557.66 | 0.703981E+10 | 0.00 | 224.64 | 0.330454E+09 | 0.00 | 81727.89 | 0.00 | 0.43 |
November | 3545081.39 | 0.619640E+10 | 0.00 | 156322.66 | 0.213578E+09 | 0.00 | 4079110.67 | 0.00 | 0.43 |
December | 3938060.16 | 0.531501E+10 | 0.00 | 226053.82 | 0.232778E+09 | 0.00 | 3802379.71 | 0.00 | 0.42 |
Annual Sum or Average | 36829277.02 | 0.826994E+11 | 0.00 | 881909.67 | 0.326668E+10 | 0.00 | 10889764.68 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.515390E+10 | 0.00 | 0.00 | 0.190597E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 22733525.53 | 0.908705E+10 | 0.00 | 441332.86 | 0.355781E+09 | 0.00 | 4079110.67 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22335072.81 | 0.513517E+10 | 0.00 | 434737.81 | 0.195527E+09 | 0.00 | 2987806.38 | 0.00 | 0.42 |
February | 4138489.60 | 0.517432E+10 | 0.00 | 18175.84 | 0.214406E+09 | 0.00 | 206904.85 | 0.00 | 0.42 |
March | 0.00 | 0.626671E+10 | 0.00 | 0.00 | 0.241187E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.744553E+10 | 0.00 | 0.00 | 0.291586E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.889650E+10 | 0.00 | 0.00 | 0.296086E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.905840E+10 | 0.00 | 0.00 | 0.267790E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.631715E+10 | 0.00 | 0.00 | 0.326477E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.819249E+10 | 0.00 | 0.00 | 0.364390E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 2173029.05 | 0.745091E+10 | 0.00 | 43638.27 | 0.356633E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 386574.84 | 0.701634E+10 | 0.00 | 215.00 | 0.334650E+09 | 0.00 | 85228.65 | 0.00 | 0.43 |
November | 3507795.02 | 0.616613E+10 | 0.00 | 160060.81 | 0.225937E+09 | 0.00 | 4141799.84 | 0.00 | 0.43 |
December | 4037450.69 | 0.529138E+10 | 0.00 | 227057.96 | 0.240845E+09 | 0.00 | 3739870.12 | 0.00 | 0.42 |
Annual Sum or Average | 36578412.02 | 0.824111E+11 | 0.00 | 883885.69 | 0.335551E+10 | 0.00 | 11161609.85 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.513517E+10 | 0.00 | 0.00 | 0.195527E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 22335072.81 | 0.905840E+10 | 0.00 | 434737.81 | 0.364390E+09 | 0.00 | 4141799.84 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22775722.66 | 0.511730E+10 | 0.00 | 438918.09 | 0.204025E+09 | 0.00 | 2297196.70 | 0.00 | 0.42 |
February | 4002866.52 | 0.516313E+10 | 0.00 | 16035.72 | 0.220137E+09 | 0.00 | 242461.88 | 0.00 | 0.42 |
March | 0.00 | 0.625672E+10 | 0.00 | 0.00 | 0.245459E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.743218E+10 | 0.00 | 0.00 | 0.301927E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.887794E+10 | 0.00 | 0.00 | 0.309855E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.904115E+10 | 0.00 | 0.00 | 0.282851E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.630910E+10 | 0.00 | 0.00 | 0.330550E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.817507E+10 | 0.00 | 0.00 | 0.375469E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 2159839.28 | 0.743906E+10 | 0.00 | 49099.26 | 0.363909E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 472113.05 | 0.699265E+10 | 0.00 | 29.48 | 0.346214E+09 | 0.00 | 33482.57 | 0.00 | 0.43 |
November | 4361218.66 | 0.614248E+10 | 0.00 | 159895.36 | 0.238624E+09 | 0.00 | 3238123.33 | 0.00 | 0.43 |
December | 4179356.39 | 0.527263E+10 | 0.00 | 228983.47 | 0.248800E+09 | 0.00 | 3605087.80 | 0.00 | 0.42 |
Annual Sum or Average | 37951116.56 | 0.822194E+11 | 0.00 | 892961.39 | 0.346782E+10 | 0.00 | 9416352.28 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.511730E+10 | 0.00 | 0.00 | 0.204025E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 22775722.66 | 0.904115E+10 | 0.00 | 438918.09 | 0.375469E+09 | 0.00 | 3605087.80 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 31420578.52 | 0.519812E+10 | 0.00 | 555282.76 | 0.139563E+09 | 0.00 | 3662141.00 | 0.00 | 0.42 |
February | 12050293.92 | 0.525896E+10 | 0.00 | 173227.02 | 0.161169E+09 | 0.00 | 485480.04 | 0.00 | 0.42 |
March | 779726.50 | 0.634682E+10 | 0.00 | 3588.11 | 0.149715E+09 | 0.00 | 89612.51 | 0.00 | 0.43 |
April | 0.00 | 0.755569E+10 | 0.00 | 0.00 | 0.200218E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 988982.47 | 0.896678E+10 | 0.00 | 70002.60 | 0.237884E+09 | 0.00 | 20494.31 | 0.00 | 0.43 |
June | 0.00 | 0.916364E+10 | 0.00 | 0.00 | 0.202844E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 290974.57 | 0.643357E+10 | 0.00 | 252.85 | 0.263800E+09 | 0.00 | 22567.95 | 0.00 | 0.42 |
August | 0.00 | 0.832779E+10 | 0.00 | 0.00 | 0.247202E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 2772413.53 | 0.759816E+10 | 0.00 | 54928.75 | 0.257794E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 954363.14 | 0.709018E+10 | 0.00 | 0.00 | 0.258133E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 5415477.28 | 0.625531E+10 | 0.00 | 188066.42 | 0.159424E+09 | 0.00 | 3597521.40 | 0.00 | 0.43 |
December | 9794462.93 | 0.536235E+10 | 0.00 | 266616.22 | 0.187208E+09 | 0.00 | 4525369.06 | 0.00 | 0.42 |
Annual Sum or Average | 64467272.87 | 0.835574E+11 | 0.00 | 1311964.74 | 0.246495E+10 | 0.00 | 12403186.26 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.519812E+10 | 0.00 | 0.00 | 0.139563E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 31420578.52 | 0.916364E+10 | 0.00 | 555282.76 | 0.263800E+09 | 0.00 | 4525369.06 | 0.00 | 0.43 |