Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:19
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2020-06-03 19:19:23
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1181.01 | 564.99 | 564.99 |
Net Site Energy | 1181.01 | 564.99 | 564.99 |
Total Source Energy | 3096.09 | 1481.16 | 1481.16 |
Net Source Energy | 3096.09 | 1481.16 | 1481.16 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 309.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 31.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 433.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 64.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 152.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 60.59 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 871.76 | 309.26 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 309.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 31.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 433.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 64.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 152.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 60.59 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 238.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 116.98 | 147.95 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 417.04 | 147.95 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 238.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 116.98 | 147.95 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 417.04 | 147.95 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 871.756 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 871.756 | 100.00 |
Total On-Site and Utility Electric Sources | 871.756 | 100.00 |
Total Electricity End Uses | 871.756 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1296.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Meter |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.29 | 0.00 | 0.00 | 124.29 | 0.00 |
Gross Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.50 | 0.00 | 0.00 | 26.24 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.75 | 20.75 | 15.7897 | 11.61 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.37 | 10.37 | 18.6637 | 11.61 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.0491 | 11.61 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.0491 | 11.61 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 17.0491 | 11.61 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.70 | 20.70 | 10.0956 | 11.61 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 10.0956 | 11.61 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 10.0956 | 11.61 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.35 | 10.35 | 10.0956 | 11.61 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.35 | 10.35 | 10.0956 | 11.61 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 13.4970 | 11.61 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.29 | 124.29 | 13.4970 | 11.61 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-AUG-15:00 | 26-DEC-09:09 | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 161878.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 24257.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 26802.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9406.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5436.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 73992.60 | 161878.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 161878.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 24257.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 26802.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9406.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5436.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 335.24 | 0.00 | 0.00 | 0.00 |
Cooling | 98.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1374.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 204.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 483.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 191.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2760.85 | 335.24 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 160.38 | 0.00 | 0.00 | 0.00 |
Cooling | 47.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 657.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 97.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 231.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 91.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1320.78 | 160.38 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 160.38 | 0.00 | 0.00 | 0.00 |
Cooling | 47.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 657.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 97.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 231.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 91.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1320.78 | 160.38 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.58 |
SMSTORE1 DIRECT AIR | 0.865509 |
SMSTORE2 DIRECT AIR | 0.984088 |
SMSTORE3 DIRECT AIR | 0.980162 |
SMSTORE4 DIRECT AIR | 0.974278 |
LGSTORE2 DIRECT AIR | 1.50 |
SMSTORE5 DIRECT AIR | 0.759482 |
SMSTORE6 DIRECT AIR | 0.748763 |
SMSTORE7 DIRECT AIR | 0.734677 |
SMSTORE8 DIRECT AIR | 0.741544 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.58 | 1.58 | 1.58 | 1.58 | 1.58 | 1.58 | 1.00 | 1.00 | 1.58 |
PSZ-AC_2:2 | 0.865509 | 0.865509 | 0.865509 | 0.865509 | 0.881610 | 0.881610 | 1.00 | 0.981737 | 0.881610 |
PSZ-AC_3:3 | 0.984088 | 0.984088 | 0.984088 | 0.984088 | 0.984088 | 0.984088 | 1.00 | 1.00 | 0.984088 |
PSZ-AC_4:4 | 0.980162 | 0.980162 | 0.980162 | 0.980162 | 0.980162 | 0.980162 | 1.00 | 1.00 | 0.980162 |
PSZ-AC_5:5 | 0.974278 | 0.974278 | 0.974278 | 0.974278 | 0.974278 | 0.974278 | 1.00 | 1.000000 | 0.974278 |
PSZ-AC_6:6 | 1.50 | 1.50 | 1.50 | 1.50 | 1.50 | 1.50 | 1.00 | 1.000000 | 1.50 |
PSZ-AC_7:7 | 0.759482 | 0.759482 | 0.759482 | 0.759482 | 0.770700 | 0.770700 | 1.00 | 0.985445 | 0.770700 |
PSZ-AC_8:8 | 0.748763 | 0.748763 | 0.748763 | 0.748763 | 0.761344 | 0.761344 | 1.00 | 0.983475 | 0.761344 |
PSZ-AC_9:9 | 0.734677 | 0.734677 | 0.734677 | 0.734677 | 0.753347 | 0.753347 | 1.00 | 0.975218 | 0.753347 |
PSZ-AC_10:10 | 0.741544 | 0.741544 | 0.741544 | 0.741544 | 0.769313 | 0.769313 | 1.00 | 0.963904 | 0.769313 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.58 | 0.411453 |
PSZ-AC_2:2_OA_CONTROLLER | 0.881610 | 0.205727 |
PSZ-AC_3:3_OA_CONTROLLER | 0.984088 | 0.205727 |
PSZ-AC_4:4_OA_CONTROLLER | 0.980162 | 0.205727 |
PSZ-AC_5:5_OA_CONTROLLER | 0.974278 | 0.205727 |
PSZ-AC_6:6_OA_CONTROLLER | 1.50 | 0.411453 |
PSZ-AC_7:7_OA_CONTROLLER | 0.770700 | 0.205727 |
PSZ-AC_8:8_OA_CONTROLLER | 0.761344 | 0.205727 |
PSZ-AC_9:9_OA_CONTROLLER | 0.753347 | 0.205727 |
PSZ-AC_10:10_OA_CONTROLLER | 0.769313 | 0.205727 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.58 | 1.58 | 1.58 | 1.04 | 27310.02 | 47944.97 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 0.881610 | 0.881610 | 0.881610 | 0.881610 | 15087.55 | 25713.45 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 0.984088 | 0.984088 | 0.984088 | 0.984088 | 16795.13 | 28385.49 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 0.980162 | 0.980162 | 0.980162 | 0.980162 | 16719.71 | 28297.03 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 0.974278 | 0.974278 | 0.974278 | 0.974278 | 16641.08 | 28164.41 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.50 | 1.50 | 1.50 | 0.992749 | 26156.84 | 46314.76 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.770700 | 0.770700 | 0.770700 | 0.770700 | 13364.43 | 23324.23 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.761344 | 0.761344 | 0.761344 | 0.761344 | 13246.60 | 23082.67 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.753347 | 0.753347 | 0.753347 | 0.753347 | 13122.76 | 22765.26 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 0.769313 | 0.769313 | 0.769313 | 0.769313 | 13267.29 | 22920.12 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 1.58 | 0.788250 | 1.05 | 26096.67 | 27310.02 | 13655.01 | 13655.01 | 0.782321 | 0.782320 | 0.782320 | 0.782320 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 0.881610 | 0.440805 | 0.587740 | 14593.78 | 15087.55 | 7543.77 | 7543.77 | 0.786623 | 0.786620 | 0.786620 | 0.786620 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 0.984090 | 0.492045 | 0.656060 | 16290.18 | 16795.13 | 8397.57 | 8397.57 | 0.787602 | 0.787600 | 0.787600 | 0.787600 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 0.980160 | 0.490080 | 0.653440 | 16225.13 | 16719.71 | 8359.85 | 8359.85 | 0.787780 | 0.787780 | 0.787780 | 0.787780 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 0.974280 | 0.487140 | 0.649520 | 16127.79 | 16641.08 | 8320.54 | 8320.54 | 0.787315 | 0.787310 | 0.787310 | 0.787310 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 1.50 | 0.752085 | 1.00 | 24899.35 | 26156.84 | 13078.42 | 13078.42 | 0.780980 | 0.780980 | 0.780980 | 0.780980 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 0.770700 | 0.385350 | 0.513800 | 12757.82 | 13364.43 | 6682.22 | 6682.22 | 0.781967 | 0.781970 | 0.781970 | 0.781970 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 0.761340 | 0.380670 | 0.507560 | 12602.88 | 13246.60 | 6623.30 | 6623.30 | 0.780789 | 0.780790 | 0.780790 | 0.780790 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 0.753350 | 0.376675 | 0.502233 | 12470.62 | 13122.76 | 6561.38 | 6561.38 | 0.780384 | 0.780380 | 0.780380 | 0.780380 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 0.769310 | 0.384655 | 0.512873 | 12734.81 | 13267.29 | 6633.65 | 6633.65 | 0.783900 | 0.783900 | 0.783900 | 0.783900 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.58 | 1686.93 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 0.881610 | 976.08 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 0.984088 | 1089.54 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.980162 | 1085.20 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 0.974278 | 1078.68 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.50 | 1609.53 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.770700 | 853.29 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.761344 | 842.93 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.753347 | 834.07 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 0.769313 | 851.75 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | 47944.97 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | 25713.45 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | 28385.49 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | 28297.03 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | 28164.41 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | 46314.76 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | 23324.23 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | 23082.67 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | 22765.26 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | 22920.12 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.76 | 20.75 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.67 | 10.37 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.43 | 20.70 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.35 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.13 | 10.35 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 15.790 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.090 | No |
2 | SMSTORE1 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 18.664 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.964 | No |
3 | SMSTORE2 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.049 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.349 | No |
4 | SMSTORE3 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.049 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.349 | No |
5 | SMSTORE4 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 17.049 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 21.349 | No |
6 | LGSTORE2 | 348.39 | 30.0 | 11.614 | 8.610E-002 | 10.096 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.396 | No |
7 | SMSTORE5 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 10.096 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.396 | No |
8 | SMSTORE6 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 10.096 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.396 | No |
9 | SMSTORE7 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 10.096 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.396 | No |
10 | SMSTORE8 | 174.19 | 15.0 | 11.614 | 8.610E-002 | 10.096 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 14.396 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 30.0 | 30.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 30 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 15.0 | 15.0 | 8.610E-002 | 11.614 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 15 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 3517.173 | 10.096 | 117.254 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3517.173 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | LGSTORE1 | 348.39 | 30.0 | 1983.751 | 5.694 | 66.134 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1983.751 |
3 | SMSTORE1_LIGHTS | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | TYPE1_LIGHT_SCH | SMSTORE1 | 174.19 | 15.0 | 1492.501 | 8.568 | 99.513 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.501 |
5 | SMSTORE2_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE2 | 174.19 | 15.0 | 1211.251 | 6.953 | 80.761 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.251 |
7 | SMSTORE3_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE3 | 174.19 | 15.0 | 1211.251 | 6.953 | 80.761 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.251 |
9 | SMSTORE4_LIGHTS | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | TYPE2_LIGHT_SCH | SMSTORE4 | 174.19 | 15.0 | 1211.251 | 6.953 | 80.761 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.251 |
11 | LGSTORE2_LIGHTS | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 3517.173 | 10.096 | 117.254 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3517.173 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | LGSTORE2 | 348.39 | 30.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE5 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE6 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE7 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 1758.587 | 10.096 | 117.255 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1758.587 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | TYPE3_LIGHT_SCH | SMSTORE8 | 174.19 | 15.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 30.0 | 1498.062 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 15.0 | 749.031 | 4.300 | 49.942 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.1464 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2111 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.756 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.659 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009596 | 2.1009596 | 2.1009596 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
23 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
24 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
25 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
26 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
27 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
28 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
29 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
30 | 7 | -0.28997596E-08 | -0.17578320E-14 | 0.22751757E-14 | -0.53829073E-16 |
31 | 6 | 0.41991781E-05 | 0.27986603E-08 | 0.31940183E-02 | -0.26794102E-04 |
32 | 5 | -0.29588474E-03 | 0.16552611E-05 | -0.22396035 | 0.19582313E-02 |
33 | 4 | 0.67666006E-02 | 0.75295852E-04 | 4.8334724 | -0.45302727E-01 |
34 | 3 | -0.59297736E-01 | 0.59838054E-03 | -38.043598 | 0.39889893 |
35 | 2 | 0.21038411 | 0.99492606E-03 | 116.52712 | -1.4185167 |
36 | 1 | -0.30354941 | 0.30287292E-03 | -143.93272 | 2.0494576 |
37 | 0 | 0.14796861 | 0.73483799E-05 | 60.838472 | |
38 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
39 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
40 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
41 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
42 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
43 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
44 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
45 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
46 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
47 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
48 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
49 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
50 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
51 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
52 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
53 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
54 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789911E-14 | -0.32998980E-16 |
55 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
56 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
57 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
58 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
59 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
60 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
61 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
62 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
63 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
64 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
65 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
66 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
67 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
68 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
69 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
70 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
71 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
72 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
73 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
74 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
75 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
76 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
77 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
78 | 7 | -0.51571905E-08 | -0.97500957E-14 | 0.15789917E-14 | -0.32998991E-16 |
79 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
80 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
81 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
82 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
83 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
84 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
85 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
86 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
87 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
88 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
89 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
90 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
91 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
92 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
93 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
94 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
95 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
96 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
97 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
98 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
99 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
100 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
101 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
102 | 7 | -0.19967951E-08 | -0.58252365E-15 | 0.72897552E-14 | -0.10630581E-15 |
103 | 6 | 0.59274927E-05 | 0.40433693E-08 | 0.31889525E-02 | -0.26751606E-04 |
104 | 5 | -0.42514865E-03 | 0.23948505E-05 | -0.22367243 | 0.19556901E-02 |
105 | 4 | 0.97725356E-02 | 0.10900143E-03 | 4.8286774 | -0.45256634E-01 |
106 | 3 | -0.85796444E-01 | 0.86675557E-03 | -38.016512 | 0.39859954 |
107 | 2 | 0.30461848 | 0.14417950E-02 | 116.47440 | -1.4178116 |
108 | 1 | -0.43965446 | 0.43929230E-03 | -143.90169 | 2.0489476 |
109 | 0 | 0.21434897 | 0.10616597E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 29 | 1 | VerySmooth | 2.159 | 0.355 | 0.274 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.021 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.51E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 30.0 | 0.159 | 4.569E-004 | 2.517E-004 | 0.317 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 15.0 | 4.561E-002 | 2.619E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 30.0 | 9.122E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 30.0 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 15.0 | 4.561E-002 | 2.618E-004 | 1.775E-004 | 0.182 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 15.0 | 0.113 | 6.514E-004 | 3.022E-004 | 0.453 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 15.0 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 17649.01340 | 21178.81607 | 1.31375 | 1.57650 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.79438E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
2 | LGSTORE1 | Heating | 16848.85765 | 20218.62918 | 0.73682 | 0.88418 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
3 | SMSTORE1 | Cooling | 10020.86885 | 12025.04262 | 0.72126 | 0.86551 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.79438E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
4 | SMSTORE1 | Heating | 8221.62317 | 9865.94780 | 0.35954 | 0.43145 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
5 | SMSTORE2 | Cooling | 11338.22674 | 13605.87208 | 0.82007 | 0.98409 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.79438E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
6 | SMSTORE2 | Heating | 8340.54783 | 10008.65739 | 0.36474 | 0.43769 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
7 | SMSTORE3 | Cooling | 11294.79088 | 13553.74905 | 0.81680 | 0.98016 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.79438E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
8 | SMSTORE3 | Heating | 8432.33415 | 10118.80098 | 0.36875 | 0.44251 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
9 | SMSTORE4 | Cooling | 11226.97876 | 13472.37452 | 0.81190 | 0.97428 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.79438E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
10 | SMSTORE4 | Heating | 8574.95320 | 10289.94384 | 0.37499 | 0.44999 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
11 | LGSTORE2 | Cooling | 16839.14056 | 20206.96867 | 1.25347 | 1.50417 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.79438E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
12 | LGSTORE2 | Heating | 16583.85232 | 19900.62279 | 0.72523 | 0.87028 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 348.38640 | 29.99610 | 0.41145 | 0.00000 |
13 | SMSTORE5 | Cooling | 8827.14890 | 10592.57868 | 0.63290 | 0.75948 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.79438E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
14 | SMSTORE5 | Heating | 8875.06296 | 10650.07556 | 0.38812 | 0.46574 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
15 | SMSTORE6 | Cooling | 8706.20210 | 10447.44252 | 0.62397 | 0.74876 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.79438E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
16 | SMSTORE6 | Heating | 8876.04347 | 10651.25216 | 0.38816 | 0.46579 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
17 | SMSTORE7 | Cooling | 8547.36208 | 10256.83449 | 0.61223 | 0.73468 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.79438E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
18 | SMSTORE7 | Heating | 9107.64810 | 10929.17772 | 0.39829 | 0.47794 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
19 | SMSTORE8 | Cooling | 8624.56296 | 10349.47555 | 0.61795 | 0.74154 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.79438E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
20 | SMSTORE8 | Heating | 10611.34665 | 12733.61598 | 0.46404 | 0.55685 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 14.99800 | 0.20573 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 23551.00 | 1.57650 | 1.57650 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 32344.24 | 0.88418 | 0.88418 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 12974.39 | 0.88161 | 0.88161 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 15932.28 | 0.43145 | 0.43145 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 13066.93 | 0.98409 | 0.98409 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 16072.92 | 0.43769 | 0.43769 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 13123.04 | 0.98016 | 0.98016 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 16181.46 | 0.44251 | 0.44251 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 12978.09 | 0.97428 | 0.97428 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 16350.11 | 0.44999 | 0.44999 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 22511.22 | 1.50417 | 1.50417 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 32030.92 | 0.87028 | 0.87028 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 11487.12 | 0.77070 | 0.77070 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 16704.99 | 0.46574 | 0.46574 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 11376.41 | 0.76134 | 0.76134 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 16706.15 | 0.46579 | 0.46579 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 11276.73 | 0.75335 | 0.75335 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 16980.03 | 0.47794 | 0.47794 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 11418.79 | 0.76931 | 0.76931 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 18758.14 | 0.55685 | 0.55685 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.57650 |
2 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.86551 |
3 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98409 |
4 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98016 |
5 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97428 |
6 | AirTerminal:SingleDuct:Uncontrolled | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.50417 |
7 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.75948 |
8 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.74876 |
9 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.73468 |
10 | AirTerminal:SingleDuct:Uncontrolled | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.74154 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.57650 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.57650 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.57650 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.57650 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.57650 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.57650 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.86551 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.86551 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.86551 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.86551 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.88161 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.88161 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.98174 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98409 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98409 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98409 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98409 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98409 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98409 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98016 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98016 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98016 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98016 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98016 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98016 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97428 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97428 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97428 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97428 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97428 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97428 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.50417 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.50417 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.50417 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.50417 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.50417 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.50417 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.75948 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.75948 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.75948 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.75948 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.77070 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.77070 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.98545 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.74876 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.74876 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.74876 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.74876 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.76134 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.76134 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.98347 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.73468 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.73468 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.73468 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.73468 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.75335 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.75335 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.97522 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.74154 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.74154 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.74154 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.74154 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.76931 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 0.76931 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.96390 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.57650 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 0.88161 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 0.98409 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 0.98016 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 0.97428 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.50417 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.77070 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.76134 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.75335 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 0.76931 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.57650 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.57650 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.57650 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.57650 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.04049 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.57650 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78825 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.05100 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 26096.67274 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 27310.02000 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13655.01000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 13655.01000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.78232 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.78232 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.78232 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.78232 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27310.02000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 47944.97194 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
122 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.57650 |
123 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1686.93322 |
124 | Coil:Heating:Fuel | PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 47944.97194 |
125 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.88161 |
126 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.88161 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.88161 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.88161 |
130 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.88161 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.88161 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.44081 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.58774 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 14593.77586 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 15087.55000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 7543.77500 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 7543.77500 |
138 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.78662 |
139 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.78662 |
140 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.78662 |
141 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.78662 |
142 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15087.55000 |
143 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25713.44742 |
144 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
146 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.88161 |
147 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 976.08215 |
148 | Coil:Heating:Fuel | PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25713.44742 |
149 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98409 |
150 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
151 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98409 |
152 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98409 |
153 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98409 |
154 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98409 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98409 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49205 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65606 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16290.18374 |
159 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16795.13000 |
160 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8397.56500 |
161 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8397.56500 |
162 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.78760 |
163 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.78760 |
164 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.78760 |
165 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.78760 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16795.13000 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28385.49245 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
170 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98409 |
171 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1089.54159 |
172 | Coil:Heating:Fuel | PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 28385.49245 |
173 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98016 |
174 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
175 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98016 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98016 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98016 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98016 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98016 |
180 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49008 |
181 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65344 |
182 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16225.12829 |
183 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16719.71000 |
184 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8359.85500 |
185 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8359.85500 |
186 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.78778 |
187 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.78778 |
188 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.78778 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.78778 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16719.71000 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28297.03029 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
193 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
194 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98016 |
195 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1085.19530 |
196 | Coil:Heating:Fuel | PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 28297.03029 |
197 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97428 |
198 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97428 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97428 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97428 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97428 |
203 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97428 |
204 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48714 |
205 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64952 |
206 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16127.79341 |
207 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 16641.08000 |
208 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8320.54000 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8320.54000 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.78732 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.78731 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.78731 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.78731 |
214 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16641.08000 |
215 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28164.41066 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
218 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97428 |
219 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1078.67990 |
220 | Coil:Heating:Fuel | PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 28164.41066 |
221 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.50417 |
222 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41145 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.50417 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.50417 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.50417 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.99275 |
227 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.50417 |
228 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.75209 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.00278 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 24899.35441 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26156.84000 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13078.42000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 13078.42000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.78098 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.78098 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.78098 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.78098 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26156.84000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 46314.76330 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
241 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
242 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.50417 |
243 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1609.52837 |
244 | Coil:Heating:Fuel | PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 46314.76330 |
245 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.77070 |
246 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.77070 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.77070 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.77070 |
250 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77070 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.77070 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.38535 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.51380 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 12757.82155 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 13364.43000 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 6682.21500 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 6682.21500 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.78197 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.78197 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.78197 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.78197 |
262 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13364.43000 |
263 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23324.22624 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
266 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.77070 |
267 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 853.28715 |
268 | Coil:Heating:Fuel | PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 23324.22624 |
269 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.76134 |
270 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
271 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.76134 |
272 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.76134 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.76134 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76134 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.76134 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.38067 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.50756 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 12602.88032 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 13246.60000 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 6623.30000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 6623.30000 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.78079 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.78079 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.78079 |
285 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.78079 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13246.60000 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23082.66752 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
290 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.76134 |
291 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 842.92896 |
292 | Coil:Heating:Fuel | PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 23082.66752 |
293 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.75335 |
294 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.75335 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.75335 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.75335 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75335 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.75335 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.37668 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.50223 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 12470.61745 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 13122.76000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 6561.38000 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 6561.38000 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.78038 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.78038 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.78038 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.78038 |
310 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13122.76000 |
311 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 22765.25776 |
312 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
313 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
314 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.75335 |
315 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 834.07453 |
316 | Coil:Heating:Fuel | PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 22765.25776 |
317 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.76931 |
318 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20573 |
319 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.76931 |
320 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.76931 |
321 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.76931 |
322 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76931 |
323 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.76931 |
324 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.38466 |
325 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.51287 |
326 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 12734.81212 |
327 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 13267.29000 |
328 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 6633.64500 |
329 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 6633.64500 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.78390 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.78390 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.78390 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.78390 |
334 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 13267.29000 |
335 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 22920.12166 |
336 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
337 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
338 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.76931 |
339 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 851.75129 |
340 | Coil:Heating:Fuel | PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 22920.12166 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 26073.7 | 11.21 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 14396.3 | 33.51 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 16023.6 | 42.01 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 15951.2 | 54.11 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 15877.2 | 66.29 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 24977.2 | 50.90 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 12760.0 | 118.13 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 12649.5 | 131.21 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 12531.9 | 144.45 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 12664.0 | 154.57 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.20 | 78.94 | 58.20 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.146 | 0.141 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.10 | 39.47 | 29.10 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 58.24 | 78.94 | 58.24 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 29.12 | 39.47 | 29.12 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.384 | 0.363 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.211 | 0.201 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 13 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.4071534360E-002 | 0.1112680855 | Pass | Pass | 0.1796834993 | 0.8332456654 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.9026956403E-002 | 0.1964764716 | Pass | Pass | 9.3516617080E-002 | 0.3469563405 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 2.6801589889E-002 | 8.9067321408E-002 | Pass | Pass | 0.1564213589 | 0.8299175344 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.1907075589E-002 | 0.1205694143 | Pass | Pass | 0.1582893605 | 0.6760552587 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.6708781624E-002 | 0.1458443464 | Pass | Pass | 0.4336608497 | 4.5150975872 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 5.2548238107E-002 | 0.2145058540 | Pass | Pass | 5.7511938395E-002 | 0.2386803769 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.8152911248E-002 | 0.2188254481 | Pass | Pass | 6.7279721071E-002 | 0.3280293756 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.9464152438E-002 | 0.2208616545 | Pass | Pass | 8.0926431076E-002 | 0.4789434351 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.3727652139E-002 | 0.2304926564 | Pass | Pass | 0.1793944504 | 1.6327180166 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 6.9395157755E-002 | 0.2804662562 | Pass | Pass | 5.0371382086E-002 | 0.2073869011 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.20 | 180.00 | 90.00 | S |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.10 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 78.94 | 58.24 | 180.00 | 90.00 | S |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 29.12 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.146 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.083 | 348.39 | 348.39 | 270.00 | 180.00 | ||
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | ||
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.211 | 174.19 | 174.19 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.159 | 0.355 | 0.361 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.159 | 0.355 | 0.361 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.159 | 0.355 | 0.361 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.355 | 0.361 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.355 | 0.361 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.355 | 0.361 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.355 | 0.361 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.355 | 0.361 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.355 | 0.361 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.355 | 0.361 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.355 | 0.361 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.159 | 0.355 | 0.361 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.38_SHGC_0.36 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.159 | 0.355 | 0.361 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | ||
Total or Average | 124.29 | 2.159 | 0.355 | 0.361 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 124.29 | 2.159 | 0.355 | 0.361 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | 10.0956 | 348.39 | 3517.17 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 64.95 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | 5.6941 | 348.39 | 1983.75 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 36.63 |
SMSTORE1_LIGHTS | SMSTORE1 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 32.48 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | 8.5681 | 174.19 | 1492.50 | LightsWired | TYPE1_LIGHT_SCH | 98.40 | 168.00 | 98.38 | 0.0000 | Y | 27.56 |
SMSTORE2_LIGHTS | SMSTORE2 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 25.74 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | 6.9535 | 174.19 | 1211.25 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 17.73 |
SMSTORE3_LIGHTS | SMSTORE3 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 25.74 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | 6.9535 | 174.19 | 1211.25 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 17.73 |
SMSTORE4_LIGHTS | SMSTORE4 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 25.74 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | 6.9535 | 174.19 | 1211.25 | LightsWired | TYPE2_LIGHT_SCH | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 17.73 |
LGSTORE2_LIGHTS | LGSTORE2 | 10.0956 | 348.39 | 3517.17 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 47.31 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | 0.0000 | 348.39 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 23.66 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 23.66 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 23.66 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | 10.0956 | 174.19 | 1758.59 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 168.00 | 71.66 | 0.0000 | Y | 23.66 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | 0.0000 | 174.19 | 0.00 | LightsWired | TYPE3_LIGHT_SCH | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.7485 | 4180.64 | 28213.04 | 433.94 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 314.61 | AstronomicalClock | - | 42.59 | 42.59 | 2.52 | |
EXTERIOR_LIGHTS_B | 4639.80 | AstronomicalClock | - | 83.55 | 71.26 | 62.06 | |
Exterior Lighting Total | 4954.41 | 64.58 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 27310.02 | 21365.17 | 5944.85 | 0.78 | 3.80 | |||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 15087.55 | 11868.17 | 3219.38 | 0.79 | 4.12 | |||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 16795.13 | 13227.84 | 3567.29 | 0.79 | 4.12 | |||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 16719.71 | 13171.45 | 3548.26 | 0.79 | 4.12 | |||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 16641.08 | 13101.69 | 3539.39 | 0.79 | 4.12 | |||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26156.84 | 20427.97 | 5728.87 | 0.78 | 3.80 | |||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 13364.43 | 10450.58 | 2913.85 | 0.78 | 4.12 | |||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 13246.60 | 10342.81 | 2903.79 | 0.78 | 4.12 | |||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 13122.76 | 10240.74 | 2882.02 | 0.78 | 4.12 | |||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 13267.29 | 10400.23 | 2867.06 | 0.78 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | 26073.7 | 11.21 | ||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | 14396.3 | 33.51 | ||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | 16023.6 | 42.01 | ||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | 15951.2 | 54.11 | ||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | 15877.2 | 66.29 | ||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | 24977.2 | 50.90 | ||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | 12760.0 | 118.13 | ||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | 12649.5 | 131.21 | ||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | 12531.9 | 144.45 | ||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | 12664.0 | 154.57 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 47944.97 | 0.80 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25713.45 | 0.80 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 28385.49 | 0.80 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 28297.03 | 0.80 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 28164.41 | 0.80 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 46314.76 | 0.80 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 23324.23 | 0.80 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 23082.67 | 0.80 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 22765.26 | 0.80 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 22920.12 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.58 | 1686.93 | 1070.05 | 1.00 | 1.35 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.88 | 976.08 | 1107.16 | 1.00 | 1.44 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1089.54 | 1107.16 | 1.00 | 1.41 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1085.20 | 1107.16 | 1.00 | 1.41 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.97 | 1078.68 | 1107.16 | 1.00 | 1.41 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.50 | 1609.53 | 1070.05 | 1.00 | 1.36 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.77 | 853.29 | 1107.16 | 1.00 | 1.48 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.76 | 842.93 | 1107.16 | 1.00 | 1.48 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.75 | 834.07 | 1107.16 | 1.00 | 1.48 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.77 | 851.75 | 1107.16 | 1.00 | 1.48 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 17649.01 | 21178.82 | 60.79 | 1.314 | 1.577 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00886 | 29.31 | 0.00879 | 0.411 | 0.00 |
SMSTORE1 | 10020.87 | 12025.04 | 69.03 | 0.721 | 0.866 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00907 | 25.45 | 0.00879 | 0.206 | 0.00 |
SMSTORE2 | 11338.23 | 13605.87 | 78.11 | 0.820 | 0.984 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00928 | 23.68 | 0.00879 | 0.206 | 0.00 |
SMSTORE3 | 11294.79 | 13553.75 | 77.81 | 0.817 | 0.980 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00925 | 23.68 | 0.00879 | 0.206 | 0.00 |
SMSTORE4 | 11226.98 | 13472.37 | 77.34 | 0.812 | 0.974 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00931 | 23.68 | 0.00879 | 0.206 | 0.00 |
LGSTORE2 | 16839.14 | 20206.97 | 58.00 | 1.253 | 1.504 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 23.89 | 23.89 | 0.00888 | 29.05 | 0.00879 | 0.411 | 0.00 |
SMSTORE5 | 8827.15 | 10592.58 | 60.81 | 0.633 | 0.759 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00941 | 25.45 | 0.00879 | 0.206 | 0.00 |
SMSTORE6 | 8706.20 | 10447.44 | 59.98 | 0.624 | 0.749 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00944 | 25.45 | 0.00879 | 0.206 | 0.00 |
SMSTORE7 | 8547.36 | 10256.83 | 58.88 | 0.612 | 0.735 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00948 | 25.45 | 0.00879 | 0.206 | 0.00 |
SMSTORE8 | 8624.56 | 10349.48 | 59.41 | 0.618 | 0.742 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00932 | 25.45 | 0.00879 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 16848.86 | 20218.63 | 58.04 | 0.737 | 0.884 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00675 | -4.20 | 0.00269 | 0.411 | 0.00 |
SMSTORE1 | 8221.62 | 9865.95 | 56.64 | 0.360 | 0.431 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00665 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE2 | 8340.55 | 10008.66 | 57.46 | 0.365 | 0.438 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00666 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE3 | 8432.33 | 10118.80 | 58.09 | 0.369 | 0.443 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00667 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE4 | 8574.95 | 10289.94 | 59.07 | 0.375 | 0.450 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00668 | -4.20 | 0.00269 | 0.206 | 0.00 |
LGSTORE2 | 16583.85 | 19900.62 | 57.12 | 0.725 | 0.870 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00677 | -4.20 | 0.00269 | 0.411 | 0.00 |
SMSTORE5 | 8875.06 | 10650.08 | 61.14 | 0.388 | 0.466 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00671 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE6 | 8876.04 | 10651.25 | 61.15 | 0.388 | 0.466 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00671 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE7 | 9107.65 | 10929.18 | 62.74 | 0.398 | 0.478 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00673 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE8 | 10611.35 | 12733.62 | 73.10 | 0.464 | 0.557 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00680 | -4.20 | 0.00269 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.58 | 1.58 | 0.88 | 0.88 | 1.5765 | 1.5765 | 1.5765 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 0.88 | 0.88 | 0.43 | 0.43 | 0.8816 | 0.8655 | 0.8816 | 0.9817 | 1.0000 |
PSZ-AC_3:3 | 0.98 | 0.98 | 0.44 | 0.44 | 0.9841 | 0.9841 | 0.9841 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 0.98 | 0.98 | 0.44 | 0.44 | 0.9802 | 0.9802 | 0.9802 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 0.97 | 0.97 | 0.45 | 0.45 | 0.9743 | 0.9743 | 0.9743 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.50 | 1.50 | 0.87 | 0.87 | 1.5042 | 1.5042 | 1.5042 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.77 | 0.77 | 0.47 | 0.47 | 0.7707 | 0.7595 | 0.7707 | 0.9854 | 1.0000 |
PSZ-AC_8:8 | 0.76 | 0.76 | 0.47 | 0.47 | 0.7613 | 0.7488 | 0.7613 | 0.9835 | 1.0000 |
PSZ-AC_9:9 | 0.75 | 0.75 | 0.48 | 0.48 | 0.7533 | 0.7347 | 0.7533 | 0.9752 | 1.0000 |
PSZ-AC_10:10 | 0.77 | 0.77 | 0.56 | 0.56 | 0.7693 | 0.7415 | 0.7693 | 0.9639 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 13655.010 | 0.000 | 1.576500 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 13655.01 | 12857.60 | 1.576500 | 25.33 | 16.98 | 0.00884645 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 26.0992 | 23.89 | 0.00886494 | 47.3279 | 17644.79 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 47944.972 | 47944.972 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 47944.97 | 47944.97 | 1.576503 | 9.33 | 6.41 | 0.00486154 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 26.0991 | 21.11 | 0.00675132 | 42.8269 | 16848.86 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 7543.775 | 0.000 | 0.881610 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 7543.77 | 7127.20 | 0.881610 | 25.18 | 16.91 | 0.00882307 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 23.3353 | 23.89 | 0.00907327 | 48.4283 | 9837.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 25713.447 | 25713.447 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 25713.45 | 25713.45 | 0.881610 | 9.04 | 6.14 | 0.00475960 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 23.3353 | 21.11 | 0.00664559 | 42.1636 | 8221.62 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 8397.565 | 0.000 | 0.984090 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8397.57 | 7935.49 | 0.984090 | 25.15 | 16.90 | 0.00882110 | 12.80 | 11.97 | 0.00850000 | 29.31 | 0.00879438 | 18.27 | 20.9053 | 23.89 | 0.00928496 | 49.5457 | 11338.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 28385.492 | 28385.492 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28385.49 | 28385.49 | 0.984088 | 9.21 | 6.26 | 0.00479316 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.9053 | 21.11 | 0.00665817 | 42.2426 | 8340.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 8359.855 | 0.000 | 0.980160 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8359.85 | 7901.01 | 0.980160 | 25.14 | 16.89 | 0.00882011 | 12.80 | 11.97 | 0.00850000 | 29.31 | 0.00879438 | 18.27 | 20.9891 | 23.89 | 0.00924714 | 49.3460 | 11294.79 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 28297.030 | 28297.030 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28297.03 | 28297.03 | 0.980162 | 9.34 | 6.36 | 0.00481821 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.9890 | 21.11 | 0.00666704 | 42.2983 | 8432.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 8320.540 | 0.000 | 0.974280 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8320.54 | 7860.89 | 0.974280 | 25.16 | 16.90 | 0.00882268 | 12.80 | 11.97 | 0.00850000 | 29.31 | 0.00879438 | 18.27 | 21.1158 | 23.89 | 0.00930818 | 49.6680 | 11226.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 28164.411 | 28164.411 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28164.41 | 28164.41 | 0.974278 | 9.54 | 6.50 | 0.00485684 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 21.1158 | 21.11 | 0.00668155 | 42.3894 | 8574.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 13078.420 | 0.000 | 1.504170 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 13078.42 | 12295.59 | 1.504170 | 25.38 | 17.01 | 0.00885689 | 12.80 | 11.97 | 0.00850000 | 29.31 | 0.00879438 | 18.27 | 27.3542 | 23.89 | 0.00888106 | 47.4127 | 16800.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 46314.763 | 46314.763 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 46314.76 | 46314.76 | 1.504166 | 9.14 | 6.29 | 0.00483953 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 27.3543 | 21.11 | 0.00676684 | 42.9240 | 16583.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 6682.215 | 0.000 | 0.770700 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6682.22 | 6287.50 | 0.770700 | 25.34 | 16.99 | 0.00885106 | 12.80 | 11.97 | 0.00850000 | 29.31 | 0.00879438 | 18.27 | 26.6935 | 23.89 | 0.00940651 | 50.1840 | 8596.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 23324.226 | 23324.226 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 23324.23 | 23324.23 | 0.770700 | 9.93 | 6.78 | 0.00493270 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 26.6935 | 21.11 | 0.00670692 | 42.5487 | 8875.06 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 6623.300 | 0.000 | 0.761340 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6623.30 | 6230.52 | 0.761340 | 25.38 | 17.01 | 0.00885359 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 27.0217 | 23.89 | 0.00943626 | 50.3406 | 8502.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 23082.668 | 23082.668 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 23082.67 | 23082.67 | 0.761344 | 9.93 | 6.78 | 0.00493302 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 27.0215 | 21.11 | 0.00670714 | 42.5501 | 8876.04 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 6561.380 | 0.000 | 0.753350 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 6561.38 | 6170.54 | 0.753350 | 25.40 | 17.01 | 0.00885565 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 27.3082 | 23.89 | 0.00947986 | 50.5700 | 8417.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 22765.258 | 22765.258 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 22765.26 | 22765.26 | 0.753347 | 10.21 | 6.99 | 0.00498992 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 27.3084 | 21.11 | 0.00672783 | 42.6800 | 9107.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 6633.645 | 0.000 | 0.769310 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 6633.65 | 6239.62 | 0.769310 | 25.27 | 16.97 | 0.00885140 | 12.80 | 11.97 | 0.00850000 | 29.05 | 0.00879438 | 18.19 | 26.7417 | 23.89 | 0.00931989 | 49.7273 | 8592.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 22920.122 | 22920.122 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 22920.12 | 22920.12 | 0.769313 | 11.76 | 8.06 | 0.00528133 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 26.7416 | 21.11 | 0.00679944 | 43.1301 | 10611.35 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13655.010 | 0.000 | 1.576500 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2851 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 13655.01 | 12857.60 | 1.0000 | 1.87129097 | 1.576500 | 25.33 | 16.98 | 0.00884645 | 47991.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13655.01 | 29.40 | 0.00879438 | 18.30 | 0.41145340 | 26.0992 | 23.89 | 0.00886485 | 23.89 | 0.00886494 | 47.3279 | 17644.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 47944.972 | 47944.972 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.576503 | 1.87129507 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 47944.97 | 47944.97 | 1.0000 | 1.87129507 | 1.576503 | 9.33 | 6.41 | 0.00486154 | 21618.7 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47944.97 | -4.20 | 0.00269032 | -4.20 | 0.41145340 | 26.0991 | 21.11 | 0.00675132 | 21.11 | 0.00675132 | 42.8269 | 16848.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 7543.775 | 0.000 | 0.881610 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2416 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 7543.77 | 7127.20 | 1.0000 | 1.04646294 | 0.881610 | 25.18 | 16.91 | 0.00882307 | 47780.0 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7543.77 | 29.40 | 0.00879438 | 18.30 | 0.20572670 | 23.3353 | 23.89 | 0.00883184 | 23.89 | 0.00907327 | 48.4283 | 9837.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25713.447 | 25713.447 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.881610 | 1.04646287 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 25713.45 | 25713.45 | 1.0000 | 1.04646287 | 0.881610 | 9.04 | 6.14 | 0.00475960 | 21067.4 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25713.45 | -4.20 | 0.00269032 | -4.20 | 0.20572670 | 23.3353 | 21.11 | 0.00664559 | 21.11 | 0.00664559 | 42.1636 | 8221.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8397.565 | 0.000 | 0.984090 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2380 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8397.57 | 7935.49 | 1.0000 | 1.16810576 | 0.984090 | 25.15 | 16.90 | 0.00882110 | 47741.7 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8397.57 | 29.31 | 0.00879438 | 18.27 | 0.20572670 | 20.9053 | 23.89 | 0.00882917 | 23.89 | 0.00928496 | 49.5457 | 11338.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28385.492 | 28385.492 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.984088 | 1.16810335 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28385.49 | 28385.49 | 1.0000 | 1.16810335 | 0.984088 | 9.21 | 6.26 | 0.00479316 | 21326.4 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28385.49 | -4.20 | 0.00269032 | -4.20 | 0.20572670 | 20.9053 | 21.11 | 0.00665817 | 21.11 | 0.00665817 | 42.2426 | 8340.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8359.855 | 0.000 | 0.980160 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2362 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8359.85 | 7901.01 | 1.0000 | 1.16344089 | 0.980160 | 25.14 | 16.89 | 0.00882011 | 47733.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8359.85 | 29.31 | 0.00879438 | 18.27 | 0.20572670 | 20.9891 | 23.89 | 0.00882783 | 23.89 | 0.00924714 | 49.3460 | 11294.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28297.030 | 28297.030 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.980162 | 1.16344367 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28297.03 | 28297.03 | 1.0000 | 1.16344367 | 0.980162 | 9.34 | 6.36 | 0.00481821 | 21520.7 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28297.03 | -4.20 | 0.00269032 | -4.20 | 0.20572670 | 20.9890 | 21.11 | 0.00666704 | 21.11 | 0.00666704 | 42.2983 | 8432.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8320.540 | 0.000 | 0.974280 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2409 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 8320.54 | 7860.89 | 1.0000 | 1.15646138 | 0.974280 | 25.16 | 16.90 | 0.00882268 | 47755.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8320.54 | 29.31 | 0.00879438 | 18.27 | 0.20572670 | 21.1158 | 23.89 | 0.00883130 | 23.89 | 0.00930818 | 49.6680 | 11226.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28164.411 | 28164.411 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.974278 | 1.15645847 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28164.41 | 28164.41 | 1.0000 | 1.15645847 | 0.974278 | 9.54 | 6.50 | 0.00485684 | 21816.4 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28164.41 | -4.20 | 0.00269032 | -4.20 | 0.20572670 | 21.1158 | 21.11 | 0.00668155 | 21.11 | 0.00668155 | 42.3894 | 8574.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13078.420 | 0.000 | 1.504170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3045 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 13078.42 | 12295.59 | 1.0000 | 1.78543593 | 1.504170 | 25.38 | 17.01 | 0.00885689 | 48067.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13078.42 | 29.31 | 0.00879438 | 18.27 | 0.41145340 | 27.3542 | 23.89 | 0.00888050 | 23.89 | 0.00888106 | 47.4127 | 16800.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 46314.763 | 46314.763 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.504166 | 1.78543079 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 46314.76 | 46314.76 | 1.0000 | 1.78543079 | 1.504166 | 9.14 | 6.29 | 0.00483953 | 21372.6 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46314.76 | -4.20 | 0.00269032 | -4.20 | 0.41145340 | 27.3543 | 21.11 | 0.00676684 | 21.11 | 0.00676684 | 42.9240 | 16583.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 6682.215 | 0.000 | 0.770700 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2937 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6682.22 | 6287.50 | 1.0000 | 0.91481380 | 0.770700 | 25.34 | 16.99 | 0.00885106 | 48017.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6682.22 | 29.31 | 0.00879438 | 18.27 | 0.20572670 | 26.6935 | 23.89 | 0.00887180 | 23.89 | 0.00940651 | 50.1840 | 8596.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23324.226 | 23324.226 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.770700 | 0.91481370 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 23324.23 | 23324.23 | 1.0000 | 0.91481370 | 0.770700 | 9.93 | 6.78 | 0.00493270 | 22404.2 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23324.23 | -4.20 | 0.00269032 | -4.20 | 0.20572670 | 26.6935 | 21.11 | 0.00670692 | 21.11 | 0.00670692 | 42.5487 | 8875.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 6623.300 | 0.000 | 0.761340 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2984 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6623.30 | 6230.52 | 1.0000 | 0.90370356 | 0.761340 | 25.38 | 17.01 | 0.00885359 | 48067.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6623.30 | 29.40 | 0.00879438 | 18.30 | 0.20572670 | 27.0217 | 23.89 | 0.00887566 | 23.89 | 0.00943626 | 50.3406 | 8502.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23082.668 | 23082.668 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.761344 | 0.90370863 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 23082.67 | 23082.67 | 1.0000 | 0.90370863 | 0.761344 | 9.93 | 6.78 | 0.00493302 | 22406.3 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23082.67 | -4.20 | 0.00269032 | -4.20 | 0.20572670 | 27.0215 | 21.11 | 0.00670714 | 21.11 | 0.00670714 | 42.5501 | 8876.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 6561.380 | 0.000 | 0.753350 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3022 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 6561.38 | 6170.54 | 1.0000 | 0.89421951 | 0.753350 | 25.40 | 17.01 | 0.00885565 | 48088.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6561.38 | 29.40 | 0.00879438 | 18.30 | 0.20572670 | 27.3082 | 23.89 | 0.00887879 | 23.89 | 0.00947986 | 50.5700 | 8417.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22765.258 | 22765.258 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.753347 | 0.89421575 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 22765.26 | 22765.26 | 1.0000 | 0.89421575 | 0.753347 | 10.21 | 6.99 | 0.00498992 | 22837.9 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22765.26 | -4.20 | 0.00269032 | -4.20 | 0.20572670 | 27.3084 | 21.11 | 0.00672783 | 21.11 | 0.00672783 | 42.6800 | 9107.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 6633.645 | 0.000 | 0.769310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2943 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 6633.65 | 6239.62 | 1.0000 | 0.91316388 | 0.769310 | 25.27 | 16.97 | 0.00885140 | 47948.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6633.65 | 29.05 | 0.00879438 | 18.19 | 0.20572670 | 26.7417 | 23.89 | 0.00887228 | 23.89 | 0.00931989 | 49.7273 | 8592.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22920.122 | 22920.122 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.769313 | 0.91316709 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 22920.12 | 22920.12 | 1.0000 | 0.91316709 | 0.769313 | 11.76 | 8.06 | 0.00528133 | 25138.3 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22920.12 | -4.20 | 0.00269032 | -4.20 | 0.20572670 | 26.7416 | 21.11 | 0.00679944 | 21.11 | 0.00679944 | 43.1301 | 10611.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.58 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.98 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.98 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.97 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.50 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 1326.00 | 3960.83 | 345.50 |
SMSTORE1 | 1315.17 | 3475.83 | 134.33 |
SMSTORE2 | 1080.83 | 2624.83 | 93.67 |
SMSTORE3 | 1093.50 | 2666.67 | 126.83 |
SMSTORE4 | 1053.83 | 2812.17 | 182.50 |
LGSTORE2 | 966.67 | 2940.67 | 422.00 |
SMSTORE5 | 940.67 | 2962.00 | 487.17 |
SMSTORE6 | 945.83 | 3010.83 | 523.17 |
SMSTORE7 | 1006.67 | 3080.00 | 624.00 |
SMSTORE8 | 1402.50 | 3223.83 | 1088.33 |
Facility | 2579.83 | 4556.00 | 1296.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 2.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2.67 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.921 | 0.230 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.662 | 0.245 | 0.000 | 0.000 |
SMSTORE2 | 3.77 | 15.00 | 902.60 | 1.212 | 0.320 | 0.000 | 0.000 |
SMSTORE3 | 3.77 | 15.00 | 902.60 | 1.205 | 0.320 | 0.000 | 0.000 |
SMSTORE4 | 3.77 | 15.00 | 902.60 | 1.176 | 0.320 | 0.000 | 0.000 |
LGSTORE2 | 13.20 | 30.00 | 1805.20 | 0.926 | 0.307 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 0.833 | 0.341 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 0.833 | 0.341 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 0.833 | 0.341 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 0.833 | 0.359 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 9.03 | 30.00 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 4.51 | 15.00 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 3.77 | 15.00 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 3.77 | 15.00 | 902.60 | 0.806 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 3.77 | 15.00 | 902.60 | 0.805 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 13.20 | 30.00 | 1805.20 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 6.60 | 15.00 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 6.60 | 15.00 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 6.60 | 15.00 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 6.60 | 15.00 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 871.76 | 3078.07 | 15-JAN-08:00 | 73992.60 | 29-AUG-16:00 |
Electricity:Building | 562.66 | 1860.07 | 01-JAN-00:10 | 34891.92 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 127.94 | 349.95 | 01-JAN-00:10 | 6574.13 | 01-JAN-10:10 |
InteriorLights:Electricity | 433.94 | 1410.65 | 01-JAN-00:10 | 26802.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 101.59 | 275.05 | 01-JAN-00:10 | 5225.88 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 433.94 | 1410.65 | 01-JAN-00:10 | 26802.39 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 73.22 | 200.01 | 01-JAN-00:10 | 3762.66 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 60.04 | 162.55 | 01-JAN-00:10 | 3088.53 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 53.93 | 185.94 | 01-JAN-00:10 | 3495.47 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 43.46 | 148.49 | 01-JAN-00:10 | 2821.35 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 53.93 | 185.94 | 01-JAN-00:10 | 3495.47 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 43.46 | 148.49 | 01-JAN-00:10 | 2821.35 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 53.93 | 185.94 | 01-JAN-00:10 | 3495.47 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 43.46 | 148.49 | 01-JAN-00:10 | 2821.35 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 66.57 | 250.76 | 01-JAN-00:10 | 4689.57 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 47.31 | 175.86 | 01-JAN-00:10 | 3341.31 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 33.29 | 125.38 | 01-JAN-00:10 | 2344.79 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 23.66 | 87.93 | 01-JAN-00:10 | 1670.66 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 33.29 | 125.38 | 01-JAN-00:10 | 2344.79 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 23.66 | 87.93 | 01-JAN-00:10 | 1670.66 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 33.29 | 125.38 | 01-JAN-00:10 | 2344.79 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 23.66 | 87.93 | 01-JAN-00:10 | 1670.66 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 33.29 | 125.38 | 01-JAN-00:10 | 2344.79 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 23.66 | 87.93 | 01-JAN-00:10 | 1670.66 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
Electricity:Plant | 60.59 | 1218.00 | 01-JAN-09:10 | 11838.75 | 03-JAN-14:50 |
WaterSystems:Electricity | 60.59 | 1218.00 | 01-JAN-09:10 | 11838.75 | 03-JAN-14:50 |
Water Heater:WaterSystems:Electricity | 60.59 | 1218.00 | 01-JAN-09:10 | 11838.75 | 03-JAN-14:50 |
ElectricityPurchased:Facility | 871.76 | 3078.07 | 15-JAN-08:00 | 73992.60 | 29-AUG-16:00 |
ElectricityPurchased:Plant | 871.76 | 3078.07 | 15-JAN-08:00 | 73992.60 | 29-AUG-16:00 |
Cogeneration:ElectricityPurchased | 871.76 | 3078.07 | 15-JAN-08:00 | 73992.60 | 29-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 871.76 | 3078.07 | 15-JAN-08:00 | 73992.60 | 29-AUG-16:00 |
ElectricityNet:Plant | 871.76 | 3078.07 | 15-JAN-08:00 | 73992.60 | 29-AUG-16:00 |
Cogeneration:ElectricityNet | 871.76 | 3078.07 | 15-JAN-08:00 | 73992.60 | 29-AUG-16:00 |
Electricity:HVAC | 183.93 | 0.00 | 01-JAN-00:10 | 34368.50 | 29-AUG-15:00 |
Fans:Electricity | 152.69 | 0.00 | 01-JAN-00:10 | 9921.37 | 07-JAN-09:10 |
General:Fans:Electricity | 152.69 | 0.00 | 01-JAN-00:10 | 9921.37 | 07-JAN-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 31.24 | 0.00 | 01-JAN-00:10 | 24896.19 | 29-AUG-15:00 |
ExteriorLights:Electricity | 64.58 | 0.00 | 01-JAN-08:10 | 4954.41 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 64.58 | 0.00 | 01-JAN-08:10 | 4954.41 | 01-JAN-06:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 309.26 | 0.00 | 01-JAN-00:10 | 161878.86 | 26-DEC-09:10 |
Gas:HVAC | 309.26 | 0.00 | 01-JAN-00:10 | 161878.86 | 26-DEC-09:10 |
Heating:Gas | 309.26 | 0.00 | 01-JAN-00:10 | 161878.86 | 26-DEC-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 727.09 | 0.00 | 01-JAN-00:10 | 211589.42 | 26-DEC-09:10 |
EnergyTransfer:Building | 341.83 | 0.00 | 01-JAN-00:10 | 82086.32 | 26-DEC-09:10 |
EnergyTransfer:Zone:LGSTORE1 | 75.14 | 0.00 | 01-JAN-00:10 | 16381.18 | 19-FEB-09:10 |
Heating:EnergyTransfer | 64.40 | 0.00 | 01-JAN-00:10 | 77514.18 | 26-DEC-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 6.65 | 0.00 | 01-JAN-00:10 | 15107.08 | 19-FEB-09:10 |
Cooling:EnergyTransfer | 277.44 | 0.00 | 01-JAN-00:10 | 70847.30 | 10-AUG-16:40 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 68.49 | 0.00 | 01-JAN-00:10 | 12440.05 | 10-AUG-17:00 |
EnergyTransfer:Zone:SMSTORE1 | 40.72 | 0.00 | 01-JAN-00:10 | 7646.63 | 19-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 1.72 | 0.00 | 01-JAN-00:10 | 7092.98 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 39.00 | 0.00 | 01-JAN-00:10 | 6586.11 | 10-AUG-16:40 |
EnergyTransfer:Zone:SMSTORE2 | 30.70 | 0.00 | 01-JAN-00:10 | 6527.44 | 10-AUG-16:30 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 3.24 | 0.00 | 01-JAN-00:10 | 5273.73 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 27.46 | 0.00 | 01-JAN-00:10 | 6527.44 | 10-AUG-16:30 |
EnergyTransfer:Zone:SMSTORE3 | 30.14 | 0.00 | 01-JAN-00:10 | 7592.27 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 3.65 | 0.00 | 01-JAN-00:10 | 6632.62 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 26.50 | 0.00 | 01-JAN-00:10 | 6519.87 | 10-AUG-16:30 |
EnergyTransfer:Zone:SMSTORE4 | 28.26 | 0.00 | 01-JAN-00:10 | 7691.60 | 20-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 4.39 | 0.00 | 01-JAN-00:10 | 7014.42 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 23.86 | 0.00 | 01-JAN-00:10 | 6381.83 | 10-AUG-16:30 |
EnergyTransfer:Zone:LGSTORE2 | 44.62 | 0.00 | 01-JAN-00:10 | 17677.38 | 26-DEC-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 10.02 | 0.00 | 01-JAN-00:10 | 16372.73 | 26-DEC-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 34.60 | 0.00 | 01-JAN-00:10 | 10657.38 | 10-AUG-16:30 |
EnergyTransfer:Zone:SMSTORE5 | 22.90 | 0.00 | 01-JAN-00:10 | 9221.00 | 26-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 6.46 | 0.00 | 01-JAN-00:10 | 8627.46 | 26-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 16.43 | 0.00 | 01-JAN-00:10 | 5501.83 | 10-AUG-16:40 |
EnergyTransfer:Zone:SMSTORE6 | 22.52 | 0.00 | 01-JAN-00:10 | 9401.83 | 26-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 6.84 | 0.00 | 01-JAN-00:10 | 8809.90 | 26-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 15.68 | 0.00 | 01-JAN-00:10 | 5440.95 | 10-AUG-16:30 |
EnergyTransfer:Zone:SMSTORE7 | 22.10 | 0.00 | 01-JAN-00:10 | 9655.89 | 16-JAN-10:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 7.97 | 0.00 | 01-JAN-00:10 | 9110.94 | 26-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 14.13 | 0.00 | 01-JAN-00:10 | 5374.93 | 10-AUG-16:40 |
EnergyTransfer:Zone:SMSTORE8 | 24.72 | 0.00 | 01-JAN-00:10 | 11012.36 | 16-JAN-10:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 13.45 | 0.00 | 01-JAN-00:10 | 11012.36 | 16-JAN-10:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 11.28 | 0.00 | 01-JAN-00:10 | 5464.80 | 10-AUG-16:30 |
EnergyTransfer:HVAC | 385.25 | 0.00 | 01-JAN-00:10 | 129503.09 | 26-DEC-09:10 |
HeatingCoils:EnergyTransfer | 247.41 | 0.00 | 01-JAN-00:10 | 129503.09 | 26-DEC-09:10 |
CoolingCoils:EnergyTransfer | 137.85 | 0.00 | 01-JAN-00:10 | 109711.47 | 29-AUG-14:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 6.647 | -68.491 | 0.000 | 0.000 | 13.589 | 101.585 | 26.357 | 14.364 | 0.000 | 0.453 | 0.003 | 0.000 | -9.640 | 0.000 | -31.441 | -53.423 |
SMSTORE1 | 0.000 | 0.000 | 1.720 | -38.999 | 0.000 | 0.000 | 6.613 | 60.038 | 13.179 | 7.090 | 0.000 | 0.246 | 0.001 | 0.000 | -5.124 | 0.000 | -15.874 | -28.889 |
SMSTORE2 | 0.000 | 0.000 | 3.239 | -27.462 | 0.000 | 0.000 | 4.027 | 43.461 | 10.467 | 7.066 | 0.000 | 0.241 | 0.001 | 0.000 | -5.079 | 0.000 | -16.407 | -19.552 |
SMSTORE3 | 0.000 | 0.000 | 3.646 | -26.498 | 0.000 | 0.000 | 4.035 | 43.461 | 10.467 | 7.079 | 0.000 | 0.241 | 0.000 | 0.000 | -5.016 | 0.000 | -16.320 | -21.094 |
SMSTORE4 | 0.000 | 0.000 | 4.395 | -23.863 | 0.000 | 0.000 | 4.053 | 43.461 | 10.467 | 7.112 | 0.000 | 0.241 | 0.002 | 0.000 | -4.927 | 0.000 | -16.158 | -24.780 |
LGSTORE2 | 0.000 | 0.000 | 10.021 | -34.604 | 0.000 | 0.000 | 14.121 | 47.311 | 19.261 | 14.400 | 0.000 | 0.435 | 0.000 | 0.000 | -9.371 | 0.000 | -28.836 | -32.738 |
SMSTORE5 | 0.000 | 0.000 | 6.464 | -16.433 | 0.000 | 0.000 | 7.046 | 23.655 | 9.631 | 7.209 | 0.000 | 0.242 | 0.003 | 0.000 | -4.663 | 0.000 | -15.753 | -17.397 |
SMSTORE6 | 0.000 | 0.000 | 6.843 | -15.682 | 0.000 | 0.000 | 7.054 | 23.655 | 9.631 | 7.223 | 0.000 | 0.242 | 0.002 | 0.000 | -4.632 | 0.000 | -15.701 | -18.633 |
SMSTORE7 | 0.000 | 0.000 | 7.974 | -14.127 | 0.000 | 0.000 | 7.072 | 23.655 | 9.631 | 7.252 | 0.000 | 0.242 | 0.000 | 0.000 | -4.555 | 0.000 | -15.584 | -21.558 |
SMSTORE8 | 0.000 | 0.000 | 13.448 | -11.276 | 0.000 | 0.000 | 7.104 | 23.655 | 9.631 | 7.327 | 0.000 | 0.252 | 0.001 | 0.000 | -4.287 | 0.000 | -19.207 | -26.647 |
Total Facility | 0.000 | 0.000 | 64.398 | -277.435 | 0.000 | 0.000 | 74.714 | 433.937 | 128.721 | 86.121 | 0.000 | 2.834 | 0.013 | 0.000 | -57.296 | 0.000 | -191.282 | -264.711 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 09-AUG-08:62 | 0.00 | 0.00 | 0.00 | -26445.82 | 0.00 | 0.00 | 95.41 | 2750.46 | 749.03 | 550.25 | 0.00 | 0.00 | 22432.02 | 0.00 | -0.00 | 0.00 | -131.35 | 0.00 |
SMSTORE1 | 03-SEP-07:02 | 0.00 | 0.00 | 0.00 | -14008.79 | 0.00 | 0.00 | 49.74 | 162.55 | 37.45 | 0.00 | 0.00 | 0.00 | 14116.04 | 0.00 | -125.67 | 0.00 | -231.33 | 0.00 |
SMSTORE2 | 16-SEP-07:02 | 0.00 | 0.00 | 0.00 | -19815.44 | 0.00 | 0.00 | 46.22 | 1484.92 | 374.52 | 0.00 | 0.00 | 0.00 | 18421.31 | 0.00 | -186.08 | 0.00 | -325.44 | 0.00 |
SMSTORE3 | 16-SEP-07:02 | 0.00 | 0.00 | 0.00 | -19725.49 | 0.00 | 0.00 | 46.27 | 1484.92 | 374.52 | 0.00 | 0.00 | 0.00 | 18330.97 | 0.00 | -185.91 | 0.00 | -325.27 | 0.00 |
SMSTORE4 | 16-SEP-07:02 | 0.00 | 0.00 | 0.00 | -19484.49 | 0.00 | 0.00 | 46.82 | 1484.92 | 374.52 | 0.00 | 0.00 | 0.00 | 18083.72 | 0.00 | -183.36 | 0.00 | -322.12 | 0.00 |
LGSTORE2 | 23-JUL-09:02 | 0.00 | 0.00 | 0.00 | -25323.02 | 0.00 | 0.00 | 214.58 | 1758.59 | 749.03 | 449.42 | 0.00 | 0.00 | 22367.82 | 0.00 | -0.00 | 0.00 | -216.41 | 0.00 |
SMSTORE5 | 24-JUL-08:62 | 0.00 | 0.00 | 0.00 | -11296.07 | 0.00 | 0.00 | 108.50 | 879.29 | 374.52 | 240.83 | 0.00 | 0.00 | 9741.50 | 0.00 | -0.00 | 0.00 | -48.57 | 0.00 |
SMSTORE6 | 24-JUL-08:62 | 0.00 | 0.00 | 0.00 | -11148.38 | 0.00 | 0.00 | 109.03 | 879.29 | 374.52 | 242.06 | 0.00 | 0.00 | 9590.69 | 0.00 | -0.00 | 0.00 | -47.22 | 0.00 |
SMSTORE7 | 24-JUL-08:62 | 0.00 | 0.00 | 0.00 | -10961.67 | 0.00 | 0.00 | 110.15 | 879.29 | 374.52 | 244.47 | 0.00 | 0.00 | 9397.40 | 0.00 | -0.00 | 0.00 | -44.17 | 0.00 |
SMSTORE8 | 10-AUG-08:62 | 0.00 | 0.00 | 0.00 | -8625.96 | 0.00 | 0.00 | 111.65 | 879.29 | 374.52 | 205.81 | 0.00 | 0.00 | 7122.81 | 0.00 | -0.00 | 0.00 | -68.12 | 0.00 |
Total Facility | 24-JUL-08:62 | 0.00 | 0.00 | 0.00 | -111730.15 | 0.00 | 0.00 | 1104.28 | 18115.80 | 5393.02 | 2911.24 | 0.00 | 0.00 | 84807.66 | 0.00 | 0.00 | 0.00 | -601.85 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 23-FEB-09:01 | 0.00 | 0.00 | 43641.95 | 0.00 | 0.00 | 0.00 | 129.44 | 2750.46 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -76.18 | 0.00 | -577.14 | -46617.55 |
SMSTORE1 | 01-APR-08:61 | 0.00 | 0.00 | 23632.28 | 0.00 | 0.00 | 0.00 | 64.88 | 1625.54 | 374.52 | 137.29 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -239.97 | -25594.54 |
SMSTORE2 | 20-FEB-09:01 | 0.00 | 0.00 | 24046.04 | 0.00 | 0.00 | 0.00 | 65.62 | 1484.92 | 374.52 | 10.41 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -501.34 | -25480.17 |
SMSTORE3 | 01-JAN-09:01 | 0.00 | 0.00 | 25195.63 | 0.00 | 0.00 | 0.00 | 65.66 | 1484.92 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -135.96 | 0.00 | -333.32 | -26651.44 |
SMSTORE4 | 01-JAN-09:01 | 0.00 | 0.00 | 25160.41 | 0.00 | 0.00 | 0.00 | 66.72 | 1484.92 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -128.97 | 0.00 | -323.54 | -26634.06 |
LGSTORE2 | 16-JAN-09:01 | 0.00 | 0.00 | 46575.04 | 0.00 | 0.00 | 0.00 | 0.00 | 175.86 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -371.15 | 0.00 | -919.09 | -45535.56 |
SMSTORE5 | 24-FEB-09:01 | 0.00 | 0.00 | 22028.07 | 0.00 | 0.00 | 0.00 | 146.58 | 879.29 | 374.52 | 153.85 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -167.99 | -23414.33 |
SMSTORE6 | 24-FEB-09:01 | 0.00 | 0.00 | 21813.39 | 0.00 | 0.00 | 0.00 | 147.08 | 879.29 | 374.52 | 155.51 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -165.64 | -23204.14 |
SMSTORE7 | 24-FEB-09:01 | 0.00 | 0.00 | 21559.62 | 0.00 | 0.00 | 0.00 | 148.40 | 879.29 | 374.52 | 159.76 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -159.55 | -22962.05 |
SMSTORE8 | 24-FEB-09:01 | 0.00 | 0.00 | 21865.00 | 0.00 | 0.00 | 0.00 | 152.07 | 879.29 | 374.52 | 172.52 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -183.06 | -23260.34 |
Total Facility | 20-FEB-09:01 | 0.00 | 0.00 | 255443.71 | 0.00 | 0.00 | 0.00 | 404.96 | 9358.34 | 2471.80 | 372.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5493.27 | -262557.64 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.5765 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.5765 | 0.2610 | 1.0000 | 0.4115 | 0.2610 | ||
PSZ-AC_2:2 | 0.8655 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8816 | 0.2334 | 1.0000 | 0.2057 | 0.2334 | ||
PSZ-AC_3:3 | 0.9841 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9841 | 0.2091 | 1.0000 | 0.2057 | 0.2091 | ||
PSZ-AC_4:4 | 0.9802 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9802 | 0.2099 | 1.0000 | 0.2057 | 0.2099 | ||
PSZ-AC_5:5 | 0.9743 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9743 | 0.2112 | 1.0000 | 0.2057 | 0.2112 | ||
PSZ-AC_6:6 | 1.5042 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.5042 | 0.2735 | 1.0000 | 0.4115 | 0.2735 | ||
PSZ-AC_7:7 | 0.7595 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7707 | 0.2669 | 1.0000 | 0.2057 | 0.2669 | ||
PSZ-AC_8:8 | 0.7488 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7613 | 0.2702 | 1.0000 | 0.2057 | 0.2702 | ||
PSZ-AC_9:9 | 0.7347 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7533 | 0.2731 | 1.0000 | 0.2057 | 0.2731 | ||
PSZ-AC_10:10 | 0.7415 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7693 | 0.2674 | 1.0000 | 0.2057 | 0.2674 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.5765 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.5765 | 1.0000 | 1.0000 | 0.4115 | 0.2610 | ||
PSZ-AC_2:2 | 0.8655 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.8655 | 1.0000 | 1.0000 | 0.2057 | 0.2377 | ||
PSZ-AC_3:3 | 0.9841 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9841 | 1.0000 | 1.0000 | 0.2057 | 0.2091 | ||
PSZ-AC_4:4 | 0.9802 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9802 | 1.0000 | 1.0000 | 0.2057 | 0.2099 | ||
PSZ-AC_5:5 | 0.9743 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.9743 | 1.0000 | 1.0000 | 0.2057 | 0.2112 | ||
PSZ-AC_6:6 | 1.5042 | 0.0000 | 29.9961 | 1.0000 | 0.4115 | 1.5042 | 1.0000 | 1.0000 | 0.4115 | 0.2735 | ||
PSZ-AC_7:7 | 0.7595 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7595 | 1.0000 | 1.0000 | 0.2057 | 0.2709 | ||
PSZ-AC_8:8 | 0.7488 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7488 | 1.0000 | 1.0000 | 0.2057 | 0.2748 | ||
PSZ-AC_9:9 | 0.7347 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7347 | 1.0000 | 1.0000 | 0.2057 | 0.2800 | ||
PSZ-AC_10:10 | 0.7415 | 0.0000 | 14.9980 | 1.0000 | 0.2057 | 0.7415 | 1.0000 | 1.0000 | 0.2057 | 0.2774 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 29.9961 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 14.9980 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 30.00 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 15.00 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.5765 | 1.5765 | 1.5765 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 0.8655 | 0.8655 | 0.8655 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 0.9841 | 0.9841 | 0.9841 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 0.9802 | 0.9802 | 0.9802 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 0.9743 | 0.9743 | 0.9743 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.5042 | 1.5042 | 1.5042 | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.7595 | 0.7595 | 0.7595 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.7488 | 0.7488 | 0.7488 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.7347 | 0.7347 | 0.7347 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 0.7415 | 0.7415 | 0.7415 | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.5765 | 1.5765 | 1.5765 | 1.5765 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.8655 | 0.8816 | 0.8655 | 0.8655 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9841 | 0.9841 | 0.9841 | 0.9841 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9802 | 0.9802 | 0.9802 | 0.9802 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9743 | 0.9743 | 0.9743 | 0.9743 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.5042 | 1.5042 | 1.5042 | 1.5042 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.7595 | 0.7707 | 0.7595 | 0.7595 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.7488 | 0.7613 | 0.7488 | 0.7488 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.7347 | 0.7533 | 0.7347 | 0.7347 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.7415 | 0.7693 | 0.7415 | 0.7415 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | 1.5765 | 1.5765 | 1.5765 | 0.4115 | 0.4653 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE1 | PSZ-AC_2:2 | 0.8655 | 0.8655 | 0.8655 | 0.2057 | 0.4768 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE2 | PSZ-AC_3:3 | 0.9841 | 0.9841 | 0.9841 | 0.2057 | 0.4700 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE3 | PSZ-AC_4:4 | 0.9802 | 0.9802 | 0.9802 | 0.2057 | 0.4649 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE4 | PSZ-AC_5:5 | 0.9743 | 0.9743 | 0.9743 | 0.2057 | 0.4572 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
LGSTORE2 | PSZ-AC_6:6 | 1.5042 | 1.5042 | 1.5042 | 0.4115 | 0.4728 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE5 | PSZ-AC_7:7 | 0.7595 | 0.7595 | 0.7595 | 0.2057 | 0.4417 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE6 | PSZ-AC_8:8 | 0.7488 | 0.7488 | 0.7488 | 0.2057 | 0.4417 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE7 | PSZ-AC_9:9 | 0.7347 | 0.7347 | 0.7347 | 0.2057 | 0.4304 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
SMSTORE8 | PSZ-AC_10:10 | 0.7415 | 0.7415 | 0.7415 | 0.2057 | 0.3694 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.5765 | 1.5765 | 1.5765 | 1.5765 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.8655 | 0.8655 | 0.8655 | 0.8655 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9841 | 0.9841 | 0.9841 | 0.9841 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9802 | 0.9802 | 0.9802 | 0.9802 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9743 | 0.9743 | 0.9743 | 0.9743 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.5042 | 1.5042 | 1.5042 | 1.5042 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.7595 | 0.7595 | 0.7595 | 0.7595 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.7488 | 0.7488 | 0.7488 | 0.7488 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.7347 | 0.7347 | 0.7347 | 0.7347 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.7415 | 0.7415 | 0.7415 | 0.7415 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:19:23
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 309.26 | 161878.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 31.24 | 24896.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 433.94 | 26802.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 64.58 | 4954.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 152.69 | 9921.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 60.59 | 11838.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 871.76 |
Natural Gas | 0.00 | 309.26 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1181.01 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 207.59 |
Space Heating | 0.00 |
Space Cooling | 14.95 |
Fans (All) | 73.05 |
Service Water Heating | 28.99 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 417.04 |
Subtotal | 417.04 |
Natural Gas [MJ/m2] | |
Space Heating | 147.95 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 147.95 |
Subtotal | 147.95 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 36.74 |
Space Heating | 26.19 |
Space Cooling | 2.65 |
Fans (All) | 12.93 |
Service Water Heating | 5.13 |
Receptacle Equipment | 10.90 |
Miscellaneous | 5.47 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
TYPE1_LIGHT_SCH | 5131. | 8760. |
TYPE2_LIGHT_SCH | 4096. | 8760. |
TYPE3_LIGHT_SCH | 3767. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.833651E+11 |
February | 0.000 | 0.563809E+11 |
March | 0.000 | 0.318280E+11 |
April | 0.000 | 0.128832E+11 |
May | 0.000 | 0.227460E+10 |
June | 0.000 | 0.635287E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.190452E+09 |
October | 0.000 | 0.837078E+10 |
November | 0.000 | 0.432878E+11 |
December | 0.000 | 0.706143E+11 |
Annual Sum or Average | 0.309259E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.833651E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.833651E+11 |
February | 0.000 | 0.563809E+11 |
March | 0.000 | 0.318280E+11 |
April | 0.000 | 0.128832E+11 |
May | 0.000 | 0.227460E+10 |
June | 0.000 | 0.635287E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.190452E+09 |
October | 0.000 | 0.837078E+10 |
November | 0.000 | 0.432878E+11 |
December | 0.000 | 0.706143E+11 |
Annual Sum or Average | 0.309259E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.833651E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Meter
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.833651E+11 |
February | 0.000 | 0.563809E+11 |
March | 0.000 | 0.318280E+11 |
April | 0.000 | 0.128832E+11 |
May | 0.000 | 0.227460E+10 |
June | 0.000 | 0.635287E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.190452E+09 |
October | 0.000 | 0.837078E+10 |
November | 0.000 | 0.432878E+11 |
December | 0.000 | 0.706143E+11 |
Annual Sum or Average | 0.309259E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.833651E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.833651E+11 |
February | 0.000 | 0.563809E+11 |
March | 0.000 | 0.318280E+11 |
April | 0.000 | 0.128832E+11 |
May | 0.000 | 0.227460E+10 |
June | 0.000 | 0.635287E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.190452E+09 |
October | 0.000 | 0.837078E+10 |
November | 0.000 | 0.432878E+11 |
December | 0.000 | 0.706143E+11 |
Annual Sum or Average | 0.309259E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.833651E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Meter
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.833651E+11 |
February | 0.000 | 0.563809E+11 |
March | 0.000 | 0.318280E+11 |
April | 0.000 | 0.128832E+11 |
May | 0.000 | 0.227460E+10 |
June | 0.000 | 0.635287E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.190452E+09 |
October | 0.000 | 0.837078E+10 |
November | 0.000 | 0.432878E+11 |
December | 0.000 | 0.706143E+11 |
Annual Sum or Average | 0.309259E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.833651E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.833651E+11 |
February | 0.000 | 0.563809E+11 |
March | 0.000 | 0.318280E+11 |
April | 0.000 | 0.128832E+11 |
May | 0.000 | 0.227460E+10 |
June | 0.000 | 0.635287E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.190452E+09 |
October | 0.000 | 0.837078E+10 |
November | 0.000 | 0.432878E+11 |
December | 0.000 | 0.706143E+11 |
Annual Sum or Average | 0.309259E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.833651E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.833651E+11 |
February | 0.000 | 0.563809E+11 |
March | 0.000 | 0.318280E+11 |
April | 0.000 | 0.128832E+11 |
May | 0.000 | 0.227460E+10 |
June | 0.000 | 0.635287E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.190452E+09 |
October | 0.000 | 0.837078E+10 |
November | 0.000 | 0.432878E+11 |
December | 0.000 | 0.706143E+11 |
Annual Sum or Average | 0.309259E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.833651E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Meter
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.833651E+11 |
February | 0.000 | 0.563809E+11 |
March | 0.000 | 0.318280E+11 |
April | 0.000 | 0.128832E+11 |
May | 0.000 | 0.227460E+10 |
June | 0.000 | 0.635287E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.190452E+09 |
October | 0.000 | 0.837078E+10 |
November | 0.000 | 0.432878E+11 |
December | 0.000 | 0.706143E+11 |
Annual Sum or Average | 0.309259E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.833651E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Meter
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.833651E+11 |
February | 0.000 | 0.563809E+11 |
March | 0.000 | 0.318280E+11 |
April | 0.000 | 0.128832E+11 |
May | 0.000 | 0.227460E+10 |
June | 0.000 | 0.635287E+08 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.190452E+09 |
October | 0.000 | 0.837078E+10 |
November | 0.000 | 0.432878E+11 |
December | 0.000 | 0.706143E+11 |
Annual Sum or Average | 0.309259E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.833651E+11 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148034E+10 | 10584.04 | 21-JAN-09:04 | -1.0 | -1.1 | 0.567412E+09 | 680.12 | 20-JAN-13:09 | 6.70 | 4.71 |
February | 0.218123E+10 | 11466.90 | 19-FEB-09:04 | -3.1 | -4.2 | 0.516723E+09 | 723.22 | 27-FEB-17:10 | 18.62 | 12.13 |
March | 0.393404E+10 | 7888.67 | 24-MAR-08:04 | 4.08 | -0.3 | 0.572136E+09 | 783.23 | 18-MAR-12:00 | 17.20 | 10.93 |
April | 0.536814E+10 | 7775.28 | 18-APR-08:02 | 4.50 | 3.26 | 0.603071E+09 | 899.00 | 29-APR-12:00 | 20.00 | 14.69 |
May | 0.706840E+10 | 7811.74 | 15-MAY-16:40 | 24.23 | 12.93 | 0.679269E+09 | 899.03 | 06-MAY-12:50 | 23.72 | 17.39 |
June | 0.775375E+10 | 13900.48 | 28-JUN-08:63 | 17.98 | 13.04 | 0.708160E+09 | 899.04 | 11-JUN-17:00 | 21.10 | 15.35 |
July | 0.100139E+11 | 24227.76 | 24-JUL-08:62 | 22.07 | 16.25 | 0.752299E+09 | 899.04 | 07-JUL-12:09 | 23.48 | 16.21 |
August | 0.106487E+11 | 26447.36 | 09-AUG-08:62 | 21.72 | 14.31 | 0.742421E+09 | 899.02 | 11-AUG-12:09 | 20.53 | 15.39 |
September | 0.824389E+10 | 16606.87 | 14-SEP-08:63 | 15.87 | 14.39 | 0.707633E+09 | 899.02 | 15-SEP-12:09 | 21.20 | 16.29 |
October | 0.644416E+10 | 7369.81 | 04-OCT-14:00 | 21.10 | 11.38 | 0.640502E+09 | 898.99 | 08-OCT-16:49 | 18.58 | 12.69 |
November | 0.331089E+10 | 9134.64 | 13-NOV-09:03 | 1.70 | 1.46 | 0.562191E+09 | 898.99 | 04-NOV-12:00 | 20.60 | 16.04 |
December | 0.204377E+10 | 10430.62 | 26-DEC-09:04 | -0.9 | -0.9 | 0.570515E+09 | 680.12 | 15-DEC-13:30 | 6.65 | 4.81 |
Annual Sum or Average | 0.684912E+11 | 0.762233E+10 | ||||||||
Minimum of Months | 0.148034E+10 | 7369.81 | -3.1 | -4.2 | 0.516723E+09 | 680.12 | 6.65 | 4.71 | ||
Maximum of Months | 0.106487E+11 | 26447.36 | 24.23 | 16.25 | 0.752299E+09 | 899.04 | 23.72 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.956259E+09 | 4545.53 | 07-JAN-08:62 | -3.8 | -3.8 | 0.294651E+09 | 406.26 | 29-JAN-18:00 | 9.40 | 5.53 |
February | 0.127800E+10 | 5122.79 | 19-FEB-09:04 | -3.1 | -4.2 | 0.273860E+09 | 448.53 | 26-FEB-18:00 | 10.00 | 7.74 |
March | 0.216017E+10 | 3823.29 | 05-MAR-09:04 | 3.40 | 2.59 | 0.312540E+09 | 449.43 | 19-MAR-17:00 | 10.00 | 6.55 |
April | 0.274648E+10 | 6030.30 | 30-APR-07:02 | 12.20 | 12.20 | 0.330547E+09 | 449.51 | 02-APR-17:00 | 17.80 | 11.25 |
May | 0.376124E+10 | 9142.56 | 07-MAY-07:02 | 14.97 | 13.12 | 0.363903E+09 | 449.52 | 14-MAY-17:49 | 22.30 | 11.95 |
June | 0.473710E+10 | 12397.68 | 11-JUN-07:02 | 12.98 | 11.37 | 0.359769E+09 | 449.52 | 04-JUN-17:00 | 15.60 | 12.33 |
July | 0.598002E+10 | 13148.87 | 16-JUL-07:02 | 13.48 | 12.72 | 0.376715E+09 | 449.52 | 23-JUL-17:30 | 26.40 | 15.73 |
August | 0.632186E+10 | 13401.92 | 09-AUG-08:62 | 21.72 | 14.31 | 0.371533E+09 | 449.51 | 04-AUG-12:09 | 17.95 | 15.54 |
September | 0.479346E+10 | 14009.58 | 03-SEP-07:02 | 13.40 | 12.40 | 0.361733E+09 | 449.51 | 22-SEP-12:09 | 20.18 | 16.43 |
October | 0.323582E+10 | 6184.18 | 09-OCT-07:01 | 10.78 | 9.78 | 0.349242E+09 | 449.51 | 08-OCT-17:49 | 16.47 | 11.89 |
November | 0.180041E+10 | 4475.85 | 11-NOV-09:04 | 0.78 | 0.55 | 0.299707E+09 | 449.51 | 04-NOV-12:50 | 20.32 | 15.90 |
December | 0.122792E+10 | 4406.19 | 06-DEC-09:04 | 1.12 | 1.00 | 0.298834E+09 | 413.75 | 03-DEC-18:00 | 8.90 | 3.54 |
Annual Sum or Average | 0.389988E+11 | 0.399303E+10 | ||||||||
Minimum of Months | 0.956259E+09 | 3823.29 | -3.8 | -4.2 | 0.273860E+09 | 406.26 | 8.90 | 3.54 | ||
Maximum of Months | 0.632186E+10 | 14009.58 | 21.72 | 14.31 | 0.376715E+09 | 449.52 | 26.40 | 16.43 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.452116E+09 | 4806.16 | 08-JAN-09:03 | -1.7 | -1.9 | 0.169297E+09 | 340.06 | 21-JAN-13:20 | 2.07 | 1.82 |
February | 0.788567E+09 | 5025.54 | 19-FEB-09:03 | -3.1 | -4.2 | 0.157552E+09 | 386.77 | 25-FEB-13:39 | 14.60 | 11.76 |
March | 0.166560E+10 | 3553.06 | 01-MAR-08:62 | 2.48 | -0.2 | 0.183690E+09 | 433.34 | 18-MAR-12:00 | 17.20 | 10.93 |
April | 0.203052E+10 | 14641.21 | 28-APR-07:03 | 11.28 | 10.33 | 0.191813E+09 | 449.50 | 29-APR-12:00 | 20.00 | 14.69 |
May | 0.267115E+10 | 19201.67 | 08-MAY-07:02 | 9.68 | 9.59 | 0.219435E+09 | 449.52 | 06-MAY-12:00 | 23.90 | 17.57 |
June | 0.332238E+10 | 19495.90 | 29-JUN-07:02 | 12.20 | 11.29 | 0.221255E+09 | 449.50 | 03-JUN-12:20 | 20.60 | 13.15 |
July | 0.420891E+10 | 19683.96 | 19-JUL-07:02 | 15.10 | 11.62 | 0.223839E+09 | 449.52 | 08-JUL-12:09 | 21.70 | 16.35 |
August | 0.469270E+10 | 19690.59 | 01-AUG-07:02 | 11.47 | 11.42 | 0.230078E+09 | 449.51 | 26-AUG-12:30 | 22.20 | 17.28 |
September | 0.333582E+10 | 19822.45 | 16-SEP-07:02 | 10.68 | 10.68 | 0.217133E+09 | 449.51 | 23-SEP-12:09 | 20.37 | 16.55 |
October | 0.239800E+10 | 18427.40 | 05-OCT-07:02 | 9.50 | 6.04 | 0.202191E+09 | 449.49 | 07-OCT-12:20 | 16.47 | 11.91 |
November | 0.121500E+10 | 3070.28 | 22-NOV-08:62 | 2.88 | 2.41 | 0.170340E+09 | 449.50 | 04-NOV-12:00 | 20.60 | 16.04 |
December | 0.681807E+09 | 4712.32 | 26-DEC-08:03 | -1.1 | -1.2 | 0.169357E+09 | 364.41 | 02-DEC-13:00 | 12.20 | 5.78 |
Annual Sum or Average | 0.274626E+11 | 0.235598E+10 | ||||||||
Minimum of Months | 0.452116E+09 | 3070.28 | -3.1 | -4.2 | 0.157552E+09 | 340.06 | 2.07 | 1.82 | ||
Maximum of Months | 0.469270E+10 | 19822.45 | 15.10 | 11.62 | 0.230078E+09 | 449.52 | 23.90 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.381261E+09 | 4778.74 | 15-JAN-09:04 | -2.5 | -3.8 | 0.169245E+09 | 340.06 | 21-JAN-13:20 | 2.07 | 1.82 |
February | 0.689386E+09 | 5183.62 | 19-FEB-09:03 | -3.1 | -4.2 | 0.157064E+09 | 381.13 | 25-FEB-13:39 | 14.60 | 11.76 |
March | 0.151958E+10 | 3493.61 | 01-MAR-08:62 | 2.48 | -0.2 | 0.182334E+09 | 429.08 | 18-MAR-12:00 | 17.20 | 10.93 |
April | 0.192058E+10 | 13378.72 | 28-APR-07:03 | 11.28 | 10.33 | 0.190080E+09 | 449.50 | 29-APR-12:00 | 20.00 | 14.69 |
May | 0.258498E+10 | 18284.71 | 08-MAY-07:02 | 9.68 | 9.59 | 0.218481E+09 | 449.52 | 06-MAY-12:00 | 23.90 | 17.57 |
June | 0.326503E+10 | 19406.31 | 29-JUN-07:02 | 12.20 | 11.29 | 0.221143E+09 | 449.50 | 03-JUN-12:20 | 20.60 | 13.15 |
July | 0.418345E+10 | 19571.62 | 19-JUL-07:02 | 15.10 | 11.62 | 0.223830E+09 | 449.52 | 08-JUL-12:09 | 21.70 | 16.35 |
August | 0.468072E+10 | 19623.37 | 01-AUG-07:02 | 11.47 | 11.42 | 0.230073E+09 | 449.51 | 26-AUG-12:30 | 22.20 | 17.28 |
September | 0.328416E+10 | 19732.45 | 16-SEP-07:02 | 10.68 | 10.68 | 0.216915E+09 | 449.51 | 23-SEP-12:09 | 20.37 | 16.55 |
October | 0.230718E+10 | 17442.08 | 05-OCT-07:02 | 9.50 | 6.04 | 0.200287E+09 | 449.49 | 07-OCT-12:20 | 16.47 | 11.91 |
November | 0.109571E+10 | 3097.65 | 26-NOV-09:03 | 4.50 | 3.49 | 0.169523E+09 | 449.50 | 04-NOV-12:00 | 20.60 | 16.04 |
December | 0.586507E+09 | 3402.00 | 12-DEC-09:01 | 2.38 | 2.38 | 0.169216E+09 | 360.58 | 02-DEC-13:00 | 12.20 | 5.78 |
Annual Sum or Average | 0.264985E+11 | 0.234819E+10 | ||||||||
Minimum of Months | 0.381261E+09 | 3097.65 | -3.1 | -4.2 | 0.157064E+09 | 340.06 | 2.07 | 1.82 | ||
Maximum of Months | 0.468072E+10 | 19732.45 | 15.10 | 11.62 | 0.230073E+09 | 449.52 | 23.90 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.275311E+09 | 4955.82 | 15-JAN-09:04 | -2.5 | -3.8 | 0.169177E+09 | 340.06 | 21-JAN-13:20 | 2.07 | 1.82 |
February | 0.545068E+09 | 5251.60 | 19-FEB-09:03 | -3.1 | -4.2 | 0.156307E+09 | 373.38 | 27-FEB-17:10 | 18.62 | 12.13 |
March | 0.127254E+10 | 3507.95 | 05-MAR-09:03 | 3.40 | 2.59 | 0.180088E+09 | 420.56 | 18-MAR-12:00 | 17.20 | 10.93 |
April | 0.168169E+10 | 9516.74 | 28-APR-07:03 | 11.28 | 10.33 | 0.186746E+09 | 449.49 | 29-APR-12:00 | 20.00 | 14.69 |
May | 0.230817E+10 | 15906.86 | 07-MAY-08:62 | 17.52 | 14.34 | 0.214831E+09 | 449.52 | 06-MAY-12:00 | 23.90 | 17.57 |
June | 0.296092E+10 | 19157.40 | 29-JUN-07:02 | 12.20 | 11.29 | 0.220456E+09 | 449.50 | 03-JUN-12:20 | 20.60 | 13.15 |
July | 0.394428E+10 | 19322.30 | 19-JUL-07:02 | 15.10 | 11.62 | 0.223765E+09 | 449.52 | 08-JUL-12:09 | 21.70 | 16.35 |
August | 0.444932E+10 | 19386.54 | 01-AUG-07:02 | 11.47 | 11.42 | 0.230019E+09 | 449.51 | 26-AUG-12:30 | 22.20 | 17.28 |
September | 0.301210E+10 | 19491.36 | 16-SEP-07:02 | 10.68 | 10.68 | 0.215670E+09 | 449.51 | 23-SEP-12:20 | 20.73 | 16.68 |
October | 0.205880E+10 | 13855.42 | 05-OCT-07:02 | 9.50 | 6.04 | 0.196395E+09 | 449.49 | 07-OCT-12:20 | 16.47 | 11.91 |
November | 0.907910E+09 | 3958.38 | 11-NOV-09:03 | 0.78 | 0.55 | 0.168186E+09 | 449.49 | 04-NOV-12:20 | 19.47 | 15.47 |
December | 0.446565E+09 | 4249.86 | 25-DEC-09:04 | -0.1 | -0.6 | 0.169050E+09 | 353.84 | 02-DEC-13:00 | 12.20 | 5.78 |
Annual Sum or Average | 0.238627E+11 | 0.233069E+10 | ||||||||
Minimum of Months | 0.275311E+09 | 3507.95 | -3.1 | -4.2 | 0.156307E+09 | 340.06 | 2.07 | 1.82 | ||
Maximum of Months | 0.444932E+10 | 19491.36 | 17.52 | 14.34 | 0.230019E+09 | 449.52 | 23.90 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137146E+09 | 10515.32 | 07-JAN-09:05 | -3.1 | -3.3 | 0.577751E+09 | 906.82 | 14-JAN-15:39 | 4.27 | 0.79 |
February | 0.513543E+09 | 10928.41 | 19-FEB-10:05 | -2.1 | -3.7 | 0.528942E+09 | 972.11 | 27-FEB-15:39 | 19.60 | 12.33 |
March | 0.144660E+10 | 8085.22 | 05-MAR-10:04 | 3.98 | 2.65 | 0.601263E+09 | 1162.32 | 18-MAR-14:00 | 20.00 | 10.31 |
April | 0.247285E+10 | 7631.99 | 18-APR-08:04 | 4.50 | 3.26 | 0.606985E+09 | 1198.67 | 29-APR-14:00 | 22.20 | 15.22 |
May | 0.397744E+10 | 6680.03 | 18-MAY-08:61 | 6.28 | 5.68 | 0.680532E+09 | 1198.67 | 06-MAY-14:00 | 23.90 | 17.26 |
June | 0.445307E+10 | 12496.22 | 28-JUN-08:63 | 17.98 | 13.04 | 0.734086E+09 | 1198.68 | 03-JUN-14:09 | 21.02 | 13.80 |
July | 0.582789E+10 | 25326.23 | 23-JUL-09:02 | 19.27 | 13.96 | 0.762345E+09 | 1198.69 | 01-JUL-14:09 | 20.00 | 14.38 |
August | 0.668513E+10 | 25128.90 | 09-AUG-08:62 | 21.72 | 14.31 | 0.786476E+09 | 1198.66 | 19-AUG-14:39 | 20.37 | 14.51 |
September | 0.479679E+10 | 14609.08 | 14-SEP-08:63 | 15.87 | 14.39 | 0.709780E+09 | 1198.69 | 09-SEP-14:09 | 21.20 | 15.01 |
October | 0.307717E+10 | 6548.40 | 30-OCT-08:02 | 7.30 | 6.71 | 0.630546E+09 | 1198.63 | 07-OCT-14:09 | 17.38 | 12.03 |
November | 0.942855E+09 | 9315.07 | 13-NOV-09:04 | 1.70 | 1.46 | 0.563521E+09 | 1198.66 | 04-NOV-14:00 | 21.10 | 15.92 |
December | 0.273454E+09 | 10437.22 | 26-DEC-09:05 | -0.9 | -0.9 | 0.578828E+09 | 906.82 | 30-DEC-15:30 | 9.15 | 7.35 |
Annual Sum or Average | 0.346039E+11 | 0.776106E+10 | ||||||||
Minimum of Months | 0.137146E+09 | 6548.40 | -3.1 | -3.7 | 0.528942E+09 | 906.82 | 4.27 | 0.79 | ||
Maximum of Months | 0.668513E+10 | 25326.23 | 21.72 | 14.39 | 0.786476E+09 | 1198.69 | 23.90 | 17.26 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111163E+09 | 5267.98 | 07-JAN-09:05 | -3.1 | -3.3 | 0.288812E+09 | 453.41 | 21-JAN-15:09 | 3.30 | 2.80 |
February | 0.278653E+09 | 5004.22 | 19-FEB-10:05 | -2.1 | -3.7 | 0.264789E+09 | 495.94 | 27-FEB-15:50 | 19.50 | 12.37 |
March | 0.744466E+09 | 3448.02 | 05-MAR-10:05 | 3.98 | 2.65 | 0.301224E+09 | 590.75 | 18-MAR-14:00 | 20.00 | 10.31 |
April | 0.110937E+10 | 3314.03 | 18-APR-08:05 | 4.50 | 3.26 | 0.305530E+09 | 599.33 | 29-APR-14:09 | 21.28 | 14.85 |
May | 0.168674E+10 | 3160.62 | 18-MAY-08:04 | 6.28 | 5.68 | 0.343853E+09 | 599.34 | 06-MAY-14:00 | 23.90 | 17.26 |
June | 0.203108E+10 | 3903.59 | 28-JUN-16:20 | 26.30 | 16.42 | 0.369282E+09 | 599.33 | 03-JUN-14:09 | 21.02 | 13.80 |
July | 0.285795E+10 | 11296.67 | 24-JUL-08:62 | 22.07 | 16.25 | 0.381613E+09 | 599.34 | 15-JUL-14:09 | 21.78 | 17.17 |
August | 0.332242E+10 | 10386.55 | 10-AUG-08:62 | 21.25 | 16.85 | 0.393514E+09 | 599.33 | 19-AUG-14:09 | 19.87 | 14.36 |
September | 0.219378E+10 | 4241.09 | 14-SEP-14:10 | 23.90 | 17.08 | 0.357889E+09 | 599.33 | 09-SEP-14:09 | 21.20 | 15.01 |
October | 0.136216E+10 | 2936.91 | 24-OCT-08:04 | 7.30 | 7.30 | 0.317625E+09 | 599.32 | 07-OCT-14:09 | 17.38 | 12.03 |
November | 0.511681E+09 | 4050.92 | 13-NOV-09:05 | 1.70 | 1.46 | 0.282011E+09 | 599.32 | 04-NOV-14:00 | 21.10 | 15.92 |
December | 0.223555E+09 | 4748.36 | 26-DEC-09:05 | -0.9 | -0.9 | 0.289299E+09 | 453.41 | 02-DEC-15:00 | 10.60 | 4.55 |
Annual Sum or Average | 0.164330E+11 | 0.389544E+10 | ||||||||
Minimum of Months | 0.111163E+09 | 2936.91 | -3.1 | -3.7 | 0.264789E+09 | 453.41 | 3.30 | 2.80 | ||
Maximum of Months | 0.332242E+10 | 11296.67 | 26.30 | 17.08 | 0.393514E+09 | 599.34 | 23.90 | 17.26 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 93261507.59 | 5285.20 | 07-JAN-09:05 | -3.1 | -3.3 | 0.288807E+09 | 453.41 | 21-JAN-15:09 | 3.30 | 2.80 |
February | 0.246966E+09 | 5028.96 | 19-FEB-10:05 | -2.1 | -3.7 | 0.264644E+09 | 492.28 | 27-FEB-15:50 | 19.50 | 12.37 |
March | 0.672036E+09 | 3475.24 | 05-MAR-10:05 | 3.98 | 2.65 | 0.300922E+09 | 586.77 | 18-MAR-14:00 | 20.00 | 10.31 |
April | 0.104020E+10 | 3341.99 | 18-APR-08:05 | 4.50 | 3.26 | 0.304503E+09 | 599.33 | 29-APR-14:09 | 21.28 | 14.85 |
May | 0.161033E+10 | 3233.34 | 18-MAY-08:04 | 6.28 | 5.68 | 0.341469E+09 | 599.34 | 06-MAY-14:00 | 23.90 | 17.26 |
June | 0.194434E+10 | 3821.07 | 28-JUN-16:20 | 26.30 | 16.42 | 0.367939E+09 | 599.33 | 03-JUN-14:09 | 21.02 | 13.80 |
July | 0.276247E+10 | 11148.98 | 24-JUL-08:62 | 22.07 | 16.25 | 0.381336E+09 | 599.34 | 15-JUL-14:09 | 21.78 | 17.17 |
August | 0.323229E+10 | 10256.87 | 10-AUG-08:62 | 21.25 | 16.85 | 0.393342E+09 | 599.33 | 19-AUG-14:09 | 19.87 | 14.36 |
September | 0.212815E+10 | 4161.77 | 14-SEP-14:10 | 23.90 | 17.08 | 0.356412E+09 | 599.33 | 09-SEP-14:09 | 21.20 | 15.01 |
October | 0.129354E+10 | 2904.62 | 24-OCT-08:04 | 7.30 | 7.30 | 0.316213E+09 | 599.32 | 07-OCT-14:09 | 17.38 | 12.03 |
November | 0.465477E+09 | 4077.62 | 13-NOV-09:05 | 1.70 | 1.46 | 0.281834E+09 | 599.32 | 04-NOV-14:00 | 21.10 | 15.92 |
December | 0.192754E+09 | 4735.48 | 26-DEC-09:05 | -0.9 | -0.9 | 0.289302E+09 | 453.41 | 02-DEC-15:00 | 10.60 | 4.55 |
Annual Sum or Average | 0.156818E+11 | 0.388672E+10 | ||||||||
Minimum of Months | 93261507.59 | 2904.62 | -3.1 | -3.7 | 0.264644E+09 | 453.41 | 3.30 | 2.80 | ||
Maximum of Months | 0.323229E+10 | 11148.98 | 26.30 | 17.08 | 0.393342E+09 | 599.34 | 23.90 | 17.26 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 54323676.21 | 5262.58 | 07-JAN-09:05 | -3.1 | -3.3 | 0.288812E+09 | 453.41 | 21-JAN-15:09 | 3.30 | 2.80 |
February | 0.178960E+09 | 5054.28 | 19-FEB-10:05 | -2.1 | -3.7 | 0.264369E+09 | 484.34 | 27-FEB-15:50 | 19.50 | 12.37 |
March | 0.504577E+09 | 3513.64 | 05-MAR-10:05 | 3.98 | 2.65 | 0.300402E+09 | 578.15 | 18-MAR-14:00 | 20.00 | 10.31 |
April | 0.882081E+09 | 3378.66 | 18-APR-08:05 | 4.50 | 3.26 | 0.302516E+09 | 599.33 | 29-APR-14:09 | 21.28 | 14.85 |
May | 0.144767E+10 | 3180.64 | 18-MAY-08:04 | 6.28 | 5.68 | 0.336829E+09 | 599.34 | 06-MAY-14:00 | 23.90 | 17.26 |
June | 0.177717E+10 | 3679.20 | 28-JUN-16:50 | 26.60 | 16.64 | 0.364908E+09 | 599.33 | 03-JUN-14:09 | 21.02 | 13.80 |
July | 0.257793E+10 | 10962.28 | 24-JUL-08:62 | 22.07 | 16.25 | 0.380640E+09 | 599.34 | 15-JUL-14:30 | 21.95 | 17.22 |
August | 0.306922E+10 | 10101.41 | 10-AUG-08:62 | 21.25 | 16.85 | 0.392929E+09 | 599.33 | 19-AUG-14:09 | 19.87 | 14.36 |
September | 0.199875E+10 | 4058.56 | 14-SEP-14:10 | 23.90 | 17.08 | 0.353206E+09 | 599.34 | 23-SEP-14:09 | 23.30 | 17.83 |
October | 0.114762E+10 | 2889.55 | 13-OCT-08:04 | 7.30 | 5.78 | 0.313609E+09 | 599.32 | 07-OCT-14:09 | 17.38 | 12.03 |
November | 0.366235E+09 | 4113.30 | 13-NOV-09:05 | 1.70 | 1.46 | 0.281590E+09 | 599.32 | 04-NOV-14:09 | 21.10 | 15.93 |
December | 0.122680E+09 | 4645.46 | 25-DEC-10:05 | -0.3 | -0.3 | 0.289286E+09 | 453.41 | 02-DEC-15:00 | 10.60 | 4.55 |
Annual Sum or Average | 0.141272E+11 | 0.386910E+10 | ||||||||
Minimum of Months | 54323676.21 | 2889.55 | -3.1 | -3.7 | 0.264369E+09 | 453.41 | 3.30 | 2.80 | ||
Maximum of Months | 0.306922E+10 | 10962.28 | 26.60 | 17.08 | 0.392929E+09 | 599.34 | 23.90 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27486179.58 | 4772.84 | 07-JAN-08:05 | -3.8 | -3.8 | 0.288807E+09 | 453.41 | 21-JAN-15:09 | 3.30 | 2.80 |
February | 55239215.27 | 4306.57 | 08-FEB-09:05 | 0.87 | -0.4 | 0.264002E+09 | 467.39 | 27-FEB-15:50 | 19.50 | 12.37 |
March | 0.141517E+09 | 3520.56 | 05-MAR-10:05 | 3.98 | 2.65 | 0.299625E+09 | 557.31 | 18-MAR-14:00 | 20.00 | 10.31 |
April | 0.500704E+09 | 3392.15 | 18-APR-08:05 | 4.50 | 3.26 | 0.299533E+09 | 599.33 | 29-APR-14:50 | 22.02 | 15.15 |
May | 0.107177E+10 | 2902.57 | 18-MAY-08:05 | 6.28 | 5.68 | 0.329516E+09 | 599.34 | 06-MAY-14:00 | 23.90 | 17.26 |
June | 0.151895E+10 | 3491.40 | 28-JUN-15:00 | 26.10 | 15.52 | 0.358787E+09 | 599.33 | 03-JUN-14:09 | 21.02 | 13.80 |
July | 0.230557E+10 | 8587.51 | 24-JUL-08:62 | 22.07 | 16.25 | 0.378467E+09 | 599.34 | 22-JUL-14:09 | 24.60 | 16.62 |
August | 0.285982E+10 | 8626.78 | 10-AUG-08:62 | 21.25 | 16.85 | 0.391466E+09 | 599.33 | 19-AUG-14:09 | 19.87 | 14.36 |
September | 0.177757E+10 | 4026.17 | 14-SEP-14:10 | 23.90 | 17.08 | 0.346782E+09 | 599.34 | 23-SEP-14:09 | 23.30 | 17.83 |
October | 0.824388E+09 | 2851.95 | 12-OCT-08:04 | 7.98 | 7.34 | 0.309329E+09 | 599.32 | 07-OCT-14:00 | 18.30 | 12.36 |
November | 0.162523E+09 | 4114.24 | 13-NOV-09:05 | 1.70 | 1.46 | 0.281199E+09 | 599.32 | 04-NOV-14:09 | 21.10 | 15.93 |
December | 30841944.38 | 4280.88 | 22-DEC-09:05 | 0.78 | -0.7 | 0.289302E+09 | 453.41 | 02-DEC-15:20 | 11.33 | 5.19 |
Annual Sum or Average | 0.112764E+11 | 0.383682E+10 | ||||||||
Minimum of Months | 27486179.58 | 2851.95 | -3.8 | -3.8 | 0.264002E+09 | 453.41 | 3.30 | 2.80 | ||
Maximum of Months | 0.285982E+10 | 8626.78 | 26.10 | 17.08 | 0.391466E+09 | 599.34 | 24.60 | 17.83 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.220856E+10 | 42011.36 | 01-JAN-09:01 | 7.80 |
February | 0.125366E+10 | 43640.75 | 23-FEB-09:01 | 11.20 |
March | 0.393182E+09 | 42294.96 | 07-MAR-09:01 | 9.22 |
April | 0.130727E+09 | 41661.99 | 12-APR-08:61 | 7.07 |
May | 67838652.73 | 2862.97 | 19-MAY-08:04 | 9.18 |
June | 61797382.18 | 729.91 | 11-JUN-07:03 | 12.98 |
July | 60439126.74 | 912.70 | 30-JUL-07:05 | 16.97 |
August | 60507304.85 | 1042.15 | 13-AUG-07:05 | 18.17 |
September | 60544053.56 | 936.37 | 03-SEP-07:03 | 13.40 |
October | 75526726.21 | 11588.79 | 28-OCT-08:61 | 8.07 |
November | 0.642297E+09 | 41786.81 | 17-NOV-09:01 | 7.38 |
December | 0.163171E+10 | 43385.43 | 16-DEC-09:01 | 10.78 |
Annual Sum or Average | 0.664679E+10 | |||
Minimum of Months | 60439126.74 | 729.91 | 7.07 | |
Maximum of Months | 0.220856E+10 | 43640.75 | 18.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.623128E+09 | 23313.70 | 11-JAN-09:01 | 10.10 |
February | 0.354913E+09 | 23597.54 | 23-FEB-09:01 | 11.20 |
March | 86095457.88 | 23156.85 | 07-MAR-09:01 | 9.22 |
April | 31593869.31 | 23632.42 | 01-APR-08:61 | 11.57 |
May | 1328201.78 | 14313.32 | 18-MAY-08:61 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 182607.82 | 619.22 | 31-JUL-08:05 | 21.28 |
August | 645835.41 | 796.46 | 09-AUG-08:05 | 21.72 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 9221853.35 | 18434.81 | 28-OCT-08:61 | 8.07 |
November | 0.146615E+09 | 23269.70 | 18-NOV-09:01 | 10.10 |
December | 0.466632E+09 | 23462.42 | 16-DEC-09:01 | 10.78 |
Annual Sum or Average | 0.172036E+10 | |||
Minimum of Months | 0.00 | 0.00 | 6.28 | |
Maximum of Months | 0.623128E+09 | 23632.42 | 21.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.888777E+09 | 23838.42 | 17-JAN-08:61 | 1.70 |
February | 0.484796E+09 | 24045.72 | 20-FEB-09:01 | 1.47 |
March | 0.143029E+09 | 3262.52 | 30-MAR-07:30 | 5.85 |
April | 0.110596E+09 | 3345.96 | 19-APR-07:40 | 5.03 |
May | 0.107941E+09 | 1058.66 | 28-MAY-07:13 | 8.30 |
June | 0.104964E+09 | 1043.41 | 18-JUN-07:01 | 11.28 |
July | 0.121433E+09 | 1594.35 | 30-JUL-16:12 | 27.43 |
August | 0.130024E+09 | 1932.00 | 10-AUG-19:03 | 29.18 |
September | 0.105175E+09 | 1047.56 | 17-SEP-07:01 | 11.10 |
October | 0.108550E+09 | 1063.46 | 29-OCT-07:13 | 6.70 |
November | 0.282386E+09 | 3550.28 | 26-NOV-09:01 | 4.50 |
December | 0.651549E+09 | 23511.06 | 25-DEC-09:01 | -0.1 |
Annual Sum or Average | 0.323922E+10 | |||
Minimum of Months | 0.104964E+09 | 1043.41 | -0.1 | |
Maximum of Months | 0.888777E+09 | 24045.72 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104566E+10 | 25195.48 | 01-JAN-09:01 | 7.80 |
February | 0.554218E+09 | 24035.58 | 20-FEB-09:01 | 1.47 |
March | 0.160731E+09 | 8625.31 | 05-MAR-09:01 | 3.40 |
April | 0.111867E+09 | 3812.49 | 18-APR-07:30 | 4.15 |
May | 0.107582E+09 | 1055.18 | 28-MAY-07:13 | 8.30 |
June | 0.104583E+09 | 1039.41 | 18-JUN-07:01 | 11.28 |
July | 0.120913E+09 | 1591.92 | 30-JUL-16:12 | 27.43 |
August | 0.129484E+09 | 1930.82 | 10-AUG-19:03 | 29.18 |
September | 0.104764E+09 | 1043.52 | 17-SEP-07:01 | 11.10 |
October | 0.108232E+09 | 1059.00 | 29-OCT-07:13 | 6.70 |
November | 0.337968E+09 | 9502.53 | 26-NOV-09:01 | 4.50 |
December | 0.759975E+09 | 23500.17 | 25-DEC-09:01 | -0.1 |
Annual Sum or Average | 0.364598E+10 | |||
Minimum of Months | 0.104583E+09 | 1039.41 | -0.1 | |
Maximum of Months | 0.104566E+10 | 25195.48 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130144E+10 | 25160.25 | 01-JAN-09:01 | 7.80 |
February | 0.692926E+09 | 23984.29 | 20-FEB-09:01 | 1.47 |
March | 0.207286E+09 | 15022.44 | 05-MAR-09:01 | 3.40 |
April | 0.115611E+09 | 1789.40 | 20-APR-07:06 | 6.05 |
May | 0.107477E+09 | 1050.50 | 28-MAY-07:13 | 8.30 |
June | 0.104596E+09 | 1033.34 | 18-JUN-07:01 | 11.28 |
July | 0.120961E+09 | 1593.15 | 30-JUL-16:12 | 27.43 |
August | 0.129747E+09 | 1936.83 | 10-AUG-19:03 | 29.18 |
September | 0.104499E+09 | 1037.45 | 17-SEP-07:01 | 11.10 |
October | 0.109179E+09 | 1277.44 | 30-OCT-07:17 | 7.20 |
November | 0.439873E+09 | 15843.05 | 26-NOV-09:01 | 4.50 |
December | 0.961351E+09 | 23449.22 | 25-DEC-09:01 | -0.1 |
Annual Sum or Average | 0.439495E+10 | |||
Minimum of Months | 0.104499E+09 | 1033.34 | -0.1 | |
Maximum of Months | 0.130144E+10 | 25160.25 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324070E+10 | 46575.03 | 16-JAN-09:01 | -0.5 |
February | 0.180669E+10 | 46541.60 | 19-FEB-09:01 | -3.1 |
March | 0.640231E+09 | 42674.02 | 08-MAR-09:01 | 12.48 |
April | 0.197635E+09 | 42285.44 | 01-APR-08:61 | 11.57 |
May | 68555280.01 | 2393.44 | 27-MAY-08:05 | 8.48 |
June | 63177598.49 | 636.65 | 29-JUN-07:13 | 12.20 |
July | 74449645.73 | 2132.66 | 30-JUL-16:03 | 27.62 |
August | 70712440.24 | 2322.71 | 13-AUG-16:03 | 28.08 |
September | 65275187.66 | 1200.24 | 28-SEP-08:07 | 10.28 |
October | 0.121567E+09 | 38159.96 | 30-OCT-08:61 | 7.30 |
November | 0.119105E+10 | 41958.32 | 27-NOV-09:01 | 10.60 |
December | 0.248065E+10 | 41999.62 | 16-DEC-09:01 | 10.78 |
Annual Sum or Average | 0.100207E+11 | |||
Minimum of Months | 63177598.49 | 636.65 | -3.1 | |
Maximum of Months | 0.324070E+10 | 46575.03 | 28.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198149E+10 | 21332.56 | 11-JAN-09:01 | 10.10 |
February | 0.116231E+10 | 22028.04 | 24-FEB-09:01 | 13.90 |
March | 0.527741E+09 | 21791.68 | 08-MAR-09:01 | 12.48 |
April | 0.190207E+09 | 21620.49 | 01-APR-08:61 | 11.57 |
May | 40830559.28 | 21412.12 | 30-MAY-08:61 | 12.38 |
June | 1189947.31 | 1434.29 | 15-JUN-08:62 | 11.97 |
July | 10251912.43 | 1466.60 | 30-JUL-16:03 | 27.62 |
August | 6938371.08 | 1549.17 | 13-AUG-16:03 | 28.08 |
September | 4061904.61 | 20887.59 | 28-SEP-08:61 | 10.28 |
October | 0.113789E+09 | 21487.99 | 31-OCT-08:61 | 11.70 |
November | 0.839439E+09 | 21599.55 | 01-NOV-08:61 | 12.30 |
December | 0.158601E+10 | 21474.70 | 16-DEC-09:01 | 10.78 |
Annual Sum or Average | 0.646426E+10 | |||
Minimum of Months | 1189947.31 | 1434.29 | 10.10 | |
Maximum of Months | 0.198149E+10 | 22028.04 | 28.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205835E+10 | 21119.57 | 11-JAN-09:01 | 10.10 |
February | 0.122565E+10 | 21813.35 | 24-FEB-09:01 | 13.90 |
March | 0.577278E+09 | 21582.66 | 08-MAR-09:01 | 12.48 |
April | 0.221564E+09 | 21411.93 | 01-APR-08:61 | 11.57 |
May | 50671500.00 | 21218.58 | 30-MAY-08:61 | 12.38 |
June | 1638781.46 | 3851.37 | 15-JUN-08:62 | 11.97 |
July | 10248111.73 | 1464.55 | 30-JUL-16:03 | 27.62 |
August | 6869874.24 | 1547.14 | 13-AUG-16:03 | 28.08 |
September | 4873651.00 | 20688.51 | 28-SEP-08:61 | 10.28 |
October | 0.139173E+09 | 21278.38 | 31-OCT-08:61 | 11.70 |
November | 0.892292E+09 | 21388.57 | 01-NOV-08:61 | 12.30 |
December | 0.165442E+10 | 21262.11 | 16-DEC-09:01 | 10.78 |
Annual Sum or Average | 0.684302E+10 | |||
Minimum of Months | 1638781.46 | 1464.55 | 10.10 | |
Maximum of Months | 0.205835E+10 | 21813.35 | 28.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233536E+10 | 20829.10 | 11-JAN-09:01 | 10.10 |
February | 0.144149E+10 | 21559.58 | 24-FEB-09:01 | 13.90 |
March | 0.710782E+09 | 21338.88 | 08-MAR-09:01 | 12.48 |
April | 0.291962E+09 | 21170.27 | 01-APR-08:61 | 11.57 |
May | 77282799.25 | 20990.19 | 30-MAY-08:61 | 12.38 |
June | 4051897.72 | 9887.44 | 15-JUN-08:62 | 11.97 |
July | 10506240.24 | 1466.39 | 30-JUL-16:03 | 27.62 |
August | 6862038.57 | 1547.58 | 13-AUG-16:03 | 28.08 |
September | 7329496.90 | 20452.94 | 28-SEP-08:61 | 10.28 |
October | 0.186823E+09 | 21027.92 | 31-OCT-08:61 | 11.70 |
November | 0.103112E+10 | 21137.31 | 01-NOV-08:61 | 12.30 |
December | 0.186991E+10 | 20979.40 | 16-DEC-09:01 | 10.78 |
Annual Sum or Average | 0.797347E+10 | |||
Minimum of Months | 4051897.72 | 1466.39 | 10.10 | |
Maximum of Months | 0.233536E+10 | 21559.58 | 28.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371085E+10 | 21008.95 | 11-JAN-09:01 | 10.10 |
February | 0.246017E+10 | 21864.97 | 24-FEB-09:01 | 13.90 |
March | 0.140808E+10 | 21578.73 | 08-MAR-09:01 | 12.48 |
April | 0.616059E+09 | 21457.64 | 23-APR-09:01 | 12.07 |
May | 0.183395E+09 | 21327.94 | 30-MAY-08:61 | 12.38 |
June | 20135497.90 | 20740.85 | 15-JUN-08:62 | 11.97 |
July | 10853040.10 | 1484.67 | 30-JUL-16:03 | 27.62 |
August | 7012734.90 | 1557.54 | 13-AUG-16:03 | 28.08 |
September | 22916704.66 | 20768.35 | 28-SEP-08:61 | 10.28 |
October | 0.393087E+09 | 21345.94 | 31-OCT-08:61 | 11.70 |
November | 0.165553E+10 | 21448.91 | 01-NOV-08:61 | 12.30 |
December | 0.296026E+10 | 21160.40 | 16-DEC-09:01 | 10.78 |
Annual Sum or Average | 0.134483E+11 | |||
Minimum of Months | 7012734.90 | 1484.67 | 10.10 | |
Maximum of Months | 0.371085E+10 | 21864.97 | 28.08 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.861445E+10 | 5225.88 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.779459E+10 | 5225.88 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.863227E+10 | 5225.88 | 01-MAR-10:09 | 0.223972E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.835898E+10 | 5225.88 | 01-APR-09:09 | 0.216880E+10 | 1348.26 | 01-APR-09:09 |
May | 0.861445E+10 | 5225.88 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.835898E+10 | 5225.88 | 01-JUN-09:09 | 0.216880E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.863227E+10 | 5225.88 | 01-JUL-09:09 | 0.223972E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.861445E+10 | 5225.88 | 01-AUG-09:09 | 0.223514E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.837681E+10 | 5225.88 | 01-SEP-09:09 | 0.217339E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.861445E+10 | 5225.88 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.832334E+10 | 5225.88 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.865009E+10 | 5225.88 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.101585E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.779459E+10 | 5225.88 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.865009E+10 | 5225.88 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.509120E+10 | 3088.53 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.460666E+10 | 3088.53 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.510174E+10 | 3088.53 | 01-MAR-10:09 | 0.111986E+10 | 674.13 | 01-MAR-10:09 |
April | 0.494022E+10 | 3088.53 | 01-APR-09:09 | 0.108440E+10 | 674.13 | 01-APR-09:09 |
May | 0.509120E+10 | 3088.53 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.494022E+10 | 3088.53 | 01-JUN-09:09 | 0.108440E+10 | 674.13 | 01-JUN-09:09 |
July | 0.510174E+10 | 3088.53 | 01-JUL-09:09 | 0.111986E+10 | 674.13 | 01-JUL-09:09 |
August | 0.509120E+10 | 3088.53 | 01-AUG-09:09 | 0.111757E+10 | 674.13 | 01-AUG-09:09 |
September | 0.495076E+10 | 3088.53 | 01-SEP-09:09 | 0.108669E+10 | 674.13 | 01-SEP-09:09 |
October | 0.509120E+10 | 3088.53 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.491916E+10 | 3088.53 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.511227E+10 | 3088.53 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.600376E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.460666E+10 | 3088.53 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.511227E+10 | 3088.53 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.366929E+10 | 2821.35 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.332289E+10 | 2821.35 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.374627E+10 | 2821.35 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.356024E+10 | 2821.35 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.370778E+10 | 2821.35 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.361797E+10 | 2821.35 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.365005E+10 | 2821.35 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.374627E+10 | 2821.35 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.356024E+10 | 2821.35 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.366929E+10 | 2821.35 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.356024E+10 | 2821.35 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.365005E+10 | 2821.35 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.434606E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.332289E+10 | 2821.35 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.374627E+10 | 2821.35 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.366929E+10 | 2821.35 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.332289E+10 | 2821.35 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.374627E+10 | 2821.35 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.356024E+10 | 2821.35 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.370778E+10 | 2821.35 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.361797E+10 | 2821.35 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.365005E+10 | 2821.35 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.374627E+10 | 2821.35 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.356024E+10 | 2821.35 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.366929E+10 | 2821.35 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.356024E+10 | 2821.35 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.365005E+10 | 2821.35 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.434606E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.332289E+10 | 2821.35 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.374627E+10 | 2821.35 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.366929E+10 | 2821.35 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.332289E+10 | 2821.35 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.374627E+10 | 2821.35 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.356024E+10 | 2821.35 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.370778E+10 | 2821.35 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.361797E+10 | 2821.35 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.365005E+10 | 2821.35 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.374627E+10 | 2821.35 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.356024E+10 | 2821.35 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.366929E+10 | 2821.35 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.356024E+10 | 2821.35 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.365005E+10 | 2821.35 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.434606E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.332289E+10 | 2821.35 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.374627E+10 | 2821.35 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.399227E+10 | 3341.31 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.361622E+10 | 3341.31 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.408344E+10 | 3341.31 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.387452E+10 | 3341.31 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.403786E+10 | 3341.31 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.394289E+10 | 3341.31 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.396948E+10 | 3341.31 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.408344E+10 | 3341.31 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.387452E+10 | 3341.31 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.399227E+10 | 3341.31 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.387452E+10 | 3341.31 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.396948E+10 | 3341.31 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.473109E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.361622E+10 | 3341.31 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.408344E+10 | 3341.31 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.199614E+10 | 1670.66 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.180811E+10 | 1670.66 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.204172E+10 | 1670.66 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.193726E+10 | 1670.66 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.201893E+10 | 1670.66 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.197145E+10 | 1670.66 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.198474E+10 | 1670.66 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.204172E+10 | 1670.66 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.193726E+10 | 1670.66 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.199614E+10 | 1670.66 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.193726E+10 | 1670.66 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.198474E+10 | 1670.66 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.236555E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.180811E+10 | 1670.66 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.204172E+10 | 1670.66 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.199614E+10 | 1670.66 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.180811E+10 | 1670.66 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.204172E+10 | 1670.66 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.193726E+10 | 1670.66 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.201893E+10 | 1670.66 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.197145E+10 | 1670.66 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.198474E+10 | 1670.66 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.204172E+10 | 1670.66 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.193726E+10 | 1670.66 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.199614E+10 | 1670.66 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.193726E+10 | 1670.66 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.198474E+10 | 1670.66 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.236555E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.180811E+10 | 1670.66 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.204172E+10 | 1670.66 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.199614E+10 | 1670.66 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.180811E+10 | 1670.66 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.204172E+10 | 1670.66 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.193726E+10 | 1670.66 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.201893E+10 | 1670.66 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.197145E+10 | 1670.66 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.198474E+10 | 1670.66 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.204172E+10 | 1670.66 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.193726E+10 | 1670.66 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.199614E+10 | 1670.66 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.193726E+10 | 1670.66 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.198474E+10 | 1670.66 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.236555E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.180811E+10 | 1670.66 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.204172E+10 | 1670.66 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.199614E+10 | 1670.66 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.180811E+10 | 1670.66 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.204172E+10 | 1670.66 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.193726E+10 | 1670.66 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.201893E+10 | 1670.66 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.197145E+10 | 1670.66 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.198474E+10 | 1670.66 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.204172E+10 | 1670.66 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.193726E+10 | 1670.66 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.199614E+10 | 1670.66 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.193726E+10 | 1670.66 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.198474E+10 | 1670.66 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.236555E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.180811E+10 | 1670.66 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.204172E+10 | 1670.66 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.180574E+10 | 0.861445E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451189E+10 |
February | 0.163016E+10 | 0.779459E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359350E+10 |
March | 0.178954E+10 | 0.863227E+10 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322200E+10 |
April | 0.174484E+10 | 0.835898E+10 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24412231.93 | 0.249377E+10 |
May | 0.179537E+10 | 0.861445E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2655508.37 | 0.211652E+10 |
June | 0.173447E+10 | 0.835898E+10 | 0.216880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13757852.54 | 0.163987E+10 |
July | 0.181028E+10 | 0.863227E+10 | 0.223972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130284E+09 | 0.114523E+10 |
August | 0.178501E+10 | 0.861445E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279132E+09 | 0.950920E+09 |
September | 0.174937E+10 | 0.837681E+10 | 0.217339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3247405.13 | 0.154032E+10 |
October | 0.180574E+10 | 0.861445E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259237E+10 |
November | 0.174613E+10 | 0.832334E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351320E+10 |
December | 0.181481E+10 | 0.865009E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412137E+10 |
Annual Sum or Average | 0.212115E+11 | 0.101585E+12 | 0.263573E+11 | 0.453489E+09 | 0.314410E+11 | ||||
Minimum of Months | 0.163016E+10 | 0.779459E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.950920E+09 |
Maximum of Months | 0.181481E+10 | 0.865009E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279132E+09 | 0.451189E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.902868E+09 | 0.509120E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226367E+10 |
February | 0.815075E+09 | 0.460666E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180682E+10 |
March | 0.894769E+09 | 0.510174E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163713E+10 |
April | 0.872416E+09 | 0.494022E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13254036.44 | 0.128155E+10 |
May | 0.897684E+09 | 0.509120E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1457501.38 | 0.110732E+10 |
June | 0.867232E+09 | 0.494022E+10 | 0.108440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7471082.81 | 0.790424E+09 |
July | 0.905135E+09 | 0.510174E+10 | 0.111986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70624424.28 | 0.523856E+09 |
August | 0.892501E+09 | 0.509120E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151737E+09 | 0.423582E+09 |
September | 0.874683E+09 | 0.495076E+10 | 0.108669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1787707.91 | 0.811360E+09 |
October | 0.902868E+09 | 0.509120E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135205E+10 |
November | 0.873064E+09 | 0.491916E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178145E+10 |
December | 0.907403E+09 | 0.511227E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209464E+10 |
Annual Sum or Average | 0.106057E+11 | 0.600376E+11 | 0.131787E+11 | 0.246332E+09 | 0.158739E+11 | ||||
Minimum of Months | 0.815075E+09 | 0.460666E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423582E+09 |
Maximum of Months | 0.907403E+09 | 0.511227E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151737E+09 | 0.226367E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232905E+10 |
February | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185867E+10 |
March | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167781E+10 |
April | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13102612.28 | 0.132754E+10 |
May | 0.544247E+09 | 0.370778E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1457171.31 | 0.115987E+10 |
June | 0.532585E+09 | 0.361797E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7470458.50 | 0.831746E+09 |
July | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67167256.66 | 0.563089E+09 |
August | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149751E+09 | 0.455787E+09 |
September | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1787293.89 | 0.842956E+09 |
October | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139134E+10 |
November | 0.518979E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181855E+10 |
December | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215070E+10 |
Annual Sum or Average | 0.638324E+10 | 0.434606E+11 | 0.104672E+11 | 0.240735E+09 | 0.164071E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455787E+09 |
Maximum of Months | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149751E+09 | 0.232905E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232347E+10 |
February | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185138E+10 |
March | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166485E+10 |
April | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13107099.25 | 0.131147E+10 |
May | 0.544247E+09 | 0.370778E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1457157.89 | 0.115090E+10 |
June | 0.532585E+09 | 0.361797E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7470456.89 | 0.829897E+09 |
July | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67170419.38 | 0.562538E+09 |
August | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149751E+09 | 0.455481E+09 |
September | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1787292.97 | 0.840841E+09 |
October | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137449E+10 |
November | 0.518979E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180890E+10 |
December | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214578E+10 |
Annual Sum or Average | 0.638324E+10 | 0.434606E+11 | 0.104672E+11 | 0.240744E+09 | 0.163200E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455481E+09 |
Maximum of Months | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149751E+09 | 0.232347E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231838E+10 |
February | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184287E+10 |
March | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164651E+10 |
April | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13119339.66 | 0.128349E+10 |
May | 0.544247E+09 | 0.370778E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1457055.28 | 0.112132E+10 |
June | 0.532585E+09 | 0.361797E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7470432.68 | 0.822059E+09 |
July | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67205845.46 | 0.559672E+09 |
August | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149777E+09 | 0.453005E+09 |
September | 0.524810E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1787175.92 | 0.830997E+09 |
October | 0.537120E+09 | 0.366929E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134323E+10 |
November | 0.518979E+09 | 0.356024E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179566E+10 |
December | 0.536472E+09 | 0.365005E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214099E+10 |
Annual Sum or Average | 0.638324E+10 | 0.434606E+11 | 0.104672E+11 | 0.240817E+09 | 0.161582E+11 | ||||
Minimum of Months | 0.487879E+09 | 0.332289E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453005E+09 |
Maximum of Months | 0.551374E+09 | 0.374627E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149777E+09 | 0.231838E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.183632E+10 | 0.399227E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422557E+10 |
February | 0.167188E+10 | 0.361622E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334520E+10 |
March | 0.189386E+10 | 0.408344E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296125E+10 |
April | 0.180380E+10 | 0.387452E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23796501.65 | 0.223850E+10 |
May | 0.186509E+10 | 0.403786E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2618506.87 | 0.187029E+10 |
June | 0.182945E+10 | 0.394289E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13441070.50 | 0.144780E+10 |
July | 0.183943E+10 | 0.396948E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121751E+09 | 0.102587E+10 |
August | 0.189386E+10 | 0.408344E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270027E+09 | 0.839642E+09 |
September | 0.180380E+10 | 0.387452E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3211608.14 | 0.141392E+10 |
October | 0.183632E+10 | 0.399227E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232885E+10 |
November | 0.176881E+10 | 0.387452E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324503E+10 |
December | 0.183943E+10 | 0.396948E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389401E+10 |
Annual Sum or Average | 0.218821E+11 | 0.473109E+11 | 0.192612E+11 | 0.434846E+09 | 0.288359E+11 | ||||
Minimum of Months | 0.167188E+10 | 0.361622E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839642E+09 |
Maximum of Months | 0.189386E+10 | 0.408344E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270027E+09 | 0.422557E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231332E+10 |
February | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182916E+10 |
March | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161403E+10 |
April | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13215014.48 | 0.121948E+10 |
May | 0.932542E+09 | 0.201893E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1457352.27 | 0.102464E+10 |
June | 0.914724E+09 | 0.197145E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7471502.71 | 0.787950E+09 |
July | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67540223.67 | 0.551329E+09 |
August | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150048E+09 | 0.448566E+09 |
September | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1787630.07 | 0.783097E+09 |
October | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127376E+10 |
November | 0.884402E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177391E+10 |
December | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213389E+10 |
Annual Sum or Average | 0.109410E+11 | 0.236555E+11 | 0.963059E+10 | 0.241519E+09 | 0.157531E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448566E+09 |
Maximum of Months | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150048E+09 | 0.231332E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231192E+10 |
February | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182723E+10 |
March | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161104E+10 |
April | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13225215.03 | 0.121318E+10 |
May | 0.932542E+09 | 0.201893E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1457298.08 | 0.101354E+10 |
June | 0.914724E+09 | 0.197145E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7471469.72 | 0.781298E+09 |
July | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67573163.23 | 0.548983E+09 |
August | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150065E+09 | 0.446910E+09 |
September | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1787588.86 | 0.776741E+09 |
October | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126640E+10 |
November | 0.884402E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177148E+10 |
December | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213262E+10 |
Annual Sum or Average | 0.109410E+11 | 0.236555E+11 | 0.963059E+10 | 0.241580E+09 | 0.157013E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446910E+09 |
Maximum of Months | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150065E+09 | 0.231192E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230706E+10 |
February | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182177E+10 |
March | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160385E+10 |
April | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13251822.65 | 0.119982E+10 |
May | 0.932542E+09 | 0.201893E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1457192.64 | 0.990872E+09 |
June | 0.914724E+09 | 0.197145E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7471413.83 | 0.765819E+09 |
July | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67636448.21 | 0.543090E+09 |
August | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150092E+09 | 0.442907E+09 |
September | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1787506.88 | 0.762550E+09 |
October | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125181E+10 |
November | 0.884402E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176605E+10 |
December | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212854E+10 |
Annual Sum or Average | 0.109410E+11 | 0.236555E+11 | 0.963059E+10 | 0.241697E+09 | 0.155841E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442907E+09 |
Maximum of Months | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150092E+09 | 0.230706E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277437E+10 |
February | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221577E+10 |
March | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198479E+10 |
April | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13956546.54 | 0.153390E+10 |
May | 0.932542E+09 | 0.201893E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1494301.91 | 0.124600E+10 |
June | 0.914724E+09 | 0.197145E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7788855.55 | 0.994170E+09 |
July | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70700038.15 | 0.743492E+09 |
August | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156177E+09 | 0.628746E+09 |
September | 0.901896E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1822578.44 | 0.883253E+09 |
October | 0.918158E+09 | 0.199614E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155314E+10 |
November | 0.884402E+09 | 0.193726E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212935E+10 |
December | 0.919713E+09 | 0.198474E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251998E+10 |
Annual Sum or Average | 0.109410E+11 | 0.236555E+11 | 0.963059E+10 | 0.251940E+09 | 0.192070E+11 | ||||
Minimum of Months | 0.835938E+09 | 0.180811E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628746E+09 |
Maximum of Months | 0.946926E+09 | 0.204172E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156177E+09 | 0.277437E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2159.72 | 01-JAN-13:09 | 5225.88 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 6852.95 | 07-JAN-12:10 |
February | 2159.72 | 03-FEB-13:09 | 5225.88 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 7083.33 | 18-FEB-18:00 |
March | 2159.72 | 03-MAR-13:09 | 5225.88 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5125.45 | 22-MAR-11:10 |
April | 2159.72 | 01-APR-12:09 | 5225.88 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 997.68 | 01-APR-16:00 | 4441.26 | 18-APR-17:00 |
May | 2159.72 | 05-MAY-12:09 | 5225.88 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 321.63 | 05-MAY-16:00 | 3998.69 | 23-MAY-17:00 |
June | 2159.72 | 02-JUN-12:09 | 5225.88 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 818.47 | 28-JUN-17:00 | 3523.12 | 13-JUN-14:00 |
July | 2159.72 | 01-JUL-12:09 | 5225.88 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1924.89 | 24-JUL-15:00 | 2984.02 | 09-JUL-13:00 |
August | 2159.72 | 04-AUG-12:09 | 5225.88 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2237.47 | 10-AUG-17:00 | 3050.42 | 01-AUG-11:10 |
September | 2159.72 | 01-SEP-12:09 | 5225.88 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 324.11 | 14-SEP-17:00 | 3380.05 | 16-SEP-11:10 |
October | 2159.72 | 01-OCT-12:09 | 5225.88 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3847.10 | 31-OCT-17:00 |
November | 2159.72 | 03-NOV-12:09 | 5225.88 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5654.11 | 12-NOV-17:00 |
December | 2159.72 | 01-DEC-13:09 | 5225.88 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6750.87 | 26-DEC-13:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2159.72 | 5225.88 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2984.02 | |||||
Maximum of Months | 2159.72 | 5225.88 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2237.47 | 7083.33 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 01-JAN-13:09 | 3088.53 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3789.48 | 07-JAN-12:10 |
February | 1079.86 | 03-FEB-13:09 | 3088.53 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3841.04 | 18-FEB-18:00 |
March | 1079.86 | 03-MAR-13:09 | 3088.53 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2780.44 | 22-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 3088.53 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 537.22 | 01-APR-16:00 | 2414.05 | 18-APR-17:00 |
May | 1079.86 | 05-MAY-12:09 | 3088.53 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.06 | 05-MAY-16:00 | 2368.73 | 23-MAY-17:00 |
June | 1079.86 | 02-JUN-12:09 | 3088.53 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.40 | 28-JUN-17:00 | 2059.36 | 13-JUN-14:00 |
July | 1079.86 | 01-JUL-12:09 | 3088.53 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.93 | 24-JUL-15:00 | 1677.86 | 09-JUL-13:00 |
August | 1079.86 | 04-AUG-12:09 | 3088.53 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.60 | 10-AUG-17:00 | 1735.18 | 01-AUG-11:10 |
September | 1079.86 | 01-SEP-12:09 | 3088.53 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.92 | 14-SEP-17:00 | 2003.02 | 16-SEP-11:10 |
October | 1079.86 | 01-OCT-12:09 | 3088.53 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2049.81 | 27-OCT-16:00 |
November | 1079.86 | 03-NOV-12:09 | 3088.53 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3112.32 | 12-NOV-17:00 |
December | 1079.86 | 01-DEC-13:09 | 3088.53 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3698.86 | 26-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 3088.53 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.86 | |||||
Maximum of Months | 1079.86 | 3088.53 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.60 | 3841.04 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2821.35 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3789.48 | 07-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 2821.35 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3841.04 | 18-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 2821.35 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2780.44 | 22-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 2821.35 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 537.21 | 01-APR-16:00 | 2414.04 | 18-APR-17:00 |
May | 1079.86 | 06-MAY-12:09 | 2821.35 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.04 | 05-MAY-16:00 | 2385.11 | 23-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 2821.35 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.40 | 28-JUN-17:00 | 2084.23 | 13-JUN-11:10 |
July | 1079.86 | 01-JUL-12:09 | 2821.35 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.93 | 24-JUL-15:00 | 1677.83 | 09-JUL-13:00 |
August | 1079.86 | 05-AUG-12:09 | 2821.35 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.59 | 10-AUG-17:00 | 1742.92 | 01-AUG-11:10 |
September | 1079.86 | 02-SEP-12:09 | 2821.35 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.90 | 14-SEP-17:00 | 2018.10 | 16-SEP-11:10 |
October | 1079.86 | 07-OCT-12:09 | 2821.35 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2053.64 | 27-OCT-16:00 |
November | 1079.86 | 04-NOV-12:09 | 2821.35 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3112.31 | 12-NOV-17:00 |
December | 1079.86 | 02-DEC-13:09 | 2821.35 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3698.86 | 26-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.83 | |||||
Maximum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.59 | 3841.04 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2821.35 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3789.48 | 07-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 2821.35 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3841.04 | 18-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 2821.35 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2780.44 | 22-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 2821.35 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 537.21 | 01-APR-16:00 | 2414.04 | 18-APR-17:00 |
May | 1079.86 | 06-MAY-12:09 | 2821.35 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.04 | 05-MAY-16:00 | 2365.08 | 23-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 2821.35 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.40 | 28-JUN-17:00 | 2081.43 | 13-JUN-11:10 |
July | 1079.86 | 01-JUL-12:09 | 2821.35 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.93 | 24-JUL-15:00 | 1677.83 | 09-JUL-13:00 |
August | 1079.86 | 05-AUG-12:09 | 2821.35 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.59 | 10-AUG-17:00 | 1742.92 | 01-AUG-11:10 |
September | 1079.86 | 02-SEP-12:09 | 2821.35 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.90 | 14-SEP-17:00 | 2018.27 | 16-SEP-11:10 |
October | 1079.86 | 07-OCT-12:09 | 2821.35 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2042.84 | 31-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 2821.35 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3112.31 | 12-NOV-17:00 |
December | 1079.86 | 02-DEC-13:09 | 2821.35 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3698.86 | 26-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.83 | |||||
Maximum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.59 | 3841.04 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1079.86 | 07-JAN-13:09 | 2821.35 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3789.48 | 07-JAN-12:10 |
February | 1079.86 | 04-FEB-13:09 | 2821.35 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3841.04 | 18-FEB-18:00 |
March | 1079.86 | 04-MAR-13:09 | 2821.35 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2780.44 | 22-MAR-11:10 |
April | 1079.86 | 01-APR-12:09 | 2821.35 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 537.21 | 01-APR-16:00 | 2414.04 | 18-APR-17:00 |
May | 1079.86 | 06-MAY-12:09 | 2821.35 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.04 | 05-MAY-16:00 | 2300.78 | 23-MAY-17:00 |
June | 1079.86 | 03-JUN-12:09 | 2821.35 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.40 | 28-JUN-17:00 | 2048.74 | 13-JUN-11:10 |
July | 1079.86 | 01-JUL-12:09 | 2821.35 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.93 | 24-JUL-15:00 | 1677.83 | 09-JUL-13:00 |
August | 1079.86 | 05-AUG-12:09 | 2821.35 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.59 | 10-AUG-17:00 | 1738.10 | 01-AUG-11:10 |
September | 1079.86 | 02-SEP-12:09 | 2821.35 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.90 | 14-SEP-17:00 | 2010.33 | 16-SEP-11:10 |
October | 1079.86 | 07-OCT-12:09 | 2821.35 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2042.84 | 31-OCT-17:00 |
November | 1079.86 | 04-NOV-12:09 | 2821.35 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3112.31 | 12-NOV-17:00 |
December | 1079.86 | 02-DEC-13:09 | 2821.35 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3698.86 | 26-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.83 | |||||
Maximum of Months | 1079.86 | 2821.35 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.59 | 3841.04 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2879.63 | 07-JAN-15:09 | 3341.31 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 6801.58 | 07-JAN-12:10 |
February | 2879.63 | 04-FEB-15:09 | 3341.31 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6910.84 | 18-FEB-18:00 |
March | 2879.63 | 04-MAR-15:09 | 3341.31 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5002.36 | 22-MAR-11:10 |
April | 2879.63 | 01-APR-14:09 | 3341.31 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 967.48 | 01-APR-16:00 | 4342.09 | 18-APR-17:00 |
May | 2879.63 | 06-MAY-14:09 | 3341.31 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 317.94 | 05-MAY-16:00 | 3927.22 | 23-MAY-17:00 |
June | 2879.63 | 03-JUN-14:09 | 3341.31 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 807.36 | 28-JUN-17:00 | 3360.29 | 13-JUN-11:10 |
July | 2879.63 | 01-JUL-14:09 | 3341.31 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1898.78 | 24-JUL-15:00 | 2806.90 | 09-JUL-13:00 |
August | 2879.63 | 05-AUG-14:09 | 3341.31 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2211.86 | 10-AUG-17:00 | 2964.02 | 01-AUG-11:10 |
September | 2879.63 | 02-SEP-14:09 | 3341.31 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 319.68 | 14-SEP-17:00 | 3332.18 | 16-SEP-11:10 |
October | 2879.63 | 07-OCT-14:09 | 3341.31 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3685.29 | 31-OCT-17:00 |
November | 2879.63 | 04-NOV-14:09 | 3341.31 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5589.29 | 12-NOV-17:00 |
December | 2879.63 | 02-DEC-15:09 | 3341.31 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6646.11 | 26-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2879.63 | 3341.31 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2806.90 | |||||
Maximum of Months | 2879.63 | 3341.31 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2211.86 | 6910.84 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1670.66 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3789.47 | 07-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 1670.66 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3841.02 | 18-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1670.66 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2780.43 | 22-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 1670.66 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 537.22 | 01-APR-16:00 | 2414.04 | 18-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 1670.66 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.05 | 05-MAY-16:00 | 2184.82 | 23-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 1670.66 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.42 | 28-JUN-17:00 | 1903.94 | 13-JUN-11:10 |
July | 1439.81 | 01-JUL-14:09 | 1670.66 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.96 | 24-JUL-15:00 | 1595.57 | 09-JUL-13:00 |
August | 1439.81 | 05-AUG-14:09 | 1670.66 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.61 | 10-AUG-17:00 | 1687.65 | 01-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 1670.66 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.92 | 14-SEP-17:00 | 1889.23 | 16-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 1670.66 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2042.85 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 1670.66 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3112.30 | 12-NOV-17:00 |
December | 1439.81 | 02-DEC-15:09 | 1670.66 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3698.86 | 26-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1595.57 | |||||
Maximum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.61 | 3841.02 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1670.66 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3789.47 | 07-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 1670.66 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3841.02 | 18-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1670.66 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2780.43 | 22-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 1670.66 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 537.22 | 01-APR-16:00 | 2414.04 | 18-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 1670.66 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.04 | 05-MAY-16:00 | 2184.82 | 23-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 1670.66 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.42 | 28-JUN-17:00 | 1888.47 | 13-JUN-11:10 |
July | 1439.81 | 01-JUL-14:09 | 1670.66 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.96 | 24-JUL-15:00 | 1584.08 | 09-JUL-13:00 |
August | 1439.81 | 05-AUG-14:09 | 1670.66 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.61 | 10-AUG-17:00 | 1677.18 | 01-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 1670.66 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.92 | 14-SEP-17:00 | 1877.84 | 16-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 1670.66 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2042.85 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 1670.66 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3112.30 | 12-NOV-17:00 |
December | 1439.81 | 02-DEC-15:09 | 1670.66 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3698.86 | 26-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1584.08 | |||||
Maximum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.61 | 3841.02 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1670.66 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3789.47 | 07-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 1670.66 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3841.02 | 18-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1670.66 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2780.43 | 22-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 1670.66 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 537.21 | 01-APR-16:00 | 2414.04 | 18-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 1670.66 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.04 | 05-MAY-16:00 | 2184.82 | 23-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 1670.66 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.41 | 28-JUN-17:00 | 1848.28 | 13-JUN-11:10 |
July | 1439.81 | 01-JUL-14:09 | 1670.66 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.96 | 24-JUL-15:00 | 1558.32 | 09-JUL-13:00 |
August | 1439.81 | 05-AUG-14:09 | 1670.66 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.61 | 10-AUG-17:00 | 1656.51 | 01-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 1670.66 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.92 | 14-SEP-17:00 | 1855.15 | 16-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 1670.66 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2042.82 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 1670.66 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3112.30 | 12-NOV-17:00 |
December | 1439.81 | 02-DEC-15:09 | 1670.66 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3698.86 | 26-DEC-12:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1558.32 | |||||
Maximum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.61 | 3841.02 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1439.81 | 07-JAN-15:09 | 1670.66 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3840.75 | 07-JAN-12:10 |
February | 1439.81 | 04-FEB-15:09 | 1670.66 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4013.27 | 18-FEB-18:00 |
March | 1439.81 | 04-MAR-15:09 | 1670.66 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2903.35 | 22-MAR-11:10 |
April | 1439.81 | 01-APR-14:09 | 1670.66 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 567.36 | 01-APR-16:00 | 2513.05 | 18-APR-17:00 |
May | 1439.81 | 06-MAY-14:09 | 1670.66 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.72 | 05-MAY-16:00 | 2255.89 | 23-MAY-17:00 |
June | 1439.81 | 03-JUN-14:09 | 1670.66 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 460.53 | 28-JUN-17:00 | 1833.79 | 13-JUN-11:10 |
July | 1439.81 | 01-JUL-14:09 | 1670.66 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1083.09 | 24-JUL-15:00 | 1527.52 | 09-JUL-13:00 |
August | 1439.81 | 05-AUG-14:09 | 1670.66 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1257.22 | 10-AUG-17:00 | 1671.78 | 01-AUG-11:10 |
September | 1439.81 | 02-SEP-14:09 | 1670.66 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.31 | 14-SEP-17:00 | 1821.61 | 16-SEP-11:10 |
October | 1439.81 | 07-OCT-14:09 | 1670.66 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2204.43 | 31-OCT-17:00 |
November | 1439.81 | 04-NOV-14:09 | 1670.66 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3177.03 | 12-NOV-17:00 |
December | 1439.81 | 02-DEC-15:09 | 1670.66 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3819.93 | 26-DEC-13:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1527.52 | |||||
Maximum of Months | 1439.81 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1257.22 | 4013.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10584.04 | 21-JAN-09:04 | 1439.81 | 22003.70 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 950.40 |
February | 11466.90 | 19-FEB-09:04 | 1619.79 | 24754.16 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1418.83 |
March | 7888.67 | 24-MAR-08:04 | 1439.81 | 22003.70 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.80 |
April | 7775.28 | 18-APR-08:02 | 1439.81 | 22003.70 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 850.98 |
May | 7811.74 | 15-MAY-16:40 | 1799.77 | 5225.88 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 98.75 | 0.00 |
June | 13900.48 | 28-JUN-08:63 | 539.93 | 8251.39 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.31 |
July | 24227.76 | 24-JUL-08:62 | 899.88 | 13752.31 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.68 |
August | 26447.36 | 09-AUG-08:62 | 719.91 | 11001.85 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.35 |
September | 16606.87 | 14-SEP-08:63 | 539.93 | 8251.39 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.85 |
October | 7369.81 | 04-OCT-14:00 | 1439.81 | 5225.88 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 834.23 |
November | 9134.64 | 13-NOV-09:03 | 1439.81 | 22003.70 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1000.57 |
December | 10430.62 | 26-DEC-09:04 | 1439.81 | 22003.70 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1143.54 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7369.81 | 539.93 | 5225.88 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26447.36 | 1799.77 | 24754.16 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 98.75 | 1418.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4545.53 | 07-JAN-08:62 | 0.00 | 650.22 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.18 |
February | 5122.79 | 19-FEB-09:04 | 809.89 | 14629.89 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.83 |
March | 3823.29 | 05-MAR-09:04 | 629.92 | 11378.81 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.57 |
April | 6030.30 | 30-APR-07:02 | 539.93 | 975.33 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.07 |
May | 9142.56 | 07-MAY-07:02 | 449.94 | 812.77 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.24 |
June | 12397.68 | 11-JUN-07:02 | 539.93 | 975.33 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.17 |
July | 13148.87 | 16-JUL-07:02 | 539.93 | 975.33 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.49 |
August | 13401.92 | 09-AUG-08:62 | 359.95 | 6502.17 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.20 |
September | 14009.58 | 03-SEP-07:02 | 539.93 | 975.33 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.33 |
October | 6184.18 | 09-OCT-07:01 | 629.92 | 1137.88 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.01 |
November | 4475.85 | 11-NOV-09:04 | 719.90 | 13004.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.49 |
December | 4406.19 | 06-DEC-09:04 | 719.90 | 13004.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.60 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3823.29 | 0.00 | 650.22 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.20 | |
Maximum of Months | 14009.58 | 809.89 | 14629.89 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4806.16 | 08-JAN-09:03 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580.72 |
February | 5025.54 | 19-FEB-09:03 | 809.89 | 13364.27 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.87 |
March | 3553.06 | 01-MAR-08:62 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.01 |
April | 14641.21 | 28-APR-07:03 | 359.95 | 5939.67 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.08 |
May | 19201.67 | 08-MAY-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.88 |
June | 19495.90 | 29-JUN-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.64 |
July | 19683.96 | 19-JUL-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.38 |
August | 19690.59 | 01-AUG-07:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.76 |
September | 19822.45 | 16-SEP-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.44 |
October | 18427.40 | 05-OCT-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.40 |
November | 3070.28 | 22-NOV-08:62 | 359.95 | 5939.67 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.47 |
December | 4712.32 | 26-DEC-08:03 | 629.92 | 10394.43 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.39 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3070.28 | 359.95 | 5939.67 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.38 | |
Maximum of Months | 19822.45 | 809.89 | 13364.27 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4778.74 | 15-JAN-09:04 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.20 |
February | 5183.62 | 19-FEB-09:03 | 809.89 | 13364.27 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 678.31 |
March | 3493.61 | 01-MAR-08:62 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.21 |
April | 13378.72 | 28-APR-07:03 | 359.95 | 5939.67 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.90 |
May | 18284.71 | 08-MAY-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.80 |
June | 19406.31 | 29-JUN-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.44 |
July | 19571.62 | 19-JUL-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.65 |
August | 19623.37 | 01-AUG-07:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.14 |
September | 19732.45 | 16-SEP-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.27 |
October | 17442.08 | 05-OCT-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.30 |
November | 3097.65 | 26-NOV-09:03 | 629.92 | 10394.43 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.59 |
December | 3402.00 | 12-DEC-09:01 | 1439.81 | 22570.76 | 5393.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.89 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3097.65 | 359.95 | 5939.67 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.65 | |
Maximum of Months | 19732.45 | 1439.81 | 22570.76 | 5393.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 678.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4955.82 | 15-JAN-09:04 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618.78 |
February | 5251.60 | 19-FEB-09:03 | 809.89 | 13364.27 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.97 |
March | 3507.95 | 05-MAR-09:03 | 629.92 | 10394.43 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.40 |
April | 9516.74 | 28-APR-07:03 | 359.95 | 5939.67 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.34 |
May | 15906.86 | 07-MAY-08:62 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.48 |
June | 19157.40 | 29-JUN-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.92 |
July | 19322.30 | 19-JUL-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.12 |
August | 19386.54 | 01-AUG-07:02 | 539.93 | 8909.51 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.86 |
September | 19491.36 | 16-SEP-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.12 |
October | 13855.42 | 05-OCT-07:02 | 449.94 | 7424.59 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.95 |
November | 3958.38 | 11-NOV-09:03 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.79 |
December | 4249.86 | 25-DEC-09:04 | 719.90 | 11879.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.73 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3507.95 | 359.95 | 5939.67 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.48 | |
Maximum of Months | 19491.36 | 809.89 | 13364.27 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10515.32 | 07-JAN-09:05 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1121.26 |
February | 10928.41 | 19-FEB-10:05 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1197.53 |
March | 8085.22 | 05-MAR-10:04 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.96 |
April | 7631.99 | 18-APR-08:04 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 771.77 |
May | 6680.03 | 18-MAY-08:61 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 747.58 |
June | 12496.22 | 28-JUN-08:63 | 1187.85 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.32 |
July | 25326.23 | 23-JUL-09:02 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.41 |
August | 25128.90 | 09-AUG-08:62 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.25 |
September | 14609.08 | 14-SEP-08:63 | 1187.85 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.70 |
October | 6548.40 | 30-OCT-08:02 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666.34 |
November | 9315.07 | 13-NOV-09:04 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 922.49 |
December | 10437.22 | 26-DEC-09:05 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1049.28 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6548.40 | 1187.85 | 5275.76 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.25 | |
Maximum of Months | 25326.23 | 3167.59 | 14068.69 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1197.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5267.98 | 07-JAN-09:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.93 |
February | 5004.22 | 19-FEB-10:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.40 |
March | 3448.02 | 05-MAR-10:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.88 |
April | 3314.03 | 18-APR-08:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.33 |
May | 3160.62 | 18-MAY-08:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.16 |
June | 3903.59 | 28-JUN-16:20 | 1277.83 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 387.84 | 0.00 |
July | 11296.67 | 24-JUL-08:62 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.57 |
August | 10386.55 | 10-AUG-08:62 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.76 |
September | 4241.09 | 14-SEP-14:10 | 1241.83 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 | 0.00 |
October | 2936.91 | 24-OCT-08:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.02 |
November | 4050.92 | 13-NOV-09:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.92 |
December | 4748.36 | 26-DEC-09:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.47 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2936.91 | 989.87 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11296.67 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 387.84 | 654.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5285.20 | 07-JAN-09:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.97 |
February | 5028.96 | 19-FEB-10:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.88 |
March | 3475.24 | 05-MAR-10:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.37 |
April | 3341.99 | 18-APR-08:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.83 |
May | 3233.34 | 18-MAY-08:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.06 |
June | 3821.07 | 28-JUN-16:20 | 1277.83 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 387.84 | 0.00 |
July | 11148.98 | 24-JUL-08:62 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.22 |
August | 10256.87 | 10-AUG-08:62 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.68 |
September | 4161.77 | 14-SEP-14:10 | 1241.83 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 | 0.00 |
October | 2904.62 | 24-OCT-08:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.59 |
November | 4077.62 | 13-NOV-09:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.41 |
December | 4735.48 | 26-DEC-09:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.97 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2904.62 | 989.87 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11148.98 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 387.84 | 654.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5262.58 | 07-JAN-09:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.68 |
February | 5054.28 | 19-FEB-10:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 655.30 |
March | 3513.64 | 05-MAR-10:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.21 |
April | 3378.66 | 18-APR-08:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.61 |
May | 3180.64 | 18-MAY-08:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.55 |
June | 3679.20 | 28-JUN-16:50 | 1277.83 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 434.10 | 0.00 |
July | 10962.28 | 24-JUL-08:62 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.17 |
August | 10101.41 | 10-AUG-08:62 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.54 |
September | 4058.56 | 14-SEP-14:10 | 1241.83 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 | 0.00 |
October | 2889.55 | 13-OCT-08:04 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.00 |
November | 4113.30 | 13-NOV-09:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.18 |
December | 4645.46 | 25-DEC-10:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.65 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2889.55 | 989.87 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10962.28 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 434.10 | 655.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4772.84 | 07-JAN-08:05 | 0.00 | 351.72 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 629.20 |
February | 4306.57 | 08-FEB-09:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.46 |
March | 3520.56 | 05-MAR-10:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.77 |
April | 3392.15 | 18-APR-08:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.27 |
May | 2902.57 | 18-MAY-08:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.29 |
June | 3491.40 | 28-JUN-15:00 | 1241.83 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 369.71 | 0.00 |
July | 8587.51 | 24-JUL-08:62 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 |
August | 8626.78 | 10-AUG-08:62 | 989.87 | 4396.47 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.12 |
September | 4026.17 | 14-SEP-14:10 | 1241.83 | 1670.66 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 | 0.00 |
October | 2851.95 | 12-OCT-08:04 | 1385.82 | 6155.05 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.82 |
November | 4114.24 | 13-NOV-09:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.93 |
December | 4280.88 | 22-DEC-09:05 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 610.09 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2851.95 | 0.00 | 351.72 | 149.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8626.78 | 1583.79 | 7034.35 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 369.71 | 629.20 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.732645E+11 | 58873.63 | 09-JAN-17:19 | 0.833651E+11 | 160552.34 | 07-JAN-09:09 |
February | 0.655663E+11 | 56633.96 | 21-FEB-19:10 | 0.563809E+11 | 150933.24 | 18-FEB-09:09 |
March | 0.723245E+11 | 58578.37 | 01-MAR-19:49 | 0.318280E+11 | 113014.08 | 24-MAR-08:09 |
April | 0.690261E+11 | 64102.03 | 27-APR-13:20 | 0.128832E+11 | 103581.19 | 18-APR-08:09 |
May | 0.718379E+11 | 63759.76 | 05-MAY-15:39 | 0.227460E+10 | 55646.71 | 18-MAY-08:09 |
June | 0.715067E+11 | 63837.96 | 28-JUN-16:00 | 63528678.35 | 11565.31 | 15-JUN-08:09 |
July | 0.775936E+11 | 70649.73 | 24-JUL-15:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.822154E+11 | 73992.60 | 29-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.726034E+11 | 65367.64 | 14-SEP-14:09 | 0.190452E+09 | 26432.55 | 28-SEP-08:09 |
October | 0.720719E+11 | 58599.95 | 04-OCT-15:30 | 0.837078E+10 | 73939.09 | 30-OCT-08:09 |
November | 0.705223E+11 | 58435.07 | 03-NOV-18:00 | 0.432878E+11 | 122228.87 | 13-NOV-09:09 |
December | 0.732230E+11 | 58746.56 | 19-DEC-17:49 | 0.706143E+11 | 161878.86 | 26-DEC-09:09 |
Annual Sum or Average | 0.871756E+12 | 0.309259E+12 | ||||
Minimum of Months | 0.655663E+11 | 56633.96 | 0.00 | 0.00 | ||
Maximum of Months | 0.822154E+11 | 73992.60 | 0.833651E+11 | 161878.86 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.366903E+11 | 0.730556E+10 | 0.108804E+11 | 0.00 | 0.131417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524647E+10 | 0.00 |
February | 0.332186E+11 | 0.593279E+10 | 0.985143E+10 | 0.00 | 0.117942E+11 | 0.00 | 0.00 | 10458951.03 | 0.00 | 0.00 | 0.00 | 0.475889E+10 | 0.00 |
March | 0.372231E+11 | 0.565574E+10 | 0.110523E+11 | 0.00 | 0.130898E+11 | 0.00 | 0.00 | 22507757.63 | 0.00 | 0.00 | 0.00 | 0.528102E+10 | 0.00 |
April | 0.356035E+11 | 0.455705E+10 | 0.105581E+11 | 0.00 | 0.124071E+11 | 0.00 | 0.00 | 0.869974E+09 | 0.00 | 0.00 | 0.00 | 0.503046E+10 | 0.00 |
May | 0.369426E+11 | 0.397098E+10 | 0.109629E+11 | 0.00 | 0.128938E+11 | 0.00 | 0.00 | 0.192779E+10 | 0.00 | 0.00 | 0.00 | 0.513984E+10 | 0.00 |
June | 0.359818E+11 | 0.346685E+10 | 0.106818E+11 | 0.00 | 0.126121E+11 | 0.00 | 0.00 | 0.383402E+10 | 0.00 | 0.00 | 0.00 | 0.493016E+10 | 0.00 |
July | 0.365926E+11 | 0.373161E+10 | 0.108460E+11 | 0.00 | 0.128238E+11 | 0.00 | 0.00 | 0.859171E+10 | 0.00 | 0.00 | 0.00 | 0.500782E+10 | 0.00 |
August | 0.371948E+11 | 0.434900E+10 | 0.110454E+11 | 0.00 | 0.131316E+11 | 0.00 | 0.00 | 0.114536E+11 | 0.00 | 0.00 | 0.00 | 0.504101E+10 | 0.00 |
September | 0.356318E+11 | 0.507429E+10 | 0.105649E+11 | 0.00 | 0.124498E+11 | 0.00 | 0.00 | 0.400861E+10 | 0.00 | 0.00 | 0.00 | 0.487397E+10 | 0.00 |
October | 0.366903E+11 | 0.619081E+10 | 0.108804E+11 | 0.00 | 0.127778E+11 | 0.00 | 0.00 | 0.447979E+09 | 0.00 | 0.00 | 0.00 | 0.508459E+10 | 0.00 |
November | 0.355468E+11 | 0.682221E+10 | 0.105443E+11 | 0.00 | 0.125491E+11 | 0.00 | 0.00 | 73206292.42 | 0.00 | 0.00 | 0.00 | 0.498665E+10 | 0.00 |
December | 0.366210E+11 | 0.752256E+10 | 0.108529E+11 | 0.00 | 0.130175E+11 | 0.00 | 0.00 | 7050.22 | 0.00 | 0.00 | 0.00 | 0.520911E+10 | 0.00 |
Annual Sum or Average | 0.433937E+12 | 0.645794E+11 | 0.128721E+12 | 0.152688E+12 | 0.00 | 0.312399E+11 | 0.605900E+11 | ||||||
Minimum of Months | 0.332186E+11 | 0.346685E+10 | 0.985143E+10 | 0.00 | 0.117942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475889E+10 | 0.00 |
Maximum of Months | 0.372231E+11 | 0.752256E+10 | 0.110523E+11 | 0.00 | 0.131417E+11 | 0.00 | 0.00 | 0.114536E+11 | 0.00 | 0.00 | 0.00 | 0.528102E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.833651E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.563809E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.318280E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.128832E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.227460E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 63528678.35 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.190452E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.837078E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.432878E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.706143E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309259E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.833651E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 26802.39 | 01-JAN-11:09 | 4954.41 | 01-JAN-06:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 9921.37 | 07-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 26802.39 | 01-FEB-10:09 | 4954.41 | 01-FEB-06:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 9880.01 | 18-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 26802.39 | 01-MAR-10:09 | 4954.41 | 01-MAR-06:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 9579.14 | 24-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26802.39 | 01-APR-09:09 | 4954.41 | 01-APR-05:10 | 8089.53 | 01-APR-09:09 | 0.00 | 9488.90 | 18-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 26802.39 | 01-MAY-09:09 | 4954.41 | 01-MAY-19:19 | 8089.53 | 01-MAY-09:09 | 0.00 | 9168.59 | 18-MAY-08:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 26802.39 | 01-JUN-09:09 | 4954.41 | 01-JUN-19:00 | 8089.53 | 01-JUN-09:09 | 0.00 | 8930.13 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 26802.39 | 01-JUL-09:09 | 4954.41 | 01-JUL-20:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 9424.59 | 31-JUL-08:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 26802.39 | 01-AUG-09:09 | 4954.41 | 01-AUG-19:40 | 8089.53 | 01-AUG-09:09 | 0.00 | 9472.31 | 29-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 26802.39 | 01-SEP-09:09 | 4954.41 | 01-SEP-05:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 9018.92 | 14-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 26802.39 | 01-OCT-10:09 | 4954.41 | 01-OCT-05:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 9275.01 | 30-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26802.39 | 01-NOV-09:09 | 4954.41 | 01-NOV-05:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 9599.33 | 13-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26802.39 | 01-DEC-10:09 | 4954.41 | 01-DEC-06:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 9898.87 | 26-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 26802.39 | 4954.41 | 8089.53 | 0.00 | 8930.13 | 0.00 | 0.00 | |||||
Maximum of Months | 26802.39 | 4954.41 | 8089.53 | 0.00 | 9921.37 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 11838.75 | 03-JAN-14:50 | 0.00 |
February | 389.91 | 27-FEB-21:19 | 0.00 | 0.00 | 0.00 | 8822.62 | 02-FEB-11:50 | 0.00 |
March | 413.09 | 18-MAR-18:10 | 0.00 | 0.00 | 0.00 | 9671.79 | 01-MAR-19:49 | 0.00 |
April | 14522.43 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 8456.85 | 28-APR-12:20 | 0.00 |
May | 13438.92 | 06-MAY-12:00 | 0.00 | 0.00 | 0.00 | 9704.17 | 30-MAY-12:20 | 0.00 |
June | 15758.77 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 | 10966.87 | 06-JUN-12:00 | 0.00 |
July | 22673.67 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 9632.67 | 16-JUL-16:40 | 0.00 |
August | 24896.19 | 29-AUG-14:00 | 0.00 | 0.00 | 0.00 | 7575.69 | 23-AUG-12:09 | 0.00 |
September | 16151.94 | 14-SEP-13:00 | 0.00 | 0.00 | 0.00 | 7576.89 | 14-SEP-12:20 | 0.00 |
October | 8337.71 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 11705.85 | 23-OCT-15:39 | 0.00 |
November | 3921.21 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 | 11652.70 | 14-NOV-14:00 | 0.00 |
December | 7.12 | 03-DEC-20:00 | 0.00 | 0.00 | 0.00 | 9629.74 | 17-DEC-11:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7575.69 | 0.00 | ||
Maximum of Months | 24896.19 | 0.00 | 0.00 | 0.00 | 11838.75 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 58873.63 | 09-JAN-17:19 | 26802.39 | 8089.53 | 4954.41 | 0.00 | 9349.53 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 56633.96 | 21-FEB-19:10 | 26802.39 | 8089.53 | 4954.41 | 0.00 | 9230.72 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 58578.37 | 01-MAR-19:49 | 26802.39 | 8089.53 | 4954.41 | 0.00 | 9060.24 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 64102.03 | 27-APR-13:20 | 26802.39 | 8089.53 | 0.00 | 0.00 | 8930.13 | 0.00 | 0.00 | 12695.87 | 0.00 |
May | 63759.76 | 05-MAY-15:39 | 26802.39 | 8089.53 | 0.00 | 0.00 | 8930.13 | 0.00 | 0.00 | 12384.84 | 0.00 |
June | 63837.96 | 28-JUN-16:00 | 26802.39 | 8089.53 | 0.00 | 0.00 | 8930.13 | 0.00 | 0.00 | 15758.77 | 0.00 |
July | 70649.73 | 24-JUL-15:39 | 26802.39 | 8089.53 | 0.00 | 0.00 | 9166.01 | 0.00 | 0.00 | 21155.30 | 0.00 |
August | 73992.60 | 29-AUG-15:00 | 26802.39 | 8089.53 | 0.00 | 0.00 | 9406.97 | 0.00 | 0.00 | 24257.38 | 0.00 |
September | 65367.64 | 14-SEP-14:09 | 26802.39 | 8089.53 | 0.00 | 0.00 | 8930.13 | 0.00 | 0.00 | 16102.83 | 0.00 |
October | 58599.95 | 04-OCT-15:30 | 26802.39 | 8089.53 | 0.00 | 0.00 | 8930.13 | 0.00 | 0.00 | 7388.45 | 0.00 |
November | 58435.07 | 03-NOV-18:00 | 26802.39 | 8089.53 | 4954.41 | 0.00 | 8930.13 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 58746.56 | 19-DEC-17:49 | 26802.39 | 8089.53 | 4954.41 | 0.00 | 9337.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 56633.96 | 26802.39 | 8089.53 | 0.00 | 0.00 | 8930.13 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73992.60 | 26802.39 | 8089.53 | 4954.41 | 0.00 | 9406.97 | 0.00 | 0.00 | 24257.38 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS [] | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 160552.34 | 07-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 150933.24 | 18-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 113014.08 | 24-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 103581.19 | 18-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 55646.71 | 18-MAY-08:09 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 11565.31 | 15-JUN-08:09 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 26432.55 | 28-SEP-08:09 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 73939.09 | 30-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 122228.87 | 13-NOV-09:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 161878.86 | 26-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 161878.86 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.67 | 20.48 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.00 | 117.00 | 20.67 | 117.00 | 20.67 |
February | 448.00 | 21.08 | 93.00 | 20.70 | 93.00 | 20.70 |
March | 496.00 | 21.17 | 35.83 | 20.51 | 35.83 | 20.51 |
April | 437.33 | 21.60 | 22.00 | 22.23 | 10.50 | 20.42 |
May | 362.33 | 22.27 | 46.00 | 23.89 | 0.00 | 0.00 |
June | 149.67 | 22.95 | 87.83 | 23.89 | 0.00 | 0.00 |
July | 39.00 | 23.40 | 289.67 | 23.90 | 0.00 | 0.00 |
August | 21.67 | 23.28 | 353.50 | 23.91 | 0.00 | 0.00 |
September | 149.00 | 22.75 | 181.33 | 23.89 | 0.00 | 0.00 |
October | 396.67 | 21.67 | 8.83 | 23.88 | 0.00 | 0.00 |
November | 469.17 | 21.20 | 25.17 | 20.65 | 23.33 | 20.39 |
December | 496.00 | 21.02 | 65.83 | 20.51 | 65.83 | 20.51 |
Annual Sum or Average | 3960.83 | 21.48 | 1326.00 | 23.04 | 345.50 | 20.60 |
Minimum of Months | 21.67 | 21.00 | 8.83 | 20.51 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.40 | 353.50 | 23.91 | 117.00 | 20.70 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.41 | 42.17 | 19.98 | 42.17 | 19.98 |
February | 444.83 | 21.65 | 30.50 | 19.93 | 30.50 | 19.93 |
March | 496.00 | 22.02 | 15.00 | 20.02 | 15.00 | 20.02 |
April | 399.17 | 22.52 | 24.50 | 23.12 | 4.67 | 19.88 |
May | 216.67 | 23.00 | 61.17 | 23.89 | 0.00 | 0.00 |
June | 50.83 | 23.19 | 120.50 | 23.89 | 0.00 | 0.00 |
July | 13.67 | 23.49 | 320.33 | 23.90 | 0.00 | 0.00 |
August | 10.00 | 23.39 | 402.33 | 23.91 | 0.00 | 0.00 |
September | 64.33 | 23.12 | 232.33 | 23.89 | 0.00 | 0.00 |
October | 340.83 | 22.61 | 16.50 | 23.89 | 0.00 | 0.00 |
November | 447.50 | 21.76 | 20.67 | 21.27 | 12.83 | 19.67 |
December | 496.00 | 21.51 | 29.17 | 19.81 | 29.17 | 19.81 |
Annual Sum or Average | 3475.83 | 22.00 | 1315.17 | 23.49 | 134.33 | 19.90 |
Minimum of Months | 10.00 | 21.41 | 15.00 | 19.81 | 0.00 | 0.00 |
Maximum of Months | 496.00 | 23.49 | 402.33 | 23.91 | 42.17 | 20.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 45.33 | 21.11 | 45.33 | 21.11 |
February | 336.00 | 21.31 | 25.50 | 21.11 | 25.50 | 21.11 |
March | 379.00 | 21.54 | 3.17 | 21.11 | 3.17 | 21.11 |
April | 307.33 | 22.15 | 18.67 | 24.02 | 0.00 | 0.00 |
May | 164.67 | 22.95 | 56.17 | 24.06 | 0.00 | 0.00 |
June | 33.50 | 23.42 | 110.33 | 24.08 | 0.00 | 0.00 |
July | 4.50 | 23.76 | 261.50 | 24.04 | 0.00 | 0.00 |
August | 2.17 | 23.68 | 326.83 | 24.02 | 0.00 | 0.00 |
September | 46.50 | 23.23 | 192.67 | 23.98 | 0.00 | 0.00 |
October | 264.83 | 22.29 | 14.17 | 23.99 | 0.00 | 0.00 |
November | 346.33 | 21.39 | 7.83 | 23.56 | 1.00 | 21.11 |
December | 369.00 | 21.13 | 18.67 | 21.11 | 18.67 | 21.11 |
Annual Sum or Average | 2624.83 | 21.67 | 1080.83 | 23.77 | 93.67 | 21.11 |
Minimum of Months | 2.17 | 21.12 | 3.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 23.76 | 326.83 | 24.08 | 45.33 | 21.11 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 57.50 | 21.11 | 57.50 | 21.11 |
February | 336.00 | 21.28 | 31.83 | 21.11 | 31.83 | 21.11 |
March | 379.00 | 21.48 | 5.67 | 21.11 | 5.67 | 21.11 |
April | 309.83 | 22.05 | 17.33 | 24.03 | 0.00 | 0.00 |
May | 185.50 | 22.94 | 53.33 | 24.06 | 0.00 | 0.00 |
June | 37.00 | 23.41 | 108.33 | 24.08 | 0.00 | 0.00 |
July | 4.83 | 23.75 | 260.17 | 24.04 | 0.00 | 0.00 |
August | 2.33 | 23.69 | 324.83 | 24.02 | 0.00 | 0.00 |
September | 51.17 | 23.20 | 186.17 | 23.98 | 0.00 | 0.00 |
October | 272.33 | 22.20 | 11.83 | 23.97 | 0.00 | 0.00 |
November | 348.67 | 21.36 | 9.33 | 22.50 | 4.67 | 21.11 |
December | 369.00 | 21.12 | 27.17 | 21.11 | 27.17 | 21.11 |
Annual Sum or Average | 2666.67 | 21.65 | 1093.50 | 23.69 | 126.83 | 21.11 |
Minimum of Months | 2.33 | 21.12 | 5.67 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 23.75 | 324.83 | 24.08 | 57.50 | 21.11 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 75.33 | 21.11 | 75.33 | 21.11 |
February | 336.00 | 21.24 | 43.33 | 21.11 | 43.33 | 21.11 |
March | 379.00 | 21.38 | 10.50 | 21.11 | 10.50 | 21.11 |
April | 320.83 | 21.92 | 14.33 | 23.98 | 0.33 | 21.11 |
May | 246.67 | 22.85 | 42.17 | 24.05 | 0.00 | 0.00 |
June | 63.67 | 23.33 | 90.67 | 24.10 | 0.00 | 0.00 |
July | 8.00 | 23.72 | 245.00 | 24.03 | 0.00 | 0.00 |
August | 5.00 | 23.61 | 310.50 | 24.02 | 0.00 | 0.00 |
September | 74.17 | 23.09 | 158.83 | 23.99 | 0.00 | 0.00 |
October | 287.67 | 22.02 | 6.83 | 23.92 | 0.00 | 0.00 |
November | 351.17 | 21.29 | 13.33 | 21.80 | 10.00 | 21.11 |
December | 369.00 | 21.11 | 43.00 | 21.11 | 43.00 | 21.11 |
Annual Sum or Average | 2812.17 | 21.64 | 1053.83 | 23.52 | 182.50 | 21.11 |
Minimum of Months | 5.00 | 21.11 | 6.83 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 23.72 | 310.50 | 24.10 | 75.33 | 21.11 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 158.00 | 21.10 | 158.00 | 21.10 |
February | 308.00 | 21.14 | 111.33 | 21.10 | 111.33 | 21.10 |
March | 348.00 | 21.17 | 27.00 | 21.11 | 27.00 | 21.11 |
April | 312.17 | 21.51 | 5.67 | 21.11 | 5.67 | 21.11 |
May | 275.83 | 22.01 | 22.83 | 23.94 | 0.00 | 0.00 |
June | 157.33 | 22.86 | 36.50 | 23.91 | 0.00 | 0.00 |
July | 39.67 | 23.22 | 166.83 | 23.93 | 0.00 | 0.00 |
August | 23.83 | 23.12 | 219.50 | 23.91 | 0.00 | 0.00 |
September | 159.00 | 22.51 | 99.00 | 23.92 | 0.00 | 0.00 |
October | 312.67 | 21.66 | 0.67 | 21.16 | 0.67 | 21.16 |
November | 326.17 | 21.15 | 22.00 | 21.10 | 22.00 | 21.10 |
December | 338.00 | 21.11 | 97.33 | 21.10 | 97.33 | 21.10 |
Annual Sum or Average | 2940.67 | 21.52 | 966.67 | 22.69 | 422.00 | 21.10 |
Minimum of Months | 23.83 | 21.11 | 0.67 | 21.10 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.22 | 219.50 | 23.94 | 158.00 | 21.16 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 168.83 | 21.10 | 168.83 | 21.10 |
February | 308.00 | 21.15 | 119.00 | 21.10 | 119.00 | 21.10 |
March | 348.00 | 21.18 | 40.83 | 21.08 | 40.83 | 21.08 |
April | 311.50 | 21.57 | 11.83 | 21.26 | 11.17 | 21.06 |
May | 282.83 | 22.19 | 16.83 | 23.79 | 1.17 | 21.06 |
June | 163.17 | 23.01 | 18.00 | 24.00 | 0.00 | 0.00 |
July | 45.83 | 23.34 | 137.00 | 23.96 | 0.00 | 0.00 |
August | 25.33 | 23.19 | 198.83 | 23.93 | 0.00 | 0.00 |
September | 159.50 | 22.66 | 83.33 | 23.94 | 0.00 | 0.00 |
October | 313.67 | 21.74 | 3.50 | 21.03 | 3.50 | 21.03 |
November | 326.17 | 21.17 | 31.50 | 21.07 | 31.50 | 21.07 |
December | 338.00 | 21.10 | 111.17 | 21.09 | 111.17 | 21.09 |
Annual Sum or Average | 2962.00 | 21.59 | 940.67 | 22.47 | 487.17 | 21.09 |
Minimum of Months | 25.33 | 21.10 | 3.50 | 21.03 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.34 | 198.83 | 24.00 | 168.83 | 21.10 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 178.17 | 21.10 | 178.17 | 21.10 |
February | 308.00 | 21.15 | 124.50 | 21.10 | 124.50 | 21.10 |
March | 348.00 | 21.17 | 46.33 | 21.08 | 46.33 | 21.08 |
April | 314.33 | 21.55 | 13.50 | 21.11 | 13.33 | 21.06 |
May | 290.33 | 22.15 | 14.17 | 23.67 | 1.67 | 21.10 |
June | 176.17 | 22.98 | 12.00 | 24.04 | 0.00 | 0.00 |
July | 51.83 | 23.31 | 127.50 | 23.96 | 0.00 | 0.00 |
August | 28.67 | 23.16 | 192.33 | 23.93 | 0.00 | 0.00 |
September | 169.00 | 22.64 | 78.33 | 23.93 | 0.17 | 21.14 |
October | 319.83 | 21.74 | 4.17 | 21.03 | 4.17 | 21.03 |
November | 326.67 | 21.16 | 35.00 | 21.08 | 35.00 | 21.08 |
December | 338.00 | 21.10 | 119.83 | 21.09 | 119.83 | 21.09 |
Annual Sum or Average | 3010.83 | 21.59 | 945.83 | 22.37 | 523.17 | 21.09 |
Minimum of Months | 28.67 | 21.10 | 4.17 | 21.03 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.31 | 192.33 | 24.04 | 178.17 | 21.14 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 207.17 | 21.10 | 207.17 | 21.10 |
February | 308.00 | 21.14 | 137.83 | 21.10 | 137.83 | 21.10 |
March | 348.00 | 21.16 | 59.00 | 21.08 | 59.00 | 21.08 |
April | 316.67 | 21.51 | 19.50 | 21.07 | 19.50 | 21.07 |
May | 299.00 | 22.04 | 13.67 | 23.57 | 2.00 | 21.06 |
June | 188.50 | 22.86 | 7.17 | 24.05 | 0.00 | 0.00 |
July | 65.67 | 23.24 | 112.67 | 23.97 | 0.00 | 0.00 |
August | 37.17 | 23.13 | 183.50 | 23.93 | 0.00 | 0.00 |
September | 185.33 | 22.55 | 67.83 | 23.93 | 0.17 | 21.03 |
October | 326.33 | 21.70 | 5.17 | 21.02 | 5.17 | 21.02 |
November | 327.33 | 21.16 | 44.67 | 21.08 | 44.67 | 21.08 |
December | 338.00 | 21.10 | 148.50 | 21.10 | 148.50 | 21.10 |
Annual Sum or Average | 3080.00 | 21.58 | 1006.67 | 22.18 | 624.00 | 21.09 |
Minimum of Months | 37.17 | 21.10 | 5.17 | 21.02 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.24 | 207.17 | 24.05 | 207.17 | 21.10 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 311.00 | 21.10 | 311.00 | 21.10 |
February | 308.00 | 21.13 | 187.67 | 21.10 | 187.67 | 21.10 |
March | 348.00 | 21.14 | 131.00 | 21.09 | 131.00 | 21.09 |
April | 319.00 | 21.44 | 45.00 | 21.08 | 45.00 | 21.08 |
May | 312.33 | 21.88 | 9.67 | 22.03 | 6.67 | 21.05 |
June | 226.33 | 22.72 | 1.50 | 23.69 | 0.50 | 21.32 |
July | 97.50 | 23.09 | 98.67 | 23.97 | 0.00 | 0.00 |
August | 60.83 | 23.02 | 154.83 | 23.93 | 0.00 | 0.00 |
September | 207.17 | 22.34 | 57.17 | 23.91 | 0.50 | 21.12 |
October | 336.67 | 21.63 | 13.33 | 21.05 | 13.33 | 21.05 |
November | 330.00 | 21.17 | 133.00 | 21.10 | 133.00 | 21.10 |
December | 338.00 | 21.10 | 259.67 | 21.10 | 259.67 | 21.10 |
Annual Sum or Average | 3223.83 | 21.57 | 1402.50 | 21.74 | 1088.33 | 21.10 |
Minimum of Months | 60.83 | 21.10 | 1.50 | 21.05 | 0.00 | 0.00 |
Maximum of Months | 348.00 | 23.09 | 311.00 | 23.97 | 311.00 | 21.32 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 20.99256 | 29.40392 | -0.5027 | 10.57555 |
February | 448.00000 | 21.07160 | 31.20163 | -0.4457 | 9.72602 |
March | 496.00000 | 21.16281 | 32.50774 | -0.3790 | 8.36675 |
April | 480.00000 | 21.79580 | 36.04347 | -0.1814 | 7.09477 |
May | 496.00000 | 22.70568 | 39.41047 | -0.9267 | 25.22496 |
June | 480.00000 | 23.58768 | 39.94194 | -0.6082 | 13.51997 |
July | 496.00000 | 23.85491 | 43.36201 | -0.4607 | 9.68882 |
August | 496.00000 | 23.87490 | 46.32167 | -0.4279 | 9.03815 |
September | 480.00000 | 23.50286 | 45.62689 | -0.5888 | 13.37450 |
October | 496.00000 | 22.11077 | 39.93500 | -0.0647 | 6.59903 |
November | 480.00000 | 21.24988 | 38.14816 | -0.3319 | 8.08830 |
December | 496.00000 | 21.01793 | 31.58764 | -0.4657 | 9.73831 |
Annual Sum or Average | 5840.00000 | 22.25040 | 37.82148 | -0.4489 | 10.93379 |
Minimum of Months | 448.00000 | 20.99256 | 29.40392 | -0.9267 | 6.59903 |
Maximum of Months | 496.00000 | 23.87490 | 46.32167 | -0.0647 | 25.22496 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.38105 | 30.24861 | -0.3802 | 8.62190 |
February | 448.00000 | 21.63535 | 31.34907 | -0.2964 | 8.02659 |
March | 496.00000 | 21.99339 | 31.92095 | -0.1841 | 6.70780 |
April | 480.00000 | 22.72213 | 35.20458 | 0.02958 | 6.36824 |
May | 496.00000 | 23.48034 | 38.24853 | -0.6750 | 15.62705 |
June | 480.00000 | 23.80550 | 39.75167 | -0.5190 | 10.90286 |
July | 496.00000 | 23.88590 | 43.40478 | -0.4369 | 9.13406 |
August | 496.00000 | 23.89686 | 46.13856 | -0.4087 | 8.61542 |
September | 480.00000 | 23.76685 | 44.57615 | -0.4969 | 10.59500 |
October | 496.00000 | 22.99792 | 38.64840 | 0.13208 | 6.37784 |
November | 480.00000 | 21.88043 | 37.95833 | -0.1787 | 7.04807 |
December | 496.00000 | 21.48298 | 32.28898 | -0.3350 | 7.98730 |
Annual Sum or Average | 5840.00000 | 22.74989 | 37.50783 | -0.3128 | 8.84214 |
Minimum of Months | 448.00000 | 21.38105 | 30.24861 | -0.6750 | 6.36824 |
Maximum of Months | 496.00000 | 23.89686 | 46.13856 | 0.13208 | 15.62705 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11377 | 29.50895 | -0.4486 | 9.31815 |
February | 336.00000 | 21.30512 | 30.73518 | -0.3702 | 8.49825 |
March | 379.00000 | 21.55119 | 31.41863 | -0.2723 | 7.11455 |
April | 360.00000 | 22.40829 | 34.42277 | -0.0371 | 6.40014 |
May | 375.00000 | 23.49370 | 37.55069 | -0.6696 | 15.50287 |
June | 366.00000 | 23.90430 | 38.62493 | -0.4967 | 10.42468 |
July | 369.00000 | 23.99629 | 43.43717 | -0.4021 | 8.62832 |
August | 379.00000 | 23.99958 | 46.62726 | -0.3710 | 8.11036 |
September | 360.00000 | 23.84673 | 44.51228 | -0.4708 | 10.09809 |
October | 371.00000 | 22.76456 | 37.81555 | 0.08335 | 6.27730 |
November | 360.00000 | 21.48709 | 37.35806 | -0.2646 | 7.42848 |
December | 369.00000 | 21.12530 | 31.30015 | -0.4189 | 8.74982 |
Annual Sum or Average | 4395.00000 | 22.59323 | 36.98421 | -0.3453 | 8.88890 |
Minimum of Months | 336.00000 | 21.11377 | 29.50895 | -0.6696 | 6.27730 |
Maximum of Months | 379.00000 | 23.99958 | 46.62726 | 0.08335 | 15.50287 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10806 | 29.52018 | -0.4616 | 9.57617 |
February | 336.00000 | 21.27435 | 30.81078 | -0.3862 | 8.69671 |
March | 379.00000 | 21.48599 | 31.54773 | -0.2941 | 7.32115 |
April | 360.00000 | 22.31400 | 34.61594 | -0.0638 | 6.49421 |
May | 375.00000 | 23.43879 | 37.68324 | -0.6925 | 16.26567 |
June | 366.00000 | 23.89562 | 38.65385 | -0.5025 | 10.55841 |
July | 369.00000 | 23.99463 | 43.44459 | -0.4039 | 8.65924 |
August | 379.00000 | 23.99862 | 46.63342 | -0.3718 | 8.12252 |
September | 360.00000 | 23.83199 | 44.56315 | -0.4783 | 10.28579 |
October | 371.00000 | 22.66236 | 38.06032 | 0.05614 | 6.31815 |
November | 360.00000 | 21.43823 | 37.48969 | -0.2838 | 7.57086 |
December | 369.00000 | 21.11667 | 31.31393 | -0.4309 | 8.96677 |
Annual Sum or Average | 4395.00000 | 22.55686 | 37.06954 | -0.3598 | 9.07994 |
Minimum of Months | 336.00000 | 21.10806 | 29.52018 | -0.6925 | 6.31815 |
Maximum of Months | 379.00000 | 23.99862 | 46.63342 | 0.05614 | 16.26567 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10088 | 29.53463 | -0.4805 | 9.96110 |
February | 336.00000 | 21.22911 | 30.92381 | -0.4106 | 9.02591 |
March | 379.00000 | 21.38151 | 31.76029 | -0.3296 | 7.69019 |
April | 360.00000 | 22.13500 | 34.98990 | -0.1146 | 6.67103 |
May | 375.00000 | 23.23221 | 38.16416 | -0.7745 | 19.13870 |
June | 366.00000 | 23.84462 | 38.80534 | -0.5339 | 11.34100 |
July | 369.00000 | 23.98442 | 43.49854 | -0.4177 | 8.90427 |
August | 379.00000 | 23.98950 | 46.69624 | -0.3843 | 8.32263 |
September | 360.00000 | 23.75285 | 44.81607 | -0.5173 | 11.31069 |
October | 371.00000 | 22.45104 | 38.56517 | -0.0013 | 6.37190 |
November | 360.00000 | 21.35824 | 37.70978 | -0.3144 | 7.80020 |
December | 369.00000 | 21.10695 | 31.32944 | -0.4486 | 9.30196 |
Annual Sum or Average | 4395.00000 | 22.47392 | 37.27462 | -0.3944 | 9.66747 |
Minimum of Months | 336.00000 | 21.10088 | 29.53463 | -0.7745 | 6.37190 |
Maximum of Months | 379.00000 | 23.98950 | 46.69624 | -0.0013 | 19.13870 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.07277 | 30.46881 | -0.5386 | 11.23332 |
February | 308.00000 | 21.11818 | 32.03909 | -0.4776 | 10.11249 |
March | 348.00000 | 21.15042 | 33.08358 | -0.4130 | 8.78231 |
April | 330.00000 | 21.62368 | 36.83684 | -0.2454 | 7.43225 |
May | 344.00000 | 22.38764 | 40.86934 | -1.0480 | 30.24470 |
June | 336.00000 | 23.40925 | 40.51762 | -0.6916 | 16.11029 |
July | 338.00000 | 23.81782 | 44.34686 | -0.4933 | 10.43235 |
August | 348.00000 | 23.84419 | 47.24799 | -0.4547 | 9.59647 |
September | 330.00000 | 23.21125 | 46.89773 | -0.7008 | 17.10405 |
October | 340.00000 | 21.83515 | 40.79820 | -0.1526 | 6.72985 |
November | 330.00000 | 21.17215 | 39.09894 | -0.3935 | 8.69710 |
December | 338.00000 | 21.08069 | 32.24333 | -0.5041 | 10.43998 |
Annual Sum or Average | 4030.00000 | 22.15288 | 38.74683 | -0.5102 | 12.27222 |
Minimum of Months | 308.00000 | 21.07277 | 30.46881 | -1.0480 | 6.72985 |
Maximum of Months | 348.00000 | 23.84419 | 47.24799 | -0.1526 | 30.24470 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06161 | 30.38532 | -0.5466 | 11.44347 |
February | 308.00000 | 21.11365 | 31.95299 | -0.4890 | 10.40097 |
March | 348.00000 | 21.14255 | 32.94510 | -0.4318 | 9.21136 |
April | 330.00000 | 21.66221 | 36.76822 | -0.2585 | 7.68497 |
May | 344.00000 | 22.46783 | 40.71580 | -1.0596 | 30.76364 |
June | 336.00000 | 23.45282 | 40.62061 | -0.7066 | 16.56805 |
July | 338.00000 | 23.82167 | 44.49845 | -0.5166 | 10.95201 |
August | 348.00000 | 23.84386 | 47.49987 | -0.4778 | 10.06546 |
September | 330.00000 | 23.27983 | 46.64312 | -0.7109 | 17.35367 |
October | 340.00000 | 21.87812 | 40.63222 | -0.1649 | 6.94739 |
November | 330.00000 | 21.16191 | 38.95443 | -0.4096 | 9.04186 |
December | 338.00000 | 21.06153 | 32.17178 | -0.5162 | 10.74821 |
Annual Sum or Average | 4030.00000 | 22.17163 | 38.69289 | -0.5248 | 12.62916 |
Minimum of Months | 308.00000 | 21.06153 | 30.38532 | -1.0596 | 6.94739 |
Maximum of Months | 348.00000 | 23.84386 | 47.49987 | -0.1649 | 30.76364 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06159 | 30.38593 | -0.5515 | 11.55924 |
February | 308.00000 | 21.10945 | 31.96352 | -0.4958 | 10.53322 |
March | 348.00000 | 21.13499 | 32.96149 | -0.4403 | 9.36166 |
April | 330.00000 | 21.62967 | 36.84172 | -0.2717 | 7.81336 |
May | 344.00000 | 22.39719 | 40.88988 | -1.0891 | 32.08606 |
June | 336.00000 | 23.40274 | 40.75274 | -0.7291 | 17.36554 |
July | 338.00000 | 23.80514 | 44.56852 | -0.5276 | 11.23915 |
August | 348.00000 | 23.83325 | 47.56331 | -0.4863 | 10.26672 |
September | 330.00000 | 23.22840 | 46.81138 | -0.7321 | 18.11646 |
October | 340.00000 | 21.83431 | 40.73295 | -0.1799 | 7.01522 |
November | 330.00000 | 21.15553 | 38.97553 | -0.4171 | 9.16422 |
December | 338.00000 | 21.06152 | 32.17240 | -0.5218 | 10.87033 |
Annual Sum or Average | 4030.00000 | 22.14706 | 38.76247 | -0.5377 | 12.98181 |
Minimum of Months | 308.00000 | 21.06152 | 30.38593 | -1.0891 | 7.01522 |
Maximum of Months | 348.00000 | 23.83325 | 47.56331 | -0.1799 | 32.08606 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06167 | 30.38598 | -0.5649 | 11.87960 |
February | 308.00000 | 21.10085 | 31.98413 | -0.5119 | 10.86626 |
March | 348.00000 | 21.12158 | 32.99018 | -0.4575 | 9.67738 |
April | 330.00000 | 21.56785 | 36.98424 | -0.2971 | 8.08147 |
May | 344.00000 | 22.25994 | 41.23311 | -1.1460 | 34.70076 |
June | 336.00000 | 23.29392 | 41.04465 | -0.7745 | 19.06647 |
July | 338.00000 | 23.76645 | 44.75189 | -0.5491 | 11.84253 |
August | 348.00000 | 23.80932 | 47.73276 | -0.5011 | 10.65011 |
September | 330.00000 | 23.11848 | 47.17531 | -0.7746 | 19.72204 |
October | 340.00000 | 21.75241 | 40.92168 | -0.2075 | 7.15440 |
November | 330.00000 | 21.14480 | 39.01106 | -0.4314 | 9.41010 |
December | 338.00000 | 21.06094 | 32.17395 | -0.5346 | 11.16126 |
Annual Sum or Average | 4030.00000 | 22.09725 | 38.91060 | -0.5634 | 13.71998 |
Minimum of Months | 308.00000 | 21.06094 | 30.38598 | -1.1460 | 7.15440 |
Maximum of Months | 348.00000 | 23.80932 | 47.73276 | -0.2075 | 34.70076 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.06101 | 30.31280 | -0.6186 | 13.24918 |
February | 308.00000 | 21.08880 | 31.93940 | -0.5685 | 12.17689 |
March | 348.00000 | 21.10113 | 32.98213 | -0.5131 | 10.81588 |
April | 330.00000 | 21.47370 | 37.15606 | -0.3557 | 8.88127 |
May | 344.00000 | 22.03346 | 41.74276 | -1.2570 | 40.01458 |
June | 336.00000 | 23.07470 | 41.59341 | -0.8675 | 22.81731 |
July | 338.00000 | 23.65407 | 45.16157 | -0.6036 | 13.59121 |
August | 348.00000 | 23.73378 | 48.15114 | -0.5377 | 11.75933 |
September | 330.00000 | 22.89734 | 47.83807 | -0.8631 | 23.35440 |
October | 340.00000 | 21.61252 | 41.17935 | -0.2671 | 7.67654 |
November | 330.00000 | 21.12925 | 38.96099 | -0.4764 | 10.29296 |
December | 338.00000 | 21.06141 | 32.10221 | -0.5839 | 12.34317 |
Annual Sum or Average | 4030.00000 | 22.00209 | 39.14002 | -0.6269 | 15.62117 |
Minimum of Months | 308.00000 | 21.06101 | 30.31280 | -1.2570 | 7.67654 |
Maximum of Months | 348.00000 | 23.73378 | 48.15114 | -0.2671 | 40.01458 |
Report: DXReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 565.09 | 159.73 | 1.00 | 565.09 | 0.00 | 0.00 | 0.00 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 | 0.37 | 18-MAR-16:10 | 0.37 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 | 0.10 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.562439E+09 | 0.146459E+09 | 42.33 | 0.535002E+09 | 27436765.29 | 0.00 | 0.81 | 27-APR-16:10 | 0.00 | 01-APR-00:05 | 10279.65 | 27-APR-16:10 | 9819.05 | 27-APR-16:10 | 769.18 | 29-APR-17:10 | 2555.94 | 27-APR-16:10 | 0.00 | 01-APR-00:05 |
May | 0.136366E+10 | 0.343638E+09 | 98.98 | 0.118977E+10 | 0.173882E+09 | 0.00 | 0.78 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 10062.03 | 06-MAY-13:00 | 8706.51 | 15-MAY-17:00 | 2128.79 | 06-MAY-12:50 | 2384.62 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.269405E+10 | 0.678818E+09 | 222.92 | 0.248838E+10 | 0.205665E+09 | 0.00 | 0.91 | 28-JUN-08:63 | 0.00 | 01-JUN-00:10 | 11861.43 | 28-JUN-17:00 | 11438.37 | 28-JUN-17:00 | 1995.80 | 28-JUN-08:63 | 2846.15 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.689188E+10 | 0.168307E+10 | 356.75 | 0.586429E+10 | 0.102759E+10 | 0.00 | 1.00 | 24-JUL-08:62 | 0.00 | 01-JUL-00:05 | 28009.71 | 31-JUL-08:62 | 23016.03 | 24-JUL-08:62 | 7168.22 | 31-JUL-08:62 | 5958.22 | 31-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.925248E+10 | 0.224423E+10 | 381.14 | 0.789134E+10 | 0.136113E+10 | 0.00 | 1.00 | 08-AUG-08:62 | 0.00 | 01-AUG-00:10 | 28077.41 | 30-AUG-08:62 | 25312.00 | 09-AUG-08:62 | 11724.26 | 30-AUG-08:62 | 5965.39 | 10-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.295000E+10 | 0.716732E+09 | 198.67 | 0.236345E+10 | 0.586542E+09 | 0.00 | 0.93 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 | 16119.94 | 14-SEP-08:63 | 10646.29 | 14-SEP-17:00 | 6020.48 | 14-SEP-08:63 | 3435.89 | 14-SEP-08:63 | 0.00 | 01-SEP-00:10 |
October | 0.161838E+09 | 41772689.43 | 45.58 | 0.158087E+09 | 3750472.19 | 0.00 | 0.54 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 6023.82 | 04-OCT-15:00 | 6023.82 | 04-OCT-15:00 | 528.14 | 08-OCT-14:00 | 1487.84 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 20346040.29 | 5521305.20 | 4.50 | 15058444.97 | 5287595.32 | 0.00 | 0.23 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2475.07 | 04-NOV-14:00 | 1850.40 | 04-NOV-14:00 | 624.67 | 04-NOV-14:00 | 663.16 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.238967E+11 | 0.586024E+10 | 1351.88 | 0.205054E+11 | 0.339129E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.925248E+10 | 0.224423E+10 | 381.14 | 0.789134E+10 | 0.136113E+10 | 0.00 | 1.00 | 0.00 | 28077.41 | 25312.00 | 11724.26 | 5965.39 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 40912942.04 | 10458833.01 | 21.92 | 40537136.39 | 375805.65 | 0.00 | 0.28 | 27-FEB-21:20 | 0.00 | 01-FEB-00:10 | 1682.12 | 27-FEB-15:00 | 1682.12 | 27-FEB-15:00 | 30.75 | 25-FEB-23:00 | 389.91 | 27-FEB-21:20 | 0.00 | 01-FEB-00:10 |
March | 86124889.83 | 22489343.15 | 49.33 | 85156816.15 | 968073.68 | 0.00 | 0.30 | 18-MAR-18:10 | 0.00 | 01-MAR-00:10 | 1671.11 | 18-MAR-17:10 | 1671.11 | 18-MAR-17:10 | 86.84 | 10-MAR-21:30 | 413.09 | 18-MAR-18:10 | 0.00 | 01-MAR-00:10 |
April | 0.944412E+09 | 0.223496E+09 | 156.56 | 0.922518E+09 | 21894153.67 | 0.00 | 0.85 | 27-APR-15:00 | 0.00 | 01-APR-00:05 | 6608.21 | 27-APR-15:00 | 6448.24 | 27-APR-15:00 | 820.09 | 30-APR-07:02 | 1417.73 | 27-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.225135E+10 | 0.516470E+09 | 288.78 | 0.213273E+10 | 0.118623E+09 | 0.00 | 0.80 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 10295.23 | 07-MAY-07:02 | 8375.96 | 07-MAY-07:02 | 1919.27 | 07-MAY-07:02 | 1957.90 | 07-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.398742E+10 | 0.899190E+09 | 399.56 | 0.387107E+10 | 0.116350E+09 | 0.00 | 0.87 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 12530.72 | 11-JUN-07:02 | 11183.34 | 11-JUN-07:02 | 1347.38 | 11-JUN-07:02 | 2432.22 | 11-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.643832E+10 | 0.140302E+10 | 461.04 | 0.594664E+10 | 0.491684E+09 | 0.00 | 1.00 | 16-JUL-07:02 | 0.00 | 01-JUL-00:05 | 15576.91 | 31-JUL-08:62 | 13702.39 | 24-JUL-08:62 | 3120.63 | 16-JUL-07:02 | 3055.66 | 24-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.744319E+10 | 0.160927E+10 | 459.92 | 0.676107E+10 | 0.682126E+09 | 0.00 | 1.00 | 09-AUG-08:62 | 0.00 | 01-AUG-00:10 | 15623.80 | 25-AUG-08:62 | 14528.01 | 09-AUG-08:62 | 3383.35 | 25-AUG-08:62 | 3057.15 | 10-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.402279E+10 | 0.893955E+09 | 375.08 | 0.364430E+10 | 0.378492E+09 | 0.00 | 1.00 | 03-SEP-07:02 | 0.00 | 01-SEP-00:10 | 15011.12 | 03-SEP-07:02 | 12962.32 | 03-SEP-07:02 | 3049.37 | 24-SEP-07:02 | 2949.37 | 03-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.111415E+10 | 0.266450E+09 | 213.01 | 0.108630E+10 | 27841723.35 | 0.00 | 0.67 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4772.30 | 04-OCT-15:00 | 4772.30 | 04-OCT-15:00 | 556.91 | 01-OCT-13:50 | 990.06 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.189111E+09 | 46670974.52 | 42.67 | 0.166073E+09 | 23038330.64 | 0.00 | 0.52 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3778.34 | 04-NOV-14:00 | 3171.96 | 04-NOV-14:00 | 610.63 | 04-NOV-13:40 | 812.61 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 25150.11 | 7050.22 | 0.50 | 25150.11 | 0.00 | 0.00 | 0.01 | 03-DEC-21:00 | 0.00 | 01-DEC-00:03 | 25.40 | 03-DEC-21:00 | 25.40 | 03-DEC-21:00 | 0.00 | 01-DEC-00:03 | 7.12 | 03-DEC-21:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.265178E+11 | 0.589148E+10 | 2468.36 | 0.246564E+11 | 0.186139E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.744319E+10 | 0.160927E+10 | 461.04 | 0.676107E+10 | 0.682126E+09 | 0.00 | 1.00 | 0.00 | 15623.80 | 14528.01 | 3383.35 | 3057.15 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 256.47 | 63.40 | 1.50 | 256.47 | 0.00 | 0.00 | 0.00 | 27-FEB-13:50 | 0.00 | 01-FEB-00:10 | 0.14 | 27-FEB-13:50 | 0.14 | 27-FEB-13:50 | 0.00 | 27-FEB-13:50 | 0.03 | 27-FEB-13:50 | 0.00 | 01-FEB-00:10 |
March | 5329.20 | 1314.08 | 4.50 | 5329.20 | 0.00 | 0.00 | 0.00 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 1.47 | 18-MAR-14:00 | 1.47 | 18-MAR-14:00 | 0.00 | 18-MAR-13:40 | 0.36 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.341316E+09 | 76929401.03 | 37.64 | 0.333448E+09 | 7867454.23 | 0.00 | 0.93 | 28-APR-07:03 | 0.00 | 01-APR-00:05 | 7858.96 | 28-APR-07:03 | 6429.13 | 27-APR-15:00 | 2273.24 | 28-APR-07:03 | 1485.56 | 28-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.708494E+09 | 0.156192E+09 | 107.70 | 0.645367E+09 | 63126104.10 | 0.00 | 1.00 | 06-MAY-07:03 | 0.00 | 01-MAY-00:10 | 16758.55 | 07-MAY-08:62 | 12154.21 | 05-MAY-07:03 | 5013.78 | 08-MAY-07:02 | 3292.40 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.126014E+10 | 0.278278E+09 | 204.41 | 0.121143E+10 | 48711082.11 | 0.00 | 1.00 | 10-JUN-07:02 | 0.00 | 01-JUN-00:10 | 16566.35 | 12-JUN-07:02 | 13590.00 | 10-JUN-07:02 | 5288.76 | 12-JUN-07:02 | 3255.03 | 12-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.301417E+10 | 0.651157E+09 | 254.68 | 0.269662E+10 | 0.317558E+09 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 17066.57 | 31-JUL-07:02 | 13732.95 | 20-JUL-07:02 | 6218.06 | 11-JUL-07:02 | 3347.71 | 31-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.422872E+10 | 0.906216E+09 | 283.44 | 0.377576E+10 | 0.452954E+09 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 17150.68 | 30-AUG-07:02 | 13971.50 | 09-AUG-07:02 | 7253.20 | 30-AUG-07:03 | 3361.80 | 30-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.131207E+10 | 0.280425E+09 | 158.43 | 0.110513E+10 | 0.206935E+09 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 16581.81 | 01-SEP-07:02 | 12299.75 | 04-SEP-08:62 | 7027.78 | 25-SEP-07:03 | 3258.12 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 68337089.47 | 15323051.94 | 54.09 | 66772002.70 | 1565086.77 | 0.00 | 0.99 | 05-OCT-07:02 | 0.00 | 01-OCT-00:10 | 8472.67 | 05-OCT-07:02 | 7925.97 | 05-OCT-07:02 | 2073.20 | 06-OCT-07:03 | 1572.95 | 05-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 15224300.95 | 3579927.26 | 5.89 | 11875384.40 | 3348916.56 | 0.00 | 0.25 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 1824.40 | 04-NOV-14:00 | 1439.05 | 04-NOV-14:00 | 385.34 | 04-NOV-14:00 | 423.86 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.109485E+11 | 0.236810E+10 | 1112.27 | 0.984641E+10 | 0.110207E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.422872E+10 | 0.906216E+09 | 283.44 | 0.377576E+10 | 0.452954E+09 | 0.00 | 1.00 | 0.00 | 17150.68 | 13971.50 | 7253.20 | 3361.80 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 136.57 | 33.77 | 1.00 | 136.57 | 0.00 | 0.00 | 0.00 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 0.05 | 27-FEB-15:00 | 0.05 | 27-FEB-15:00 | 0.00 | 27-FEB-14:10 | 0.01 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 4704.18 | 1159.89 | 4.00 | 4704.18 | 0.00 | 0.00 | 0.00 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 1.33 | 18-MAR-14:00 | 1.33 | 18-MAR-14:00 | 0.00 | 18-MAR-15:50 | 0.33 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.326793E+09 | 73937812.02 | 36.60 | 0.319404E+09 | 7389434.21 | 0.00 | 0.77 | 27-APR-15:00 | 0.00 | 01-APR-00:05 | 6426.78 | 27-APR-15:00 | 6283.03 | 27-APR-15:00 | 1769.56 | 28-APR-07:03 | 1415.98 | 27-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.684034E+09 | 0.150993E+09 | 101.97 | 0.623255E+09 | 60778670.19 | 0.00 | 1.00 | 06-MAY-07:03 | 0.00 | 01-MAY-00:10 | 16681.62 | 07-MAY-08:62 | 12074.18 | 06-MAY-07:03 | 4773.12 | 07-MAY-08:62 | 3277.29 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.123732E+10 | 0.273386E+09 | 202.99 | 0.119008E+10 | 47238345.31 | 0.00 | 1.00 | 10-JUN-07:02 | 0.00 | 01-JUN-00:10 | 16490.42 | 12-JUN-07:02 | 13520.98 | 10-JUN-07:02 | 5270.28 | 12-JUN-07:02 | 3240.11 | 12-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.299835E+10 | 0.647585E+09 | 253.91 | 0.268225E+10 | 0.316095E+09 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 16990.49 | 31-JUL-07:02 | 13668.61 | 20-JUL-07:02 | 6193.38 | 11-JUL-07:02 | 3332.77 | 31-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.421668E+10 | 0.903374E+09 | 283.14 | 0.376484E+10 | 0.451839E+09 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 17073.69 | 30-AUG-07:02 | 13911.94 | 09-AUG-07:02 | 7220.40 | 30-AUG-07:03 | 3346.70 | 30-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.129628E+10 | 0.277095E+09 | 157.55 | 0.109231E+10 | 0.203971E+09 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 16506.65 | 01-SEP-07:02 | 11947.31 | 11-SEP-07:02 | 6889.23 | 24-SEP-08:62 | 3243.35 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 63994114.77 | 14409658.63 | 50.16 | 62854669.06 | 1139445.71 | 0.00 | 0.90 | 05-OCT-07:02 | 0.00 | 01-OCT-00:10 | 7450.37 | 05-OCT-07:02 | 6965.82 | 05-OCT-07:02 | 1699.32 | 06-OCT-07:03 | 1424.16 | 05-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 12132354.03 | 2873560.59 | 5.17 | 9475887.13 | 2656466.90 | 0.00 | 0.21 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 1557.46 | 04-NOV-14:00 | 1227.77 | 04-NOV-14:00 | 329.69 | 04-NOV-14:00 | 365.03 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.108356E+11 | 0.234365E+10 | 1096.49 | 0.974447E+10 | 0.109111E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.421668E+10 | 0.903374E+09 | 283.14 | 0.376484E+10 | 0.451839E+09 | 0.00 | 1.00 | 0.00 | 17073.69 | 13911.94 | 7220.40 | 3346.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 84.32 | 20.85 | 0.50 | 84.32 | 0.00 | 0.00 | 0.00 | 27-FEB-14:40 | 0.00 | 01-FEB-00:10 | 0.08 | 27-FEB-14:40 | 0.08 | 27-FEB-14:40 | 0.00 | 01-FEB-00:10 | 0.02 | 27-FEB-14:40 | 0.00 | 01-FEB-00:10 |
March | 3487.88 | 859.81 | 3.33 | 3487.88 | 0.00 | 0.00 | 0.00 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 1.00 | 18-MAR-14:00 | 1.00 | 18-MAR-14:00 | 0.00 | 18-MAR-14:20 | 0.25 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.293054E+09 | 67001225.92 | 31.54 | 0.286838E+09 | 6216562.50 | 0.00 | 0.73 | 27-APR-15:00 | 0.00 | 01-APR-00:05 | 6041.66 | 27-APR-15:00 | 5901.07 | 27-APR-15:00 | 291.14 | 29-APR-15:00 | 1345.42 | 27-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.603280E+09 | 0.133980E+09 | 88.11 | 0.549868E+09 | 53412662.38 | 0.00 | 1.00 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 | 16596.94 | 07-MAY-08:62 | 11810.11 | 07-MAY-08:62 | 4786.83 | 07-MAY-08:62 | 3260.71 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.113785E+10 | 0.252451E+09 | 193.77 | 0.109572E+10 | 42128330.94 | 0.00 | 1.00 | 10-JUN-07:02 | 0.00 | 01-JUN-00:10 | 16406.25 | 12-JUN-07:02 | 13408.78 | 10-JUN-07:02 | 5277.87 | 12-JUN-07:02 | 3223.55 | 12-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.286132E+10 | 0.620097E+09 | 249.73 | 0.255976E+10 | 0.301560E+09 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 16906.04 | 31-JUL-07:02 | 13569.77 | 20-JUL-07:02 | 6193.87 | 11-JUL-07:02 | 3316.32 | 31-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.405096E+10 | 0.870330E+09 | 279.42 | 0.361941E+10 | 0.431555E+09 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 16988.55 | 30-AUG-07:02 | 13812.38 | 09-AUG-07:02 | 7212.45 | 30-AUG-07:03 | 3330.16 | 30-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.120788E+10 | 0.259084E+09 | 142.22 | 0.101907E+10 | 0.188814E+09 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 16423.94 | 01-SEP-07:02 | 11857.53 | 11-SEP-07:02 | 6128.89 | 14-SEP-07:02 | 3227.08 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 51876588.27 | 11781454.03 | 41.70 | 51572762.97 | 303825.30 | 0.00 | 0.50 | 05-OCT-07:02 | 0.00 | 01-OCT-00:10 | 3625.91 | 05-OCT-07:02 | 3380.13 | 05-OCT-07:02 | 288.41 | 06-OCT-07:03 | 782.88 | 05-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 6907731.97 | 1659032.69 | 3.67 | 5407246.45 | 1500485.52 | 0.00 | 0.15 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 1059.96 | 04-NOV-14:00 | 833.86 | 04-NOV-14:00 | 226.11 | 04-NOV-14:00 | 252.67 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.102131E+11 | 0.221639E+10 | 1033.99 | 0.918764E+10 | 0.102549E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.405096E+10 | 0.870330E+09 | 279.42 | 0.361941E+10 | 0.431555E+09 | 0.00 | 1.00 | 0.00 | 16988.55 | 13812.38 | 7212.45 | 3330.16 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.353156E+09 | 93908782.65 | 25.00 | 0.335062E+09 | 18094024.32 | 0.00 | 0.74 | 27-APR-15:00 | 0.00 | 01-APR-00:05 | 8804.04 | 27-APR-15:00 | 8214.73 | 27-APR-15:00 | 669.85 | 29-APR-15:00 | 2240.70 | 27-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.744464E+09 | 0.191421E+09 | 61.33 | 0.650272E+09 | 94192617.26 | 0.00 | 0.71 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 8675.90 | 06-MAY-13:30 | 7002.04 | 06-MAY-13:50 | 1823.82 | 06-MAY-12:50 | 2097.09 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.164994E+10 | 0.422478E+09 | 136.47 | 0.153309E+10 | 0.116847E+09 | 0.00 | 0.84 | 28-JUN-08:63 | 0.00 | 01-JUN-00:10 | 10190.21 | 28-JUN-17:00 | 9749.14 | 28-JUN-17:00 | 1651.30 | 28-JUN-08:63 | 2502.93 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.455435E+10 | 0.112579E+10 | 237.22 | 0.388777E+10 | 0.666585E+09 | 0.00 | 1.00 | 23-JUL-09:02 | 0.00 | 01-JUL-00:05 | 26825.98 | 31-JUL-08:62 | 22289.28 | 24-JUL-08:62 | 6866.47 | 31-JUL-08:62 | 5706.46 | 31-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.652405E+10 | 0.159386E+10 | 271.33 | 0.558493E+10 | 0.939126E+09 | 0.00 | 1.00 | 08-AUG-08:62 | 0.00 | 01-AUG-00:10 | 26893.75 | 30-AUG-08:62 | 24051.14 | 09-AUG-08:62 | 11291.22 | 30-AUG-08:62 | 5711.79 | 10-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.192855E+10 | 0.471917E+09 | 109.47 | 0.154291E+10 | 0.385643E+09 | 0.00 | 0.91 | 13-SEP-08:63 | 0.00 | 01-SEP-00:10 | 13945.50 | 14-SEP-08:63 | 9249.40 | 12-SEP-14:10 | 5307.97 | 14-SEP-08:63 | 2973.13 | 14-SEP-08:63 | 0.00 | 01-SEP-00:10 |
October | 74322842.05 | 19384392.25 | 16.33 | 73636091.29 | 686750.76 | 0.00 | 0.44 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4577.48 | 04-OCT-15:00 | 4577.48 | 04-OCT-15:00 | 220.92 | 08-OCT-14:10 | 1163.17 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 5074377.68 | 1411054.42 | 2.33 | 3756239.25 | 1318138.43 | 0.00 | 0.10 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 983.97 | 04-NOV-14:30 | 731.00 | 04-NOV-14:30 | 252.98 | 04-NOV-14:30 | 272.62 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.158339E+11 | 0.392017E+10 | 859.49 | 0.136114E+11 | 0.222249E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.652405E+10 | 0.159386E+10 | 271.33 | 0.558493E+10 | 0.939126E+09 | 0.00 | 1.00 | 0.00 | 26893.75 | 24051.14 | 11291.22 | 5711.79 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 60833.73 | 14920.97 | 0.17 | 60833.73 | 0.00 | 0.00 | 0.02 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 101.39 | 18-MAR-16:00 | 101.39 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 24.87 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.231386E+09 | 53458328.03 | 29.50 | 0.223985E+09 | 7401633.09 | 0.00 | 0.73 | 27-APR-15:00 | 0.00 | 01-APR-00:05 | 4830.77 | 27-APR-15:00 | 4637.31 | 27-APR-15:00 | 275.01 | 29-APR-14:10 | 1075.40 | 27-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.565516E+09 | 0.126863E+09 | 73.00 | 0.514934E+09 | 50582650.16 | 0.00 | 0.70 | 06-MAY-13:40 | 0.00 | 01-MAY-00:10 | 4712.26 | 06-MAY-13:40 | 3989.92 | 06-MAY-14:10 | 771.60 | 06-MAY-13:10 | 997.74 | 06-MAY-13:40 | 0.00 | 01-MAY-00:10 |
June | 0.131782E+10 | 0.295204E+09 | 183.33 | 0.126819E+10 | 49628806.35 | 0.00 | 0.81 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5521.56 | 28-JUN-17:00 | 5451.01 | 28-JUN-17:00 | 335.97 | 21-JUN-17:00 | 1189.75 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.307227E+10 | 0.666098E+09 | 273.79 | 0.276429E+10 | 0.307988E+09 | 0.00 | 1.00 | 24-JUL-08:62 | 0.00 | 01-JUL-00:05 | 13787.81 | 31-JUL-08:62 | 12103.54 | 24-JUL-08:62 | 2794.86 | 31-JUL-08:62 | 2702.83 | 31-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.408125E+10 | 0.878330E+09 | 301.14 | 0.362886E+10 | 0.452390E+09 | 0.00 | 1.00 | 10-AUG-08:62 | 0.00 | 01-AUG-00:10 | 13800.78 | 10-AUG-08:62 | 10990.55 | 10-AUG-08:62 | 2810.23 | 10-AUG-08:62 | 2703.74 | 10-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.141228E+10 | 0.304045E+09 | 147.50 | 0.122367E+10 | 0.188603E+09 | 0.00 | 0.86 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 6099.42 | 14-SEP-14:10 | 5172.95 | 12-SEP-14:10 | 1277.71 | 14-SEP-13:00 | 1228.41 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 0.116533E+09 | 26630240.20 | 28.83 | 0.114772E+09 | 1760808.32 | 0.00 | 0.52 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3157.30 | 04-OCT-15:00 | 3157.30 | 04-OCT-15:00 | 150.46 | 08-OCT-14:00 | 684.24 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 15525698.23 | 3628754.98 | 4.00 | 12422600.66 | 3103097.57 | 0.00 | 0.26 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 1568.55 | 04-NOV-14:30 | 1265.46 | 04-NOV-14:30 | 303.20 | 04-NOV-14:10 | 362.23 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.108126E+11 | 0.235427E+10 | 1041.26 | 0.975119E+10 | 0.106146E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.408125E+10 | 0.878330E+09 | 301.14 | 0.362886E+10 | 0.452390E+09 | 0.00 | 1.00 | 0.00 | 13800.78 | 12103.54 | 2810.23 | 2703.74 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.217633E+09 | 50432757.13 | 28.00 | 0.210563E+09 | 7070206.19 | 0.00 | 0.72 | 27-APR-15:00 | 0.00 | 01-APR-00:05 | 4707.77 | 27-APR-15:00 | 4512.16 | 27-APR-15:00 | 267.06 | 29-APR-14:40 | 1051.20 | 27-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.526135E+09 | 0.118404E+09 | 71.17 | 0.478082E+09 | 48053815.70 | 0.00 | 0.68 | 06-MAY-13:40 | 0.00 | 01-MAY-00:10 | 4579.54 | 06-MAY-13:40 | 3868.81 | 06-MAY-14:10 | 759.67 | 06-MAY-13:10 | 972.92 | 06-MAY-13:40 | 0.00 | 01-MAY-00:10 |
June | 0.123210E+10 | 0.276485E+09 | 175.67 | 0.118530E+10 | 46803591.18 | 0.00 | 0.81 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5439.53 | 28-JUN-17:00 | 5361.77 | 28-JUN-17:00 | 334.81 | 21-JUN-17:00 | 1173.52 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.296335E+10 | 0.643259E+09 | 269.29 | 0.266112E+10 | 0.302232E+09 | 0.00 | 1.00 | 24-JUL-08:62 | 0.00 | 01-JUL-00:05 | 13411.28 | 24-JUL-08:62 | 11948.11 | 24-JUL-08:62 | 2578.29 | 31-JUL-08:62 | 2665.06 | 24-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.397432E+10 | 0.856008E+09 | 297.95 | 0.352888E+10 | 0.445443E+09 | 0.00 | 1.00 | 10-AUG-08:62 | 0.00 | 01-AUG-00:10 | 13675.54 | 10-AUG-08:62 | 10850.83 | 10-AUG-08:62 | 2824.71 | 10-AUG-08:62 | 2679.36 | 10-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.134713E+10 | 0.290277E+09 | 141.67 | 0.116388E+10 | 0.183257E+09 | 0.00 | 0.85 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 6006.48 | 14-SEP-14:10 | 5075.75 | 12-SEP-14:10 | 1269.26 | 14-SEP-13:00 | 1211.36 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 0.100816E+09 | 23077161.29 | 26.67 | 99345713.91 | 1470482.38 | 0.00 | 0.50 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3009.95 | 04-OCT-15:00 | 3009.95 | 04-OCT-15:00 | 140.35 | 08-OCT-14:10 | 655.53 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 13919330.13 | 3263437.16 | 3.83 | 11108949.16 | 2810380.97 | 0.00 | 0.25 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 1469.23 | 04-NOV-14:30 | 1181.76 | 04-NOV-14:30 | 287.76 | 04-NOV-14:20 | 340.51 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.103754E+11 | 0.226121E+10 | 1014.24 | 0.933827E+10 | 0.103714E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.397432E+10 | 0.856008E+09 | 297.95 | 0.352888E+10 | 0.445443E+09 | 0.00 | 1.00 | 0.00 | 13675.54 | 11948.11 | 2824.71 | 2679.36 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.194352E+09 | 45327064.61 | 25.83 | 0.188080E+09 | 6271991.45 | 0.00 | 0.69 | 27-APR-15:00 | 0.00 | 01-APR-00:05 | 4490.42 | 27-APR-15:00 | 4302.25 | 27-APR-15:00 | 246.18 | 29-APR-15:00 | 1009.35 | 27-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.457735E+09 | 0.103639E+09 | 66.83 | 0.415285E+09 | 42449954.77 | 0.00 | 0.66 | 06-MAY-13:40 | 0.00 | 01-MAY-00:10 | 4335.91 | 06-MAY-13:40 | 3660.04 | 06-MAY-14:10 | 727.55 | 06-MAY-13:10 | 928.12 | 06-MAY-13:40 | 0.00 | 01-MAY-00:10 |
June | 0.108670E+10 | 0.244709E+09 | 158.00 | 0.104685E+10 | 39851461.62 | 0.00 | 0.80 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5289.74 | 28-JUN-17:00 | 5213.58 | 28-JUN-17:00 | 322.93 | 21-JUN-17:00 | 1145.45 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.276307E+10 | 0.601373E+09 | 259.44 | 0.247862E+10 | 0.284452E+09 | 0.00 | 1.00 | 24-JUL-08:62 | 0.00 | 01-JUL-00:05 | 13276.87 | 24-JUL-08:62 | 11773.30 | 24-JUL-08:62 | 2027.16 | 31-JUL-08:62 | 2638.67 | 24-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.378720E+10 | 0.817017E+09 | 290.90 | 0.336299E+10 | 0.424204E+09 | 0.00 | 1.00 | 10-AUG-08:62 | 0.00 | 01-AUG-00:10 | 13541.79 | 10-AUG-08:62 | 10697.34 | 10-AUG-08:62 | 2844.45 | 10-AUG-08:62 | 2653.43 | 10-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.123911E+10 | 0.267463E+09 | 129.67 | 0.106791E+10 | 0.171195E+09 | 0.00 | 0.84 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 5881.37 | 14-SEP-14:10 | 4938.67 | 12-SEP-14:10 | 1250.87 | 14-SEP-13:00 | 1189.03 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 75550319.61 | 17325777.40 | 20.33 | 74648396.22 | 901923.39 | 0.00 | 0.47 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2749.38 | 04-OCT-15:00 | 2749.38 | 04-OCT-15:00 | 113.67 | 08-OCT-14:10 | 604.70 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 11242151.93 | 2651463.18 | 3.33 | 8958596.21 | 2283555.72 | 0.00 | 0.22 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 1284.86 | 04-NOV-14:40 | 1032.26 | 04-NOV-14:40 | 253.93 | 04-NOV-14:30 | 299.96 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.961495E+10 | 0.209951E+10 | 954.34 | 0.864334E+10 | 0.971611E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.378720E+10 | 0.817017E+09 | 290.90 | 0.336299E+10 | 0.424204E+09 | 0.00 | 1.00 | 0.00 | 13541.79 | 11773.30 | 2844.45 | 2653.43 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.165702E+09 | 39023171.62 | 23.17 | 0.160852E+09 | 4849532.35 | 0.00 | 0.66 | 27-APR-15:00 | 0.00 | 01-APR-00:05 | 4304.80 | 27-APR-15:00 | 4138.38 | 27-APR-15:00 | 199.09 | 29-APR-15:00 | 976.38 | 27-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.377535E+09 | 86195659.61 | 59.83 | 0.343721E+09 | 33814250.90 | 0.00 | 0.63 | 06-MAY-13:40 | 0.00 | 01-MAY-00:10 | 4131.37 | 06-MAY-13:30 | 3477.19 | 06-MAY-13:50 | 689.01 | 06-MAY-13:10 | 892.52 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.940772E+09 | 0.213024E+09 | 137.67 | 0.909395E+09 | 31376815.52 | 0.00 | 0.76 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 5072.21 | 28-JUN-17:00 | 5019.62 | 28-JUN-17:00 | 289.41 | 21-JUN-17:00 | 1109.75 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.251865E+10 | 0.550265E+09 | 240.31 | 0.226937E+10 | 0.249280E+09 | 0.00 | 1.00 | 31-JUL-13:30 | 0.00 | 01-JUL-00:05 | 10555.34 | 24-JUL-08:62 | 9342.23 | 24-JUL-08:62 | 1243.99 | 31-JUL-08:62 | 2060.22 | 24-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.359099E+10 | 0.774946E+09 | 271.35 | 0.320610E+10 | 0.384889E+09 | 0.00 | 1.00 | 13-AUG-15:20 | 0.00 | 01-AUG-00:10 | 11597.35 | 10-AUG-08:62 | 9200.86 | 10-AUG-08:62 | 2396.49 | 10-AUG-08:62 | 2245.91 | 10-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.114495E+10 | 0.247618E+09 | 116.33 | 0.988368E+09 | 0.156582E+09 | 0.00 | 0.83 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 5842.37 | 14-SEP-14:10 | 4911.38 | 14-SEP-14:10 | 1244.00 | 14-SEP-13:00 | 1185.48 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 51471584.64 | 11824454.95 | 14.00 | 51162449.75 | 309134.89 | 0.00 | 0.41 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2419.35 | 04-OCT-15:00 | 2419.35 | 04-OCT-15:00 | 62.73 | 08-OCT-14:10 | 540.37 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 8181560.99 | 1946782.41 | 3.00 | 6543363.18 | 1638197.81 | 0.00 | 0.18 | 04-NOV-14:50 | 0.00 | 01-NOV-00:10 | 1049.60 | 04-NOV-14:50 | 845.93 | 04-NOV-14:50 | 204.52 | 04-NOV-14:30 | 247.64 | 04-NOV-14:50 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.879825E+10 | 0.192484E+10 | 865.66 | 0.793551E+10 | 0.862739E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.359099E+10 | 0.774946E+09 | 271.35 | 0.320610E+10 | 0.384889E+09 | 0.00 | 1.00 | 0.00 | 11597.35 | 9342.23 | 2396.49 | 2245.91 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.45 | 71.57 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 76.55 | 62.52 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 81.50 | 52.98 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 80.35 | 43.73 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 66.11 | 38.03 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 56.93 | 31.41 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 68.93 | 28.57 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.50 | 27.75 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 99.14 | 38.54 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 92.54 | 48.72 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 48.13 | 58.59 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 53.19 | 72.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 71.06 | 47.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.45 | 27.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 99.14 | 72.48 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.45 | 71.57 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 76.55 | 62.52 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 81.50 | 52.98 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 80.35 | 43.73 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 66.11 | 38.03 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 56.93 | 31.41 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 68.93 | 28.57 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.50 | 27.75 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 99.14 | 38.54 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 92.54 | 48.72 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 48.13 | 58.59 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 53.19 | 72.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 71.06 | 47.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.45 | 27.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 99.14 | 72.48 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.45 | 71.57 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 76.55 | 62.52 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 81.50 | 52.98 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 80.35 | 43.73 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 66.11 | 38.03 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 56.93 | 31.41 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 68.93 | 28.57 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.50 | 27.75 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 99.14 | 38.54 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 92.54 | 48.72 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 48.13 | 58.59 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 53.19 | 72.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 71.06 | 47.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.45 | 27.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 99.14 | 72.48 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.45 | 71.57 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 76.55 | 62.52 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 81.50 | 52.98 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 80.35 | 43.73 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 66.11 | 38.03 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 56.93 | 31.41 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 68.93 | 28.57 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.50 | 27.75 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 99.14 | 38.54 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 92.54 | 48.72 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 48.13 | 58.59 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 53.19 | 72.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 71.06 | 47.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.45 | 27.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 99.14 | 72.48 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.26 | 37.56 | 25.70 | 53.61 | 85.41 | 0.00 | 0.00 | 744.00 |
February | 97.32 | 60.24 | 37.08 | 92.25 | 74.66 | 0.00 | 0.00 | 672.00 |
March | 104.72 | 55.87 | 48.86 | 98.18 | 63.27 | 0.00 | 0.00 | 744.00 |
April | 110.53 | 48.00 | 62.53 | 96.82 | 52.25 | 0.00 | 0.00 | 720.00 |
May | 101.05 | 30.09 | 70.95 | 79.68 | 45.46 | 0.00 | 0.00 | 744.00 |
June | 92.45 | 24.81 | 67.64 | 68.61 | 37.56 | 0.00 | 0.00 | 720.00 |
July | 100.81 | 36.91 | 63.90 | 83.00 | 34.19 | 0.00 | 0.00 | 744.00 |
August | 108.32 | 50.51 | 57.81 | 102.89 | 33.23 | 0.00 | 0.00 | 744.00 |
September | 120.06 | 66.32 | 53.74 | 119.33 | 46.13 | 0.00 | 0.00 | 720.00 |
October | 108.75 | 67.16 | 41.59 | 111.43 | 58.25 | 0.00 | 0.00 | 744.00 |
November | 64.27 | 36.83 | 27.44 | 58.01 | 69.98 | 0.00 | 0.00 | 720.00 |
December | 67.23 | 43.50 | 23.73 | 64.08 | 86.55 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 94.86 | 46.40 | 48.46 | 85.60 | 57.17 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 63.26 | 24.81 | 23.73 | 53.61 | 33.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 120.06 | 67.16 | 70.95 | 119.33 | 86.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.26 | 37.56 | 25.70 | 53.61 | 85.41 | 0.00 | 0.00 | 744.00 |
February | 97.32 | 60.24 | 37.08 | 92.25 | 74.66 | 0.00 | 0.00 | 672.00 |
March | 104.72 | 55.87 | 48.86 | 98.18 | 63.27 | 0.00 | 0.00 | 744.00 |
April | 110.53 | 48.00 | 62.53 | 96.82 | 52.25 | 0.00 | 0.00 | 720.00 |
May | 101.05 | 30.09 | 70.95 | 79.68 | 45.46 | 0.00 | 0.00 | 744.00 |
June | 92.45 | 24.81 | 67.64 | 68.61 | 37.56 | 0.00 | 0.00 | 720.00 |
July | 100.81 | 36.91 | 63.90 | 83.00 | 34.19 | 0.00 | 0.00 | 744.00 |
August | 108.32 | 50.51 | 57.81 | 102.89 | 33.23 | 0.00 | 0.00 | 744.00 |
September | 120.06 | 66.32 | 53.74 | 119.33 | 46.13 | 0.00 | 0.00 | 720.00 |
October | 108.75 | 67.16 | 41.59 | 111.43 | 58.25 | 0.00 | 0.00 | 744.00 |
November | 64.27 | 36.83 | 27.44 | 58.01 | 69.98 | 0.00 | 0.00 | 720.00 |
December | 67.23 | 43.50 | 23.73 | 64.08 | 86.55 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 94.86 | 46.40 | 48.46 | 85.60 | 57.17 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 63.26 | 24.81 | 23.73 | 53.61 | 33.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 120.06 | 67.16 | 70.95 | 119.33 | 86.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 43.89 | 75.41 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 75.61 | 66.41 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 80.33 | 57.63 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 78.67 | 47.99 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 64.30 | 41.35 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 56.04 | 32.93 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 68.61 | 29.36 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.20 | 28.47 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 98.42 | 40.04 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 91.24 | 52.90 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 47.41 | 62.46 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 52.67 | 76.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 70.16 | 50.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 43.89 | 28.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 98.42 | 76.32 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 43.89 | 75.41 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 75.61 | 66.41 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 80.33 | 57.63 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 78.67 | 47.99 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 64.30 | 41.35 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 56.04 | 32.93 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 68.61 | 29.36 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.20 | 28.47 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 98.42 | 40.04 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 91.24 | 52.90 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 47.41 | 62.46 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 52.67 | 76.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 70.16 | 50.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 43.89 | 28.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 98.42 | 76.32 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.26 | 37.56 | 25.70 | 52.94 | 89.98 | 0.00 | 0.00 | 744.00 |
February | 97.32 | 60.24 | 37.08 | 91.13 | 79.28 | 0.00 | 0.00 | 672.00 |
March | 104.72 | 55.87 | 48.86 | 96.78 | 68.79 | 0.00 | 0.00 | 744.00 |
April | 110.53 | 48.00 | 62.53 | 94.81 | 57.30 | 0.00 | 0.00 | 720.00 |
May | 101.05 | 30.09 | 70.95 | 77.51 | 49.40 | 0.00 | 0.00 | 744.00 |
June | 92.45 | 24.81 | 67.64 | 67.53 | 39.36 | 0.00 | 0.00 | 720.00 |
July | 100.81 | 36.91 | 63.90 | 82.60 | 35.12 | 0.00 | 0.00 | 744.00 |
August | 108.32 | 50.51 | 57.81 | 102.53 | 34.08 | 0.00 | 0.00 | 744.00 |
September | 120.06 | 66.32 | 53.74 | 118.47 | 47.93 | 0.00 | 0.00 | 720.00 |
October | 108.75 | 67.16 | 41.59 | 109.88 | 63.21 | 0.00 | 0.00 | 744.00 |
November | 64.27 | 36.83 | 27.44 | 57.14 | 74.57 | 0.00 | 0.00 | 720.00 |
December | 67.23 | 43.50 | 23.73 | 63.47 | 91.11 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 94.86 | 46.40 | 48.46 | 84.51 | 60.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 63.26 | 24.81 | 23.73 | 52.94 | 34.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 120.06 | 67.16 | 70.95 | 118.47 | 91.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 43.93 | 73.47 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 75.69 | 64.71 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 80.39 | 56.26 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 78.65 | 47.27 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 63.97 | 41.80 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 55.71 | 33.88 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 68.32 | 30.63 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 84.97 | 29.83 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 98.20 | 41.11 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 91.18 | 52.59 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 47.47 | 60.99 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 52.72 | 74.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 70.06 | 50.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 43.93 | 29.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 98.20 | 74.48 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 43.93 | 73.47 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 75.69 | 64.71 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 80.39 | 56.26 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 78.65 | 47.27 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 63.97 | 41.80 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 55.71 | 33.88 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 68.32 | 30.63 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 84.97 | 29.83 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 98.20 | 41.11 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 91.18 | 52.59 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 47.47 | 60.99 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 52.72 | 74.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 70.06 | 50.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 43.93 | 29.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 98.20 | 74.48 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.91 | 37.35 | 25.56 | 52.70 | 87.18 | 0.00 | 0.00 | 744.00 |
February | 96.78 | 59.91 | 36.87 | 90.73 | 76.83 | 0.00 | 0.00 | 672.00 |
March | 104.15 | 55.56 | 48.59 | 96.33 | 66.80 | 0.00 | 0.00 | 744.00 |
April | 109.93 | 47.74 | 62.19 | 94.27 | 56.12 | 0.00 | 0.00 | 720.00 |
May | 100.49 | 29.93 | 70.57 | 76.70 | 49.65 | 0.00 | 0.00 | 744.00 |
June | 91.94 | 24.68 | 67.27 | 66.78 | 40.25 | 0.00 | 0.00 | 720.00 |
July | 100.26 | 36.71 | 63.55 | 81.82 | 36.41 | 0.00 | 0.00 | 744.00 |
August | 107.73 | 50.23 | 57.50 | 101.69 | 35.47 | 0.00 | 0.00 | 744.00 |
September | 119.41 | 65.96 | 53.45 | 117.56 | 48.90 | 0.00 | 0.00 | 720.00 |
October | 108.16 | 66.79 | 41.37 | 109.21 | 62.48 | 0.00 | 0.00 | 744.00 |
November | 63.92 | 36.62 | 27.29 | 56.91 | 72.42 | 0.00 | 0.00 | 720.00 |
December | 66.87 | 43.26 | 23.60 | 63.18 | 88.44 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 94.34 | 46.14 | 48.20 | 83.94 | 60.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.91 | 24.68 | 23.60 | 52.70 | 35.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 119.41 | 66.79 | 70.57 | 117.56 | 88.44 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.03 | 72.46 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 75.87 | 63.82 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 80.59 | 55.34 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 78.93 | 46.42 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 64.18 | 41.29 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 55.78 | 33.67 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 68.35 | 30.54 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 84.98 | 29.78 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 98.26 | 40.87 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 91.39 | 51.72 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 47.63 | 60.07 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 52.82 | 73.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 70.19 | 49.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.03 | 29.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 98.26 | 73.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.03 | 72.46 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 75.87 | 63.82 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 80.59 | 55.34 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 78.93 | 46.42 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 64.18 | 41.29 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 55.78 | 33.67 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 68.35 | 30.54 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 84.98 | 29.78 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 98.26 | 40.87 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 91.39 | 51.72 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 47.63 | 60.07 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 52.82 | 73.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 70.19 | 49.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.03 | 29.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 98.26 | 73.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.91 | 37.35 | 25.56 | 52.82 | 85.98 | 0.00 | 0.00 | 744.00 |
February | 96.78 | 59.91 | 36.87 | 90.95 | 75.77 | 0.00 | 0.00 | 672.00 |
March | 104.15 | 55.56 | 48.59 | 96.57 | 65.70 | 0.00 | 0.00 | 744.00 |
April | 109.93 | 47.74 | 62.19 | 94.61 | 55.12 | 0.00 | 0.00 | 720.00 |
May | 100.49 | 29.93 | 70.57 | 76.95 | 49.05 | 0.00 | 0.00 | 744.00 |
June | 91.94 | 24.68 | 67.27 | 66.86 | 40.00 | 0.00 | 0.00 | 720.00 |
July | 100.26 | 36.71 | 63.55 | 81.84 | 36.31 | 0.00 | 0.00 | 744.00 |
August | 107.73 | 50.23 | 57.50 | 101.70 | 35.41 | 0.00 | 0.00 | 744.00 |
September | 119.41 | 65.96 | 53.45 | 117.63 | 48.61 | 0.00 | 0.00 | 720.00 |
October | 108.16 | 66.79 | 41.37 | 109.47 | 61.45 | 0.00 | 0.00 | 744.00 |
November | 63.92 | 36.62 | 27.29 | 57.10 | 71.33 | 0.00 | 0.00 | 720.00 |
December | 66.87 | 43.26 | 23.60 | 63.30 | 87.36 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 94.34 | 46.14 | 48.20 | 84.10 | 59.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.91 | 24.68 | 23.60 | 52.82 | 35.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 119.41 | 66.79 | 70.57 | 117.63 | 87.36 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.19 | 71.49 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 76.14 | 62.94 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 80.91 | 54.28 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 79.49 | 45.27 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 64.89 | 40.12 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 56.14 | 33.04 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 68.53 | 30.14 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.14 | 29.40 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 98.55 | 40.12 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 91.87 | 50.32 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 47.88 | 59.08 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 52.97 | 72.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 70.51 | 49.01 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.19 | 29.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 98.55 | 72.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.19 | 71.49 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 76.14 | 62.94 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 80.91 | 54.28 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 79.49 | 45.27 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 64.89 | 40.12 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 56.14 | 33.04 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 68.53 | 30.14 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.14 | 29.40 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 98.55 | 40.12 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 91.87 | 50.32 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 47.88 | 59.08 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 52.97 | 72.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 70.51 | 49.01 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.19 | 29.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 98.55 | 72.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.91 | 37.35 | 25.56 | 53.01 | 84.82 | 0.00 | 0.00 | 744.00 |
February | 96.78 | 59.91 | 36.87 | 91.27 | 74.73 | 0.00 | 0.00 | 672.00 |
March | 104.15 | 55.56 | 48.59 | 96.96 | 64.45 | 0.00 | 0.00 | 744.00 |
April | 109.93 | 47.74 | 62.19 | 95.27 | 53.76 | 0.00 | 0.00 | 720.00 |
May | 100.49 | 29.93 | 70.57 | 77.80 | 47.65 | 0.00 | 0.00 | 744.00 |
June | 91.94 | 24.68 | 67.27 | 67.29 | 39.25 | 0.00 | 0.00 | 720.00 |
July | 100.26 | 36.71 | 63.55 | 82.06 | 35.83 | 0.00 | 0.00 | 744.00 |
August | 107.73 | 50.23 | 57.50 | 101.90 | 34.96 | 0.00 | 0.00 | 744.00 |
September | 119.41 | 65.96 | 53.45 | 117.99 | 47.73 | 0.00 | 0.00 | 720.00 |
October | 108.16 | 66.79 | 41.37 | 110.04 | 59.79 | 0.00 | 0.00 | 744.00 |
November | 63.92 | 36.62 | 27.29 | 57.40 | 70.14 | 0.00 | 0.00 | 720.00 |
December | 66.87 | 43.26 | 23.60 | 63.49 | 86.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 94.34 | 46.14 | 48.20 | 84.48 | 58.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.91 | 24.68 | 23.60 | 53.01 | 34.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 119.41 | 66.79 | 70.57 | 117.99 | 86.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.75 | 68.68 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 76.97 | 60.52 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 81.73 | 51.77 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 80.80 | 42.57 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 66.75 | 37.05 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 57.26 | 31.02 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 68.93 | 28.75 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.43 | 28.05 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 99.51 | 37.85 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 93.09 | 47.17 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 48.54 | 56.54 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 53.48 | 70.07 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 71.39 | 46.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.75 | 28.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 99.51 | 70.07 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.75 | 68.68 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 76.97 | 60.52 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 81.73 | 51.77 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 80.80 | 42.57 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 66.75 | 37.05 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 57.26 | 31.02 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 68.93 | 28.75 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.43 | 28.05 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 99.51 | 37.85 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 93.09 | 47.17 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 48.54 | 56.54 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 53.48 | 70.07 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 71.39 | 46.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.75 | 28.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 99.51 | 70.07 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.75 | 68.68 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 76.97 | 60.52 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 81.73 | 51.77 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 80.80 | 42.57 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 66.75 | 37.05 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 57.26 | 31.02 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 68.93 | 28.75 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.43 | 28.05 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 99.51 | 37.85 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 93.09 | 47.17 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 48.54 | 56.54 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 53.48 | 70.07 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 71.39 | 46.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.75 | 28.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 99.51 | 70.07 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.75 | 68.68 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 76.97 | 60.52 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 81.73 | 51.77 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 80.80 | 42.57 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 66.75 | 37.05 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 57.26 | 31.02 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 68.93 | 28.75 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.43 | 28.05 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 99.51 | 37.85 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 93.09 | 47.17 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 48.54 | 56.54 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 53.48 | 70.07 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 71.39 | 46.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.75 | 28.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 99.51 | 70.07 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.91 | 37.35 | 25.56 | 53.69 | 81.50 | 0.00 | 0.00 | 744.00 |
February | 96.78 | 59.91 | 36.87 | 92.27 | 71.86 | 0.00 | 0.00 | 672.00 |
March | 104.15 | 55.56 | 48.59 | 97.94 | 61.47 | 0.00 | 0.00 | 744.00 |
April | 109.93 | 47.74 | 62.19 | 96.84 | 50.56 | 0.00 | 0.00 | 720.00 |
May | 100.49 | 29.93 | 70.57 | 80.01 | 44.02 | 0.00 | 0.00 | 744.00 |
June | 91.94 | 24.68 | 67.27 | 68.64 | 36.87 | 0.00 | 0.00 | 720.00 |
July | 100.26 | 36.71 | 63.55 | 82.55 | 34.19 | 0.00 | 0.00 | 744.00 |
August | 107.73 | 50.23 | 57.50 | 102.26 | 33.37 | 0.00 | 0.00 | 744.00 |
September | 119.41 | 65.96 | 53.45 | 119.14 | 45.03 | 0.00 | 0.00 | 720.00 |
October | 108.16 | 66.79 | 41.37 | 111.49 | 56.06 | 0.00 | 0.00 | 744.00 |
November | 63.92 | 36.62 | 27.29 | 58.18 | 67.13 | 0.00 | 0.00 | 720.00 |
December | 66.87 | 43.26 | 23.60 | 64.10 | 83.18 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 94.34 | 46.14 | 48.20 | 85.54 | 55.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.91 | 24.68 | 23.60 | 53.69 | 33.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 119.41 | 66.79 | 70.57 | 119.14 | 83.18 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.91 | 37.35 | 25.56 | 53.69 | 81.50 | 0.00 | 0.00 | 744.00 |
February | 96.78 | 59.91 | 36.87 | 92.27 | 71.86 | 0.00 | 0.00 | 672.00 |
March | 104.15 | 55.56 | 48.59 | 97.94 | 61.47 | 0.00 | 0.00 | 744.00 |
April | 109.93 | 47.74 | 62.19 | 96.84 | 50.56 | 0.00 | 0.00 | 720.00 |
May | 100.49 | 29.93 | 70.57 | 80.01 | 44.02 | 0.00 | 0.00 | 744.00 |
June | 91.94 | 24.68 | 67.27 | 68.64 | 36.87 | 0.00 | 0.00 | 720.00 |
July | 100.26 | 36.71 | 63.55 | 82.55 | 34.19 | 0.00 | 0.00 | 744.00 |
August | 107.73 | 50.23 | 57.50 | 102.26 | 33.37 | 0.00 | 0.00 | 744.00 |
September | 119.41 | 65.96 | 53.45 | 119.14 | 45.03 | 0.00 | 0.00 | 720.00 |
October | 108.16 | 66.79 | 41.37 | 111.49 | 56.06 | 0.00 | 0.00 | 744.00 |
November | 63.92 | 36.62 | 27.29 | 58.18 | 67.13 | 0.00 | 0.00 | 720.00 |
December | 66.87 | 43.26 | 23.60 | 64.10 | 83.18 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 94.34 | 46.14 | 48.20 | 85.54 | 55.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.91 | 24.68 | 23.60 | 53.69 | 33.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 119.41 | 66.79 | 70.57 | 119.14 | 83.18 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.65 | 68.79 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 76.92 | 60.46 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 81.76 | 51.42 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 80.93 | 42.27 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 66.95 | 36.75 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 57.48 | 30.78 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 69.15 | 28.47 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.62 | 27.75 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 99.59 | 37.58 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 93.12 | 46.81 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 48.58 | 56.33 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 53.47 | 70.03 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 71.47 | 46.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.65 | 27.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 99.59 | 70.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.65 | 68.79 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 76.92 | 60.46 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 81.76 | 51.42 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 80.93 | 42.27 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 66.95 | 36.75 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 57.48 | 30.78 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 69.15 | 28.47 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.62 | 27.75 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 99.59 | 37.58 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 93.12 | 46.81 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 48.58 | 56.33 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 53.47 | 70.03 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 71.47 | 46.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.65 | 27.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 99.59 | 70.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.91 | 37.35 | 25.56 | 53.57 | 81.60 | 0.00 | 0.00 | 744.00 |
February | 96.78 | 59.91 | 36.87 | 92.22 | 71.77 | 0.00 | 0.00 | 672.00 |
March | 104.15 | 55.56 | 48.59 | 97.98 | 61.04 | 0.00 | 0.00 | 744.00 |
April | 109.93 | 47.74 | 62.19 | 97.01 | 50.20 | 0.00 | 0.00 | 720.00 |
May | 100.49 | 29.93 | 70.57 | 80.26 | 43.66 | 0.00 | 0.00 | 744.00 |
June | 91.94 | 24.68 | 67.27 | 68.91 | 36.58 | 0.00 | 0.00 | 720.00 |
July | 100.26 | 36.71 | 63.55 | 82.82 | 33.85 | 0.00 | 0.00 | 744.00 |
August | 107.73 | 50.23 | 57.50 | 102.50 | 33.01 | 0.00 | 0.00 | 744.00 |
September | 119.41 | 65.96 | 53.45 | 119.24 | 44.71 | 0.00 | 0.00 | 720.00 |
October | 108.16 | 66.79 | 41.37 | 111.54 | 55.62 | 0.00 | 0.00 | 744.00 |
November | 63.92 | 36.62 | 27.29 | 58.24 | 66.87 | 0.00 | 0.00 | 720.00 |
December | 66.87 | 43.26 | 23.60 | 64.09 | 83.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 94.34 | 46.14 | 48.20 | 85.64 | 55.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.91 | 24.68 | 23.60 | 53.57 | 33.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 119.41 | 66.79 | 70.57 | 119.24 | 83.12 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.69 | 68.51 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 77.01 | 60.16 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 81.87 | 51.07 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 81.12 | 41.92 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 67.23 | 36.33 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 57.73 | 30.47 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 69.29 | 28.26 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.74 | 27.58 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 99.76 | 37.27 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 93.28 | 46.41 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 48.66 | 56.00 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 53.53 | 69.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 71.61 | 46.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.69 | 27.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 99.76 | 69.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.69 | 68.51 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 77.01 | 60.16 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 81.87 | 51.07 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 81.12 | 41.92 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 67.23 | 36.33 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 57.73 | 30.47 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 69.29 | 28.26 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.74 | 27.58 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 99.76 | 37.27 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 93.28 | 46.41 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 48.66 | 56.00 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 53.53 | 69.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 71.61 | 46.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.69 | 27.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 99.76 | 69.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.91 | 37.35 | 25.56 | 53.63 | 81.27 | 0.00 | 0.00 | 744.00 |
February | 96.78 | 59.91 | 36.87 | 92.33 | 71.41 | 0.00 | 0.00 | 672.00 |
March | 104.15 | 55.56 | 48.59 | 98.11 | 60.62 | 0.00 | 0.00 | 744.00 |
April | 109.93 | 47.74 | 62.19 | 97.24 | 49.78 | 0.00 | 0.00 | 720.00 |
May | 100.49 | 29.93 | 70.57 | 80.60 | 43.16 | 0.00 | 0.00 | 744.00 |
June | 91.94 | 24.68 | 67.27 | 69.20 | 36.21 | 0.00 | 0.00 | 720.00 |
July | 100.26 | 36.71 | 63.55 | 82.99 | 33.61 | 0.00 | 0.00 | 744.00 |
August | 107.73 | 50.23 | 57.50 | 102.63 | 32.81 | 0.00 | 0.00 | 744.00 |
September | 119.41 | 65.96 | 53.45 | 119.44 | 44.34 | 0.00 | 0.00 | 720.00 |
October | 108.16 | 66.79 | 41.37 | 111.74 | 55.15 | 0.00 | 0.00 | 744.00 |
November | 63.92 | 36.62 | 27.29 | 58.34 | 66.48 | 0.00 | 0.00 | 720.00 |
December | 66.87 | 43.26 | 23.60 | 64.16 | 82.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 94.34 | 46.14 | 48.20 | 85.81 | 54.73 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.91 | 24.68 | 23.60 | 53.63 | 32.81 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 119.41 | 66.79 | 70.57 | 119.44 | 82.77 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.83 | 67.61 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 77.24 | 59.27 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 82.10 | 50.17 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 81.49 | 41.06 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 67.78 | 35.40 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 58.22 | 29.77 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 69.57 | 27.79 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.94 | 27.20 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 100.09 | 36.57 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 93.60 | 45.57 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 48.82 | 55.23 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 53.66 | 68.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 71.90 | 45.32 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.83 | 27.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 100.09 | 68.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 44.83 | 67.61 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 77.24 | 59.27 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 82.10 | 50.17 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 81.49 | 41.06 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 67.78 | 35.40 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 58.22 | 29.77 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 69.57 | 27.79 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 85.94 | 27.20 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 100.09 | 36.57 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 93.60 | 45.57 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 48.82 | 55.23 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 53.66 | 68.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 71.90 | 45.32 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 44.83 | 27.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 100.09 | 68.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.91 | 37.35 | 25.56 | 53.79 | 80.20 | 0.00 | 0.00 | 744.00 |
February | 96.78 | 59.91 | 36.87 | 92.61 | 70.36 | 0.00 | 0.00 | 672.00 |
March | 104.15 | 55.56 | 48.59 | 98.39 | 59.56 | 0.00 | 0.00 | 744.00 |
April | 109.93 | 47.74 | 62.19 | 97.68 | 48.77 | 0.00 | 0.00 | 720.00 |
May | 100.49 | 29.93 | 70.57 | 81.26 | 42.06 | 0.00 | 0.00 | 744.00 |
June | 91.94 | 24.68 | 67.27 | 69.79 | 35.38 | 0.00 | 0.00 | 720.00 |
July | 100.26 | 36.71 | 63.55 | 83.33 | 33.04 | 0.00 | 0.00 | 744.00 |
August | 107.73 | 50.23 | 57.50 | 102.88 | 32.36 | 0.00 | 0.00 | 744.00 |
September | 119.41 | 65.96 | 53.45 | 119.84 | 43.51 | 0.00 | 0.00 | 720.00 |
October | 108.16 | 66.79 | 41.37 | 112.11 | 54.15 | 0.00 | 0.00 | 744.00 |
November | 63.92 | 36.62 | 27.29 | 58.54 | 65.56 | 0.00 | 0.00 | 720.00 |
December | 66.87 | 43.26 | 23.60 | 64.32 | 81.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 94.34 | 46.14 | 48.20 | 86.16 | 53.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.91 | 24.68 | 23.60 | 53.79 | 32.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 119.41 | 66.79 | 70.57 | 119.84 | 81.77 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 45.33 | 63.97 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 78.03 | 55.79 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 82.84 | 46.78 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 82.44 | 38.12 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 69.00 | 32.68 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 59.29 | 27.59 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 70.30 | 26.08 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 86.45 | 25.76 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 100.82 | 34.56 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 94.31 | 42.99 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 49.32 | 52.50 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 54.13 | 65.60 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 72.64 | 42.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 45.33 | 25.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 100.82 | 65.60 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.54 | 31.19 | 21.35 | 45.33 | 63.97 | 0.00 | 0.00 | 744.00 |
February | 80.83 | 50.04 | 30.79 | 78.03 | 55.79 | 0.00 | 0.00 | 672.00 |
March | 86.98 | 46.40 | 40.58 | 82.84 | 46.78 | 0.00 | 0.00 | 744.00 |
April | 91.81 | 39.87 | 51.94 | 82.44 | 38.12 | 0.00 | 0.00 | 720.00 |
May | 83.93 | 24.99 | 58.93 | 69.00 | 32.68 | 0.00 | 0.00 | 744.00 |
June | 76.79 | 20.61 | 56.18 | 59.29 | 27.59 | 0.00 | 0.00 | 720.00 |
July | 83.74 | 30.66 | 53.08 | 70.30 | 26.08 | 0.00 | 0.00 | 744.00 |
August | 89.97 | 41.95 | 48.02 | 86.45 | 25.76 | 0.00 | 0.00 | 744.00 |
September | 99.73 | 55.09 | 44.64 | 100.82 | 34.56 | 0.00 | 0.00 | 720.00 |
October | 90.33 | 55.78 | 34.55 | 94.31 | 42.99 | 0.00 | 0.00 | 744.00 |
November | 53.38 | 30.59 | 22.79 | 49.32 | 52.50 | 0.00 | 0.00 | 720.00 |
December | 55.84 | 36.13 | 19.71 | 54.13 | 65.60 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 78.79 | 38.54 | 40.25 | 72.64 | 42.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 52.54 | 20.61 | 19.71 | 45.33 | 25.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.73 | 55.78 | 58.93 | 100.82 | 65.60 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.91 | 37.35 | 25.56 | 54.41 | 75.87 | 0.00 | 0.00 | 744.00 |
February | 96.78 | 59.91 | 36.87 | 93.57 | 66.22 | 0.00 | 0.00 | 672.00 |
March | 104.15 | 55.56 | 48.59 | 99.30 | 55.54 | 0.00 | 0.00 | 744.00 |
April | 109.93 | 47.74 | 62.19 | 98.83 | 45.28 | 0.00 | 0.00 | 720.00 |
May | 100.49 | 29.93 | 70.57 | 82.73 | 38.84 | 0.00 | 0.00 | 744.00 |
June | 91.94 | 24.68 | 67.27 | 71.08 | 32.80 | 0.00 | 0.00 | 720.00 |
July | 100.26 | 36.71 | 63.55 | 84.20 | 31.02 | 0.00 | 0.00 | 744.00 |
August | 107.73 | 50.23 | 57.50 | 103.48 | 30.66 | 0.00 | 0.00 | 744.00 |
September | 119.41 | 65.96 | 53.45 | 120.71 | 41.12 | 0.00 | 0.00 | 720.00 |
October | 108.16 | 66.79 | 41.37 | 112.97 | 51.10 | 0.00 | 0.00 | 744.00 |
November | 63.92 | 36.62 | 27.29 | 59.14 | 62.31 | 0.00 | 0.00 | 720.00 |
December | 66.87 | 43.26 | 23.60 | 64.89 | 77.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 94.34 | 46.14 | 48.20 | 87.05 | 50.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.91 | 24.68 | 23.60 | 54.41 | 30.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 119.41 | 66.79 | 70.57 | 120.71 | 77.84 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.119061E+09 | 0.191681E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.185180E+09 | 0.151247E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.218292E+09 | 0.141893E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.208263E+09 | 0.113341E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.177063E+09 | 0.101851E+09 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.147574E+09 | 81416342.18 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.184626E+09 | 76531967.90 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.229000E+09 | 74330525.89 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.256962E+09 | 99886253.05 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.247859E+09 | 0.130491E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.124756E+09 | 0.151873E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.142452E+09 | 0.194132E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.224109E+10 | 0.150867E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.119061E+09 | 74330525.89 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.256962E+09 | 0.194132E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.119061E+09 | 0.191681E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.185180E+09 | 0.151247E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.218292E+09 | 0.141893E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.208263E+09 | 0.113341E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.177063E+09 | 0.101851E+09 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.147574E+09 | 81416342.18 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.184626E+09 | 76531967.90 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.229000E+09 | 74330525.89 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.256962E+09 | 99886253.05 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.247859E+09 | 0.130491E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.124756E+09 | 0.151873E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.142452E+09 | 0.194132E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.224109E+10 | 0.150867E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.119061E+09 | 74330525.89 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.256962E+09 | 0.194132E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.119061E+09 | 0.191681E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.185180E+09 | 0.151247E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.218292E+09 | 0.141893E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.208263E+09 | 0.113341E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.177063E+09 | 0.101851E+09 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.147574E+09 | 81416342.18 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.184626E+09 | 76531967.90 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.229000E+09 | 74330525.89 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.256962E+09 | 99886253.05 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.247859E+09 | 0.130491E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.124756E+09 | 0.151873E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.142452E+09 | 0.194132E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.224109E+10 | 0.150867E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.119061E+09 | 74330525.89 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.256962E+09 | 0.194132E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.119061E+09 | 0.191681E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.185180E+09 | 0.151247E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.218292E+09 | 0.141893E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.208263E+09 | 0.113341E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.177063E+09 | 0.101851E+09 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.147574E+09 | 81416342.18 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.184626E+09 | 76531967.90 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.229000E+09 | 74330525.89 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.256962E+09 | 99886253.05 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.247859E+09 | 0.130491E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.124756E+09 | 0.151873E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.142452E+09 | 0.194132E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.224109E+10 | 0.150867E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.119061E+09 | 74330525.89 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.256962E+09 | 0.194132E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169433E+09 | 0.100588E+09 | 68844739.83 | 0.143599E+09 | 0.228761E+09 |
February | 0.235429E+09 | 0.145737E+09 | 89692139.39 | 0.223181E+09 | 0.180617E+09 |
March | 0.280490E+09 | 0.149634E+09 | 0.130856E+09 | 0.262978E+09 | 0.169476E+09 |
April | 0.286500E+09 | 0.124410E+09 | 0.162090E+09 | 0.250963E+09 | 0.135422E+09 |
May | 0.270640E+09 | 80600039.79 | 0.190040E+09 | 0.213405E+09 | 0.121748E+09 |
June | 0.239620E+09 | 64309394.27 | 0.175311E+09 | 0.177840E+09 | 97357695.66 |
July | 0.270020E+09 | 98865897.85 | 0.171154E+09 | 0.222295E+09 | 91584303.63 |
August | 0.290130E+09 | 0.135281E+09 | 0.154849E+09 | 0.275584E+09 | 88998422.25 |
September | 0.311205E+09 | 0.171902E+09 | 0.139303E+09 | 0.309304E+09 | 0.119571E+09 |
October | 0.291281E+09 | 0.179874E+09 | 0.111407E+09 | 0.298465E+09 | 0.156019E+09 |
November | 0.166582E+09 | 95451245.34 | 71130762.77 | 0.150351E+09 | 0.181399E+09 |
December | 0.180078E+09 | 0.116515E+09 | 63563708.60 | 0.171640E+09 | 0.231816E+09 |
Annual Sum or Average | 0.299141E+10 | 0.146317E+10 | 0.152824E+10 | 0.269960E+10 | 0.180277E+10 |
Minimum of Months | 0.166582E+09 | 64309394.27 | 63563708.60 | 0.143599E+09 | 88998422.25 |
Maximum of Months | 0.311205E+09 | 0.179874E+09 | 0.190040E+09 | 0.309304E+09 | 0.231816E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169433E+09 | 0.100588E+09 | 68844739.83 | 0.143599E+09 | 0.228761E+09 |
February | 0.235429E+09 | 0.145737E+09 | 89692139.39 | 0.223181E+09 | 0.180617E+09 |
March | 0.280490E+09 | 0.149634E+09 | 0.130856E+09 | 0.262978E+09 | 0.169476E+09 |
April | 0.286500E+09 | 0.124410E+09 | 0.162090E+09 | 0.250963E+09 | 0.135422E+09 |
May | 0.270640E+09 | 80600039.79 | 0.190040E+09 | 0.213405E+09 | 0.121748E+09 |
June | 0.239620E+09 | 64309394.27 | 0.175311E+09 | 0.177840E+09 | 97357695.66 |
July | 0.270020E+09 | 98865897.85 | 0.171154E+09 | 0.222295E+09 | 91584303.63 |
August | 0.290130E+09 | 0.135281E+09 | 0.154849E+09 | 0.275584E+09 | 88998422.25 |
September | 0.311205E+09 | 0.171902E+09 | 0.139303E+09 | 0.309304E+09 | 0.119571E+09 |
October | 0.291281E+09 | 0.179874E+09 | 0.111407E+09 | 0.298465E+09 | 0.156019E+09 |
November | 0.166582E+09 | 95451245.34 | 71130762.77 | 0.150351E+09 | 0.181399E+09 |
December | 0.180078E+09 | 0.116515E+09 | 63563708.60 | 0.171640E+09 | 0.231816E+09 |
Annual Sum or Average | 0.299141E+10 | 0.146317E+10 | 0.152824E+10 | 0.269960E+10 | 0.180277E+10 |
Minimum of Months | 0.166582E+09 | 64309394.27 | 63563708.60 | 0.143599E+09 | 88998422.25 |
Maximum of Months | 0.311205E+09 | 0.179874E+09 | 0.190040E+09 | 0.309304E+09 | 0.231816E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.117563E+09 | 0.201984E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.182927E+09 | 0.160670E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.215157E+09 | 0.154350E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.203918E+09 | 0.124396E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.172218E+09 | 0.110749E+09 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.145251E+09 | 85346881.60 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.183756E+09 | 78626728.42 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.228209E+09 | 76258940.61 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.255109E+09 | 0.103796E+09 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.244372E+09 | 0.141686E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.122882E+09 | 0.161906E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.141083E+09 | 0.204409E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.221244E+10 | 0.160418E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.117563E+09 | 76258940.61 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.255109E+09 | 0.204409E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.117563E+09 | 0.201984E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.182927E+09 | 0.160670E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.215157E+09 | 0.154350E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.203918E+09 | 0.124396E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.172218E+09 | 0.110749E+09 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.145251E+09 | 85346881.60 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.183756E+09 | 78626728.42 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.228209E+09 | 76258940.61 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.255109E+09 | 0.103796E+09 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.244372E+09 | 0.141686E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.122882E+09 | 0.161906E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.141083E+09 | 0.204409E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.221244E+10 | 0.160418E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.117563E+09 | 76258940.61 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.255109E+09 | 0.204409E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169433E+09 | 0.100588E+09 | 68844739.83 | 0.141783E+09 | 0.240999E+09 |
February | 0.235429E+09 | 0.145737E+09 | 89692139.39 | 0.220462E+09 | 0.191790E+09 |
March | 0.280490E+09 | 0.149634E+09 | 0.130856E+09 | 0.259217E+09 | 0.184252E+09 |
April | 0.286500E+09 | 0.124410E+09 | 0.162090E+09 | 0.245753E+09 | 0.148522E+09 |
May | 0.270640E+09 | 80600039.79 | 0.190040E+09 | 0.207603E+09 | 0.132309E+09 |
June | 0.239620E+09 | 64309394.27 | 0.175311E+09 | 0.175049E+09 | 0.102023E+09 |
July | 0.270020E+09 | 98865897.85 | 0.171154E+09 | 0.221238E+09 | 94066632.01 |
August | 0.290130E+09 | 0.135281E+09 | 0.154849E+09 | 0.274626E+09 | 91290055.75 |
September | 0.311205E+09 | 0.171902E+09 | 0.139303E+09 | 0.307085E+09 | 0.124225E+09 |
October | 0.291281E+09 | 0.179874E+09 | 0.111407E+09 | 0.294303E+09 | 0.169297E+09 |
November | 0.166582E+09 | 95451245.34 | 71130762.77 | 0.148098E+09 | 0.193289E+09 |
December | 0.180078E+09 | 0.116515E+09 | 63563708.60 | 0.169988E+09 | 0.244023E+09 |
Annual Sum or Average | 0.299141E+10 | 0.146317E+10 | 0.152824E+10 | 0.266521E+10 | 0.191609E+10 |
Minimum of Months | 0.166582E+09 | 64309394.27 | 63563708.60 | 0.141783E+09 | 91290055.75 |
Maximum of Months | 0.311205E+09 | 0.179874E+09 | 0.190040E+09 | 0.307085E+09 | 0.244023E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.117661E+09 | 0.196776E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.183119E+09 | 0.156548E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.215319E+09 | 0.150691E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.203855E+09 | 0.122517E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.171335E+09 | 0.111963E+09 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.144411E+09 | 87815980.34 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.183001E+09 | 82035274.24 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.227583E+09 | 79883638.37 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.254538E+09 | 0.106548E+09 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.244207E+09 | 0.140844E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.123050E+09 | 0.158088E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.141204E+09 | 0.199495E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.220928E+10 | 0.159320E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.117661E+09 | 79883638.37 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.254538E+09 | 0.199495E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.117661E+09 | 0.196776E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.183119E+09 | 0.156548E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.215319E+09 | 0.150691E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.203855E+09 | 0.122517E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.171335E+09 | 0.111963E+09 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.144411E+09 | 87815980.34 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.183001E+09 | 82035274.24 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.227583E+09 | 79883638.37 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.254538E+09 | 0.106548E+09 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.244207E+09 | 0.140844E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.123050E+09 | 0.158088E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.141204E+09 | 0.199495E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.220928E+10 | 0.159320E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.117661E+09 | 79883638.37 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.254538E+09 | 0.199495E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168507E+09 | 0.100038E+09 | 68468539.07 | 0.141140E+09 | 0.233507E+09 |
February | 0.234142E+09 | 0.144940E+09 | 89202018.41 | 0.219504E+09 | 0.185865E+09 |
March | 0.278957E+09 | 0.148816E+09 | 0.130140E+09 | 0.258003E+09 | 0.178919E+09 |
April | 0.284935E+09 | 0.123730E+09 | 0.161204E+09 | 0.244344E+09 | 0.145474E+09 |
May | 0.269161E+09 | 80159602.41 | 0.189002E+09 | 0.205426E+09 | 0.132982E+09 |
June | 0.238311E+09 | 63957976.82 | 0.174353E+09 | 0.173099E+09 | 0.104327E+09 |
July | 0.268544E+09 | 98325647.04 | 0.170218E+09 | 0.219137E+09 | 97518595.55 |
August | 0.288545E+09 | 0.134541E+09 | 0.154003E+09 | 0.272378E+09 | 95011643.31 |
September | 0.309505E+09 | 0.170963E+09 | 0.138542E+09 | 0.304727E+09 | 0.126741E+09 |
October | 0.289689E+09 | 0.178891E+09 | 0.110798E+09 | 0.292501E+09 | 0.167348E+09 |
November | 0.165672E+09 | 94929653.84 | 70742070.08 | 0.147500E+09 | 0.187709E+09 |
December | 0.179094E+09 | 0.115878E+09 | 63216365.93 | 0.169219E+09 | 0.236868E+09 |
Annual Sum or Average | 0.297506E+10 | 0.145517E+10 | 0.151989E+10 | 0.264698E+10 | 0.189227E+10 |
Minimum of Months | 0.165672E+09 | 63957976.82 | 63216365.93 | 0.141140E+09 | 95011643.31 |
Maximum of Months | 0.309505E+09 | 0.178891E+09 | 0.189002E+09 | 0.304727E+09 | 0.236868E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.117931E+09 | 0.194072E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.183553E+09 | 0.154393E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.215853E+09 | 0.148217E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.204596E+09 | 0.120329E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.171900E+09 | 0.110603E+09 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.144585E+09 | 87272011.27 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.183059E+09 | 81801015.42 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.227604E+09 | 79749665.04 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.254682E+09 | 0.105924E+09 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.244783E+09 | 0.138526E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.123459E+09 | 0.155709E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.141481E+09 | 0.197066E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.221349E+10 | 0.157366E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.117931E+09 | 79749665.04 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.254682E+09 | 0.197066E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.117931E+09 | 0.194072E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.183553E+09 | 0.154393E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.215853E+09 | 0.148217E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.204596E+09 | 0.120329E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.171900E+09 | 0.110603E+09 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.144585E+09 | 87272011.27 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.183059E+09 | 81801015.42 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.227604E+09 | 79749665.04 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.254682E+09 | 0.105924E+09 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.244783E+09 | 0.138526E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.123459E+09 | 0.155709E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.141481E+09 | 0.197066E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.221349E+10 | 0.157366E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.117931E+09 | 79749665.04 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.254682E+09 | 0.197066E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168507E+09 | 0.100038E+09 | 68468539.07 | 0.141469E+09 | 0.230285E+09 |
February | 0.234142E+09 | 0.144940E+09 | 89202018.41 | 0.220030E+09 | 0.183303E+09 |
March | 0.278957E+09 | 0.148816E+09 | 0.130140E+09 | 0.258645E+09 | 0.175978E+09 |
April | 0.284935E+09 | 0.123730E+09 | 0.161204E+09 | 0.245232E+09 | 0.142877E+09 |
May | 0.269161E+09 | 80159602.41 | 0.189002E+09 | 0.206103E+09 | 0.131368E+09 |
June | 0.238311E+09 | 63957976.82 | 0.174353E+09 | 0.173309E+09 | 0.103682E+09 |
July | 0.268544E+09 | 98325647.04 | 0.170218E+09 | 0.219207E+09 | 97240320.32 |
August | 0.288545E+09 | 0.134541E+09 | 0.154003E+09 | 0.272404E+09 | 94851941.67 |
September | 0.309505E+09 | 0.170963E+09 | 0.138542E+09 | 0.304902E+09 | 0.125998E+09 |
October | 0.289689E+09 | 0.178891E+09 | 0.110798E+09 | 0.293192E+09 | 0.164596E+09 |
November | 0.165672E+09 | 94929653.84 | 70742070.08 | 0.147995E+09 | 0.184880E+09 |
December | 0.179094E+09 | 0.115878E+09 | 63216365.93 | 0.169553E+09 | 0.233973E+09 |
Annual Sum or Average | 0.297506E+10 | 0.145517E+10 | 0.151989E+10 | 0.265204E+10 | 0.186903E+10 |
Minimum of Months | 0.165672E+09 | 63957976.82 | 63216365.93 | 0.141469E+09 | 94851941.67 |
Maximum of Months | 0.309505E+09 | 0.178891E+09 | 0.189002E+09 | 0.304902E+09 | 0.233973E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.118349E+09 | 0.191471E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.184197E+09 | 0.152267E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.216720E+09 | 0.145385E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.206031E+09 | 0.117343E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.173799E+09 | 0.107447E+09 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.145510E+09 | 85634721.09 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.183543E+09 | 80721857.09 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.228029E+09 | 78735661.73 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.255450E+09 | 0.103993E+09 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.246056E+09 | 0.134773E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.124114E+09 | 0.153130E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.141885E+09 | 0.194689E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.222368E+10 | 0.154559E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.118349E+09 | 78735661.73 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.255450E+09 | 0.194689E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.118349E+09 | 0.191471E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.184197E+09 | 0.152267E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.216720E+09 | 0.145385E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.206031E+09 | 0.117343E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.173799E+09 | 0.107447E+09 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.145510E+09 | 85634721.09 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.183543E+09 | 80721857.09 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.228029E+09 | 78735661.73 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.255450E+09 | 0.103993E+09 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.246056E+09 | 0.134773E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.124114E+09 | 0.153130E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.141885E+09 | 0.194689E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.222368E+10 | 0.154559E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.118349E+09 | 78735661.73 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.255450E+09 | 0.194689E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168507E+09 | 0.100038E+09 | 68468539.07 | 0.141978E+09 | 0.227183E+09 |
February | 0.234142E+09 | 0.144940E+09 | 89202018.41 | 0.220811E+09 | 0.180775E+09 |
March | 0.278957E+09 | 0.148816E+09 | 0.130140E+09 | 0.259687E+09 | 0.172612E+09 |
April | 0.284935E+09 | 0.123730E+09 | 0.161204E+09 | 0.246952E+09 | 0.139335E+09 |
May | 0.269161E+09 | 80159602.41 | 0.189002E+09 | 0.208377E+09 | 0.127624E+09 |
June | 0.238311E+09 | 63957976.82 | 0.174353E+09 | 0.174423E+09 | 0.101741E+09 |
July | 0.268544E+09 | 98325647.04 | 0.170218E+09 | 0.219792E+09 | 95961452.82 |
August | 0.288545E+09 | 0.134541E+09 | 0.154003E+09 | 0.272918E+09 | 93649863.51 |
September | 0.309505E+09 | 0.170963E+09 | 0.138542E+09 | 0.305827E+09 | 0.123705E+09 |
October | 0.289689E+09 | 0.178891E+09 | 0.110798E+09 | 0.294718E+09 | 0.160144E+09 |
November | 0.165672E+09 | 94929653.84 | 70742070.08 | 0.148785E+09 | 0.181813E+09 |
December | 0.179094E+09 | 0.115878E+09 | 63216365.93 | 0.170047E+09 | 0.231138E+09 |
Annual Sum or Average | 0.297506E+10 | 0.145517E+10 | 0.151989E+10 | 0.266432E+10 | 0.183568E+10 |
Minimum of Months | 0.165672E+09 | 63957976.82 | 63216365.93 | 0.141978E+09 | 93649863.51 |
Maximum of Months | 0.309505E+09 | 0.178891E+09 | 0.189002E+09 | 0.305827E+09 | 0.231138E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.119853E+09 | 0.183965E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.186207E+09 | 0.146412E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.218914E+09 | 0.138660E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.209428E+09 | 0.110343E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.178780E+09 | 99231541.69 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.148427E+09 | 80411692.80 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.184615E+09 | 77011344.94 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.228815E+09 | 75122421.32 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.257942E+09 | 98100469.41 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.249321E+09 | 0.126343E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.125806E+09 | 0.146548E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.143244E+09 | 0.187671E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.225135E+10 | 0.146982E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.119853E+09 | 75122421.32 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.257942E+09 | 0.187671E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.119853E+09 | 0.183965E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.186207E+09 | 0.146412E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.218914E+09 | 0.138660E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.209428E+09 | 0.110343E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.178780E+09 | 99231541.69 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.148427E+09 | 80411692.80 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.184615E+09 | 77011344.94 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.228815E+09 | 75122421.32 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.257942E+09 | 98100469.41 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.249321E+09 | 0.126343E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.125806E+09 | 0.146548E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.143244E+09 | 0.187671E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.225135E+10 | 0.146982E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.119853E+09 | 75122421.32 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.257942E+09 | 0.187671E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.119853E+09 | 0.183965E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.186207E+09 | 0.146412E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.218914E+09 | 0.138660E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.209428E+09 | 0.110343E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.178780E+09 | 99231541.69 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.148427E+09 | 80411692.80 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.184615E+09 | 77011344.94 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.228815E+09 | 75122421.32 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.257942E+09 | 98100469.41 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.249321E+09 | 0.126343E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.125806E+09 | 0.146548E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.143244E+09 | 0.187671E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.225135E+10 | 0.146982E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.119853E+09 | 75122421.32 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.257942E+09 | 0.187671E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.119853E+09 | 0.183965E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.186207E+09 | 0.146412E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.218914E+09 | 0.138660E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.209428E+09 | 0.110343E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.178780E+09 | 99231541.69 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.148427E+09 | 80411692.80 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.184615E+09 | 77011344.94 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.228815E+09 | 75122421.32 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.257942E+09 | 98100469.41 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.249321E+09 | 0.126343E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.125806E+09 | 0.146548E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.143244E+09 | 0.187671E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.225135E+10 | 0.146982E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.119853E+09 | 75122421.32 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.257942E+09 | 0.187671E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168507E+09 | 0.100038E+09 | 68468539.07 | 0.143793E+09 | 0.218284E+09 |
February | 0.234142E+09 | 0.144940E+09 | 89202018.41 | 0.223217E+09 | 0.173837E+09 |
March | 0.278957E+09 | 0.148816E+09 | 0.130140E+09 | 0.262314E+09 | 0.164647E+09 |
April | 0.284935E+09 | 0.123730E+09 | 0.161204E+09 | 0.251007E+09 | 0.131062E+09 |
May | 0.269161E+09 | 80159602.41 | 0.189002E+09 | 0.214309E+09 | 0.117910E+09 |
June | 0.238311E+09 | 63957976.82 | 0.174353E+09 | 0.177911E+09 | 95571062.99 |
July | 0.268544E+09 | 98325647.04 | 0.170218E+09 | 0.221102E+09 | 91577397.61 |
August | 0.288545E+09 | 0.134541E+09 | 0.154003E+09 | 0.273890E+09 | 89380858.33 |
September | 0.309505E+09 | 0.170963E+09 | 0.138542E+09 | 0.308808E+09 | 0.116724E+09 |
October | 0.289689E+09 | 0.178891E+09 | 0.110798E+09 | 0.298603E+09 | 0.150164E+09 |
November | 0.165672E+09 | 94929653.84 | 70742070.08 | 0.150811E+09 | 0.174008E+09 |
December | 0.179094E+09 | 0.115878E+09 | 63216365.93 | 0.171676E+09 | 0.222800E+09 |
Annual Sum or Average | 0.297506E+10 | 0.145517E+10 | 0.151989E+10 | 0.269744E+10 | 0.174596E+10 |
Minimum of Months | 0.165672E+09 | 63957976.82 | 63216365.93 | 0.143793E+09 | 89380858.33 |
Maximum of Months | 0.309505E+09 | 0.178891E+09 | 0.189002E+09 | 0.308808E+09 | 0.222800E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168507E+09 | 0.100038E+09 | 68468539.07 | 0.143793E+09 | 0.218284E+09 |
February | 0.234142E+09 | 0.144940E+09 | 89202018.41 | 0.223217E+09 | 0.173837E+09 |
March | 0.278957E+09 | 0.148816E+09 | 0.130140E+09 | 0.262314E+09 | 0.164647E+09 |
April | 0.284935E+09 | 0.123730E+09 | 0.161204E+09 | 0.251007E+09 | 0.131062E+09 |
May | 0.269161E+09 | 80159602.41 | 0.189002E+09 | 0.214309E+09 | 0.117910E+09 |
June | 0.238311E+09 | 63957976.82 | 0.174353E+09 | 0.177911E+09 | 95571062.99 |
July | 0.268544E+09 | 98325647.04 | 0.170218E+09 | 0.221102E+09 | 91577397.61 |
August | 0.288545E+09 | 0.134541E+09 | 0.154003E+09 | 0.273890E+09 | 89380858.33 |
September | 0.309505E+09 | 0.170963E+09 | 0.138542E+09 | 0.308808E+09 | 0.116724E+09 |
October | 0.289689E+09 | 0.178891E+09 | 0.110798E+09 | 0.298603E+09 | 0.150164E+09 |
November | 0.165672E+09 | 94929653.84 | 70742070.08 | 0.150811E+09 | 0.174008E+09 |
December | 0.179094E+09 | 0.115878E+09 | 63216365.93 | 0.171676E+09 | 0.222800E+09 |
Annual Sum or Average | 0.297506E+10 | 0.145517E+10 | 0.151989E+10 | 0.269744E+10 | 0.174596E+10 |
Minimum of Months | 0.165672E+09 | 63957976.82 | 63216365.93 | 0.143793E+09 | 89380858.33 |
Maximum of Months | 0.309505E+09 | 0.178891E+09 | 0.189002E+09 | 0.308808E+09 | 0.222800E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.119586E+09 | 0.184244E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.186080E+09 | 0.146262E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.218984E+09 | 0.137719E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.209772E+09 | 0.109570E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.179311E+09 | 98437015.50 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.148996E+09 | 79792983.88 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.185217E+09 | 76252778.06 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.229335E+09 | 74323877.52 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.258136E+09 | 97413191.05 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.249403E+09 | 0.125370E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.125910E+09 | 0.146001E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.143222E+09 | 0.187575E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.225395E+10 | 0.146296E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.119586E+09 | 74323877.52 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.258136E+09 | 0.187575E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.119586E+09 | 0.184244E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.186080E+09 | 0.146262E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.218984E+09 | 0.137719E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.209772E+09 | 0.109570E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.179311E+09 | 98437015.50 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.148996E+09 | 79792983.88 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.185217E+09 | 76252778.06 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.229335E+09 | 74323877.52 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.258136E+09 | 97413191.05 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.249403E+09 | 0.125370E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.125910E+09 | 0.146001E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.143222E+09 | 0.187575E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.225395E+10 | 0.146296E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.119586E+09 | 74323877.52 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.258136E+09 | 0.187575E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168507E+09 | 0.100038E+09 | 68468539.07 | 0.143494E+09 | 0.218564E+09 |
February | 0.234142E+09 | 0.144940E+09 | 89202018.41 | 0.223095E+09 | 0.173623E+09 |
March | 0.278957E+09 | 0.148816E+09 | 0.130140E+09 | 0.262433E+09 | 0.163498E+09 |
April | 0.284935E+09 | 0.123730E+09 | 0.161204E+09 | 0.251450E+09 | 0.130119E+09 |
May | 0.269161E+09 | 80159602.41 | 0.189002E+09 | 0.214974E+09 | 0.116942E+09 |
June | 0.238311E+09 | 63957976.82 | 0.174353E+09 | 0.178609E+09 | 94815896.41 |
July | 0.268544E+09 | 98325647.04 | 0.170218E+09 | 0.221832E+09 | 90664847.07 |
August | 0.288545E+09 | 0.134541E+09 | 0.154003E+09 | 0.274525E+09 | 88422848.13 |
September | 0.309505E+09 | 0.170963E+09 | 0.138542E+09 | 0.309067E+09 | 0.115892E+09 |
October | 0.289689E+09 | 0.178891E+09 | 0.110798E+09 | 0.298739E+09 | 0.148981E+09 |
November | 0.165672E+09 | 94929653.84 | 70742070.08 | 0.150955E+09 | 0.173318E+09 |
December | 0.179094E+09 | 0.115878E+09 | 63216365.93 | 0.171669E+09 | 0.222639E+09 |
Annual Sum or Average | 0.297506E+10 | 0.145517E+10 | 0.151989E+10 | 0.270084E+10 | 0.173748E+10 |
Minimum of Months | 0.165672E+09 | 63957976.82 | 63216365.93 | 0.143494E+09 | 88422848.13 |
Maximum of Months | 0.309505E+09 | 0.178891E+09 | 0.189002E+09 | 0.309067E+09 | 0.222639E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.119710E+09 | 0.183505E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.186303E+09 | 0.145537E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.219278E+09 | 0.136775E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.210257E+09 | 0.108646E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.180065E+09 | 97316070.50 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.149628E+09 | 78990510.54 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.185595E+09 | 75701104.73 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.229639E+09 | 73860040.53 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.258573E+09 | 96607563.30 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.249854E+09 | 0.124312E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.126125E+09 | 0.145156E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.143370E+09 | 0.186780E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.225840E+10 | 0.145319E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.119710E+09 | 73860040.53 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.258573E+09 | 0.186780E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.119710E+09 | 0.183505E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.186303E+09 | 0.145537E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.219278E+09 | 0.136775E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.210257E+09 | 0.108646E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.180065E+09 | 97316070.50 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.149628E+09 | 78990510.54 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.185595E+09 | 75701104.73 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.229639E+09 | 73860040.53 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.258573E+09 | 96607563.30 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.249854E+09 | 0.124312E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.126125E+09 | 0.145156E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.143370E+09 | 0.186780E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.225840E+10 | 0.145319E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.119710E+09 | 73860040.53 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.258573E+09 | 0.186780E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168507E+09 | 0.100038E+09 | 68468539.07 | 0.143645E+09 | 0.217681E+09 |
February | 0.234142E+09 | 0.144940E+09 | 89202018.41 | 0.223365E+09 | 0.172759E+09 |
March | 0.278957E+09 | 0.148816E+09 | 0.130140E+09 | 0.262789E+09 | 0.162373E+09 |
April | 0.284935E+09 | 0.123730E+09 | 0.161204E+09 | 0.252035E+09 | 0.129021E+09 |
May | 0.269161E+09 | 80159602.41 | 0.189002E+09 | 0.215877E+09 | 0.115611E+09 |
June | 0.238311E+09 | 63957976.82 | 0.174353E+09 | 0.179366E+09 | 93863881.07 |
July | 0.268544E+09 | 98325647.04 | 0.170218E+09 | 0.222288E+09 | 90010046.61 |
August | 0.288545E+09 | 0.134541E+09 | 0.154003E+09 | 0.274891E+09 | 87871583.87 |
September | 0.309505E+09 | 0.170963E+09 | 0.138542E+09 | 0.309591E+09 | 0.114933E+09 |
October | 0.289689E+09 | 0.178891E+09 | 0.110798E+09 | 0.299280E+09 | 0.147723E+09 |
November | 0.165672E+09 | 94929653.84 | 70742070.08 | 0.151214E+09 | 0.172310E+09 |
December | 0.179094E+09 | 0.115878E+09 | 63216365.93 | 0.171848E+09 | 0.221690E+09 |
Annual Sum or Average | 0.297506E+10 | 0.145517E+10 | 0.151989E+10 | 0.270619E+10 | 0.172585E+10 |
Minimum of Months | 0.165672E+09 | 63957976.82 | 63216365.93 | 0.143645E+09 | 87871583.87 |
Maximum of Months | 0.309505E+09 | 0.178891E+09 | 0.189002E+09 | 0.309591E+09 | 0.221690E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.120060E+09 | 0.181094E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.186857E+09 | 0.143391E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.219895E+09 | 0.134380E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.211224E+09 | 0.106439E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.181543E+09 | 94825258.43 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.150901E+09 | 77159886.43 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.186350E+09 | 74428249.98 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.230188E+09 | 72850441.23 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.259434E+09 | 94793268.29 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.250693E+09 | 0.122041E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.126548E+09 | 0.143159E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.143720E+09 | 0.184528E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.226741E+10 | 0.142909E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.120060E+09 | 72850441.23 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.259434E+09 | 0.184528E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.120060E+09 | 0.181094E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.186857E+09 | 0.143391E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.219895E+09 | 0.134380E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.211224E+09 | 0.106439E+09 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.181543E+09 | 94825258.43 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.150901E+09 | 77159886.43 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.186350E+09 | 74428249.98 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.230188E+09 | 72850441.23 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.259434E+09 | 94793268.29 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.250693E+09 | 0.122041E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.126548E+09 | 0.143159E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.143720E+09 | 0.184528E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.226741E+10 | 0.142909E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.120060E+09 | 72850441.23 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.259434E+09 | 0.184528E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168507E+09 | 0.100038E+09 | 68468539.07 | 0.144074E+09 | 0.214811E+09 |
February | 0.234142E+09 | 0.144940E+09 | 89202018.41 | 0.224037E+09 | 0.170203E+09 |
March | 0.278957E+09 | 0.148816E+09 | 0.130140E+09 | 0.263538E+09 | 0.159523E+09 |
April | 0.284935E+09 | 0.123730E+09 | 0.161204E+09 | 0.253198E+09 | 0.126401E+09 |
May | 0.269161E+09 | 80159602.41 | 0.189002E+09 | 0.217647E+09 | 0.112658E+09 |
June | 0.238311E+09 | 63957976.82 | 0.174353E+09 | 0.180890E+09 | 91694735.06 |
July | 0.268544E+09 | 98325647.04 | 0.170218E+09 | 0.223193E+09 | 88502228.21 |
August | 0.288545E+09 | 0.134541E+09 | 0.154003E+09 | 0.275552E+09 | 86676103.32 |
September | 0.309505E+09 | 0.170963E+09 | 0.138542E+09 | 0.310624E+09 | 0.112781E+09 |
October | 0.289689E+09 | 0.178891E+09 | 0.110798E+09 | 0.300286E+09 | 0.145027E+09 |
November | 0.165672E+09 | 94929653.84 | 70742070.08 | 0.151728E+09 | 0.169932E+09 |
December | 0.179094E+09 | 0.115878E+09 | 63216365.93 | 0.172274E+09 | 0.219003E+09 |
Annual Sum or Average | 0.297506E+10 | 0.145517E+10 | 0.151989E+10 | 0.271704E+10 | 0.169721E+10 |
Minimum of Months | 0.165672E+09 | 63957976.82 | 63216365.93 | 0.144074E+09 | 86676103.32 |
Maximum of Months | 0.309505E+09 | 0.178891E+09 | 0.189002E+09 | 0.310624E+09 | 0.219003E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.121422E+09 | 0.171335E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.188779E+09 | 0.134968E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.221885E+09 | 0.125309E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.213688E+09 | 98804108.62 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.184822E+09 | 87540906.21 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.153690E+09 | 71507059.80 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.188278E+09 | 69843249.25 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.231537E+09 | 68998436.89 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.261317E+09 | 89579267.62 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.252600E+09 | 0.115153E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.127831E+09 | 0.136068E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.144969E+09 | 0.175703E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.229082E+10 | 0.134481E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.121422E+09 | 68998436.89 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.261317E+09 | 0.175703E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140731E+09 | 83548602.39 | 57182516.14 | 0.121422E+09 | 0.171335E+09 |
February | 0.195547E+09 | 0.121049E+09 | 74498389.00 | 0.188779E+09 | 0.134968E+09 |
March | 0.232975E+09 | 0.124286E+09 | 0.108689E+09 | 0.221885E+09 | 0.125309E+09 |
April | 0.237968E+09 | 0.103335E+09 | 0.134632E+09 | 0.213688E+09 | 98804108.62 |
May | 0.224794E+09 | 66946481.14 | 0.157848E+09 | 0.184822E+09 | 87540906.21 |
June | 0.199029E+09 | 53415453.16 | 0.145613E+09 | 0.153690E+09 | 71507059.80 |
July | 0.224279E+09 | 82118122.80 | 0.142160E+09 | 0.188278E+09 | 69843249.25 |
August | 0.240982E+09 | 0.112364E+09 | 0.128618E+09 | 0.231537E+09 | 68998436.89 |
September | 0.258488E+09 | 0.142782E+09 | 0.115705E+09 | 0.261317E+09 | 89579267.62 |
October | 0.241938E+09 | 0.149404E+09 | 92534677.61 | 0.252600E+09 | 0.115153E+09 |
November | 0.138363E+09 | 79281908.70 | 59081289.30 | 0.127831E+09 | 0.136068E+09 |
December | 0.149573E+09 | 96777100.61 | 52796085.83 | 0.144969E+09 | 0.175703E+09 |
Annual Sum or Average | 0.248467E+10 | 0.121531E+10 | 0.126936E+10 | 0.229082E+10 | 0.134481E+10 |
Minimum of Months | 0.138363E+09 | 53415453.16 | 52796085.83 | 0.121422E+09 | 68998436.89 |
Maximum of Months | 0.258488E+09 | 0.149404E+09 | 0.157848E+09 | 0.261317E+09 | 0.175703E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168507E+09 | 0.100038E+09 | 68468539.07 | 0.145740E+09 | 0.203207E+09 |
February | 0.234142E+09 | 0.144940E+09 | 89202018.41 | 0.226373E+09 | 0.160195E+09 |
March | 0.278957E+09 | 0.148816E+09 | 0.130140E+09 | 0.265958E+09 | 0.148751E+09 |
April | 0.284935E+09 | 0.123730E+09 | 0.161204E+09 | 0.256172E+09 | 0.117355E+09 |
May | 0.269161E+09 | 80159602.41 | 0.189002E+09 | 0.221584E+09 | 0.104032E+09 |
June | 0.238311E+09 | 63957976.82 | 0.174353E+09 | 0.184227E+09 | 85007496.14 |
July | 0.268544E+09 | 98325647.04 | 0.170218E+09 | 0.225508E+09 | 83077937.33 |
August | 0.288545E+09 | 0.134541E+09 | 0.154003E+09 | 0.277168E+09 | 82115632.38 |
September | 0.309505E+09 | 0.170963E+09 | 0.138542E+09 | 0.312881E+09 | 0.106596E+09 |
October | 0.289689E+09 | 0.178891E+09 | 0.110798E+09 | 0.302582E+09 | 0.136860E+09 |
November | 0.165672E+09 | 94929653.84 | 70742070.08 | 0.153285E+09 | 0.161505E+09 |
December | 0.179094E+09 | 0.115878E+09 | 63216365.93 | 0.173795E+09 | 0.208500E+09 |
Annual Sum or Average | 0.297506E+10 | 0.145517E+10 | 0.151989E+10 | 0.274527E+10 | 0.159720E+10 |
Minimum of Months | 0.165672E+09 | 63957976.82 | 63216365.93 | 0.145740E+09 | 82115632.38 |
Maximum of Months | 0.309505E+09 | 0.178891E+09 | 0.189002E+09 | 0.312881E+09 | 0.208500E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 285.04 | 457.08 | 336.69 | 199.88 | 136.81 | 0.00 | 0.00 |
February | 490.69 | 399.40 | 517.96 | 320.63 | 197.33 | 0.00 | 0.00 |
March | 522.37 | 338.46 | 557.38 | 297.35 | 260.03 | 0.00 | 0.00 |
April | 515.04 | 279.40 | 588.30 | 255.46 | 332.84 | 0.00 | 0.00 |
May | 423.78 | 243.02 | 537.80 | 160.17 | 377.64 | 0.00 | 0.00 |
June | 364.96 | 200.76 | 492.04 | 132.05 | 359.98 | 0.00 | 0.00 |
July | 441.72 | 182.68 | 536.57 | 196.46 | 340.11 | 0.00 | 0.00 |
August | 547.78 | 177.46 | 576.53 | 268.82 | 307.71 | 0.00 | 0.00 |
September | 635.21 | 246.41 | 639.03 | 352.98 | 286.04 | 0.00 | 0.00 |
October | 593.03 | 311.38 | 578.82 | 357.44 | 221.38 | 0.00 | 0.00 |
November | 308.54 | 374.34 | 342.06 | 196.00 | 146.06 | 0.00 | 0.00 |
December | 340.91 | 463.02 | 357.84 | 231.53 | 126.31 | 0.00 | 0.00 |
Annual Sum or Average | 455.47 | 305.69 | 504.87 | 246.94 | 257.92 | 0.00 | 0.00 |
Minimum of Months | 285.04 | 177.46 | 336.69 | 132.05 | 126.31 | 0.00 | 0.00 |
Maximum of Months | 635.21 | 463.02 | 639.03 | 357.44 | 377.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 140.72 | 240.80 | 168.34 | 99.94 | 68.40 | 0.00 | 0.00 |
February | 242.36 | 212.11 | 258.98 | 160.32 | 98.66 | 0.00 | 0.00 |
March | 257.44 | 184.05 | 278.69 | 148.67 | 130.02 | 0.00 | 0.00 |
April | 252.16 | 153.28 | 294.15 | 127.73 | 166.42 | 0.00 | 0.00 |
May | 206.11 | 132.10 | 268.90 | 80.08 | 188.82 | 0.00 | 0.00 |
June | 179.61 | 105.21 | 246.02 | 66.03 | 179.99 | 0.00 | 0.00 |
July | 219.81 | 93.83 | 268.29 | 98.23 | 170.05 | 0.00 | 0.00 |
August | 272.94 | 91.03 | 288.27 | 134.41 | 153.86 | 0.00 | 0.00 |
September | 315.32 | 128.02 | 319.51 | 176.49 | 143.02 | 0.00 | 0.00 |
October | 292.36 | 169.01 | 289.41 | 178.72 | 110.69 | 0.00 | 0.00 |
November | 151.95 | 199.50 | 171.03 | 98.00 | 73.03 | 0.00 | 0.00 |
December | 168.81 | 243.74 | 178.92 | 115.77 | 63.16 | 0.00 | 0.00 |
Annual Sum or Average | 224.83 | 162.49 | 252.43 | 123.47 | 128.96 | 0.00 | 0.00 |
Minimum of Months | 140.72 | 91.03 | 168.34 | 66.03 | 63.16 | 0.00 | 0.00 |
Maximum of Months | 315.32 | 243.74 | 319.51 | 178.72 | 188.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 140.55 | 234.12 | 168.00 | 99.74 | 68.26 | 0.00 | 0.00 |
February | 242.12 | 206.25 | 258.45 | 159.99 | 98.46 | 0.00 | 0.00 |
March | 257.11 | 179.32 | 278.12 | 148.37 | 129.75 | 0.00 | 0.00 |
April | 251.56 | 150.66 | 293.55 | 127.47 | 166.08 | 0.00 | 0.00 |
May | 204.64 | 133.25 | 268.35 | 79.92 | 188.43 | 0.00 | 0.00 |
June | 178.21 | 108.01 | 245.51 | 65.89 | 179.62 | 0.00 | 0.00 |
July | 218.47 | 97.67 | 267.73 | 98.03 | 169.71 | 0.00 | 0.00 |
August | 271.63 | 95.12 | 287.68 | 134.14 | 153.54 | 0.00 | 0.00 |
September | 313.97 | 131.11 | 318.86 | 176.13 | 142.73 | 0.00 | 0.00 |
October | 291.56 | 167.65 | 288.82 | 178.35 | 110.46 | 0.00 | 0.00 |
November | 151.85 | 194.40 | 170.68 | 97.80 | 72.88 | 0.00 | 0.00 |
December | 168.62 | 237.40 | 178.55 | 115.53 | 63.03 | 0.00 | 0.00 |
Annual Sum or Average | 224.05 | 161.04 | 251.92 | 123.22 | 128.70 | 0.00 | 0.00 |
Minimum of Months | 140.55 | 95.12 | 168.00 | 65.89 | 63.03 | 0.00 | 0.00 |
Maximum of Months | 313.97 | 237.40 | 318.86 | 178.35 | 188.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 140.88 | 230.89 | 168.00 | 99.74 | 68.26 | 0.00 | 0.00 |
February | 242.70 | 203.41 | 258.45 | 159.99 | 98.46 | 0.00 | 0.00 |
March | 257.75 | 176.38 | 278.12 | 148.37 | 129.75 | 0.00 | 0.00 |
April | 252.48 | 147.97 | 293.55 | 127.47 | 166.08 | 0.00 | 0.00 |
May | 205.31 | 131.64 | 268.35 | 79.92 | 188.43 | 0.00 | 0.00 |
June | 178.43 | 107.34 | 245.51 | 65.89 | 179.62 | 0.00 | 0.00 |
July | 218.54 | 97.39 | 267.73 | 98.03 | 169.71 | 0.00 | 0.00 |
August | 271.66 | 94.96 | 287.68 | 134.14 | 153.54 | 0.00 | 0.00 |
September | 314.15 | 130.34 | 318.86 | 176.13 | 142.73 | 0.00 | 0.00 |
October | 292.25 | 164.89 | 288.82 | 178.35 | 110.46 | 0.00 | 0.00 |
November | 152.36 | 191.47 | 170.68 | 97.80 | 72.88 | 0.00 | 0.00 |
December | 168.95 | 234.51 | 178.55 | 115.53 | 63.03 | 0.00 | 0.00 |
Annual Sum or Average | 224.47 | 159.07 | 251.92 | 123.22 | 128.70 | 0.00 | 0.00 |
Minimum of Months | 140.88 | 94.96 | 168.00 | 65.89 | 63.03 | 0.00 | 0.00 |
Maximum of Months | 314.15 | 234.51 | 318.86 | 178.35 | 188.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 141.38 | 227.79 | 168.00 | 99.74 | 68.26 | 0.00 | 0.00 |
February | 243.55 | 200.61 | 258.45 | 159.99 | 98.46 | 0.00 | 0.00 |
March | 258.78 | 173.01 | 278.12 | 148.37 | 129.75 | 0.00 | 0.00 |
April | 254.25 | 144.30 | 293.55 | 127.47 | 166.08 | 0.00 | 0.00 |
May | 207.58 | 127.88 | 268.35 | 79.92 | 188.43 | 0.00 | 0.00 |
June | 179.57 | 105.33 | 245.51 | 65.89 | 179.62 | 0.00 | 0.00 |
July | 219.12 | 96.10 | 267.73 | 98.03 | 169.71 | 0.00 | 0.00 |
August | 272.17 | 93.76 | 287.68 | 134.14 | 153.54 | 0.00 | 0.00 |
September | 315.10 | 127.97 | 318.86 | 176.13 | 142.73 | 0.00 | 0.00 |
October | 293.77 | 160.43 | 288.82 | 178.35 | 110.46 | 0.00 | 0.00 |
November | 153.17 | 188.30 | 170.68 | 97.80 | 72.88 | 0.00 | 0.00 |
December | 169.44 | 231.67 | 178.55 | 115.53 | 63.03 | 0.00 | 0.00 |
Annual Sum or Average | 225.51 | 156.23 | 251.92 | 123.22 | 128.70 | 0.00 | 0.00 |
Minimum of Months | 141.38 | 93.76 | 168.00 | 65.89 | 63.03 | 0.00 | 0.00 |
Maximum of Months | 315.10 | 231.67 | 318.86 | 178.35 | 188.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 286.36 | 437.73 | 336.00 | 199.47 | 136.52 | 0.00 | 0.00 |
February | 492.42 | 385.80 | 516.90 | 319.97 | 196.92 | 0.00 | 0.00 |
March | 522.80 | 330.02 | 556.23 | 296.74 | 259.50 | 0.00 | 0.00 |
April | 516.87 | 271.41 | 587.09 | 254.94 | 332.15 | 0.00 | 0.00 |
May | 427.02 | 236.24 | 536.70 | 159.84 | 376.86 | 0.00 | 0.00 |
June | 366.33 | 197.84 | 491.03 | 131.78 | 359.24 | 0.00 | 0.00 |
July | 440.81 | 183.39 | 535.47 | 196.06 | 339.41 | 0.00 | 0.00 |
August | 546.24 | 178.93 | 575.35 | 268.27 | 307.08 | 0.00 | 0.00 |
September | 636.34 | 241.45 | 637.72 | 352.26 | 285.46 | 0.00 | 0.00 |
October | 595.31 | 300.81 | 577.63 | 356.70 | 220.93 | 0.00 | 0.00 |
November | 310.51 | 360.42 | 341.36 | 195.60 | 145.76 | 0.00 | 0.00 |
December | 342.12 | 446.64 | 357.11 | 231.06 | 126.05 | 0.00 | 0.00 |
Annual Sum or Average | 456.63 | 297.16 | 503.83 | 246.44 | 257.40 | 0.00 | 0.00 |
Minimum of Months | 286.36 | 178.93 | 336.00 | 131.78 | 126.05 | 0.00 | 0.00 |
Maximum of Months | 636.34 | 446.64 | 637.72 | 356.70 | 376.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 142.87 | 219.18 | 168.00 | 99.74 | 68.26 | 0.00 | 0.00 |
February | 246.05 | 192.69 | 258.45 | 159.99 | 98.46 | 0.00 | 0.00 |
March | 261.50 | 163.88 | 278.12 | 148.37 | 129.75 | 0.00 | 0.00 |
April | 258.87 | 134.74 | 293.55 | 127.47 | 166.08 | 0.00 | 0.00 |
May | 214.16 | 117.17 | 268.35 | 79.92 | 188.43 | 0.00 | 0.00 |
June | 183.87 | 98.15 | 245.51 | 65.89 | 179.62 | 0.00 | 0.00 |
July | 221.13 | 90.79 | 267.73 | 98.03 | 169.71 | 0.00 | 0.00 |
August | 273.74 | 88.51 | 287.68 | 134.14 | 153.54 | 0.00 | 0.00 |
September | 318.42 | 119.88 | 318.86 | 176.13 | 142.73 | 0.00 | 0.00 |
October | 297.77 | 149.24 | 288.82 | 178.35 | 110.46 | 0.00 | 0.00 |
November | 155.39 | 179.52 | 170.68 | 97.80 | 72.88 | 0.00 | 0.00 |
December | 171.04 | 223.19 | 178.55 | 115.53 | 63.03 | 0.00 | 0.00 |
Annual Sum or Average | 228.59 | 147.88 | 251.92 | 123.22 | 128.70 | 0.00 | 0.00 |
Minimum of Months | 142.87 | 88.51 | 168.00 | 65.89 | 63.03 | 0.00 | 0.00 |
Maximum of Months | 318.42 | 223.19 | 318.86 | 178.35 | 188.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 143.02 | 218.30 | 168.00 | 99.74 | 68.26 | 0.00 | 0.00 |
February | 246.35 | 191.73 | 258.45 | 159.99 | 98.46 | 0.00 | 0.00 |
March | 261.85 | 162.75 | 278.12 | 148.37 | 129.75 | 0.00 | 0.00 |
April | 259.47 | 133.61 | 293.55 | 127.47 | 166.08 | 0.00 | 0.00 |
May | 215.06 | 115.83 | 268.35 | 79.92 | 188.43 | 0.00 | 0.00 |
June | 184.65 | 97.16 | 245.51 | 65.89 | 179.62 | 0.00 | 0.00 |
July | 221.58 | 90.13 | 267.73 | 98.03 | 169.71 | 0.00 | 0.00 |
August | 274.11 | 87.96 | 287.68 | 134.14 | 153.54 | 0.00 | 0.00 |
September | 318.96 | 118.88 | 318.86 | 176.13 | 142.73 | 0.00 | 0.00 |
October | 298.31 | 147.98 | 288.82 | 178.35 | 110.46 | 0.00 | 0.00 |
November | 155.66 | 178.48 | 170.68 | 97.80 | 72.88 | 0.00 | 0.00 |
December | 171.22 | 222.24 | 178.55 | 115.53 | 63.03 | 0.00 | 0.00 |
Annual Sum or Average | 229.04 | 146.89 | 251.92 | 123.22 | 128.70 | 0.00 | 0.00 |
Minimum of Months | 143.02 | 87.96 | 168.00 | 65.89 | 63.03 | 0.00 | 0.00 |
Maximum of Months | 318.96 | 222.24 | 318.86 | 178.35 | 188.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 143.44 | 215.43 | 168.00 | 99.74 | 68.26 | 0.00 | 0.00 |
February | 247.09 | 188.90 | 258.45 | 159.99 | 98.46 | 0.00 | 0.00 |
March | 262.59 | 159.90 | 278.12 | 148.37 | 129.75 | 0.00 | 0.00 |
April | 260.67 | 130.89 | 293.55 | 127.47 | 166.08 | 0.00 | 0.00 |
May | 216.82 | 112.87 | 268.35 | 79.92 | 188.43 | 0.00 | 0.00 |
June | 186.22 | 94.91 | 245.51 | 65.89 | 179.62 | 0.00 | 0.00 |
July | 222.48 | 88.62 | 267.73 | 98.03 | 169.71 | 0.00 | 0.00 |
August | 274.76 | 86.76 | 287.68 | 134.14 | 153.54 | 0.00 | 0.00 |
September | 320.02 | 116.65 | 318.86 | 176.13 | 142.73 | 0.00 | 0.00 |
October | 299.31 | 145.28 | 288.82 | 178.35 | 110.46 | 0.00 | 0.00 |
November | 156.18 | 176.02 | 170.68 | 97.80 | 72.88 | 0.00 | 0.00 |
December | 171.64 | 219.56 | 178.55 | 115.53 | 63.03 | 0.00 | 0.00 |
Annual Sum or Average | 229.95 | 144.45 | 251.92 | 123.22 | 128.70 | 0.00 | 0.00 |
Minimum of Months | 143.44 | 86.76 | 168.00 | 65.89 | 63.03 | 0.00 | 0.00 |
Maximum of Months | 320.02 | 219.56 | 318.86 | 178.35 | 188.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 145.08 | 203.81 | 168.00 | 99.74 | 68.26 | 0.00 | 0.00 |
February | 249.64 | 177.80 | 258.45 | 159.99 | 98.46 | 0.00 | 0.00 |
March | 264.98 | 149.11 | 278.12 | 148.37 | 129.75 | 0.00 | 0.00 |
April | 263.71 | 121.51 | 293.55 | 127.47 | 166.08 | 0.00 | 0.00 |
May | 220.74 | 104.21 | 268.35 | 79.92 | 188.43 | 0.00 | 0.00 |
June | 189.66 | 87.97 | 245.51 | 65.89 | 179.62 | 0.00 | 0.00 |
July | 224.79 | 83.17 | 267.73 | 98.03 | 169.71 | 0.00 | 0.00 |
August | 276.37 | 82.18 | 287.68 | 134.14 | 153.54 | 0.00 | 0.00 |
September | 322.34 | 110.24 | 318.86 | 176.13 | 142.73 | 0.00 | 0.00 |
October | 301.59 | 137.08 | 288.82 | 178.35 | 110.46 | 0.00 | 0.00 |
November | 157.77 | 167.30 | 170.68 | 97.80 | 72.88 | 0.00 | 0.00 |
December | 173.14 | 209.04 | 178.55 | 115.53 | 63.03 | 0.00 | 0.00 |
Annual Sum or Average | 232.33 | 135.93 | 251.92 | 123.22 | 128.70 | 0.00 | 0.00 |
Minimum of Months | 145.08 | 82.18 | 168.00 | 65.89 | 63.03 | 0.00 | 0.00 |
Maximum of Months | 322.34 | 209.04 | 318.86 | 178.35 | 188.43 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.763442E+09 | 0.122425E+10 | 0.901790E+09 | 0.535371E+09 | 0.366420E+09 | 0.00 | 0.00 |
February | 0.118708E+10 | 0.966221E+09 | 0.125305E+10 | 0.775669E+09 | 0.477378E+09 | 0.00 | 0.00 |
March | 0.139912E+10 | 0.906519E+09 | 0.149288E+10 | 0.796413E+09 | 0.696466E+09 | 0.00 | 0.00 |
April | 0.133498E+10 | 0.724206E+09 | 0.152487E+10 | 0.662161E+09 | 0.862710E+09 | 0.00 | 0.00 |
May | 0.113506E+10 | 0.650900E+09 | 0.144046E+10 | 0.428986E+09 | 0.101147E+10 | 0.00 | 0.00 |
June | 0.945973E+09 | 0.520380E+09 | 0.127536E+10 | 0.342281E+09 | 0.933076E+09 | 0.00 | 0.00 |
July | 0.118309E+10 | 0.489295E+09 | 0.143715E+10 | 0.526204E+09 | 0.910949E+09 | 0.00 | 0.00 |
August | 0.146717E+10 | 0.475319E+09 | 0.154419E+10 | 0.720018E+09 | 0.824172E+09 | 0.00 | 0.00 |
September | 0.164646E+10 | 0.638688E+09 | 0.165636E+10 | 0.914932E+09 | 0.741428E+09 | 0.00 | 0.00 |
October | 0.158836E+10 | 0.834002E+09 | 0.155032E+10 | 0.957364E+09 | 0.592952E+09 | 0.00 | 0.00 |
November | 0.799726E+09 | 0.970290E+09 | 0.886617E+09 | 0.508030E+09 | 0.378587E+09 | 0.00 | 0.00 |
December | 0.913085E+09 | 0.124016E+10 | 0.958449E+09 | 0.620137E+09 | 0.338312E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.143636E+11 | 0.964023E+10 | 0.159215E+11 | 0.778757E+10 | 0.813392E+10 | 0.00 | 0.00 |
Minimum of Months | 0.763442E+09 | 0.475319E+09 | 0.886617E+09 | 0.342281E+09 | 0.338312E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164646E+10 | 0.124016E+10 | 0.165636E+10 | 0.957364E+09 | 0.101147E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.376908E+09 | 0.644967E+09 | 0.450895E+09 | 0.267685E+09 | 0.183210E+09 | 0.00 | 0.00 |
February | 0.586315E+09 | 0.513129E+09 | 0.626523E+09 | 0.387835E+09 | 0.238689E+09 | 0.00 | 0.00 |
March | 0.689531E+09 | 0.492952E+09 | 0.746440E+09 | 0.398207E+09 | 0.348233E+09 | 0.00 | 0.00 |
April | 0.653588E+09 | 0.397313E+09 | 0.762435E+09 | 0.331081E+09 | 0.431355E+09 | 0.00 | 0.00 |
May | 0.552040E+09 | 0.353806E+09 | 0.720228E+09 | 0.214493E+09 | 0.505735E+09 | 0.00 | 0.00 |
June | 0.465550E+09 | 0.272717E+09 | 0.637678E+09 | 0.171140E+09 | 0.466538E+09 | 0.00 | 0.00 |
July | 0.588750E+09 | 0.251320E+09 | 0.718577E+09 | 0.263102E+09 | 0.455475E+09 | 0.00 | 0.00 |
August | 0.731044E+09 | 0.243808E+09 | 0.772095E+09 | 0.360009E+09 | 0.412086E+09 | 0.00 | 0.00 |
September | 0.817303E+09 | 0.331818E+09 | 0.828180E+09 | 0.457466E+09 | 0.370714E+09 | 0.00 | 0.00 |
October | 0.783047E+09 | 0.452669E+09 | 0.775158E+09 | 0.478682E+09 | 0.296476E+09 | 0.00 | 0.00 |
November | 0.393862E+09 | 0.517102E+09 | 0.443308E+09 | 0.254015E+09 | 0.189293E+09 | 0.00 | 0.00 |
December | 0.452153E+09 | 0.652841E+09 | 0.479225E+09 | 0.310069E+09 | 0.169156E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.709009E+10 | 0.512444E+10 | 0.796074E+10 | 0.389378E+10 | 0.406696E+10 | 0.00 | 0.00 |
Minimum of Months | 0.376908E+09 | 0.243808E+09 | 0.443308E+09 | 0.171140E+09 | 0.169156E+09 | 0.00 | 0.00 |
Maximum of Months | 0.817303E+09 | 0.652841E+09 | 0.828180E+09 | 0.478682E+09 | 0.505735E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.376461E+09 | 0.627058E+09 | 0.449969E+09 | 0.267136E+09 | 0.182834E+09 | 0.00 | 0.00 |
February | 0.585740E+09 | 0.498960E+09 | 0.625237E+09 | 0.387038E+09 | 0.238199E+09 | 0.00 | 0.00 |
March | 0.688641E+09 | 0.480301E+09 | 0.744907E+09 | 0.397389E+09 | 0.347518E+09 | 0.00 | 0.00 |
April | 0.652053E+09 | 0.390508E+09 | 0.760870E+09 | 0.330401E+09 | 0.430469E+09 | 0.00 | 0.00 |
May | 0.548096E+09 | 0.356907E+09 | 0.718750E+09 | 0.214053E+09 | 0.504697E+09 | 0.00 | 0.00 |
June | 0.461920E+09 | 0.279958E+09 | 0.636369E+09 | 0.170789E+09 | 0.465580E+09 | 0.00 | 0.00 |
July | 0.585139E+09 | 0.261589E+09 | 0.717101E+09 | 0.262562E+09 | 0.454539E+09 | 0.00 | 0.00 |
August | 0.727543E+09 | 0.254779E+09 | 0.770510E+09 | 0.359270E+09 | 0.411240E+09 | 0.00 | 0.00 |
September | 0.813802E+09 | 0.339836E+09 | 0.826480E+09 | 0.456527E+09 | 0.369953E+09 | 0.00 | 0.00 |
October | 0.780915E+09 | 0.449035E+09 | 0.773566E+09 | 0.477699E+09 | 0.295867E+09 | 0.00 | 0.00 |
November | 0.393599E+09 | 0.503884E+09 | 0.442398E+09 | 0.253493E+09 | 0.188905E+09 | 0.00 | 0.00 |
December | 0.451627E+09 | 0.635858E+09 | 0.478241E+09 | 0.309432E+09 | 0.168809E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.706554E+10 | 0.507867E+10 | 0.794440E+10 | 0.388579E+10 | 0.405861E+10 | 0.00 | 0.00 |
Minimum of Months | 0.376461E+09 | 0.254779E+09 | 0.442398E+09 | 0.170789E+09 | 0.168809E+09 | 0.00 | 0.00 |
Maximum of Months | 0.813802E+09 | 0.635858E+09 | 0.826480E+09 | 0.477699E+09 | 0.504697E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.377331E+09 | 0.618429E+09 | 0.449969E+09 | 0.267136E+09 | 0.182834E+09 | 0.00 | 0.00 |
February | 0.587135E+09 | 0.492087E+09 | 0.625237E+09 | 0.387038E+09 | 0.238199E+09 | 0.00 | 0.00 |
March | 0.690350E+09 | 0.472412E+09 | 0.744907E+09 | 0.397389E+09 | 0.347518E+09 | 0.00 | 0.00 |
April | 0.654425E+09 | 0.383534E+09 | 0.760870E+09 | 0.330401E+09 | 0.430469E+09 | 0.00 | 0.00 |
May | 0.549902E+09 | 0.352573E+09 | 0.718750E+09 | 0.214053E+09 | 0.504697E+09 | 0.00 | 0.00 |
June | 0.462479E+09 | 0.278225E+09 | 0.636369E+09 | 0.170789E+09 | 0.465580E+09 | 0.00 | 0.00 |
July | 0.585325E+09 | 0.260842E+09 | 0.717101E+09 | 0.262562E+09 | 0.454539E+09 | 0.00 | 0.00 |
August | 0.727612E+09 | 0.254351E+09 | 0.770510E+09 | 0.359270E+09 | 0.411240E+09 | 0.00 | 0.00 |
September | 0.814266E+09 | 0.337845E+09 | 0.826480E+09 | 0.456527E+09 | 0.369953E+09 | 0.00 | 0.00 |
October | 0.782758E+09 | 0.441647E+09 | 0.773566E+09 | 0.477699E+09 | 0.295867E+09 | 0.00 | 0.00 |
November | 0.394912E+09 | 0.496298E+09 | 0.442398E+09 | 0.253493E+09 | 0.188905E+09 | 0.00 | 0.00 |
December | 0.452514E+09 | 0.628106E+09 | 0.478241E+09 | 0.309432E+09 | 0.168809E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.707901E+10 | 0.501635E+10 | 0.794440E+10 | 0.388579E+10 | 0.405861E+10 | 0.00 | 0.00 |
Minimum of Months | 0.377331E+09 | 0.254351E+09 | 0.442398E+09 | 0.170789E+09 | 0.168809E+09 | 0.00 | 0.00 |
Maximum of Months | 0.814266E+09 | 0.628106E+09 | 0.826480E+09 | 0.477699E+09 | 0.504697E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.378676E+09 | 0.610123E+09 | 0.449969E+09 | 0.267136E+09 | 0.182834E+09 | 0.00 | 0.00 |
February | 0.589204E+09 | 0.485308E+09 | 0.625237E+09 | 0.387038E+09 | 0.238199E+09 | 0.00 | 0.00 |
March | 0.693126E+09 | 0.463382E+09 | 0.744907E+09 | 0.397389E+09 | 0.347518E+09 | 0.00 | 0.00 |
April | 0.659014E+09 | 0.374020E+09 | 0.760870E+09 | 0.330401E+09 | 0.430469E+09 | 0.00 | 0.00 |
May | 0.555974E+09 | 0.342516E+09 | 0.718750E+09 | 0.214053E+09 | 0.504697E+09 | 0.00 | 0.00 |
June | 0.465443E+09 | 0.273010E+09 | 0.636369E+09 | 0.170789E+09 | 0.465580E+09 | 0.00 | 0.00 |
July | 0.586878E+09 | 0.257405E+09 | 0.717101E+09 | 0.262562E+09 | 0.454539E+09 | 0.00 | 0.00 |
August | 0.728976E+09 | 0.251121E+09 | 0.770510E+09 | 0.359270E+09 | 0.411240E+09 | 0.00 | 0.00 |
September | 0.816726E+09 | 0.331690E+09 | 0.826480E+09 | 0.456527E+09 | 0.369953E+09 | 0.00 | 0.00 |
October | 0.786830E+09 | 0.429690E+09 | 0.773566E+09 | 0.477699E+09 | 0.295867E+09 | 0.00 | 0.00 |
November | 0.397013E+09 | 0.488072E+09 | 0.442398E+09 | 0.253493E+09 | 0.188905E+09 | 0.00 | 0.00 |
December | 0.453817E+09 | 0.620514E+09 | 0.478241E+09 | 0.309432E+09 | 0.168809E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.711168E+10 | 0.492685E+10 | 0.794440E+10 | 0.388579E+10 | 0.405861E+10 | 0.00 | 0.00 |
Minimum of Months | 0.378676E+09 | 0.251121E+09 | 0.442398E+09 | 0.170789E+09 | 0.168809E+09 | 0.00 | 0.00 |
Maximum of Months | 0.816726E+09 | 0.620514E+09 | 0.826480E+09 | 0.477699E+09 | 0.504697E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.766996E+09 | 0.117242E+10 | 0.899938E+09 | 0.534271E+09 | 0.365667E+09 | 0.00 | 0.00 |
February | 0.119126E+10 | 0.933320E+09 | 0.125047E+10 | 0.774076E+09 | 0.476398E+09 | 0.00 | 0.00 |
March | 0.140028E+10 | 0.883933E+09 | 0.148981E+10 | 0.794778E+09 | 0.695036E+09 | 0.00 | 0.00 |
April | 0.133973E+10 | 0.703495E+09 | 0.152174E+10 | 0.660802E+09 | 0.860938E+09 | 0.00 | 0.00 |
May | 0.114374E+10 | 0.632745E+09 | 0.143750E+10 | 0.428105E+09 | 0.100939E+10 | 0.00 | 0.00 |
June | 0.949528E+09 | 0.512788E+09 | 0.127274E+10 | 0.341578E+09 | 0.931160E+09 | 0.00 | 0.00 |
July | 0.118066E+10 | 0.491199E+09 | 0.143420E+10 | 0.525124E+09 | 0.909079E+09 | 0.00 | 0.00 |
August | 0.146304E+10 | 0.479251E+09 | 0.154102E+10 | 0.718540E+09 | 0.822479E+09 | 0.00 | 0.00 |
September | 0.164939E+10 | 0.625849E+09 | 0.165296E+10 | 0.913054E+09 | 0.739906E+09 | 0.00 | 0.00 |
October | 0.159449E+10 | 0.805699E+09 | 0.154713E+10 | 0.955398E+09 | 0.591735E+09 | 0.00 | 0.00 |
November | 0.804846E+09 | 0.934208E+09 | 0.884796E+09 | 0.506987E+09 | 0.377809E+09 | 0.00 | 0.00 |
December | 0.916329E+09 | 0.119628E+10 | 0.956481E+09 | 0.618864E+09 | 0.337617E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.144003E+11 | 0.937120E+10 | 0.158888E+11 | 0.777158E+10 | 0.811722E+10 | 0.00 | 0.00 |
Minimum of Months | 0.766996E+09 | 0.479251E+09 | 0.884796E+09 | 0.341578E+09 | 0.337617E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164939E+10 | 0.119628E+10 | 0.165296E+10 | 0.955398E+09 | 0.100939E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.382664E+09 | 0.587052E+09 | 0.449969E+09 | 0.267136E+09 | 0.182834E+09 | 0.00 | 0.00 |
February | 0.595255E+09 | 0.466146E+09 | 0.625237E+09 | 0.387038E+09 | 0.238199E+09 | 0.00 | 0.00 |
March | 0.700400E+09 | 0.438935E+09 | 0.744907E+09 | 0.397389E+09 | 0.347518E+09 | 0.00 | 0.00 |
April | 0.670993E+09 | 0.349259E+09 | 0.760870E+09 | 0.330401E+09 | 0.430469E+09 | 0.00 | 0.00 |
May | 0.573595E+09 | 0.313815E+09 | 0.718750E+09 | 0.214053E+09 | 0.504697E+09 | 0.00 | 0.00 |
June | 0.476600E+09 | 0.254402E+09 | 0.636369E+09 | 0.170789E+09 | 0.465580E+09 | 0.00 | 0.00 |
July | 0.592265E+09 | 0.243170E+09 | 0.717101E+09 | 0.262562E+09 | 0.454539E+09 | 0.00 | 0.00 |
August | 0.733194E+09 | 0.237071E+09 | 0.770510E+09 | 0.359270E+09 | 0.411240E+09 | 0.00 | 0.00 |
September | 0.825340E+09 | 0.310718E+09 | 0.826480E+09 | 0.456527E+09 | 0.369953E+09 | 0.00 | 0.00 |
October | 0.797545E+09 | 0.399720E+09 | 0.773566E+09 | 0.477699E+09 | 0.295867E+09 | 0.00 | 0.00 |
November | 0.402775E+09 | 0.465320E+09 | 0.442398E+09 | 0.253493E+09 | 0.188905E+09 | 0.00 | 0.00 |
December | 0.458113E+09 | 0.597788E+09 | 0.478241E+09 | 0.309432E+09 | 0.168809E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.720874E+10 | 0.466340E+10 | 0.794440E+10 | 0.388579E+10 | 0.405861E+10 | 0.00 | 0.00 |
Minimum of Months | 0.382664E+09 | 0.237071E+09 | 0.442398E+09 | 0.170789E+09 | 0.168809E+09 | 0.00 | 0.00 |
Maximum of Months | 0.825340E+09 | 0.597788E+09 | 0.826480E+09 | 0.477699E+09 | 0.504697E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.383064E+09 | 0.584691E+09 | 0.449969E+09 | 0.267136E+09 | 0.182834E+09 | 0.00 | 0.00 |
February | 0.595970E+09 | 0.463833E+09 | 0.625237E+09 | 0.387038E+09 | 0.238199E+09 | 0.00 | 0.00 |
March | 0.701343E+09 | 0.435922E+09 | 0.744907E+09 | 0.397389E+09 | 0.347518E+09 | 0.00 | 0.00 |
April | 0.672549E+09 | 0.346313E+09 | 0.760870E+09 | 0.330401E+09 | 0.430469E+09 | 0.00 | 0.00 |
May | 0.576006E+09 | 0.310243E+09 | 0.718750E+09 | 0.214053E+09 | 0.504697E+09 | 0.00 | 0.00 |
June | 0.478622E+09 | 0.251845E+09 | 0.636369E+09 | 0.170789E+09 | 0.465580E+09 | 0.00 | 0.00 |
July | 0.593479E+09 | 0.241412E+09 | 0.717101E+09 | 0.262562E+09 | 0.454539E+09 | 0.00 | 0.00 |
August | 0.734169E+09 | 0.235591E+09 | 0.770510E+09 | 0.359270E+09 | 0.411240E+09 | 0.00 | 0.00 |
September | 0.826736E+09 | 0.308148E+09 | 0.826480E+09 | 0.456527E+09 | 0.369953E+09 | 0.00 | 0.00 |
October | 0.798988E+09 | 0.396346E+09 | 0.773566E+09 | 0.477699E+09 | 0.295867E+09 | 0.00 | 0.00 |
November | 0.403463E+09 | 0.462622E+09 | 0.442398E+09 | 0.253493E+09 | 0.188905E+09 | 0.00 | 0.00 |
December | 0.458586E+09 | 0.595249E+09 | 0.478241E+09 | 0.309432E+09 | 0.168809E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.722298E+10 | 0.463221E+10 | 0.794440E+10 | 0.388579E+10 | 0.405861E+10 | 0.00 | 0.00 |
Minimum of Months | 0.383064E+09 | 0.235591E+09 | 0.442398E+09 | 0.170789E+09 | 0.168809E+09 | 0.00 | 0.00 |
Maximum of Months | 0.826736E+09 | 0.595249E+09 | 0.826480E+09 | 0.477699E+09 | 0.504697E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.384191E+09 | 0.576997E+09 | 0.449969E+09 | 0.267136E+09 | 0.182834E+09 | 0.00 | 0.00 |
February | 0.597750E+09 | 0.456985E+09 | 0.625237E+09 | 0.387038E+09 | 0.238199E+09 | 0.00 | 0.00 |
March | 0.703328E+09 | 0.428281E+09 | 0.744907E+09 | 0.397389E+09 | 0.347518E+09 | 0.00 | 0.00 |
April | 0.675645E+09 | 0.339277E+09 | 0.760870E+09 | 0.330401E+09 | 0.430469E+09 | 0.00 | 0.00 |
May | 0.580733E+09 | 0.302308E+09 | 0.718750E+09 | 0.214053E+09 | 0.504697E+09 | 0.00 | 0.00 |
June | 0.482692E+09 | 0.246014E+09 | 0.636369E+09 | 0.170789E+09 | 0.465580E+09 | 0.00 | 0.00 |
July | 0.595892E+09 | 0.237359E+09 | 0.717101E+09 | 0.262562E+09 | 0.454539E+09 | 0.00 | 0.00 |
August | 0.735927E+09 | 0.232377E+09 | 0.770510E+09 | 0.359270E+09 | 0.411240E+09 | 0.00 | 0.00 |
September | 0.829493E+09 | 0.302367E+09 | 0.826480E+09 | 0.456527E+09 | 0.369953E+09 | 0.00 | 0.00 |
October | 0.801672E+09 | 0.389109E+09 | 0.773566E+09 | 0.477699E+09 | 0.295867E+09 | 0.00 | 0.00 |
November | 0.404824E+09 | 0.456251E+09 | 0.442398E+09 | 0.253493E+09 | 0.188905E+09 | 0.00 | 0.00 |
December | 0.459713E+09 | 0.588059E+09 | 0.478241E+09 | 0.309432E+09 | 0.168809E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.725186E+10 | 0.455538E+10 | 0.794440E+10 | 0.388579E+10 | 0.405861E+10 | 0.00 | 0.00 |
Minimum of Months | 0.384191E+09 | 0.232377E+09 | 0.442398E+09 | 0.170789E+09 | 0.168809E+09 | 0.00 | 0.00 |
Maximum of Months | 0.829493E+09 | 0.588059E+09 | 0.826480E+09 | 0.477699E+09 | 0.504697E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.388583E+09 | 0.545876E+09 | 0.449969E+09 | 0.267136E+09 | 0.182834E+09 | 0.00 | 0.00 |
February | 0.603932E+09 | 0.430130E+09 | 0.625237E+09 | 0.387038E+09 | 0.238199E+09 | 0.00 | 0.00 |
March | 0.709726E+09 | 0.399367E+09 | 0.744907E+09 | 0.397389E+09 | 0.347518E+09 | 0.00 | 0.00 |
April | 0.683548E+09 | 0.314963E+09 | 0.760870E+09 | 0.330401E+09 | 0.430469E+09 | 0.00 | 0.00 |
May | 0.591228E+09 | 0.279113E+09 | 0.718750E+09 | 0.214053E+09 | 0.504697E+09 | 0.00 | 0.00 |
June | 0.491606E+09 | 0.228021E+09 | 0.636369E+09 | 0.170789E+09 | 0.465580E+09 | 0.00 | 0.00 |
July | 0.602064E+09 | 0.222764E+09 | 0.717101E+09 | 0.262562E+09 | 0.454539E+09 | 0.00 | 0.00 |
August | 0.740242E+09 | 0.220113E+09 | 0.770510E+09 | 0.359270E+09 | 0.411240E+09 | 0.00 | 0.00 |
September | 0.835514E+09 | 0.285754E+09 | 0.826480E+09 | 0.456527E+09 | 0.369953E+09 | 0.00 | 0.00 |
October | 0.807782E+09 | 0.367166E+09 | 0.773566E+09 | 0.477699E+09 | 0.295867E+09 | 0.00 | 0.00 |
November | 0.408945E+09 | 0.433640E+09 | 0.442398E+09 | 0.253493E+09 | 0.188905E+09 | 0.00 | 0.00 |
December | 0.463733E+09 | 0.559905E+09 | 0.478241E+09 | 0.309432E+09 | 0.168809E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.732690E+10 | 0.428681E+10 | 0.794440E+10 | 0.388579E+10 | 0.405861E+10 | 0.00 | 0.00 |
Minimum of Months | 0.388583E+09 | 0.220113E+09 | 0.442398E+09 | 0.170789E+09 | 0.168809E+09 | 0.00 | 0.00 |
Maximum of Months | 0.835514E+09 | 0.559905E+09 | 0.826480E+09 | 0.477699E+09 | 0.504697E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.11 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.09 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.03 | 5.25 | 4.23 | 1.21 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.01 | 7.49 | 3.85 | 3.74 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.79 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.40 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.56 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.54 | 10.74 | 2.23 | 5.46 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.18 | 7.19 | 4.02 | 2.09 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.12 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.11 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.56 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.48 | 7.20 | 8.40 | 3.88 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.15 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.40 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.20 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.35 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.72 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.76 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.67 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.67 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.47 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.93 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.42 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.42 | 0.00 | 0.00 | 3.88 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.76 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -1.9 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.18 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.56 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.56 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.48 | 11-JAN-21:00 | 11.10 | 10.00 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 12.41 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.44 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.27 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.57 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.72 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.16 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.12 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.96 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.04 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.70 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.48 | 11.10 | 6.70 | 0.00 | 6.35 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 28.90 | 15.70 | 6.70 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.48 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.34 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.09 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.76 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.92 | 2.10 | 6.88 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.00 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.09 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.308633E+09 | -233292427.7 | 0.00 | 0.00 | 744.00 | 0.00 | -75340219.6 | 58.99 | 0.00 | 0.00 |
February | 0.281128E+09 | -213324673.1 | 0.00 | 0.00 | 672.00 | 0.00 | -67803261.2 | 58.99 | 0.00 | 0.00 |
March | 0.311789E+09 | -237164962.8 | 0.00 | 0.00 | 744.00 | 0.00 | -74624196.0 | 58.99 | 0.00 | 0.00 |
April | 0.291594E+09 | -220621696.5 | 0.00 | 0.00 | 720.00 | 0.00 | -70971970.9 | 59.00 | 0.00 | 0.00 |
May | 0.290955E+09 | -219626054.6 | 0.00 | 0.00 | 744.00 | 0.00 | -71328946.7 | 58.99 | 0.00 | 0.00 |
June | 0.273629E+09 | -206384835.6 | 0.00 | 0.00 | 720.00 | 0.00 | -67244175.4 | 59.00 | 0.00 | 0.00 |
July | 0.272143E+09 | -203417843.9 | 0.00 | 0.00 | 744.00 | 0.00 | -68724997.6 | 58.99 | 0.00 | 0.00 |
August | 0.274216E+09 | -205603438.4 | 0.00 | 0.00 | 744.00 | 0.00 | -68612294.1 | 59.00 | 0.00 | 0.00 |
September | 0.266904E+09 | -199744570.3 | 0.00 | 0.00 | 720.00 | 0.00 | -67159560.8 | 58.98 | 0.00 | 0.00 |
October | 0.283142E+09 | -210826340.4 | 0.00 | 0.00 | 744.00 | 0.00 | -72315214.0 | 58.99 | 0.00 | 0.00 |
November | 0.283596E+09 | -211657258.4 | 0.00 | 0.00 | 720.00 | 0.00 | -71939234.0 | 58.99 | 0.00 | 0.00 |
December | 0.302921E+09 | -227820362.3 | 0.00 | 0.00 | 744.00 | 0.00 | -75100949.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.344065E+10 | -.258948E+10 | 8760.00 | -851165019.3 | 58.99 | |||||
Minimum of Months | 0.266904E+09 | -237164962.8 | 0.00 | 0.00 | 672.00 | 0.00 | -75340219.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.311789E+09 | -199744570.3 | 0.00 | 0.00 | 744.00 | 0.00 | -67159560.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.307468E+09 | -233299844.4 | 0.00 | 0.00 | 744.00 | 0.00 | -74168220.1 | 58.99 | 0.00 | 0.00 |
February | 0.279835E+09 | -213311986.3 | 0.00 | 0.00 | 672.00 | 0.00 | -66523119.6 | 59.00 | 0.00 | 0.00 |
March | 0.309887E+09 | -237151938.8 | 0.00 | 0.00 | 744.00 | 0.00 | -72734997.3 | 59.00 | 0.00 | 0.00 |
April | 0.289616E+09 | -220643555.0 | 0.00 | 0.00 | 720.00 | 0.00 | -68972654.6 | 58.98 | 0.00 | 0.00 |
May | 0.289237E+09 | -219630971.9 | 0.00 | 0.00 | 744.00 | 0.00 | -69606417.7 | 58.99 | 0.00 | 0.00 |
June | 0.272952E+09 | -206388967.1 | 0.00 | 0.00 | 720.00 | 0.00 | -66563350.1 | 58.99 | 0.00 | 0.00 |
July | 0.271848E+09 | -203414843.4 | 0.00 | 0.00 | 744.00 | 0.00 | -68433335.6 | 58.99 | 0.00 | 0.00 |
August | 0.273945E+09 | -205622044.7 | 0.00 | 0.00 | 744.00 | 0.00 | -68323015.1 | 58.99 | 0.00 | 0.00 |
September | 0.266255E+09 | -199730046.7 | 0.00 | 0.00 | 720.00 | 0.00 | -66525198.5 | 59.00 | 0.00 | 0.00 |
October | 0.281285E+09 | -210827783.9 | 0.00 | 0.00 | 744.00 | 0.00 | -70457563.0 | 58.99 | 0.00 | 0.00 |
November | 0.282147E+09 | -211656593.1 | 0.00 | 0.00 | 720.00 | 0.00 | -70490659.0 | 58.99 | 0.00 | 0.00 |
December | 0.301695E+09 | -227805260.5 | 0.00 | 0.00 | 744.00 | 0.00 | -73890119.1 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342617E+10 | -.258948E+10 | 8760.00 | -836688649.6 | 58.99 | |||||
Minimum of Months | 0.266255E+09 | -237151938.8 | 0.00 | 0.00 | 672.00 | 0.00 | -74168220.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.309887E+09 | -199730046.7 | 0.00 | 0.00 | 744.00 | 0.00 | -66523119.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.280222E+09 | -205139304.9 | 0.00 | 0.00 | 744.00 | 0.00 | -75082578.1 | 59.01 | 0.00 | 0.00 |
February | 0.255017E+09 | -187735791.6 | 0.00 | 0.00 | 672.00 | 0.00 | -67280846.2 | 58.99 | 0.00 | 0.00 |
March | 0.285311E+09 | -211824383.5 | 0.00 | 0.00 | 744.00 | 0.00 | -73486201.8 | 59.00 | 0.00 | 0.00 |
April | 0.263278E+09 | -193894909.5 | 0.00 | 0.00 | 720.00 | 0.00 | -69382947.5 | 58.99 | 0.00 | 0.00 |
May | 0.264145E+09 | -194789326.6 | 0.00 | 0.00 | 744.00 | 0.00 | -69355791.1 | 58.99 | 0.00 | 0.00 |
June | 0.249996E+09 | -183944974.6 | 0.00 | 0.00 | 720.00 | 0.00 | -66050871.5 | 59.00 | 0.00 | 0.00 |
July | 0.245422E+09 | -177690043.2 | 0.00 | 0.00 | 744.00 | 0.00 | -67731794.1 | 59.00 | 0.00 | 0.00 |
August | 0.251394E+09 | -183790567.5 | 0.00 | 0.00 | 744.00 | 0.00 | -67603361.4 | 58.99 | 0.00 | 0.00 |
September | 0.241412E+09 | -175390899.1 | 0.00 | 0.00 | 720.00 | 0.00 | -66021530.2 | 59.00 | 0.00 | 0.00 |
October | 0.256089E+09 | -185419798.2 | 0.00 | 0.00 | 744.00 | 0.00 | -70669438.2 | 58.99 | 0.00 | 0.00 |
November | 0.258101E+09 | -186869409.4 | 0.00 | 0.00 | 720.00 | 0.00 | -71231806.1 | 59.00 | 0.00 | 0.00 |
December | 0.273629E+09 | -198855005.0 | 0.00 | 0.00 | 744.00 | 0.00 | -74774238.3 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.312402E+10 | -.228534E+10 | 8760.00 | -838671404.3 | 59.00 | |||||
Minimum of Months | 0.241412E+09 | -211824383.5 | 0.00 | 0.00 | 672.00 | 0.00 | -75082578.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.285311E+09 | -175390899.1 | 0.00 | 0.00 | 744.00 | 0.00 | -66021530.2 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.280489E+09 | -205147421.4 | 0.00 | 0.00 | 744.00 | 0.00 | -75341260.4 | 59.00 | 0.00 | 0.00 |
February | 0.255278E+09 | -187736941.7 | 0.00 | 0.00 | 672.00 | 0.00 | -67540677.1 | 58.99 | 0.00 | 0.00 |
March | 0.285611E+09 | -211822484.5 | 0.00 | 0.00 | 744.00 | 0.00 | -73788624.7 | 58.99 | 0.00 | 0.00 |
April | 0.263604E+09 | -193890769.6 | 0.00 | 0.00 | 720.00 | 0.00 | -69713312.6 | 59.00 | 0.00 | 0.00 |
May | 0.264350E+09 | -194790533.3 | 0.00 | 0.00 | 744.00 | 0.00 | -69559255.7 | 58.99 | 0.00 | 0.00 |
June | 0.250067E+09 | -183941036.8 | 0.00 | 0.00 | 720.00 | 0.00 | -66125868.7 | 59.00 | 0.00 | 0.00 |
July | 0.245447E+09 | -177694398.8 | 0.00 | 0.00 | 744.00 | 0.00 | -67752897.7 | 59.00 | 0.00 | 0.00 |
August | 0.251413E+09 | -183795426.7 | 0.00 | 0.00 | 744.00 | 0.00 | -67617518.4 | 58.99 | 0.00 | 0.00 |
September | 0.241496E+09 | -175408307.8 | 0.00 | 0.00 | 720.00 | 0.00 | -66087714.4 | 58.99 | 0.00 | 0.00 |
October | 0.256403E+09 | -185403227.8 | 0.00 | 0.00 | 744.00 | 0.00 | -71000135.9 | 58.99 | 0.00 | 0.00 |
November | 0.258383E+09 | -186883378.5 | 0.00 | 0.00 | 720.00 | 0.00 | -71499954.1 | 58.99 | 0.00 | 0.00 |
December | 0.273874E+09 | -198856053.8 | 0.00 | 0.00 | 744.00 | 0.00 | -75018290.9 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.312642E+10 | -.228537E+10 | 8760.00 | -841045510.5 | 58.99 | |||||
Minimum of Months | 0.241496E+09 | -211822484.5 | 0.00 | 0.00 | 672.00 | 0.00 | -75341260.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.285611E+09 | -175408307.8 | 0.00 | 0.00 | 744.00 | 0.00 | -66087714.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.270294E+09 | -193897214.3 | 0.00 | 0.00 | 744.00 | 0.00 | -76397103.3 | 59.00 | 0.00 | 0.00 |
February | 0.246089E+09 | -177535143.0 | 0.00 | 0.00 | 672.00 | 0.00 | -68553511.2 | 58.99 | 0.00 | 0.00 |
March | 0.275530E+09 | -200432621.2 | 0.00 | 0.00 | 744.00 | 0.00 | -75097762.3 | 58.99 | 0.00 | 0.00 |
April | 0.254937E+09 | -183473319.6 | 0.00 | 0.00 | 720.00 | 0.00 | -71463996.7 | 59.00 | 0.00 | 0.00 |
May | 0.256062E+09 | -184197096.5 | 0.00 | 0.00 | 744.00 | 0.00 | -71865109.4 | 58.99 | 0.00 | 0.00 |
June | 0.241462E+09 | -174058095.2 | 0.00 | 0.00 | 720.00 | 0.00 | -67403938.3 | 59.00 | 0.00 | 0.00 |
July | 0.236585E+09 | -168068638.6 | 0.00 | 0.00 | 744.00 | 0.00 | -68516249.2 | 58.99 | 0.00 | 0.00 |
August | 0.242237E+09 | -173904228.9 | 0.00 | 0.00 | 744.00 | 0.00 | -68333055.3 | 58.99 | 0.00 | 0.00 |
September | 0.233474E+09 | -165993652.3 | 0.00 | 0.00 | 720.00 | 0.00 | -67480674.7 | 58.99 | 0.00 | 0.00 |
October | 0.248195E+09 | -175239818.9 | 0.00 | 0.00 | 744.00 | 0.00 | -72955133.3 | 58.99 | 0.00 | 0.00 |
November | 0.249158E+09 | -176506566.5 | 0.00 | 0.00 | 720.00 | 0.00 | -72651058.6 | 58.99 | 0.00 | 0.00 |
December | 0.264070E+09 | -188070757.2 | 0.00 | 0.00 | 744.00 | 0.00 | -75999521.7 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301809E+10 | -.216138E+10 | 8760.00 | -856717113.9 | 58.99 | |||||
Minimum of Months | 0.233474E+09 | -200432621.2 | 0.00 | 0.00 | 672.00 | 0.00 | -76397103.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.275530E+09 | -165993652.3 | 0.00 | 0.00 | 744.00 | 0.00 | -67403938.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.270369E+09 | -193899572.7 | 0.00 | 0.00 | 744.00 | 0.00 | -76469254.3 | 59.00 | 0.00 | 0.00 |
February | 0.246194E+09 | -177534366.1 | 0.00 | 0.00 | 672.00 | 0.00 | -68659433.4 | 58.99 | 0.00 | 0.00 |
March | 0.275708E+09 | -200435488.4 | 0.00 | 0.00 | 744.00 | 0.00 | -75272375.1 | 58.99 | 0.00 | 0.00 |
April | 0.255065E+09 | -183483641.3 | 0.00 | 0.00 | 720.00 | 0.00 | -71581016.3 | 58.99 | 0.00 | 0.00 |
May | 0.256177E+09 | -184208034.9 | 0.00 | 0.00 | 744.00 | 0.00 | -71969013.7 | 58.99 | 0.00 | 0.00 |
June | 0.241563E+09 | -174059701.6 | 0.00 | 0.00 | 720.00 | 0.00 | -67502942.0 | 58.99 | 0.00 | 0.00 |
July | 0.236713E+09 | -168060340.9 | 0.00 | 0.00 | 744.00 | 0.00 | -68652832.2 | 58.99 | 0.00 | 0.00 |
August | 0.242375E+09 | -173886221.8 | 0.00 | 0.00 | 744.00 | 0.00 | -68488836.4 | 59.00 | 0.00 | 0.00 |
September | 0.233563E+09 | -165986113.1 | 0.00 | 0.00 | 720.00 | 0.00 | -67576718.9 | 59.00 | 0.00 | 0.00 |
October | 0.248337E+09 | -175237258.3 | 0.00 | 0.00 | 744.00 | 0.00 | -73099658.5 | 58.99 | 0.00 | 0.00 |
November | 0.249316E+09 | -176507729.7 | 0.00 | 0.00 | 720.00 | 0.00 | -72808267.9 | 58.99 | 0.00 | 0.00 |
December | 0.264201E+09 | -188079417.4 | 0.00 | 0.00 | 744.00 | 0.00 | -76121799.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.301958E+10 | -.216138E+10 | 8760.00 | -858202147.7 | 58.99 | |||||
Minimum of Months | 0.233563E+09 | -200435488.4 | 0.00 | 0.00 | 672.00 | 0.00 | -76469254.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.275708E+09 | -165986113.1 | 0.00 | 0.00 | 744.00 | 0.00 | -67502942.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.270434E+09 | -193900387.3 | 0.00 | 0.00 | 744.00 | 0.00 | -76533650.8 | 58.99 | 0.00 | 0.00 |
February | 0.246271E+09 | -177533852.6 | 0.00 | 0.00 | 672.00 | 0.00 | -68737409.1 | 58.99 | 0.00 | 0.00 |
March | 0.275812E+09 | -200423606.4 | 0.00 | 0.00 | 744.00 | 0.00 | -75388440.4 | 59.00 | 0.00 | 0.00 |
April | 0.255194E+09 | -183486563.8 | 0.00 | 0.00 | 720.00 | 0.00 | -71707872.9 | 58.99 | 0.00 | 0.00 |
May | 0.256361E+09 | -184211301.5 | 0.00 | 0.00 | 744.00 | 0.00 | -72149966.3 | 58.98 | 0.00 | 0.00 |
June | 0.241715E+09 | -174058173.2 | 0.00 | 0.00 | 720.00 | 0.00 | -67656341.6 | 59.00 | 0.00 | 0.00 |
July | 0.236798E+09 | -168073598.6 | 0.00 | 0.00 | 744.00 | 0.00 | -68723946.4 | 58.99 | 0.00 | 0.00 |
August | 0.242441E+09 | -173917618.4 | 0.00 | 0.00 | 744.00 | 0.00 | -68523258.3 | 58.98 | 0.00 | 0.00 |
September | 0.233694E+09 | -165977560.0 | 0.00 | 0.00 | 720.00 | 0.00 | -67716780.0 | 59.00 | 0.00 | 0.00 |
October | 0.248482E+09 | -175238560.9 | 0.00 | 0.00 | 744.00 | 0.00 | -73242993.9 | 58.99 | 0.00 | 0.00 |
November | 0.249400E+09 | -176511495.3 | 0.00 | 0.00 | 720.00 | 0.00 | -72888609.7 | 58.99 | 0.00 | 0.00 |
December | 0.264273E+09 | -188081111.5 | 0.00 | 0.00 | 744.00 | 0.00 | -76191485.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.302087E+10 | -.216141E+10 | 8760.00 | -859460755.2 | 58.99 | |||||
Minimum of Months | 0.233694E+09 | -200423606.4 | 0.00 | 0.00 | 672.00 | 0.00 | -76533650.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.275812E+09 | -165977560.0 | 0.00 | 0.00 | 744.00 | 0.00 | -67656341.6 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | ||||||||||
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126956E+11 | 47944.97 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.879545E+10 | 47944.97 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.493934E+10 | 47944.97 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187750E+10 | 47944.97 | 11-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.192782E+09 | 7930.02 | 19-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1917280.54 | 1323.53 | 28-SEP-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.999019E+09 | 17229.80 | 28-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.647647E+10 | 47944.97 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108608E+11 | 47944.97 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.468389E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126956E+11 | 47944.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.359288E+10 | 25713.45 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221050E+10 | 25713.45 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.687722E+09 | 25713.45 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135275E+09 | 25713.45 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3713962.97 | 17511.52 | 18-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27947039.21 | 21297.76 | 28-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141954E+10 | 25713.45 | 10-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.282392E+10 | 25713.45 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109015E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.359288E+10 | 25713.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.409097E+10 | 28385.49 | 08-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253842E+10 | 28385.49 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.864466E+09 | 6530.80 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170661E+09 | 6492.84 | 19-APR-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 562451.66 | 513.77 | 18-MAY-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22468480.09 | 1452.84 | 30-OCT-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171717E+10 | 6681.73 | 26-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.329010E+10 | 28385.49 | 25-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126948E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.409097E+10 | 28385.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.432518E+10 | 28297.03 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.270000E+10 | 28297.03 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101121E+10 | 12231.55 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.229042E+09 | 7203.66 | 18-APR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 830661.22 | 889.29 | 18-MAY-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 48983727.25 | 2627.04 | 30-OCT-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187741E+10 | 12861.39 | 26-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.349944E+10 | 28297.03 | 25-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136921E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.432518E+10 | 28297.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.469599E+10 | 28164.41 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.297388E+10 | 28164.41 | 12-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127619E+10 | 18876.47 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.356351E+09 | 4422.87 | 20-APR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5852073.60 | 1388.59 | 18-MAY-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127876E+09 | 3634.09 | 30-OCT-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214130E+10 | 19440.52 | 26-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.384895E+10 | 28164.41 | 25-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154264E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.469599E+10 | 28164.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114582E+11 | 46314.76 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.792807E+10 | 46314.76 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.507756E+10 | 46314.76 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.222320E+10 | 46314.76 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.332161E+09 | 8377.32 | 18-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18076788.24 | 5813.07 | 28-SEP-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164899E+10 | 44345.22 | 30-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.660154E+10 | 46314.76 | 10-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.998308E+10 | 46314.76 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.452709E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114582E+11 | 46314.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.586705E+10 | 23324.23 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.398421E+10 | 23324.23 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.239063E+10 | 23324.23 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100971E+10 | 23324.23 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173631E+09 | 23324.23 | 11-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 382092.94 | 2977.12 | 15-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10830906.35 | 23324.23 | 28-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.716247E+09 | 23324.23 | 12-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.319798E+10 | 23324.23 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.502206E+10 | 23324.23 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223727E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.586705E+10 | 23324.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.597569E+10 | 23082.67 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.409028E+10 | 23082.67 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252337E+10 | 23082.67 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109847E+10 | 23082.67 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211577E+09 | 23082.67 | 11-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1260920.54 | 5490.32 | 15-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13857674.23 | 23082.67 | 28-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.792603E+09 | 23082.67 | 12-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.330624E+10 | 23082.67 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.513511E+10 | 23082.67 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231485E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.597569E+10 | 23082.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.630410E+10 | 22765.26 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.438221E+10 | 22765.26 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.283071E+10 | 22765.26 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129305E+10 | 22765.26 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.299702E+09 | 22765.26 | 02-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6653662.50 | 11748.58 | 15-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24546680.78 | 22765.26 | 27-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.942637E+09 | 22765.26 | 11-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.354853E+10 | 22765.26 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.543271E+10 | 22765.26 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250648E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.630410E+10 | 22765.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.768639E+10 | 22920.12 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.550167E+10 | 22920.12 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.386122E+10 | 22920.12 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191330E+10 | 22920.12 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.598871E+09 | 22920.12 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42526266.69 | 22920.12 | 15-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83132228.38 | 22920.12 | 27-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136986E+10 | 22920.12 | 11-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.434405E+10 | 22920.12 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.659524E+10 | 22920.12 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319963E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.768639E+10 | 22920.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 565.09 | 565.09 | 0.37 | 18-MAR-16:10 | 0.37 | 0.00 |
April | 0.00 | 0.00 | 0.562439E+09 | 0.535002E+09 | 10279.65 | 27-APR-16:10 | 9819.05 | 0.00 |
May | 0.00 | 0.00 | 0.136366E+10 | 0.118977E+10 | 10062.03 | 06-MAY-13:00 | 8022.53 | 0.00 |
June | 0.00 | 0.00 | 0.269405E+10 | 0.248838E+10 | 11861.43 | 28-JUN-17:00 | 11438.37 | 0.00 |
July | 0.00 | 0.00 | 0.689188E+10 | 0.586429E+10 | 28009.71 | 31-JUL-08:62 | 20841.50 | 0.00 |
August | 0.00 | 0.00 | 0.925248E+10 | 0.789134E+10 | 28077.41 | 30-AUG-08:62 | 16353.15 | 0.00 |
September | 0.00 | 0.00 | 0.295000E+10 | 0.236345E+10 | 16119.94 | 14-SEP-08:63 | 10099.46 | 0.00 |
October | 0.00 | 0.00 | 0.161838E+09 | 0.158087E+09 | 6023.82 | 04-OCT-15:00 | 6023.82 | 0.00 |
November | 0.00 | 0.00 | 20346040.29 | 15058444.97 | 2475.07 | 04-NOV-14:00 | 1850.40 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.238967E+11 | 0.205054E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.925248E+10 | 0.789134E+10 | 28077.41 | 20841.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 40912942.04 | 40537136.39 | 1682.12 | 27-FEB-15:00 | 1682.12 | 0.00 |
March | 0.00 | 0.00 | 86124889.83 | 85156816.15 | 1671.11 | 18-MAR-17:10 | 1671.11 | 0.00 |
April | 0.00 | 0.00 | 0.944412E+09 | 0.922518E+09 | 6608.21 | 27-APR-15:00 | 6448.24 | 0.00 |
May | 0.00 | 0.00 | 0.225135E+10 | 0.213273E+10 | 10295.23 | 07-MAY-07:02 | 8375.96 | 0.00 |
June | 0.00 | 0.00 | 0.398742E+10 | 0.387107E+10 | 12530.72 | 11-JUN-07:02 | 11183.34 | 0.00 |
July | 0.00 | 0.00 | 0.643832E+10 | 0.594664E+10 | 15576.91 | 31-JUL-08:62 | 12842.99 | 0.00 |
August | 0.00 | 0.00 | 0.744319E+10 | 0.676107E+10 | 15623.80 | 25-AUG-08:62 | 12240.45 | 0.00 |
September | 0.00 | 0.00 | 0.402279E+10 | 0.364430E+10 | 15011.12 | 03-SEP-07:02 | 12962.32 | 0.00 |
October | 0.00 | 0.00 | 0.111415E+10 | 0.108630E+10 | 4772.30 | 04-OCT-15:00 | 4772.30 | 0.00 |
November | 0.00 | 0.00 | 0.189111E+09 | 0.166073E+09 | 3778.34 | 04-NOV-14:00 | 3171.96 | 0.00 |
December | 0.00 | 0.00 | 25150.11 | 25150.11 | 25.40 | 03-DEC-21:00 | 25.40 | 0.00 |
Annual Sum or Average | 0.265178E+11 | 0.246564E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.744319E+10 | 0.676107E+10 | 15623.80 | 12962.32 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 256.47 | 256.47 | 0.14 | 27-FEB-13:50 | 0.14 | 0.00 |
March | 0.00 | 0.00 | 5329.20 | 5329.20 | 1.47 | 18-MAR-14:00 | 1.47 | 0.00 |
April | 0.00 | 0.00 | 0.341316E+09 | 0.333448E+09 | 7858.96 | 28-APR-07:03 | 5585.73 | 0.00 |
May | 0.00 | 0.00 | 0.708494E+09 | 0.645367E+09 | 16758.55 | 07-MAY-08:62 | 11970.40 | 0.00 |
June | 0.00 | 0.00 | 0.126014E+10 | 0.121143E+10 | 16566.35 | 12-JUN-07:02 | 11277.59 | 0.00 |
July | 0.00 | 0.00 | 0.301417E+10 | 0.269662E+10 | 17066.57 | 31-JUL-07:02 | 12647.98 | 0.00 |
August | 0.00 | 0.00 | 0.422872E+10 | 0.377576E+10 | 17150.68 | 30-AUG-07:02 | 10005.63 | 0.00 |
September | 0.00 | 0.00 | 0.131207E+10 | 0.110513E+10 | 16581.81 | 01-SEP-07:02 | 10983.69 | 0.00 |
October | 0.00 | 0.00 | 68337089.47 | 66772002.70 | 8472.67 | 05-OCT-07:02 | 7925.97 | 0.00 |
November | 0.00 | 0.00 | 15224300.95 | 11875384.40 | 1824.40 | 04-NOV-14:00 | 1439.05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.109485E+11 | 0.984641E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.422872E+10 | 0.377576E+10 | 17150.68 | 12647.98 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 136.57 | 136.57 | 0.05 | 27-FEB-15:00 | 0.05 | 0.00 |
March | 0.00 | 0.00 | 4704.18 | 4704.18 | 1.33 | 18-MAR-14:00 | 1.33 | 0.00 |
April | 0.00 | 0.00 | 0.326793E+09 | 0.319404E+09 | 6426.78 | 27-APR-15:00 | 6283.03 | 0.00 |
May | 0.00 | 0.00 | 0.684034E+09 | 0.623255E+09 | 16681.62 | 07-MAY-08:62 | 11908.50 | 0.00 |
June | 0.00 | 0.00 | 0.123732E+10 | 0.119008E+10 | 16490.42 | 12-JUN-07:02 | 11220.14 | 0.00 |
July | 0.00 | 0.00 | 0.299835E+10 | 0.268225E+10 | 16990.49 | 31-JUL-07:02 | 12595.93 | 0.00 |
August | 0.00 | 0.00 | 0.421668E+10 | 0.376484E+10 | 17073.69 | 30-AUG-07:02 | 9960.51 | 0.00 |
September | 0.00 | 0.00 | 0.129628E+10 | 0.109231E+10 | 16506.65 | 01-SEP-07:02 | 10931.81 | 0.00 |
October | 0.00 | 0.00 | 63994114.77 | 62854669.06 | 7450.37 | 05-OCT-07:02 | 6965.82 | 0.00 |
November | 0.00 | 0.00 | 12132354.03 | 9475887.13 | 1557.46 | 04-NOV-14:00 | 1227.77 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.108356E+11 | 0.974447E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.421668E+10 | 0.376484E+10 | 17073.69 | 12595.93 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 84.32 | 84.32 | 0.08 | 27-FEB-14:40 | 0.08 | 0.00 |
March | 0.00 | 0.00 | 3487.88 | 3487.88 | 1.00 | 18-MAR-14:00 | 1.00 | 0.00 |
April | 0.00 | 0.00 | 0.293054E+09 | 0.286838E+09 | 6041.66 | 27-APR-15:00 | 5901.07 | 0.00 |
May | 0.00 | 0.00 | 0.603280E+09 | 0.549868E+09 | 16596.94 | 07-MAY-08:62 | 11810.11 | 0.00 |
June | 0.00 | 0.00 | 0.113785E+10 | 0.109572E+10 | 16406.25 | 12-JUN-07:02 | 11128.38 | 0.00 |
July | 0.00 | 0.00 | 0.286132E+10 | 0.255976E+10 | 16906.04 | 31-JUL-07:02 | 12504.53 | 0.00 |
August | 0.00 | 0.00 | 0.405096E+10 | 0.361941E+10 | 16988.55 | 30-AUG-07:02 | 9880.61 | 0.00 |
September | 0.00 | 0.00 | 0.120788E+10 | 0.101907E+10 | 16423.94 | 01-SEP-07:02 | 10848.27 | 0.00 |
October | 0.00 | 0.00 | 51876588.27 | 51572762.97 | 3625.91 | 05-OCT-07:02 | 3380.13 | 0.00 |
November | 0.00 | 0.00 | 6907731.97 | 5407246.45 | 1059.96 | 04-NOV-14:00 | 833.86 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.102131E+11 | 0.918764E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.405096E+10 | 0.361941E+10 | 16988.55 | 12504.53 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.353156E+09 | 0.335062E+09 | 8804.04 | 27-APR-15:00 | 8214.73 | 0.00 |
May | 0.00 | 0.00 | 0.744464E+09 | 0.650272E+09 | 8675.90 | 06-MAY-13:30 | 6949.49 | 0.00 |
June | 0.00 | 0.00 | 0.164994E+10 | 0.153309E+10 | 10190.21 | 28-JUN-17:00 | 9749.14 | 0.00 |
July | 0.00 | 0.00 | 0.455435E+10 | 0.388777E+10 | 26825.98 | 31-JUL-08:62 | 19959.51 | 0.00 |
August | 0.00 | 0.00 | 0.652405E+10 | 0.558493E+10 | 26893.75 | 30-AUG-08:62 | 15602.53 | 0.00 |
September | 0.00 | 0.00 | 0.192855E+10 | 0.154291E+10 | 13945.50 | 14-SEP-08:63 | 8637.53 | 0.00 |
October | 0.00 | 0.00 | 74322842.05 | 73636091.29 | 4577.48 | 04-OCT-15:00 | 4577.48 | 0.00 |
November | 0.00 | 0.00 | 5074377.68 | 3756239.25 | 983.97 | 04-NOV-14:30 | 731.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.158339E+11 | 0.136114E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.652405E+10 | 0.558493E+10 | 26893.75 | 19959.51 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 60833.73 | 60833.73 | 101.39 | 18-MAR-16:00 | 101.39 | 0.00 |
April | 0.00 | 0.00 | 0.231386E+09 | 0.223985E+09 | 4830.77 | 27-APR-15:00 | 4637.31 | 0.00 |
May | 0.00 | 0.00 | 0.565516E+09 | 0.514934E+09 | 4712.26 | 06-MAY-13:40 | 3976.17 | 0.00 |
June | 0.00 | 0.00 | 0.131782E+10 | 0.126819E+10 | 5521.56 | 28-JUN-17:00 | 5451.01 | 0.00 |
July | 0.00 | 0.00 | 0.307227E+10 | 0.276429E+10 | 13787.81 | 31-JUL-08:62 | 10992.95 | 0.00 |
August | 0.00 | 0.00 | 0.408125E+10 | 0.362886E+10 | 13800.78 | 10-AUG-08:62 | 10990.55 | 0.00 |
September | 0.00 | 0.00 | 0.141228E+10 | 0.122367E+10 | 6099.42 | 14-SEP-14:10 | 5128.87 | 0.00 |
October | 0.00 | 0.00 | 0.116533E+09 | 0.114772E+09 | 3157.30 | 04-OCT-15:00 | 3157.30 | 0.00 |
November | 0.00 | 0.00 | 15525698.23 | 12422600.66 | 1568.55 | 04-NOV-14:30 | 1265.46 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.108126E+11 | 0.975119E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.408125E+10 | 0.362886E+10 | 13800.78 | 10992.95 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.217633E+09 | 0.210563E+09 | 4707.77 | 27-APR-15:00 | 4512.16 | 0.00 |
May | 0.00 | 0.00 | 0.526135E+09 | 0.478082E+09 | 4579.54 | 06-MAY-13:40 | 3853.98 | 0.00 |
June | 0.00 | 0.00 | 0.123210E+10 | 0.118530E+10 | 5439.53 | 28-JUN-17:00 | 5361.77 | 0.00 |
July | 0.00 | 0.00 | 0.296335E+10 | 0.266112E+10 | 13411.28 | 24-JUL-08:62 | 11948.11 | 0.00 |
August | 0.00 | 0.00 | 0.397432E+10 | 0.352888E+10 | 13675.54 | 10-AUG-08:62 | 10850.83 | 0.00 |
September | 0.00 | 0.00 | 0.134713E+10 | 0.116388E+10 | 6006.48 | 14-SEP-14:10 | 5039.11 | 0.00 |
October | 0.00 | 0.00 | 0.100816E+09 | 99345713.91 | 3009.95 | 04-OCT-15:00 | 3009.95 | 0.00 |
November | 0.00 | 0.00 | 13919330.13 | 11108949.16 | 1469.23 | 04-NOV-14:30 | 1181.76 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.103754E+11 | 0.933827E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.397432E+10 | 0.352888E+10 | 13675.54 | 11948.11 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.194352E+09 | 0.188080E+09 | 4490.42 | 27-APR-15:00 | 4302.25 | 0.00 |
May | 0.00 | 0.00 | 0.457735E+09 | 0.415285E+09 | 4335.91 | 06-MAY-13:40 | 3640.09 | 0.00 |
June | 0.00 | 0.00 | 0.108670E+10 | 0.104685E+10 | 5289.74 | 28-JUN-17:00 | 5213.58 | 0.00 |
July | 0.00 | 0.00 | 0.276307E+10 | 0.247862E+10 | 13276.87 | 24-JUL-08:62 | 11773.30 | 0.00 |
August | 0.00 | 0.00 | 0.378720E+10 | 0.336299E+10 | 13541.79 | 10-AUG-08:62 | 10697.34 | 0.00 |
September | 0.00 | 0.00 | 0.123911E+10 | 0.106791E+10 | 5881.37 | 14-SEP-14:10 | 4926.70 | 0.00 |
October | 0.00 | 0.00 | 75550319.61 | 74648396.22 | 2749.38 | 04-OCT-15:00 | 2749.38 | 0.00 |
November | 0.00 | 0.00 | 11242151.93 | 8958596.21 | 1284.86 | 04-NOV-14:40 | 1032.26 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.961495E+10 | 0.864334E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.378720E+10 | 0.336299E+10 | 13541.79 | 11773.30 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.165702E+09 | 0.160852E+09 | 4304.80 | 27-APR-15:00 | 4138.38 | 0.00 |
May | 0.00 | 0.00 | 0.377535E+09 | 0.343721E+09 | 4131.37 | 06-MAY-13:30 | 3454.72 | 0.00 |
June | 0.00 | 0.00 | 0.940772E+09 | 0.909395E+09 | 5072.21 | 28-JUN-17:00 | 5019.62 | 0.00 |
July | 0.00 | 0.00 | 0.251865E+10 | 0.226937E+10 | 10555.34 | 24-JUL-08:62 | 9342.23 | 0.00 |
August | 0.00 | 0.00 | 0.359099E+10 | 0.320610E+10 | 11597.35 | 10-AUG-08:62 | 9200.86 | 0.00 |
September | 0.00 | 0.00 | 0.114495E+10 | 0.988368E+09 | 5842.37 | 14-SEP-14:10 | 4911.38 | 0.00 |
October | 0.00 | 0.00 | 51471584.64 | 51162449.75 | 2419.35 | 04-OCT-15:00 | 2419.35 | 0.00 |
November | 0.00 | 0.00 | 8181560.99 | 6543363.18 | 1049.60 | 04-NOV-14:50 | 845.93 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.879825E+10 | 0.793551E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.359099E+10 | 0.320610E+10 | 11597.35 | 9342.23 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149274E+10 | 0.41 | 1686.93 | 01-JAN-09:01 | 0.89 |
February | 0.129368E+10 | 0.40 | 1686.93 | 01-FEB-09:01 | 0.89 |
March | 0.133104E+10 | 0.39 | 1686.93 | 05-MAR-09:01 | 0.89 |
April | 0.122751E+10 | 0.37 | 1686.93 | 11-APR-08:61 | 0.89 |
May | 0.122838E+10 | 0.36 | 842.18 | 19-MAY-08:04 | 0.62 |
June | 0.118787E+10 | 0.36 | 674.77 | 29-JUN-15:20 | 0.54 |
July | 0.123094E+10 | 0.36 | 1686.93 | 24-JUL-08:62 | 0.88 |
August | 0.124628E+10 | 0.37 | 1686.93 | 08-AUG-08:62 | 0.88 |
September | 0.119038E+10 | 0.36 | 867.95 | 14-SEP-08:63 | 0.63 |
October | 0.124540E+10 | 0.37 | 1038.51 | 28-OCT-08:61 | 0.70 |
November | 0.131977E+10 | 0.39 | 1686.93 | 11-NOV-09:01 | 0.89 |
December | 0.145872E+10 | 0.41 | 1686.93 | 01-DEC-09:01 | 0.89 |
Annual Sum or Average | 0.154527E+11 | 0.38 | |||
Minimum of Months | 0.118787E+10 | 0.36 | 674.77 | 0.54 | |
Maximum of Months | 0.149274E+10 | 0.41 | 1686.93 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132474E+10 | 0.47 | 976.08 | 06-JAN-15:00 | 0.92 |
February | 0.120226E+10 | 0.49 | 976.08 | 04-FEB-18:20 | 0.92 |
March | 0.135796E+10 | 0.54 | 976.08 | 18-MAR-17:30 | 0.92 |
April | 0.134791E+10 | 0.62 | 976.08 | 01-APR-08:40 | 0.92 |
May | 0.146838E+10 | 0.65 | 976.08 | 07-MAY-08:00 | 0.91 |
June | 0.148166E+10 | 0.65 | 976.08 | 01-JUN-10:10 | 0.92 |
July | 0.155679E+10 | 0.65 | 976.08 | 02-JUL-13:40 | 0.92 |
August | 0.157734E+10 | 0.64 | 976.08 | 16-AUG-18:00 | 0.91 |
September | 0.147372E+10 | 0.65 | 976.08 | 05-SEP-09:50 | 0.92 |
October | 0.141269E+10 | 0.64 | 976.08 | 07-OCT-14:00 | 0.92 |
November | 0.130641E+10 | 0.52 | 976.08 | 14-NOV-18:45 | 0.92 |
December | 0.131772E+10 | 0.46 | 976.08 | 12-DEC-20:53 | 0.92 |
Annual Sum or Average | 0.168276E+11 | 0.58 | |||
Minimum of Months | 0.120226E+10 | 0.46 | 976.08 | 0.91 | |
Maximum of Months | 0.157734E+10 | 0.65 | 976.08 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157678E+10 | 0.50 | 1089.54 | 01-JAN-10:09 | 0.92 |
February | 0.142774E+10 | 0.50 | 1089.54 | 01-FEB-09:01 | 0.92 |
March | 0.160816E+10 | 0.51 | 1089.54 | 01-MAR-08:25 | 0.92 |
April | 0.152972E+10 | 0.50 | 1089.54 | 01-APR-07:08 | 0.92 |
May | 0.159247E+10 | 0.50 | 1089.54 | 01-MAY-07:03 | 0.92 |
June | 0.155325E+10 | 0.50 | 1089.54 | 01-JUN-10:10 | 0.92 |
July | 0.156894E+10 | 0.49 | 1089.54 | 01-JUL-07:50 | 0.92 |
August | 0.160816E+10 | 0.50 | 1089.54 | 01-AUG-08:10 | 0.91 |
September | 0.152972E+10 | 0.50 | 1089.54 | 01-SEP-10:00 | 0.91 |
October | 0.157678E+10 | 0.50 | 1089.54 | 01-OCT-13:40 | 0.91 |
November | 0.152972E+10 | 0.50 | 1089.54 | 01-NOV-08:00 | 0.92 |
December | 0.156894E+10 | 0.49 | 1089.54 | 01-DEC-09:04 | 0.92 |
Annual Sum or Average | 0.186704E+11 | 0.50 | |||
Minimum of Months | 0.142774E+10 | 0.49 | 1089.54 | 0.91 | |
Maximum of Months | 0.160816E+10 | 0.51 | 1089.54 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157049E+10 | 0.50 | 1085.20 | 02-JAN-11:50 | 0.92 |
February | 0.142204E+10 | 0.50 | 1085.20 | 03-FEB-09:08 | 0.92 |
March | 0.160175E+10 | 0.51 | 1085.20 | 01-MAR-09:08 | 0.92 |
April | 0.152361E+10 | 0.50 | 1085.20 | 01-APR-16:50 | 0.92 |
May | 0.158612E+10 | 0.50 | 1085.20 | 04-MAY-10:20 | 0.92 |
June | 0.154705E+10 | 0.50 | 1085.20 | 08-JUN-16:30 | 0.92 |
July | 0.156268E+10 | 0.49 | 1085.20 | 02-JUL-12:10 | 0.92 |
August | 0.160175E+10 | 0.50 | 1085.20 | 01-AUG-19:00 | 0.91 |
September | 0.152361E+10 | 0.50 | 1085.20 | 01-SEP-14:00 | 0.91 |
October | 0.157049E+10 | 0.50 | 1085.20 | 05-OCT-18:30 | 0.92 |
November | 0.152361E+10 | 0.50 | 1085.20 | 02-NOV-08:08 | 0.92 |
December | 0.156268E+10 | 0.49 | 1085.20 | 03-DEC-10:01 | 0.92 |
Annual Sum or Average | 0.185959E+11 | 0.50 | |||
Minimum of Months | 0.142204E+10 | 0.49 | 1085.20 | 0.91 | |
Maximum of Months | 0.160175E+10 | 0.51 | 1085.20 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156107E+10 | 0.50 | 1078.68 | 01-JAN-10:03 | 0.92 |
February | 0.141350E+10 | 0.50 | 1078.68 | 01-FEB-08:40 | 0.92 |
March | 0.159213E+10 | 0.51 | 1078.68 | 01-MAR-08:08 | 0.92 |
April | 0.151447E+10 | 0.50 | 1078.68 | 01-APR-07:05 | 0.92 |
May | 0.157660E+10 | 0.50 | 1078.68 | 02-MAY-13:20 | 0.92 |
June | 0.153777E+10 | 0.50 | 1078.68 | 01-JUN-10:30 | 0.92 |
July | 0.155330E+10 | 0.49 | 1078.68 | 01-JUL-07:30 | 0.92 |
August | 0.159213E+10 | 0.50 | 1078.68 | 01-AUG-08:17 | 0.91 |
September | 0.151447E+10 | 0.50 | 1078.68 | 01-SEP-12:40 | 0.91 |
October | 0.156107E+10 | 0.50 | 1078.68 | 01-OCT-14:10 | 0.91 |
November | 0.151447E+10 | 0.50 | 1078.68 | 01-NOV-08:61 | 0.92 |
December | 0.155330E+10 | 0.49 | 1078.68 | 01-DEC-09:01 | 0.92 |
Annual Sum or Average | 0.184843E+11 | 0.50 | |||
Minimum of Months | 0.141350E+10 | 0.49 | 1078.68 | 0.91 | |
Maximum of Months | 0.159213E+10 | 0.51 | 1078.68 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109879E+10 | 0.31 | 1609.53 | 01-JAN-10:01 | 0.89 |
February | 0.944064E+09 | 0.30 | 1609.53 | 01-FEB-09:01 | 0.89 |
March | 0.984289E+09 | 0.29 | 1609.53 | 01-MAR-09:01 | 0.89 |
April | 0.880736E+09 | 0.28 | 1609.53 | 01-APR-08:61 | 0.89 |
May | 0.876071E+09 | 0.27 | 818.49 | 18-MAY-08:04 | 0.63 |
June | 0.848286E+09 | 0.27 | 643.81 | 27-JUN-20:00 | 0.54 |
July | 0.858420E+09 | 0.27 | 1609.53 | 23-JUL-09:02 | 0.88 |
August | 0.891464E+09 | 0.27 | 1609.53 | 08-AUG-08:62 | 0.88 |
September | 0.834771E+09 | 0.27 | 765.02 | 28-SEP-08:07 | 0.60 |
October | 0.894258E+09 | 0.27 | 1568.46 | 30-OCT-08:61 | 0.88 |
November | 0.972029E+09 | 0.30 | 1609.53 | 10-NOV-09:01 | 0.89 |
December | 0.106340E+10 | 0.31 | 1609.53 | 01-DEC-09:01 | 0.89 |
Annual Sum or Average | 0.111466E+11 | 0.28 | |||
Minimum of Months | 0.834771E+09 | 0.27 | 643.81 | 0.54 | |
Maximum of Months | 0.109879E+10 | 0.31 | 1609.53 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.113965E+10 | 0.46 | 853.29 | 01-JAN-09:01 | 0.92 |
February | 0.103214E+10 | 0.46 | 853.29 | 08-FEB-18:50 | 0.92 |
March | 0.116422E+10 | 0.47 | 853.29 | 01-MAR-09:09 | 0.92 |
April | 0.110586E+10 | 0.46 | 853.29 | 13-APR-09:30 | 0.92 |
May | 0.115194E+10 | 0.46 | 853.29 | 30-MAY-08:40 | 0.92 |
June | 0.112429E+10 | 0.47 | 853.29 | 18-JUN-13:30 | 0.92 |
July | 0.113351E+10 | 0.45 | 853.29 | 01-JUL-12:30 | 0.92 |
August | 0.116422E+10 | 0.47 | 853.29 | 04-AUG-19:30 | 0.91 |
September | 0.110586E+10 | 0.46 | 853.29 | 01-SEP-10:00 | 0.91 |
October | 0.113965E+10 | 0.46 | 853.29 | 03-OCT-08:62 | 0.92 |
November | 0.110586E+10 | 0.46 | 853.29 | 01-NOV-08:08 | 0.92 |
December | 0.113351E+10 | 0.46 | 853.29 | 01-DEC-09:04 | 0.92 |
Annual Sum or Average | 0.135007E+11 | 0.46 | |||
Minimum of Months | 0.103214E+10 | 0.45 | 853.29 | 0.91 | |
Maximum of Months | 0.116422E+10 | 0.47 | 853.29 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112582E+10 | 0.46 | 842.93 | 28-JAN-09:08 | 0.92 |
February | 0.101961E+10 | 0.46 | 842.93 | 01-FEB-19:10 | 0.92 |
March | 0.115009E+10 | 0.47 | 842.93 | 07-MAR-18:30 | 0.92 |
April | 0.109244E+10 | 0.46 | 842.93 | 26-APR-16:30 | 0.92 |
May | 0.113795E+10 | 0.46 | 842.93 | 02-MAY-08:20 | 0.92 |
June | 0.111064E+10 | 0.47 | 842.93 | 02-JUN-18:50 | 0.92 |
July | 0.111975E+10 | 0.45 | 842.93 | 18-JUL-13:00 | 0.92 |
August | 0.115009E+10 | 0.47 | 842.93 | 01-AUG-13:30 | 0.91 |
September | 0.109244E+10 | 0.46 | 842.93 | 01-SEP-16:50 | 0.91 |
October | 0.112582E+10 | 0.46 | 842.93 | 13-OCT-09:00 | 0.92 |
November | 0.109244E+10 | 0.46 | 842.93 | 07-NOV-18:10 | 0.92 |
December | 0.111975E+10 | 0.46 | 842.93 | 25-DEC-16:40 | 0.92 |
Annual Sum or Average | 0.133368E+11 | 0.46 | |||
Minimum of Months | 0.101961E+10 | 0.45 | 842.93 | 0.91 | |
Maximum of Months | 0.115009E+10 | 0.47 | 842.93 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.111399E+10 | 0.46 | 834.07 | 12-JAN-09:20 | 0.92 |
February | 0.100890E+10 | 0.46 | 834.07 | 24-FEB-16:50 | 0.92 |
March | 0.113801E+10 | 0.47 | 834.07 | 02-MAR-13:40 | 0.92 |
April | 0.108096E+10 | 0.46 | 834.07 | 25-APR-08:40 | 0.92 |
May | 0.112600E+10 | 0.46 | 834.07 | 01-MAY-08:20 | 0.92 |
June | 0.109898E+10 | 0.47 | 834.07 | 01-JUN-18:20 | 0.92 |
July | 0.110798E+10 | 0.45 | 834.07 | 01-JUL-13:10 | 0.92 |
August | 0.113801E+10 | 0.47 | 834.07 | 01-AUG-14:30 | 0.91 |
September | 0.108096E+10 | 0.46 | 834.07 | 01-SEP-10:30 | 0.91 |
October | 0.111399E+10 | 0.46 | 834.07 | 15-OCT-14:20 | 0.92 |
November | 0.108096E+10 | 0.46 | 834.07 | 01-NOV-18:40 | 0.91 |
December | 0.110798E+10 | 0.46 | 834.07 | 01-DEC-08:07 | 0.92 |
Annual Sum or Average | 0.131967E+11 | 0.46 | |||
Minimum of Months | 0.100890E+10 | 0.45 | 834.07 | 0.91 | |
Maximum of Months | 0.113801E+10 | 0.47 | 834.07 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.113760E+10 | 0.46 | 851.75 | 01-JAN-12:00 | 0.92 |
February | 0.103028E+10 | 0.46 | 851.75 | 03-FEB-09:15 | 0.92 |
March | 0.116213E+10 | 0.47 | 851.75 | 01-MAR-18:10 | 0.92 |
April | 0.110387E+10 | 0.46 | 851.75 | 01-APR-08:30 | 0.92 |
May | 0.114986E+10 | 0.46 | 851.75 | 03-MAY-15:00 | 0.92 |
June | 0.112227E+10 | 0.47 | 851.75 | 09-JUN-12:20 | 0.92 |
July | 0.113147E+10 | 0.45 | 851.75 | 07-JUL-11:50 | 0.91 |
August | 0.116213E+10 | 0.47 | 851.75 | 01-AUG-15:10 | 0.91 |
September | 0.110387E+10 | 0.46 | 851.75 | 01-SEP-18:50 | 0.91 |
October | 0.113760E+10 | 0.46 | 851.75 | 07-OCT-08:40 | 0.92 |
November | 0.110387E+10 | 0.46 | 851.75 | 01-NOV-16:00 | 0.91 |
December | 0.113147E+10 | 0.46 | 851.75 | 01-DEC-11:20 | 0.92 |
Annual Sum or Average | 0.134764E+11 | 0.46 | |||
Minimum of Months | 0.103028E+10 | 0.45 | 851.75 | 0.91 | |
Maximum of Months | 0.116213E+10 | 0.47 | 851.75 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.61 | 0.55 |
February | 0.39 | 1.29 |
March | 0.00 | 0.00 |
April | 0.22 | 1.50 |
May | 0.67 | 1.50 |
June | 0.67 | 1.50 |
July | 0.42 | 1.50 |
August | 0.25 | 1.50 |
September | 0.78 | 1.50 |
October | 0.89 | 1.50 |
November | 0.08 | 1.50 |
December | 0.40 | 1.09 |
Annual Sum or Average | 5.38 | 1.34 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.89 | 1.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.69 | 0.52 |
February | 1.89 | 1.21 |
March | 3.64 | 2.31 |
April | 2.33 | 1.77 |
May | 1.53 | 1.38 |
June | 0.97 | 0.51 |
July | 0.11 | 0.75 |
August | 0.31 | 0.14 |
September | 1.28 | 0.52 |
October | 1.76 | 2.30 |
November | 2.58 | 1.72 |
December | 2.68 | 1.68 |
Annual Sum or Average | 21.78 | 1.50 |
Minimum of Months | 0.11 | 0.14 |
Maximum of Months | 3.64 | 2.31 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.22 | 0.75 |
March | 0.75 | 0.75 |
April | 2.47 | 0.72 |
May | 2.97 | 0.75 |
June | 1.92 | 0.75 |
July | 2.25 | 0.75 |
August | 2.32 | 0.75 |
September | 0.92 | 0.75 |
October | 2.68 | 0.75 |
November | 0.36 | 0.75 |
December | 0.00 | 0.00 |
Annual Sum or Average | 16.86 | 0.75 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.97 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.14 | 0.75 |
March | 0.47 | 0.75 |
April | 2.00 | 0.72 |
May | 2.72 | 0.75 |
June | 2.00 | 0.75 |
July | 2.25 | 0.75 |
August | 2.32 | 0.75 |
September | 0.92 | 0.75 |
October | 2.43 | 0.75 |
November | 0.19 | 0.75 |
December | 0.00 | 0.00 |
Annual Sum or Average | 15.44 | 0.75 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.72 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.06 | 0.75 |
March | 0.25 | 0.75 |
April | 1.19 | 0.70 |
May | 2.92 | 0.75 |
June | 1.42 | 0.75 |
July | 2.41 | 0.75 |
August | 2.23 | 0.75 |
September | 1.61 | 0.75 |
October | 1.85 | 0.75 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 13.94 | 0.75 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.92 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.12 | 0.00 |
February | 0.08 | 0.00 |
March | 0.00 | 0.00 |
April | 0.17 | 1.65 |
May | 0.44 | 3.30 |
June | 0.50 | 3.30 |
July | 0.72 | 3.30 |
August | 0.38 | 3.30 |
September | 0.42 | 3.30 |
October | 0.47 | 3.30 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 3.31 | 3.01 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.72 | 3.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.33 | 0.00 |
February | 0.44 | 0.00 |
March | 1.78 | 0.00 |
April | 1.53 | 0.00 |
May | 1.25 | 0.00 |
June | 0.67 | 0.00 |
July | 0.58 | 1.33 |
August | 0.60 | 0.81 |
September | 1.00 | 0.00 |
October | 1.40 | 0.00 |
November | 0.86 | 0.00 |
December | 0.36 | 0.00 |
Annual Sum or Average | 10.81 | 0.12 |
Minimum of Months | 0.33 | 0.00 |
Maximum of Months | 1.78 | 1.33 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.33 | 0.00 |
February | 0.50 | 0.00 |
March | 1.67 | 0.00 |
April | 1.44 | 0.00 |
May | 1.17 | 0.00 |
June | 0.61 | 0.00 |
July | 0.58 | 1.33 |
August | 0.52 | 0.68 |
September | 1.00 | 0.00 |
October | 1.40 | 0.00 |
November | 0.72 | 0.00 |
December | 0.25 | 0.00 |
Annual Sum or Average | 10.20 | 0.11 |
Minimum of Months | 0.25 | 0.00 |
Maximum of Months | 1.67 | 1.33 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.25 | 0.00 |
February | 0.50 | 0.00 |
March | 0.75 | 0.00 |
April | 1.14 | 0.00 |
May | 1.11 | 0.00 |
June | 0.50 | 0.00 |
July | 0.52 | 1.48 |
August | 0.38 | 0.93 |
September | 0.89 | 0.00 |
October | 1.40 | 0.00 |
November | 0.33 | 0.00 |
December | 0.08 | 0.00 |
Annual Sum or Average | 7.86 | 0.14 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 1.40 | 1.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.36 | 0.00 |
February | 0.97 | 0.00 |
March | 0.14 | 0.00 |
April | 0.17 | 0.00 |
May | 0.11 | 0.00 |
June | 0.00 | 0.00 |
July | 0.47 | 1.65 |
August | 0.21 | 1.65 |
September | 0.22 | 0.00 |
October | 0.32 | 0.00 |
November | 0.08 | 0.00 |
December | 0.36 | 0.00 |
Annual Sum or Average | 4.42 | 0.26 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.36 | 1.65 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.149274E+10 | 0.158695E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.129368E+10 | 0.109943E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.133104E+10 | 0.617418E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.137397E+10 | 0.234688E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.157202E+10 | 0.240977E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.186669E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.291401E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.349051E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.190711E+10 | 2396600.67 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.128717E+10 | 0.124877E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.132530E+10 | 0.809559E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.145872E+10 | 0.135761E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.213130E+11 | 0.585487E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.128717E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.349051E+10 | 0.158695E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.132474E+10 | 0.449110E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.121272E+10 | 0.276313E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.138045E+10 | 0.859652E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.157141E+10 | 0.169093E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.198485E+10 | 4642453.71 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.238085E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.295981E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.318662E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.236767E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.167914E+10 | 34933799.02 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.135308E+10 | 0.177443E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.131772E+10 | 0.352990E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.227191E+11 | 0.136269E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.121272E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.318662E+10 | 0.449110E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.157678E+10 | 0.511371E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.142774E+10 | 0.317303E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.160816E+10 | 0.108058E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.160665E+10 | 0.213327E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.174867E+10 | 703064.58 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.183153E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.222010E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.251438E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.181014E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.159211E+10 | 28085600.11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.153330E+10 | 0.214646E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.156894E+10 | 0.411262E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.210385E+11 | 0.158685E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.142774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.251438E+10 | 0.511371E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.157049E+10 | 0.540648E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.142204E+10 | 0.337500E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.160175E+10 | 0.126401E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.159755E+10 | 0.286302E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.173711E+10 | 1038326.52 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.182044E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.221027E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.250512E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.180071E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.158490E+10 | 61229659.07 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.152649E+10 | 0.234676E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.156268E+10 | 0.437430E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.209396E+11 | 0.171151E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.142204E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.250512E+10 | 0.540648E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.156107E+10 | 0.586998E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.141350E+10 | 0.371734E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159213E+10 | 0.159523E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.158147E+10 | 0.445439E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.171058E+10 | 7315092.01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.179022E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.217340E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.246246E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.177355E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.157285E+10 | 0.159845E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.151613E+10 | 0.267663E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.155330E+10 | 0.481118E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.207006E+11 | 0.192830E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.141350E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.246246E+10 | 0.586998E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.109879E+10 | 0.143228E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.944064E+09 | 0.991009E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.984289E+09 | 0.634695E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.974645E+09 | 0.277900E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.106749E+10 | 0.415201E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.127076E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.198421E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.248533E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.130669E+10 | 22595985.29 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.913642E+09 | 0.206124E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.973440E+09 | 0.825193E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.106340E+10 | 0.124789E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.150667E+11 | 0.565887E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.913642E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.248533E+10 | 0.143228E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.113965E+10 | 0.733381E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.103214E+10 | 0.498026E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.116424E+10 | 0.298828E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.115932E+10 | 0.126213E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.127880E+10 | 0.217039E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.141950E+10 | 477616.18 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.179960E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.204256E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.140991E+10 | 13538632.93 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.116628E+10 | 0.895308E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.110949E+10 | 0.399747E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.113351E+10 | 0.627757E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.158550E+11 | 0.279659E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.103214E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.204256E+10 | 0.733381E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.112582E+10 | 0.746962E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.101961E+10 | 0.511285E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.115009E+10 | 0.315421E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.114287E+10 | 0.137309E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.125636E+10 | 0.264471E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.138713E+10 | 1576150.68 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.176301E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.200610E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.138271E+10 | 17322092.78 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.114889E+10 | 0.990754E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.109570E+10 | 0.413280E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.111975E+10 | 0.641889E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.155980E+11 | 0.289356E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.101961E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.200610E+10 | 0.746962E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.111399E+10 | 0.788012E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.100890E+10 | 0.547776E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.113801E+10 | 0.353838E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.112629E+10 | 0.161631E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.122964E+10 | 0.374628E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.134369E+10 | 8317078.13 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.170936E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.195503E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.134842E+10 | 30683350.97 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.113132E+10 | 0.117830E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.108361E+10 | 0.443566E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.110798E+10 | 0.679088E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.152962E+11 | 0.313310E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.100890E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.195503E+10 | 0.788012E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.113760E+10 | 0.960798E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.103028E+10 | 0.687709E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.116213E+10 | 0.482653E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.114289E+10 | 0.239163E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.123606E+10 | 0.748588E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.133529E+10 | 53157833.36 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.168173E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.193708E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.135149E+10 | 0.103915E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.114942E+10 | 0.171232E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.110582E+10 | 0.543006E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.113147E+10 | 0.824406E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.154013E+11 | 0.399953E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.103028E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.193708E+10 | 0.960798E+10 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149274E+10 | 0.00 | 0.126956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129368E+10 | 0.00 | 0.879545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133104E+10 | 565.09 | 0.493934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122751E+10 | 0.562439E+09 | 0.187750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122838E+10 | 0.136366E+10 | 0.192782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118787E+10 | 0.269405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123094E+10 | 0.689188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124628E+10 | 0.925248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119038E+10 | 0.295000E+10 | 1917280.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124540E+10 | 0.161838E+09 | 0.999019E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131977E+10 | 20346040.29 | 0.647647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145872E+10 | 0.00 | 0.108608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154527E+11 | 0.238967E+11 | 0.468389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149274E+10 | 0.925248E+10 | 0.126956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.132474E+10 | 0.00 | 0.359288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120226E+10 | 40912942.04 | 0.221050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135796E+10 | 86124889.83 | 0.687722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134791E+10 | 0.944412E+09 | 0.135275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146838E+10 | 0.225135E+10 | 3713962.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148166E+10 | 0.398742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155679E+10 | 0.643832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157734E+10 | 0.744319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147372E+10 | 0.402279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141269E+10 | 0.111415E+10 | 27947039.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130641E+10 | 0.189111E+09 | 0.141954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131772E+10 | 25150.11 | 0.282392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168276E+11 | 0.265178E+11 | 0.109015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157734E+10 | 0.744319E+10 | 0.359288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157678E+10 | 0.00 | 0.409097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142774E+10 | 256.47 | 0.253842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160816E+10 | 5329.20 | 0.864466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152972E+10 | 0.341316E+09 | 0.170661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159247E+10 | 0.708494E+09 | 562451.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155325E+10 | 0.126014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156894E+10 | 0.301417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160816E+10 | 0.422872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152972E+10 | 0.131207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157678E+10 | 68337089.47 | 22468480.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152972E+10 | 15224300.95 | 0.171717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156894E+10 | 0.00 | 0.329010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186704E+11 | 0.109485E+11 | 0.126948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160816E+10 | 0.422872E+10 | 0.409097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157049E+10 | 0.00 | 0.432518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142204E+10 | 136.57 | 0.270000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160175E+10 | 4704.18 | 0.101121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152361E+10 | 0.326793E+09 | 0.229042E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158612E+10 | 0.684034E+09 | 830661.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154705E+10 | 0.123732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156268E+10 | 0.299835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160175E+10 | 0.421668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152361E+10 | 0.129628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157049E+10 | 63994114.77 | 48983727.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152361E+10 | 12132354.03 | 0.187741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156268E+10 | 0.00 | 0.349944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185959E+11 | 0.108356E+11 | 0.136921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160175E+10 | 0.421668E+10 | 0.432518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156107E+10 | 0.00 | 0.469599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141350E+10 | 84.32 | 0.297388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159213E+10 | 3487.88 | 0.127619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151447E+10 | 0.293054E+09 | 0.356351E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157660E+10 | 0.603280E+09 | 5852073.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153777E+10 | 0.113785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155330E+10 | 0.286132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159213E+10 | 0.405096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151447E+10 | 0.120788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156107E+10 | 51876588.27 | 0.127876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151447E+10 | 6907731.97 | 0.214130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155330E+10 | 0.00 | 0.384895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184843E+11 | 0.102131E+11 | 0.154264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159213E+10 | 0.405096E+10 | 0.469599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109879E+10 | 0.00 | 0.114582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.944064E+09 | 0.00 | 0.792807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.984289E+09 | 0.00 | 0.507756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.880736E+09 | 0.353156E+09 | 0.222320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.876071E+09 | 0.744464E+09 | 0.332161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.848286E+09 | 0.164994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.858420E+09 | 0.455435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.891464E+09 | 0.652405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.834771E+09 | 0.192855E+10 | 18076788.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.894258E+09 | 74322842.05 | 0.164899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.972029E+09 | 5074377.68 | 0.660154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106340E+10 | 0.00 | 0.998308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111466E+11 | 0.158339E+11 | 0.452709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.834771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109879E+10 | 0.652405E+10 | 0.114582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.113965E+10 | 0.00 | 0.586705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103214E+10 | 0.00 | 0.398421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116422E+10 | 60833.73 | 0.239063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110586E+10 | 0.231386E+09 | 0.100971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115194E+10 | 0.565516E+09 | 0.173631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112429E+10 | 0.131782E+10 | 382092.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113351E+10 | 0.307227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116422E+10 | 0.408125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110586E+10 | 0.141228E+10 | 10830906.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113965E+10 | 0.116533E+09 | 0.716247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110586E+10 | 15525698.23 | 0.319798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113351E+10 | 0.00 | 0.502206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135007E+11 | 0.108126E+11 | 0.223727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116422E+10 | 0.408125E+10 | 0.586705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.112582E+10 | 0.00 | 0.597569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101961E+10 | 0.00 | 0.409028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115009E+10 | 0.00 | 0.252337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109244E+10 | 0.217633E+09 | 0.109847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113795E+10 | 0.526135E+09 | 0.211577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111064E+10 | 0.123210E+10 | 1260920.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111975E+10 | 0.296335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115009E+10 | 0.397432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109244E+10 | 0.134713E+10 | 13857674.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112582E+10 | 0.100816E+09 | 0.792603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109244E+10 | 13919330.13 | 0.330624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111975E+10 | 0.00 | 0.513511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133368E+11 | 0.103754E+11 | 0.231485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115009E+10 | 0.397432E+10 | 0.597569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.111399E+10 | 0.00 | 0.630410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100890E+10 | 0.00 | 0.438221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113801E+10 | 0.00 | 0.283071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108096E+10 | 0.194352E+09 | 0.129305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112600E+10 | 0.457735E+09 | 0.299702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109898E+10 | 0.108670E+10 | 6653662.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110798E+10 | 0.276307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113801E+10 | 0.378720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108096E+10 | 0.123911E+10 | 24546680.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111399E+10 | 75550319.61 | 0.942637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108096E+10 | 11242151.93 | 0.354853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110798E+10 | 0.00 | 0.543271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131967E+11 | 0.961495E+10 | 0.250648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.100890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113801E+10 | 0.378720E+10 | 0.630410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.113760E+10 | 0.00 | 0.768639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103028E+10 | 0.00 | 0.550167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116213E+10 | 0.00 | 0.386122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110387E+10 | 0.165702E+09 | 0.191330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114986E+10 | 0.377535E+09 | 0.598871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112227E+10 | 0.940772E+09 | 42526266.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113147E+10 | 0.251865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116213E+10 | 0.359099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110387E+10 | 0.114495E+10 | 83132228.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113760E+10 | 51471584.64 | 0.136986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110387E+10 | 8181560.99 | 0.434405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113147E+10 | 0.00 | 0.659524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134764E+11 | 0.879825E+10 | 0.319963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116213E+10 | 0.359099E+10 | 0.768639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.149274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133104E+10 | 0.00 | 0.00 | 0.00 | 159.73 | 0.00 | 0.617418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122751E+10 | 0.00 | 0.00 | 0.00 | 0.146459E+09 | 0.00 | 0.234688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122838E+10 | 0.00 | 0.00 | 0.00 | 0.343638E+09 | 0.00 | 0.240977E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118787E+10 | 0.00 | 0.00 | 0.00 | 0.678818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123094E+10 | 0.00 | 0.00 | 0.00 | 0.168307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124628E+10 | 0.00 | 0.00 | 0.00 | 0.224423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119038E+10 | 0.00 | 0.00 | 0.00 | 0.716732E+09 | 0.00 | 2396600.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124540E+10 | 0.00 | 0.00 | 0.00 | 41772689.43 | 0.00 | 0.124877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131977E+10 | 0.00 | 0.00 | 0.00 | 5521305.20 | 0.00 | 0.809559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154527E+11 | 0.00 | 0.00 | 0.00 | 0.586024E+10 | 0.00 | 0.585487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.118787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149274E+10 | 0.00 | 0.00 | 0.00 | 0.224423E+10 | 0.00 | 0.158695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.132474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120226E+10 | 0.00 | 0.00 | 0.00 | 10458833.01 | 0.00 | 0.276313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135796E+10 | 0.00 | 0.00 | 0.00 | 22489343.15 | 0.00 | 0.859652E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134791E+10 | 0.00 | 0.00 | 0.00 | 0.223496E+09 | 0.00 | 0.169093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146838E+10 | 0.00 | 0.00 | 0.00 | 0.516470E+09 | 0.00 | 4642453.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148166E+10 | 0.00 | 0.00 | 0.00 | 0.899190E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155679E+10 | 0.00 | 0.00 | 0.00 | 0.140302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157734E+10 | 0.00 | 0.00 | 0.00 | 0.160927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147372E+10 | 0.00 | 0.00 | 0.00 | 0.893955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141269E+10 | 0.00 | 0.00 | 0.00 | 0.266450E+09 | 0.00 | 34933799.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130641E+10 | 0.00 | 0.00 | 0.00 | 46670974.52 | 0.00 | 0.177443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131772E+10 | 0.00 | 0.00 | 0.00 | 7050.22 | 0.00 | 0.352990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168276E+11 | 0.00 | 0.00 | 0.00 | 0.589148E+10 | 0.00 | 0.136269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.120226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157734E+10 | 0.00 | 0.00 | 0.00 | 0.160927E+10 | 0.00 | 0.449110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.157678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142774E+10 | 0.00 | 0.00 | 0.00 | 63.40 | 0.00 | 0.317303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160816E+10 | 0.00 | 0.00 | 0.00 | 1314.08 | 0.00 | 0.108058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152972E+10 | 0.00 | 0.00 | 0.00 | 76929401.03 | 0.00 | 0.213327E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159247E+10 | 0.00 | 0.00 | 0.00 | 0.156192E+09 | 0.00 | 703064.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155325E+10 | 0.00 | 0.00 | 0.00 | 0.278278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156894E+10 | 0.00 | 0.00 | 0.00 | 0.651157E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160816E+10 | 0.00 | 0.00 | 0.00 | 0.906216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152972E+10 | 0.00 | 0.00 | 0.00 | 0.280425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157678E+10 | 0.00 | 0.00 | 0.00 | 15323051.94 | 0.00 | 28085600.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152972E+10 | 0.00 | 0.00 | 0.00 | 3579927.26 | 0.00 | 0.214646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186704E+11 | 0.00 | 0.00 | 0.00 | 0.236810E+10 | 0.00 | 0.158685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.142774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160816E+10 | 0.00 | 0.00 | 0.00 | 0.906216E+09 | 0.00 | 0.511371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.157049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142204E+10 | 0.00 | 0.00 | 0.00 | 33.77 | 0.00 | 0.337500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160175E+10 | 0.00 | 0.00 | 0.00 | 1159.89 | 0.00 | 0.126401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152361E+10 | 0.00 | 0.00 | 0.00 | 73937812.02 | 0.00 | 0.286302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158612E+10 | 0.00 | 0.00 | 0.00 | 0.150993E+09 | 0.00 | 1038326.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154705E+10 | 0.00 | 0.00 | 0.00 | 0.273386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156268E+10 | 0.00 | 0.00 | 0.00 | 0.647585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160175E+10 | 0.00 | 0.00 | 0.00 | 0.903374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152361E+10 | 0.00 | 0.00 | 0.00 | 0.277095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157049E+10 | 0.00 | 0.00 | 0.00 | 14409658.63 | 0.00 | 61229659.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152361E+10 | 0.00 | 0.00 | 0.00 | 2873560.59 | 0.00 | 0.234676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185959E+11 | 0.00 | 0.00 | 0.00 | 0.234365E+10 | 0.00 | 0.171151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.142204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160175E+10 | 0.00 | 0.00 | 0.00 | 0.903374E+09 | 0.00 | 0.540648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.156107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141350E+10 | 0.00 | 0.00 | 0.00 | 20.85 | 0.00 | 0.371734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159213E+10 | 0.00 | 0.00 | 0.00 | 859.81 | 0.00 | 0.159523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151447E+10 | 0.00 | 0.00 | 0.00 | 67001225.92 | 0.00 | 0.445439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157660E+10 | 0.00 | 0.00 | 0.00 | 0.133980E+09 | 0.00 | 7315092.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153777E+10 | 0.00 | 0.00 | 0.00 | 0.252451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155330E+10 | 0.00 | 0.00 | 0.00 | 0.620097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159213E+10 | 0.00 | 0.00 | 0.00 | 0.870330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151447E+10 | 0.00 | 0.00 | 0.00 | 0.259084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156107E+10 | 0.00 | 0.00 | 0.00 | 11781454.03 | 0.00 | 0.159845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151447E+10 | 0.00 | 0.00 | 0.00 | 1659032.69 | 0.00 | 0.267663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184843E+11 | 0.00 | 0.00 | 0.00 | 0.221639E+10 | 0.00 | 0.192830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.141350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159213E+10 | 0.00 | 0.00 | 0.00 | 0.870330E+09 | 0.00 | 0.586998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.109879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.944064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.991009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.984289E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.880736E+09 | 0.00 | 0.00 | 0.00 | 93908782.65 | 0.00 | 0.277900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.876071E+09 | 0.00 | 0.00 | 0.00 | 0.191421E+09 | 0.00 | 0.415201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.848286E+09 | 0.00 | 0.00 | 0.00 | 0.422478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.858420E+09 | 0.00 | 0.00 | 0.00 | 0.112579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.891464E+09 | 0.00 | 0.00 | 0.00 | 0.159386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.834771E+09 | 0.00 | 0.00 | 0.00 | 0.471917E+09 | 0.00 | 22595985.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.894258E+09 | 0.00 | 0.00 | 0.00 | 19384392.25 | 0.00 | 0.206124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.972029E+09 | 0.00 | 0.00 | 0.00 | 1411054.42 | 0.00 | 0.825193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111466E+11 | 0.00 | 0.00 | 0.00 | 0.392017E+10 | 0.00 | 0.565887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.834771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109879E+10 | 0.00 | 0.00 | 0.00 | 0.159386E+10 | 0.00 | 0.143228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.113965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116422E+10 | 0.00 | 0.00 | 0.00 | 14920.97 | 0.00 | 0.298828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110586E+10 | 0.00 | 0.00 | 0.00 | 53458328.03 | 0.00 | 0.126213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115194E+10 | 0.00 | 0.00 | 0.00 | 0.126863E+09 | 0.00 | 0.217039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112429E+10 | 0.00 | 0.00 | 0.00 | 0.295204E+09 | 0.00 | 477616.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113351E+10 | 0.00 | 0.00 | 0.00 | 0.666098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116422E+10 | 0.00 | 0.00 | 0.00 | 0.878330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110586E+10 | 0.00 | 0.00 | 0.00 | 0.304045E+09 | 0.00 | 13538632.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113965E+10 | 0.00 | 0.00 | 0.00 | 26630240.20 | 0.00 | 0.895308E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110586E+10 | 0.00 | 0.00 | 0.00 | 3628754.98 | 0.00 | 0.399747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135007E+11 | 0.00 | 0.00 | 0.00 | 0.235427E+10 | 0.00 | 0.279659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.103214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116422E+10 | 0.00 | 0.00 | 0.00 | 0.878330E+09 | 0.00 | 0.733381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.112582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.746962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109244E+10 | 0.00 | 0.00 | 0.00 | 50432757.13 | 0.00 | 0.137309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113795E+10 | 0.00 | 0.00 | 0.00 | 0.118404E+09 | 0.00 | 0.264471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111064E+10 | 0.00 | 0.00 | 0.00 | 0.276485E+09 | 0.00 | 1576150.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111975E+10 | 0.00 | 0.00 | 0.00 | 0.643259E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115009E+10 | 0.00 | 0.00 | 0.00 | 0.856008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109244E+10 | 0.00 | 0.00 | 0.00 | 0.290277E+09 | 0.00 | 17322092.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112582E+10 | 0.00 | 0.00 | 0.00 | 23077161.29 | 0.00 | 0.990754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109244E+10 | 0.00 | 0.00 | 0.00 | 3263437.16 | 0.00 | 0.413280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133368E+11 | 0.00 | 0.00 | 0.00 | 0.226121E+10 | 0.00 | 0.289356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.101961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115009E+10 | 0.00 | 0.00 | 0.00 | 0.856008E+09 | 0.00 | 0.746962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.111399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108096E+10 | 0.00 | 0.00 | 0.00 | 45327064.61 | 0.00 | 0.161631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112600E+10 | 0.00 | 0.00 | 0.00 | 0.103639E+09 | 0.00 | 0.374628E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109898E+10 | 0.00 | 0.00 | 0.00 | 0.244709E+09 | 0.00 | 8317078.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110798E+10 | 0.00 | 0.00 | 0.00 | 0.601373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113801E+10 | 0.00 | 0.00 | 0.00 | 0.817017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108096E+10 | 0.00 | 0.00 | 0.00 | 0.267463E+09 | 0.00 | 30683350.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111399E+10 | 0.00 | 0.00 | 0.00 | 17325777.40 | 0.00 | 0.117830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108096E+10 | 0.00 | 0.00 | 0.00 | 2651463.18 | 0.00 | 0.443566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131967E+11 | 0.00 | 0.00 | 0.00 | 0.209951E+10 | 0.00 | 0.313310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.100890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113801E+10 | 0.00 | 0.00 | 0.00 | 0.817017E+09 | 0.00 | 0.788012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.113760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110387E+10 | 0.00 | 0.00 | 0.00 | 39023171.62 | 0.00 | 0.239163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114986E+10 | 0.00 | 0.00 | 0.00 | 86195659.61 | 0.00 | 0.748588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112227E+10 | 0.00 | 0.00 | 0.00 | 0.213024E+09 | 0.00 | 53157833.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113147E+10 | 0.00 | 0.00 | 0.00 | 0.550265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116213E+10 | 0.00 | 0.00 | 0.00 | 0.774946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110387E+10 | 0.00 | 0.00 | 0.00 | 0.247618E+09 | 0.00 | 0.103915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113760E+10 | 0.00 | 0.00 | 0.00 | 11824454.95 | 0.00 | 0.171232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110387E+10 | 0.00 | 0.00 | 0.00 | 1946782.41 | 0.00 | 0.543006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134764E+11 | 0.00 | 0.00 | 0.00 | 0.192484E+10 | 0.00 | 0.399953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.103028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116213E+10 | 0.00 | 0.00 | 0.00 | 0.774946E+09 | 0.00 | 0.960798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.706693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683548E+10 | 0.00 | 0.00 | 0.53 |
February | 0.731277E+10 | 0.00 | 0.00 | 2899.62 | 0.00 | 0.407319E+10 | 7372969.88 | 0.00 | 0.53 |
March | 0.858553E+10 | 0.00 | 0.00 | 28551.76 | 0.00 | 0.161419E+10 | 39185653.32 | 0.00 | 0.53 |
April | 0.733814E+10 | 34551402.20 | 0.00 | 1139657.28 | 0.00 | 0.252333E+09 | 0.671383E+09 | 0.00 | 0.55 |
May | 0.574149E+10 | 23346125.93 | 0.00 | 3799284.79 | 0.00 | 5176934.23 | 0.188526E+10 | 0.00 | 0.61 |
June | 0.216937E+10 | 35296134.09 | 0.00 | 9342667.03 | 0.00 | 0.00 | 0.461894E+10 | 0.00 | 0.72 |
July | 0.517049E+09 | 0.442977E+09 | 0.00 | 12083626.26 | 636710.57 | 0.00 | 0.499234E+10 | 0.00 | 0.80 |
August | 0.373183E+09 | 0.930632E+09 | 0.00 | 10500252.40 | 804657.83 | 0.00 | 0.399965E+10 | 0.00 | 0.77 |
September | 0.262936E+10 | 63520891.34 | 0.00 | 8815630.36 | 0.00 | 0.00 | 0.452328E+10 | 0.00 | 0.71 |
October | 0.699555E+10 | 0.00 | 0.00 | 2433325.50 | 0.00 | 31479103.16 | 0.192118E+10 | 0.00 | 0.56 |
November | 0.778746E+10 | 0.00 | 0.00 | 136385.27 | 0.00 | 0.295459E+10 | 0.140706E+09 | 0.00 | 0.53 |
December | 0.781382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535010E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.643306E+11 | 0.153032E+10 | 0.00 | 48282280.27 | 1441368.40 | 0.211165E+11 | 0.227993E+11 | 0.00 | 0.61 |
Minimum of Months | 0.373183E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.858553E+10 | 0.930632E+09 | 0.00 | 12083626.26 | 804657.83 | 0.683548E+10 | 0.499234E+10 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.291733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256875E+10 | 0.00 | 0.00 | 0.42 |
February | 0.325202E+10 | 0.00 | 0.00 | 106518.23 | 0.00 | 0.118723E+10 | 60373365.18 | 0.00 | 0.42 |
March | 0.399060E+10 | 0.00 | 0.00 | 193080.68 | 0.00 | 0.201872E+09 | 87989323.52 | 0.00 | 0.43 |
April | 0.297777E+10 | 15600416.27 | 0.00 | 1501596.92 | 0.00 | 26518639.63 | 0.495642E+09 | 0.00 | 0.44 |
May | 0.174318E+10 | 9881547.16 | 0.00 | 4246136.62 | 0.00 | 516940.16 | 0.152355E+10 | 0.00 | 0.46 |
June | 0.631364E+09 | 12961041.93 | 0.00 | 7181038.71 | 0.00 | 0.00 | 0.188973E+10 | 0.00 | 0.48 |
July | 0.275210E+09 | 0.191281E+09 | 0.00 | 7710506.05 | 0.00 | 0.00 | 0.141708E+10 | 0.00 | 0.49 |
August | 0.243376E+09 | 0.420534E+09 | 0.00 | 6695088.51 | 0.00 | 0.00 | 0.108367E+10 | 0.00 | 0.50 |
September | 0.786097E+09 | 22050661.07 | 0.00 | 6642619.07 | 0.00 | 0.00 | 0.183525E+10 | 0.00 | 0.48 |
October | 0.268794E+10 | 0.00 | 0.00 | 2706614.43 | 0.00 | 3493545.37 | 0.112651E+10 | 0.00 | 0.45 |
November | 0.358994E+10 | 0.00 | 0.00 | 355239.20 | 0.00 | 0.714921E+09 | 0.129068E+09 | 0.00 | 0.43 |
December | 0.317363E+10 | 0.00 | 0.00 | 61.39 | 0.00 | 0.197084E+10 | 22258.29 | 0.00 | 0.42 |
Annual Sum or Average | 0.262685E+11 | 0.672309E+09 | 0.00 | 37338499.82 | 0.00 | 0.667414E+10 | 0.964888E+10 | 0.00 | 0.45 |
Minimum of Months | 0.243376E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.399060E+10 | 0.420534E+09 | 0.00 | 7710506.05 | 0.00 | 0.256875E+10 | 0.188973E+10 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.219475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312598E+10 | 0.00 | 0.00 | 0.41 |
February | 0.267489E+10 | 0.00 | 0.00 | 34912.64 | 0.00 | 0.162427E+10 | 47600085.29 | 0.00 | 0.42 |
March | 0.381730E+10 | 0.00 | 0.00 | 33631.05 | 0.00 | 0.237960E+09 | 58735560.82 | 0.00 | 0.43 |
April | 0.289630E+10 | 16433246.28 | 0.00 | 627745.34 | 0.00 | 19602976.36 | 0.474047E+09 | 0.00 | 0.48 |
May | 0.174479E+10 | 11427285.28 | 0.00 | 2621020.52 | 0.00 | 0.00 | 0.185261E+10 | 0.00 | 0.64 |
June | 0.487140E+09 | 17025809.63 | 0.00 | 5218753.60 | 46068.76 | 0.00 | 0.319416E+10 | 0.00 | 0.87 |
July | 0.184435E+09 | 0.176289E+09 | 0.00 | 6164168.25 | 3704890.53 | 0.00 | 0.282421E+10 | 0.00 | 0.96 |
August | 0.168638E+09 | 0.396702E+09 | 0.00 | 5759869.16 | 6998270.59 | 0.00 | 0.241855E+10 | 0.00 | 0.91 |
September | 0.706719E+09 | 21821538.37 | 0.00 | 4875956.91 | 0.00 | 0.00 | 0.293185E+10 | 0.00 | 0.81 |
October | 0.262633E+10 | 0.00 | 0.00 | 1554906.22 | 0.00 | 0.00 | 0.133503E+10 | 0.00 | 0.52 |
November | 0.303797E+10 | 0.00 | 0.00 | 101963.47 | 0.00 | 0.113437E+10 | 94952708.77 | 0.00 | 0.43 |
December | 0.258296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239484E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.231222E+11 | 0.639699E+09 | 0.00 | 26992927.16 | 10749229.88 | 0.853703E+10 | 0.152318E+11 | 0.00 | 0.61 |
Minimum of Months | 0.168638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.381730E+10 | 0.396702E+09 | 0.00 | 6164168.25 | 6998270.59 | 0.312598E+10 | 0.319416E+10 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.202969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329005E+10 | 0.00 | 0.00 | 0.41 |
February | 0.250613E+10 | 0.00 | 0.00 | 21861.58 | 0.00 | 0.178859E+10 | 37948240.70 | 0.00 | 0.42 |
March | 0.364230E+10 | 0.00 | 0.00 | 25878.23 | 0.00 | 0.397804E+09 | 48311197.05 | 0.00 | 0.43 |
April | 0.287506E+10 | 16404152.05 | 0.00 | 559982.77 | 0.00 | 50485979.96 | 0.417326E+09 | 0.00 | 0.47 |
May | 0.184501E+10 | 11283492.28 | 0.00 | 2390122.50 | 0.00 | 0.00 | 0.168320E+10 | 0.00 | 0.63 |
June | 0.513848E+09 | 16987077.06 | 0.00 | 5068821.36 | 46474.70 | 0.00 | 0.312657E+10 | 0.00 | 0.87 |
July | 0.187184E+09 | 0.176080E+09 | 0.00 | 6112236.37 | 3706439.28 | 0.00 | 0.280577E+10 | 0.00 | 0.95 |
August | 0.170718E+09 | 0.396256E+09 | 0.00 | 5749644.87 | 6991549.10 | 0.00 | 0.240995E+10 | 0.00 | 0.90 |
September | 0.741520E+09 | 21574755.17 | 0.00 | 4737365.48 | 0.00 | 0.00 | 0.285459E+10 | 0.00 | 0.81 |
October | 0.265255E+10 | 0.00 | 0.00 | 1429996.82 | 0.00 | 1634182.15 | 0.123885E+10 | 0.00 | 0.51 |
November | 0.281945E+10 | 0.00 | 0.00 | 82089.74 | 0.00 | 0.134889E+10 | 79033815.72 | 0.00 | 0.43 |
December | 0.238259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259307E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.223660E+11 | 0.638585E+09 | 0.00 | 26177999.73 | 10744463.07 | 0.947052E+10 | 0.147016E+11 | 0.00 | 0.60 |
Minimum of Months | 0.170718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.364230E+10 | 0.396256E+09 | 0.00 | 6112236.37 | 6991549.10 | 0.329005E+10 | 0.312657E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.171550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360287E+10 | 0.00 | 0.00 | 0.41 |
February | 0.214239E+10 | 0.00 | 0.00 | 6903.59 | 0.00 | 0.215229E+10 | 19336549.21 | 0.00 | 0.42 |
March | 0.335252E+10 | 0.00 | 0.00 | 13454.32 | 0.00 | 0.665587E+09 | 29436243.56 | 0.00 | 0.43 |
April | 0.284961E+10 | 16378432.10 | 0.00 | 415334.85 | 0.00 | 95092605.73 | 0.304325E+09 | 0.00 | 0.46 |
May | 0.214507E+10 | 10742651.21 | 0.00 | 1746689.16 | 0.00 | 0.00 | 0.117651E+10 | 0.00 | 0.60 |
June | 0.723540E+09 | 16952413.13 | 0.00 | 4324583.97 | 47616.83 | 0.00 | 0.270067E+10 | 0.00 | 0.83 |
July | 0.204513E+09 | 0.174575E+09 | 0.00 | 5598918.85 | 3763962.79 | 0.00 | 0.267409E+10 | 0.00 | 0.93 |
August | 0.186566E+09 | 0.393215E+09 | 0.00 | 5282407.05 | 7062898.68 | 0.00 | 0.231336E+10 | 0.00 | 0.89 |
September | 0.997615E+09 | 20464478.31 | 0.00 | 4037302.13 | 0.00 | 0.00 | 0.240186E+10 | 0.00 | 0.77 |
October | 0.272054E+10 | 0.00 | 0.00 | 1074837.98 | 0.00 | 12173069.08 | 0.988462E+09 | 0.00 | 0.49 |
November | 0.261666E+10 | 0.00 | 0.00 | 55748.50 | 0.00 | 0.153969E+10 | 58890388.93 | 0.00 | 0.43 |
December | 0.211407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285924E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.217686E+11 | 0.632328E+09 | 0.00 | 22556180.41 | 10874478.30 | 0.109269E+11 | 0.126669E+11 | 0.00 | 0.59 |
Minimum of Months | 0.186566E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.335252E+10 | 0.393215E+09 | 0.00 | 5598918.85 | 7062898.68 | 0.360287E+10 | 0.270067E+10 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846256E+10 | 0.00 | 0.00 | 0.38 |
February | 0.237881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551972E+10 | 0.00 | 0.00 | 0.38 |
March | 0.492056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235032E+10 | 0.00 | 0.00 | 0.39 |
April | 0.464327E+10 | 25315465.04 | 0.00 | 330248.04 | 0.00 | 0.607797E+09 | 0.175152E+09 | 0.00 | 0.39 |
May | 0.419485E+10 | 12915790.06 | 0.00 | 1420561.61 | 0.00 | 28130515.50 | 0.628584E+09 | 0.00 | 0.43 |
June | 0.216718E+10 | 25875806.16 | 0.00 | 4185050.18 | 212105.42 | 0.00 | 0.198998E+10 | 0.00 | 0.49 |
July | 0.686823E+09 | 0.341666E+09 | 0.00 | 6104649.85 | 7147870.65 | 0.00 | 0.240639E+10 | 0.00 | 0.52 |
August | 0.477289E+09 | 0.783705E+09 | 0.00 | 5286979.22 | 6911053.74 | 0.00 | 0.210637E+10 | 0.00 | 0.52 |
September | 0.265426E+10 | 29618925.29 | 0.00 | 3769488.26 | 0.00 | 2633807.00 | 0.160141E+10 | 0.00 | 0.47 |
October | 0.503492E+10 | 0.00 | 0.00 | 599911.58 | 0.00 | 0.307592E+09 | 0.515498E+09 | 0.00 | 0.39 |
November | 0.369137E+10 | 0.00 | 0.00 | 43257.88 | 0.00 | 0.395041E+10 | 42420752.07 | 0.00 | 0.38 |
December | 0.231255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688892E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.345152E+11 | 0.121910E+10 | 0.00 | 21740146.61 | 14271029.81 | 0.281181E+11 | 0.946580E+10 | 0.00 | 0.43 |
Minimum of Months | 0.477289E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.503492E+10 | 0.783705E+09 | 0.00 | 6104649.85 | 7147870.65 | 0.846256E+10 | 0.240639E+10 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.742349E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457027E+10 | 0.00 | 0.00 | 0.41 |
February | 0.126125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302797E+10 | 0.00 | 0.00 | 0.42 |
March | 0.243501E+10 | 0.00 | 0.00 | 57.72 | 0.00 | 0.154240E+10 | 802824.52 | 0.00 | 0.42 |
April | 0.242477E+10 | 11604985.07 | 0.00 | 166801.87 | 0.00 | 0.481116E+09 | 89797998.44 | 0.00 | 0.42 |
May | 0.232854E+10 | 4880370.00 | 0.00 | 686214.93 | 0.00 | 51916877.26 | 0.248569E+09 | 0.00 | 0.42 |
June | 0.126381E+10 | 9623522.61 | 0.00 | 2077789.62 | 86084.74 | 283115.58 | 0.820165E+09 | 0.00 | 0.43 |
July | 0.535387E+09 | 0.150136E+09 | 0.00 | 2961703.50 | 2463638.94 | 0.00 | 0.852615E+09 | 0.00 | 0.42 |
August | 0.394497E+09 | 0.356344E+09 | 0.00 | 2504068.21 | 2120929.09 | 0.00 | 0.752433E+09 | 0.00 | 0.43 |
September | 0.151545E+10 | 8728062.88 | 0.00 | 1911643.41 | 0.00 | 3387576.53 | 0.661267E+09 | 0.00 | 0.42 |
October | 0.257709E+10 | 0.00 | 0.00 | 314893.21 | 0.00 | 0.368384E+09 | 0.256623E+09 | 0.00 | 0.42 |
November | 0.190049E+10 | 0.00 | 0.00 | 20077.51 | 0.00 | 0.222775E+10 | 16580274.96 | 0.00 | 0.41 |
December | 0.123098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373905E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.186096E+11 | 0.541317E+09 | 0.00 | 10643249.98 | 4670652.76 | 0.160125E+11 | 0.369885E+10 | 0.00 | 0.42 |
Minimum of Months | 0.394497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.257709E+10 | 0.356344E+09 | 0.00 | 2961703.50 | 2463638.94 | 0.457027E+10 | 0.852615E+09 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.583118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472922E+10 | 0.00 | 0.00 | 0.41 |
February | 0.118966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309754E+10 | 0.00 | 0.00 | 0.42 |
March | 0.232667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164703E+10 | 0.00 | 0.00 | 0.42 |
April | 0.233420E+10 | 11614002.26 | 0.00 | 145364.37 | 0.00 | 0.573923E+09 | 74937805.99 | 0.00 | 0.42 |
May | 0.230620E+10 | 4729173.36 | 0.00 | 623136.28 | 0.00 | 75320976.16 | 0.222429E+09 | 0.00 | 0.42 |
June | 0.130798E+10 | 9673486.02 | 0.00 | 1919117.35 | 88556.65 | 676028.83 | 0.758820E+09 | 0.00 | 0.43 |
July | 0.562695E+09 | 0.149891E+09 | 0.00 | 2810945.48 | 2527217.35 | 0.00 | 0.822056E+09 | 0.00 | 0.42 |
August | 0.413740E+09 | 0.355826E+09 | 0.00 | 2377158.38 | 2138050.96 | 0.00 | 0.732621E+09 | 0.00 | 0.43 |
September | 0.154397E+10 | 8489827.85 | 0.00 | 1794344.73 | 0.00 | 3371041.51 | 0.617888E+09 | 0.00 | 0.42 |
October | 0.253933E+10 | 0.00 | 0.00 | 267906.69 | 0.00 | 0.435027E+09 | 0.210859E+09 | 0.00 | 0.42 |
November | 0.177576E+10 | 0.00 | 0.00 | 17849.54 | 0.00 | 0.234968E+10 | 16086497.44 | 0.00 | 0.41 |
December | 0.111744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385186E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.180007E+11 | 0.540223E+09 | 0.00 | 9955822.82 | 4753824.97 | 0.167636E+11 | 0.345570E+10 | 0.00 | 0.42 |
Minimum of Months | 0.413740E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.253933E+10 | 0.355826E+09 | 0.00 | 2810945.48 | 2527217.35 | 0.472922E+10 | 0.822056E+09 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.313916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499758E+10 | 0.00 | 0.00 | 0.41 |
February | 0.929981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335268E+10 | 0.00 | 0.00 | 0.42 |
March | 0.205020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191458E+10 | 0.00 | 0.00 | 0.42 |
April | 0.214149E+10 | 11565062.26 | 0.00 | 107052.71 | 0.00 | 0.761864E+09 | 54300173.98 | 0.00 | 0.41 |
May | 0.221321E+10 | 4327205.82 | 0.00 | 516491.26 | 0.00 | 0.140954E+09 | 0.199892E+09 | 0.00 | 0.42 |
June | 0.134901E+10 | 9630876.46 | 0.00 | 1631305.91 | 92420.01 | 1877536.26 | 0.679590E+09 | 0.00 | 0.43 |
July | 0.615228E+09 | 0.147812E+09 | 0.00 | 2520657.61 | 2811860.51 | 0.00 | 0.763003E+09 | 0.00 | 0.42 |
August | 0.452084E+09 | 0.352039E+09 | 0.00 | 2151557.99 | 2142240.81 | 0.00 | 0.693971E+09 | 0.00 | 0.43 |
September | 0.160171E+10 | 7813612.79 | 0.00 | 1593315.35 | 0.00 | 7923918.57 | 0.523413E+09 | 0.00 | 0.42 |
October | 0.241748E+10 | 0.00 | 0.00 | 200393.13 | 0.00 | 0.566033E+09 | 0.168871E+09 | 0.00 | 0.42 |
November | 0.149560E+10 | 0.00 | 0.00 | 14101.95 | 0.00 | 0.262572E+10 | 13678489.59 | 0.00 | 0.41 |
December | 0.796802E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417072E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.163767E+11 | 0.533188E+09 | 0.00 | 8734875.91 | 5046521.33 | 0.185399E+11 | 0.309672E+10 | 0.00 | 0.42 |
Minimum of Months | 0.313916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.241748E+10 | 0.352039E+09 | 0.00 | 2520657.61 | 2811860.51 | 0.499758E+10 | 0.763003E+09 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2020-06-03 19:19:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 65246136.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523044E+10 | 0.00 | 0.00 | 0.41 |
February | 0.264288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399792E+10 | 0.00 | 0.00 | 0.42 |
March | 0.828918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311212E+10 | 0.00 | 0.00 | 0.42 |
April | 0.149508E+10 | 11486071.89 | 0.00 | 67034.11 | 0.00 | 0.137831E+10 | 30269489.83 | 0.00 | 0.41 |
May | 0.195721E+10 | 3663747.75 | 0.00 | 382122.69 | 0.00 | 0.328315E+09 | 0.161426E+09 | 0.00 | 0.42 |
June | 0.143311E+10 | 9433085.20 | 0.00 | 1268409.81 | 95908.91 | 15460983.37 | 0.491829E+09 | 0.00 | 0.43 |
July | 0.677423E+09 | 0.144068E+09 | 0.00 | 2071877.31 | 2446954.86 | 0.00 | 0.657124E+09 | 0.00 | 0.42 |
August | 0.538423E+09 | 0.347029E+09 | 0.00 | 1747534.89 | 2086288.88 | 0.00 | 0.595817E+09 | 0.00 | 0.43 |
September | 0.162534E+10 | 6930536.60 | 0.00 | 1390545.89 | 0.00 | 27129934.61 | 0.396693E+09 | 0.00 | 0.42 |
October | 0.196590E+10 | 0.00 | 0.00 | 114554.43 | 0.00 | 0.100924E+10 | 0.101263E+09 | 0.00 | 0.42 |
November | 0.571867E+09 | 0.00 | 0.00 | 9360.79 | 0.00 | 0.351926E+10 | 11610698.72 | 0.00 | 0.41 |
December | 0.106170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484600E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.115290E+11 | 0.522610E+09 | 0.00 | 7051439.93 | 4629152.65 | 0.234642E+11 | 0.244603E+10 | 0.00 | 0.42 |
Minimum of Months | 65246136.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.196590E+10 | 0.347029E+09 | 0.00 | 2071877.31 | 2446954.86 | 0.523044E+10 | 0.657124E+09 | 0.00 | 0.43 |