Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:19
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2020-06-03 19:19:16
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1962.09 | 938.66 | 938.66 |
Net Site Energy | 1962.09 | 938.66 | 938.66 |
Total Source Energy | 3922.28 | 1876.40 | 1876.40 |
Net Source Energy | 3922.28 | 1876.40 | 1876.40 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1100.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 48.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 433.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 64.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 122.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 63.58 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 861.91 | 1100.18 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1100.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 48.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 433.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 64.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 122.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 63.58 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 238.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 112.28 | 526.32 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 412.34 | 526.32 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 238.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 112.28 | 526.32 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 412.34 | 526.32 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 861.914 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 861.914 | 100.00 |
Total On-Site and Utility Electric Sources | 861.914 | 100.00 |
Total Electricity End Uses | 861.914 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3210.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 15.7897 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 18.6637 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.0491 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.0491 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.0491 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 10.0956 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 10.0956 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 10.0956 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 10.0956 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 10.0956 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 13.4970 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 13.4970 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-15:00 | 06-JAN-09:09 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 351868.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 43534.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 26802.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8691.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 91837.13 | 351868.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 351868.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 43534.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 26802.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8691.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 4719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1192.60 | 0.00 | 0.00 | 0.00 |
Cooling | 154.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1374.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 204.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 387.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 201.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2729.68 | 1192.60 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 570.53 | 0.00 | 0.00 | 0.00 |
Cooling | 74.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 657.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 97.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 185.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 96.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1305.87 | 570.53 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 570.53 | 0.00 | 0.00 | 0.00 |
Cooling | 74.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 657.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 97.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 185.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 96.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1305.87 | 570.53 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.79 |
SMSTORE1 DIRECT AIR | 0.897453 |
SMSTORE2 DIRECT AIR | 1.03 |
SMSTORE3 DIRECT AIR | 1.02 |
SMSTORE4 DIRECT AIR | 1.02 |
LGSTORE2 DIRECT AIR | 1.73 |
SMSTORE5 DIRECT AIR | 0.935582 |
SMSTORE6 DIRECT AIR | 0.934763 |
SMSTORE7 DIRECT AIR | 0.945005 |
SMSTORE8 DIRECT AIR | 1.08 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.79 | 1.79 | 1.79 | 1.79 | 1.79 | 1.79 | 1.00 | 1.00 | 1.79 |
PSZ-AC_2:2 | 0.897453 | 0.897453 | 0.897453 | 0.897453 | 0.897453 | 0.897453 | 1.00 | 1.00 | 0.897453 |
PSZ-AC_3:3 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 1.00 | 1.03 |
PSZ-AC_4:4 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.00 | 1.00 | 1.02 |
PSZ-AC_5:5 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.00 | 1.00 | 1.02 |
PSZ-AC_6:6 | 1.73 | 1.73 | 1.73 | 1.73 | 1.73 | 1.73 | 1.00 | 1.00 | 1.73 |
PSZ-AC_7:7 | 0.935582 | 0.935582 | 0.935582 | 0.935582 | 0.935582 | 0.935582 | 1.00 | 1.00 | 0.935582 |
PSZ-AC_8:8 | 0.934763 | 0.934763 | 0.934763 | 0.934763 | 0.934763 | 0.934763 | 1.00 | 1.00 | 0.934763 |
PSZ-AC_9:9 | 0.945005 | 0.945005 | 0.945005 | 0.945005 | 0.945005 | 0.945005 | 1.00 | 1.00 | 0.945005 |
PSZ-AC_10:10 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.00 | 1.08 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.79 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 0.897453 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 1.03 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 1.02 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 1.02 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 1.73 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 0.935582 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 0.934763 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 0.945005 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 1.08 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.79 | 1.79 | 1.79 | 1.18 | 37393.10 | 64994.54 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 0.897453 | 0.897453 | 0.897453 | 0.897453 | 18281.66 | 32497.30 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 1.03 | 18492.24 | 35342.33 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 0.675366 | 20780.04 | 35254.06 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 0.671671 | 20724.41 | 35131.41 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.73 | 1.73 | 1.73 | 1.14 | 36475.79 | 63622.25 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.935582 | 0.935582 | 0.935582 | 0.617484 | 19679.11 | 33332.63 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.934763 | 0.934763 | 0.934763 | 0.616943 | 19714.88 | 33314.67 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.945005 | 0.945005 | 0.945005 | 0.623703 | 19982.06 | 33539.07 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 0.710021 | 22596.62 | 36404.55 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 1.79 | 0.897465 | 1.20 | 35159.06 | 37393.10 | 18696.55 | 18696.55 | 0.723138 | 0.723140 | 0.723140 | 0.723140 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 0.897450 | 0.448725 | 0.598300 | 17157.87 | 18281.66 | 9140.83 | 9140.83 | 0.729763 | 0.729760 | 0.729760 | 0.729760 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.03 | 0.513655 | 0.684873 | 17188.46 | 18492.24 | 9246.12 | 9246.12 | 0.769099 | 0.769100 | 0.769100 | 0.769100 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.02 | 0.511640 | 0.682187 | 19497.67 | 20780.04 | 10390.02 | 10390.02 | 0.730695 | 0.730700 | 0.730700 | 0.730700 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.02 | 0.508840 | 0.678453 | 19449.95 | 20724.41 | 10362.20 | 10362.20 | 0.729855 | 0.729860 | 0.729860 | 0.729860 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 1.73 | 0.866150 | 1.15 | 34325.86 | 36475.79 | 18237.90 | 18237.90 | 0.720035 | 0.720030 | 0.720030 | 0.720030 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 0.935580 | 0.467790 | 0.623720 | 18517.54 | 19679.11 | 9839.56 | 9839.56 | 0.720339 | 0.720340 | 0.720340 | 0.720340 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 0.934760 | 0.467380 | 0.623173 | 18555.15 | 19714.88 | 9857.44 | 9857.44 | 0.719561 | 0.719560 | 0.719560 | 0.719560 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 0.945010 | 0.472505 | 0.630007 | 18810.58 | 19982.06 | 9991.03 | 9991.03 | 0.718825 | 0.718820 | 0.718820 | 0.718820 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.08 | 0.537895 | 0.717193 | 21261.55 | 22596.62 | 11298.31 | 11298.31 | 0.720745 | 0.720740 | 0.720740 | 0.720740 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.79 | 1920.65 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 0.897453 | 993.62 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1137.40 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1132.94 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1126.74 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.73 | 1853.64 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.935582 | 1035.84 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.934763 | 1034.93 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.945005 | 1046.27 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.08 | 1191.07 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 64994.54 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 32497.30 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 35342.33 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 35254.06 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 35131.41 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 63622.25 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 33332.63 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 33314.67 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 33539.07 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 36404.55 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 15.790 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.090 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.664 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.964 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.049 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.349 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.049 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.349 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.049 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.349 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 10.096 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.396 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 10.096 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.396 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 10.096 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.396 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 10.096 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.396 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 10.096 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.396 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 3517.173 | 10.096 | 117.254 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3517.173 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 1983.751 | 5.694 | 66.134 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1983.751 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1492.501 | 8.568 | 99.513 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.501 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 1211.251 | 6.953 | 80.761 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.251 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 1211.251 | 6.953 | 80.761 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.251 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 1211.251 | 6.953 | 80.761 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.251 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 3517.173 | 10.096 | 117.254 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3517.173 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1078 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.6115E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.6115E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.6115E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.6115E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.6115E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.6115E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.6115E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.6115E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1551 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 9.201 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.28 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.28 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.28 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.28 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.28 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.28 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.28 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.28 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.371 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009596 | 2.1009596 | 2.1009596 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
19 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
20 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
21 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
22 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
23 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
24 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
25 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
26 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
27 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
28 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
29 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
30 | 7 | -0.39532248E-08 | -0.44064807E-14 | 0.10109291E-14 | -0.41601153E-16 |
31 | 6 | 0.32173895E-05 | 0.20629171E-08 | 0.31970178E-02 | -0.26819265E-04 |
32 | 5 | -0.22044530E-03 | 0.12181552E-05 | -0.22413079 | 0.19597358E-02 |
33 | 4 | 0.49988388E-02 | 0.55368910E-04 | 4.8363104 | -0.45330008E-01 |
34 | 3 | -0.43669331E-01 | 0.43971237E-03 | -38.059625 | 0.39907609 |
35 | 2 | 0.15474085 | 0.73065327E-03 | 116.55831 | -1.4189339 |
36 | 1 | -0.22313860 | 0.22222429E-03 | -143.95108 | 2.0497593 |
37 | 0 | 0.10874004 | 0.53957455E-05 | 60.838472 | |
38 | 7 | -0.70007713E-08 | -0.80410658E-14 | -0.90308164E-15 | 0.82137675E-17 |
39 | 6 | 0.21712725E-05 | 0.11838265E-08 | 0.32006334E-02 | -0.26849596E-04 |
40 | 5 | -0.13301509E-03 | 0.69458749E-06 | -0.22433613 | 0.19615483E-02 |
41 | 4 | 0.29052452E-02 | 0.31467785E-04 | 4.8397276 | -0.45362860E-01 |
42 | 3 | -0.25016136E-01 | 0.24921377E-03 | -38.078914 | 0.39928933 |
43 | 2 | 0.88121217E-01 | 0.41303221E-03 | 116.59583 | -1.4194359 |
44 | 1 | -0.12672960 | 0.12519520E-03 | -143.97316 | 2.0501223 |
45 | 0 | 0.61672764E-01 | 0.30323733E-05 | 60.838472 | |
46 | 7 | -0.70007713E-08 | -0.80410659E-14 | -0.90308145E-15 | 0.82137644E-17 |
47 | 6 | 0.21712725E-05 | 0.11838265E-08 | 0.32006334E-02 | -0.26849596E-04 |
48 | 5 | -0.13301509E-03 | 0.69458749E-06 | -0.22433613 | 0.19615483E-02 |
49 | 4 | 0.29052452E-02 | 0.31467785E-04 | 4.8397276 | -0.45362860E-01 |
50 | 3 | -0.25016136E-01 | 0.24921377E-03 | -38.078914 | 0.39928933 |
51 | 2 | 0.88121217E-01 | 0.41303221E-03 | 116.59583 | -1.4194359 |
52 | 1 | -0.12672960 | 0.12519520E-03 | -143.97316 | 2.0501223 |
53 | 0 | 0.61672764E-01 | 0.30323733E-05 | 60.838472 | |
54 | 7 | -0.70007713E-08 | -0.80410658E-14 | -0.90308157E-15 | 0.82137664E-17 |
55 | 6 | 0.21712725E-05 | 0.11838265E-08 | 0.32006334E-02 | -0.26849596E-04 |
56 | 5 | -0.13301509E-03 | 0.69458749E-06 | -0.22433613 | 0.19615483E-02 |
57 | 4 | 0.29052452E-02 | 0.31467785E-04 | 4.8397276 | -0.45362860E-01 |
58 | 3 | -0.25016136E-01 | 0.24921377E-03 | -38.078914 | 0.39928933 |
59 | 2 | 0.88121217E-01 | 0.41303221E-03 | 116.59583 | -1.4194359 |
60 | 1 | -0.12672960 | 0.12519520E-03 | -143.97316 | 2.0501223 |
61 | 0 | 0.61672764E-01 | 0.30323733E-05 | 60.838472 | |
62 | 7 | -0.70007713E-08 | -0.80410657E-14 | -0.90308142E-15 | 0.82137640E-17 |
63 | 6 | 0.21712725E-05 | 0.11838265E-08 | 0.32006334E-02 | -0.26849596E-04 |
64 | 5 | -0.13301509E-03 | 0.69458749E-06 | -0.22433613 | 0.19615483E-02 |
65 | 4 | 0.29052452E-02 | 0.31467785E-04 | 4.8397276 | -0.45362860E-01 |
66 | 3 | -0.25016136E-01 | 0.24921377E-03 | -38.078914 | 0.39928933 |
67 | 2 | 0.88121217E-01 | 0.41303221E-03 | 116.59583 | -1.4194359 |
68 | 1 | -0.12672960 | 0.12519520E-03 | -143.97316 | 2.0501223 |
69 | 0 | 0.61672764E-01 | 0.30323733E-05 | 60.838472 | |
70 | 7 | -0.70007713E-08 | -0.80410659E-14 | -0.90308145E-15 | 0.82137644E-17 |
71 | 6 | 0.21712725E-05 | 0.11838265E-08 | 0.32006334E-02 | -0.26849596E-04 |
72 | 5 | -0.13301509E-03 | 0.69458749E-06 | -0.22433613 | 0.19615483E-02 |
73 | 4 | 0.29052452E-02 | 0.31467785E-04 | 4.8397276 | -0.45362860E-01 |
74 | 3 | -0.25016136E-01 | 0.24921377E-03 | -38.078914 | 0.39928933 |
75 | 2 | 0.88121217E-01 | 0.41303221E-03 | 116.59583 | -1.4194359 |
76 | 1 | -0.12672960 | 0.12519520E-03 | -143.97316 | 2.0501223 |
77 | 0 | 0.61672764E-01 | 0.30323733E-05 | 60.838472 | |
78 | 7 | -0.70007713E-08 | -0.80410659E-14 | -0.90308158E-15 | 0.82137665E-17 |
79 | 6 | 0.21712725E-05 | 0.11838265E-08 | 0.32006334E-02 | -0.26849596E-04 |
80 | 5 | -0.13301509E-03 | 0.69458749E-06 | -0.22433613 | 0.19615483E-02 |
81 | 4 | 0.29052452E-02 | 0.31467785E-04 | 4.8397276 | -0.45362860E-01 |
82 | 3 | -0.25016136E-01 | 0.24921377E-03 | -38.078914 | 0.39928933 |
83 | 2 | 0.88121217E-01 | 0.41303221E-03 | 116.59583 | -1.4194359 |
84 | 1 | -0.12672960 | 0.12519520E-03 | -143.97316 | 2.0501223 |
85 | 0 | 0.61672764E-01 | 0.30323733E-05 | 60.838472 | |
86 | 7 | -0.70007713E-08 | -0.80410658E-14 | -0.90308164E-15 | 0.82137675E-17 |
87 | 6 | 0.21712725E-05 | 0.11838265E-08 | 0.32006334E-02 | -0.26849596E-04 |
88 | 5 | -0.13301509E-03 | 0.69458749E-06 | -0.22433613 | 0.19615483E-02 |
89 | 4 | 0.29052452E-02 | 0.31467785E-04 | 4.8397276 | -0.45362860E-01 |
90 | 3 | -0.25016136E-01 | 0.24921377E-03 | -38.078914 | 0.39928933 |
91 | 2 | 0.88121217E-01 | 0.41303221E-03 | 116.59583 | -1.4194359 |
92 | 1 | -0.12672960 | 0.12519520E-03 | -143.97316 | 2.0501223 |
93 | 0 | 0.61672764E-01 | 0.30323733E-05 | 60.838472 | |
94 | 7 | -0.70007713E-08 | -0.80410659E-14 | -0.90308145E-15 | 0.82137644E-17 |
95 | 6 | 0.21712725E-05 | 0.11838265E-08 | 0.32006334E-02 | -0.26849596E-04 |
96 | 5 | -0.13301509E-03 | 0.69458749E-06 | -0.22433613 | 0.19615483E-02 |
97 | 4 | 0.29052452E-02 | 0.31467785E-04 | 4.8397276 | -0.45362860E-01 |
98 | 3 | -0.25016136E-01 | 0.24921377E-03 | -38.078914 | 0.39928933 |
99 | 2 | 0.88121217E-01 | 0.41303221E-03 | 116.59583 | -1.4194359 |
100 | 1 | -0.12672960 | 0.12519520E-03 | -143.97316 | 2.0501223 |
101 | 0 | 0.61672764E-01 | 0.30323733E-05 | 60.838472 | |
102 | 7 | -0.27342154E-08 | -0.14755226E-14 | 0.78892317E-14 | -0.11406260E-15 |
103 | 6 | 0.44275096E-05 | 0.29655051E-08 | 0.31933384E-02 | -0.26788399E-04 |
104 | 5 | -0.31313574E-03 | 0.17544743E-05 | -0.22392171 | 0.19578903E-02 |
105 | 4 | 0.71689416E-02 | 0.79816958E-04 | 4.8328290 | -0.45296542E-01 |
106 | 3 | -0.62848542E-01 | 0.63438109E-03 | -38.039963 | 0.39885876 |
107 | 2 | 0.22301735 | 0.10548637E-02 | 116.52005 | -1.4184221 |
108 | 1 | -0.32179990 | 0.32117902E-03 | -143.92856 | 2.0493892 |
109 | 0 | 0.15687064 | 0.77839935E-05 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 29 | 1 | VerySmooth | 1.647 | 0.445 | 0.367 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 4.26414E-002 | 0.36619 | 0.44111 | 0.44111 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.159 | 4.569E-004 | 2.517E-004 | 0.317 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 4.561E-002 | 2.619E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 9.122E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.113 | 6.514E-004 | 3.022E-004 | 0.453 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 17389.78120 | 20867.73744 | 1.33177 | 1.59813 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.10000 | 1.27032E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 33254.55523 | 39905.46628 | 1.49577 | 1.79493 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 10043.69368 | 12052.43242 | 0.74441 | 0.89329 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27032E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 16627.36219 | 19952.83462 | 0.74788 | 0.89745 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 11492.30157 | 13790.76188 | 0.85609 | 1.02731 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.28000 | 1.27032E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 16786.60160 | 20143.92192 | 0.75504 | 0.90605 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 11448.94320 | 13738.73184 | 0.85273 | 1.02328 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.28000 | 1.27032E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 16855.84933 | 20227.01920 | 0.75815 | 0.90979 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 11387.42208 | 13664.90649 | 0.84807 | 1.01768 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.28000 | 1.27032E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 16976.37350 | 20371.64819 | 0.76358 | 0.91629 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 16623.46252 | 19948.15503 | 1.22480 | 1.46976 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27032E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 32094.02919 | 38512.83503 | 1.44358 | 1.73230 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 8872.56385 | 10647.07662 | 0.65506 | 0.78607 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27032E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 17333.74734 | 20800.49680 | 0.77965 | 0.93558 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 8750.14837 | 10500.17804 | 0.64577 | 0.77492 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27032E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 17318.56363 | 20782.27636 | 0.77897 | 0.93476 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 8580.70359 | 10296.84431 | 0.63291 | 0.75949 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27032E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 17508.32099 | 21009.98519 | 0.78750 | 0.94501 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 8616.38884 | 10339.66661 | 0.63569 | 0.76282 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27032E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 19931.55434 | 23917.86521 | 0.89649 | 1.07579 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 23509.24 | 1.59813 | 1.59813 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 64994.54 | 1.79493 | 1.79493 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 12980.19 | 0.89565 | 0.89565 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 32497.30 | 0.89745 | 0.89745 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 13091.01 | 1.02731 | 1.02731 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 32685.60 | 0.90605 | 0.90605 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 13139.50 | 1.02328 | 1.02328 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 32767.49 | 0.90979 | 0.90979 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 12995.76 | 1.01768 | 1.01768 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 32910.02 | 0.91629 | 0.91629 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 22536.89 | 1.52595 | 1.52595 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 63622.25 | 1.73230 | 1.73230 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 11502.32 | 0.79029 | 0.79029 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 33332.63 | 0.93558 | 0.93558 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 11390.37 | 0.78053 | 0.78053 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 33314.67 | 0.93476 | 0.93476 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 11285.35 | 0.76767 | 0.76767 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 33539.07 | 0.94501 | 0.94501 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 11418.81 | 0.78068 | 0.78068 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 36404.55 | 1.07579 | 1.07579 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.79493 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.89745 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02731 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02328 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01768 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.73230 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.93558 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.93476 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94501 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07579 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.79493 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.79493 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.79493 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.79493 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.79493 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.79493 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.89745 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.89745 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.89745 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.89745 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.89745 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.89745 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02731 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02731 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02731 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02731 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02731 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02731 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02328 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02328 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02328 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02328 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02328 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02328 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.01768 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.01768 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.01768 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.01768 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01768 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01768 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.73230 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.73230 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.73230 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.73230 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.73230 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.73230 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.93558 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.93558 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.93558 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.93558 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.93558 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.93558 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.93476 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.93476 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.93476 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.93476 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.93476 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.93476 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94501 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94501 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94501 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94501 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.94501 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.94501 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07579 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07579 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07579 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07579 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07579 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.07579 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.79493 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 0.89745 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.02731 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.02328 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.01768 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.73230 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.93558 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.93476 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.94501 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.07579 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.79493 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.79493 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.79493 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.79493 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.18465 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.79493 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.89747 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.19662 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 35159.05736 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 37393.10000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 18696.55000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 18696.55000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72314 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72314 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72314 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72314 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 37393.10000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 64994.53845 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.79493 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1920.65488 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 64994.53845 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.89745 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.89745 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.89745 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.89745 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.89745 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.89745 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.44873 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.59830 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17157.87386 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18281.66000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9140.83000 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9140.83000 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72976 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72976 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72976 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72976 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18281.66000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32497.29850 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.89745 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 993.62292 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32497.29850 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02731 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02731 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02731 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02731 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02731 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02731 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51366 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68487 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17188.45798 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18492.24000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9246.12000 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9246.12000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76910 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76910 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76910 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76910 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18492.24000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35342.33131 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02731 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1137.39590 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 35342.33131 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02328 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02328 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02328 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02328 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67537 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02328 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51164 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68219 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19497.66670 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20780.04000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10390.02000 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10390.02000 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73070 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73070 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73070 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73070 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20780.04000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35254.06111 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02328 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1132.93529 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 35254.06111 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01768 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01768 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01768 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01768 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67167 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01768 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50884 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67845 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19449.95179 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20724.41000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10362.20500 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10362.20500 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72986 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72986 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72986 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72986 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20724.41000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35131.41252 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01768 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1126.73765 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 35131.41252 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.73230 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.73230 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.73230 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.73230 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.14332 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.73230 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.86615 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.15487 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 34325.85938 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 36475.79000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 18237.89500 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 18237.89500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72003 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72003 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72003 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72003 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36475.79000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 63622.24867 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.73230 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1853.63854 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 63622.24867 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.93558 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.93558 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.93558 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.93558 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.61748 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.93558 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46779 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.62372 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18517.53860 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19679.11000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9839.55500 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9839.55500 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72034 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72034 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72034 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72034 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19679.11000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33332.62766 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.93558 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1035.83798 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 33332.62766 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.93476 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.93476 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.93476 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.93476 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.61694 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.93476 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46738 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.62317 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18555.15356 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19714.88000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9857.44000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9857.44000 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71956 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71956 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71956 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71956 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19714.88000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33314.67264 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.93476 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1034.93062 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 33314.67264 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.94501 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.94501 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.94501 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.94501 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62370 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.94501 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47251 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.63001 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18810.58387 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19982.06000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9991.03000 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9991.03000 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71882 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71882 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71882 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71882 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19982.06000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33539.06641 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.94501 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1046.27059 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 33539.06641 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07579 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07579 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07579 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07579 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.71002 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07579 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53790 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71719 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21261.54547 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22596.62000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11298.31000 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11298.31000 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72075 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72074 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72074 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72074 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22596.62000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36404.55353 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07579 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1191.06916 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 36404.55353 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 35981.6 | 11.61 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 17576.2 | 37.66 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 17686.2 | 48.56 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 19975.7 | 52.80 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 19924.4 | 64.53 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 35113.3 | 48.47 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 18943.3 | 101.45 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 18979.6 | 112.94 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 19238.7 | 123.12 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 21750.5 | 120.40 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.108 | 0.105 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 6.115E-002 | 6.026E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 6.115E-002 | 6.026E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 6.115E-002 | 6.026E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 6.115E-002 | 6.026E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 6.115E-002 | 6.026E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 6.115E-002 | 6.026E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 6.115E-002 | 6.026E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 6.115E-002 | 6.026E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.155 | 0.149 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 6 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 8.4071664440E-002 | 0.3306694119 | Pass | Pass | 7.6178157275E-002 | 0.3101339286 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 6.3646886735E-002 | 0.2575227033 | Pass | Pass | 0.1415627720 | 0.7102431249 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 8.3388364278E-002 | 0.3216645402 | Pass | Pass | 4.4198886475E-002 | 0.1423160087 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 9.2455512467E-002 | 0.3305297167 | Pass | Pass | 0.1364211348 | 1.1112919056 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 0.1013264282 | 0.3226645653 | Pass | Pass | 0.3666167569 | 3.3636579910 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 0.1307968646 | 0.3304888259 | Pass | Pass | 0.2259256238 | 0.9826981930 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 0.1279273140 | 0.3297263296 | Pass | Pass | 0.2715337016 | 1.1694385522 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 0.1286420246 | 0.3309787051 | Pass | Pass | 0.1616389267 | 0.5757737614 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 0.1486571609 | 0.3605706186 | Pass | Pass | 0.3491212472 | 0.9935830974 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 0.3039913225 | 0.4558532015 | Pass | Pass | 0.2799472887 | 0.8373502267 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.108 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.061 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.061 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.061 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.061 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.061 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.061 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.061 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.061 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.155 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.647 | 0.445 | 0.451 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.647 | 0.445 | 0.451 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.647 | 0.445 | 0.451 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.647 | 0.445 | 0.451 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.647 | 0.445 | 0.451 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.647 | 0.445 | 0.451 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.647 | 0.445 | 0.451 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.647 | 0.445 | 0.451 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.647 | 0.445 | 0.451 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.647 | 0.445 | 0.451 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.647 | 0.445 | 0.451 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.647 | 0.445 | 0.451 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.29_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.647 | 0.445 | 0.451 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 1.647 | 0.445 | 0.451 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 1.647 | 0.445 | 0.451 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 10.0956 | 348.39 | 3517.17 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 64.95 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 5.6941 | 348.39 | 1983.75 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 36.63 |
SMSTORE1_LIGHTS | SMSTORE1 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 32.48 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 8.5681 | 174.19 | 1492.50 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 27.56 |
SMSTORE2_LIGHTS | SMSTORE2 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 25.74 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 6.9535 | 174.19 | 1211.25 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 17.73 |
SMSTORE3_LIGHTS | SMSTORE3 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 25.74 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 6.9535 | 174.19 | 1211.25 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 17.73 |
SMSTORE4_LIGHTS | SMSTORE4 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 25.74 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 6.9535 | 174.19 | 1211.25 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 17.73 |
LGSTORE2_LIGHTS | LGSTORE2 | 10.0956 | 348.39 | 3517.17 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 47.31 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 23.66 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 23.66 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 23.66 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 23.66 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.7485 | 4180.64 | 28213.04 | 433.94 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 314.61 | AstronomicalClock | - | 42.55 | 42.55 | 2.51 | |
EXTERIOR_LIGHTS_B | 4639.80 | AstronomicalClock | - | 83.52 | 71.23 | 62.04 | |
Exterior Lighting Total | 4954.41 | 64.55 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 37393.10 | 27040.45 | 10352.65 | 0.72 | 3.80 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 18281.66 | 13341.22 | 4940.44 | 0.73 | 4.12 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 18492.24 | 14222.38 | 4269.86 | 0.77 | 4.12 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 20780.04 | 15183.98 | 5596.06 | 0.73 | 3.80 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 20724.41 | 15125.92 | 5598.49 | 0.73 | 3.80 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 36475.79 | 26263.66 | 10212.13 | 0.72 | 3.80 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 19679.11 | 14175.65 | 5503.46 | 0.72 | 3.80 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 19714.88 | 14186.04 | 5528.84 | 0.72 | 3.80 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 19982.06 | 14363.50 | 5618.56 | 0.72 | 3.80 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22596.62 | 16286.29 | 6310.33 | 0.72 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 35981.6 | 11.61 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 17576.2 | 37.66 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 17686.2 | 48.56 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 19975.7 | 52.80 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 19924.4 | 64.53 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 35113.3 | 48.47 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 18943.3 | 101.45 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 18979.6 | 112.94 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 19238.7 | 123.12 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 21750.5 | 120.40 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 64994.54 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32497.30 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 35342.33 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 35254.06 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 35131.41 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 63622.25 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 33332.63 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 33314.67 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 33539.07 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 36404.55 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.79 | 1920.65 | 1070.05 | 1.00 | 1.33 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.90 | 993.62 | 1107.16 | 1.00 | 1.43 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1137.40 | 1107.16 | 1.00 | 1.40 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1132.94 | 1107.16 | 1.00 | 1.40 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1126.74 | 1107.16 | 1.00 | 1.40 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.73 | 1853.64 | 1070.05 | 1.00 | 1.34 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.94 | 1035.84 | 1107.16 | 1.00 | 1.42 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.93 | 1034.93 | 1107.16 | 1.00 | 1.42 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.95 | 1046.27 | 1107.16 | 1.00 | 1.42 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.08 | 1191.07 | 1107.16 | 1.00 | 1.38 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 17389.78 | 20867.74 | 59.90 | 1.332 | 1.598 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 23.89 | 23.89 | 0.00947 | 30.10 | 0.01270 | 0.411 | 0.00 |
SMSTORE1 | 10043.69 | 12052.43 | 69.19 | 0.744 | 0.893 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00917 | 25.39 | 0.01270 | 0.206 | 0.00 |
SMSTORE2 | 11492.30 | 13790.76 | 79.17 | 0.856 | 1.027 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00936 | 23.28 | 0.01270 | 0.206 | 0.00 |
SMSTORE3 | 11448.94 | 13738.73 | 78.87 | 0.853 | 1.023 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00932 | 23.28 | 0.01270 | 0.206 | 0.00 |
SMSTORE4 | 11387.42 | 13664.91 | 78.45 | 0.848 | 1.018 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00938 | 23.28 | 0.01270 | 0.206 | 0.00 |
LGSTORE2 | 16623.46 | 19948.16 | 57.26 | 1.225 | 1.470 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00964 | 25.39 | 0.01270 | 0.411 | 0.00 |
SMSTORE5 | 8872.56 | 10647.08 | 61.12 | 0.655 | 0.786 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00952 | 25.39 | 0.01270 | 0.206 | 0.00 |
SMSTORE6 | 8750.15 | 10500.18 | 60.28 | 0.646 | 0.775 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00955 | 25.39 | 0.01270 | 0.206 | 0.00 |
SMSTORE7 | 8580.70 | 10296.84 | 59.11 | 0.633 | 0.759 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00960 | 25.39 | 0.01270 | 0.206 | 0.00 |
SMSTORE8 | 8616.39 | 10339.67 | 59.36 | 0.636 | 0.763 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00954 | 25.39 | 0.01270 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 33254.56 | 39905.47 | 114.54 | 1.496 | 1.795 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00673 | -32.70 | 0.00018 | 0.411 | 0.00 |
SMSTORE1 | 16627.36 | 19952.83 | 114.54 | 0.748 | 0.897 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00662 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE2 | 16786.60 | 20143.92 | 115.64 | 0.755 | 0.906 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00663 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE3 | 16855.85 | 20227.02 | 116.12 | 0.758 | 0.910 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00664 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE4 | 16976.37 | 20371.65 | 116.95 | 0.764 | 0.916 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00664 | -32.70 | 0.00018 | 0.206 | 0.00 |
LGSTORE2 | 32094.03 | 38512.84 | 110.55 | 1.444 | 1.732 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00671 | -32.70 | 0.00018 | 0.411 | 0.00 |
SMSTORE5 | 17333.75 | 20800.50 | 119.41 | 0.780 | 0.936 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00666 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE6 | 17318.56 | 20782.28 | 119.31 | 0.779 | 0.935 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00666 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE7 | 17508.32 | 21009.99 | 120.61 | 0.788 | 0.945 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00667 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE8 | 19931.55 | 23917.87 | 137.31 | 0.896 | 1.076 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00678 | -32.70 | 0.00018 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.60 | 1.60 | 1.79 | 1.79 | 1.7949 | 1.7949 | 1.7949 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 0.90 | 0.90 | 0.90 | 0.90 | 0.8975 | 0.8975 | 0.8975 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.03 | 1.03 | 0.91 | 0.91 | 1.0273 | 1.0273 | 1.0273 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.02 | 1.02 | 0.91 | 0.91 | 1.0233 | 1.0233 | 1.0233 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.02 | 1.02 | 0.92 | 0.92 | 1.0177 | 1.0177 | 1.0177 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.53 | 1.53 | 1.73 | 1.73 | 1.7323 | 1.7323 | 1.7323 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.79 | 0.79 | 0.94 | 0.94 | 0.9356 | 0.9356 | 0.9356 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 0.78 | 0.78 | 0.93 | 0.93 | 0.9348 | 0.9348 | 0.9348 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 0.77 | 0.77 | 0.95 | 0.95 | 0.9450 | 0.9450 | 0.9450 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 0.78 | 0.78 | 1.08 | 1.08 | 1.0758 | 1.0758 | 1.0758 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 18696.550 | 0.000 | 1.794930 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 18696.55 | 14282.00 | 1.794930 | 25.49 | 17.91 | 0.01029889 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 22.9231 | 23.89 | 0.00946523 | 49.0839 | 17389.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 64994.538 | 64994.538 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 64994.54 | 64994.54 | 1.794925 | 8.77 | 6.37 | 0.00523151 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 22.9231 | 21.10 | 0.00673285 | 41.5303 | 33254.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 9140.830 | 0.000 | 0.897450 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 9140.83 | 7081.01 | 0.897450 | 25.32 | 17.76 | 0.01017328 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 22.9235 | 23.89 | 0.00916788 | 47.5640 | 9732.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 32497.298 | 32497.298 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32497.30 | 32497.30 | 0.897453 | 8.77 | 6.27 | 0.00514693 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 22.9234 | 21.10 | 0.00662314 | 40.8618 | 16627.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 9246.120 | 0.000 | 1.027310 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 9246.12 | 7131.86 | 1.027310 | 23.79 | 17.14 | 0.01002571 | 12.80 | 11.72 | 0.00850000 | 23.28 | 0.01270325 | 19.06 | 20.0258 | 23.89 | 0.00935525 | 48.5259 | 11492.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 35342.331 | 35342.331 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35342.33 | 35342.33 | 1.027311 | 8.89 | 6.35 | 0.00516836 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 20.0258 | 21.10 | 0.00663275 | 40.9204 | 16786.60 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 10390.020 | 0.000 | 1.023280 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 10390.02 | 8066.46 | 1.023280 | 25.30 | 17.74 | 0.01015471 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 20.1046 | 23.89 | 0.00931734 | 48.3313 | 9867.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 35254.061 | 35254.061 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35254.06 | 35254.06 | 1.023282 | 8.94 | 6.38 | 0.00517756 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 20.1046 | 21.10 | 0.00663687 | 40.9456 | 16855.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 10362.205 | 0.000 | 1.017680 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 10362.20 | 8028.93 | 1.017680 | 25.31 | 17.76 | 0.01017142 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 20.2153 | 23.89 | 0.00937792 | 48.6420 | 11387.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 35131.413 | 35131.413 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35131.41 | 35131.41 | 1.017684 | 9.02 | 6.45 | 0.00519348 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 20.2152 | 21.10 | 0.00664403 | 40.9893 | 16976.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 18237.895 | 0.000 | 1.732300 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 18237.90 | 13836.43 | 1.732300 | 25.57 | 17.99 | 0.01036134 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 23.7519 | 23.89 | 0.00963614 | 49.9613 | 16566.79 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 63622.249 | 63622.249 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 63622.25 | 63622.25 | 1.732296 | 8.33 | 6.07 | 0.00516173 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 23.7519 | 21.10 | 0.00671252 | 41.4059 | 32094.03 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 9839.555 | 0.000 | 0.935580 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 9839.56 | 7454.67 | 0.935580 | 25.53 | 17.98 | 0.01036696 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 21.9892 | 23.89 | 0.00952100 | 49.3722 | 8481.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 33332.628 | 33332.628 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33332.63 | 33332.63 | 0.935582 | 9.27 | 6.62 | 0.00523955 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 21.9892 | 21.10 | 0.00666475 | 41.1158 | 17333.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 9857.440 | 0.000 | 0.934760 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 9857.44 | 7454.55 | 0.934760 | 25.55 | 18.00 | 0.01038346 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 22.0085 | 23.89 | 0.00955401 | 49.5411 | 8386.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 33314.673 | 33314.673 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33314.67 | 33314.67 | 0.934763 | 9.26 | 6.61 | 0.00523762 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 22.0084 | 21.10 | 0.00666388 | 41.1105 | 17318.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 9991.030 | 0.000 | 0.945010 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 9991.03 | 7542.44 | 0.945010 | 25.56 | 18.02 | 0.01039919 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 21.7698 | 23.89 | 0.00960430 | 49.7983 | 8297.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 33539.066 | 33539.066 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33539.07 | 33539.07 | 0.945005 | 9.39 | 6.70 | 0.00526148 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 21.7699 | 21.10 | 0.00667462 | 41.1761 | 17508.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 11298.310 | 0.000 | 1.075790 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 11298.31 | 8534.11 | 1.075790 | 25.48 | 17.98 | 0.01038390 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01270324 | 21.04 | 19.1233 | 23.89 | 0.00954037 | 49.4710 | 8452.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 36404.554 | 36404.554 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36404.55 | 36404.55 | 1.075789 | 10.82 | 7.67 | 0.00551640 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 19.1233 | 21.10 | 0.00677739 | 41.8038 | 19931.55 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18696.550 | 0.000 | 1.794930 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9851 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 18696.55 | 14282.00 | 1.0000 | 2.07121434 | 1.794930 | 25.49 | 17.91 | 0.01029889 | 51854.8 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18696.55 | 30.10 | 0.01270324 | 21.10 | 0.41145340 | 22.9231 | 23.89 | 0.00946523 | 23.89 | 0.00946523 | 49.0839 | 17389.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 64994.538 | 64994.538 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.794925 | 2.07120888 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 64994.54 | 64994.54 | 1.0000 | 2.07120888 | 1.794925 | 8.77 | 6.37 | 0.00523151 | 21983.2 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 64994.54 | -32.70 | 0.00018338 | -32.70 | 0.41145340 | 22.9231 | 21.11 | 0.00673285 | 21.10 | 0.00673285 | 41.5303 | 33254.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9140.830 | 0.000 | 0.897450 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7516 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 9140.83 | 7081.01 | 1.0000 | 1.03558986 | 0.897450 | 25.32 | 17.76 | 0.01017328 | 51360.1 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9140.83 | 30.10 | 0.01270324 | 21.10 | 0.20572670 | 22.9235 | 23.89 | 0.00941750 | 23.89 | 0.00916788 | 47.5640 | 9732.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32497.298 | 32497.298 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.897453 | 1.03559332 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32497.30 | 32497.30 | 1.0000 | 1.03559332 | 0.897453 | 8.77 | 6.27 | 0.00514693 | 21769.9 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32497.30 | -32.70 | 0.00018338 | -32.70 | 0.20572670 | 22.9234 | 21.11 | 0.00662314 | 21.10 | 0.00662314 | 40.8618 | 16627.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9246.120 | 0.000 | 1.027310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4773 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 9246.12 | 7131.86 | 1.0000 | 1.18543854 | 1.027310 | 23.79 | 17.14 | 0.01002571 | 49422.0 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9246.12 | 23.28 | 0.01270325 | 19.06 | 0.20572670 | 20.0258 | 23.92 | 0.00935525 | 23.89 | 0.00935525 | 48.5259 | 11492.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35342.331 | 35342.331 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.027311 | 1.18543923 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35342.33 | 35342.33 | 1.0000 | 1.18543923 | 1.027311 | 8.89 | 6.35 | 0.00516836 | 21942.5 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35342.33 | -32.70 | 0.00018338 | -32.70 | 0.20572670 | 20.0258 | 21.11 | 0.00663275 | 21.10 | 0.00663275 | 40.9204 | 16786.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10390.020 | 0.000 | 1.023280 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7171 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 10390.02 | 8066.46 | 1.0000 | 1.18078823 | 1.023280 | 25.30 | 17.74 | 0.01015471 | 51292.8 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10390.02 | 30.10 | 0.01270324 | 21.10 | 0.20572670 | 20.1046 | 23.89 | 0.00940684 | 23.89 | 0.00931734 | 48.3313 | 9867.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35254.061 | 35254.061 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.023282 | 1.18079021 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35254.06 | 35254.06 | 1.0000 | 1.18079021 | 1.023282 | 8.94 | 6.38 | 0.00517756 | 22016.6 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35254.06 | -32.70 | 0.00018338 | -32.70 | 0.20572670 | 20.1046 | 21.11 | 0.00663687 | 21.10 | 0.00663687 | 40.9456 | 16855.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10362.205 | 0.000 | 1.017680 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7482 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 10362.20 | 8028.93 | 1.0000 | 1.17432625 | 1.017680 | 25.31 | 17.76 | 0.01017142 | 51353.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10362.20 | 30.10 | 0.01270324 | 21.10 | 0.20572670 | 20.2153 | 23.89 | 0.00941641 | 23.89 | 0.00937792 | 48.6420 | 11387.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35131.413 | 35131.413 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.017684 | 1.17433078 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35131.41 | 35131.41 | 1.0000 | 1.17433078 | 1.017684 | 9.02 | 6.45 | 0.00519348 | 22144.3 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35131.41 | -32.70 | 0.00018338 | -32.70 | 0.20572670 | 20.2152 | 21.11 | 0.00664403 | 21.10 | 0.00664403 | 40.9893 | 16976.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18237.895 | 0.000 | 1.732300 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1012 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 18237.90 | 13836.43 | 1.0000 | 1.99894403 | 1.732300 | 25.57 | 17.99 | 0.01036134 | 52095.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18237.90 | 30.10 | 0.01270324 | 21.10 | 0.41145340 | 23.7519 | 23.89 | 0.00949405 | 23.89 | 0.00963614 | 49.9613 | 16566.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 63622.249 | 63622.249 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.732296 | 1.99893935 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 63622.25 | 63622.25 | 1.0000 | 1.99893935 | 1.732296 | 8.33 | 6.07 | 0.00516173 | 21355.2 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 63622.25 | -32.70 | 0.00018338 | -32.70 | 0.41145340 | 23.7519 | 21.11 | 0.00671252 | 21.10 | 0.00671252 | 41.4059 | 32094.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9839.555 | 0.000 | 0.935580 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1117 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 9839.56 | 7454.67 | 1.0000 | 1.07958902 | 0.935580 | 25.53 | 17.98 | 0.01036696 | 52069.5 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9839.56 | 30.10 | 0.01270324 | 21.10 | 0.20572670 | 21.9892 | 23.89 | 0.00952920 | 23.89 | 0.00952100 | 49.3722 | 8481.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33332.628 | 33332.628 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.935582 | 1.07959153 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33332.63 | 33332.63 | 1.0000 | 1.07959153 | 0.935582 | 9.27 | 6.62 | 0.00523955 | 22513.1 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33332.63 | -32.70 | 0.00018338 | -32.70 | 0.20572670 | 21.9892 | 21.11 | 0.00666475 | 21.10 | 0.00666475 | 41.1158 | 17333.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9857.440 | 0.000 | 0.934760 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1423 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 9857.44 | 7454.55 | 1.0000 | 1.07864280 | 0.934760 | 25.55 | 18.00 | 0.01038346 | 52130.5 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9857.44 | 30.10 | 0.01270324 | 21.10 | 0.20572670 | 22.0085 | 23.89 | 0.00953878 | 23.89 | 0.00955401 | 49.5411 | 8386.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33314.673 | 33314.673 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.934763 | 1.07864584 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33314.67 | 33314.67 | 1.0000 | 1.07864584 | 0.934763 | 9.26 | 6.61 | 0.00523762 | 22497.7 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33314.67 | -32.70 | 0.00018338 | -32.70 | 0.20572670 | 22.0084 | 21.11 | 0.00666388 | 21.10 | 0.00666388 | 41.1105 | 17318.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9991.030 | 0.000 | 0.945010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1716 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 9991.03 | 7542.44 | 1.0000 | 1.09047053 | 0.945010 | 25.56 | 18.02 | 0.01039919 | 52188.8 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9991.03 | 30.10 | 0.01270324 | 21.10 | 0.20572670 | 21.7698 | 23.89 | 0.00954794 | 23.89 | 0.00960430 | 49.7983 | 8297.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33539.066 | 33539.066 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.945005 | 1.09046481 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33539.07 | 33539.07 | 1.0000 | 1.09046481 | 0.945005 | 9.39 | 6.70 | 0.00526148 | 22688.0 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33539.07 | -32.70 | 0.00018338 | -32.70 | 0.20572670 | 21.7699 | 21.11 | 0.00667462 | 21.10 | 0.00667462 | 41.1761 | 17508.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11298.310 | 0.000 | 1.075790 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1432 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 11298.31 | 8534.11 | 1.0000 | 1.24138082 | 1.075790 | 25.48 | 17.98 | 0.01038390 | 52062.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11298.31 | 29.89 | 0.01270324 | 21.04 | 0.20572670 | 19.1233 | 23.89 | 0.00954833 | 23.89 | 0.00954037 | 49.4710 | 8452.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36404.554 | 36404.554 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.075789 | 1.24137964 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36404.55 | 36404.55 | 1.0000 | 1.24137964 | 1.075789 | 10.82 | 7.67 | 0.00551640 | 24775.3 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36404.55 | -32.70 | 0.00018338 | -32.70 | 0.20572670 | 19.1233 | 21.11 | 0.00677739 | 21.10 | 0.00677739 | 41.8038 | 19931.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.79 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.90 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.03 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.02 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.02 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.73 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.94 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.93 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.95 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.08 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3616.67 | 4256.33 | 2517.00 |
SMSTORE1 | 3038.83 | 3931.17 | 1773.83 |
SMSTORE2 | 2592.00 | 3066.17 | 1645.67 |
SMSTORE3 | 2604.83 | 3086.67 | 1665.00 |
SMSTORE4 | 2650.83 | 3151.00 | 1767.33 |
LGSTORE2 | 2572.67 | 3035.67 | 1903.83 |
SMSTORE5 | 2554.83 | 3072.00 | 1945.83 |
SMSTORE6 | 2568.00 | 3099.83 | 1979.00 |
SMSTORE7 | 2612.83 | 3154.00 | 2061.17 |
SMSTORE8 | 2753.00 | 3258.00 | 2290.50 |
Facility | 4425.83 | 4726.67 | 3210.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 8.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 4.67 | 0.17 | 0.00 | 0.17 |
SMSTORE2 | 0.00 | 1.00 | 0.00 | 1.00 |
SMSTORE3 | 0.00 | 0.17 | 0.00 | 0.17 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 58.83 | 0.00 | 0.00 | 0.00 |
Facility | 69.67 | 1.17 | 0.00 | 1.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.02 | 30.00 | 1805.20 | 0.943 | 0.237 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.952 | 0.252 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 1.193 | 0.329 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 1.018 | 0.329 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 1.007 | 0.329 | 0.000 | 0.000 |
LGSTORE2 | 13.24 | 30.00 | 1805.20 | 0.954 | 0.316 | 0.000 | 0.000 |
SMSTORE5 | 6.62 | 15.00 | 902.60 | 0.969 | 0.351 | 0.000 | 0.000 |
SMSTORE6 | 6.62 | 15.00 | 902.60 | 0.964 | 0.351 | 0.000 | 0.000 |
SMSTORE7 | 6.62 | 15.00 | 902.60 | 0.958 | 0.351 | 0.000 | 0.000 |
SMSTORE8 | 6.62 | 15.00 | 902.60 | 0.967 | 0.372 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.02 | 30.00 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.24 | 30.00 | 1805.20 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.62 | 15.00 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.62 | 15.00 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.62 | 15.00 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.62 | 15.00 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 861.91 | 3078.07 | 29-JAN-08:00 | 91837.13 | 29-JUN-16:00 |
Electricity:Building | 562.66 | 1860.07 | 01-JAN-00:10 | 34891.92 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 127.94 | 349.95 | 01-JAN-00:10 | 6574.13 | 01-JAN-10:10 |
InteriorLights:Electricity | 433.94 | 1410.65 | 01-JAN-00:10 | 26802.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 101.59 | 275.05 | 01-JAN-00:10 | 5225.88 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 433.94 | 1410.65 | 01-JAN-00:10 | 26802.39 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 73.22 | 200.01 | 01-JAN-00:10 | 3762.66 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 60.04 | 162.55 | 01-JAN-00:10 | 3088.53 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 53.93 | 185.94 | 01-JAN-00:10 | 3495.47 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 43.46 | 148.49 | 01-JAN-00:10 | 2821.35 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 53.93 | 185.94 | 01-JAN-00:10 | 3495.47 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 43.46 | 148.49 | 01-JAN-00:10 | 2821.35 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 53.93 | 185.94 | 01-JAN-00:10 | 3495.47 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 43.46 | 148.49 | 01-JAN-00:10 | 2821.35 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 66.57 | 250.76 | 01-JAN-00:10 | 4689.57 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 47.31 | 175.86 | 01-JAN-00:10 | 3341.31 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 33.29 | 125.38 | 01-JAN-00:10 | 2344.79 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 23.66 | 87.93 | 01-JAN-00:10 | 1670.66 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 33.29 | 125.38 | 01-JAN-00:10 | 2344.79 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 23.66 | 87.93 | 01-JAN-00:10 | 1670.66 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 33.29 | 125.38 | 01-JAN-00:10 | 2344.79 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 23.66 | 87.93 | 01-JAN-00:10 | 1670.66 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 33.29 | 125.38 | 01-JAN-00:10 | 2344.79 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 23.66 | 87.93 | 01-JAN-00:10 | 1670.66 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
Electricity:Plant | 63.58 | 1218.00 | 03-JAN-08:10 | 13929.06 | 06-JAN-17:40 |
WaterSystems:Electricity | 63.58 | 1218.00 | 03-JAN-08:10 | 13929.06 | 06-JAN-17:40 |
Water Heater:WaterSystems:Electricity | 63.58 | 1218.00 | 03-JAN-08:10 | 13929.06 | 06-JAN-17:40 |
ElectricityPurchased:Facility | 861.91 | 3078.07 | 29-JAN-08:00 | 91837.13 | 29-JUN-16:00 |
ElectricityPurchased:Plant | 861.91 | 3078.07 | 29-JAN-08:00 | 91837.13 | 29-JUN-16:00 |
Cogeneration:ElectricityPurchased | 861.91 | 3078.07 | 29-JAN-08:00 | 91837.13 | 29-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 861.91 | 3078.07 | 29-JAN-08:00 | 91837.13 | 29-JUN-16:00 |
ElectricityNet:Plant | 861.91 | 3078.07 | 29-JAN-08:00 | 91837.13 | 29-JUN-16:00 |
Cogeneration:ElectricityNet | 861.91 | 3078.07 | 29-JAN-08:00 | 91837.13 | 29-JUN-16:00 |
Electricity:HVAC | 171.12 | 0.00 | 01-JAN-00:40 | 52683.94 | 29-JUN-16:10 |
Fans:Electricity | 122.25 | 0.00 | 01-JAN-00:40 | 10707.83 | 06-JAN-09:10 |
General:Fans:Electricity | 122.25 | 0.00 | 01-JAN-00:40 | 10707.83 | 06-JAN-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 48.87 | 0.00 | 01-JAN-00:10 | 43911.35 | 29-JUN-16:10 |
ExteriorLights:Electricity | 64.55 | 0.00 | 01-JAN-08:20 | 4954.41 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 64.55 | 0.00 | 01-JAN-08:20 | 4954.41 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1100.18 | 0.00 | 01-JAN-00:40 | 351868.14 | 06-JAN-09:10 |
Gas:HVAC | 1100.18 | 0.00 | 01-JAN-00:40 | 351868.14 | 06-JAN-09:10 |
Heating:Gas | 1100.18 | 0.00 | 01-JAN-00:40 | 351868.14 | 06-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1652.62 | 0.00 | 01-JAN-00:40 | 415336.71 | 09-JAN-09:10 |
EnergyTransfer:Building | 567.57 | 0.00 | 01-JAN-00:40 | 140056.04 | 09-JAN-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 107.81 | 0.00 | 01-JAN-00:10 | 24909.00 | 17-FEB-09:10 |
Heating:EnergyTransfer | 321.90 | 0.00 | 01-JAN-00:40 | 139713.86 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 49.89 | 0.00 | 01-JAN-00:10 | 24442.74 | 06-JAN-09:10 |
Cooling:EnergyTransfer | 245.67 | 0.00 | 01-JAN-00:10 | 76934.49 | 29-JUN-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 57.92 | 0.00 | 01-JAN-00:10 | 22709.87 | 06-JAN-00:10 |
EnergyTransfer:Zone:SMSTORE1 | 50.96 | 0.00 | 01-JAN-00:10 | 11797.36 | 05-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 18.23 | 0.00 | 01-JAN-00:10 | 11104.14 | 05-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 32.73 | 0.00 | 01-JAN-00:10 | 9663.52 | 21-MAY-19:40 |
EnergyTransfer:Zone:SMSTORE2 | 44.56 | 0.00 | 01-JAN-00:10 | 13644.57 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 21.13 | 0.00 | 01-JAN-00:10 | 13454.58 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 23.43 | 0.00 | 01-JAN-00:10 | 7065.34 | 29-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 45.36 | 0.00 | 01-JAN-00:10 | 14041.92 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 21.77 | 0.00 | 01-JAN-00:10 | 13889.73 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 23.59 | 0.00 | 01-JAN-00:10 | 7052.78 | 29-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE4 | 45.57 | 0.00 | 01-JAN-00:10 | 14192.45 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 23.77 | 0.00 | 01-JAN-00:10 | 14192.45 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 21.80 | 0.00 | 01-JAN-00:10 | 6920.13 | 29-JUN-16:10 |
EnergyTransfer:Zone:LGSTORE2 | 81.62 | 0.00 | 01-JAN-00:10 | 25643.82 | 25-DEC-10:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 50.32 | 0.00 | 01-JAN-00:10 | 25334.53 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 31.29 | 0.00 | 01-JAN-00:10 | 11714.14 | 29-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE5 | 43.67 | 0.00 | 01-JAN-00:10 | 13690.66 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 28.44 | 0.00 | 01-JAN-00:10 | 13690.66 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 15.24 | 0.00 | 01-JAN-00:10 | 6084.04 | 29-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE6 | 43.66 | 0.00 | 01-JAN-00:10 | 14774.69 | 23-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 28.98 | 0.00 | 01-JAN-00:10 | 13726.96 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 14.68 | 0.00 | 01-JAN-00:10 | 6019.77 | 29-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE7 | 44.94 | 0.00 | 01-JAN-00:10 | 14049.93 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 31.41 | 0.00 | 01-JAN-00:10 | 14049.93 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 13.54 | 0.00 | 01-JAN-00:10 | 5923.18 | 29-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE8 | 59.43 | 0.00 | 01-JAN-00:40 | 16937.27 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 47.97 | 0.00 | 01-JAN-00:40 | 16937.27 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 11.45 | 0.00 | 01-JAN-00:10 | 5943.37 | 30-JUN-13:00 |
EnergyTransfer:HVAC | 1085.05 | 0.00 | 01-JAN-00:40 | 281494.51 | 06-JAN-09:10 |
HeatingCoils:EnergyTransfer | 880.14 | 0.00 | 01-JAN-00:40 | 281494.51 | 06-JAN-09:10 |
CoolingCoils:EnergyTransfer | 204.91 | 0.00 | 01-JAN-00:10 | 175467.23 | 15-JUL-14:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 49.889 | -57.917 | 0.000 | 0.000 | 13.712 | 101.585 | 26.357 | 21.933 | 0.000 | 0.871 | 0.004 | 0.000 | -11.834 | 0.000 | -56.600 | -87.996 |
SMSTORE1 | 0.000 | 0.000 | 18.231 | -32.728 | 0.000 | 0.000 | 6.756 | 60.038 | 13.179 | 10.873 | 0.000 | 0.471 | 0.003 | 0.000 | -6.156 | 0.000 | -28.276 | -42.387 |
SMSTORE2 | 0.000 | 0.000 | 21.126 | -23.432 | 0.000 | 0.000 | 4.093 | 43.461 | 10.467 | 10.850 | 0.000 | 0.464 | 0.000 | 0.000 | -6.102 | 0.000 | -29.025 | -31.901 |
SMSTORE3 | 0.000 | 0.000 | 21.770 | -23.588 | 0.000 | 0.000 | 4.113 | 43.461 | 10.467 | 10.874 | 0.000 | 0.465 | 0.000 | 0.000 | -6.038 | 0.000 | -28.856 | -32.668 |
SMSTORE4 | 0.000 | 0.000 | 23.772 | -21.802 | 0.000 | 0.000 | 4.121 | 43.461 | 10.467 | 10.898 | 0.000 | 0.465 | 0.000 | 0.000 | -5.981 | 0.000 | -28.766 | -36.635 |
LGSTORE2 | 0.000 | 0.000 | 50.323 | -31.294 | 0.000 | 0.000 | 14.192 | 47.311 | 19.261 | 21.891 | 0.000 | 0.839 | 0.003 | 0.000 | -11.652 | 0.000 | -52.550 | -58.320 |
SMSTORE5 | 0.000 | 0.000 | 28.437 | -15.236 | 0.000 | 0.000 | 7.101 | 23.655 | 9.631 | 10.940 | 0.000 | 0.466 | 0.002 | 0.000 | -5.830 | 0.000 | -28.728 | -30.435 |
SMSTORE6 | 0.000 | 0.000 | 28.978 | -14.678 | 0.000 | 0.000 | 7.106 | 23.655 | 9.631 | 10.950 | 0.000 | 0.466 | 0.001 | 0.000 | -5.811 | 0.000 | -28.694 | -31.603 |
SMSTORE7 | 0.000 | 0.000 | 31.406 | -13.537 | 0.000 | 0.000 | 7.116 | 23.655 | 9.631 | 10.975 | 0.000 | 0.467 | 0.000 | 0.000 | -5.749 | 0.000 | -28.601 | -35.363 |
SMSTORE8 | 0.000 | 0.000 | 47.972 | -11.454 | 0.000 | 0.000 | 7.137 | 23.655 | 9.631 | 11.054 | 0.000 | 0.492 | 0.001 | 0.000 | -5.498 | 0.000 | -35.058 | -47.931 |
Total Facility | 0.000 | 0.000 | 321.903 | -245.666 | 0.000 | 0.000 | 75.447 | 433.937 | 128.721 | 131.238 | 0.000 | 5.466 | 0.014 | 0.000 | -70.651 | 0.000 | -345.156 | -435.240 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 02-SEP-08:62 | 0.00 | 0.00 | 0.00 | -35028.61 | 0.00 | 0.00 | 96.85 | 2750.46 | 749.03 | 713.20 | 0.00 | 0.00 | 31139.19 | 0.00 | -0.00 | 0.00 | -420.12 | 0.00 |
SMSTORE1 | 21-MAY-19:50 | 0.00 | 0.00 | 0.00 | -20104.31 | 0.00 | 0.00 | 470.58 | 3088.53 | 674.13 | 0.00 | 0.00 | 0.00 | 16023.30 | 0.00 | -139.12 | 0.00 | -13.11 | 0.00 |
SMSTORE2 | 06-SEP-07:01 | 0.00 | 0.00 | 0.00 | -27497.76 | 0.00 | 0.00 | 48.94 | 1484.92 | 374.52 | 0.00 | 0.00 | 0.00 | 26081.39 | 0.00 | -56.11 | 0.00 | -435.89 | 0.00 |
SMSTORE3 | 08-SEP-07:02 | 0.00 | 0.00 | 0.00 | -21394.79 | 0.00 | 0.00 | 48.34 | 1484.92 | 374.52 | 22.79 | 0.00 | 0.00 | 19768.77 | 0.00 | -0.00 | 0.00 | -304.55 | 0.00 |
SMSTORE4 | 02-AUG-07:02 | 0.00 | 0.00 | 0.00 | -20999.69 | 0.00 | 0.00 | 48.12 | 1484.92 | 374.52 | 102.65 | 0.00 | 0.00 | 19260.94 | 0.00 | -0.00 | 0.00 | -271.46 | 0.00 |
LGSTORE2 | 07-JUL-08:62 | 0.00 | 0.00 | 0.00 | -33503.46 | 0.00 | 0.00 | 213.40 | 1758.59 | 749.03 | 618.10 | 0.00 | 0.00 | 30494.71 | 0.00 | -0.00 | 0.00 | -330.36 | 0.00 |
SMSTORE5 | 07-JUL-08:62 | 0.00 | 0.00 | 0.00 | -17915.79 | 0.00 | 0.00 | 107.41 | 879.29 | 374.52 | 310.12 | 0.00 | 0.00 | 16420.45 | 0.00 | -0.00 | 0.00 | -176.01 | 0.00 |
SMSTORE6 | 07-JUL-08:62 | 0.00 | 0.00 | 0.00 | -17869.42 | 0.00 | 0.00 | 107.91 | 879.29 | 374.52 | 311.03 | 0.00 | 0.00 | 16371.10 | 0.00 | -0.00 | 0.00 | -174.43 | 0.00 |
SMSTORE7 | 01-JUL-08:62 | 0.00 | 0.00 | 0.00 | -16719.28 | 0.00 | 0.00 | 107.14 | 879.29 | 374.52 | 343.13 | 0.00 | 0.00 | 15151.59 | 0.00 | -0.00 | 0.00 | -136.39 | 0.00 |
SMSTORE8 | 10-AUG-08:61 | 0.00 | 0.00 | 0.00 | -16954.98 | 0.00 | 0.00 | 109.39 | 879.29 | 374.52 | 390.37 | 0.00 | 0.00 | 15376.16 | 0.00 | -0.00 | 0.00 | -174.75 | 0.00 |
Total Facility | 02-SEP-08:62 | 0.00 | 0.00 | 0.00 | -152420.10 | 0.00 | 0.00 | 1107.98 | 18115.80 | 5393.02 | 4301.68 | 0.00 | 0.00 | 125997.07 | 0.00 | 0.00 | 0.00 | -2495.45 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 18-MAR-07:01 | 0.00 | 0.00 | 64985.36 | 0.00 | 0.00 | 0.00 | 0.00 | 275.05 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -779.41 | 0.00 | -1683.30 | -62872.61 |
SMSTORE1 | 20-DEC-08:61 | 0.00 | 0.00 | 32527.50 | 0.00 | 0.00 | 0.00 | 74.02 | 162.55 | 37.45 | 0.78 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1369.58 | -31432.73 |
SMSTORE2 | 01-JAN-08:61 | 0.00 | 0.00 | 35269.89 | 0.00 | 0.00 | 0.00 | 0.00 | 148.49 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -641.55 | 0.00 | -1229.14 | -33585.14 |
SMSTORE3 | 01-JAN-08:61 | 0.00 | 0.00 | 35189.80 | 0.00 | 0.00 | 0.00 | 0.00 | 148.49 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -636.54 | 0.00 | -1223.71 | -33515.50 |
SMSTORE4 | 25-DEC-08:61 | 0.00 | 0.00 | 35118.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.49 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -652.98 | 0.00 | -1251.96 | -33399.00 |
LGSTORE2 | 20-DEC-08:61 | 0.00 | 0.00 | 63759.41 | 0.00 | 0.00 | 0.00 | 0.00 | 175.86 | 74.90 | 47.34 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2444.61 | -61612.90 |
SMSTORE5 | 24-DEC-09:01 | 0.00 | 0.00 | 33365.46 | 0.00 | 0.00 | 0.00 | 0.00 | 87.93 | 37.45 | 1270.09 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1462.13 | -33298.80 |
SMSTORE6 | 25-DEC-09:01 | 0.00 | 0.00 | 33336.31 | 0.00 | 0.00 | 0.00 | 0.00 | 87.93 | 37.45 | 642.42 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1218.88 | -32885.23 |
SMSTORE7 | 20-DEC-08:61 | 0.00 | 0.00 | 33573.12 | 0.00 | 0.00 | 0.00 | 0.00 | 87.93 | 37.45 | 22.04 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1341.35 | -32379.19 |
SMSTORE8 | 24-DEC-09:01 | 0.00 | 0.00 | 36437.25 | 0.00 | 0.00 | 0.00 | 0.00 | 87.93 | 37.45 | 1283.32 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1852.15 | -35993.80 |
Total Facility | 16-FEB-08:61 | 0.00 | 0.00 | 379131.87 | 0.00 | 0.00 | 0.00 | 431.90 | 5419.93 | 1460.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2621.16 | 0.00 | -12129.49 | -371693.67 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.7949 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.7949 | 0.2575 | 1.0000 | 0.4115 | 0.2292 | ||
PSZ-AC_2:2 | 0.8975 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8975 | 0.2297 | 1.0000 | 0.2057 | 0.2292 | ||
PSZ-AC_3:3 | 1.0273 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0273 | 0.2003 | 1.0000 | 0.2057 | 0.2003 | ||
PSZ-AC_4:4 | 1.0233 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0233 | 0.2010 | 1.0000 | 0.2057 | 0.2010 | ||
PSZ-AC_5:5 | 1.0177 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0177 | 0.2022 | 1.0000 | 0.2057 | 0.2022 | ||
PSZ-AC_6:6 | 1.7323 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.7323 | 0.2696 | 1.0000 | 0.4115 | 0.2375 | ||
PSZ-AC_7:7 | 0.9356 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9356 | 0.2603 | 1.0000 | 0.2057 | 0.2199 | ||
PSZ-AC_8:8 | 0.9348 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9348 | 0.2636 | 1.0000 | 0.2057 | 0.2201 | ||
PSZ-AC_9:9 | 0.9450 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9450 | 0.2680 | 1.0000 | 0.2057 | 0.2177 | ||
PSZ-AC_10:10 | 1.0758 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0758 | 0.2635 | 1.0000 | 0.2057 | 0.1912 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.7949 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.7949 | 1.0000 | 1.0000 | 0.4115 | 0.2292 | ||
PSZ-AC_2:2 | 0.8975 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8975 | 1.0000 | 1.0000 | 0.2057 | 0.2292 | ||
PSZ-AC_3:3 | 1.0273 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0273 | 1.0000 | 1.0000 | 0.2057 | 0.2003 | ||
PSZ-AC_4:4 | 1.0233 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0233 | 1.0000 | 1.0000 | 0.2057 | 0.2010 | ||
PSZ-AC_5:5 | 1.0177 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0177 | 1.0000 | 1.0000 | 0.2057 | 0.2022 | ||
PSZ-AC_6:6 | 1.7323 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.7323 | 1.0000 | 1.0000 | 0.4115 | 0.2375 | ||
PSZ-AC_7:7 | 0.9356 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9356 | 1.0000 | 1.0000 | 0.2057 | 0.2199 | ||
PSZ-AC_8:8 | 0.9348 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9348 | 1.0000 | 1.0000 | 0.2057 | 0.2201 | ||
PSZ-AC_9:9 | 0.9450 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9450 | 1.0000 | 1.0000 | 0.2057 | 0.2177 | ||
PSZ-AC_10:10 | 1.0758 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0758 | 1.0000 | 1.0000 | 0.2057 | 0.1912 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.7949 | 1.7949 | 1.7949 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 0.8975 | 0.8975 | 0.8975 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.0273 | 1.0273 | 1.0273 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.0233 | 1.0233 | 1.0233 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.0177 | 1.0177 | 1.0177 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.7323 | 1.7323 | 1.7323 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.9356 | 0.9356 | 0.9356 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.9348 | 0.9348 | 0.9348 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.9450 | 0.9450 | 0.9450 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0758 | 1.0758 | 1.0758 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.7949 | 1.7949 | 1.7949 | 1.7949 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.8975 | 0.8975 | 0.8975 | 0.8975 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0273 | 1.0273 | 1.0273 | 1.0273 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0233 | 1.0233 | 1.0233 | 1.0233 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0177 | 1.0177 | 1.0177 | 1.0177 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7323 | 1.7323 | 1.7323 | 1.7323 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9356 | 0.9356 | 0.9356 | 0.9356 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9348 | 0.9348 | 0.9348 | 0.9348 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9450 | 0.9450 | 0.9450 | 0.9450 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0758 | 1.0758 | 1.0758 | 1.0758 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.7949 | 1.7949 | 1.7949 | 0.4115 | 0.2292 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 0.8975 | 0.8975 | 0.8975 | 0.2057 | 0.2292 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.0273 | 1.0273 | 1.0273 | 0.2057 | 0.2271 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.0233 | 1.0233 | 1.0233 | 0.2057 | 0.2261 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.0177 | 1.0177 | 1.0177 | 0.2057 | 0.2245 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.7323 | 1.7323 | 1.7323 | 0.4115 | 0.2375 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.9356 | 0.9356 | 0.9356 | 0.2057 | 0.2199 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.9348 | 0.9348 | 0.9348 | 0.2057 | 0.2201 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.9450 | 0.9450 | 0.9450 | 0.2057 | 0.2177 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0758 | 1.0758 | 1.0758 | 0.2057 | 0.1912 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.7949 | 1.7949 | 1.7949 | 1.7949 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.8975 | 0.8975 | 0.8975 | 0.8975 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0273 | 1.0273 | 1.0273 | 1.0273 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0233 | 1.0233 | 1.0233 | 1.0233 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0177 | 1.0177 | 1.0177 | 1.0177 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7323 | 1.7323 | 1.7323 | 1.7323 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9356 | 0.9356 | 0.9356 | 0.9356 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9348 | 0.9348 | 0.9348 | 0.9348 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9450 | 0.9450 | 0.9450 | 0.9450 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0758 | 1.0758 | 1.0758 | 1.0758 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:16
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1.17 |
Number of hours not met | 1.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1100.18 | 351868.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 48.87 | 43911.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 433.94 | 26802.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 64.55 | 4954.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 122.25 | 10707.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 63.58 | 13929.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 861.91 |
Natural Gas | 0.00 | 1100.18 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1962.09 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 207.59 |
Space Heating | 0.00 |
Space Cooling | 23.38 |
Fans (All) | 58.48 |
Service Water Heating | 30.42 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 412.34 |
Subtotal | 412.34 |
Natural Gas [MJ/m2] | |
Space Heating | 526.32 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 526.32 |
Subtotal | 526.32 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 22.12 |
Space Heating | 56.07 |
Space Cooling | 2.49 |
Fans (All) | 6.23 |
Service Water Heating | 3.24 |
Receptacle Equipment | 6.56 |
Miscellaneous | 3.29 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5131. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.270925E+12 |
February | 0.000 | 0.184642E+12 |
March | 0.000 | 0.157566E+12 |
April | 0.000 | 0.608263E+11 |
May | 0.000 | 0.551158E+10 |
June | 0.000 | 0.497827E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2417705.577 |
September | 0.000 | 0.353771E+10 |
October | 0.000 | 0.466378E+11 |
November | 0.000 | 0.118898E+12 |
December | 0.000 | 0.251584E+12 |
Annual Sum or Average | 0.110018E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.270925E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.270925E+12 |
February | 0.000 | 0.184642E+12 |
March | 0.000 | 0.157566E+12 |
April | 0.000 | 0.608263E+11 |
May | 0.000 | 0.551158E+10 |
June | 0.000 | 0.497827E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2417705.577 |
September | 0.000 | 0.353771E+10 |
October | 0.000 | 0.466378E+11 |
November | 0.000 | 0.118898E+12 |
December | 0.000 | 0.251584E+12 |
Annual Sum or Average | 0.110018E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.270925E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Meter
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.270925E+12 |
February | 0.000 | 0.184642E+12 |
March | 0.000 | 0.157566E+12 |
April | 0.000 | 0.608263E+11 |
May | 0.000 | 0.551158E+10 |
June | 0.000 | 0.497827E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2417705.577 |
September | 0.000 | 0.353771E+10 |
October | 0.000 | 0.466378E+11 |
November | 0.000 | 0.118898E+12 |
December | 0.000 | 0.251584E+12 |
Annual Sum or Average | 0.110018E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.270925E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.270925E+12 |
February | 0.000 | 0.184642E+12 |
March | 0.000 | 0.157566E+12 |
April | 0.000 | 0.608263E+11 |
May | 0.000 | 0.551158E+10 |
June | 0.000 | 0.497827E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2417705.577 |
September | 0.000 | 0.353771E+10 |
October | 0.000 | 0.466378E+11 |
November | 0.000 | 0.118898E+12 |
December | 0.000 | 0.251584E+12 |
Annual Sum or Average | 0.110018E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.270925E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.270925E+12 |
February | 0.000 | 0.184642E+12 |
March | 0.000 | 0.157566E+12 |
April | 0.000 | 0.608263E+11 |
May | 0.000 | 0.551158E+10 |
June | 0.000 | 0.497827E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2417705.577 |
September | 0.000 | 0.353771E+10 |
October | 0.000 | 0.466378E+11 |
November | 0.000 | 0.118898E+12 |
December | 0.000 | 0.251584E+12 |
Annual Sum or Average | 0.110018E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.270925E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.270925E+12 |
February | 0.000 | 0.184642E+12 |
March | 0.000 | 0.157566E+12 |
April | 0.000 | 0.608263E+11 |
May | 0.000 | 0.551158E+10 |
June | 0.000 | 0.497827E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2417705.577 |
September | 0.000 | 0.353771E+10 |
October | 0.000 | 0.466378E+11 |
November | 0.000 | 0.118898E+12 |
December | 0.000 | 0.251584E+12 |
Annual Sum or Average | 0.110018E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.270925E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.270925E+12 |
February | 0.000 | 0.184642E+12 |
March | 0.000 | 0.157566E+12 |
April | 0.000 | 0.608263E+11 |
May | 0.000 | 0.551158E+10 |
June | 0.000 | 0.497827E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2417705.577 |
September | 0.000 | 0.353771E+10 |
October | 0.000 | 0.466378E+11 |
November | 0.000 | 0.118898E+12 |
December | 0.000 | 0.251584E+12 |
Annual Sum or Average | 0.110018E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.270925E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Meter
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.270925E+12 |
February | 0.000 | 0.184642E+12 |
March | 0.000 | 0.157566E+12 |
April | 0.000 | 0.608263E+11 |
May | 0.000 | 0.551158E+10 |
June | 0.000 | 0.497827E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2417705.577 |
September | 0.000 | 0.353771E+10 |
October | 0.000 | 0.466378E+11 |
November | 0.000 | 0.118898E+12 |
December | 0.000 | 0.251584E+12 |
Annual Sum or Average | 0.110018E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.270925E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Meter
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.270925E+12 |
February | 0.000 | 0.184642E+12 |
March | 0.000 | 0.157566E+12 |
April | 0.000 | 0.608263E+11 |
May | 0.000 | 0.551158E+10 |
June | 0.000 | 0.497827E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 2417705.577 |
September | 0.000 | 0.353771E+10 |
October | 0.000 | 0.466378E+11 |
November | 0.000 | 0.118898E+12 |
December | 0.000 | 0.251584E+12 |
Annual Sum or Average | 0.110018E+13 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.270925E+12 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.364060E+09 | 24109.56 | 06-JAN-00:01 | -32.3 | -32.4 | 0.566279E+09 | 680.12 | 15-JAN-13:09 | -6.9 | -7.6 |
February | 0.558884E+09 | 20260.43 | 25-FEB-00:01 | -24.1 | -24.4 | 0.511263E+09 | 680.12 | 26-FEB-13:09 | -4.3 | -4.6 |
March | 0.906582E+09 | 17193.33 | 03-MAR-00:01 | -17.7 | -17.9 | 0.561521E+09 | 680.12 | 03-MAR-13:20 | -3.3 | -4.1 |
April | 0.282072E+10 | 13738.65 | 05-APR-08:04 | -8.5 | -10.2 | 0.571083E+09 | 898.99 | 23-APR-12:00 | 22.80 | 15.29 |
May | 0.703823E+10 | 32890.99 | 27-MAY-08:62 | 19.02 | 13.46 | 0.690064E+09 | 899.02 | 27-MAY-12:00 | 21.90 | 13.68 |
June | 0.893365E+10 | 28264.91 | 21-JUN-08:62 | 19.18 | 15.22 | 0.709977E+09 | 899.01 | 17-JUN-12:00 | 23.30 | 13.55 |
July | 0.117106E+11 | 33919.40 | 07-JUL-08:62 | 17.38 | 13.03 | 0.751760E+09 | 899.05 | 01-JUL-12:30 | 17.80 | 15.04 |
August | 0.109703E+11 | 33267.49 | 14-AUG-08:62 | 15.60 | 13.82 | 0.739093E+09 | 899.06 | 13-AUG-16:10 | 22.20 | 14.89 |
September | 0.813609E+10 | 35037.24 | 02-SEP-08:62 | 15.37 | 12.65 | 0.679711E+09 | 899.02 | 24-SEP-16:10 | 20.40 | 13.59 |
October | 0.463914E+10 | 12599.65 | 30-OCT-08:04 | -6.1 | -6.6 | 0.599311E+09 | 899.00 | 22-OCT-16:10 | 18.53 | 12.08 |
November | 0.133110E+10 | 15942.92 | 25-NOV-00:01 | -15.0 | -15.4 | 0.549800E+09 | 680.12 | 05-NOV-16:40 | -0.2 | -1.3 |
December | 0.507695E+09 | 19914.73 | 02-DEC-00:01 | -23.5 | -23.7 | 0.569172E+09 | 680.12 | 16-DEC-13:09 | -8.3 | -8.6 |
Annual Sum or Average | 0.579171E+11 | 0.749903E+10 | ||||||||
Minimum of Months | 0.364060E+09 | 12599.65 | -32.3 | -32.4 | 0.511263E+09 | 680.12 | -8.3 | -8.6 | ||
Maximum of Months | 0.117106E+11 | 35037.24 | 19.18 | 15.22 | 0.751760E+09 | 899.06 | 23.30 | 15.29 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37641942.79 | 7449.61 | 18-JAN-09:04 | -12.9 | -13.2 | 0.284732E+09 | 358.34 | 29-JAN-18:00 | -3.3 | -4.0 |
February | 0.172597E+09 | 9583.22 | 01-FEB-20:01 | -25.0 | -25.4 | 0.259019E+09 | 383.93 | 20-FEB-18:00 | 4.40 | 1.27 |
March | 0.463590E+09 | 8228.41 | 18-MAR-08:04 | -16.5 | -17.0 | 0.287900E+09 | 415.53 | 26-MAR-17:00 | 8.90 | 4.39 |
April | 0.147196E+10 | 16048.80 | 23-APR-20:35 | 20.17 | 13.62 | 0.306158E+09 | 449.51 | 23-APR-12:00 | 22.80 | 15.29 |
May | 0.408899E+10 | 20105.06 | 21-MAY-19:50 | 16.57 | 8.91 | 0.361316E+09 | 449.50 | 26-MAY-12:09 | 25.25 | 19.62 |
June | 0.552976E+10 | 18745.68 | 07-JUN-08:62 | 20.18 | 11.25 | 0.359247E+09 | 449.54 | 25-JUN-12:00 | 22.80 | 19.74 |
July | 0.696160E+10 | 17967.59 | 17-JUL-08:62 | 15.00 | 12.42 | 0.375367E+09 | 449.52 | 09-JUL-16:10 | 19.68 | 15.47 |
August | 0.650939E+10 | 18311.79 | 02-AUG-08:62 | 13.58 | 11.91 | 0.370040E+09 | 449.53 | 20-AUG-17:10 | 22.02 | 15.42 |
September | 0.445883E+10 | 18518.60 | 08-SEP-20:15 | 12.77 | 7.65 | 0.353850E+09 | 449.52 | 03-SEP-17:10 | 21.52 | 16.00 |
October | 0.231317E+10 | 19183.85 | 21-OCT-20:54 | 9.40 | 6.25 | 0.320647E+09 | 449.50 | 21-OCT-12:20 | 18.33 | 11.06 |
November | 0.664293E+09 | 7633.04 | 29-NOV-09:04 | -13.8 | -14.3 | 0.284632E+09 | 390.85 | 05-NOV-17:00 | -1.7 | -2.3 |
December | 56190669.72 | 9357.00 | 01-DEC-09:04 | -21.5 | -21.7 | 0.286503E+09 | 356.78 | 31-DEC-18:00 | -5.6 | -5.9 |
Annual Sum or Average | 0.327280E+11 | 0.384941E+10 | ||||||||
Minimum of Months | 37641942.79 | 7449.61 | -25.0 | -25.4 | 0.259019E+09 | 356.78 | -5.6 | -5.9 | ||
Maximum of Months | 0.696160E+10 | 20105.06 | 20.18 | 13.62 | 0.375367E+09 | 449.54 | 25.25 | 19.74 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12925735.86 | 9353.59 | 21-JAN-08:03 | -22.1 | -22.3 | 0.169007E+09 | 340.06 | 28-JAN-13:09 | -10.4 | -11.6 |
February | 83396264.08 | 9486.39 | 24-FEB-08:04 | -23.7 | -24.0 | 0.153530E+09 | 340.06 | 04-FEB-13:09 | 5.37 | 1.21 |
March | 0.266901E+09 | 8948.10 | 18-MAR-07:03 | -20.6 | -20.8 | 0.173597E+09 | 340.06 | 11-MAR-13:09 | -1.7 | -4.2 |
April | 0.110053E+10 | 5443.66 | 06-APR-07:02 | -4.6 | -5.6 | 0.177204E+09 | 434.72 | 22-APR-12:00 | 16.10 | 6.64 |
May | 0.287387E+10 | 23194.20 | 20-MAY-07:01 | 6.20 | 3.45 | 0.216258E+09 | 449.49 | 27-MAY-12:00 | 21.90 | 13.68 |
June | 0.396502E+10 | 21207.31 | 16-JUN-07:02 | 12.43 | 10.81 | 0.221552E+09 | 449.50 | 17-JUN-12:00 | 23.30 | 13.55 |
July | 0.500168E+10 | 20623.72 | 08-JUL-07:02 | 13.40 | 11.19 | 0.224038E+09 | 449.52 | 01-JUL-12:09 | 19.27 | 15.51 |
August | 0.473526E+10 | 20753.58 | 18-AUG-07:02 | 11.28 | 10.55 | 0.229765E+09 | 449.51 | 05-AUG-12:09 | 20.60 | 14.58 |
September | 0.319066E+10 | 27501.50 | 06-SEP-07:01 | 4.05 | 3.63 | 0.209718E+09 | 449.51 | 02-SEP-12:09 | 19.50 | 14.40 |
October | 0.173546E+10 | 26598.53 | 23-OCT-07:01 | 5.60 | 4.05 | 0.182525E+09 | 449.49 | 21-OCT-12:20 | 18.33 | 11.06 |
November | 0.448129E+09 | 8508.97 | 25-NOV-08:04 | -18.2 | -18.6 | 0.164646E+09 | 354.20 | 01-NOV-17:40 | 13.70 | 11.40 |
December | 18453148.74 | 8832.25 | 08-DEC-08:04 | -19.9 | -20.2 | 0.168813E+09 | 340.06 | 16-DEC-13:09 | -8.3 | -8.6 |
Annual Sum or Average | 0.234323E+11 | 0.229065E+10 | ||||||||
Minimum of Months | 12925735.86 | 5443.66 | -23.7 | -24.0 | 0.153530E+09 | 340.06 | -10.4 | -11.6 | ||
Maximum of Months | 0.500168E+10 | 27501.50 | 13.40 | 11.19 | 0.229765E+09 | 449.52 | 23.30 | 15.51 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11854197.42 | 8056.34 | 18-JAN-08:04 | -13.8 | -14.0 | 0.168998E+09 | 340.06 | 28-JAN-13:09 | -10.4 | -11.6 |
February | 63404665.58 | 8497.10 | 11-FEB-08:04 | -15.5 | -15.9 | 0.153514E+09 | 340.06 | 04-FEB-13:09 | 5.37 | 1.21 |
March | 0.233848E+09 | 8961.55 | 23-MAR-07:03 | -17.6 | -17.9 | 0.173520E+09 | 340.05 | 11-MAR-13:09 | -1.7 | -4.2 |
April | 0.110403E+10 | 7496.23 | 05-APR-07:03 | -11.2 | -12.1 | 0.173835E+09 | 407.65 | 22-APR-12:00 | 16.10 | 6.64 |
May | 0.300373E+10 | 20728.67 | 19-MAY-07:02 | 14.87 | 10.67 | 0.211081E+09 | 449.51 | 27-MAY-12:00 | 21.90 | 13.68 |
June | 0.394946E+10 | 19563.13 | 07-JUN-07:02 | 19.50 | 11.25 | 0.219910E+09 | 449.50 | 17-JUN-12:00 | 23.30 | 13.55 |
July | 0.499071E+10 | 20111.71 | 17-JUL-07:02 | 14.50 | 12.48 | 0.223567E+09 | 449.52 | 01-JUL-12:39 | 17.07 | 14.76 |
August | 0.472601E+10 | 21264.04 | 03-AUG-07:02 | 11.97 | 11.24 | 0.229168E+09 | 449.51 | 19-AUG-12:20 | 20.57 | 14.09 |
September | 0.335251E+10 | 21400.39 | 08-SEP-07:02 | 11.28 | 10.32 | 0.204704E+09 | 449.50 | 09-SEP-12:00 | 18.30 | 10.30 |
October | 0.172794E+10 | 6979.94 | 23-OCT-07:01 | 5.60 | 4.05 | 0.178911E+09 | 449.49 | 21-OCT-12:20 | 18.33 | 11.06 |
November | 0.410775E+09 | 8532.80 | 29-NOV-08:04 | -15.8 | -16.1 | 0.164014E+09 | 340.06 | 18-NOV-13:50 | 5.00 | 1.48 |
December | 14158447.83 | 8115.22 | 01-DEC-08:04 | -21.0 | -21.2 | 0.168798E+09 | 340.06 | 16-DEC-13:09 | -8.3 | -8.6 |
Annual Sum or Average | 0.235884E+11 | 0.227002E+10 | ||||||||
Minimum of Months | 11854197.42 | 6979.94 | -21.0 | -21.2 | 0.153514E+09 | 340.05 | -10.4 | -11.6 | ||
Maximum of Months | 0.499071E+10 | 21400.39 | 19.50 | 12.48 | 0.229168E+09 | 449.52 | 23.30 | 14.76 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8421425.09 | 7653.58 | 22-JAN-09:04 | -11.9 | -12.5 | 0.168997E+09 | 340.06 | 28-JAN-13:09 | -10.4 | -11.6 |
February | 43708716.43 | 8478.19 | 11-FEB-08:04 | -15.5 | -15.9 | 0.153510E+09 | 340.06 | 04-FEB-13:09 | 5.37 | 1.21 |
March | 0.173539E+09 | 7768.94 | 11-MAR-08:04 | -12.3 | -12.5 | 0.173510E+09 | 340.05 | 11-MAR-13:09 | -1.7 | -4.2 |
April | 0.913708E+09 | 7508.27 | 05-APR-07:03 | -11.2 | -12.1 | 0.172541E+09 | 398.59 | 22-APR-12:00 | 16.10 | 6.64 |
May | 0.274026E+10 | 18860.89 | 27-MAY-07:02 | 17.20 | 13.07 | 0.208752E+09 | 449.51 | 27-MAY-12:00 | 21.90 | 13.68 |
June | 0.369566E+10 | 18608.83 | 21-JUN-07:02 | 16.57 | 14.02 | 0.219010E+09 | 449.50 | 17-JUN-12:00 | 23.30 | 13.55 |
July | 0.478983E+10 | 19906.06 | 17-JUL-07:02 | 14.50 | 12.48 | 0.223367E+09 | 449.52 | 01-JUL-12:39 | 17.07 | 14.76 |
August | 0.451166E+10 | 21005.24 | 02-AUG-07:02 | 12.88 | 11.28 | 0.228835E+09 | 449.51 | 19-AUG-12:20 | 20.57 | 14.09 |
September | 0.311097E+10 | 20941.61 | 02-SEP-07:02 | 13.17 | 11.14 | 0.202778E+09 | 449.50 | 09-SEP-12:00 | 18.30 | 10.30 |
October | 0.149343E+10 | 5065.30 | 09-OCT-08:05 | -1.1 | -2.2 | 0.177856E+09 | 449.49 | 21-OCT-12:30 | 18.60 | 11.13 |
November | 0.310432E+09 | 7249.77 | 24-NOV-08:04 | -10.0 | -10.6 | 0.163854E+09 | 340.06 | 18-NOV-13:00 | 5.00 | 1.48 |
December | 11036467.79 | 8429.13 | 10-DEC-09:04 | -26.6 | -26.8 | 0.168795E+09 | 340.06 | 16-DEC-13:09 | -8.3 | -8.6 |
Annual Sum or Average | 0.218026E+11 | 0.226181E+10 | ||||||||
Minimum of Months | 8421425.09 | 5065.30 | -26.6 | -26.8 | 0.153510E+09 | 340.05 | -10.4 | -11.6 | ||
Maximum of Months | 0.478983E+10 | 21005.24 | 17.20 | 14.02 | 0.228835E+09 | 449.52 | 23.30 | 14.76 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9911998.01 | 11720.96 | 29-JAN-10:04 | -4.2 | -4.6 | 0.577623E+09 | 906.81 | 14-JAN-15:00 | -12.8 | -13.3 |
February | 27238917.06 | 13409.08 | 23-FEB-09:04 | -7.7 | -8.6 | 0.525902E+09 | 906.81 | 04-FEB-15:09 | 7.80 | 2.57 |
March | 0.117498E+09 | 13444.63 | 10-MAR-09:04 | -7.9 | -8.2 | 0.595766E+09 | 906.81 | 25-MAR-14:09 | 0.60 | -1.0 |
April | 0.104179E+10 | 13316.29 | 04-APR-08:04 | -7.6 | -9.7 | 0.583909E+09 | 1097.02 | 22-APR-14:00 | 18.30 | 7.79 |
May | 0.386516E+10 | 31694.07 | 27-MAY-08:62 | 19.02 | 13.46 | 0.698305E+09 | 1198.70 | 27-MAY-14:00 | 22.20 | 14.07 |
June | 0.549741E+10 | 29331.80 | 21-JUN-08:62 | 19.18 | 15.22 | 0.742635E+09 | 1198.66 | 17-JUN-14:09 | 23.90 | 13.77 |
July | 0.736575E+10 | 33510.35 | 07-JUL-08:62 | 17.38 | 13.03 | 0.763115E+09 | 1198.56 | 01-JUL-14:09 | 21.78 | 16.77 |
August | 0.686708E+10 | 32628.09 | 14-AUG-08:62 | 15.60 | 13.82 | 0.781447E+09 | 1198.67 | 05-AUG-14:00 | 22.20 | 14.42 |
September | 0.446593E+10 | 33424.87 | 02-SEP-08:62 | 15.37 | 12.65 | 0.683784E+09 | 1198.66 | 02-SEP-14:00 | 17.80 | 14.75 |
October | 0.179794E+10 | 12691.39 | 30-OCT-08:04 | -6.1 | -6.6 | 0.602012E+09 | 1198.64 | 21-OCT-14:09 | 20.00 | 11.40 |
November | 0.224085E+09 | 13731.74 | 07-NOV-09:04 | -8.4 | -9.2 | 0.557260E+09 | 906.80 | 18-NOV-15:09 | 4.90 | 1.39 |
December | 14499801.56 | 12211.19 | 07-DEC-09:04 | -7.8 | -7.9 | 0.578602E+09 | 906.81 | 16-DEC-15:09 | -5.6 | -6.2 |
Annual Sum or Average | 0.312943E+11 | 0.769036E+10 | ||||||||
Minimum of Months | 9911998.01 | 11720.96 | -8.4 | -9.7 | 0.525902E+09 | 906.80 | -12.8 | -13.3 | ||
Maximum of Months | 0.736575E+10 | 33510.35 | 19.18 | 15.22 | 0.781447E+09 | 1198.70 | 23.90 | 16.77 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3808785.42 | 6794.68 | 20-JAN-09:04 | -8.3 | -8.9 | 0.288811E+09 | 453.40 | 14-JAN-15:00 | -12.8 | -13.3 |
February | 9032476.00 | 6722.67 | 23-FEB-09:04 | -7.7 | -8.6 | 0.262951E+09 | 453.40 | 04-FEB-15:09 | 7.80 | 2.57 |
March | 49098525.64 | 7041.87 | 11-MAR-09:04 | -9.4 | -9.9 | 0.297880E+09 | 453.40 | 25-MAR-14:09 | 0.60 | -1.0 |
April | 0.453468E+09 | 6851.51 | 05-APR-08:04 | -8.5 | -10.2 | 0.291206E+09 | 541.82 | 22-APR-14:00 | 18.30 | 7.79 |
May | 0.182684E+10 | 15416.43 | 27-MAY-08:62 | 19.02 | 13.46 | 0.347647E+09 | 599.35 | 27-MAY-14:00 | 22.20 | 14.07 |
June | 0.270347E+10 | 14432.82 | 26-JUN-08:62 | 18.58 | 16.33 | 0.370361E+09 | 599.33 | 17-JUN-14:09 | 23.90 | 13.77 |
July | 0.370604E+10 | 17919.79 | 07-JUL-08:62 | 17.38 | 13.03 | 0.381418E+09 | 599.28 | 01-JUL-14:09 | 21.78 | 16.77 |
August | 0.342627E+10 | 17457.62 | 14-AUG-08:62 | 15.60 | 13.82 | 0.390514E+09 | 599.31 | 19-AUG-14:09 | 21.78 | 14.60 |
September | 0.213530E+10 | 17864.31 | 02-SEP-08:62 | 15.37 | 12.65 | 0.340997E+09 | 599.33 | 02-SEP-14:09 | 14.97 | 13.41 |
October | 0.826071E+09 | 6362.65 | 30-OCT-08:04 | -6.1 | -6.6 | 0.300660E+09 | 599.32 | 21-OCT-14:09 | 20.00 | 11.40 |
November | 90518336.40 | 7234.22 | 23-NOV-10:04 | -10.0 | -10.5 | 0.278574E+09 | 453.40 | 25-NOV-15:09 | -13.9 | -14.6 |
December | 6448923.50 | 6709.61 | 07-DEC-09:04 | -7.8 | -7.9 | 0.289300E+09 | 453.41 | 16-DEC-15:09 | -5.6 | -6.2 |
Annual Sum or Average | 0.152364E+11 | 0.384032E+10 | ||||||||
Minimum of Months | 3808785.42 | 6362.65 | -10.0 | -10.5 | 0.262951E+09 | 453.40 | -13.9 | -14.6 | ||
Maximum of Months | 0.370604E+10 | 17919.79 | 19.02 | 16.33 | 0.390514E+09 | 599.35 | 23.90 | 16.77 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4376779.66 | 9666.05 | 23-JAN-09:05 | -22.1 | -22.3 | 0.288811E+09 | 453.40 | 14-JAN-15:00 | -12.8 | -13.3 |
February | 9388913.04 | 6726.26 | 23-FEB-09:04 | -7.7 | -8.6 | 0.262951E+09 | 453.40 | 04-FEB-15:09 | 7.80 | 2.57 |
March | 42974442.65 | 6969.55 | 11-MAR-09:04 | -9.4 | -9.9 | 0.297877E+09 | 453.40 | 25-MAR-14:09 | 0.60 | -1.0 |
April | 0.410298E+09 | 6838.05 | 05-APR-08:04 | -8.5 | -10.2 | 0.290601E+09 | 537.51 | 22-APR-14:00 | 18.30 | 7.79 |
May | 0.172585E+10 | 14504.13 | 26-MAY-08:62 | 20.60 | 16.94 | 0.346177E+09 | 599.35 | 27-MAY-14:00 | 22.20 | 14.07 |
June | 0.260439E+10 | 14369.05 | 26-JUN-08:62 | 18.58 | 16.33 | 0.369267E+09 | 599.33 | 17-JUN-14:09 | 23.90 | 13.77 |
July | 0.362042E+10 | 17873.44 | 07-JUL-08:62 | 17.38 | 13.03 | 0.381265E+09 | 599.28 | 01-JUL-14:09 | 21.78 | 16.77 |
August | 0.334136E+10 | 17408.64 | 14-AUG-08:62 | 15.60 | 13.82 | 0.390217E+09 | 599.31 | 19-AUG-14:09 | 21.78 | 14.60 |
September | 0.205531E+10 | 17827.04 | 02-SEP-08:62 | 15.37 | 12.65 | 0.340043E+09 | 599.33 | 02-SEP-14:09 | 14.97 | 13.41 |
October | 0.776746E+09 | 6367.44 | 30-OCT-08:04 | -6.1 | -6.6 | 0.300323E+09 | 599.32 | 21-OCT-14:09 | 20.00 | 11.40 |
November | 80711413.75 | 7232.47 | 23-NOV-10:04 | -10.0 | -10.5 | 0.278529E+09 | 453.40 | 25-NOV-15:09 | -13.9 | -14.6 |
December | 6280062.50 | 6699.48 | 07-DEC-09:04 | -7.8 | -7.9 | 0.289300E+09 | 453.41 | 16-DEC-15:09 | -5.6 | -6.2 |
Annual Sum or Average | 0.146781E+11 | 0.383536E+10 | ||||||||
Minimum of Months | 4376779.66 | 6367.44 | -22.1 | -22.3 | 0.262951E+09 | 453.40 | -13.9 | -14.6 | ||
Maximum of Months | 0.362042E+10 | 17873.44 | 20.60 | 16.94 | 0.390217E+09 | 599.35 | 23.90 | 16.77 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2911093.80 | 6252.84 | 20-JAN-09:04 | -8.3 | -8.9 | 0.288811E+09 | 453.40 | 14-JAN-15:00 | -12.8 | -13.3 |
February | 6496289.06 | 6721.48 | 23-FEB-09:04 | -7.7 | -8.6 | 0.262951E+09 | 453.40 | 04-FEB-15:09 | 7.80 | 2.57 |
March | 30400869.91 | 6683.13 | 10-MAR-09:04 | -7.9 | -8.2 | 0.297872E+09 | 453.40 | 25-MAR-14:09 | 0.60 | -1.0 |
April | 0.319871E+09 | 6609.26 | 04-APR-08:04 | -7.6 | -9.7 | 0.289317E+09 | 527.67 | 22-APR-14:00 | 18.30 | 7.79 |
May | 0.150758E+10 | 14430.84 | 26-MAY-08:62 | 20.60 | 16.94 | 0.342942E+09 | 599.35 | 27-MAY-14:50 | 22.17 | 14.02 |
June | 0.240784E+10 | 14315.22 | 26-JUN-08:62 | 18.58 | 16.33 | 0.366956E+09 | 599.33 | 17-JUN-14:09 | 23.90 | 13.77 |
July | 0.346244E+10 | 16722.88 | 01-JUL-08:62 | 17.57 | 14.63 | 0.380873E+09 | 599.29 | 01-JUL-14:09 | 21.78 | 16.77 |
August | 0.318206E+10 | 15898.50 | 10-AUG-08:61 | 15.87 | 15.41 | 0.389473E+09 | 599.31 | 19-AUG-14:09 | 21.78 | 14.60 |
September | 0.188621E+10 | 15512.06 | 02-SEP-08:62 | 15.37 | 12.65 | 0.338075E+09 | 599.33 | 02-SEP-14:09 | 14.97 | 13.41 |
October | 0.665282E+09 | 6358.12 | 30-OCT-08:04 | -6.1 | -6.6 | 0.299635E+09 | 599.32 | 21-OCT-14:09 | 20.00 | 11.40 |
November | 61341524.13 | 7179.72 | 23-NOV-10:04 | -10.0 | -10.5 | 0.278415E+09 | 453.40 | 25-NOV-15:09 | -13.9 | -14.6 |
December | 4835998.92 | 6669.06 | 07-DEC-09:04 | -7.8 | -7.9 | 0.289300E+09 | 453.41 | 16-DEC-15:09 | -5.6 | -6.2 |
Annual Sum or Average | 0.135373E+11 | 0.382462E+10 | ||||||||
Minimum of Months | 2911093.80 | 6252.84 | -10.0 | -10.5 | 0.262951E+09 | 453.40 | -13.9 | -14.6 | ||
Maximum of Months | 0.346244E+10 | 16722.88 | 20.60 | 16.94 | 0.389473E+09 | 599.35 | 23.90 | 16.77 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1725017.53 | 5710.38 | 19-JAN-09:04 | -3.8 | -3.9 | 0.288811E+09 | 453.40 | 14-JAN-15:00 | -12.8 | -13.3 |
February | 4162612.38 | 6606.83 | 23-FEB-09:04 | -7.7 | -8.6 | 0.262951E+09 | 453.41 | 04-FEB-15:09 | 7.80 | 2.57 |
March | 7670710.81 | 6183.27 | 20-MAR-08:04 | -6.1 | -6.4 | 0.297871E+09 | 453.41 | 25-MAR-14:09 | 0.60 | -1.0 |
April | 0.132671E+09 | 5831.38 | 02-APR-09:04 | -4.5 | -6.0 | 0.287349E+09 | 516.92 | 23-APR-14:00 | 25.60 | 16.46 |
May | 0.102150E+10 | 4507.66 | 01-MAY-08:04 | 1.73 | -2.1 | 0.337157E+09 | 599.35 | 27-MAY-14:50 | 22.17 | 14.02 |
June | 0.207323E+10 | 13104.09 | 28-JUN-08:61 | 25.37 | 20.51 | 0.362356E+09 | 599.33 | 17-JUN-14:09 | 23.90 | 13.77 |
July | 0.327577E+10 | 14605.72 | 14-JUL-08:61 | 19.78 | 18.12 | 0.379684E+09 | 599.30 | 29-JUL-14:09 | 29.50 | 21.34 |
August | 0.295068E+10 | 16960.94 | 10-AUG-08:61 | 15.87 | 15.41 | 0.387291E+09 | 599.32 | 19-AUG-14:09 | 21.78 | 14.60 |
September | 0.155441E+10 | 11363.28 | 01-SEP-08:62 | 18.17 | 16.90 | 0.334308E+09 | 599.33 | 02-SEP-14:09 | 14.97 | 13.41 |
October | 0.404360E+09 | 6277.73 | 30-OCT-08:04 | -6.1 | -6.6 | 0.298582E+09 | 599.32 | 21-OCT-14:09 | 20.00 | 11.40 |
November | 24842544.91 | 6798.08 | 07-NOV-09:04 | -8.4 | -9.2 | 0.278254E+09 | 453.40 | 25-NOV-15:09 | -13.9 | -14.6 |
December | 3020030.41 | 6184.42 | 07-DEC-09:04 | -7.8 | -7.9 | 0.289301E+09 | 453.41 | 16-DEC-15:09 | -5.6 | -6.2 |
Annual Sum or Average | 0.114540E+11 | 0.380392E+10 | ||||||||
Minimum of Months | 1725017.53 | 4507.66 | -8.4 | -9.2 | 0.262951E+09 | 453.40 | -13.9 | -14.6 | ||
Maximum of Months | 0.327577E+10 | 16960.94 | 25.37 | 20.51 | 0.387291E+09 | 599.35 | 29.50 | 21.34 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143376E+11 | 64941.58 | 01-JAN-08:61 | -26.7 |
February | 0.874153E+10 | 64944.61 | 27-FEB-08:61 | -17.9 |
March | 0.666079E+10 | 64985.40 | 18-MAR-07:01 | -20.6 |
April | 0.180939E+10 | 58435.31 | 11-APR-08:61 | 6.33 |
May | 0.102089E+09 | 56514.08 | 02-MAY-08:61 | 8.18 |
June | 70078030.15 | 1924.23 | 30-JUN-08:06 | 25.97 |
July | 66578294.51 | 1260.47 | 30-JUL-07:05 | 21.65 |
August | 69274245.18 | 1132.05 | 27-AUG-07:03 | 12.88 |
September | 73861521.38 | 2497.07 | 22-SEP-08:20 | 10.20 |
October | 0.760271E+09 | 55894.25 | 14-OCT-08:61 | 1.47 |
November | 0.402878E+10 | 64463.46 | 25-NOV-08:61 | -18.2 |
December | 0.131681E+11 | 64978.23 | 20-DEC-08:61 | -29.2 |
Annual Sum or Average | 0.498883E+11 | |||
Minimum of Months | 66578294.51 | 1132.05 | -29.2 | |
Maximum of Months | 0.143376E+11 | 64985.40 | 25.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.549423E+10 | 32510.64 | 01-JAN-08:61 | -26.7 |
February | 0.303919E+10 | 32432.38 | 17-FEB-08:61 | -28.5 |
March | 0.218256E+10 | 32396.49 | 06-MAR-08:61 | -18.7 |
April | 0.470441E+09 | 27106.09 | 06-APR-08:61 | -2.4 |
May | 95494929.20 | 2281.31 | 01-MAY-08:02 | 1.73 |
June | 86709354.94 | 1523.76 | 30-JUN-08:08 | 25.97 |
July | 84620957.97 | 1471.43 | 16-JUL-07:05 | 17.38 |
August | 89699927.85 | 1453.76 | 27-AUG-07:03 | 12.88 |
September | 88395490.31 | 1398.89 | 03-SEP-07:04 | 14.50 |
October | 0.216522E+09 | 17480.14 | 30-OCT-08:61 | -6.1 |
November | 0.133314E+10 | 26322.81 | 13-NOV-09:01 | -5.7 |
December | 0.504971E+10 | 32527.51 | 20-DEC-08:61 | -29.2 |
Annual Sum or Average | 0.182307E+11 | |||
Minimum of Months | 84620957.97 | 1398.89 | -29.2 | |
Maximum of Months | 0.549423E+10 | 32527.51 | 25.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.611764E+10 | 35269.90 | 01-JAN-08:61 | -26.7 |
February | 0.353466E+10 | 35144.23 | 19-FEB-08:61 | -23.5 |
March | 0.254892E+10 | 34941.81 | 06-MAR-07:01 | -19.3 |
April | 0.621633E+09 | 30467.92 | 10-APR-07:01 | -0.2 |
May | 0.123728E+09 | 3672.15 | 01-MAY-07:02 | -0.9 |
June | 0.131185E+09 | 2322.91 | 29-JUN-19:12 | 30.37 |
July | 0.150250E+09 | 2077.61 | 29-JUL-17:12 | 29.43 |
August | 0.122815E+09 | 1320.70 | 08-AUG-19:03 | 26.42 |
September | 0.108761E+09 | 1103.97 | 10-SEP-07:01 | 6.75 |
October | 0.328381E+09 | 19809.74 | 30-OCT-07:01 | -9.0 |
November | 0.171972E+10 | 29212.60 | 27-NOV-08:61 | -6.7 |
December | 0.561833E+10 | 35269.88 | 25-DEC-08:61 | -27.8 |
Annual Sum or Average | 0.211260E+11 | |||
Minimum of Months | 0.108761E+09 | 1103.97 | -27.8 | |
Maximum of Months | 0.611764E+10 | 35269.90 | 30.37 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.638552E+10 | 35189.81 | 01-JAN-08:61 | -26.7 |
February | 0.371178E+10 | 35060.78 | 19-FEB-08:61 | -23.5 |
March | 0.269987E+10 | 34860.38 | 06-MAR-07:01 | -19.3 |
April | 0.652148E+09 | 30716.74 | 09-APR-08:61 | 1.70 |
May | 56391662.78 | 16784.44 | 01-MAY-07:02 | -0.9 |
June | 53992862.26 | 1803.46 | 29-JUN-19:03 | 30.73 |
July | 61199082.74 | 1553.57 | 23-JUL-16:02 | 29.72 |
August | 46973564.63 | 814.89 | 08-AUG-19:03 | 26.42 |
September | 44326502.66 | 807.40 | 29-SEP-07:09 | 7.88 |
October | 0.337346E+09 | 28212.55 | 30-OCT-07:01 | -9.0 |
November | 0.186703E+10 | 29455.98 | 08-NOV-08:61 | -3.0 |
December | 0.585361E+10 | 35188.37 | 25-DEC-08:61 | -27.8 |
Annual Sum or Average | 0.217702E+11 | |||
Minimum of Months | 44326502.66 | 807.40 | -27.8 | |
Maximum of Months | 0.638552E+10 | 35189.81 | 30.73 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.680825E+10 | 35095.12 | 01-JAN-08:61 | -26.7 |
February | 0.405935E+10 | 34944.40 | 19-FEB-08:61 | -23.5 |
March | 0.302414E+10 | 34746.23 | 06-MAR-07:01 | -19.3 |
April | 0.792845E+09 | 30670.16 | 09-APR-08:61 | 1.70 |
May | 62725738.99 | 21503.62 | 01-MAY-07:02 | -0.9 |
June | 54280118.32 | 1809.12 | 29-JUN-19:03 | 30.73 |
July | 61479834.25 | 1557.85 | 23-JUL-16:02 | 29.72 |
August | 47000840.10 | 820.46 | 08-AUG-19:03 | 26.42 |
September | 44749453.07 | 1012.31 | 28-SEP-07:07 | 6.78 |
October | 0.427348E+09 | 28165.62 | 30-OCT-07:01 | -9.0 |
November | 0.212621E+10 | 29625.06 | 30-NOV-08:62 | -1.1 |
December | 0.626343E+10 | 35118.00 | 25-DEC-08:61 | -27.8 |
Annual Sum or Average | 0.237718E+11 | |||
Minimum of Months | 44749453.07 | 820.46 | -27.8 | |
Maximum of Months | 0.680825E+10 | 35118.00 | 30.73 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139643E+11 | 63660.36 | 01-JAN-09:01 | -26.3 |
February | 0.853836E+10 | 63627.27 | 27-FEB-08:61 | -17.9 |
March | 0.661808E+10 | 63607.46 | 16-MAR-07:01 | -20.8 |
April | 0.189611E+10 | 61327.71 | 04-APR-07:01 | -8.2 |
May | 0.123480E+09 | 57745.32 | 02-MAY-08:61 | 8.18 |
June | 81781944.53 | 2933.68 | 24-JUN-17:03 | 29.22 |
July | 0.100774E+09 | 3114.51 | 23-JUL-16:02 | 29.72 |
August | 75764770.97 | 1232.22 | 26-AUG-17:03 | 25.63 |
September | 76586086.72 | 5168.80 | 30-SEP-08:10 | 10.97 |
October | 0.114482E+10 | 57221.76 | 31-OCT-08:61 | 7.15 |
November | 0.474711E+10 | 63358.34 | 27-NOV-08:61 | -6.7 |
December | 0.129552E+11 | 63759.42 | 20-DEC-08:61 | -29.2 |
Annual Sum or Average | 0.503223E+11 | |||
Minimum of Months | 75764770.97 | 1232.22 | -29.2 | |
Maximum of Months | 0.139643E+11 | 63759.42 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.771916E+10 | 33359.74 | 08-JAN-09:01 | -23.2 |
February | 0.481337E+10 | 33328.00 | 27-FEB-08:61 | -17.9 |
March | 0.380644E+10 | 33317.44 | 16-MAR-07:01 | -20.8 |
April | 0.116804E+10 | 30862.63 | 04-APR-07:01 | -8.2 |
May | 79551133.12 | 30378.24 | 02-MAY-08:61 | 8.18 |
June | 45508486.80 | 1491.87 | 24-JUN-17:03 | 29.22 |
July | 55656570.23 | 1576.63 | 23-JUL-16:02 | 29.72 |
August | 42543034.29 | 642.97 | 26-AUG-17:03 | 25.63 |
September | 44094488.26 | 2644.11 | 23-SEP-08:62 | 7.07 |
October | 0.725478E+09 | 30107.32 | 31-OCT-08:61 | 7.15 |
November | 0.275772E+10 | 33176.10 | 27-NOV-08:61 | -6.7 |
December | 0.717902E+10 | 33365.46 | 24-DEC-09:01 | -30.9 |
Annual Sum or Average | 0.284366E+11 | |||
Minimum of Months | 42543034.29 | 642.97 | -30.9 | |
Maximum of Months | 0.771916E+10 | 33365.46 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.779026E+10 | 33328.70 | 01-JAN-09:01 | -26.3 |
February | 0.489635E+10 | 33310.67 | 27-FEB-08:61 | -17.9 |
March | 0.390516E+10 | 33319.90 | 18-MAR-07:01 | -20.6 |
April | 0.124053E+10 | 33166.00 | 04-APR-07:01 | -8.2 |
May | 91023850.97 | 30389.98 | 02-MAY-08:61 | 8.18 |
June | 45684864.35 | 1494.91 | 24-JUN-17:03 | 29.22 |
July | 55770458.42 | 1579.05 | 29-JUL-17:03 | 29.72 |
August | 42571848.48 | 645.38 | 26-AUG-17:03 | 25.63 |
September | 47777501.00 | 3864.58 | 23-SEP-08:62 | 7.07 |
October | 0.769271E+09 | 30111.52 | 31-OCT-08:61 | 7.15 |
November | 0.284210E+10 | 33244.68 | 23-NOV-09:01 | -10.0 |
December | 0.725187E+10 | 33336.31 | 25-DEC-09:01 | -26.7 |
Annual Sum or Average | 0.289784E+11 | |||
Minimum of Months | 42571848.48 | 645.38 | -26.7 | |
Maximum of Months | 0.779026E+10 | 33336.31 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.820738E+10 | 33570.65 | 08-JAN-09:01 | -23.2 |
February | 0.527965E+10 | 33528.75 | 27-FEB-08:61 | -17.9 |
March | 0.433740E+10 | 33540.96 | 18-MAR-07:01 | -20.6 |
April | 0.151563E+10 | 33405.32 | 05-APR-07:01 | -11.2 |
May | 0.130146E+09 | 30700.20 | 02-MAY-08:61 | 8.18 |
June | 46994575.88 | 1504.52 | 24-JUN-17:03 | 29.22 |
July | 56763721.64 | 1584.45 | 29-JUL-17:03 | 29.72 |
August | 43213850.23 | 651.15 | 26-AUG-17:03 | 25.63 |
September | 52944261.21 | 7063.74 | 23-SEP-08:62 | 7.07 |
October | 0.912551E+09 | 30398.46 | 31-OCT-08:61 | 7.15 |
November | 0.316142E+10 | 33461.88 | 23-NOV-09:01 | -10.0 |
December | 0.766148E+10 | 33573.13 | 20-DEC-08:61 | -29.2 |
Annual Sum or Average | 0.314056E+11 | |||
Minimum of Months | 43213850.23 | 651.15 | -29.2 | |
Maximum of Months | 0.820738E+10 | 33573.13 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119433E+11 | 36428.55 | 12-JAN-08:61 | -19.0 |
February | 0.822456E+10 | 36380.53 | 14-FEB-08:61 | -31.2 |
March | 0.695458E+10 | 36317.05 | 18-MAR-07:01 | -20.6 |
April | 0.284977E+10 | 36151.18 | 05-APR-07:01 | -11.2 |
May | 0.330435E+09 | 34131.41 | 10-MAY-08:62 | 13.62 |
June | 53328426.48 | 1547.30 | 24-JUN-17:03 | 29.22 |
July | 60601834.50 | 1605.09 | 29-JUL-17:03 | 29.72 |
August | 47347205.69 | 681.42 | 26-AUG-17:03 | 25.63 |
September | 0.118304E+09 | 17750.53 | 28-SEP-08:62 | 7.30 |
October | 0.153325E+10 | 35761.75 | 30-OCT-07:01 | -9.0 |
November | 0.480415E+10 | 36205.40 | 23-NOV-09:01 | -10.0 |
December | 0.110524E+11 | 36437.25 | 24-DEC-09:01 | -30.9 |
Annual Sum or Average | 0.479721E+11 | |||
Minimum of Months | 47347205.69 | 681.42 | -31.2 | |
Maximum of Months | 0.119433E+11 | 36437.25 | 29.72 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.861445E+10 | 5225.88 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.779459E+10 | 5225.88 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.863227E+10 | 5225.88 | 01-MAR-10:09 | 0.223972E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.835898E+10 | 5225.88 | 01-APR-09:09 | 0.216880E+10 | 1348.26 | 01-APR-09:09 |
May | 0.861445E+10 | 5225.88 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.835898E+10 | 5225.88 | 01-JUN-09:09 | 0.216880E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.863227E+10 | 5225.88 | 01-JUL-09:09 | 0.223972E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.861445E+10 | 5225.88 | 01-AUG-09:09 | 0.223514E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.837681E+10 | 5225.88 | 01-SEP-09:09 | 0.217339E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.861445E+10 | 5225.88 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.832334E+10 | 5225.88 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.865009E+10 | 5225.88 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.101585E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.779459E+10 | 5225.88 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.865009E+10 | 5225.88 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.509120E+10 | 3088.53 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.460666E+10 | 3088.53 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.510174E+10 | 3088.53 | 01-MAR-10:09 | 0.111986E+10 | 674.13 | 01-MAR-10:09 |
April | 0.494022E+10 | 3088.53 | 01-APR-09:09 | 0.108440E+10 | 674.13 | 01-APR-09:09 |
May | 0.509120E+10 | 3088.53 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.494022E+10 | 3088.53 | 01-JUN-09:09 | 0.108440E+10 | 674.13 | 01-JUN-09:09 |
July | 0.510174E+10 | 3088.53 | 01-JUL-09:09 | 0.111986E+10 | 674.13 | 01-JUL-09:09 |
August | 0.509120E+10 | 3088.53 | 01-AUG-09:09 | 0.111757E+10 | 674.13 | 01-AUG-09:09 |
September | 0.495076E+10 | 3088.53 | 01-SEP-09:09 | 0.108669E+10 | 674.13 | 01-SEP-09:09 |
October | 0.509120E+10 | 3088.53 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.491916E+10 | 3088.53 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.511227E+10 | 3088.53 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.600376E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.460666E+10 | 3088.53 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.511227E+10 | 3088.53 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.366929E+10 | 2821.35 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.332289E+10 | 2821.35 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.374627E+10 | 2821.35 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.356024E+10 | 2821.35 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.370778E+10 | 2821.35 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.361797E+10 | 2821.35 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.365005E+10 | 2821.35 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.374627E+10 | 2821.35 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.356024E+10 | 2821.35 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.366929E+10 | 2821.35 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.356024E+10 | 2821.35 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.365005E+10 | 2821.35 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.434606E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.332289E+10 | 2821.35 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.374627E+10 | 2821.35 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.366929E+10 | 2821.35 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.332289E+10 | 2821.35 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.374627E+10 | 2821.35 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.356024E+10 | 2821.35 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.370778E+10 | 2821.35 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.361797E+10 | 2821.35 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.365005E+10 | 2821.35 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.374627E+10 | 2821.35 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.356024E+10 | 2821.35 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.366929E+10 | 2821.35 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.356024E+10 | 2821.35 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.365005E+10 | 2821.35 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.434606E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.332289E+10 | 2821.35 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.374627E+10 | 2821.35 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.366929E+10 | 2821.35 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.332289E+10 | 2821.35 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.374627E+10 | 2821.35 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.356024E+10 | 2821.35 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.370778E+10 | 2821.35 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.361797E+10 | 2821.35 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.365005E+10 | 2821.35 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.374627E+10 | 2821.35 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.356024E+10 | 2821.35 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.366929E+10 | 2821.35 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.356024E+10 | 2821.35 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.365005E+10 | 2821.35 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.434606E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.332289E+10 | 2821.35 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.374627E+10 | 2821.35 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.399227E+10 | 3341.31 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.361622E+10 | 3341.31 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.408344E+10 | 3341.31 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.387452E+10 | 3341.31 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.403786E+10 | 3341.31 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.394289E+10 | 3341.31 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.396948E+10 | 3341.31 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.408344E+10 | 3341.31 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.387452E+10 | 3341.31 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.399227E+10 | 3341.31 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.387452E+10 | 3341.31 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.396948E+10 | 3341.31 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.473109E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.361622E+10 | 3341.31 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.408344E+10 | 3341.31 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.199614E+10 | 1670.66 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.180811E+10 | 1670.66 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.204172E+10 | 1670.66 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.193726E+10 | 1670.66 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.201893E+10 | 1670.66 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.197145E+10 | 1670.66 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.198474E+10 | 1670.66 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.204172E+10 | 1670.66 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.193726E+10 | 1670.66 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.199614E+10 | 1670.66 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.193726E+10 | 1670.66 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.198474E+10 | 1670.66 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.236555E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.180811E+10 | 1670.66 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.204172E+10 | 1670.66 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.199614E+10 | 1670.66 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.180811E+10 | 1670.66 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.204172E+10 | 1670.66 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.193726E+10 | 1670.66 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.201893E+10 | 1670.66 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.197145E+10 | 1670.66 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.198474E+10 | 1670.66 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.204172E+10 | 1670.66 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.193726E+10 | 1670.66 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.199614E+10 | 1670.66 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.193726E+10 | 1670.66 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.198474E+10 | 1670.66 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.236555E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.180811E+10 | 1670.66 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.204172E+10 | 1670.66 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.199614E+10 | 1670.66 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.180811E+10 | 1670.66 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.204172E+10 | 1670.66 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.193726E+10 | 1670.66 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.201893E+10 | 1670.66 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.197145E+10 | 1670.66 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.198474E+10 | 1670.66 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.204172E+10 | 1670.66 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.193726E+10 | 1670.66 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.199614E+10 | 1670.66 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.193726E+10 | 1670.66 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.198474E+10 | 1670.66 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.236555E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.180811E+10 | 1670.66 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.204172E+10 | 1670.66 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.199614E+10 | 1670.66 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.180811E+10 | 1670.66 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.204172E+10 | 1670.66 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.193726E+10 | 1670.66 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.201893E+10 | 1670.66 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.197145E+10 | 1670.66 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.198474E+10 | 1670.66 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.204172E+10 | 1670.66 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.193726E+10 | 1670.66 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.199614E+10 | 1670.66 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.193726E+10 | 1670.66 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.198474E+10 | 1670.66 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.236555E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.180811E+10 | 1670.66 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.204172E+10 | 1670.66 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.861445E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108389E+11 |
February | 0.163016E+10 | 0.779459E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794364E+10 |
March | 0.178954E+10 | 0.863227E+10 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690840E+10 |
April | 0.174484E+10 | 0.835898E+10 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7136178.35 | 0.408537E+10 |
May | 0.179537E+10 | 0.861445E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102837E+09 | 0.178745E+10 |
June | 0.173447E+10 | 0.835898E+10 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250152E+09 | 0.936439E+09 |
July | 0.181028E+10 | 0.863227E+10 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355130E+09 | 0.606687E+09 |
August | 0.178501E+10 | 0.861445E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148136E+09 | 0.949795E+09 |
September | 0.174937E+10 | 0.837681E+10 | 0.217339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7125023.02 | 0.213430E+10 |
October | 0.180574E+10 | 0.861445E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378288E+10 |
November | 0.174613E+10 | 0.832334E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611909E+10 |
December | 0.181481E+10 | 0.865009E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105073E+11 |
Annual Sum or Average | 0.212115E+11 | 0.101585E+12 | 0.263573E+11 | 0.870517E+09 | 0.566003E+11 | ||||
Minimum of Months | 0.163016E+10 | 0.779459E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606687E+09 |
Maximum of Months | 0.181481E+10 | 0.865009E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355130E+09 | 0.108389E+11 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.509120E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545440E+10 |
February | 0.815075E+09 | 0.460666E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393394E+10 |
March | 0.894769E+09 | 0.510174E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348325E+10 |
April | 0.872416E+09 | 0.494022E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3741073.04 | 0.202278E+10 |
May | 0.897684E+09 | 0.509120E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55987752.67 | 0.912363E+09 |
June | 0.867232E+09 | 0.494022E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134125E+09 | 0.457705E+09 |
July | 0.905135E+09 | 0.510174E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192509E+09 | 0.283385E+09 |
August | 0.892501E+09 | 0.509120E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80428603.81 | 0.443416E+09 |
September | 0.874683E+09 | 0.495076E+10 | 0.108669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3902561.05 | 0.107568E+10 |
October | 0.902868E+09 | 0.509120E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192928E+10 |
November | 0.873064E+09 | 0.491916E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302163E+10 |
December | 0.907403E+09 | 0.511227E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525811E+10 |
Annual Sum or Average | 0.106057E+11 | 0.600376E+11 | 0.131787E+11 | 0.470694E+09 | 0.282759E+11 | ||||
Minimum of Months | 0.815075E+09 | 0.460666E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283385E+09 |
Maximum of Months | 0.907403E+09 | 0.511227E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192509E+09 | 0.545440E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557617E+10 |
February | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405789E+10 |
March | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355140E+10 |
April | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2512198.28 | 0.207581E+10 |
May | 0.544247E+09 | 0.370778E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55974832.10 | 0.941800E+09 |
June | 0.532585E+09 | 0.361797E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133067E+09 | 0.480170E+09 |
July | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188514E+09 | 0.304831E+09 |
August | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80329907.99 | 0.468487E+09 |
September | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3901894.63 | 0.110167E+10 |
October | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196718E+10 |
November | 0.518979E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310210E+10 |
December | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539780E+10 |
Annual Sum or Average | 0.638324E+10 | 0.434606E+11 | 0.104672E+11 | 0.464300E+09 | 0.290253E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304831E+09 |
Maximum of Months | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188514E+09 | 0.557617E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557084E+10 |
February | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405283E+10 |
March | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354752E+10 |
April | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2795966.49 | 0.205169E+10 |
May | 0.544247E+09 | 0.370778E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55976682.03 | 0.906176E+09 |
June | 0.532585E+09 | 0.361797E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133125E+09 | 0.467495E+09 |
July | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188786E+09 | 0.301227E+09 |
August | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80341560.10 | 0.463754E+09 |
September | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3901828.07 | 0.106831E+10 |
October | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194164E+10 |
November | 0.518979E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309276E+10 |
December | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539198E+10 |
Annual Sum or Average | 0.638324E+10 | 0.434606E+11 | 0.104672E+11 | 0.464927E+09 | 0.288562E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301227E+09 |
Maximum of Months | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188786E+09 | 0.557084E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556701E+10 |
February | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404876E+10 |
March | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354423E+10 |
April | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2945811.56 | 0.203991E+10 |
May | 0.544247E+09 | 0.370778E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55976807.46 | 0.887379E+09 |
June | 0.532585E+09 | 0.361797E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133224E+09 | 0.459370E+09 |
July | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188850E+09 | 0.298639E+09 |
August | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80343010.75 | 0.460014E+09 |
September | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3901710.48 | 0.105430E+10 |
October | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193165E+10 |
November | 0.518979E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308738E+10 |
December | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538762E+10 |
Annual Sum or Average | 0.638324E+10 | 0.434606E+11 | 0.104672E+11 | 0.465241E+09 | 0.287663E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298639E+09 |
Maximum of Months | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188850E+09 | 0.556701E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.399227E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101764E+11 |
February | 0.167188E+10 | 0.361622E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741880E+10 |
March | 0.189386E+10 | 0.408344E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647176E+10 |
April | 0.180380E+10 | 0.387452E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6009577.42 | 0.372588E+10 |
May | 0.186509E+10 | 0.403786E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100694E+09 | 0.158325E+10 |
June | 0.182945E+10 | 0.394289E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240380E+09 | 0.822918E+09 |
July | 0.183943E+10 | 0.396948E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340076E+09 | 0.553342E+09 |
August | 0.189386E+10 | 0.408344E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144600E+09 | 0.849177E+09 |
September | 0.180380E+10 | 0.387452E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7012571.87 | 0.191160E+10 |
October | 0.183632E+10 | 0.399227E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351608E+10 |
November | 0.176881E+10 | 0.387452E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565994E+10 |
December | 0.183943E+10 | 0.396948E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986111E+10 |
Annual Sum or Average | 0.218821E+11 | 0.473109E+11 | 0.192612E+11 | 0.838773E+09 | 0.525502E+11 | ||||
Minimum of Months | 0.167188E+10 | 0.361622E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553342E+09 |
Maximum of Months | 0.189386E+10 | 0.408344E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340076E+09 | 0.101764E+11 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558574E+10 |
February | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405921E+10 |
March | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355227E+10 |
April | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3394390.37 | 0.202658E+10 |
May | 0.932542E+09 | 0.201893E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55994648.03 | 0.851672E+09 |
June | 0.914724E+09 | 0.197145E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133530E+09 | 0.439931E+09 |
July | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189115E+09 | 0.296670E+09 |
August | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80383539.00 | 0.456498E+09 |
September | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3902690.33 | 0.103620E+10 |
October | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192376E+10 |
November | 0.884402E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309334E+10 |
December | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540606E+10 |
Annual Sum or Average | 0.109410E+11 | 0.236555E+11 | 0.963059E+10 | 0.466320E+09 | 0.287279E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296670E+09 |
Maximum of Months | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189115E+09 | 0.558574E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558508E+10 |
February | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405817E+10 |
March | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355111E+10 |
April | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3469280.42 | 0.202217E+10 |
May | 0.932542E+09 | 0.201893E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55995436.25 | 0.843874E+09 |
June | 0.914724E+09 | 0.197145E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133575E+09 | 0.434512E+09 |
July | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189147E+09 | 0.295245E+09 |
August | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80384105.43 | 0.454567E+09 |
September | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3902672.39 | 0.103152E+10 |
October | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192107E+10 |
November | 0.884402E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309155E+10 |
December | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540524E+10 |
Annual Sum or Average | 0.109410E+11 | 0.236555E+11 | 0.963059E+10 | 0.466473E+09 | 0.286941E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295245E+09 |
Maximum of Months | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189147E+09 | 0.558508E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558077E+10 |
February | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405304E+10 |
March | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354621E+10 |
April | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3652903.94 | 0.201033E+10 |
May | 0.932542E+09 | 0.201893E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55995138.51 | 0.825990E+09 |
June | 0.914724E+09 | 0.197145E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133687E+09 | 0.422526E+09 |
July | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189198E+09 | 0.291646E+09 |
August | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80384022.42 | 0.449828E+09 |
September | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3902905.99 | 0.102134E+10 |
October | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191418E+10 |
November | 0.884402E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308507E+10 |
December | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540029E+10 |
Annual Sum or Average | 0.109410E+11 | 0.236555E+11 | 0.963059E+10 | 0.466820E+09 | 0.286012E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291646E+09 |
Maximum of Months | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189198E+09 | 0.558077E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670942E+10 |
February | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501744E+10 |
March | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422497E+10 |
April | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5145587.70 | 0.252835E+10 |
May | 0.932542E+09 | 0.201893E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58292969.57 | 0.104465E+10 |
June | 0.914724E+09 | 0.197145E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142976E+09 | 0.544362E+09 |
July | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197772E+09 | 0.394882E+09 |
August | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83811994.94 | 0.608218E+09 |
September | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4015933.54 | 0.128955E+10 |
October | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231051E+10 |
November | 0.884402E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381839E+10 |
December | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656774E+10 |
Annual Sum or Average | 0.109410E+11 | 0.236555E+11 | 0.963059E+10 | 0.492014E+09 | 0.350585E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394882E+09 |
Maximum of Months | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197772E+09 | 0.670942E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 5225.88 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 18210.40 | 04-JAN-12:10 |
February | 2159.72 | 03-FEB-13:09 | 5225.88 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 14918.54 | 13-FEB-12:10 |
March | 2159.72 | 03-MAR-13:09 | 5225.88 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 12269.84 | 15-MAR-11:10 |
April | 2159.72 | 01-APR-12:09 | 5225.88 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 844.25 | 23-APR-16:00 | 8522.07 | 04-APR-17:00 |
May | 2159.72 | 05-MAY-12:09 | 5225.88 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1467.88 | 25-MAY-17:00 | 4401.70 | 01-MAY-11:10 |
June | 2159.72 | 02-JUN-12:09 | 5225.88 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3163.84 | 29-JUN-16:00 | 3194.31 | 09-JUN-11:10 |
July | 2159.72 | 01-JUL-12:09 | 5225.88 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2110.03 | 15-JUL-15:00 | 2923.36 | 08-JUL-11:10 |
August | 2159.72 | 04-AUG-12:09 | 5225.88 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1967.18 | 08-AUG-16:00 | 3699.62 | 17-AUG-14:00 |
September | 2159.72 | 01-SEP-12:09 | 5225.88 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 626.97 | 01-SEP-15:00 | 4247.82 | 27-SEP-11:10 |
October | 2159.72 | 01-OCT-12:09 | 5225.88 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 7101.18 | 31-OCT-17:00 |
November | 2159.72 | 03-NOV-12:09 | 5225.88 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 12046.93 | 25-NOV-12:10 |
December | 2159.72 | 01-DEC-13:09 | 5225.88 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 17471.39 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 5225.88 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2923.36 | |||||
Maximum of Months | 2159.72 | 5225.88 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3163.84 | 18210.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 3088.53 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9742.80 | 04-JAN-12:10 |
February | 1079.86 | 03-FEB-13:09 | 3088.53 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.94 | 01-FEB-18:00 |
March | 1079.86 | 03-MAR-13:09 | 3088.53 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6690.54 | 15-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 3088.53 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 446.27 | 23-APR-16:00 | 4575.68 | 04-APR-11:10 |
May | 1079.86 | 05-MAY-12:09 | 3088.53 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.40 | 25-MAY-17:00 | 2518.95 | 08-MAY-11:05 |
June | 1079.86 | 02-JUN-12:09 | 3088.53 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1707.57 | 29-JUN-16:00 | 1885.16 | 09-JUN-11:10 |
July | 1079.86 | 01-JUL-12:09 | 3088.53 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1127.88 | 15-JUL-15:00 | 1716.56 | 08-JUL-11:10 |
August | 1079.86 | 04-AUG-12:09 | 3088.53 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.21 | 08-AUG-16:00 | 2107.13 | 17-AUG-14:00 |
September | 1079.86 | 01-SEP-12:09 | 3088.53 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.42 | 01-SEP-15:00 | 2498.58 | 27-SEP-11:05 |
October | 1079.86 | 01-OCT-12:09 | 3088.53 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3840.04 | 29-OCT-17:00 |
November | 1079.86 | 03-NOV-12:09 | 3088.53 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6608.58 | 25-NOV-17:00 |
December | 1079.86 | 01-DEC-13:09 | 3088.53 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 9450.38 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3088.53 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1716.56 | |||||
Maximum of Months | 1079.86 | 3088.53 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1707.57 | 9742.80 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2821.35 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9742.76 | 04-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 2821.35 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.94 | 01-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 2821.35 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6690.54 | 15-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 2821.35 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 446.28 | 23-APR-16:00 | 4575.67 | 04-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 2821.35 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.37 | 25-MAY-17:00 | 2498.93 | 08-MAY-11:05 |
June | 1079.86 | 03-JUN-12:09 | 2821.35 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1707.51 | 29-JUN-16:00 | 1907.05 | 09-JUN-11:10 |
July | 1079.86 | 01-JUL-12:09 | 2821.35 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1127.83 | 15-JUL-15:00 | 1728.52 | 08-JUL-11:10 |
August | 1079.86 | 05-AUG-12:09 | 2821.35 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.15 | 08-AUG-16:00 | 2112.70 | 17-AUG-14:00 |
September | 1079.86 | 02-SEP-12:09 | 2821.35 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.39 | 01-SEP-15:00 | 2493.41 | 27-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 2821.35 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3840.05 | 29-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 2821.35 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6608.57 | 25-NOV-17:00 |
December | 1079.86 | 02-DEC-13:09 | 2821.35 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 9450.36 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1728.52 | |||||
Maximum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1707.51 | 9742.76 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2821.35 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9742.76 | 04-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 2821.35 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.94 | 01-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 2821.35 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6690.54 | 15-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 2821.35 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 446.34 | 23-APR-16:00 | 4575.67 | 04-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 2821.35 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.38 | 25-MAY-17:00 | 2419.93 | 01-MAY-11:10 |
June | 1079.86 | 03-JUN-12:09 | 2821.35 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1707.61 | 29-JUN-16:00 | 1827.36 | 09-JUN-11:10 |
July | 1079.86 | 01-JUL-12:09 | 2821.35 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1127.96 | 15-JUL-15:00 | 1705.30 | 08-JUL-11:10 |
August | 1079.86 | 05-AUG-12:09 | 2821.35 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.27 | 08-AUG-16:00 | 2037.67 | 17-AUG-14:00 |
September | 1079.86 | 02-SEP-12:09 | 2821.35 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.40 | 01-SEP-15:00 | 2358.06 | 27-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 2821.35 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3840.05 | 29-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 2821.35 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6608.57 | 25-NOV-17:00 |
December | 1079.86 | 02-DEC-13:09 | 2821.35 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 9450.37 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1705.30 | |||||
Maximum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1707.61 | 9742.76 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2821.35 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9742.76 | 04-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 2821.35 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.94 | 01-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 2821.35 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6690.54 | 15-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 2821.35 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 446.33 | 23-APR-16:00 | 4575.67 | 04-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 2821.35 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.36 | 25-MAY-17:00 | 2419.93 | 01-MAY-11:10 |
June | 1079.86 | 03-JUN-12:09 | 2821.35 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1707.60 | 29-JUN-16:00 | 1795.45 | 09-JUN-11:10 |
July | 1079.86 | 01-JUL-12:09 | 2821.35 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1127.96 | 15-JUL-15:00 | 1690.78 | 08-JUL-11:10 |
August | 1079.86 | 05-AUG-12:09 | 2821.35 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.27 | 08-AUG-16:00 | 2009.36 | 17-AUG-14:00 |
September | 1079.86 | 02-SEP-12:09 | 2821.35 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.39 | 01-SEP-15:00 | 2319.23 | 27-SEP-11:05 |
October | 1079.86 | 07-OCT-12:09 | 2821.35 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3840.05 | 29-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 2821.35 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6608.57 | 25-NOV-17:00 |
December | 1079.86 | 02-DEC-13:09 | 2821.35 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 9450.37 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1690.78 | |||||
Maximum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1707.60 | 9742.76 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 3341.31 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 17559.09 | 04-JAN-12:10 |
February | 2879.63 | 04-FEB-15:09 | 3341.31 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 14741.77 | 01-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 3341.31 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 12029.40 | 15-MAR-11:10 |
April | 2879.63 | 01-APR-14:09 | 3341.31 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 805.63 | 23-APR-16:00 | 8232.22 | 04-APR-11:10 |
May | 2879.63 | 06-MAY-14:09 | 3341.31 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.76 | 25-MAY-17:00 | 4346.53 | 01-MAY-11:10 |
June | 2879.63 | 03-JUN-14:09 | 3341.31 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3074.19 | 29-JUN-16:00 | 3063.25 | 09-JUN-11:10 |
July | 2879.63 | 01-JUL-14:09 | 3341.31 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2033.14 | 15-JUL-15:00 | 2890.67 | 08-JUL-11:10 |
August | 2879.63 | 05-AUG-14:09 | 3341.31 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1907.55 | 08-AUG-16:00 | 3448.89 | 17-AUG-14:00 |
September | 2879.63 | 02-SEP-14:09 | 3341.31 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 617.13 | 01-SEP-15:00 | 4167.83 | 27-SEP-11:10 |
October | 2879.63 | 07-OCT-14:09 | 3341.31 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 6896.23 | 29-OCT-17:00 |
November | 2879.63 | 04-NOV-14:09 | 3341.31 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 11864.51 | 25-NOV-17:00 |
December | 2879.63 | 02-DEC-15:09 | 3341.31 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 17008.64 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 3341.31 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2890.67 | |||||
Maximum of Months | 2879.63 | 3341.31 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3074.19 | 17559.09 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1670.66 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9742.76 | 04-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 1670.66 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.93 | 01-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1670.66 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6690.53 | 15-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 1670.66 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 446.33 | 23-APR-16:00 | 4575.66 | 04-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 1670.66 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.33 | 25-MAY-17:00 | 2419.92 | 01-MAY-11:10 |
June | 1439.81 | 03-JUN-14:09 | 1670.66 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1707.63 | 29-JUN-16:00 | 1692.70 | 09-JUN-11:10 |
July | 1439.81 | 01-JUL-14:09 | 1670.66 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1127.99 | 15-JUL-15:00 | 1602.75 | 08-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 1670.66 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.29 | 08-AUG-16:00 | 1908.46 | 17-AUG-12:00 |
September | 1439.81 | 02-SEP-14:09 | 1670.66 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.40 | 01-SEP-15:00 | 2318.33 | 27-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 1670.66 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3840.04 | 29-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 1670.66 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6608.56 | 25-NOV-17:00 |
December | 1439.81 | 02-DEC-15:09 | 1670.66 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 9450.37 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1602.75 | |||||
Maximum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1707.63 | 9742.76 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1670.66 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9742.76 | 04-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 1670.66 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.93 | 01-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1670.66 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6690.53 | 15-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 1670.66 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 446.33 | 23-APR-16:00 | 4575.66 | 04-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 1670.66 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.45 | 25-MAY-17:00 | 2419.92 | 01-MAY-11:10 |
June | 1439.81 | 03-JUN-14:09 | 1670.66 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1707.63 | 29-JUN-16:00 | 1679.72 | 09-JUN-11:10 |
July | 1439.81 | 01-JUL-14:09 | 1670.66 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1127.99 | 15-JUL-15:00 | 1593.84 | 08-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 1670.66 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.29 | 08-AUG-16:00 | 1898.15 | 17-AUG-12:00 |
September | 1439.81 | 02-SEP-14:09 | 1670.66 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.40 | 01-SEP-15:00 | 2318.33 | 27-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 1670.66 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3840.04 | 29-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 1670.66 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6608.56 | 25-NOV-17:00 |
December | 1439.81 | 02-DEC-15:09 | 1670.66 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 9450.37 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1593.84 | |||||
Maximum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1707.63 | 9742.76 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1670.66 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9742.76 | 04-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 1670.66 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.93 | 01-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1670.66 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6690.53 | 15-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 1670.66 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 446.33 | 23-APR-16:00 | 4575.66 | 04-APR-11:10 |
May | 1439.81 | 06-MAY-14:09 | 1670.66 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.45 | 25-MAY-17:00 | 2419.92 | 01-MAY-11:10 |
June | 1439.81 | 03-JUN-14:09 | 1670.66 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1707.62 | 29-JUN-16:00 | 1644.36 | 09-JUN-11:10 |
July | 1439.81 | 01-JUL-14:09 | 1670.66 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1127.98 | 15-JUL-15:00 | 1569.58 | 08-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 1670.66 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.14 | 08-AUG-16:00 | 1872.54 | 17-AUG-12:00 |
September | 1439.81 | 02-SEP-14:09 | 1670.66 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.38 | 01-SEP-15:00 | 2318.33 | 27-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 1670.66 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 3840.04 | 29-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 1670.66 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6608.56 | 25-NOV-17:00 |
December | 1439.81 | 02-DEC-15:09 | 1670.66 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 9450.37 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1569.58 | |||||
Maximum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1707.62 | 9742.76 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1670.66 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10393.19 | 04-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 1670.66 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8461.60 | 13-FEB-12:10 |
March | 1439.81 | 04-MAR-15:09 | 1670.66 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6930.63 | 15-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 1670.66 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 484.85 | 23-APR-16:00 | 4865.94 | 04-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 1670.66 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.42 | 25-MAY-17:00 | 2475.01 | 01-MAY-11:10 |
June | 1439.81 | 03-JUN-14:09 | 1670.66 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1797.15 | 29-JUN-16:00 | 1620.37 | 09-JUN-11:10 |
July | 1439.81 | 01-JUL-14:09 | 1670.66 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1204.80 | 15-JUL-15:00 | 1531.96 | 08-JUL-11:10 |
August | 1439.81 | 05-AUG-14:09 | 1670.66 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1118.77 | 08-AUG-16:00 | 1959.10 | 17-AUG-14:00 |
September | 1439.81 | 02-SEP-14:09 | 1670.66 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 353.34 | 01-SEP-15:00 | 2398.22 | 27-SEP-11:05 |
October | 1439.81 | 07-OCT-14:09 | 1670.66 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 4038.75 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 1670.66 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6814.89 | 25-NOV-12:10 |
December | 1439.81 | 02-DEC-15:09 | 1670.66 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 9912.51 | 24-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1531.96 | |||||
Maximum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1797.15 | 10393.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24109.56 | 06-JAN-00:01 | 1799.77 | 27504.62 | 7490.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.44 |
February | 20260.43 | 25-FEB-00:01 | 1619.79 | 24754.16 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.82 |
March | 17193.33 | 03-MAR-00:01 | 1259.84 | 19253.23 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13738.65 | 05-APR-08:04 | 1439.81 | 22003.70 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1525.23 |
May | 32890.99 | 27-MAY-08:62 | 1079.86 | 16502.77 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.03 |
June | 28264.91 | 21-JUN-08:62 | 899.88 | 13752.31 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.10 |
July | 33919.40 | 07-JUL-08:62 | 1079.86 | 16502.77 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.86 |
August | 33267.49 | 14-AUG-08:62 | 1079.86 | 16502.77 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.94 |
September | 35037.24 | 02-SEP-08:62 | 1079.86 | 16502.77 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.12 |
October | 12599.65 | 30-OCT-08:04 | 1439.81 | 22003.70 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1432.13 |
November | 15942.92 | 25-NOV-00:01 | 1259.84 | 19253.23 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.25 |
December | 19914.73 | 02-DEC-00:01 | 1439.81 | 22003.70 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.64 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12599.65 | 899.88 | 13752.31 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35037.24 | 1799.77 | 27504.62 | 7490.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1525.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7449.61 | 18-JAN-09:04 | 719.90 | 13004.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 915.58 |
February | 9583.22 | 01-FEB-20:01 | 3779.50 | 21619.73 | 4718.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.00 |
March | 8228.41 | 18-MAR-08:04 | 719.90 | 13004.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 900.57 |
April | 16048.80 | 23-APR-20:35 | 4319.42 | 24708.26 | 5393.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 |
May | 20105.06 | 21-MAY-19:50 | 2159.71 | 9265.60 | 2022.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.11 |
June | 18745.68 | 07-JUN-08:62 | 449.94 | 8127.72 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.15 |
July | 17967.59 | 17-JUL-08:62 | 449.94 | 8127.72 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.26 |
August | 18311.79 | 02-AUG-08:62 | 449.94 | 8127.72 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.56 |
September | 18518.60 | 08-SEP-20:15 | 1079.86 | 6177.07 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.71 |
October | 19183.85 | 21-OCT-20:54 | 5399.28 | 30885.33 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.34 |
November | 7633.04 | 29-NOV-09:04 | 719.90 | 13004.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 932.62 |
December | 9357.00 | 01-DEC-09:04 | 719.90 | 13004.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1247.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7449.61 | 449.94 | 6177.07 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.11 | |
Maximum of Months | 20105.06 | 5399.28 | 30885.33 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1247.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9353.59 | 21-JAN-08:03 | 809.89 | 13364.27 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1047.42 |
February | 9486.39 | 24-FEB-08:04 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1334.44 |
March | 8948.10 | 18-MAR-07:03 | 899.88 | 14849.19 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1011.46 |
April | 5443.66 | 06-APR-07:02 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.50 |
May | 23194.20 | 20-MAY-07:01 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.36 |
June | 21207.31 | 16-JUN-07:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.20 |
July | 20623.72 | 08-JUL-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.06 |
August | 20753.58 | 18-AUG-07:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.93 |
September | 27501.50 | 06-SEP-07:01 | 809.89 | 13364.27 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.89 |
October | 26598.53 | 23-OCT-07:01 | 809.89 | 13364.27 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.39 |
November | 8508.97 | 25-NOV-08:04 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.27 |
December | 8832.25 | 08-DEC-08:04 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1094.24 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5443.66 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.06 | |
Maximum of Months | 27501.50 | 899.88 | 14849.19 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1334.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8056.34 | 18-JAN-08:04 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 916.22 |
February | 8497.10 | 11-FEB-08:04 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 866.98 |
March | 8961.55 | 23-MAR-07:03 | 809.89 | 13364.27 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 928.89 |
April | 7496.23 | 05-APR-07:03 | 809.89 | 13364.27 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 767.01 |
May | 20728.67 | 19-MAY-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.34 |
June | 19563.13 | 07-JUN-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.44 |
July | 20111.71 | 17-JUL-07:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.32 |
August | 21264.04 | 03-AUG-07:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.43 |
September | 21400.39 | 08-SEP-07:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.55 |
October | 6979.94 | 23-OCT-07:01 | 809.89 | 13364.27 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.71 |
November | 8532.80 | 29-NOV-08:04 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 992.37 |
December | 8115.22 | 01-DEC-08:04 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1238.43 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6979.94 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.44 | |
Maximum of Months | 21400.39 | 809.89 | 13364.27 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1238.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7653.58 | 22-JAN-09:04 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 983.02 |
February | 8478.19 | 11-FEB-08:04 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 863.46 |
March | 7768.94 | 11-MAR-08:04 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 855.21 |
April | 7508.27 | 05-APR-07:03 | 809.89 | 13364.27 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 764.58 |
May | 18860.89 | 27-MAY-07:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.22 |
June | 18608.83 | 21-JUN-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.87 |
July | 19906.06 | 17-JUL-07:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.38 |
August | 21005.24 | 02-AUG-07:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.46 |
September | 20941.61 | 02-SEP-07:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.47 |
October | 5065.30 | 09-OCT-08:05 | 359.95 | 5939.67 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.29 |
November | 7249.77 | 24-NOV-08:04 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 794.04 |
December | 8429.13 | 10-DEC-09:04 | 899.88 | 14849.19 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1395.97 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5065.30 | 359.95 | 5939.67 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.87 | |
Maximum of Months | 21005.24 | 899.88 | 14849.19 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1395.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11720.96 | 29-JAN-10:04 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.34 |
February | 13409.08 | 23-FEB-09:04 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1380.63 |
March | 13444.63 | 10-MAR-09:04 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1168.25 |
April | 13316.29 | 04-APR-08:04 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1462.16 |
May | 31694.07 | 27-MAY-08:62 | 2375.69 | 10551.52 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.04 |
June | 29331.80 | 21-JUN-08:62 | 1979.74 | 8792.93 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.04 |
July | 33510.35 | 07-JUL-08:62 | 2375.69 | 10551.52 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.36 |
August | 32628.09 | 14-AUG-08:62 | 2375.69 | 10551.52 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.35 |
September | 33424.87 | 02-SEP-08:62 | 2375.69 | 10551.52 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.89 |
October | 12691.39 | 30-OCT-08:04 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1292.48 |
November | 13731.74 | 07-NOV-09:04 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1409.75 |
December | 12211.19 | 07-DEC-09:04 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1326.82 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11720.96 | 1979.74 | 8792.93 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.04 | |
Maximum of Months | 33510.35 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1462.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6794.68 | 20-JAN-09:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831.03 |
February | 6722.67 | 23-FEB-09:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 761.06 |
March | 7041.87 | 11-MAR-09:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 806.53 |
April | 6851.51 | 05-APR-08:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 766.73 |
May | 15416.43 | 27-MAY-08:62 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.51 |
June | 14432.82 | 26-JUN-08:62 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.16 |
July | 17919.79 | 07-JUL-08:62 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.01 |
August | 17457.62 | 14-AUG-08:62 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.82 |
September | 17864.31 | 02-SEP-08:62 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.80 |
October | 6362.65 | 30-OCT-08:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 713.93 |
November | 7234.22 | 23-NOV-10:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831.44 |
December | 6709.61 | 07-DEC-09:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 734.06 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6362.65 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.51 | |
Maximum of Months | 17919.79 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9666.05 | 23-JAN-09:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1125.38 |
February | 6726.26 | 23-FEB-09:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 761.18 |
March | 6969.55 | 11-MAR-09:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 806.01 |
April | 6838.05 | 05-APR-08:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 765.94 |
May | 14504.13 | 26-MAY-08:62 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.75 |
June | 14369.05 | 26-JUN-08:62 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.23 |
July | 17873.44 | 07-JUL-08:62 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.43 |
August | 17408.64 | 14-AUG-08:62 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.30 |
September | 17827.04 | 02-SEP-08:62 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.63 |
October | 6367.44 | 30-OCT-08:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 714.11 |
November | 7232.47 | 23-NOV-10:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831.26 |
December | 6699.48 | 07-DEC-09:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733.48 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6367.44 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.75 | |
Maximum of Months | 17873.44 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1125.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6252.84 | 20-JAN-09:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 830.23 |
February | 6721.48 | 23-FEB-09:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 761.01 |
March | 6683.13 | 10-MAR-09:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.08 |
April | 6609.26 | 04-APR-08:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 798.34 |
May | 14430.84 | 26-MAY-08:62 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.68 |
June | 14315.22 | 26-JUN-08:62 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.27 |
July | 16722.88 | 01-JUL-08:62 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.39 |
August | 15898.50 | 10-AUG-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.40 |
September | 15512.06 | 02-SEP-08:62 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.04 |
October | 6358.12 | 30-OCT-08:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 713.70 |
November | 7179.72 | 23-NOV-10:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 828.52 |
December | 6669.06 | 07-DEC-09:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 732.04 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6252.84 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.68 | |
Maximum of Months | 16722.88 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 830.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5710.38 | 19-JAN-09:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 750.98 |
February | 6606.83 | 23-FEB-09:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 919.72 |
March | 6183.27 | 20-MAR-08:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.89 |
April | 5831.38 | 02-APR-09:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 885.81 |
May | 4507.66 | 01-MAY-08:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.82 |
June | 13104.09 | 28-JUN-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 24.29 | 0.00 |
July | 14605.72 | 14-JUL-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.16 |
August | 16960.94 | 10-AUG-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.75 |
September | 11363.28 | 01-SEP-08:62 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.85 |
October | 6277.73 | 30-OCT-08:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 845.63 |
November | 6798.08 | 07-NOV-09:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 924.80 |
December | 6184.42 | 07-DEC-09:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 839.17 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4507.66 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16960.94 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 24.29 | 924.80 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.729574E+11 | 63664.33 | 06-JAN-17:40 | 0.270925E+12 | 351868.14 | 06-JAN-09:09 |
February | 0.646092E+11 | 61248.79 | 01-FEB-17:30 | 0.184642E+12 | 314839.82 | 14-FEB-09:09 |
March | 0.707520E+11 | 57356.40 | 07-MAR-18:49 | 0.157566E+12 | 284889.56 | 15-MAR-08:09 |
April | 0.657531E+11 | 57679.04 | 23-APR-15:50 | 0.608263E+11 | 198917.54 | 05-APR-08:09 |
May | 0.709221E+11 | 72311.43 | 25-MAY-14:50 | 0.551158E+10 | 118870.51 | 01-MAY-08:09 |
June | 0.758699E+11 | 91837.13 | 29-JUN-15:00 | 49782728.81 | 3359.63 | 03-JUN-08:30 |
July | 0.838158E+11 | 87630.03 | 15-JUL-14:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.800907E+11 | 82699.51 | 08-AUG-14:00 | 2417705.58 | 834.80 | 19-AUG-08:20 |
September | 0.671635E+11 | 72993.79 | 01-SEP-15:20 | 0.353771E+10 | 38127.89 | 23-SEP-08:09 |
October | 0.688320E+11 | 54679.84 | 23-OCT-17:00 | 0.466378E+11 | 173676.98 | 30-OCT-08:09 |
November | 0.684245E+11 | 55400.85 | 15-NOV-18:00 | 0.118898E+12 | 258870.34 | 25-NOV-09:09 |
December | 0.727233E+11 | 58406.26 | 19-DEC-17:19 | 0.251584E+12 | 323386.67 | 24-DEC-12:09 |
Annual Sum or Average | 0.861914E+12 | 0.110018E+13 | ||||
Minimum of Months | 0.646092E+11 | 54679.84 | 0.00 | 0.00 | ||
Maximum of Months | 0.838158E+11 | 91837.13 | 0.270925E+12 | 351868.14 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.366903E+11 | 0.737987E+10 | 0.108804E+11 | 0.00 | 0.124514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555537E+10 | 0.00 |
February | 0.332186E+11 | 0.596846E+10 | 0.985143E+10 | 0.00 | 0.105055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506520E+10 | 0.00 |
March | 0.372231E+11 | 0.566168E+10 | 0.110523E+11 | 0.00 | 0.111731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564174E+10 | 0.00 |
April | 0.356035E+11 | 0.452732E+10 | 0.105581E+11 | 0.00 | 0.955997E+10 | 0.00 | 0.00 | 0.145804E+09 | 0.00 | 0.00 | 0.00 | 0.535844E+10 | 0.00 |
May | 0.369426E+11 | 0.390251E+10 | 0.109629E+11 | 0.00 | 0.936279E+10 | 0.00 | 0.00 | 0.432226E+10 | 0.00 | 0.00 | 0.00 | 0.542907E+10 | 0.00 |
June | 0.359818E+11 | 0.338269E+10 | 0.106818E+11 | 0.00 | 0.922233E+10 | 0.00 | 0.00 | 0.114376E+11 | 0.00 | 0.00 | 0.00 | 0.516370E+10 | 0.00 |
July | 0.365926E+11 | 0.365627E+10 | 0.108460E+11 | 0.00 | 0.933874E+10 | 0.00 | 0.00 | 0.181836E+11 | 0.00 | 0.00 | 0.00 | 0.519857E+10 | 0.00 |
August | 0.371948E+11 | 0.430041E+10 | 0.110454E+11 | 0.00 | 0.946959E+10 | 0.00 | 0.00 | 0.128734E+11 | 0.00 | 0.00 | 0.00 | 0.520710E+10 | 0.00 |
September | 0.356318E+11 | 0.506240E+10 | 0.105649E+11 | 0.00 | 0.905561E+10 | 0.00 | 0.00 | 0.181791E+10 | 0.00 | 0.00 | 0.00 | 0.503079E+10 | 0.00 |
October | 0.366903E+11 | 0.621757E+10 | 0.108804E+11 | 0.00 | 0.968525E+10 | 0.00 | 0.00 | 93699068.80 | 0.00 | 0.00 | 0.00 | 0.526473E+10 | 0.00 |
November | 0.355468E+11 | 0.688166E+10 | 0.105443E+11 | 0.00 | 0.102565E+11 | 0.00 | 0.00 | 4131.89 | 0.00 | 0.00 | 0.00 | 0.519526E+10 | 0.00 |
December | 0.366210E+11 | 0.760877E+10 | 0.108529E+11 | 0.00 | 0.121685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547223E+10 | 0.00 |
Annual Sum or Average | 0.433937E+12 | 0.645496E+11 | 0.128721E+12 | 0.122249E+12 | 0.00 | 0.488742E+11 | 0.635822E+11 | ||||||
Minimum of Months | 0.332186E+11 | 0.338269E+10 | 0.985143E+10 | 0.00 | 0.905561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503079E+10 | 0.00 |
Maximum of Months | 0.372231E+11 | 0.760877E+10 | 0.110523E+11 | 0.00 | 0.124514E+11 | 0.00 | 0.00 | 0.181836E+11 | 0.00 | 0.00 | 0.00 | 0.564174E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.270925E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.184642E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.157566E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.608263E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.551158E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 49782728.81 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 2417705.58 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.353771E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.466378E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.118898E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.251584E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110018E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.270925E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 26802.39 | 01-JAN-11:09 | 4954.41 | 01-JAN-06:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 10707.83 | 06-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 26802.39 | 01-FEB-10:09 | 4954.41 | 01-FEB-06:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 10265.66 | 14-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 26802.39 | 01-MAR-10:09 | 4954.41 | 01-MAR-06:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 9889.15 | 15-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26802.39 | 01-APR-09:09 | 4954.41 | 01-APR-05:10 | 8089.53 | 01-APR-09:09 | 0.00 | 8850.62 | 05-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 26802.39 | 01-MAY-09:09 | 4954.41 | 01-MAY-19:30 | 8089.53 | 01-MAY-09:09 | 0.00 | 7892.85 | 01-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 26802.39 | 01-JUN-09:09 | 4954.41 | 01-JUN-19:00 | 8089.53 | 01-JUN-09:09 | 0.00 | 8772.59 | 29-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 26802.39 | 01-JUL-09:09 | 4954.41 | 01-JUL-20:19 | 8089.53 | 01-JUL-09:09 | 0.00 | 8401.14 | 15-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 26802.39 | 01-AUG-09:09 | 4954.41 | 01-AUG-19:49 | 8089.53 | 01-AUG-09:09 | 0.00 | 7532.60 | 09-AUG-08:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 26802.39 | 01-SEP-09:09 | 4954.41 | 01-SEP-05:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 7006.82 | 01-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 26802.39 | 01-OCT-10:09 | 4954.41 | 01-OCT-05:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 8569.21 | 30-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26802.39 | 01-NOV-09:09 | 4954.41 | 01-NOV-05:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 9568.96 | 25-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26802.39 | 01-DEC-10:09 | 4954.41 | 01-DEC-06:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 10340.87 | 20-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 26802.39 | 4954.41 | 8089.53 | 0.00 | 7006.82 | 0.00 | 0.00 | |||||
Maximum of Months | 26802.39 | 4954.41 | 8089.53 | 0.00 | 10707.83 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 13929.06 | 06-JAN-17:40 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 11846.24 | 01-FEB-15:00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 11890.08 | 08-MAR-14:50 | 0.00 |
April | 11360.41 | 23-APR-15:00 | 0.00 | 0.00 | 0.00 | 9747.25 | 19-APR-13:30 | 0.00 |
May | 24302.09 | 25-MAY-16:10 | 0.00 | 0.00 | 0.00 | 10224.17 | 06-MAY-12:50 | 0.00 |
June | 43911.35 | 29-JUN-16:10 | 0.00 | 0.00 | 0.00 | 7605.24 | 01-JUN-12:20 | 0.00 |
July | 40144.89 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 7594.86 | 10-JUL-12:09 | 0.00 |
August | 34944.63 | 08-AUG-14:00 | 0.00 | 0.00 | 0.00 | 11837.14 | 26-AUG-12:50 | 0.00 |
September | 22942.88 | 01-SEP-14:09 | 0.00 | 0.00 | 0.00 | 9676.84 | 27-SEP-16:30 | 0.00 |
October | 4692.23 | 19-OCT-14:00 | 0.00 | 0.00 | 0.00 | 9508.61 | 23-OCT-19:49 | 0.00 |
November | 6.89 | 01-NOV-22:10 | 0.00 | 0.00 | 0.00 | 9314.20 | 29-NOV-13:09 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 11924.24 | 19-DEC-13:20 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7594.86 | 0.00 | ||
Maximum of Months | 43911.35 | 0.00 | 0.00 | 0.00 | 13929.06 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 63664.33 | 06-JAN-17:40 | 26802.39 | 8089.53 | 4954.41 | 0.00 | 9888.93 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 61248.79 | 01-FEB-17:30 | 26802.39 | 8089.53 | 4954.41 | 0.00 | 9573.95 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 57356.40 | 07-MAR-18:49 | 26802.39 | 8089.53 | 4954.41 | 0.00 | 7802.69 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 57679.04 | 23-APR-15:50 | 26802.39 | 8089.53 | 0.00 | 0.00 | 6267.85 | 0.00 | 0.00 | 11079.94 | 0.00 |
May | 72311.43 | 25-MAY-14:50 | 26802.39 | 8089.53 | 0.00 | 0.00 | 6267.85 | 0.00 | 0.00 | 23637.15 | 0.00 |
June | 91837.13 | 29-JUN-15:00 | 26802.39 | 8089.53 | 0.00 | 0.00 | 8691.00 | 0.00 | 0.00 | 43534.80 | 0.00 |
July | 87630.03 | 15-JUL-14:09 | 26802.39 | 8089.53 | 0.00 | 0.00 | 8348.67 | 0.00 | 0.00 | 39838.97 | 0.00 |
August | 82699.51 | 08-AUG-14:00 | 26802.39 | 8089.53 | 0.00 | 0.00 | 7409.53 | 0.00 | 0.00 | 34944.63 | 0.00 |
September | 72993.79 | 01-SEP-15:20 | 26802.39 | 8089.53 | 0.00 | 0.00 | 6267.85 | 0.00 | 0.00 | 22166.10 | 0.00 |
October | 54679.84 | 23-OCT-17:00 | 26802.39 | 8089.53 | 4954.41 | 0.00 | 6349.83 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 55400.85 | 15-NOV-18:00 | 26802.39 | 8089.53 | 4954.41 | 0.00 | 6834.16 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 58406.26 | 19-DEC-17:19 | 26802.39 | 8089.53 | 4954.41 | 0.00 | 9911.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 54679.84 | 26802.39 | 8089.53 | 0.00 | 0.00 | 6267.85 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91837.13 | 26802.39 | 8089.53 | 4954.41 | 0.00 | 9911.29 | 0.00 | 0.00 | 43534.80 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 351868.14 | 06-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 314839.82 | 14-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 284889.56 | 15-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 198917.54 | 05-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 118870.51 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 3359.63 | 03-JUN-08:30 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 834.80 | 19-AUG-08:20 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 38127.89 | 23-SEP-08:09 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 173676.98 | 30-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 258870.34 | 25-NOV-09:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 323386.67 | 24-DEC-12:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 351868.14 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 19.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.50 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.50 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.33 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8.50 | 20.24 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.60 | 0.17 | 24.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.83 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.67 | 20.48 | 0.00 | 0.17 | 24.60 | 0.17 | 24.60 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.55 | 0.00 | 0.00 | 0.17 | 24.60 | 0.17 | 24.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.53 | 0.50 | 24.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.50 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 24.51 | 1.00 | 24.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.53 | 0.50 | 24.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 14.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 14.99 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 14.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 15.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 15.00 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 15.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 15.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 15.00 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 15.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 14.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 14.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 14.94 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 14.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.00 | 14.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11.50 | 14.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5.33 | 14.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.33 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16.83 | 14.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.83 | 14.86 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.00 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 20.90 | 496.00 | 20.90 | 496.00 | 20.90 |
February | 448.00 | 20.91 | 417.67 | 20.89 | 417.67 | 20.89 |
March | 496.00 | 20.93 | 397.83 | 20.89 | 397.83 | 20.89 |
April | 470.67 | 21.23 | 171.33 | 20.82 | 171.33 | 20.82 |
May | 328.83 | 22.30 | 83.50 | 23.42 | 12.33 | 20.73 |
June | 184.67 | 23.34 | 241.17 | 23.91 | 74.00 | 23.94 |
July | 88.00 | 23.74 | 446.83 | 23.91 | 71.00 | 23.91 |
August | 62.33 | 23.41 | 419.67 | 23.92 | 32.00 | 23.96 |
September | 239.17 | 22.16 | 100.33 | 23.87 | 6.00 | 23.89 |
October | 466.67 | 21.31 | 48.17 | 20.87 | 44.67 | 20.64 |
November | 480.00 | 20.99 | 298.17 | 20.89 | 298.17 | 20.89 |
December | 496.00 | 20.91 | 496.00 | 20.91 | 496.00 | 20.91 |
Annual Sum or Average | 4256.33 | 21.38 | 3616.67 | 21.96 | 2517.00 | 21.11 |
Minimum of Months | 62.33 | 20.90 | 48.17 | 20.82 | 6.00 | 20.64 |
Maximum of Months | 496.00 | 23.74 | 496.00 | 23.92 | 496.00 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.02 | 455.67 | 20.98 | 455.67 | 20.98 |
February | 448.00 | 21.12 | 316.17 | 20.98 | 316.17 | 20.98 |
March | 496.00 | 21.26 | 245.33 | 20.98 | 245.33 | 20.98 |
April | 465.83 | 22.01 | 47.33 | 21.21 | 41.83 | 20.86 |
May | 279.50 | 23.16 | 92.33 | 23.88 | 1.17 | 21.07 |
June | 104.33 | 23.77 | 283.83 | 23.92 | 54.33 | 23.88 |
July | 46.17 | 23.89 | 456.83 | 23.91 | 45.83 | 23.90 |
August | 37.00 | 23.83 | 425.83 | 23.93 | 29.17 | 23.99 |
September | 147.83 | 22.90 | 130.17 | 23.90 | 4.33 | 23.89 |
October | 434.50 | 22.03 | 7.50 | 22.97 | 2.17 | 20.72 |
November | 480.00 | 21.43 | 126.67 | 20.96 | 126.67 | 20.96 |
December | 496.00 | 21.05 | 451.17 | 21.00 | 451.17 | 21.00 |
Annual Sum or Average | 3931.17 | 21.70 | 3038.83 | 22.33 | 1773.83 | 21.20 |
Minimum of Months | 37.00 | 21.02 | 7.50 | 20.96 | 1.17 | 20.72 |
Maximum of Months | 496.00 | 23.89 | 456.83 | 23.93 | 455.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 371.00 | 21.11 | 371.00 | 21.11 |
February | 336.00 | 21.11 | 272.83 | 21.11 | 272.83 | 21.11 |
March | 379.00 | 21.11 | 234.33 | 21.11 | 234.33 | 21.11 |
April | 354.67 | 21.62 | 66.83 | 21.17 | 66.00 | 21.11 |
May | 214.67 | 22.86 | 94.83 | 23.95 | 3.83 | 21.10 |
June | 104.17 | 23.90 | 229.17 | 24.05 | 68.67 | 24.06 |
July | 63.50 | 24.13 | 358.33 | 24.04 | 63.33 | 24.13 |
August | 49.67 | 23.93 | 345.50 | 24.02 | 42.33 | 24.05 |
September | 130.50 | 22.54 | 97.33 | 23.98 | 6.83 | 24.01 |
October | 334.00 | 21.50 | 14.17 | 22.21 | 8.83 | 21.11 |
November | 360.00 | 21.16 | 146.83 | 21.11 | 146.83 | 21.11 |
December | 369.00 | 21.11 | 360.83 | 21.11 | 360.83 | 21.11 |
Annual Sum or Average | 3066.17 | 21.60 | 2592.00 | 22.38 | 1645.67 | 21.43 |
Minimum of Months | 49.67 | 21.11 | 14.17 | 21.11 | 3.83 | 21.10 |
Maximum of Months | 379.00 | 24.13 | 371.00 | 24.05 | 371.00 | 24.13 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 371.00 | 21.11 | 371.00 | 21.11 |
February | 336.00 | 21.11 | 285.67 | 21.11 | 285.67 | 21.11 |
March | 379.00 | 21.11 | 249.33 | 21.11 | 249.33 | 21.11 |
April | 355.17 | 21.46 | 83.00 | 21.15 | 82.17 | 21.11 |
May | 228.33 | 22.46 | 80.83 | 23.85 | 4.83 | 21.11 |
June | 104.33 | 23.57 | 211.67 | 24.01 | 51.00 | 24.02 |
July | 44.67 | 24.10 | 347.67 | 24.02 | 42.33 | 24.14 |
August | 35.00 | 23.63 | 339.17 | 23.99 | 23.00 | 23.99 |
September | 161.33 | 22.20 | 83.00 | 23.95 | 6.17 | 23.94 |
October | 342.83 | 21.36 | 19.83 | 21.68 | 15.83 | 21.11 |
November | 360.00 | 21.14 | 167.17 | 21.11 | 167.17 | 21.11 |
December | 369.00 | 21.11 | 366.50 | 21.11 | 366.50 | 21.11 |
Annual Sum or Average | 3086.67 | 21.49 | 2604.83 | 22.29 | 1665.00 | 21.32 |
Minimum of Months | 35.00 | 21.11 | 19.83 | 21.11 | 4.83 | 21.11 |
Maximum of Months | 379.00 | 24.10 | 371.00 | 24.02 | 371.00 | 24.14 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 371.00 | 21.11 | 371.00 | 21.11 |
February | 336.00 | 21.11 | 303.17 | 21.11 | 303.17 | 21.11 |
March | 379.00 | 21.11 | 267.67 | 21.11 | 267.67 | 21.11 |
April | 355.67 | 21.40 | 100.33 | 21.14 | 99.67 | 21.11 |
May | 234.17 | 22.31 | 75.17 | 23.77 | 6.33 | 21.11 |
June | 125.17 | 23.45 | 194.17 | 24.02 | 54.00 | 24.02 |
July | 50.00 | 24.04 | 342.33 | 24.01 | 45.67 | 24.10 |
August | 42.00 | 23.54 | 331.50 | 23.98 | 24.50 | 23.98 |
September | 182.50 | 22.15 | 74.17 | 23.93 | 6.50 | 23.92 |
October | 346.50 | 21.32 | 25.33 | 21.38 | 22.83 | 21.11 |
November | 360.00 | 21.13 | 197.00 | 21.11 | 197.00 | 21.11 |
December | 369.00 | 21.11 | 369.00 | 21.11 | 369.00 | 21.11 |
Annual Sum or Average | 3151.00 | 21.49 | 2650.83 | 22.21 | 1767.33 | 21.32 |
Minimum of Months | 42.00 | 21.11 | 25.33 | 21.11 | 6.33 | 21.11 |
Maximum of Months | 379.00 | 24.04 | 371.00 | 24.02 | 371.00 | 24.10 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 340.00 | 21.10 | 340.00 | 21.10 |
February | 308.00 | 21.10 | 306.17 | 21.10 | 306.17 | 21.10 |
March | 348.00 | 21.11 | 300.67 | 21.11 | 300.67 | 21.11 |
April | 328.83 | 21.31 | 153.00 | 21.11 | 152.83 | 21.11 |
May | 235.83 | 22.13 | 51.83 | 23.35 | 10.33 | 21.11 |
June | 153.17 | 23.24 | 145.33 | 23.91 | 60.17 | 23.90 |
July | 66.33 | 23.76 | 294.33 | 23.94 | 50.33 | 24.02 |
August | 59.17 | 23.27 | 285.00 | 23.91 | 29.83 | 23.89 |
September | 197.17 | 22.08 | 54.50 | 23.85 | 11.67 | 23.60 |
October | 331.17 | 21.35 | 58.00 | 21.11 | 58.00 | 21.11 |
November | 330.00 | 21.12 | 245.83 | 21.11 | 245.83 | 21.11 |
December | 338.00 | 21.10 | 338.00 | 21.10 | 338.00 | 21.10 |
Annual Sum or Average | 3035.67 | 21.51 | 2572.67 | 22.00 | 1903.83 | 21.33 |
Minimum of Months | 59.17 | 21.10 | 51.83 | 21.10 | 10.33 | 21.10 |
Maximum of Months | 348.00 | 23.76 | 340.00 | 23.94 | 340.00 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 340.00 | 21.10 | 340.00 | 21.10 |
February | 308.00 | 21.11 | 307.17 | 21.11 | 307.17 | 21.11 |
March | 348.00 | 21.11 | 306.17 | 21.11 | 306.17 | 21.11 |
April | 329.17 | 21.30 | 164.67 | 21.11 | 164.67 | 21.11 |
May | 239.50 | 22.10 | 46.83 | 23.11 | 13.33 | 21.11 |
June | 167.50 | 23.23 | 139.33 | 23.91 | 61.00 | 23.90 |
July | 69.50 | 23.75 | 273.17 | 23.94 | 52.67 | 24.03 |
August | 65.00 | 23.31 | 271.00 | 23.91 | 35.17 | 23.89 |
September | 203.83 | 22.10 | 52.33 | 23.85 | 11.50 | 23.58 |
October | 333.50 | 21.36 | 64.50 | 21.11 | 64.50 | 21.11 |
November | 330.00 | 21.12 | 251.67 | 21.11 | 251.67 | 21.11 |
December | 338.00 | 21.10 | 338.00 | 21.10 | 338.00 | 21.10 |
Annual Sum or Average | 3072.00 | 21.52 | 2554.83 | 21.95 | 1945.83 | 21.34 |
Minimum of Months | 65.00 | 21.10 | 46.83 | 21.10 | 11.50 | 21.10 |
Maximum of Months | 348.00 | 23.75 | 340.00 | 23.94 | 340.00 | 24.03 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 340.00 | 21.10 | 340.00 | 21.10 |
February | 308.00 | 21.11 | 308.00 | 21.11 | 308.00 | 21.11 |
March | 348.00 | 21.11 | 309.50 | 21.11 | 309.50 | 21.11 |
April | 329.17 | 21.28 | 174.17 | 21.11 | 174.17 | 21.11 |
May | 244.17 | 22.08 | 48.67 | 22.88 | 17.83 | 21.11 |
June | 177.67 | 23.20 | 138.17 | 23.91 | 62.00 | 23.89 |
July | 71.83 | 23.74 | 268.67 | 23.94 | 54.33 | 24.02 |
August | 69.17 | 23.30 | 265.33 | 23.91 | 37.50 | 23.89 |
September | 208.83 | 22.09 | 51.50 | 23.83 | 11.67 | 23.53 |
October | 335.00 | 21.36 | 69.33 | 21.11 | 69.33 | 21.11 |
November | 330.00 | 21.11 | 256.67 | 21.11 | 256.67 | 21.11 |
December | 338.00 | 21.10 | 338.00 | 21.10 | 338.00 | 21.10 |
Annual Sum or Average | 3099.83 | 21.53 | 2568.00 | 21.93 | 1979.00 | 21.34 |
Minimum of Months | 69.17 | 21.10 | 48.67 | 21.10 | 11.67 | 21.10 |
Maximum of Months | 348.00 | 23.74 | 340.00 | 23.94 | 340.00 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 340.00 | 21.10 | 340.00 | 21.10 |
February | 308.00 | 21.11 | 308.00 | 21.11 | 308.00 | 21.11 |
March | 348.00 | 21.11 | 321.33 | 21.11 | 321.33 | 21.11 |
April | 329.33 | 21.25 | 191.67 | 21.11 | 191.67 | 21.11 |
May | 254.00 | 22.02 | 49.67 | 22.61 | 22.83 | 21.11 |
June | 191.50 | 23.11 | 135.83 | 23.89 | 63.83 | 23.86 |
July | 77.83 | 23.70 | 263.00 | 23.94 | 58.33 | 24.01 |
August | 81.83 | 23.30 | 256.50 | 23.91 | 45.33 | 23.89 |
September | 219.17 | 22.07 | 49.33 | 23.77 | 12.33 | 23.31 |
October | 336.33 | 21.35 | 88.50 | 21.11 | 88.50 | 21.11 |
November | 330.00 | 21.11 | 271.00 | 21.11 | 271.00 | 21.11 |
December | 338.00 | 21.10 | 338.00 | 21.10 | 338.00 | 21.10 |
Annual Sum or Average | 3154.00 | 21.53 | 2612.83 | 21.89 | 2061.17 | 21.35 |
Minimum of Months | 77.83 | 21.10 | 49.33 | 21.10 | 12.33 | 21.10 |
Maximum of Months | 348.00 | 23.70 | 340.00 | 23.94 | 340.00 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 340.00 | 21.10 | 340.00 | 21.10 |
February | 308.00 | 21.11 | 308.00 | 21.11 | 308.00 | 21.11 |
March | 348.00 | 21.11 | 348.00 | 21.11 | 348.00 | 21.11 |
April | 330.00 | 21.21 | 264.50 | 21.11 | 264.50 | 21.11 |
May | 272.67 | 21.93 | 58.00 | 21.96 | 40.33 | 21.12 |
June | 219.50 | 22.97 | 125.83 | 23.81 | 69.83 | 23.73 |
July | 91.00 | 23.59 | 249.17 | 23.94 | 66.50 | 24.00 |
August | 105.33 | 23.17 | 233.50 | 23.92 | 53.17 | 23.88 |
September | 238.50 | 22.03 | 38.17 | 23.58 | 12.33 | 22.83 |
October | 337.00 | 21.32 | 140.67 | 21.11 | 140.67 | 21.11 |
November | 330.00 | 21.11 | 309.17 | 21.11 | 309.17 | 21.11 |
December | 338.00 | 21.10 | 338.00 | 21.10 | 338.00 | 21.10 |
Annual Sum or Average | 3258.00 | 21.54 | 2753.00 | 21.78 | 2290.50 | 21.34 |
Minimum of Months | 91.00 | 21.10 | 38.17 | 21.10 | 12.33 | 21.10 |
Maximum of Months | 348.00 | 23.59 | 348.00 | 23.94 | 348.00 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 20.87265 | 7.63214 | -0.7958 | 19.01366 |
February | 448.00000 | 20.88285 | 9.59373 | -0.7337 | 17.07625 |
March | 496.00000 | 20.91302 | 13.59566 | -0.6722 | 15.19822 |
April | 480.00000 | 21.26808 | 18.80527 | -0.4724 | 10.87724 |
May | 496.00000 | 22.83498 | 31.70185 | -0.9435 | 27.06137 |
June | 480.00000 | 23.67126 | 46.63177 | -0.5270 | 12.19626 |
July | 496.00000 | 23.88759 | 52.48602 | -0.3642 | 8.03071 |
August | 496.00000 | 23.84960 | 51.11195 | -0.3947 | 8.70228 |
September | 480.00000 | 23.01283 | 40.05926 | -0.7881 | 20.99182 |
October | 496.00000 | 21.46438 | 28.64794 | -0.3151 | 8.45626 |
November | 480.00000 | 20.97712 | 17.53943 | -0.5875 | 12.86287 |
December | 496.00000 | 20.88130 | 8.95218 | -0.7762 | 18.31366 |
Annual Sum or Average | 5840.00000 | 22.05043 | 27.33605 | -0.6134 | 14.88779 |
Minimum of Months | 448.00000 | 20.87265 | 7.63214 | -0.9435 | 8.03071 |
Maximum of Months | 496.00000 | 23.88759 | 52.48602 | -0.3151 | 27.06137 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 20.98579 | 8.90640 | -0.6947 | 15.67823 |
February | 448.00000 | 21.08553 | 11.04434 | -0.6156 | 13.53009 |
March | 496.00000 | 21.23757 | 14.82421 | -0.5346 | 11.68363 |
April | 480.00000 | 22.04638 | 19.16253 | -0.2688 | 8.01341 |
May | 496.00000 | 23.47286 | 30.95953 | -0.7291 | 18.02149 |
June | 480.00000 | 23.87761 | 45.44239 | -0.4462 | 9.63338 |
July | 496.00000 | 23.90785 | 51.41813 | -0.3539 | 7.82249 |
August | 496.00000 | 23.90942 | 50.55310 | -0.3690 | 8.09119 |
September | 480.00000 | 23.57887 | 38.88183 | -0.6104 | 14.15209 |
October | 496.00000 | 22.24658 | 28.74282 | -0.1313 | 6.93580 |
November | 480.00000 | 21.40861 | 18.39187 | -0.4513 | 9.99847 |
December | 496.00000 | 21.01858 | 10.23616 | -0.6728 | 15.00599 |
Annual Sum or Average | 5840.00000 | 22.40515 | 27.48069 | -0.4893 | 11.54292 |
Minimum of Months | 448.00000 | 20.98579 | 8.90640 | -0.7291 | 6.93580 |
Maximum of Months | 496.00000 | 23.90942 | 51.41813 | -0.1313 | 18.02149 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.07033 | 6.97553 | -0.7150 | 15.99054 |
February | 336.00000 | 21.07614 | 9.14268 | -0.6459 | 14.04258 |
March | 379.00000 | 21.08876 | 13.24166 | -0.5835 | 12.42223 |
April | 360.00000 | 21.65623 | 17.61620 | -0.3567 | 8.98557 |
May | 375.00000 | 23.34579 | 31.54497 | -0.7619 | 19.91565 |
June | 366.00000 | 23.95607 | 46.12894 | -0.4157 | 9.30410 |
July | 369.00000 | 24.03764 | 52.68425 | -0.2998 | 7.24934 |
August | 379.00000 | 23.99239 | 52.15218 | -0.3285 | 7.60215 |
September | 360.00000 | 23.43126 | 38.44500 | -0.6530 | 16.01202 |
October | 371.00000 | 21.75211 | 28.22009 | -0.2338 | 7.69026 |
November | 360.00000 | 21.15316 | 17.40233 | -0.5180 | 11.05535 |
December | 369.00000 | 21.07357 | 8.56261 | -0.6962 | 15.42078 |
Annual Sum or Average | 4395.00000 | 22.31393 | 27.00189 | -0.5165 | 12.12995 |
Minimum of Months | 336.00000 | 21.07033 | 6.97553 | -0.7619 | 7.24934 |
Maximum of Months | 379.00000 | 24.03764 | 52.68425 | -0.2338 | 19.91565 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.06739 | 6.98186 | -0.7266 | 16.35133 |
February | 336.00000 | 21.07084 | 9.16261 | -0.6581 | 14.38873 |
March | 379.00000 | 21.07918 | 13.26053 | -0.5959 | 12.74867 |
April | 360.00000 | 21.48021 | 17.80562 | -0.4011 | 9.40584 |
May | 375.00000 | 23.04566 | 31.62010 | -0.8551 | 23.61023 |
June | 366.00000 | 23.84002 | 45.47153 | -0.4589 | 10.34803 |
July | 369.00000 | 23.99474 | 51.05413 | -0.3236 | 7.51386 |
August | 379.00000 | 23.93814 | 50.82412 | -0.3551 | 7.99387 |
September | 360.00000 | 23.12760 | 38.96810 | -0.7442 | 19.44969 |
October | 371.00000 | 21.55259 | 28.62175 | -0.2831 | 7.97839 |
November | 360.00000 | 21.11481 | 17.49689 | -0.5377 | 11.43719 |
December | 369.00000 | 21.06865 | 8.57068 | -0.7080 | 15.78277 |
Annual Sum or Average | 4395.00000 | 22.20921 | 26.80654 | -0.5532 | 13.07518 |
Minimum of Months | 336.00000 | 21.06739 | 6.98186 | -0.8551 | 7.51386 |
Maximum of Months | 379.00000 | 23.99474 | 51.05413 | -0.2831 | 23.61023 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.06701 | 6.98232 | -0.7413 | 16.81240 |
February | 336.00000 | 21.06941 | 9.16406 | -0.6747 | 14.86403 |
March | 379.00000 | 21.07631 | 13.26363 | -0.6126 | 13.19120 |
April | 360.00000 | 21.41587 | 17.87982 | -0.4302 | 9.79609 |
May | 375.00000 | 22.91908 | 31.87812 | -0.9099 | 25.86988 |
June | 366.00000 | 23.78101 | 45.75252 | -0.4895 | 11.22939 |
July | 369.00000 | 23.98084 | 51.31049 | -0.3350 | 7.68856 |
August | 379.00000 | 23.91488 | 51.06775 | -0.3703 | 8.29241 |
September | 360.00000 | 23.01469 | 39.29161 | -0.7920 | 21.27033 |
October | 371.00000 | 21.49271 | 28.74980 | -0.3093 | 8.21789 |
November | 360.00000 | 21.10485 | 17.51905 | -0.5563 | 11.85656 |
December | 369.00000 | 21.06766 | 8.57172 | -0.7230 | 16.24429 |
Annual Sum or Average | 4395.00000 | 22.16946 | 26.94020 | -0.5779 | 13.76962 |
Minimum of Months | 336.00000 | 21.06701 | 6.98232 | -0.9099 | 7.68856 |
Maximum of Months | 379.00000 | 23.98084 | 51.31049 | -0.3093 | 25.86988 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06185 | 7.75264 | -0.7916 | 18.41756 |
February | 308.00000 | 21.06289 | 9.98067 | -0.7258 | 16.34991 |
March | 348.00000 | 21.06639 | 14.13790 | -0.6627 | 14.53605 |
April | 330.00000 | 21.29795 | 18.68731 | -0.4938 | 10.84509 |
May | 344.00000 | 22.68234 | 33.26655 | -1.0160 | 30.18923 |
June | 336.00000 | 23.60128 | 47.10761 | -0.5725 | 13.54725 |
July | 338.00000 | 23.89504 | 52.45945 | -0.3804 | 8.41133 |
August | 348.00000 | 23.80573 | 52.32749 | -0.4239 | 9.35702 |
September | 330.00000 | 22.80691 | 40.55345 | -0.8828 | 24.67055 |
October | 340.00000 | 21.40112 | 29.73449 | -0.3621 | 8.85708 |
November | 330.00000 | 21.08226 | 18.29996 | -0.6105 | 13.16742 |
December | 338.00000 | 21.06201 | 9.35278 | -0.7742 | 17.84572 |
Annual Sum or Average | 4030.00000 | 22.07947 | 27.96587 | -0.6406 | 15.50898 |
Minimum of Months | 308.00000 | 21.06185 | 7.75264 | -1.0160 | 8.41133 |
Maximum of Months | 348.00000 | 23.89504 | 52.45945 | -0.3621 | 30.18923 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06216 | 7.69885 | -0.7847 | 18.18973 |
February | 308.00000 | 21.06323 | 9.92797 | -0.7240 | 16.29440 |
March | 348.00000 | 21.06635 | 14.08558 | -0.6646 | 14.58172 |
April | 330.00000 | 21.27874 | 18.65667 | -0.5079 | 11.08775 |
May | 344.00000 | 22.64253 | 33.32283 | -1.0487 | 31.54827 |
June | 336.00000 | 23.57021 | 47.26508 | -0.6034 | 14.42685 |
July | 338.00000 | 23.88943 | 52.66721 | -0.4037 | 8.79711 |
August | 348.00000 | 23.79897 | 52.54534 | -0.4467 | 9.79483 |
September | 330.00000 | 22.78285 | 40.60211 | -0.9109 | 25.69793 |
October | 340.00000 | 21.39190 | 29.70133 | -0.3747 | 9.01156 |
November | 330.00000 | 21.08055 | 18.25004 | -0.6146 | 13.25905 |
December | 338.00000 | 21.06236 | 9.29829 | -0.7681 | 17.64799 |
Annual Sum or Average | 4030.00000 | 22.06804 | 27.99697 | -0.6537 | 15.85692 |
Minimum of Months | 308.00000 | 21.06216 | 7.69885 | -1.0487 | 8.79711 |
Maximum of Months | 348.00000 | 23.88943 | 52.66721 | -0.3747 | 31.54827 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06210 | 7.69890 | -0.7870 | 18.26649 |
February | 308.00000 | 21.06313 | 9.92805 | -0.7277 | 16.40613 |
March | 348.00000 | 21.06590 | 14.08622 | -0.6695 | 14.71720 |
April | 330.00000 | 21.26140 | 18.67668 | -0.5186 | 11.29103 |
May | 344.00000 | 22.59795 | 33.43205 | -1.0714 | 32.54901 |
June | 336.00000 | 23.53225 | 47.44127 | -0.6222 | 15.07289 |
July | 338.00000 | 23.88329 | 52.80129 | -0.4099 | 8.92284 |
August | 348.00000 | 23.78810 | 52.66974 | -0.4546 | 9.99093 |
September | 330.00000 | 22.74959 | 40.70782 | -0.9272 | 26.33332 |
October | 340.00000 | 21.38062 | 29.72686 | -0.3825 | 9.11523 |
November | 330.00000 | 21.07873 | 18.25374 | -0.6201 | 13.40171 |
December | 338.00000 | 21.06232 | 9.29833 | -0.7705 | 17.72782 |
Annual Sum or Average | 4030.00000 | 22.05432 | 28.05580 | -0.6629 | 16.14620 |
Minimum of Months | 308.00000 | 21.06210 | 7.69890 | -1.0714 | 8.92284 |
Maximum of Months | 348.00000 | 23.88329 | 52.80129 | -0.3825 | 32.54901 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06206 | 7.69884 | -0.7985 | 18.65343 |
February | 308.00000 | 21.06307 | 9.92760 | -0.7420 | 16.85254 |
March | 348.00000 | 21.06490 | 14.08732 | -0.6866 | 15.20982 |
April | 330.00000 | 21.22351 | 18.72152 | -0.5457 | 11.85998 |
May | 344.00000 | 22.49748 | 33.67765 | -1.1211 | 34.77433 |
June | 336.00000 | 23.44958 | 47.83451 | -0.6600 | 16.43996 |
July | 338.00000 | 23.86728 | 53.07777 | -0.4209 | 9.17835 |
August | 348.00000 | 23.75997 | 52.94319 | -0.4698 | 10.41187 |
September | 330.00000 | 22.67970 | 40.92855 | -0.9593 | 27.60674 |
October | 340.00000 | 21.35636 | 29.78035 | -0.4004 | 9.38850 |
November | 330.00000 | 21.07352 | 18.26404 | -0.6363 | 13.83757 |
December | 338.00000 | 21.06223 | 9.29827 | -0.7822 | 18.11161 |
Annual Sum or Average | 4030.00000 | 22.02368 | 28.18350 | -0.6847 | 16.85901 |
Minimum of Months | 308.00000 | 21.06206 | 7.69884 | -1.1211 | 9.17835 |
Maximum of Months | 348.00000 | 23.86728 | 53.07777 | -0.4004 | 34.77433 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06215 | 7.60816 | -0.8686 | 21.14142 |
February | 308.00000 | 21.06308 | 9.79978 | -0.8130 | 19.22023 |
March | 348.00000 | 21.06473 | 13.96574 | -0.7631 | 17.58164 |
April | 330.00000 | 21.16547 | 18.69445 | -0.6254 | 13.81595 |
May | 344.00000 | 22.31108 | 34.00226 | -1.2363 | 40.01068 |
June | 336.00000 | 23.28593 | 48.57019 | -0.7411 | 19.50650 |
July | 338.00000 | 23.82490 | 53.67606 | -0.4443 | 9.87431 |
August | 348.00000 | 23.67600 | 53.58233 | -0.5076 | 11.60564 |
September | 330.00000 | 22.53353 | 41.23339 | -1.0327 | 30.73407 |
October | 340.00000 | 21.31536 | 29.74249 | -0.4524 | 10.39320 |
November | 330.00000 | 21.06647 | 18.23479 | -0.6964 | 15.58165 |
December | 338.00000 | 21.06233 | 9.20536 | -0.8493 | 20.44975 |
Annual Sum or Average | 4030.00000 | 21.96256 | 28.35936 | -0.7519 | 19.15871 |
Minimum of Months | 308.00000 | 21.06215 | 7.60816 | -1.2363 | 9.87431 |
Maximum of Months | 348.00000 | 23.82490 | 53.67606 | -0.4443 | 40.01068 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.164849E+09 | 44584911.39 | 10.75 | 0.138434E+09 | 26414825.41 | 0.00 | 0.53 | 23-APR-16:10 | 0.00 | 01-APR-00:05 | 8497.67 | 23-APR-16:10 | 7218.63 | 23-APR-16:07 | 1302.19 | 23-APR-17:00 | 2282.25 | 23-APR-16:10 | 0.00 | 01-APR-00:05 |
May | 0.324451E+10 | 0.839763E+09 | 170.87 | 0.270927E+10 | 0.535240E+09 | 0.00 | 1.00 | 26-MAY-08:62 | 0.00 | 01-MAY-00:10 | 38521.71 | 26-MAY-08:62 | 28109.71 | 27-MAY-08:62 | 13642.35 | 26-MAY-08:62 | 8170.34 | 26-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.923502E+10 | 0.227163E+10 | 308.29 | 0.641849E+10 | 0.281654E+10 | 0.00 | 1.00 | 19-JUN-08:62 | 0.00 | 01-JUN-00:10 | 41479.51 | 30-JUN-08:61 | 25055.32 | 28-JUN-08:03 | 20703.57 | 23-JUN-08:62 | 8921.09 | 30-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.154474E+11 | 0.371170E+10 | 413.80 | 0.101036E+11 | 0.534381E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 41203.96 | 23-JUL-07:02 | 26826.19 | 12-JUL-08:62 | 22453.84 | 05-JUL-08:03 | 8703.39 | 29-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.107934E+11 | 0.261041E+10 | 365.39 | 0.716671E+10 | 0.362667E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 40279.98 | 30-AUG-08:61 | 24550.95 | 26-AUG-08:62 | 20390.85 | 30-AUG-08:03 | 8413.56 | 30-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.154971E+10 | 0.392392E+09 | 146.97 | 0.118959E+10 | 0.360126E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 38942.19 | 01-SEP-08:62 | 24675.95 | 02-SEP-08:62 | 18630.00 | 01-SEP-08:62 | 8238.10 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 89737857.15 | 24454672.37 | 18.06 | 79847527.18 | 9890329.97 | 0.00 | 0.25 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 | 3548.31 | 19-OCT-15:00 | 3219.54 | 19-OCT-15:00 | 526.82 | 22-OCT-14:00 | 962.17 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.405246E+11 | 0.989494E+10 | 1434.14 | 0.278059E+11 | 0.127187E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.154474E+11 | 0.371170E+10 | 413.80 | 0.101036E+11 | 0.534381E+10 | 0.00 | 1.00 | 0.00 | 41479.51 | 28109.71 | 22453.84 | 8921.09 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.147707E+09 | 33099529.84 | 22.92 | 0.131061E+09 | 16646730.47 | 0.00 | 1.00 | 23-APR-18:41 | 0.00 | 01-APR-00:05 | 18054.73 | 23-APR-18:41 | 15779.97 | 23-APR-18:47 | 3134.35 | 23-APR-20:50 | 3689.21 | 23-APR-18:41 | 0.00 | 01-APR-00:05 |
May | 0.244000E+10 | 0.529555E+09 | 174.77 | 0.213234E+10 | 0.307662E+09 | 0.00 | 1.00 | 03-MAY-20:12 | 0.00 | 01-MAY-00:10 | 18766.06 | 26-MAY-08:62 | 17204.57 | 03-MAY-20:12 | 6449.06 | 26-MAY-20:01 | 3759.43 | 25-MAY-20:32 | 0.00 | 01-MAY-00:10 |
June | 0.608989E+10 | 0.128607E+10 | 286.59 | 0.444157E+10 | 0.164833E+10 | 0.00 | 1.00 | 04-JUN-17:01 | 0.00 | 01-JUN-00:10 | 20121.44 | 30-JUN-08:61 | 17388.14 | 17-JUN-18:06 | 10714.62 | 19-JUN-20:03 | 4017.84 | 30-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.955686E+10 | 0.196778E+10 | 356.52 | 0.655253E+10 | 0.300432E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 19960.92 | 23-JUL-07:02 | 14721.17 | 02-JUL-17:02 | 10806.35 | 25-JUL-20:02 | 3922.32 | 29-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.675361E+10 | 0.138998E+10 | 309.40 | 0.466978E+10 | 0.208384E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 19848.52 | 31-AUG-20:03 | 15868.34 | 05-AUG-18:01 | 10408.56 | 28-AUG-20:02 | 3885.39 | 31-AUG-20:03 | 0.00 | 01-AUG-00:10 |
September | 0.106331E+10 | 0.228438E+09 | 158.68 | 0.853317E+09 | 0.209994E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 19076.37 | 17-SEP-17:02 | 17003.33 | 08-SEP-20:15 | 9310.34 | 19-SEP-08:62 | 3721.53 | 17-SEP-17:02 | 0.00 | 01-SEP-00:10 |
October | 84193764.82 | 19695310.50 | 31.43 | 79223693.50 | 4970071.33 | 0.00 | 1.00 | 21-OCT-20:54 | 0.00 | 01-OCT-00:05 | 17204.57 | 21-OCT-20:54 | 16948.37 | 21-OCT-20:54 | 267.58 | 22-OCT-13:40 | 3360.85 | 21-OCT-20:54 | 0.00 | 01-OCT-00:05 |
November | 14653.83 | 4131.89 | 0.17 | 12684.73 | 1969.10 | 0.00 | 0.00 | 01-NOV-22:10 | 0.00 | 01-NOV-00:05 | 24.42 | 01-NOV-22:10 | 21.14 | 01-NOV-22:10 | 3.28 | 01-NOV-22:10 | 6.89 | 01-NOV-22:10 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.261356E+11 | 0.545461E+10 | 1340.47 | 0.188598E+11 | 0.727576E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.955686E+10 | 0.196778E+10 | 356.52 | 0.655253E+10 | 0.300432E+10 | 0.00 | 1.00 | 0.00 | 20121.44 | 17388.14 | 10806.35 | 4017.84 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 53250921.37 | 12250939.45 | 17.83 | 49165933.21 | 4084988.15 | 0.00 | 0.58 | 23-APR-16:00 | 0.00 | 01-APR-00:05 | 5035.94 | 23-APR-16:00 | 4731.85 | 23-APR-16:00 | 348.68 | 23-APR-13:40 | 1166.32 | 23-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.178097E+10 | 0.395171E+09 | 146.16 | 0.161751E+10 | 0.163456E+09 | 0.00 | 1.00 | 18-MAY-07:02 | 0.00 | 01-MAY-00:10 | 18944.80 | 26-MAY-07:01 | 15028.97 | 18-MAY-07:02 | 5805.09 | 26-MAY-07:03 | 3711.45 | 26-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.449211E+10 | 0.962913E+09 | 251.54 | 0.346114E+10 | 0.103096E+10 | 0.00 | 1.00 | 07-JUN-07:02 | 0.00 | 01-JUN-00:10 | 20525.74 | 30-JUN-07:01 | 17151.68 | 18-JUN-08:62 | 9708.60 | 23-JUN-07:02 | 4063.67 | 30-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.687179E+10 | 0.143262E+10 | 304.06 | 0.503562E+10 | 0.183617E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 20449.60 | 23-JUL-08:61 | 13592.57 | 30-JUL-08:61 | 10437.26 | 05-JUL-07:04 | 3985.95 | 30-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.484306E+10 | 0.101152E+10 | 271.24 | 0.354591E+10 | 0.129715E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 19642.19 | 30-AUG-07:01 | 13611.42 | 20-AUG-08:62 | 9862.92 | 30-AUG-07:03 | 3809.03 | 30-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.677582E+09 | 0.146960E+09 | 129.42 | 0.572942E+09 | 0.104640E+09 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 19120.41 | 01-SEP-07:01 | 17271.37 | 09-SEP-07:02 | 9297.70 | 01-SEP-07:03 | 3738.85 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 |
October | 46243164.38 | 10891341.34 | 23.10 | 44971430.05 | 1271734.33 | 0.00 | 0.84 | 23-OCT-07:01 | 0.00 | 01-OCT-00:05 | 15764.69 | 23-OCT-07:01 | 12629.10 | 23-OCT-07:01 | 3135.58 | 23-OCT-07:01 | 3058.93 | 23-OCT-07:01 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.187650E+11 | 0.397232E+10 | 1143.35 | 0.143273E+11 | 0.443773E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.687179E+10 | 0.143262E+10 | 304.06 | 0.503562E+10 | 0.183617E+10 | 0.00 | 1.00 | 0.00 | 20525.74 | 17271.37 | 10437.26 | 4063.67 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 42692883.63 | 11554819.74 | 6.67 | 36100146.96 | 6592736.67 | 0.00 | 0.49 | 23-APR-16:00 | 0.00 | 01-APR-00:05 | 4312.08 | 23-APR-16:00 | 3730.33 | 23-APR-16:00 | 581.74 | 23-APR-16:00 | 1174.42 | 23-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.167861E+10 | 0.433009E+09 | 133.86 | 0.141404E+10 | 0.264577E+09 | 0.00 | 1.00 | 25-MAY-07:02 | 0.00 | 01-MAY-00:10 | 21247.61 | 26-MAY-07:01 | 15008.81 | 28-MAY-08:62 | 7008.54 | 26-MAY-07:01 | 4512.87 | 26-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.439147E+10 | 0.108278E+10 | 244.68 | 0.316902E+10 | 0.122245E+10 | 0.00 | 1.00 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 | 23043.68 | 30-JUN-07:01 | 17539.39 | 18-JUN-08:62 | 11153.74 | 23-JUN-07:02 | 4948.71 | 30-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.688534E+10 | 0.165851E+10 | 305.51 | 0.469335E+10 | 0.219199E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 22951.64 | 23-JUL-08:61 | 14416.20 | 07-JUL-07:02 | 11951.89 | 05-JUL-07:03 | 4849.08 | 30-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.501036E+10 | 0.121253E+10 | 273.19 | 0.339875E+10 | 0.161161E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 22018.75 | 30-AUG-07:01 | 14585.44 | 05-AUG-07:02 | 11251.44 | 30-AUG-07:03 | 4632.00 | 30-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.790302E+09 | 0.199675E+09 | 123.47 | 0.623382E+09 | 0.166921E+09 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 21451.27 | 01-SEP-07:01 | 13125.65 | 02-SEP-07:02 | 10672.72 | 19-SEP-07:02 | 4547.75 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 |
October | 53735608.76 | 14604023.47 | 17.19 | 48676307.70 | 5059301.06 | 0.00 | 0.26 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 | 2071.79 | 19-OCT-15:00 | 1902.56 | 19-OCT-15:00 | 283.10 | 22-OCT-13:50 | 560.03 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.188525E+11 | 0.461267E+10 | 1104.56 | 0.133833E+11 | 0.546919E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.688534E+10 | 0.165851E+10 | 305.51 | 0.469335E+10 | 0.219199E+10 | 0.00 | 1.00 | 0.00 | 23043.68 | 17539.39 | 11951.89 | 4948.71 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 36556026.60 | 10011225.51 | 6.00 | 30858039.70 | 5697986.90 | 0.00 | 0.46 | 23-APR-16:00 | 0.00 | 01-APR-00:05 | 3932.03 | 23-APR-16:00 | 3389.45 | 23-APR-16:00 | 542.58 | 23-APR-16:00 | 1082.19 | 23-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.154827E+10 | 0.401809E+09 | 125.10 | 0.130022E+10 | 0.248053E+09 | 0.00 | 1.00 | 25-MAY-07:02 | 0.00 | 01-MAY-00:10 | 21184.96 | 26-MAY-07:01 | 14510.88 | 27-MAY-07:02 | 7034.60 | 26-MAY-07:01 | 4499.76 | 26-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.416733E+10 | 0.102996E+10 | 236.82 | 0.299201E+10 | 0.117532E+10 | 0.00 | 1.00 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 | 22971.26 | 30-JUN-07:01 | 15127.54 | 18-JUN-08:62 | 11173.38 | 23-JUN-07:02 | 4935.29 | 30-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.663917E+10 | 0.160418E+10 | 302.47 | 0.451415E+10 | 0.212502E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 22887.24 | 23-JUL-08:61 | 14338.42 | 07-JUL-07:02 | 11950.51 | 05-JUL-07:03 | 4835.50 | 30-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.477988E+10 | 0.116070E+10 | 269.85 | 0.323793E+10 | 0.154194E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 21956.96 | 30-AUG-07:01 | 14455.78 | 06-AUG-08:62 | 11256.92 | 30-AUG-07:03 | 4619.22 | 30-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.700670E+09 | 0.177064E+09 | 113.63 | 0.553268E+09 | 0.147403E+09 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 21391.26 | 01-SEP-07:01 | 13052.38 | 02-SEP-07:02 | 10655.46 | 01-SEP-07:01 | 4535.14 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 |
October | 37347147.93 | 10241994.54 | 15.83 | 33770308.35 | 3576839.58 | 0.00 | 0.22 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 | 1716.92 | 19-OCT-15:00 | 1574.20 | 19-OCT-15:00 | 226.01 | 22-OCT-14:00 | 469.25 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.179092E+11 | 0.439398E+10 | 1069.70 | 0.126622E+11 | 0.524702E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.663917E+10 | 0.160418E+10 | 302.47 | 0.451415E+10 | 0.212502E+10 | 0.00 | 1.00 | 0.00 | 22971.26 | 15127.54 | 11950.51 | 4935.29 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 50675353.91 | 14087514.43 | 3.33 | 41826207.67 | 8849146.24 | 0.00 | 0.39 | 23-APR-16:00 | 0.00 | 01-APR-00:05 | 5890.57 | 23-APR-16:00 | 4945.66 | 23-APR-16:00 | 981.44 | 23-APR-15:00 | 1647.19 | 23-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.236855E+10 | 0.621603E+09 | 120.02 | 0.195079E+10 | 0.417756E+09 | 0.00 | 1.00 | 26-MAY-08:62 | 0.00 | 01-MAY-00:10 | 37509.76 | 26-MAY-08:62 | 26977.53 | 27-MAY-08:62 | 13123.53 | 26-MAY-08:62 | 7958.59 | 26-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.671044E+10 | 0.166141E+10 | 222.44 | 0.467760E+10 | 0.203283E+10 | 0.00 | 1.00 | 19-JUN-08:62 | 0.00 | 01-JUN-00:10 | 40164.65 | 30-JUN-08:61 | 25361.36 | 28-JUN-08:03 | 20309.30 | 23-JUN-08:62 | 8692.90 | 30-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.108979E+11 | 0.263891E+10 | 291.53 | 0.724673E+10 | 0.365117E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 40343.20 | 23-JUL-09:01 | 26321.02 | 07-JUL-08:62 | 21675.80 | 05-JUL-08:03 | 8618.17 | 23-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.775390E+10 | 0.189178E+10 | 263.43 | 0.513358E+10 | 0.262033E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 39264.05 | 30-AUG-08:61 | 23797.04 | 13-AUG-09:02 | 20056.01 | 29-AUG-08:62 | 8204.17 | 30-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.987336E+09 | 0.249578E+09 | 88.11 | 0.766415E+09 | 0.220921E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 38020.59 | 01-SEP-08:62 | 23355.09 | 02-SEP-08:62 | 18371.04 | 01-SEP-08:62 | 8041.19 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 29779194.20 | 8282544.29 | 13.33 | 26655398.71 | 3123795.48 | 0.00 | 0.16 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 | 2252.72 | 19-OCT-15:00 | 2023.48 | 19-OCT-15:00 | 249.13 | 22-OCT-14:10 | 624.40 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.287986E+11 | 0.708566E+10 | 1002.21 | 0.198436E+11 | 0.895498E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.108979E+11 | 0.263891E+10 | 291.53 | 0.724673E+10 | 0.365117E+10 | 0.00 | 1.00 | 0.00 | 40343.20 | 26977.53 | 21675.80 | 8692.90 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 23570018.10 | 6608849.75 | 3.17 | 19451411.88 | 4118606.22 | 0.00 | 0.37 | 23-APR-16:00 | 0.00 | 01-APR-00:05 | 2930.25 | 23-APR-16:00 | 2456.29 | 23-APR-16:00 | 484.16 | 23-APR-15:00 | 825.79 | 23-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.116394E+10 | 0.308032E+09 | 115.02 | 0.958694E+09 | 0.205249E+09 | 0.00 | 1.00 | 26-MAY-08:62 | 0.00 | 01-MAY-00:10 | 20236.54 | 26-MAY-08:62 | 13157.93 | 26-MAY-08:62 | 7078.62 | 26-MAY-08:62 | 4293.68 | 26-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.335488E+10 | 0.836222E+09 | 214.80 | 0.233290E+10 | 0.102198E+10 | 0.00 | 1.00 | 19-JUN-08:62 | 0.00 | 01-JUN-00:10 | 21654.81 | 30-JUN-08:61 | 13617.76 | 28-JUN-08:03 | 10955.08 | 23-JUN-08:62 | 4680.37 | 30-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.548880E+10 | 0.133949E+10 | 288.26 | 0.365354E+10 | 0.183526E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 21757.47 | 23-JUL-09:01 | 14198.58 | 07-JUL-08:62 | 11700.31 | 05-JUL-08:03 | 4649.38 | 23-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.385688E+10 | 0.948284E+09 | 259.44 | 0.255812E+10 | 0.129875E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 21191.58 | 30-AUG-08:61 | 12722.03 | 26-AUG-08:62 | 10831.40 | 29-AUG-08:62 | 4427.12 | 30-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.464960E+09 | 0.117899E+09 | 82.00 | 0.360140E+09 | 0.104820E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 20519.95 | 01-SEP-08:62 | 12593.87 | 02-SEP-08:62 | 9932.06 | 01-SEP-08:62 | 4339.44 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 9364283.25 | 2625267.57 | 12.33 | 8395341.07 | 968942.18 | 0.00 | 0.14 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 | 995.85 | 19-OCT-15:00 | 895.50 | 19-OCT-15:00 | 100.35 | 19-OCT-15:00 | 278.09 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.143624E+11 | 0.355916E+10 | 975.03 | 0.989124E+10 | 0.447116E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.548880E+10 | 0.133949E+10 | 288.26 | 0.365354E+10 | 0.183526E+10 | 0.00 | 1.00 | 0.00 | 21757.47 | 14198.58 | 11700.31 | 4680.37 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 21816539.86 | 6145046.78 | 3.00 | 17982728.21 | 3833811.66 | 0.00 | 0.35 | 23-APR-16:00 | 0.00 | 01-APR-00:05 | 2804.21 | 23-APR-16:00 | 2346.51 | 23-APR-16:00 | 462.15 | 23-APR-15:00 | 793.46 | 23-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.111117E+10 | 0.295132E+09 | 110.63 | 0.913982E+09 | 0.197187E+09 | 0.00 | 1.00 | 26-MAY-08:62 | 0.00 | 01-MAY-00:10 | 20271.12 | 26-MAY-08:62 | 13149.75 | 26-MAY-08:62 | 7121.36 | 26-MAY-08:62 | 4301.11 | 26-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.326127E+10 | 0.814206E+09 | 210.47 | 0.225953E+10 | 0.100174E+10 | 0.00 | 1.00 | 22-JUN-08:62 | 0.00 | 01-JUN-00:10 | 21691.52 | 30-JUN-08:61 | 13578.30 | 28-JUN-08:03 | 10139.60 | 23-JUN-08:62 | 4688.81 | 30-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.538179E+10 | 0.131586E+10 | 286.40 | 0.357612E+10 | 0.180567E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 21793.10 | 23-JUL-09:01 | 14200.38 | 07-JUL-08:62 | 11738.18 | 05-JUL-08:03 | 4657.73 | 23-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.376101E+10 | 0.926521E+09 | 256.92 | 0.249198E+10 | 0.126903E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 21230.16 | 30-AUG-08:61 | 12722.07 | 26-AUG-08:62 | 10866.95 | 29-AUG-08:62 | 4435.18 | 30-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.444120E+09 | 0.112675E+09 | 78.75 | 0.343011E+09 | 0.101109E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 20557.37 | 01-SEP-08:62 | 12597.77 | 02-SEP-08:62 | 9970.95 | 01-SEP-08:62 | 4347.35 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 6686773.93 | 1881964.69 | 11.33 | 5981594.72 | 705179.21 | 0.00 | 0.12 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 | 892.39 | 19-OCT-15:00 | 801.73 | 19-OCT-15:00 | 90.65 | 19-OCT-15:00 | 250.09 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.139879E+11 | 0.347242E+10 | 957.50 | 0.960860E+10 | 0.437927E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.538179E+10 | 0.131586E+10 | 286.40 | 0.357612E+10 | 0.180567E+10 | 0.00 | 1.00 | 0.00 | 21793.10 | 14200.38 | 11738.18 | 4688.81 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 17515672.99 | 4990999.23 | 2.83 | 14397031.70 | 3118641.29 | 0.00 | 0.31 | 23-APR-16:00 | 0.00 | 01-APR-00:05 | 2478.78 | 23-APR-16:00 | 2065.41 | 23-APR-16:00 | 413.37 | 23-APR-16:00 | 709.20 | 23-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.100327E+10 | 0.268690E+09 | 103.59 | 0.823228E+09 | 0.180045E+09 | 0.00 | 1.00 | 26-MAY-08:62 | 0.00 | 01-MAY-00:10 | 20539.04 | 26-MAY-08:62 | 13260.26 | 26-MAY-08:62 | 7278.77 | 26-MAY-08:62 | 4358.24 | 26-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.307662E+10 | 0.771591E+09 | 199.78 | 0.211904E+10 | 0.957585E+09 | 0.00 | 1.00 | 25-JUN-09:02 | 0.00 | 01-JUN-00:10 | 21976.47 | 30-JUN-08:61 | 13816.09 | 28-JUN-08:61 | 9783.05 | 25-JUN-09:02 | 4752.09 | 30-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.518665E+10 | 0.127402E+10 | 279.96 | 0.343749E+10 | 0.174916E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 22076.79 | 23-JUL-09:01 | 13425.19 | 25-JUL-08:61 | 11935.60 | 05-JUL-08:03 | 4720.53 | 23-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.358210E+10 | 0.886382E+09 | 251.54 | 0.237101E+10 | 0.121109E+10 | 0.00 | 1.00 | 08-AUG-08:62 | 0.00 | 01-AUG-00:10 | 21517.62 | 30-AUG-08:61 | 12850.52 | 26-AUG-08:62 | 11053.15 | 29-AUG-08:62 | 4495.26 | 30-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.406336E+09 | 0.103252E+09 | 70.92 | 0.311945E+09 | 94391021.70 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 20835.67 | 01-SEP-08:62 | 10689.27 | 02-SEP-08:62 | 10151.53 | 01-SEP-08:62 | 4406.22 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 2919634.06 | 827628.46 | 9.17 | 2598345.00 | 321289.07 | 0.00 | 0.09 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 | 690.47 | 19-OCT-15:00 | 619.35 | 19-OCT-15:00 | 71.12 | 19-OCT-15:00 | 194.91 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.132754E+11 | 0.330976E+10 | 917.78 | 0.907970E+10 | 0.419571E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.518665E+10 | 0.127402E+10 | 279.96 | 0.343749E+10 | 0.174916E+10 | 0.00 | 1.00 | 0.00 | 22076.79 | 13816.09 | 11935.60 | 4752.09 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 8386626.12 | 2469699.92 | 2.00 | 6871913.85 | 1514712.27 | 0.00 | 0.19 | 23-APR-16:00 | 0.00 | 01-APR-00:05 | 1671.61 | 23-APR-16:00 | 1382.57 | 23-APR-16:00 | 289.04 | 23-APR-16:00 | 493.50 | 23-APR-16:00 | 0.00 | 01-APR-00:05 |
May | 0.837822E+09 | 0.229498E+09 | 85.89 | 0.687854E+09 | 0.149969E+09 | 0.00 | 0.69 | 25-MAY-16:10 | 0.00 | 01-MAY-00:10 | 7094.89 | 25-MAY-16:10 | 5409.89 | 25-MAY-16:20 | 1919.18 | 26-MAY-12:10 | 1874.48 | 25-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 0.282310E+10 | 0.720783E+09 | 181.21 | 0.193807E+10 | 0.885032E+09 | 0.00 | 1.00 | 25-JUN-09:02 | 0.00 | 01-JUN-00:10 | 25243.92 | 30-JUN-08:61 | 15330.11 | 28-JUN-08:61 | 12663.56 | 30-JUN-08:02 | 5380.42 | 30-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.495543E+10 | 0.124048E+10 | 268.24 | 0.329840E+10 | 0.165704E+10 | 0.00 | 1.00 | 04-JUL-09:02 | 0.00 | 01-JUL-00:05 | 25053.95 | 23-JUL-09:01 | 15080.81 | 25-JUL-08:61 | 13705.93 | 05-JUL-08:61 | 5340.42 | 23-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.332144E+10 | 0.835282E+09 | 232.67 | 0.221894E+10 | 0.110250E+10 | 0.00 | 1.00 | 09-AUG-08:61 | 0.00 | 01-AUG-00:10 | 24339.12 | 30-AUG-08:61 | 12938.18 | 09-AUG-08:61 | 12515.52 | 30-AUG-08:61 | 5084.09 | 30-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.351557E+09 | 89975506.91 | 61.22 | 0.268352E+09 | 83204779.57 | 0.00 | 0.75 | 01-SEP-14:10 | 0.00 | 01-SEP-00:10 | 16684.42 | 01-SEP-08:62 | 8367.64 | 01-SEP-08:62 | 8316.78 | 01-SEP-08:62 | 3530.96 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 678226.29 | 194321.56 | 6.17 | 607041.49 | 71184.79 | 0.00 | 0.04 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 | 350.97 | 19-OCT-15:00 | 315.77 | 19-OCT-15:00 | 35.20 | 19-OCT-15:00 | 100.37 | 19-OCT-15:00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.122984E+11 | 0.311869E+10 | 837.40 | 0.841909E+10 | 0.387933E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.495543E+10 | 0.124048E+10 | 268.24 | 0.329840E+10 | 0.165704E+10 | 0.00 | 1.00 | 0.00 | 25243.92 | 15330.11 | 13705.93 | 5380.42 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 111.67 | 115.09 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 153.68 | 96.06 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 129.28 | 79.14 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 116.39 | 50.80 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 97.12 | 29.30 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 89.77 | 20.65 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 102.46 | 19.30 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.58 | 23.05 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 124.34 | 35.70 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 101.56 | 51.72 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 85.04 | 74.25 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 80.00 | 111.31 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 108.51 | 58.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 80.00 | 19.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 153.68 | 115.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 111.67 | 115.09 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 153.68 | 96.06 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 129.28 | 79.14 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 116.39 | 50.80 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 97.12 | 29.30 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 89.77 | 20.65 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 102.46 | 19.30 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.58 | 23.05 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 124.34 | 35.70 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 101.56 | 51.72 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 85.04 | 74.25 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 80.00 | 111.31 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 108.51 | 58.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 80.00 | 19.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 153.68 | 115.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 111.67 | 115.09 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 153.68 | 96.06 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 129.28 | 79.14 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 116.39 | 50.80 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 97.12 | 29.30 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 89.77 | 20.65 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 102.46 | 19.30 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.58 | 23.05 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 124.34 | 35.70 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 101.56 | 51.72 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 85.04 | 74.25 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 80.00 | 111.31 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 108.51 | 58.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 80.00 | 19.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 153.68 | 115.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 111.67 | 115.09 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 153.68 | 96.06 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 129.28 | 79.14 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 116.39 | 50.80 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 97.12 | 29.30 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 89.77 | 20.65 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 102.46 | 19.30 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.58 | 23.05 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 124.34 | 35.70 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 101.56 | 51.72 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 85.04 | 74.25 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 80.00 | 111.31 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 108.51 | 58.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 80.00 | 19.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 153.68 | 115.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.03 | 110.45 | 48.57 | 134.72 | 137.50 | 0.00 | 0.00 | 744.00 |
February | 201.74 | 136.14 | 65.60 | 185.27 | 114.80 | 0.00 | 0.00 | 672.00 |
March | 178.35 | 112.97 | 65.38 | 155.82 | 94.59 | 0.00 | 0.00 | 744.00 |
April | 161.90 | 88.14 | 73.77 | 140.24 | 60.78 | 0.00 | 0.00 | 720.00 |
May | 136.16 | 46.89 | 89.27 | 116.95 | 35.11 | 0.00 | 0.00 | 744.00 |
June | 122.18 | 32.91 | 89.27 | 108.05 | 24.76 | 0.00 | 0.00 | 720.00 |
July | 133.61 | 42.70 | 90.91 | 123.29 | 23.17 | 0.00 | 0.00 | 744.00 |
August | 142.60 | 59.93 | 82.66 | 137.90 | 27.64 | 0.00 | 0.00 | 744.00 |
September | 152.56 | 81.41 | 71.15 | 149.70 | 42.77 | 0.00 | 0.00 | 720.00 |
October | 129.98 | 76.45 | 53.53 | 122.33 | 61.93 | 0.00 | 0.00 | 744.00 |
November | 115.44 | 72.32 | 43.12 | 102.52 | 88.78 | 0.00 | 0.00 | 720.00 |
December | 122.77 | 80.34 | 42.43 | 96.55 | 132.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 146.00 | 78.02 | 67.98 | 130.73 | 70.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 115.44 | 32.91 | 42.43 | 96.55 | 23.17 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 201.74 | 136.14 | 90.91 | 185.27 | 137.50 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.03 | 110.45 | 48.57 | 134.72 | 137.50 | 0.00 | 0.00 | 744.00 |
February | 201.74 | 136.14 | 65.60 | 185.27 | 114.80 | 0.00 | 0.00 | 672.00 |
March | 178.35 | 112.97 | 65.38 | 155.82 | 94.59 | 0.00 | 0.00 | 744.00 |
April | 161.90 | 88.14 | 73.77 | 140.24 | 60.78 | 0.00 | 0.00 | 720.00 |
May | 136.16 | 46.89 | 89.27 | 116.95 | 35.11 | 0.00 | 0.00 | 744.00 |
June | 122.18 | 32.91 | 89.27 | 108.05 | 24.76 | 0.00 | 0.00 | 720.00 |
July | 133.61 | 42.70 | 90.91 | 123.29 | 23.17 | 0.00 | 0.00 | 744.00 |
August | 142.60 | 59.93 | 82.66 | 137.90 | 27.64 | 0.00 | 0.00 | 744.00 |
September | 152.56 | 81.41 | 71.15 | 149.70 | 42.77 | 0.00 | 0.00 | 720.00 |
October | 129.98 | 76.45 | 53.53 | 122.33 | 61.93 | 0.00 | 0.00 | 744.00 |
November | 115.44 | 72.32 | 43.12 | 102.52 | 88.78 | 0.00 | 0.00 | 720.00 |
December | 122.77 | 80.34 | 42.43 | 96.55 | 132.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 146.00 | 78.02 | 67.98 | 130.73 | 70.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 115.44 | 32.91 | 42.43 | 96.55 | 23.17 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 201.74 | 136.14 | 90.91 | 185.27 | 137.50 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 110.77 | 118.24 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 152.53 | 99.31 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 128.29 | 82.57 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 114.95 | 54.41 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 95.60 | 31.29 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 88.90 | 21.57 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 102.17 | 19.64 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.25 | 23.54 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 123.32 | 37.57 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 100.56 | 54.85 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 84.21 | 77.34 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 79.24 | 114.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 107.59 | 61.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 79.24 | 19.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 152.53 | 118.24 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 110.77 | 118.24 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 152.53 | 99.31 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 128.29 | 82.57 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 114.95 | 54.41 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 95.60 | 31.29 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 88.90 | 21.57 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 102.17 | 19.64 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.25 | 23.54 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 123.32 | 37.57 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 100.56 | 54.85 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 84.21 | 77.34 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 79.24 | 114.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 107.59 | 61.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 79.24 | 19.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 152.53 | 118.24 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.03 | 110.45 | 48.57 | 133.63 | 141.26 | 0.00 | 0.00 | 744.00 |
February | 201.74 | 136.14 | 65.60 | 183.89 | 118.68 | 0.00 | 0.00 | 672.00 |
March | 178.35 | 112.97 | 65.38 | 154.61 | 98.69 | 0.00 | 0.00 | 744.00 |
April | 161.90 | 88.14 | 73.77 | 138.50 | 65.07 | 0.00 | 0.00 | 720.00 |
May | 136.16 | 46.89 | 89.27 | 115.13 | 37.48 | 0.00 | 0.00 | 744.00 |
June | 122.18 | 32.91 | 89.27 | 107.00 | 25.87 | 0.00 | 0.00 | 720.00 |
July | 133.61 | 42.70 | 90.91 | 122.93 | 23.56 | 0.00 | 0.00 | 744.00 |
August | 142.60 | 59.93 | 82.66 | 137.50 | 28.23 | 0.00 | 0.00 | 744.00 |
September | 152.56 | 81.41 | 71.15 | 148.48 | 45.00 | 0.00 | 0.00 | 720.00 |
October | 129.98 | 76.45 | 53.53 | 121.13 | 65.63 | 0.00 | 0.00 | 744.00 |
November | 115.44 | 72.32 | 43.12 | 101.52 | 92.46 | 0.00 | 0.00 | 720.00 |
December | 122.77 | 80.34 | 42.43 | 95.63 | 136.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 146.00 | 78.02 | 67.98 | 129.62 | 73.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 115.44 | 32.91 | 42.43 | 95.63 | 23.56 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 201.74 | 136.14 | 90.91 | 183.89 | 141.26 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 110.82 | 116.37 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 152.59 | 97.84 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 128.32 | 81.41 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 115.11 | 53.42 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 95.62 | 31.65 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 88.67 | 22.55 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 101.73 | 21.04 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.06 | 24.85 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 123.34 | 38.15 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 100.76 | 53.89 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 84.36 | 75.93 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 79.28 | 112.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 107.58 | 60.67 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 79.28 | 21.04 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 152.59 | 116.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 110.82 | 116.37 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 152.59 | 97.84 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 128.32 | 81.41 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 115.11 | 53.42 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 95.62 | 31.65 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 88.67 | 22.55 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 101.73 | 21.04 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.06 | 24.85 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 123.34 | 38.15 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 100.76 | 53.89 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 84.36 | 75.93 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 79.28 | 112.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 107.58 | 60.67 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 79.28 | 21.04 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 152.59 | 116.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.16 | 109.85 | 48.31 | 132.97 | 138.27 | 0.00 | 0.00 | 744.00 |
February | 200.64 | 135.40 | 65.24 | 182.96 | 116.29 | 0.00 | 0.00 | 672.00 |
March | 177.38 | 112.35 | 65.02 | 153.81 | 96.77 | 0.00 | 0.00 | 744.00 |
April | 161.02 | 87.66 | 73.36 | 137.93 | 63.56 | 0.00 | 0.00 | 720.00 |
May | 135.41 | 46.63 | 88.78 | 114.52 | 37.69 | 0.00 | 0.00 | 744.00 |
June | 121.51 | 32.73 | 88.78 | 106.14 | 26.87 | 0.00 | 0.00 | 720.00 |
July | 132.88 | 42.47 | 90.41 | 121.75 | 25.09 | 0.00 | 0.00 | 744.00 |
August | 141.82 | 59.61 | 82.21 | 136.53 | 29.61 | 0.00 | 0.00 | 744.00 |
September | 151.73 | 80.97 | 70.76 | 147.70 | 45.43 | 0.00 | 0.00 | 720.00 |
October | 129.27 | 76.03 | 53.24 | 120.71 | 64.15 | 0.00 | 0.00 | 744.00 |
November | 114.81 | 71.93 | 42.88 | 101.15 | 90.28 | 0.00 | 0.00 | 720.00 |
December | 122.10 | 79.90 | 42.20 | 95.16 | 134.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.20 | 77.59 | 67.61 | 128.90 | 72.15 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.81 | 32.73 | 42.20 | 95.16 | 25.09 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 200.64 | 135.40 | 90.41 | 182.96 | 138.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 110.94 | 115.56 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 152.73 | 97.10 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 128.44 | 80.71 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 115.47 | 52.52 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 96.20 | 30.97 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 88.96 | 22.25 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 101.82 | 20.98 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.16 | 24.70 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 123.80 | 37.40 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 101.11 | 52.93 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 84.53 | 75.11 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 79.37 | 112.07 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 107.81 | 60.03 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 79.37 | 20.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 152.73 | 115.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 110.94 | 115.56 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 152.73 | 97.10 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 128.44 | 80.71 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 115.47 | 52.52 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 96.20 | 30.97 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 88.96 | 22.25 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 101.82 | 20.98 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.16 | 24.70 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 123.80 | 37.40 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 101.11 | 52.93 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 84.53 | 75.11 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 79.37 | 112.07 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 107.81 | 60.03 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 79.37 | 20.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 152.73 | 115.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.16 | 109.85 | 48.31 | 133.11 | 137.31 | 0.00 | 0.00 | 744.00 |
February | 200.64 | 135.40 | 65.24 | 183.13 | 115.40 | 0.00 | 0.00 | 672.00 |
March | 177.38 | 112.35 | 65.02 | 153.96 | 95.94 | 0.00 | 0.00 | 744.00 |
April | 161.02 | 87.66 | 73.36 | 138.37 | 62.48 | 0.00 | 0.00 | 720.00 |
May | 135.41 | 46.63 | 88.78 | 115.21 | 36.88 | 0.00 | 0.00 | 744.00 |
June | 121.51 | 32.73 | 88.78 | 106.48 | 26.51 | 0.00 | 0.00 | 720.00 |
July | 132.88 | 42.47 | 90.41 | 121.85 | 25.02 | 0.00 | 0.00 | 744.00 |
August | 141.82 | 59.61 | 82.21 | 136.65 | 29.43 | 0.00 | 0.00 | 744.00 |
September | 151.73 | 80.97 | 70.76 | 148.25 | 44.54 | 0.00 | 0.00 | 720.00 |
October | 129.27 | 76.03 | 53.24 | 121.13 | 63.00 | 0.00 | 0.00 | 744.00 |
November | 114.81 | 71.93 | 42.88 | 101.35 | 89.31 | 0.00 | 0.00 | 720.00 |
December | 122.10 | 79.90 | 42.20 | 95.27 | 133.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.20 | 77.59 | 67.61 | 129.19 | 71.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.81 | 32.73 | 42.20 | 95.27 | 25.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 200.64 | 135.40 | 90.41 | 183.13 | 137.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 111.08 | 114.95 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 152.92 | 96.45 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 128.61 | 80.07 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 115.79 | 51.80 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 96.66 | 30.33 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 89.30 | 21.82 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 101.99 | 20.74 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.32 | 24.40 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 124.12 | 36.78 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 101.36 | 52.27 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 84.70 | 74.43 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 79.49 | 111.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 108.05 | 59.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 79.49 | 20.74 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 152.92 | 114.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 111.08 | 114.95 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 152.92 | 96.45 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 128.61 | 80.07 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 115.79 | 51.80 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 96.66 | 30.33 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 89.30 | 21.82 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 101.99 | 20.74 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.32 | 24.40 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 124.12 | 36.78 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 101.36 | 52.27 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 84.70 | 74.43 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 79.49 | 111.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 108.05 | 59.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 79.49 | 20.74 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 152.92 | 114.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.16 | 109.85 | 48.31 | 133.28 | 136.57 | 0.00 | 0.00 | 744.00 |
February | 200.64 | 135.40 | 65.24 | 183.36 | 114.64 | 0.00 | 0.00 | 672.00 |
March | 177.38 | 112.35 | 65.02 | 154.17 | 95.17 | 0.00 | 0.00 | 744.00 |
April | 161.02 | 87.66 | 73.36 | 138.75 | 61.63 | 0.00 | 0.00 | 720.00 |
May | 135.41 | 46.63 | 88.78 | 115.77 | 36.13 | 0.00 | 0.00 | 744.00 |
June | 121.51 | 32.73 | 88.78 | 106.89 | 26.01 | 0.00 | 0.00 | 720.00 |
July | 132.88 | 42.47 | 90.41 | 122.05 | 24.73 | 0.00 | 0.00 | 744.00 |
August | 141.82 | 59.61 | 82.21 | 136.85 | 29.08 | 0.00 | 0.00 | 744.00 |
September | 151.73 | 80.97 | 70.76 | 148.63 | 43.80 | 0.00 | 0.00 | 720.00 |
October | 129.27 | 76.03 | 53.24 | 121.43 | 62.21 | 0.00 | 0.00 | 744.00 |
November | 114.81 | 71.93 | 42.88 | 101.56 | 88.49 | 0.00 | 0.00 | 720.00 |
December | 122.10 | 79.90 | 42.20 | 95.42 | 132.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.20 | 77.59 | 67.61 | 129.47 | 70.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.81 | 32.73 | 42.20 | 95.42 | 24.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 200.64 | 135.40 | 90.41 | 183.36 | 136.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 111.76 | 112.74 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 153.76 | 94.38 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 129.21 | 78.11 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 116.41 | 50.15 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 97.25 | 29.03 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 89.69 | 20.80 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 101.97 | 20.00 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.37 | 23.55 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 124.46 | 35.59 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 101.79 | 50.91 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 85.27 | 72.52 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 80.07 | 109.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 108.52 | 57.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 80.07 | 20.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 153.76 | 112.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 111.76 | 112.74 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 153.76 | 94.38 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 129.21 | 78.11 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 116.41 | 50.15 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 97.25 | 29.03 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 89.69 | 20.80 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 101.97 | 20.00 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.37 | 23.55 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 124.46 | 35.59 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 101.79 | 50.91 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 85.27 | 72.52 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 80.07 | 109.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 108.52 | 57.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 80.07 | 20.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 153.76 | 112.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 111.76 | 112.74 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 153.76 | 94.38 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 129.21 | 78.11 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 116.41 | 50.15 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 97.25 | 29.03 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 89.69 | 20.80 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 101.97 | 20.00 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.37 | 23.55 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 124.46 | 35.59 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 101.79 | 50.91 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 85.27 | 72.52 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 80.07 | 109.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 108.52 | 57.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 80.07 | 20.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 153.76 | 112.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 111.76 | 112.74 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 153.76 | 94.38 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 129.21 | 78.11 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 116.41 | 50.15 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 97.25 | 29.03 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 89.69 | 20.80 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 101.97 | 20.00 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.37 | 23.55 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 124.46 | 35.59 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 101.79 | 50.91 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 85.27 | 72.52 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 80.07 | 109.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 108.52 | 57.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 80.07 | 20.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 153.76 | 112.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.16 | 109.85 | 48.31 | 134.09 | 133.97 | 0.00 | 0.00 | 744.00 |
February | 200.64 | 135.40 | 65.24 | 184.36 | 112.18 | 0.00 | 0.00 | 672.00 |
March | 177.38 | 112.35 | 65.02 | 154.89 | 92.85 | 0.00 | 0.00 | 744.00 |
April | 161.02 | 87.66 | 73.36 | 139.51 | 59.67 | 0.00 | 0.00 | 720.00 |
May | 135.41 | 46.63 | 88.78 | 116.48 | 34.58 | 0.00 | 0.00 | 744.00 |
June | 121.51 | 32.73 | 88.78 | 107.38 | 24.79 | 0.00 | 0.00 | 720.00 |
July | 132.88 | 42.47 | 90.41 | 122.04 | 23.85 | 0.00 | 0.00 | 744.00 |
August | 141.82 | 59.61 | 82.21 | 136.91 | 28.07 | 0.00 | 0.00 | 744.00 |
September | 151.73 | 80.97 | 70.76 | 149.04 | 42.39 | 0.00 | 0.00 | 720.00 |
October | 129.27 | 76.03 | 53.24 | 121.95 | 60.60 | 0.00 | 0.00 | 744.00 |
November | 114.81 | 71.93 | 42.88 | 102.24 | 86.22 | 0.00 | 0.00 | 720.00 |
December | 122.10 | 79.90 | 42.20 | 96.12 | 129.66 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.20 | 77.59 | 67.61 | 130.04 | 68.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.81 | 32.73 | 42.20 | 96.12 | 23.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 200.64 | 135.40 | 90.41 | 184.36 | 133.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.16 | 109.85 | 48.31 | 134.09 | 133.97 | 0.00 | 0.00 | 744.00 |
February | 200.64 | 135.40 | 65.24 | 184.36 | 112.18 | 0.00 | 0.00 | 672.00 |
March | 177.38 | 112.35 | 65.02 | 154.89 | 92.85 | 0.00 | 0.00 | 744.00 |
April | 161.02 | 87.66 | 73.36 | 139.51 | 59.67 | 0.00 | 0.00 | 720.00 |
May | 135.41 | 46.63 | 88.78 | 116.48 | 34.58 | 0.00 | 0.00 | 744.00 |
June | 121.51 | 32.73 | 88.78 | 107.38 | 24.79 | 0.00 | 0.00 | 720.00 |
July | 132.88 | 42.47 | 90.41 | 122.04 | 23.85 | 0.00 | 0.00 | 744.00 |
August | 141.82 | 59.61 | 82.21 | 136.91 | 28.07 | 0.00 | 0.00 | 744.00 |
September | 151.73 | 80.97 | 70.76 | 149.04 | 42.39 | 0.00 | 0.00 | 720.00 |
October | 129.27 | 76.03 | 53.24 | 121.95 | 60.60 | 0.00 | 0.00 | 744.00 |
November | 114.81 | 71.93 | 42.88 | 102.24 | 86.22 | 0.00 | 0.00 | 720.00 |
December | 122.10 | 79.90 | 42.20 | 96.12 | 129.66 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.20 | 77.59 | 67.61 | 130.04 | 68.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.81 | 32.73 | 42.20 | 96.12 | 23.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 200.64 | 135.40 | 90.41 | 184.36 | 133.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 111.43 | 113.33 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 153.42 | 94.77 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 129.01 | 78.34 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 116.38 | 50.06 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 97.43 | 28.77 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 89.93 | 20.53 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 102.15 | 19.77 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.46 | 23.32 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 124.49 | 35.36 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 101.71 | 50.80 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 85.09 | 72.71 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 79.80 | 109.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 108.46 | 57.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 79.80 | 19.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 153.42 | 113.33 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 111.43 | 113.33 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 153.42 | 94.77 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 129.01 | 78.34 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 116.38 | 50.06 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 97.43 | 28.77 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 89.93 | 20.53 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 102.15 | 19.77 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.46 | 23.32 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 124.49 | 35.36 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 101.71 | 50.80 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 85.09 | 72.71 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 79.80 | 109.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 108.46 | 57.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 79.80 | 19.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 153.42 | 113.33 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.16 | 109.85 | 48.31 | 133.71 | 134.64 | 0.00 | 0.00 | 744.00 |
February | 200.64 | 135.40 | 65.24 | 183.98 | 112.63 | 0.00 | 0.00 | 672.00 |
March | 177.38 | 112.35 | 65.02 | 154.66 | 93.10 | 0.00 | 0.00 | 744.00 |
April | 161.02 | 87.66 | 73.36 | 139.48 | 59.55 | 0.00 | 0.00 | 720.00 |
May | 135.41 | 46.63 | 88.78 | 116.70 | 34.26 | 0.00 | 0.00 | 744.00 |
June | 121.51 | 32.73 | 88.78 | 107.66 | 24.47 | 0.00 | 0.00 | 720.00 |
July | 132.88 | 42.47 | 90.41 | 122.26 | 23.57 | 0.00 | 0.00 | 744.00 |
August | 141.82 | 59.61 | 82.21 | 137.02 | 27.79 | 0.00 | 0.00 | 744.00 |
September | 151.73 | 80.97 | 70.76 | 149.08 | 42.11 | 0.00 | 0.00 | 720.00 |
October | 129.27 | 76.03 | 53.24 | 121.87 | 60.46 | 0.00 | 0.00 | 744.00 |
November | 114.81 | 71.93 | 42.88 | 102.04 | 86.43 | 0.00 | 0.00 | 720.00 |
December | 122.10 | 79.90 | 42.20 | 95.80 | 130.37 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.20 | 77.59 | 67.61 | 129.98 | 68.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.81 | 32.73 | 42.20 | 95.80 | 23.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 200.64 | 135.40 | 90.41 | 183.98 | 134.64 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 111.45 | 113.22 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 153.46 | 94.61 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 129.07 | 78.13 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 116.52 | 49.77 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 97.66 | 28.49 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 90.15 | 20.31 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 102.26 | 19.66 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.55 | 23.18 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 124.62 | 35.14 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 101.80 | 50.57 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 85.15 | 72.49 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 79.82 | 109.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 108.56 | 57.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 79.82 | 19.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 153.46 | 113.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 111.45 | 113.22 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 153.46 | 94.61 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 129.07 | 78.13 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 116.52 | 49.77 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 97.66 | 28.49 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 90.15 | 20.31 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 102.26 | 19.66 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.55 | 23.18 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 124.62 | 35.14 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 101.80 | 50.57 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 85.15 | 72.49 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 79.82 | 109.65 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 108.56 | 57.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 79.82 | 19.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 153.46 | 113.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.16 | 109.85 | 48.31 | 133.74 | 134.51 | 0.00 | 0.00 | 744.00 |
February | 200.64 | 135.40 | 65.24 | 184.03 | 112.44 | 0.00 | 0.00 | 672.00 |
March | 177.38 | 112.35 | 65.02 | 154.73 | 92.86 | 0.00 | 0.00 | 744.00 |
April | 161.02 | 87.66 | 73.36 | 139.64 | 59.21 | 0.00 | 0.00 | 720.00 |
May | 135.41 | 46.63 | 88.78 | 116.97 | 33.93 | 0.00 | 0.00 | 744.00 |
June | 121.51 | 32.73 | 88.78 | 107.92 | 24.21 | 0.00 | 0.00 | 720.00 |
July | 132.88 | 42.47 | 90.41 | 122.39 | 23.44 | 0.00 | 0.00 | 744.00 |
August | 141.82 | 59.61 | 82.21 | 137.14 | 27.63 | 0.00 | 0.00 | 744.00 |
September | 151.73 | 80.97 | 70.76 | 149.24 | 41.84 | 0.00 | 0.00 | 720.00 |
October | 129.27 | 76.03 | 53.24 | 121.97 | 60.19 | 0.00 | 0.00 | 744.00 |
November | 114.81 | 71.93 | 42.88 | 102.11 | 86.17 | 0.00 | 0.00 | 720.00 |
December | 122.10 | 79.90 | 42.20 | 95.83 | 130.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.20 | 77.59 | 67.61 | 130.10 | 68.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.81 | 32.73 | 42.20 | 95.83 | 23.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 200.64 | 135.40 | 90.41 | 184.03 | 134.51 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 111.57 | 112.56 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 153.65 | 93.85 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 129.26 | 77.27 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 116.88 | 48.86 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 98.18 | 27.81 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 90.60 | 19.83 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 102.45 | 19.42 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.74 | 22.89 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 124.88 | 34.66 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 102.01 | 49.95 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 85.33 | 71.71 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 79.93 | 108.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 108.81 | 57.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 79.93 | 19.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 153.65 | 112.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 111.57 | 112.56 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 153.65 | 93.85 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 129.26 | 77.27 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 116.88 | 48.86 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 98.18 | 27.81 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 90.60 | 19.83 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 102.45 | 19.42 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 114.74 | 22.89 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 124.88 | 34.66 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 102.01 | 49.95 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 85.33 | 71.71 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 79.93 | 108.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 108.81 | 57.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 79.93 | 19.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 153.65 | 112.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.16 | 109.85 | 48.31 | 133.88 | 133.72 | 0.00 | 0.00 | 744.00 |
February | 200.64 | 135.40 | 65.24 | 184.26 | 111.53 | 0.00 | 0.00 | 672.00 |
March | 177.38 | 112.35 | 65.02 | 154.97 | 91.83 | 0.00 | 0.00 | 744.00 |
April | 161.02 | 87.66 | 73.36 | 140.08 | 58.12 | 0.00 | 0.00 | 720.00 |
May | 135.41 | 46.63 | 88.78 | 117.60 | 33.12 | 0.00 | 0.00 | 744.00 |
June | 121.51 | 32.73 | 88.78 | 108.46 | 23.64 | 0.00 | 0.00 | 720.00 |
July | 132.88 | 42.47 | 90.41 | 122.63 | 23.16 | 0.00 | 0.00 | 744.00 |
August | 141.82 | 59.61 | 82.21 | 137.36 | 27.28 | 0.00 | 0.00 | 744.00 |
September | 151.73 | 80.97 | 70.76 | 149.55 | 41.27 | 0.00 | 0.00 | 720.00 |
October | 129.27 | 76.03 | 53.24 | 122.23 | 59.45 | 0.00 | 0.00 | 744.00 |
November | 114.81 | 71.93 | 42.88 | 102.34 | 85.24 | 0.00 | 0.00 | 720.00 |
December | 122.10 | 79.90 | 42.20 | 95.96 | 129.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.20 | 77.59 | 67.61 | 130.40 | 67.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.81 | 32.73 | 42.20 | 95.96 | 23.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 200.64 | 135.40 | 90.41 | 184.26 | 133.72 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 112.23 | 109.37 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 154.47 | 90.44 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 130.07 | 73.45 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 117.97 | 45.34 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 99.56 | 25.61 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 91.70 | 18.30 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 102.97 | 18.49 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 115.21 | 21.85 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 125.53 | 33.07 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 102.64 | 47.71 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 85.98 | 68.54 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 80.48 | 105.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 109.58 | 54.67 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 80.48 | 18.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 154.47 | 109.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.09 | 91.74 | 40.35 | 112.23 | 109.37 | 0.00 | 0.00 | 744.00 |
February | 167.57 | 113.08 | 54.48 | 154.47 | 90.44 | 0.00 | 0.00 | 672.00 |
March | 148.14 | 93.83 | 54.31 | 130.07 | 73.45 | 0.00 | 0.00 | 744.00 |
April | 134.48 | 73.21 | 61.27 | 117.97 | 45.34 | 0.00 | 0.00 | 720.00 |
May | 113.09 | 38.95 | 74.15 | 99.56 | 25.61 | 0.00 | 0.00 | 744.00 |
June | 101.48 | 27.34 | 74.15 | 91.70 | 18.30 | 0.00 | 0.00 | 720.00 |
July | 110.98 | 35.47 | 75.51 | 102.97 | 18.49 | 0.00 | 0.00 | 744.00 |
August | 118.44 | 49.78 | 68.66 | 115.21 | 21.85 | 0.00 | 0.00 | 744.00 |
September | 126.72 | 67.62 | 59.10 | 125.53 | 33.07 | 0.00 | 0.00 | 720.00 |
October | 107.96 | 63.50 | 44.47 | 102.64 | 47.71 | 0.00 | 0.00 | 744.00 |
November | 95.89 | 60.07 | 35.81 | 85.98 | 68.54 | 0.00 | 0.00 | 720.00 |
December | 101.97 | 66.73 | 35.24 | 80.48 | 105.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 121.26 | 64.80 | 56.46 | 109.58 | 54.67 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 95.89 | 27.34 | 35.24 | 80.48 | 18.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 167.57 | 113.08 | 75.51 | 154.47 | 109.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.16 | 109.85 | 48.31 | 134.69 | 129.89 | 0.00 | 0.00 | 744.00 |
February | 200.64 | 135.40 | 65.24 | 185.25 | 107.45 | 0.00 | 0.00 | 672.00 |
March | 177.38 | 112.35 | 65.02 | 155.96 | 87.27 | 0.00 | 0.00 | 744.00 |
April | 161.02 | 87.66 | 73.36 | 141.41 | 53.94 | 0.00 | 0.00 | 720.00 |
May | 135.41 | 46.63 | 88.78 | 119.26 | 30.51 | 0.00 | 0.00 | 744.00 |
June | 121.51 | 32.73 | 88.78 | 109.79 | 21.82 | 0.00 | 0.00 | 720.00 |
July | 132.88 | 42.47 | 90.41 | 123.25 | 22.05 | 0.00 | 0.00 | 744.00 |
August | 141.82 | 59.61 | 82.21 | 137.92 | 26.05 | 0.00 | 0.00 | 744.00 |
September | 151.73 | 80.97 | 70.76 | 150.33 | 39.38 | 0.00 | 0.00 | 720.00 |
October | 129.27 | 76.03 | 53.24 | 122.99 | 56.78 | 0.00 | 0.00 | 744.00 |
November | 114.81 | 71.93 | 42.88 | 103.12 | 81.47 | 0.00 | 0.00 | 720.00 |
December | 122.10 | 79.90 | 42.20 | 96.63 | 125.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.20 | 77.59 | 67.61 | 131.34 | 65.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.81 | 32.73 | 42.20 | 96.63 | 21.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 200.64 | 135.40 | 90.41 | 185.25 | 129.89 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.299110E+09 | 0.308258E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.371771E+09 | 0.232397E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.346265E+09 | 0.211975E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.301682E+09 | 0.131664E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.260115E+09 | 78465724.40 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.232682E+09 | 53512357.75 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.274424E+09 | 51704828.19 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.306887E+09 | 61728229.38 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.322288E+09 | 92527485.21 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.272006E+09 | 0.138534E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.220414E+09 | 0.192462E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.214266E+09 | 0.298131E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.342191E+10 | 0.185136E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.214266E+09 | 51704828.19 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.371771E+09 | 0.308258E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.299110E+09 | 0.308258E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.371771E+09 | 0.232397E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.346265E+09 | 0.211975E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.301682E+09 | 0.131664E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.260115E+09 | 78465724.40 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.232682E+09 | 53512357.75 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.274424E+09 | 51704828.19 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.306887E+09 | 61728229.38 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.322288E+09 | 92527485.21 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.272006E+09 | 0.138534E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.220414E+09 | 0.192462E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.214266E+09 | 0.298131E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.342191E+10 | 0.185136E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.214266E+09 | 51704828.19 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.371771E+09 | 0.308258E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.299110E+09 | 0.308258E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.371771E+09 | 0.232397E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.346265E+09 | 0.211975E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.301682E+09 | 0.131664E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.260115E+09 | 78465724.40 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.232682E+09 | 53512357.75 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.274424E+09 | 51704828.19 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.306887E+09 | 61728229.38 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.322288E+09 | 92527485.21 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.272006E+09 | 0.138534E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.220414E+09 | 0.192462E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.214266E+09 | 0.298131E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.342191E+10 | 0.185136E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.214266E+09 | 51704828.19 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.371771E+09 | 0.308258E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.299110E+09 | 0.308258E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.371771E+09 | 0.232397E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.346265E+09 | 0.211975E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.301682E+09 | 0.131664E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.260115E+09 | 78465724.40 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.232682E+09 | 53512357.75 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.274424E+09 | 51704828.19 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.306887E+09 | 61728229.38 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.322288E+09 | 92527485.21 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.272006E+09 | 0.138534E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.220414E+09 | 0.192462E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.214266E+09 | 0.298131E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.342191E+10 | 0.185136E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.214266E+09 | 51704828.19 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.371771E+09 | 0.308258E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425937E+09 | 0.295837E+09 | 0.130099E+09 | 0.360839E+09 | 0.368272E+09 |
February | 0.488053E+09 | 0.329361E+09 | 0.158692E+09 | 0.448207E+09 | 0.277735E+09 |
March | 0.477692E+09 | 0.302577E+09 | 0.175115E+09 | 0.417344E+09 | 0.253361E+09 |
April | 0.419657E+09 | 0.228452E+09 | 0.191204E+09 | 0.363501E+09 | 0.157545E+09 |
May | 0.364682E+09 | 0.125585E+09 | 0.239097E+09 | 0.313236E+09 | 94026566.30 |
June | 0.316685E+09 | 85303751.30 | 0.231381E+09 | 0.280055E+09 | 64182849.15 |
July | 0.357870E+09 | 0.114373E+09 | 0.243497E+09 | 0.330210E+09 | 62052201.69 |
August | 0.381935E+09 | 0.160526E+09 | 0.221409E+09 | 0.369355E+09 | 74035647.91 |
September | 0.395438E+09 | 0.211016E+09 | 0.184422E+09 | 0.388031E+09 | 0.110868E+09 |
October | 0.348142E+09 | 0.204757E+09 | 0.143384E+09 | 0.327639E+09 | 0.165864E+09 |
November | 0.299223E+09 | 0.187460E+09 | 0.111764E+09 | 0.265723E+09 | 0.230124E+09 |
December | 0.328818E+09 | 0.215174E+09 | 0.113644E+09 | 0.258604E+09 | 0.356093E+09 |
Annual Sum or Average | 0.460413E+10 | 0.246042E+10 | 0.214371E+10 | 0.412275E+10 | 0.221416E+10 |
Minimum of Months | 0.299223E+09 | 85303751.30 | 0.111764E+09 | 0.258604E+09 | 62052201.69 |
Maximum of Months | 0.488053E+09 | 0.329361E+09 | 0.243497E+09 | 0.448207E+09 | 0.368272E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425937E+09 | 0.295837E+09 | 0.130099E+09 | 0.360839E+09 | 0.368272E+09 |
February | 0.488053E+09 | 0.329361E+09 | 0.158692E+09 | 0.448207E+09 | 0.277735E+09 |
March | 0.477692E+09 | 0.302577E+09 | 0.175115E+09 | 0.417344E+09 | 0.253361E+09 |
April | 0.419657E+09 | 0.228452E+09 | 0.191204E+09 | 0.363501E+09 | 0.157545E+09 |
May | 0.364682E+09 | 0.125585E+09 | 0.239097E+09 | 0.313236E+09 | 94026566.30 |
June | 0.316685E+09 | 85303751.30 | 0.231381E+09 | 0.280055E+09 | 64182849.15 |
July | 0.357870E+09 | 0.114373E+09 | 0.243497E+09 | 0.330210E+09 | 62052201.69 |
August | 0.381935E+09 | 0.160526E+09 | 0.221409E+09 | 0.369355E+09 | 74035647.91 |
September | 0.395438E+09 | 0.211016E+09 | 0.184422E+09 | 0.388031E+09 | 0.110868E+09 |
October | 0.348142E+09 | 0.204757E+09 | 0.143384E+09 | 0.327639E+09 | 0.165864E+09 |
November | 0.299223E+09 | 0.187460E+09 | 0.111764E+09 | 0.265723E+09 | 0.230124E+09 |
December | 0.328818E+09 | 0.215174E+09 | 0.113644E+09 | 0.258604E+09 | 0.356093E+09 |
Annual Sum or Average | 0.460413E+10 | 0.246042E+10 | 0.214371E+10 | 0.412275E+10 | 0.221416E+10 |
Minimum of Months | 0.299223E+09 | 85303751.30 | 0.111764E+09 | 0.258604E+09 | 62052201.69 |
Maximum of Months | 0.488053E+09 | 0.329361E+09 | 0.243497E+09 | 0.448207E+09 | 0.368272E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.296693E+09 | 0.316700E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.369012E+09 | 0.240257E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.343601E+09 | 0.221155E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.297949E+09 | 0.141020E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.256061E+09 | 83798020.38 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.230433E+09 | 55911937.39 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.273643E+09 | 52592180.00 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.305996E+09 | 63053706.03 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.319640E+09 | 97387118.53 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.269330E+09 | 0.146899E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.218279E+09 | 0.200478E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.212234E+09 | 0.307072E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.339287E+10 | 0.192632E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.212234E+09 | 52592180.00 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.369012E+09 | 0.316700E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.296693E+09 | 0.316700E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.369012E+09 | 0.240257E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.343601E+09 | 0.221155E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.297949E+09 | 0.141020E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.256061E+09 | 83798020.38 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.230433E+09 | 55911937.39 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.273643E+09 | 52592180.00 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.305996E+09 | 63053706.03 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.319640E+09 | 97387118.53 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.269330E+09 | 0.146899E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.218279E+09 | 0.200478E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.212234E+09 | 0.307072E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.339287E+10 | 0.192632E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.212234E+09 | 52592180.00 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.369012E+09 | 0.316700E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425937E+09 | 0.295837E+09 | 0.130099E+09 | 0.357916E+09 | 0.378364E+09 |
February | 0.488053E+09 | 0.329361E+09 | 0.158692E+09 | 0.444873E+09 | 0.287118E+09 |
March | 0.477692E+09 | 0.302577E+09 | 0.175115E+09 | 0.414109E+09 | 0.264326E+09 |
April | 0.419657E+09 | 0.228452E+09 | 0.191204E+09 | 0.358988E+09 | 0.168674E+09 |
May | 0.364682E+09 | 0.125585E+09 | 0.239097E+09 | 0.308367E+09 | 0.100376E+09 |
June | 0.316685E+09 | 85303751.30 | 0.231381E+09 | 0.277342E+09 | 67051116.33 |
July | 0.357870E+09 | 0.114373E+09 | 0.243497E+09 | 0.329260E+09 | 63115721.81 |
August | 0.381935E+09 | 0.160526E+09 | 0.221409E+09 | 0.368283E+09 | 75614489.08 |
September | 0.395438E+09 | 0.211016E+09 | 0.184422E+09 | 0.384864E+09 | 0.116644E+09 |
October | 0.348142E+09 | 0.204757E+09 | 0.143384E+09 | 0.324422E+09 | 0.175796E+09 |
November | 0.299223E+09 | 0.187460E+09 | 0.111764E+09 | 0.263148E+09 | 0.239666E+09 |
December | 0.328818E+09 | 0.215174E+09 | 0.113644E+09 | 0.256136E+09 | 0.366764E+09 |
Annual Sum or Average | 0.460413E+10 | 0.246042E+10 | 0.214371E+10 | 0.408771E+10 | 0.230351E+10 |
Minimum of Months | 0.299223E+09 | 85303751.30 | 0.111764E+09 | 0.256136E+09 | 63115721.81 |
Maximum of Months | 0.488053E+09 | 0.329361E+09 | 0.243497E+09 | 0.444873E+09 | 0.378364E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.296833E+09 | 0.311680E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.369140E+09 | 0.236693E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.343691E+09 | 0.218038E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.298353E+09 | 0.138475E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.256098E+09 | 84769146.92 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.229830E+09 | 58452544.01 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.272481E+09 | 56365378.46 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.305496E+09 | 66547025.07 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.319701E+09 | 98882678.24 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.269867E+09 | 0.144346E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.218665E+09 | 0.196805E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.212335E+09 | 0.302329E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.339249E+10 | 0.191338E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.212335E+09 | 56365378.46 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.369140E+09 | 0.311680E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.296833E+09 | 0.311680E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.369140E+09 | 0.236693E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.343691E+09 | 0.218038E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.298353E+09 | 0.138475E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.256098E+09 | 84769146.92 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.229830E+09 | 58452544.01 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.272481E+09 | 56365378.46 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.305496E+09 | 66547025.07 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.319701E+09 | 98882678.24 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.269867E+09 | 0.144346E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.218665E+09 | 0.196805E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.212335E+09 | 0.302329E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.339249E+10 | 0.191338E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.212335E+09 | 56365378.46 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.369140E+09 | 0.311680E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.423609E+09 | 0.294221E+09 | 0.129388E+09 | 0.356147E+09 | 0.370343E+09 |
February | 0.485386E+09 | 0.327561E+09 | 0.157825E+09 | 0.442615E+09 | 0.281328E+09 |
March | 0.475081E+09 | 0.300923E+09 | 0.174158E+09 | 0.411966E+09 | 0.259184E+09 |
April | 0.417363E+09 | 0.227204E+09 | 0.190160E+09 | 0.357518E+09 | 0.164741E+09 |
May | 0.362689E+09 | 0.124899E+09 | 0.237790E+09 | 0.306729E+09 | 0.100948E+09 |
June | 0.314954E+09 | 84837610.58 | 0.230117E+09 | 0.275116E+09 | 69657960.89 |
July | 0.355914E+09 | 0.113748E+09 | 0.242166E+09 | 0.326087E+09 | 67196528.88 |
August | 0.379848E+09 | 0.159649E+09 | 0.220199E+09 | 0.365676E+09 | 79295464.08 |
September | 0.393277E+09 | 0.209863E+09 | 0.183414E+09 | 0.382834E+09 | 0.117746E+09 |
October | 0.346239E+09 | 0.203639E+09 | 0.142601E+09 | 0.323300E+09 | 0.171807E+09 |
November | 0.297588E+09 | 0.186435E+09 | 0.111153E+09 | 0.262186E+09 | 0.234002E+09 |
December | 0.327021E+09 | 0.213998E+09 | 0.113023E+09 | 0.254871E+09 | 0.359134E+09 |
Annual Sum or Average | 0.457897E+10 | 0.244698E+10 | 0.213199E+10 | 0.406504E+10 | 0.227538E+10 |
Minimum of Months | 0.297588E+09 | 84837610.58 | 0.111153E+09 | 0.254871E+09 | 67196528.88 |
Maximum of Months | 0.485386E+09 | 0.327561E+09 | 0.242166E+09 | 0.442615E+09 | 0.370343E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.297130E+09 | 0.309525E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.369482E+09 | 0.234897E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.344015E+09 | 0.216177E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.299311E+09 | 0.136131E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.257658E+09 | 82942264.01 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.230580E+09 | 57662308.13 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.272712E+09 | 56206078.43 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.305774E+09 | 66155907.57 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.320894E+09 | 96948905.79 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.270823E+09 | 0.141762E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.219089E+09 | 0.194690E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.212575E+09 | 0.300165E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.340004E+10 | 0.189326E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.212575E+09 | 56206078.43 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.369482E+09 | 0.309525E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.297130E+09 | 0.309525E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.369482E+09 | 0.234897E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.344015E+09 | 0.216177E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.299311E+09 | 0.136131E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.257658E+09 | 82942264.01 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.230580E+09 | 57662308.13 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.272712E+09 | 56206078.43 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.305774E+09 | 66155907.57 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.320894E+09 | 96948905.79 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.270823E+09 | 0.141762E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.219089E+09 | 0.194690E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.212575E+09 | 0.300165E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.340004E+10 | 0.189326E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.212575E+09 | 56206078.43 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.369482E+09 | 0.309525E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.423609E+09 | 0.294221E+09 | 0.129388E+09 | 0.356510E+09 | 0.367770E+09 |
February | 0.485386E+09 | 0.327561E+09 | 0.157825E+09 | 0.443032E+09 | 0.279186E+09 |
March | 0.475081E+09 | 0.300923E+09 | 0.174158E+09 | 0.412362E+09 | 0.256964E+09 |
April | 0.417363E+09 | 0.227204E+09 | 0.190160E+09 | 0.358666E+09 | 0.161956E+09 |
May | 0.362689E+09 | 0.124899E+09 | 0.237790E+09 | 0.308583E+09 | 98780281.59 |
June | 0.314954E+09 | 84837610.58 | 0.230117E+09 | 0.276007E+09 | 68719663.38 |
July | 0.355914E+09 | 0.113748E+09 | 0.242166E+09 | 0.326359E+09 | 67010065.18 |
August | 0.379848E+09 | 0.159649E+09 | 0.220199E+09 | 0.366005E+09 | 78834667.47 |
September | 0.393277E+09 | 0.209863E+09 | 0.183414E+09 | 0.384252E+09 | 0.115452E+09 |
October | 0.346239E+09 | 0.203639E+09 | 0.142601E+09 | 0.324442E+09 | 0.168734E+09 |
November | 0.297588E+09 | 0.186435E+09 | 0.111153E+09 | 0.262699E+09 | 0.231480E+09 |
December | 0.327021E+09 | 0.213998E+09 | 0.113023E+09 | 0.255167E+09 | 0.356551E+09 |
Annual Sum or Average | 0.457897E+10 | 0.244698E+10 | 0.213199E+10 | 0.407409E+10 | 0.225144E+10 |
Minimum of Months | 0.297588E+09 | 84837610.58 | 0.111153E+09 | 0.255167E+09 | 67010065.18 |
Maximum of Months | 0.485386E+09 | 0.327561E+09 | 0.242166E+09 | 0.443032E+09 | 0.367770E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.297510E+09 | 0.307872E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.369942E+09 | 0.233340E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.344478E+09 | 0.214461E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.300117E+09 | 0.134276E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.258905E+09 | 81241035.32 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.231464E+09 | 56560766.66 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.273158E+09 | 55550933.28 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.306207E+09 | 65350304.06 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.321729E+09 | 95337918.20 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.271488E+09 | 0.139992E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.219546E+09 | 0.192924E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.212897E+09 | 0.298417E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.340744E+10 | 0.187532E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.212897E+09 | 55550933.28 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.369942E+09 | 0.307872E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.297510E+09 | 0.307872E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.369942E+09 | 0.233340E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.344478E+09 | 0.214461E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.300117E+09 | 0.134276E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.258905E+09 | 81241035.32 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.231464E+09 | 56560766.66 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.273158E+09 | 55550933.28 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.306207E+09 | 65350304.06 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.321729E+09 | 95337918.20 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.271488E+09 | 0.139992E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.219546E+09 | 0.192924E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.212897E+09 | 0.298417E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.340744E+10 | 0.187532E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.212897E+09 | 55550933.28 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.369942E+09 | 0.307872E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.423609E+09 | 0.294221E+09 | 0.129388E+09 | 0.356975E+09 | 0.365792E+09 |
February | 0.485386E+09 | 0.327561E+09 | 0.157825E+09 | 0.443594E+09 | 0.277326E+09 |
March | 0.475081E+09 | 0.300923E+09 | 0.174158E+09 | 0.412928E+09 | 0.254914E+09 |
April | 0.417363E+09 | 0.227204E+09 | 0.190160E+09 | 0.359640E+09 | 0.159747E+09 |
May | 0.362689E+09 | 0.124899E+09 | 0.237790E+09 | 0.310079E+09 | 96758929.67 |
June | 0.314954E+09 | 84837610.58 | 0.230117E+09 | 0.277070E+09 | 67410668.42 |
July | 0.355914E+09 | 0.113748E+09 | 0.242166E+09 | 0.326896E+09 | 66231832.10 |
August | 0.379848E+09 | 0.159649E+09 | 0.220199E+09 | 0.366527E+09 | 77877890.21 |
September | 0.393277E+09 | 0.209863E+09 | 0.183414E+09 | 0.385253E+09 | 0.113536E+09 |
October | 0.346239E+09 | 0.203639E+09 | 0.142601E+09 | 0.325245E+09 | 0.166624E+09 |
November | 0.297588E+09 | 0.186435E+09 | 0.111153E+09 | 0.263255E+09 | 0.229374E+09 |
December | 0.327021E+09 | 0.213998E+09 | 0.113023E+09 | 0.255565E+09 | 0.354463E+09 |
Annual Sum or Average | 0.457897E+10 | 0.244698E+10 | 0.213199E+10 | 0.408303E+10 | 0.223005E+10 |
Minimum of Months | 0.297588E+09 | 84837610.58 | 0.111153E+09 | 0.255565E+09 | 66231832.10 |
Maximum of Months | 0.485386E+09 | 0.327561E+09 | 0.242166E+09 | 0.443594E+09 | 0.365792E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.299329E+09 | 0.301971E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.371969E+09 | 0.228329E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.346085E+09 | 0.209205E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.301736E+09 | 0.130001E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.260478E+09 | 77762516.82 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.232484E+09 | 53912594.21 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.273105E+09 | 53564686.56 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.306327E+09 | 63072063.35 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.322611E+09 | 92253643.81 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.272641E+09 | 0.136353E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.221012E+09 | 0.187961E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.214460E+09 | 0.292344E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.342224E+10 | 0.182673E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.214460E+09 | 53564686.56 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.371969E+09 | 0.301971E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.299329E+09 | 0.301971E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.371969E+09 | 0.228329E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.346085E+09 | 0.209205E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.301736E+09 | 0.130001E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.260478E+09 | 77762516.82 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.232484E+09 | 53912594.21 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.273105E+09 | 53564686.56 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.306327E+09 | 63072063.35 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.322611E+09 | 92253643.81 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.272641E+09 | 0.136353E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.221012E+09 | 0.187961E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.214460E+09 | 0.292344E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.342224E+10 | 0.182673E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.214460E+09 | 53564686.56 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.371969E+09 | 0.301971E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.299329E+09 | 0.301971E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.371969E+09 | 0.228329E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.346085E+09 | 0.209205E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.301736E+09 | 0.130001E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.260478E+09 | 77762516.82 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.232484E+09 | 53912594.21 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.273105E+09 | 53564686.56 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.306327E+09 | 63072063.35 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.322611E+09 | 92253643.81 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.272641E+09 | 0.136353E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.221012E+09 | 0.187961E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.214460E+09 | 0.292344E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.342224E+10 | 0.182673E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.214460E+09 | 53564686.56 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.371969E+09 | 0.301971E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.299329E+09 | 0.301971E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.371969E+09 | 0.228329E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.346085E+09 | 0.209205E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.301736E+09 | 0.130001E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.260478E+09 | 77762516.82 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.232484E+09 | 53912594.21 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.273105E+09 | 53564686.56 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.306327E+09 | 63072063.35 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.322611E+09 | 92253643.81 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.272641E+09 | 0.136353E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.221012E+09 | 0.187961E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.214460E+09 | 0.292344E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.342224E+10 | 0.182673E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.214460E+09 | 53564686.56 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.371969E+09 | 0.301971E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.423609E+09 | 0.294221E+09 | 0.129388E+09 | 0.359153E+09 | 0.358815E+09 |
February | 0.485386E+09 | 0.327561E+09 | 0.157825E+09 | 0.446014E+09 | 0.271396E+09 |
March | 0.475081E+09 | 0.300923E+09 | 0.174158E+09 | 0.414867E+09 | 0.248678E+09 |
April | 0.417363E+09 | 0.227204E+09 | 0.190160E+09 | 0.361600E+09 | 0.154677E+09 |
May | 0.362689E+09 | 0.124899E+09 | 0.237790E+09 | 0.311984E+09 | 92628814.11 |
June | 0.314954E+09 | 84837610.58 | 0.230117E+09 | 0.278319E+09 | 64262042.08 |
July | 0.355914E+09 | 0.113748E+09 | 0.242166E+09 | 0.326869E+09 | 63871258.86 |
August | 0.379848E+09 | 0.159649E+09 | 0.220199E+09 | 0.366698E+09 | 75173217.34 |
September | 0.393277E+09 | 0.209863E+09 | 0.183414E+09 | 0.386320E+09 | 0.109874E+09 |
October | 0.346239E+09 | 0.203639E+09 | 0.142601E+09 | 0.326636E+09 | 0.162302E+09 |
November | 0.297588E+09 | 0.186435E+09 | 0.111153E+09 | 0.265015E+09 | 0.223480E+09 |
December | 0.327021E+09 | 0.213998E+09 | 0.113023E+09 | 0.257438E+09 | 0.347280E+09 |
Annual Sum or Average | 0.457897E+10 | 0.244698E+10 | 0.213199E+10 | 0.410091E+10 | 0.217244E+10 |
Minimum of Months | 0.297588E+09 | 84837610.58 | 0.111153E+09 | 0.257438E+09 | 63871258.86 |
Maximum of Months | 0.485386E+09 | 0.327561E+09 | 0.242166E+09 | 0.446014E+09 | 0.358815E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.423609E+09 | 0.294221E+09 | 0.129388E+09 | 0.359153E+09 | 0.358815E+09 |
February | 0.485386E+09 | 0.327561E+09 | 0.157825E+09 | 0.446014E+09 | 0.271396E+09 |
March | 0.475081E+09 | 0.300923E+09 | 0.174158E+09 | 0.414867E+09 | 0.248678E+09 |
April | 0.417363E+09 | 0.227204E+09 | 0.190160E+09 | 0.361600E+09 | 0.154677E+09 |
May | 0.362689E+09 | 0.124899E+09 | 0.237790E+09 | 0.311984E+09 | 92628814.11 |
June | 0.314954E+09 | 84837610.58 | 0.230117E+09 | 0.278319E+09 | 64262042.08 |
July | 0.355914E+09 | 0.113748E+09 | 0.242166E+09 | 0.326869E+09 | 63871258.86 |
August | 0.379848E+09 | 0.159649E+09 | 0.220199E+09 | 0.366698E+09 | 75173217.34 |
September | 0.393277E+09 | 0.209863E+09 | 0.183414E+09 | 0.386320E+09 | 0.109874E+09 |
October | 0.346239E+09 | 0.203639E+09 | 0.142601E+09 | 0.326636E+09 | 0.162302E+09 |
November | 0.297588E+09 | 0.186435E+09 | 0.111153E+09 | 0.265015E+09 | 0.223480E+09 |
December | 0.327021E+09 | 0.213998E+09 | 0.113023E+09 | 0.257438E+09 | 0.347280E+09 |
Annual Sum or Average | 0.457897E+10 | 0.244698E+10 | 0.213199E+10 | 0.410091E+10 | 0.217244E+10 |
Minimum of Months | 0.297588E+09 | 84837610.58 | 0.111153E+09 | 0.257438E+09 | 63871258.86 |
Maximum of Months | 0.485386E+09 | 0.327561E+09 | 0.242166E+09 | 0.446014E+09 | 0.358815E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.298448E+09 | 0.303546E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.371150E+09 | 0.229268E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.345539E+09 | 0.209822E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.301656E+09 | 0.129759E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.260954E+09 | 77051172.59 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.233102E+09 | 53206305.01 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.273606E+09 | 52951818.45 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.306571E+09 | 62455707.92 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.322685E+09 | 91655507.86 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.272426E+09 | 0.136075E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.220550E+09 | 0.188461E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.213740E+09 | 0.294006E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.342043E+10 | 0.182826E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.213740E+09 | 52951818.45 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.371150E+09 | 0.303546E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.298448E+09 | 0.303546E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.371150E+09 | 0.229268E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.345539E+09 | 0.209822E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.301656E+09 | 0.129759E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.260954E+09 | 77051172.59 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.233102E+09 | 53206305.01 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.273606E+09 | 52951818.45 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.306571E+09 | 62455707.92 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.322685E+09 | 91655507.86 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.272426E+09 | 0.136075E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.220550E+09 | 0.188461E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.213740E+09 | 0.294006E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.342043E+10 | 0.182826E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.213740E+09 | 52951818.45 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.371150E+09 | 0.303546E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.423609E+09 | 0.294221E+09 | 0.129388E+09 | 0.358131E+09 | 0.360626E+09 |
February | 0.485386E+09 | 0.327561E+09 | 0.157825E+09 | 0.445073E+09 | 0.272469E+09 |
March | 0.475081E+09 | 0.300923E+09 | 0.174158E+09 | 0.414239E+09 | 0.249372E+09 |
April | 0.417363E+09 | 0.227204E+09 | 0.190160E+09 | 0.361526E+09 | 0.154365E+09 |
May | 0.362689E+09 | 0.124899E+09 | 0.237790E+09 | 0.312566E+09 | 91773849.50 |
June | 0.314954E+09 | 84837610.58 | 0.230117E+09 | 0.279063E+09 | 63418064.12 |
July | 0.355914E+09 | 0.113748E+09 | 0.242166E+09 | 0.327472E+09 | 63140677.30 |
August | 0.379848E+09 | 0.159649E+09 | 0.220199E+09 | 0.367003E+09 | 74432954.36 |
September | 0.393277E+09 | 0.209863E+09 | 0.183414E+09 | 0.386428E+09 | 0.109147E+09 |
October | 0.346239E+09 | 0.203639E+09 | 0.142601E+09 | 0.326404E+09 | 0.161947E+09 |
November | 0.297588E+09 | 0.186435E+09 | 0.111153E+09 | 0.264488E+09 | 0.224037E+09 |
December | 0.327021E+09 | 0.213998E+09 | 0.113023E+09 | 0.256602E+09 | 0.349190E+09 |
Annual Sum or Average | 0.457897E+10 | 0.244698E+10 | 0.213199E+10 | 0.409899E+10 | 0.217392E+10 |
Minimum of Months | 0.297588E+09 | 84837610.58 | 0.111153E+09 | 0.256602E+09 | 63140677.30 |
Maximum of Months | 0.485386E+09 | 0.327561E+09 | 0.242166E+09 | 0.445073E+09 | 0.360626E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.298509E+09 | 0.303249E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.371261E+09 | 0.228882E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.345688E+09 | 0.209275E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.302008E+09 | 0.128999E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.261566E+09 | 76301063.62 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.233665E+09 | 52643254.81 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.273881E+09 | 52651652.93 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.306822E+09 | 62090613.68 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.323019E+09 | 91079551.37 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.272662E+09 | 0.135458E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.220706E+09 | 0.187890E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.213798E+09 | 0.293683E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.342359E+10 | 0.182220E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.213798E+09 | 52643254.81 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.371261E+09 | 0.303249E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.298509E+09 | 0.303249E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.371261E+09 | 0.228882E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.345688E+09 | 0.209275E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.302008E+09 | 0.128999E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.261566E+09 | 76301063.62 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.233665E+09 | 52643254.81 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.273881E+09 | 52651652.93 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.306822E+09 | 62090613.68 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.323019E+09 | 91079551.37 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.272662E+09 | 0.135458E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.220706E+09 | 0.187890E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.213798E+09 | 0.293683E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.342359E+10 | 0.182220E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.213798E+09 | 52643254.81 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.371261E+09 | 0.303249E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.423609E+09 | 0.294221E+09 | 0.129388E+09 | 0.358205E+09 | 0.360270E+09 |
February | 0.485386E+09 | 0.327561E+09 | 0.157825E+09 | 0.445209E+09 | 0.272008E+09 |
March | 0.475081E+09 | 0.300923E+09 | 0.174158E+09 | 0.414422E+09 | 0.248719E+09 |
April | 0.417363E+09 | 0.227204E+09 | 0.190160E+09 | 0.361952E+09 | 0.153461E+09 |
May | 0.362689E+09 | 0.124899E+09 | 0.237790E+09 | 0.313301E+09 | 90880969.91 |
June | 0.314954E+09 | 84837610.58 | 0.230117E+09 | 0.279738E+09 | 62747342.12 |
July | 0.355914E+09 | 0.113748E+09 | 0.242166E+09 | 0.327803E+09 | 62782674.69 |
August | 0.379848E+09 | 0.159649E+09 | 0.220199E+09 | 0.367305E+09 | 73998335.54 |
September | 0.393277E+09 | 0.209863E+09 | 0.183414E+09 | 0.386829E+09 | 0.108462E+09 |
October | 0.346239E+09 | 0.203639E+09 | 0.142601E+09 | 0.326690E+09 | 0.161211E+09 |
November | 0.297588E+09 | 0.186435E+09 | 0.111153E+09 | 0.264678E+09 | 0.223354E+09 |
December | 0.327021E+09 | 0.213998E+09 | 0.113023E+09 | 0.256673E+09 | 0.348804E+09 |
Annual Sum or Average | 0.457897E+10 | 0.244698E+10 | 0.213199E+10 | 0.410281E+10 | 0.216670E+10 |
Minimum of Months | 0.297588E+09 | 84837610.58 | 0.111153E+09 | 0.256673E+09 | 62747342.12 |
Maximum of Months | 0.485386E+09 | 0.327561E+09 | 0.242166E+09 | 0.445209E+09 | 0.360270E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.298824E+09 | 0.301473E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.371707E+09 | 0.227034E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.346215E+09 | 0.206962E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.302944E+09 | 0.126642E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.262956E+09 | 74484821.91 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.234836E+09 | 51396409.44 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.274413E+09 | 52009482.09 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.307313E+09 | 61317229.96 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.323696E+09 | 89829333.07 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.273223E+09 | 0.133787E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.221180E+09 | 0.185875E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.214073E+09 | 0.291837E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.343138E+10 | 0.180265E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.214073E+09 | 51396409.44 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.371707E+09 | 0.301473E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.298824E+09 | 0.301473E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.371707E+09 | 0.227034E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.346215E+09 | 0.206962E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.302944E+09 | 0.126642E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.262956E+09 | 74484821.91 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.234836E+09 | 51396409.44 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.274413E+09 | 52009482.09 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.307313E+09 | 61317229.96 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.323696E+09 | 89829333.07 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.273223E+09 | 0.133787E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.221180E+09 | 0.185875E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.214073E+09 | 0.291837E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.343138E+10 | 0.180265E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.214073E+09 | 51396409.44 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.371707E+09 | 0.301473E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.423609E+09 | 0.294221E+09 | 0.129388E+09 | 0.358591E+09 | 0.358148E+09 |
February | 0.485386E+09 | 0.327561E+09 | 0.157825E+09 | 0.445752E+09 | 0.269801E+09 |
March | 0.475081E+09 | 0.300923E+09 | 0.174158E+09 | 0.415066E+09 | 0.245956E+09 |
April | 0.417363E+09 | 0.227204E+09 | 0.190160E+09 | 0.363086E+09 | 0.150654E+09 |
May | 0.362689E+09 | 0.124899E+09 | 0.237790E+09 | 0.314969E+09 | 88721387.01 |
June | 0.314954E+09 | 84837610.58 | 0.230117E+09 | 0.281141E+09 | 61264823.08 |
July | 0.355914E+09 | 0.113748E+09 | 0.242166E+09 | 0.328442E+09 | 62020300.19 |
August | 0.379848E+09 | 0.159649E+09 | 0.220199E+09 | 0.367895E+09 | 73080091.87 |
September | 0.393277E+09 | 0.209863E+09 | 0.183414E+09 | 0.387643E+09 | 0.106975E+09 |
October | 0.346239E+09 | 0.203639E+09 | 0.142601E+09 | 0.327370E+09 | 0.159221E+09 |
November | 0.297588E+09 | 0.186435E+09 | 0.111153E+09 | 0.265254E+09 | 0.220949E+09 |
December | 0.327021E+09 | 0.213998E+09 | 0.113023E+09 | 0.257012E+09 | 0.346599E+09 |
Annual Sum or Average | 0.457897E+10 | 0.244698E+10 | 0.213199E+10 | 0.411222E+10 | 0.214339E+10 |
Minimum of Months | 0.297588E+09 | 84837610.58 | 0.111153E+09 | 0.257012E+09 | 61264823.08 |
Maximum of Months | 0.485386E+09 | 0.327561E+09 | 0.242166E+09 | 0.445752E+09 | 0.358148E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.300589E+09 | 0.292930E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.373688E+09 | 0.218782E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.348392E+09 | 0.196734E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.305788E+09 | 0.117521E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.266660E+09 | 68582633.52 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.237697E+09 | 47435861.14 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.275802E+09 | 49520481.49 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.308579E+09 | 58533722.44 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.325365E+09 | 85706460.49 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.274899E+09 | 0.127779E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.222853E+09 | 0.177662E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.215546E+09 | 0.282947E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.345586E+10 | 0.172413E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.215546E+09 | 47435861.14 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.373688E+09 | 0.292930E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353783E+09 | 0.245723E+09 | 0.108061E+09 | 0.300589E+09 | 0.292930E+09 |
February | 0.405377E+09 | 0.273567E+09 | 0.131810E+09 | 0.373688E+09 | 0.218782E+09 |
March | 0.396771E+09 | 0.251321E+09 | 0.145451E+09 | 0.348392E+09 | 0.196734E+09 |
April | 0.348567E+09 | 0.189753E+09 | 0.158815E+09 | 0.305788E+09 | 0.117521E+09 |
May | 0.302905E+09 | 0.104311E+09 | 0.198594E+09 | 0.266660E+09 | 68582633.52 |
June | 0.263039E+09 | 70853389.05 | 0.192185E+09 | 0.237697E+09 | 47435861.14 |
July | 0.297247E+09 | 94998309.53 | 0.202249E+09 | 0.275802E+09 | 49520481.49 |
August | 0.317236E+09 | 0.133333E+09 | 0.183903E+09 | 0.308579E+09 | 58533722.44 |
September | 0.328451E+09 | 0.175270E+09 | 0.153181E+09 | 0.325365E+09 | 85706460.49 |
October | 0.289167E+09 | 0.170072E+09 | 0.119095E+09 | 0.274899E+09 | 0.127779E+09 |
November | 0.248535E+09 | 0.155704E+09 | 92831080.47 | 0.222853E+09 | 0.177662E+09 |
December | 0.273117E+09 | 0.178723E+09 | 94393043.76 | 0.215546E+09 | 0.282947E+09 |
Annual Sum or Average | 0.382420E+10 | 0.204363E+10 | 0.178057E+10 | 0.345586E+10 | 0.172413E+10 |
Minimum of Months | 0.248535E+09 | 70853389.05 | 92831080.47 | 0.215546E+09 | 47435861.14 |
Maximum of Months | 0.405377E+09 | 0.273567E+09 | 0.202249E+09 | 0.373688E+09 | 0.292930E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.423609E+09 | 0.294221E+09 | 0.129388E+09 | 0.360754E+09 | 0.347904E+09 |
February | 0.485386E+09 | 0.327561E+09 | 0.157825E+09 | 0.448169E+09 | 0.259932E+09 |
March | 0.475081E+09 | 0.300923E+09 | 0.174158E+09 | 0.417728E+09 | 0.233744E+09 |
April | 0.417363E+09 | 0.227204E+09 | 0.190160E+09 | 0.366539E+09 | 0.139806E+09 |
May | 0.362689E+09 | 0.124899E+09 | 0.237790E+09 | 0.319418E+09 | 81711166.51 |
June | 0.314954E+09 | 84837610.58 | 0.230117E+09 | 0.284566E+09 | 56558722.09 |
July | 0.355914E+09 | 0.113748E+09 | 0.242166E+09 | 0.330104E+09 | 59063888.77 |
August | 0.379848E+09 | 0.159649E+09 | 0.220199E+09 | 0.369412E+09 | 69778406.86 |
September | 0.393277E+09 | 0.209863E+09 | 0.183414E+09 | 0.389646E+09 | 0.102082E+09 |
October | 0.346239E+09 | 0.203639E+09 | 0.142601E+09 | 0.329406E+09 | 0.152079E+09 |
November | 0.297588E+09 | 0.186435E+09 | 0.111153E+09 | 0.267290E+09 | 0.211172E+09 |
December | 0.327021E+09 | 0.213998E+09 | 0.113023E+09 | 0.258823E+09 | 0.335960E+09 |
Annual Sum or Average | 0.457897E+10 | 0.244698E+10 | 0.213199E+10 | 0.414185E+10 | 0.204979E+10 |
Minimum of Months | 0.297588E+09 | 84837610.58 | 0.111153E+09 | 0.258823E+09 | 56558722.09 |
Maximum of Months | 0.485386E+09 | 0.327561E+09 | 0.242166E+09 | 0.448169E+09 | 0.347904E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 716.14 | 735.35 | 846.40 | 587.88 | 258.53 | 0.00 | 0.00 |
February | 985.24 | 613.86 | 1073.75 | 724.62 | 349.13 | 0.00 | 0.00 |
March | 828.76 | 505.76 | 949.25 | 601.27 | 347.98 | 0.00 | 0.00 |
April | 746.04 | 324.75 | 861.72 | 469.10 | 392.62 | 0.00 | 0.00 |
May | 622.36 | 187.39 | 724.68 | 249.56 | 475.12 | 0.00 | 0.00 |
June | 575.17 | 132.10 | 650.28 | 175.16 | 475.12 | 0.00 | 0.00 |
July | 656.41 | 123.55 | 711.14 | 227.28 | 483.87 | 0.00 | 0.00 |
August | 734.12 | 147.47 | 758.96 | 318.99 | 439.97 | 0.00 | 0.00 |
September | 796.76 | 228.34 | 811.99 | 433.30 | 378.69 | 0.00 | 0.00 |
October | 650.87 | 330.74 | 691.81 | 406.89 | 284.93 | 0.00 | 0.00 |
November | 545.18 | 474.57 | 614.42 | 384.93 | 229.50 | 0.00 | 0.00 |
December | 513.09 | 711.14 | 653.41 | 427.58 | 225.83 | 0.00 | 0.00 |
Annual Sum or Average | 695.49 | 375.25 | 777.05 | 415.25 | 361.80 | 0.00 | 0.00 |
Minimum of Months | 513.09 | 123.55 | 614.42 | 175.16 | 225.83 | 0.00 | 0.00 |
Maximum of Months | 985.24 | 735.35 | 1073.75 | 724.62 | 483.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 355.18 | 377.75 | 423.20 | 293.94 | 129.26 | 0.00 | 0.00 |
February | 488.96 | 317.31 | 536.87 | 362.31 | 174.57 | 0.00 | 0.00 |
March | 411.18 | 263.83 | 474.62 | 300.63 | 173.99 | 0.00 | 0.00 |
April | 368.40 | 173.89 | 430.86 | 234.55 | 196.31 | 0.00 | 0.00 |
May | 306.34 | 100.05 | 362.34 | 124.78 | 237.56 | 0.00 | 0.00 |
June | 284.80 | 69.01 | 325.14 | 87.58 | 237.56 | 0.00 | 0.00 |
July | 327.26 | 62.84 | 355.57 | 113.64 | 241.93 | 0.00 | 0.00 |
August | 365.99 | 75.31 | 379.48 | 159.50 | 219.99 | 0.00 | 0.00 |
September | 395.12 | 120.15 | 406.00 | 216.65 | 189.35 | 0.00 | 0.00 |
October | 322.24 | 175.33 | 345.91 | 203.44 | 142.46 | 0.00 | 0.00 |
November | 269.95 | 247.15 | 307.21 | 192.46 | 114.75 | 0.00 | 0.00 |
December | 254.11 | 366.23 | 326.71 | 213.79 | 112.91 | 0.00 | 0.00 |
Annual Sum or Average | 344.79 | 195.21 | 388.52 | 207.63 | 180.90 | 0.00 | 0.00 |
Minimum of Months | 254.11 | 62.84 | 307.21 | 87.58 | 112.91 | 0.00 | 0.00 |
Maximum of Months | 488.96 | 377.75 | 536.87 | 362.31 | 241.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 354.62 | 371.01 | 422.33 | 293.33 | 129.00 | 0.00 | 0.00 |
February | 488.13 | 311.97 | 535.77 | 361.56 | 174.21 | 0.00 | 0.00 |
March | 410.45 | 259.58 | 473.65 | 300.02 | 173.63 | 0.00 | 0.00 |
April | 368.14 | 170.41 | 429.98 | 234.07 | 195.91 | 0.00 | 0.00 |
May | 305.75 | 100.99 | 361.60 | 124.52 | 237.07 | 0.00 | 0.00 |
June | 283.48 | 71.98 | 324.47 | 87.40 | 237.07 | 0.00 | 0.00 |
July | 325.21 | 67.18 | 354.84 | 113.41 | 241.44 | 0.00 | 0.00 |
August | 364.65 | 79.30 | 378.70 | 159.17 | 219.54 | 0.00 | 0.00 |
September | 394.38 | 121.72 | 405.16 | 216.21 | 188.96 | 0.00 | 0.00 |
October | 322.22 | 171.93 | 345.20 | 203.02 | 142.17 | 0.00 | 0.00 |
November | 269.87 | 242.13 | 306.58 | 192.07 | 114.51 | 0.00 | 0.00 |
December | 253.71 | 359.84 | 326.04 | 213.35 | 112.68 | 0.00 | 0.00 |
Annual Sum or Average | 344.05 | 193.50 | 387.73 | 207.20 | 180.53 | 0.00 | 0.00 |
Minimum of Months | 253.71 | 67.18 | 306.58 | 87.40 | 112.68 | 0.00 | 0.00 |
Maximum of Months | 488.13 | 371.01 | 535.77 | 361.56 | 241.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 354.98 | 368.44 | 422.33 | 293.33 | 129.00 | 0.00 | 0.00 |
February | 488.59 | 309.60 | 535.77 | 361.56 | 174.21 | 0.00 | 0.00 |
March | 410.84 | 257.36 | 473.65 | 300.02 | 173.63 | 0.00 | 0.00 |
April | 369.32 | 167.52 | 429.98 | 234.07 | 195.91 | 0.00 | 0.00 |
May | 307.61 | 98.81 | 361.60 | 124.52 | 237.07 | 0.00 | 0.00 |
June | 284.40 | 71.00 | 324.47 | 87.40 | 237.07 | 0.00 | 0.00 |
July | 325.49 | 66.99 | 354.84 | 113.41 | 241.44 | 0.00 | 0.00 |
August | 364.98 | 78.83 | 378.70 | 159.17 | 219.54 | 0.00 | 0.00 |
September | 395.85 | 119.35 | 405.16 | 216.21 | 188.96 | 0.00 | 0.00 |
October | 323.36 | 168.85 | 345.20 | 203.02 | 142.17 | 0.00 | 0.00 |
November | 270.40 | 239.53 | 306.58 | 192.07 | 114.51 | 0.00 | 0.00 |
December | 254.00 | 357.26 | 326.04 | 213.35 | 112.68 | 0.00 | 0.00 |
Annual Sum or Average | 344.82 | 191.46 | 387.73 | 207.20 | 180.53 | 0.00 | 0.00 |
Minimum of Months | 254.00 | 66.99 | 306.58 | 87.40 | 112.68 | 0.00 | 0.00 |
Maximum of Months | 488.59 | 368.44 | 535.77 | 361.56 | 241.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 355.43 | 366.46 | 422.33 | 293.33 | 129.00 | 0.00 | 0.00 |
February | 489.20 | 307.54 | 535.77 | 361.56 | 174.21 | 0.00 | 0.00 |
March | 411.40 | 255.31 | 473.65 | 300.02 | 173.63 | 0.00 | 0.00 |
April | 370.32 | 165.24 | 429.98 | 234.07 | 195.91 | 0.00 | 0.00 |
May | 309.10 | 96.79 | 361.60 | 124.52 | 237.07 | 0.00 | 0.00 |
June | 285.49 | 69.65 | 324.47 | 87.40 | 237.07 | 0.00 | 0.00 |
July | 326.02 | 66.21 | 354.84 | 113.41 | 241.44 | 0.00 | 0.00 |
August | 365.49 | 77.87 | 378.70 | 159.17 | 219.54 | 0.00 | 0.00 |
September | 396.88 | 117.37 | 405.16 | 216.21 | 188.96 | 0.00 | 0.00 |
October | 324.16 | 166.74 | 345.20 | 203.02 | 142.17 | 0.00 | 0.00 |
November | 270.97 | 237.35 | 306.58 | 192.07 | 114.51 | 0.00 | 0.00 |
December | 254.39 | 355.17 | 326.04 | 213.35 | 112.68 | 0.00 | 0.00 |
Annual Sum or Average | 345.57 | 189.65 | 387.73 | 207.20 | 180.53 | 0.00 | 0.00 |
Minimum of Months | 254.39 | 66.21 | 306.58 | 87.40 | 112.68 | 0.00 | 0.00 |
Maximum of Months | 489.20 | 366.46 | 535.77 | 361.56 | 241.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 715.21 | 718.90 | 844.67 | 586.67 | 258.00 | 0.00 | 0.00 |
February | 983.76 | 601.90 | 1071.54 | 723.13 | 348.42 | 0.00 | 0.00 |
March | 826.64 | 498.12 | 947.30 | 600.03 | 347.27 | 0.00 | 0.00 |
April | 744.65 | 319.97 | 859.95 | 468.14 | 391.81 | 0.00 | 0.00 |
May | 621.97 | 185.30 | 723.19 | 249.04 | 474.15 | 0.00 | 0.00 |
June | 573.52 | 132.78 | 648.94 | 174.80 | 474.14 | 0.00 | 0.00 |
July | 651.94 | 127.69 | 709.68 | 226.81 | 482.87 | 0.00 | 0.00 |
August | 731.30 | 150.33 | 757.41 | 318.34 | 439.07 | 0.00 | 0.00 |
September | 795.94 | 227.15 | 810.32 | 432.41 | 377.91 | 0.00 | 0.00 |
October | 651.07 | 324.83 | 690.39 | 406.05 | 284.34 | 0.00 | 0.00 |
November | 545.55 | 462.50 | 613.16 | 384.14 | 229.02 | 0.00 | 0.00 |
December | 512.51 | 695.91 | 652.07 | 426.71 | 225.37 | 0.00 | 0.00 |
Annual Sum or Average | 694.15 | 369.48 | 775.45 | 414.40 | 361.06 | 0.00 | 0.00 |
Minimum of Months | 512.51 | 127.69 | 613.16 | 174.80 | 225.37 | 0.00 | 0.00 |
Maximum of Months | 983.76 | 718.90 | 1071.54 | 723.13 | 482.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 356.57 | 361.30 | 422.33 | 293.33 | 129.00 | 0.00 | 0.00 |
February | 490.81 | 302.17 | 535.77 | 361.56 | 174.21 | 0.00 | 0.00 |
March | 412.68 | 249.78 | 473.65 | 300.02 | 173.63 | 0.00 | 0.00 |
April | 372.24 | 159.68 | 429.98 | 234.07 | 195.91 | 0.00 | 0.00 |
May | 311.56 | 91.80 | 361.60 | 124.52 | 237.07 | 0.00 | 0.00 |
June | 287.53 | 65.52 | 324.47 | 87.40 | 237.07 | 0.00 | 0.00 |
July | 326.57 | 63.11 | 354.84 | 113.41 | 241.44 | 0.00 | 0.00 |
August | 365.94 | 74.43 | 378.70 | 159.17 | 219.54 | 0.00 | 0.00 |
September | 398.07 | 112.83 | 405.16 | 216.21 | 188.96 | 0.00 | 0.00 |
October | 325.29 | 162.07 | 345.20 | 203.02 | 142.17 | 0.00 | 0.00 |
November | 272.22 | 231.85 | 306.58 | 192.07 | 114.51 | 0.00 | 0.00 |
December | 255.41 | 349.91 | 326.04 | 213.35 | 112.68 | 0.00 | 0.00 |
Annual Sum or Average | 346.90 | 184.88 | 387.73 | 207.20 | 180.53 | 0.00 | 0.00 |
Minimum of Months | 255.41 | 63.11 | 306.58 | 87.40 | 112.68 | 0.00 | 0.00 |
Maximum of Months | 490.81 | 361.30 | 535.77 | 361.56 | 241.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 356.64 | 360.95 | 422.33 | 293.33 | 129.00 | 0.00 | 0.00 |
February | 490.96 | 301.66 | 535.77 | 361.56 | 174.21 | 0.00 | 0.00 |
March | 412.86 | 249.13 | 473.65 | 300.02 | 173.63 | 0.00 | 0.00 |
April | 372.67 | 158.74 | 429.98 | 234.07 | 195.91 | 0.00 | 0.00 |
May | 312.29 | 90.91 | 361.60 | 124.52 | 237.07 | 0.00 | 0.00 |
June | 288.22 | 64.83 | 324.47 | 87.40 | 237.07 | 0.00 | 0.00 |
July | 326.90 | 62.76 | 354.84 | 113.41 | 241.44 | 0.00 | 0.00 |
August | 366.24 | 73.99 | 378.70 | 159.17 | 219.54 | 0.00 | 0.00 |
September | 398.48 | 112.12 | 405.16 | 216.21 | 188.96 | 0.00 | 0.00 |
October | 325.57 | 161.34 | 345.20 | 203.02 | 142.17 | 0.00 | 0.00 |
November | 272.41 | 231.15 | 306.58 | 192.07 | 114.51 | 0.00 | 0.00 |
December | 255.48 | 349.53 | 326.04 | 213.35 | 112.68 | 0.00 | 0.00 |
Annual Sum or Average | 347.22 | 184.27 | 387.73 | 207.20 | 180.53 | 0.00 | 0.00 |
Minimum of Months | 255.48 | 62.76 | 306.58 | 87.40 | 112.68 | 0.00 | 0.00 |
Maximum of Months | 490.96 | 360.95 | 535.77 | 361.56 | 241.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 357.02 | 358.83 | 422.33 | 293.33 | 129.00 | 0.00 | 0.00 |
February | 491.55 | 299.22 | 535.77 | 361.56 | 174.21 | 0.00 | 0.00 |
March | 413.49 | 246.37 | 473.65 | 300.02 | 173.63 | 0.00 | 0.00 |
April | 373.83 | 155.84 | 429.98 | 234.07 | 195.91 | 0.00 | 0.00 |
May | 313.95 | 88.74 | 361.60 | 124.52 | 237.07 | 0.00 | 0.00 |
June | 289.67 | 63.29 | 324.47 | 87.40 | 237.07 | 0.00 | 0.00 |
July | 327.53 | 61.99 | 354.84 | 113.41 | 241.44 | 0.00 | 0.00 |
August | 366.83 | 73.07 | 378.70 | 159.17 | 219.54 | 0.00 | 0.00 |
September | 399.32 | 110.58 | 405.16 | 216.21 | 188.96 | 0.00 | 0.00 |
October | 326.25 | 159.35 | 345.20 | 203.02 | 142.17 | 0.00 | 0.00 |
November | 273.00 | 228.67 | 306.58 | 192.07 | 114.51 | 0.00 | 0.00 |
December | 255.81 | 347.32 | 326.04 | 213.35 | 112.68 | 0.00 | 0.00 |
Annual Sum or Average | 348.01 | 182.29 | 387.73 | 207.20 | 180.53 | 0.00 | 0.00 |
Minimum of Months | 255.81 | 61.99 | 306.58 | 87.40 | 112.68 | 0.00 | 0.00 |
Maximum of Months | 491.55 | 358.83 | 535.77 | 361.56 | 241.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 359.14 | 348.63 | 422.33 | 293.33 | 129.00 | 0.00 | 0.00 |
February | 494.19 | 288.32 | 535.77 | 361.56 | 174.21 | 0.00 | 0.00 |
March | 416.11 | 234.17 | 473.65 | 300.02 | 173.63 | 0.00 | 0.00 |
April | 377.36 | 144.62 | 429.98 | 234.07 | 195.91 | 0.00 | 0.00 |
May | 318.38 | 81.72 | 361.60 | 124.52 | 237.07 | 0.00 | 0.00 |
June | 293.19 | 58.42 | 324.47 | 87.40 | 237.07 | 0.00 | 0.00 |
July | 329.19 | 59.03 | 354.84 | 113.41 | 241.44 | 0.00 | 0.00 |
August | 368.34 | 69.76 | 378.70 | 159.17 | 219.54 | 0.00 | 0.00 |
September | 401.38 | 105.52 | 405.16 | 216.21 | 188.96 | 0.00 | 0.00 |
October | 328.26 | 152.19 | 345.20 | 203.02 | 142.17 | 0.00 | 0.00 |
November | 275.08 | 218.56 | 306.58 | 192.07 | 114.51 | 0.00 | 0.00 |
December | 257.58 | 336.71 | 326.04 | 213.35 | 112.68 | 0.00 | 0.00 |
Annual Sum or Average | 350.51 | 174.34 | 387.73 | 207.20 | 180.53 | 0.00 | 0.00 |
Minimum of Months | 257.58 | 58.42 | 306.58 | 87.40 | 112.68 | 0.00 | 0.00 |
Maximum of Months | 494.19 | 348.63 | 535.77 | 361.56 | 241.44 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.191812E+10 | 0.196957E+10 | 0.226701E+10 | 0.157457E+10 | 0.692441E+09 | 0.00 | 0.00 |
February | 0.238350E+10 | 0.148505E+10 | 0.259761E+10 | 0.175299E+10 | 0.844623E+09 | 0.00 | 0.00 |
March | 0.221974E+10 | 0.135462E+10 | 0.254247E+10 | 0.161044E+10 | 0.932032E+09 | 0.00 | 0.00 |
April | 0.193373E+10 | 0.841745E+09 | 0.223358E+10 | 0.121591E+10 | 0.101767E+10 | 0.00 | 0.00 |
May | 0.166693E+10 | 0.501916E+09 | 0.194098E+10 | 0.668415E+09 | 0.127257E+10 | 0.00 | 0.00 |
June | 0.149084E+10 | 0.342415E+09 | 0.168552E+10 | 0.454021E+09 | 0.123150E+10 | 0.00 | 0.00 |
July | 0.175812E+10 | 0.330923E+09 | 0.190473E+10 | 0.608739E+09 | 0.129599E+10 | 0.00 | 0.00 |
August | 0.196626E+10 | 0.394984E+09 | 0.203281E+10 | 0.854383E+09 | 0.117843E+10 | 0.00 | 0.00 |
September | 0.206521E+10 | 0.591846E+09 | 0.210468E+10 | 0.112311E+10 | 0.981568E+09 | 0.00 | 0.00 |
October | 0.174330E+10 | 0.885866E+09 | 0.185295E+10 | 0.108980E+10 | 0.763150E+09 | 0.00 | 0.00 |
November | 0.141310E+10 | 0.123010E+10 | 0.159259E+10 | 0.997736E+09 | 0.594852E+09 | 0.00 | 0.00 |
December | 0.137427E+10 | 0.190471E+10 | 0.175010E+10 | 0.114524E+10 | 0.604861E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.219331E+11 | 0.118337E+11 | 0.245050E+11 | 0.130954E+11 | 0.114097E+11 | 0.00 | 0.00 |
Minimum of Months | 0.137427E+10 | 0.330923E+09 | 0.159259E+10 | 0.454021E+09 | 0.594852E+09 | 0.00 | 0.00 |
Maximum of Months | 0.238350E+10 | 0.196957E+10 | 0.259761E+10 | 0.175299E+10 | 0.129599E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.951301E+09 | 0.101176E+10 | 0.113350E+10 | 0.787283E+09 | 0.346220E+09 | 0.00 | 0.00 |
February | 0.118290E+10 | 0.767631E+09 | 0.129881E+10 | 0.876495E+09 | 0.422312E+09 | 0.00 | 0.00 |
March | 0.110131E+10 | 0.706637E+09 | 0.127123E+10 | 0.805218E+09 | 0.466016E+09 | 0.00 | 0.00 |
April | 0.954887E+09 | 0.450714E+09 | 0.111679E+10 | 0.607957E+09 | 0.508834E+09 | 0.00 | 0.00 |
May | 0.820488E+09 | 0.267972E+09 | 0.970492E+09 | 0.334207E+09 | 0.636284E+09 | 0.00 | 0.00 |
June | 0.738208E+09 | 0.178875E+09 | 0.842762E+09 | 0.227011E+09 | 0.615751E+09 | 0.00 | 0.00 |
July | 0.876545E+09 | 0.168300E+09 | 0.952364E+09 | 0.304370E+09 | 0.647995E+09 | 0.00 | 0.00 |
August | 0.980275E+09 | 0.201722E+09 | 0.101641E+10 | 0.427191E+09 | 0.589214E+09 | 0.00 | 0.00 |
September | 0.102414E+10 | 0.311418E+09 | 0.105234E+10 | 0.561556E+09 | 0.490784E+09 | 0.00 | 0.00 |
October | 0.863082E+09 | 0.469595E+09 | 0.926476E+09 | 0.544901E+09 | 0.381575E+09 | 0.00 | 0.00 |
November | 0.699705E+09 | 0.640621E+09 | 0.796294E+09 | 0.498868E+09 | 0.297426E+09 | 0.00 | 0.00 |
December | 0.680602E+09 | 0.980906E+09 | 0.875051E+09 | 0.572621E+09 | 0.302430E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108734E+11 | 0.615615E+10 | 0.122525E+11 | 0.654768E+10 | 0.570484E+10 | 0.00 | 0.00 |
Minimum of Months | 0.680602E+09 | 0.168300E+09 | 0.796294E+09 | 0.227011E+09 | 0.297426E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118290E+10 | 0.101176E+10 | 0.129881E+10 | 0.876495E+09 | 0.647995E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.949811E+09 | 0.993702E+09 | 0.113118E+10 | 0.785666E+09 | 0.345510E+09 | 0.00 | 0.00 |
February | 0.118089E+10 | 0.754714E+09 | 0.129614E+10 | 0.874695E+09 | 0.421444E+09 | 0.00 | 0.00 |
March | 0.109935E+10 | 0.695260E+09 | 0.126862E+10 | 0.803564E+09 | 0.465059E+09 | 0.00 | 0.00 |
April | 0.954223E+09 | 0.441691E+09 | 0.111450E+10 | 0.606709E+09 | 0.507789E+09 | 0.00 | 0.00 |
May | 0.818924E+09 | 0.270486E+09 | 0.968499E+09 | 0.333521E+09 | 0.634978E+09 | 0.00 | 0.00 |
June | 0.734775E+09 | 0.186563E+09 | 0.841031E+09 | 0.226544E+09 | 0.614487E+09 | 0.00 | 0.00 |
July | 0.871049E+09 | 0.179927E+09 | 0.950409E+09 | 0.303745E+09 | 0.646664E+09 | 0.00 | 0.00 |
August | 0.976668E+09 | 0.212389E+09 | 0.101432E+10 | 0.426314E+09 | 0.588005E+09 | 0.00 | 0.00 |
September | 0.102224E+10 | 0.315511E+09 | 0.105018E+10 | 0.560403E+09 | 0.489776E+09 | 0.00 | 0.00 |
October | 0.863033E+09 | 0.460499E+09 | 0.924573E+09 | 0.543782E+09 | 0.380791E+09 | 0.00 | 0.00 |
November | 0.699516E+09 | 0.627611E+09 | 0.794659E+09 | 0.497843E+09 | 0.296815E+09 | 0.00 | 0.00 |
December | 0.679537E+09 | 0.963788E+09 | 0.873254E+09 | 0.571445E+09 | 0.301809E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108500E+11 | 0.610214E+10 | 0.122274E+11 | 0.653423E+10 | 0.569313E+10 | 0.00 | 0.00 |
Minimum of Months | 0.679537E+09 | 0.179927E+09 | 0.794659E+09 | 0.226544E+09 | 0.296815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118089E+10 | 0.993702E+09 | 0.129614E+10 | 0.874695E+09 | 0.646664E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.950769E+09 | 0.986818E+09 | 0.113118E+10 | 0.785666E+09 | 0.345510E+09 | 0.00 | 0.00 |
February | 0.118200E+10 | 0.748980E+09 | 0.129614E+10 | 0.874695E+09 | 0.421444E+09 | 0.00 | 0.00 |
March | 0.110039E+10 | 0.689316E+09 | 0.126862E+10 | 0.803564E+09 | 0.465059E+09 | 0.00 | 0.00 |
April | 0.957288E+09 | 0.434217E+09 | 0.111450E+10 | 0.606709E+09 | 0.507789E+09 | 0.00 | 0.00 |
May | 0.823899E+09 | 0.264665E+09 | 0.968499E+09 | 0.333521E+09 | 0.634978E+09 | 0.00 | 0.00 |
June | 0.737166E+09 | 0.184044E+09 | 0.841031E+09 | 0.226544E+09 | 0.614487E+09 | 0.00 | 0.00 |
July | 0.871783E+09 | 0.179422E+09 | 0.950409E+09 | 0.303745E+09 | 0.646664E+09 | 0.00 | 0.00 |
August | 0.977553E+09 | 0.211146E+09 | 0.101432E+10 | 0.426314E+09 | 0.588005E+09 | 0.00 | 0.00 |
September | 0.102604E+10 | 0.309350E+09 | 0.105018E+10 | 0.560403E+09 | 0.489776E+09 | 0.00 | 0.00 |
October | 0.866087E+09 | 0.452258E+09 | 0.924573E+09 | 0.543782E+09 | 0.380791E+09 | 0.00 | 0.00 |
November | 0.700877E+09 | 0.620859E+09 | 0.794659E+09 | 0.497843E+09 | 0.296815E+09 | 0.00 | 0.00 |
December | 0.680313E+09 | 0.956878E+09 | 0.873254E+09 | 0.571445E+09 | 0.301809E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108742E+11 | 0.603795E+10 | 0.122274E+11 | 0.653423E+10 | 0.569313E+10 | 0.00 | 0.00 |
Minimum of Months | 0.680313E+09 | 0.179422E+09 | 0.794659E+09 | 0.226544E+09 | 0.296815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118200E+10 | 0.986818E+09 | 0.129614E+10 | 0.874695E+09 | 0.646664E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.951994E+09 | 0.981535E+09 | 0.113118E+10 | 0.785666E+09 | 0.345510E+09 | 0.00 | 0.00 |
February | 0.118348E+10 | 0.744004E+09 | 0.129614E+10 | 0.874695E+09 | 0.421444E+09 | 0.00 | 0.00 |
March | 0.110188E+10 | 0.683835E+09 | 0.126862E+10 | 0.803564E+09 | 0.465059E+09 | 0.00 | 0.00 |
April | 0.959873E+09 | 0.428300E+09 | 0.111450E+10 | 0.606709E+09 | 0.507789E+09 | 0.00 | 0.00 |
May | 0.827889E+09 | 0.259241E+09 | 0.968499E+09 | 0.333521E+09 | 0.634978E+09 | 0.00 | 0.00 |
June | 0.739999E+09 | 0.180532E+09 | 0.841031E+09 | 0.226544E+09 | 0.614487E+09 | 0.00 | 0.00 |
July | 0.873213E+09 | 0.177334E+09 | 0.950409E+09 | 0.303745E+09 | 0.646664E+09 | 0.00 | 0.00 |
August | 0.978942E+09 | 0.208578E+09 | 0.101432E+10 | 0.426314E+09 | 0.588005E+09 | 0.00 | 0.00 |
September | 0.102871E+10 | 0.304212E+09 | 0.105018E+10 | 0.560403E+09 | 0.489776E+09 | 0.00 | 0.00 |
October | 0.868220E+09 | 0.446607E+09 | 0.924573E+09 | 0.543782E+09 | 0.380791E+09 | 0.00 | 0.00 |
November | 0.702347E+09 | 0.615222E+09 | 0.794659E+09 | 0.497843E+09 | 0.296815E+09 | 0.00 | 0.00 |
December | 0.681356E+09 | 0.951293E+09 | 0.873254E+09 | 0.571445E+09 | 0.301809E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108979E+11 | 0.598069E+10 | 0.122274E+11 | 0.653423E+10 | 0.569313E+10 | 0.00 | 0.00 |
Minimum of Months | 0.681356E+09 | 0.177334E+09 | 0.794659E+09 | 0.226544E+09 | 0.296815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118348E+10 | 0.981535E+09 | 0.129614E+10 | 0.874695E+09 | 0.646664E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.191562E+10 | 0.192551E+10 | 0.226235E+10 | 0.157133E+10 | 0.691019E+09 | 0.00 | 0.00 |
February | 0.237990E+10 | 0.145611E+10 | 0.259228E+10 | 0.174939E+10 | 0.842889E+09 | 0.00 | 0.00 |
March | 0.221407E+10 | 0.133417E+10 | 0.253725E+10 | 0.160713E+10 | 0.930118E+09 | 0.00 | 0.00 |
April | 0.193014E+10 | 0.829358E+09 | 0.222900E+10 | 0.121342E+10 | 0.101558E+10 | 0.00 | 0.00 |
May | 0.166588E+10 | 0.496308E+09 | 0.193700E+10 | 0.667042E+09 | 0.126996E+10 | 0.00 | 0.00 |
June | 0.148657E+10 | 0.344174E+09 | 0.168206E+10 | 0.453089E+09 | 0.122897E+10 | 0.00 | 0.00 |
July | 0.174616E+10 | 0.342001E+09 | 0.190082E+10 | 0.607489E+09 | 0.129333E+10 | 0.00 | 0.00 |
August | 0.195871E+10 | 0.402635E+09 | 0.202864E+10 | 0.852629E+09 | 0.117601E+10 | 0.00 | 0.00 |
September | 0.206308E+10 | 0.588762E+09 | 0.210036E+10 | 0.112081E+10 | 0.979552E+09 | 0.00 | 0.00 |
October | 0.174384E+10 | 0.870017E+09 | 0.184915E+10 | 0.108756E+10 | 0.761583E+09 | 0.00 | 0.00 |
November | 0.141408E+10 | 0.119880E+10 | 0.158932E+10 | 0.995687E+09 | 0.593630E+09 | 0.00 | 0.00 |
December | 0.137271E+10 | 0.186393E+10 | 0.174651E+10 | 0.114289E+10 | 0.603619E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.218908E+11 | 0.116518E+11 | 0.244547E+11 | 0.130685E+11 | 0.113863E+11 | 0.00 | 0.00 |
Minimum of Months | 0.137271E+10 | 0.342001E+09 | 0.158932E+10 | 0.453089E+09 | 0.593630E+09 | 0.00 | 0.00 |
Maximum of Months | 0.237990E+10 | 0.192551E+10 | 0.259228E+10 | 0.174939E+10 | 0.129333E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.955027E+09 | 0.967717E+09 | 0.113118E+10 | 0.785666E+09 | 0.345510E+09 | 0.00 | 0.00 |
February | 0.118737E+10 | 0.731005E+09 | 0.129614E+10 | 0.874695E+09 | 0.421444E+09 | 0.00 | 0.00 |
March | 0.110532E+10 | 0.669014E+09 | 0.126862E+10 | 0.803564E+09 | 0.465059E+09 | 0.00 | 0.00 |
April | 0.964839E+09 | 0.413883E+09 | 0.111450E+10 | 0.606709E+09 | 0.507789E+09 | 0.00 | 0.00 |
May | 0.834474E+09 | 0.245876E+09 | 0.968499E+09 | 0.333521E+09 | 0.634978E+09 | 0.00 | 0.00 |
June | 0.745268E+09 | 0.169831E+09 | 0.841031E+09 | 0.226544E+09 | 0.614487E+09 | 0.00 | 0.00 |
July | 0.874685E+09 | 0.169044E+09 | 0.950409E+09 | 0.303745E+09 | 0.646664E+09 | 0.00 | 0.00 |
August | 0.980145E+09 | 0.199344E+09 | 0.101432E+10 | 0.426314E+09 | 0.588005E+09 | 0.00 | 0.00 |
September | 0.103180E+10 | 0.292458E+09 | 0.105018E+10 | 0.560403E+09 | 0.489776E+09 | 0.00 | 0.00 |
October | 0.871256E+09 | 0.434097E+09 | 0.924573E+09 | 0.543782E+09 | 0.380791E+09 | 0.00 | 0.00 |
November | 0.705587E+09 | 0.600959E+09 | 0.794659E+09 | 0.497843E+09 | 0.296815E+09 | 0.00 | 0.00 |
December | 0.684080E+09 | 0.937201E+09 | 0.873254E+09 | 0.571445E+09 | 0.301809E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109398E+11 | 0.583043E+10 | 0.122274E+11 | 0.653423E+10 | 0.569313E+10 | 0.00 | 0.00 |
Minimum of Months | 0.684080E+09 | 0.169044E+09 | 0.794659E+09 | 0.226544E+09 | 0.296815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118737E+10 | 0.967717E+09 | 0.129614E+10 | 0.874695E+09 | 0.646664E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.955221E+09 | 0.966767E+09 | 0.113118E+10 | 0.785666E+09 | 0.345510E+09 | 0.00 | 0.00 |
February | 0.118773E+10 | 0.729771E+09 | 0.129614E+10 | 0.874695E+09 | 0.421444E+09 | 0.00 | 0.00 |
March | 0.110580E+10 | 0.667267E+09 | 0.126862E+10 | 0.803564E+09 | 0.465059E+09 | 0.00 | 0.00 |
April | 0.965968E+09 | 0.411459E+09 | 0.111450E+10 | 0.606709E+09 | 0.507789E+09 | 0.00 | 0.00 |
May | 0.836433E+09 | 0.243483E+09 | 0.968499E+09 | 0.333521E+09 | 0.634978E+09 | 0.00 | 0.00 |
June | 0.747069E+09 | 0.168034E+09 | 0.841031E+09 | 0.226544E+09 | 0.614487E+09 | 0.00 | 0.00 |
July | 0.875566E+09 | 0.168086E+09 | 0.950409E+09 | 0.303745E+09 | 0.646664E+09 | 0.00 | 0.00 |
August | 0.980949E+09 | 0.198179E+09 | 0.101432E+10 | 0.426314E+09 | 0.588005E+09 | 0.00 | 0.00 |
September | 0.103287E+10 | 0.290621E+09 | 0.105018E+10 | 0.560403E+09 | 0.489776E+09 | 0.00 | 0.00 |
October | 0.872015E+09 | 0.432126E+09 | 0.924573E+09 | 0.543782E+09 | 0.380791E+09 | 0.00 | 0.00 |
November | 0.706089E+09 | 0.599134E+09 | 0.794659E+09 | 0.497843E+09 | 0.296815E+09 | 0.00 | 0.00 |
December | 0.684268E+09 | 0.936168E+09 | 0.873254E+09 | 0.571445E+09 | 0.301809E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109500E+11 | 0.581110E+10 | 0.122274E+11 | 0.653423E+10 | 0.569313E+10 | 0.00 | 0.00 |
Minimum of Months | 0.684268E+09 | 0.168034E+09 | 0.794659E+09 | 0.226544E+09 | 0.296815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118773E+10 | 0.966767E+09 | 0.129614E+10 | 0.874695E+09 | 0.646664E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.956236E+09 | 0.961092E+09 | 0.113118E+10 | 0.785666E+09 | 0.345510E+09 | 0.00 | 0.00 |
February | 0.118916E+10 | 0.723869E+09 | 0.129614E+10 | 0.874695E+09 | 0.421444E+09 | 0.00 | 0.00 |
March | 0.110750E+10 | 0.659879E+09 | 0.126862E+10 | 0.803564E+09 | 0.465059E+09 | 0.00 | 0.00 |
April | 0.968975E+09 | 0.403938E+09 | 0.111450E+10 | 0.606709E+09 | 0.507789E+09 | 0.00 | 0.00 |
May | 0.840881E+09 | 0.237691E+09 | 0.968499E+09 | 0.333521E+09 | 0.634978E+09 | 0.00 | 0.00 |
June | 0.750813E+09 | 0.164058E+09 | 0.841031E+09 | 0.226544E+09 | 0.614487E+09 | 0.00 | 0.00 |
July | 0.877268E+09 | 0.166039E+09 | 0.950409E+09 | 0.303745E+09 | 0.646664E+09 | 0.00 | 0.00 |
August | 0.982520E+09 | 0.195715E+09 | 0.101432E+10 | 0.426314E+09 | 0.588005E+09 | 0.00 | 0.00 |
September | 0.103504E+10 | 0.286634E+09 | 0.105018E+10 | 0.560403E+09 | 0.489776E+09 | 0.00 | 0.00 |
October | 0.873816E+09 | 0.426795E+09 | 0.924573E+09 | 0.543782E+09 | 0.380791E+09 | 0.00 | 0.00 |
November | 0.707613E+09 | 0.592700E+09 | 0.794659E+09 | 0.497843E+09 | 0.296815E+09 | 0.00 | 0.00 |
December | 0.685155E+09 | 0.930271E+09 | 0.873254E+09 | 0.571445E+09 | 0.301809E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109750E+11 | 0.574868E+10 | 0.122274E+11 | 0.653423E+10 | 0.569313E+10 | 0.00 | 0.00 |
Minimum of Months | 0.685155E+09 | 0.164058E+09 | 0.794659E+09 | 0.226544E+09 | 0.296815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118916E+10 | 0.961092E+09 | 0.129614E+10 | 0.874695E+09 | 0.646664E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.961930E+09 | 0.933762E+09 | 0.113118E+10 | 0.785666E+09 | 0.345510E+09 | 0.00 | 0.00 |
February | 0.119554E+10 | 0.697495E+09 | 0.129614E+10 | 0.874695E+09 | 0.421444E+09 | 0.00 | 0.00 |
March | 0.111451E+10 | 0.627210E+09 | 0.126862E+10 | 0.803564E+09 | 0.465059E+09 | 0.00 | 0.00 |
April | 0.978114E+09 | 0.374848E+09 | 0.111450E+10 | 0.606709E+09 | 0.507789E+09 | 0.00 | 0.00 |
May | 0.852738E+09 | 0.218876E+09 | 0.968499E+09 | 0.333521E+09 | 0.634978E+09 | 0.00 | 0.00 |
June | 0.759960E+09 | 0.151430E+09 | 0.841031E+09 | 0.226544E+09 | 0.614487E+09 | 0.00 | 0.00 |
July | 0.881708E+09 | 0.158105E+09 | 0.950409E+09 | 0.303745E+09 | 0.646664E+09 | 0.00 | 0.00 |
August | 0.986570E+09 | 0.186846E+09 | 0.101432E+10 | 0.426314E+09 | 0.588005E+09 | 0.00 | 0.00 |
September | 0.104038E+10 | 0.273495E+09 | 0.105018E+10 | 0.560403E+09 | 0.489776E+09 | 0.00 | 0.00 |
October | 0.879204E+09 | 0.407637E+09 | 0.924573E+09 | 0.543782E+09 | 0.380791E+09 | 0.00 | 0.00 |
November | 0.712995E+09 | 0.566495E+09 | 0.794659E+09 | 0.497843E+09 | 0.296815E+09 | 0.00 | 0.00 |
December | 0.689914E+09 | 0.901852E+09 | 0.873254E+09 | 0.571445E+09 | 0.301809E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110536E+11 | 0.549805E+10 | 0.122274E+11 | 0.653423E+10 | 0.569313E+10 | 0.00 | 0.00 |
Minimum of Months | 0.689914E+09 | 0.151430E+09 | 0.794659E+09 | 0.226544E+09 | 0.296815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119554E+10 | 0.933762E+09 | 0.129614E+10 | 0.874695E+09 | 0.646664E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.3 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.6 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.5 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.48 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.18 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.96 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.19 | 13.59 | 3.45 | 8.98 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.33 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.48 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.07 | -2.0 | 3.82 | -8.5 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.3 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.98 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -0.9 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.85 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.46 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.93 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.24 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.70 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.34 | 23.33 | 8.07 | 19.92 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.35 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.80 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.60 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.43 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -0.9 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.34 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.3 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.0 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.61 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.6 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.4 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.33 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.46 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.93 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.90 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.70 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.75 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.35 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.70 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.4 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.75 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.24 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.06 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.90 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.75 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.35 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.22 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.16 | 3.43 | 9.18 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 06-DEC-02:00 | 0.00 | -0.0 | 3.60 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.75 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.357416E+09 | -280361745.5 | 0.00 | 0.00 | 744.00 | 0.00 | -77054235.8 | 58.99 | 0.00 | 0.00 |
February | 0.329794E+09 | -260428294.7 | 0.00 | 0.00 | 672.00 | 0.00 | -69365569.0 | 58.99 | 0.00 | 0.00 |
March | 0.367994E+09 | -291682892.0 | 0.00 | 0.00 | 744.00 | 0.00 | -76310870.7 | 58.99 | 0.00 | 0.00 |
April | 0.343140E+09 | -270602236.3 | 0.00 | 0.00 | 720.00 | 0.00 | -72537519.2 | 59.00 | 0.00 | 0.00 |
May | 0.336898E+09 | -265732716.6 | 0.00 | 0.00 | 744.00 | 0.00 | -71164832.4 | 58.99 | 0.00 | 0.00 |
June | 0.311166E+09 | -244142797.7 | 0.00 | 0.00 | 720.00 | 0.00 | -67023631.0 | 58.99 | 0.00 | 0.00 |
July | 0.302973E+09 | -234518539.4 | 0.00 | 0.00 | 744.00 | 0.00 | -68454453.2 | 58.98 | 0.00 | 0.00 |
August | 0.300700E+09 | -232134866.2 | 0.00 | 0.00 | 744.00 | 0.00 | -68564991.6 | 58.99 | 0.00 | 0.00 |
September | 0.291813E+09 | -223650121.7 | 0.00 | 0.00 | 720.00 | 0.00 | -68163364.2 | 58.98 | 0.00 | 0.00 |
October | 0.311518E+09 | -237656161.9 | 0.00 | 0.00 | 744.00 | 0.00 | -73862302.7 | 58.99 | 0.00 | 0.00 |
November | 0.316178E+09 | -242956337.5 | 0.00 | 0.00 | 720.00 | 0.00 | -73221463.8 | 58.99 | 0.00 | 0.00 |
December | 0.344595E+09 | -267625124.8 | 0.00 | 0.00 | 744.00 | 0.00 | -76970091.5 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391419E+10 | -.305149E+10 | 8760.00 | -862693325.3 | 58.99 | |||||
Minimum of Months | 0.291813E+09 | -291682892.0 | 0.00 | 0.00 | 672.00 | 0.00 | -77054235.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.367994E+09 | -223650121.7 | 0.00 | 0.00 | 744.00 | 0.00 | -67023631.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.356521E+09 | -280357494.1 | 0.00 | 0.00 | 744.00 | 0.00 | -76163909.7 | 59.00 | 0.00 | 0.00 |
February | 0.328816E+09 | -260423331.3 | 0.00 | 0.00 | 672.00 | 0.00 | -68392797.1 | 58.99 | 0.00 | 0.00 |
March | 0.366740E+09 | -291679500.0 | 0.00 | 0.00 | 744.00 | 0.00 | -75060095.2 | 58.99 | 0.00 | 0.00 |
April | 0.341246E+09 | -270606861.9 | 0.00 | 0.00 | 720.00 | 0.00 | -70639547.4 | 58.99 | 0.00 | 0.00 |
May | 0.335408E+09 | -265717050.9 | 0.00 | 0.00 | 744.00 | 0.00 | -69691088.5 | 59.00 | 0.00 | 0.00 |
June | 0.310519E+09 | -244141528.7 | 0.00 | 0.00 | 720.00 | 0.00 | -66377309.9 | 58.99 | 0.00 | 0.00 |
July | 0.302771E+09 | -234487054.2 | 0.00 | 0.00 | 744.00 | 0.00 | -68283703.5 | 59.01 | 0.00 | 0.00 |
August | 0.300412E+09 | -232126623.7 | 0.00 | 0.00 | 744.00 | 0.00 | -68285158.7 | 59.00 | 0.00 | 0.00 |
September | 0.290592E+09 | -223610937.1 | 0.00 | 0.00 | 720.00 | 0.00 | -66980959.1 | 59.01 | 0.00 | 0.00 |
October | 0.309752E+09 | -237653868.9 | 0.00 | 0.00 | 744.00 | 0.00 | -72097701.8 | 58.99 | 0.00 | 0.00 |
November | 0.314923E+09 | -242958886.4 | 0.00 | 0.00 | 720.00 | 0.00 | -71963725.7 | 58.99 | 0.00 | 0.00 |
December | 0.343618E+09 | -267664422.0 | 0.00 | 0.00 | 744.00 | 0.00 | -75953078.6 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.390132E+10 | -.305143E+10 | 8760.00 | -849889075.2 | 59.00 | |||||
Minimum of Months | 0.290592E+09 | -291679500.0 | 0.00 | 0.00 | 672.00 | 0.00 | -76163909.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.366740E+09 | -223610937.1 | 0.00 | 0.00 | 744.00 | 0.00 | -66377309.9 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.323855E+09 | -246532612.5 | 0.00 | 0.00 | 744.00 | 0.00 | -77322038.4 | 59.00 | 0.00 | 0.00 |
February | 0.298456E+09 | -229183109.5 | 0.00 | 0.00 | 672.00 | 0.00 | -69272874.0 | 58.99 | 0.00 | 0.00 |
March | 0.336425E+09 | -260507972.2 | 0.00 | 0.00 | 744.00 | 0.00 | -75917266.9 | 59.00 | 0.00 | 0.00 |
April | 0.309275E+09 | -237816973.6 | 0.00 | 0.00 | 720.00 | 0.00 | -71457926.6 | 58.99 | 0.00 | 0.00 |
May | 0.305295E+09 | -235695127.9 | 0.00 | 0.00 | 744.00 | 0.00 | -69600073.2 | 58.99 | 0.00 | 0.00 |
June | 0.283390E+09 | -217575747.3 | 0.00 | 0.00 | 720.00 | 0.00 | -65814162.5 | 59.01 | 0.00 | 0.00 |
July | 0.272117E+09 | -204839927.9 | 0.00 | 0.00 | 744.00 | 0.00 | -67277280.1 | 58.99 | 0.00 | 0.00 |
August | 0.275009E+09 | -207484163.0 | 0.00 | 0.00 | 744.00 | 0.00 | -67524682.3 | 59.00 | 0.00 | 0.00 |
September | 0.263203E+09 | -196394681.6 | 0.00 | 0.00 | 720.00 | 0.00 | -66808106.5 | 58.99 | 0.00 | 0.00 |
October | 0.281931E+09 | -209011124.8 | 0.00 | 0.00 | 744.00 | 0.00 | -72919697.1 | 58.99 | 0.00 | 0.00 |
November | 0.287448E+09 | -214507356.6 | 0.00 | 0.00 | 720.00 | 0.00 | -72940787.3 | 58.99 | 0.00 | 0.00 |
December | 0.310715E+09 | -233611396.7 | 0.00 | 0.00 | 744.00 | 0.00 | -77103914.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.354712E+10 | -.269316E+10 | 8760.00 | -853958809.0 | 59.00 | |||||
Minimum of Months | 0.263203E+09 | -260507972.2 | 0.00 | 0.00 | 672.00 | 0.00 | -77322038.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.336425E+09 | -196394681.6 | 0.00 | 0.00 | 744.00 | 0.00 | -65814162.5 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.324134E+09 | -246536351.7 | 0.00 | 0.00 | 744.00 | 0.00 | -77597154.3 | 59.00 | 0.00 | 0.00 |
February | 0.298694E+09 | -229186866.6 | 0.00 | 0.00 | 672.00 | 0.00 | -69507318.4 | 58.99 | 0.00 | 0.00 |
March | 0.336672E+09 | -260516441.8 | 0.00 | 0.00 | 744.00 | 0.00 | -76155978.9 | 58.99 | 0.00 | 0.00 |
April | 0.309770E+09 | -237818798.2 | 0.00 | 0.00 | 720.00 | 0.00 | -71950957.6 | 58.99 | 0.00 | 0.00 |
May | 0.305891E+09 | -235702540.5 | 0.00 | 0.00 | 744.00 | 0.00 | -70188131.8 | 58.99 | 0.00 | 0.00 |
June | 0.283637E+09 | -217612490.2 | 0.00 | 0.00 | 720.00 | 0.00 | -66024926.1 | 58.98 | 0.00 | 0.00 |
July | 0.272215E+09 | -204849963.6 | 0.00 | 0.00 | 744.00 | 0.00 | -67365324.4 | 58.99 | 0.00 | 0.00 |
August | 0.275125E+09 | -207504511.3 | 0.00 | 0.00 | 744.00 | 0.00 | -67620323.0 | 58.98 | 0.00 | 0.00 |
September | 0.263764E+09 | -196382448.0 | 0.00 | 0.00 | 720.00 | 0.00 | -67381261.0 | 59.00 | 0.00 | 0.00 |
October | 0.282468E+09 | -209012370.2 | 0.00 | 0.00 | 744.00 | 0.00 | -73456106.6 | 58.99 | 0.00 | 0.00 |
November | 0.287758E+09 | -214511555.4 | 0.00 | 0.00 | 720.00 | 0.00 | -73245999.3 | 58.99 | 0.00 | 0.00 |
December | 0.310991E+09 | -233610653.6 | 0.00 | 0.00 | 744.00 | 0.00 | -77380075.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.355112E+10 | -.269324E+10 | 8760.00 | -857873556.4 | 58.99 | |||||
Minimum of Months | 0.263764E+09 | -260516441.8 | 0.00 | 0.00 | 672.00 | 0.00 | -77597154.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.336672E+09 | -196382448.0 | 0.00 | 0.00 | 744.00 | 0.00 | -66024926.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.311731E+09 | -233038236.4 | 0.00 | 0.00 | 744.00 | 0.00 | -78692577.0 | 58.98 | 0.00 | 0.00 |
February | 0.287282E+09 | -216725813.0 | 0.00 | 0.00 | 672.00 | 0.00 | -70555965.0 | 58.99 | 0.00 | 0.00 |
March | 0.323739E+09 | -246503153.4 | 0.00 | 0.00 | 744.00 | 0.00 | -77235864.5 | 58.99 | 0.00 | 0.00 |
April | 0.298141E+09 | -225058765.3 | 0.00 | 0.00 | 720.00 | 0.00 | -73082222.5 | 58.98 | 0.00 | 0.00 |
May | 0.294339E+09 | -222895397.6 | 0.00 | 0.00 | 744.00 | 0.00 | -71443967.8 | 59.00 | 0.00 | 0.00 |
June | 0.272853E+09 | -205892539.4 | 0.00 | 0.00 | 720.00 | 0.00 | -66960687.8 | 58.99 | 0.00 | 0.00 |
July | 0.261650E+09 | -193730696.7 | 0.00 | 0.00 | 744.00 | 0.00 | -67919618.1 | 58.99 | 0.00 | 0.00 |
August | 0.264576E+09 | -196338575.5 | 0.00 | 0.00 | 744.00 | 0.00 | -68237912.5 | 58.99 | 0.00 | 0.00 |
September | 0.254183E+09 | -185844732.7 | 0.00 | 0.00 | 720.00 | 0.00 | -68338753.0 | 58.99 | 0.00 | 0.00 |
October | 0.271952E+09 | -197547000.9 | 0.00 | 0.00 | 744.00 | 0.00 | -74405196.7 | 58.99 | 0.00 | 0.00 |
November | 0.276849E+09 | -202609071.9 | 0.00 | 0.00 | 720.00 | 0.00 | -74239846.8 | 58.98 | 0.00 | 0.00 |
December | 0.299439E+09 | -220937223.5 | 0.00 | 0.00 | 744.00 | 0.00 | -78501530.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.341674E+10 | -.254712E+10 | 8760.00 | -869614141.7 | 58.99 | |||||
Minimum of Months | 0.254183E+09 | -246503153.4 | 0.00 | 0.00 | 672.00 | 0.00 | -78692577.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.323739E+09 | -185844732.7 | 0.00 | 0.00 | 744.00 | 0.00 | -66960687.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.311664E+09 | -233035817.9 | 0.00 | 0.00 | 744.00 | 0.00 | -78628054.0 | 58.99 | 0.00 | 0.00 |
February | 0.287241E+09 | -216731157.5 | 0.00 | 0.00 | 672.00 | 0.00 | -70510034.3 | 58.99 | 0.00 | 0.00 |
March | 0.323728E+09 | -246507571.3 | 0.00 | 0.00 | 744.00 | 0.00 | -77220724.7 | 58.99 | 0.00 | 0.00 |
April | 0.298222E+09 | -225056344.0 | 0.00 | 0.00 | 720.00 | 0.00 | -73166012.7 | 58.98 | 0.00 | 0.00 |
May | 0.294501E+09 | -222893134.0 | 0.00 | 0.00 | 744.00 | 0.00 | -71607477.5 | 59.00 | 0.00 | 0.00 |
June | 0.272996E+09 | -205897144.3 | 0.00 | 0.00 | 720.00 | 0.00 | -67098599.4 | 58.99 | 0.00 | 0.00 |
July | 0.261761E+09 | -193729989.0 | 0.00 | 0.00 | 744.00 | 0.00 | -68030548.4 | 58.99 | 0.00 | 0.00 |
August | 0.264677E+09 | -196337167.0 | 0.00 | 0.00 | 744.00 | 0.00 | -68339379.2 | 58.98 | 0.00 | 0.00 |
September | 0.254308E+09 | -185846799.9 | 0.00 | 0.00 | 720.00 | 0.00 | -68461630.1 | 58.99 | 0.00 | 0.00 |
October | 0.272036E+09 | -197548062.5 | 0.00 | 0.00 | 744.00 | 0.00 | -74488269.0 | 58.99 | 0.00 | 0.00 |
November | 0.276885E+09 | -202591610.5 | 0.00 | 0.00 | 720.00 | 0.00 | -74293419.4 | 59.00 | 0.00 | 0.00 |
December | 0.299371E+09 | -220930773.8 | 0.00 | 0.00 | 744.00 | 0.00 | -78440574.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.341739E+10 | -.254711E+10 | 8760.00 | -870284722.8 | 58.99 | |||||
Minimum of Months | 0.254308E+09 | -246507571.3 | 0.00 | 0.00 | 672.00 | 0.00 | -78628054.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.323728E+09 | -185846799.9 | 0.00 | 0.00 | 744.00 | 0.00 | -67098599.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.311697E+09 | -233036721.5 | 0.00 | 0.00 | 744.00 | 0.00 | -78660745.0 | 58.98 | 0.00 | 0.00 |
February | 0.287293E+09 | -216727214.1 | 0.00 | 0.00 | 672.00 | 0.00 | -70565499.5 | 58.99 | 0.00 | 0.00 |
March | 0.323802E+09 | -246501150.6 | 0.00 | 0.00 | 744.00 | 0.00 | -77300583.0 | 58.99 | 0.00 | 0.00 |
April | 0.298350E+09 | -225054342.8 | 0.00 | 0.00 | 720.00 | 0.00 | -73295787.9 | 58.99 | 0.00 | 0.00 |
May | 0.294657E+09 | -222907280.1 | 0.00 | 0.00 | 744.00 | 0.00 | -71750094.5 | 58.99 | 0.00 | 0.00 |
June | 0.273144E+09 | -205888852.9 | 0.00 | 0.00 | 720.00 | 0.00 | -67254670.0 | 59.00 | 0.00 | 0.00 |
July | 0.261822E+09 | -193728377.1 | 0.00 | 0.00 | 744.00 | 0.00 | -68093614.9 | 58.99 | 0.00 | 0.00 |
August | 0.264752E+09 | -196336555.7 | 0.00 | 0.00 | 744.00 | 0.00 | -68415736.0 | 58.99 | 0.00 | 0.00 |
September | 0.254422E+09 | -185842475.5 | 0.00 | 0.00 | 720.00 | 0.00 | -68579220.3 | 58.99 | 0.00 | 0.00 |
October | 0.272130E+09 | -197548573.2 | 0.00 | 0.00 | 744.00 | 0.00 | -74581124.2 | 58.99 | 0.00 | 0.00 |
November | 0.276955E+09 | -202595122.8 | 0.00 | 0.00 | 720.00 | 0.00 | -74359641.1 | 59.00 | 0.00 | 0.00 |
December | 0.299412E+09 | -220923886.4 | 0.00 | 0.00 | 744.00 | 0.00 | -78487717.6 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.341843E+10 | -.254709E+10 | 8760.00 | -871344434.0 | 58.99 | |||||
Minimum of Months | 0.254422E+09 | -246501150.6 | 0.00 | 0.00 | 672.00 | 0.00 | -78660745.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.323802E+09 | -185842475.5 | 0.00 | 0.00 | 744.00 | 0.00 | -67254670.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | ||||||||||
Minimum of Months | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.418506E+11 | 64994.54 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.289305E+11 | 64994.54 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.244967E+11 | 64994.54 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.965096E+10 | 64994.54 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.644753E+09 | 64994.54 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.313142E+09 | 7113.21 | 22-SEP-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.693753E+10 | 64994.54 | 06-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184196E+11 | 64994.54 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.390343E+11 | 64994.54 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170278E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.418506E+11 | 64994.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.150968E+11 | 32497.30 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.969379E+10 | 32497.30 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.782436E+10 | 32497.30 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.222970E+10 | 32497.30 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37887848.56 | 5914.92 | 01-MAY-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142980E+10 | 23502.65 | 30-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.553783E+10 | 32497.30 | 07-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139284E+11 | 32497.30 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.557786E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.150968E+11 | 32497.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.162728E+11 | 35342.33 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107301E+11 | 35342.33 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.878581E+10 | 35342.33 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.269432E+10 | 35342.33 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 77286314.82 | 7936.57 | 01-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 420295.54 | 348.63 | 29-SEP-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186619E+10 | 26592.79 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.634605E+10 | 35342.33 | 12-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149903E+11 | 35342.33 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.617633E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162728E+11 | 35342.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171979E+11 | 35254.06 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115962E+11 | 35254.06 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.978250E+10 | 35254.06 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.347948E+10 | 35254.06 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.191768E+09 | 21906.00 | 01-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 57280574.37 | 3477.84 | 29-SEP-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.263785E+10 | 35254.06 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.733112E+10 | 35254.06 | 05-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159044E+11 | 35254.06 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.681785E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171979E+11 | 35254.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.176210E+11 | 35131.41 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119608E+11 | 35131.41 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101643E+11 | 35131.41 | 01-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.377737E+10 | 35131.41 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.260570E+09 | 26810.85 | 01-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126813E+09 | 4271.76 | 23-SEP-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.291107E+10 | 35131.41 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.768607E+10 | 35131.41 | 05-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163143E+11 | 35131.41 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.708223E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.176210E+11 | 35131.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.338377E+11 | 63622.25 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230333E+11 | 63622.25 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198689E+11 | 63622.25 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.785445E+10 | 63622.25 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.753660E+09 | 63622.25 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.592693E+09 | 9331.67 | 30-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.647883E+10 | 63622.25 | 06-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153207E+11 | 63622.25 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.314613E+11 | 63622.25 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139201E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.338377E+11 | 63622.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.175681E+11 | 33332.63 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119914E+11 | 33332.63 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103631E+11 | 33332.63 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.414328E+10 | 33332.63 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.418067E+09 | 33332.63 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4556.12 | 7.59 | 03-JUN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.326324E+09 | 5609.89 | 23-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.339303E+10 | 33332.63 | 06-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.799450E+10 | 33332.63 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163463E+11 | 33332.63 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.725441E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.175681E+11 | 33332.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.176380E+11 | 33314.67 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120732E+11 | 33314.67 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104667E+11 | 33314.67 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.425133E+10 | 33314.67 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.463119E+09 | 33314.67 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 395877.57 | 579.95 | 03-JUN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.357164E+09 | 6858.58 | 23-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347606E+10 | 33314.67 | 06-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.808727E+10 | 33314.67 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164188E+11 | 33314.67 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.732319E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.176380E+11 | 33314.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.180421E+11 | 33539.07 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124468E+11 | 33539.07 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108973E+11 | 33539.07 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.459131E+10 | 33539.07 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.578805E+09 | 33539.07 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2596756.33 | 1577.37 | 03-JUN-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.427654E+09 | 10139.75 | 23-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.370490E+10 | 33539.07 | 06-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.841301E+10 | 33539.07 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168156E+11 | 33539.07 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.759202E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.180421E+11 | 33539.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.216150E+11 | 36404.55 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152578E+11 | 36404.55 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134033E+11 | 36404.55 | 01-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.598884E+10 | 36404.55 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.983345E+09 | 36404.55 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36828993.02 | 3291.21 | 03-JUN-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1934164.46 | 995.13 | 19-AUG-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.628675E+09 | 21218.39 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.447496E+10 | 36404.55 | 04-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.998198E+10 | 36404.55 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200531E+11 | 36404.55 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.924257E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.216150E+11 | 36404.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.164849E+09 | 0.138434E+09 | 8497.67 | 23-APR-16:10 | 7217.43 | 0.00 |
May | 0.00 | 0.00 | 0.324451E+10 | 0.270927E+10 | 38521.71 | 26-MAY-08:62 | 24879.36 | 0.00 |
June | 0.00 | 0.00 | 0.923502E+10 | 0.641849E+10 | 41479.51 | 30-JUN-08:61 | 22705.28 | 0.00 |
July | 0.00 | 0.00 | 0.154474E+11 | 0.101036E+11 | 41203.96 | 23-JUL-07:02 | 18808.84 | 0.00 |
August | 0.00 | 0.00 | 0.107934E+11 | 0.716671E+10 | 40279.98 | 30-AUG-08:61 | 19964.97 | 0.00 |
September | 0.00 | 0.00 | 0.154971E+10 | 0.118959E+10 | 38942.19 | 01-SEP-08:62 | 20312.19 | 0.00 |
October | 0.00 | 0.00 | 89737857.15 | 79847527.18 | 3548.31 | 19-OCT-15:00 | 3219.54 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.405246E+11 | 0.278059E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.154474E+11 | 0.101036E+11 | 41479.51 | 24879.36 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.147707E+09 | 0.131061E+09 | 18054.73 | 23-APR-18:41 | 15755.82 | 0.00 |
May | 0.00 | 0.00 | 0.244000E+10 | 0.213234E+10 | 18766.06 | 26-MAY-08:62 | 12735.19 | 0.00 |
June | 0.00 | 0.00 | 0.608989E+10 | 0.444157E+10 | 20121.44 | 30-JUN-08:61 | 12121.20 | 0.00 |
July | 0.00 | 0.00 | 0.955686E+10 | 0.655253E+10 | 19960.92 | 23-JUL-07:02 | 9915.34 | 0.00 |
August | 0.00 | 0.00 | 0.675361E+10 | 0.466978E+10 | 19848.52 | 31-AUG-20:03 | 10328.73 | 0.00 |
September | 0.00 | 0.00 | 0.106331E+10 | 0.853317E+09 | 19076.37 | 17-SEP-17:02 | 10944.26 | 0.00 |
October | 0.00 | 0.00 | 84193764.82 | 79223693.50 | 17204.57 | 21-OCT-20:54 | 16948.37 | 0.00 |
November | 0.00 | 0.00 | 14653.83 | 12684.73 | 24.42 | 01-NOV-22:10 | 21.14 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.261356E+11 | 0.188598E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.955686E+10 | 0.655253E+10 | 20121.44 | 16948.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 53250921.37 | 49165933.21 | 5035.94 | 23-APR-16:00 | 4731.85 | 0.00 |
May | 0.00 | 0.00 | 0.178097E+10 | 0.161751E+10 | 18944.80 | 26-MAY-07:01 | 13233.82 | 0.00 |
June | 0.00 | 0.00 | 0.449211E+10 | 0.346114E+10 | 20525.74 | 30-JUN-07:01 | 12328.09 | 0.00 |
July | 0.00 | 0.00 | 0.687179E+10 | 0.503562E+10 | 20449.60 | 23-JUL-08:61 | 10679.43 | 0.00 |
August | 0.00 | 0.00 | 0.484306E+10 | 0.354591E+10 | 19642.19 | 30-AUG-07:01 | 9839.58 | 0.00 |
September | 0.00 | 0.00 | 0.677582E+09 | 0.572942E+09 | 19120.41 | 01-SEP-07:01 | 9865.90 | 0.00 |
October | 0.00 | 0.00 | 46243164.38 | 44971430.05 | 15764.69 | 23-OCT-07:01 | 12629.10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.187650E+11 | 0.143273E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.687179E+10 | 0.503562E+10 | 20525.74 | 13233.82 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 42692883.63 | 36100146.96 | 4312.08 | 23-APR-16:00 | 3730.33 | 0.00 |
May | 0.00 | 0.00 | 0.167861E+10 | 0.141404E+10 | 21247.61 | 26-MAY-07:01 | 14239.07 | 0.00 |
June | 0.00 | 0.00 | 0.439147E+10 | 0.316902E+10 | 23043.68 | 30-JUN-07:01 | 13154.38 | 0.00 |
July | 0.00 | 0.00 | 0.688534E+10 | 0.469335E+10 | 22951.64 | 23-JUL-08:61 | 11604.70 | 0.00 |
August | 0.00 | 0.00 | 0.501036E+10 | 0.339875E+10 | 22018.75 | 30-AUG-07:01 | 10818.12 | 0.00 |
September | 0.00 | 0.00 | 0.790302E+09 | 0.623382E+09 | 21451.27 | 01-SEP-07:01 | 10807.69 | 0.00 |
October | 0.00 | 0.00 | 53735608.76 | 48676307.70 | 2071.79 | 19-OCT-15:00 | 1902.56 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.188525E+11 | 0.133833E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.688534E+10 | 0.469335E+10 | 23043.68 | 14239.07 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 36556026.60 | 30858039.70 | 3932.03 | 23-APR-16:00 | 3389.45 | 0.00 |
May | 0.00 | 0.00 | 0.154827E+10 | 0.130022E+10 | 21184.96 | 26-MAY-07:01 | 14150.36 | 0.00 |
June | 0.00 | 0.00 | 0.416733E+10 | 0.299201E+10 | 22971.26 | 30-JUN-07:01 | 13012.24 | 0.00 |
July | 0.00 | 0.00 | 0.663917E+10 | 0.451415E+10 | 22887.24 | 23-JUL-08:61 | 11535.18 | 0.00 |
August | 0.00 | 0.00 | 0.477988E+10 | 0.323793E+10 | 21956.96 | 30-AUG-07:01 | 10748.52 | 0.00 |
September | 0.00 | 0.00 | 0.700670E+09 | 0.553268E+09 | 21391.26 | 01-SEP-07:01 | 10735.79 | 0.00 |
October | 0.00 | 0.00 | 37347147.93 | 33770308.35 | 1716.92 | 19-OCT-15:00 | 1574.20 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.179092E+11 | 0.126622E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.663917E+10 | 0.451415E+10 | 22971.26 | 14150.36 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 50675353.91 | 41826207.67 | 5890.57 | 23-APR-16:00 | 4945.66 | 0.00 |
May | 0.00 | 0.00 | 0.236855E+10 | 0.195079E+10 | 37509.76 | 26-MAY-08:62 | 24386.24 | 0.00 |
June | 0.00 | 0.00 | 0.671044E+10 | 0.467760E+10 | 40164.65 | 30-JUN-08:61 | 22827.71 | 0.00 |
July | 0.00 | 0.00 | 0.108979E+11 | 0.724673E+10 | 40343.20 | 23-JUL-09:01 | 22593.80 | 0.00 |
August | 0.00 | 0.00 | 0.775390E+10 | 0.513358E+10 | 39264.05 | 30-AUG-08:61 | 19477.05 | 0.00 |
September | 0.00 | 0.00 | 0.987336E+09 | 0.766415E+09 | 38020.59 | 01-SEP-08:62 | 19649.55 | 0.00 |
October | 0.00 | 0.00 | 29779194.20 | 26655398.71 | 2252.72 | 19-OCT-15:00 | 2023.48 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.287986E+11 | 0.198436E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108979E+11 | 0.724673E+10 | 40343.20 | 24386.24 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 23570018.10 | 19451411.88 | 2930.25 | 23-APR-16:00 | 2456.29 | 0.00 |
May | 0.00 | 0.00 | 0.116394E+10 | 0.958694E+09 | 20236.54 | 26-MAY-08:62 | 13157.93 | 0.00 |
June | 0.00 | 0.00 | 0.335488E+10 | 0.233290E+10 | 21654.81 | 30-JUN-08:61 | 12299.17 | 0.00 |
July | 0.00 | 0.00 | 0.548880E+10 | 0.365354E+10 | 21757.47 | 23-JUL-09:01 | 12178.95 | 0.00 |
August | 0.00 | 0.00 | 0.385688E+10 | 0.255812E+10 | 21191.58 | 30-AUG-08:61 | 10488.58 | 0.00 |
September | 0.00 | 0.00 | 0.464960E+09 | 0.360140E+09 | 20519.95 | 01-SEP-08:62 | 10587.90 | 0.00 |
October | 0.00 | 0.00 | 9364283.25 | 8395341.07 | 995.85 | 19-OCT-15:00 | 895.50 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.143624E+11 | 0.989124E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.548880E+10 | 0.365354E+10 | 21757.47 | 13157.93 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 21816539.86 | 17982728.21 | 2804.21 | 23-APR-16:00 | 2346.51 | 0.00 |
May | 0.00 | 0.00 | 0.111117E+10 | 0.913982E+09 | 20271.12 | 26-MAY-08:62 | 13149.75 | 0.00 |
June | 0.00 | 0.00 | 0.326127E+10 | 0.225953E+10 | 21691.52 | 30-JUN-08:61 | 12273.41 | 0.00 |
July | 0.00 | 0.00 | 0.538179E+10 | 0.357612E+10 | 21793.10 | 23-JUL-09:01 | 12154.18 | 0.00 |
August | 0.00 | 0.00 | 0.376101E+10 | 0.249198E+10 | 21230.16 | 30-AUG-08:61 | 10484.67 | 0.00 |
September | 0.00 | 0.00 | 0.444120E+09 | 0.343011E+09 | 20557.37 | 01-SEP-08:62 | 10586.41 | 0.00 |
October | 0.00 | 0.00 | 6686773.93 | 5981594.72 | 892.39 | 19-OCT-15:00 | 801.73 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.139879E+11 | 0.960860E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.538179E+10 | 0.357612E+10 | 21793.10 | 13149.75 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 17515672.99 | 14397031.70 | 2478.78 | 23-APR-16:00 | 2065.41 | 0.00 |
May | 0.00 | 0.00 | 0.100327E+10 | 0.823228E+09 | 20539.04 | 26-MAY-08:62 | 13260.26 | 0.00 |
June | 0.00 | 0.00 | 0.307662E+10 | 0.211904E+10 | 21976.47 | 30-JUN-08:61 | 12355.24 | 0.00 |
July | 0.00 | 0.00 | 0.518665E+10 | 0.343749E+10 | 22076.79 | 23-JUL-09:01 | 12240.57 | 0.00 |
August | 0.00 | 0.00 | 0.358210E+10 | 0.237101E+10 | 21517.62 | 30-AUG-08:61 | 10576.68 | 0.00 |
September | 0.00 | 0.00 | 0.406336E+09 | 0.311945E+09 | 20835.67 | 01-SEP-08:62 | 10684.14 | 0.00 |
October | 0.00 | 0.00 | 2919634.06 | 2598345.00 | 690.47 | 19-OCT-15:00 | 619.35 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.132754E+11 | 0.907970E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.518665E+10 | 0.343749E+10 | 22076.79 | 13260.26 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 8386626.12 | 6871913.85 | 1671.61 | 23-APR-16:00 | 1382.57 | 0.00 |
May | 0.00 | 0.00 | 0.837822E+09 | 0.687854E+09 | 7094.89 | 25-MAY-16:10 | 5406.74 | 0.00 |
June | 0.00 | 0.00 | 0.282310E+10 | 0.193807E+10 | 25243.92 | 30-JUN-08:61 | 12596.20 | 0.00 |
July | 0.00 | 0.00 | 0.495543E+10 | 0.329840E+10 | 25053.95 | 23-JUL-09:01 | 13594.87 | 0.00 |
August | 0.00 | 0.00 | 0.332144E+10 | 0.221894E+10 | 24339.12 | 30-AUG-08:61 | 11823.61 | 0.00 |
September | 0.00 | 0.00 | 0.351557E+09 | 0.268352E+09 | 16684.42 | 01-SEP-08:62 | 8367.64 | 0.00 |
October | 0.00 | 0.00 | 678226.29 | 607041.49 | 350.97 | 19-OCT-15:00 | 315.77 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.122984E+11 | 0.841909E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.495543E+10 | 0.329840E+10 | 25243.92 | 13594.87 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.214103E+10 | 0.50 | 1920.65 | 01-JAN-08:61 | 0.92 |
February | 0.177684E+10 | 0.47 | 1920.65 | 01-FEB-08:61 | 0.92 |
March | 0.183347E+10 | 0.46 | 1920.65 | 01-MAR-09:01 | 0.92 |
April | 0.152423E+10 | 0.41 | 1920.65 | 01-APR-08:61 | 0.92 |
May | 0.140573E+10 | 0.38 | 1920.65 | 01-MAY-08:61 | 0.92 |
June | 0.137781E+10 | 0.38 | 1920.65 | 19-JUN-08:62 | 0.90 |
July | 0.141849E+10 | 0.38 | 1920.65 | 01-JUL-08:62 | 0.91 |
August | 0.140182E+10 | 0.37 | 1920.65 | 01-AUG-08:62 | 0.90 |
September | 0.136108E+10 | 0.38 | 1920.65 | 01-SEP-08:62 | 0.90 |
October | 0.151701E+10 | 0.40 | 1920.65 | 06-OCT-08:61 | 0.92 |
November | 0.167473E+10 | 0.44 | 1920.65 | 03-NOV-08:61 | 0.92 |
December | 0.209543E+10 | 0.49 | 1920.65 | 01-DEC-08:61 | 0.92 |
Annual Sum or Average | 0.195277E+11 | 0.42 | |||
Minimum of Months | 0.136108E+10 | 0.37 | 1920.65 | 0.90 | |
Maximum of Months | 0.214103E+10 | 0.50 | 1920.65 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135986E+10 | 0.58 | 993.62 | 03-JAN-08:30 | 0.95 |
February | 0.122306E+10 | 0.53 | 993.62 | 04-FEB-17:30 | 0.95 |
March | 0.137164E+10 | 0.51 | 993.62 | 01-MAR-15:50 | 0.95 |
April | 0.133821E+10 | 0.53 | 993.62 | 01-APR-17:20 | 0.95 |
May | 0.157635E+10 | 0.61 | 993.62 | 05-MAY-13:40 | 0.95 |
June | 0.161388E+10 | 0.61 | 993.62 | 01-JUN-09:40 | 0.94 |
July | 0.165301E+10 | 0.59 | 993.62 | 02-JUL-10:00 | 0.94 |
August | 0.167084E+10 | 0.60 | 993.62 | 01-AUG-08:15 | 0.94 |
September | 0.158576E+10 | 0.63 | 993.62 | 02-SEP-08:30 | 0.94 |
October | 0.141689E+10 | 0.54 | 993.62 | 01-OCT-15:10 | 0.95 |
November | 0.131020E+10 | 0.49 | 993.62 | 05-NOV-09:00 | 0.95 |
December | 0.135030E+10 | 0.57 | 993.62 | 10-DEC-10:03 | 0.95 |
Annual Sum or Average | 0.174700E+11 | 0.57 | |||
Minimum of Months | 0.122306E+10 | 0.49 | 993.62 | 0.94 | |
Maximum of Months | 0.167084E+10 | 0.63 | 993.62 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.164604E+10 | 0.51 | 1137.40 | 01-JAN-08:07 | 0.95 |
February | 0.149044E+10 | 0.52 | 1137.40 | 01-FEB-08:07 | 0.95 |
March | 0.167880E+10 | 0.52 | 1137.40 | 01-MAR-08:05 | 0.95 |
April | 0.159690E+10 | 0.51 | 1137.40 | 01-APR-07:05 | 0.95 |
May | 0.166242E+10 | 0.52 | 1137.40 | 01-MAY-07:02 | 0.95 |
June | 0.162147E+10 | 0.52 | 1137.40 | 01-JUN-09:20 | 0.94 |
July | 0.163785E+10 | 0.50 | 1137.40 | 01-JUL-09:50 | 0.94 |
August | 0.167880E+10 | 0.52 | 1137.40 | 01-AUG-09:30 | 0.94 |
September | 0.159690E+10 | 0.51 | 1137.40 | 02-SEP-12:00 | 0.94 |
October | 0.164604E+10 | 0.51 | 1137.40 | 03-OCT-16:10 | 0.95 |
November | 0.159690E+10 | 0.51 | 1137.40 | 01-NOV-08:07 | 0.95 |
December | 0.163785E+10 | 0.51 | 1137.40 | 01-DEC-09:06 | 0.95 |
Annual Sum or Average | 0.194904E+11 | 0.51 | |||
Minimum of Months | 0.149044E+10 | 0.50 | 1137.40 | 0.94 | |
Maximum of Months | 0.167880E+10 | 0.52 | 1137.40 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.987537E+09 | 0.40 | 1132.94 | 01-JAN-08:61 | 0.95 |
February | 0.817435E+09 | 0.38 | 1132.94 | 01-FEB-07:02 | 0.95 |
March | 0.857509E+09 | 0.37 | 1132.94 | 02-MAR-08:61 | 0.95 |
April | 0.703347E+09 | 0.33 | 1132.94 | 02-APR-08:61 | 0.95 |
May | 0.666546E+09 | 0.31 | 1132.94 | 25-MAY-07:02 | 0.94 |
June | 0.658487E+09 | 0.32 | 1132.94 | 19-JUN-07:02 | 0.93 |
July | 0.662862E+09 | 0.31 | 1132.94 | 01-JUL-07:01 | 0.94 |
August | 0.673208E+09 | 0.31 | 1132.94 | 01-AUG-07:02 | 0.94 |
September | 0.637951E+09 | 0.31 | 1132.94 | 01-SEP-07:01 | 0.93 |
October | 0.706696E+09 | 0.32 | 1132.94 | 30-OCT-07:01 | 0.95 |
November | 0.777614E+09 | 0.35 | 1132.94 | 05-NOV-08:61 | 0.95 |
December | 0.959262E+09 | 0.39 | 1132.94 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.910845E+10 | 0.34 | |||
Minimum of Months | 0.637951E+09 | 0.31 | 1132.94 | 0.93 | |
Maximum of Months | 0.987537E+09 | 0.40 | 1132.94 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.991534E+09 | 0.40 | 1126.74 | 01-JAN-08:61 | 0.95 |
February | 0.820756E+09 | 0.38 | 1126.74 | 01-FEB-07:02 | 0.95 |
March | 0.860820E+09 | 0.37 | 1126.74 | 01-MAR-08:62 | 0.95 |
April | 0.705465E+09 | 0.33 | 1126.74 | 02-APR-08:61 | 0.95 |
May | 0.664098E+09 | 0.31 | 1126.74 | 25-MAY-07:02 | 0.94 |
June | 0.653862E+09 | 0.32 | 1126.74 | 19-JUN-07:02 | 0.93 |
July | 0.657994E+09 | 0.31 | 1126.74 | 01-JUL-07:01 | 0.94 |
August | 0.669117E+09 | 0.31 | 1126.74 | 01-AUG-07:02 | 0.94 |
September | 0.635617E+09 | 0.31 | 1126.74 | 01-SEP-07:01 | 0.93 |
October | 0.708264E+09 | 0.33 | 1126.74 | 30-OCT-07:01 | 0.95 |
November | 0.780681E+09 | 0.35 | 1126.74 | 05-NOV-08:61 | 0.95 |
December | 0.963068E+09 | 0.39 | 1126.74 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.911128E+10 | 0.34 | |||
Minimum of Months | 0.635617E+09 | 0.31 | 1126.74 | 0.93 | |
Maximum of Months | 0.991534E+09 | 0.40 | 1126.74 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158388E+10 | 0.38 | 1853.64 | 01-JAN-09:01 | 0.92 |
February | 0.129968E+10 | 0.35 | 1853.64 | 01-FEB-08:61 | 0.92 |
March | 0.135903E+10 | 0.34 | 1853.64 | 01-MAR-09:01 | 0.92 |
April | 0.109823E+10 | 0.30 | 1853.64 | 01-APR-08:61 | 0.92 |
May | 0.101442E+10 | 0.28 | 1853.64 | 01-MAY-08:61 | 0.92 |
June | 0.997200E+09 | 0.28 | 1853.64 | 19-JUN-08:62 | 0.90 |
July | 0.100152E+10 | 0.27 | 1853.64 | 01-JUL-08:62 | 0.91 |
August | 0.101778E+10 | 0.28 | 1853.64 | 01-AUG-08:62 | 0.91 |
September | 0.971510E+09 | 0.28 | 1853.64 | 01-SEP-08:62 | 0.90 |
October | 0.110354E+10 | 0.30 | 1853.64 | 06-OCT-08:61 | 0.92 |
November | 0.122875E+10 | 0.32 | 1853.64 | 03-NOV-08:61 | 0.92 |
December | 0.153652E+10 | 0.37 | 1853.64 | 01-DEC-08:61 | 0.92 |
Annual Sum or Average | 0.142121E+11 | 0.31 | |||
Minimum of Months | 0.971510E+09 | 0.27 | 1853.64 | 0.90 | |
Maximum of Months | 0.158388E+10 | 0.38 | 1853.64 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.881962E+09 | 0.39 | 1035.84 | 01-JAN-09:01 | 0.95 |
February | 0.724859E+09 | 0.36 | 1035.84 | 01-FEB-08:61 | 0.95 |
March | 0.758562E+09 | 0.35 | 1035.84 | 01-MAR-09:01 | 0.95 |
April | 0.614232E+09 | 0.31 | 1035.84 | 01-APR-08:61 | 0.95 |
May | 0.567269E+09 | 0.29 | 1035.84 | 01-MAY-08:61 | 0.95 |
June | 0.554664E+09 | 0.29 | 1035.84 | 19-JUN-08:62 | 0.93 |
July | 0.556640E+09 | 0.28 | 1035.84 | 01-JUL-08:62 | 0.94 |
August | 0.567834E+09 | 0.29 | 1035.84 | 01-AUG-08:62 | 0.94 |
September | 0.543187E+09 | 0.29 | 1035.84 | 01-SEP-08:62 | 0.93 |
October | 0.616651E+09 | 0.31 | 1035.84 | 06-OCT-08:61 | 0.95 |
November | 0.686040E+09 | 0.33 | 1035.84 | 03-NOV-08:61 | 0.95 |
December | 0.855948E+09 | 0.38 | 1035.84 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.792785E+10 | 0.32 | |||
Minimum of Months | 0.543187E+09 | 0.28 | 1035.84 | 0.93 | |
Maximum of Months | 0.881962E+09 | 0.39 | 1035.84 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.882735E+09 | 0.39 | 1034.93 | 01-JAN-09:01 | 0.95 |
February | 0.725871E+09 | 0.36 | 1034.93 | 01-FEB-08:61 | 0.95 |
March | 0.759943E+09 | 0.35 | 1034.93 | 01-MAR-09:01 | 0.95 |
April | 0.615749E+09 | 0.31 | 1034.93 | 01-APR-08:61 | 0.95 |
May | 0.567594E+09 | 0.29 | 1034.93 | 01-MAY-08:61 | 0.95 |
June | 0.553729E+09 | 0.29 | 1034.93 | 22-JUN-08:62 | 0.94 |
July | 0.555561E+09 | 0.28 | 1034.93 | 01-JUL-08:62 | 0.94 |
August | 0.567091E+09 | 0.29 | 1034.93 | 01-AUG-08:62 | 0.94 |
September | 0.543289E+09 | 0.29 | 1034.93 | 01-SEP-08:62 | 0.93 |
October | 0.617692E+09 | 0.31 | 1034.93 | 06-OCT-08:61 | 0.95 |
November | 0.687248E+09 | 0.33 | 1034.93 | 03-NOV-08:61 | 0.95 |
December | 0.856760E+09 | 0.38 | 1034.93 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.793326E+10 | 0.32 | |||
Minimum of Months | 0.543289E+09 | 0.28 | 1034.93 | 0.93 | |
Maximum of Months | 0.882735E+09 | 0.39 | 1034.93 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.898269E+09 | 0.40 | 1046.27 | 01-JAN-09:01 | 0.95 |
February | 0.739480E+09 | 0.37 | 1046.27 | 01-FEB-08:61 | 0.95 |
March | 0.775088E+09 | 0.36 | 1046.27 | 01-MAR-09:01 | 0.95 |
April | 0.628324E+09 | 0.32 | 1046.27 | 01-APR-08:61 | 0.95 |
May | 0.575883E+09 | 0.29 | 1046.27 | 01-MAY-08:61 | 0.95 |
June | 0.558736E+09 | 0.29 | 1046.27 | 25-JUN-09:02 | 0.93 |
July | 0.560371E+09 | 0.28 | 1046.27 | 01-JUL-08:62 | 0.94 |
August | 0.572741E+09 | 0.29 | 1046.27 | 08-AUG-08:62 | 0.93 |
September | 0.550497E+09 | 0.29 | 1046.27 | 01-SEP-08:62 | 0.93 |
October | 0.628306E+09 | 0.31 | 1046.27 | 06-OCT-08:61 | 0.95 |
November | 0.699856E+09 | 0.34 | 1046.27 | 01-NOV-08:61 | 0.95 |
December | 0.871983E+09 | 0.39 | 1046.27 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.805953E+10 | 0.33 | |||
Minimum of Months | 0.550497E+09 | 0.28 | 1046.27 | 0.93 | |
Maximum of Months | 0.898269E+09 | 0.40 | 1046.27 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.107852E+10 | 0.53 | 1191.07 | 01-JAN-09:01 | 0.95 |
February | 0.887120E+09 | 0.49 | 1191.07 | 01-FEB-08:61 | 0.95 |
March | 0.918224E+09 | 0.41 | 1191.07 | 01-MAR-08:62 | 0.95 |
April | 0.735276E+09 | 0.32 | 1191.07 | 01-APR-08:61 | 0.95 |
May | 0.662481E+09 | 0.29 | 1191.07 | 01-MAY-08:61 | 0.95 |
June | 0.632489E+09 | 0.29 | 1191.07 | 25-JUN-09:02 | 0.93 |
July | 0.634441E+09 | 0.28 | 1191.07 | 04-JUL-09:02 | 0.93 |
August | 0.650364E+09 | 0.29 | 1191.07 | 09-AUG-08:61 | 0.93 |
September | 0.629821E+09 | 0.29 | 892.96 | 28-SEP-08:62 | 0.83 |
October | 0.724163E+09 | 0.31 | 1191.07 | 04-OCT-08:62 | 0.95 |
November | 0.814499E+09 | 0.35 | 1191.07 | 01-NOV-08:61 | 0.95 |
December | 0.104133E+10 | 0.51 | 1191.07 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.940873E+10 | 0.36 | |||
Minimum of Months | 0.629821E+09 | 0.28 | 892.96 | 0.83 | |
Maximum of Months | 0.107852E+10 | 0.53 | 1191.07 | 0.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.93 | 0.24 |
February | 2.31 | 0.61 |
March | 2.91 | 0.65 |
April | 0.78 | 0.80 |
May | 0.78 | 1.23 |
June | 0.58 | 0.79 |
July | 0.22 | 1.12 |
August | 0.58 | 1.50 |
September | 1.14 | 1.13 |
October | 0.46 | 1.14 |
November | 1.48 | 0.50 |
December | 3.89 | 0.55 |
Annual Sum or Average | 18.06 | 0.66 |
Minimum of Months | 0.22 | 0.24 |
Maximum of Months | 3.89 | 1.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.91 | 0.00 |
February | 0.39 | 0.00 |
March | 0.50 | 5.50 |
April | 1.35 | 3.76 |
May | 4.00 | 3.71 |
June | 7.35 | 3.92 |
July | 12.90 | 3.59 |
August | 9.19 | 4.09 |
September | 2.41 | 3.77 |
October | 2.08 | 3.83 |
November | 0.32 | 4.50 |
December | 0.42 | 0.00 |
Annual Sum or Average | 41.83 | 3.68 |
Minimum of Months | 0.32 | 0.00 |
Maximum of Months | 12.90 | 5.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.60 | 0.00 |
February | 0.09 | 0.00 |
March | 0.00 | 0.00 |
April | 0.33 | 0.75 |
May | 2.07 | 0.75 |
June | 1.22 | 0.75 |
July | 2.07 | 0.75 |
August | 0.74 | 0.75 |
September | 1.26 | 0.75 |
October | 1.01 | 0.75 |
November | 0.00 | 0.00 |
December | 0.33 | 0.00 |
Annual Sum or Average | 9.72 | 0.67 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.07 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.78 | 0.00 |
February | 0.35 | 0.00 |
March | 0.00 | 0.00 |
April | 0.12 | 0.75 |
May | 1.67 | 0.75 |
June | 1.22 | 0.75 |
July | 1.57 | 0.75 |
August | 0.85 | 0.75 |
September | 1.25 | 0.75 |
October | 0.79 | 0.75 |
November | 0.00 | 0.00 |
December | 0.41 | 0.00 |
Annual Sum or Average | 9.01 | 0.62 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.67 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.16 | 0.00 |
February | 0.47 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 1.10 | 0.75 |
June | 1.05 | 0.75 |
July | 1.40 | 0.75 |
August | 0.85 | 0.75 |
September | 1.22 | 0.75 |
October | 0.60 | 0.75 |
November | 0.03 | 0.00 |
December | 0.48 | 0.00 |
Annual Sum or Average | 8.36 | 0.56 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.40 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.27 | 0.00 |
February | 1.21 | 0.00 |
March | 0.53 | 0.00 |
April | 0.00 | 0.00 |
May | 0.17 | 3.30 |
June | 0.26 | 3.30 |
July | 0.86 | 3.30 |
August | 0.58 | 3.30 |
September | 0.89 | 3.30 |
October | 0.00 | 0.00 |
November | 0.21 | 0.00 |
December | 1.18 | 0.00 |
Annual Sum or Average | 8.15 | 1.11 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.27 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.70 | 0.00 |
February | 1.01 | 0.00 |
March | 0.43 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.17 | 1.65 |
July | 0.55 | 1.65 |
August | 0.50 | 1.65 |
September | 0.56 | 1.65 |
October | 0.00 | 0.00 |
November | 0.15 | 0.00 |
December | 1.09 | 0.00 |
Annual Sum or Average | 6.16 | 0.48 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.70 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.73 | 0.02 |
February | 1.05 | 0.00 |
March | 0.43 | 0.00 |
April | 0.08 | 0.00 |
May | 0.00 | 0.00 |
June | 0.17 | 1.65 |
July | 0.55 | 1.65 |
August | 0.58 | 1.65 |
September | 0.81 | 1.65 |
October | 0.00 | 0.00 |
November | 0.21 | 0.00 |
December | 1.09 | 0.00 |
Annual Sum or Average | 6.70 | 0.53 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.73 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.11 | 0.00 |
February | 1.29 | 0.00 |
March | 0.78 | 0.00 |
April | 0.31 | 0.45 |
May | 0.00 | 0.00 |
June | 0.17 | 1.65 |
July | 0.39 | 1.65 |
August | 0.42 | 1.65 |
September | 0.50 | 1.65 |
October | 0.00 | 0.00 |
November | 0.47 | 0.00 |
December | 1.28 | 0.00 |
Annual Sum or Average | 7.71 | 0.33 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.11 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.81 | 0.00 |
February | 3.05 | 0.00 |
March | 2.12 | 0.00 |
April | 1.53 | 0.18 |
May | 0.00 | 0.00 |
June | 0.09 | 1.65 |
July | 0.44 | 1.65 |
August | 0.17 | 1.65 |
September | 0.42 | 1.65 |
October | 0.22 | 0.00 |
November | 2.05 | 0.00 |
December | 3.51 | 0.00 |
Annual Sum or Average | 17.41 | 0.12 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.81 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.214103E+10 | 0.523132E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.177684E+10 | 0.361631E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.183347E+10 | 0.306208E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.156882E+10 | 0.120637E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.224549E+10 | 0.805941E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.364945E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.513019E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.401223E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.175347E+10 | 0.391428E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.154147E+10 | 0.867191E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.167473E+10 | 0.230245E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.209543E+10 | 0.487929E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.294226E+11 | 0.212848E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.154147E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.513019E+10 | 0.523132E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.135986E+10 | 0.188710E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.122306E+10 | 0.121172E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.137164E+10 | 0.978045E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.137131E+10 | 0.278713E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.210590E+10 | 47359810.70 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.289995E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.362078E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.306081E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.181420E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.143658E+10 | 0.178725E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.131020E+10 | 0.692229E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.135030E+10 | 0.174106E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.229246E+11 | 0.697233E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.122306E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.362078E+10 | 0.188710E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.164604E+10 | 0.203410E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.149044E+10 | 0.134126E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.167880E+10 | 0.109823E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.160915E+10 | 0.336790E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.205759E+10 | 96607893.52 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.258438E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.307047E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.269031E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.174386E+10 | 525369.42 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.165693E+10 | 0.233274E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.159690E+10 | 0.793256E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.163785E+10 | 0.187379E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.234627E+11 | 0.772041E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.149044E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.307047E+10 | 0.203410E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.987537E+09 | 0.214974E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.817435E+09 | 0.144952E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.857509E+09 | 0.122281E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.714902E+09 | 0.434936E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.109956E+10 | 0.239710E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.174126E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.232138E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.188574E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.837626E+09 | 71600717.97 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.721300E+09 | 0.329731E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.777614E+09 | 0.916390E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.959262E+09 | 0.198805E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.137211E+11 | 0.852232E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.714902E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.232138E+10 | 0.214974E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.991534E+09 | 0.220262E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.820756E+09 | 0.149510E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.860820E+09 | 0.127054E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.715476E+09 | 0.472171E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.106591E+10 | 0.325712E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.168383E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.226218E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.182982E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.812680E+09 | 0.158516E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.718506E+09 | 0.363884E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.780681E+09 | 0.960759E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.963068E+09 | 0.203929E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.135053E+11 | 0.885279E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.715476E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.226218E+10 | 0.220262E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.158388E+10 | 0.422971E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.129968E+10 | 0.287916E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.135903E+10 | 0.248361E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.111232E+10 | 0.981806E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.163603E+10 | 0.942075E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.265861E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.364043E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.290957E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.122109E+10 | 0.740867E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.111183E+10 | 0.809854E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.122875E+10 | 0.191509E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.153652E+10 | 0.393266E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.212977E+11 | 0.174002E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.111183E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.364043E+10 | 0.422971E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.881962E+09 | 0.219602E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.724859E+09 | 0.149892E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.758562E+09 | 0.129539E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.620841E+09 | 0.517910E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.875301E+09 | 0.522583E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.139089E+10 | 5695.15 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.189613E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.151612E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.661087E+09 | 0.407905E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.619276E+09 | 0.424128E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.686040E+09 | 0.999312E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.855948E+09 | 0.204329E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.114870E+11 | 0.906801E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.619276E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.189613E+10 | 0.219602E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.882735E+09 | 0.220475E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.725871E+09 | 0.150914E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.759943E+09 | 0.130834E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.621894E+09 | 0.531416E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.862726E+09 | 0.578899E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.136794E+10 | 494846.96 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.187142E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.149361E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.655964E+09 | 0.446455E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.619574E+09 | 0.434507E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.687248E+09 | 0.101091E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.856760E+09 | 0.205234E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.114057E+11 | 0.915399E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.619574E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.187142E+10 | 0.220475E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.898269E+09 | 0.225527E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.739480E+09 | 0.155585E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.775088E+09 | 0.136217E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.633315E+09 | 0.573914E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.844572E+09 | 0.723507E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.133033E+10 | 3245945.41 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.183440E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.145912E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.653749E+09 | 0.534568E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.629133E+09 | 0.463113E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.699856E+09 | 0.105163E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.871983E+09 | 0.210195E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.113693E+11 | 0.949002E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.629133E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.183440E+10 | 0.225527E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.107852E+10 | 0.270187E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.887120E+09 | 0.190723E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.918224E+09 | 0.167541E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.737745E+09 | 0.748605E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.891979E+09 | 0.122918E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.135327E+10 | 46036241.28 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.187492E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.148565E+10 | 2417705.58 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.719797E+09 | 0.785844E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.724357E+09 | 0.559370E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.814499E+09 | 0.124775E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.104133E+10 | 0.250664E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.125274E+11 | 0.115532E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.719797E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.187492E+10 | 0.270187E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.214103E+10 | 0.00 | 0.418506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177684E+10 | 0.00 | 0.289305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183347E+10 | 0.00 | 0.244967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152423E+10 | 0.164849E+09 | 0.965096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140573E+10 | 0.324451E+10 | 0.644753E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137781E+10 | 0.923502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141849E+10 | 0.154474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140182E+10 | 0.107934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136108E+10 | 0.154971E+10 | 0.313142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151701E+10 | 89737857.15 | 0.693753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167473E+10 | 0.00 | 0.184196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209543E+10 | 0.00 | 0.390343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195277E+11 | 0.405246E+11 | 0.170278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.214103E+10 | 0.154474E+11 | 0.418506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135986E+10 | 0.00 | 0.150968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122306E+10 | 0.00 | 0.969379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137164E+10 | 0.00 | 0.782436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133821E+10 | 0.147707E+09 | 0.222970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157635E+10 | 0.244000E+10 | 37887848.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161388E+10 | 0.608989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165301E+10 | 0.955686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167084E+10 | 0.675361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158576E+10 | 0.106331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141689E+10 | 84193764.82 | 0.142980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131020E+10 | 14653.83 | 0.553783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135030E+10 | 0.00 | 0.139284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174700E+11 | 0.261356E+11 | 0.557786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167084E+10 | 0.955686E+10 | 0.150968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.164604E+10 | 0.00 | 0.162728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149044E+10 | 0.00 | 0.107301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167880E+10 | 0.00 | 0.878581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159690E+10 | 53250921.37 | 0.269432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166242E+10 | 0.178097E+10 | 77286314.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162147E+10 | 0.449211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163785E+10 | 0.687179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167880E+10 | 0.484306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159690E+10 | 0.677582E+09 | 420295.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164604E+10 | 46243164.38 | 0.186619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159690E+10 | 0.00 | 0.634605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163785E+10 | 0.00 | 0.149903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194904E+11 | 0.187650E+11 | 0.617633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167880E+10 | 0.687179E+10 | 0.162728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.987537E+09 | 0.00 | 0.171979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.817435E+09 | 0.00 | 0.115962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.857509E+09 | 0.00 | 0.978250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.703347E+09 | 42692883.63 | 0.347948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.666546E+09 | 0.167861E+10 | 0.191768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.658487E+09 | 0.439147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.662862E+09 | 0.688534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.673208E+09 | 0.501036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.637951E+09 | 0.790302E+09 | 57280574.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.706696E+09 | 53735608.76 | 0.263785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.777614E+09 | 0.00 | 0.733112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.959262E+09 | 0.00 | 0.159044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.910845E+10 | 0.188525E+11 | 0.681785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.637951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.987537E+09 | 0.688534E+10 | 0.171979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.991534E+09 | 0.00 | 0.176210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.820756E+09 | 0.00 | 0.119608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.860820E+09 | 0.00 | 0.101643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.705465E+09 | 36556026.60 | 0.377737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.664098E+09 | 0.154827E+10 | 0.260570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.653862E+09 | 0.416733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.657994E+09 | 0.663917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.669117E+09 | 0.477988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.635617E+09 | 0.700670E+09 | 0.126813E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.708264E+09 | 37347147.93 | 0.291107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.780681E+09 | 0.00 | 0.768607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.963068E+09 | 0.00 | 0.163143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.911128E+10 | 0.179092E+11 | 0.708223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.635617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.991534E+09 | 0.663917E+10 | 0.176210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158388E+10 | 0.00 | 0.338377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129968E+10 | 0.00 | 0.230333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135903E+10 | 0.00 | 0.198689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109823E+10 | 50675353.91 | 0.785445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101442E+10 | 0.236855E+10 | 0.753660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.997200E+09 | 0.671044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100152E+10 | 0.108979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101778E+10 | 0.775390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.971510E+09 | 0.987336E+09 | 0.592693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110354E+10 | 29779194.20 | 0.647883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122875E+10 | 0.00 | 0.153207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153652E+10 | 0.00 | 0.314613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142121E+11 | 0.287986E+11 | 0.139201E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.971510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158388E+10 | 0.108979E+11 | 0.338377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.881962E+09 | 0.00 | 0.175681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.724859E+09 | 0.00 | 0.119914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.758562E+09 | 0.00 | 0.103631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.614232E+09 | 23570018.10 | 0.414328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.567269E+09 | 0.116394E+10 | 0.418067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.554664E+09 | 0.335488E+10 | 4556.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.556640E+09 | 0.548880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.567834E+09 | 0.385688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.543187E+09 | 0.464960E+09 | 0.326324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.616651E+09 | 9364283.25 | 0.339303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.686040E+09 | 0.00 | 0.799450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.855948E+09 | 0.00 | 0.163463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.792785E+10 | 0.143624E+11 | 0.725441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.543187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.881962E+09 | 0.548880E+10 | 0.175681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.882735E+09 | 0.00 | 0.176380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.725871E+09 | 0.00 | 0.120732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.759943E+09 | 0.00 | 0.104667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.615749E+09 | 21816539.86 | 0.425133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.567594E+09 | 0.111117E+10 | 0.463119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.553729E+09 | 0.326127E+10 | 395877.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.555561E+09 | 0.538179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.567091E+09 | 0.376101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.543289E+09 | 0.444120E+09 | 0.357164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.617692E+09 | 6686773.93 | 0.347606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.687248E+09 | 0.00 | 0.808727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.856760E+09 | 0.00 | 0.164188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.793326E+10 | 0.139879E+11 | 0.732319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.543289E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.882735E+09 | 0.538179E+10 | 0.176380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.898269E+09 | 0.00 | 0.180421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.739480E+09 | 0.00 | 0.124468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.775088E+09 | 0.00 | 0.108973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.628324E+09 | 17515672.99 | 0.459131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.575883E+09 | 0.100327E+10 | 0.578805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.558736E+09 | 0.307662E+10 | 2596756.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.560371E+09 | 0.518665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.572741E+09 | 0.358210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.550497E+09 | 0.406336E+09 | 0.427654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.628306E+09 | 2919634.06 | 0.370490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.699856E+09 | 0.00 | 0.841301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.871983E+09 | 0.00 | 0.168156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.805953E+10 | 0.132754E+11 | 0.759202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.550497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.898269E+09 | 0.518665E+10 | 0.180421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.107852E+10 | 0.00 | 0.216150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.887120E+09 | 0.00 | 0.152578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.918224E+09 | 0.00 | 0.134033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.735276E+09 | 8386626.12 | 0.598884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.662481E+09 | 0.837822E+09 | 0.983345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.632489E+09 | 0.282310E+10 | 36828993.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.634441E+09 | 0.495543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.650364E+09 | 0.332144E+10 | 1934164.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.629821E+09 | 0.351557E+09 | 0.628675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.724163E+09 | 678226.29 | 0.447496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.814499E+09 | 0.00 | 0.998198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104133E+10 | 0.00 | 0.200531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.940873E+10 | 0.122984E+11 | 0.924257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.629821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107852E+10 | 0.495543E+10 | 0.216150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.214103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152423E+10 | 0.00 | 0.00 | 0.00 | 44584911.39 | 0.00 | 0.120637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140573E+10 | 0.00 | 0.00 | 0.00 | 0.839763E+09 | 0.00 | 0.805941E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137781E+10 | 0.00 | 0.00 | 0.00 | 0.227163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141849E+10 | 0.00 | 0.00 | 0.00 | 0.371170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140182E+10 | 0.00 | 0.00 | 0.00 | 0.261041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136108E+10 | 0.00 | 0.00 | 0.00 | 0.392392E+09 | 0.00 | 0.391428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151701E+10 | 0.00 | 0.00 | 0.00 | 24454672.37 | 0.00 | 0.867191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195277E+11 | 0.00 | 0.00 | 0.00 | 0.989494E+10 | 0.00 | 0.212848E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.136108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.214103E+10 | 0.00 | 0.00 | 0.00 | 0.371170E+10 | 0.00 | 0.523132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.135986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.978045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133821E+10 | 0.00 | 0.00 | 0.00 | 33099529.84 | 0.00 | 0.278713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157635E+10 | 0.00 | 0.00 | 0.00 | 0.529555E+09 | 0.00 | 47359810.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161388E+10 | 0.00 | 0.00 | 0.00 | 0.128607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165301E+10 | 0.00 | 0.00 | 0.00 | 0.196778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167084E+10 | 0.00 | 0.00 | 0.00 | 0.138998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158576E+10 | 0.00 | 0.00 | 0.00 | 0.228438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141689E+10 | 0.00 | 0.00 | 0.00 | 19695310.50 | 0.00 | 0.178725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131020E+10 | 0.00 | 0.00 | 0.00 | 4131.89 | 0.00 | 0.692229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174700E+11 | 0.00 | 0.00 | 0.00 | 0.545461E+10 | 0.00 | 0.697233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.122306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167084E+10 | 0.00 | 0.00 | 0.00 | 0.196778E+10 | 0.00 | 0.188710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.164604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159690E+10 | 0.00 | 0.00 | 0.00 | 12250939.45 | 0.00 | 0.336790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166242E+10 | 0.00 | 0.00 | 0.00 | 0.395171E+09 | 0.00 | 96607893.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162147E+10 | 0.00 | 0.00 | 0.00 | 0.962913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163785E+10 | 0.00 | 0.00 | 0.00 | 0.143262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167880E+10 | 0.00 | 0.00 | 0.00 | 0.101152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159690E+10 | 0.00 | 0.00 | 0.00 | 0.146960E+09 | 0.00 | 525369.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164604E+10 | 0.00 | 0.00 | 0.00 | 10891341.34 | 0.00 | 0.233274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.793256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194904E+11 | 0.00 | 0.00 | 0.00 | 0.397232E+10 | 0.00 | 0.772041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.149044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167880E+10 | 0.00 | 0.00 | 0.00 | 0.143262E+10 | 0.00 | 0.203410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.987537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.817435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.857509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.703347E+09 | 0.00 | 0.00 | 0.00 | 11554819.74 | 0.00 | 0.434936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.666546E+09 | 0.00 | 0.00 | 0.00 | 0.433009E+09 | 0.00 | 0.239710E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.658487E+09 | 0.00 | 0.00 | 0.00 | 0.108278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.662862E+09 | 0.00 | 0.00 | 0.00 | 0.165851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.673208E+09 | 0.00 | 0.00 | 0.00 | 0.121253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.637951E+09 | 0.00 | 0.00 | 0.00 | 0.199675E+09 | 0.00 | 71600717.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.706696E+09 | 0.00 | 0.00 | 0.00 | 14604023.47 | 0.00 | 0.329731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.777614E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.916390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.959262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.910845E+10 | 0.00 | 0.00 | 0.00 | 0.461267E+10 | 0.00 | 0.852232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.637951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.987537E+09 | 0.00 | 0.00 | 0.00 | 0.165851E+10 | 0.00 | 0.214974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.991534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.820756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.860820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.705465E+09 | 0.00 | 0.00 | 0.00 | 10011225.51 | 0.00 | 0.472171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.664098E+09 | 0.00 | 0.00 | 0.00 | 0.401809E+09 | 0.00 | 0.325712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.653862E+09 | 0.00 | 0.00 | 0.00 | 0.102996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.657994E+09 | 0.00 | 0.00 | 0.00 | 0.160418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.669117E+09 | 0.00 | 0.00 | 0.00 | 0.116070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.635617E+09 | 0.00 | 0.00 | 0.00 | 0.177064E+09 | 0.00 | 0.158516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.708264E+09 | 0.00 | 0.00 | 0.00 | 10241994.54 | 0.00 | 0.363884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.780681E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.963068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.911128E+10 | 0.00 | 0.00 | 0.00 | 0.439398E+10 | 0.00 | 0.885279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.635617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.991534E+09 | 0.00 | 0.00 | 0.00 | 0.160418E+10 | 0.00 | 0.220262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.158388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109823E+10 | 0.00 | 0.00 | 0.00 | 14087514.43 | 0.00 | 0.981806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101442E+10 | 0.00 | 0.00 | 0.00 | 0.621603E+09 | 0.00 | 0.942075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.997200E+09 | 0.00 | 0.00 | 0.00 | 0.166141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100152E+10 | 0.00 | 0.00 | 0.00 | 0.263891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101778E+10 | 0.00 | 0.00 | 0.00 | 0.189178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.971510E+09 | 0.00 | 0.00 | 0.00 | 0.249578E+09 | 0.00 | 0.740867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110354E+10 | 0.00 | 0.00 | 0.00 | 8282544.29 | 0.00 | 0.809854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142121E+11 | 0.00 | 0.00 | 0.00 | 0.708566E+10 | 0.00 | 0.174002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.971510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158388E+10 | 0.00 | 0.00 | 0.00 | 0.263891E+10 | 0.00 | 0.422971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.881962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.724859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.758562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.614232E+09 | 0.00 | 0.00 | 0.00 | 6608849.75 | 0.00 | 0.517910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.567269E+09 | 0.00 | 0.00 | 0.00 | 0.308032E+09 | 0.00 | 0.522583E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.554664E+09 | 0.00 | 0.00 | 0.00 | 0.836222E+09 | 0.00 | 5695.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.556640E+09 | 0.00 | 0.00 | 0.00 | 0.133949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.567834E+09 | 0.00 | 0.00 | 0.00 | 0.948284E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.543187E+09 | 0.00 | 0.00 | 0.00 | 0.117899E+09 | 0.00 | 0.407905E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.616651E+09 | 0.00 | 0.00 | 0.00 | 2625267.57 | 0.00 | 0.424128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.686040E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.855948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.792785E+10 | 0.00 | 0.00 | 0.00 | 0.355916E+10 | 0.00 | 0.906801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.543187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.881962E+09 | 0.00 | 0.00 | 0.00 | 0.133949E+10 | 0.00 | 0.219602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.882735E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.725871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.759943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.615749E+09 | 0.00 | 0.00 | 0.00 | 6145046.78 | 0.00 | 0.531416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.567594E+09 | 0.00 | 0.00 | 0.00 | 0.295132E+09 | 0.00 | 0.578899E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.553729E+09 | 0.00 | 0.00 | 0.00 | 0.814206E+09 | 0.00 | 494846.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.555561E+09 | 0.00 | 0.00 | 0.00 | 0.131586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.567091E+09 | 0.00 | 0.00 | 0.00 | 0.926521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.543289E+09 | 0.00 | 0.00 | 0.00 | 0.112675E+09 | 0.00 | 0.446455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.617692E+09 | 0.00 | 0.00 | 0.00 | 1881964.69 | 0.00 | 0.434507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.687248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.856760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.793326E+10 | 0.00 | 0.00 | 0.00 | 0.347242E+10 | 0.00 | 0.915399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.543289E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.882735E+09 | 0.00 | 0.00 | 0.00 | 0.131586E+10 | 0.00 | 0.220475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.898269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.739480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.775088E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.628324E+09 | 0.00 | 0.00 | 0.00 | 4990999.23 | 0.00 | 0.573914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.575883E+09 | 0.00 | 0.00 | 0.00 | 0.268690E+09 | 0.00 | 0.723507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.558736E+09 | 0.00 | 0.00 | 0.00 | 0.771591E+09 | 0.00 | 3245945.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.560371E+09 | 0.00 | 0.00 | 0.00 | 0.127402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.572741E+09 | 0.00 | 0.00 | 0.00 | 0.886382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.550497E+09 | 0.00 | 0.00 | 0.00 | 0.103252E+09 | 0.00 | 0.534568E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.628306E+09 | 0.00 | 0.00 | 0.00 | 827628.46 | 0.00 | 0.463113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.699856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.871983E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.805953E+10 | 0.00 | 0.00 | 0.00 | 0.330976E+10 | 0.00 | 0.949002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.550497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.898269E+09 | 0.00 | 0.00 | 0.00 | 0.127402E+10 | 0.00 | 0.225527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.107852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.887120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.918224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.735276E+09 | 0.00 | 0.00 | 0.00 | 2469699.92 | 0.00 | 0.748605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.662481E+09 | 0.00 | 0.00 | 0.00 | 0.229498E+09 | 0.00 | 0.122918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.632489E+09 | 0.00 | 0.00 | 0.00 | 0.720783E+09 | 0.00 | 46036241.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.634441E+09 | 0.00 | 0.00 | 0.00 | 0.124048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.650364E+09 | 0.00 | 0.00 | 0.00 | 0.835282E+09 | 0.00 | 2417705.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.629821E+09 | 0.00 | 0.00 | 0.00 | 89975506.91 | 0.00 | 0.785844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.724163E+09 | 0.00 | 0.00 | 0.00 | 194321.56 | 0.00 | 0.559370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.814499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.940873E+10 | 0.00 | 0.00 | 0.00 | 0.311869E+10 | 0.00 | 0.115532E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.629821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107852E+10 | 0.00 | 0.00 | 0.00 | 0.124048E+10 | 0.00 | 0.270187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.880722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295541E+11 | 0.00 | 0.00 | 0.52 |
February | 0.230482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205994E+11 | 0.00 | 0.00 | 0.52 |
March | 0.437708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166278E+11 | 0.00 | 0.00 | 0.53 |
April | 0.749596E+10 | 20233647.14 | 0.00 | 397598.16 | 143197.01 | 0.485433E+10 | 0.102531E+09 | 0.00 | 0.53 |
May | 0.457328E+10 | 0.399346E+09 | 0.00 | 6910113.50 | 302248.02 | 0.108425E+09 | 0.208732E+10 | 0.00 | 0.66 |
June | 0.144816E+10 | 0.220372E+10 | 0.00 | 10527879.38 | 5526576.17 | 0.00 | 0.286322E+10 | 0.00 | 0.78 |
July | 0.340115E+09 | 0.376892E+10 | 0.00 | 13258045.97 | 8986627.36 | 0.00 | 0.265975E+10 | 0.00 | 0.82 |
August | 0.711659E+09 | 0.179762E+10 | 0.00 | 17248306.37 | 1386985.07 | 0.00 | 0.382535E+10 | 0.00 | 0.87 |
September | 0.444322E+10 | 81438441.08 | 0.00 | 8349231.07 | 0.00 | 5507323.13 | 0.444626E+10 | 0.00 | 0.70 |
October | 0.907388E+10 | 0.00 | 0.00 | 901028.15 | 0.00 | 0.301140E+10 | 0.662461E+09 | 0.00 | 0.55 |
November | 0.667242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111372E+11 | 0.00 | 10543.80 | 0.53 |
December | 0.117061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277249E+11 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.434919E+11 | 0.827128E+10 | 0.00 | 57592202.59 | 16345633.64 | 0.113623E+12 | 0.166469E+11 | 10543.80 | 0.63 |
Minimum of Months | 0.340115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.907388E+10 | 0.376892E+10 | 0.00 | 17248306.37 | 8986627.36 | 0.295541E+11 | 0.444626E+10 | 10543.80 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.629768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105606E+11 | 0.00 | 0.00 | 0.39 |
February | 0.139076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682230E+10 | 0.00 | 0.00 | 0.38 |
March | 0.251468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516409E+10 | 0.00 | 0.00 | 0.39 |
April | 0.267262E+10 | 9148538.13 | 0.00 | 515482.77 | 0.00 | 0.150687E+10 | 0.450519E+09 | 0.00 | 0.43 |
May | 0.129856E+10 | 0.197840E+09 | 0.00 | 4586753.06 | 425210.19 | 8575328.47 | 0.238870E+10 | 0.00 | 0.77 |
June | 0.203636E+09 | 0.118313E+10 | 0.00 | 6022187.31 | 4838428.52 | 0.00 | 0.252645E+10 | 0.00 | 1.00 |
July | 18442467.47 | 0.207602E+10 | 0.00 | 5702622.08 | 10514901.44 | 0.00 | 0.184705E+10 | 0.00 | 0.98 |
August | 93748393.02 | 0.960163E+09 | 0.00 | 8320544.69 | 1327740.67 | 0.00 | 0.281814E+10 | 0.00 | 1.13 |
September | 0.112985E+10 | 38467532.87 | 0.00 | 6617053.73 | 0.00 | 0.00 | 0.411076E+10 | 0.00 | 0.88 |
October | 0.350794E+10 | 0.00 | 0.00 | 1296596.65 | 0.00 | 0.660335E+09 | 0.939993E+09 | 0.00 | 0.48 |
November | 0.262560E+10 | 0.00 | 0.00 | 5732.69 | 0.00 | 0.373618E+10 | 4213438.06 | 0.00 | 0.39 |
December | 0.714623E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.975730E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.168002E+11 | 0.446477E+10 | 0.00 | 33066972.98 | 17106280.82 | 0.382163E+11 | 0.150858E+11 | 0.00 | 0.63 |
Minimum of Months | 18442467.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.350794E+10 | 0.207602E+10 | 0.00 | 8320544.69 | 10514901.44 | 0.105606E+11 | 0.411076E+10 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117926E+11 | 0.00 | 0.00 | 0.41 |
February | 0.751571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.809670E+10 | 0.00 | 0.00 | 0.41 |
March | 0.177255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651103E+10 | 0.00 | 0.00 | 0.42 |
April | 0.275311E+10 | 4576869.88 | 0.00 | 181219.05 | 1061756.59 | 0.182056E+10 | 0.234058E+09 | 0.00 | 0.44 |
May | 0.164118E+10 | 0.151656E+09 | 0.00 | 2372252.22 | 1740625.84 | 36022731.33 | 0.132148E+10 | 0.00 | 0.67 |
June | 0.347474E+09 | 0.845957E+09 | 0.00 | 4215807.00 | 37887557.12 | 0.00 | 0.185330E+10 | 0.00 | 0.90 |
July | 87555281.52 | 0.131284E+10 | 0.00 | 5059133.24 | 81172533.11 | 0.00 | 0.148961E+10 | 0.00 | 0.86 |
August | 0.246130E+09 | 0.677529E+09 | 0.00 | 6447255.67 | 15869585.03 | 0.00 | 0.227567E+10 | 0.00 | 1.01 |
September | 0.150995E+10 | 31885384.08 | 0.00 | 4059601.42 | 0.00 | 0.00 | 0.269002E+10 | 0.00 | 0.76 |
October | 0.344491E+10 | 0.00 | 0.00 | 592570.76 | 0.00 | 0.109175E+10 | 0.465402E+09 | 0.00 | 0.47 |
November | 0.214188E+10 | 0.00 | 49.41 | 0.00 | 34740.09 | 0.461612E+10 | 0.00 | 678.00 | 0.41 |
December | 0.213065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109126E+11 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.150320E+11 | 0.302445E+10 | 49.41 | 22927839.35 | 0.137767E+09 | 0.448774E+11 | 0.103295E+11 | 678.00 | 0.60 |
Minimum of Months | 87555281.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.344491E+10 | 0.131284E+10 | 49.41 | 6447255.67 | 81172533.11 | 0.117926E+11 | 0.269002E+10 | 678.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 65648563.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118497E+11 | 0.00 | 0.00 | 0.41 |
February | 0.636691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821309E+10 | 0.00 | 0.00 | 0.41 |
March | 0.150450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677937E+10 | 0.00 | 0.00 | 0.42 |
April | 0.264324E+10 | 5605770.90 | 0.00 | 64403.60 | 1768718.13 | 0.199189E+10 | 62739743.84 | 0.00 | 0.42 |
May | 0.176347E+10 | 0.200946E+09 | 0.00 | 1690627.67 | 3166858.15 | 48696775.01 | 0.698497E+09 | 0.00 | 0.54 |
June | 0.530746E+09 | 0.936373E+09 | 0.00 | 3298301.43 | 47868311.05 | 0.00 | 0.104630E+10 | 0.00 | 0.67 |
July | 0.144631E+09 | 0.149067E+10 | 0.00 | 3914368.45 | 98455073.00 | 0.00 | 0.839223E+09 | 0.00 | 0.65 |
August | 0.256870E+09 | 0.816366E+09 | 0.00 | 5025706.25 | 22937073.87 | 0.00 | 0.142444E+10 | 0.00 | 0.74 |
September | 0.179023E+10 | 43962290.23 | 0.00 | 3106435.60 | 0.00 | 530193.32 | 0.165632E+10 | 0.00 | 0.60 |
October | 0.324894E+10 | 0.00 | 0.00 | 398724.04 | 0.00 | 0.130584E+10 | 0.259711E+09 | 0.00 | 0.44 |
November | 0.199046E+10 | 0.00 | 53383.60 | 0.00 | 26336.76 | 0.475901E+10 | 0.00 | 5249.82 | 0.41 |
December | 0.130416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109954E+11 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.147058E+11 | 0.349393E+10 | 53383.60 | 17498567.02 | 0.174222E+09 | 0.459435E+11 | 0.598723E+10 | 5249.82 | 0.51 |
Minimum of Months | 65648563.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.324894E+10 | 0.149067E+10 | 53383.60 | 5025706.25 | 98455073.00 | 0.118497E+11 | 0.165632E+10 | 5249.82 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 38679399.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118767E+11 | 0.00 | 0.00 | 0.41 |
February | 0.424978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842466E+10 | 0.00 | 0.00 | 0.41 |
March | 0.113082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715281E+10 | 0.00 | 0.00 | 0.42 |
April | 0.236226E+10 | 5278736.04 | 0.00 | 33117.19 | 1866987.53 | 0.227666E+10 | 32190926.45 | 0.00 | 0.42 |
May | 0.180268E+10 | 0.195180E+09 | 0.00 | 1393253.84 | 3141187.59 | 64779043.53 | 0.559601E+09 | 0.00 | 0.53 |
June | 0.574573E+09 | 0.918398E+09 | 0.00 | 2865715.57 | 47847632.75 | 0.00 | 0.941515E+09 | 0.00 | 0.65 |
July | 0.167834E+09 | 0.146024E+10 | 0.00 | 3627595.43 | 97210160.12 | 0.00 | 0.813357E+09 | 0.00 | 0.65 |
August | 0.320455E+09 | 0.791818E+09 | 0.00 | 4609574.01 | 22577497.92 | 0.00 | 0.133717E+10 | 0.00 | 0.73 |
September | 0.185906E+10 | 42824555.69 | 0.00 | 2698731.57 | 0.00 | 3055607.87 | 0.149362E+10 | 0.00 | 0.59 |
October | 0.301790E+10 | 0.00 | 0.00 | 318052.62 | 0.00 | 0.153312E+10 | 0.227997E+09 | 0.00 | 0.44 |
November | 0.170791E+10 | 0.00 | 45399.16 | 0.00 | 37880.92 | 0.503913E+10 | 0.00 | 8945.30 | 0.41 |
December | 58828486.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110668E+11 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.134660E+11 | 0.341374E+10 | 45399.16 | 15546040.23 | 0.172681E+09 | 0.474377E+11 | 0.540545E+10 | 8945.30 | 0.51 |
Minimum of Months | 38679399.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.301790E+10 | 0.146024E+10 | 45399.16 | 4609574.01 | 97210160.12 | 0.118767E+11 | 0.149362E+10 | 8945.30 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 37811208.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217840E+11 | 0.00 | 0.00 | 0.38 |
February | 0.171249E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159594E+11 | 0.00 | 0.00 | 0.38 |
March | 0.880731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142254E+11 | 0.00 | 0.00 | 0.39 |
April | 0.307542E+10 | 7607034.95 | 0.00 | 7213.16 | 5270406.02 | 0.534348E+10 | 1059141.12 | 0.00 | 0.38 |
May | 0.311955E+10 | 0.336747E+09 | 0.00 | 1540285.46 | 390899.15 | 0.181702E+09 | 0.717056E+09 | 0.00 | 0.45 |
June | 0.113232E+10 | 0.169095E+10 | 0.00 | 3625288.34 | 33038010.17 | 0.00 | 0.130553E+10 | 0.00 | 0.54 |
July | 0.298326E+09 | 0.267438E+10 | 0.00 | 4893881.58 | 95058570.18 | 0.00 | 0.129914E+10 | 0.00 | 0.54 |
August | 0.621754E+09 | 0.139642E+10 | 0.00 | 6081486.55 | 8905991.52 | 0.00 | 0.198312E+10 | 0.00 | 0.60 |
September | 0.343695E+10 | 67286067.61 | 0.00 | 3400102.88 | 0.00 | 9102207.68 | 0.213700E+10 | 0.00 | 0.48 |
October | 0.447344E+10 | 0.00 | 0.00 | 310169.28 | 0.00 | 0.387321E+10 | 0.280495E+09 | 0.00 | 0.39 |
November | 0.161265E+10 | 0.00 | 191562.70 | 0.00 | 173616.22 | 0.107655E+11 | 0.00 | 67918.45 | 0.38 |
December | 64476739.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203486E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.189247E+11 | 0.617340E+10 | 191562.70 | 19858427.26 | 0.142837E+09 | 0.924905E+11 | 0.772340E+10 | 67918.45 | 0.44 |
Minimum of Months | 37811208.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.447344E+10 | 0.267438E+10 | 191562.70 | 6081486.55 | 95058570.18 | 0.217840E+11 | 0.213700E+10 | 67918.45 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10042972.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108946E+11 | 0.00 | 0.00 | 0.38 |
February | 62528395.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799728E+10 | 0.00 | 0.00 | 0.38 |
March | 0.364346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718243E+10 | 0.00 | 0.00 | 0.39 |
April | 0.137306E+10 | 3681087.16 | 59673.82 | 1966.30 | 2632526.50 | 0.282470E+10 | 325348.73 | 18.32 | 0.38 |
May | 0.150508E+10 | 0.166451E+09 | 0.00 | 701881.34 | 163926.01 | 0.149498E+09 | 0.344713E+09 | 0.00 | 0.45 |
June | 0.576801E+09 | 0.842204E+09 | 0.00 | 1710191.34 | 15923759.29 | 0.00 | 0.656045E+09 | 0.00 | 0.55 |
July | 0.148105E+09 | 0.132760E+10 | 0.00 | 2395771.16 | 47005265.84 | 0.00 | 0.704670E+09 | 0.00 | 0.56 |
August | 0.317674E+09 | 0.689066E+09 | 0.00 | 2992912.52 | 4422988.66 | 0.00 | 0.105323E+10 | 0.00 | 0.62 |
September | 0.170601E+10 | 33561225.27 | 0.00 | 1611089.42 | 0.00 | 29003837.17 | 0.106185E+10 | 0.00 | 0.49 |
October | 0.205589E+10 | 0.00 | 0.00 | 133897.46 | 0.00 | 0.211494E+10 | 0.133227E+09 | 0.00 | 0.39 |
November | 0.655774E+09 | 0.00 | 84664.91 | 0.00 | 80874.93 | 0.552670E+10 | 0.00 | 37214.77 | 0.38 |
December | 15239779.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101851E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.879054E+10 | 0.306256E+10 | 144338.73 | 9547709.54 | 70229341.24 | 0.469042E+11 | 0.395407E+10 | 37233.09 | 0.45 |
Minimum of Months | 10042972.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.205589E+10 | 0.132760E+10 | 84664.91 | 2992912.52 | 47005265.84 | 0.108946E+11 | 0.106185E+10 | 37214.77 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 11589087.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108930E+11 | 0.00 | 0.00 | 0.38 |
February | 41607526.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801818E+10 | 0.00 | 0.00 | 0.38 |
March | 0.329153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721758E+10 | 0.00 | 0.00 | 0.39 |
April | 0.125295E+10 | 3587433.24 | 73335.88 | 1330.55 | 2736145.49 | 0.294009E+10 | 160602.18 | 9.73 | 0.38 |
May | 0.146594E+10 | 0.163107E+09 | 0.00 | 628962.44 | 181454.93 | 0.194517E+09 | 0.318250E+09 | 0.00 | 0.45 |
June | 0.597521E+09 | 0.834382E+09 | 0.00 | 1573022.06 | 15594424.61 | 0.00 | 0.614816E+09 | 0.00 | 0.55 |
July | 0.152665E+09 | 0.131302E+10 | 0.00 | 2304634.27 | 47138109.95 | 0.00 | 0.699677E+09 | 0.00 | 0.56 |
August | 0.327162E+09 | 0.678450E+09 | 0.00 | 2868856.40 | 4297886.71 | 0.00 | 0.103686E+10 | 0.00 | 0.62 |
September | 0.170558E+10 | 33103092.31 | 0.00 | 1509228.77 | 0.00 | 44978244.86 | 0.101140E+10 | 0.00 | 0.48 |
October | 0.197879E+10 | 0.00 | 0.00 | 117659.45 | 0.00 | 0.219864E+10 | 0.119539E+09 | 0.00 | 0.39 |
November | 0.564526E+09 | 0.00 | 120285.40 | 0.00 | 40250.03 | 0.561760E+10 | 0.00 | 39803.37 | 0.38 |
December | 15236191.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101851E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.844272E+10 | 0.302565E+10 | 193621.28 | 9003693.96 | 69988271.72 | 0.473097E+11 | 0.380071E+10 | 39813.11 | 0.44 |
Minimum of Months | 11589087.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.197879E+10 | 0.131302E+10 | 120285.40 | 2868856.40 | 47138109.95 | 0.108930E+11 | 0.103686E+10 | 39803.37 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8039900.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108966E+11 | 0.00 | 0.00 | 0.38 |
February | 13490339.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.804622E+10 | 0.00 | 0.00 | 0.38 |
March | 0.209418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733719E+10 | 0.00 | 0.00 | 0.39 |
April | 0.993116E+09 | 3324712.15 | 338785.63 | 233.48 | 2798676.17 | 0.318984E+10 | 1021.55 | 8107.03 | 0.38 |
May | 0.138031E+10 | 0.156934E+09 | 0.00 | 468800.96 | 149368.35 | 0.292081E+09 | 0.267071E+09 | 0.00 | 0.44 |
June | 0.610594E+09 | 0.815717E+09 | 0.00 | 1336254.55 | 16309520.65 | 0.00 | 0.563980E+09 | 0.00 | 0.54 |
July | 0.159149E+09 | 0.128612E+10 | 0.00 | 2142455.99 | 47862043.55 | 0.00 | 0.696349E+09 | 0.00 | 0.56 |
August | 0.355855E+09 | 0.659521E+09 | 0.00 | 2638062.16 | 4757247.31 | 0.00 | 0.100062E+10 | 0.00 | 0.62 |
September | 0.170915E+10 | 32434813.68 | 0.00 | 1309461.52 | 0.00 | 67213363.63 | 0.921173E+09 | 0.00 | 0.47 |
October | 0.172153E+10 | 0.00 | 0.00 | 90484.24 | 0.00 | 0.246200E+10 | 0.100061E+09 | 0.00 | 0.39 |
November | 0.369384E+09 | 0.00 | 100940.80 | 0.00 | 91505.78 | 0.581176E+10 | 0.00 | 50282.97 | 0.38 |
December | 14167483.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101861E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.754421E+10 | 0.295405E+10 | 439726.43 | 7985752.90 | 71968361.81 | 0.482890E+11 | 0.354925E+10 | 58390.01 | 0.44 |
Minimum of Months | 8039900.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.172153E+10 | 0.128612E+10 | 338785.63 | 2638062.16 | 47862043.55 | 0.108966E+11 | 0.100062E+10 | 50282.97 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2801906.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108913E+11 | 0.00 | 0.00 | 0.38 |
February | 4933807.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.804142E+10 | 0.00 | 0.00 | 0.38 |
March | 11157226.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.752099E+10 | 0.00 | 0.00 | 0.39 |
April | 0.458595E+09 | 2096888.05 | 290024.87 | 0.00 | 4479902.76 | 0.369835E+10 | 0.00 | 31379.76 | 0.38 |
May | 0.110511E+10 | 0.146524E+09 | 0.00 | 264882.67 | 709234.31 | 0.584453E+09 | 0.172457E+09 | 0.00 | 0.44 |
June | 0.631887E+09 | 0.776185E+09 | 0.00 | 1001311.12 | 14895228.12 | 2368193.85 | 0.491551E+09 | 0.00 | 0.55 |
July | 0.166209E+09 | 0.124094E+10 | 0.00 | 1821294.80 | 45000694.90 | 0.00 | 0.748670E+09 | 0.00 | 0.58 |
August | 0.453669E+09 | 0.632313E+09 | 0.00 | 2173253.19 | 4032219.31 | 0.00 | 0.942483E+09 | 0.00 | 0.64 |
September | 0.149401E+10 | 32861040.99 | 0.00 | 994354.41 | 0.00 | 0.333830E+09 | 0.775808E+09 | 0.00 | 0.46 |
October | 0.116777E+10 | 0.00 | 0.00 | 57559.12 | 0.00 | 0.300719E+10 | 75065969.85 | 0.00 | 0.39 |
November | 89885260.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608480E+10 | 0.00 | 23469.54 | 0.38 |
December | 3119383.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101866E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.558915E+10 | 0.283092E+10 | 290024.87 | 6312655.31 | 69117279.40 | 0.503513E+11 | 0.320603E+10 | 54849.31 | 0.44 |
Minimum of Months | 2801906.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.149401E+10 | 0.124094E+10 | 290024.87 | 2173253.19 | 45000694.90 | 0.108913E+11 | 0.942483E+09 | 31379.76 | 0.64 |