Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:20
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2020-06-03 19:20:39
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1145.32 | 547.91 | 547.91 |
Net Site Energy | 1145.32 | 547.91 | 547.91 |
Total Source Energy | 3588.64 | 1716.79 | 1716.79 |
Net Source Energy | 3588.64 | 1716.79 | 1716.79 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 18.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 347.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 433.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 64.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 95.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 56.39 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1126.80 | 18.52 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 18.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 347.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 433.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 64.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 95.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 56.39 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 238.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 239.07 | 8.86 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 539.06 | 8.86 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 238.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 239.07 | 8.86 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 539.06 | 8.86 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1126.799 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1126.799 | 100.00 |
Total On-Site and Utility Electric Sources | 1126.799 | 100.00 |
Total Electricity End Uses | 1126.799 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 24.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1402.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 15.7897 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 18.6637 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.0491 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.0491 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.0491 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 10.0956 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 10.0956 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 10.0956 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 10.0956 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 10.0956 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 13.4970 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 13.4970 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-SEP-13:39 | 05-FEB-10:09 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 95357.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71651.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 26802.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11548.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5414.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 123506.62 | 95357.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 95357.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 71651.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 26802.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 11548.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5414.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 20.07 | 0.00 | 0.00 | 0.00 |
Cooling | 1101.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1374.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 203.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 302.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 178.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3568.57 | 20.07 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 9.60 | 0.00 | 0.00 | 0.00 |
Cooling | 527.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 657.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 97.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 144.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 85.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1707.19 | 9.60 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 9.60 | 0.00 | 0.00 | 0.00 |
Cooling | 527.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 657.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 97.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 144.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 85.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1707.19 | 9.60 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.90 |
SMSTORE1 DIRECT AIR | 1.03 |
SMSTORE2 DIRECT AIR | 1.04 |
SMSTORE3 DIRECT AIR | 1.04 |
SMSTORE4 DIRECT AIR | 1.04 |
LGSTORE2 DIRECT AIR | 1.77 |
SMSTORE5 DIRECT AIR | 0.926989 |
SMSTORE6 DIRECT AIR | 0.921593 |
SMSTORE7 DIRECT AIR | 0.923686 |
SMSTORE8 DIRECT AIR | 1.02 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.90 | 1.90 | 1.90 | 1.90 | 1.90 | 1.90 | 1.00 | 1.00 | 1.90 |
PSZ-AC_2:2 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 1.00 | 1.03 |
PSZ-AC_3:3 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.00 | 1.04 |
PSZ-AC_4:4 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.00 | 1.04 |
PSZ-AC_5:5 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.00 | 1.04 |
PSZ-AC_6:6 | 1.77 | 1.77 | 1.77 | 1.77 | 1.77 | 1.77 | 1.00 | 1.00 | 1.77 |
PSZ-AC_7:7 | 0.926989 | 0.926989 | 0.926989 | 0.926989 | 0.926989 | 0.926989 | 1.00 | 1.000000 | 0.926989 |
PSZ-AC_8:8 | 0.921593 | 0.921593 | 0.921593 | 0.921593 | 0.921593 | 0.921593 | 1.00 | 1.00 | 0.921593 |
PSZ-AC_9:9 | 0.923686 | 0.923686 | 0.923686 | 0.923686 | 0.923686 | 0.923686 | 1.00 | 1.00 | 0.923686 |
PSZ-AC_10:10 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.00 | 1.00 | 1.02 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.90 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 1.03 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 1.04 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 1.04 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 1.04 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 1.77 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 0.926989 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 0.921593 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 0.923686 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 1.02 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.90 | 1.90 | 1.90 | 1.26 | 47277.20 | 51696.54 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 0.677464 | 25489.48 | 27550.79 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.689584 | 25945.46 | 27970.21 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.685697 | 25799.24 | 27835.71 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.684568 | 25756.76 | 27796.63 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.77 | 1.77 | 1.77 | 1.17 | 43931.02 | 48618.78 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.926989 | 0.926989 | 0.926989 | 0.611813 | 23019.35 | 25278.83 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.921593 | 0.921593 | 0.921593 | 0.608251 | 22885.35 | 25155.57 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.923686 | 0.923686 | 0.923686 | 0.609633 | 22937.33 | 25203.38 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 0.676059 | 25436.61 | 27502.24 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 1.90 | 0.951925 | 1.27 | 46763.42 | 47277.20 | 23638.60 | 23638.60 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 1.03 | 0.513230 | 0.684307 | 24902.43 | 25489.48 | 12744.74 | 12744.74 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 1.04 | 0.522410 | 0.696547 | 25324.60 | 25945.46 | 12972.73 | 12972.73 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 1.04 | 0.519470 | 0.692627 | 25156.83 | 25799.24 | 12899.62 | 12899.62 | 0.676084 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 1.04 | 0.518610 | 0.691480 | 25185.02 | 25756.76 | 12878.38 | 12878.38 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 1.77 | 0.884550 | 1.18 | 43930.97 | 43931.02 | 21965.51 | 21965.51 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 0.926990 | 0.463495 | 0.617993 | 23019.37 | 23019.35 | 11509.67 | 11509.67 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 0.921590 | 0.460795 | 0.614393 | 22885.27 | 22885.35 | 11442.67 | 11442.67 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 0.923690 | 0.461845 | 0.615793 | 22937.42 | 22937.33 | 11468.67 | 11468.67 | 0.676084 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 1.02 | 0.512165 | 0.682887 | 24717.04 | 25436.61 | 12718.31 | 12718.31 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.90 | 2037.21 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1136.46 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1156.79 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1150.27 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1148.37 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.77 | 1893.02 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.926989 | 1026.32 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.921593 | 1020.35 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.923686 | 1022.67 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1134.10 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 51696.54 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 27550.79 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 27970.21 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 27835.71 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 27796.63 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 48618.78 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 25278.83 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 25155.57 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 25203.38 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 27502.24 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 15.790 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.090 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.664 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.964 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.049 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.349 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.049 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.349 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.049 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.349 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 10.096 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.396 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 10.096 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.396 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 10.096 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.396 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 10.096 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.396 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 10.096 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.396 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 3517.173 | 10.096 | 117.254 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3517.173 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 1983.751 | 5.694 | 66.134 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1983.751 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1492.501 | 8.568 | 99.513 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.501 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 1211.251 | 6.953 | 80.761 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.251 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 1211.251 | 6.953 | 80.761 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.251 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 1211.251 | 6.953 | 80.761 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.251 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 3517.173 | 10.096 | 117.254 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3517.173 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.4678 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.903 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.37383775E-12 | 0.81582362E-15 | -0.12542534E-12 | 0.11541335E-15 |
23 | 6 | 0.32294454E-07 | 0.13597119E-09 | 0.73677206E-08 | -0.15476624E-12 |
24 | 5 | -0.20833553E-03 | 0.11386595E-05 | -0.10688959E-03 | 0.72710034E-08 |
25 | 4 | 0.31322919 | 0.54351077E-03 | 0.10727732 | -0.36571185E-04 |
26 | 3 | -7.6832781 | 0.16549290E-01 | -2.4626776 | 0.31053958E-01 |
27 | 2 | 42.245606 | 0.57933024E-01 | 15.771342 | -0.34865193 |
28 | 1 | -81.598353 | 0.25789083E-01 | -29.595166 | 1.1010509 |
29 | 0 | 46.824332 | 0.51189598E-03 | 16.280659 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 29 | 1 | VerySmooth | 2.843 | 0.252 | 0.162 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.16139 | 0.61114 | 0.61114 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.159 | 4.569E-004 | 2.517E-004 | 0.317 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 4.561E-002 | 2.619E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 9.122E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.113 | 6.514E-004 | 3.022E-004 | 0.453 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 21593.65725 | 25912.38870 | 1.58654 | 1.90385 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 33.90000 | 1.65138E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 14599.96220 | 17519.95464 | 0.62991 | 0.75589 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 11641.93583 | 13970.32300 | 0.85538 | 1.02646 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65138E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 7539.97371 | 9047.96845 | 0.32531 | 0.39037 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 12182.41548 | 14618.89857 | 0.87069 | 1.04482 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 29.55500 | 1.65138E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 7638.85270 | 9166.62325 | 0.32957 | 0.39549 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 12115.94409 | 14539.13291 | 0.86578 | 1.03894 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 29.55500 | 1.65138E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 7709.18324 | 9251.01988 | 0.33261 | 0.39913 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 12096.08916 | 14515.30699 | 0.86435 | 1.03722 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 29.55500 | 1.65138E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 7827.32323 | 9392.78787 | 0.33771 | 0.40525 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 20065.98103 | 24079.17723 | 1.47425 | 1.76910 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 33.76833 | 1.65138E-002 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 14700.86158 | 17641.03390 | 0.63426 | 0.76112 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 10513.97363 | 12616.76835 | 0.77249 | 0.92699 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 33.76833 | 1.65138E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 8035.53558 | 9642.64270 | 0.34669 | 0.41603 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 10452.77091 | 12543.32510 | 0.76799 | 0.92159 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 33.76833 | 1.65138E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 8032.20727 | 9638.64873 | 0.34654 | 0.41585 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 10476.51632 | 12571.81958 | 0.76974 | 0.92369 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 33.76833 | 1.65138E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 8195.67490 | 9834.80988 | 0.35360 | 0.42432 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 11620.30755 | 13944.36906 | 0.85361 | 1.02433 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 33.50500 | 1.65138E-002 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 9120.07822 | 10944.09386 | 0.39348 | 0.47217 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 30494.45 | 1.90385 | 1.90385 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 25476.89 | 0.75589 | 0.75589 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 16243.60 | 1.02646 | 1.02646 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 13022.21 | 0.39037 | 0.39037 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 16283.76 | 1.04482 | 1.04482 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 13139.13 | 0.39549 | 0.39549 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16327.65 | 1.03894 | 1.03894 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 13222.30 | 0.39913 | 0.39913 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 16206.65 | 1.03722 | 1.03722 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 13362.01 | 0.40525 | 0.40525 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 28675.19 | 1.76910 | 1.76910 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 25596.22 | 0.76112 | 0.76112 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 14905.01 | 0.92699 | 0.92699 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 13608.22 | 0.41603 | 0.41603 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 14832.94 | 0.92159 | 0.92159 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 13604.28 | 0.41585 | 0.41585 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14859.68 | 0.92369 | 0.92369 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 13797.59 | 0.42432 | 0.42432 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 16121.34 | 1.02433 | 1.02433 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 14890.70 | 0.47217 | 0.47217 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.90385 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02646 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04482 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03894 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03722 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.76910 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.92699 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.92159 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.92369 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02433 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.90385 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.90385 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.90385 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.90385 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.90385 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.90385 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02646 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02646 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02646 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02646 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02646 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02646 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04482 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04482 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04482 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04482 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04482 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04482 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03894 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03894 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03894 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03894 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03894 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.03894 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03722 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03722 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03722 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03722 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03722 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.03722 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.76910 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.76910 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.76910 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.76910 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.76910 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.76910 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.92699 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.92699 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.92699 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.92699 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.92699 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.92699 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.92159 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.92159 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.92159 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.92159 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.92159 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.92159 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.92369 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.92369 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.92369 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.92369 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.92369 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.92369 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02433 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02433 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02433 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02433 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02433 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02433 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.90385 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.02646 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.04482 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.03894 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.03722 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.76910 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.92699 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.92159 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.92369 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.02433 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.90385 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.90385 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.90385 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.90385 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.25654 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.90385 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.95193 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.26923 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 46763.41647 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 47277.20000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 23638.60000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 23638.60000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 47277.20000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 51696.53649 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.90385 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2037.21261 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 51696.53649 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02646 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02646 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02646 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02646 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67746 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02646 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51323 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68431 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 24902.42580 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 25489.48000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12744.74000 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12744.74000 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25489.48000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27550.78768 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02646 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1136.45553 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 27550.78768 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04482 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04482 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04482 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04482 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68958 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04482 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52241 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69655 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 25324.59755 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 25945.46000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12972.73000 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12972.73000 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25945.46000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27970.20746 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04482 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1156.78571 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 27970.20746 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03894 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03894 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03894 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03894 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68570 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03894 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51947 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69263 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 25156.82789 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 25799.24000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12899.62000 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12899.62000 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25799.24000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27835.71023 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03894 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1150.26622 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 27835.71023 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03722 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03722 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03722 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03722 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68457 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03722 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51861 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69148 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 25185.01761 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 25756.76000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12878.38000 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12878.38000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25756.76000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27796.62911 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03722 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1148.37222 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 27796.62911 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.76910 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.76910 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.76910 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.76910 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.16761 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.76910 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.88455 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.17940 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 43930.96598 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 43931.02000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 21965.51000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 21965.51000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 43931.02000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 48618.77640 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.76910 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1893.02304 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 48618.77640 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.92699 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.92699 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.92699 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.92699 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.61181 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.92699 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46350 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.61799 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 23019.36926 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23019.35000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11509.67500 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11509.67500 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23019.35000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25278.82928 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.92699 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1026.32436 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25278.82928 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.92159 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.92159 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.92159 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.92159 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.60825 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.92159 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46080 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.61439 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22885.27440 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22885.35000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11442.67500 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11442.67500 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22885.35000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25155.57050 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.92159 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1020.34958 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25155.57050 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.92369 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.92369 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.92369 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.92369 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.60963 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.92369 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46185 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.61579 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22937.42240 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22937.33000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11468.66500 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11468.66500 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22937.33000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25203.38109 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.92369 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1022.66744 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25203.38109 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02433 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02433 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02433 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02433 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67606 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02433 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51217 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68289 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 24717.04396 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 25436.61000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12718.30500 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12718.30500 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25436.61000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27502.23551 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02433 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1134.09848 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 27502.23551 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 45775.2 | 11.77 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 24679.7 | 34.11 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 25121.2 | 45.46 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 24979.6 | 57.66 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 24938.5 | 69.71 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 42535.4 | 52.02 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 22288.0 | 112.75 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 22158.3 | 125.36 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 22208.6 | 137.02 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 24628.5 | 135.51 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.468 | 0.437 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 7 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.0911028712E-002 | 9.7492782738E-002 | Pass | Pass | 3.8284416888E-002 | 0.1069019160 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 2.4550778246E-002 | 0.1293589494 | Pass | Pass | 3.6551113763E-002 | 0.1071745746 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 4.5633866200E-002 | 0.1655433042 | Pass | Pass | 0.1505967730 | 1.3435765228 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 4.5642455816E-002 | 0.1661468273 | Pass | Pass | 0.1500882935 | 1.3396376258 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 4.5656479765E-002 | 0.1645916363 | Pass | Pass | 0.1538838007 | 1.3625567129 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.4998220372E-002 | 0.1475067198 | Pass | Pass | 0.1286115740 | 1.0503742217 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.3754905520E-002 | 0.1418704568 | Pass | Pass | 0.1587086057 | 1.3027411853 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.3636279055E-002 | 0.1399549192 | Pass | Pass | 0.1509478933 | 1.2972937671 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.4290263333E-002 | 0.1401119280 | Pass | Pass | 0.1547005620 | 1.3225433933 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 4.9286172675E-002 | 0.1455479518 | Pass | Pass | 0.1771456165 | 1.5395062919 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.437 | 0.468 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.843 | 0.252 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.843 | 0.252 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.843 | 0.252 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.5_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.843 | 0.252 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.843 | 0.252 | 0.251 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.843 | 0.252 | 0.251 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 10.0956 | 348.39 | 3517.17 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 64.95 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 5.6941 | 348.39 | 1983.75 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 36.63 |
SMSTORE1_LIGHTS | SMSTORE1 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 32.48 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 8.5681 | 174.19 | 1492.50 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 27.56 |
SMSTORE2_LIGHTS | SMSTORE2 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 25.74 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 6.9535 | 174.19 | 1211.25 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 17.73 |
SMSTORE3_LIGHTS | SMSTORE3 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 25.74 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 6.9535 | 174.19 | 1211.25 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 17.73 |
SMSTORE4_LIGHTS | SMSTORE4 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 25.74 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 6.9535 | 174.19 | 1211.25 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 17.73 |
LGSTORE2_LIGHTS | LGSTORE2 | 10.0956 | 348.39 | 3517.17 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 47.31 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 23.66 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 23.66 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 23.66 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 23.66 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.7485 | 4180.64 | 28213.04 | 433.94 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 314.61 | AstronomicalClock | - | 41.73 | 41.73 | 2.46 | |
EXTERIOR_LIGHTS_B | 4639.80 | AstronomicalClock | - | 83.73 | 71.13 | 61.95 | |
Exterior Lighting Total | 4954.41 | 64.41 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 47277.20 | 31963.17 | 15314.03 | 0.68 | 3.73 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 25489.48 | 17232.93 | 8256.55 | 0.68 | 3.80 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 25945.46 | 17541.21 | 8404.25 | 0.68 | 3.80 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 25799.24 | 17442.35 | 8356.89 | 0.68 | 3.80 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 25756.76 | 17413.63 | 8343.13 | 0.68 | 3.80 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 43931.02 | 29700.88 | 14230.14 | 0.68 | 3.73 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 23019.35 | 15562.92 | 7456.43 | 0.68 | 3.80 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22885.35 | 15472.33 | 7413.02 | 0.68 | 3.80 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22937.33 | 15507.47 | 7429.86 | 0.68 | 3.80 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 25436.61 | 17197.18 | 8239.43 | 0.68 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 45775.2 | 11.77 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 24679.7 | 34.11 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 25121.2 | 45.46 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 24979.6 | 57.66 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 24938.5 | 69.71 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 42535.4 | 52.02 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 22288.0 | 112.75 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 22158.3 | 125.36 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 22208.6 | 137.02 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 24628.5 | 135.51 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 51696.54 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 27550.79 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 27970.21 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 27835.71 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 27796.63 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 48618.78 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25278.83 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25155.57 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25203.38 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 27502.24 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.90 | 2037.21 | 1070.05 | 1.00 | 1.32 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1136.46 | 1107.16 | 1.00 | 1.40 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1156.79 | 1107.16 | 1.00 | 1.39 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1150.27 | 1107.16 | 1.00 | 1.39 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1148.37 | 1107.16 | 1.00 | 1.39 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.77 | 1893.02 | 1070.05 | 1.00 | 1.33 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.93 | 1026.32 | 1107.16 | 1.00 | 1.42 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.92 | 1020.35 | 1107.16 | 1.00 | 1.42 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.92 | 1022.67 | 1107.16 | 1.00 | 1.42 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1134.10 | 1107.16 | 1.00 | 1.40 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 21593.66 | 25912.39 | 74.38 | 1.587 | 1.904 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 23.89 | 23.88 | 0.01026 | 33.90 | 0.01651 | 0.411 | 0.00 |
SMSTORE1 | 11641.94 | 13970.32 | 80.20 | 0.855 | 1.026 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01030 | 33.83 | 0.01651 | 0.206 | 0.00 |
SMSTORE2 | 12182.42 | 14618.90 | 83.92 | 0.871 | 1.045 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00940 | 29.55 | 0.01651 | 0.206 | 0.00 |
SMSTORE3 | 12115.94 | 14539.13 | 83.47 | 0.866 | 1.039 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00938 | 29.55 | 0.01651 | 0.206 | 0.00 |
SMSTORE4 | 12096.09 | 14515.31 | 83.33 | 0.864 | 1.037 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00941 | 29.55 | 0.01651 | 0.206 | 0.00 |
LGSTORE2 | 20065.98 | 24079.18 | 69.12 | 1.474 | 1.769 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.88 | 0.01035 | 33.77 | 0.01651 | 0.411 | 0.00 |
SMSTORE5 | 10513.97 | 12616.77 | 72.43 | 0.772 | 0.927 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.88 | 0.01045 | 33.77 | 0.01651 | 0.206 | 0.00 |
SMSTORE6 | 10452.77 | 12543.33 | 72.01 | 0.768 | 0.922 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.88 | 0.01046 | 33.77 | 0.01651 | 0.206 | 0.00 |
SMSTORE7 | 10476.52 | 12571.82 | 72.17 | 0.770 | 0.924 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.88 | 0.01046 | 33.77 | 0.01651 | 0.206 | 0.00 |
SMSTORE8 | 11620.31 | 13944.37 | 80.05 | 0.854 | 1.024 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 23.89 | 23.88 | 0.01030 | 33.50 | 0.01651 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 14599.96 | 17519.95 | 50.29 | 0.630 | 0.756 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00703 | 4.60 | 0.00526 | 0.411 | 0.00 |
SMSTORE1 | 7539.97 | 9047.97 | 51.94 | 0.325 | 0.390 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00696 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE2 | 7638.85 | 9166.62 | 52.62 | 0.330 | 0.395 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00697 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE3 | 7709.18 | 9251.02 | 53.11 | 0.333 | 0.399 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00697 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE4 | 7827.32 | 9392.79 | 53.92 | 0.338 | 0.405 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00698 | 4.60 | 0.00526 | 0.206 | 0.00 |
LGSTORE2 | 14700.86 | 17641.03 | 50.64 | 0.634 | 0.761 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00704 | 4.60 | 0.00526 | 0.411 | 0.00 |
SMSTORE5 | 8035.54 | 9642.64 | 55.36 | 0.347 | 0.416 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00700 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE6 | 8032.21 | 9638.65 | 55.33 | 0.347 | 0.416 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00700 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE7 | 8195.67 | 9834.81 | 56.46 | 0.354 | 0.424 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00701 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE8 | 9120.08 | 10944.09 | 62.83 | 0.393 | 0.472 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00705 | 4.60 | 0.00526 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.90 | 1.90 | 0.76 | 0.76 | 1.9039 | 1.9039 | 1.9039 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.03 | 1.03 | 0.39 | 0.39 | 1.0265 | 1.0265 | 1.0265 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.04 | 1.04 | 0.40 | 0.40 | 1.0448 | 1.0448 | 1.0448 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.04 | 1.04 | 0.40 | 0.40 | 1.0389 | 1.0389 | 1.0389 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.04 | 1.04 | 0.41 | 0.41 | 1.0372 | 1.0372 | 1.0372 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.77 | 1.77 | 0.76 | 0.76 | 1.7691 | 1.7691 | 1.7691 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.93 | 0.93 | 0.42 | 0.42 | 0.9270 | 0.9270 | 0.9270 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 0.92 | 0.92 | 0.42 | 0.42 | 0.9216 | 0.9216 | 0.9216 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 0.92 | 0.92 | 0.42 | 0.42 | 0.9237 | 0.9237 | 0.9237 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.02 | 1.02 | 0.47 | 0.47 | 1.0243 | 1.0243 | 1.0243 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 23638.600 | 0.000 | 1.903850 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 23638.60 | 15373.05 | 1.903850 | 26.05 | 19.57 | 0.01161308 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01651378 | 25.10 | 21.6116 | 23.88 | 0.01026196 | 55.4282 | 21593.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 51696.536 | 51696.536 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 51696.54 | 51696.54 | 1.903853 | 12.12 | 9.23 | 0.00606726 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 21.6116 | 21.11 | 0.00703498 | 45.2109 | 14599.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 12744.740 | 0.000 | 1.026460 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 12744.74 | 8318.75 | 1.026460 | 25.89 | 19.47 | 0.01154745 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01651378 | 25.10 | 20.0423 | 23.88 | 0.01030114 | 55.6375 | 11640.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 27550.788 | 27550.788 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27550.79 | 27550.79 | 1.026461 | 12.41 | 9.35 | 0.00606387 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 20.0423 | 21.11 | 0.00696272 | 44.7522 | 7539.97 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 12972.730 | 0.000 | 1.044820 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 12972.73 | 8473.09 | 1.044820 | 25.89 | 19.46 | 0.01154050 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01651378 | 25.10 | 19.6902 | 23.89 | 0.00939942 | 50.8316 | 11674.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 27970.207 | 27970.207 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27970.21 | 27970.21 | 1.044824 | 12.52 | 9.42 | 0.00607830 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.6901 | 21.11 | 0.00696854 | 44.7892 | 7638.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 12899.620 | 0.000 | 1.038940 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 12899.62 | 8431.36 | 1.038940 | 25.88 | 19.45 | 0.01153290 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01651378 | 25.10 | 19.8016 | 23.89 | 0.00937951 | 50.7249 | 11711.26 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 27835.710 | 27835.710 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27835.71 | 27835.71 | 1.038935 | 12.60 | 9.47 | 0.00608898 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.8017 | 21.11 | 0.00697381 | 44.8227 | 7709.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 12878.380 | 0.000 | 1.037220 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 12878.38 | 8400.84 | 1.037220 | 25.90 | 19.47 | 0.01155396 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01651378 | 25.10 | 19.8344 | 23.89 | 0.00941160 | 50.8966 | 11608.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 27796.629 | 27796.629 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27796.63 | 27796.63 | 1.037225 | 12.73 | 9.54 | 0.00610691 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.8343 | 21.11 | 0.00698311 | 44.8818 | 7827.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 21965.510 | 0.000 | 1.769100 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 21965.51 | 14062.35 | 1.769100 | 26.21 | 19.75 | 0.01179106 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01651378 | 25.10 | 23.2578 | 23.88 | 0.01035312 | 55.9121 | 20053.86 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 48618.776 | 48618.776 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 48618.78 | 48618.78 | 1.769102 | 12.18 | 9.27 | 0.00607816 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 23.2578 | 21.11 | 0.00704426 | 45.2698 | 14700.86 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 11509.675 | 0.000 | 0.926990 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 11509.67 | 7341.80 | 0.926990 | 26.11 | 19.73 | 0.01180030 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01651378 | 25.10 | 22.1930 | 23.88 | 0.01044958 | 56.4257 | 10507.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 25278.829 | 25278.829 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 25278.83 | 25278.83 | 0.926989 | 12.94 | 9.67 | 0.00613604 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 22.1930 | 21.11 | 0.00699583 | 44.9628 | 8035.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 11442.675 | 0.000 | 0.921590 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 11442.67 | 7289.58 | 0.921590 | 26.12 | 19.74 | 0.01181509 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01651378 | 25.10 | 22.3230 | 23.88 | 0.01045847 | 56.4729 | 10446.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 25155.570 | 25155.570 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 25155.57 | 25155.57 | 0.921593 | 12.94 | 9.67 | 0.00613562 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 22.3229 | 21.11 | 0.00699569 | 44.9619 | 8032.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 11468.665 | 0.000 | 0.923690 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 11468.67 | 7309.67 | 0.923690 | 26.12 | 19.74 | 0.01180959 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01651378 | 25.10 | 22.2723 | 23.88 | 0.01045501 | 56.4545 | 10468.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 25203.381 | 25203.381 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 25203.38 | 25203.38 | 0.923686 | 13.10 | 9.77 | 0.00615876 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 22.2724 | 21.11 | 0.00700732 | 45.0358 | 8195.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 12718.305 | 0.000 | 1.024330 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 12718.31 | 8284.46 | 1.024330 | 25.82 | 19.44 | 0.01154990 | 12.80 | 12.09 | 0.00850000 | 33.50 | 0.01651377 | 25.00 | 20.0840 | 23.88 | 0.01030241 | 55.6434 | 11605.97 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 27502.236 | 27502.236 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27502.24 | 27502.24 | 1.024332 | 13.92 | 10.25 | 0.00627010 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 20.0840 | 21.11 | 0.00705221 | 45.3214 | 9120.08 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23638.600 | 0.000 | 1.903850 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.4281 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 23638.60 | 15373.05 | 1.0000 | 2.29064930 | 1.903850 | 26.05 | 19.57 | 0.01161308 | 55780.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23638.60 | 33.90 | 0.01651378 | 25.10 | 0.41145340 | 21.6116 | 23.88 | 0.01026196 | 23.88 | 0.01026196 | 55.4282 | 21593.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 51696.536 | 51696.536 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.903853 | 2.29065280 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 51696.54 | 51696.54 | 1.0000 | 2.29065280 | 1.903853 | 12.12 | 9.23 | 0.00606726 | 27491.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51696.54 | 4.60 | 0.00525715 | 4.60 | 0.41145340 | 21.6116 | 21.11 | 0.00703498 | 21.11 | 0.00703498 | 45.2109 | 14599.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12744.740 | 0.000 | 1.026460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.3061 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 12744.74 | 8318.75 | 1.0000 | 1.23500269 | 1.026460 | 25.89 | 19.47 | 0.01154745 | 55451.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12744.74 | 33.90 | 0.01651378 | 25.10 | 0.20572670 | 20.0423 | 23.88 | 0.01030235 | 23.88 | 0.01030114 | 55.6375 | 11640.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27550.788 | 27550.788 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.026461 | 1.23500418 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27550.79 | 27550.79 | 1.0000 | 1.23500418 | 1.026461 | 12.41 | 9.35 | 0.00606387 | 27773.6 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27550.79 | 4.60 | 0.00525715 | 4.60 | 0.20572670 | 20.0423 | 21.11 | 0.00696272 | 21.11 | 0.00696272 | 44.7522 | 7539.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12972.730 | 0.000 | 1.044820 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2932 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 12972.73 | 8473.09 | 1.0000 | 1.25709284 | 1.044820 | 25.89 | 19.46 | 0.01154050 | 55427.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12972.73 | 33.90 | 0.01651378 | 25.10 | 0.20572670 | 19.6902 | 23.88 | 0.01029819 | 23.89 | 0.00939942 | 50.8316 | 11674.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27970.207 | 27970.207 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.044824 | 1.25709731 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27970.21 | 27970.21 | 1.0000 | 1.25709731 | 1.044824 | 12.52 | 9.42 | 0.00607830 | 27924.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27970.21 | 4.60 | 0.00525715 | 4.60 | 0.20572670 | 19.6901 | 21.11 | 0.00696854 | 21.11 | 0.00696854 | 44.7892 | 7638.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12899.620 | 0.000 | 1.038940 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2791 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 12899.62 | 8431.36 | 1.0000 | 1.25001822 | 1.038940 | 25.88 | 19.45 | 0.01153290 | 55402.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12899.62 | 33.90 | 0.01651378 | 25.10 | 0.20572670 | 19.8016 | 23.88 | 0.01029363 | 23.89 | 0.00937951 | 50.7249 | 11711.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27835.710 | 27835.710 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.038935 | 1.25001248 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27835.71 | 27835.71 | 1.0000 | 1.25001248 | 1.038935 | 12.60 | 9.47 | 0.00608898 | 28031.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27835.71 | 4.60 | 0.00525715 | 4.60 | 0.20572670 | 19.8017 | 21.11 | 0.00697381 | 21.11 | 0.00697381 | 44.8227 | 7709.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12878.380 | 0.000 | 1.037220 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.3182 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 12878.38 | 8400.84 | 1.0000 | 1.24794877 | 1.037220 | 25.90 | 19.47 | 0.01155396 | 55473.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12878.38 | 33.90 | 0.01651378 | 25.10 | 0.20572670 | 19.8344 | 23.88 | 0.01030629 | 23.89 | 0.00941160 | 50.8966 | 11608.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27796.629 | 27796.629 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.037225 | 1.24795424 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27796.63 | 27796.63 | 1.0000 | 1.24795424 | 1.037225 | 12.73 | 9.54 | 0.00610691 | 28206.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27796.63 | 4.60 | 0.00525715 | 4.60 | 0.20572670 | 19.8343 | 21.11 | 0.00698311 | 21.11 | 0.00698311 | 44.8818 | 7827.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21965.510 | 0.000 | 1.769100 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.7590 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 21965.51 | 14062.35 | 1.0000 | 2.12852256 | 1.769100 | 26.21 | 19.75 | 0.01179106 | 56404.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21965.51 | 33.90 | 0.01651378 | 25.10 | 0.41145340 | 23.2578 | 23.88 | 0.01035869 | 23.88 | 0.01035312 | 55.9121 | 20053.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 48618.776 | 48618.776 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.769102 | 2.12852527 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 48618.78 | 48618.78 | 1.0000 | 2.12852527 | 1.769102 | 12.18 | 9.27 | 0.00607816 | 27581.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48618.78 | 4.60 | 0.00525715 | 4.60 | 0.41145340 | 23.2578 | 21.11 | 0.00704426 | 21.11 | 0.00704426 | 45.2698 | 14700.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11509.675 | 0.000 | 0.926990 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.7762 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 11509.67 | 7341.80 | 1.0000 | 1.11532368 | 0.926990 | 26.11 | 19.73 | 0.01180030 | 56318.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11509.67 | 33.90 | 0.01651378 | 25.10 | 0.20572670 | 22.1930 | 23.88 | 0.01045477 | 23.88 | 0.01044958 | 56.4257 | 10507.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25278.829 | 25278.829 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.926989 | 1.11532290 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 25278.83 | 25278.83 | 1.0000 | 1.11532290 | 0.926989 | 12.94 | 9.67 | 0.00613604 | 28501.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25278.83 | 4.60 | 0.00525715 | 4.60 | 0.20572670 | 22.1930 | 21.11 | 0.00699583 | 21.11 | 0.00699583 | 44.9628 | 8035.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11442.675 | 0.000 | 0.921590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.8037 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 11442.67 | 7289.58 | 1.0000 | 1.10882658 | 0.921590 | 26.12 | 19.74 | 0.01181509 | 56369.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11442.67 | 33.90 | 0.01651378 | 25.10 | 0.20572670 | 22.3230 | 23.88 | 0.01046371 | 23.88 | 0.01045847 | 56.4729 | 10446.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25155.570 | 25155.570 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.921593 | 1.10883002 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 25155.57 | 25155.57 | 1.0000 | 1.10883002 | 0.921593 | 12.94 | 9.67 | 0.00613562 | 28496.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25155.57 | 4.60 | 0.00525715 | 4.60 | 0.20572670 | 22.3229 | 21.11 | 0.00699569 | 21.11 | 0.00699569 | 44.9619 | 8032.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11468.665 | 0.000 | 0.923690 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.7934 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 11468.67 | 7309.67 | 1.0000 | 1.11135323 | 0.923690 | 26.12 | 19.74 | 0.01180959 | 56350.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11468.67 | 33.90 | 0.01651378 | 25.10 | 0.20572670 | 22.2723 | 23.88 | 0.01046038 | 23.88 | 0.01045501 | 56.4545 | 10468.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25203.381 | 25203.381 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.923686 | 1.11134887 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 25203.38 | 25203.38 | 1.0000 | 1.11134887 | 0.923686 | 13.10 | 9.77 | 0.00615876 | 28720.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25203.38 | 4.60 | 0.00525715 | 4.60 | 0.20572670 | 22.2724 | 21.11 | 0.00700732 | 21.11 | 0.00700732 | 45.0358 | 8195.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12718.305 | 0.000 | 1.024330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.3107 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 12718.31 | 8284.46 | 1.0000 | 1.23243995 | 1.024330 | 25.82 | 19.44 | 0.01154990 | 55382.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12718.31 | 33.50 | 0.01651377 | 25.00 | 0.20572670 | 20.0840 | 23.89 | 0.01030241 | 23.88 | 0.01030241 | 55.6434 | 11605.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27502.236 | 27502.236 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.024332 | 1.23244275 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27502.24 | 27502.24 | 1.0000 | 1.23244275 | 1.024332 | 13.92 | 10.25 | 0.00627010 | 29826.2 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27502.24 | 4.60 | 0.00525715 | 4.60 | 0.20572670 | 20.0840 | 21.11 | 0.00705221 | 21.11 | 0.00705221 | 45.3214 | 9120.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 1.90 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.03 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.04 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.04 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.04 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 1.77 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.93 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.92 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.92 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.02 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 4398.17 | 1696.17 | 731.67 |
SMSTORE1 | 4349.83 | 1175.50 | 389.17 |
SMSTORE2 | 3324.83 | 1359.33 | 691.67 |
SMSTORE3 | 3299.83 | 1390.33 | 687.33 |
SMSTORE4 | 3269.83 | 1493.33 | 739.50 |
LGSTORE2 | 2934.00 | 1722.50 | 909.83 |
SMSTORE5 | 2888.50 | 1827.17 | 976.33 |
SMSTORE6 | 2878.50 | 1875.83 | 1008.50 |
SMSTORE7 | 2867.33 | 1922.00 | 1033.17 |
SMSTORE8 | 2887.00 | 1886.00 | 986.67 |
Facility | 4575.33 | 2668.67 | 1402.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 7.33 | 0.00 | 7.33 |
SMSTORE1 | 0.00 | 0.33 | 0.00 | 0.33 |
SMSTORE2 | 0.00 | 10.67 | 0.00 | 10.67 |
SMSTORE3 | 0.00 | 11.83 | 0.00 | 11.83 |
SMSTORE4 | 0.00 | 10.33 | 0.00 | 10.33 |
LGSTORE2 | 0.00 | 11.33 | 0.00 | 11.33 |
SMSTORE5 | 0.00 | 8.50 | 0.00 | 8.50 |
SMSTORE6 | 0.00 | 7.83 | 0.00 | 7.83 |
SMSTORE7 | 0.00 | 7.33 | 0.00 | 7.33 |
SMSTORE8 | 0.00 | 6.83 | 0.00 | 6.83 |
Facility | 0.00 | 24.83 | 0.00 | 24.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.02 | 30.00 | 1805.20 | 0.897 | 0.345 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.793 | 0.384 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.951 | 0.504 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.947 | 0.504 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.941 | 0.504 | 0.000 | 0.000 |
LGSTORE2 | 13.23 | 30.00 | 1805.20 | 0.909 | 0.471 | 0.000 | 0.000 |
SMSTORE5 | 6.62 | 15.00 | 902.60 | 0.913 | 0.537 | 0.000 | 0.000 |
SMSTORE6 | 6.62 | 15.00 | 902.60 | 0.910 | 0.537 | 0.000 | 0.000 |
SMSTORE7 | 6.62 | 15.00 | 902.60 | 0.908 | 0.537 | 0.000 | 0.000 |
SMSTORE8 | 6.62 | 15.00 | 902.60 | 0.916 | 0.553 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.02 | 30.00 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.78 | 15.00 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.78 | 15.00 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.78 | 15.00 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.23 | 30.00 | 1805.20 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.62 | 15.00 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.62 | 15.00 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.62 | 15.00 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.62 | 15.00 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1126.80 | 3078.07 | 01-JAN-07:30 | 123506.62 | 10-SEP-13:40 |
Electricity:Building | 562.66 | 1860.07 | 01-JAN-00:10 | 34891.92 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 127.94 | 349.95 | 01-JAN-00:10 | 6574.13 | 01-JAN-10:10 |
InteriorLights:Electricity | 433.94 | 1410.65 | 01-JAN-00:10 | 26802.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 101.59 | 275.05 | 01-JAN-00:10 | 5225.88 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 433.94 | 1410.65 | 01-JAN-00:10 | 26802.39 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 73.22 | 200.01 | 01-JAN-00:10 | 3762.66 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 60.04 | 162.55 | 01-JAN-00:10 | 3088.53 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 53.93 | 185.94 | 01-JAN-00:10 | 3495.47 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 43.46 | 148.49 | 01-JAN-00:10 | 2821.35 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 53.93 | 185.94 | 01-JAN-00:10 | 3495.47 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 43.46 | 148.49 | 01-JAN-00:10 | 2821.35 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 53.93 | 185.94 | 01-JAN-00:10 | 3495.47 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 43.46 | 148.49 | 01-JAN-00:10 | 2821.35 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 66.57 | 250.76 | 01-JAN-00:10 | 4689.57 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 47.31 | 175.86 | 01-JAN-00:10 | 3341.31 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 33.29 | 125.38 | 01-JAN-00:10 | 2344.79 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 23.66 | 87.93 | 01-JAN-00:10 | 1670.66 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 33.29 | 125.38 | 01-JAN-00:10 | 2344.79 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 23.66 | 87.93 | 01-JAN-00:10 | 1670.66 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 33.29 | 125.38 | 01-JAN-00:10 | 2344.79 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 23.66 | 87.93 | 01-JAN-00:10 | 1670.66 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 33.29 | 125.38 | 01-JAN-00:10 | 2344.79 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 23.66 | 87.93 | 01-JAN-00:10 | 1670.66 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
Electricity:Plant | 56.39 | 1218.00 | 03-JAN-07:10 | 11797.53 | 11-DEC-13:30 |
WaterSystems:Electricity | 56.39 | 1218.00 | 03-JAN-07:10 | 11797.53 | 11-DEC-13:30 |
Water Heater:WaterSystems:Electricity | 56.39 | 1218.00 | 03-JAN-07:10 | 11797.53 | 11-DEC-13:30 |
ElectricityPurchased:Facility | 1126.80 | 3078.07 | 01-JAN-07:30 | 123506.62 | 10-SEP-13:40 |
ElectricityPurchased:Plant | 1126.80 | 3078.07 | 01-JAN-07:30 | 123506.62 | 10-SEP-13:40 |
Cogeneration:ElectricityPurchased | 1126.80 | 3078.07 | 01-JAN-07:30 | 123506.62 | 10-SEP-13:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1126.80 | 3078.07 | 01-JAN-07:30 | 123506.62 | 10-SEP-13:40 |
ElectricityNet:Plant | 1126.80 | 3078.07 | 01-JAN-07:30 | 123506.62 | 10-SEP-13:40 |
Cogeneration:ElectricityNet | 1126.80 | 3078.07 | 01-JAN-07:30 | 123506.62 | 10-SEP-13:40 |
Electricity:HVAC | 443.34 | 0.00 | 01-JAN-00:10 | 83262.39 | 10-SEP-13:30 |
Fans:Electricity | 95.45 | 0.00 | 01-JAN-00:10 | 11623.24 | 10-SEP-12:50 |
General:Fans:Electricity | 95.45 | 0.00 | 01-JAN-00:10 | 11623.24 | 10-SEP-12:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 347.89 | 0.00 | 01-JAN-00:10 | 71682.25 | 10-SEP-13:30 |
ExteriorLights:Electricity | 64.41 | 0.00 | 01-JAN-07:30 | 4954.41 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 64.41 | 0.00 | 01-JAN-07:30 | 4954.41 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 18.52 | 0.00 | 01-JAN-00:10 | 95357.07 | 05-FEB-10:10 |
Gas:HVAC | 18.52 | 0.00 | 01-JAN-00:10 | 95357.07 | 05-FEB-10:10 |
Heating:Gas | 18.52 | 0.00 | 01-JAN-00:10 | 95357.07 | 05-FEB-10:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2210.38 | 0.00 | 01-JAN-00:10 | 396284.87 | 10-SEP-13:00 |
EnergyTransfer:Building | 745.62 | 0.00 | 01-JAN-00:10 | 112736.56 | 10-SEP-14:10 |
EnergyTransfer:Zone:LGSTORE1 | 156.86 | 0.00 | 01-JAN-00:10 | 18176.15 | 10-SEP-14:00 |
Heating:EnergyTransfer | 10.45 | 0.00 | 01-JAN-00:10 | 36198.29 | 06-FEB-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 1.08 | 0.00 | 01-JAN-00:10 | 11153.10 | 05-FEB-09:10 |
Cooling:EnergyTransfer | 735.16 | 0.00 | 01-JAN-00:10 | 112736.56 | 10-SEP-14:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 155.78 | 0.00 | 01-JAN-00:10 | 18176.15 | 10-SEP-14:00 |
EnergyTransfer:Zone:SMSTORE1 | 85.69 | 0.00 | 01-JAN-00:10 | 9665.97 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.55 | 0.00 | 01-JAN-00:10 | 1936.12 | 11-MAR-12:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 85.15 | 0.00 | 01-JAN-00:10 | 9665.97 | 10-SEP-14:00 |
EnergyTransfer:Zone:SMSTORE2 | 66.08 | 0.00 | 01-JAN-00:10 | 9834.63 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.02 | 0.00 | 01-JAN-00:10 | 3019.31 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 65.06 | 0.00 | 01-JAN-00:10 | 9834.63 | 10-SEP-14:00 |
EnergyTransfer:Zone:SMSTORE3 | 65.79 | 0.00 | 01-JAN-00:10 | 9904.83 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.01 | 0.00 | 01-JAN-00:10 | 3757.70 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 64.78 | 0.00 | 01-JAN-00:10 | 9904.83 | 10-SEP-14:00 |
EnergyTransfer:Zone:SMSTORE4 | 63.73 | 0.00 | 01-JAN-00:10 | 9816.79 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.06 | 0.00 | 01-JAN-00:10 | 4392.30 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 62.67 | 0.00 | 01-JAN-00:10 | 9816.79 | 10-SEP-14:00 |
EnergyTransfer:Zone:LGSTORE2 | 100.91 | 0.00 | 01-JAN-00:10 | 17445.59 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.58 | 0.00 | 01-JAN-00:10 | 7581.82 | 13-MAR-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 99.32 | 0.00 | 01-JAN-00:10 | 17445.59 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE5 | 51.66 | 0.00 | 01-JAN-00:10 | 9256.93 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.91 | 0.00 | 01-JAN-00:10 | 4241.96 | 10-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 50.74 | 0.00 | 01-JAN-00:10 | 9256.93 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 50.96 | 0.00 | 01-JAN-00:10 | 9213.83 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.93 | 0.00 | 01-JAN-00:10 | 4434.05 | 10-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 50.03 | 0.00 | 01-JAN-00:10 | 9213.83 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 50.28 | 0.00 | 01-JAN-00:10 | 9281.88 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 1.00 | 0.00 | 01-JAN-00:10 | 5627.67 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 49.28 | 0.00 | 01-JAN-00:10 | 9281.88 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE8 | 53.66 | 0.00 | 01-JAN-00:10 | 10444.41 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 1.31 | 0.00 | 01-JAN-00:10 | 7892.55 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 52.35 | 0.00 | 01-JAN-00:10 | 10444.41 | 10-SEP-14:10 |
EnergyTransfer:HVAC | 1464.76 | 0.00 | 01-JAN-00:10 | 285508.75 | 10-SEP-13:00 |
HeatingCoils:EnergyTransfer | 14.81 | 0.00 | 01-JAN-00:10 | 76285.65 | 05-FEB-10:10 |
CoolingCoils:EnergyTransfer | 1449.95 | 0.00 | 01-JAN-00:10 | 285508.75 | 10-SEP-13:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 1.084 | -155.774 | 0.000 | 0.000 | 12.571 | 101.585 | 26.357 | 17.388 | 0.000 | 14.111 | 0.002 | 0.000 | -5.223 | 0.000 | -10.711 | -1.388 |
SMSTORE1 | 0.000 | 0.000 | 0.545 | -85.147 | 0.000 | 0.000 | 6.249 | 60.038 | 13.179 | 8.662 | 0.000 | 7.920 | 0.000 | 0.000 | -2.706 | 0.000 | -5.571 | -3.167 |
SMSTORE2 | 0.000 | 0.000 | 1.017 | -65.057 | 0.000 | 0.000 | 3.772 | 43.461 | 10.467 | 8.612 | 0.000 | 7.799 | 0.002 | 0.000 | -2.800 | 0.000 | -5.675 | -1.596 |
SMSTORE3 | 0.000 | 0.000 | 1.013 | -64.779 | 0.000 | 0.000 | 3.776 | 43.461 | 10.467 | 8.617 | 0.000 | 7.797 | 0.001 | 0.000 | -2.785 | 0.000 | -5.636 | -1.930 |
SMSTORE4 | 0.000 | 0.000 | 1.061 | -62.669 | 0.000 | 0.000 | 3.781 | 43.461 | 10.467 | 8.639 | 0.000 | 7.800 | 0.000 | 0.000 | -2.736 | 0.000 | -5.562 | -4.242 |
LGSTORE2 | 0.000 | 0.000 | 1.582 | -99.322 | 0.000 | 0.000 | 13.014 | 47.311 | 19.261 | 17.349 | 0.000 | 13.636 | 2.088 | 0.000 | -5.181 | 0.000 | -9.738 | -0.000 |
SMSTORE5 | 0.000 | 0.000 | 0.911 | -50.743 | 0.000 | 0.000 | 6.513 | 23.655 | 9.631 | 8.690 | 0.000 | 7.781 | 1.493 | 0.000 | -2.553 | 0.000 | -5.378 | -0.002 |
SMSTORE6 | 0.000 | 0.000 | 0.933 | -50.025 | 0.000 | 0.000 | 6.517 | 23.655 | 9.631 | 8.701 | 0.000 | 7.783 | 0.689 | 0.000 | -2.535 | 0.000 | -5.349 | -0.001 |
SMSTORE7 | 0.000 | 0.000 | 1.001 | -49.279 | 0.000 | 0.000 | 6.523 | 23.655 | 9.631 | 8.713 | 0.000 | 7.785 | 0.000 | 0.000 | -2.507 | 0.000 | -5.294 | -0.227 |
SMSTORE8 | 0.000 | 0.000 | 1.307 | -52.349 | 0.000 | 0.000 | 6.529 | 23.655 | 9.631 | 8.709 | 0.000 | 7.991 | 3.392 | 0.000 | -2.426 | 0.000 | -6.439 | -0.000 |
Total Facility | 0.000 | 0.000 | 10.454 | -735.144 | 0.000 | 0.000 | 69.244 | 433.937 | 128.721 | 104.079 | 0.000 | 90.403 | 7.667 | 0.000 | -31.452 | 0.000 | -65.354 | -12.553 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -42212.95 | 0.00 | 0.00 | 89.02 | 2750.46 | 749.03 | 320.70 | 0.00 | 0.00 | 38639.94 | 0.00 | -0.00 | 0.00 | -336.21 | 0.00 |
SMSTORE1 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -23155.64 | 0.00 | 0.00 | 44.06 | 1625.54 | 374.52 | 158.18 | 0.00 | 0.00 | 21129.11 | 0.00 | -0.00 | 0.00 | -175.77 | 0.00 |
SMSTORE2 | 17-OCT-07:02 | 0.00 | 0.00 | 0.00 | -25682.63 | 0.00 | 0.00 | 45.55 | 1484.92 | 374.52 | 0.00 | 0.00 | 0.00 | 24347.53 | 0.00 | -166.25 | 0.00 | -403.63 | 0.00 |
SMSTORE3 | 17-OCT-07:02 | 0.00 | 0.00 | 0.00 | -25585.71 | 0.00 | 0.00 | 45.41 | 1484.92 | 374.52 | 0.00 | 0.00 | 0.00 | 24253.48 | 0.00 | -167.19 | 0.00 | -405.42 | 0.00 |
SMSTORE4 | 17-OCT-07:02 | 0.00 | 0.00 | 0.00 | -25443.01 | 0.00 | 0.00 | 45.77 | 1484.92 | 374.52 | 0.00 | 0.00 | 0.00 | 24104.63 | 0.00 | -165.22 | 0.00 | -401.61 | 0.00 |
LGSTORE2 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -38682.40 | 0.00 | 0.00 | 198.85 | 1758.59 | 749.03 | 322.91 | 0.00 | 0.00 | 35954.31 | 0.00 | -0.00 | 0.00 | -301.29 | 0.00 |
SMSTORE5 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -20134.75 | 0.00 | 0.00 | 100.25 | 879.29 | 374.52 | 162.55 | 0.00 | 0.00 | 18782.25 | 0.00 | -0.00 | 0.00 | -164.12 | 0.00 |
SMSTORE6 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -19988.70 | 0.00 | 0.00 | 100.51 | 879.29 | 374.52 | 163.27 | 0.00 | 0.00 | 18634.11 | 0.00 | -0.00 | 0.00 | -163.01 | 0.00 |
SMSTORE7 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -20004.13 | 0.00 | 0.00 | 100.75 | 879.29 | 374.52 | 163.46 | 0.00 | 0.00 | 18647.81 | 0.00 | -0.00 | 0.00 | -161.70 | 0.00 |
SMSTORE8 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -22299.55 | 0.00 | 0.00 | 100.64 | 879.29 | 374.52 | 162.96 | 0.00 | 0.00 | 20964.74 | 0.00 | -0.00 | 0.00 | -182.60 | 0.00 |
Total Facility | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | -197463.83 | 0.00 | 0.00 | 1049.29 | 18115.80 | 5393.02 | 1986.78 | 0.00 | 0.00 | 172757.31 | 0.00 | 0.00 | 0.00 | -1838.37 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-FEB-09:01 | 0.00 | 0.00 | 43491.47 | 0.00 | 0.00 | 0.00 | 128.12 | 2750.46 | 749.03 | 1054.72 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1175.49 | -46998.31 |
SMSTORE1 | 05-FEB-09:02 | 0.00 | 0.00 | 3627.71 | 0.00 | 0.00 | 0.00 | 62.46 | 1625.54 | 374.52 | 445.71 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1021.14 | -5114.80 |
SMSTORE2 | 05-FEB-09:02 | 0.00 | 0.00 | 9381.60 | 0.00 | 0.00 | 0.00 | 63.70 | 1484.92 | 374.52 | 453.66 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1019.74 | -10738.65 |
SMSTORE3 | 05-FEB-09:02 | 0.00 | 0.00 | 11905.18 | 0.00 | 0.00 | 0.00 | 64.24 | 1484.92 | 374.52 | 458.13 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1019.07 | -13267.90 |
SMSTORE4 | 05-FEB-09:02 | 0.00 | 0.00 | 14416.80 | 0.00 | 0.00 | 0.00 | 64.77 | 1484.92 | 374.52 | 462.35 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1018.36 | -15784.98 |
LGSTORE2 | 12-MAR-09:01 | 0.00 | 0.00 | 44308.75 | 0.00 | 0.00 | 0.00 | 286.22 | 1758.59 | 749.03 | 579.83 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -717.14 | -46965.28 |
SMSTORE5 | 12-MAR-09:01 | 0.00 | 0.00 | 23138.11 | 0.00 | 0.00 | 0.00 | 143.71 | 879.29 | 374.52 | 290.96 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -403.56 | -24423.02 |
SMSTORE6 | 12-MAR-09:01 | 0.00 | 0.00 | 23041.30 | 0.00 | 0.00 | 0.00 | 144.21 | 879.29 | 374.52 | 292.87 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -399.86 | -24332.33 |
SMSTORE7 | 12-MAR-09:01 | 0.00 | 0.00 | 23154.74 | 0.00 | 0.00 | 0.00 | 145.91 | 879.29 | 374.52 | 298.83 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -388.18 | -24465.10 |
SMSTORE8 | 12-MAR-09:01 | 0.00 | 0.00 | 25494.03 | 0.00 | 0.00 | 0.00 | 150.08 | 879.29 | 374.52 | 314.14 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -398.37 | -26813.69 |
Total Facility | 06-FEB-09:01 | -3355.51 | 3355.51 | 178000.70 | -3355.51 | 0.00 | 0.00 | 1436.46 | 18115.80 | 5393.02 | 6361.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7066.39 | -198885.19 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9039 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.9039 | 0.2161 | 1.0000 | 0.4115 | 0.2161 | ||
PSZ-AC_2:2 | 1.0265 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0265 | 0.2004 | 1.0000 | 0.2057 | 0.2004 | ||
PSZ-AC_3:3 | 1.0448 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0448 | 0.1969 | 1.0000 | 0.2057 | 0.1969 | ||
PSZ-AC_4:4 | 1.0389 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0389 | 0.1980 | 1.0000 | 0.2057 | 0.1980 | ||
PSZ-AC_5:5 | 1.0372 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0372 | 0.1983 | 1.0000 | 0.2057 | 0.1983 | ||
PSZ-AC_6:6 | 1.7691 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.7691 | 0.2326 | 1.0000 | 0.4115 | 0.2326 | ||
PSZ-AC_7:7 | 0.9270 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9270 | 0.2219 | 1.0000 | 0.2057 | 0.2219 | ||
PSZ-AC_8:8 | 0.9216 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9216 | 0.2232 | 1.0000 | 0.2057 | 0.2232 | ||
PSZ-AC_9:9 | 0.9237 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9237 | 0.2227 | 1.0000 | 0.2057 | 0.2227 | ||
PSZ-AC_10:10 | 1.0243 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0243 | 0.2008 | 1.0000 | 0.2057 | 0.2008 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9039 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.9039 | 1.0000 | 1.0000 | 0.4115 | 0.2161 | ||
PSZ-AC_2:2 | 1.0265 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0265 | 1.0000 | 1.0000 | 0.2057 | 0.2004 | ||
PSZ-AC_3:3 | 1.0448 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0448 | 1.0000 | 1.0000 | 0.2057 | 0.1969 | ||
PSZ-AC_4:4 | 1.0389 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0389 | 1.0000 | 1.0000 | 0.2057 | 0.1980 | ||
PSZ-AC_5:5 | 1.0372 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0372 | 1.0000 | 1.0000 | 0.2057 | 0.1983 | ||
PSZ-AC_6:6 | 1.7691 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.7691 | 1.0000 | 1.0000 | 0.4115 | 0.2326 | ||
PSZ-AC_7:7 | 0.9270 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9270 | 1.0000 | 1.0000 | 0.2057 | 0.2219 | ||
PSZ-AC_8:8 | 0.9216 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9216 | 1.0000 | 1.0000 | 0.2057 | 0.2232 | ||
PSZ-AC_9:9 | 0.9237 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9237 | 1.0000 | 1.0000 | 0.2057 | 0.2227 | ||
PSZ-AC_10:10 | 1.0243 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 1.0243 | 1.0000 | 1.0000 | 0.2057 | 0.2008 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.9039 | 1.9039 | 1.9039 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.0265 | 1.0265 | 1.0265 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.0448 | 1.0448 | 1.0448 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.0389 | 1.0389 | 1.0389 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.0372 | 1.0372 | 1.0372 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.7691 | 1.7691 | 1.7691 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.9270 | 0.9270 | 0.9270 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.9216 | 0.9216 | 0.9216 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.9237 | 0.9237 | 0.9237 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0243 | 1.0243 | 1.0243 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9039 | 1.9039 | 1.9039 | 1.9039 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0265 | 1.0265 | 1.0265 | 1.0265 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0448 | 1.0448 | 1.0448 | 1.0448 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0389 | 1.0389 | 1.0389 | 1.0389 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0372 | 1.0372 | 1.0372 | 1.0372 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7691 | 1.7691 | 1.7691 | 1.7691 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9270 | 0.9270 | 0.9270 | 0.9270 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9216 | 0.9216 | 0.9216 | 0.9216 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9237 | 0.9237 | 0.9237 | 0.9237 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0243 | 1.0243 | 1.0243 | 1.0243 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.9039 | 1.9039 | 1.9039 | 0.4115 | 0.5443 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 1.0265 | 1.0265 | 1.0265 | 0.2057 | 0.5270 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 1.0448 | 1.0448 | 1.0448 | 0.2057 | 0.5202 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 1.0389 | 1.0389 | 1.0389 | 0.2057 | 0.5154 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 1.0372 | 1.0372 | 1.0372 | 0.2057 | 0.5077 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.7691 | 1.7691 | 1.7691 | 0.4115 | 0.5406 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.9270 | 0.9270 | 0.9270 | 0.2057 | 0.4945 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.9216 | 0.9216 | 0.9216 | 0.2057 | 0.4947 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.9237 | 0.9237 | 0.9237 | 0.2057 | 0.4848 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 1.0243 | 1.0243 | 1.0243 | 0.2057 | 0.4357 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9039 | 1.9039 | 1.9039 | 1.9039 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0265 | 1.0265 | 1.0265 | 1.0265 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0448 | 1.0448 | 1.0448 | 1.0448 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0389 | 1.0389 | 1.0389 | 1.0389 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0372 | 1.0372 | 1.0372 | 1.0372 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7691 | 1.7691 | 1.7691 | 1.7691 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9270 | 0.9270 | 0.9270 | 0.9270 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9216 | 0.9216 | 0.9216 | 0.9216 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9237 | 0.9237 | 0.9237 | 0.9237 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0243 | 1.0243 | 1.0243 | 1.0243 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:20:39
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 24.83 |
Number of hours not met | 24.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 18.52 | 95357.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 347.89 | 71682.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 433.94 | 26802.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 64.41 | 4954.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 95.45 | 11623.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 56.39 | 11797.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1126.80 |
Natural Gas | 0.00 | 18.52 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1145.32 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 207.59 |
Space Heating | 0.00 |
Space Cooling | 166.43 |
Fans (All) | 45.66 |
Service Water Heating | 26.98 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 539.06 |
Subtotal | 539.06 |
Natural Gas [MJ/m2] | |
Space Heating | 8.86 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 8.86 |
Subtotal | 8.86 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 37.89 |
Space Heating | 1.62 |
Space Cooling | 30.38 |
Fans (All) | 8.33 |
Service Water Heating | 4.92 |
Receptacle Equipment | 11.24 |
Miscellaneous | 5.62 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5131. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.511668E+10 |
February | 0.000 | 0.523286E+10 |
March | 0.000 | 0.370254E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 608893.155 |
December | 0.000 | 0.446393E+10 |
Annual Sum or Average | 0.185166E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.523286E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.511668E+10 |
February | 0.000 | 0.523286E+10 |
March | 0.000 | 0.370254E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 608893.155 |
December | 0.000 | 0.446393E+10 |
Annual Sum or Average | 0.185166E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.523286E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.511668E+10 |
February | 0.000 | 0.523286E+10 |
March | 0.000 | 0.370254E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 608893.155 |
December | 0.000 | 0.446393E+10 |
Annual Sum or Average | 0.185166E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.523286E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.511668E+10 |
February | 0.000 | 0.523286E+10 |
March | 0.000 | 0.370254E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 608893.155 |
December | 0.000 | 0.446393E+10 |
Annual Sum or Average | 0.185166E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.523286E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.511668E+10 |
February | 0.000 | 0.523286E+10 |
March | 0.000 | 0.370254E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 608893.155 |
December | 0.000 | 0.446393E+10 |
Annual Sum or Average | 0.185166E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.523286E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.511668E+10 |
February | 0.000 | 0.523286E+10 |
March | 0.000 | 0.370254E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 608893.155 |
December | 0.000 | 0.446393E+10 |
Annual Sum or Average | 0.185166E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.523286E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.511668E+10 |
February | 0.000 | 0.523286E+10 |
March | 0.000 | 0.370254E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 608893.155 |
December | 0.000 | 0.446393E+10 |
Annual Sum or Average | 0.185166E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.523286E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.511668E+10 |
February | 0.000 | 0.523286E+10 |
March | 0.000 | 0.370254E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 608893.155 |
December | 0.000 | 0.446393E+10 |
Annual Sum or Average | 0.185166E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.523286E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.511668E+10 |
February | 0.000 | 0.523286E+10 |
March | 0.000 | 0.370254E+10 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 608893.155 |
December | 0.000 | 0.446393E+10 |
Annual Sum or Average | 0.185166E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.523286E+10 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.771060E+10 | 28252.55 | 02-JAN-09:02 | 18.33 | 16.36 | 0.677695E+09 | 899.02 | 15-JAN-17:30 | 19.15 | 13.62 |
February | 0.714208E+10 | 29908.79 | 28-FEB-09:02 | 20.08 | 18.59 | 0.636584E+09 | 899.03 | 20-FEB-18:00 | 18.80 | 17.36 |
March | 0.810927E+10 | 28260.53 | 30-MAR-08:62 | 21.78 | 19.48 | 0.709088E+09 | 899.01 | 04-MAR-13:00 | 25.50 | 14.62 |
April | 0.105802E+11 | 28672.83 | 25-APR-08:62 | 22.07 | 18.95 | 0.725965E+09 | 899.06 | 16-APR-17:10 | 19.30 | 13.52 |
May | 0.159929E+11 | 29186.43 | 07-MAY-07:02 | 24.60 | 22.14 | 0.748353E+09 | 898.95 | 07-MAY-17:40 | 32.97 | 22.86 |
June | 0.167174E+11 | 29863.30 | 11-JUN-07:02 | 23.58 | 20.40 | 0.723075E+09 | 898.98 | 11-JUN-16:30 | 32.75 | 21.52 |
July | 0.177533E+11 | 29386.59 | 09-JUL-07:01 | 28.48 | 25.78 | 0.754706E+09 | 898.92 | 23-JUL-16:30 | 31.95 | 26.58 |
August | 0.184967E+11 | 31599.39 | 20-AUG-07:02 | 24.17 | 22.65 | 0.744392E+09 | 898.95 | 27-AUG-17:00 | 31.00 | 24.50 |
September | 0.166960E+11 | 29194.05 | 22-SEP-08:61 | 23.58 | 20.80 | 0.729221E+09 | 898.93 | 03-SEP-16:30 | 31.65 | 24.78 |
October | 0.165132E+11 | 42230.16 | 26-OCT-08:61 | 21.18 | 12.92 | 0.752431E+09 | 899.03 | 28-OCT-12:39 | 20.33 | 13.36 |
November | 0.109541E+11 | 31444.89 | 06-NOV-09:02 | 22.47 | 19.37 | 0.723518E+09 | 899.04 | 26-NOV-17:19 | 18.10 | 14.44 |
December | 0.911048E+10 | 33808.51 | 17-DEC-08:62 | 19.83 | 15.87 | 0.715666E+09 | 899.03 | 17-DEC-13:09 | 19.00 | 12.76 |
Annual Sum or Average | 0.155776E+12 | 0.864069E+10 | ||||||||
Minimum of Months | 0.714208E+10 | 28252.55 | 18.33 | 12.92 | 0.636584E+09 | 898.92 | 18.10 | 12.76 | ||
Maximum of Months | 0.184967E+11 | 42230.16 | 28.48 | 25.78 | 0.754706E+09 | 899.06 | 32.97 | 26.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.386708E+10 | 17445.83 | 02-JAN-09:02 | 18.33 | 16.36 | 0.353492E+09 | 449.51 | 15-JAN-17:30 | 19.15 | 13.62 |
February | 0.389797E+10 | 17716.88 | 28-FEB-09:02 | 20.08 | 18.59 | 0.326299E+09 | 449.51 | 19-FEB-17:10 | 20.05 | 14.05 |
March | 0.457783E+10 | 17459.24 | 30-MAR-08:62 | 21.78 | 19.48 | 0.361473E+09 | 449.50 | 04-MAR-13:00 | 25.50 | 14.62 |
April | 0.614984E+10 | 17221.58 | 24-APR-08:62 | 19.50 | 19.50 | 0.362813E+09 | 449.53 | 16-APR-16:00 | 19.40 | 13.56 |
May | 0.893120E+10 | 18334.61 | 07-MAY-07:02 | 24.60 | 22.14 | 0.374241E+09 | 449.47 | 07-MAY-17:40 | 32.97 | 22.86 |
June | 0.919843E+10 | 18088.89 | 11-JUN-07:02 | 23.58 | 20.40 | 0.361587E+09 | 449.49 | 11-JUN-16:30 | 32.75 | 21.52 |
July | 0.968987E+10 | 18235.75 | 09-JUL-07:01 | 28.48 | 25.78 | 0.377381E+09 | 449.46 | 30-JUL-16:30 | 27.20 | 24.52 |
August | 0.989068E+10 | 18874.05 | 20-AUG-07:02 | 24.17 | 22.65 | 0.372216E+09 | 449.46 | 27-AUG-16:30 | 33.00 | 23.76 |
September | 0.899027E+10 | 17733.11 | 03-SEP-07:02 | 26.78 | 24.08 | 0.364631E+09 | 449.46 | 03-SEP-16:30 | 31.65 | 24.78 |
October | 0.893668E+10 | 23163.64 | 26-OCT-08:61 | 21.18 | 12.92 | 0.376122E+09 | 449.52 | 28-OCT-12:30 | 20.00 | 13.24 |
November | 0.610072E+10 | 18630.45 | 06-NOV-09:02 | 22.47 | 19.37 | 0.362534E+09 | 449.51 | 26-NOV-17:19 | 18.10 | 14.44 |
December | 0.491830E+10 | 19036.83 | 17-DEC-08:62 | 19.83 | 15.87 | 0.364305E+09 | 449.52 | 17-DEC-13:09 | 19.00 | 12.76 |
Annual Sum or Average | 0.851489E+11 | 0.435710E+10 | ||||||||
Minimum of Months | 0.386708E+10 | 17221.58 | 18.33 | 12.92 | 0.326299E+09 | 449.46 | 18.10 | 12.76 | ||
Maximum of Months | 0.989068E+10 | 23163.64 | 28.48 | 25.78 | 0.377381E+09 | 449.53 | 33.00 | 24.78 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298905E+10 | 20425.00 | 02-JAN-08:62 | 15.50 | 14.72 | 0.203959E+09 | 449.50 | 28-JAN-13:30 | 21.00 | 13.45 |
February | 0.290480E+10 | 19113.54 | 03-FEB-08:62 | 16.00 | 15.24 | 0.192401E+09 | 449.47 | 11-FEB-13:00 | 22.70 | 17.76 |
March | 0.340893E+10 | 20930.22 | 01-MAR-08:62 | 13.77 | 13.12 | 0.219878E+09 | 449.50 | 04-MAR-13:00 | 25.50 | 14.62 |
April | 0.448649E+10 | 16925.96 | 25-APR-07:02 | 20.27 | 17.95 | 0.218737E+09 | 449.51 | 08-APR-12:50 | 20.13 | 18.10 |
May | 0.693114E+10 | 16285.66 | 12-MAY-07:01 | 23.98 | 20.88 | 0.227479E+09 | 449.45 | 13-MAY-12:09 | 24.08 | 22.01 |
June | 0.723267E+10 | 15953.16 | 14-JUN-07:01 | 26.88 | 23.47 | 0.222661E+09 | 449.41 | 10-JUN-12:00 | 32.20 | 21.33 |
July | 0.744788E+10 | 13779.14 | 19-JUL-07:01 | 28.07 | 25.39 | 0.224348E+09 | 449.37 | 15-JUL-12:00 | 28.30 | 23.96 |
August | 0.780369E+10 | 15915.12 | 31-AUG-07:01 | 25.45 | 23.80 | 0.230508E+09 | 449.41 | 12-AUG-12:09 | 30.08 | 23.82 |
September | 0.686175E+10 | 15908.62 | 22-SEP-07:01 | 21.97 | 19.92 | 0.219343E+09 | 449.35 | 30-SEP-12:09 | 29.87 | 24.57 |
October | 0.682828E+10 | 25696.54 | 17-OCT-07:02 | 15.17 | 9.87 | 0.224342E+09 | 449.51 | 28-OCT-12:30 | 20.00 | 13.24 |
November | 0.451769E+10 | 19468.94 | 05-NOV-08:62 | 18.17 | 15.30 | 0.215569E+09 | 449.49 | 25-NOV-13:00 | 20.00 | 14.20 |
December | 0.364714E+10 | 20698.00 | 17-DEC-09:02 | 19.00 | 14.28 | 0.211557E+09 | 449.51 | 23-DEC-13:00 | 21.00 | 14.47 |
Annual Sum or Average | 0.650595E+11 | 0.261078E+10 | ||||||||
Minimum of Months | 0.290480E+10 | 13779.14 | 13.77 | 9.87 | 0.192401E+09 | 449.35 | 20.00 | 13.24 | ||
Maximum of Months | 0.780369E+10 | 25696.54 | 28.07 | 25.39 | 0.230508E+09 | 449.51 | 32.20 | 24.57 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286433E+10 | 20314.85 | 02-JAN-08:62 | 15.50 | 14.72 | 0.202681E+09 | 449.50 | 28-JAN-13:39 | 21.33 | 13.51 |
February | 0.280297E+10 | 18979.19 | 03-FEB-08:62 | 16.00 | 15.24 | 0.191690E+09 | 449.47 | 11-FEB-13:00 | 22.70 | 17.76 |
March | 0.331781E+10 | 20513.69 | 01-MAR-08:62 | 13.77 | 13.12 | 0.219360E+09 | 449.50 | 04-MAR-13:00 | 25.50 | 14.62 |
April | 0.444569E+10 | 16839.80 | 25-APR-07:02 | 20.27 | 17.95 | 0.218711E+09 | 449.51 | 08-APR-12:50 | 20.13 | 18.10 |
May | 0.695645E+10 | 16218.68 | 12-MAY-07:01 | 23.98 | 20.88 | 0.227481E+09 | 449.45 | 13-MAY-12:09 | 24.08 | 22.01 |
June | 0.726768E+10 | 15880.95 | 14-JUN-07:01 | 26.88 | 23.47 | 0.222664E+09 | 449.42 | 10-JUN-12:00 | 32.20 | 21.33 |
July | 0.749939E+10 | 13724.25 | 19-JUL-07:01 | 28.07 | 25.39 | 0.224351E+09 | 449.37 | 15-JUL-12:00 | 28.30 | 23.96 |
August | 0.784619E+10 | 15844.94 | 31-AUG-07:01 | 25.45 | 23.80 | 0.230510E+09 | 449.37 | 12-AUG-12:09 | 30.08 | 23.82 |
September | 0.690119E+10 | 15842.43 | 22-SEP-07:01 | 21.97 | 19.92 | 0.219345E+09 | 449.35 | 30-SEP-12:09 | 29.87 | 24.57 |
October | 0.685635E+10 | 25599.48 | 17-OCT-07:02 | 15.17 | 9.87 | 0.224342E+09 | 449.51 | 28-OCT-12:39 | 20.33 | 13.36 |
November | 0.446622E+10 | 19385.78 | 05-NOV-08:62 | 18.17 | 15.30 | 0.215501E+09 | 449.49 | 25-NOV-13:00 | 20.00 | 14.20 |
December | 0.355736E+10 | 20595.27 | 17-DEC-09:02 | 19.00 | 14.28 | 0.211010E+09 | 449.50 | 23-DEC-13:00 | 21.00 | 14.47 |
Annual Sum or Average | 0.647816E+11 | 0.260764E+10 | ||||||||
Minimum of Months | 0.280297E+10 | 13724.25 | 13.77 | 9.87 | 0.191690E+09 | 449.35 | 20.00 | 13.36 | ||
Maximum of Months | 0.784619E+10 | 25599.48 | 28.07 | 25.39 | 0.230510E+09 | 449.51 | 32.20 | 24.57 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265721E+10 | 20175.73 | 02-JAN-08:62 | 15.50 | 14.72 | 0.200881E+09 | 449.50 | 28-JAN-13:50 | 21.67 | 13.56 |
February | 0.260696E+10 | 18790.35 | 03-FEB-08:62 | 16.00 | 15.24 | 0.190512E+09 | 449.47 | 11-FEB-13:00 | 22.70 | 17.76 |
March | 0.310462E+10 | 18542.20 | 01-MAR-08:62 | 13.77 | 13.12 | 0.218339E+09 | 449.51 | 04-MAR-13:00 | 25.50 | 14.62 |
April | 0.424393E+10 | 16672.25 | 25-APR-07:02 | 20.27 | 17.95 | 0.218631E+09 | 449.50 | 08-APR-12:50 | 20.13 | 18.10 |
May | 0.679155E+10 | 16072.12 | 12-MAY-07:01 | 23.98 | 20.88 | 0.227458E+09 | 449.45 | 13-MAY-12:09 | 24.08 | 22.01 |
June | 0.711414E+10 | 15800.45 | 12-JUN-07:01 | 25.18 | 21.23 | 0.222642E+09 | 449.41 | 10-JUN-12:00 | 32.20 | 21.33 |
July | 0.736044E+10 | 13621.85 | 19-JUL-07:01 | 28.07 | 25.39 | 0.224334E+09 | 449.37 | 15-JUL-12:00 | 28.30 | 23.96 |
August | 0.769853E+10 | 15714.58 | 31-AUG-07:01 | 25.45 | 23.80 | 0.230492E+09 | 449.41 | 12-AUG-12:09 | 30.08 | 23.82 |
September | 0.676110E+10 | 15675.98 | 22-SEP-07:01 | 21.97 | 19.92 | 0.219326E+09 | 449.35 | 30-SEP-12:09 | 29.87 | 24.57 |
October | 0.670193E+10 | 25456.72 | 17-OCT-07:02 | 15.17 | 9.87 | 0.224312E+09 | 449.51 | 28-OCT-12:39 | 20.33 | 13.36 |
November | 0.427518E+10 | 19245.80 | 05-NOV-08:62 | 18.17 | 15.30 | 0.215305E+09 | 449.49 | 25-NOV-13:00 | 20.00 | 14.20 |
December | 0.335589E+10 | 20441.94 | 17-DEC-09:02 | 19.00 | 14.28 | 0.210117E+09 | 449.50 | 23-DEC-13:00 | 21.00 | 14.47 |
Annual Sum or Average | 0.626715E+11 | 0.260235E+10 | ||||||||
Minimum of Months | 0.260696E+10 | 13621.85 | 13.77 | 9.87 | 0.190512E+09 | 449.35 | 20.00 | 13.36 | ||
Maximum of Months | 0.769853E+10 | 25456.72 | 28.07 | 25.39 | 0.230492E+09 | 449.51 | 32.20 | 24.57 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388847E+10 | 32000.65 | 01-JAN-10:02 | 20.33 | 16.40 | 0.674031E+09 | 1198.66 | 14-JAN-15:50 | 19.60 | 12.65 |
February | 0.380513E+10 | 27413.85 | 28-FEB-09:02 | 20.08 | 18.59 | 0.642393E+09 | 1198.63 | 11-FEB-15:09 | 22.20 | 18.15 |
March | 0.453439E+10 | 26102.31 | 30-MAR-08:62 | 21.78 | 19.48 | 0.739684E+09 | 1198.68 | 04-MAR-15:09 | 25.50 | 14.61 |
April | 0.640226E+10 | 26563.63 | 25-APR-08:62 | 22.07 | 18.95 | 0.750273E+09 | 1198.65 | 08-APR-14:00 | 20.00 | 18.16 |
May | 0.109729E+11 | 27048.07 | 12-MAY-08:61 | 24.78 | 21.41 | 0.778077E+09 | 1198.43 | 20-MAY-14:30 | 26.65 | 23.50 |
June | 0.116249E+11 | 26490.93 | 10-JUN-08:61 | 27.80 | 21.57 | 0.763216E+09 | 1198.42 | 24-JUN-14:00 | 27.20 | 23.26 |
July | 0.120154E+11 | 24178.09 | 14-JUL-08:61 | 23.90 | 21.87 | 0.767876E+09 | 1198.29 | 01-JUL-14:00 | 26.10 | 24.52 |
August | 0.126812E+11 | 26770.70 | 31-AUG-08:61 | 27.88 | 24.09 | 0.789986E+09 | 1198.43 | 12-AUG-14:50 | 26.20 | 23.32 |
September | 0.109919E+11 | 26396.39 | 22-SEP-08:61 | 23.58 | 20.80 | 0.752788E+09 | 1198.29 | 23-SEP-14:00 | 28.80 | 24.08 |
October | 0.108954E+11 | 38698.74 | 26-OCT-08:61 | 21.18 | 12.92 | 0.765610E+09 | 1198.66 | 28-OCT-14:09 | 21.00 | 14.40 |
November | 0.649229E+10 | 29434.24 | 05-NOV-09:02 | 20.78 | 17.18 | 0.731865E+09 | 1198.70 | 25-NOV-15:30 | 19.40 | 14.63 |
December | 0.502058E+10 | 35239.55 | 17-DEC-10:02 | 19.17 | 14.28 | 0.712180E+09 | 1198.65 | 23-DEC-15:00 | 22.00 | 14.83 |
Annual Sum or Average | 0.993250E+11 | 0.886798E+10 | ||||||||
Minimum of Months | 0.380513E+10 | 24178.09 | 19.17 | 12.92 | 0.642393E+09 | 1198.29 | 19.40 | 12.65 | ||
Maximum of Months | 0.126812E+11 | 38698.74 | 27.88 | 24.09 | 0.789986E+09 | 1198.70 | 28.80 | 24.52 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184318E+10 | 16626.17 | 01-JAN-10:02 | 20.33 | 16.40 | 0.335059E+09 | 599.32 | 28-JAN-15:00 | 23.00 | 14.03 |
February | 0.183694E+10 | 14226.12 | 28-FEB-09:02 | 20.08 | 18.59 | 0.319859E+09 | 599.32 | 11-FEB-15:50 | 22.20 | 18.15 |
March | 0.220712E+10 | 13565.79 | 30-MAR-08:62 | 21.78 | 19.48 | 0.368651E+09 | 599.34 | 04-MAR-15:09 | 25.50 | 14.61 |
April | 0.323734E+10 | 13799.10 | 25-APR-08:62 | 22.07 | 18.95 | 0.374995E+09 | 599.32 | 08-APR-14:09 | 20.00 | 18.16 |
May | 0.570202E+10 | 14065.15 | 12-MAY-08:61 | 24.78 | 21.41 | 0.389007E+09 | 599.21 | 20-MAY-14:30 | 26.65 | 23.50 |
June | 0.604784E+10 | 13774.53 | 10-JUN-08:61 | 27.80 | 21.57 | 0.381573E+09 | 599.19 | 10-JUN-14:09 | 33.30 | 22.09 |
July | 0.625440E+10 | 12548.75 | 14-JUL-08:61 | 23.90 | 21.87 | 0.383904E+09 | 599.13 | 01-JUL-14:00 | 26.10 | 24.52 |
August | 0.659407E+10 | 13939.82 | 31-AUG-08:61 | 27.88 | 24.09 | 0.394961E+09 | 599.20 | 12-AUG-14:50 | 26.20 | 23.32 |
September | 0.569472E+10 | 13719.39 | 22-SEP-08:61 | 23.58 | 20.80 | 0.376363E+09 | 599.13 | 23-SEP-14:00 | 28.80 | 24.08 |
October | 0.561923E+10 | 20143.59 | 26-OCT-08:61 | 21.18 | 12.92 | 0.382765E+09 | 599.33 | 28-OCT-14:09 | 21.00 | 14.40 |
November | 0.325317E+10 | 15296.86 | 05-NOV-09:02 | 20.78 | 17.18 | 0.365633E+09 | 599.35 | 25-NOV-15:20 | 19.60 | 14.67 |
December | 0.245463E+10 | 18339.65 | 17-DEC-10:02 | 19.17 | 14.28 | 0.354980E+09 | 599.32 | 23-DEC-15:09 | 22.00 | 14.83 |
Annual Sum or Average | 0.507447E+11 | 0.442775E+10 | ||||||||
Minimum of Months | 0.183694E+10 | 12548.75 | 19.17 | 12.92 | 0.319859E+09 | 599.13 | 19.60 | 14.03 | ||
Maximum of Months | 0.659407E+10 | 20143.59 | 27.88 | 24.09 | 0.394961E+09 | 599.35 | 33.30 | 24.52 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178012E+10 | 16486.27 | 01-JAN-10:02 | 20.33 | 16.40 | 0.334152E+09 | 599.32 | 28-JAN-15:00 | 23.00 | 14.03 |
February | 0.177883E+10 | 14088.74 | 28-FEB-09:02 | 20.08 | 18.59 | 0.319097E+09 | 599.32 | 11-FEB-15:39 | 22.20 | 18.15 |
March | 0.213856E+10 | 13430.07 | 30-MAR-08:62 | 21.78 | 19.48 | 0.367965E+09 | 599.34 | 04-MAR-15:09 | 25.50 | 14.61 |
April | 0.316914E+10 | 13672.86 | 25-APR-08:62 | 22.07 | 18.95 | 0.374887E+09 | 599.33 | 01-APR-14:50 | 19.58 | 16.07 |
May | 0.563784E+10 | 13945.33 | 12-MAY-08:61 | 24.78 | 21.41 | 0.388996E+09 | 599.21 | 20-MAY-14:30 | 26.65 | 23.50 |
June | 0.598680E+10 | 13656.54 | 10-JUN-08:61 | 27.80 | 21.57 | 0.381564E+09 | 599.19 | 24-JUN-14:00 | 27.20 | 23.26 |
July | 0.619876E+10 | 12425.98 | 14-JUL-08:61 | 23.90 | 21.87 | 0.383895E+09 | 599.14 | 01-JUL-14:00 | 26.10 | 24.52 |
August | 0.654003E+10 | 13816.30 | 31-AUG-08:61 | 27.88 | 24.09 | 0.394954E+09 | 599.20 | 12-AUG-14:50 | 26.20 | 23.32 |
September | 0.564419E+10 | 13605.23 | 22-SEP-08:61 | 23.58 | 20.80 | 0.376356E+09 | 599.13 | 23-SEP-14:00 | 28.80 | 24.08 |
October | 0.556204E+10 | 19997.45 | 26-OCT-08:61 | 21.18 | 12.92 | 0.382739E+09 | 599.33 | 28-OCT-14:09 | 21.00 | 14.40 |
November | 0.319388E+10 | 15181.75 | 05-NOV-09:02 | 20.78 | 17.18 | 0.365443E+09 | 599.34 | 25-NOV-15:20 | 19.60 | 14.67 |
December | 0.239605E+10 | 18199.64 | 17-DEC-10:02 | 19.17 | 14.28 | 0.354296E+09 | 599.32 | 23-DEC-15:09 | 22.00 | 14.83 |
Annual Sum or Average | 0.500262E+11 | 0.442434E+10 | ||||||||
Minimum of Months | 0.177883E+10 | 12425.98 | 19.17 | 12.92 | 0.319097E+09 | 599.13 | 19.58 | 14.03 | ||
Maximum of Months | 0.654003E+10 | 19997.45 | 27.88 | 24.09 | 0.394954E+09 | 599.34 | 28.80 | 24.52 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167069E+10 | 16398.07 | 01-JAN-10:02 | 20.33 | 16.40 | 0.332770E+09 | 599.32 | 28-JAN-15:00 | 23.00 | 14.03 |
February | 0.167727E+10 | 13636.04 | 28-FEB-09:02 | 20.08 | 18.59 | 0.317746E+09 | 599.33 | 11-FEB-15:09 | 22.20 | 18.15 |
March | 0.201681E+10 | 11774.06 | 30-MAR-08:62 | 21.78 | 19.48 | 0.366647E+09 | 599.34 | 04-MAR-15:09 | 25.50 | 14.61 |
April | 0.304394E+10 | 13426.52 | 22-APR-08:62 | 22.57 | 19.96 | 0.374590E+09 | 599.32 | 08-APR-14:09 | 20.00 | 18.16 |
May | 0.557547E+10 | 13918.15 | 12-MAY-08:61 | 24.78 | 21.41 | 0.388980E+09 | 599.21 | 20-MAY-14:00 | 25.00 | 22.92 |
June | 0.594856E+10 | 13636.48 | 10-JUN-08:61 | 27.80 | 21.57 | 0.381552E+09 | 599.20 | 24-JUN-14:00 | 27.20 | 23.26 |
July | 0.619114E+10 | 12393.42 | 18-JUL-08:61 | 28.58 | 24.21 | 0.383890E+09 | 599.14 | 01-JUL-14:00 | 26.10 | 24.52 |
August | 0.655427E+10 | 13847.53 | 31-AUG-08:61 | 27.88 | 24.09 | 0.394953E+09 | 599.20 | 12-AUG-14:50 | 26.20 | 23.32 |
September | 0.564578E+10 | 13604.27 | 22-SEP-08:61 | 23.58 | 20.80 | 0.376352E+09 | 599.13 | 23-SEP-14:00 | 28.80 | 24.08 |
October | 0.553958E+10 | 20012.91 | 26-OCT-08:61 | 21.18 | 12.92 | 0.382695E+09 | 599.33 | 28-OCT-14:09 | 21.00 | 14.40 |
November | 0.311588E+10 | 14547.74 | 05-NOV-09:02 | 20.78 | 17.18 | 0.365109E+09 | 599.35 | 25-NOV-15:09 | 19.80 | 14.71 |
December | 0.230106E+10 | 18160.66 | 17-DEC-10:02 | 19.17 | 14.28 | 0.353114E+09 | 599.33 | 23-DEC-15:00 | 22.00 | 14.83 |
Annual Sum or Average | 0.492805E+11 | 0.441840E+10 | ||||||||
Minimum of Months | 0.167069E+10 | 11774.06 | 19.17 | 12.92 | 0.317746E+09 | 599.13 | 19.80 | 14.03 | ||
Maximum of Months | 0.655427E+10 | 20012.91 | 28.58 | 24.21 | 0.394953E+09 | 599.35 | 28.80 | 24.52 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153003E+10 | 17509.76 | 01-JAN-10:02 | 20.33 | 16.40 | 0.331897E+09 | 599.32 | 28-JAN-15:00 | 23.00 | 14.03 |
February | 0.155790E+10 | 8567.85 | 28-FEB-09:02 | 20.08 | 18.59 | 0.315955E+09 | 599.33 | 11-FEB-15:39 | 22.20 | 18.15 |
March | 0.191022E+10 | 8470.25 | 07-MAR-09:02 | 23.67 | 21.82 | 0.364734E+09 | 599.35 | 04-MAR-15:00 | 25.50 | 14.61 |
April | 0.301455E+10 | 14073.92 | 23-APR-09:02 | 24.68 | 20.66 | 0.374038E+09 | 599.33 | 01-APR-14:30 | 19.95 | 16.45 |
May | 0.590977E+10 | 14417.06 | 12-MAY-08:61 | 24.78 | 21.41 | 0.388983E+09 | 599.23 | 20-MAY-14:00 | 25.00 | 22.92 |
June | 0.643191E+10 | 14604.79 | 11-JUN-09:01 | 28.07 | 20.79 | 0.381569E+09 | 599.26 | 10-JUN-14:09 | 33.30 | 22.09 |
July | 0.682443E+10 | 13295.31 | 14-JUL-08:61 | 23.90 | 21.87 | 0.383937E+09 | 599.17 | 15-JUL-14:00 | 28.30 | 24.58 |
August | 0.734875E+10 | 15658.59 | 31-AUG-08:61 | 27.88 | 24.09 | 0.395001E+09 | 599.18 | 05-AUG-14:20 | 28.63 | 25.50 |
September | 0.627810E+10 | 14492.52 | 22-SEP-08:61 | 23.58 | 20.80 | 0.376409E+09 | 599.12 | 23-SEP-14:00 | 28.80 | 24.08 |
October | 0.608323E+10 | 22309.19 | 26-OCT-08:61 | 21.18 | 12.92 | 0.382656E+09 | 599.33 | 28-OCT-14:09 | 21.00 | 14.40 |
November | 0.322956E+10 | 15562.97 | 06-NOV-09:02 | 22.47 | 19.37 | 0.364797E+09 | 599.34 | 25-NOV-15:09 | 19.80 | 14.71 |
December | 0.223229E+10 | 20056.72 | 17-DEC-10:02 | 19.17 | 14.28 | 0.351736E+09 | 599.33 | 23-DEC-15:00 | 22.00 | 14.83 |
Annual Sum or Average | 0.523508E+11 | 0.441171E+10 | ||||||||
Minimum of Months | 0.153003E+10 | 8470.25 | 19.17 | 12.92 | 0.315955E+09 | 599.12 | 19.80 | 14.03 | ||
Maximum of Months | 0.734875E+10 | 22309.19 | 28.07 | 24.09 | 0.395001E+09 | 599.35 | 33.30 | 25.50 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 86710082.68 | 18133.88 | 10-JAN-09:02 | 5.33 |
February | 0.111718E+09 | 43491.78 | 06-FEB-09:01 | 7.47 |
March | 0.163141E+09 | 25260.22 | 11-MAR-09:02 | 6.52 |
April | 75555659.27 | 1653.50 | 28-APR-08:05 | 24.68 |
May | 86974552.97 | 3142.86 | 16-MAY-08:06 | 27.98 |
June | 87644064.04 | 4063.78 | 17-JUN-08:06 | 30.00 |
July | 70388348.90 | 3336.03 | 18-JUL-08:06 | 28.58 |
August | 80934828.25 | 3316.68 | 02-AUG-08:06 | 28.48 |
September | 76819849.12 | 2183.22 | 09-SEP-08:20 | 26.97 |
October | 76165446.59 | 2367.65 | 06-OCT-08:08 | 26.67 |
November | 73131410.47 | 1575.48 | 11-NOV-08:05 | 20.73 |
December | 94417642.82 | 40338.30 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.108360E+10 | |||
Minimum of Months | 70388348.90 | 1575.48 | 5.33 | |
Maximum of Months | 0.163141E+09 | 43491.78 | 30.00 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44523506.54 | 1747.76 | 10-JAN-09:05 | 5.33 |
February | 43538087.66 | 3627.85 | 05-FEB-09:02 | -0.3 |
March | 61710802.64 | 1936.12 | 11-MAR-12:10 | 6.28 |
April | 41979176.56 | 1194.22 | 29-APR-08:05 | 25.78 |
May | 46182072.09 | 1650.93 | 27-MAY-08:06 | 27.98 |
June | 45840556.78 | 1964.32 | 17-JUN-08:06 | 30.00 |
July | 42886578.85 | 1941.28 | 19-JUL-08:06 | 29.68 |
August | 45871531.74 | 1774.50 | 22-AUG-08:06 | 29.00 |
September | 43932059.42 | 1793.92 | 02-SEP-08:06 | 28.58 |
October | 42941041.22 | 1338.03 | 14-OCT-08:06 | 27.17 |
November | 40190151.67 | 952.56 | 11-NOV-08:05 | 20.73 |
December | 45697085.55 | 1654.46 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.545293E+09 | |||
Minimum of Months | 40190151.67 | 952.56 | -0.3 | |
Maximum of Months | 61710802.64 | 3627.85 | 30.00 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 48446745.84 | 1412.17 | 05-JAN-08:05 | 1.00 |
February | 57898592.39 | 9381.70 | 05-FEB-09:02 | -0.3 |
March | 72188477.60 | 4701.73 | 12-MAR-08:63 | 9.18 |
April | 54819068.53 | 1709.24 | 22-APR-17:03 | 30.13 |
May | 0.122130E+09 | 2522.31 | 28-MAY-16:02 | 33.43 |
June | 0.134230E+09 | 2342.49 | 25-JUN-16:02 | 32.70 |
July | 0.132423E+09 | 2834.35 | 22-JUL-17:02 | 34.63 |
August | 0.118710E+09 | 2563.78 | 27-AUG-16:02 | 33.67 |
September | 92967200.34 | 3269.79 | 09-SEP-17:02 | 36.18 |
October | 83227527.19 | 1847.46 | 08-OCT-16:02 | 30.67 |
November | 48761310.75 | 910.35 | 05-NOV-16:03 | 27.02 |
December | 51147801.16 | 1644.75 | 21-DEC-08:03 | 3.50 |
Annual Sum or Average | 0.101695E+10 | |||
Minimum of Months | 48446745.84 | 910.35 | -0.3 | |
Maximum of Months | 0.134230E+09 | 9381.70 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49795766.33 | 2388.42 | 05-JAN-08:03 | 1.00 |
February | 61556391.72 | 11905.31 | 05-FEB-09:02 | -0.3 |
March | 77072742.70 | 7109.51 | 12-MAR-08:63 | 9.18 |
April | 54546661.24 | 1709.85 | 22-APR-17:03 | 30.13 |
May | 0.121023E+09 | 2521.69 | 28-MAY-16:02 | 33.43 |
June | 0.132517E+09 | 2341.22 | 25-JUN-16:02 | 32.70 |
July | 0.127535E+09 | 2833.82 | 22-JUL-17:02 | 34.63 |
August | 0.114818E+09 | 2562.02 | 27-AUG-16:02 | 33.67 |
September | 90025104.77 | 3269.42 | 09-SEP-17:02 | 36.18 |
October | 81073317.86 | 1845.31 | 08-OCT-16:02 | 30.67 |
November | 48515637.61 | 910.05 | 05-NOV-16:03 | 27.02 |
December | 53951248.67 | 3306.66 | 20-DEC-12:40 | 7.00 |
Annual Sum or Average | 0.101243E+10 | |||
Minimum of Months | 48515637.61 | 910.05 | -0.3 | |
Maximum of Months | 0.132517E+09 | 11905.31 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 53183321.69 | 3175.73 | 10-JAN-08:62 | 4.17 |
February | 69250762.44 | 14416.94 | 05-FEB-09:02 | -0.3 |
March | 85949523.85 | 9255.19 | 12-MAR-08:63 | 9.18 |
April | 54926289.72 | 1716.47 | 22-APR-17:03 | 30.13 |
May | 0.122803E+09 | 2525.63 | 28-MAY-16:02 | 33.43 |
June | 0.135494E+09 | 2345.01 | 25-JUN-16:02 | 32.70 |
July | 0.133719E+09 | 2838.52 | 22-JUL-17:02 | 34.63 |
August | 0.120834E+09 | 2565.40 | 27-AUG-16:02 | 33.67 |
September | 93203108.88 | 3273.28 | 09-SEP-17:02 | 36.18 |
October | 83837807.17 | 1848.43 | 08-OCT-16:02 | 30.67 |
November | 49043675.25 | 916.04 | 05-NOV-16:03 | 27.02 |
December | 58267977.45 | 4854.66 | 21-DEC-08:62 | 3.50 |
Annual Sum or Average | 0.106051E+10 | |||
Minimum of Months | 49043675.25 | 916.04 | -0.3 | |
Maximum of Months | 0.135494E+09 | 14416.94 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105318E+09 | 36998.67 | 10-JAN-09:02 | 5.33 |
February | 0.146186E+09 | 42687.33 | 06-FEB-09:01 | 7.47 |
March | 0.179931E+09 | 44310.10 | 12-MAR-09:01 | 11.47 |
April | 96112779.91 | 3446.22 | 22-APR-17:03 | 30.13 |
May | 0.152763E+09 | 5063.21 | 28-MAY-16:02 | 33.43 |
June | 0.157364E+09 | 4700.17 | 25-JUN-16:02 | 32.70 |
July | 0.159639E+09 | 5687.71 | 22-JUL-17:02 | 34.63 |
August | 0.130366E+09 | 5147.78 | 27-AUG-16:02 | 33.67 |
September | 0.146709E+09 | 6536.41 | 09-SEP-17:02 | 36.18 |
October | 0.117026E+09 | 3697.16 | 08-OCT-16:02 | 30.67 |
November | 79050006.59 | 1850.84 | 05-NOV-16:03 | 27.02 |
December | 0.111572E+09 | 41783.64 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.158204E+10 | |||
Minimum of Months | 79050006.59 | 1850.84 | 5.33 | |
Maximum of Months | 0.179931E+09 | 44310.10 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70648907.15 | 21181.68 | 10-JAN-09:02 | 5.33 |
February | 0.103702E+09 | 22345.64 | 06-FEB-09:01 | 7.47 |
March | 0.109121E+09 | 23138.79 | 12-MAR-09:01 | 11.47 |
April | 52277832.15 | 1740.40 | 22-APR-17:03 | 30.13 |
May | 78891548.01 | 2538.95 | 28-MAY-16:02 | 33.43 |
June | 80896429.07 | 2358.15 | 25-JUN-16:02 | 32.70 |
July | 85489831.03 | 2859.03 | 22-JUL-17:02 | 34.63 |
August | 70163170.80 | 2579.99 | 27-AUG-16:02 | 33.67 |
September | 78012558.37 | 3284.77 | 09-SEP-17:02 | 36.18 |
October | 63091800.24 | 1858.82 | 08-OCT-16:02 | 30.67 |
November | 43248727.85 | 937.81 | 05-NOV-16:03 | 27.02 |
December | 75796634.54 | 21882.61 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.911340E+09 | |||
Minimum of Months | 43248727.85 | 937.81 | 5.33 | |
Maximum of Months | 0.109121E+09 | 23138.79 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 75597861.16 | 21398.61 | 10-JAN-09:02 | 5.33 |
February | 0.111040E+09 | 22247.88 | 06-FEB-09:01 | 7.47 |
March | 0.112759E+09 | 23041.98 | 12-MAR-09:01 | 11.47 |
April | 52227288.14 | 1741.80 | 22-APR-17:03 | 30.13 |
May | 78932102.94 | 2539.99 | 28-MAY-16:02 | 33.43 |
June | 80945077.41 | 2359.13 | 25-JUN-16:02 | 32.70 |
July | 86211239.89 | 2860.12 | 22-JUL-17:02 | 34.63 |
August | 70683812.83 | 2580.89 | 27-AUG-16:02 | 33.67 |
September | 78388825.95 | 3285.37 | 09-SEP-17:02 | 36.18 |
October | 63040104.68 | 1859.60 | 08-OCT-16:02 | 30.67 |
November | 43037861.95 | 939.21 | 05-NOV-16:03 | 27.02 |
December | 79731171.48 | 21780.79 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.932595E+09 | |||
Minimum of Months | 43037861.95 | 939.21 | 5.33 | |
Maximum of Months | 0.112759E+09 | 23041.98 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 90104138.66 | 21495.53 | 10-JAN-09:02 | 5.33 |
February | 0.132979E+09 | 22367.16 | 06-FEB-09:01 | 7.47 |
March | 0.130852E+09 | 23155.43 | 12-MAR-09:01 | 11.47 |
April | 52710112.86 | 1744.69 | 22-APR-17:03 | 30.13 |
May | 79190365.16 | 2541.46 | 28-MAY-16:02 | 33.43 |
June | 81381002.93 | 2360.13 | 25-JUN-16:02 | 32.70 |
July | 87038824.70 | 2860.09 | 22-JUL-17:02 | 34.63 |
August | 70940690.54 | 2580.43 | 27-AUG-16:02 | 33.67 |
September | 78564418.41 | 3285.35 | 09-SEP-17:02 | 36.18 |
October | 63298560.66 | 1859.25 | 08-OCT-16:02 | 30.67 |
November | 43093909.18 | 941.24 | 05-NOV-16:03 | 27.02 |
December | 91230031.72 | 21880.94 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.100138E+10 | |||
Minimum of Months | 43093909.18 | 941.24 | 5.33 | |
Maximum of Months | 0.132979E+09 | 23155.43 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156983E+09 | 24387.69 | 23-JAN-09:02 | 9.50 |
February | 0.212517E+09 | 25007.66 | 18-FEB-09:02 | 12.15 |
March | 0.213873E+09 | 25494.38 | 12-MAR-09:01 | 11.47 |
April | 55561952.19 | 1752.91 | 22-APR-17:03 | 30.13 |
May | 83137833.75 | 2540.56 | 28-MAY-16:02 | 33.43 |
June | 83436219.61 | 2357.02 | 25-JUN-16:02 | 32.70 |
July | 87681219.32 | 2844.92 | 22-JUL-17:02 | 34.63 |
August | 70147874.00 | 2563.79 | 27-AUG-16:02 | 33.67 |
September | 79065099.77 | 3273.76 | 09-SEP-17:02 | 36.18 |
October | 65437916.68 | 1847.60 | 08-OCT-16:02 | 30.67 |
November | 45649425.98 | 942.80 | 05-NOV-16:03 | 27.02 |
December | 0.153205E+09 | 24288.49 | 21-DEC-09:01 | 6.33 |
Annual Sum or Average | 0.130670E+10 | |||
Minimum of Months | 45649425.98 | 942.80 | 6.33 | |
Maximum of Months | 0.213873E+09 | 25494.38 | 36.18 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.861445E+10 | 5225.88 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.779459E+10 | 5225.88 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.863227E+10 | 5225.88 | 01-MAR-10:09 | 0.223972E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.835898E+10 | 5225.88 | 01-APR-09:09 | 0.216880E+10 | 1348.26 | 01-APR-09:09 |
May | 0.861445E+10 | 5225.88 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.835898E+10 | 5225.88 | 01-JUN-09:09 | 0.216880E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.863227E+10 | 5225.88 | 01-JUL-09:09 | 0.223972E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.861445E+10 | 5225.88 | 01-AUG-09:09 | 0.223514E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.837681E+10 | 5225.88 | 01-SEP-09:09 | 0.217339E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.861445E+10 | 5225.88 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.832334E+10 | 5225.88 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.865009E+10 | 5225.88 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.101585E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.779459E+10 | 5225.88 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.865009E+10 | 5225.88 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.509120E+10 | 3088.53 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.460666E+10 | 3088.53 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.510174E+10 | 3088.53 | 01-MAR-10:09 | 0.111986E+10 | 674.13 | 01-MAR-10:09 |
April | 0.494022E+10 | 3088.53 | 01-APR-09:09 | 0.108440E+10 | 674.13 | 01-APR-09:09 |
May | 0.509120E+10 | 3088.53 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.494022E+10 | 3088.53 | 01-JUN-09:09 | 0.108440E+10 | 674.13 | 01-JUN-09:09 |
July | 0.510174E+10 | 3088.53 | 01-JUL-09:09 | 0.111986E+10 | 674.13 | 01-JUL-09:09 |
August | 0.509120E+10 | 3088.53 | 01-AUG-09:09 | 0.111757E+10 | 674.13 | 01-AUG-09:09 |
September | 0.495076E+10 | 3088.53 | 01-SEP-09:09 | 0.108669E+10 | 674.13 | 01-SEP-09:09 |
October | 0.509120E+10 | 3088.53 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.491916E+10 | 3088.53 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.511227E+10 | 3088.53 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.600376E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.460666E+10 | 3088.53 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.511227E+10 | 3088.53 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.366929E+10 | 2821.35 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.332289E+10 | 2821.35 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.374627E+10 | 2821.35 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.356024E+10 | 2821.35 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.370778E+10 | 2821.35 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.361797E+10 | 2821.35 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.365005E+10 | 2821.35 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.374627E+10 | 2821.35 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.356024E+10 | 2821.35 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.366929E+10 | 2821.35 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.356024E+10 | 2821.35 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.365005E+10 | 2821.35 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.434606E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.332289E+10 | 2821.35 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.374627E+10 | 2821.35 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.366929E+10 | 2821.35 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.332289E+10 | 2821.35 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.374627E+10 | 2821.35 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.356024E+10 | 2821.35 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.370778E+10 | 2821.35 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.361797E+10 | 2821.35 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.365005E+10 | 2821.35 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.374627E+10 | 2821.35 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.356024E+10 | 2821.35 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.366929E+10 | 2821.35 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.356024E+10 | 2821.35 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.365005E+10 | 2821.35 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.434606E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.332289E+10 | 2821.35 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.374627E+10 | 2821.35 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.366929E+10 | 2821.35 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.332289E+10 | 2821.35 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.374627E+10 | 2821.35 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.356024E+10 | 2821.35 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.370778E+10 | 2821.35 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.361797E+10 | 2821.35 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.365005E+10 | 2821.35 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.374627E+10 | 2821.35 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.356024E+10 | 2821.35 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.366929E+10 | 2821.35 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.356024E+10 | 2821.35 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.365005E+10 | 2821.35 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.434606E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.332289E+10 | 2821.35 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.374627E+10 | 2821.35 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.399227E+10 | 3341.31 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.361622E+10 | 3341.31 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.408344E+10 | 3341.31 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.387452E+10 | 3341.31 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.403786E+10 | 3341.31 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.394289E+10 | 3341.31 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.396948E+10 | 3341.31 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.408344E+10 | 3341.31 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.387452E+10 | 3341.31 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.399227E+10 | 3341.31 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.387452E+10 | 3341.31 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.396948E+10 | 3341.31 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.473109E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.361622E+10 | 3341.31 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.408344E+10 | 3341.31 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.199614E+10 | 1670.66 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.180811E+10 | 1670.66 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.204172E+10 | 1670.66 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.193726E+10 | 1670.66 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.201893E+10 | 1670.66 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.197145E+10 | 1670.66 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.198474E+10 | 1670.66 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.204172E+10 | 1670.66 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.193726E+10 | 1670.66 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.199614E+10 | 1670.66 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.193726E+10 | 1670.66 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.198474E+10 | 1670.66 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.236555E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.180811E+10 | 1670.66 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.204172E+10 | 1670.66 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.199614E+10 | 1670.66 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.180811E+10 | 1670.66 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.204172E+10 | 1670.66 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.193726E+10 | 1670.66 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.201893E+10 | 1670.66 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.197145E+10 | 1670.66 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.198474E+10 | 1670.66 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.204172E+10 | 1670.66 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.193726E+10 | 1670.66 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.199614E+10 | 1670.66 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.193726E+10 | 1670.66 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.198474E+10 | 1670.66 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.236555E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.180811E+10 | 1670.66 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.204172E+10 | 1670.66 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.199614E+10 | 1670.66 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.180811E+10 | 1670.66 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.204172E+10 | 1670.66 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.193726E+10 | 1670.66 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.201893E+10 | 1670.66 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.197145E+10 | 1670.66 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.198474E+10 | 1670.66 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.204172E+10 | 1670.66 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.193726E+10 | 1670.66 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.199614E+10 | 1670.66 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.193726E+10 | 1670.66 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.198474E+10 | 1670.66 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.236555E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.180811E+10 | 1670.66 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.204172E+10 | 1670.66 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.199614E+10 | 1670.66 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.180811E+10 | 1670.66 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.204172E+10 | 1670.66 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.193726E+10 | 1670.66 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.201893E+10 | 1670.66 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.197145E+10 | 1670.66 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.198474E+10 | 1670.66 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.204172E+10 | 1670.66 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.193726E+10 | 1670.66 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.199614E+10 | 1670.66 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.193726E+10 | 1670.66 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.198474E+10 | 1670.66 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.236555E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.180811E+10 | 1670.66 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.204172E+10 | 1670.66 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.861445E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70656830.67 | 0.258044E+10 |
February | 0.163016E+10 | 0.779459E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122226E+09 | 0.188084E+10 |
March | 0.178954E+10 | 0.863227E+10 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267195E+09 | 0.165513E+10 |
April | 0.174484E+10 | 0.835898E+10 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756250E+09 | 0.592410E+09 |
May | 0.179537E+10 | 0.861445E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216051E+10 | 30988307.95 |
June | 0.173447E+10 | 0.835898E+10 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233643E+10 | 24698846.15 |
July | 0.181028E+10 | 0.863227E+10 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226833E+10 | 15903490.29 |
August | 0.178501E+10 | 0.861445E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232506E+10 | 39492862.33 |
September | 0.174937E+10 | 0.837681E+10 | 0.217339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165528E+10 | 78772705.89 |
October | 0.180574E+10 | 0.861445E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153290E+10 | 0.382204E+09 |
November | 0.174613E+10 | 0.832334E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373461E+09 | 0.118935E+10 |
December | 0.181481E+10 | 0.865009E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242509E+09 | 0.224097E+10 |
Annual Sum or Average | 0.212115E+11 | 0.101585E+12 | 0.263573E+11 | 0.141108E+11 | 0.107112E+11 | ||||
Minimum of Months | 0.163016E+10 | 0.779459E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70656830.67 | 15903490.29 |
Maximum of Months | 0.181481E+10 | 0.865009E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233643E+10 | 0.258044E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.509120E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39942238.80 | 0.138736E+10 |
February | 0.815075E+09 | 0.460666E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68965395.41 | 0.100452E+10 |
March | 0.894769E+09 | 0.510174E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150206E+09 | 0.865127E+09 |
April | 0.872416E+09 | 0.494022E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426671E+09 | 0.295378E+09 |
May | 0.897684E+09 | 0.509120E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121341E+10 | 11844151.57 |
June | 0.867232E+09 | 0.494022E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131461E+10 | 8784937.70 |
July | 0.905135E+09 | 0.510174E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127143E+10 | 7174917.72 |
August | 0.892501E+09 | 0.509120E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130313E+10 | 13890201.65 |
September | 0.874683E+09 | 0.495076E+10 | 0.108669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925700E+09 | 32181475.41 |
October | 0.902868E+09 | 0.509120E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857618E+09 | 0.167976E+09 |
November | 0.873064E+09 | 0.491916E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211070E+09 | 0.604934E+09 |
December | 0.907403E+09 | 0.511227E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137145E+09 | 0.117180E+10 |
Annual Sum or Average | 0.106057E+11 | 0.600376E+11 | 0.131787E+11 | 0.791990E+10 | 0.557098E+10 | ||||
Minimum of Months | 0.815075E+09 | 0.460666E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39942238.80 | 7174917.72 |
Maximum of Months | 0.907403E+09 | 0.511227E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131461E+10 | 0.138736E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39937379.01 | 0.138697E+10 |
February | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68886887.45 | 0.101337E+10 |
March | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147916E+09 | 0.880392E+09 |
April | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421647E+09 | 0.310141E+09 |
May | 0.544247E+09 | 0.370778E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119421E+10 | 14977240.63 |
June | 0.532585E+09 | 0.361797E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130053E+10 | 11538508.06 |
July | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124795E+10 | 8622372.69 |
August | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129078E+10 | 20945915.36 |
September | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903883E+09 | 39126977.88 |
October | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838558E+09 | 0.182260E+09 |
November | 0.518979E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208086E+09 | 0.619766E+09 |
December | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136666E+09 | 0.118661E+10 |
Annual Sum or Average | 0.638324E+10 | 0.434606E+11 | 0.104672E+11 | 0.779904E+10 | 0.567472E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39937379.01 | 8622372.69 |
Maximum of Months | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130053E+10 | 0.138697E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39936432.35 | 0.137084E+10 |
February | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68885817.18 | 0.100402E+10 |
March | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147925E+09 | 0.873126E+09 |
April | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421642E+09 | 0.309541E+09 |
May | 0.544247E+09 | 0.370778E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119397E+10 | 15415407.31 |
June | 0.532585E+09 | 0.361797E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130024E+10 | 11927942.03 |
July | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124734E+10 | 9038792.76 |
August | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129040E+10 | 21539643.15 |
September | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903436E+09 | 39787557.94 |
October | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838446E+09 | 0.183040E+09 |
November | 0.518979E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208086E+09 | 0.618547E+09 |
December | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136667E+09 | 0.117916E+10 |
Annual Sum or Average | 0.638324E+10 | 0.434606E+11 | 0.104672E+11 | 0.779698E+10 | 0.563598E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39936432.35 | 9038792.76 |
Maximum of Months | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130024E+10 | 0.137084E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39934101.76 | 0.134912E+10 |
February | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68882500.49 | 0.989524E+09 |
March | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147946E+09 | 0.859652E+09 |
April | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421721E+09 | 0.307430E+09 |
May | 0.544247E+09 | 0.370778E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119448E+10 | 14105410.40 |
June | 0.532585E+09 | 0.361797E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130072E+10 | 11061272.86 |
July | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124811E+10 | 8396284.42 |
August | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129089E+10 | 20327306.56 |
September | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903858E+09 | 38518229.14 |
October | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838700E+09 | 0.181072E+09 |
November | 0.518979E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208102E+09 | 0.615021E+09 |
December | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136667E+09 | 0.116760E+10 |
Annual Sum or Average | 0.638324E+10 | 0.434606E+11 | 0.104672E+11 | 0.780001E+10 | 0.556183E+10 | ||||
Minimum of Months | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39934101.76 | 8396284.42 |
Maximum of Months | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130072E+10 | 0.134912E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.399227E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69971612.31 | 0.233128E+10 |
February | 0.167188E+10 | 0.361622E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120733E+09 | 0.171232E+10 |
March | 0.189386E+10 | 0.408344E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259668E+09 | 0.149205E+10 |
April | 0.180380E+10 | 0.387452E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739429E+09 | 0.551017E+09 |
May | 0.186509E+10 | 0.403786E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208703E+10 | 24851269.57 |
June | 0.182945E+10 | 0.394289E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227155E+10 | 20213319.74 |
July | 0.183943E+10 | 0.396948E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217867E+10 | 14288118.05 |
August | 0.189386E+10 | 0.408344E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225454E+10 | 36394477.10 |
September | 0.180380E+10 | 0.387452E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158040E+10 | 74516395.51 |
October | 0.183632E+10 | 0.399227E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146980E+10 | 0.340965E+09 |
November | 0.176881E+10 | 0.387452E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364780E+09 | 0.109603E+10 |
December | 0.183943E+10 | 0.396948E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239477E+09 | 0.204427E+10 |
Annual Sum or Average | 0.218821E+11 | 0.473109E+11 | 0.192612E+11 | 0.136361E+11 | 0.973820E+10 | ||||
Minimum of Months | 0.167188E+10 | 0.361622E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69971612.31 | 14288118.05 |
Maximum of Months | 0.189386E+10 | 0.408344E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227155E+10 | 0.233128E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39931331.38 | 0.129159E+10 |
February | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68881486.36 | 0.949871E+09 |
March | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148074E+09 | 0.822346E+09 |
April | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422045E+09 | 0.303844E+09 |
May | 0.932542E+09 | 0.201893E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119120E+10 | 11688947.54 |
June | 0.914724E+09 | 0.197145E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129670E+10 | 9570719.47 |
July | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124353E+10 | 7159576.61 |
August | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128611E+10 | 17521776.95 |
September | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901375E+09 | 38033608.39 |
October | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838240E+09 | 0.182941E+09 |
November | 0.884402E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208189E+09 | 0.608425E+09 |
December | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136675E+09 | 0.113535E+10 |
Annual Sum or Average | 0.109410E+11 | 0.236555E+11 | 0.963059E+10 | 0.778096E+10 | 0.537834E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39931331.38 | 7159576.61 |
Maximum of Months | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129670E+10 | 0.129159E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39930543.79 | 0.128445E+10 |
February | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68880584.04 | 0.944019E+09 |
March | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148088E+09 | 0.816949E+09 |
April | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422084E+09 | 0.302361E+09 |
May | 0.932542E+09 | 0.201893E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119162E+10 | 11306651.00 |
June | 0.914724E+09 | 0.197145E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129706E+10 | 9319770.42 |
July | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124399E+10 | 7003607.51 |
August | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128638E+10 | 17191721.09 |
September | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901604E+09 | 37640649.25 |
October | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838382E+09 | 0.182136E+09 |
November | 0.884402E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208197E+09 | 0.606388E+09 |
December | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136675E+09 | 0.112993E+10 |
Annual Sum or Average | 0.109410E+11 | 0.236555E+11 | 0.963059E+10 | 0.778290E+10 | 0.534870E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39930543.79 | 7003607.51 |
Maximum of Months | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129706E+10 | 0.128445E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39929198.82 | 0.127285E+10 |
February | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68878801.62 | 0.932895E+09 |
March | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148110E+09 | 0.805920E+09 |
April | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422137E+09 | 0.298495E+09 |
May | 0.932542E+09 | 0.201893E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119235E+10 | 10509867.19 |
June | 0.914724E+09 | 0.197145E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129755E+10 | 8880148.92 |
July | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124437E+10 | 6792787.41 |
August | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128645E+10 | 16963567.00 |
September | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901587E+09 | 37263709.71 |
October | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838417E+09 | 0.181012E+09 |
November | 0.884402E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208205E+09 | 0.602694E+09 |
December | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136674E+09 | 0.112018E+10 |
Annual Sum or Average | 0.109410E+11 | 0.236555E+11 | 0.963059E+10 | 0.778465E+10 | 0.529445E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39929198.82 | 6792787.41 |
Maximum of Months | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129755E+10 | 0.127285E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40599577.58 | 0.150808E+10 |
February | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70228444.94 | 0.108797E+10 |
March | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151816E+09 | 0.978359E+09 |
April | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430023E+09 | 0.368287E+09 |
May | 0.932542E+09 | 0.201893E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122490E+10 | 19224800.02 |
June | 0.914724E+09 | 0.197145E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132865E+10 | 18236529.76 |
July | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127969E+10 | 10842926.63 |
August | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132257E+10 | 36922756.94 |
September | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929497E+09 | 67849635.24 |
October | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862826E+09 | 0.274262E+09 |
November | 0.884402E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211670E+09 | 0.736684E+09 |
December | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138872E+09 | 0.133265E+10 |
Annual Sum or Average | 0.109410E+11 | 0.236555E+11 | 0.963059E+10 | 0.799134E+10 | 0.643937E+10 | ||||
Minimum of Months | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40599577.58 | 10842926.63 |
Maximum of Months | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132865E+10 | 0.150808E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 5225.88 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1460.18 | 16-JAN-15:00 | 7670.10 | 04-JAN-18:00 |
February | 2159.72 | 03-FEB-13:09 | 5225.88 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2109.13 | 02-FEB-13:00 | 8466.39 | 04-FEB-18:00 |
March | 2159.72 | 03-MAR-13:09 | 5225.88 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2855.81 | 26-MAR-14:00 | 7634.99 | 11-MAR-12:10 |
April | 2159.72 | 01-APR-12:09 | 5225.88 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4374.35 | 28-APR-15:00 | 3412.50 | 02-APR-11:10 |
May | 2159.72 | 05-MAY-12:09 | 5225.88 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4663.48 | 07-MAY-14:00 | 524.21 | 31-MAY-13:00 |
June | 2159.72 | 02-JUN-12:09 | 5225.88 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5076.61 | 14-JUN-14:00 | 533.77 | 01-JUN-13:00 |
July | 2159.72 | 01-JUL-12:09 | 5225.88 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5555.38 | 22-JUL-16:00 | 529.00 | 12-JUL-15:00 |
August | 2159.72 | 04-AUG-12:09 | 5225.88 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5651.15 | 30-AUG-16:00 | 1007.48 | 16-AUG-17:00 |
September | 2159.72 | 01-SEP-12:09 | 5225.88 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5775.89 | 09-SEP-17:00 | 1979.80 | 07-SEP-17:00 |
October | 2159.72 | 01-OCT-12:09 | 5225.88 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4645.77 | 05-OCT-15:00 | 3396.47 | 27-OCT-16:00 |
November | 2159.72 | 03-NOV-12:09 | 5225.88 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2840.88 | 01-NOV-14:00 | 5976.34 | 15-NOV-18:00 |
December | 2159.72 | 01-DEC-13:09 | 5225.88 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2868.52 | 13-DEC-15:00 | 8686.36 | 20-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 5225.88 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1460.18 | 524.21 | |||||
Maximum of Months | 2159.72 | 5225.88 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5775.89 | 8686.36 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 3088.53 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.67 | 16-JAN-15:00 | 4347.46 | 04-JAN-18:00 |
February | 1079.86 | 03-FEB-13:09 | 3088.53 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.62 | 02-FEB-13:00 | 4746.28 | 04-FEB-18:00 |
March | 1079.86 | 03-MAR-13:09 | 3088.53 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.68 | 26-MAR-14:00 | 4293.50 | 11-MAR-12:10 |
April | 1079.86 | 01-APR-12:09 | 3088.53 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2467.69 | 28-APR-15:00 | 1957.56 | 02-APR-11:10 |
May | 1079.86 | 05-MAY-12:09 | 3088.53 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2630.81 | 07-MAY-14:00 | 296.59 | 31-MAY-13:00 |
June | 1079.86 | 02-JUN-12:09 | 3088.53 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2882.15 | 14-JUN-14:00 | 299.07 | 01-JUN-13:00 |
July | 1079.86 | 01-JUL-12:09 | 3088.53 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3160.08 | 22-JUL-16:00 | 298.40 | 12-JUL-15:00 |
August | 1079.86 | 04-AUG-12:09 | 3088.53 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3205.21 | 30-AUG-16:00 | 570.31 | 16-AUG-17:00 |
September | 1079.86 | 01-SEP-12:09 | 3088.53 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3255.24 | 09-SEP-17:00 | 1121.08 | 07-SEP-17:00 |
October | 1079.86 | 01-OCT-12:09 | 3088.53 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2633.31 | 05-OCT-15:00 | 1916.00 | 27-OCT-16:00 |
November | 1079.86 | 03-NOV-12:09 | 3088.53 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1613.42 | 01-NOV-14:00 | 3455.18 | 15-NOV-18:00 |
December | 1079.86 | 01-DEC-13:09 | 3088.53 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1623.37 | 13-DEC-15:00 | 4940.94 | 20-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3088.53 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.67 | 296.59 | |||||
Maximum of Months | 1079.86 | 3088.53 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3255.24 | 4940.94 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2821.35 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.60 | 16-JAN-15:00 | 4347.46 | 04-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 2821.35 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.59 | 02-FEB-13:00 | 4746.27 | 04-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 2821.35 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.57 | 26-MAR-14:00 | 4293.50 | 11-MAR-12:10 |
April | 1079.86 | 01-APR-12:09 | 2821.35 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2467.66 | 28-APR-15:00 | 1947.96 | 02-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 2821.35 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2630.78 | 07-MAY-14:00 | 296.59 | 31-MAY-13:00 |
June | 1079.86 | 03-JUN-12:09 | 2821.35 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2882.12 | 14-JUN-14:00 | 299.08 | 01-JUN-13:00 |
July | 1079.86 | 01-JUL-12:09 | 2821.35 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3160.07 | 22-JUL-16:00 | 298.43 | 12-JUL-15:00 |
August | 1079.86 | 05-AUG-12:09 | 2821.35 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3205.19 | 30-AUG-16:00 | 570.34 | 16-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 2821.35 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3255.16 | 09-SEP-17:00 | 1121.09 | 07-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 2821.35 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2633.28 | 05-OCT-15:00 | 1916.00 | 27-OCT-16:00 |
November | 1079.86 | 04-NOV-12:09 | 2821.35 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1613.37 | 01-NOV-14:00 | 3423.18 | 15-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 2821.35 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1623.44 | 13-DEC-15:00 | 4940.94 | 20-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.60 | 296.59 | |||||
Maximum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3255.16 | 4940.94 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2821.35 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.58 | 16-JAN-15:00 | 4347.47 | 04-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 2821.35 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.59 | 02-FEB-13:00 | 4746.27 | 04-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 2821.35 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.57 | 26-MAR-14:00 | 4293.50 | 11-MAR-12:10 |
April | 1079.86 | 01-APR-12:09 | 2821.35 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2467.66 | 28-APR-15:00 | 1943.17 | 02-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 2821.35 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2630.78 | 07-MAY-14:00 | 296.58 | 31-MAY-13:00 |
June | 1079.86 | 03-JUN-12:09 | 2821.35 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2882.12 | 14-JUN-14:00 | 299.08 | 01-JUN-13:00 |
July | 1079.86 | 01-JUL-12:09 | 2821.35 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3160.08 | 22-JUL-16:00 | 298.42 | 12-JUL-15:00 |
August | 1079.86 | 05-AUG-12:09 | 2821.35 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3205.19 | 30-AUG-16:00 | 570.33 | 16-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 2821.35 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3255.16 | 09-SEP-17:00 | 1121.09 | 07-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 2821.35 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2633.29 | 05-OCT-15:00 | 1916.00 | 27-OCT-16:00 |
November | 1079.86 | 04-NOV-12:09 | 2821.35 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1613.36 | 01-NOV-14:00 | 3407.06 | 15-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 2821.35 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1623.44 | 13-DEC-15:00 | 4940.94 | 20-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.58 | 296.58 | |||||
Maximum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3255.16 | 4940.94 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2821.35 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.56 | 16-JAN-15:00 | 4347.46 | 04-JAN-18:00 |
February | 1079.86 | 04-FEB-13:09 | 2821.35 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.57 | 02-FEB-13:00 | 4746.27 | 04-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 2821.35 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.53 | 26-MAR-14:00 | 4293.50 | 11-MAR-12:10 |
April | 1079.86 | 01-APR-12:09 | 2821.35 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2467.65 | 28-APR-15:00 | 1930.97 | 02-APR-11:10 |
May | 1079.86 | 06-MAY-12:09 | 2821.35 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2630.77 | 07-MAY-14:00 | 296.60 | 31-MAY-13:00 |
June | 1079.86 | 03-JUN-12:09 | 2821.35 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2882.11 | 14-JUN-14:00 | 299.10 | 01-JUN-13:00 |
July | 1079.86 | 01-JUL-12:09 | 2821.35 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3160.06 | 22-JUL-16:00 | 298.44 | 12-JUL-15:00 |
August | 1079.86 | 05-AUG-12:09 | 2821.35 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3205.18 | 30-AUG-16:00 | 570.35 | 16-AUG-17:00 |
September | 1079.86 | 02-SEP-12:09 | 2821.35 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3255.15 | 09-SEP-17:00 | 1121.11 | 07-SEP-17:00 |
October | 1079.86 | 07-OCT-12:09 | 2821.35 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2633.28 | 05-OCT-15:00 | 1916.00 | 27-OCT-16:00 |
November | 1079.86 | 04-NOV-12:09 | 2821.35 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1613.34 | 01-NOV-14:00 | 3369.75 | 15-NOV-18:00 |
December | 1079.86 | 02-DEC-13:09 | 2821.35 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1623.40 | 13-DEC-15:00 | 4940.94 | 20-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.56 | 296.60 | |||||
Maximum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3255.15 | 4940.94 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 3341.31 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1449.48 | 16-JAN-15:00 | 7614.98 | 04-JAN-18:00 |
February | 2879.63 | 04-FEB-15:09 | 3341.31 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2071.63 | 02-FEB-13:00 | 8326.89 | 04-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 3341.31 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2832.45 | 26-MAR-14:00 | 7529.12 | 11-MAR-12:10 |
April | 2879.63 | 01-APR-14:09 | 3341.31 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4325.33 | 28-APR-15:00 | 3225.64 | 01-APR-17:00 |
May | 2879.63 | 06-MAY-14:09 | 3341.31 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4611.13 | 07-MAY-14:00 | 519.70 | 31-MAY-13:00 |
June | 2879.63 | 03-JUN-14:09 | 3341.31 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5047.02 | 14-JUN-14:00 | 524.86 | 01-JUN-13:00 |
July | 2879.63 | 01-JUL-14:09 | 3341.31 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5532.23 | 22-JUL-16:00 | 523.07 | 12-JUL-15:00 |
August | 2879.63 | 05-AUG-14:09 | 3341.31 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5613.64 | 30-AUG-16:00 | 999.32 | 16-AUG-17:00 |
September | 2879.63 | 02-SEP-14:09 | 3341.31 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5706.27 | 09-SEP-17:00 | 1964.09 | 07-SEP-17:00 |
October | 2879.63 | 07-OCT-14:09 | 3341.31 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4612.44 | 05-OCT-15:00 | 3358.39 | 27-OCT-16:00 |
November | 2879.63 | 04-NOV-14:09 | 3341.31 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2824.95 | 01-NOV-14:00 | 5659.17 | 15-NOV-18:00 |
December | 2879.63 | 02-DEC-15:09 | 3341.31 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2844.13 | 13-DEC-15:00 | 8650.09 | 20-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 3341.31 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1449.48 | 519.70 | |||||
Maximum of Months | 2879.63 | 3341.31 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5706.27 | 8650.09 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1670.66 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.52 | 16-JAN-15:00 | 4347.45 | 04-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 1670.66 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.56 | 02-FEB-13:00 | 4746.26 | 04-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1670.66 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.78 | 26-MAR-14:00 | 4293.49 | 11-MAR-12:10 |
April | 1439.81 | 01-APR-14:09 | 1670.66 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2467.70 | 28-APR-15:00 | 1817.26 | 01-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 1670.66 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2630.77 | 07-MAY-14:00 | 296.63 | 31-MAY-13:00 |
June | 1439.81 | 03-JUN-14:09 | 1670.66 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2882.11 | 14-JUN-14:00 | 299.15 | 01-JUN-13:00 |
July | 1439.81 | 01-JUL-14:09 | 1670.66 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3160.12 | 22-JUL-16:00 | 298.43 | 12-JUL-15:00 |
August | 1439.81 | 05-AUG-14:09 | 1670.66 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3205.23 | 30-AUG-16:00 | 570.43 | 16-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 1670.66 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3255.15 | 09-SEP-17:00 | 1121.43 | 07-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 1670.66 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2633.34 | 05-OCT-15:00 | 1916.01 | 27-OCT-16:00 |
November | 1439.81 | 04-NOV-14:09 | 1670.66 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1613.30 | 01-NOV-14:00 | 3204.58 | 15-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 1670.66 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1623.40 | 13-DEC-15:00 | 4940.93 | 20-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.52 | 296.63 | |||||
Maximum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3255.15 | 4940.93 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1670.66 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.51 | 16-JAN-15:00 | 4347.45 | 04-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 1670.66 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.56 | 02-FEB-13:00 | 4746.26 | 04-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1670.66 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.77 | 26-MAR-14:00 | 4293.49 | 11-MAR-12:10 |
April | 1439.81 | 01-APR-14:09 | 1670.66 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2467.70 | 28-APR-15:00 | 1810.07 | 01-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 1670.66 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2630.76 | 07-MAY-14:00 | 296.63 | 31-MAY-13:00 |
June | 1439.81 | 03-JUN-14:09 | 1670.66 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2882.11 | 14-JUN-14:00 | 299.16 | 01-JUN-13:00 |
July | 1439.81 | 01-JUL-14:09 | 1670.66 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3160.11 | 22-JUL-16:00 | 298.44 | 12-JUL-15:00 |
August | 1439.81 | 05-AUG-14:09 | 1670.66 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3205.22 | 30-AUG-16:00 | 570.43 | 16-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 1670.66 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3255.15 | 09-SEP-17:00 | 1121.43 | 07-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 1670.66 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2633.34 | 05-OCT-15:00 | 1914.70 | 27-OCT-16:00 |
November | 1439.81 | 04-NOV-14:09 | 1670.66 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1613.29 | 01-NOV-14:00 | 3187.86 | 15-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 1670.66 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1623.40 | 13-DEC-15:00 | 4940.93 | 20-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.51 | 296.63 | |||||
Maximum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3255.15 | 4940.93 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1670.66 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.50 | 16-JAN-15:00 | 4347.45 | 04-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 1670.66 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.55 | 02-FEB-13:00 | 4746.26 | 04-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1670.66 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.76 | 26-MAR-14:00 | 4293.49 | 11-MAR-12:10 |
April | 1439.81 | 01-APR-14:09 | 1670.66 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2467.69 | 28-APR-15:00 | 1798.75 | 01-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 1670.66 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2630.76 | 07-MAY-14:00 | 296.64 | 31-MAY-13:00 |
June | 1439.81 | 03-JUN-14:09 | 1670.66 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2882.11 | 14-JUN-14:00 | 299.16 | 01-JUN-13:00 |
July | 1439.81 | 01-JUL-14:09 | 1670.66 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3160.11 | 22-JUL-16:00 | 298.44 | 12-JUL-15:00 |
August | 1439.81 | 05-AUG-14:09 | 1670.66 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3205.22 | 30-AUG-16:00 | 570.44 | 16-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 1670.66 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3255.15 | 09-SEP-17:00 | 1121.43 | 07-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 1670.66 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2633.34 | 05-OCT-15:00 | 1913.16 | 27-OCT-16:10 |
November | 1439.81 | 04-NOV-14:09 | 1670.66 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1613.29 | 01-NOV-14:00 | 3163.06 | 15-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 1670.66 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1623.39 | 13-DEC-15:00 | 4940.93 | 20-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 827.50 | 296.64 | |||||
Maximum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3255.15 | 4940.93 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1670.66 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 837.96 | 16-JAN-15:00 | 4402.46 | 04-JAN-18:00 |
February | 1439.81 | 04-FEB-15:09 | 1670.66 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1217.97 | 02-FEB-13:00 | 4885.57 | 04-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1670.66 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1640.33 | 26-MAR-14:00 | 4399.19 | 11-MAR-12:10 |
April | 1439.81 | 01-APR-14:09 | 1670.66 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2516.69 | 28-APR-15:00 | 1835.39 | 01-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 1670.66 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2683.02 | 07-MAY-14:00 | 301.12 | 31-MAY-13:00 |
June | 1439.81 | 03-JUN-14:09 | 1670.66 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2911.63 | 14-JUN-14:00 | 308.05 | 01-JUN-13:00 |
July | 1439.81 | 01-JUL-14:09 | 1670.66 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3183.30 | 22-JUL-16:00 | 304.35 | 12-JUL-15:00 |
August | 1439.81 | 05-AUG-14:09 | 1670.66 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3242.71 | 30-AUG-16:00 | 578.72 | 16-AUG-17:00 |
September | 1439.81 | 02-SEP-14:09 | 1670.66 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3324.50 | 09-SEP-17:00 | 1136.96 | 07-SEP-17:00 |
October | 1439.81 | 07-OCT-14:09 | 1670.66 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2666.70 | 05-OCT-15:00 | 1954.06 | 27-OCT-16:00 |
November | 1439.81 | 04-NOV-14:09 | 1670.66 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1629.04 | 01-NOV-14:00 | 3169.28 | 15-NOV-18:00 |
December | 1439.81 | 02-DEC-15:09 | 1670.66 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1647.65 | 13-DEC-15:00 | 4977.13 | 20-DEC-18:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 837.96 | 301.12 | |||||
Maximum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3324.50 | 4977.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28252.55 | 02-JAN-09:02 | 719.91 | 11001.85 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.06 |
February | 29908.79 | 28-FEB-09:02 | 899.88 | 13752.31 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.32 |
March | 28260.53 | 30-MAR-08:62 | 899.88 | 13752.31 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.79 |
April | 28672.83 | 25-APR-08:62 | 899.88 | 13752.31 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.21 |
May | 29186.43 | 07-MAY-07:02 | 899.88 | 1375.23 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | 0.00 |
June | 29863.30 | 11-JUN-07:02 | 899.88 | 1375.23 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.73 |
July | 29386.59 | 09-JUL-07:01 | 1259.84 | 1925.32 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 213.04 | 0.00 |
August | 31599.39 | 20-AUG-07:02 | 1079.86 | 1650.28 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.75 |
September | 29194.05 | 22-SEP-08:61 | 1259.84 | 19253.23 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.03 |
October | 42230.16 | 26-OCT-08:61 | 1259.84 | 19253.23 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.21 |
November | 31444.89 | 06-NOV-09:02 | 1079.86 | 16502.77 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.56 |
December | 33808.51 | 17-DEC-08:62 | 899.88 | 1375.23 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.68 |
Annual Sum or Average | |||||||||||
Minimum of Months | 28252.55 | 719.91 | 1375.23 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42230.16 | 1259.84 | 19253.23 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 213.04 | 450.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17445.83 | 02-JAN-09:02 | 359.95 | 6502.17 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.99 |
February | 17716.88 | 28-FEB-09:02 | 449.94 | 8127.72 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.06 |
March | 17459.24 | 30-MAR-08:62 | 449.94 | 8127.72 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.77 |
April | 17221.58 | 24-APR-08:62 | 449.94 | 8127.72 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.24 |
May | 18334.61 | 07-MAY-07:02 | 449.94 | 812.77 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8.25 | 0.00 |
June | 18088.89 | 11-JUN-07:02 | 449.94 | 812.77 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.78 |
July | 18235.75 | 09-JUL-07:01 | 629.92 | 1137.88 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 120.71 | 0.00 |
August | 18874.05 | 20-AUG-07:02 | 539.93 | 975.33 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.12 |
September | 17733.11 | 03-SEP-07:02 | 539.93 | 975.33 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 66.45 | 0.00 |
October | 23163.64 | 26-OCT-08:61 | 629.92 | 11378.81 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.77 |
November | 18630.45 | 06-NOV-09:02 | 539.93 | 9753.26 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.73 |
December | 19036.83 | 17-DEC-08:62 | 449.94 | 812.77 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.43 |
Annual Sum or Average | |||||||||||
Minimum of Months | 17221.58 | 359.95 | 812.77 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23163.64 | 629.92 | 11378.81 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 120.71 | 240.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20425.00 | 02-JAN-08:62 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.92 |
February | 19113.54 | 03-FEB-08:62 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.92 |
March | 20930.22 | 01-MAR-08:62 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.63 |
April | 16925.96 | 25-APR-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.34 |
May | 16285.66 | 12-MAY-07:01 | 629.92 | 10394.43 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.05 |
June | 15953.16 | 14-JUN-07:01 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 31.87 | 0.00 |
July | 13779.14 | 19-JUL-07:01 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 76.17 | 0.00 |
August | 15915.12 | 31-AUG-07:01 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.15 |
September | 15908.62 | 22-SEP-07:01 | 629.92 | 10394.43 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.49 |
October | 25696.54 | 17-OCT-07:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.63 |
November | 19468.94 | 05-NOV-08:62 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.56 |
December | 20698.00 | 17-DEC-09:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.46 |
Annual Sum or Average | |||||||||||
Minimum of Months | 13779.14 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25696.54 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 76.17 | 438.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20314.85 | 02-JAN-08:62 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.09 |
February | 18979.19 | 03-FEB-08:62 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.93 |
March | 20513.69 | 01-MAR-08:62 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.50 |
April | 16839.80 | 25-APR-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.65 |
May | 16218.68 | 12-MAY-07:01 | 629.92 | 10394.43 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.32 |
June | 15880.95 | 14-JUN-07:01 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 31.35 | 0.00 |
July | 13724.25 | 19-JUL-07:01 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 76.05 | 0.00 |
August | 15844.94 | 31-AUG-07:01 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.92 |
September | 15842.43 | 22-SEP-07:01 | 629.92 | 10394.43 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.35 |
October | 25599.48 | 17-OCT-07:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.42 |
November | 19385.78 | 05-NOV-08:62 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.60 |
December | 20595.27 | 17-DEC-09:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.02 |
Annual Sum or Average | |||||||||||
Minimum of Months | 13724.25 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25599.48 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 76.05 | 438.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20175.73 | 02-JAN-08:62 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.99 |
February | 18790.35 | 03-FEB-08:62 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.95 |
March | 18542.20 | 01-MAR-08:62 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.96 |
April | 16672.25 | 25-APR-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.97 |
May | 16072.12 | 12-MAY-07:01 | 629.92 | 10394.43 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.18 |
June | 15800.45 | 12-JUN-07:01 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.85 |
July | 13621.85 | 19-JUL-07:01 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 76.03 | 0.00 |
August | 15714.58 | 31-AUG-07:01 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 |
September | 15675.98 | 22-SEP-07:01 | 629.92 | 10394.43 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.51 |
October | 25456.72 | 17-OCT-07:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.61 |
November | 19245.80 | 05-NOV-08:62 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.37 |
December | 20441.94 | 17-DEC-09:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.26 |
Annual Sum or Average | |||||||||||
Minimum of Months | 13621.85 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25456.72 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 76.03 | 437.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32000.65 | 01-JAN-10:02 | 1979.74 | 8792.93 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.61 |
February | 27413.85 | 28-FEB-09:02 | 1979.74 | 8792.93 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.14 |
March | 26102.31 | 30-MAR-08:62 | 1979.74 | 8792.93 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.70 |
April | 26563.63 | 25-APR-08:62 | 1979.74 | 8792.93 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.55 |
May | 27048.07 | 12-MAY-08:61 | 2771.64 | 12310.11 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 |
June | 26490.93 | 10-JUN-08:61 | 2771.64 | 12310.11 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 174.62 | 0.00 |
July | 24178.09 | 14-JUL-08:61 | 2771.64 | 12310.11 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.30 |
August | 26770.70 | 31-AUG-08:61 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 139.82 | 0.00 |
September | 26396.39 | 22-SEP-08:61 | 2771.64 | 12310.11 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.73 |
October | 38698.74 | 26-OCT-08:61 | 2771.64 | 12310.11 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.29 |
November | 29434.24 | 05-NOV-09:02 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.28 |
December | 35239.55 | 17-DEC-10:02 | 2375.69 | 10551.52 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.30 |
Annual Sum or Average | |||||||||||
Minimum of Months | 24178.09 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38698.74 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 174.62 | 457.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16626.17 | 01-JAN-10:02 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.67 |
February | 14226.12 | 28-FEB-09:02 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.42 |
March | 13565.79 | 30-MAR-08:62 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.34 |
April | 13799.10 | 25-APR-08:62 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.34 |
May | 14065.15 | 12-MAY-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.18 |
June | 13774.53 | 10-JUN-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 104.04 | 0.00 |
July | 12548.75 | 14-JUL-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 |
August | 13939.82 | 31-AUG-08:61 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 84.99 | 0.00 |
September | 13719.39 | 22-SEP-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.17 |
October | 20143.59 | 26-OCT-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.12 |
November | 15296.86 | 05-NOV-09:02 | 791.89 | 3517.17 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.27 |
December | 18339.65 | 17-DEC-10:02 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.09 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12548.75 | 791.89 | 3517.17 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20143.59 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 104.04 | 251.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16486.27 | 01-JAN-10:02 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.77 |
February | 14088.74 | 28-FEB-09:02 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.63 |
March | 13430.07 | 30-MAR-08:62 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.60 |
April | 13672.86 | 25-APR-08:62 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.71 |
May | 13945.33 | 12-MAY-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 |
June | 13656.54 | 10-JUN-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 105.56 | 0.00 |
July | 12425.98 | 14-JUL-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.61 |
August | 13816.30 | 31-AUG-08:61 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 86.13 | 0.00 |
September | 13605.23 | 22-SEP-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.99 |
October | 19997.45 | 26-OCT-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.01 |
November | 15181.75 | 05-NOV-09:02 | 791.89 | 3517.17 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.11 |
December | 18199.64 | 17-DEC-10:02 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.58 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12425.98 | 791.89 | 3517.17 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19997.45 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 105.56 | 249.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16398.07 | 01-JAN-10:02 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.34 |
February | 13636.04 | 28-FEB-09:02 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.22 |
March | 11774.06 | 30-MAR-08:62 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.10 |
April | 13426.52 | 22-APR-08:62 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.99 |
May | 13918.15 | 12-MAY-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 |
June | 13636.48 | 10-JUN-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 108.21 | 0.00 |
July | 12393.42 | 18-JUL-08:61 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 110.87 | 0.00 |
August | 13847.53 | 31-AUG-08:61 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 86.56 | 0.00 |
September | 13604.27 | 22-SEP-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.38 |
October | 20012.91 | 26-OCT-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.70 |
November | 14547.74 | 05-NOV-09:02 | 791.89 | 3517.17 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.37 |
December | 18160.66 | 17-DEC-10:02 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.96 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11774.06 | 791.89 | 3517.17 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20012.91 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 110.87 | 245.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17509.76 | 01-JAN-10:02 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.15 |
February | 8567.85 | 28-FEB-09:02 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.78 |
March | 8470.25 | 07-MAR-09:02 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.32 |
April | 14073.92 | 23-APR-09:02 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 13.09 | 0.00 |
May | 14417.06 | 12-MAY-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 |
June | 14604.79 | 11-JUN-09:01 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 111.85 | 0.00 |
July | 13295.31 | 14-JUL-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.83 |
August | 15658.59 | 31-AUG-08:61 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 88.63 | 0.00 |
September | 14492.52 | 22-SEP-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.36 |
October | 22309.19 | 26-OCT-08:61 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.60 |
November | 15562.97 | 06-NOV-09:02 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.03 |
December | 20056.72 | 17-DEC-10:02 | 1187.84 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.87 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8470.25 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22309.19 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 111.85 | 282.87 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.718964E+11 | 77005.39 | 19-JAN-13:00 | 0.511668E+10 | 77908.62 | 10-JAN-09:09 |
February | 0.673970E+11 | 75405.19 | 24-FEB-12:00 | 0.523286E+10 | 95357.07 | 05-FEB-10:09 |
March | 0.771697E+11 | 77871.50 | 30-MAR-13:20 | 0.370254E+10 | 89318.21 | 11-MAR-12:09 |
April | 0.831046E+11 | 93271.31 | 28-APR-16:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.109317E+12 | 99309.86 | 30-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.110923E+12 | 106070.10 | 28-JUN-13:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.117552E+12 | 113920.87 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.118971E+12 | 105658.95 | 03-AUG-15:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.108743E+12 | 123506.62 | 10-SEP-13:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.105168E+12 | 111632.13 | 07-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.801303E+11 | 91346.18 | 07-NOV-13:09 | 608893.15 | 629.58 | 15-NOV-17:00 |
December | 0.764266E+11 | 84914.75 | 15-DEC-13:00 | 0.446393E+10 | 83502.46 | 20-DEC-17:00 |
Annual Sum or Average | 0.112680E+13 | 0.185166E+11 | ||||
Minimum of Months | 0.673970E+11 | 75405.19 | 0.00 | 0.00 | ||
Maximum of Months | 0.118971E+12 | 123506.62 | 0.523286E+10 | 95357.07 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.366903E+11 | 0.633647E+10 | 0.108804E+11 | 0.00 | 0.753301E+10 | 0.00 | 0.00 | 0.551779E+10 | 0.00 | 0.00 | 0.00 | 0.493838E+10 | 0.00 |
February | 0.332186E+11 | 0.542744E+10 | 0.985143E+10 | 0.00 | 0.685831E+10 | 0.00 | 0.00 | 0.758272E+10 | 0.00 | 0.00 | 0.00 | 0.445853E+10 | 0.00 |
March | 0.372231E+11 | 0.556359E+10 | 0.110523E+11 | 0.00 | 0.765362E+10 | 0.00 | 0.00 | 0.107594E+11 | 0.00 | 0.00 | 0.00 | 0.491765E+10 | 0.00 |
April | 0.356035E+11 | 0.495241E+10 | 0.105581E+11 | 0.00 | 0.731752E+10 | 0.00 | 0.00 | 0.200172E+11 | 0.00 | 0.00 | 0.00 | 0.465596E+10 | 0.00 |
May | 0.369426E+11 | 0.472827E+10 | 0.109629E+11 | 0.00 | 0.810557E+10 | 0.00 | 0.00 | 0.438454E+11 | 0.00 | 0.00 | 0.00 | 0.473256E+10 | 0.00 |
June | 0.359818E+11 | 0.436383E+10 | 0.106818E+11 | 0.00 | 0.831563E+10 | 0.00 | 0.00 | 0.470486E+11 | 0.00 | 0.00 | 0.00 | 0.453087E+10 | 0.00 |
July | 0.365926E+11 | 0.462126E+10 | 0.108460E+11 | 0.00 | 0.902414E+10 | 0.00 | 0.00 | 0.518474E+11 | 0.00 | 0.00 | 0.00 | 0.462043E+10 | 0.00 |
August | 0.371948E+11 | 0.493636E+10 | 0.110454E+11 | 0.00 | 0.910654E+10 | 0.00 | 0.00 | 0.520255E+11 | 0.00 | 0.00 | 0.00 | 0.466235E+10 | 0.00 |
September | 0.356318E+11 | 0.520211E+10 | 0.105649E+11 | 0.00 | 0.827384E+10 | 0.00 | 0.00 | 0.445333E+11 | 0.00 | 0.00 | 0.00 | 0.453741E+10 | 0.00 |
October | 0.366903E+11 | 0.582815E+10 | 0.108804E+11 | 0.00 | 0.833829E+10 | 0.00 | 0.00 | 0.386779E+11 | 0.00 | 0.00 | 0.00 | 0.475298E+10 | 0.00 |
November | 0.355468E+11 | 0.601662E+10 | 0.105443E+11 | 0.00 | 0.736539E+10 | 0.00 | 0.00 | 0.159781E+11 | 0.00 | 0.00 | 0.00 | 0.467905E+10 | 0.00 |
December | 0.366210E+11 | 0.643457E+10 | 0.108529E+11 | 0.00 | 0.755791E+10 | 0.00 | 0.00 | 0.100566E+11 | 0.00 | 0.00 | 0.00 | 0.490373E+10 | 0.00 |
Annual Sum or Average | 0.433937E+12 | 0.644111E+11 | 0.128721E+12 | 0.954498E+11 | 0.00 | 0.347890E+12 | 0.563899E+11 | ||||||
Minimum of Months | 0.332186E+11 | 0.436383E+10 | 0.985143E+10 | 0.00 | 0.685831E+10 | 0.00 | 0.00 | 0.551779E+10 | 0.00 | 0.00 | 0.00 | 0.445853E+10 | 0.00 |
Maximum of Months | 0.372231E+11 | 0.643457E+10 | 0.110523E+11 | 0.00 | 0.910654E+10 | 0.00 | 0.00 | 0.520255E+11 | 0.00 | 0.00 | 0.00 | 0.493838E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.511668E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.523286E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.370254E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 608893.15 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.446393E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185166E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.523286E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 26802.39 | 01-JAN-11:09 | 4954.41 | 01-JAN-06:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 6597.83 | 10-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 26802.39 | 01-FEB-10:09 | 4954.41 | 01-FEB-06:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 6937.94 | 05-FEB-10:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 26802.39 | 01-MAR-10:09 | 4954.41 | 01-MAR-06:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 6822.49 | 11-MAR-12:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26802.39 | 01-APR-09:09 | 4954.41 | 01-APR-05:10 | 8089.53 | 01-APR-09:09 | 0.00 | 7188.17 | 28-APR-16:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 26802.39 | 01-MAY-09:09 | 4954.41 | 01-MAY-05:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 7949.64 | 30-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 26802.39 | 01-JUN-09:09 | 4954.41 | 01-JUN-05:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 9102.81 | 28-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 26802.39 | 01-JUL-09:09 | 4954.41 | 01-JUL-05:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 10236.18 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 26802.39 | 01-AUG-09:09 | 4954.41 | 01-AUG-05:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 9061.39 | 07-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 26802.39 | 01-SEP-09:09 | 4954.41 | 01-SEP-05:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 11623.24 | 10-SEP-12:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 26802.39 | 01-OCT-10:09 | 4954.41 | 01-OCT-05:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 10291.82 | 07-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26802.39 | 01-NOV-09:09 | 4954.41 | 01-NOV-05:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 7081.53 | 02-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26802.39 | 01-DEC-10:09 | 4954.41 | 01-DEC-06:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 6835.63 | 16-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 26802.39 | 4954.41 | 8089.53 | 0.00 | 6597.83 | 0.00 | 0.00 | |||||
Maximum of Months | 26802.39 | 4954.41 | 8089.53 | 0.00 | 11623.24 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 28435.96 | 19-JAN-13:00 | 0.00 | 0.00 | 0.00 | 11236.49 | 14-JAN-14:30 | 0.00 |
February | 30669.69 | 24-FEB-13:09 | 0.00 | 0.00 | 0.00 | 7978.28 | 03-FEB-15:00 | 0.00 |
March | 34028.14 | 30-MAR-12:00 | 0.00 | 0.00 | 0.00 | 9089.62 | 19-MAR-15:39 | 0.00 |
April | 47224.60 | 28-APR-16:10 | 0.00 | 0.00 | 0.00 | 7554.80 | 21-APR-13:30 | 0.00 |
May | 51076.28 | 24-MAY-12:00 | 0.00 | 0.00 | 0.00 | 7552.03 | 13-MAY-12:09 | 0.00 |
June | 57944.06 | 28-JUN-13:00 | 0.00 | 0.00 | 0.00 | 7499.92 | 03-JUN-09:50 | 0.00 |
July | 65472.15 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 7541.81 | 14-JUL-13:20 | 0.00 |
August | 57673.40 | 28-AUG-12:00 | 0.00 | 0.00 | 0.00 | 7680.10 | 19-AUG-11:00 | 0.00 |
September | 71682.25 | 10-SEP-13:30 | 0.00 | 0.00 | 0.00 | 7529.29 | 26-SEP-17:49 | 0.00 |
October | 63117.43 | 07-OCT-12:00 | 0.00 | 0.00 | 0.00 | 7549.99 | 04-OCT-13:09 | 0.00 |
November | 45497.18 | 02-NOV-12:00 | 0.00 | 0.00 | 0.00 | 7563.88 | 30-NOV-13:20 | 0.00 |
December | 37438.58 | 15-DEC-13:00 | 0.00 | 0.00 | 0.00 | 11797.53 | 11-DEC-13:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 28435.96 | 0.00 | 0.00 | 0.00 | 7499.92 | 0.00 | ||
Maximum of Months | 71682.25 | 0.00 | 0.00 | 0.00 | 11797.53 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 77005.39 | 19-JAN-13:00 | 26802.39 | 8089.53 | 0.00 | 0.00 | 5090.22 | 0.00 | 0.00 | 28435.96 | 0.00 |
February | 75405.19 | 24-FEB-12:00 | 26802.39 | 8089.53 | 0.00 | 0.00 | 5090.22 | 0.00 | 0.00 | 29977.76 | 0.00 |
March | 77871.50 | 30-MAR-13:20 | 26802.39 | 8089.53 | 0.00 | 0.00 | 5090.22 | 0.00 | 0.00 | 32587.41 | 0.00 |
April | 93271.31 | 28-APR-16:10 | 26802.39 | 8089.53 | 0.00 | 0.00 | 7188.17 | 0.00 | 0.00 | 47224.60 | 0.00 |
May | 99309.86 | 30-MAY-12:00 | 26802.39 | 8089.53 | 0.00 | 0.00 | 7949.64 | 0.00 | 0.00 | 51029.87 | 0.00 |
June | 106070.10 | 28-JUN-13:39 | 26802.39 | 8089.53 | 0.00 | 0.00 | 8930.89 | 0.00 | 0.00 | 56812.82 | 0.00 |
July | 113920.87 | 22-JUL-15:00 | 26802.39 | 8089.53 | 0.00 | 0.00 | 10236.18 | 0.00 | 0.00 | 65472.15 | 0.00 |
August | 105658.95 | 03-AUG-15:09 | 26802.39 | 8089.53 | 0.00 | 0.00 | 8807.63 | 0.00 | 0.00 | 57272.47 | 0.00 |
September | 123506.62 | 10-SEP-13:39 | 26802.39 | 8089.53 | 0.00 | 0.00 | 11548.76 | 0.00 | 0.00 | 71651.15 | 0.00 |
October | 111632.13 | 07-OCT-12:00 | 26802.39 | 8089.53 | 0.00 | 0.00 | 10291.82 | 0.00 | 0.00 | 63117.43 | 0.00 |
November | 91346.18 | 07-NOV-13:09 | 26802.39 | 8089.53 | 0.00 | 0.00 | 6586.45 | 0.00 | 0.00 | 42308.50 | 0.00 |
December | 84914.75 | 15-DEC-13:00 | 26802.39 | 8089.53 | 0.00 | 0.00 | 5517.63 | 0.00 | 0.00 | 37438.58 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 75405.19 | 26802.39 | 8089.53 | 0.00 | 0.00 | 5090.22 | 0.00 | 0.00 | 28435.96 | 0.00 | |
Maximum of Months | 123506.62 | 26802.39 | 8089.53 | 0.00 | 0.00 | 11548.76 | 0.00 | 0.00 | 71651.15 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 77908.62 | 10-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 95357.07 | 05-FEB-10:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 89318.21 | 11-MAR-12:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 629.58 | 15-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 83502.46 | 20-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 95357.07 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.47 | 0.67 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.52 | 2.67 | 24.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.53 | 2.17 | 24.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.52 | 1.00 | 24.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.56 | 0.83 | 24.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.33 | 24.52 | 7.33 | 24.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.56 | 2.67 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.33 | 24.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.48 | 0.33 | 24.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.33 | 24.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.33 | 24.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.52 | 1.17 | 24.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.54 | 4.00 | 24.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.55 | 2.17 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.55 | 1.83 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.54 | 1.17 | 24.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.67 | 24.54 | 10.67 | 24.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.55 | 4.00 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.47 | 0.83 | 24.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.51 | 1.67 | 24.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.55 | 4.00 | 24.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.55 | 2.33 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.56 | 1.83 | 24.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.55 | 1.17 | 24.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.83 | 24.54 | 11.83 | 24.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.56 | 4.00 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.50 | 24.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.53 | 1.00 | 24.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.55 | 3.67 | 24.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.55 | 2.17 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.55 | 1.83 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.54 | 1.17 | 24.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.33 | 24.54 | 10.33 | 24.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.55 | 3.67 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.54 | 0.83 | 24.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.60 | 1.17 | 24.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.64 | 3.67 | 24.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.64 | 2.33 | 24.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.65 | 2.00 | 24.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.58 | 1.33 | 24.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.33 | 24.62 | 11.33 | 24.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.65 | 3.67 | 24.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.52 | 0.50 | 24.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.58 | 0.83 | 24.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.62 | 3.00 | 24.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.66 | 1.67 | 24.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.63 | 1.67 | 24.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.58 | 0.83 | 24.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.50 | 24.61 | 8.50 | 24.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.66 | 3.00 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.53 | 0.33 | 24.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.56 | 0.83 | 24.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.63 | 2.67 | 24.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.68 | 1.50 | 24.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.63 | 1.67 | 24.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.58 | 0.83 | 24.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.83 | 24.62 | 7.83 | 24.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.68 | 2.67 | 24.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.33 | 24.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.53 | 0.83 | 24.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.65 | 2.33 | 24.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.68 | 1.50 | 24.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.62 | 1.67 | 24.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.60 | 0.67 | 24.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.33 | 24.62 | 7.33 | 24.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.68 | 2.33 | 24.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.56 | 0.17 | 24.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.50 | 0.50 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.64 | 2.33 | 24.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.59 | 1.67 | 24.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.64 | 1.50 | 24.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.60 | 0.67 | 24.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.83 | 24.61 | 6.83 | 24.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.64 | 2.33 | 24.64 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 324.50 | 22.04 | 157.17 | 23.80 | 25.83 | 23.33 |
February | 242.33 | 22.49 | 224.83 | 23.81 | 48.00 | 23.52 |
March | 216.33 | 22.46 | 216.33 | 23.86 | 24.50 | 23.50 |
April | 66.33 | 23.73 | 355.17 | 23.91 | 38.67 | 23.93 |
May | 74.00 | 24.20 | 496.00 | 23.96 | 74.00 | 24.20 |
June | 55.33 | 24.32 | 480.00 | 23.97 | 55.33 | 24.32 |
July | 141.00 | 24.18 | 496.00 | 23.97 | 141.00 | 24.18 |
August | 98.17 | 24.33 | 496.00 | 23.99 | 98.17 | 24.33 |
September | 109.17 | 24.18 | 480.00 | 23.96 | 109.17 | 24.18 |
October | 73.50 | 24.03 | 450.67 | 23.96 | 66.33 | 24.10 |
November | 78.17 | 23.50 | 322.67 | 23.93 | 20.50 | 24.19 |
December | 217.33 | 22.38 | 223.33 | 23.88 | 30.17 | 23.81 |
Annual Sum or Average | 1696.17 | 23.04 | 4398.17 | 23.94 | 731.67 | 24.08 |
Minimum of Months | 55.33 | 22.04 | 157.17 | 23.80 | 20.50 | 23.33 |
Maximum of Months | 324.50 | 24.33 | 496.00 | 23.99 | 141.00 | 24.33 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 274.33 | 22.68 | 153.33 | 23.90 | 9.83 | 23.57 |
February | 172.00 | 22.80 | 216.67 | 23.88 | 19.33 | 23.73 |
March | 157.67 | 22.79 | 213.67 | 23.92 | 3.67 | 23.89 |
April | 27.00 | 23.76 | 345.17 | 23.91 | 8.67 | 23.89 |
May | 34.33 | 24.01 | 494.83 | 23.97 | 34.33 | 24.01 |
June | 27.17 | 23.89 | 480.00 | 23.97 | 27.17 | 23.89 |
July | 89.67 | 23.95 | 496.00 | 23.97 | 89.67 | 23.95 |
August | 57.67 | 24.01 | 496.00 | 23.99 | 57.67 | 24.01 |
September | 71.83 | 23.96 | 480.00 | 23.96 | 71.83 | 23.96 |
October | 47.67 | 23.87 | 438.33 | 23.97 | 42.00 | 23.92 |
November | 42.50 | 23.62 | 307.67 | 23.94 | 10.00 | 23.89 |
December | 173.67 | 22.74 | 228.17 | 23.92 | 15.00 | 23.89 |
Annual Sum or Average | 1175.50 | 23.14 | 4349.83 | 23.95 | 389.17 | 23.93 |
Minimum of Months | 27.00 | 22.68 | 153.33 | 23.88 | 3.67 | 23.57 |
Maximum of Months | 274.33 | 24.01 | 496.00 | 23.99 | 89.67 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 233.33 | 22.19 | 118.17 | 23.90 | 14.83 | 23.58 |
February | 156.50 | 22.53 | 167.50 | 23.90 | 26.00 | 23.66 |
March | 144.67 | 22.52 | 167.50 | 23.98 | 12.00 | 24.05 |
April | 49.17 | 23.89 | 275.00 | 24.01 | 31.67 | 24.11 |
May | 72.50 | 24.33 | 375.00 | 24.08 | 72.50 | 24.33 |
June | 63.67 | 24.52 | 366.00 | 24.09 | 63.67 | 24.52 |
July | 137.50 | 24.32 | 369.00 | 24.11 | 137.50 | 24.32 |
August | 99.17 | 24.34 | 379.00 | 24.09 | 99.17 | 24.34 |
September | 114.33 | 24.29 | 360.00 | 24.08 | 114.33 | 24.29 |
October | 74.83 | 24.22 | 335.83 | 24.08 | 70.00 | 24.28 |
November | 52.67 | 23.68 | 243.17 | 23.99 | 24.50 | 24.21 |
December | 161.00 | 22.45 | 168.67 | 23.96 | 25.50 | 24.00 |
Annual Sum or Average | 1359.33 | 23.30 | 3324.83 | 24.05 | 691.67 | 24.26 |
Minimum of Months | 49.17 | 22.19 | 118.17 | 23.90 | 12.00 | 23.58 |
Maximum of Months | 233.33 | 24.52 | 379.00 | 24.11 | 137.50 | 24.52 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 240.67 | 22.14 | 117.00 | 23.89 | 16.33 | 23.56 |
February | 165.50 | 22.51 | 164.00 | 23.89 | 26.67 | 23.62 |
March | 158.50 | 22.57 | 160.83 | 23.98 | 14.00 | 24.04 |
April | 50.83 | 23.87 | 274.17 | 24.01 | 31.83 | 24.11 |
May | 72.33 | 24.34 | 375.00 | 24.08 | 72.33 | 24.34 |
June | 62.33 | 24.54 | 366.00 | 24.09 | 62.33 | 24.54 |
July | 134.00 | 24.34 | 369.00 | 24.11 | 134.00 | 24.34 |
August | 97.67 | 24.35 | 379.00 | 24.09 | 97.67 | 24.35 |
September | 112.67 | 24.30 | 360.00 | 24.08 | 112.67 | 24.30 |
October | 73.50 | 24.22 | 335.50 | 24.08 | 68.83 | 24.28 |
November | 54.50 | 23.66 | 237.17 | 23.99 | 24.67 | 24.21 |
December | 167.83 | 22.43 | 162.17 | 23.96 | 26.00 | 23.96 |
Annual Sum or Average | 1390.33 | 23.26 | 3299.83 | 24.05 | 687.33 | 24.26 |
Minimum of Months | 50.83 | 22.14 | 117.00 | 23.89 | 14.00 | 23.56 |
Maximum of Months | 240.67 | 24.54 | 379.00 | 24.11 | 134.00 | 24.54 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 250.00 | 22.06 | 115.33 | 23.85 | 20.17 | 23.42 |
February | 180.33 | 22.47 | 162.17 | 23.87 | 30.17 | 23.55 |
March | 174.50 | 22.56 | 152.50 | 23.97 | 17.67 | 23.98 |
April | 57.50 | 23.84 | 271.83 | 24.00 | 35.33 | 24.09 |
May | 75.00 | 24.30 | 375.00 | 24.08 | 75.00 | 24.30 |
June | 67.50 | 24.50 | 366.00 | 24.09 | 67.50 | 24.50 |
July | 141.33 | 24.31 | 369.00 | 24.10 | 141.33 | 24.31 |
August | 102.00 | 24.31 | 379.00 | 24.09 | 102.00 | 24.31 |
September | 119.83 | 24.28 | 360.00 | 24.08 | 119.83 | 24.28 |
October | 78.00 | 24.20 | 333.67 | 24.07 | 72.67 | 24.27 |
November | 64.67 | 23.61 | 226.67 | 23.99 | 27.83 | 24.16 |
December | 182.67 | 22.44 | 158.67 | 23.94 | 30.00 | 23.89 |
Annual Sum or Average | 1493.33 | 23.23 | 3269.83 | 24.04 | 739.50 | 24.22 |
Minimum of Months | 57.50 | 22.06 | 115.33 | 23.85 | 17.67 | 23.42 |
Maximum of Months | 250.00 | 24.50 | 379.00 | 24.10 | 141.33 | 24.50 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 265.67 | 22.05 | 92.50 | 23.73 | 38.17 | 23.48 |
February | 187.50 | 22.35 | 147.17 | 23.75 | 38.50 | 23.33 |
March | 208.50 | 22.60 | 130.67 | 23.89 | 34.17 | 23.79 |
April | 76.50 | 23.78 | 237.83 | 23.93 | 38.33 | 24.01 |
May | 92.67 | 24.08 | 344.00 | 23.96 | 92.67 | 24.08 |
June | 76.67 | 24.14 | 336.00 | 23.96 | 76.67 | 24.14 |
July | 167.67 | 24.09 | 338.00 | 23.99 | 167.67 | 24.09 |
August | 115.17 | 24.05 | 348.00 | 23.96 | 115.17 | 24.05 |
September | 143.67 | 24.09 | 330.00 | 23.98 | 143.67 | 24.09 |
October | 94.67 | 24.03 | 302.00 | 23.96 | 87.50 | 24.08 |
November | 92.67 | 23.53 | 191.33 | 23.92 | 40.50 | 23.94 |
December | 201.17 | 22.43 | 136.50 | 23.86 | 36.83 | 23.73 |
Annual Sum or Average | 1722.50 | 23.16 | 2934.00 | 23.94 | 909.83 | 23.99 |
Minimum of Months | 76.50 | 22.05 | 92.50 | 23.73 | 34.17 | 23.33 |
Maximum of Months | 265.67 | 24.14 | 348.00 | 23.99 | 167.67 | 24.14 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 271.83 | 22.03 | 89.83 | 23.71 | 39.50 | 23.45 |
February | 191.67 | 22.32 | 146.83 | 23.72 | 41.00 | 23.25 |
March | 217.17 | 22.60 | 128.33 | 23.87 | 36.83 | 23.72 |
April | 85.17 | 23.78 | 230.67 | 23.93 | 43.50 | 24.00 |
May | 96.50 | 24.08 | 344.00 | 23.96 | 96.50 | 24.08 |
June | 88.50 | 24.09 | 336.00 | 23.96 | 88.50 | 24.09 |
July | 179.17 | 24.07 | 338.00 | 23.99 | 179.17 | 24.07 |
August | 120.83 | 24.03 | 348.00 | 23.96 | 120.83 | 24.03 |
September | 155.50 | 24.07 | 330.00 | 23.98 | 155.50 | 24.07 |
October | 102.33 | 24.01 | 297.50 | 23.96 | 92.17 | 24.06 |
November | 106.00 | 23.54 | 171.67 | 23.92 | 43.50 | 23.94 |
December | 212.50 | 22.46 | 127.67 | 23.85 | 39.33 | 23.69 |
Annual Sum or Average | 1827.17 | 23.17 | 2888.50 | 23.93 | 976.33 | 23.97 |
Minimum of Months | 85.17 | 22.03 | 89.83 | 23.71 | 36.83 | 23.25 |
Maximum of Months | 271.83 | 24.09 | 348.00 | 23.99 | 179.17 | 24.09 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 276.17 | 22.03 | 89.83 | 23.68 | 41.67 | 23.41 |
February | 194.67 | 22.29 | 146.00 | 23.70 | 42.50 | 23.21 |
March | 221.83 | 22.59 | 126.67 | 23.86 | 38.83 | 23.71 |
April | 89.67 | 23.76 | 229.67 | 23.92 | 45.17 | 24.00 |
May | 99.00 | 24.08 | 344.00 | 23.96 | 99.00 | 24.08 |
June | 92.17 | 24.08 | 336.00 | 23.96 | 92.17 | 24.08 |
July | 185.17 | 24.07 | 338.00 | 23.99 | 185.17 | 24.07 |
August | 125.33 | 24.02 | 348.00 | 23.96 | 125.33 | 24.02 |
September | 160.00 | 24.06 | 330.00 | 23.98 | 160.00 | 24.06 |
October | 104.67 | 24.01 | 297.33 | 23.96 | 93.50 | 24.06 |
November | 109.67 | 23.53 | 167.33 | 23.92 | 44.67 | 23.94 |
December | 217.50 | 22.45 | 125.67 | 23.83 | 40.50 | 23.66 |
Annual Sum or Average | 1875.83 | 23.17 | 2878.50 | 23.93 | 1008.50 | 23.96 |
Minimum of Months | 89.67 | 22.03 | 89.83 | 23.68 | 38.83 | 23.21 |
Maximum of Months | 276.17 | 24.08 | 348.00 | 23.99 | 185.17 | 24.08 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 278.67 | 22.00 | 89.17 | 23.64 | 43.67 | 23.36 |
February | 202.00 | 22.27 | 146.33 | 23.66 | 48.17 | 23.16 |
March | 229.67 | 22.56 | 125.67 | 23.84 | 42.50 | 23.65 |
April | 99.17 | 23.73 | 226.17 | 23.92 | 49.67 | 23.98 |
May | 101.67 | 24.07 | 344.00 | 23.96 | 101.67 | 24.07 |
June | 94.50 | 24.07 | 336.00 | 23.96 | 94.50 | 24.07 |
July | 185.00 | 24.07 | 338.00 | 23.99 | 185.00 | 24.07 |
August | 126.00 | 24.02 | 348.00 | 23.96 | 126.00 | 24.02 |
September | 160.50 | 24.06 | 330.00 | 23.98 | 160.50 | 24.06 |
October | 105.33 | 24.00 | 296.83 | 23.96 | 93.17 | 24.06 |
November | 113.83 | 23.50 | 163.83 | 23.92 | 45.33 | 23.94 |
December | 225.67 | 22.43 | 123.33 | 23.82 | 43.00 | 23.64 |
Annual Sum or Average | 1922.00 | 23.15 | 2867.33 | 23.92 | 1033.17 | 23.94 |
Minimum of Months | 94.50 | 22.00 | 89.17 | 23.64 | 42.50 | 23.16 |
Maximum of Months | 278.67 | 24.07 | 348.00 | 23.99 | 185.00 | 24.07 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 281.83 | 21.98 | 93.67 | 23.54 | 48.33 | 23.19 |
February | 210.33 | 22.22 | 151.33 | 23.53 | 58.33 | 22.93 |
March | 238.17 | 22.50 | 131.67 | 23.69 | 53.67 | 23.33 |
April | 116.17 | 23.64 | 218.33 | 23.92 | 56.00 | 23.95 |
May | 107.83 | 24.06 | 344.00 | 23.96 | 107.83 | 24.06 |
June | 83.33 | 24.12 | 336.00 | 23.96 | 83.33 | 24.12 |
July | 159.50 | 24.10 | 338.00 | 23.99 | 159.50 | 24.10 |
August | 111.00 | 24.07 | 348.00 | 23.96 | 111.00 | 24.07 |
September | 136.67 | 24.10 | 330.00 | 23.98 | 136.67 | 24.10 |
October | 95.50 | 24.00 | 298.67 | 23.97 | 82.50 | 24.10 |
November | 114.67 | 23.44 | 168.33 | 23.92 | 42.83 | 23.95 |
December | 231.00 | 22.38 | 129.00 | 23.75 | 46.67 | 23.45 |
Annual Sum or Average | 1886.00 | 23.08 | 2887.00 | 23.90 | 986.67 | 23.89 |
Minimum of Months | 83.33 | 21.98 | 93.67 | 23.53 | 42.83 | 22.93 |
Maximum of Months | 281.83 | 24.12 | 348.00 | 23.99 | 159.50 | 24.12 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 22.67896 | 42.71324 | 0.11578 | 7.85375 |
February | 448.00000 | 23.12892 | 46.37243 | 0.24713 | 8.94844 |
March | 496.00000 | 23.25759 | 44.86644 | 0.26193 | 8.68231 |
April | 480.00000 | 23.87992 | 51.50412 | 0.48543 | 10.21057 |
May | 496.00000 | 23.97714 | 59.25827 | -0.2443 | 6.38997 |
June | 480.00000 | 23.98700 | 58.89232 | -0.2230 | 6.22989 |
July | 496.00000 | 23.99324 | 62.46566 | -0.1846 | 5.94356 |
August | 496.00000 | 24.00837 | 60.51014 | -0.1806 | 5.94704 |
September | 480.00000 | 23.98435 | 61.38150 | -0.1948 | 6.01939 |
October | 496.00000 | 23.96192 | 54.17230 | 0.58911 | 12.59532 |
November | 480.00000 | 23.84620 | 46.46375 | 0.45940 | 9.93927 |
December | 496.00000 | 23.22386 | 44.51447 | 0.27473 | 8.80939 |
Annual Sum or Average | 5840.00000 | 23.66210 | 52.79232 | 0.11596 | 8.12436 |
Minimum of Months | 448.00000 | 22.67896 | 42.71324 | -0.2443 | 5.94356 |
Maximum of Months | 496.00000 | 24.00837 | 62.46566 | 0.58911 | 12.59532 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.21690 | 40.79664 | 0.22222 | 7.63895 |
February | 448.00000 | 23.46325 | 44.46394 | 0.31327 | 8.75007 |
March | 496.00000 | 23.53802 | 42.73468 | 0.31779 | 8.44893 |
April | 480.00000 | 23.90285 | 48.66588 | 0.47769 | 9.97868 |
May | 496.00000 | 23.98766 | 55.79610 | -0.2681 | 6.67481 |
June | 480.00000 | 23.99534 | 55.84100 | -0.2500 | 6.51999 |
July | 496.00000 | 23.99715 | 59.40212 | -0.2160 | 6.21703 |
August | 496.00000 | 24.01090 | 57.82937 | -0.2171 | 6.25141 |
September | 480.00000 | 23.98756 | 58.37864 | -0.2297 | 6.34068 |
October | 496.00000 | 23.96671 | 51.66761 | 0.56356 | 11.94306 |
November | 480.00000 | 23.89722 | 44.73139 | 0.45915 | 9.75277 |
December | 496.00000 | 23.49545 | 43.09505 | 0.32623 | 8.69155 |
Annual Sum or Average | 5840.00000 | 23.78920 | 50.31361 | 0.12348 | 8.09480 |
Minimum of Months | 448.00000 | 23.21690 | 40.79664 | -0.2681 | 6.21703 |
Maximum of Months | 496.00000 | 24.01090 | 59.40212 | 0.56356 | 11.94306 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.83631 | 41.05878 | 0.14946 | 7.77875 |
February | 336.00000 | 23.26450 | 45.56854 | 0.28363 | 9.02700 |
March | 379.00000 | 23.38280 | 43.88779 | 0.29429 | 8.78545 |
April | 360.00000 | 23.96028 | 50.90507 | 0.50629 | 10.71145 |
May | 375.00000 | 24.07204 | 59.18662 | -0.2112 | 6.32027 |
June | 366.00000 | 24.08289 | 59.30159 | -0.1902 | 6.20517 |
July | 369.00000 | 24.09714 | 63.26466 | -0.1481 | 5.97393 |
August | 379.00000 | 24.08510 | 61.46680 | -0.1586 | 5.97661 |
September | 360.00000 | 24.07496 | 62.32122 | -0.1670 | 6.03655 |
October | 371.00000 | 24.04756 | 54.35618 | 0.60808 | 13.22150 |
November | 360.00000 | 23.90303 | 46.06131 | 0.47458 | 10.21599 |
December | 369.00000 | 23.28595 | 44.01859 | 0.29314 | 8.95437 |
Annual Sum or Average | 4395.00000 | 23.75987 | 52.66662 | 0.14232 | 8.25387 |
Minimum of Months | 336.00000 | 22.83631 | 41.05878 | -0.2112 | 5.97393 |
Maximum of Months | 379.00000 | 24.09714 | 63.26466 | 0.60808 | 13.22150 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.76676 | 41.28432 | 0.12877 | 7.75810 |
February | 336.00000 | 23.21809 | 45.76104 | 0.26863 | 8.95158 |
March | 379.00000 | 23.35049 | 44.01838 | 0.28329 | 8.75028 |
April | 360.00000 | 23.95664 | 50.94461 | 0.50413 | 10.67536 |
May | 375.00000 | 24.07262 | 59.13111 | -0.2102 | 6.31670 |
June | 366.00000 | 24.08372 | 59.22583 | -0.1887 | 6.20025 |
July | 369.00000 | 24.09784 | 63.13859 | -0.1462 | 5.97053 |
August | 379.00000 | 24.08568 | 61.36753 | -0.1571 | 5.97306 |
September | 360.00000 | 24.07552 | 62.21763 | -0.1657 | 6.03496 |
October | 371.00000 | 24.04765 | 54.29360 | 0.60862 | 13.24016 |
November | 360.00000 | 23.89662 | 46.11163 | 0.47146 | 10.17142 |
December | 369.00000 | 23.25011 | 44.11951 | 0.28140 | 8.90909 |
Annual Sum or Average | 4395.00000 | 23.74411 | 52.68351 | 0.13770 | 8.23306 |
Minimum of Months | 336.00000 | 22.76676 | 41.28432 | -0.2102 | 5.97053 |
Maximum of Months | 379.00000 | 24.09784 | 63.13859 | 0.60862 | 13.24016 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.66960 | 41.67369 | 0.10019 | 7.73454 |
February | 336.00000 | 23.14140 | 46.16594 | 0.24457 | 8.82288 |
March | 379.00000 | 23.28687 | 44.37427 | 0.26246 | 8.65077 |
April | 360.00000 | 23.94463 | 51.27870 | 0.49707 | 10.54457 |
May | 375.00000 | 24.06786 | 59.44098 | -0.2159 | 6.34701 |
June | 366.00000 | 24.07922 | 59.51214 | -0.1941 | 6.22261 |
July | 369.00000 | 24.09440 | 63.43438 | -0.1505 | 5.97898 |
August | 379.00000 | 24.08211 | 61.65787 | -0.1616 | 5.98472 |
September | 360.00000 | 24.07155 | 62.52775 | -0.1701 | 6.04999 |
October | 371.00000 | 24.04236 | 54.54234 | 0.60492 | 13.14679 |
November | 360.00000 | 23.87774 | 46.37778 | 0.46290 | 10.04173 |
December | 369.00000 | 23.19045 | 44.39854 | 0.26206 | 8.81357 |
Annual Sum or Average | 4395.00000 | 23.71487 | 52.99717 | 0.12640 | 8.18281 |
Minimum of Months | 336.00000 | 22.66960 | 41.67369 | -0.2159 | 5.97898 |
Maximum of Months | 379.00000 | 24.09440 | 63.43438 | 0.60492 | 13.14679 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.45202 | 43.25075 | 0.03720 | 7.73999 |
February | 308.00000 | 22.95006 | 47.70583 | 0.18633 | 8.49030 |
March | 348.00000 | 23.11893 | 45.97310 | 0.20911 | 8.35418 |
April | 330.00000 | 23.87659 | 52.52713 | 0.46876 | 9.97925 |
May | 344.00000 | 23.98013 | 61.04258 | -0.2519 | 6.57065 |
June | 336.00000 | 23.98220 | 60.95472 | -0.2311 | 6.39024 |
July | 338.00000 | 24.00917 | 65.09540 | -0.1813 | 6.06176 |
August | 348.00000 | 23.98225 | 63.21869 | -0.1960 | 6.07874 |
September | 330.00000 | 23.99696 | 64.33763 | -0.1974 | 6.18122 |
October | 340.00000 | 23.96100 | 56.01247 | 0.58552 | 12.61021 |
November | 330.00000 | 23.80326 | 47.65541 | 0.43532 | 9.57809 |
December | 338.00000 | 23.02357 | 45.76395 | 0.21153 | 8.53124 |
Annual Sum or Average | 4030.00000 | 23.59748 | 54.51196 | 0.08755 | 8.03730 |
Minimum of Months | 308.00000 | 22.45202 | 43.25075 | -0.2519 | 6.06176 |
Maximum of Months | 348.00000 | 24.00917 | 65.09540 | 0.58552 | 12.61021 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.40318 | 43.42949 | 0.01401 | 7.75383 |
February | 308.00000 | 22.90720 | 47.93545 | 0.16442 | 8.40330 |
March | 348.00000 | 23.08624 | 46.14592 | 0.18954 | 8.23884 |
April | 330.00000 | 23.86973 | 52.70646 | 0.45438 | 9.70654 |
May | 344.00000 | 23.97704 | 61.27273 | -0.2753 | 6.82209 |
June | 336.00000 | 23.97873 | 61.19974 | -0.2561 | 6.63688 |
July | 338.00000 | 24.00584 | 65.42073 | -0.2061 | 6.25579 |
August | 348.00000 | 23.97905 | 63.51685 | -0.2216 | 6.29613 |
September | 330.00000 | 23.99381 | 64.68345 | -0.2213 | 6.38113 |
October | 340.00000 | 23.95814 | 56.25051 | 0.56826 | 12.18350 |
November | 330.00000 | 23.79229 | 47.81323 | 0.41947 | 9.31375 |
December | 338.00000 | 22.99062 | 45.90527 | 0.19126 | 8.39216 |
Annual Sum or Average | 4030.00000 | 23.58143 | 54.74048 | 0.06626 | 8.02366 |
Minimum of Months | 308.00000 | 22.40318 | 43.42949 | -0.2753 | 6.25579 |
Maximum of Months | 348.00000 | 24.00584 | 65.42073 | 0.56826 | 12.18350 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.37686 | 43.54857 | 0.00477 | 7.77407 |
February | 308.00000 | 22.87792 | 48.09993 | 0.15446 | 8.38999 |
March | 348.00000 | 23.06283 | 46.28922 | 0.18098 | 8.21855 |
April | 330.00000 | 23.86317 | 52.84494 | 0.45054 | 9.64854 |
May | 344.00000 | 23.97587 | 61.40889 | -0.2782 | 6.85045 |
June | 336.00000 | 23.97763 | 61.32562 | -0.2589 | 6.66200 |
July | 338.00000 | 24.00491 | 65.54817 | -0.2085 | 6.27190 |
August | 348.00000 | 23.97833 | 63.62886 | -0.2239 | 6.31363 |
September | 330.00000 | 23.99294 | 64.80433 | -0.2235 | 6.39771 |
October | 340.00000 | 23.95628 | 56.35150 | 0.56632 | 12.13955 |
November | 330.00000 | 23.78330 | 47.90690 | 0.41529 | 9.26442 |
December | 338.00000 | 22.96592 | 46.02354 | 0.18294 | 8.36781 |
Annual Sum or Average | 4030.00000 | 23.57105 | 54.86529 | 0.06140 | 8.01679 |
Minimum of Months | 308.00000 | 22.37686 | 43.54857 | -0.2782 | 6.27190 |
Maximum of Months | 348.00000 | 24.00491 | 65.54817 | 0.56632 | 12.13955 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.33476 | 43.73391 | -0.0091 | 7.83419 |
February | 308.00000 | 22.82428 | 48.43831 | 0.13790 | 8.41141 |
March | 348.00000 | 23.01638 | 46.54267 | 0.16550 | 8.22002 |
April | 330.00000 | 23.84505 | 53.14598 | 0.44361 | 9.56369 |
May | 344.00000 | 23.97384 | 61.56153 | -0.2793 | 6.85483 |
June | 336.00000 | 23.97607 | 61.41991 | -0.2590 | 6.65705 |
July | 338.00000 | 24.00400 | 65.58537 | -0.2071 | 6.25753 |
August | 348.00000 | 23.97804 | 63.61103 | -0.2216 | 6.29245 |
September | 330.00000 | 23.99240 | 64.81679 | -0.2217 | 6.38196 |
October | 340.00000 | 23.95317 | 56.39331 | 0.56628 | 12.15052 |
November | 330.00000 | 23.76572 | 48.03725 | 0.40979 | 9.21979 |
December | 338.00000 | 22.92145 | 46.21142 | 0.16967 | 8.36096 |
Annual Sum or Average | 4030.00000 | 23.55202 | 55.00678 | 0.05586 | 8.00901 |
Minimum of Months | 308.00000 | 22.33476 | 43.73391 | -0.2793 | 6.25753 |
Maximum of Months | 348.00000 | 24.00400 | 65.58537 | 0.56628 | 12.15052 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.29560 | 43.72698 | -0.0272 | 8.05122 |
February | 308.00000 | 22.74171 | 48.66210 | 0.10839 | 8.55842 |
March | 348.00000 | 22.93622 | 46.72619 | 0.13650 | 8.37262 |
April | 330.00000 | 23.80119 | 53.55046 | 0.43117 | 9.46788 |
May | 344.00000 | 23.97279 | 61.62109 | -0.2630 | 6.67896 |
June | 336.00000 | 23.97666 | 61.10822 | -0.2364 | 6.44086 |
July | 338.00000 | 24.00773 | 64.99544 | -0.1783 | 6.06891 |
August | 348.00000 | 23.98255 | 62.89681 | -0.1866 | 6.03738 |
September | 330.00000 | 23.99755 | 64.10421 | -0.1923 | 6.18926 |
October | 340.00000 | 23.94986 | 55.95953 | 0.58200 | 12.61695 |
November | 330.00000 | 23.74379 | 47.88999 | 0.40828 | 9.31842 |
December | 338.00000 | 22.86056 | 46.32321 | 0.15035 | 8.52202 |
Annual Sum or Average | 4030.00000 | 23.52579 | 54.84258 | 0.05925 | 8.01817 |
Minimum of Months | 308.00000 | 22.29560 | 43.72698 | -0.2630 | 6.03738 |
Maximum of Months | 348.00000 | 24.00773 | 64.99544 | 0.58200 | 12.61695 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.466908E+10 | 0.117261E+10 | 145.14 | 0.288303E+10 | 0.178604E+10 | 0.00 | 1.00 | 19-JAN-09:02 | 0.00 | 01-JAN-00:05 | 51640.87 | 19-JAN-09:02 | 27719.12 | 19-JAN-09:02 | 26368.35 | 31-JAN-09:02 | 10917.50 | 19-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.608902E+10 | 0.152483E+10 | 180.55 | 0.375361E+10 | 0.233541E+10 | 0.00 | 1.00 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 | 50197.94 | 28-FEB-09:02 | 25990.30 | 28-FEB-09:02 | 24413.53 | 27-FEB-09:02 | 10739.92 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.877136E+10 | 0.221540E+10 | 247.20 | 0.556395E+10 | 0.320741E+10 | 0.00 | 1.00 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 | 51887.46 | 07-MAR-09:02 | 30962.68 | 30-MAR-08:62 | 23896.77 | 07-MAR-09:02 | 11169.74 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.161500E+11 | 0.406851E+10 | 396.33 | 0.103959E+11 | 0.575410E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 52406.84 | 29-APR-08:62 | 30967.86 | 22-APR-08:62 | 27778.75 | 24-APR-08:62 | 11431.42 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.362620E+11 | 0.887153E+10 | 475.86 | 0.217665E+11 | 0.144954E+11 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 53411.43 | 24-MAY-08:61 | 33536.93 | 07-MAY-07:02 | 27578.25 | 24-MAY-08:04 | 11707.65 | 27-MAY-08:04 | 0.00 | 01-MAY-00:10 |
June | 0.387417E+11 | 0.943506E+10 | 461.22 | 0.231072E+11 | 0.156345E+11 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 53348.17 | 19-JUN-08:61 | 34251.15 | 11-JUN-07:02 | 26820.69 | 19-JUN-08:04 | 11990.02 | 17-JUN-08:02 | 0.00 | 01-JUN-00:10 |
July | 0.443764E+11 | 0.106160E+11 | 480.44 | 0.246157E+11 | 0.197607E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 53564.23 | 03-JUL-08:61 | 33243.04 | 09-JUL-07:01 | 27677.15 | 31-JUL-08:04 | 11982.77 | 19-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.435758E+11 | 0.104520E+11 | 477.50 | 0.249905E+11 | 0.185853E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 53705.56 | 07-AUG-08:61 | 35718.98 | 20-AUG-07:02 | 27416.10 | 07-AUG-08:05 | 11872.04 | 22-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.388258E+11 | 0.921843E+10 | 463.64 | 0.216127E+11 | 0.172131E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 53953.54 | 05-SEP-08:61 | 32234.31 | 03-SEP-07:02 | 29728.00 | 05-SEP-08:61 | 12220.12 | 10-SEP-07:13 | 0.00 | 01-SEP-00:10 |
October | 0.329515E+11 | 0.791180E+10 | 451.87 | 0.197018E+11 | 0.132497E+11 | 0.00 | 1.00 | 02-OCT-08:62 | 0.00 | 01-OCT-00:05 | 53962.36 | 06-OCT-08:61 | 38232.79 | 26-OCT-08:61 | 28971.67 | 24-OCT-08:13 | 11880.76 | 07-OCT-08:13 | 0.00 | 01-OCT-00:05 |
November | 0.132340E+11 | 0.324218E+10 | 345.07 | 0.821330E+10 | 0.502065E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 52266.14 | 02-NOV-08:61 | 33923.53 | 06-NOV-09:02 | 25545.67 | 04-NOV-08:62 | 11241.93 | 02-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.843561E+10 | 0.206589E+10 | 219.46 | 0.518667E+10 | 0.324893E+10 | 0.00 | 1.00 | 09-DEC-09:02 | 0.00 | 01-DEC-00:10 | 52102.29 | 15-DEC-09:02 | 29631.03 | 11-DEC-09:02 | 24501.12 | 15-DEC-09:03 | 11044.87 | 15-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.292082E+12 | 0.707942E+11 | 4344.29 | 0.171791E+12 | 0.120291E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.466908E+10 | 0.117261E+10 | 145.14 | 0.288303E+10 | 0.178604E+10 | 0.00 | 1.00 | 0.00 | 50197.94 | 25990.30 | 23896.77 | 10739.92 | 0.00 | |||||||
Maximum of Months | 0.443764E+11 | 0.106160E+11 | 480.44 | 0.249905E+11 | 0.197607E+11 | 0.00 | 1.00 | 0.00 | 53962.36 | 38232.79 | 29728.00 | 12220.12 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.290169E+10 | 0.717626E+09 | 147.39 | 0.186794E+10 | 0.103374E+10 | 0.00 | 1.00 | 16-JAN-18:02 | 0.00 | 01-JAN-00:05 | 26920.11 | 19-JAN-09:02 | 17899.62 | 19-JAN-09:02 | 12612.27 | 16-JAN-22:00 | 5682.74 | 19-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.381677E+10 | 0.940776E+09 | 186.71 | 0.242228E+10 | 0.139449E+10 | 0.00 | 1.00 | 01-FEB-21:10 | 0.00 | 01-FEB-00:05 | 27470.78 | 24-FEB-09:02 | 18920.86 | 28-FEB-09:02 | 14160.28 | 21-FEB-21:10 | 5736.64 | 24-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.528782E+10 | 0.131497E+10 | 255.11 | 0.350530E+10 | 0.178252E+10 | 0.00 | 1.00 | 04-MAR-19:01 | 0.00 | 01-MAR-00:05 | 27265.33 | 07-MAR-09:02 | 20806.81 | 04-MAR-19:01 | 13586.15 | 28-MAR-21:44 | 5865.42 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.920452E+10 | 0.229351E+10 | 385.49 | 0.615757E+10 | 0.304695E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:05 | 27421.03 | 29-APR-08:62 | 19179.39 | 16-APR-17:07 | 13908.06 | 15-APR-18:10 | 6021.55 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.186296E+11 | 0.456475E+10 | 476.16 | 0.116501E+11 | 0.697946E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 28021.66 | 24-MAY-08:61 | 20898.13 | 07-MAY-07:02 | 12181.86 | 24-MAY-08:04 | 6197.46 | 27-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.196960E+11 | 0.480844E+10 | 461.71 | 0.121933E+11 | 0.750268E+10 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 27848.16 | 19-JUN-08:61 | 20653.55 | 11-JUN-07:02 | 11478.76 | 19-JUN-08:04 | 6337.92 | 17-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.222596E+11 | 0.534840E+10 | 481.79 | 0.128508E+11 | 0.940879E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 28168.34 | 03-JUL-08:61 | 20439.27 | 09-JUL-07:01 | 12519.98 | 03-JUL-08:13 | 6331.17 | 19-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.218060E+11 | 0.524677E+10 | 478.88 | 0.129498E+11 | 0.885626E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 28178.66 | 16-AUG-08:61 | 21259.69 | 20-AUG-07:02 | 12625.90 | 16-AUG-08:04 | 6270.57 | 22-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.195059E+11 | 0.464341E+10 | 463.74 | 0.112970E+11 | 0.820886E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 28459.40 | 05-SEP-08:61 | 20077.46 | 03-SEP-07:02 | 13694.39 | 05-SEP-08:04 | 6458.19 | 10-SEP-07:01 | 0.00 | 01-SEP-00:10 |
October | 0.168974E+11 | 0.406048E+10 | 447.54 | 0.105178E+11 | 0.637963E+10 | 0.00 | 1.00 | 02-OCT-08:62 | 0.00 | 01-OCT-00:05 | 28342.39 | 06-OCT-08:61 | 21564.84 | 26-OCT-20:07 | 13151.95 | 06-OCT-08:13 | 6298.88 | 07-OCT-08:13 | 0.00 | 01-OCT-00:05 |
November | 0.739728E+10 | 0.179481E+10 | 325.71 | 0.475691E+10 | 0.264037E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 27491.27 | 02-NOV-08:61 | 20138.87 | 06-NOV-09:02 | 13804.76 | 29-NOV-21:02 | 5916.43 | 02-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.466937E+10 | 0.113689E+10 | 227.54 | 0.299328E+10 | 0.167609E+10 | 0.00 | 1.00 | 08-DEC-21:10 | 0.00 | 01-DEC-00:10 | 27295.04 | 13-DEC-09:02 | 18406.41 | 09-DEC-09:02 | 12751.73 | 08-DEC-21:44 | 5781.66 | 15-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.152072E+12 | 0.368708E+11 | 4337.77 | 0.931621E+11 | 0.589098E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.290169E+10 | 0.717626E+09 | 147.39 | 0.186794E+10 | 0.103374E+10 | 0.00 | 1.00 | 0.00 | 26920.11 | 17899.62 | 11478.76 | 5682.74 | 0.00 | |||||||
Maximum of Months | 0.222596E+11 | 0.534840E+10 | 481.79 | 0.129498E+11 | 0.940879E+10 | 0.00 | 1.00 | 0.00 | 28459.40 | 21564.84 | 14160.28 | 6458.19 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.214115E+10 | 0.530401E+09 | 114.67 | 0.135320E+10 | 0.787950E+09 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 27920.67 | 31-JAN-08:62 | 16195.15 | 01-JAN-09:02 | 15312.27 | 31-JAN-08:62 | 5834.80 | 31-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.293562E+10 | 0.723489E+09 | 143.53 | 0.183461E+10 | 0.110101E+10 | 0.00 | 1.00 | 03-FEB-08:62 | 0.00 | 01-FEB-00:05 | 27505.33 | 28-FEB-08:62 | 14036.00 | 28-FEB-08:62 | 13931.43 | 27-FEB-08:62 | 5785.13 | 28-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.403321E+10 | 0.100033E+10 | 191.32 | 0.260569E+10 | 0.142752E+10 | 0.00 | 1.00 | 07-MAR-08:62 | 0.00 | 01-MAR-00:05 | 28207.03 | 07-MAR-08:62 | 16425.08 | 18-MAR-07:03 | 14646.12 | 07-MAR-08:62 | 5881.63 | 07-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.716566E+10 | 0.177669E+10 | 294.20 | 0.471125E+10 | 0.245441E+10 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 28828.10 | 29-APR-07:02 | 16624.96 | 27-APR-07:02 | 16158.67 | 24-APR-07:03 | 6061.37 | 29-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.154250E+11 | 0.370479E+10 | 342.71 | 0.937435E+10 | 0.605061E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 29554.71 | 21-MAY-08:61 | 17975.92 | 12-MAY-07:01 | 15727.59 | 24-MAY-07:03 | 6276.95 | 28-MAY-08:04 | 0.00 | 01-MAY-00:10 |
June | 0.165249E+11 | 0.395470E+10 | 336.66 | 0.992806E+10 | 0.659679E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 29850.87 | 19-JUN-07:01 | 18176.52 | 14-JUN-07:01 | 17010.45 | 19-JUN-07:03 | 6356.56 | 17-JUN-07:04 | 0.00 | 01-JUN-00:10 |
July | 0.183298E+11 | 0.431117E+10 | 347.79 | 0.102207E+11 | 0.810909E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 29923.54 | 31-JUL-07:01 | 16291.75 | 19-JUL-07:01 | 17296.65 | 02-JUL-08:04 | 6448.11 | 09-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.183785E+11 | 0.434024E+10 | 356.29 | 0.105620E+11 | 0.781649E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 29897.63 | 14-AUG-07:01 | 17793.27 | 31-AUG-07:01 | 17524.62 | 14-AUG-07:04 | 6321.14 | 06-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.159538E+11 | 0.371167E+10 | 334.02 | 0.887413E+10 | 0.707963E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 29952.17 | 05-SEP-07:01 | 17311.76 | 23-SEP-07:01 | 17393.51 | 05-SEP-07:01 | 6671.56 | 10-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.136523E+11 | 0.322245E+10 | 323.04 | 0.822075E+10 | 0.543158E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:05 | 29847.15 | 08-OCT-08:61 | 20613.47 | 26-OCT-07:01 | 16601.13 | 25-OCT-07:02 | 6244.82 | 14-OCT-07:02 | 0.00 | 01-OCT-00:05 |
November | 0.591750E+10 | 0.142959E+10 | 264.52 | 0.374036E+10 | 0.217714E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 28793.08 | 02-NOV-07:01 | 17430.65 | 07-NOV-08:61 | 15110.19 | 04-NOV-07:03 | 6044.42 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.374613E+10 | 0.902872E+09 | 172.36 | 0.233814E+10 | 0.140798E+10 | 0.00 | 1.00 | 09-DEC-08:62 | 0.00 | 01-DEC-00:10 | 28580.73 | 16-DEC-08:62 | 16868.49 | 17-DEC-09:02 | 15896.66 | 14-DEC-08:62 | 5936.53 | 15-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.124203E+12 | 0.296084E+11 | 3221.12 | 0.737632E+11 | 0.504402E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.214115E+10 | 0.530401E+09 | 114.67 | 0.135320E+10 | 0.787950E+09 | 0.00 | 1.00 | 0.00 | 27505.33 | 14036.00 | 13931.43 | 5785.13 | 0.00 | |||||||
Maximum of Months | 0.183785E+11 | 0.434024E+10 | 356.29 | 0.105620E+11 | 0.810909E+10 | 0.00 | 1.00 | 0.00 | 29952.17 | 20613.47 | 17524.62 | 6671.56 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.207280E+10 | 0.514171E+09 | 112.28 | 0.130571E+10 | 0.767084E+09 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 27762.82 | 31-JAN-08:62 | 16103.55 | 01-JAN-09:02 | 15260.64 | 31-JAN-08:62 | 5801.86 | 31-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.285958E+10 | 0.705279E+09 | 140.84 | 0.178245E+10 | 0.107713E+10 | 0.00 | 1.00 | 03-FEB-08:62 | 0.00 | 01-FEB-00:05 | 27350.09 | 28-FEB-08:62 | 13945.69 | 28-FEB-08:62 | 13862.11 | 27-FEB-08:62 | 5752.50 | 28-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.395883E+10 | 0.982159E+09 | 188.14 | 0.254980E+10 | 0.140904E+10 | 0.00 | 1.00 | 07-MAR-08:62 | 0.00 | 01-MAR-00:05 | 28047.44 | 07-MAR-08:62 | 16253.13 | 18-MAR-07:03 | 14578.42 | 07-MAR-08:62 | 5848.42 | 07-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.712329E+10 | 0.176549E+10 | 293.16 | 0.467815E+10 | 0.244513E+10 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 28667.66 | 29-APR-07:02 | 16514.36 | 27-APR-07:02 | 16063.79 | 24-APR-07:03 | 6027.27 | 29-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.154612E+11 | 0.370985E+10 | 343.44 | 0.939952E+10 | 0.606169E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 29393.06 | 21-MAY-08:61 | 17885.56 | 12-MAY-07:01 | 15638.79 | 24-MAY-07:03 | 6241.48 | 28-MAY-08:04 | 0.00 | 01-MAY-00:10 |
June | 0.165760E+11 | 0.396332E+10 | 338.39 | 0.996451E+10 | 0.661152E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 29682.59 | 19-JUN-07:01 | 18082.65 | 14-JUN-07:01 | 16873.81 | 19-JUN-07:03 | 6320.72 | 17-JUN-07:04 | 0.00 | 01-JUN-00:10 |
July | 0.184130E+11 | 0.432817E+10 | 350.98 | 0.102790E+11 | 0.813407E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 29754.85 | 31-JUL-07:01 | 16220.33 | 19-JUL-07:01 | 17152.21 | 02-JUL-08:04 | 6411.86 | 09-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.184456E+11 | 0.435294E+10 | 359.35 | 0.106093E+11 | 0.783625E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 29729.08 | 14-AUG-07:01 | 17700.29 | 31-AUG-07:01 | 17299.27 | 14-AUG-07:04 | 6285.53 | 06-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.160172E+11 | 0.372333E+10 | 336.04 | 0.891666E+10 | 0.710058E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 29746.68 | 05-SEP-07:01 | 17220.97 | 23-SEP-07:01 | 17153.00 | 05-SEP-07:01 | 6635.30 | 10-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.136930E+11 | 0.322952E+10 | 324.22 | 0.824996E+10 | 0.544302E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:05 | 29657.53 | 08-OCT-08:61 | 20502.99 | 26-OCT-07:01 | 16477.44 | 25-OCT-07:02 | 6209.64 | 14-OCT-07:02 | 0.00 | 01-OCT-00:05 |
November | 0.586832E+10 | 0.141689E+10 | 263.14 | 0.370291E+10 | 0.216541E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 28633.68 | 02-NOV-07:01 | 17335.67 | 07-NOV-08:61 | 15025.54 | 04-NOV-07:03 | 6010.43 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.370188E+10 | 0.891478E+09 | 168.92 | 0.230502E+10 | 0.139686E+10 | 0.00 | 1.00 | 09-DEC-08:62 | 0.00 | 01-DEC-00:10 | 28421.06 | 16-DEC-08:62 | 16774.68 | 17-DEC-09:02 | 15811.87 | 14-DEC-08:62 | 5903.20 | 15-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.124191E+12 | 0.295826E+11 | 3218.89 | 0.737430E+11 | 0.504478E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.207280E+10 | 0.514171E+09 | 112.28 | 0.130571E+10 | 0.767084E+09 | 0.00 | 1.00 | 0.00 | 27350.09 | 13945.69 | 13862.11 | 5752.50 | 0.00 | |||||||
Maximum of Months | 0.184456E+11 | 0.435294E+10 | 359.35 | 0.106093E+11 | 0.813407E+10 | 0.00 | 1.00 | 0.00 | 29754.85 | 20502.99 | 17299.27 | 6635.30 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.194164E+10 | 0.483790E+09 | 108.43 | 0.121600E+10 | 0.725642E+09 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 27652.07 | 19-JAN-08:62 | 16053.37 | 01-JAN-09:02 | 15039.65 | 19-JAN-08:62 | 5785.12 | 19-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.269248E+10 | 0.666695E+09 | 136.08 | 0.167037E+10 | 0.102212E+10 | 0.00 | 1.00 | 03-FEB-08:62 | 0.00 | 01-FEB-00:05 | 27303.42 | 28-FEB-08:62 | 13880.60 | 28-FEB-08:62 | 13422.82 | 28-FEB-08:62 | 5742.81 | 28-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.375722E+10 | 0.935683E+09 | 181.68 | 0.240363E+10 | 0.135359E+10 | 0.00 | 1.00 | 07-MAR-08:62 | 0.00 | 01-MAR-00:05 | 27998.71 | 07-MAR-08:62 | 14543.92 | 18-MAR-07:03 | 14598.71 | 07-MAR-08:62 | 5838.56 | 07-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.687050E+10 | 0.170791E+10 | 290.51 | 0.449853E+10 | 0.237197E+10 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 28615.97 | 29-APR-07:02 | 16377.70 | 27-APR-07:02 | 16034.64 | 24-APR-07:02 | 6017.22 | 29-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.152199E+11 | 0.365706E+10 | 342.90 | 0.922716E+10 | 0.599274E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 29335.08 | 21-MAY-08:61 | 17762.44 | 12-MAY-07:01 | 15707.23 | 24-MAY-07:03 | 6231.30 | 28-MAY-08:04 | 0.00 | 01-MAY-00:10 |
June | 0.163521E+11 | 0.391299E+10 | 336.08 | 0.980194E+10 | 0.655016E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 29633.77 | 19-JUN-07:01 | 17983.25 | 14-JUN-07:01 | 16907.58 | 19-JUN-07:03 | 6310.33 | 17-JUN-07:04 | 0.00 | 01-JUN-00:10 |
July | 0.181960E+11 | 0.427833E+10 | 346.14 | 0.101266E+11 | 0.806945E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 29705.92 | 31-JUL-07:01 | 16116.89 | 19-JUL-07:01 | 17204.93 | 02-JUL-08:04 | 6401.12 | 09-JUL-08:13 | 0.00 | 01-JUL-00:05 |
August | 0.182199E+11 | 0.430167E+10 | 353.95 | 0.104484E+11 | 0.777147E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 29680.19 | 14-AUG-07:01 | 17588.76 | 31-AUG-07:01 | 17393.26 | 14-AUG-07:04 | 6274.58 | 06-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.158013E+11 | 0.367633E+10 | 333.87 | 0.876791E+10 | 0.703335E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:10 | 29717.60 | 05-SEP-07:01 | 17100.85 | 23-SEP-07:01 | 17201.90 | 05-SEP-07:01 | 6623.10 | 10-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.134885E+11 | 0.318362E+10 | 320.43 | 0.810052E+10 | 0.538799E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:05 | 29631.45 | 08-OCT-08:61 | 20435.35 | 26-OCT-07:01 | 16571.44 | 25-OCT-07:02 | 6199.37 | 14-OCT-07:02 | 0.00 | 01-OCT-00:05 |
November | 0.565636E+10 | 0.136785E+10 | 258.86 | 0.354886E+10 | 0.210750E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 28581.76 | 02-NOV-07:01 | 17222.30 | 07-NOV-08:61 | 15040.81 | 04-NOV-07:03 | 5999.88 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.356055E+10 | 0.859324E+09 | 161.78 | 0.220512E+10 | 0.135542E+10 | 0.00 | 1.00 | 09-DEC-08:62 | 0.00 | 01-DEC-00:10 | 28370.26 | 16-DEC-08:62 | 16719.99 | 17-DEC-09:02 | 15822.33 | 14-DEC-08:62 | 5893.27 | 15-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.121756E+12 | 0.290312E+11 | 3170.70 | 0.720150E+11 | 0.497414E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.194164E+10 | 0.483790E+09 | 108.43 | 0.121600E+10 | 0.725642E+09 | 0.00 | 1.00 | 0.00 | 27303.42 | 13880.60 | 13422.82 | 5742.81 | 0.00 | |||||||
Maximum of Months | 0.182199E+11 | 0.430167E+10 | 353.95 | 0.104484E+11 | 0.806945E+10 | 0.00 | 1.00 | 0.00 | 29717.60 | 20435.35 | 17393.26 | 6623.10 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.285365E+10 | 0.724851E+09 | 94.05 | 0.174340E+10 | 0.111025E+10 | 0.00 | 1.00 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 | 47943.68 | 19-JAN-09:02 | 28357.47 | 01-JAN-10:02 | 22841.04 | 19-JAN-09:02 | 10141.17 | 19-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.413210E+10 | 0.104277E+10 | 122.19 | 0.250287E+10 | 0.162923E+10 | 0.00 | 1.00 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 | 46652.10 | 28-FEB-09:02 | 23984.91 | 28-FEB-09:02 | 22667.19 | 28-FEB-09:02 | 9980.69 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.580764E+10 | 0.147117E+10 | 166.48 | 0.361134E+10 | 0.219630E+10 | 0.00 | 1.00 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 | 48162.11 | 07-MAR-09:02 | 28464.67 | 30-MAR-08:62 | 22563.63 | 07-MAR-09:02 | 10376.27 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.112079E+11 | 0.283085E+10 | 275.70 | 0.720585E+10 | 0.400200E+10 | 0.00 | 1.00 | 15-APR-08:62 | 0.00 | 01-APR-00:05 | 48536.73 | 29-APR-08:62 | 28883.63 | 22-APR-08:62 | 27908.44 | 30-APR-09:02 | 10618.91 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.261005E+11 | 0.634724E+10 | 333.90 | 0.155737E+11 | 0.105268E+11 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 50067.90 | 21-MAY-09:01 | 30063.16 | 12-MAY-08:61 | 27017.86 | 21-MAY-09:01 | 11038.82 | 28-MAY-09:13 | 0.00 | 01-MAY-00:10 |
June | 0.283550E+11 | 0.686239E+10 | 327.33 | 0.167338E+11 | 0.116212E+11 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 50431.08 | 19-JUN-08:61 | 30883.14 | 10-JUN-08:61 | 29051.27 | 19-JUN-08:04 | 11141.38 | 17-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.314903E+11 | 0.749118E+10 | 331.87 | 0.171944E+11 | 0.142959E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 50657.46 | 31-JUL-08:61 | 28704.10 | 19-JUL-08:61 | 29246.91 | 31-JUL-08:03 | 11233.19 | 09-JUL-09:13 | 0.00 | 01-JUL-00:05 |
August | 0.317709E+11 | 0.758932E+10 | 342.13 | 0.179076E+11 | 0.138633E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 50500.99 | 07-AUG-08:61 | 30974.16 | 31-AUG-08:61 | 29734.83 | 14-AUG-08:05 | 11051.93 | 27-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.270897E+11 | 0.637327E+10 | 321.67 | 0.146779E+11 | 0.124118E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 50709.10 | 05-SEP-08:61 | 29194.35 | 23-SEP-08:61 | 29879.35 | 05-SEP-08:03 | 11669.50 | 10-SEP-09:18 | 0.00 | 01-SEP-00:10 |
October | 0.233448E+11 | 0.557952E+10 | 311.12 | 0.137459E+11 | 0.959884E+10 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:05 | 50552.51 | 08-OCT-09:01 | 35073.37 | 26-OCT-08:61 | 28390.19 | 22-OCT-09:01 | 11034.06 | 07-OCT-08:13 | 0.00 | 01-OCT-00:05 |
November | 0.920265E+10 | 0.224975E+10 | 235.31 | 0.561320E+10 | 0.358945E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 48529.71 | 02-NOV-08:61 | 29730.81 | 28-NOV-09:02 | 24173.97 | 04-NOV-08:62 | 10451.17 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.576517E+10 | 0.140730E+10 | 138.26 | 0.347923E+10 | 0.228594E+10 | 0.00 | 1.00 | 09-DEC-09:02 | 0.00 | 01-DEC-00:10 | 48348.79 | 15-DEC-09:02 | 30035.40 | 10-DEC-10:02 | 22940.21 | 15-DEC-09:03 | 10365.23 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.207120E+12 | 0.499696E+11 | 2999.99 | 0.119989E+12 | 0.871309E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.285365E+10 | 0.724851E+09 | 94.05 | 0.174340E+10 | 0.111025E+10 | 0.00 | 1.00 | 0.00 | 46652.10 | 23984.91 | 22563.63 | 9980.69 | 0.00 | |||||||
Maximum of Months | 0.317709E+11 | 0.758932E+10 | 342.13 | 0.179076E+11 | 0.142959E+11 | 0.00 | 1.00 | 0.00 | 50709.10 | 35073.37 | 29879.35 | 11669.50 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.141796E+10 | 0.354878E+09 | 90.10 | 0.865680E+09 | 0.552284E+09 | 0.00 | 1.00 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 | 25122.66 | 19-JAN-09:02 | 14858.94 | 01-JAN-10:02 | 11975.73 | 19-JAN-09:02 | 5220.77 | 19-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.206744E+10 | 0.514103E+09 | 120.80 | 0.125071E+10 | 0.816738E+09 | 0.00 | 1.00 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 | 24444.97 | 28-FEB-09:02 | 12569.76 | 28-FEB-09:02 | 11875.21 | 28-FEB-09:02 | 5138.07 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.292786E+10 | 0.730797E+09 | 162.39 | 0.181559E+10 | 0.111226E+10 | 0.00 | 1.00 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 | 25225.06 | 07-MAR-09:02 | 14927.02 | 30-MAR-08:62 | 11821.88 | 07-MAR-09:02 | 5341.11 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.572139E+10 | 0.142321E+10 | 272.41 | 0.367801E+10 | 0.204339E+10 | 0.00 | 1.00 | 15-APR-08:62 | 0.00 | 01-APR-00:05 | 25420.61 | 29-APR-08:62 | 15137.58 | 22-APR-08:62 | 14628.52 | 30-APR-09:02 | 5466.37 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.134880E+11 | 0.323265E+10 | 334.38 | 0.805116E+10 | 0.543684E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 26235.66 | 21-MAY-09:01 | 15741.56 | 12-MAY-08:61 | 14213.24 | 21-MAY-09:01 | 5682.95 | 28-MAY-09:13 | 0.00 | 01-MAY-00:10 |
June | 0.146603E+11 | 0.349642E+10 | 327.52 | 0.865267E+10 | 0.600765E+10 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 26425.29 | 19-JUN-08:61 | 16138.97 | 10-JUN-08:61 | 15313.97 | 19-JUN-08:04 | 5735.63 | 17-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.162864E+11 | 0.381620E+10 | 330.43 | 0.889520E+10 | 0.739121E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 26543.91 | 31-JUL-08:61 | 15002.41 | 19-JUL-08:61 | 15408.96 | 31-JUL-08:03 | 5782.44 | 09-JUL-09:13 | 0.00 | 01-JUL-00:05 |
August | 0.164242E+11 | 0.386517E+10 | 342.13 | 0.925962E+10 | 0.716462E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 26461.93 | 07-AUG-08:61 | 16206.13 | 31-AUG-08:61 | 15672.25 | 14-AUG-08:04 | 5689.60 | 27-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.139890E+11 | 0.324172E+10 | 321.72 | 0.758309E+10 | 0.640594E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 26570.98 | 05-SEP-08:61 | 15289.40 | 23-SEP-08:61 | 15678.17 | 05-SEP-08:03 | 6008.73 | 10-SEP-09:18 | 0.00 | 01-SEP-00:10 |
October | 0.120422E+11 | 0.283380E+10 | 309.39 | 0.708861E+10 | 0.495362E+10 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:05 | 26488.92 | 08-OCT-09:01 | 18392.06 | 26-OCT-08:61 | 14956.27 | 22-OCT-09:01 | 5681.29 | 07-OCT-08:13 | 0.00 | 01-OCT-00:05 |
November | 0.467946E+10 | 0.112591E+10 | 230.75 | 0.284769E+10 | 0.183177E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 25418.17 | 02-NOV-08:61 | 15539.16 | 06-NOV-09:02 | 12673.41 | 04-NOV-08:62 | 5380.01 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.293518E+10 | 0.705406E+09 | 134.12 | 0.176823E+10 | 0.116695E+10 | 0.00 | 1.00 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 | 25327.81 | 15-DEC-09:02 | 15700.82 | 10-DEC-10:02 | 12013.01 | 15-DEC-09:03 | 5335.87 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.106640E+12 | 0.253403E+11 | 2976.15 | 0.617563E+11 | 0.448833E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.141796E+10 | 0.354878E+09 | 90.10 | 0.865680E+09 | 0.552284E+09 | 0.00 | 1.00 | 0.00 | 24444.97 | 12569.76 | 11821.88 | 5138.07 | 0.00 | |||||||
Maximum of Months | 0.164242E+11 | 0.386517E+10 | 342.13 | 0.925962E+10 | 0.739121E+10 | 0.00 | 1.00 | 0.00 | 26570.98 | 18392.06 | 15678.17 | 6008.73 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.137777E+10 | 0.345151E+09 | 89.40 | 0.839828E+09 | 0.537938E+09 | 0.00 | 1.00 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 | 24972.30 | 19-JAN-09:02 | 14761.68 | 01-JAN-10:02 | 11938.48 | 19-JAN-09:02 | 5190.03 | 19-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.201433E+10 | 0.501388E+09 | 119.38 | 0.121638E+10 | 0.797955E+09 | 0.00 | 1.00 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 | 24304.53 | 28-FEB-09:02 | 12474.77 | 28-FEB-09:02 | 11829.76 | 28-FEB-09:02 | 5108.40 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.285943E+10 | 0.714395E+09 | 160.23 | 0.176789E+10 | 0.109154E+10 | 0.00 | 1.00 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 | 25083.75 | 07-MAR-09:02 | 14783.50 | 30-MAR-08:62 | 11828.16 | 07-MAR-09:02 | 5310.33 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.563216E+10 | 0.140165E+10 | 270.32 | 0.361546E+10 | 0.201670E+10 | 0.00 | 1.00 | 15-APR-08:62 | 0.00 | 01-APR-00:05 | 25276.31 | 29-APR-08:62 | 15009.08 | 22-APR-08:62 | 14552.22 | 30-APR-09:02 | 5434.63 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.133894E+11 | 0.320895E+10 | 334.43 | 0.798264E+10 | 0.540679E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 26079.29 | 21-MAY-09:01 | 15615.92 | 12-MAY-08:61 | 14155.30 | 21-MAY-09:01 | 5649.82 | 28-MAY-09:13 | 0.00 | 01-MAY-00:10 |
June | 0.145683E+11 | 0.347381E+10 | 327.52 | 0.858743E+10 | 0.598086E+10 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 26271.49 | 19-JUN-08:61 | 16015.38 | 10-JUN-08:61 | 15249.05 | 19-JUN-08:04 | 5702.24 | 17-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.161982E+11 | 0.379437E+10 | 329.98 | 0.883477E+10 | 0.736341E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 26389.42 | 31-JUL-08:61 | 14878.45 | 19-JUL-08:61 | 15339.22 | 31-JUL-08:03 | 5748.29 | 09-JUL-09:13 | 0.00 | 01-JUL-00:05 |
August | 0.163404E+11 | 0.384423E+10 | 341.74 | 0.920102E+10 | 0.713935E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 26307.91 | 07-AUG-08:61 | 16076.34 | 31-AUG-08:61 | 15601.54 | 14-AUG-08:04 | 5656.50 | 27-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.139081E+11 | 0.322227E+10 | 321.43 | 0.752852E+10 | 0.637956E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 26416.32 | 05-SEP-08:61 | 15170.36 | 23-SEP-08:61 | 15603.53 | 05-SEP-08:03 | 5973.15 | 10-SEP-09:18 | 0.00 | 01-SEP-00:10 |
October | 0.119625E+11 | 0.281448E+10 | 309.37 | 0.703158E+10 | 0.493093E+10 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:05 | 26334.75 | 08-OCT-09:01 | 18274.02 | 26-OCT-08:61 | 14893.98 | 22-OCT-09:01 | 5647.89 | 07-OCT-08:13 | 0.00 | 01-OCT-00:05 |
November | 0.461511E+10 | 0.111031E+10 | 228.50 | 0.280151E+10 | 0.181361E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 25274.31 | 02-NOV-08:61 | 15421.00 | 06-NOV-09:02 | 12616.51 | 04-NOV-08:62 | 5348.76 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.289131E+10 | 0.695035E+09 | 131.90 | 0.173751E+10 | 0.115380E+10 | 0.00 | 1.00 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 | 25183.31 | 15-DEC-09:02 | 15571.89 | 10-DEC-10:02 | 11925.13 | 15-DEC-09:02 | 5304.43 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.105757E+12 | 0.251260E+11 | 2964.20 | 0.611445E+11 | 0.446125E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.137777E+10 | 0.345151E+09 | 89.40 | 0.839828E+09 | 0.537938E+09 | 0.00 | 1.00 | 0.00 | 24304.53 | 12474.77 | 11828.16 | 5108.40 | 0.00 | |||||||
Maximum of Months | 0.163404E+11 | 0.384423E+10 | 341.74 | 0.920102E+10 | 0.736341E+10 | 0.00 | 1.00 | 0.00 | 26416.32 | 18274.02 | 15603.53 | 5973.15 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.132154E+10 | 0.331824E+09 | 87.69 | 0.804394E+09 | 0.517146E+09 | 0.00 | 1.00 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 | 23675.92 | 01-JAN-10:02 | 14770.03 | 01-JAN-10:02 | 11001.94 | 19-JAN-09:02 | 5019.49 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 |
February | 0.192018E+10 | 0.479275E+09 | 115.41 | 0.115570E+10 | 0.764481E+09 | 0.00 | 0.97 | 27-FEB-09:02 | 0.00 | 01-FEB-00:05 | 23698.77 | 28-FEB-09:02 | 12112.17 | 28-FEB-09:02 | 11586.60 | 28-FEB-09:02 | 4981.33 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.275064E+10 | 0.689355E+09 | 157.48 | 0.169274E+10 | 0.105790E+10 | 0.00 | 1.00 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 | 25144.01 | 07-MAR-09:02 | 13148.28 | 07-MAR-09:02 | 11995.73 | 07-MAR-09:02 | 5322.57 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.546843E+10 | 0.136401E+10 | 266.71 | 0.350294E+10 | 0.196550E+10 | 0.00 | 1.00 | 22-APR-08:62 | 0.00 | 01-APR-00:05 | 25330.12 | 29-APR-08:62 | 14970.11 | 22-APR-08:62 | 14605.10 | 30-APR-09:02 | 5446.89 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.132932E+11 | 0.318918E+10 | 334.49 | 0.791810E+10 | 0.537515E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 26129.84 | 21-MAY-09:01 | 15611.21 | 12-MAY-08:61 | 14232.30 | 21-MAY-09:01 | 5662.64 | 28-MAY-09:13 | 0.00 | 01-MAY-00:10 |
June | 0.145101E+11 | 0.346203E+10 | 327.49 | 0.854744E+10 | 0.596267E+10 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 26331.12 | 19-JUN-08:61 | 16015.41 | 10-JUN-08:61 | 15323.91 | 19-JUN-08:04 | 5715.19 | 17-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.161828E+11 | 0.379223E+10 | 329.39 | 0.882645E+10 | 0.735637E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 26449.32 | 31-JUL-08:61 | 14905.15 | 19-JUL-08:61 | 15394.24 | 31-JUL-08:03 | 5761.37 | 09-JUL-09:13 | 0.00 | 01-JUL-00:05 |
August | 0.163606E+11 | 0.384987E+10 | 341.44 | 0.921618E+10 | 0.714440E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 26367.62 | 07-AUG-08:61 | 16115.49 | 31-AUG-08:61 | 15639.51 | 14-AUG-08:04 | 5669.34 | 27-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.139090E+11 | 0.322366E+10 | 321.60 | 0.753072E+10 | 0.637832E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 26476.29 | 05-SEP-08:61 | 15191.05 | 23-SEP-08:61 | 15644.04 | 05-SEP-08:03 | 5987.19 | 10-SEP-09:18 | 0.00 | 01-SEP-00:10 |
October | 0.119364E+11 | 0.280931E+10 | 307.89 | 0.701405E+10 | 0.492236E+10 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:05 | 26394.52 | 08-OCT-09:01 | 18310.12 | 26-OCT-08:61 | 14944.27 | 22-OCT-09:01 | 5660.82 | 07-OCT-08:13 | 0.00 | 01-OCT-00:05 |
November | 0.453679E+10 | 0.109214E+10 | 224.60 | 0.274541E+10 | 0.179138E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 25330.63 | 02-NOV-08:61 | 15419.36 | 06-NOV-09:02 | 12659.21 | 04-NOV-08:62 | 5360.72 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.283381E+10 | 0.682354E+09 | 129.33 | 0.169793E+10 | 0.113587E+10 | 0.00 | 1.00 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 | 25238.41 | 15-DEC-09:02 | 15547.19 | 10-DEC-10:02 | 12009.75 | 15-DEC-09:02 | 5315.51 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.105024E+12 | 0.249652E+11 | 2943.52 | 0.606520E+11 | 0.443715E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.132154E+10 | 0.331824E+09 | 87.69 | 0.804394E+09 | 0.517146E+09 | 0.00 | 0.97 | 0.00 | 23675.92 | 12112.17 | 11001.94 | 4981.33 | 0.00 | |||||||
Maximum of Months | 0.163606E+11 | 0.384987E+10 | 341.44 | 0.921618E+10 | 0.735637E+10 | 0.00 | 1.00 | 0.00 | 26476.29 | 18310.12 | 15644.04 | 5987.19 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.135231E+10 | 0.342486E+09 | 87.15 | 0.828271E+09 | 0.524038E+09 | 0.00 | 0.96 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 | 25435.00 | 01-JAN-10:02 | 15985.48 | 01-JAN-10:02 | 9449.52 | 01-JAN-10:02 | 5395.38 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 |
February | 0.191744E+10 | 0.484113E+09 | 113.91 | 0.116064E+10 | 0.756800E+09 | 0.00 | 0.82 | 24-FEB-13:10 | 0.00 | 01-FEB-00:05 | 14302.64 | 28-FEB-09:02 | 7055.32 | 28-FEB-09:02 | 7247.32 | 28-FEB-09:02 | 3009.93 | 28-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.278312E+10 | 0.705157E+09 | 155.22 | 0.171808E+10 | 0.106504E+10 | 0.00 | 0.91 | 30-MAR-08:62 | 0.00 | 01-MAR-00:05 | 20196.05 | 07-MAR-09:02 | 9817.93 | 07-MAR-09:02 | 10378.12 | 07-MAR-09:02 | 4258.55 | 07-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.548884E+10 | 0.138538E+10 | 261.09 | 0.353234E+10 | 0.195650E+10 | 0.00 | 1.00 | 23-APR-09:02 | 0.00 | 01-APR-00:05 | 28330.08 | 29-APR-08:62 | 16344.47 | 23-APR-09:02 | 16262.84 | 30-APR-09:02 | 6044.61 | 29-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.138730E+11 | 0.335939E+10 | 334.12 | 0.830059E+10 | 0.557238E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 29084.81 | 24-MAY-08:61 | 16747.35 | 31-MAY-08:61 | 16566.87 | 23-MAY-08:62 | 6276.44 | 28-MAY-09:13 | 0.00 | 01-MAY-00:10 |
June | 0.153030E+11 | 0.367943E+10 | 327.54 | 0.908074E+10 | 0.622221E+10 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 29200.23 | 19-JUN-08:61 | 17182.03 | 11-JUN-09:01 | 17278.31 | 19-JUN-08:04 | 6337.90 | 17-JUN-08:04 | 0.00 | 01-JUN-00:10 |
July | 0.172437E+11 | 0.407136E+10 | 330.97 | 0.952166E+10 | 0.772204E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 29331.31 | 31-JUL-08:61 | 16032.87 | 19-JUL-08:61 | 17408.05 | 02-JUL-09:03 | 6389.62 | 09-JUL-09:13 | 0.00 | 01-JUL-00:05 |
August | 0.176734E+11 | 0.418334E+10 | 343.27 | 0.100825E+11 | 0.759093E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 29240.71 | 07-AUG-08:61 | 18170.12 | 31-AUG-08:61 | 17361.47 | 14-AUG-08:04 | 6286.68 | 27-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.150001E+11 | 0.349925E+10 | 322.66 | 0.824102E+10 | 0.675911E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:10 | 29361.21 | 05-SEP-08:61 | 16741.05 | 01-SEP-08:61 | 17410.30 | 05-SEP-08:03 | 6642.69 | 10-SEP-09:18 | 0.00 | 01-SEP-00:10 |
October | 0.128200E+11 | 0.303298E+10 | 307.68 | 0.761095E+10 | 0.520909E+10 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:05 | 29324.39 | 22-OCT-09:01 | 20540.64 | 26-OCT-08:61 | 17016.26 | 22-OCT-09:01 | 6264.50 | 07-OCT-08:13 | 0.00 | 01-OCT-00:05 |
November | 0.473879E+10 | 0.114872E+10 | 220.34 | 0.288700E+10 | 0.185179E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 28340.42 | 02-NOV-08:61 | 17076.74 | 06-NOV-09:02 | 14239.42 | 04-NOV-08:62 | 5956.49 | 11-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.291236E+10 | 0.710017E+09 | 127.70 | 0.175415E+10 | 0.115822E+10 | 0.00 | 1.00 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 | 28201.04 | 15-DEC-09:02 | 17116.73 | 10-DEC-10:02 | 15389.10 | 11-DEC-09:02 | 5897.24 | 10-DEC-10:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.111106E+12 | 0.266016E+11 | 2931.65 | 0.647179E+11 | 0.463881E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.135231E+10 | 0.342486E+09 | 87.15 | 0.828271E+09 | 0.524038E+09 | 0.00 | 0.82 | 0.00 | 14302.64 | 7055.32 | 7247.32 | 3009.93 | 0.00 | |||||||
Maximum of Months | 0.176734E+11 | 0.418334E+10 | 343.27 | 0.100825E+11 | 0.772204E+10 | 0.00 | 1.00 | 0.00 | 29361.21 | 20540.64 | 17410.30 | 6642.69 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 126.23 | 54.78 | 0.00 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 112.17 | 48.11 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 67.01 | 42.95 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 50.07 | 27.87 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.91 | 6.96 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 58.18 | 6.08 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 60.42 | 3.99 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.86 | 6.55 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.66 | 9.44 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.77 | 17.58 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.39 | 38.27 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 128.40 | 49.73 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 86.14 | 25.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 50.07 | 3.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 128.40 | 54.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 126.23 | 54.78 | 0.00 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 112.17 | 48.11 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 67.01 | 42.95 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 50.07 | 27.87 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.91 | 6.96 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 58.18 | 6.08 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 60.42 | 3.99 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.86 | 6.55 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.66 | 9.44 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.77 | 17.58 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.39 | 38.27 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 128.40 | 49.73 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 86.14 | 25.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 50.07 | 3.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 128.40 | 54.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 126.23 | 54.78 | 0.00 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 112.17 | 48.11 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 67.01 | 42.95 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 50.07 | 27.87 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.91 | 6.96 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 58.18 | 6.08 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 60.42 | 3.99 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.86 | 6.55 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.66 | 9.44 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.77 | 17.58 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.39 | 38.27 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 128.40 | 49.73 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 86.14 | 25.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 50.07 | 3.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 128.40 | 54.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 126.23 | 54.78 | 0.00 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 112.17 | 48.11 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 67.01 | 42.95 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 50.07 | 27.87 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.91 | 6.96 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 58.18 | 6.08 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 60.42 | 3.99 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.86 | 6.55 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.66 | 9.44 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.77 | 17.58 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.39 | 38.27 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 128.40 | 49.73 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 86.14 | 25.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 50.07 | 3.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 128.40 | 54.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.70 | 76.82 | 30.88 | 151.79 | 65.43 | 0.00 | 0.00 | 744.00 |
February | 97.66 | 63.22 | 34.44 | 134.88 | 57.49 | 0.00 | 0.00 | 672.00 |
March | 62.33 | 28.12 | 34.21 | 80.57 | 51.31 | 0.00 | 0.00 | 744.00 |
April | 46.19 | 10.81 | 35.38 | 60.13 | 33.36 | 0.00 | 0.00 | 720.00 |
May | 35.29 | 1.49 | 33.81 | 65.73 | 8.38 | 0.00 | 0.00 | 744.00 |
June | 34.87 | 0.32 | 34.55 | 69.62 | 7.32 | 0.00 | 0.00 | 720.00 |
July | 36.50 | 0.66 | 35.84 | 72.28 | 4.82 | 0.00 | 0.00 | 744.00 |
August | 42.94 | 5.14 | 37.80 | 80.04 | 7.89 | 0.00 | 0.00 | 744.00 |
September | 51.52 | 13.57 | 37.95 | 88.30 | 11.37 | 0.00 | 0.00 | 720.00 |
October | 79.95 | 41.64 | 38.31 | 132.93 | 21.08 | 0.00 | 0.00 | 744.00 |
November | 101.78 | 70.08 | 31.69 | 151.86 | 45.79 | 0.00 | 0.00 | 720.00 |
December | 105.24 | 75.59 | 29.65 | 154.33 | 59.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.67 | 32.13 | 34.54 | 103.40 | 31.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.87 | 0.32 | 29.65 | 60.13 | 4.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 107.70 | 76.82 | 38.31 | 154.33 | 65.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.70 | 76.82 | 30.88 | 151.79 | 65.43 | 0.00 | 0.00 | 744.00 |
February | 97.66 | 63.22 | 34.44 | 134.88 | 57.49 | 0.00 | 0.00 | 672.00 |
March | 62.33 | 28.12 | 34.21 | 80.57 | 51.31 | 0.00 | 0.00 | 744.00 |
April | 46.19 | 10.81 | 35.38 | 60.13 | 33.36 | 0.00 | 0.00 | 720.00 |
May | 35.29 | 1.49 | 33.81 | 65.73 | 8.38 | 0.00 | 0.00 | 744.00 |
June | 34.87 | 0.32 | 34.55 | 69.62 | 7.32 | 0.00 | 0.00 | 720.00 |
July | 36.50 | 0.66 | 35.84 | 72.28 | 4.82 | 0.00 | 0.00 | 744.00 |
August | 42.94 | 5.14 | 37.80 | 80.04 | 7.89 | 0.00 | 0.00 | 744.00 |
September | 51.52 | 13.57 | 37.95 | 88.30 | 11.37 | 0.00 | 0.00 | 720.00 |
October | 79.95 | 41.64 | 38.31 | 132.93 | 21.08 | 0.00 | 0.00 | 744.00 |
November | 101.78 | 70.08 | 31.69 | 151.86 | 45.79 | 0.00 | 0.00 | 720.00 |
December | 105.24 | 75.59 | 29.65 | 154.33 | 59.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.67 | 32.13 | 34.54 | 103.40 | 31.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.87 | 0.32 | 29.65 | 60.13 | 4.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 107.70 | 76.82 | 38.31 | 154.33 | 65.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 124.83 | 57.82 | 0.00 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 111.07 | 50.36 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 66.21 | 45.16 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 49.76 | 28.61 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.90 | 7.25 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 58.30 | 6.29 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 60.65 | 4.10 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 67.22 | 6.54 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.88 | 9.45 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.82 | 17.69 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 125.96 | 38.87 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 127.57 | 51.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 85.82 | 26.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 49.76 | 4.10 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 127.57 | 57.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 124.83 | 57.82 | 0.00 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 111.07 | 50.36 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 66.21 | 45.16 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 49.76 | 28.61 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.90 | 7.25 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 58.30 | 6.29 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 60.65 | 4.10 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 67.22 | 6.54 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.88 | 9.45 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.82 | 17.69 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 125.96 | 38.87 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 127.57 | 51.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 85.82 | 26.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 49.76 | 4.10 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 127.57 | 57.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.70 | 76.82 | 30.88 | 150.13 | 69.02 | 0.00 | 0.00 | 744.00 |
February | 97.66 | 63.22 | 34.44 | 133.57 | 60.15 | 0.00 | 0.00 | 672.00 |
March | 62.33 | 28.12 | 34.21 | 79.61 | 53.93 | 0.00 | 0.00 | 744.00 |
April | 46.19 | 10.81 | 35.38 | 59.75 | 34.24 | 0.00 | 0.00 | 720.00 |
May | 35.29 | 1.49 | 33.81 | 65.72 | 8.72 | 0.00 | 0.00 | 744.00 |
June | 34.87 | 0.32 | 34.55 | 69.77 | 7.57 | 0.00 | 0.00 | 720.00 |
July | 36.50 | 0.66 | 35.84 | 72.55 | 4.95 | 0.00 | 0.00 | 744.00 |
August | 42.94 | 5.14 | 37.80 | 80.48 | 7.87 | 0.00 | 0.00 | 744.00 |
September | 51.52 | 13.57 | 37.95 | 88.57 | 11.37 | 0.00 | 0.00 | 720.00 |
October | 79.95 | 41.64 | 38.31 | 133.00 | 21.21 | 0.00 | 0.00 | 744.00 |
November | 101.78 | 70.08 | 31.69 | 151.35 | 46.51 | 0.00 | 0.00 | 720.00 |
December | 105.24 | 75.59 | 29.65 | 153.35 | 61.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.67 | 32.13 | 34.54 | 103.02 | 32.11 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.87 | 0.32 | 29.65 | 59.75 | 4.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 107.70 | 76.82 | 38.31 | 153.35 | 69.02 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 125.33 | 56.86 | 0.00 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 111.42 | 49.92 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 66.34 | 45.06 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 49.65 | 29.75 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.20 | 8.99 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 57.55 | 8.17 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 59.08 | 5.66 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.24 | 8.36 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.21 | 11.54 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.44 | 19.82 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.04 | 39.92 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 127.86 | 51.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 85.50 | 27.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 49.65 | 5.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 127.86 | 56.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 125.33 | 56.86 | 0.00 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 111.42 | 49.92 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 66.34 | 45.06 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 49.65 | 29.75 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.20 | 8.99 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 57.55 | 8.17 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 59.08 | 5.66 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.24 | 8.36 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.21 | 11.54 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.44 | 19.82 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.04 | 39.92 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 127.86 | 51.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 85.50 | 27.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 49.65 | 5.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 127.86 | 56.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.12 | 76.40 | 30.71 | 149.91 | 67.50 | 1.33 | 0.00 | 744.00 |
February | 97.13 | 62.87 | 34.26 | 133.26 | 59.28 | 0.00 | 0.00 | 672.00 |
March | 61.98 | 27.96 | 34.02 | 79.33 | 53.49 | 0.00 | 0.00 | 744.00 |
April | 45.94 | 10.75 | 35.19 | 59.29 | 35.37 | 0.00 | 0.00 | 720.00 |
May | 35.10 | 1.48 | 33.62 | 64.54 | 10.72 | 0.00 | 0.00 | 744.00 |
June | 34.68 | 0.32 | 34.36 | 68.51 | 9.74 | 0.00 | 0.00 | 720.00 |
July | 36.30 | 0.66 | 35.64 | 70.34 | 6.77 | 0.00 | 0.00 | 744.00 |
August | 42.70 | 5.11 | 37.59 | 78.91 | 9.96 | 0.00 | 0.00 | 744.00 |
September | 51.24 | 13.49 | 37.75 | 87.30 | 13.76 | 0.00 | 0.00 | 720.00 |
October | 79.51 | 41.42 | 38.10 | 131.83 | 23.58 | 0.00 | 0.00 | 744.00 |
November | 101.22 | 69.70 | 31.52 | 150.62 | 47.45 | 0.00 | 0.00 | 720.00 |
December | 104.67 | 75.18 | 29.49 | 152.86 | 61.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.30 | 31.95 | 34.35 | 102.09 | 33.09 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 34.68 | 0.32 | 29.49 | 59.29 | 6.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 107.12 | 76.40 | 38.10 | 152.86 | 67.50 | 1.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 125.65 | 56.04 | 1.33 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 111.67 | 49.26 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 66.49 | 44.54 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 49.68 | 29.61 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.16 | 9.12 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 57.49 | 8.33 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 58.98 | 5.86 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.18 | 8.55 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.15 | 11.72 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.41 | 19.96 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.10 | 39.74 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 128.04 | 51.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 85.55 | 27.70 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 49.68 | 5.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 128.04 | 56.04 | 1.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 125.65 | 56.04 | 1.33 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 111.67 | 49.26 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 66.49 | 44.54 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 49.68 | 29.61 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.16 | 9.12 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 57.49 | 8.33 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 58.98 | 5.86 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.18 | 8.55 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.15 | 11.72 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.41 | 19.96 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.10 | 39.74 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 128.04 | 51.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 85.55 | 27.70 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 49.68 | 5.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 128.04 | 56.04 | 1.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.12 | 76.40 | 30.71 | 150.29 | 66.53 | 1.33 | 0.00 | 744.00 |
February | 97.13 | 62.87 | 34.26 | 133.56 | 58.50 | 0.00 | 0.00 | 672.00 |
March | 61.98 | 27.96 | 34.02 | 79.52 | 52.88 | 0.00 | 0.00 | 744.00 |
April | 45.94 | 10.75 | 35.19 | 59.34 | 35.21 | 0.00 | 0.00 | 720.00 |
May | 35.10 | 1.48 | 33.62 | 64.49 | 10.87 | 0.00 | 0.00 | 744.00 |
June | 34.68 | 0.32 | 34.36 | 68.44 | 9.94 | 0.00 | 0.00 | 720.00 |
July | 36.30 | 0.66 | 35.64 | 70.21 | 7.01 | 0.00 | 0.00 | 744.00 |
August | 42.70 | 5.11 | 37.59 | 78.83 | 10.20 | 0.00 | 0.00 | 744.00 |
September | 51.24 | 13.49 | 37.75 | 87.22 | 13.97 | 0.00 | 0.00 | 720.00 |
October | 79.51 | 41.42 | 38.10 | 131.79 | 23.75 | 0.00 | 0.00 | 744.00 |
November | 101.22 | 69.70 | 31.52 | 150.69 | 47.24 | 0.00 | 0.00 | 720.00 |
December | 104.67 | 75.18 | 29.49 | 153.07 | 60.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.30 | 31.95 | 34.35 | 102.15 | 32.92 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 34.68 | 0.32 | 29.49 | 59.34 | 7.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 107.12 | 76.40 | 38.10 | 153.07 | 66.53 | 1.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 126.09 | 55.12 | 1.50 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 112.07 | 48.43 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 66.81 | 43.76 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 49.86 | 29.16 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.31 | 8.81 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 57.64 | 8.04 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 59.13 | 5.62 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.31 | 8.27 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.25 | 11.43 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.52 | 19.64 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.29 | 39.29 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 128.33 | 50.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 85.77 | 27.21 | 1.50 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 49.86 | 5.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 128.33 | 55.12 | 1.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 126.09 | 55.12 | 1.50 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 112.07 | 48.43 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 66.81 | 43.76 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 49.86 | 29.16 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.31 | 8.81 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 57.64 | 8.04 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 59.13 | 5.62 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.31 | 8.27 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.25 | 11.43 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.52 | 19.64 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.29 | 39.29 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 128.33 | 50.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 85.77 | 27.21 | 1.50 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 49.86 | 5.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 128.33 | 55.12 | 1.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.12 | 76.40 | 30.71 | 150.81 | 65.44 | 1.50 | 0.00 | 744.00 |
February | 97.13 | 62.87 | 34.26 | 134.03 | 57.51 | 0.00 | 0.00 | 672.00 |
March | 61.98 | 27.96 | 34.02 | 79.90 | 51.95 | 0.00 | 0.00 | 744.00 |
April | 45.94 | 10.75 | 35.19 | 59.55 | 34.67 | 0.00 | 0.00 | 720.00 |
May | 35.10 | 1.48 | 33.62 | 64.68 | 10.51 | 0.00 | 0.00 | 744.00 |
June | 34.68 | 0.32 | 34.36 | 68.62 | 9.59 | 0.00 | 0.00 | 720.00 |
July | 36.30 | 0.66 | 35.64 | 70.40 | 6.71 | 0.00 | 0.00 | 744.00 |
August | 42.70 | 5.11 | 37.59 | 78.99 | 9.86 | 0.00 | 0.00 | 744.00 |
September | 51.24 | 13.49 | 37.75 | 87.35 | 13.63 | 0.00 | 0.00 | 720.00 |
October | 79.51 | 41.42 | 38.10 | 131.92 | 23.37 | 0.00 | 0.00 | 744.00 |
November | 101.22 | 69.70 | 31.52 | 150.92 | 46.71 | 0.00 | 0.00 | 720.00 |
December | 104.67 | 75.18 | 29.49 | 153.42 | 59.73 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.30 | 31.95 | 34.35 | 102.41 | 32.34 | 1.50 | 0.00 | 8760.00 |
Minimum of Months | 34.68 | 0.32 | 29.49 | 59.55 | 6.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 107.12 | 76.40 | 38.10 | 153.42 | 65.44 | 1.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 127.18 | 52.95 | 1.67 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 113.10 | 46.35 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 67.60 | 41.67 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 50.21 | 27.72 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.33 | 7.74 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 57.59 | 6.96 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 59.15 | 4.77 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.24 | 7.21 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.08 | 10.34 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.55 | 18.49 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.72 | 37.91 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 129.06 | 48.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 86.11 | 25.76 | 1.67 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 50.21 | 4.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 129.06 | 52.95 | 1.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 127.18 | 52.95 | 1.67 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 113.10 | 46.35 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 67.60 | 41.67 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 50.21 | 27.72 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.33 | 7.74 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 57.59 | 6.96 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 59.15 | 4.77 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.24 | 7.21 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.08 | 10.34 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.55 | 18.49 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.72 | 37.91 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 129.06 | 48.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 86.11 | 25.76 | 1.67 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 50.21 | 4.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 129.06 | 52.95 | 1.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 127.18 | 52.95 | 1.67 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 113.10 | 46.35 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 67.60 | 41.67 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 50.21 | 27.72 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.33 | 7.74 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 57.59 | 6.96 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 59.15 | 4.77 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.24 | 7.21 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.08 | 10.34 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.55 | 18.49 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.72 | 37.91 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 129.06 | 48.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 86.11 | 25.76 | 1.67 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 50.21 | 4.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 129.06 | 52.95 | 1.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 127.18 | 52.95 | 1.67 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 113.10 | 46.35 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 67.60 | 41.67 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 50.21 | 27.72 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.33 | 7.74 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 57.59 | 6.96 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 59.15 | 4.77 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.24 | 7.21 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.08 | 10.34 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.55 | 18.49 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.72 | 37.91 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 129.06 | 48.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 86.11 | 25.76 | 1.67 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 50.21 | 4.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 129.06 | 52.95 | 1.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.12 | 76.40 | 30.71 | 152.11 | 62.86 | 1.67 | 0.00 | 744.00 |
February | 97.13 | 62.87 | 34.26 | 135.26 | 55.05 | 0.00 | 0.00 | 672.00 |
March | 61.98 | 27.96 | 34.02 | 80.84 | 49.48 | 0.00 | 0.00 | 744.00 |
April | 45.94 | 10.75 | 35.19 | 59.98 | 32.97 | 0.00 | 0.00 | 720.00 |
May | 35.10 | 1.48 | 33.62 | 64.72 | 9.23 | 0.00 | 0.00 | 744.00 |
June | 34.68 | 0.32 | 34.36 | 68.58 | 8.30 | 0.00 | 0.00 | 720.00 |
July | 36.30 | 0.66 | 35.64 | 70.44 | 5.70 | 0.00 | 0.00 | 744.00 |
August | 42.70 | 5.11 | 37.59 | 78.92 | 8.60 | 0.00 | 0.00 | 744.00 |
September | 51.24 | 13.49 | 37.75 | 87.16 | 12.34 | 0.00 | 0.00 | 720.00 |
October | 79.51 | 41.42 | 38.10 | 131.97 | 22.01 | 0.00 | 0.00 | 744.00 |
November | 101.22 | 69.70 | 31.52 | 151.43 | 45.08 | 0.00 | 0.00 | 720.00 |
December | 104.67 | 75.18 | 29.49 | 154.29 | 57.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.30 | 31.95 | 34.35 | 102.83 | 30.63 | 1.67 | 0.00 | 8760.00 |
Minimum of Months | 34.68 | 0.32 | 29.49 | 59.98 | 5.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 107.12 | 76.40 | 38.10 | 154.29 | 62.86 | 1.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.12 | 76.40 | 30.71 | 152.11 | 62.86 | 1.67 | 0.00 | 744.00 |
February | 97.13 | 62.87 | 34.26 | 135.26 | 55.05 | 0.00 | 0.00 | 672.00 |
March | 61.98 | 27.96 | 34.02 | 80.84 | 49.48 | 0.00 | 0.00 | 744.00 |
April | 45.94 | 10.75 | 35.19 | 59.98 | 32.97 | 0.00 | 0.00 | 720.00 |
May | 35.10 | 1.48 | 33.62 | 64.72 | 9.23 | 0.00 | 0.00 | 744.00 |
June | 34.68 | 0.32 | 34.36 | 68.58 | 8.30 | 0.00 | 0.00 | 720.00 |
July | 36.30 | 0.66 | 35.64 | 70.44 | 5.70 | 0.00 | 0.00 | 744.00 |
August | 42.70 | 5.11 | 37.59 | 78.92 | 8.60 | 0.00 | 0.00 | 744.00 |
September | 51.24 | 13.49 | 37.75 | 87.16 | 12.34 | 0.00 | 0.00 | 720.00 |
October | 79.51 | 41.42 | 38.10 | 131.97 | 22.01 | 0.00 | 0.00 | 744.00 |
November | 101.22 | 69.70 | 31.52 | 151.43 | 45.08 | 0.00 | 0.00 | 720.00 |
December | 104.67 | 75.18 | 29.49 | 154.29 | 57.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.30 | 31.95 | 34.35 | 102.83 | 30.63 | 1.67 | 0.00 | 8760.00 |
Minimum of Months | 34.68 | 0.32 | 29.49 | 59.98 | 5.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 107.12 | 76.40 | 38.10 | 154.29 | 62.86 | 1.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 127.14 | 52.58 | 1.67 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 113.09 | 45.97 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 67.65 | 41.30 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 50.33 | 27.39 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.65 | 7.35 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 57.94 | 6.57 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 59.58 | 4.41 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.58 | 6.79 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.30 | 9.90 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.64 | 18.08 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.68 | 37.59 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 129.01 | 48.03 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 86.27 | 25.38 | 1.67 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 50.33 | 4.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 129.01 | 52.58 | 1.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 127.14 | 52.58 | 1.67 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 113.09 | 45.97 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 67.65 | 41.30 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 50.33 | 27.39 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.65 | 7.35 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 57.94 | 6.57 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 59.58 | 4.41 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.58 | 6.79 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.30 | 9.90 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.64 | 18.08 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.68 | 37.59 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 129.01 | 48.03 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 86.27 | 25.38 | 1.67 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 50.33 | 4.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 129.01 | 52.58 | 1.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.12 | 76.40 | 30.71 | 152.09 | 62.42 | 1.67 | 0.00 | 744.00 |
February | 97.13 | 62.87 | 34.26 | 135.28 | 54.59 | 0.00 | 0.00 | 672.00 |
March | 61.98 | 27.96 | 34.02 | 80.92 | 49.03 | 0.00 | 0.00 | 744.00 |
April | 45.94 | 10.75 | 35.19 | 60.13 | 32.57 | 0.00 | 0.00 | 720.00 |
May | 35.10 | 1.48 | 33.62 | 65.10 | 8.78 | 0.00 | 0.00 | 744.00 |
June | 34.68 | 0.32 | 34.36 | 69.00 | 7.84 | 0.00 | 0.00 | 720.00 |
July | 36.30 | 0.66 | 35.64 | 70.95 | 5.28 | 0.00 | 0.00 | 744.00 |
August | 42.70 | 5.11 | 37.59 | 79.34 | 8.11 | 0.00 | 0.00 | 744.00 |
September | 51.24 | 13.49 | 37.75 | 87.44 | 11.81 | 0.00 | 0.00 | 720.00 |
October | 79.51 | 41.42 | 38.10 | 132.10 | 21.52 | 0.00 | 0.00 | 744.00 |
November | 101.22 | 69.70 | 31.52 | 151.41 | 44.69 | 0.00 | 0.00 | 720.00 |
December | 104.67 | 75.18 | 29.49 | 154.24 | 57.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.30 | 31.95 | 34.35 | 103.02 | 30.17 | 1.67 | 0.00 | 8760.00 |
Minimum of Months | 34.68 | 0.32 | 29.49 | 60.13 | 5.28 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 107.12 | 76.40 | 38.10 | 154.24 | 62.42 | 1.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 127.31 | 52.28 | 1.67 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 113.27 | 45.64 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 67.79 | 40.98 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 50.43 | 27.20 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.74 | 7.24 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 58.03 | 6.47 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 59.67 | 4.33 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.65 | 6.71 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.36 | 9.81 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.71 | 17.97 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.78 | 37.42 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 129.14 | 47.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 86.37 | 25.21 | 1.67 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 50.43 | 4.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 129.14 | 52.28 | 1.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 127.31 | 52.28 | 1.67 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 113.27 | 45.64 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 67.79 | 40.98 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 50.43 | 27.20 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.74 | 7.24 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 58.03 | 6.47 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 59.67 | 4.33 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.65 | 6.71 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.36 | 9.81 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.71 | 17.97 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.78 | 37.42 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 129.14 | 47.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 86.37 | 25.21 | 1.67 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 50.43 | 4.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 129.14 | 52.28 | 1.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.12 | 76.40 | 30.71 | 152.28 | 62.07 | 1.67 | 0.00 | 744.00 |
February | 97.13 | 62.87 | 34.26 | 135.49 | 54.21 | 0.00 | 0.00 | 672.00 |
March | 61.98 | 27.96 | 34.02 | 81.09 | 48.65 | 0.00 | 0.00 | 744.00 |
April | 45.94 | 10.75 | 35.19 | 60.25 | 32.35 | 0.00 | 0.00 | 720.00 |
May | 35.10 | 1.48 | 33.62 | 65.21 | 8.65 | 0.00 | 0.00 | 744.00 |
June | 34.68 | 0.32 | 34.36 | 69.11 | 7.73 | 0.00 | 0.00 | 720.00 |
July | 36.30 | 0.66 | 35.64 | 71.06 | 5.19 | 0.00 | 0.00 | 744.00 |
August | 42.70 | 5.11 | 37.59 | 79.42 | 8.01 | 0.00 | 0.00 | 744.00 |
September | 51.24 | 13.49 | 37.75 | 87.51 | 11.70 | 0.00 | 0.00 | 720.00 |
October | 79.51 | 41.42 | 38.10 | 132.17 | 21.39 | 0.00 | 0.00 | 744.00 |
November | 101.22 | 69.70 | 31.52 | 151.53 | 44.49 | 0.00 | 0.00 | 720.00 |
December | 104.67 | 75.18 | 29.49 | 154.40 | 56.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.30 | 31.95 | 34.35 | 103.15 | 29.96 | 1.67 | 0.00 | 8760.00 |
Minimum of Months | 34.68 | 0.32 | 29.49 | 60.25 | 5.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 107.12 | 76.40 | 38.10 | 154.40 | 62.07 | 1.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 127.58 | 51.74 | 1.67 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 113.60 | 45.00 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 68.05 | 40.31 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 50.61 | 26.78 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.82 | 7.12 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 58.07 | 6.39 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 59.66 | 4.32 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.60 | 6.74 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.33 | 9.81 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.71 | 17.91 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.92 | 37.15 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 129.37 | 47.26 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 86.49 | 24.93 | 1.67 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 50.61 | 4.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 129.37 | 51.74 | 1.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 127.58 | 51.74 | 1.67 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 113.60 | 45.00 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 68.05 | 40.31 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 50.61 | 26.78 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.82 | 7.12 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 58.07 | 6.39 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 59.66 | 4.32 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 66.60 | 6.74 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 73.33 | 9.81 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.71 | 17.91 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 126.92 | 37.15 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 129.37 | 47.26 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 86.49 | 24.93 | 1.67 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 50.61 | 4.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 129.37 | 51.74 | 1.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.12 | 76.40 | 30.71 | 152.61 | 61.42 | 1.67 | 0.00 | 744.00 |
February | 97.13 | 62.87 | 34.26 | 135.89 | 53.44 | 0.00 | 0.00 | 672.00 |
March | 61.98 | 27.96 | 34.02 | 81.40 | 47.86 | 0.00 | 0.00 | 744.00 |
April | 45.94 | 10.75 | 35.19 | 60.47 | 31.85 | 0.00 | 0.00 | 720.00 |
May | 35.10 | 1.48 | 33.62 | 65.31 | 8.50 | 0.00 | 0.00 | 744.00 |
June | 34.68 | 0.32 | 34.36 | 69.15 | 7.63 | 0.00 | 0.00 | 720.00 |
July | 36.30 | 0.66 | 35.64 | 71.04 | 5.17 | 0.00 | 0.00 | 744.00 |
August | 42.70 | 5.11 | 37.59 | 79.36 | 8.05 | 0.00 | 0.00 | 744.00 |
September | 51.24 | 13.49 | 37.75 | 87.47 | 11.71 | 0.00 | 0.00 | 720.00 |
October | 79.51 | 41.42 | 38.10 | 132.18 | 21.31 | 0.00 | 0.00 | 744.00 |
November | 101.22 | 69.70 | 31.52 | 151.70 | 44.17 | 0.00 | 0.00 | 720.00 |
December | 104.67 | 75.18 | 29.49 | 154.68 | 56.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.30 | 31.95 | 34.35 | 103.29 | 29.64 | 1.67 | 0.00 | 8760.00 |
Minimum of Months | 34.68 | 0.32 | 29.49 | 60.47 | 5.17 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 107.12 | 76.40 | 38.10 | 154.68 | 61.42 | 1.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 128.06 | 49.97 | 0.00 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 114.25 | 42.91 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 68.48 | 38.03 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 50.95 | 25.24 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.69 | 6.75 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 57.74 | 6.22 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 59.04 | 4.42 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 65.85 | 7.14 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 72.72 | 10.12 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.32 | 17.90 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 127.04 | 36.33 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 129.77 | 45.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 86.45 | 24.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 50.95 | 4.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 129.77 | 49.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 63.81 | 25.65 | 128.06 | 49.97 | 0.00 | 0.00 | 744.00 |
February | 81.12 | 52.51 | 28.61 | 114.25 | 42.91 | 0.00 | 0.00 | 672.00 |
March | 51.77 | 23.35 | 28.41 | 68.48 | 38.03 | 0.00 | 0.00 | 744.00 |
April | 38.36 | 8.98 | 29.39 | 50.95 | 25.24 | 0.00 | 0.00 | 720.00 |
May | 29.31 | 1.23 | 28.08 | 54.69 | 6.75 | 0.00 | 0.00 | 744.00 |
June | 28.96 | 0.26 | 28.70 | 57.74 | 6.22 | 0.00 | 0.00 | 720.00 |
July | 30.32 | 0.55 | 29.77 | 59.04 | 4.42 | 0.00 | 0.00 | 744.00 |
August | 35.66 | 4.27 | 31.39 | 65.85 | 7.14 | 0.00 | 0.00 | 744.00 |
September | 42.80 | 11.27 | 31.52 | 72.72 | 10.12 | 0.00 | 0.00 | 720.00 |
October | 66.41 | 34.59 | 31.82 | 110.32 | 17.90 | 0.00 | 0.00 | 744.00 |
November | 84.54 | 58.21 | 26.33 | 127.04 | 36.33 | 0.00 | 0.00 | 720.00 |
December | 87.42 | 62.78 | 24.63 | 129.77 | 45.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 55.37 | 26.69 | 28.69 | 86.45 | 24.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.96 | 0.26 | 24.63 | 50.95 | 4.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 89.46 | 63.81 | 31.82 | 129.77 | 49.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.12 | 76.40 | 30.71 | 153.18 | 59.33 | 0.00 | 0.00 | 744.00 |
February | 97.13 | 62.87 | 34.26 | 136.66 | 50.97 | 0.00 | 0.00 | 672.00 |
March | 61.98 | 27.96 | 34.02 | 81.91 | 45.15 | 0.00 | 0.00 | 744.00 |
April | 45.94 | 10.75 | 35.19 | 60.87 | 30.02 | 0.00 | 0.00 | 720.00 |
May | 35.10 | 1.48 | 33.62 | 65.15 | 8.07 | 0.00 | 0.00 | 744.00 |
June | 34.68 | 0.32 | 34.36 | 68.75 | 7.43 | 0.00 | 0.00 | 720.00 |
July | 36.30 | 0.66 | 35.64 | 70.30 | 5.30 | 0.00 | 0.00 | 744.00 |
August | 42.70 | 5.11 | 37.59 | 78.46 | 8.52 | 0.00 | 0.00 | 744.00 |
September | 51.24 | 13.49 | 37.75 | 86.74 | 12.09 | 0.00 | 0.00 | 720.00 |
October | 79.51 | 41.42 | 38.10 | 131.71 | 21.31 | 0.00 | 0.00 | 744.00 |
November | 101.22 | 69.70 | 31.52 | 151.84 | 43.20 | 0.00 | 0.00 | 720.00 |
December | 104.67 | 75.18 | 29.49 | 155.15 | 54.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.30 | 31.95 | 34.35 | 103.24 | 28.69 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 34.68 | 0.32 | 29.49 | 60.87 | 5.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 107.12 | 76.40 | 38.10 | 155.15 | 59.33 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.338100E+09 | 0.146722E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.271359E+09 | 0.116397E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.179478E+09 | 0.115032E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.129789E+09 | 72234510.35 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.147072E+09 | 18647895.49 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.150809E+09 | 15758920.06 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.161827E+09 | 10688438.50 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.179066E+09 | 17550069.19 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.190930E+09 | 24473880.44 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296695E+09 | 47083146.10 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.327614E+09 | 99200065.82 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.343914E+09 | 0.133199E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.271665E+10 | 0.816987E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.129789E+09 | 10688438.50 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.343914E+09 | 0.146722E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.338100E+09 | 0.146722E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.271359E+09 | 0.116397E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.179478E+09 | 0.115032E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.129789E+09 | 72234510.35 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.147072E+09 | 18647895.49 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.150809E+09 | 15758920.06 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.161827E+09 | 10688438.50 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.179066E+09 | 17550069.19 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.190930E+09 | 24473880.44 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296695E+09 | 47083146.10 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.327614E+09 | 99200065.82 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.343914E+09 | 0.133199E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.271665E+10 | 0.816987E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.129789E+09 | 10688438.50 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.343914E+09 | 0.146722E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.338100E+09 | 0.146722E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.271359E+09 | 0.116397E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.179478E+09 | 0.115032E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.129789E+09 | 72234510.35 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.147072E+09 | 18647895.49 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.150809E+09 | 15758920.06 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.161827E+09 | 10688438.50 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.179066E+09 | 17550069.19 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.190930E+09 | 24473880.44 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296695E+09 | 47083146.10 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.327614E+09 | 99200065.82 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.343914E+09 | 0.133199E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.271665E+10 | 0.816987E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.129789E+09 | 10688438.50 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.343914E+09 | 0.146722E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.338100E+09 | 0.146722E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.271359E+09 | 0.116397E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.179478E+09 | 0.115032E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.129789E+09 | 72234510.35 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.147072E+09 | 18647895.49 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.150809E+09 | 15758920.06 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.161827E+09 | 10688438.50 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.179066E+09 | 17550069.19 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.190930E+09 | 24473880.44 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296695E+09 | 47083146.10 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.327614E+09 | 99200065.82 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.343914E+09 | 0.133199E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.271665E+10 | 0.816987E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.129789E+09 | 10688438.50 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.343914E+09 | 0.146722E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.288476E+09 | 0.205758E+09 | 82718498.25 | 0.406560E+09 | 0.175258E+09 |
February | 0.236263E+09 | 0.152936E+09 | 83327122.21 | 0.326292E+09 | 0.139080E+09 |
March | 0.166933E+09 | 75309570.66 | 91623155.03 | 0.215794E+09 | 0.137424E+09 |
April | 0.119720E+09 | 28013115.54 | 91707225.53 | 0.155846E+09 | 86463001.29 |
May | 94528109.60 | 3981294.19 | 90546815.41 | 0.176048E+09 | 22450111.25 |
June | 90383688.44 | 824940.46 | 89558747.98 | 0.180467E+09 | 18977982.42 |
July | 97766236.89 | 1773500.03 | 95992736.87 | 0.193592E+09 | 12901890.76 |
August | 0.115006E+09 | 13769619.29 | 0.101236E+09 | 0.214386E+09 | 21122978.26 |
September | 0.133549E+09 | 35171147.31 | 98377368.32 | 0.228870E+09 | 29460319.27 |
October | 0.214142E+09 | 0.111539E+09 | 0.102604E+09 | 0.356050E+09 | 56457133.19 |
November | 0.263806E+09 | 0.181653E+09 | 82153251.64 | 0.393622E+09 | 0.118699E+09 |
December | 0.281884E+09 | 0.202460E+09 | 79424662.39 | 0.413362E+09 | 0.159183E+09 |
Annual Sum or Average | 0.210246E+10 | 0.101319E+10 | 0.108927E+10 | 0.326089E+10 | 0.977477E+09 |
Minimum of Months | 90383688.44 | 824940.46 | 79424662.39 | 0.155846E+09 | 12901890.76 |
Maximum of Months | 0.288476E+09 | 0.205758E+09 | 0.102604E+09 | 0.413362E+09 | 0.175258E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.288476E+09 | 0.205758E+09 | 82718498.25 | 0.406560E+09 | 0.175258E+09 |
February | 0.236263E+09 | 0.152936E+09 | 83327122.21 | 0.326292E+09 | 0.139080E+09 |
March | 0.166933E+09 | 75309570.66 | 91623155.03 | 0.215794E+09 | 0.137424E+09 |
April | 0.119720E+09 | 28013115.54 | 91707225.53 | 0.155846E+09 | 86463001.29 |
May | 94528109.60 | 3981294.19 | 90546815.41 | 0.176048E+09 | 22450111.25 |
June | 90383688.44 | 824940.46 | 89558747.98 | 0.180467E+09 | 18977982.42 |
July | 97766236.89 | 1773500.03 | 95992736.87 | 0.193592E+09 | 12901890.76 |
August | 0.115006E+09 | 13769619.29 | 0.101236E+09 | 0.214386E+09 | 21122978.26 |
September | 0.133549E+09 | 35171147.31 | 98377368.32 | 0.228870E+09 | 29460319.27 |
October | 0.214142E+09 | 0.111539E+09 | 0.102604E+09 | 0.356050E+09 | 56457133.19 |
November | 0.263806E+09 | 0.181653E+09 | 82153251.64 | 0.393622E+09 | 0.118699E+09 |
December | 0.281884E+09 | 0.202460E+09 | 79424662.39 | 0.413362E+09 | 0.159183E+09 |
Annual Sum or Average | 0.210246E+10 | 0.101319E+10 | 0.108927E+10 | 0.326089E+10 | 0.977477E+09 |
Minimum of Months | 90383688.44 | 824940.46 | 79424662.39 | 0.155846E+09 | 12901890.76 |
Maximum of Months | 0.288476E+09 | 0.205758E+09 | 0.102604E+09 | 0.413362E+09 | 0.175258E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.334332E+09 | 0.154855E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.268690E+09 | 0.121831E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.177330E+09 | 0.120961E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.128986E+09 | 74161221.05 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.147055E+09 | 19410908.70 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.151125E+09 | 16303614.62 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.162432E+09 | 10983401.80 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.180029E+09 | 17510962.57 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.191498E+09 | 24485344.56 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296808E+09 | 47389448.70 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.326484E+09 | 0.100762E+09 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.341692E+09 | 0.138153E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.270646E+10 | 0.846808E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.128986E+09 | 10983401.80 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.341692E+09 | 0.154855E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.334332E+09 | 0.154855E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.268690E+09 | 0.121831E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.177330E+09 | 0.120961E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.128986E+09 | 74161221.05 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.147055E+09 | 19410908.70 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.151125E+09 | 16303614.62 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.162432E+09 | 10983401.80 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.180029E+09 | 17510962.57 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.191498E+09 | 24485344.56 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296808E+09 | 47389448.70 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.326484E+09 | 0.100762E+09 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.341692E+09 | 0.138153E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.270646E+10 | 0.846808E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.128986E+09 | 10983401.80 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.341692E+09 | 0.154855E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.288476E+09 | 0.205758E+09 | 82718498.25 | 0.402097E+09 | 0.184857E+09 |
February | 0.236263E+09 | 0.152936E+09 | 83327122.21 | 0.323128E+09 | 0.145505E+09 |
March | 0.166933E+09 | 75309570.66 | 91623155.03 | 0.213234E+09 | 0.144446E+09 |
April | 0.119720E+09 | 28013115.54 | 91707225.53 | 0.154878E+09 | 88752135.01 |
May | 94528109.60 | 3981294.19 | 90546815.41 | 0.176018E+09 | 23364485.17 |
June | 90383688.44 | 824940.46 | 89558747.98 | 0.180837E+09 | 19630620.96 |
July | 97766236.89 | 1773500.03 | 95992736.87 | 0.194311E+09 | 13255330.61 |
August | 0.115006E+09 | 13769619.29 | 0.101236E+09 | 0.215544E+09 | 21072484.15 |
September | 0.133549E+09 | 35171147.31 | 98377368.32 | 0.229561E+09 | 29470380.80 |
October | 0.214142E+09 | 0.111539E+09 | 0.102604E+09 | 0.356215E+09 | 56810488.42 |
November | 0.263806E+09 | 0.181653E+09 | 82153251.64 | 0.392303E+09 | 0.120542E+09 |
December | 0.281884E+09 | 0.202460E+09 | 79424662.39 | 0.410743E+09 | 0.165029E+09 |
Annual Sum or Average | 0.210246E+10 | 0.101319E+10 | 0.108927E+10 | 0.324887E+10 | 0.101273E+10 |
Minimum of Months | 90383688.44 | 824940.46 | 79424662.39 | 0.154878E+09 | 13255330.61 |
Maximum of Months | 0.288476E+09 | 0.205758E+09 | 0.102604E+09 | 0.410743E+09 | 0.184857E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.335696E+09 | 0.152301E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.269542E+09 | 0.120762E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.177673E+09 | 0.120680E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.128680E+09 | 77116769.73 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.145172E+09 | 24076637.12 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.149164E+09 | 21166989.01 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.158243E+09 | 15167231.52 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.177422E+09 | 22382599.84 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.189755E+09 | 29911642.26 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.295795E+09 | 53086584.36 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.326686E+09 | 0.103469E+09 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.342463E+09 | 0.138020E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.269629E+10 | 0.878140E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.128680E+09 | 15167231.52 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.342463E+09 | 0.152301E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.335696E+09 | 0.152301E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.269542E+09 | 0.120762E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.177673E+09 | 0.120680E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.128680E+09 | 77116769.73 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.145172E+09 | 24076637.12 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.149164E+09 | 21166989.01 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.158243E+09 | 15167231.52 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.177422E+09 | 22382599.84 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.189755E+09 | 29911642.26 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.295795E+09 | 53086584.36 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.326686E+09 | 0.103469E+09 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.342463E+09 | 0.138020E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.269629E+10 | 0.878140E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.128680E+09 | 15167231.52 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.342463E+09 | 0.152301E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.286900E+09 | 0.204634E+09 | 82266484.59 | 0.401523E+09 | 0.180789E+09 |
February | 0.234972E+09 | 0.152100E+09 | 82871782.74 | 0.322378E+09 | 0.143399E+09 |
March | 0.166021E+09 | 74898042.95 | 91122482.05 | 0.212481E+09 | 0.143274E+09 |
April | 0.119066E+09 | 27860038.41 | 91206093.15 | 0.153675E+09 | 91682685.66 |
May | 94011562.55 | 3959538.48 | 90052024.07 | 0.172868E+09 | 28709678.51 |
June | 89889788.50 | 820432.58 | 89069355.92 | 0.177571E+09 | 25236012.46 |
July | 97231995.16 | 1763808.77 | 95468186.39 | 0.188388E+09 | 18126943.35 |
August | 0.114377E+09 | 13694375.47 | 0.100683E+09 | 0.211340E+09 | 26689688.90 |
September | 0.132819E+09 | 34978955.25 | 97839787.08 | 0.226272E+09 | 35664479.84 |
October | 0.212972E+09 | 0.110929E+09 | 0.102043E+09 | 0.353087E+09 | 63165001.11 |
November | 0.262365E+09 | 0.180661E+09 | 81704326.77 | 0.390395E+09 | 0.123002E+09 |
December | 0.280344E+09 | 0.201353E+09 | 78990647.84 | 0.409414E+09 | 0.163910E+09 |
Annual Sum or Average | 0.209097E+10 | 0.100765E+10 | 0.108332E+10 | 0.321939E+10 | 0.104365E+10 |
Minimum of Months | 89889788.50 | 820432.58 | 78990647.84 | 0.153675E+09 | 18126943.35 |
Maximum of Months | 0.286900E+09 | 0.204634E+09 | 0.102043E+09 | 0.409414E+09 | 0.180789E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.336544E+09 | 0.150105E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.270151E+09 | 0.119179E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.178099E+09 | 0.119303E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.128781E+09 | 76755388.99 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.145061E+09 | 24422644.99 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.149017E+09 | 21602232.96 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.157970E+09 | 15707746.02 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.177247E+09 | 22911298.73 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.189592E+09 | 30375634.59 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.295712E+09 | 53467400.09 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.326846E+09 | 0.103007E+09 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.342931E+09 | 0.136627E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.269795E+10 | 0.873463E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.128781E+09 | 15707746.02 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.342931E+09 | 0.150105E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.336544E+09 | 0.150105E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.270151E+09 | 0.119179E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.178099E+09 | 0.119303E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.128781E+09 | 76755388.99 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.145061E+09 | 24422644.99 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.149017E+09 | 21602232.96 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.157970E+09 | 15707746.02 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.177247E+09 | 22911298.73 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.189592E+09 | 30375634.59 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.295712E+09 | 53467400.09 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.326846E+09 | 0.103007E+09 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.342931E+09 | 0.136627E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.269795E+10 | 0.873463E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.128781E+09 | 15707746.02 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.342931E+09 | 0.150105E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.286900E+09 | 0.204634E+09 | 82266484.59 | 0.402538E+09 | 0.178185E+09 |
February | 0.234972E+09 | 0.152100E+09 | 82871782.74 | 0.323106E+09 | 0.141521E+09 |
March | 0.166021E+09 | 74898042.95 | 91122482.05 | 0.212994E+09 | 0.141638E+09 |
April | 0.119066E+09 | 27860038.41 | 91206093.15 | 0.153797E+09 | 91253497.79 |
May | 94011562.55 | 3959538.48 | 90052024.07 | 0.172734E+09 | 29120251.64 |
June | 89889788.50 | 820432.58 | 89069355.92 | 0.177395E+09 | 25753654.72 |
July | 97231995.16 | 1763808.77 | 95468186.39 | 0.188061E+09 | 18768716.07 |
August | 0.114377E+09 | 13694375.47 | 0.100683E+09 | 0.211130E+09 | 27317779.41 |
September | 0.132819E+09 | 34978955.25 | 97839787.08 | 0.226076E+09 | 36215383.78 |
October | 0.212972E+09 | 0.110929E+09 | 0.102043E+09 | 0.352986E+09 | 63617102.61 |
November | 0.262365E+09 | 0.180661E+09 | 81704326.77 | 0.390588E+09 | 0.122454E+09 |
December | 0.280344E+09 | 0.201353E+09 | 78990647.84 | 0.409974E+09 | 0.162256E+09 |
Annual Sum or Average | 0.209097E+10 | 0.100765E+10 | 0.108332E+10 | 0.322138E+10 | 0.103810E+10 |
Minimum of Months | 89889788.50 | 820432.58 | 78990647.84 | 0.153797E+09 | 18768716.07 |
Maximum of Months | 0.286900E+09 | 0.204634E+09 | 0.102043E+09 | 0.409974E+09 | 0.178185E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.337709E+09 | 0.147639E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.271110E+09 | 0.117169E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.178934E+09 | 0.117206E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.129235E+09 | 75572297.76 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.145474E+09 | 23595939.66 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.149401E+09 | 20838214.35 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.158384E+09 | 15039990.47 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.177600E+09 | 22141726.73 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.189877E+09 | 29628131.00 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296007E+09 | 52604532.88 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.327342E+09 | 0.101848E+09 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.343710E+09 | 0.134712E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.270478E+10 | 0.857994E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.129235E+09 | 15039990.47 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.343710E+09 | 0.147639E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.337709E+09 | 0.147639E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.271110E+09 | 0.117169E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.178934E+09 | 0.117206E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.129235E+09 | 75572297.76 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.145474E+09 | 23595939.66 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.149401E+09 | 20838214.35 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.158384E+09 | 15039990.47 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.177600E+09 | 22141726.73 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.189877E+09 | 29628131.00 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296007E+09 | 52604532.88 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.327342E+09 | 0.101848E+09 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.343710E+09 | 0.134712E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.270478E+10 | 0.857994E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.129235E+09 | 15039990.47 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.343710E+09 | 0.147639E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.286900E+09 | 0.204634E+09 | 82266484.59 | 0.403932E+09 | 0.175262E+09 |
February | 0.234972E+09 | 0.152100E+09 | 82871782.74 | 0.324255E+09 | 0.139139E+09 |
March | 0.166021E+09 | 74898042.95 | 91122482.05 | 0.213996E+09 | 0.139152E+09 |
April | 0.119066E+09 | 27860038.41 | 91206093.15 | 0.154346E+09 | 89853468.60 |
May | 94011562.55 | 3959538.48 | 90052024.07 | 0.173231E+09 | 28143702.17 |
June | 89889788.50 | 820432.58 | 89069355.92 | 0.177857E+09 | 24849884.70 |
July | 97231995.16 | 1763808.77 | 95468186.39 | 0.188558E+09 | 17979762.82 |
August | 0.114377E+09 | 13694375.47 | 0.100683E+09 | 0.211555E+09 | 26407277.84 |
September | 0.132819E+09 | 34978955.25 | 97839787.08 | 0.226420E+09 | 35331907.47 |
October | 0.212972E+09 | 0.110929E+09 | 0.102043E+09 | 0.353343E+09 | 62596425.20 |
November | 0.262365E+09 | 0.180661E+09 | 81704326.77 | 0.391186E+09 | 0.121080E+09 |
December | 0.280344E+09 | 0.201353E+09 | 78990647.84 | 0.410908E+09 | 0.159985E+09 |
Annual Sum or Average | 0.209097E+10 | 0.100765E+10 | 0.108332E+10 | 0.322959E+10 | 0.101978E+10 |
Minimum of Months | 89889788.50 | 820432.58 | 78990647.84 | 0.154346E+09 | 17979762.82 |
Maximum of Months | 0.286900E+09 | 0.204634E+09 | 0.102043E+09 | 0.410908E+09 | 0.175262E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.340650E+09 | 0.141809E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.273600E+09 | 0.112131E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.181055E+09 | 0.111598E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.130135E+09 | 71860237.34 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.145529E+09 | 20721813.88 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.149266E+09 | 18037871.88 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.158423E+09 | 12764784.17 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.177407E+09 | 19302424.63 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.189422E+09 | 26802298.09 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296093E+09 | 49524879.67 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.328454E+09 | 98269163.46 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.345676E+09 | 0.129597E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.271571E+10 | 0.812419E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.130135E+09 | 12764784.17 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.345676E+09 | 0.141809E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.340650E+09 | 0.141809E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.273600E+09 | 0.112131E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.181055E+09 | 0.111598E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.130135E+09 | 71860237.34 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.145529E+09 | 20721813.88 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.149266E+09 | 18037871.88 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.158423E+09 | 12764784.17 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.177407E+09 | 19302424.63 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.189422E+09 | 26802298.09 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296093E+09 | 49524879.67 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.328454E+09 | 98269163.46 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.345676E+09 | 0.129597E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.271571E+10 | 0.812419E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.130135E+09 | 12764784.17 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.345676E+09 | 0.141809E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.340650E+09 | 0.141809E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.273600E+09 | 0.112131E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.181055E+09 | 0.111598E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.130135E+09 | 71860237.34 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.145529E+09 | 20721813.88 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.149266E+09 | 18037871.88 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.158423E+09 | 12764784.17 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.177407E+09 | 19302424.63 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.189422E+09 | 26802298.09 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296093E+09 | 49524879.67 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.328454E+09 | 98269163.46 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.345676E+09 | 0.129597E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.271571E+10 | 0.812419E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.130135E+09 | 12764784.17 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.345676E+09 | 0.141809E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.340650E+09 | 0.141809E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.273600E+09 | 0.112131E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.181055E+09 | 0.111598E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.130135E+09 | 71860237.34 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.145529E+09 | 20721813.88 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.149266E+09 | 18037871.88 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.158423E+09 | 12764784.17 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.177407E+09 | 19302424.63 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.189422E+09 | 26802298.09 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296093E+09 | 49524879.67 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.328454E+09 | 98269163.46 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.345676E+09 | 0.129597E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.271571E+10 | 0.812419E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.130135E+09 | 12764784.17 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.345676E+09 | 0.141809E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.286900E+09 | 0.204634E+09 | 82266484.59 | 0.407417E+09 | 0.168374E+09 |
February | 0.234972E+09 | 0.152100E+09 | 82871782.74 | 0.327217E+09 | 0.133182E+09 |
March | 0.166021E+09 | 74898042.95 | 91122482.05 | 0.216535E+09 | 0.132514E+09 |
April | 0.119066E+09 | 27860038.41 | 91206093.15 | 0.155457E+09 | 85458708.70 |
May | 94011562.55 | 3959538.48 | 90052024.07 | 0.173355E+09 | 24730360.95 |
June | 89889788.50 | 820432.58 | 89069355.92 | 0.177752E+09 | 21521182.35 |
July | 97231995.16 | 1763808.77 | 95468186.39 | 0.188661E+09 | 15268340.12 |
August | 0.114377E+09 | 13694375.47 | 0.100683E+09 | 0.211380E+09 | 23038079.53 |
September | 0.132819E+09 | 34978955.25 | 97839787.08 | 0.225931E+09 | 31982468.29 |
October | 0.212972E+09 | 0.110929E+09 | 0.102043E+09 | 0.353470E+09 | 58948101.84 |
November | 0.262365E+09 | 0.180661E+09 | 81704326.77 | 0.392519E+09 | 0.116842E+09 |
December | 0.280344E+09 | 0.201353E+09 | 78990647.84 | 0.413242E+09 | 0.153939E+09 |
Annual Sum or Average | 0.209097E+10 | 0.100765E+10 | 0.108332E+10 | 0.324293E+10 | 0.965798E+09 |
Minimum of Months | 89889788.50 | 820432.58 | 78990647.84 | 0.155457E+09 | 15268340.12 |
Maximum of Months | 0.286900E+09 | 0.204634E+09 | 0.102043E+09 | 0.413242E+09 | 0.168374E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.286900E+09 | 0.204634E+09 | 82266484.59 | 0.407417E+09 | 0.168374E+09 |
February | 0.234972E+09 | 0.152100E+09 | 82871782.74 | 0.327217E+09 | 0.133182E+09 |
March | 0.166021E+09 | 74898042.95 | 91122482.05 | 0.216535E+09 | 0.132514E+09 |
April | 0.119066E+09 | 27860038.41 | 91206093.15 | 0.155457E+09 | 85458708.70 |
May | 94011562.55 | 3959538.48 | 90052024.07 | 0.173355E+09 | 24730360.95 |
June | 89889788.50 | 820432.58 | 89069355.92 | 0.177752E+09 | 21521182.35 |
July | 97231995.16 | 1763808.77 | 95468186.39 | 0.188661E+09 | 15268340.12 |
August | 0.114377E+09 | 13694375.47 | 0.100683E+09 | 0.211380E+09 | 23038079.53 |
September | 0.132819E+09 | 34978955.25 | 97839787.08 | 0.225931E+09 | 31982468.29 |
October | 0.212972E+09 | 0.110929E+09 | 0.102043E+09 | 0.353470E+09 | 58948101.84 |
November | 0.262365E+09 | 0.180661E+09 | 81704326.77 | 0.392519E+09 | 0.116842E+09 |
December | 0.280344E+09 | 0.201353E+09 | 78990647.84 | 0.413242E+09 | 0.153939E+09 |
Annual Sum or Average | 0.209097E+10 | 0.100765E+10 | 0.108332E+10 | 0.324293E+10 | 0.965798E+09 |
Minimum of Months | 89889788.50 | 820432.58 | 78990647.84 | 0.155457E+09 | 15268340.12 |
Maximum of Months | 0.286900E+09 | 0.204634E+09 | 0.102043E+09 | 0.413242E+09 | 0.168374E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.340537E+09 | 0.140840E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.273596E+09 | 0.111203E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.181197E+09 | 0.110608E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.130453E+09 | 70994090.99 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.146381E+09 | 19687746.67 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.150181E+09 | 17029322.22 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.159569E+09 | 11816436.93 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.178334E+09 | 18197473.72 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.189997E+09 | 25655480.76 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296343E+09 | 48423470.58 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.328363E+09 | 97440306.40 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.345529E+09 | 0.128645E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.272048E+10 | 0.800541E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.130453E+09 | 11816436.93 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.345529E+09 | 0.140840E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.340537E+09 | 0.140840E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.273596E+09 | 0.111203E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.181197E+09 | 0.110608E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.130453E+09 | 70994090.99 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.146381E+09 | 19687746.67 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.150181E+09 | 17029322.22 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.159569E+09 | 11816436.93 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.178334E+09 | 18197473.72 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.189997E+09 | 25655480.76 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296343E+09 | 48423470.58 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.328363E+09 | 97440306.40 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.345529E+09 | 0.128645E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.272048E+10 | 0.800541E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.130453E+09 | 11816436.93 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.345529E+09 | 0.140840E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.286900E+09 | 0.204634E+09 | 82266484.59 | 0.407345E+09 | 0.167192E+09 |
February | 0.234972E+09 | 0.152100E+09 | 82871782.74 | 0.327262E+09 | 0.132060E+09 |
March | 0.166021E+09 | 74898042.95 | 91122482.05 | 0.216740E+09 | 0.131315E+09 |
April | 0.119066E+09 | 27860038.41 | 91206093.15 | 0.155855E+09 | 84423172.29 |
May | 94011562.55 | 3959538.48 | 90052024.07 | 0.174377E+09 | 23504149.43 |
June | 89889788.50 | 820432.58 | 89069355.92 | 0.178852E+09 | 20325565.51 |
July | 97231995.16 | 1763808.77 | 95468186.39 | 0.190030E+09 | 14141088.69 |
August | 0.114377E+09 | 13694375.47 | 0.100683E+09 | 0.212493E+09 | 21727143.93 |
September | 0.132819E+09 | 34978955.25 | 97839787.08 | 0.226636E+09 | 30621349.77 |
October | 0.212972E+09 | 0.110929E+09 | 0.102043E+09 | 0.353810E+09 | 57637122.10 |
November | 0.262365E+09 | 0.180661E+09 | 81704326.77 | 0.392460E+09 | 0.115842E+09 |
December | 0.280344E+09 | 0.201353E+09 | 78990647.84 | 0.413125E+09 | 0.152778E+09 |
Annual Sum or Average | 0.209097E+10 | 0.100765E+10 | 0.108332E+10 | 0.324899E+10 | 0.951566E+09 |
Minimum of Months | 89889788.50 | 820432.58 | 78990647.84 | 0.155855E+09 | 14141088.69 |
Maximum of Months | 0.286900E+09 | 0.204634E+09 | 0.102043E+09 | 0.413125E+09 | 0.167192E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.340983E+09 | 0.140038E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.274034E+09 | 0.110423E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.181580E+09 | 0.109762E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.130709E+09 | 70504706.51 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.146625E+09 | 19401616.11 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.150409E+09 | 16776463.95 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.159817E+09 | 11609868.14 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.178524E+09 | 17977363.06 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.190153E+09 | 25415150.14 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296513E+09 | 48121651.81 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.328610E+09 | 97000766.15 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.345890E+09 | 0.127909E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.272385E+10 | 0.794939E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.130709E+09 | 11609868.14 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.345890E+09 | 0.140038E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.340983E+09 | 0.140038E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.274034E+09 | 0.110423E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.181580E+09 | 0.109762E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.130709E+09 | 70504706.51 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.146625E+09 | 19401616.11 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.150409E+09 | 16776463.95 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.159817E+09 | 11609868.14 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.178524E+09 | 17977363.06 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.190153E+09 | 25415150.14 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296513E+09 | 48121651.81 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.328610E+09 | 97000766.15 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.345890E+09 | 0.127909E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.272385E+10 | 0.794939E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.130709E+09 | 11609868.14 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.345890E+09 | 0.140038E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.286900E+09 | 0.204634E+09 | 82266484.59 | 0.407880E+09 | 0.166240E+09 |
February | 0.234972E+09 | 0.152100E+09 | 82871782.74 | 0.327788E+09 | 0.131134E+09 |
March | 0.166021E+09 | 74898042.95 | 91122482.05 | 0.217200E+09 | 0.130311E+09 |
April | 0.119066E+09 | 27860038.41 | 91206093.15 | 0.156163E+09 | 83842664.47 |
May | 94011562.55 | 3959538.48 | 90052024.07 | 0.174671E+09 | 23164196.25 |
June | 89889788.50 | 820432.58 | 89069355.92 | 0.179125E+09 | 20024209.20 |
July | 97231995.16 | 1763808.77 | 95468186.39 | 0.190326E+09 | 13894627.72 |
August | 0.114377E+09 | 13694375.47 | 0.100683E+09 | 0.212723E+09 | 21465806.24 |
September | 0.132819E+09 | 34978955.25 | 97839787.08 | 0.226825E+09 | 30335372.59 |
October | 0.212972E+09 | 0.110929E+09 | 0.102043E+09 | 0.354015E+09 | 57278452.61 |
November | 0.262365E+09 | 0.180661E+09 | 81704326.77 | 0.392758E+09 | 0.115319E+09 |
December | 0.280344E+09 | 0.201353E+09 | 78990647.84 | 0.413558E+09 | 0.151904E+09 |
Annual Sum or Average | 0.209097E+10 | 0.100765E+10 | 0.108332E+10 | 0.325303E+10 | 0.944914E+09 |
Minimum of Months | 89889788.50 | 820432.58 | 78990647.84 | 0.156163E+09 | 13894627.72 |
Maximum of Months | 0.286900E+09 | 0.204634E+09 | 0.102043E+09 | 0.413558E+09 | 0.166240E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.341720E+09 | 0.138583E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.274828E+09 | 0.108865E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.182263E+09 | 0.107962E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.131180E+09 | 69423600.06 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.146831E+09 | 19065210.36 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.150511E+09 | 16566056.87 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.159783E+09 | 11560603.10 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.178395E+09 | 18049805.75 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.190068E+09 | 25433272.97 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296535E+09 | 47957812.52 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.328975E+09 | 96302785.48 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.346498E+09 | 0.126579E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.272759E+10 | 0.786349E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.131180E+09 | 11560603.10 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.346498E+09 | 0.138583E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.341720E+09 | 0.138583E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.274828E+09 | 0.108865E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.182263E+09 | 0.107962E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.131180E+09 | 69423600.06 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.146831E+09 | 19065210.36 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.150511E+09 | 16566056.87 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.159783E+09 | 11560603.10 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.178395E+09 | 18049805.75 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.190068E+09 | 25433272.97 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.296535E+09 | 47957812.52 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.328975E+09 | 96302785.48 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.346498E+09 | 0.126579E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.272759E+10 | 0.786349E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.131180E+09 | 11560603.10 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.346498E+09 | 0.138583E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.286900E+09 | 0.204634E+09 | 82266484.59 | 0.408762E+09 | 0.164518E+09 |
February | 0.234972E+09 | 0.152100E+09 | 82871782.74 | 0.328738E+09 | 0.129289E+09 |
March | 0.166021E+09 | 74898042.95 | 91122482.05 | 0.218020E+09 | 0.128180E+09 |
April | 0.119066E+09 | 27860038.41 | 91206093.15 | 0.156728E+09 | 82562891.61 |
May | 94011562.55 | 3959538.48 | 90052024.07 | 0.174916E+09 | 22768545.98 |
June | 89889788.50 | 820432.58 | 89069355.92 | 0.179246E+09 | 19778105.90 |
July | 97231995.16 | 1763808.77 | 95468186.39 | 0.190283E+09 | 13840486.19 |
August | 0.114377E+09 | 13694375.47 | 0.100683E+09 | 0.212565E+09 | 21556203.04 |
September | 0.132819E+09 | 34978955.25 | 97839787.08 | 0.226721E+09 | 30362026.85 |
October | 0.212972E+09 | 0.110929E+09 | 0.102043E+09 | 0.354040E+09 | 57088668.78 |
November | 0.262365E+09 | 0.180661E+09 | 81704326.77 | 0.393194E+09 | 0.114495E+09 |
December | 0.280344E+09 | 0.201353E+09 | 78990647.84 | 0.414284E+09 | 0.150328E+09 |
Annual Sum or Average | 0.209097E+10 | 0.100765E+10 | 0.108332E+10 | 0.325750E+10 | 0.934767E+09 |
Minimum of Months | 89889788.50 | 820432.58 | 78990647.84 | 0.156728E+09 | 13840486.19 |
Maximum of Months | 0.286900E+09 | 0.204634E+09 | 0.102043E+09 | 0.414284E+09 | 0.164518E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.342990E+09 | 0.133834E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.276385E+09 | 0.103814E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.183412E+09 | 0.101846E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.132052E+09 | 65420759.35 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.146482E+09 | 18092509.30 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.149651E+09 | 16121396.03 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.158128E+09 | 11851862.77 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.176385E+09 | 19112042.50 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.188503E+09 | 26241085.56 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.295480E+09 | 47934293.04 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.329288E+09 | 94180042.65 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.347563E+09 | 0.122393E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.272632E+10 | 0.760842E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.132052E+09 | 11851862.77 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.347563E+09 | 0.133834E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239609E+09 | 0.170903E+09 | 68706075.05 | 0.342990E+09 | 0.133834E+09 |
February | 0.196241E+09 | 0.127029E+09 | 69211598.77 | 0.276385E+09 | 0.103814E+09 |
March | 0.138655E+09 | 62552211.70 | 76102292.70 | 0.183412E+09 | 0.101846E+09 |
April | 99439846.14 | 23267724.39 | 76172121.75 | 0.132052E+09 | 65420759.35 |
May | 78515151.14 | 3306867.30 | 75208283.84 | 0.146482E+09 | 18092509.30 |
June | 75072790.40 | 685196.44 | 74387593.95 | 0.149651E+09 | 16121396.03 |
July | 81204743.21 | 1473071.06 | 79731672.15 | 0.158128E+09 | 11851862.77 |
August | 95523826.33 | 11437060.83 | 84086765.50 | 0.176385E+09 | 19112042.50 |
September | 0.110926E+09 | 29213193.39 | 81712349.65 | 0.188503E+09 | 26241085.56 |
October | 0.177867E+09 | 92644050.05 | 85222812.30 | 0.295480E+09 | 47934293.04 |
November | 0.219118E+09 | 0.150881E+09 | 68236580.60 | 0.329288E+09 | 94180042.65 |
December | 0.234133E+09 | 0.168163E+09 | 65970211.39 | 0.347563E+09 | 0.122393E+09 |
Annual Sum or Average | 0.174630E+10 | 0.841556E+09 | 0.904748E+09 | 0.272632E+10 | 0.760842E+09 |
Minimum of Months | 75072790.40 | 685196.44 | 65970211.39 | 0.132052E+09 | 11851862.77 |
Maximum of Months | 0.239609E+09 | 0.170903E+09 | 85222812.30 | 0.347563E+09 | 0.133834E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.286900E+09 | 0.204634E+09 | 82266484.59 | 0.410283E+09 | 0.158901E+09 |
February | 0.234972E+09 | 0.152100E+09 | 82871782.74 | 0.330603E+09 | 0.123313E+09 |
March | 0.166021E+09 | 74898042.95 | 91122482.05 | 0.219401E+09 | 0.120942E+09 |
April | 0.119066E+09 | 27860038.41 | 91206093.15 | 0.157775E+09 | 77822655.07 |
May | 94011562.55 | 3959538.48 | 90052024.07 | 0.174485E+09 | 21615045.00 |
June | 89889788.50 | 820432.58 | 89069355.92 | 0.178201E+09 | 19251169.17 |
July | 97231995.16 | 1763808.77 | 95468186.39 | 0.188289E+09 | 14190118.01 |
August | 0.114377E+09 | 13694375.47 | 0.100683E+09 | 0.210143E+09 | 22824102.76 |
September | 0.132819E+09 | 34978955.25 | 97839787.08 | 0.224832E+09 | 31327770.89 |
October | 0.212972E+09 | 0.110929E+09 | 0.102043E+09 | 0.352759E+09 | 57073063.82 |
November | 0.262365E+09 | 0.180661E+09 | 81704326.77 | 0.393558E+09 | 0.111987E+09 |
December | 0.280344E+09 | 0.201353E+09 | 78990647.84 | 0.415553E+09 | 0.145377E+09 |
Annual Sum or Average | 0.209097E+10 | 0.100765E+10 | 0.108332E+10 | 0.325588E+10 | 0.904624E+09 |
Minimum of Months | 89889788.50 | 820432.58 | 78990647.84 | 0.157775E+09 | 14190118.01 |
Maximum of Months | 0.286900E+09 | 0.204634E+09 | 0.102043E+09 | 0.415553E+09 | 0.158901E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 808.51 | 349.99 | 573.25 | 408.87 | 164.37 | 0.00 | 0.00 |
February | 718.43 | 307.43 | 519.80 | 336.47 | 183.33 | 0.00 | 0.00 |
March | 429.17 | 274.41 | 331.72 | 149.65 | 182.07 | 0.00 | 0.00 |
April | 320.54 | 178.19 | 245.83 | 57.52 | 188.31 | 0.00 | 0.00 |
May | 351.10 | 44.61 | 187.84 | 7.91 | 179.93 | 0.00 | 0.00 |
June | 371.98 | 38.96 | 185.59 | 1.69 | 183.90 | 0.00 | 0.00 |
July | 386.23 | 25.60 | 194.28 | 3.52 | 190.75 | 0.00 | 0.00 |
August | 427.51 | 41.98 | 228.53 | 27.36 | 201.17 | 0.00 | 0.00 |
September | 471.24 | 60.50 | 274.23 | 72.22 | 202.01 | 0.00 | 0.00 |
October | 708.96 | 112.47 | 425.53 | 221.64 | 203.89 | 0.00 | 0.00 |
November | 809.30 | 244.67 | 541.70 | 373.01 | 168.69 | 0.00 | 0.00 |
December | 822.27 | 317.79 | 560.15 | 402.32 | 157.83 | 0.00 | 0.00 |
Annual Sum or Average | 551.38 | 165.62 | 354.84 | 171.00 | 183.84 | 0.00 | 0.00 |
Minimum of Months | 320.54 | 25.60 | 185.59 | 1.69 | 157.83 | 0.00 | 0.00 |
Maximum of Months | 822.27 | 349.99 | 573.25 | 408.87 | 203.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 399.78 | 184.65 | 286.62 | 204.44 | 82.19 | 0.00 | 0.00 |
February | 355.70 | 160.87 | 259.90 | 168.23 | 91.66 | 0.00 | 0.00 |
March | 212.03 | 144.25 | 165.86 | 74.83 | 91.03 | 0.00 | 0.00 |
April | 159.28 | 91.46 | 122.92 | 28.76 | 94.16 | 0.00 | 0.00 |
May | 175.53 | 23.22 | 93.92 | 3.96 | 89.97 | 0.00 | 0.00 |
June | 186.38 | 20.15 | 92.80 | 0.85 | 91.95 | 0.00 | 0.00 |
July | 193.84 | 13.15 | 97.14 | 1.76 | 95.38 | 0.00 | 0.00 |
August | 214.91 | 20.94 | 114.27 | 13.68 | 100.59 | 0.00 | 0.00 |
September | 236.33 | 30.26 | 137.11 | 36.11 | 101.00 | 0.00 | 0.00 |
October | 354.63 | 56.60 | 212.77 | 110.82 | 101.94 | 0.00 | 0.00 |
November | 403.27 | 124.25 | 270.85 | 186.50 | 84.35 | 0.00 | 0.00 |
December | 408.50 | 164.78 | 280.07 | 201.16 | 78.91 | 0.00 | 0.00 |
Annual Sum or Average | 274.66 | 85.82 | 177.42 | 85.50 | 91.92 | 0.00 | 0.00 |
Minimum of Months | 159.28 | 13.15 | 92.80 | 0.85 | 78.91 | 0.00 | 0.00 |
Maximum of Months | 408.50 | 184.65 | 286.62 | 204.44 | 101.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 400.58 | 181.22 | 286.04 | 204.02 | 82.02 | 0.00 | 0.00 |
February | 356.09 | 159.11 | 259.36 | 167.89 | 91.47 | 0.00 | 0.00 |
March | 212.00 | 143.61 | 165.52 | 74.67 | 90.85 | 0.00 | 0.00 |
April | 158.58 | 94.88 | 122.66 | 28.70 | 93.96 | 0.00 | 0.00 |
May | 172.94 | 28.70 | 93.73 | 3.95 | 89.78 | 0.00 | 0.00 |
June | 183.60 | 26.07 | 92.61 | 0.85 | 91.76 | 0.00 | 0.00 |
July | 188.50 | 18.09 | 96.94 | 1.76 | 95.18 | 0.00 | 0.00 |
August | 211.39 | 26.68 | 114.03 | 13.65 | 100.38 | 0.00 | 0.00 |
September | 233.71 | 36.84 | 136.83 | 36.04 | 100.80 | 0.00 | 0.00 |
October | 352.70 | 63.22 | 212.33 | 110.59 | 101.74 | 0.00 | 0.00 |
November | 402.69 | 127.29 | 270.29 | 186.12 | 84.17 | 0.00 | 0.00 |
December | 408.58 | 164.26 | 279.50 | 200.75 | 78.75 | 0.00 | 0.00 |
Annual Sum or Average | 273.08 | 88.79 | 177.05 | 85.32 | 91.73 | 0.00 | 0.00 |
Minimum of Months | 158.58 | 18.09 | 92.61 | 0.85 | 78.75 | 0.00 | 0.00 |
Maximum of Months | 408.58 | 181.22 | 286.04 | 204.02 | 101.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 401.59 | 178.61 | 286.04 | 204.02 | 82.02 | 0.00 | 0.00 |
February | 356.90 | 157.03 | 259.36 | 167.89 | 91.47 | 0.00 | 0.00 |
March | 212.51 | 141.97 | 165.52 | 74.67 | 90.85 | 0.00 | 0.00 |
April | 158.70 | 94.43 | 122.66 | 28.70 | 93.96 | 0.00 | 0.00 |
May | 172.81 | 29.11 | 93.73 | 3.95 | 89.78 | 0.00 | 0.00 |
June | 183.42 | 26.60 | 92.61 | 0.85 | 91.76 | 0.00 | 0.00 |
July | 188.17 | 18.74 | 96.94 | 1.76 | 95.18 | 0.00 | 0.00 |
August | 211.18 | 27.31 | 114.03 | 13.65 | 100.38 | 0.00 | 0.00 |
September | 233.51 | 37.41 | 136.83 | 36.04 | 100.80 | 0.00 | 0.00 |
October | 352.60 | 63.68 | 212.33 | 110.59 | 101.74 | 0.00 | 0.00 |
November | 402.89 | 126.72 | 270.29 | 186.12 | 84.17 | 0.00 | 0.00 |
December | 409.14 | 162.60 | 279.50 | 200.75 | 78.75 | 0.00 | 0.00 |
Annual Sum or Average | 273.25 | 88.31 | 177.05 | 85.32 | 91.73 | 0.00 | 0.00 |
Minimum of Months | 158.70 | 18.74 | 92.61 | 0.85 | 78.75 | 0.00 | 0.00 |
Maximum of Months | 409.14 | 178.61 | 286.04 | 204.02 | 101.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 402.98 | 175.68 | 286.04 | 204.02 | 82.02 | 0.00 | 0.00 |
February | 358.17 | 154.38 | 259.36 | 167.89 | 91.47 | 0.00 | 0.00 |
March | 213.51 | 139.47 | 165.52 | 74.67 | 90.85 | 0.00 | 0.00 |
April | 159.27 | 92.98 | 122.66 | 28.70 | 93.96 | 0.00 | 0.00 |
May | 173.30 | 28.13 | 93.73 | 3.95 | 89.78 | 0.00 | 0.00 |
June | 183.90 | 25.67 | 92.61 | 0.85 | 91.76 | 0.00 | 0.00 |
July | 188.67 | 17.94 | 96.94 | 1.76 | 95.18 | 0.00 | 0.00 |
August | 211.60 | 26.39 | 114.03 | 13.65 | 100.38 | 0.00 | 0.00 |
September | 233.86 | 36.49 | 136.83 | 36.04 | 100.80 | 0.00 | 0.00 |
October | 352.96 | 62.65 | 212.33 | 110.59 | 101.74 | 0.00 | 0.00 |
November | 403.50 | 125.30 | 270.29 | 186.12 | 84.17 | 0.00 | 0.00 |
December | 410.07 | 160.32 | 279.50 | 200.75 | 78.75 | 0.00 | 0.00 |
Annual Sum or Average | 273.95 | 86.75 | 177.05 | 85.32 | 91.73 | 0.00 | 0.00 |
Minimum of Months | 159.27 | 17.94 | 92.61 | 0.85 | 78.75 | 0.00 | 0.00 |
Maximum of Months | 410.07 | 175.68 | 286.04 | 204.02 | 101.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 812.96 | 337.51 | 572.07 | 408.03 | 164.04 | 0.00 | 0.00 |
February | 722.90 | 295.51 | 518.73 | 335.78 | 182.95 | 0.00 | 0.00 |
March | 432.08 | 265.61 | 331.04 | 149.34 | 181.70 | 0.00 | 0.00 |
April | 320.78 | 176.84 | 245.33 | 57.40 | 187.92 | 0.00 | 0.00 |
May | 346.78 | 49.41 | 187.46 | 7.90 | 179.56 | 0.00 | 0.00 |
June | 367.50 | 44.44 | 185.21 | 1.69 | 183.52 | 0.00 | 0.00 |
July | 377.47 | 30.46 | 193.88 | 3.52 | 190.36 | 0.00 | 0.00 |
August | 422.79 | 46.03 | 228.07 | 27.31 | 200.76 | 0.00 | 0.00 |
September | 466.65 | 66.04 | 273.66 | 72.07 | 201.59 | 0.00 | 0.00 |
October | 706.14 | 117.98 | 424.66 | 221.19 | 203.47 | 0.00 | 0.00 |
November | 809.74 | 241.81 | 540.59 | 372.24 | 168.35 | 0.00 | 0.00 |
December | 824.82 | 308.49 | 559.00 | 401.49 | 157.51 | 0.00 | 0.00 |
Annual Sum or Average | 550.12 | 164.30 | 354.11 | 170.65 | 183.46 | 0.00 | 0.00 |
Minimum of Months | 320.78 | 30.46 | 185.21 | 1.69 | 157.51 | 0.00 | 0.00 |
Maximum of Months | 824.82 | 337.51 | 572.07 | 408.03 | 203.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 406.37 | 167.59 | 286.04 | 204.02 | 82.02 | 0.00 | 0.00 |
February | 361.46 | 146.52 | 259.36 | 167.89 | 91.47 | 0.00 | 0.00 |
March | 216.22 | 131.62 | 165.52 | 74.67 | 90.85 | 0.00 | 0.00 |
April | 160.79 | 87.35 | 122.66 | 28.70 | 93.96 | 0.00 | 0.00 |
May | 174.41 | 23.48 | 93.73 | 3.95 | 89.78 | 0.00 | 0.00 |
June | 184.88 | 20.98 | 92.61 | 0.85 | 91.76 | 0.00 | 0.00 |
July | 190.10 | 14.10 | 96.94 | 1.76 | 95.18 | 0.00 | 0.00 |
August | 212.50 | 21.70 | 114.03 | 13.65 | 100.38 | 0.00 | 0.00 |
September | 234.04 | 31.61 | 136.83 | 36.04 | 100.80 | 0.00 | 0.00 |
October | 353.38 | 57.68 | 212.33 | 110.59 | 101.74 | 0.00 | 0.00 |
November | 404.78 | 119.88 | 270.29 | 186.12 | 84.17 | 0.00 | 0.00 |
December | 412.25 | 153.10 | 279.50 | 200.75 | 78.75 | 0.00 | 0.00 |
Annual Sum or Average | 275.56 | 80.94 | 177.05 | 85.32 | 91.73 | 0.00 | 0.00 |
Minimum of Months | 160.79 | 14.10 | 92.61 | 0.85 | 78.75 | 0.00 | 0.00 |
Maximum of Months | 412.25 | 167.59 | 286.04 | 204.02 | 101.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 406.90 | 166.64 | 286.04 | 204.02 | 82.02 | 0.00 | 0.00 |
February | 362.04 | 145.49 | 259.36 | 167.89 | 91.47 | 0.00 | 0.00 |
March | 216.68 | 130.61 | 165.52 | 74.67 | 90.85 | 0.00 | 0.00 |
April | 161.10 | 86.75 | 122.66 | 28.70 | 93.96 | 0.00 | 0.00 |
May | 174.70 | 23.14 | 93.73 | 3.95 | 89.78 | 0.00 | 0.00 |
June | 185.16 | 20.67 | 92.61 | 0.85 | 91.76 | 0.00 | 0.00 |
July | 190.40 | 13.86 | 96.94 | 1.76 | 95.18 | 0.00 | 0.00 |
August | 212.73 | 21.44 | 114.03 | 13.65 | 100.38 | 0.00 | 0.00 |
September | 234.23 | 31.31 | 136.83 | 36.04 | 100.80 | 0.00 | 0.00 |
October | 353.58 | 57.32 | 212.33 | 110.59 | 101.74 | 0.00 | 0.00 |
November | 405.08 | 119.34 | 270.29 | 186.12 | 84.17 | 0.00 | 0.00 |
December | 412.69 | 152.23 | 279.50 | 200.75 | 78.75 | 0.00 | 0.00 |
Annual Sum or Average | 275.90 | 80.38 | 177.05 | 85.32 | 91.73 | 0.00 | 0.00 |
Minimum of Months | 161.10 | 13.86 | 92.61 | 0.85 | 78.75 | 0.00 | 0.00 |
Maximum of Months | 412.69 | 166.64 | 286.04 | 204.02 | 101.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 407.78 | 164.91 | 286.04 | 204.02 | 82.02 | 0.00 | 0.00 |
February | 363.09 | 143.44 | 259.36 | 167.89 | 91.47 | 0.00 | 0.00 |
March | 217.50 | 128.47 | 165.52 | 74.67 | 90.85 | 0.00 | 0.00 |
April | 161.69 | 85.42 | 122.66 | 28.70 | 93.96 | 0.00 | 0.00 |
May | 174.95 | 22.74 | 93.73 | 3.95 | 89.78 | 0.00 | 0.00 |
June | 185.29 | 20.41 | 92.61 | 0.85 | 91.76 | 0.00 | 0.00 |
July | 190.36 | 13.80 | 96.94 | 1.76 | 95.18 | 0.00 | 0.00 |
August | 212.57 | 21.53 | 114.03 | 13.65 | 100.38 | 0.00 | 0.00 |
September | 234.13 | 31.34 | 136.83 | 36.04 | 100.80 | 0.00 | 0.00 |
October | 353.61 | 57.13 | 212.33 | 110.59 | 101.74 | 0.00 | 0.00 |
November | 405.53 | 118.48 | 270.29 | 186.12 | 84.17 | 0.00 | 0.00 |
December | 413.41 | 150.64 | 279.50 | 200.75 | 78.75 | 0.00 | 0.00 |
Annual Sum or Average | 276.28 | 79.51 | 177.05 | 85.32 | 91.73 | 0.00 | 0.00 |
Minimum of Months | 161.69 | 13.80 | 92.61 | 0.85 | 78.75 | 0.00 | 0.00 |
Maximum of Months | 413.41 | 164.91 | 286.04 | 204.02 | 101.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 409.30 | 159.26 | 286.04 | 204.02 | 82.02 | 0.00 | 0.00 |
February | 365.15 | 136.80 | 259.36 | 167.89 | 91.47 | 0.00 | 0.00 |
March | 218.87 | 121.20 | 165.52 | 74.67 | 90.85 | 0.00 | 0.00 |
April | 162.76 | 80.50 | 122.66 | 28.70 | 93.96 | 0.00 | 0.00 |
May | 174.53 | 21.58 | 93.73 | 3.95 | 89.78 | 0.00 | 0.00 |
June | 184.22 | 19.87 | 92.61 | 0.85 | 91.76 | 0.00 | 0.00 |
July | 188.38 | 14.15 | 96.94 | 1.76 | 95.18 | 0.00 | 0.00 |
August | 210.17 | 22.79 | 114.03 | 13.65 | 100.38 | 0.00 | 0.00 |
September | 232.19 | 32.33 | 136.83 | 36.04 | 100.80 | 0.00 | 0.00 |
October | 352.34 | 57.10 | 212.33 | 110.59 | 101.74 | 0.00 | 0.00 |
November | 405.92 | 115.87 | 270.29 | 186.12 | 84.17 | 0.00 | 0.00 |
December | 414.68 | 145.67 | 279.50 | 200.75 | 78.75 | 0.00 | 0.00 |
Annual Sum or Average | 276.15 | 76.94 | 177.05 | 85.32 | 91.73 | 0.00 | 0.00 |
Minimum of Months | 162.76 | 14.15 | 92.61 | 0.85 | 78.75 | 0.00 | 0.00 |
Maximum of Months | 414.68 | 159.26 | 286.04 | 204.02 | 101.74 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.216552E+10 | 0.937405E+09 | 0.153539E+10 | 0.109513E+10 | 0.440261E+09 | 0.00 | 0.00 |
February | 0.173802E+10 | 0.743746E+09 | 0.125749E+10 | 0.813988E+09 | 0.443501E+09 | 0.00 | 0.00 |
March | 0.114950E+10 | 0.734976E+09 | 0.888483E+09 | 0.400828E+09 | 0.487655E+09 | 0.00 | 0.00 |
April | 0.830846E+09 | 0.461863E+09 | 0.637200E+09 | 0.149097E+09 | 0.488103E+09 | 0.00 | 0.00 |
May | 0.940385E+09 | 0.119491E+09 | 0.503117E+09 | 21190057.59 | 0.481927E+09 | 0.00 | 0.00 |
June | 0.964170E+09 | 0.100991E+09 | 0.481059E+09 | 4390666.69 | 0.476668E+09 | 0.00 | 0.00 |
July | 0.103449E+10 | 68555481.99 | 0.520351E+09 | 9439284.29 | 0.510912E+09 | 0.00 | 0.00 |
August | 0.114504E+10 | 0.112445E+09 | 0.612107E+09 | 73287481.93 | 0.538819E+09 | 0.00 | 0.00 |
September | 0.122146E+10 | 0.156816E+09 | 0.710799E+09 | 0.187195E+09 | 0.523604E+09 | 0.00 | 0.00 |
October | 0.189888E+10 | 0.301246E+09 | 0.113975E+10 | 0.593653E+09 | 0.546099E+09 | 0.00 | 0.00 |
November | 0.209770E+10 | 0.634197E+09 | 0.140408E+10 | 0.966832E+09 | 0.437253E+09 | 0.00 | 0.00 |
December | 0.220238E+10 | 0.851163E+09 | 0.150030E+10 | 0.107757E+10 | 0.422730E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.173884E+11 | 0.522290E+10 | 0.111901E+11 | 0.539260E+10 | 0.579753E+10 | 0.00 | 0.00 |
Minimum of Months | 0.830846E+09 | 68555481.99 | 0.481059E+09 | 4390666.69 | 0.422730E+09 | 0.00 | 0.00 |
Maximum of Months | 0.220238E+10 | 0.937405E+09 | 0.153539E+10 | 0.109513E+10 | 0.546099E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.107076E+10 | 0.494567E+09 | 0.767694E+09 | 0.547564E+09 | 0.220131E+09 | 0.00 | 0.00 |
February | 0.860509E+09 | 0.389168E+09 | 0.628744E+09 | 0.406994E+09 | 0.221750E+09 | 0.00 | 0.00 |
March | 0.567894E+09 | 0.386369E+09 | 0.444242E+09 | 0.200414E+09 | 0.243828E+09 | 0.00 | 0.00 |
April | 0.412850E+09 | 0.237075E+09 | 0.318600E+09 | 74548564.31 | 0.244051E+09 | 0.00 | 0.00 |
May | 0.470127E+09 | 62186096.66 | 0.251558E+09 | 10595028.80 | 0.240963E+09 | 0.00 | 0.00 |
June | 0.483086E+09 | 52237089.75 | 0.240529E+09 | 2195333.35 | 0.238334E+09 | 0.00 | 0.00 |
July | 0.519175E+09 | 35221565.70 | 0.260176E+09 | 4719642.15 | 0.255456E+09 | 0.00 | 0.00 |
August | 0.575602E+09 | 56094093.40 | 0.306053E+09 | 36643740.96 | 0.269410E+09 | 0.00 | 0.00 |
September | 0.612556E+09 | 78440443.50 | 0.355400E+09 | 93597534.09 | 0.261802E+09 | 0.00 | 0.00 |
October | 0.949830E+09 | 0.151589E+09 | 0.569876E+09 | 0.296827E+09 | 0.273049E+09 | 0.00 | 0.00 |
November | 0.104527E+10 | 0.322067E+09 | 0.702042E+09 | 0.483416E+09 | 0.218626E+09 | 0.00 | 0.00 |
December | 0.109413E+10 | 0.441334E+09 | 0.750151E+09 | 0.538786E+09 | 0.211365E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.866179E+10 | 0.270635E+10 | 0.559507E+10 | 0.269630E+10 | 0.289877E+10 | 0.00 | 0.00 |
Minimum of Months | 0.412850E+09 | 35221565.70 | 0.240529E+09 | 2195333.35 | 0.211365E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109413E+10 | 0.494567E+09 | 0.767694E+09 | 0.547564E+09 | 0.273049E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.107291E+10 | 0.485390E+09 | 0.766118E+09 | 0.546439E+09 | 0.219679E+09 | 0.00 | 0.00 |
February | 0.861462E+09 | 0.384923E+09 | 0.627453E+09 | 0.406158E+09 | 0.221295E+09 | 0.00 | 0.00 |
March | 0.567827E+09 | 0.384634E+09 | 0.443330E+09 | 0.200002E+09 | 0.243327E+09 | 0.00 | 0.00 |
April | 0.411035E+09 | 0.245916E+09 | 0.317946E+09 | 74395487.18 | 0.243550E+09 | 0.00 | 0.00 |
May | 0.463212E+09 | 76862904.70 | 0.251042E+09 | 10573273.09 | 0.240469E+09 | 0.00 | 0.00 |
June | 0.475899E+09 | 67569948.42 | 0.240035E+09 | 2190825.47 | 0.237845E+09 | 0.00 | 0.00 |
July | 0.504873E+09 | 48461220.99 | 0.259641E+09 | 4709950.89 | 0.254932E+09 | 0.00 | 0.00 |
August | 0.566183E+09 | 71454701.79 | 0.305425E+09 | 36568497.14 | 0.268856E+09 | 0.00 | 0.00 |
September | 0.605782E+09 | 95487581.68 | 0.354670E+09 | 93405342.03 | 0.261264E+09 | 0.00 | 0.00 |
October | 0.944676E+09 | 0.169338E+09 | 0.568706E+09 | 0.296217E+09 | 0.272489E+09 | 0.00 | 0.00 |
November | 0.104377E+10 | 0.329939E+09 | 0.700601E+09 | 0.482423E+09 | 0.218177E+09 | 0.00 | 0.00 |
December | 0.109434E+10 | 0.439950E+09 | 0.748611E+09 | 0.537680E+09 | 0.210931E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.861197E+10 | 0.279993E+10 | 0.558358E+10 | 0.269076E+10 | 0.289281E+10 | 0.00 | 0.00 |
Minimum of Months | 0.411035E+09 | 48461220.99 | 0.240035E+09 | 2190825.47 | 0.210931E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109434E+10 | 0.485390E+09 | 0.766118E+09 | 0.546439E+09 | 0.272489E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.107563E+10 | 0.478395E+09 | 0.766118E+09 | 0.546439E+09 | 0.219679E+09 | 0.00 | 0.00 |
February | 0.863407E+09 | 0.379879E+09 | 0.627453E+09 | 0.406158E+09 | 0.221295E+09 | 0.00 | 0.00 |
March | 0.569193E+09 | 0.380243E+09 | 0.443330E+09 | 0.200002E+09 | 0.243327E+09 | 0.00 | 0.00 |
April | 0.411358E+09 | 0.244764E+09 | 0.317946E+09 | 74395487.18 | 0.243550E+09 | 0.00 | 0.00 |
May | 0.462855E+09 | 77965431.53 | 0.251042E+09 | 10573273.09 | 0.240469E+09 | 0.00 | 0.00 |
June | 0.475429E+09 | 68957961.16 | 0.240035E+09 | 2190825.47 | 0.237845E+09 | 0.00 | 0.00 |
July | 0.504000E+09 | 50183989.22 | 0.259641E+09 | 4709950.89 | 0.254932E+09 | 0.00 | 0.00 |
August | 0.565625E+09 | 73140312.02 | 0.305425E+09 | 36568497.14 | 0.268856E+09 | 0.00 | 0.00 |
September | 0.605260E+09 | 96966381.91 | 0.354670E+09 | 93405342.03 | 0.261264E+09 | 0.00 | 0.00 |
October | 0.944410E+09 | 0.170552E+09 | 0.568706E+09 | 0.296217E+09 | 0.272489E+09 | 0.00 | 0.00 |
November | 0.104428E+10 | 0.328469E+09 | 0.700601E+09 | 0.482423E+09 | 0.218177E+09 | 0.00 | 0.00 |
December | 0.109584E+10 | 0.435510E+09 | 0.748611E+09 | 0.537680E+09 | 0.210931E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.861728E+10 | 0.278503E+10 | 0.558358E+10 | 0.269076E+10 | 0.289281E+10 | 0.00 | 0.00 |
Minimum of Months | 0.411358E+09 | 50183989.22 | 0.240035E+09 | 2190825.47 | 0.210931E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109584E+10 | 0.478395E+09 | 0.766118E+09 | 0.546439E+09 | 0.272489E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.107935E+10 | 0.470539E+09 | 0.766118E+09 | 0.546439E+09 | 0.219679E+09 | 0.00 | 0.00 |
February | 0.866475E+09 | 0.373477E+09 | 0.627453E+09 | 0.406158E+09 | 0.221295E+09 | 0.00 | 0.00 |
March | 0.571864E+09 | 0.373564E+09 | 0.443330E+09 | 0.200002E+09 | 0.243327E+09 | 0.00 | 0.00 |
April | 0.412815E+09 | 0.240998E+09 | 0.317946E+09 | 74395487.18 | 0.243550E+09 | 0.00 | 0.00 |
May | 0.464180E+09 | 75335540.35 | 0.251042E+09 | 10573273.09 | 0.240469E+09 | 0.00 | 0.00 |
June | 0.476659E+09 | 66526313.19 | 0.240035E+09 | 2190825.47 | 0.237845E+09 | 0.00 | 0.00 |
July | 0.505327E+09 | 48059635.41 | 0.259641E+09 | 4709950.89 | 0.254932E+09 | 0.00 | 0.00 |
August | 0.566756E+09 | 70690731.30 | 0.305425E+09 | 36568497.14 | 0.268856E+09 | 0.00 | 0.00 |
September | 0.606173E+09 | 94588100.25 | 0.354670E+09 | 93405342.03 | 0.261264E+09 | 0.00 | 0.00 |
October | 0.945357E+09 | 0.167805E+09 | 0.568706E+09 | 0.296217E+09 | 0.272489E+09 | 0.00 | 0.00 |
November | 0.104587E+10 | 0.324775E+09 | 0.700601E+09 | 0.482423E+09 | 0.218177E+09 | 0.00 | 0.00 |
December | 0.109833E+10 | 0.429408E+09 | 0.748611E+09 | 0.537680E+09 | 0.210931E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.863915E+10 | 0.273577E+10 | 0.558358E+10 | 0.269076E+10 | 0.289281E+10 | 0.00 | 0.00 |
Minimum of Months | 0.412815E+09 | 48059635.41 | 0.240035E+09 | 2190825.47 | 0.210931E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109833E+10 | 0.470539E+09 | 0.766118E+09 | 0.546439E+09 | 0.272489E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.217743E+10 | 0.903986E+09 | 0.153224E+10 | 0.109288E+10 | 0.439357E+09 | 0.00 | 0.00 |
February | 0.174884E+10 | 0.714887E+09 | 0.125491E+10 | 0.812317E+09 | 0.442590E+09 | 0.00 | 0.00 |
March | 0.115729E+10 | 0.711421E+09 | 0.886659E+09 | 0.400005E+09 | 0.486654E+09 | 0.00 | 0.00 |
April | 0.831452E+09 | 0.458358E+09 | 0.635892E+09 | 0.148791E+09 | 0.487101E+09 | 0.00 | 0.00 |
May | 0.928825E+09 | 0.132348E+09 | 0.502084E+09 | 21146546.18 | 0.480937E+09 | 0.00 | 0.00 |
June | 0.952566E+09 | 0.115193E+09 | 0.480071E+09 | 4381650.95 | 0.475689E+09 | 0.00 | 0.00 |
July | 0.101101E+10 | 81594489.00 | 0.519283E+09 | 9419901.78 | 0.509863E+09 | 0.00 | 0.00 |
August | 0.113239E+10 | 0.123285E+09 | 0.610850E+09 | 73136994.29 | 0.537713E+09 | 0.00 | 0.00 |
September | 0.120955E+10 | 0.171174E+09 | 0.709340E+09 | 0.186811E+09 | 0.522529E+09 | 0.00 | 0.00 |
October | 0.189131E+10 | 0.315996E+09 | 0.113741E+10 | 0.592434E+09 | 0.544977E+09 | 0.00 | 0.00 |
November | 0.209885E+10 | 0.626760E+09 | 0.140120E+10 | 0.964847E+09 | 0.436355E+09 | 0.00 | 0.00 |
December | 0.220919E+10 | 0.826266E+09 | 0.149722E+10 | 0.107536E+10 | 0.421862E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.173487E+11 | 0.518127E+10 | 0.111672E+11 | 0.538153E+10 | 0.578563E+10 | 0.00 | 0.00 |
Minimum of Months | 0.831452E+09 | 81594489.00 | 0.480071E+09 | 4381650.95 | 0.421862E+09 | 0.00 | 0.00 |
Maximum of Months | 0.220919E+10 | 0.903986E+09 | 0.153224E+10 | 0.109288E+10 | 0.544977E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.108842E+10 | 0.448871E+09 | 0.766118E+09 | 0.546439E+09 | 0.219679E+09 | 0.00 | 0.00 |
February | 0.874454E+09 | 0.354465E+09 | 0.627453E+09 | 0.406158E+09 | 0.221295E+09 | 0.00 | 0.00 |
March | 0.579134E+09 | 0.352532E+09 | 0.443330E+09 | 0.200002E+09 | 0.243327E+09 | 0.00 | 0.00 |
April | 0.416762E+09 | 0.226411E+09 | 0.317946E+09 | 74395487.18 | 0.243550E+09 | 0.00 | 0.00 |
May | 0.467139E+09 | 62879599.17 | 0.251042E+09 | 10573273.09 | 0.240469E+09 | 0.00 | 0.00 |
June | 0.479214E+09 | 54383915.20 | 0.240035E+09 | 2190825.47 | 0.237845E+09 | 0.00 | 0.00 |
July | 0.509168E+09 | 37773809.22 | 0.259641E+09 | 4709950.89 | 0.254932E+09 | 0.00 | 0.00 |
August | 0.569161E+09 | 58121872.83 | 0.305425E+09 | 36568497.14 | 0.268856E+09 | 0.00 | 0.00 |
September | 0.606630E+09 | 81932225.73 | 0.354670E+09 | 93405342.03 | 0.261264E+09 | 0.00 | 0.00 |
October | 0.946496E+09 | 0.154484E+09 | 0.568706E+09 | 0.296217E+09 | 0.272489E+09 | 0.00 | 0.00 |
November | 0.104919E+10 | 0.310722E+09 | 0.700601E+09 | 0.482423E+09 | 0.218177E+09 | 0.00 | 0.00 |
December | 0.110418E+10 | 0.410069E+09 | 0.748611E+09 | 0.537680E+09 | 0.210931E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.868995E+10 | 0.255265E+10 | 0.558358E+10 | 0.269076E+10 | 0.289281E+10 | 0.00 | 0.00 |
Minimum of Months | 0.416762E+09 | 37773809.22 | 0.240035E+09 | 2190825.47 | 0.210931E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110418E+10 | 0.448871E+09 | 0.766118E+09 | 0.546439E+09 | 0.272489E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.108985E+10 | 0.446316E+09 | 0.766118E+09 | 0.546439E+09 | 0.219679E+09 | 0.00 | 0.00 |
February | 0.875856E+09 | 0.351979E+09 | 0.627453E+09 | 0.406158E+09 | 0.221295E+09 | 0.00 | 0.00 |
March | 0.580359E+09 | 0.349834E+09 | 0.443330E+09 | 0.200002E+09 | 0.243327E+09 | 0.00 | 0.00 |
April | 0.417582E+09 | 0.224852E+09 | 0.317946E+09 | 74395487.18 | 0.243550E+09 | 0.00 | 0.00 |
May | 0.467920E+09 | 61967157.69 | 0.251042E+09 | 10573273.09 | 0.240469E+09 | 0.00 | 0.00 |
June | 0.479943E+09 | 53577087.30 | 0.240035E+09 | 2190825.47 | 0.237845E+09 | 0.00 | 0.00 |
July | 0.509960E+09 | 37114238.41 | 0.259641E+09 | 4709950.89 | 0.254932E+09 | 0.00 | 0.00 |
August | 0.569771E+09 | 57420418.23 | 0.305425E+09 | 36568497.14 | 0.268856E+09 | 0.00 | 0.00 |
September | 0.607131E+09 | 81165602.83 | 0.354670E+09 | 93405342.03 | 0.261264E+09 | 0.00 | 0.00 |
October | 0.947041E+09 | 0.153522E+09 | 0.568706E+09 | 0.296217E+09 | 0.272489E+09 | 0.00 | 0.00 |
November | 0.104998E+10 | 0.309321E+09 | 0.700601E+09 | 0.482423E+09 | 0.218177E+09 | 0.00 | 0.00 |
December | 0.110534E+10 | 0.407722E+09 | 0.748611E+09 | 0.537680E+09 | 0.210931E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.870072E+10 | 0.253479E+10 | 0.558358E+10 | 0.269076E+10 | 0.289281E+10 | 0.00 | 0.00 |
Minimum of Months | 0.417582E+09 | 37114238.41 | 0.240035E+09 | 2190825.47 | 0.210931E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110534E+10 | 0.446316E+09 | 0.766118E+09 | 0.546439E+09 | 0.272489E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.109220E+10 | 0.441684E+09 | 0.766118E+09 | 0.546439E+09 | 0.219679E+09 | 0.00 | 0.00 |
February | 0.878395E+09 | 0.347020E+09 | 0.627453E+09 | 0.406158E+09 | 0.221295E+09 | 0.00 | 0.00 |
March | 0.582545E+09 | 0.344104E+09 | 0.443330E+09 | 0.200002E+09 | 0.243327E+09 | 0.00 | 0.00 |
April | 0.419088E+09 | 0.221410E+09 | 0.317946E+09 | 74395487.18 | 0.243550E+09 | 0.00 | 0.00 |
May | 0.468577E+09 | 60898705.73 | 0.251042E+09 | 10573273.09 | 0.240469E+09 | 0.00 | 0.00 |
June | 0.480267E+09 | 52910164.07 | 0.240035E+09 | 2190825.47 | 0.237845E+09 | 0.00 | 0.00 |
July | 0.509848E+09 | 36961424.41 | 0.259641E+09 | 4709950.89 | 0.254932E+09 | 0.00 | 0.00 |
August | 0.569355E+09 | 57655678.79 | 0.305425E+09 | 36568497.14 | 0.268856E+09 | 0.00 | 0.00 |
September | 0.606857E+09 | 81228418.25 | 0.354670E+09 | 93405342.03 | 0.261264E+09 | 0.00 | 0.00 |
October | 0.947109E+09 | 0.153004E+09 | 0.568706E+09 | 0.296217E+09 | 0.272489E+09 | 0.00 | 0.00 |
November | 0.105114E+10 | 0.307101E+09 | 0.700601E+09 | 0.482423E+09 | 0.218177E+09 | 0.00 | 0.00 |
December | 0.110728E+10 | 0.403485E+09 | 0.748611E+09 | 0.537680E+09 | 0.210931E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.871267E+10 | 0.250746E+10 | 0.558358E+10 | 0.269076E+10 | 0.289281E+10 | 0.00 | 0.00 |
Minimum of Months | 0.419088E+09 | 36961424.41 | 0.240035E+09 | 2190825.47 | 0.210931E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110728E+10 | 0.441684E+09 | 0.766118E+09 | 0.546439E+09 | 0.272489E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.109626E+10 | 0.426569E+09 | 0.766118E+09 | 0.546439E+09 | 0.219679E+09 | 0.00 | 0.00 |
February | 0.883373E+09 | 0.330941E+09 | 0.627453E+09 | 0.406158E+09 | 0.221295E+09 | 0.00 | 0.00 |
March | 0.586224E+09 | 0.324635E+09 | 0.443330E+09 | 0.200002E+09 | 0.243327E+09 | 0.00 | 0.00 |
April | 0.421878E+09 | 0.208664E+09 | 0.317946E+09 | 74395487.18 | 0.243550E+09 | 0.00 | 0.00 |
May | 0.467449E+09 | 57799936.89 | 0.251042E+09 | 10573273.09 | 0.240469E+09 | 0.00 | 0.00 |
June | 0.477504E+09 | 51493862.24 | 0.240035E+09 | 2190825.47 | 0.237845E+09 | 0.00 | 0.00 |
July | 0.504545E+09 | 37893631.48 | 0.259641E+09 | 4709950.89 | 0.254932E+09 | 0.00 | 0.00 |
August | 0.562913E+09 | 61048118.07 | 0.305425E+09 | 36568497.14 | 0.268856E+09 | 0.00 | 0.00 |
September | 0.601837E+09 | 83809913.63 | 0.354670E+09 | 93405342.03 | 0.261264E+09 | 0.00 | 0.00 |
October | 0.943718E+09 | 0.152942E+09 | 0.568706E+09 | 0.296217E+09 | 0.272489E+09 | 0.00 | 0.00 |
November | 0.105213E+10 | 0.300347E+09 | 0.700601E+09 | 0.482423E+09 | 0.218177E+09 | 0.00 | 0.00 |
December | 0.111068E+10 | 0.390164E+09 | 0.748611E+09 | 0.537680E+09 | 0.210931E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.870852E+10 | 0.242631E+10 | 0.558358E+10 | 0.269076E+10 | 0.289281E+10 | 0.00 | 0.00 |
Minimum of Months | 0.421878E+09 | 37893631.48 | 0.240035E+09 | 2190825.47 | 0.210931E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111068E+10 | 0.426569E+09 | 0.766118E+09 | 0.546439E+09 | 0.272489E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.01 | 8.64 | 3.24 | 3.12 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.57 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.53 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.81 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.36 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.89 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.01 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.46 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.87 | 10.53 | 3.17 | 6.00 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.01 | 8.64 | 2.44 | 3.12 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.65 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.77 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.86 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.04 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.75 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.93 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.95 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.72 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.63 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.03 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.82 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.65 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.63 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.2 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -1.8 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.94 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.57 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 17.99 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.55 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.11 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.8 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.2 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.10 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.48 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.76 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.54 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.83 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.16 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.78 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.48 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.10 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.54 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.08 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.78 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.260461E+09 | -189192181.5 | 0.00 | 0.00 | 744.00 | 0.00 | -71268353.0 | 58.99 | 0.00 | 0.00 |
February | 0.233908E+09 | -170405803.4 | 0.00 | 0.00 | 672.00 | 0.00 | -63502384.4 | 58.97 | 0.00 | 0.00 |
March | 0.254372E+09 | -184299342.5 | 0.00 | 0.00 | 744.00 | 0.00 | -70072891.0 | 58.99 | 0.00 | 0.00 |
April | 0.231800E+09 | -165472541.4 | 0.00 | 0.00 | 720.00 | 0.00 | -66326963.5 | 58.98 | 0.00 | 0.00 |
May | 0.226832E+09 | -159021100.9 | 0.00 | 0.00 | 744.00 | 0.00 | -67810477.5 | 58.98 | 0.00 | 0.00 |
June | 0.211245E+09 | -145687758.5 | 0.00 | 0.00 | 720.00 | 0.00 | -65557056.1 | 58.99 | 0.00 | 0.00 |
July | 0.210537E+09 | -142942722.2 | 0.00 | 0.00 | 744.00 | 0.00 | -67594140.8 | 58.99 | 0.00 | 0.00 |
August | 0.214871E+09 | -147331098.8 | 0.00 | 0.00 | 744.00 | 0.00 | -67540147.7 | 58.99 | 0.00 | 0.00 |
September | 0.213867E+09 | -148445483.2 | 0.00 | 0.00 | 720.00 | 0.00 | -65421150.0 | 58.98 | 0.00 | 0.00 |
October | 0.230847E+09 | -163039844.7 | 0.00 | 0.00 | 744.00 | 0.00 | -67807483.8 | 58.98 | 0.00 | 0.00 |
November | 0.235226E+09 | -168889086.0 | 0.00 | 0.00 | 720.00 | 0.00 | -66336822.5 | 58.99 | 0.00 | 0.00 |
December | 0.254803E+09 | -184823357.2 | 0.00 | 0.00 | 744.00 | 0.00 | -69979962.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.277877E+10 | -.196955E+10 | 8760.00 | -809217833.2 | 58.98 | |||||
Minimum of Months | 0.210537E+09 | -189192181.5 | 0.00 | 0.00 | 672.00 | 0.00 | -71268353.0 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.260461E+09 | -142942722.2 | 0.00 | 0.00 | 744.00 | 0.00 | -63502384.4 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.259252E+09 | -189189760.7 | 0.00 | 0.00 | 744.00 | 0.00 | -70062714.6 | 58.99 | 0.00 | 0.00 |
February | 0.233159E+09 | -170390196.7 | 0.00 | 0.00 | 672.00 | 0.00 | -62768991.5 | 58.98 | 0.00 | 0.00 |
March | 0.253615E+09 | -184296137.2 | 0.00 | 0.00 | 744.00 | 0.00 | -69319260.2 | 58.99 | 0.00 | 0.00 |
April | 0.231579E+09 | -165462554.0 | 0.00 | 0.00 | 720.00 | 0.00 | -66116787.1 | 58.99 | 0.00 | 0.00 |
May | 0.226707E+09 | -158976850.7 | 0.00 | 0.00 | 744.00 | 0.00 | -67730017.0 | 59.00 | 0.00 | 0.00 |
June | 0.211134E+09 | -145690234.9 | 0.00 | 0.00 | 720.00 | 0.00 | -65443611.4 | 58.99 | 0.00 | 0.00 |
July | 0.210481E+09 | -142946080.5 | 0.00 | 0.00 | 744.00 | 0.00 | -67534992.3 | 58.99 | 0.00 | 0.00 |
August | 0.214821E+09 | -147324757.2 | 0.00 | 0.00 | 744.00 | 0.00 | -67496225.2 | 58.99 | 0.00 | 0.00 |
September | 0.213818E+09 | -148420031.2 | 0.00 | 0.00 | 720.00 | 0.00 | -65398178.6 | 58.99 | 0.00 | 0.00 |
October | 0.230780E+09 | -163016953.0 | 0.00 | 0.00 | 744.00 | 0.00 | -67762664.0 | 58.99 | 0.00 | 0.00 |
November | 0.234996E+09 | -168879704.7 | 0.00 | 0.00 | 720.00 | 0.00 | -66115920.7 | 58.99 | 0.00 | 0.00 |
December | 0.254112E+09 | -184787459.8 | 0.00 | 0.00 | 744.00 | 0.00 | -69325029.4 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277446E+10 | -.196938E+10 | 8760.00 | -805074392.0 | 58.99 | |||||
Minimum of Months | 0.210481E+09 | -189189760.7 | 0.00 | 0.00 | 672.00 | 0.00 | -70062714.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.259252E+09 | -142946080.5 | 0.00 | 0.00 | 744.00 | 0.00 | -62768991.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.236883E+09 | -166364858.0 | 0.00 | 0.00 | 744.00 | 0.00 | -70518231.4 | 58.99 | 0.00 | 0.00 |
February | 0.212922E+09 | -149944670.6 | 0.00 | 0.00 | 672.00 | 0.00 | -62977358.8 | 59.00 | 0.00 | 0.00 |
March | 0.233912E+09 | -164594496.2 | 0.00 | 0.00 | 744.00 | 0.00 | -69317778.7 | 58.99 | 0.00 | 0.00 |
April | 0.210976E+09 | -145421305.0 | 0.00 | 0.00 | 720.00 | 0.00 | -65554287.1 | 58.99 | 0.00 | 0.00 |
May | 0.207669E+09 | -141034821.3 | 0.00 | 0.00 | 744.00 | 0.00 | -66634463.7 | 58.99 | 0.00 | 0.00 |
June | 0.194193E+09 | -129851335.2 | 0.00 | 0.00 | 720.00 | 0.00 | -64342134.4 | 58.99 | 0.00 | 0.00 |
July | 0.191077E+09 | -124881930.2 | 0.00 | 0.00 | 744.00 | 0.00 | -66195099.5 | 58.99 | 0.00 | 0.00 |
August | 0.197992E+09 | -131695093.9 | 0.00 | 0.00 | 744.00 | 0.00 | -66297218.9 | 58.99 | 0.00 | 0.00 |
September | 0.194625E+09 | -130373602.5 | 0.00 | 0.00 | 720.00 | 0.00 | -64250972.2 | 58.99 | 0.00 | 0.00 |
October | 0.210053E+09 | -143395524.4 | 0.00 | 0.00 | 744.00 | 0.00 | -66657860.1 | 58.98 | 0.00 | 0.00 |
November | 0.214789E+09 | -149113806.0 | 0.00 | 0.00 | 720.00 | 0.00 | -65674838.4 | 58.99 | 0.00 | 0.00 |
December | 0.230658E+09 | -161334310.9 | 0.00 | 0.00 | 744.00 | 0.00 | -69323213.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.253575E+10 | -.173801E+10 | 8760.00 | -797743456.9 | 58.99 | |||||
Minimum of Months | 0.191077E+09 | -166364858.0 | 0.00 | 0.00 | 672.00 | 0.00 | -70518231.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.236883E+09 | -124881930.2 | 0.00 | 0.00 | 744.00 | 0.00 | -62977358.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.237135E+09 | -166369076.6 | 0.00 | 0.00 | 744.00 | 0.00 | -70765882.9 | 58.99 | 0.00 | 0.00 |
February | 0.213103E+09 | -149955210.1 | 0.00 | 0.00 | 672.00 | 0.00 | -63147445.7 | 58.99 | 0.00 | 0.00 |
March | 0.234072E+09 | -164605690.5 | 0.00 | 0.00 | 744.00 | 0.00 | -69466391.2 | 58.99 | 0.00 | 0.00 |
April | 0.210999E+09 | -145417193.4 | 0.00 | 0.00 | 720.00 | 0.00 | -65581353.3 | 58.98 | 0.00 | 0.00 |
May | 0.207633E+09 | -141031575.0 | 0.00 | 0.00 | 744.00 | 0.00 | -66601307.9 | 58.99 | 0.00 | 0.00 |
June | 0.194133E+09 | -129855039.3 | 0.00 | 0.00 | 720.00 | 0.00 | -64277965.9 | 58.98 | 0.00 | 0.00 |
July | 0.191009E+09 | -124869032.6 | 0.00 | 0.00 | 744.00 | 0.00 | -66139699.5 | 58.99 | 0.00 | 0.00 |
August | 0.197923E+09 | -131696300.8 | 0.00 | 0.00 | 744.00 | 0.00 | -66226663.4 | 58.98 | 0.00 | 0.00 |
September | 0.194582E+09 | -130380226.0 | 0.00 | 0.00 | 720.00 | 0.00 | -64202039.0 | 58.99 | 0.00 | 0.00 |
October | 0.210016E+09 | -143358229.8 | 0.00 | 0.00 | 744.00 | 0.00 | -66657844.5 | 59.00 | 0.00 | 0.00 |
November | 0.214834E+09 | -149089301.5 | 0.00 | 0.00 | 720.00 | 0.00 | -65744749.5 | 59.00 | 0.00 | 0.00 |
December | 0.230815E+09 | -161326620.1 | 0.00 | 0.00 | 744.00 | 0.00 | -69487926.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.253625E+10 | -.173795E+10 | 8760.00 | -798299268.8 | 58.99 | |||||
Minimum of Months | 0.191009E+09 | -166369076.6 | 0.00 | 0.00 | 672.00 | 0.00 | -70765882.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.237135E+09 | -124869032.6 | 0.00 | 0.00 | 744.00 | 0.00 | -63147445.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.229058E+09 | -157228533.5 | 0.00 | 0.00 | 744.00 | 0.00 | -71829266.2 | 59.00 | 0.00 | 0.00 |
February | 0.205839E+09 | -141804283.4 | 0.00 | 0.00 | 672.00 | 0.00 | -64034941.2 | 58.99 | 0.00 | 0.00 |
March | 0.226116E+09 | -155749816.0 | 0.00 | 0.00 | 744.00 | 0.00 | -70366661.2 | 58.98 | 0.00 | 0.00 |
April | 0.203761E+09 | -137608517.2 | 0.00 | 0.00 | 720.00 | 0.00 | -66152030.7 | 58.99 | 0.00 | 0.00 |
May | 0.200423E+09 | -133376919.5 | 0.00 | 0.00 | 744.00 | 0.00 | -67046015.3 | 58.99 | 0.00 | 0.00 |
June | 0.187601E+09 | -122863107.5 | 0.00 | 0.00 | 720.00 | 0.00 | -64737794.5 | 58.99 | 0.00 | 0.00 |
July | 0.184630E+09 | -118092260.8 | 0.00 | 0.00 | 744.00 | 0.00 | -66538150.0 | 58.99 | 0.00 | 0.00 |
August | 0.191288E+09 | -124613153.4 | 0.00 | 0.00 | 744.00 | 0.00 | -66674576.8 | 58.99 | 0.00 | 0.00 |
September | 0.187915E+09 | -123375011.4 | 0.00 | 0.00 | 720.00 | 0.00 | -64540145.6 | 58.99 | 0.00 | 0.00 |
October | 0.202581E+09 | -135523523.0 | 0.00 | 0.00 | 744.00 | 0.00 | -67057664.5 | 58.99 | 0.00 | 0.00 |
November | 0.207077E+09 | -140831003.4 | 0.00 | 0.00 | 720.00 | 0.00 | -66246015.1 | 58.99 | 0.00 | 0.00 |
December | 0.222882E+09 | -152559045.8 | 0.00 | 0.00 | 744.00 | 0.00 | -70323113.7 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.244917E+10 | -.164363E+10 | 8760.00 | -805546374.8 | 58.99 | |||||
Minimum of Months | 0.184630E+09 | -157228533.5 | 0.00 | 0.00 | 672.00 | 0.00 | -71829266.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.229058E+09 | -118092260.8 | 0.00 | 0.00 | 744.00 | 0.00 | -64034941.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.229210E+09 | -157241052.7 | 0.00 | 0.00 | 744.00 | 0.00 | -71968661.1 | 58.99 | 0.00 | 0.00 |
February | 0.205967E+09 | -141798238.4 | 0.00 | 0.00 | 672.00 | 0.00 | -64168800.6 | 58.99 | 0.00 | 0.00 |
March | 0.226252E+09 | -155734583.7 | 0.00 | 0.00 | 744.00 | 0.00 | -70517468.5 | 59.00 | 0.00 | 0.00 |
April | 0.203831E+09 | -137595833.3 | 0.00 | 0.00 | 720.00 | 0.00 | -66235517.4 | 58.99 | 0.00 | 0.00 |
May | 0.200535E+09 | -133375239.7 | 0.00 | 0.00 | 744.00 | 0.00 | -67160200.8 | 59.00 | 0.00 | 0.00 |
June | 0.187714E+09 | -122871225.7 | 0.00 | 0.00 | 720.00 | 0.00 | -64842545.4 | 58.99 | 0.00 | 0.00 |
July | 0.184742E+09 | -118102589.4 | 0.00 | 0.00 | 744.00 | 0.00 | -66639764.1 | 58.99 | 0.00 | 0.00 |
August | 0.191407E+09 | -124606218.4 | 0.00 | 0.00 | 744.00 | 0.00 | -66800798.9 | 58.99 | 0.00 | 0.00 |
September | 0.188029E+09 | -123383414.8 | 0.00 | 0.00 | 720.00 | 0.00 | -64645606.0 | 58.99 | 0.00 | 0.00 |
October | 0.202685E+09 | -135515686.4 | 0.00 | 0.00 | 744.00 | 0.00 | -67169384.5 | 58.99 | 0.00 | 0.00 |
November | 0.207171E+09 | -140832238.8 | 0.00 | 0.00 | 720.00 | 0.00 | -66338731.2 | 58.99 | 0.00 | 0.00 |
December | 0.223010E+09 | -152559360.9 | 0.00 | 0.00 | 744.00 | 0.00 | -70450712.5 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245055E+10 | -.164362E+10 | 8760.00 | -806938191.0 | 58.99 | |||||
Minimum of Months | 0.184742E+09 | -157241052.7 | 0.00 | 0.00 | 672.00 | 0.00 | -71968661.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.229210E+09 | -118102589.4 | 0.00 | 0.00 | 744.00 | 0.00 | -64168800.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.229306E+09 | -157246438.3 | 0.00 | 0.00 | 744.00 | 0.00 | -72059701.0 | 58.99 | 0.00 | 0.00 |
February | 0.206063E+09 | -141805912.1 | 0.00 | 0.00 | 672.00 | 0.00 | -64256978.2 | 58.99 | 0.00 | 0.00 |
March | 0.226350E+09 | -155743813.4 | 0.00 | 0.00 | 744.00 | 0.00 | -70606268.4 | 58.99 | 0.00 | 0.00 |
April | 0.203890E+09 | -137610123.1 | 0.00 | 0.00 | 720.00 | 0.00 | -66279426.2 | 58.99 | 0.00 | 0.00 |
May | 0.200569E+09 | -133381382.2 | 0.00 | 0.00 | 744.00 | 0.00 | -67187168.7 | 58.99 | 0.00 | 0.00 |
June | 0.187745E+09 | -122868646.0 | 0.00 | 0.00 | 720.00 | 0.00 | -64876523.9 | 58.99 | 0.00 | 0.00 |
July | 0.184778E+09 | -118097082.1 | 0.00 | 0.00 | 744.00 | 0.00 | -66680766.5 | 58.99 | 0.00 | 0.00 |
August | 0.191434E+09 | -124617284.9 | 0.00 | 0.00 | 744.00 | 0.00 | -66816295.5 | 58.99 | 0.00 | 0.00 |
September | 0.188045E+09 | -123382413.5 | 0.00 | 0.00 | 720.00 | 0.00 | -64662850.4 | 58.98 | 0.00 | 0.00 |
October | 0.202721E+09 | -135507009.0 | 0.00 | 0.00 | 744.00 | 0.00 | -67213976.5 | 58.99 | 0.00 | 0.00 |
November | 0.207230E+09 | -140824334.0 | 0.00 | 0.00 | 720.00 | 0.00 | -66405549.4 | 59.00 | 0.00 | 0.00 |
December | 0.223090E+09 | -152586142.6 | 0.00 | 0.00 | 744.00 | 0.00 | -70503645.5 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.245122E+10 | -.164367E+10 | 8760.00 | -807549150.1 | 58.99 | |||||
Minimum of Months | 0.184778E+09 | -157246438.3 | 0.00 | 0.00 | 672.00 | 0.00 | -72059701.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.229306E+09 | -118097082.1 | 0.00 | 0.00 | 744.00 | 0.00 | -64256978.2 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 307.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 295.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 353.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 390.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 380.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 342.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 308.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | ||||||||||
Minimum of Months | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.475623E+09 | 25198.97 | 10-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.697767E+09 | 49683.08 | 06-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.440171E+09 | 31915.89 | 11-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.478523E+09 | 47212.98 | 21-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209208E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.697767E+09 | 49683.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 46880951.60 | 5101.84 | 10-JAN-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137937E+09 | 8481.40 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107826E+09 | 5080.96 | 11-MAR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109252E+09 | 5298.23 | 20-DEC-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.401896E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137937E+09 | 8481.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.148681E+09 | 5839.65 | 05-JAN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.225239E+09 | 14411.91 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157335E+09 | 7328.80 | 12-MAR-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171885E+09 | 5793.24 | 20-DEC-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.703140E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.225239E+09 | 14411.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.191542E+09 | 6762.34 | 05-JAN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.251545E+09 | 17035.27 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174862E+09 | 9844.66 | 12-MAR-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193374E+09 | 7501.66 | 20-DEC-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.811324E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.251545E+09 | 17035.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.259352E+09 | 6861.19 | 10-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.293989E+09 | 19658.76 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203375E+09 | 12098.83 | 12-MAR-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235096E+09 | 8731.18 | 21-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.991811E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.293989E+09 | 19658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.774895E+09 | 44440.70 | 10-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.703457E+09 | 48618.78 | 05-FEB-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.490258E+09 | 48618.78 | 12-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.646323E+09 | 48618.78 | 21-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261493E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.774895E+09 | 48618.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.445867E+09 | 24951.09 | 10-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.397756E+09 | 25278.83 | 05-FEB-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.279487E+09 | 25278.83 | 12-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.367599E+09 | 25278.83 | 21-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149071E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.445867E+09 | 25278.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.480077E+09 | 25155.57 | 10-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.418187E+09 | 25155.57 | 05-FEB-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.296034E+09 | 25155.57 | 12-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.387181E+09 | 25155.57 | 21-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158148E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.480077E+09 | 25155.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.551718E+09 | 25203.38 | 10-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.465199E+09 | 25203.38 | 05-FEB-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.339030E+09 | 25203.38 | 11-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.430245E+09 | 25203.38 | 21-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178619E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.551718E+09 | 25203.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.718711E+09 | 27502.24 | 05-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.595213E+09 | 27502.24 | 05-FEB-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.473658E+09 | 27502.24 | 10-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 487114.52 | 503.67 | 15-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.551668E+09 | 27502.24 | 20-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233974E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.718711E+09 | 27502.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.466908E+10 | 0.288303E+10 | 51640.87 | 19-JAN-09:02 | 27719.12 | 0.00 |
February | 0.00 | 0.00 | 0.608902E+10 | 0.375361E+10 | 50197.94 | 28-FEB-09:02 | 25990.30 | 0.00 |
March | 0.00 | 0.00 | 0.877136E+10 | 0.556395E+10 | 51887.46 | 07-MAR-09:02 | 27990.69 | 0.00 |
April | 0.00 | 0.00 | 0.161500E+11 | 0.103959E+11 | 52406.84 | 29-APR-08:62 | 27754.27 | 0.00 |
May | 0.00 | 0.00 | 0.362620E+11 | 0.217665E+11 | 53411.43 | 24-MAY-08:61 | 25913.15 | 0.00 |
June | 0.00 | 0.00 | 0.387417E+11 | 0.231072E+11 | 53348.17 | 19-JUN-08:61 | 26746.69 | 0.00 |
July | 0.00 | 0.00 | 0.443764E+11 | 0.246157E+11 | 53564.23 | 03-JUL-08:61 | 26344.57 | 0.00 |
August | 0.00 | 0.00 | 0.435758E+11 | 0.249905E+11 | 53705.56 | 07-AUG-08:61 | 26541.25 | 0.00 |
September | 0.00 | 0.00 | 0.388258E+11 | 0.216127E+11 | 53953.54 | 05-SEP-08:61 | 24225.54 | 0.00 |
October | 0.00 | 0.00 | 0.329515E+11 | 0.197018E+11 | 53962.36 | 06-OCT-08:61 | 25590.02 | 0.00 |
November | 0.00 | 0.00 | 0.132340E+11 | 0.821330E+10 | 52266.14 | 02-NOV-08:61 | 28383.63 | 0.00 |
December | 0.00 | 0.00 | 0.843561E+10 | 0.518667E+10 | 52102.29 | 15-DEC-09:02 | 27753.47 | 0.00 |
Annual Sum or Average | 0.292082E+12 | 0.171791E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.466908E+10 | 0.288303E+10 | 50197.94 | 24225.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.443764E+11 | 0.249905E+11 | 53962.36 | 28383.63 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.290169E+10 | 0.186794E+10 | 26920.11 | 19-JAN-09:02 | 17899.62 | 0.00 |
February | 0.00 | 0.00 | 0.381677E+10 | 0.242228E+10 | 27470.78 | 24-FEB-09:02 | 15765.49 | 0.00 |
March | 0.00 | 0.00 | 0.528782E+10 | 0.350530E+10 | 27265.33 | 07-MAR-09:02 | 17305.40 | 0.00 |
April | 0.00 | 0.00 | 0.920452E+10 | 0.615757E+10 | 27421.03 | 29-APR-08:62 | 17355.41 | 0.00 |
May | 0.00 | 0.00 | 0.186296E+11 | 0.116501E+11 | 28021.66 | 24-MAY-08:61 | 16153.97 | 0.00 |
June | 0.00 | 0.00 | 0.196960E+11 | 0.121933E+11 | 27848.16 | 19-JUN-08:61 | 16797.31 | 0.00 |
July | 0.00 | 0.00 | 0.222596E+11 | 0.128508E+11 | 28168.34 | 03-JUL-08:61 | 16105.43 | 0.00 |
August | 0.00 | 0.00 | 0.218060E+11 | 0.129498E+11 | 28178.66 | 16-AUG-08:61 | 15800.56 | 0.00 |
September | 0.00 | 0.00 | 0.195059E+11 | 0.112970E+11 | 28459.40 | 05-SEP-08:61 | 14970.87 | 0.00 |
October | 0.00 | 0.00 | 0.168974E+11 | 0.105178E+11 | 28342.39 | 06-OCT-08:61 | 15738.75 | 0.00 |
November | 0.00 | 0.00 | 0.739728E+10 | 0.475691E+10 | 27491.27 | 02-NOV-08:61 | 17305.98 | 0.00 |
December | 0.00 | 0.00 | 0.466937E+10 | 0.299328E+10 | 27295.04 | 13-DEC-09:02 | 17107.67 | 0.00 |
Annual Sum or Average | 0.152072E+12 | 0.931621E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.290169E+10 | 0.186794E+10 | 26920.11 | 14970.87 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.222596E+11 | 0.129498E+11 | 28459.40 | 17899.62 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.214115E+10 | 0.135320E+10 | 27920.67 | 31-JAN-08:62 | 12608.40 | 0.00 |
February | 0.00 | 0.00 | 0.293562E+10 | 0.183461E+10 | 27505.33 | 28-FEB-08:62 | 14036.00 | 0.00 |
March | 0.00 | 0.00 | 0.403321E+10 | 0.260569E+10 | 28207.03 | 07-MAR-08:62 | 13560.91 | 0.00 |
April | 0.00 | 0.00 | 0.716566E+10 | 0.471125E+10 | 28828.10 | 29-APR-07:02 | 15208.10 | 0.00 |
May | 0.00 | 0.00 | 0.154250E+11 | 0.937435E+10 | 29554.71 | 21-MAY-08:61 | 13871.74 | 0.00 |
June | 0.00 | 0.00 | 0.165249E+11 | 0.992806E+10 | 29850.87 | 19-JUN-07:01 | 12892.15 | 0.00 |
July | 0.00 | 0.00 | 0.183298E+11 | 0.102207E+11 | 29923.54 | 31-JUL-07:01 | 12883.61 | 0.00 |
August | 0.00 | 0.00 | 0.183785E+11 | 0.105620E+11 | 29897.63 | 14-AUG-07:01 | 12432.50 | 0.00 |
September | 0.00 | 0.00 | 0.159538E+11 | 0.887413E+10 | 29952.17 | 05-SEP-07:01 | 12558.66 | 0.00 |
October | 0.00 | 0.00 | 0.136523E+11 | 0.822075E+10 | 29847.15 | 08-OCT-08:61 | 13369.60 | 0.00 |
November | 0.00 | 0.00 | 0.591750E+10 | 0.374036E+10 | 28793.08 | 02-NOV-07:01 | 15323.47 | 0.00 |
December | 0.00 | 0.00 | 0.374613E+10 | 0.233814E+10 | 28580.73 | 16-DEC-08:62 | 15389.24 | 0.00 |
Annual Sum or Average | 0.124203E+12 | 0.737632E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.214115E+10 | 0.135320E+10 | 27505.33 | 12432.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.183785E+11 | 0.105620E+11 | 29952.17 | 15389.24 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.207280E+10 | 0.130571E+10 | 27762.82 | 31-JAN-08:62 | 12502.18 | 0.00 |
February | 0.00 | 0.00 | 0.285958E+10 | 0.178245E+10 | 27350.09 | 28-FEB-08:62 | 13945.69 | 0.00 |
March | 0.00 | 0.00 | 0.395883E+10 | 0.254980E+10 | 28047.44 | 07-MAR-08:62 | 13469.02 | 0.00 |
April | 0.00 | 0.00 | 0.712329E+10 | 0.467815E+10 | 28667.66 | 29-APR-07:02 | 15111.29 | 0.00 |
May | 0.00 | 0.00 | 0.154612E+11 | 0.939952E+10 | 29393.06 | 21-MAY-08:61 | 13815.13 | 0.00 |
June | 0.00 | 0.00 | 0.165760E+11 | 0.996451E+10 | 29682.59 | 19-JUN-07:01 | 12862.33 | 0.00 |
July | 0.00 | 0.00 | 0.184130E+11 | 0.102790E+11 | 29754.85 | 31-JUL-07:01 | 12859.94 | 0.00 |
August | 0.00 | 0.00 | 0.184456E+11 | 0.106093E+11 | 29729.08 | 14-AUG-07:01 | 12477.94 | 0.00 |
September | 0.00 | 0.00 | 0.160172E+11 | 0.891666E+10 | 29746.68 | 05-SEP-07:01 | 12593.68 | 0.00 |
October | 0.00 | 0.00 | 0.136930E+11 | 0.824996E+10 | 29657.53 | 08-OCT-08:61 | 13349.52 | 0.00 |
November | 0.00 | 0.00 | 0.586832E+10 | 0.370291E+10 | 28633.68 | 02-NOV-07:01 | 15222.34 | 0.00 |
December | 0.00 | 0.00 | 0.370188E+10 | 0.230502E+10 | 28421.06 | 16-DEC-08:62 | 15288.70 | 0.00 |
Annual Sum or Average | 0.124191E+12 | 0.737430E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.207280E+10 | 0.130571E+10 | 27350.09 | 12477.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.184456E+11 | 0.106093E+11 | 29754.85 | 15288.70 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.194164E+10 | 0.121600E+10 | 27652.07 | 19-JAN-08:62 | 12612.42 | 0.00 |
February | 0.00 | 0.00 | 0.269248E+10 | 0.167037E+10 | 27303.42 | 28-FEB-08:62 | 13880.60 | 0.00 |
March | 0.00 | 0.00 | 0.375722E+10 | 0.240363E+10 | 27998.71 | 07-MAR-08:62 | 13400.00 | 0.00 |
April | 0.00 | 0.00 | 0.687050E+10 | 0.449853E+10 | 28615.97 | 29-APR-07:02 | 14974.12 | 0.00 |
May | 0.00 | 0.00 | 0.152199E+11 | 0.922716E+10 | 29335.08 | 21-MAY-08:61 | 13718.77 | 0.00 |
June | 0.00 | 0.00 | 0.163521E+11 | 0.980194E+10 | 29633.77 | 19-JUN-07:01 | 12776.31 | 0.00 |
July | 0.00 | 0.00 | 0.181960E+11 | 0.101266E+11 | 29705.92 | 31-JUL-07:01 | 12784.71 | 0.00 |
August | 0.00 | 0.00 | 0.182199E+11 | 0.104484E+11 | 29680.19 | 14-AUG-07:01 | 12348.17 | 0.00 |
September | 0.00 | 0.00 | 0.158013E+11 | 0.876791E+10 | 29717.60 | 05-SEP-07:01 | 12515.71 | 0.00 |
October | 0.00 | 0.00 | 0.134885E+11 | 0.810052E+10 | 29631.45 | 08-OCT-08:61 | 13266.42 | 0.00 |
November | 0.00 | 0.00 | 0.565636E+10 | 0.354886E+10 | 28581.76 | 02-NOV-07:01 | 15082.41 | 0.00 |
December | 0.00 | 0.00 | 0.356055E+10 | 0.220512E+10 | 28370.26 | 16-DEC-08:62 | 15157.84 | 0.00 |
Annual Sum or Average | 0.121756E+12 | 0.720150E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.194164E+10 | 0.121600E+10 | 27303.42 | 12348.17 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.182199E+11 | 0.104484E+11 | 29717.60 | 15157.84 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.285365E+10 | 0.174340E+10 | 47943.68 | 19-JAN-09:02 | 25102.64 | 0.00 |
February | 0.00 | 0.00 | 0.413210E+10 | 0.250287E+10 | 46652.10 | 28-FEB-09:02 | 23984.91 | 0.00 |
March | 0.00 | 0.00 | 0.580764E+10 | 0.361134E+10 | 48162.11 | 07-MAR-09:02 | 25598.48 | 0.00 |
April | 0.00 | 0.00 | 0.112079E+11 | 0.720585E+10 | 48536.73 | 29-APR-08:62 | 26002.35 | 0.00 |
May | 0.00 | 0.00 | 0.261005E+11 | 0.155737E+11 | 50067.90 | 21-MAY-09:01 | 23050.03 | 0.00 |
June | 0.00 | 0.00 | 0.283550E+11 | 0.167338E+11 | 50431.08 | 19-JUN-08:61 | 21518.47 | 0.00 |
July | 0.00 | 0.00 | 0.314903E+11 | 0.171944E+11 | 50657.46 | 31-JUL-08:61 | 21417.24 | 0.00 |
August | 0.00 | 0.00 | 0.317709E+11 | 0.179076E+11 | 50500.99 | 07-AUG-08:61 | 22363.85 | 0.00 |
September | 0.00 | 0.00 | 0.270897E+11 | 0.146779E+11 | 50709.10 | 05-SEP-08:61 | 20888.00 | 0.00 |
October | 0.00 | 0.00 | 0.233448E+11 | 0.137459E+11 | 50552.51 | 08-OCT-09:01 | 22354.96 | 0.00 |
November | 0.00 | 0.00 | 0.920265E+10 | 0.561320E+10 | 48529.71 | 02-NOV-08:61 | 25926.28 | 0.00 |
December | 0.00 | 0.00 | 0.576517E+10 | 0.347923E+10 | 48348.79 | 15-DEC-09:02 | 25537.76 | 0.00 |
Annual Sum or Average | 0.207120E+12 | 0.119989E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.285365E+10 | 0.174340E+10 | 46652.10 | 20888.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.317709E+11 | 0.179076E+11 | 50709.10 | 26002.35 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.141796E+10 | 0.865680E+09 | 25122.66 | 19-JAN-09:02 | 13146.93 | 0.00 |
February | 0.00 | 0.00 | 0.206744E+10 | 0.125071E+10 | 24444.97 | 28-FEB-09:02 | 12569.76 | 0.00 |
March | 0.00 | 0.00 | 0.292786E+10 | 0.181559E+10 | 25225.06 | 07-MAR-09:02 | 13403.18 | 0.00 |
April | 0.00 | 0.00 | 0.572139E+10 | 0.367801E+10 | 25420.61 | 29-APR-08:62 | 13604.28 | 0.00 |
May | 0.00 | 0.00 | 0.134880E+11 | 0.805116E+10 | 26235.66 | 21-MAY-09:01 | 12022.42 | 0.00 |
June | 0.00 | 0.00 | 0.146603E+11 | 0.865267E+10 | 26425.29 | 19-JUN-08:61 | 11171.58 | 0.00 |
July | 0.00 | 0.00 | 0.162864E+11 | 0.889520E+10 | 26543.91 | 31-JUL-08:61 | 11143.44 | 0.00 |
August | 0.00 | 0.00 | 0.164242E+11 | 0.925962E+10 | 26461.93 | 07-AUG-08:61 | 11628.84 | 0.00 |
September | 0.00 | 0.00 | 0.139890E+11 | 0.758309E+10 | 26570.98 | 05-SEP-08:61 | 10921.78 | 0.00 |
October | 0.00 | 0.00 | 0.120422E+11 | 0.708861E+10 | 26488.92 | 08-OCT-09:01 | 11660.93 | 0.00 |
November | 0.00 | 0.00 | 0.467946E+10 | 0.284769E+10 | 25418.17 | 02-NOV-08:61 | 13589.39 | 0.00 |
December | 0.00 | 0.00 | 0.293518E+10 | 0.176823E+10 | 25327.81 | 15-DEC-09:02 | 13381.42 | 0.00 |
Annual Sum or Average | 0.106640E+12 | 0.617563E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.141796E+10 | 0.865680E+09 | 24444.97 | 10921.78 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.164242E+11 | 0.925962E+10 | 26570.98 | 13604.28 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.137777E+10 | 0.839828E+09 | 24972.30 | 19-JAN-09:02 | 13033.82 | 0.00 |
February | 0.00 | 0.00 | 0.201433E+10 | 0.121638E+10 | 24304.53 | 28-FEB-09:02 | 12474.77 | 0.00 |
March | 0.00 | 0.00 | 0.285943E+10 | 0.176789E+10 | 25083.75 | 07-MAR-09:02 | 13255.59 | 0.00 |
April | 0.00 | 0.00 | 0.563216E+10 | 0.361546E+10 | 25276.31 | 29-APR-08:62 | 13479.10 | 0.00 |
May | 0.00 | 0.00 | 0.133894E+11 | 0.798264E+10 | 26079.29 | 21-MAY-09:01 | 11923.98 | 0.00 |
June | 0.00 | 0.00 | 0.145683E+11 | 0.858743E+10 | 26271.49 | 19-JUN-08:61 | 11078.78 | 0.00 |
July | 0.00 | 0.00 | 0.161982E+11 | 0.883477E+10 | 26389.42 | 31-JUL-08:61 | 11056.27 | 0.00 |
August | 0.00 | 0.00 | 0.163404E+11 | 0.920102E+10 | 26307.91 | 07-AUG-08:61 | 11543.30 | 0.00 |
September | 0.00 | 0.00 | 0.139081E+11 | 0.752852E+10 | 26416.32 | 05-SEP-08:61 | 10840.63 | 0.00 |
October | 0.00 | 0.00 | 0.119625E+11 | 0.703158E+10 | 26334.75 | 08-OCT-09:01 | 11572.36 | 0.00 |
November | 0.00 | 0.00 | 0.461511E+10 | 0.280151E+10 | 25274.31 | 02-NOV-08:61 | 13467.73 | 0.00 |
December | 0.00 | 0.00 | 0.289131E+10 | 0.173751E+10 | 25183.31 | 15-DEC-09:02 | 13258.18 | 0.00 |
Annual Sum or Average | 0.105757E+12 | 0.611445E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.137777E+10 | 0.839828E+09 | 24304.53 | 10840.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.163404E+11 | 0.920102E+10 | 26416.32 | 13479.10 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.132154E+10 | 0.804394E+09 | 23675.92 | 01-JAN-10:02 | 14770.03 | 0.00 |
February | 0.00 | 0.00 | 0.192018E+10 | 0.115570E+10 | 23698.77 | 28-FEB-09:02 | 12112.17 | 0.00 |
March | 0.00 | 0.00 | 0.275064E+10 | 0.169274E+10 | 25144.01 | 07-MAR-09:02 | 13148.28 | 0.00 |
April | 0.00 | 0.00 | 0.546843E+10 | 0.350294E+10 | 25330.12 | 29-APR-08:62 | 13431.25 | 0.00 |
May | 0.00 | 0.00 | 0.132932E+11 | 0.791810E+10 | 26129.84 | 21-MAY-09:01 | 11897.54 | 0.00 |
June | 0.00 | 0.00 | 0.145101E+11 | 0.854744E+10 | 26331.12 | 19-JUN-08:61 | 11058.64 | 0.00 |
July | 0.00 | 0.00 | 0.161828E+11 | 0.882645E+10 | 26449.32 | 31-JUL-08:61 | 11056.96 | 0.00 |
August | 0.00 | 0.00 | 0.163606E+11 | 0.921618E+10 | 26367.62 | 07-AUG-08:61 | 11570.00 | 0.00 |
September | 0.00 | 0.00 | 0.139090E+11 | 0.753072E+10 | 26476.29 | 05-SEP-08:61 | 10860.17 | 0.00 |
October | 0.00 | 0.00 | 0.119364E+11 | 0.701405E+10 | 26394.52 | 08-OCT-09:01 | 11595.11 | 0.00 |
November | 0.00 | 0.00 | 0.453679E+10 | 0.274541E+10 | 25330.63 | 02-NOV-08:61 | 13460.02 | 0.00 |
December | 0.00 | 0.00 | 0.283381E+10 | 0.169793E+10 | 25238.41 | 15-DEC-09:02 | 13228.66 | 0.00 |
Annual Sum or Average | 0.105024E+12 | 0.606520E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.132154E+10 | 0.804394E+09 | 23675.92 | 10860.17 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.163606E+11 | 0.921618E+10 | 26476.29 | 14770.03 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.135231E+10 | 0.828271E+09 | 25435.00 | 01-JAN-10:02 | 15985.48 | 0.00 |
February | 0.00 | 0.00 | 0.191744E+10 | 0.116064E+10 | 14302.64 | 28-FEB-09:02 | 7055.32 | 0.00 |
March | 0.00 | 0.00 | 0.278312E+10 | 0.171808E+10 | 20196.05 | 07-MAR-09:02 | 9817.93 | 0.00 |
April | 0.00 | 0.00 | 0.548884E+10 | 0.353234E+10 | 28330.08 | 29-APR-08:62 | 13994.81 | 0.00 |
May | 0.00 | 0.00 | 0.138730E+11 | 0.830059E+10 | 29084.81 | 24-MAY-08:61 | 12563.21 | 0.00 |
June | 0.00 | 0.00 | 0.153030E+11 | 0.908074E+10 | 29200.23 | 19-JUN-08:61 | 11946.87 | 0.00 |
July | 0.00 | 0.00 | 0.172437E+11 | 0.952166E+10 | 29331.31 | 31-JUL-08:61 | 12065.78 | 0.00 |
August | 0.00 | 0.00 | 0.176734E+11 | 0.100825E+11 | 29240.71 | 07-AUG-08:61 | 12384.99 | 0.00 |
September | 0.00 | 0.00 | 0.150001E+11 | 0.824102E+10 | 29361.21 | 05-SEP-08:61 | 11982.32 | 0.00 |
October | 0.00 | 0.00 | 0.128200E+11 | 0.761095E+10 | 29324.39 | 22-OCT-09:01 | 12308.13 | 0.00 |
November | 0.00 | 0.00 | 0.473879E+10 | 0.288700E+10 | 28340.42 | 02-NOV-08:61 | 14296.29 | 0.00 |
December | 0.00 | 0.00 | 0.291236E+10 | 0.175415E+10 | 28201.04 | 15-DEC-09:02 | 14011.83 | 0.00 |
Annual Sum or Average | 0.111106E+12 | 0.647179E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.135231E+10 | 0.828271E+09 | 14302.64 | 7055.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.176734E+11 | 0.100825E+11 | 29361.21 | 15985.48 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149047E+10 | 0.36 | 2037.21 | 19-JAN-09:02 | 0.86 |
February | 0.135474E+10 | 0.36 | 2037.21 | 28-FEB-09:02 | 0.87 |
March | 0.149278E+10 | 0.36 | 2037.21 | 07-MAR-09:02 | 0.86 |
April | 0.144416E+10 | 0.36 | 2037.21 | 01-APR-08:62 | 0.86 |
May | 0.157255E+10 | 0.37 | 2037.21 | 01-MAY-08:62 | 0.86 |
June | 0.159616E+10 | 0.38 | 2037.21 | 01-JUN-08:62 | 0.86 |
July | 0.173893E+10 | 0.39 | 2037.21 | 01-JUL-08:61 | 0.86 |
August | 0.173590E+10 | 0.39 | 2037.21 | 01-AUG-08:61 | 0.86 |
September | 0.161363E+10 | 0.38 | 2037.21 | 01-SEP-08:61 | 0.86 |
October | 0.162589E+10 | 0.38 | 2037.21 | 02-OCT-08:62 | 0.87 |
November | 0.144627E+10 | 0.36 | 2037.21 | 01-NOV-08:62 | 0.86 |
December | 0.149851E+10 | 0.36 | 2037.21 | 09-DEC-09:02 | 0.87 |
Annual Sum or Average | 0.186100E+11 | 0.37 | |||
Minimum of Months | 0.135474E+10 | 0.36 | 2037.21 | 0.86 | |
Maximum of Months | 0.173893E+10 | 0.39 | 2037.21 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.695931E+09 | 0.36 | 1136.46 | 19-JAN-09:02 | 0.90 |
February | 0.658866E+09 | 0.36 | 1136.46 | 24-FEB-09:02 | 0.90 |
March | 0.731290E+09 | 0.37 | 1136.46 | 07-MAR-09:02 | 0.90 |
April | 0.732874E+09 | 0.38 | 1136.46 | 01-APR-08:62 | 0.90 |
May | 0.799258E+09 | 0.39 | 1136.46 | 01-MAY-08:62 | 0.90 |
June | 0.816675E+09 | 0.40 | 1136.46 | 01-JUN-08:62 | 0.90 |
July | 0.894704E+09 | 0.41 | 1136.46 | 01-JUL-08:61 | 0.90 |
August | 0.888915E+09 | 0.41 | 1136.46 | 01-AUG-08:61 | 0.90 |
September | 0.818131E+09 | 0.40 | 1136.46 | 01-SEP-08:61 | 0.90 |
October | 0.823224E+09 | 0.39 | 1136.46 | 02-OCT-08:62 | 0.90 |
November | 0.754024E+09 | 0.37 | 1136.46 | 01-NOV-08:62 | 0.90 |
December | 0.748047E+09 | 0.37 | 1136.46 | 09-DEC-09:02 | 0.90 |
Annual Sum or Average | 0.936194E+10 | 0.38 | |||
Minimum of Months | 0.658866E+09 | 0.36 | 1136.46 | 0.90 | |
Maximum of Months | 0.894704E+09 | 0.41 | 1136.46 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.673872E+09 | 0.30 | 1156.79 | 01-JAN-09:02 | 0.90 |
February | 0.612598E+09 | 0.30 | 1156.79 | 03-FEB-08:62 | 0.90 |
March | 0.687707E+09 | 0.30 | 1156.79 | 07-MAR-08:62 | 0.89 |
April | 0.654597E+09 | 0.30 | 1156.79 | 01-APR-07:02 | 0.89 |
May | 0.721258E+09 | 0.31 | 1156.79 | 01-MAY-07:02 | 0.89 |
June | 0.736726E+09 | 0.32 | 1156.79 | 01-JUN-07:02 | 0.89 |
July | 0.788584E+09 | 0.32 | 1156.79 | 01-JUL-07:01 | 0.89 |
August | 0.801056E+09 | 0.33 | 1156.79 | 01-AUG-07:01 | 0.89 |
September | 0.726796E+09 | 0.31 | 1156.79 | 01-SEP-07:01 | 0.89 |
October | 0.735848E+09 | 0.31 | 1156.79 | 01-OCT-08:62 | 0.90 |
November | 0.657068E+09 | 0.30 | 1156.79 | 01-NOV-07:02 | 0.89 |
December | 0.671779E+09 | 0.30 | 1156.79 | 09-DEC-08:62 | 0.90 |
Annual Sum or Average | 0.846789E+10 | 0.31 | |||
Minimum of Months | 0.612598E+09 | 0.30 | 1156.79 | 0.89 | |
Maximum of Months | 0.801056E+09 | 0.33 | 1156.79 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.671138E+09 | 0.30 | 1150.27 | 01-JAN-09:02 | 0.90 |
February | 0.609764E+09 | 0.30 | 1150.27 | 03-FEB-08:62 | 0.90 |
March | 0.684254E+09 | 0.30 | 1150.27 | 07-MAR-08:62 | 0.89 |
April | 0.651021E+09 | 0.30 | 1150.27 | 01-APR-07:02 | 0.89 |
May | 0.719764E+09 | 0.31 | 1150.27 | 01-MAY-07:02 | 0.89 |
June | 0.736118E+09 | 0.32 | 1150.27 | 01-JUN-07:02 | 0.89 |
July | 0.789607E+09 | 0.32 | 1150.27 | 01-JUL-07:01 | 0.89 |
August | 0.801283E+09 | 0.33 | 1150.27 | 01-AUG-07:01 | 0.89 |
September | 0.726315E+09 | 0.31 | 1150.27 | 01-SEP-07:01 | 0.89 |
October | 0.734714E+09 | 0.31 | 1150.27 | 01-OCT-08:62 | 0.90 |
November | 0.653587E+09 | 0.30 | 1150.27 | 01-NOV-07:02 | 0.89 |
December | 0.668576E+09 | 0.30 | 1150.27 | 09-DEC-08:62 | 0.90 |
Annual Sum or Average | 0.844614E+10 | 0.31 | |||
Minimum of Months | 0.609764E+09 | 0.30 | 1150.27 | 0.89 | |
Maximum of Months | 0.801283E+09 | 0.33 | 1150.27 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.671667E+09 | 0.30 | 1148.37 | 01-JAN-09:02 | 0.90 |
February | 0.609672E+09 | 0.30 | 1148.37 | 03-FEB-08:62 | 0.90 |
March | 0.683709E+09 | 0.30 | 1148.37 | 07-MAR-08:62 | 0.89 |
April | 0.649465E+09 | 0.30 | 1148.37 | 01-APR-07:02 | 0.89 |
May | 0.714431E+09 | 0.31 | 1148.37 | 01-MAY-07:02 | 0.89 |
June | 0.730162E+09 | 0.32 | 1148.37 | 01-JUN-07:02 | 0.89 |
July | 0.783308E+09 | 0.32 | 1148.37 | 01-JUL-07:01 | 0.89 |
August | 0.794881E+09 | 0.33 | 1148.37 | 01-AUG-07:01 | 0.89 |
September | 0.721407E+09 | 0.31 | 1148.37 | 01-SEP-07:01 | 0.89 |
October | 0.729998E+09 | 0.31 | 1148.37 | 01-OCT-08:62 | 0.90 |
November | 0.651594E+09 | 0.30 | 1148.37 | 01-NOV-07:02 | 0.89 |
December | 0.668382E+09 | 0.30 | 1148.37 | 09-DEC-08:62 | 0.90 |
Annual Sum or Average | 0.840868E+10 | 0.31 | |||
Minimum of Months | 0.609672E+09 | 0.30 | 1148.37 | 0.89 | |
Maximum of Months | 0.794881E+09 | 0.33 | 1148.37 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.102989E+10 | 0.27 | 1893.02 | 01-JAN-10:02 | 0.87 |
February | 0.932679E+09 | 0.27 | 1893.02 | 05-FEB-10:01 | 0.88 |
March | 0.104514E+10 | 0.27 | 1893.02 | 07-MAR-09:02 | 0.86 |
April | 0.990432E+09 | 0.26 | 1893.02 | 15-APR-08:62 | 0.86 |
May | 0.112042E+10 | 0.28 | 1893.02 | 01-MAY-08:62 | 0.86 |
June | 0.115993E+10 | 0.29 | 1893.02 | 01-JUN-08:62 | 0.86 |
July | 0.126196E+10 | 0.29 | 1893.02 | 01-JUL-08:61 | 0.86 |
August | 0.127686E+10 | 0.30 | 1893.02 | 01-AUG-08:61 | 0.86 |
September | 0.114574E+10 | 0.29 | 1893.02 | 01-SEP-08:61 | 0.86 |
October | 0.115282E+10 | 0.28 | 1893.02 | 01-OCT-09:02 | 0.87 |
November | 0.996429E+09 | 0.27 | 1893.02 | 01-NOV-08:62 | 0.86 |
December | 0.102323E+10 | 0.26 | 1893.02 | 09-DEC-09:02 | 0.87 |
Annual Sum or Average | 0.131355E+11 | 0.28 | |||
Minimum of Months | 0.932679E+09 | 0.26 | 1893.02 | 0.86 | |
Maximum of Months | 0.127686E+10 | 0.30 | 1893.02 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.559366E+09 | 0.28 | 1026.32 | 01-JAN-10:02 | 0.90 |
February | 0.506379E+09 | 0.28 | 1026.32 | 05-FEB-10:01 | 0.91 |
March | 0.567180E+09 | 0.28 | 1026.32 | 07-MAR-09:02 | 0.89 |
April | 0.536679E+09 | 0.27 | 1026.32 | 15-APR-08:62 | 0.89 |
May | 0.605859E+09 | 0.29 | 1026.32 | 01-MAY-08:62 | 0.89 |
June | 0.626412E+09 | 0.30 | 1026.32 | 01-JUN-08:62 | 0.89 |
July | 0.680507E+09 | 0.30 | 1026.32 | 01-JUL-08:61 | 0.89 |
August | 0.688755E+09 | 0.31 | 1026.32 | 01-AUG-08:61 | 0.89 |
September | 0.618342E+09 | 0.29 | 1026.32 | 01-SEP-08:61 | 0.89 |
October | 0.621953E+09 | 0.29 | 1026.32 | 01-OCT-09:02 | 0.90 |
November | 0.539603E+09 | 0.28 | 1026.32 | 01-NOV-08:62 | 0.89 |
December | 0.555306E+09 | 0.27 | 1026.32 | 10-DEC-10:02 | 0.90 |
Annual Sum or Average | 0.710634E+10 | 0.29 | |||
Minimum of Months | 0.506379E+09 | 0.27 | 1026.32 | 0.89 | |
Maximum of Months | 0.688755E+09 | 0.31 | 1026.32 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.556988E+09 | 0.28 | 1020.35 | 01-JAN-10:02 | 0.90 |
February | 0.503963E+09 | 0.28 | 1020.35 | 05-FEB-10:01 | 0.91 |
March | 0.564304E+09 | 0.28 | 1020.35 | 07-MAR-09:02 | 0.89 |
April | 0.533510E+09 | 0.27 | 1020.35 | 15-APR-08:62 | 0.89 |
May | 0.602223E+09 | 0.29 | 1020.35 | 01-MAY-08:62 | 0.89 |
June | 0.622848E+09 | 0.30 | 1020.35 | 01-JUN-08:62 | 0.89 |
July | 0.677083E+09 | 0.30 | 1020.35 | 01-JUL-08:61 | 0.89 |
August | 0.685387E+09 | 0.31 | 1020.35 | 01-AUG-08:61 | 0.89 |
September | 0.615136E+09 | 0.29 | 1020.35 | 01-SEP-08:61 | 0.89 |
October | 0.618535E+09 | 0.29 | 1020.35 | 01-OCT-09:02 | 0.90 |
November | 0.536407E+09 | 0.28 | 1020.35 | 01-NOV-08:62 | 0.89 |
December | 0.552544E+09 | 0.27 | 1020.35 | 10-DEC-10:02 | 0.90 |
Annual Sum or Average | 0.706893E+10 | 0.29 | |||
Minimum of Months | 0.503963E+09 | 0.27 | 1020.35 | 0.89 | |
Maximum of Months | 0.685387E+09 | 0.31 | 1020.35 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.559942E+09 | 0.28 | 1022.67 | 01-JAN-10:02 | 0.90 |
February | 0.506203E+09 | 0.28 | 1022.67 | 05-FEB-10:01 | 0.91 |
March | 0.566560E+09 | 0.28 | 1022.67 | 07-MAR-09:02 | 0.89 |
April | 0.534373E+09 | 0.27 | 1022.67 | 22-APR-08:62 | 0.90 |
May | 0.601159E+09 | 0.29 | 1022.67 | 01-MAY-08:62 | 0.89 |
June | 0.622110E+09 | 0.30 | 1022.67 | 01-JUN-08:62 | 0.89 |
July | 0.677579E+09 | 0.30 | 1022.67 | 01-JUL-08:61 | 0.89 |
August | 0.686717E+09 | 0.31 | 1022.67 | 01-AUG-08:61 | 0.89 |
September | 0.616173E+09 | 0.29 | 1022.67 | 01-SEP-08:61 | 0.89 |
October | 0.619296E+09 | 0.29 | 1022.67 | 01-OCT-09:02 | 0.90 |
November | 0.537252E+09 | 0.27 | 1022.67 | 01-NOV-08:62 | 0.89 |
December | 0.554678E+09 | 0.27 | 1022.67 | 10-DEC-10:02 | 0.90 |
Annual Sum or Average | 0.708204E+10 | 0.29 | |||
Minimum of Months | 0.506203E+09 | 0.27 | 1022.67 | 0.89 | |
Maximum of Months | 0.686717E+09 | 0.31 | 1022.67 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.623742E+09 | 0.28 | 1134.10 | 05-JAN-09:02 | 0.91 |
February | 0.563454E+09 | 0.28 | 1134.10 | 05-FEB-10:01 | 0.91 |
March | 0.630701E+09 | 0.28 | 1134.10 | 10-MAR-09:02 | 0.91 |
April | 0.590406E+09 | 0.27 | 1134.10 | 23-APR-09:02 | 0.90 |
May | 0.648645E+09 | 0.28 | 1134.10 | 01-MAY-08:62 | 0.89 |
June | 0.668487E+09 | 0.29 | 1134.10 | 01-JUN-08:62 | 0.89 |
July | 0.731885E+09 | 0.30 | 1134.10 | 01-JUL-08:61 | 0.89 |
August | 0.746794E+09 | 0.31 | 1134.10 | 01-AUG-08:61 | 0.89 |
September | 0.672166E+09 | 0.29 | 1134.10 | 01-SEP-08:61 | 0.89 |
October | 0.676014E+09 | 0.29 | 1134.10 | 01-OCT-09:02 | 0.90 |
November | 0.593150E+09 | 0.27 | 1134.10 | 01-NOV-08:62 | 0.89 |
December | 0.616848E+09 | 0.28 | 1134.10 | 10-DEC-10:02 | 0.90 |
Annual Sum or Average | 0.776229E+10 | 0.29 | |||
Minimum of Months | 0.563454E+09 | 0.27 | 1134.10 | 0.89 | |
Maximum of Months | 0.746794E+09 | 0.31 | 1134.10 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.31 | 0.82 |
February | 0.08 | 1.50 |
March | 0.31 | 1.50 |
April | 0.08 | 1.50 |
May | 0.06 | 0.00 |
June | 0.44 | 0.00 |
July | 1.14 | 0.00 |
August | 1.81 | 0.00 |
September | 0.72 | 0.00 |
October | 1.14 | 0.44 |
November | 0.47 | 1.50 |
December | 0.47 | 1.50 |
Annual Sum or Average | 7.03 | 0.41 |
Minimum of Months | 0.06 | 0.00 |
Maximum of Months | 1.81 | 1.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.66 | 4.35 |
February | 1.65 | 5.02 |
March | 2.39 | 3.56 |
April | 2.22 | 5.36 |
May | 0.14 | 0.00 |
June | 0.69 | 0.00 |
July | 1.81 | 0.00 |
August | 2.22 | 0.00 |
September | 0.97 | 0.00 |
October | 2.12 | 1.44 |
November | 3.36 | 4.68 |
December | 2.31 | 3.73 |
Annual Sum or Average | 23.54 | 3.06 |
Minimum of Months | 0.14 | 0.00 |
Maximum of Months | 3.66 | 5.36 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.24 | 0.75 |
February | 0.54 | 0.75 |
March | 1.40 | 0.71 |
April | 0.84 | 0.75 |
May | 2.70 | 0.75 |
June | 3.15 | 0.73 |
July | 3.48 | 0.75 |
August | 2.76 | 0.75 |
September | 2.17 | 0.75 |
October | 1.46 | 0.75 |
November | 1.28 | 0.67 |
December | 2.22 | 0.72 |
Annual Sum or Average | 23.24 | 0.74 |
Minimum of Months | 0.54 | 0.67 |
Maximum of Months | 3.48 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.96 | 0.75 |
February | 0.54 | 0.75 |
March | 1.54 | 0.71 |
April | 0.64 | 0.75 |
May | 2.70 | 0.75 |
June | 3.15 | 0.73 |
July | 3.48 | 0.75 |
August | 2.76 | 0.75 |
September | 2.17 | 0.75 |
October | 1.46 | 0.75 |
November | 1.11 | 0.66 |
December | 2.14 | 0.72 |
Annual Sum or Average | 22.65 | 0.74 |
Minimum of Months | 0.54 | 0.66 |
Maximum of Months | 3.48 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.85 | 0.75 |
February | 0.65 | 0.75 |
March | 1.37 | 0.70 |
April | 0.81 | 0.75 |
May | 2.61 | 0.75 |
June | 3.15 | 0.73 |
July | 3.48 | 0.75 |
August | 2.76 | 0.75 |
September | 2.08 | 0.75 |
October | 1.38 | 0.75 |
November | 1.50 | 0.68 |
December | 1.85 | 0.72 |
Annual Sum or Average | 22.50 | 0.74 |
Minimum of Months | 0.65 | 0.68 |
Maximum of Months | 3.48 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 3.30 |
February | 0.25 | 3.30 |
March | 0.43 | 2.66 |
April | 0.28 | 3.30 |
May | 0.96 | 3.30 |
June | 1.30 | 2.81 |
July | 1.95 | 2.64 |
August | 1.24 | 2.26 |
September | 1.25 | 3.15 |
October | 1.35 | 1.81 |
November | 0.19 | 0.94 |
December | 0.22 | 2.06 |
Annual Sum or Average | 9.60 | 2.63 |
Minimum of Months | 0.17 | 0.94 |
Maximum of Months | 1.95 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 1.65 |
February | 0.17 | 1.65 |
March | 0.35 | 1.65 |
April | 0.28 | 1.65 |
May | 0.82 | 1.65 |
June | 1.14 | 1.49 |
July | 1.65 | 1.43 |
August | 1.20 | 1.11 |
September | 1.08 | 1.57 |
October | 0.81 | 1.08 |
November | 0.19 | 0.47 |
December | 0.22 | 1.03 |
Annual Sum or Average | 8.07 | 1.39 |
Minimum of Months | 0.17 | 0.47 |
Maximum of Months | 1.65 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.25 | 1.65 |
March | 0.35 | 1.65 |
April | 0.28 | 1.65 |
May | 0.82 | 1.65 |
June | 1.14 | 1.49 |
July | 1.65 | 1.43 |
August | 1.13 | 1.24 |
September | 1.08 | 1.57 |
October | 0.81 | 1.08 |
November | 0.19 | 0.47 |
December | 0.22 | 1.03 |
Annual Sum or Average | 7.92 | 1.41 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.65 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.08 | 1.65 |
March | 0.35 | 1.65 |
April | 0.28 | 1.65 |
May | 0.82 | 1.65 |
June | 1.14 | 1.49 |
July | 1.65 | 1.43 |
August | 1.14 | 1.17 |
September | 1.03 | 1.56 |
October | 0.81 | 1.08 |
November | 0.19 | 0.47 |
December | 0.14 | 0.66 |
Annual Sum or Average | 7.63 | 1.39 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.65 | 1.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.18 | 1.65 |
April | 0.28 | 1.65 |
May | 0.87 | 1.65 |
June | 1.39 | 1.22 |
July | 2.12 | 1.22 |
August | 1.78 | 0.75 |
September | 1.25 | 1.47 |
October | 1.44 | 0.85 |
November | 0.11 | 0.82 |
December | 0.00 | 0.00 |
Annual Sum or Average | 9.42 | 1.16 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.12 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.266308E+10 | 0.594528E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.287957E+10 | 0.872209E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.370817E+10 | 0.550213E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.551268E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.104441E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.110312E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.123550E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.121878E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.108321E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.953768E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.468845E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.356440E+10 | 0.598154E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.894042E+11 | 0.261510E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.266308E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.123550E+11 | 0.872209E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.141356E+10 | 58601189.50 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.159964E+10 | 0.172421E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.204626E+10 | 0.134782E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.302638E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.536401E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.562512E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.624311E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.613568E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.546154E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.488370E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.254883E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.188493E+10 | 0.136565E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.462328E+11 | 0.502370E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.141356E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.624311E+10 | 0.172421E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.120427E+10 | 0.185852E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.133609E+10 | 0.281549E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.168804E+10 | 0.196669E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.243129E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.442604E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.469143E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.509975E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.514129E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.443846E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.395829E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.208666E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.157465E+10 | 0.214856E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.380763E+11 | 0.878925E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.120427E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.514129E+10 | 0.281549E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.118531E+10 | 0.239428E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.131504E+10 | 0.314432E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.166641E+10 | 0.218578E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.241651E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.442961E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.469944E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.511778E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.515422E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.444964E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.396423E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.207047E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.156005E+10 | 0.241717E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.380287E+11 | 0.101415E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.118531E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.515422E+10 | 0.314432E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.115546E+10 | 0.324190E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.127637E+10 | 0.367486E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.161939E+10 | 0.254219E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.235737E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.437149E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.464316E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.506163E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.509655E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.439773E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.391362E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.201944E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.152771E+10 | 0.293870E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.374399E+11 | 0.123976E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.115546E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.509655E+10 | 0.367486E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.175474E+10 | 0.968619E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.197545E+10 | 0.879322E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.251632E+10 | 0.612823E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.382129E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.746767E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.802231E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.875314E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.886618E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.751901E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.673234E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.324617E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.243054E+10 | 0.807904E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.631052E+11 | 0.326867E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.175474E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.886618E+10 | 0.968619E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.914243E+09 | 0.557333E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.102048E+10 | 0.497195E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.129798E+10 | 0.349358E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.195989E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.383851E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.412283E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.449671E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.455392E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.386006E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.345575E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.166551E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.126071E+10 | 0.459499E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.324466E+11 | 0.186339E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.914243E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.455392E+10 | 0.557333E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.902138E+09 | 0.600096E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.100535E+10 | 0.522734E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.127870E+10 | 0.370042E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.193516E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.381118E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.409666E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.447146E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.452962E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.383741E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.343301E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.164672E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.124758E+10 | 0.483976E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.321950E+11 | 0.197685E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.902138E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.452962E+10 | 0.600096E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.891766E+09 | 0.689648E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.985478E+09 | 0.581499E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.125591E+10 | 0.423787E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.189838E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.379034E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.408414E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.446981E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.453658E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.383983E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.342860E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.162939E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.123703E+10 | 0.537806E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.320473E+11 | 0.223274E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.891766E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.453658E+10 | 0.689648E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.966228E+09 | 0.898389E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.104757E+10 | 0.744016E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.133586E+10 | 0.592072E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.197579E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.400804E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.434791E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.480324E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.493013E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.417142E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.370899E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.174187E+10 | 608893.15 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.132687E+10 | 0.689585E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.343639E+11 | 0.292467E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.966228E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.493013E+10 | 0.898389E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149047E+10 | 0.466908E+10 | 0.475623E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135474E+10 | 0.608902E+10 | 0.697767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149278E+10 | 0.877136E+10 | 0.440171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144416E+10 | 0.161500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157255E+10 | 0.362620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159616E+10 | 0.387417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.173893E+10 | 0.443764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173590E+10 | 0.435758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161363E+10 | 0.388258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162589E+10 | 0.329515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144627E+10 | 0.132340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149851E+10 | 0.843561E+10 | 0.478523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186100E+11 | 0.292082E+12 | 0.209208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135474E+10 | 0.466908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173893E+10 | 0.443764E+11 | 0.697767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.695931E+09 | 0.287066E+10 | 46880951.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.658866E+09 | 0.378962E+10 | 0.137937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.731290E+09 | 0.523746E+10 | 0.107826E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.732874E+09 | 0.913921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.799258E+09 | 0.186296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.816675E+09 | 0.196960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.894704E+09 | 0.222596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.888915E+09 | 0.218060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.818131E+09 | 0.195059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.823224E+09 | 0.168507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.754024E+09 | 0.733260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.748047E+09 | 0.465295E+10 | 0.109252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.936194E+10 | 0.151770E+12 | 0.401896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.658866E+09 | 0.287066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.894704E+09 | 0.222596E+11 | 0.137937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.673872E+09 | 0.214115E+10 | 0.148681E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.612598E+09 | 0.293562E+10 | 0.225239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.687707E+09 | 0.403321E+10 | 0.157335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.654597E+09 | 0.716566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.721258E+09 | 0.154250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.736726E+09 | 0.165249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.788584E+09 | 0.183298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.801056E+09 | 0.183785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.726796E+09 | 0.159538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.735848E+09 | 0.136523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.657068E+09 | 0.591750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.671779E+09 | 0.374613E+10 | 0.171885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.846789E+10 | 0.124203E+12 | 0.703140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.612598E+09 | 0.214115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.801056E+09 | 0.183785E+11 | 0.225239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.671138E+09 | 0.207280E+10 | 0.191542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.609764E+09 | 0.285958E+10 | 0.251545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.684254E+09 | 0.395883E+10 | 0.174862E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.651021E+09 | 0.712329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.719764E+09 | 0.154612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.736118E+09 | 0.165760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.789607E+09 | 0.184130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.801283E+09 | 0.184456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.726315E+09 | 0.160172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.734714E+09 | 0.136930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.653587E+09 | 0.586832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.668576E+09 | 0.370188E+10 | 0.193374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.844614E+10 | 0.124191E+12 | 0.811324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.609764E+09 | 0.207280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.801283E+09 | 0.184456E+11 | 0.251545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.671667E+09 | 0.194164E+10 | 0.259352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.609672E+09 | 0.269248E+10 | 0.293989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.683709E+09 | 0.375722E+10 | 0.203375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.649465E+09 | 0.687050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.714431E+09 | 0.152199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.730162E+09 | 0.163521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.783308E+09 | 0.181960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.794881E+09 | 0.182199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.721407E+09 | 0.158013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.729998E+09 | 0.134885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.651594E+09 | 0.565636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.668382E+09 | 0.356055E+10 | 0.235096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.840868E+10 | 0.121756E+12 | 0.991811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.609672E+09 | 0.194164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.794881E+09 | 0.182199E+11 | 0.293989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.102989E+10 | 0.285365E+10 | 0.774895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.932679E+09 | 0.413210E+10 | 0.703457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104514E+10 | 0.580764E+10 | 0.490258E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.990432E+09 | 0.112079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112042E+10 | 0.261005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115993E+10 | 0.283550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.126196E+10 | 0.314903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127686E+10 | 0.317709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114574E+10 | 0.270897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115282E+10 | 0.233448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.996429E+09 | 0.920265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102323E+10 | 0.576517E+10 | 0.646323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131355E+11 | 0.207120E+12 | 0.261493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.932679E+09 | 0.285365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127686E+10 | 0.317709E+11 | 0.774895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.559366E+09 | 0.141796E+10 | 0.445867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.506379E+09 | 0.206744E+10 | 0.397756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.567180E+09 | 0.292786E+10 | 0.279487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.536679E+09 | 0.572139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.605859E+09 | 0.134880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.626412E+09 | 0.146603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.680507E+09 | 0.162864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.688755E+09 | 0.164242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.618342E+09 | 0.139890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.621953E+09 | 0.120422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.539603E+09 | 0.467946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.555306E+09 | 0.293518E+10 | 0.367599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.710634E+10 | 0.106640E+12 | 0.149071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.506379E+09 | 0.141796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.688755E+09 | 0.164242E+11 | 0.445867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.556988E+09 | 0.137777E+10 | 0.480077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.503963E+09 | 0.201433E+10 | 0.418187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.564304E+09 | 0.285943E+10 | 0.296034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.533510E+09 | 0.563216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.602223E+09 | 0.133894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.622848E+09 | 0.145683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677083E+09 | 0.161982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.685387E+09 | 0.163404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.615136E+09 | 0.139081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.618535E+09 | 0.119625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.536407E+09 | 0.461511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.552544E+09 | 0.289131E+10 | 0.387181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.706893E+10 | 0.105757E+12 | 0.158148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.503963E+09 | 0.137777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.685387E+09 | 0.163404E+11 | 0.480077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.559942E+09 | 0.132154E+10 | 0.551718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.506203E+09 | 0.192018E+10 | 0.465199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.566560E+09 | 0.275064E+10 | 0.339030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.534373E+09 | 0.546843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.601159E+09 | 0.132932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.622110E+09 | 0.145101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677579E+09 | 0.161828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.686717E+09 | 0.163606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.616173E+09 | 0.139090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.619296E+09 | 0.119364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.537252E+09 | 0.453679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.554678E+09 | 0.283381E+10 | 0.430245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.708204E+10 | 0.105024E+12 | 0.178619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.506203E+09 | 0.132154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.686717E+09 | 0.163606E+11 | 0.551718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.623742E+09 | 0.135231E+10 | 0.718711E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.563454E+09 | 0.191744E+10 | 0.595213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.630701E+09 | 0.278312E+10 | 0.473658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.590406E+09 | 0.548884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.648645E+09 | 0.138730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.668487E+09 | 0.153030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.731885E+09 | 0.172437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.746794E+09 | 0.176734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.672166E+09 | 0.150001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.676014E+09 | 0.128200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.593150E+09 | 0.473879E+10 | 487114.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.616848E+09 | 0.291236E+10 | 0.551668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.776229E+10 | 0.111106E+12 | 0.233974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.563454E+09 | 0.135231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.746794E+09 | 0.176734E+11 | 0.718711E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.149047E+10 | 0.00 | 0.00 | 0.00 | 0.117261E+10 | 0.00 | 0.594528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135474E+10 | 0.00 | 0.00 | 0.00 | 0.152483E+10 | 0.00 | 0.872209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149278E+10 | 0.00 | 0.00 | 0.00 | 0.221540E+10 | 0.00 | 0.550213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144416E+10 | 0.00 | 0.00 | 0.00 | 0.406851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157255E+10 | 0.00 | 0.00 | 0.00 | 0.887153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159616E+10 | 0.00 | 0.00 | 0.00 | 0.943506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.173893E+10 | 0.00 | 0.00 | 0.00 | 0.106160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173590E+10 | 0.00 | 0.00 | 0.00 | 0.104520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161363E+10 | 0.00 | 0.00 | 0.00 | 0.921843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162589E+10 | 0.00 | 0.00 | 0.00 | 0.791180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144627E+10 | 0.00 | 0.00 | 0.00 | 0.324218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149851E+10 | 0.00 | 0.00 | 0.00 | 0.206589E+10 | 0.00 | 0.598154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186100E+11 | 0.00 | 0.00 | 0.00 | 0.707942E+11 | 0.00 | 0.261510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.135474E+10 | 0.00 | 0.00 | 0.00 | 0.117261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173893E+10 | 0.00 | 0.00 | 0.00 | 0.106160E+11 | 0.00 | 0.872209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.695931E+09 | 0.00 | 0.00 | 0.00 | 0.717626E+09 | 0.00 | 58601189.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.658866E+09 | 0.00 | 0.00 | 0.00 | 0.940776E+09 | 0.00 | 0.172421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.731290E+09 | 0.00 | 0.00 | 0.00 | 0.131497E+10 | 0.00 | 0.134782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.732874E+09 | 0.00 | 0.00 | 0.00 | 0.229351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.799258E+09 | 0.00 | 0.00 | 0.00 | 0.456475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.816675E+09 | 0.00 | 0.00 | 0.00 | 0.480844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.894704E+09 | 0.00 | 0.00 | 0.00 | 0.534840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.888915E+09 | 0.00 | 0.00 | 0.00 | 0.524677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.818131E+09 | 0.00 | 0.00 | 0.00 | 0.464341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.823224E+09 | 0.00 | 0.00 | 0.00 | 0.406048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.754024E+09 | 0.00 | 0.00 | 0.00 | 0.179481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.748047E+09 | 0.00 | 0.00 | 0.00 | 0.113689E+10 | 0.00 | 0.136565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.936194E+10 | 0.00 | 0.00 | 0.00 | 0.368708E+11 | 0.00 | 0.502370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.658866E+09 | 0.00 | 0.00 | 0.00 | 0.717626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.894704E+09 | 0.00 | 0.00 | 0.00 | 0.534840E+10 | 0.00 | 0.172421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.673872E+09 | 0.00 | 0.00 | 0.00 | 0.530401E+09 | 0.00 | 0.185852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.612598E+09 | 0.00 | 0.00 | 0.00 | 0.723489E+09 | 0.00 | 0.281549E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.687707E+09 | 0.00 | 0.00 | 0.00 | 0.100033E+10 | 0.00 | 0.196669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.654597E+09 | 0.00 | 0.00 | 0.00 | 0.177669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.721258E+09 | 0.00 | 0.00 | 0.00 | 0.370479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.736726E+09 | 0.00 | 0.00 | 0.00 | 0.395470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.788584E+09 | 0.00 | 0.00 | 0.00 | 0.431117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.801056E+09 | 0.00 | 0.00 | 0.00 | 0.434024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.726796E+09 | 0.00 | 0.00 | 0.00 | 0.371167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.735848E+09 | 0.00 | 0.00 | 0.00 | 0.322245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.657068E+09 | 0.00 | 0.00 | 0.00 | 0.142959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.671779E+09 | 0.00 | 0.00 | 0.00 | 0.902872E+09 | 0.00 | 0.214856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.846789E+10 | 0.00 | 0.00 | 0.00 | 0.296084E+11 | 0.00 | 0.878925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.612598E+09 | 0.00 | 0.00 | 0.00 | 0.530401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.801056E+09 | 0.00 | 0.00 | 0.00 | 0.434024E+10 | 0.00 | 0.281549E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.671138E+09 | 0.00 | 0.00 | 0.00 | 0.514171E+09 | 0.00 | 0.239428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.609764E+09 | 0.00 | 0.00 | 0.00 | 0.705279E+09 | 0.00 | 0.314432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.684254E+09 | 0.00 | 0.00 | 0.00 | 0.982159E+09 | 0.00 | 0.218578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.651021E+09 | 0.00 | 0.00 | 0.00 | 0.176549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.719764E+09 | 0.00 | 0.00 | 0.00 | 0.370985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.736118E+09 | 0.00 | 0.00 | 0.00 | 0.396332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.789607E+09 | 0.00 | 0.00 | 0.00 | 0.432817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.801283E+09 | 0.00 | 0.00 | 0.00 | 0.435294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.726315E+09 | 0.00 | 0.00 | 0.00 | 0.372333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.734714E+09 | 0.00 | 0.00 | 0.00 | 0.322952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.653587E+09 | 0.00 | 0.00 | 0.00 | 0.141689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.668576E+09 | 0.00 | 0.00 | 0.00 | 0.891478E+09 | 0.00 | 0.241717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.844614E+10 | 0.00 | 0.00 | 0.00 | 0.295826E+11 | 0.00 | 0.101415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.609764E+09 | 0.00 | 0.00 | 0.00 | 0.514171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.801283E+09 | 0.00 | 0.00 | 0.00 | 0.435294E+10 | 0.00 | 0.314432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.671667E+09 | 0.00 | 0.00 | 0.00 | 0.483790E+09 | 0.00 | 0.324190E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.609672E+09 | 0.00 | 0.00 | 0.00 | 0.666695E+09 | 0.00 | 0.367486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.683709E+09 | 0.00 | 0.00 | 0.00 | 0.935683E+09 | 0.00 | 0.254219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.649465E+09 | 0.00 | 0.00 | 0.00 | 0.170791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.714431E+09 | 0.00 | 0.00 | 0.00 | 0.365706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.730162E+09 | 0.00 | 0.00 | 0.00 | 0.391299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.783308E+09 | 0.00 | 0.00 | 0.00 | 0.427833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.794881E+09 | 0.00 | 0.00 | 0.00 | 0.430167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.721407E+09 | 0.00 | 0.00 | 0.00 | 0.367633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.729998E+09 | 0.00 | 0.00 | 0.00 | 0.318362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.651594E+09 | 0.00 | 0.00 | 0.00 | 0.136785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.668382E+09 | 0.00 | 0.00 | 0.00 | 0.859324E+09 | 0.00 | 0.293870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.840868E+10 | 0.00 | 0.00 | 0.00 | 0.290312E+11 | 0.00 | 0.123976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.609672E+09 | 0.00 | 0.00 | 0.00 | 0.483790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.794881E+09 | 0.00 | 0.00 | 0.00 | 0.430167E+10 | 0.00 | 0.367486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.102989E+10 | 0.00 | 0.00 | 0.00 | 0.724851E+09 | 0.00 | 0.968619E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.932679E+09 | 0.00 | 0.00 | 0.00 | 0.104277E+10 | 0.00 | 0.879322E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104514E+10 | 0.00 | 0.00 | 0.00 | 0.147117E+10 | 0.00 | 0.612823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.990432E+09 | 0.00 | 0.00 | 0.00 | 0.283085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112042E+10 | 0.00 | 0.00 | 0.00 | 0.634724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115993E+10 | 0.00 | 0.00 | 0.00 | 0.686239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.126196E+10 | 0.00 | 0.00 | 0.00 | 0.749118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127686E+10 | 0.00 | 0.00 | 0.00 | 0.758932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114574E+10 | 0.00 | 0.00 | 0.00 | 0.637327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115282E+10 | 0.00 | 0.00 | 0.00 | 0.557952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.996429E+09 | 0.00 | 0.00 | 0.00 | 0.224975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102323E+10 | 0.00 | 0.00 | 0.00 | 0.140730E+10 | 0.00 | 0.807904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131355E+11 | 0.00 | 0.00 | 0.00 | 0.499696E+11 | 0.00 | 0.326867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.932679E+09 | 0.00 | 0.00 | 0.00 | 0.724851E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127686E+10 | 0.00 | 0.00 | 0.00 | 0.758932E+10 | 0.00 | 0.968619E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.559366E+09 | 0.00 | 0.00 | 0.00 | 0.354878E+09 | 0.00 | 0.557333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.506379E+09 | 0.00 | 0.00 | 0.00 | 0.514103E+09 | 0.00 | 0.497195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.567180E+09 | 0.00 | 0.00 | 0.00 | 0.730797E+09 | 0.00 | 0.349358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.536679E+09 | 0.00 | 0.00 | 0.00 | 0.142321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.605859E+09 | 0.00 | 0.00 | 0.00 | 0.323265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.626412E+09 | 0.00 | 0.00 | 0.00 | 0.349642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.680507E+09 | 0.00 | 0.00 | 0.00 | 0.381620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.688755E+09 | 0.00 | 0.00 | 0.00 | 0.386517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.618342E+09 | 0.00 | 0.00 | 0.00 | 0.324172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.621953E+09 | 0.00 | 0.00 | 0.00 | 0.283380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.539603E+09 | 0.00 | 0.00 | 0.00 | 0.112591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.555306E+09 | 0.00 | 0.00 | 0.00 | 0.705406E+09 | 0.00 | 0.459499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.710634E+10 | 0.00 | 0.00 | 0.00 | 0.253403E+11 | 0.00 | 0.186339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.506379E+09 | 0.00 | 0.00 | 0.00 | 0.354878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.688755E+09 | 0.00 | 0.00 | 0.00 | 0.386517E+10 | 0.00 | 0.557333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.556988E+09 | 0.00 | 0.00 | 0.00 | 0.345151E+09 | 0.00 | 0.600096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.503963E+09 | 0.00 | 0.00 | 0.00 | 0.501388E+09 | 0.00 | 0.522734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.564304E+09 | 0.00 | 0.00 | 0.00 | 0.714395E+09 | 0.00 | 0.370042E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.533510E+09 | 0.00 | 0.00 | 0.00 | 0.140165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.602223E+09 | 0.00 | 0.00 | 0.00 | 0.320895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.622848E+09 | 0.00 | 0.00 | 0.00 | 0.347381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677083E+09 | 0.00 | 0.00 | 0.00 | 0.379437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.685387E+09 | 0.00 | 0.00 | 0.00 | 0.384423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.615136E+09 | 0.00 | 0.00 | 0.00 | 0.322227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.618535E+09 | 0.00 | 0.00 | 0.00 | 0.281448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.536407E+09 | 0.00 | 0.00 | 0.00 | 0.111031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.552544E+09 | 0.00 | 0.00 | 0.00 | 0.695035E+09 | 0.00 | 0.483976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.706893E+10 | 0.00 | 0.00 | 0.00 | 0.251260E+11 | 0.00 | 0.197685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.503963E+09 | 0.00 | 0.00 | 0.00 | 0.345151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.685387E+09 | 0.00 | 0.00 | 0.00 | 0.384423E+10 | 0.00 | 0.600096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.559942E+09 | 0.00 | 0.00 | 0.00 | 0.331824E+09 | 0.00 | 0.689648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.506203E+09 | 0.00 | 0.00 | 0.00 | 0.479275E+09 | 0.00 | 0.581499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.566560E+09 | 0.00 | 0.00 | 0.00 | 0.689355E+09 | 0.00 | 0.423787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.534373E+09 | 0.00 | 0.00 | 0.00 | 0.136401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.601159E+09 | 0.00 | 0.00 | 0.00 | 0.318918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.622110E+09 | 0.00 | 0.00 | 0.00 | 0.346203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677579E+09 | 0.00 | 0.00 | 0.00 | 0.379223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.686717E+09 | 0.00 | 0.00 | 0.00 | 0.384987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.616173E+09 | 0.00 | 0.00 | 0.00 | 0.322366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.619296E+09 | 0.00 | 0.00 | 0.00 | 0.280931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.537252E+09 | 0.00 | 0.00 | 0.00 | 0.109214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.554678E+09 | 0.00 | 0.00 | 0.00 | 0.682354E+09 | 0.00 | 0.537806E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.708204E+10 | 0.00 | 0.00 | 0.00 | 0.249652E+11 | 0.00 | 0.223274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.506203E+09 | 0.00 | 0.00 | 0.00 | 0.331824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.686717E+09 | 0.00 | 0.00 | 0.00 | 0.384987E+10 | 0.00 | 0.689648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.623742E+09 | 0.00 | 0.00 | 0.00 | 0.342486E+09 | 0.00 | 0.898389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.563454E+09 | 0.00 | 0.00 | 0.00 | 0.484113E+09 | 0.00 | 0.744016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.630701E+09 | 0.00 | 0.00 | 0.00 | 0.705157E+09 | 0.00 | 0.592072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.590406E+09 | 0.00 | 0.00 | 0.00 | 0.138538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.648645E+09 | 0.00 | 0.00 | 0.00 | 0.335939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.668487E+09 | 0.00 | 0.00 | 0.00 | 0.367943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.731885E+09 | 0.00 | 0.00 | 0.00 | 0.407136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.746794E+09 | 0.00 | 0.00 | 0.00 | 0.418334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.672166E+09 | 0.00 | 0.00 | 0.00 | 0.349925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.676014E+09 | 0.00 | 0.00 | 0.00 | 0.303298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.593150E+09 | 0.00 | 0.00 | 0.00 | 0.114872E+10 | 0.00 | 608893.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.616848E+09 | 0.00 | 0.00 | 0.00 | 0.710017E+09 | 0.00 | 0.689585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.776229E+10 | 0.00 | 0.00 | 0.00 | 0.266016E+11 | 0.00 | 0.292467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.563454E+09 | 0.00 | 0.00 | 0.00 | 0.342486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.746794E+09 | 0.00 | 0.00 | 0.00 | 0.418334E+10 | 0.00 | 0.898389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.561066E+10 | 0.822187E+09 | 0.00 | 2868120.04 | 7623682.15 | 21514461.82 | 0.115316E+10 | 0.00 | 0.60 |
February | 0.338192E+10 | 0.105542E+10 | 0.00 | 3723468.59 | 2848427.82 | 0.181116E+09 | 0.172066E+10 | 0.00 | 0.64 |
March | 0.263244E+10 | 0.189255E+10 | 0.00 | 3917937.48 | 15444185.71 | 0.187331E+09 | 0.169768E+10 | 0.00 | 0.63 |
April | 0.196360E+09 | 0.431920E+10 | 0.00 | 5538887.11 | 29477746.87 | 0.00 | 0.219959E+10 | 0.00 | 0.67 |
May | 0.00 | 0.138090E+11 | 0.00 | 0.00 | 75586839.67 | 0.00 | 0.00 | 0.00 | 0.54 |
June | 0.00 | 0.153372E+11 | 0.00 | 0.00 | 82200501.42 | 0.00 | 0.00 | 0.00 | 0.54 |
July | 0.00 | 0.184448E+11 | 0.00 | 0.00 | 36847876.57 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.171144E+11 | 0.00 | 0.00 | 49348611.37 | 0.00 | 0.00 | 0.00 | 0.53 |
September | 0.00 | 0.146093E+11 | 0.00 | 0.00 | 47392487.54 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 69607916.85 | 0.112015E+11 | 0.00 | 3486003.54 | 35832713.84 | 0.00 | 0.999941E+09 | 0.00 | 0.59 |
November | 0.746218E+09 | 0.335583E+10 | 0.00 | 8995124.58 | 23012583.72 | 0.00 | 0.382432E+10 | 0.00 | 0.74 |
December | 0.322325E+10 | 0.205685E+10 | 0.00 | 4471280.54 | 24333797.77 | 99047989.17 | 0.287558E+10 | 0.00 | 0.63 |
Annual Sum or Average | 0.158605E+11 | 0.104018E+12 | 0.00 | 33000821.88 | 0.429949E+09 | 0.489009E+09 | 0.144709E+11 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.822187E+09 | 0.00 | 0.00 | 2848427.82 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.561066E+10 | 0.184448E+11 | 0.00 | 8995124.58 | 82200501.42 | 0.187331E+09 | 0.382432E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184086E+10 | 0.451565E+09 | 0.00 | 1801606.62 | 7500543.47 | 857627.49 | 0.898112E+09 | 0.00 | 0.51 |
February | 0.101188E+10 | 0.586415E+09 | 0.00 | 2240487.18 | 5340356.65 | 29104312.63 | 0.111445E+10 | 0.00 | 0.58 |
March | 0.785548E+09 | 0.100359E+10 | 0.00 | 2358413.06 | 17378987.13 | 54569505.40 | 0.116251E+10 | 0.00 | 0.56 |
April | 48323348.39 | 0.208301E+10 | 0.00 | 2573304.24 | 32688785.21 | 0.00 | 0.106548E+10 | 0.00 | 0.61 |
May | 0.00 | 0.619340E+10 | 0.00 | 0.00 | 43223607.16 | 0.00 | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.685688E+10 | 0.00 | 0.00 | 52056765.53 | 0.00 | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.812551E+10 | 0.00 | 0.00 | 42732619.31 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.762425E+10 | 0.00 | 0.00 | 46428729.46 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.646843E+10 | 0.00 | 0.00 | 43409108.69 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 19786734.74 | 0.500573E+10 | 0.00 | 1496852.48 | 28760727.98 | 0.00 | 0.455745E+09 | 0.00 | 0.51 |
November | 0.198794E+09 | 0.157972E+10 | 0.00 | 4774583.80 | 18091194.42 | 0.00 | 0.203833E+10 | 0.00 | 0.72 |
December | 0.104255E+10 | 0.991400E+09 | 0.00 | 3216473.67 | 16717365.27 | 13508942.68 | 0.188686E+10 | 0.00 | 0.61 |
Annual Sum or Average | 0.494773E+10 | 0.469699E+11 | 0.00 | 18461721.06 | 0.354329E+09 | 98040388.20 | 0.862148E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.451565E+09 | 0.00 | 0.00 | 5340356.65 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.184086E+10 | 0.812551E+10 | 0.00 | 4774583.80 | 52056765.53 | 54569505.40 | 0.203833E+10 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.207808E+10 | 0.362333E+09 | 0.00 | 839164.03 | 12024723.33 | 17831924.91 | 0.336763E+09 | 0.00 | 0.47 |
February | 0.120098E+10 | 0.484548E+09 | 0.00 | 1247153.29 | 8564016.39 | 88846853.93 | 0.518100E+09 | 0.00 | 0.50 |
March | 0.101786E+10 | 0.847458E+09 | 0.00 | 1305312.51 | 23289253.16 | 73928434.15 | 0.615643E+09 | 0.00 | 0.51 |
April | 0.145976E+09 | 0.168517E+10 | 0.00 | 1850188.63 | 94090483.15 | 0.00 | 0.609089E+09 | 0.00 | 0.54 |
May | 0.00 | 0.514448E+10 | 0.00 | 0.00 | 0.358644E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 626709.05 | 0.575783E+10 | 0.00 | 94134.12 | 0.407687E+09 | 0.00 | 166021.57 | 0.00 | 0.43 |
July | 0.00 | 0.661580E+10 | 0.00 | 54279.91 | 0.448405E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.641543E+10 | 0.00 | 0.00 | 0.403770E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 431126.38 | 0.526900E+10 | 0.00 | 199958.36 | 0.327874E+09 | 0.00 | 13645.04 | 0.00 | 0.42 |
October | 64119330.55 | 0.413764E+10 | 0.00 | 1827163.23 | 0.249572E+09 | 0.00 | 0.396968E+09 | 0.00 | 0.48 |
November | 0.386191E+09 | 0.133800E+10 | 0.00 | 3063391.98 | 75662430.49 | 0.00 | 0.120014E+10 | 0.00 | 0.60 |
December | 0.132490E+10 | 0.843659E+09 | 0.00 | 1732676.52 | 39177166.58 | 45187022.02 | 0.867898E+09 | 0.00 | 0.52 |
Annual Sum or Average | 0.621916E+10 | 0.389014E+11 | 0.00 | 12213422.59 | 0.244876E+10 | 0.225794E+09 | 0.454478E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.362333E+09 | 0.00 | 0.00 | 8564016.39 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.207808E+10 | 0.661580E+10 | 0.00 | 3063391.98 | 0.448405E+09 | 88846853.93 | 0.120014E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.205601E+10 | 0.353835E+09 | 0.00 | 752769.49 | 11911535.01 | 38817149.61 | 0.302737E+09 | 0.00 | 0.46 |
February | 0.122039E+10 | 0.477047E+09 | 0.00 | 1141601.18 | 8435253.96 | 97643312.36 | 0.467680E+09 | 0.00 | 0.50 |
March | 0.102589E+10 | 0.839895E+09 | 0.00 | 1191901.56 | 23415854.31 | 87518937.46 | 0.571840E+09 | 0.00 | 0.50 |
April | 0.147676E+09 | 0.168199E+10 | 0.00 | 1813170.32 | 93819464.07 | 0.00 | 0.598647E+09 | 0.00 | 0.54 |
May | 0.00 | 0.515288E+10 | 0.00 | 0.00 | 0.358707E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 630615.70 | 0.577048E+10 | 0.00 | 98681.23 | 0.406265E+09 | 0.00 | 166616.58 | 0.00 | 0.43 |
July | 0.00 | 0.663421E+10 | 0.00 | 40893.62 | 0.449244E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.643227E+10 | 0.00 | 0.00 | 0.402469E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 440528.36 | 0.528387E+10 | 0.00 | 175929.96 | 0.328464E+09 | 0.00 | 14667.44 | 0.00 | 0.42 |
October | 65708656.41 | 0.414705E+10 | 0.00 | 1843017.56 | 0.249583E+09 | 0.00 | 0.395862E+09 | 0.00 | 0.47 |
November | 0.400169E+09 | 0.133506E+10 | 0.00 | 2986469.01 | 75574998.32 | 0.00 | 0.117419E+10 | 0.00 | 0.60 |
December | 0.134038E+10 | 0.841323E+09 | 0.00 | 1591495.91 | 39489175.25 | 56045297.09 | 0.805334E+09 | 0.00 | 0.51 |
Annual Sum or Average | 0.625730E+10 | 0.389499E+11 | 0.00 | 11635929.85 | 0.244738E+10 | 0.280025E+09 | 0.431648E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.353835E+09 | 0.00 | 0.00 | 8435253.96 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.205601E+10 | 0.663421E+10 | 0.00 | 2986469.01 | 0.449244E+09 | 97643312.36 | 0.117419E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.203124E+10 | 0.332445E+09 | 0.00 | 641605.74 | 12215947.12 | 62046957.19 | 0.254788E+09 | 0.00 | 0.46 |
February | 0.122699E+10 | 0.457131E+09 | 0.00 | 971880.67 | 7971913.51 | 0.116800E+09 | 0.407250E+09 | 0.00 | 0.49 |
March | 0.110361E+10 | 0.813013E+09 | 0.00 | 989145.04 | 22203236.51 | 0.100743E+09 | 0.439494E+09 | 0.00 | 0.50 |
April | 0.160594E+09 | 0.164762E+10 | 0.00 | 1662945.39 | 92637211.55 | 0.00 | 0.576304E+09 | 0.00 | 0.53 |
May | 0.00 | 0.510865E+10 | 0.00 | 0.00 | 0.357003E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 602952.66 | 0.572717E+10 | 0.00 | 81911.85 | 0.408231E+09 | 0.00 | 158070.79 | 0.00 | 0.43 |
July | 0.00 | 0.659079E+10 | 0.00 | 52460.81 | 0.448919E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.638917E+10 | 0.00 | 0.00 | 0.401592E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 444507.91 | 0.524064E+10 | 0.00 | 188148.71 | 0.327092E+09 | 0.00 | 12904.30 | 0.00 | 0.42 |
October | 70921192.67 | 0.411488E+10 | 0.00 | 1749648.29 | 0.247876E+09 | 0.00 | 0.381299E+09 | 0.00 | 0.47 |
November | 0.426783E+09 | 0.131012E+10 | 0.00 | 2738508.86 | 77081601.61 | 0.00 | 0.112530E+10 | 0.00 | 0.59 |
December | 0.137960E+10 | 0.824700E+09 | 0.00 | 1339036.85 | 39486303.05 | 69214209.36 | 0.699213E+09 | 0.00 | 0.50 |
Annual Sum or Average | 0.640079E+10 | 0.385563E+11 | 0.00 | 10415292.21 | 0.244231E+10 | 0.348805E+09 | 0.388382E+10 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.332445E+09 | 0.00 | 0.00 | 7971913.51 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.203124E+10 | 0.659079E+10 | 0.00 | 2738508.86 | 0.448919E+09 | 0.116800E+09 | 0.112530E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.359780E+10 | 0.515588E+09 | 0.00 | 848425.52 | 25459196.19 | 0.144947E+09 | 0.350740E+09 | 0.00 | 0.41 |
February | 0.214752E+10 | 0.761045E+09 | 0.00 | 1031014.43 | 16877295.30 | 0.303304E+09 | 0.516726E+09 | 0.00 | 0.43 |
March | 0.203410E+10 | 0.137209E+10 | 0.00 | 966675.88 | 38452446.80 | 0.224637E+09 | 0.497257E+09 | 0.00 | 0.44 |
April | 0.272833E+09 | 0.298424E+10 | 0.00 | 1858303.57 | 97929172.70 | 0.00 | 0.848128E+09 | 0.00 | 0.45 |
May | 0.00 | 0.952037E+10 | 0.00 | 0.00 | 0.245760E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.108246E+11 | 0.00 | 0.00 | 0.252111E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.122800E+11 | 0.00 | 0.00 | 0.333271E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.120448E+11 | 0.00 | 0.00 | 0.220430E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.963981E+10 | 0.00 | 140358.16 | 0.279599E+09 | 0.00 | 15848329.10 | 0.00 | 0.39 |
October | 79060053.61 | 0.772870E+10 | 0.00 | 2087748.71 | 0.168295E+09 | 0.00 | 0.549285E+09 | 0.00 | 0.42 |
November | 0.676778E+09 | 0.240643E+10 | 0.00 | 3543756.28 | 59813933.65 | 0.00 | 0.179832E+10 | 0.00 | 0.49 |
December | 0.265267E+10 | 0.145388E+10 | 0.00 | 1319849.00 | 54768194.77 | 0.165591E+09 | 0.785235E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.114608E+11 | 0.715315E+11 | 0.00 | 11796131.55 | 0.179277E+10 | 0.838479E+09 | 0.536154E+10 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.515588E+09 | 0.00 | 0.00 | 16877295.30 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.359780E+10 | 0.122800E+11 | 0.00 | 3543756.28 | 0.333271E+09 | 0.303304E+09 | 0.179832E+10 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.175894E+10 | 0.246644E+09 | 0.00 | 399256.86 | 14216239.34 | 0.125114E+09 | 0.151005E+09 | 0.00 | 0.42 |
February | 0.100852E+10 | 0.366567E+09 | 0.00 | 490066.10 | 8527762.85 | 0.222863E+09 | 0.243326E+09 | 0.00 | 0.43 |
March | 0.101775E+10 | 0.669395E+09 | 0.00 | 433401.24 | 18932476.97 | 0.124155E+09 | 0.222931E+09 | 0.00 | 0.44 |
April | 0.147490E+09 | 0.147345E+10 | 0.00 | 865061.91 | 48187365.51 | 0.00 | 0.417127E+09 | 0.00 | 0.46 |
May | 0.00 | 0.473492E+10 | 0.00 | 0.00 | 0.116550E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.538154E+10 | 0.00 | 0.00 | 0.124137E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.609931E+10 | 0.00 | 0.00 | 0.162937E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.597950E+10 | 0.00 | 0.00 | 0.111414E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.477591E+10 | 0.00 | 78336.28 | 0.138549E+09 | 0.00 | 10990956.63 | 0.00 | 0.39 |
October | 41885884.12 | 0.383337E+10 | 0.00 | 1013731.45 | 82749468.00 | 0.00 | 0.274032E+09 | 0.00 | 0.42 |
November | 0.362451E+09 | 0.118708E+10 | 0.00 | 1679918.61 | 29140135.87 | 0.00 | 0.884016E+09 | 0.00 | 0.50 |
December | 0.128380E+10 | 0.715464E+09 | 0.00 | 582300.64 | 27071054.13 | 0.149341E+09 | 0.350327E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.562084E+10 | 0.354632E+11 | 0.00 | 5542073.08 | 0.882410E+09 | 0.621474E+09 | 0.255375E+10 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.246644E+09 | 0.00 | 0.00 | 8527762.85 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.175894E+10 | 0.609931E+10 | 0.00 | 1679918.61 | 0.162937E+09 | 0.222863E+09 | 0.884016E+09 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.174641E+10 | 0.240661E+09 | 0.00 | 377620.47 | 15251617.82 | 0.136268E+09 | 0.145492E+09 | 0.00 | 0.42 |
February | 0.995064E+09 | 0.359146E+09 | 0.00 | 458187.06 | 8583618.83 | 0.240252E+09 | 0.229666E+09 | 0.00 | 0.43 |
March | 0.101374E+10 | 0.659752E+09 | 0.00 | 403141.23 | 18461502.03 | 0.132464E+09 | 0.209832E+09 | 0.00 | 0.44 |
April | 0.157570E+09 | 0.145901E+10 | 0.00 | 815608.33 | 48587037.40 | 0.00 | 0.401032E+09 | 0.00 | 0.45 |
May | 0.00 | 0.471623E+10 | 0.00 | 0.00 | 0.115939E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.536207E+10 | 0.00 | 0.00 | 0.126184E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.607784E+10 | 0.00 | 0.00 | 0.166578E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.596353E+10 | 0.00 | 0.00 | 0.111181E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.475783E+10 | 0.00 | 76703.54 | 0.140230E+09 | 0.00 | 11257899.09 | 0.00 | 0.39 |
October | 43098453.84 | 0.382082E+10 | 0.00 | 986212.71 | 82259955.61 | 0.00 | 0.270080E+09 | 0.00 | 0.42 |
November | 0.375651E+09 | 0.117884E+10 | 0.00 | 1610436.92 | 29324625.51 | 0.00 | 0.858083E+09 | 0.00 | 0.50 |
December | 0.127431E+10 | 0.708658E+09 | 0.00 | 545782.55 | 27133275.86 | 0.169046E+09 | 0.326006E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.560585E+10 | 0.353044E+11 | 0.00 | 5273692.81 | 0.889713E+09 | 0.678030E+09 | 0.245145E+10 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.240661E+09 | 0.00 | 0.00 | 8583618.83 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.174641E+10 | 0.607784E+10 | 0.00 | 1610436.92 | 0.166578E+09 | 0.240252E+09 | 0.858083E+09 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170872E+10 | 0.232330E+09 | 0.00 | 346115.77 | 17207262.89 | 0.170057E+09 | 0.140258E+09 | 0.00 | 0.42 |
February | 0.979154E+09 | 0.342758E+09 | 0.00 | 445474.85 | 9331884.45 | 0.261876E+09 | 0.214071E+09 | 0.00 | 0.43 |
March | 0.985845E+09 | 0.642819E+09 | 0.00 | 354400.77 | 18294994.84 | 0.162641E+09 | 0.191897E+09 | 0.00 | 0.44 |
April | 0.184251E+09 | 0.143172E+10 | 0.00 | 735469.25 | 49079474.98 | 0.00 | 0.367357E+09 | 0.00 | 0.45 |
May | 0.00 | 0.469039E+10 | 0.00 | 0.00 | 0.120578E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.534911E+10 | 0.00 | 0.00 | 0.126529E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.607027E+10 | 0.00 | 0.00 | 0.169378E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.596589E+10 | 0.00 | 0.00 | 0.111658E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.475642E+10 | 0.00 | 75920.74 | 0.140213E+09 | 0.00 | 11336827.87 | 0.00 | 0.39 |
October | 50999657.12 | 0.381576E+10 | 0.00 | 945289.20 | 83455555.45 | 0.00 | 0.259265E+09 | 0.00 | 0.42 |
November | 0.396964E+09 | 0.117003E+10 | 0.00 | 1500494.65 | 29533866.22 | 0.00 | 0.820978E+09 | 0.00 | 0.49 |
December | 0.124651E+10 | 0.699365E+09 | 0.00 | 483292.27 | 27687785.09 | 0.204374E+09 | 0.298306E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.555245E+10 | 0.351669E+11 | 0.00 | 4886457.51 | 0.902947E+09 | 0.798948E+09 | 0.230347E+10 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.232330E+09 | 0.00 | 0.00 | 9331884.45 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.170872E+10 | 0.607027E+10 | 0.00 | 1500494.65 | 0.169378E+09 | 0.261876E+09 | 0.820978E+09 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:20:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.156880E+10 | 0.233057E+09 | 0.00 | 319526.81 | 15200102.07 | 0.285192E+09 | 0.144827E+09 | 0.00 | 0.42 |
February | 0.889149E+09 | 0.338078E+09 | 0.00 | 380802.51 | 9580807.65 | 0.333846E+09 | 0.208090E+09 | 0.00 | 0.43 |
March | 0.845607E+09 | 0.628370E+09 | 102486.65 | 313560.45 | 17613138.34 | 0.269202E+09 | 0.188809E+09 | 85.84 | 0.44 |
April | 0.206842E+09 | 0.140259E+10 | 0.00 | 615343.95 | 46407852.67 | 0.00 | 0.344265E+09 | 0.00 | 0.46 |
May | 0.00 | 0.468636E+10 | 0.00 | 0.00 | 0.116868E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.539587E+10 | 0.00 | 0.00 | 0.124612E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.615366E+10 | 0.00 | 0.00 | 0.169577E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.607319E+10 | 0.00 | 0.00 | 0.108333E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.485157E+10 | 0.00 | 45374.30 | 0.137250E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
October | 56888762.83 | 0.387707E+10 | 0.00 | 919836.14 | 79084101.95 | 0.00 | 0.251630E+09 | 0.00 | 0.43 |
November | 0.406433E+09 | 0.118224E+10 | 0.00 | 1474944.23 | 27317303.73 | 0.00 | 0.816269E+09 | 0.00 | 0.51 |
December | 0.108369E+10 | 0.692540E+09 | 0.00 | 508439.78 | 21878547.28 | 0.357003E+09 | 0.285823E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.505740E+10 | 0.355146E+11 | 102486.65 | 4577828.16 | 0.873722E+09 | 0.124524E+10 | 0.223971E+10 | 85.84 | 0.42 |
Minimum of Months | 0.00 | 0.233057E+09 | 0.00 | 0.00 | 9580807.65 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.156880E+10 | 0.615366E+10 | 102486.65 | 1474944.23 | 0.169577E+09 | 0.357003E+09 | 0.816269E+09 | 85.84 | 0.51 |